You are on page 1of 4

I W AIN W R O D N D PE O SL

TH

PA

HYX / PHYX Series


Horizontal Recessed Ceiling Fan Coils 3 - 5 Tons Cooling Cooling Only (No Electric Heat)

The space-saving HYX / PHYX Series fan coils are only 16 1/2" high , allowing them to recess in a ceiling. Recessed ceiling fan coils save valuable oor space and eliminate costly "equipment" closets. The HYX is an "uncased" ceiling fan coil. The PHYX is the same product but with a factory installed return air plenum. With the PHYX model, return air can be eld ducted directly to the fan coil plenum. The PHYX plenum can also be eld converted from end return to bottom return.
HYX Series
(HYB shown)

The HYX / PHYX fan coils are compatible with most split-system condensing units and heat pumps. Contact the factory for correct matches with outdoor units. All HYX / PHYX fan coils include a 240/24V transformer and are completely prewired. Sloped drain pans allow positive drainage of condensate.

PHYX Series
(PHYB shown) (with return air plenum)

Standard Features: Drain pan has 3/4" NPT primary and secondary (overow) ttings 240V motor, 24V controls Copper tube/aluminum n cooling coils Insulated and coated galvanized steel drain pan is sloped for proper drainage Higher efciency cooling coil with piston-type metering device. Contact factory for correct match with outdoor unit Throw away lter (PHYX only) 4-speed motors Optional Accessories: (Field installed) Condensate overow switch (Part # SS3) Factory or eld installed TXV's (R22 or R410A)

FIRST OPERATIONS, LP - P.O. Box 270969 - Dallas, Texas 75227 - Ph. (214) 388-5751 - Fax (214) 388-2255 - www.rstco.com

HYX Series
3, 4, and 5 tons
(See P. 4 for Model Numbers)
BLOWER DATA NOM. COOL BTUH MIN. CKT. AMPACITY 230 208 MAX. CKT. PROTECTION 230 208 CFM vs. EXTERNAL STATIC PRESSURE BLOWER SPEED HIGH MED. HI MED. LOW LOW HIGH MED. HI MED. LOW LOW HIGH MED. HI MED. LOW LOW 0.1 1530 1200 930 650 1700 1320 1040 680 2250 1760 1490 1140 0.2 1500 1150 880 580 1650 1260 970 590 2200 1680 1380 1020 0.3 1450 1110 830 500 1600 1200 890 500 2140 1620 1310 930 0.4 1400 1060 780 430 1550 1130 810 400 2080 1550 1230 840 0.5 1360 1010 720 360 1490 1050 720 320 2020 1480 1150 740 0.6 1300 950 650 300 1420 960 620 220 1950 1400 1050 640

UINT MODEL

HP

*AMPS (240V)

FEATURES
1. 4-speed direct drive motors 2. 1/2" copper tubing 3. Piston-type metering device for heat pump or straight cool operation 4. Primary and secondary condensate drains on one end 5. Rubber isolation grommets 6. 208-240/1/50-60Hz. motors (2) 7. 24V transformer

36HYX0

36,000

1/5

4.4

5.5

5.5

15

15

48HYX0

48,000

1/5

4.4

5.5

5.5

15

15

60HYX0

60,000

1/4

5.8

7.5

7.5

15

15

Notes: * Amps is total for (2) motors * Blower data is with 240V/1PH/60Hz. motors

PHYSICAL DIMENSIONS
MODEL 36HYX 48HYX 60HYX A 41 51 60 B 32-1/2 42-1/2 51-1/2 C 28 38 47 D 31-1/4 41-1/4 50-1/4

Approved for installation with 0" clearance to combustible materials

In keeping with its policy of continuous progress and product improvement, First Operations reserves the right to make changes without notice. Maintenance for all First Co. products is available under "Product Maintenance" at www.rstco.com.

-2-

PHYX Series (HYX with plenum)


3, 4, and 5 tons
(See P. 4 for Model Numbers)
BLOWER DATA NOM. COOL BTUH MIN. CKT. AMPACITY 230 208 MAX. CKT. PROTECTION 230 208 CFM vs. EXTERNAL STATIC PRESSURE BLOWER SPEED HIGH MED. HI MED. LOW LOW HIGH MED. HI MED. LOW LOW HIGH MED. HI MED. LOW LOW 0.1 1480 1160 910 620 1640 1240 960 620 2190 1700 1410 1060 0.2 1440 1110 860 550 1590 1210 920 590 2130 1630 1340 980 0.3 1400 1060 800 490 1540 1140 850 500 2060 1560 1260 900 0.4 1350 1010 740 420 1480 1060 780 420 1990 1480 1180 810 0.5 1300 960 670 350 1410 980 700 330 1920 1400 1100 720 0.6 1240 890 600 280 1340 900 620 240 1840 1310 1010 610

UINT MODEL

HP

*AMPS (240V)

FEATURES
1. 4-speed direct drive motors 2. 1/2" copper tubing 3. Piston-type metering device for heat pump or straight cool operation 4. Primary and secondary condensate drains on one end 5. Return air plenum - eld convertible from end return to bottom return 6. Throw away lter 7. Rubber isolation grommets 8. 208-240/1/50-60Hz. motors (2) 9. 24V transformer

36PHYX0

36,000

1/5

4.4

5.5

5.5

15

15

48PHYX0

48,000

1/5

4.4

5.5

5.5

15

15

60PHYX0

60,000

1/4

5.8

7.5

7.5

15

15

Notes: * Amps is total for (2) motors * Blower data is with 240V/1PH/60Hz. motors

PHYSICAL DIMENSIONS
MO D E L 36PHYX 48PHYX 60PHYX A 41 51 60 B 32-1/2 42-1/2 51-1/2 C 28 38 47 D 31-1/4 41-1/4 50-1/4 E 28-1/4 38-1/4 47-1/4 F 28 38 47 FILTER SIZE 14 X 28 X 1 14 X 38 X 1 14 X 47 X 1

Approved for installation with 0" clearance to combustible materials

In keeping with its policy of continuous progress and product improvement, First Operations reserves the right to make changes without notice. Maintenance for all First Co. products is available under "Product Maintenance" at www.rstco.com.

-3-

Model Numbers:

FACTORY INSTALLED TXVS MODEL SIZE (BTU) 36,000 48,000 60,000 MODEL (PISTON) 36(P)HYX0 48(P)HYX0 60(P)HYX0 MODEL (R22 TXV) 36(P)HYX0 w/R22 TXV 48(P)HYX0 w/R22 TXV 60(P)HYX0 w/R22 TXV MODEL (R410A TXV) 36(P)HYX0 w/R410A TXV 48(P)HYX0 w/R410A TXV 60(P)HYX0 w/R410A TXV

All TXV's are approved for cooling only or heat pump operation.
NOTE: Expansion valve requirement depends on the selected outdoor unit. Go to www.rstco.com or contact the factory for assistance.

ACCESSORIES - (all eld installed)


EXPANSION VALVE KITS (Field installed) (cooling only or heat pump) PART NUMBER R22 9EVR22-2 9EVR22-3 R410A 9EVR410-1 9EVR410-2 36(P)HYX 48/60(P)HYX FITS 36(P)HYX 48/60(P)HYX

NOTES: 1. Above expansion valve kits are approved for both cooling only (non heat pump) and heat pump applications. 2. Valves are external equalizing, internal bleed. 3. Valves have screw-on connections.

In keeping with its policy of continuous progress and product improvement, First Operations reserves the right to make changes without notice. Maintenance for all First Co. products is available under Product Maintenance at www. rstco.com.

Catalog No. HYX/PHYX1007 (Replaces HYX/PHYX906) -4-