Basic Design PLTG 28 MW Siak Pusako

PLTG Siak - Pusako 28 MW


1 Electrical system Generator Generator Circuit Breaker Switchgear Generator Transformator Switchyard 115 kV Gas Circuit Breaker DS and DSE (SWITCH) Fuse Cut Out Auxiliary Transformer Synchronous type, 13.8 kV, 60 Hz, Noise </= 85 dB Vacuum, 13.8 kV 13.8 kV, 1200 A, 60 Hz, 16 Bay 13.8 kV/115 kV, 60 Hz, ONAN/ONAF with LTC Ring bus, 115 kV, 60 Hz 115 kV, 1200 A, 60 Hz 115 kV Motor Operated Switch For 13.8 kV and 115 kV System 2500 KVA, 13,8 kV / 480 kV, 60 Hz 1600 kVA, 13,8 kV / 480 V, 60 Hz 500 kVA, 13,8 kV / 0.22 kV, 60 Hz Available 3 Phasa, 1000 kw, 480 V, 60 Hz, pf=0.8 Station DC Distribution Center,Battery and battery Charger 125 VDC, 110 VDC, 24/48 VDC, 125 VDC Distribution Panel with breaker 125 VDC or 110 VDC for each gas power station and CCR Relay protection for Control and Instrument Duplex Panel 115 kV and 13.8 kV system for protection equipment Minimum conductor 240 mm2 MV cable 12/20 kV, LV 0.6/1 kV For power MV and LV For control, lighting, instrument, and communication Class 0.2 Stated feed 27 pcs 3 Unit LM 1800e with NDC 28 MW 3 Unit (following Generator set) MV Switchgear 3 unit, 20 MVA Ring bus type, 3 incoming bay and 3 outgoing bay Minimum 6 unit Including High Speed earthing or grounding switch and Isolation switch N/A For Gas Compressor dan BOP SS#1 Transformer stated in feed by BOB SS#2 Transformer stated in feed by BOB Supplied from Emergency Diesel Generator 1000 kw, 480 V, 60 Hz, pf=0.8 Complete with piping, tank and accessories control, protection and instrumentation system 110 V DC for distribution panel for each GTG, 125 V DC battery and charger for CCR, 115 kv and 13.8 kV, 24/48 V DC for GTG control and instrumentation complete with rectifier, auctioning diode, solid state regulation transformer, static transfer inverter, alternate supply regulating transformer, static transfer, instrumentation and distribution panel Comply with relevant International Standard, for protection plan with safely disconnected System shall be designed in accordance with IEC or IEEE standard, Including Grounding grid 115 kV, Grounding Equipment, Grounding LA, Grounding Control Building, Grounding System MV cable have XLPE Insulation, LV cable have XLPE or PVC insulation Control, instrumentation, and Communication cable have PVC insulation TBA TBA Including calibration certificate TBA

Design Requirement

Remark

Black Start Capabiity Emergency Diesel Generator DC Power System Uninterruptible Power Supply System Protective Relaying and Circuit Breaker Control System Surge and Lightning Protection System Equipment Grounding Power Cable Control and data Cable Cable tray or ladder and conduits & fittings Underground electrical duct Metering System Potensial Transformer Lighting and clock System Plant Communication System Panel, MCC and Power Distribution Center

Plants area, All Building include CCR, Cubicle, Road, Shall be based on recognized international standard and usage Emergency, Security Lighting, Stack Lighting, Flood Light Emergency and maintenance telephone, radio telephone, PABX shall be fully compatible with public Service Telephone Network (PT TELKOM) Intercom Panel Switchgear, Panel Gas Compressor, Panel MCC GTG, Panel Main Distribution Board, TCP, GCP, DB AC 220 V, DB DC 125 V, Protection Panel MV 13.8 kV, Panel LV 480 V, Panel LV 220 V Panel, Control Panel Included in vendor system supply LV distribution panel, local motor starter panel Equip with LCD display for monitoring, control system Monitoring and Security and common control desk For Junction Boxes, Room emergency diesel generator room, central control building, admin building For All equipment and building Governing system, GTG tripping system, GTG control system, lubricating oil system, fuel control system, cooling water system Monitoring analysis and computation , logging including alarm daily & weekly, LCD display Tripping and safety shutdown system Exciter control system, governing, overspeed trip HSD & Natural Gas Fuel Oil Control Including Ligtning Arrester 13.8 kV and 115 kV for Main Equipment, Switchyard and building

Miscellaneous Electrical Close Circuit Television System (CCTV) Air Conditioning System

Lightning Protection System Instrumentation & Control Gas Turbine Control System Plant Monitoring System and Man Machine Interface Generator Group Control System GT Generator Control System Turbine Oil and barring gear Fuel control system

Catatan (Berdasarkan Feed Document) :


- Switchyard menggunakan tipe Ring Bus - Tipe, Jenis, Merek, dan Kapasitas masing-masing Pembangkit Listrik Tenaga Gas harus sama (tipikal) - Jumlah pembangkit listrik minimal 3 unit dan maksimal 6 unit - Jika salah satu unit pembangkit trip maka tidak akan terjadi pelepasan beban (load shedding) dibuktikan dengan test load dan step load - Daya yang dihasilkan pembangkit harus memenuhi NDC 28 MW dikurangi BOP dan rugi-rugi peralatan listrik dan diukur pada tegangan 115 kV setelah Transformator Stepup - Availability sistem 99.5 % - Availability individu 97 % - Maintenance maksimum 43 jam pertahun - Realibility 99 %