Schneider Electric is committed to supporting its customers at every stage of a project. Our 180 sales engineers, the largest dedicated sales force in the UK electrical industry, operate from 4 customer support centres. Our sales engineers are skilled at assessing individual requirements and combined with the expert support of our product specialists, will develop the most effective and economical answer taking relevant regulations and standards fully into account. To access the expertise of the Schneider Electric group, please contact your local customer support centre. Each centre includes facilities for demonstrations and training, and presentation rooms fully equipped with audio visual and video, providing excellent meeting facilities.

Telemecanique Coordination and protection of Canalis Busbar trunking A designers guide

Produced by Schneider Electric Marketing Communications Department UK and Parenthesis Coventry +44 (0) 24 7622 9658

Regional product showrooms


Midlands University of Warwick Science Park, Sir William Lyons Road, Coventry, CV4 7EZ. Tel: 024 7641 6255 Fax: 024 7641 7517 North East 123 Jack Lane, Hunslet, Leeds, LS10 1BS. Tel: 0113 290 3500 Fax: 0113 290 3710

Local customer support centres


Scotland Unit 11000, Academy Business Park, Gower Street, Glasgow, G51 1PR. Tel: 0141 419 3300 Fax: 0141 419 3323 Email address: North West 8 Brindley Road, City Park Business Village, Cornbrook, Manchester, M16 9HQ. Tel: 0161 877 0424 Fax: 0161 877 0410 Email address: South West 190 Park Avenue, Aztec West, Almondsbury, Bristol, BS32 4TP. Tel: 01454 628000 Fax: 01454 628010 Email address: Greater London 33 Golden Square, London, W1R 3PA. Tel: 020 7440 2400 Fax: 020 7440 2424 Email address:

Medium Low High power

ScotlandGB@schneider.co.uk NorthernGB@schneider.co.uk SouthwestGB@schneider.co.uk SoutheastGB@schneider.co.uk

Schneider - expertise in electrical distribution, automation and control


Schneider Electric is the leading UK and world expert in the development and manufacture of products for the distribution and industrial applications of electricity. In the UK, Schneider Electric operates from 18 industrial and commercial sites, providing employment for 2,500 people, and achieves an annual turnover in excess of 270 million. With its brands, Merlin Gerin, Modicon, Square D and Telemecanique, Schneider Electric offers a full range of products and services for Panel Builders, OEMs, Contractors, Specifiers and the electrical supply industry for commercial and industrial applications.

Merlin Gerin is one of the leading experts in electrical distribution technology. Its comprehensive array of extra-high, medium and low voltage products and systems is designed to manage and protect electrical installations, ensure safety and supply power reliability and continuity for commercial and industrial buildings.

Modicon is a leading manufacturer and worldwide marketer of high technology programmable controllers (PLCs) and motion control systems used in industrial automation. Its international catalogue of products and services include PLCs, numerical controllers, specialised programming and software, fieldbus communication networks and interface terminals. Square D is a total quality organisation and its business is to put electricity to work productively and effectively, protecting people, buildings and equipment. Its low voltage electrical distribution equipment, systems and services are used world wide in commercial applications.

Busbar

Telemecanique is a UK market leader and world expert in industrial control and automation. It provides complete solutions, with its range of components, programmable logic controllers, variable speed drives and communications software. In addition, it offers power distribution through prefabricated busbar trunking.

Internet address: http://www.schneider.co.uk


CAN 1658 AUG 1999

Contents
Contents
Introduction and coordination examples Coordination Masterpact, Compact , Multi 9 / Canalis KLE, KBA, KBB, KN, KSA at 380/415 V Coordination Masterpact, Compact / Canalis KVC, KTC, KHF at 380/415 V Coordination Masterpact, Compact / Canalis KSA, KVC, KTC, KHF at 660/690 V Enhanced coordination definition and examples Enhanced coordination 1350 1200 A busbar trunking Enhanced coordination 1000 A busbar trunking Enhanced coordination 800 500 A busbar trunking Enhanced coordination 400 160 A busbar trunking 19 21 17 18 15 16 14 15 9 10 11 13 78 6 25

Introduction
Introduction
In terms of simple electrical theory and design, Canalis Busbar trunking is no different to a traditional cable distribution system. Consideration needs to be made towards checking and verifying the performance of Canalis against criteria such as: The full load design current. The prospective short circuit current in an installation. The prospective peak current in the event of a fault. The let through energy of the upstream protective device. Although a fairly straightforward process, this can be time consuming and the availability of data from the manufacturers of protective devices and busbar trunking can vary considerably. Both Merlin Gerin circuit breakers and Canalis Busbar trunking form part of the comprehensive Schneider Electric product portfolio. Through this close relationship, Schneider Electric has now been able to co-ordinate and enhance the performance of the two product ranges. The following tables make the selection and coordination of Canalis Busbar trunking and Merlin Gerin circuit breakers a simple, fast and reliable process. The supply of circuit protection and distribution products from a single source goes another step towards ensuring: Continuity of supply in the event of a fault. The safety of both property and personnel.
NC100 MCB Interpact lis cana
lis cana

5000A

Masterpact ACB

KTC busbar trunking

Prisma switchboard

Compact MCCB

KS busbar trunking

800A

Compact NS MCCB

KN busbar trunking

100A

Compact NS MCCB

NAS tap-off unit

KLE/KBA/KBB busbar trunking

40A
2

C60H MCB

Prisma distribution board

Coordination between Merlin Gerin circuit breakers and Telemecanique Canalis Busbar trunking systems

Overview
When chosing a circuit breaker to protect a busbar trunking system, it is necessary to take into account: Overload protection afforded by the upstream device: Ib Ir Inc where Ib = maximum load current Ir = circuit breaker over-current setting Inc = current rating of the busbar trunking Electrodynamic withstand of the busbar trunking: The peak current I limited by the circuit breaker must be less than the electrodynamic withstand capacity (or rated peak current) of the busbar trunking.

Coordination tables
The following tables (from page 6 onwards) for coordinating Merlin Gerin Multi 9, Compact, Compact CM and Masterpact circuit breakers with Telemecanique Canalis Busbar trunking, indicate the maximum prospective short circuit current for which the busbar is protected.

Example
Consider two 630 kVA/400 V transformers (Usc 4%) supplying a main LV switchboard for which the prospective short-circuit current on the busbars is 44 kA. From the switchboard, a 30-metre long Canalis KVC63 transmission busbar trunking system (630A) supplies a Canalis KSA63 trunking system (630A) for distribution with high-density tap-offs. A tap-off on the KSA63 trunking supplies a Canalis KSA16 trunking system. The short-circuit levels are: 44 kA downstream of circuit-breaker CB1 and at the upstream connection of the KVA63 trunking. 33 kA at the junction between the KVC63
LV main swichboard Prospective Isc 44 kA 630 kVA 400 V 630 kVA 400 V

What circuit breakers should be chosen for CB1 and CB2 to protect the installation against short-circuits ?

CB1 Prospective Isc Circuit breakers Isc protection level for KVC63 trunking Isc protection level for KSA16 trunking 44 kA NS630N (45 kA breaking capacity) 45 kA

CB2 33 kA NS160N (35 kA breaking capacity)

35 kA

Traditional circuit breaker selection method


The circuit breaker used to protect a distribution circuit is chosen according to two fundamental criteria:

Installation example

Application for Compact NS range

transmission trunking and the KSA63 trunking for high-density tap-offs.


D1 Disconnector Prospective Isc 44 kA Prospective Isc 33 kA Canalis KSA 63

CB1

CB1 = NS400H (Breaking capacity = 70 kA) A 30-meter KVC63 transmission BBT system D2 Disconnector CB2 CB2 = NS160H (Breaking capacity = 70 kA)

Ib = 360 A

Isc = 65 kA

The maximum load current Ib flowing in the supply circuit; The prospective short-circuit current Isc at a point where the circuit breaker is to be installed. The circuit breaker is chosen such that: Ir circuit breaker Ib, Breaking capacity of the circuit breaker Icu/Ics Isc.
Ib = 140 A Isc = 65 kA

Canalis KSA

The different types of Telemecanique busbar trunking


Type of busbar trunking Busbar trunking for transmission and distribution with low-density tap-offs Busbar trunking for distribution with high-density tap-offs Busbar trunking for lighting distribution and management KN 40 to 100 A (380/415 V) KLE, KBA, KBB K System (380/415 V) Low power Medium power KVC 200 to 800 A (380/415 V - 660/690 V) KSA 100 to 800 A (380/415 V - 660/690 V) High power KTC 1000 to 4000 A (380/415 V - 660/690 V) KHF 1000 to 4500 A (380/415 V - 660/690 V)

Coordination tables between Merlin Gerin circuit breakers and Telemecanique Canalis Busbar trunking Voltage: 380/415 V
Type of Canalis Busbar trunking Trunking rating (in A at 35C) Type of circuit breaker Isc max. in KA ms. Multi 9 C60H16/20 C60H25 NC100LH25 C60H40 NC100LH40 C60H63 NC100LH63 NS100N (1) NS100H (1) NS100L (1) 25 25 25 KLE-16/20 16/20 15 15 50 15 50 15 50 15 50 15 50 15 50 25 25 25 25 25 25 KBA-25 25 KBB-25 25 KBA-40 40 KBB-40 40 KN-04 40 KN-06 63 KN-10 100

Voltage: 380/415 V
Type of Canalis Busbar trunking Trunking rating (in A at 35C) Type of circuit breaker Isc max. in KA ms. Compact NS250N NS250H NS250L NS400N NS400H NS400L NS630N NS630H NS630L C801N C801H C801L C1001N C1001H C1001L Masterpact M08H1 M10H1 M08H2 M10H2 M08L1 M10L1 36 70 150 36 70 150 45 45 45 30 30 30 45 70 150 45 70 150 26 26 30 45 70 150 30 30 40 45 70 150 40 40 55 40 40 55 45 70 150 50 50 80 50 50 80 50 50 24 24 24 24 24 24 24 24 24 24 26 26 26 26 26 26 26 32 32 32 32 32 32 32 32 32 32 40 40 40 38 38 38 38 38 38 38 50 50 50 Type of Canalis Busbar trunking Trunking rating (in A at 35C) Type of circuit breaker Isc max. in KA ms. Compact C1001N C1001H C1001L C1251N C1251H Masterpact M10H1 M12H1 M16H1 M20H1 M25H1 M32H1 M40H1 M50H1 M63H1 M10H2 M12H2 M16H2 M20H2 M25H2 M32H2 M40H2 M50H2 M63H2 M10L1 M12L1 M16L1 M20L1 M25L1 KTC-10 1000 50 55 100 50 55 40 40 40 KTC-13 1350 50 70 150 50 70 50 50 50 60 60 60 60 60 65 65 65 73 73 KTC-16 1600 KTC-20 2000 KTC-25 2500 KTC-30 3000 KTC-40 4000 KTC-50 5000 KVC-20 200 35 70 100 35 35 35 45 70 150 45 70 150 45 70 150 45 70 150 45 70 150 45 70 150 40 40 70 40 40 70 36 36 36 36 40 40 50 60 110 50 60 110 40 40 40 40 55 55 KVC-31 315 KVA-40 400 KVA-63 630 KVC-80 800

(1) TM-D trip unit, rating 40 or 63 or 100 A and STR22SE rating 40 or 100 A
Type of Canalis Busbar trunking Trunking rating (in A at 35C) Type of circuit breaker Isc max. in KA ms. Compact NS100N NS100H NS100L NS160N NS160H NS160L NS250N NS250H NS250L NS400N NS400H NS400L NS630N NS630H NS630L C801N C801H C801L C1001N C1001H C1001L C1251N C1251H CM Masterpact M08H1 M10H1 M12H1 M08H2 M10H2 M12H2 M08L1 M10L1 M12L1 KSA-10 100 25 25 25 20 20 20 17 17 17 KSA-16 160 25 70 90 36 70 70 36 55 55 30 30 30 KSA-25 250 KSA-40 400 KSA-50 500 KSA-63 630 KSA-80 800

75 75 75 75

75 75 75 75

75 75 90 90

95 95

40 40 40

50 50 50

60 60 60 60 60

73 73 73 73 73

82 82 82 82

82 82 82 82

90 90 90 90

95 95

55 55

85 85 65 65 65

130 130 105 105 105

130 130 130

130 130 130

130 130 130

Coordination tables between Merlin Gerin circuit breakers and Telemecanique Canalis Busbar trunking (cont.) Voltage: 380/415 V
Type of Canalis Busbar trunking Trunking rating (in A at 35C) Type of circuit breaker Isc max. in KA ms. Compact C801N C801H C801L C1001N C1001H C1001L C1251N C1251H CM Masterpact M08H1 M10H1 M12H1 M16H1 M20H1 M25H1 M32H1 M40H1 M50H1 M63H1 M08H2 M10H2 M12H2 M16H2 M20H2 M25H2 M32H2 M40H2 M50H2 M63H2 M08L1 M10L1 M12L1 M16L1 M20L1 M25L1 KHF 1000 28 28 45 28 28 45 28 28 28 28 28 28 28 28 28 50 50 80 50 50 38 38 38 38 38 38 38 70 70 KHF 1200/1450 KHF 2200/2500 KHF 3000/3400 KHF 4000/4500

Voltage: 660/690 V
Type of Canalis Busbar trunking Trunking rating (in A at 35C) Type of circuit breaker Isc max. in KA ms. Compact NS100N NS100H NS100L NS160N NS160H NS160L NS250N NS250H NS250L NS400N NS400H NS400L 65 75 75 75 75 90 90 75 75 75 75 100 100 NS630N NS630H NS630L 75 75 100 100 C801N C801H C801L C1001N C1001H C1001L C1251N C1251H CM 100 100 125 125 Masterpact M08H1 M10H1 M12H1 M08H2 M10H2 M12H2 M08L1 M10L1 M12L1 24 24 24 24 24 24 24 24 24 24 26 26 26 26 26 26 26 26 26 26 32 32 32 32 32 32 32 32 32 32 KSA-10 100 8 10 20 8 10 20 8 10 15 KSA-16 160 8 10 75 8 10 75 8 10 20 10 17 14 8 10 75 8 10 20 10 20 28 10 20 35 10 20 35 25 26 26 10 20 35 25 29 30 10 20 35 25 35 45 25 35 45 20 20 35 25 40 60 25 40 60 25 40 38 38 38 38 38 38 38 38 38 38 KSA-25 250 KSA-40 400 KSA-50 500 KSA-63 630 KSA-80 800

28 28 28 28 28 28 28

38 38 38 38 38 38 38

90 90 90 90 90 90 90

100 100 100 100 120 120

35 35 35 28 28 28

50 50 50 42 42 42

130 130 130

130 130

Type of Canalis Busbar trunking Trunking rating (in A at 35C) Type of circuit breaker Isc max. in KA ms. Compact NS250N NS250H NS250L NS400N NS400H NS400L NS630N NS630H NS630L C801N C801H C801L C1001N C1001H C1001L Masterpact M08H1 M10H1 M08H2 M10H2 M08L1 M10L1

KVC-20 200 8 10 20 10 20 20

KVC-31 315

KVC-40 400

KVC-63 630

KVC-80 800

10 20 75 10 20 35

10 20 75 10 20 35

10 20 75 10 20 35 25 36 60 25 36 60 36 36 36 36 36 36 25 40 60 25 40 60 40 40 40 40 40 40

Coordination tables between Merlin Gerin circuit breakers and Telemecanique Canalis Busbar trunking (cont.) Voltage: 660/690 V
Type of Canalis Busbar trunking Trunking rating (in A at 35C) Type of circuit breaker Isc max. in KA ms. Compact C1001N C1001H C1001L C1251N C1251H Masterpact M10H1 M12H1 M16H1 M20H1 M25H1 M32H1 M40H1 M50H1 M63H1 M10H2 M12H2 M16H2 M20H2 M25H2 M32H2 M40H2 M50H2 M63H2 M10L1 M12L1 M16L1 M20L1 M25L1 KTC-10 1000 25 40 60 25 40 40 40 40 KTC-13 1350 25 40 60 25 40 50 50 50 60 60 60 60 60 65 65 65 65 65 KTC-16 1600 KTC-20 2000 KTC-25 2500 KTC-30 3000 KTC-40 4000 KTC-50 5000

Enhanced coordina
Enhanced coordination
One of the main keys to continuity of supply Enhanced coordination, ensures enhanced discrimination between circuit breakers is maintained, whilst going one step further to ensure that Canalis Busbar trunking is protected against the harmful thermal and mechanical stresses of a short circuit. Not only that, but the coordination and combined current limiting of two Merlin Gerin circuit breakers, means that Canalis can be provided with adequate protection by a circuit breaker operating above its normal current limiting capabilities. For example: A C60H circuit breaker could be used to offer overload and short circuit protection to KN 40A trunking up to a maximum prospective short circuit of 40kA. The following tables indicate that when an NS160H MCCB is used upstream: The maximum breaking capacity of the C60H is raised from 15kA to 40kA. Discrimination between the C60H and NS160H is to the maximum 40kA. Canalis short circuit protection is the maximum 40kA. The following tables are an easy to use, reliable source of coordination guidance, providing an opportunity for reduced installation costs and yet even higher levels of safety. These are but a few of the benefits of selecting protection and distribution equipment from the brands of a leading electrical equipment manufacturer, Schneider Electric. in an electrical installation is the use of discrimination. In the event of a fault, correctly applied discrimination will ensure that only the

65 65 75 75

75 75 75 75

75 75 85 85

85 85

protective device immediately upstream of a fault disconnects, hence the supply is maintained to other adjacent circuits.

40 40 40

50 50 50

60 60 60 60 60

73 73 73 73 73

80 80 80 80

82 82 82 82

Cascading is a principle which has been developed by Merlin Gerin and which is
85 85 85 85

recognised within the BS7671 Requirements for


85 85

Electrical Installations (wiring regulations). Cascading allows circuit breakers to be installed at a given point within an installation where the prospective short circuit current, is greater than the circuit breakers nominal breaking capacity. In order for this practice to be used, upstream protective devices are used to assist in the clearance of a short circuit. Traditionally, discrimination and cascading were principles, which needed to be considered separately. Successful cascading could be at the cost of discrimination, at higher fault current. Recent advances through the introduction of products such as Compact NS now mean that cascading and discrimination principles can be applied simultaneously. This ENHANCED DISCRIMINATION means that cascading can be applied to a product, and discrimination maintained, even at fault currents in excess of the downstream products breaking capacity. Today, Canalis is now able to become part of this coordination chain with the introduction of ENHANCED COORDINATION.

55 55

65 65 50 50 50

65 65 65 65 65

65 65 65

65 65 65

10

11

Enhanced coordination between Merlin Gerin circuit breakers and Telemecanique Canalis Busbar trunking systems

Circuit breaker selection and coordination


The use of current-limiting circuit breakers makes it possible to utilise coordination techniques. This improves circuit breaker performance in terms of breaking capacity and continuity of supply. Coordination techniques are described and recognised by the following standards: Product standards BSEN60947-1 and BSEN60947-2 BS7671 wiring regulations.

Enhanced coordination
This technique is the direct application of cascading and discrimination techniques to the protection of busbar trunking systems. For various upstream circuit breakers and upstream busbar trunking systems, the tables below indicate: 1 The level of short-circuit protection of the upstream busbar trunking;

Applied to a Canalis distribution system:


Enhanced breaking capacity of the NS 160N (CB2) up to 70 kA;

Source
CB1 = NS400H

Cascading
The use of a current-limiting circuit breaker upstream to reinforce the breaking capacity of a downstream circuit breaker.

Principle
Cascading and reinforced discrimination

Application for Compact NS range


Cascading and reinforced discrimination

2 The downstream circuit breaker and associated trip unit;

KSA40 (400 A)

CB1

3 The downstream busbar trunking and rating;


CB1 = NS400H

4 The level of enhanced discrimination of the upstream and downstream circuit breakers;
Reinforced break. cap. 70 kA CB2 Isc = 65 kA CB2 = NS160N (Breaking cap. = 35 kA)

CB2 = NS160N

5 The enhanced breaking capacity of the downstream circuit breaker; 6 The level of enhanced protection of the downstream busbar trunking.

KSA16 (160 A)

70 kA

CB2 breaking capacity

Discrimination between CB1 and CB2 ensured up to 70 kA; Protection of Canalis KSA 16 busbar trunking

Discrimination
In the event of an electrical fault on one outgoing circuit, discrimination is the ability of the electrical installation to maintain continuity of electrical supply to other adjacent circuits. As a general rule, cascading and discrimination techniques are applied independently. Schneider Electric has developed a unique system to combine cascading and discrimination. This system ensures discrimination up to the reinforced breaking capacity of the association of circuit breakers CB1 and CB2. The combination of discrimination and cascading principles is known as enhanced discrimination.
12

up to 70 kA. Principle
Cascading and reinforced discrimination

Application for Compact NS range


Cascading and reinforced discrimination

Example of a table corresponding to the above diagram.


CB1 CB1 = NS400H

Rated current of the upstream busbar trunking: 315 and 400 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking
CB2 = NS160N Isc = 65 kA

Break. cap. + discrimination reinforced 70 kA CB2 Isc = 65 kA

NS400N STR23SE / STR53UE KSA / KVC 315 and 400 A 45 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A

NS400H STR23SE / STR53UE KSA / KVC 315 and 400 A 70 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A

NS400L STR23SE / STR53UE KSA / KVC 315 and 400 A

Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

1 2 3

150 NS100H NS160H TMD / STR22SE KSA 100 A KSA 160 A

CB2 breaking capacity

Discrimination ensured up to the reinforced breaking capacity of CB2

45

45

70

70

150

150

45 45

45 45

70 70

70 70

5 6

150 70

150 70

13

Enhanced coordination tables between Merlin Gerin circuit breakers and Telemecanique Canalis Busbar trunking systems (cont.) Voltage : 380/415 V
Source

Rated current of the upstream busbar trunking: 1200 and 1350 A (cont.)
Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) C1251H STR35SE / STR55UE KTC-13 1200 and 1350 A 70 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315-400 A 50-630 A C1251H STR45AE KTC-13 1200 and 1350 A 70 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315-400 A 500-630 A

Upstream circuit breaker

Downstream circuit breaker Associated trip unit Downstream busbar trunking


Level of protection of the upstream busbar trunking Upstream busbar trunking

Reinforced cascading and discrimination between the 2 circuit breakers Downstream circuit breaker

Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

70

70

70

45

40

70

70

70

70

70

70 70

70 70

70 70

70 70

70 70

70 70

70 70

70 70

70 70

70 70

Reinforced protection of the downstream busbar trunking

Downstream busbar trunking

Rated current of the upstream busbar trunking: 1200 and 1350 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) C1251N STR35SE / STR55UE KTC-13 1200 and 1350 A 50 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315-400 A 500-630 A C1251N STR45AE KTA-12 / KTC-13 1200 and 1350 A 50 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315-400 A 500-630 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

C1251H STR35SE / STR55UE KTC-13 1200 and 1350 A 70 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A

C1251H STR45AE KTC-13 1200 and 1350 A 70 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A

70

70

70

70

70

70

70 50

70 50

70 50

70 50

70 50

70 50

50

50

50

45

40

50

50

50

50

50

50 25

50 50

50 50

50 50

50 50

50 25

50 50

50 50

50 50

50 50

Rated current of the upstream busbar trunking: 1000 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) C1251N STR35SE / STR55UE KTC-13 1200 and 1350 A 50 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A C1251N STR45AE KTC-13 1200 and 1350 A 50 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) C1001N STR35SE / STR55UE KTC-10 1000 A 50 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315-400 A 500-630 A C1001N STR45AE KTC-10 1000 A 50 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315-400 A 500-630 A

50

50

50

50

50

50

50

50

50

45

40

50

50

50

50

50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

14

15

Enhanced coordination tables between Merlin Gerin circuit breakers and Telemecanique Canalis Busbar trunking systems (cont.) Rated current of the upstream busbar trunking: 1000 A (cont.)
Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) C1001N STR35SE / STR55UE KTC-10 1000 A 50 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A C1001N STR45AE KTC-10 1000 A 50 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A

Rated current of the upstream busbar trunking: 800 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) C801N STR35SE / STR55UE KVC-80 800 A 50 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N STR23SE / STR53UE KSA / KVA / KVC 315-400 A C801N STR45AE KVC-80 800 A 50 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N STR23SE / STR53UE KSA / KVA / KVC 315-400 A

50

50

50

50

50

50

50

50

50

35

50

50

50

35

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

50 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

C1001H STR35SE / STR55UE KTC-10 1000 A 55 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315-400 A 500-630 A

C1001H STR45AE KTC-10 1000 A 55 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N NS630N STR23SE / STR53UE KSA / KVA / KVC 315-400 A 500-630 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

C801N STR35SE / STR55UE KVC-80 800 A 50 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A

C801N STR45AE KVC-80 800 A 50 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A

70

70

70

45

40

70

70

70

70

70

50

50

50

50

50

50

70 55

70 55

70 55

70 55

70 55

70 55

70 55

70 55

70 55

70 55

50 50

50 50

50 50

50 50

50 50

50 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

C1001H STR35SE / STR55UE KTC-10 1000 A 55 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A

C1001H STR45UE KTC-10 1000 A 55 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

C801H STR35SE / STR55UE KVC-80 800 A 60 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N STR23SE / STR53UE KSA / KVA / KVC 315-400 A

C801H STR45AE KVC-80 800 A 60 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS400N STR23SE / STR53UE KSA / KVA / KVC 315-400 A

70

70

70

70

70

70

70

70

70

35

70

70

70

35

70 50

70 50

70 50

70 50

70 50

70 50

70 60

70 60

70 60

70 60

70 60

70 60

70 60

70 60

16

17

Enhanced coordination tables between Merlin Gerin circuit breakers and Telemecanique Canalis Busbar trunking systems (cont.) Rated current of the upstream busbar trunking: 800 A (cont.)
Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) C801H STR35SE / STR55UE KVC-80 800 A 60 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A C801H STR45AE KVC-80 800 A 60 NS100N TMD / STR22SE 40 A 63 A 100 A KN 40 A KN 63 A KN 100 A

Rated current of the upstream busbar trunking: 315 and 400 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) NS400N STR23SE / STR53UE KSA / KVC 315 and 400 A 45 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS400H STR23SE / STR53UE KSA / KVC 315 and 400 A 70 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS400L STR23SE / STR53UE KSA / KVC 315 and 400 A 150 NS100H NS160H TMD / STR22SE KSA 100 A KSA 160 A

70

70

70

70

70

70

45

45

70

70

150

150

70 50

70 50

70 50

70 50

70 50

70 50

45 45

45 45

70 70

70 70

150 70

150 70

Rated current of the upstream busbar trunking: 500 and 630 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) NS630N STR23SE / STR53UE KSA / KVC 500 and 630 A 45 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS630H STR23SE / STR53UE KSA / KVC 500 and 630 A 70 NS100N NS160N TMD / STR22SE KSA 100 A KSA 160 A NS250N KSA 250 A NS630L STR23SE / STR53UE KSA / KVA / KVC 500 and 630 A 150 NS100H NS160H TMD / STR22SE KSA 100 A KSA 160 A NS250H KSA 250 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

NS400N STR23SE / STR53UE KSA / KVC 315 and 400 A 45 NS100N TMD / STR22SE 40 A 63 A KN 40 A KN 63 A

NS400H STR23SE / STR53UE KSA / KVC 315 and 400 A 70 NS100N TMD / STR22SE 40 A 63 A KN 40 A KN 63 A

NS400L STR23SE / STR53UE KSA / KVC 315 and 400 A 150 NS100N TMD / STR22SE 40 A 63 A KN 40 A KN 63 A

100 A KN 100 A

100 A KN 100 A

100 A KN 100 A

45

45

45

70

70

70

150

150

150

45 45

45 45

45 45

70 50

70 50

70 50

150 50

150 50

150 50

45

45

45

70

70

70

150

150

150

45 45

45 45

45 45

70 70

70 70

70 70

150 70

150 70

150 70

Rated current of the upstream busbar trunking: 200 and 250 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) 18 NS630N STR23SE / STR53UE KSA / KVA / KVC 500 and 630 A 45 NS100N TMD / STR22SE 40 A 63 A KN 40 A KN 63 A NS630H STR23SE / STR53UE KSA / KVA / KVC 500 and 630 A 70 NS100N TMD / STR22SE 40 A 63 A KN 40 A KN 63 A NS630L STR23SE / STR53UE KSA / KVA / KVC 500 and 630 A 150 NS100N TMD / STR22SE 40 A 63 A KN 40 A KN 63 A Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) 100 A KN 100 A Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) NS250N TMD / STR22SE KSA / KVC 200 and 250 A 36 NS100N TMD / STR22SE KSA-10 100 A NS250H TMD / STR22SE KSA / KVC 200 and 250 A 70 NS100N TMD / STR22SE KSA-10 100 A NS250L TMD / STR22SE KSA / KVC 200 and 250 A 150 NS100H TMD / STR22SE KSA-10 100 A

100 A KN 100 A

100 A KN 100 A

45

45

45

70

70

70

150

150

150

36

36

36

45 45

45 45

45 45

70 50

70 50

70 50

150 50

150 50

150 50

36 36

70 70

150 70 19

Enhanced coordination tables between Merlin Gerin circuit breakers and Telemecanique Canalis Busbar trunking systems (cont.) Rated current of the upstream busbar trunking: 200 and 250 A (cont.)
Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) NS250N TMD / STR22SE KSA / KVC 200 and 250 A 36 NS100N TMD / STR22SE 40 A 63 A KN 40 A KN 63 A NS250H TMD / STR22SE KSA / KVC 200 and 250 A 70 NS100N TMD / STR22SE 40 A 63 A KN 40 A KN 63 A NS250L TMD / STR22SE KSA / KVC 200 and 250 A 150 NS100N TMD / STR22SE 40 A 63 A KN 40 A KN 63 A

Rated current of the upstream busbar trunking: 160 A


Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) 100 A KN 100 A Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA) NS160N TMD / STR22SE KSA 160 A 36 NC100L 40 A KN 40 A NC100L 63 A KN 63 A NS160H TMD / STR22SE KSA 160 A 70 C60H 40 A KN 40 A C60H 63 A KN 63 A NC100L 40 A KN 40 A NC100L 63 A KN 63 A NC100LH 40 A KN 40 A NC100LH 63 A KN 63 A

100 A KN 100 A

100 A KN 100 A

36

36

36

36

36

36

36

36

36

36

36

40

40

50

50

70

70

36 36

36 36

36 36

70 50

70 50

70 50

150 50

150 50

150 50

36 36

36 36

40 40

40 40

50 50

50 50

70 50

70 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit (rating A) Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

NS250N TMD / STR22SE KSA / KVC 200 and 250 A 36 NC100L 25/40 KBA / KBB 25 - 40 A

NS250H TMD / STR22SE KSA / KVC 200 and 250 A 70 C60H 16 KLE 16 A C60H 25/40 KBA / KBB 25 - 40 A NC100L 25/40 KBA / KBB 25 - 40 A NC100LH 25/40 KBA / KBB 25 - 40 A

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit (rating A) Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

NS160N TMD / STR22SE KSA 160 A 36 NC100L 25/40 KBA / KBB 25 - 40 A C60H 16 KLE 16 A

NS160H TMD / STR22SE KSA 160 A 70 C60H 25/40 KBA / KBB 25 - 40 A NC100L 25/40 KBA / KBB 25 - 40 A NC100LH 25/40 KBA / KBB 25 - 40 A

36

40

40

50

70

36

40

40

50

70

36 36

40 40

40 40

50 50

70 50

36 36

40 40

40 40

50 50

70 50

Upstream circuit breaker Associated trip unit Upstream busbar trunking Level of protection of the upstream busbar trunking (kA) Downstream circuit breaker Associated trip unit Downstream busbar trunking Enhanced discrimination limit between upstream and downstream circuit breakers (kA) Enhanced breaking capacity of the downstream circuit breaker (kA) Enhanced protection of the downstream busbar trunking (kA)

NS250N TMD / STR22SE KSA / KVC 200 and 250 A 36 NC100L 40 A KN 40 A NC100L 63 A KN 63 A

NS250H TMD / STR22SE KSA / KVC 200 and 250 A 70 C60H 40 A KN 40 A C60H 63 A KN 63 A NC100L 40 A KN 40 A NC100L 63 A KN 63 A NC100LH 40 A KN 40 A NC100LH 63 A KN 63 A

36

36

40

30

50

50

70

70

36 36

36 36

40 40

30 30

50 50

50 50

70 50

70 50

20

21