Buswire Supervision for High Impedance Schemes

The MVTP is a monitoring device, used to ensure the integrity of busbar, and restricted earth fault schemes. The MVTP relay is available in two types: > Type MVTP 11 - single phase relay. > Type MVTP 31 - three phase relay. These provide continuous supervision of the buswires in high impedance type busbar protection schemes, detecting open-circuited buswires as well as open-circuited main current transformers.
Type MVTP

In earth-fault only protection schemes, the single-phase relay is employed. MVTP relays have a setting range of 2-14V, adjusted by means of a plug bridge on the relay front panel. Relays are continuously rated at 600V rms and no external components are required. The ac voltage input is continuously monitored and when it exceeds the level pre-set by means of the plug setting, the output relay is actuated after a three second delay. The hand reset contacts of the output relay are normally connected across the buswires of the busbar protection thus short-circuiting the busbar protection relay and rendering the protection of the zone concerned inoperative. On the same output relay are hand reset contacts for alarm purposes. Operation of the relay is indicated by a hand resettable mechanical flag.

Customer Benefits Integral buswire shorting facility Low ac burden No external resistors required Ensures the availability of MCAG and MFAC schemes

T&D

P1

S1 See note 3 S2

P1 S1

Phase rotation S2 P2 Power supply circuits


RL1-1
1 3 1 3

a b c n

P2

Vx

23

VA

24 25 RL1-2
2 4

v Case earth

87 A

87 B

Alarm contacts

87 C

VB

26 27

>Vs

Output circuits

RL1 6

RL1-3 RL1-4

1 3 5 7 9 11 13 15 17 19 21 23 25 27

2 4 6 8 10 12 14 16 18 20 22 24 26 28

VC

28 13 14 22 RL1-5

7 6 8

See note 3

+ve ve

Power supply circuits Case earth connection

RL1-6

9 11

Module terminal block viewed from rear

Notes 1 (a) (b) (c)

CT shorting links make before (b) & (c) disconnect. Short terminals break before (c) Long terminals

2 Earthing connections as shown are typical only 3 CT connections are typical only.

Figure 1

Application diagram: static modular buswire voltage supervision relay, type MVTP 31.

TECHNICAL DATA
> Burdens
Measuring circuit - typical burdens Applied voltage Vac Burden VA 2 8 14 600

> Settings
Setting range (VS) 2-14V rms adjusted by means of a plug bridge in 7 equal steps.

0.01x10-3

0.7x10-3 2.2x10-3

4.0

2, 4, 6, 8, 10, 12, 14V

Auxiliary supply - typical burdens at the upper rated voltage Vx rated voltage (V dc) 30/34 48/54 110/125 220/250 Output relay not energised mA 24 24 24 24 W 0.82 1.3 3.0 6.0 Output relay energised mA 90 90 35 35 W 3.06 4.86 4.37 8.75

2>3

Self monitoring for high impedance unit protection, for peace of mind

> Auxiliary supplies (VX)


Rating (V dc) 24/27* 30/34 48/54 110/125 220/250 Operative range (V dc) 19.2-30.2 24-37.5 37.5-60 87.5-137.5 175 -275

> Thermal rating


Continuous 600V rms per phase on all three phases simultaneously (at any setting). Short time The relay will withstand 2kV rms per phase, for 3 seconds on all three phases simultaneously (at any setting)

* Use a 30/34V relay with a separate MSTZ 02 dc/dc converter. All relays are rated continuously at the maximum voltage in the operative range.

> Cases
Types MVTP 11 and MVTP 31 are supplied in size 4 and size 6 cases respectively, as shown in Figures 2 and 3.

Frequency 50 and 60 Hz Operative range 47-61 Hz Operating time Fixed at 3 seconds Contact disengaging time <150ms Drop off/pick up ratio >85% after 3 second delay >98% before 3 second delay

INFORMATION REQUIRED WITH ORDER


> Relay type > DC auxiliary voltage > Configuration of alarm contacts

CONTACTS
Buswire shorting contacts are normally open type. The two alarm contacts may be specified in any combination of make or break (2M, 1M 1B, or 2B)

> Contact ratings


Make and carry Continuously AC 1250VA with maxima of 5 amps and 300V 1250 watts with maxima of 5 amps and 300V Make and carry for 3 seconds 7500VA with maxima of 30 amps and 300V 7500 watts with maxima of 30 amps and 300V Break

1250VA with maxima of 5 amps and 300V 100 watts (resistive) 50 watts (inductive) and maxima of 5 amps and 300V

DC

The hand-reset contacts will carry 150A rms for 0.5 seconds.

Type MVTP relay withdrawn from case.

97

52

4 holes 4.4

23.5

AREVA TRACK RECORD BUSBAR PROTECTION


>> Over 43000 MCAG schemes installed

since 1984
>> Over 21000 MFAC schemes installed
168 159

since 1983
>> MVTP buswire supervision shipped

Push button projection 10 max


99 32 212

Panel cut-out: Flush mounting fixing details


25 min.

worldwide since 1983


>> MiCOM P740 available for low impedance,

biased differential busbar protection

177 157 max.

103

Reset

All dimensions in mm

Flush mounting

11

Figure 2

MVTP 11. Case outline size 4

149

4 holes

4.4

103.6 24

168

159

Push button projection 10 max

151 Panel cut-out: Flush mounting fixing details 32 212 25 min.

177

157 max. Reset

155

Flush mounting

11

All dimensions in mm

Figure 3

MVTP 31. Case outline size 6

AREVA T&D Worldwide Contact Centre: http://www.areva-td.com/contactcentre/ Tel.: +44 (0) 1785 250 070

www.areva-td.com

Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advise on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

AUTOMATION-L3-MVTP-BR-01.05-0796-GB - - AREVA - 2004. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA. MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP