Xantrex, the Schneider Electric logo, and Xantrex are trademarks or registered trademarks of the Schneider Electric group of companies. No part of this document may be reproduced in any form or disclosed to third parties without the express written consent of: Xantex Technology Inc. 161-G south Vasco Road Livermore, California USA 94551.
Xantrex, the Schneider Electric logo, and Xantrex are trademarks or registered trademarks of the Schneider Electric group of companies. No part of this document may be reproduced in any form or disclosed to third parties without the express written consent of: Xantex Technology Inc. 161-G south Vasco Road Livermore, California USA 94551.
Xantrex, the Schneider Electric logo, and Xantrex are trademarks or registered trademarks of the Schneider Electric group of companies. No part of this document may be reproduced in any form or disclosed to third parties without the express written consent of: Xantex Technology Inc. 161-G south Vasco Road Livermore, California USA 94551.
Grid-Tied Photovoltaic Inverters Xantrex GT500 E Xantrex GT630 E Xantrex GT500 E GI Xantrex GT630 E GI Xantrex GT630 E GI 1K
Operation Manual www.schneider-electric.com Xantrex GT500 E 500 kW and Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters Operation Manual www.schneider-electric.com Trademarks Schneider Electric, the Schneider Electric logo, and Xantrex are trademarks or registered trademarks of the Schneider Electric group of companies. Other trademarks, registered trademarks, and product names are the property of their respective owners and are used herein for identification purposes only. Notice of Copyright Copyright 2009, 2010 Xantrex Technology Inc. All rights reserved. No part of this document may be reproduced in any form or disclosed to third parties without the express written consent of: Xantrex Technology Inc. 161-G South Vasco Road Livermore, California USA 94551 Xantrex Technology Inc. reserves the right to revise this document and to periodically make changes to the content hereof without obligation or organization of such revisions or changes unless required to do so by prior arrangement. Exclusion for Documentation UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (XANTREX) (A) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION; (B) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSSES, DAMAGES, COSTS OR EXPENSES, WHETHER SPECIAL, DIRECT, INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USERS RISK; AND (C) REMINDS YOU THAT IF THIS MANUAL IS IN ANY LANGUAGE OTHER THAN ENGLISH, ALTHOUGH STEPS HAVE BEEN TAKEN TO MAINTAIN THE ACCURACY OF THE TRANSLATION, THE ACCURACY CANNOT BE GUARANTEED. APPROVED XANTREX CONTENT IS CONTAINED WITH THE ENGLISH LANGUAGE VERSION WHICH IS POSTED AT WWW.SCHNEIDER-ELECTRIC.COM. Date and Revision May 2010 Revision A Part Number 975-0582-01-01 Contact Information www.schneider-electric.com
North America 1 408 987 6255 1 925 245 1022 re.techsupport@schneider-electric.com La France +0825012999 fr-re-techsupport@fr.schneider-electric.com Deutschland +49 (0) 180 575 6575 +49 (0) 2102 404 7101 solarservice@de.schneider-electric.com Espaa +34 93 498 7466 +34 93 305 5026 re.techsupport@es.schneider-electric.com L'Italia +39 035 4151111 +39 035415 3200 IT-pronto-contatto@it.schneider-electric.com For other country details please contact your local Schneider Electric Sales Representative or visit our website at: http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page iii
About This Manual Purpose The purpose of this Operation Manual is to provide explanations and procedures for operating, maintaining, and troubleshooting the Schneider Electric Xantrex GT500 E 500 kW and the Schneider Electric Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters. Installation instructions are available in the Xantrex GT500 E and Xantrex GT630 E Planning and Installation Manual. Scope This Manual provides safety guidelines and information about operating and troubleshooting the unit. Audience This Manual is intended for anyone who needs to operate the Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters. Operators must be familiar with all the safety regulations pertaining to operating high-voltage equipment as dictated by local code. Operators must also have a complete understanding of this equipments features and functions. The Xantrex inverter must be installed by qualified personnel as described in Xantrex GT500 E and Xantrex GT630 E Planning and Installation Manual. Installation, servicing and maintenance must be performed by qualified personnel. Qualified personnel have training, knowledge, and experience in: installing electrical equipment and PV power systems (up to 1000 V), applying all applicable installation codes, analyzing and reducing the hazards involved in performing electrical work, and, selecting and using Personal Protective Equipment (PPE). Organization This Manual is organized into four chapters and one appendix. Chapter 1, Introduction contains information about the features and functions of the Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters. Chapter 2, Operation contains information on the basic operation of the Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters. Chapter 3, Troubleshooting contains information and procedures for operators to perform basic troubleshooting of the Xantrex inverter. Chapter 4, Preventative Maintenance contains information for site maintenance personnel on when to book an appointment with qualified personnel for preventative maintenance on the Xantrex inverter. About This Manual iv 975-0582-01-01
Appendix A provides the environmental and electrical specifications for the Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters. Conventions Used The following conventions are used in this guide. Product Names This manual includes information for two products: Xantrex GT500 E and Xantrex GT630 E. Both inverters can have Grid Interactive Options (VAR control and low voltage ride-through). The Xantrex GT630 E GI can have the additional option of 1000 Vdc input voltage. Unless explicitly stated otherwise, the term Xantrex inverter will be used to describe inverters both with and without any of the options. Abbreviations and Acronyms Related Information You can find more information about Schneider Electric as well as its products and services at www.schneider-electric.com. WARNING Warnings identify conditions or practices that could result in personal injury or loss of life. CAUTION Cautions identify conditions or practices that could result in damage to the unit or other equipment. Important: These notes describe things which are important for you to know, but not as serious as a caution or warning. ANSI American National Standards Institute DSP Digital Signal Processor FPGA Field Programmable Gate Array GUI Graphical User Interface IEEE Institute of Electrical and Electronics Engineers IGBT Insulated Gate Bipolar Transistor IPM Intelligent Power Module NFPA National Fire Protection Association PSL Phase-Shift Loop PV Photovoltaic UFCU Universal Frontpanel Control Unit v
Important Safety Instructions READ AND SAVE THESE INSTRUCTIONS - DO NOT DISCARD This manual contains important safety instructions for the Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters Xantrex inverter that must be followed during operation and maintenance procedures. WARNING: Risk of electric shock, explosion, and arc flash Before installing the Xantrex inverter read all instructions, cautionary markings, and all other appropriate sections of this manual. Exercise extreme caution at all times to prevent accidents. Failure to follow these instructions will result in death or serious injury. WARNING: Risk of electric shock, explosion, and arc flash. Risk of equipment damage Unsafe conditions and damage to the inverter may result if the instructions, and electrical, physical, and environmental installation specifications in this manual are not obeyed. WARNING: Risk of electric shock, explosion, and arc flash The Xantrex inverter enclosures contain exposed conductors and parts operating at lethal voltage and at high enough energy to create an arc flash. Electrocution or severe burns may result. The enclosure doors should remain closed with the latches tightened, except during installation, maintenance or testing. Installation, servicing and maintenance must be performed by qualified personnel. To reduce the risk of electric shock or arc flash, do not open any doors or remove any covers unless you are qualified to do so, are properly equipped with appropriate personal protective equipment, and have locked out and tagged out all sources of energy and verified that the inverter is de-energized. Do not open the cabinet doors if moisture is present (rain or heavy dew). WARNING: Multiple sources with risk of electric shock, explosion, and arc flash The Xantrex inverter is energized from the PV array, from the AC grid, and from an auxiliary AC source (backed up with a Xantrex UPS for Xantrex GT500 E & Xantrex GT630 E units with low-voltage ride-through capability). All 3 sources (4 including a Xantrex UPS) must be disconnected, locked-out and tagged-out, and all circuits tested to verify that the inverter is fully de-energized, by following the Lock-out and Tag-out and other Safety instructions found in the Important Safety chapter of your Xantrex GT500 E and Xantrex GT630 E Grid-Tied Photovoltaic Inverter Planning and Installation Manual (Part #: 975-0581-01-01), before servicing or maintenance. Opening the AC and DC disconnect switches on the inverter does not remove all power from the inverter. Wait 20 minutes for the DC bus capacitors, located within the cabinet, to discharge after removing power. Safety vi 975-0582-01-01
WARNING: Limitations on use The Xantrex inverter is not intended for use in connection with life support systems or other medical equipment or devices. The Xantrex inverter may only be used in grid-interconnected PV systems; it is not suitable for any other application areas. WARNING: Explosion hazard The IGBT module may explode in the event of a major malfunction. Do not operate the inverter with the doors open. WARNING: Crush hazard The inverters have a very high balance point and can easily fall over if they are moved without caution. The inverter must be securely attached to the mounting surface after positioning. WARNING: Burn hazard Inverters contain internal components that become hot during normal operation. Use caution when servicing if inverter has been operating. Allow time for parts to cool before contact. WARNING: Risk of electric shock, explosion, and arc flash When installing the Xantrex inverter use only components recommended or sold by the manufacturer. Doing otherwise may result in a risk of fire, electric shock, injury to persons, and will void the warranty. WARNING: Risk of electric shock, explosion, and arc flash Do not attempt to operate the Xantrex inverter if it has been dropped, or received more than cosmetic damage during transport or shipping. If the Xantrex inverter is damaged, or suspected to be damaged, see the Warranty for this unit in the Xantrex GT500 E and Xantrex GT630 E Planning and Installation Manual. WARNING: Risk of fire and equipment damage The overcurrent protective devices within the Xantrex inverter are intended for protecting the Xantrex inverter circuitry only. It is the installer's responsibility to determine the overcurrent protection required for the PV array or external AC or DC cabling, in accordance with the applicable installation codes. WARNING: Risk of electric shock, explosion, and arc flash. Risk of equipment damage Unsafe conditions and damage to the inverter may result if the inverter is energized with condensation present inside the unit. Storage, transportation, and operational conditions must ensure that internal condensation is not created, or that the inverter is dry before energizing. Obey the environmental specifications and classifications in Table A-2 and Table A-3. Safety 975-0582-01-01 vii
Personal Safety Follow these instructions to ensure your safety while working with the Xantrex inverter. Qualified Personnel Only qualified personnel shall perform the installation, initial operation and maintenance of the Xantrex inverter. Follow all applicable workplace safety procedures and regulations regarding work practices, personal protective equipment (PPE), installation and test equipment, etc. Service personnel must be equipped with personal protective equipment appropriate for the work to be performed, which may include some or all of the following: Electrically rated safety gloves Safety glasses Ear protection Electrical safety shoes/boots Electrical safety hard hat Padlocks and tags (for lock-out/tag-out of disconnects) Appropriately rated meter to verify that the circuits are de-energized (1000 Vac and DC rated, minimum) Check local safety regulations for other requirements. All servicing must be done in accordance with the instructions and safety information found in your Xantrex GT500 E and Xantrex GT630 E Grid-Tied Photovoltaic Inverter Planning and Installation Manual (Part #: 975-0581-01-01). CAUTION: Risk of overheating The inverters have supply air and exhaust air areas, which must remain unobstructed. The inverter can overheat and will cease power production if the installation, maintenance and clearance instructions are not adhered to. Ensure you remove the tracks required for transportation located at the top of the inverter. CAUTION: Risk of equipment damage Inverter electronics can be destroyed by static charge. Wear static protection gear, and use anti-static tools and procedures when servicing the inverter. Install external surge arrestors at the input of the UPS and ensure the CCU communication interfaces also have over voltage protection devices. viii ix
1 Introduction Chapter 1, Introduction contains information about the features and functions of the Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters. The Xantrex GT500 E 500 kW Grid-Tied Photovoltaic Inverter with optional Ride- through Capability and optional VAR Control is a utility interactive, three-phase power conversion system for grid- connected photovoltaic arrays with a power rating of 500 kW. The Xantrex GT630 E 630kW Grid-Tied Photovoltaic Inverter with optional Ride- through Capability, optional VAR Control and optional 1000 Vdc, which provides input range capability up to 1000 Vdc, is a utility interactive, three-phase power conversion system for grid-connected photovoltaic arrays with a power rating of 630 kW. Introduction 12 975-0582-01-01
Description of the Xantrex inverter Designed to be easy to install and operate, the Xantrex inverter automates start- up, shutdown, and fault detection scenarios. With user-settable power tracking that matches the inverter to the array and adjustable delay periods, users are able to customize start up and shut down sequences. Multiple Xantrex GT500 E or Xantrex GT630 E inverters are easily paralleled for larger power installations. The Xantrex inverter power conversion system consists of a pulse-width modulated (PWM) inverter, switch gear for isolation and protection of the connected AC and DC power sources. Housed in a rugged IP20 rated, galvanized steel enclosure, the Xantrex inverter incorporates sophisticated Intellimod
(IPM) insulated gate bipolar transistors (IGBTs) as the main power
switching devices. An advanced, field-proven, maximum peak power tracker (MPPT) integrated within the Xantrex inverter control firmware ensures the optimum power throughput for harvesting energy from the photovoltaic array. Protection Features The advanced design of the Xantrex inverter includes an EMI output filter and the main AC contactor located electrically on the inverter side of the isolation transformer. Additionally, the Xantrex inverter integrated controller contains self- protection features including over and under-voltage and frequency safeguards. An integral anti-island protection scheme (Xantrex GT500 E and Xantrex GT630 E base units only) prevents the inverter from feeding power to the grid in the event of a utility outage. User Interface The Xantrex inverter includes a local user interface comprised of a 3 (stand-by/ power-on) switch (called ON/OFF on older models), a keypad, and a 4-line, 80 character display. The display provides an interface for the user to query Xantrex inverter system status, control, metering/data logging and protective functions. These features can be accessed remotely using an optional communication kit. Physical Characteristics The Xantrex inverter comes in a set of three enclosures to house the Electronics described above. The left one-door section is the AC interface enclosure (+H0). The center two-door section is the main inverter enclosure (+H1). The right one- door section is the DC interface enclosure (+H2). The three enclosures are constructed and delivered as one complete assembly. These components are identified in Figure 1-1 on page 13 and the dimensions are identified in Figure A-1 on page A6. Grid Interactive Options The Xantrex GT500 E GI or Xantrex GT630 E GI has all of the features of the Xantrex GT500 E or Xantrex GT630 E base unit (respectively), with the addition of either VAR control or VAR control and low voltage ride through together. The low- voltage ride-through capability allows the inverter to continue operation during dips in the AC voltage and power-factor compensation, by using array, not line voltage to compensate for extra capacitance or inductance on the grid based on the user-settable parameters. To facilitate these features, the ride-through option does not provide anti-islanding protection. The VAR control provides reactive power control for full power across the power factor range. 1000 V Input Option The Xantrex GT630 E GI 1K enables the Xantrex GT630 E to accept input voltages up to 1000 Vdc. Physical Characteristics 975-0582-01-01 13
Physical Characteristics The Xantrex inverter comes in a set of 3 enclosures to house the electronics described above. The left 1-door section is the AC interface enclosure (+H0). The center 2-door section is the inverter enclosure (+H1). The right 1-door section is the DC interface enclosure (+H2). The 3 enclosures are constructed and delivered as one complete assembly. The Xantrex inverter is IP20 rated. These components are identified in Figure 1-1. Figure 1-1 Xantrex inverter Major Components DC Interface Enclosure +H2 AC Interface Enclosure -HO Main Inverter Enclosure (Front View) +H1 Introduction 14 975-0582-01-01
AC Interface Enclosure (+H0) The AC interface enclosure houses the connection for the utility (see Figure 1-1 to locate the AC interface enclosure). This enclosure contains the AC disconnect switch, which has an integral over-current and over-temperature protection. The terminals for the auxiliary AC voltage and the main AC contactor are also located in this enclosure. Inverter Enclosure (+H1) The Xantrex inverter inverter enclosure contains the power distribution panel, the converter control unit, and power electronics matrix. Also found within the main inverter enclosure are some of the system protection devices (such as the sense and control power fuses). Power Distribution Panel Located in the middle right side of the inverter enclosure, this power distribution panel contains many of the Electromechanical, protective, and control power components necessary to support the operation of the Xantrex inverter. Converter Control Unit The control unit is a digital signal processor (DSP) based control board that performs numerous control and diagnostic functions associated with Xantrex inverter operation. Its most significant tasks are control of the Xantrex inverter electromechanical components and power electronics converters and communication with the universal front panel control unit, and system sensors. The control unit also contains the necessary DC power supplies to support its operation. Power Electronics Matrix The power conversion matrix is located behind the inner doors of the inverter enclosure. The matrix consists of switching transistors (IGBTs), transistor gate drive electronics, laminated bus structure, DC capacitors and an aluminium extrusion heatsink with cooling fans. The fans are located below the heatsink. DC Interface Enclosure (+H2) The DC interface serves as the connection interface between the PV array and the Xantrex inverter (see Figure 1-1 on page 13 to locate the DC interface). This enclosure is where the DC disconnect switch resides. Optionally the DC interface enclosure can include PV string fuses and master/slave combiner contactors. Operator Interface Controls 975-0582-01-01 15
Operator Interface Controls Operator interface controls are located on the front door of the inverter enclosure. These controls include a 3 (stand-by/power-on) switch (called ON/OFF on older models), an emergency stop (E-STOP) pushbutton, a 4-line display and a keypad called the universal frontpanel control unit (UFCU). Figure 1-2 Xantrex inverter Operator Interface Components Display Universal Frontpanel Control Unit (UFCU) 3 stand-by/ power-on Switch Main Inverter Enclosure (Front View) DC Interface Enclosure E-STOP Pushbutton AC Interface Enclosure Introduction 16 975-0582-01-01
3 stand-by/power-on Switch The Xantrex inverter incorporates a maintained position 3 (stand-by/power-on) switch (called ON/OFF on older models) located on the right center door, under the main control display. Under normal conditions, the 3 (stand-by/power-on) switch is in the 2 (power-on) position. Turning the switch to the 1 (stand-by) position initiates an immediate controlled shutdown of the Xantrex inverter and opens both the main AC contactor and DC disconnect switch within the unit. Turning the switch to the 1 (stand-by) position will not de-energize unit; it only stops power production. The main AC contactor and DC disconnect switch cannot be closed unless the switch is in the 2 (power-on) position. The Xantrex inverter is prevented from being restarted until the 3 (stand-by/power-on) switch is turned back to the 2 (power-on) position. Figure 1-3 3 stand-by/power-on Switch Operator Interface Controls 975-0582-01-01 17
Emergency Stop (E-STOP) The Xantrex inverter incorporates a maintained position E-STOP pushbutton located on the inverter enclosure. Under normal conditions, the E-STOP pushbutton is in the CLOSED (extended) position. Pushing the pushbutton to the OPEN (depressed) position initiates an immediate controlled shutdown of the Xantrex inverter and opens both the main AC contactor and DC disconnect switch within the unit. Both the main AC contactor and DC disconnect switch cannot be closed unless the pushbutton is in the CLOSED (extended) position. The Xantrex inverter is prevented from being restarted until the E-STOP pushbutton is in the CLOSED (extended) position. Provisions are supplied for adding a remote emergency stop circuit. Figure 1-4 Emergency Stop Introduction 18 975-0582-01-01
AC and DC Disconnect Switches The main AC disconnect switch is located inside the AC interface enclosure and the DC disconnect switch is located inside the DC interface enclosure. Additional external AC and DC disconnecting means, capable of being locked-out and tagged-out, must be provided as part of the installation, to facilitate safe servicing of the inverter. The main AC and DC disconnect switches are each equipped with an auxiliary contact block which enables the switch to be used as a load break disconnect. In the event of a fault, the DC disconnect switch automatically opens, and it is capable of breaking the full DC load current. For Xantrex GT500 E & Xantrex GT630 E units with UPS backup, the UPS breaker (-F5) is installed in the center (+H1) enclosure. All Xantrex inverter enclosure doors must be closed and locked during normal operation. WARNING: Multiple sources with risk of electric shock, explosion, and arc flash The Xantrex inverter is energized from the PV array, from the AC grid, and from an auxiliary AC source (backed up with a Xantrex UPS for Xantrex GT500 E & Xantrex GT630 E units with low-voltage ride-through capability). All 3 sources (4 including a Xantrex UPS) must be disconnected, locked-out and tagged-out, and all circuits tested to verify that the inverter is fully de-energized, by following the Lock-out and Tag-out and other Safety instructions found in the Important Safety chapter of your Xantrex GT500 E and Xantrex GT630 E Grid-Tied Photovoltaic Inverter Planning and Installation Manual (Part #: 975-0581-01-01), before servicing or maintenance. Opening the AC and DC disconnect switches on the inverter does not remove all power from the inverter. Wait 20 minutes for the DC bus capacitors, located within the cabinet, to discharge after removing power. Operator Interface Controls 975-0582-01-01 19
Figure 1-5 AC and DC Disconnect Switches AC Disconnect Switch (-Q1) AC Interface Enclosure DC Disconnect Switch (-Q11) DC Interface Enclosure AC Disconnect Switch DC Disconnect Switch UPS Breaker (-F5) Located in center enclosure Introduction 110 975-0582-01-01
Operation Features The Xantrex inverter has the following operation features. Fixed Unity Power Factor Operation (Xantrex GT500 E and Xantrex GT630 E) The Xantrex GT500 E and Xantrex GT630 E maintain unity power factor during operation. The control software constantly senses utility voltage, and constructs the output current waveform to match the utility voltage. The Xantrex GT500 E and Xantrex GT630 E are not capable of operation without the presence of normal utility voltage, nor are they capable of varying the output power factor off unity. Variable Power Factor Operation The Xantrex inverters with the VAR control option have user-settable parameters for varying the output power factor off unity. In addition, the inverter can compensate for reactive loads on the grid by varying the power factor it supplies according to the user-settable parameters. Maximum Peak Power Tracking An advanced, field-proven, maximum peak power tracking (MPPT) algorithm integrated within the Xantrex inverter control software ensures the optimum power throughput for harvesting energy from the photovoltaic array. The peak power voltage point of a PV array can vary, primarily depending upon solar irradiance and surface temperature of the PV panels. This peak power voltage point is somewhat volatile, and can easily move along the I-V curve of the PV array every few seconds. The MPPT algorithm allows the Xantrex inverter to constantly seek the optimum voltage and current operating points of the PV array, and maintain the maximum peak PV output power. Accessible via the UFCU, there are five user-settable parameters that control the behavior of the maximum peak power tracker within the Xantrex inverter. As shown in Figure 1-6 on page 111, user- settable parameters include: PPT V Ref (ID# 37), I PPT Max (ID#42), PPT Enable (ID# 44), PPT Rate (ID# 45), and PPT V Step (ID# 46). Upon entering the Power Tracking mode, it takes approximately 20 seconds for the Xantrex inverter to ramp the PV voltage to the PPT V Ref setpoint regardless of the actual PV voltage. With the PPT Enable set to 0 (power tracker disabled), the Xantrex inverter regulates the DC Bus at the PPT V Ref setpoint. Regulating the DC bus means drawing more or less current out of the PV array to maintain this desired voltage. Operation Features 975-0582-01-01 111
With the PPT Enable set to 1 (power tracker enabled), followed by the expiration of the PPT Rate (MPPT decision frequency), the MPPT reduces the reference voltage by an amount equal to the PPT V Step value. At this point the MPPT compares the amount of AC output power produced to the previous amount of AC power produced by the Xantrex inverter. If the output power has increased, the next change made (after PPT Rate has again expired) to the reference voltage, will be in the same direction. Conversely, if the power comparison proves undesirable, the power tracker reverses the direction of the change to the PPT_V Step. The MPPT algorithm within the Xantrex inverter then continues this ongoing process of stepping and comparing in order to seek the maximum power throughput from the PV array. The changes made by the MPPT to the reference voltage are restricted by the maximum and minimum PV input voltage: 880 and 450 V respectively for the Xantrex GT500 E, 880 and 495 V respectively for the Xantrex GT500 E with VAR control, 880 and 575 Vdc respectively for the Xantrex GT630 E, 880 and 575 Vdc respectively for the Xantrex GT630 E with VAR control. Also, the MPPT will not attempt to produce power greater than that allowed by the I PPT Max setpoint. If available PV power is above the maximum allowable power level of the Xantrex inverter, the MPPT increases voltage as needed to maintain output power below rated maximum. Optimization of the Xantrex inverter MPPT results in an increase in energy production. You are encouraged to study the PV arrays I-V curves and to adjust the MPPT user-settable parameters accordingly. Figure 1-6 Maximum Peak Power Tracking Introduction 112 975-0582-01-01
Utility Voltage/Frequency Fault Automatic Reset In the event of a utility voltage or frequency excursion outside of preset limits, the Xantrex inverter stops operation and displays a fault at the operator interface. Once the utility voltage has stabilized within acceptable limits for a period of at least 5 minutes, the Xantrex inverter automatically clears the fault and resumes normal operation. Voltage and frequency fault setpoints are detailed later in this section. Safety Features Anti-Island Protection (Xantrex GT500 E and Xantrex GT630 E base units only) A condition referred to as Islanding occurs when a distributed generation source (such as the Xantrex inverter Grid-tied Photovoltaic Inverter) continues to energize a portion of the utility grid after the utility experiences an interruption in service. This type of condition may compromise personnel safety, restoration of service, and equipment reliability. The Xantrex inverter employs a method for detecting the islanding condition using a Phase-Shift-Loop (PSL). This method is implemented in the control unit to prevent islanding of the Xantrex inverter. The control unit continuously makes minor adjustments to the output phase angle above and below unity. In the event of a utility interruption or outage, these adjustments destabilize the feedback between the inverter and the remaining load, resulting in an over/under- frequency or voltage condition. Upon detection of such a condition, the Xantrex inverter then performs an immediate orderly shutdown and opens both the main AC contactor and DC disconnect switch. The fault condition remains latched until the utility voltage and frequency have returned to normal for at least 5 minutes. Low Voltage Ride-through Capability If the Xantrex inverter has the grid interactive option of low voltage ride-through the inverter continues to function for 1.5 to 2.5 seconds (length of time dependant on a site specific requirement) if the AC voltage is below the minimum, but greater than 5% of the nominal operational voltage. In other words, the inverter rides through voltage dips, and continues to operate even in unstable grid conditions by delivering the same output AC current prior, during and after a low voltage ride-through event. Safety Features 975-0582-01-01 113
PV Ground Insulation Detection The Xantrex inverter may be equipped with an optional PV ground insulation detection circuits for ungrounded arrays, positive grounded arrays, or negative grounded arrays. For ungrounded arrays the PV ground insulation detection circuit will activate when the impedance drops below a preset value, the Xantrex inverter executes an immediate orderly shutdown, opens both the AC and DC contactors and reports a PV Ground Insulation Fault on the display of the UFCU. The Xantrex inverter automatically clears the fault when the fault is remedied. No parallel switching of the ground fault relays is allowed. For positive or negative grounded arrays the detection circuit will activate when the leakage current exceeds the threshold. The Xantrex inverter then executes an immediate orderly shutdown, opens both the AC and DC contactors and reports a PV Ground Insulation Fault on the display of the UFCU. The detection device must be reset manually. PV Over-voltage Detection In the event of PV voltage greater than 940 Vdc during normal operation, all Xantrex GT500 E & Xantrex GT630 E units (with the exception of those with the 1000 Vdc input option) will execute an orderly shutdown and report a fault to the operator interface. If PV voltage remains greater than 940 Vdc, these inverters may be irreparably damaged. For the Xantrex GT630 E GI 1K the PV voltage can be as high as 1000 Vdc while the inverter is not running. After the 1000 Vdc input option pulls down the array voltage to a value within the inverter's operating range the inverter will start, the PV over-voltage detection works as normal and protects the inverter from PV voltages greater than 940 Vdc. See Chapter 3, Troubleshooting for further information on this fault condition. WARNING: Risk of electric shock or fire When the PV ground insulation fault is displayed on the UFCU, some part of the PV array that is supposed to be floating and isolated from earth ground has become grounded or has damaged isolation. Both shock and fire hazards are present under these conditions, and the system requires servicing by qualified personnel. Introduction 114 975-0582-01-01
Ground Fault Monitoring The Xantrex inverter is equipped with a ground fault detection circuit by means of hall effect current transducers (+T14) (-T13) installed in the DC+ and DC- circuits. This circuit is active when the PV array is properly grounded. The current flowing in the PV+ and PV- circuits should be the same magnitude but opposite polarity. Any difference is considered ground current. In the event this imbalanced current exceed a predetermined value; the Xantrex inverter executes an immediate orderly shutdown, opens both the AC contactor and the DC disconnect switch, and reports a ground fault on the display of the UFCU. The Xantrex inverter remains faulted until the ground fault is remedied and the advisory is cleared at the operator interface. Lightning Protection Lightning arrestors are incorporated to obtain maximum protection. The control voltage is secured against over-voltages by means of a TYP2 PRD40R 1P (-F30) located in the AC interface enclosure. The AC output is secured against over- voltages by means of (3) DBM 1 760 FM (-F31, -F32, -F33) located in the AC interface enclosure and the DC input using a DGY PV 1000 (-F34) located in the DC interface enclosure. The lightning arrestors are equipped with an indicator. A green light on the indicator states that the lightning arrestor is OK; a red light on the indicator means that the lightning arrestor must be replaced. If a DBM 1 760 FM needs to be replaced, the back-up fuses (-F35) must be checked as well. For any service or replacement of lightning arrestors, call Schneider Electric customer service. Figure 1-7 Xantrex inverter Current Transducers Current Transducers (+T14) and (-T13) Safety Features 975-0582-01-01 115
Figure 1-8 AC Lightning Protection Figure 1-9 DC Lightning Protection Figure 1-10 AUX Lightning Protection DBM 1 760 FM (-F31) (-F32) (F33) Backup Fuses (-F35) DGY PV 1000 (-F34) YP2 PRD40R 1P (-F30) Introduction 116 975-0582-01-01
Communication Features and Methods The Xantrex inverter provides two types of information to the user: system status and/or fault information, and data logging information. System status and fault information can be accessed using the universal front panel control unit (UFCU) or an optional monitoring system. Data logging access requires the use of an optional monitoring system. System Status and Fault Reporting Basic system status and all fault conditions detected by the Xantrex inverter are reported to the UFCU. The unit stores the time and details of all faults in non- volatile memory. The 4-line display shows a hexadecimal value and a brief text description of the fault. The fault value is also made available to the optional monitoring system and has a more extensive description of the fault. The UFCU keypad is located on the right center door to manipulate and view system operation and status. The keypad is comprised of 20 touch-sensitive keys that provide a means to navigate through the menus and alter user- changeable settings. See the Xantrex GT500 E and Xantrex GT630 E Grid-Tied Photovoltaic Inverter Planning and Installation Manual (Part #: 975-0581-01-01) for details. This information can also be accessed using an optional monitoring system. Types of status information include: Current Operating State or Goal State Figure 1-11 Display and UFCU Location Universal Front Panel Control Unit (UFCU) Display Communication Features and Methods 975-0582-01-01 117
Fault Code (if applicable) Inverter State Line Voltage and Current Inverter Matrix Temperature Inverter Power PV State PV Voltage and Current PV Power Grid Frequency Peak Power Tracker Enabled Reactive Power Magnitude Software Upgrade Configurable Parameters Data Logging The inverter stores data values and software metrics for debugging. These values are stored within the control unit controller board in non-volatile memory. Data logging access requires the use of an optional monitoring connection. The data logging features include: Operational Values Internal Metrics Data Log Acquisition Graphic Data Analysis Fault Log Acquisition Accumulated Values Monitoring Connection Methods Computers can be used to access the system status, control and programming features of the Xantrex inverter. Computers can be connected either directly or remotely. Software is available to provide a graphic user interface that relates important system information using the appropriate optional hardware and software. This software is called Graphic Interface (GUI). Direct Access Connection The Xantrex inverter can be directly accessed by a computer or other RS232 devices. This connection requires using the optional RS232 Converter kit. The kit contains an RS232/FO converter configured for PC use with an adapter, a DB9/ DB25 serial cable and a fiber optic harness. Remote Access Connection The Xantrex inverter can be remotely accessed through several methods such as a Local Area Network (LAN). Optional hardware and software is needed for these features. 118 Communication Features and Methods 975-0582-01-01 119
Introduction 120 975-0582-01-01
2 Operation Chapter 2, Operation contains information on the basic operation of the Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters. Operation 22 975-0582-01-01
Description of System Operation Overview The Xantrex inverter is a fully automated grid-interactive photovoltaic inverter. System startup, system shutdown, PV power tracking, and fault detection scenarios are all governed and monitored by the control unit within the Xantrex inverter. Manual interaction or control of the inverter is necessary only in the event of a system fault. Additionally, the following conditions govern operation of the Xantrex inverter. Stable utility AC voltage and frequency as specified in Table A-4 must be present for all states of operation. PV voltage as specified in Table A-4 must be present. The 3 (stand-by/power-on) switch (called ON/OFF on older models), located on the front door of the Xantrex inverter enclosure, must be switched to the 2 (power-on) position for all operating states. Both the AC and DC disconnect switches must be in the ON or closed position. Fault conditions must not be present. Faults Fault states are automatic from any state of operation. In the event of a fault condition, the Xantrex inverter immediately stops processing power and executes an immediate orderly shutdown, opens both the main AC contactor and DC disconnect switch, and remains in a faulted state until the fault is remedied and cleared (manually or automatically depending on the type of fault). All non- auto-clearing faults must be cleared by qualified personnel. Most faults are latching, and only those faults associated with grid disturbances are auto-clearing and thus enable the Xantrex inverter to restart after a 5 minute delay period. All fault conditions detected by the Xantrex inverter are reported to the universal frontpanel control unit (UFCU). The 4-line display on the UFCU displays a hexadecimal value (fault code) and a brief text description of the fault. The following faults are auto-clearing: 0000 (No Fault) 0010 (AC Frequency Low) 0011 (AC Frequency High) 0012 AC Voltage Low) 0013 (AC Voltage High) 0015 (Grid Disconnection) 0021 (PV Over Voltage) 0023 (Bus Voltage High) 0035 (Fault Class 35: PV Ground Insulation or Enclosure Temperature Low and Humidity High) Description of System Operation 975-0582-01-01 23
Figure 2-1 Operating States Flow Chart PV Voltage < 450V GT500E, 495V - GT500E with VAR control, 575V GT630E (Min. Oper.) INITIALIZING PV disconnect opened. Inverter matrix off. Grid contactor open. Green LED on. Red off. POWER UP KEY DISABLE PV disconnect open. Inverter matrix off. Grid contactor open. System State: Key Disable Inverter State: Standby PV State: Sleep SLEEP for at least 10 seconds System State: Shutdown Inverter State: Standby PV State: Sleep Inverter matrix off. Line contactor open WAKE UP for 5.0 min. (PV T START) PV Voltage < 600V GT500E, 750V GT630E (PV V Start) PV Voltage > 600V GT500E 750V GT630E (PV V START) K1 Settle for .5 seconds ON LINE PV Power < 5.0kW (PV P STOP) PV Power > 5.0kW (PV P STOP) PV Voltage < 450V GT500E, 495V GT500E with VAR control, 575V GT630E (Min. Oper.) TEST for 5.0 min. (PV T STOP) 5 minutes elapsed System State: Shutdown Inverter State: Standby PV State: Wake Up System State: Shutdown Inverter State: Main Settling PV State: Wake Up System State: Power Tracking Inverter State: On Line PV State: On Line System State: Power Tracking Inverter State: On Line PV State: Sleep Test Grid Contactor K1 Close Inverter Matrix On FAULT PV disconnect opened. Inverter matrix off. Grid contactor open. Red LED on. Green off. Fault from any State Fault Cleared R e t r u n
t o
S l e e p
S t a t e Bold - constant value Italic - User settable. Underline - Default value. Enable Key R e t u r n
t o
S l e e p
S t a t e Operation 24 975-0582-01-01
Operating States A state machine implemented within the control unit software governs the operation of the Xantrex inverter with clearly defined transitions between its operating states. There are five steady-state operating states and numerous intermediate transition states. Power Tracking Transition Shutdown Fault Automatic Sleep Test Power Tracking This is the standard operating state of the Xantrex inverter. The Xantrex inverters maximum power tracker demands maximum power from the PV array, given sufficient PV irradiance. You should be aware of the following conditions governing Xantrex inverter state transitions: Qualified utility voltage must be present for all states of operation. Fault states are automatic from any state of operation. A fault causes the Xantrex inverter to immediately stop processing all power. The fault condition is reported to the operator interface display. Most Xantrex inverter faults are latching and must be cleared at the operator interface keypad before transitioning to another operating state. The 3 (stand-by/power-on) switch (called ON/OFF on older models), located on the front door of the Xantrex inverter enclosure, must be switched to the 2 (power-on) position for all operating states. Transition The intermediate transition states provide an orderly progression from one operating state to the next. You have the ability to manually transition the Xantrex inverter between operating states via the operator interface keypad or remotely using the GUI software. Manual transitions are initiated by entering a Goal State, where the goal state is the desired operating state. Given all applicable system parameters are within acceptable limits, and the request is valid within the state machine, the Xantrex inverter initiates the proper sequence of operations necessary to progress to the requested goal state. Refer to Figure 2-1 on page 23 for an illustration of valid state transitions. Shutdown The line interface controller is idle. The control unit monitors the status of the PV array and utility grid, waiting in standby until the PV array is available to produce power to the grid. Operating States 975-0582-01-01 25
Fault The Xantrex inverter has encountered a fault condition. When this happens, regardless of the Xantrex inverter state of operation, the Xantrex inverter stops processing all power and executes an orderly system shutdown. A description of the fault and fault code appears on the operator interface display. The Fault state may be cleared from the keypad once the cause of the fault has been corrected. See Chapter 3, Troubleshooting for a complete description of all fault codes. Automatic Sleep Test Toward the end of every solar day, the Xantrex inverter automatically determines when to stop producing power dependent upon the output power of the inverter. As the net output power of the Xantrex inverter nears zero, a timer is started to allow the inverter to ride through any brief irradiance reductions. Operation 26 975-0582-01-01
Operator Interface The purpose of the operator interface is to provide a means of communicating critical operational information to and from the unit. This communication occurs between the operator and the UFCU Keypad and display or between the operator and an optional remote monitoring system. UFCU Keypad Operation and Display The UFCU keypad is located on the front of the main inverter enclosure to manipulate and view system operation and status. The keypad is comprised of 20 touch-sensitive keys that provide a means to navigate through the menus and alter user-changeable settings. Four function keys are available. F1 - When in the READ menu, this key is used to clear faults. If there is no fault it jumps to display "INV A Volts:". In the WRITE menu, it jumps to display "Goal:". F2 - When in the READ menu, this key jumps to display "INV kW:". In the WRITE menu, it jumps to display "PPT V Ref:". F3 - When in the READ menu, this key jumps display to "PV kW:". In the WRITE menu, it jumps to display "PPT Enable:". F4 - When in the READ menu, this key jumps to display "kWH:". In the WRITE menu, it jumps to display "Role 0=SA 1=M 2=S:". Two Navigation keys are available. /\ or \/ moves forward or backward within the menu structure. Upon reaching the end of the menu, it rolls-over to the beginning of the same menu. Ten numeric keys (0 through 9), two symbol keys (. and -), and <ENTER> are available for entering user-settable parameters. The <MENU> key allows you to enter the password-protected Write parameters. Figure 2-2 The Universal Front Panel Control Unit (UFCU) and Display Display UFCU Keypad \sto: uk 1ra|ng |nv: 0n||n v: 0n||n |Nv u: Standard Display Operator Interface 975-0582-01-01 27
Display - Initialization Screen Any time AC power is applied to the unit, the display cycles through the following displays while the system initializes. Once its done with this process, the standard display appears. Standard Display The standard display provides the following information: First Line - System Status (ID 1) Second Line - Inverter Status (ID 4) Third Line - PV Status (ID 13) Fourth Line - INV kW: (ID 11) Menu Structure The operator interface consists of three levels: READ Menu - operation information provided to you from the Xantrex inverter. The READ menu consists of all operational values, the date and time. These can be viewed any time the Xantrex inverter has control power. WRITE Menu - operational parameters provided to the Xantrex inverter from you. The WRITE menu consists of a goal state sub-menu, and all system configurable parameters. The WRITE menu is password protected and may only be changed by qualified service technicians. In particular are parameters relating to utility protection setpoints. Data Logging - the collection of specific parameters values over a period of time. The data logging feature is only available if using the GUI. However, you do not have the ability to view a snapshot of specific data using the Read by ID feature. Figure 2-3 Initialization Screens \sto: uk 1ra|ng |nv: 0n||n v: 0n||n |Nv u: Front Panel Initialization - Screen 1 Standard Display Operation 28 975-0582-01-01
Information reported back to you (READ menu) occurs at the display above the universal front panel control unit (UFCU) and (if used) at the computer running the GUI monitoring program. Making changes to the parameters within the WRITE menu is done with the UFCU keypad or the GUI software program and requires a password. Upon system powerup, the operator interface display shows the system operating state on the first line. The inverters state of operation is reported on the second line. The PV Arrays state of operation is reported on the third line. The Inverter kW is reported on the fourth line. READ Menu The READ menu includes the following information: Current Operating State or Goal State Fault Code Front Panel Software Version Control Unit Software Version Inverter Model Date & Time Goal State Read by ID# Inverter Voltage and current Inverter Power Inverter Temperature PV Voltage and Current Important: Specific grid-interface parameters within the WRITE menu have been set in the factory to the limits mandated by the utility. Any changes to these setpoints should be agreed upon by the local utility and the equipment owner. Important: While in the WRITE menu, the operator interface display resets itself to the standard display if there is no input for more than 2 minutes. Figure 2-4 Operator Interface Menu Diagram Enter Goal State Set Date/Time Change Parameters WRITE Menu Password Standard Display READ Menu \sto: uk 1ra|ng |nvrtr: 0n||n v: 0n||n |Nv u: Operator Interface 975-0582-01-01 29
PV Power Grid Frequency PV PPT Enable Ground Current Accumulated Power Reactive Power (Xantrex inverter with VAR control only) Phase Angle (Xantrex inverter with VAR control only) Table 2-1 shows how the third and fourth line of the display changes as the operator continues scrolling through the menu. Table 2-2 on page 210 provides a detailed description of READ menu operational values that are shown on the display. To display any operational value in the READ menu: From the standard display, use the /\ or \/ keys on the operator interface keypad to scroll through the READ menu. The fourth line of the display changes to display the appropriate information. See Table 2-1. The \/ key scrolls downward through the menu. The /\ key scrolls upward through the menu. Operation 210 975-0582-01-01
Upon reaching the end of the menu, it the display goes back to the beginning of the menu. Table 2-1 Scrolling through the READ Menu Parameters READ Menu Value Fourth Line of the Display Front Panel Software Version FP 151-XXXX-nn-nn Control Unit Software Version CCU 151-XXXX-nn-nn Inverter Model Xantrex GT500 E Date & Time European format DD-MMM-YYYY HH:MM:SS Goal State Goal: Read by ID# Value by ID# Inverter L1-L2 Volt INV A Volts: Inverter L2-L3 Volt INV B Volts: Inverter L3-L1 Volt INV C Volts: Inverter L1-L2 Current INV A Amps: Inverter L2-L3 Current INV B Amps: Inverter L3-L1 Current INV C Amps: Inverter Power INV kW: Inverter Temperature INV Temp: PV Voltage PV Volts: PV Current PV Amps: PV Power PV kW: Grid Frequency Grid Freq: PV PPT Enable PV PPT: Ground Current Ground I: Accumulated Power KWH Reactive Power (Xantrex inverter with VAR control only) kVar Phase Angle (Xantrex inverter with VAR control only)
Table 2-2 READ Menu Descriptions
Operational Parameter Description ID Units Current Operating State Displays as: \sto: where * can be any one of the states listed in the description for this parameter. Current system states include the following. |n|t|a|||ng :(; k-d|sah|d :|; \hutdun :,; \tart|ng :; uk 1ra|ng :; nanua| urrnt :;; natr| 1st :(; lau|td :7; 1 N/A Operator Interface 975-0582-01-01 211
System Goal State Displays as: (a|: where * can be any one of the states listed in the description for this parameter. Goal States include the following. (: \hut )un :(; |: uk 1ra|ng :(; ,: nanua| urrnt :(; : natr| 1st :(; 2 N/A Fault code See Faults and Fault Codes on page 32 for a detailed list of Fault Codes. 3 N/A Inverter State Displays as: |nvrtr: where * can be any one of the states listed in the description for this parameter. Inverter States includes the following. \hut )un :(; \tand-h :|; \tart|ng :,; na|n-\tt|ng :; 0n-}|n :; 4 N/A PV State Displays as: v: where * can be any one of the states listed in the description for this parameter. PV States include the following. \hut )un :(; \| :|; uau :,; 0n-||n :; \|-tst :; 5 N/A Front Panel Software Version In form FP 151-0407-nn-nn N/A N/A Control Unit Software Version In form CCU 151-0125-nn-nn N/A N/A Inverter Model Xantrex GT500 E N/A N/A Line L1L2 voltage Displays as: |Nv / v|ts: Line to line voltage 6 V rms Line L2L3 voltage Displays as: |Nv H v|ts: Line to line voltage 7 V rms Line L3L1 voltage Displays as: |Nv v|ts: Line to line voltage 8 V rms Table 2-2 READ Menu Descriptions Operational Parameter Description ID Units Operation 212 975-0582-01-01
Phase L1 current Displays as: |Nv / aos: Phase L1 current 9 A rms Phase L2 current Displays as: |Nv H aos: Phase L2 current 10 A rms Phase L3 current Displays as: |Nv aos: Phase L3 current 11 A rms Inverter Real Power Displays as: |Nv ku: Inverter Real Power 12 kW Inverter Matrix Temperature Displays as: |Nv 1o: Temperature of the Inverter IGBT matrix heatsink 13 C PV Voltage Displays as: v v|ts: PV Voltage 14 Vdc PV Current Displays as: v aos: PV Current 15 Adc PV Power Displays as: v u: PV Power 16 kW Grid Frequency Displays as: (r|d lr: Grid Frequency 17 Hz Table 2-2 READ Menu Descriptions Operational Parameter Description ID Units Operator Interface 975-0582-01-01 213
Peak Power Tracker Enable Displays as: v 1: where * can be any one of the states listed in the description for this parameter. Indication as to whether the PPT is enabled or disabled. 0ff :(; 0n :|; 18 N/A Ground Current Displays as: (rund |: Ground Current 19 N/A kW Accumulated Displays as: uu: kW Accumulated 20 N/A Reactive Power (Xantrex inverter with VAR control only) Displays as: var: kVar supplied or absorbed. Value has + or - symbol. - fr su||ng - fr ahsrh|ng 55 kVar Phase Angle (Xantrex inverter with VAR control only) Displays as: Phase Angle (-22 to +22) 56 Table 2-2 READ Menu Descriptions Operational Parameter Description ID Units Operation 214 975-0582-01-01
Read-by-ID The Read-by-ID feature enables you to view any Read or Write parameter available within the menu structure and provides a means to view data logging information. See Table 2-2 for a list of the READ menu parameters. To use the Read-by-ID Feature: 1. From the standard display, press the /\ key seven times to scroll upward through the menu to the Read-by-ID menu item. Stop when the 3rd and 4th line of the display change as shown in Figure 2-5. 2. Press <ENTER> to enter the Read-by-ID feature. 3. Use the keypad to enter the ID number of the Data Log Configuration and press <ENTER>. See Table 2-2 for a list of READ menu items and their ID numbers. a) Press the . key to move upward in the menu structure. b) Press the - key to move backward in the menu structure. These keys only function in the Read-by-ID feature. The only user-settable parameters are: Day start Hour Day Log Rate Night Start Hour Night Log Rate Figure 2-5 Read-by-ID Feature \sto: \hutdun |nv: \tandh u|t }N1}k r r - va|u h |) \sto: \hutdun |nv: \tandh u|t }N1}k r r - kad |) : Press <ENTER> when this screen appears to access the Read-by-ID feature. Use the keypad to enter the desired ID number and press <ENTER>. The display changes as shown and shows the requested value. where: xxx = any menu ID xxx = operational value of menu ID Use the . and - buttons to scroll backward and forward within the Read-by-ID menu. Operator Interface 975-0582-01-01 215
WRITE Menu The WRITE menu includes the following parameters: Goal State Date Time Max AC Min AC Max Frequency Min Frequency Max Ground Current Power Tracker Reference Voltage PV Wakeup Voltage Time Delay for Wake Up Time Delay for Sleep test PV Power to enter Sleep test Maximum Output Current Phase Angle (Xantrex inverter with VAR control only) Manual Current Output Enable Peak Power Tracker Power Tracker Rate Power Tracker Step Language Role Selection Master/Slave High Power Master/Slave Low Power Role Reversal Master/Slave Transition Time Reset kWH Factory Default Table 2-3 provides a detailed description of WRITE parameters that are shown on the display. Table 2-3 shows additional WRITE menu parameters that may be available depending upon the configuration of the system. WARNING: Risk of electric shock and fire Some setpoints available in the WRITE menu are related to safety functions and must only be adjusted by authorized personnel aware of the impact of changing the setpoints, and only with the agreement of the utility and the system owner. Operation 216 975-0582-01-01
The WRITE menu is password protected and you will need to contact customer service for the password. Changing and Displaying WRITE Menu Parameter Values Follow the procedure below to change WRITE menu parameters. To change WRITE menu parameters: 1. From the standard display or anywhere in the READ menu, you may access the WRITE menu parameters by pressing <MENU>. You are prompted for a password. 2. Enter the password (as assigned by customer service) and press <ENTER>. a) If the wrong password is entered, the display prompts you for the password again. b) If a mistake is made while keying in the password, the /\ or \/ keys may be used as a backspace key. 3. Once within the WRITE menu, the first item is the Set Goal State. Use the /\ or \/ keys on the operator interface keypad to scroll through the WRITE menu parameters. a) To change the displayed parameter, press <ENTER>. b) Enter the desired value and press <ENTER>. If the value entered is outside the acceptable range for the parameter, the original value remains. c) To leave the WRITE menu and return to the READ menu, press <MENU> once and the standard information reappears on the display. Table 2-3 WRITE Menu Parameters Parameter Description ID Units Default Value Maximum Value Minimum Value Set Goal State Displays as: u|t }N1}k t st (a|: Commands a Goal State. Set Date Displays as: ddoo The date is entered day- month-year (ddmmyy): April 28, 2005 is entered 280405. Set Time: Displays as: |(((( The time is entered in military hours-minutes-seconds (i.e., 24-hour clock): 4:30 pm is entered |((((. Operator Interface 975-0582-01-01 217
Maximum Grid Voltage Displays as: na / v|ts x: This parameter sets the trigger point value for AC voltage High (0013) fault. If the grid voltage is over this parameters value, the fault is triggered. 32 Percenta ge of Nominal voltage 110 112 97 Minimum Grid Voltage Displays as: n|n / v|tsx: This parameter sets the trigger point value for AC voltage low (0012) fault. If the grid voltage is below this parameters value, the fault is triggered. 33 Percenta ge of Nominal voltage 90 105 88 Maximum Grid Frequency Displays as: na / lr: This parameter sets the trigger point value for AC frequency high (0011) fault. If the grid frequency is over this parameters value, the fault is triggered. 34 Hertz 51.0 for 50 Hz grid 60.5 for 60 Hz grid 53.0 for 50 Hz grid 65.0 for 60 Hz grid 49.5 for 50 Hz grid 59.5 for 60 Hz grid Minimum Grid Frequency Displays as: n|n / lr: This parameter sets the trigger point value for AC frequency low (0010) fault. If the grid frequency is below this parameters value, the fault is triggered. 35 Hertz 49.0 for 50 Hz grid 59.5 for 60 Hz grid 50.5 for 50 Hz grid 60.5 for 60 Hz grid 47.0 for 50 Hz grid 55.0 for 60 Hz grid Maximum Ground Fault Current Displays as: na (nd l|t |: This parameter sets the trigger point value for Ground Over- Current (0033) fault. Once the current through the ground cable is greater than the value of this parameter, the fault is triggered. 36 Amps 30 30 1 Table 2-3 WRITE Menu Parameters Parameter Description ID Units Default Value Maximum Value Minimum Value Operation 218 975-0582-01-01
Peak Power Tracker Reference Voltage Displays as: 1 v kf: This is the initial PV voltage the inverter is going to try to keep as it goes into on line mode. If the power tracker is off, the inverter draws current from the PV array to maintain this reference voltage. If the power tracker is on, this is the reference voltage from which the inverter start exploring voltages that produce more power. 37 Volts 700 880 450 Xantrex GT500 E 495 Xantrex GT500 E with VAR control 540 Xantrex GT630 E 575 Xantrex GT630 E with VAR control PV Wakeup Voltage Displays as: v v \tart: This is the trigger point that transitions the inverter from PV Sleep state to PV Wake Up state. When the PV voltage reaches the value of this parameter the inverter transitions into PV Wake Up mode. 38 Volts 750 880 450 Xantrex GT500 E 495 Xantrex GT500 E with VAR control 540 Xantrex GT630 E 575 Xantrex GT630 E with VAR control Time Delay for PV Wake up Displays as: v 1 \tart: Time delay to transition from PV wake up state to PV On-line state. Once the inverter is in PV Wake Up mode, it waits for the amount of time determine by this parameter before transitioning into PV on-line mode. During this time the inverter checks that the PV voltage is no less than the PV wake voltage, otherwise it goes into PV Sleep mode. 39 Seconds 30 1200 0 Table 2-3 WRITE Menu Parameters Parameter Description ID Units Default Value Maximum Value Minimum Value Operator Interface 975-0582-01-01 219
Time delay for PV Sleep Test Displays as: v 1 \t: This is the amount of time the inverter will be in Sleep Test mode if the output power continues to be below PV P Stop. The inverter exits Sleep Test mode towards on-line mode if the power is over PV P Stop or towards Shutdown mode if the PV T Stop timer expires. 40 Seconds 300 1200 0 PV Output Power to Enter Sleep Test Mode Displays as: v \t: This is the output power trigger point for the inverter to transition into sleep test mode. When the output power is below the value of this parameter the inverter enters sleep test mode. 41 KW 5.0 50.0 1.0 Power Tracker Maximum Output Power Displays as: | 1 na: This parameter sets the percentage of maximum rated current the inverter produces when in power tracker mode. For example, a 500 kW system with this parameter set to 50 will not attempt to produce more than 250 kW. 42 Percenta ge of maximum output current. 100 100 0 Phase Angle Displays as:
(only for inverters
with VAR control) The phase angle is the offset in phase between the AC current and the AC voltage. This user- settable parameter sets the power factor in order to compensate for any reactance on the grid. 56 0 +22 -22 Manual Current Output Displays as: | nanua|x: This parameter sets the percentage of maximum output current the inverter attempts to produce while in manual current mode. 43 Percenta ge of maximum output current. 25 110 0 Table 2-3 WRITE Menu Parameters Parameter Description ID Units Default Value Maximum Value Minimum Value Operation 220 975-0582-01-01
Enable Peak Power Tracker Displays as: 1 }nah|: This parameter switches on and off the Power Tracker function. When the Power Tracker is on, the inverter regulates the bus voltage to optimize output power. When the Power Tracker is off, the inverter regulates the bus voltage to maintain it at PPT V Ref volts. 44 0 = OFF 1 = ON 1 1 0 Power Tracker Rate Displays as: 1 kat: This parameter sets the rate at which the Power Tracker function makes changes to the voltage reference point as it tries to find the optimal position. For example, if the value of this parameter is 0.5, then every half a second the power tracker increases or decreases the voltage reference point to check if more power can be produced at the new level. 45 Seconds 0.5 10.0 0.1 Power Tracker Step Displays as: 1 v \t: This parameter sets the size of the change the Power Tracker makes to the voltage reference point as it tries to find the optimal position. For example, if the value of this parameter is set to 1, the Power Tracker increases or decreases the voltage reference point by one volt at a speed of PPT Rate to check if more power can be produced at the new level. 46 Volts 1 10.0 0.1 Language Selection Displays as: Language Code: This parameter sets the language used to display messages. 48 0 = English 10 = German 20 = Spanish 30 = French 0 20 0 Table 2-3 WRITE Menu Parameters Parameter Description ID Units Default Value Maximum Value Minimum Value Operator Interface 975-0582-01-01 221
Role Selection Displays as: Role 0=SA 1=M 2=S: This parameter sets the Master/Slave default state of the Unit. If Stand Alone is selected; there is no Master/Slave operation. 50 0 = Standalone 1 = Master 2 = Slave 0 2 1 Master/Slave High Power Displays as: MS High kW: This parameter sets the power level where the master unit disconnects from the full array and enables the slave unit to operate. 51 kW 400 500 0 Master/Slave Low Power Displays as: MS Low kW: This parameter sets the power level where the master unit disables the slave unit and re- connects to the full array. 52 kW 100 500 0 Master/Slave transition time Displays as: MS Trans Secs: This parameter sets the time the power level must remain above the MS High kW level before the Master disconnects from the full array and enables the slave unit to operate. This parameter also sets the time the power level must remain below the MS Low kW level before the Master disables the slave unit and re- connects to the full array. 53 Seconds 30 1000 0 Role Reversal Displays as: 0=OFF 1=ROLE REV: This Parameter Sets The Condition Of The Role Reversal function: 54 0 = OFF 1 = ON 0 0 1 Table 2-3 WRITE Menu Parameters Parameter Description ID Units Default Value Maximum Value Minimum Value Operation 222 975-0582-01-01
Reset kWH Displays as: Reset kWH: The parameter allows the operator to reset the accumulated power reading to Zero. Press the ENTER to reset to Zero. Hit F4 to confirm appears. N/A kWh N/A N/A N/A Factory Default Displays as: Factory Default: The parameter allows the operator to reset all the settable parameters back to the Factory Default settings: Press the ENTER to reset to Factory Default. Hit F4 to confirm appears. N/A N/A N/A N/A N/A Table 2-3 WRITE Menu Parameters Parameter Description ID Units Default Value Maximum Value Minimum Value Operator Interface 975-0582-01-01 223
Commanding Goal State Changes To change the Goal State: 1. From the standard display press <MENU>. This prompts you for a password. The display changes the third line to 1 and u|t }N1}k and fourth line of the display to assurd:. 2. Enter the password (as assigned by customer service) and press <ENTER>. The display changes the third line to u|t }N1}k t st and fourth line of the display to (a|:. 3. Press <ENTER> again. The Goal State menu shows on the display. 4. Scroll through the goal state menu with the /\ or \/ keys until the desired goal state is displayed on the fourth line of the display. 5. Press <ENTER>. The display then prompts you by showing the following text on the third line: rss l t nf|ro. 6. Press <F4> and the Xantrex inverter transitions to this goal state. If the goal state requested violates the conditions of the state machine, the Xantrex inverter remains in the previous state of operation. Figure 2-6 State Transition Diagram SHUTDOWN Inverter = Disabled POWER TRACKING Inverter = PV Power MATRIX TEST Inverter = Idle MANUAL CURRENT Inverter = PV Current FAULT Automatic Manual Manual Operation 224 975-0582-01-01
Setting the Date and Time Follow the procedure below to change the date and time. To change the Date and Time: 1. From the standard display, press <MENU>. This prompts you for the password. The display changes the third and fourth lines as follows: 1 and u|t }N1}k assurd:. 2. Enter the password (as assigned by customer service) and press <ENTER>. 3. Scroll down with the \/ key until date or time parameters are reached. a) If you are changing the date, the third and fourth lines of the display is as follows: 1 and h|t }N1}k \t )at: ))nnYY b) If you are changing the time, the third and fourth lines of the display is as follows: 1 and h|t }N1}k \t 1|o: uunn\\ 4. Press <ENTER>. Enter the proper date or time in a six digit format. For example: a) The date is entered day-month-year (ddmmyy): April 28, 2005 is entered ,A((; <ENTER>. b) The time is entered in military hours-minutes-seconds (i.e., 24-hour clock): 4:30 pm is entered |(((( <ENTER>. If a mistake is made while entering the date or time, the /\ or \/ keys may be used as a backspace key. Any two-digit year YY may be entered for the date, but regardless of the keyed entry, the maximum Day-Month DDMM that the UFCU accepts is a 3112 or Dec. 31st. The maximum allowable time entry the UFCU accepts is 235959. 5. Once the entry is accepted, the third and fourth lines of the display revert back to the following: a) If you are changing the date, the third and fourth lines of the display is as follows: u|t }N1}k t st \t )at: b) If you are changing the time, the third and fourth lines of the display is as follows: u|t }N1}k t st \t 1|o: 6. Press <MENU> to return you to the standard display. Operator Interface 975-0582-01-01 225
Manual State Transitions State conditions can also be transitioned manually. Refer to Commanding Goal State Changes on page 223 for instructions on commanding Xantrex inverter goal states for manual transitions. Power Tracking Manual Current Power Tracking or Shutdown 1. Verify the PV manual current parameter (| nanua| x) is set to the desired percent of rated. 2. Command the Xantrex inverter to Manual Current mode from the operator interface keypad. While in the manual current mode, you may change the PV manual current parameter. However, you may demand greater current than the capacity of the PV array. If this causes the PV voltage to drop below the minimum operating voltage, the Xantrex inverter transitions to Shutdown. 3. To exit the Manual Current mode, you must manually command the Xantrex inverter to Power Tracking. Automatic State Transitions State conditions can also be transitioned automatically. Refer to page 223 for instructions on commanding Xantrex inverter goal states. Shutdown Power Tracking Shutdown 1. The 3 (stand-by/power-on) switch (called ON/OFF on older models) must be switched to the 2 (power-on) position. 2. Once the PV voltage exceeds the PV voltage start set point (v v \tart) the Xantrex inverter starts a wake-up timer (v 1 \tart). a) If the PV voltage remains above the PV start voltage set point for the duration of the wake-up timer, the Xantrex inverter transitions to Power Tracking. b) If the PV power drops below the PV power stop set point, (v \t) the Xantrex inverter starts a PV sleep timer (v 1 \t). c) If the PV voltage and power remain below their respective setpoints for the duration of the sleep timer, the Xantrex inverter transitions to Shutdown. Any State Fault If the Xantrex inverter encounters a fault, regardless of operating state, it transitions to the Fault state. The Xantrex inverter remains in this state until the fault condition has been remedied and cleared. The Fault Code number appears on the first line of the display. A description of the fault shows on the second line. The third line of the display reads l| t |ar lau|t^. The fourth line shows the goal state. Operation 226 975-0582-01-01
To clear the fault: 1. See Table 3-1, Fault Codes on page 34 for a complete listing of Fault Codes and possible remedies. Correct the fault condition if possible and attempt to clear the fault by pressing F1. 2. The ability to clear the fault can only be done from the READ menu. If a fault occurs while accessing the WRITE menu, pressing <MENU> once returns to the READ menu, and l| t |ar lau|t appears on the third line of the display. Auto-restart Feature In the event of a utility voltage or frequency excursion outside of those specified in Table A-4, the Xantrex inverter automatically transitions to a Fault condition. Once the Utility recovers for a period of five minutes, the Xantrex inverter automatically clears the fault, then resumes normal operation. Energize Procedure (Startup) To start up the Xantrex inverter: 1. Ensure nobody is working on any circuits in the system, and that the inverter cabinet and all other enclosures are closed and secured. 2. Turn the 3 (stand-by/power-on) switch (called ON/OFF on older models) to the 2 (power-on) position. After a 15 second initialization period, the Xantrex inverter automatically transitions to Waking Up, given the PV voltage is greater than the PV V Start set point. Figure 2-7 Display Showing Fault Code Display Showing Fault Code UFCU Keypad lau|t: xxxx l/u}1 )}\k|1|0N l| t |ar lau|t |Nv u:
3 Troubleshooting Chapter 3, Troubleshooting contains information and procedures for operators to perform basic troubleshooting of the Xantrex inverter. It provides descriptions of common situations and errors that may occur and lists auto-clearing faults. Non-auto-clearing faults need to be manually cleared by qualified personnel (see Xantrex GT500 E and Xantrex GT630 E Planning and Installation Manual). Troubleshooting 32 975-0582-01-01
Faults and Fault Codes Fault states are automatic from any state of operation. In the event of an alarm or fault condition, the Xantrex inverter immediately stops processing power and executes an immediate orderly shutdown, opens both the main AC contactor and DC disconnect switch, and remains in a faulted state until the alarm or fault is remedied and cleared (manually or automatically). Faults associated with a grid disturbance clear automatically. The Xantrex inverter automatically re-starts after a 5-minute delay. All other faults must be cleared manually by qualified personnel. All fault conditions detected by the Xantrex inverter are reported to the UFCU (Universal Frontpanel Control Unit). The 4-line display shows a hexadecimal value (fault code) and a brief text description of the fault. Most faults are latching and only those faults associated with grid disturbances are auto-clearing and thus enable the Xantrex inverter to restart after a 5 minute delay period. General Troubleshooting Respond to any Xantrex inverter alarm or fault as follows: 1. Note and document the alarm or fault code and brief text description. 2. Determine the source of the alarm or fault by referring to Table 3-1. 3. If the fault is auto-clearing wait for the Xantrex inverter to restart once the fault condition clears. 4. If the auto-clearing fault condition is sustained or it is a condition that must be manually cleared contact either your Distributor / Reseller, or Customer Service. Automatically Clearing Faults 975-0582-01-01 33
Automatically Clearing Faults Faults associated with a grid disturbance clear automatically. These faults include: 0000 (No Fault) 0010 (AC Frequency Low) 0011 (AC Frequency High) 0012 AC Voltage Low) 0013 (AC Voltage High) 0015 (Grid Disconnection) 0021 (PV Over Voltage) 0023 (Bus Voltage High) 0035 (Fault Class 35: PV Ground Insulation, Temperature Low or Humidity High) 0049 (Control Voltage Low) 0054 (Control Voltage High) Once the values return to within the acceptable range, the Xantrex inverter clears the fault and automatically restart after a 5-minute delay. Troubleshooting 34 975-0582-01-01
Fault Code Descriptions Table 3-1 provides a complete description of all the fault conditions that may occur on the Xantrex inverter. Default values are shown, but some limits are user- adjustable. Table 3-1 Fault Codes Error Code Fault Source(s) Fault Type H=Hardware S=Software Fault Description Actions 0000 No Faults N/A N/A N/A 0010 AC Frequency Low S This fault indicates that the Utility grid frequency is below or fell below the setting of Min AC Freq: for greater than 6 cycles. This fault is auto-clearing. Once the Utility grid frequency has recovered within the acceptable operating range, the Xantrex GT500 E & Xantrex GT630 E qualifies the value and automatically clears this fault and resumes normal operation after 5 minute delay period. Allow the Xantrex inverter to auto-clear the fault once the condition corrects itself. If the fault does not auto-clear, contact your Distributor / Reseller, or Customer Service. 0011 AC Frequency High S This fault indicates that the Utility grid frequency is above or rose above the setting of Max AC Freq: for greater than 6 cycles. This fault is auto-clearing. Once the Utility grid frequency has recovered within the acceptable operating range, the Xantrex GT500 E & Xantrex GT630 E qualifies the value and automatically clears this fault and resumes normal operation after 5 minute delay period. Allow the Xantrex inverter to auto-clear the fault once the condition corrects itself. If the fault does not auto-clear, contact your Distributor / Reseller, or Customer Service. Fault Code Descriptions 975-0582-01-01 35
0012 AC Voltage Low S This fault indicates that the utility grid voltage is below or fell below the setting of Min AC Volt%: of nominal Vac for greater than 6 cycles. Xantrex inverter units with the low voltage ride-through option are able to continue to supply current through the fault for 1500 2500 ms (site dependant) or the voltage drops below 5% of nominal Vac. This fault is auto- clearing. Once the utility grid voltage has recovered within the acceptable operating range, the Xantrex inverter qualifies the value and automatically clears this fault and resumes normal operation after a 5 minute delay period. Allow the Xantrex inverter to auto-clear the fault once the condition corrects itself. If the fault does not auto-clear, contact your Distributor / Reseller, or Customer Service. 0013 AC Voltage High S This fault indicates that the utility grid voltage is above or rose above the setting of Max AC Volt%: of nominal Vac for greater than 6 cycles. This fault is auto- clearing. Once the utility grid voltage has recovered within the acceptable operating range, the Xantrex inverter qualifies the value and automatically clears this fault and resumes normal operation after 5 minute delay period. Allow the Xantrex inverter to auto-clear the fault once the condition corrects itself. If the fault does not auto-clear, contact your Distributor / Reseller, or Customer Service. 0015 Grid Disconnection S This fault indicates that the Xantrex inverter has detected a sudden AC voltage increase of greater than 40% of the nominal peak-to-peak value. This normally is the result of a sudden disconnection from the Utility grid while the Xantrex inverter was processing power. Allow the Xantrex inverter to auto-clear the fault once the condition corrects itself. If the fault does not auto-clear, contact your Distributor / Reseller, or Customer Service. 0016 DC Disconnect Switch S This fault indicates that upon entering the Power Tracking State, the Xantrex inverter has detected that the DC disconnect switch is in the wrong state. Contact your Distributor / Reseller, or Customer Service. Table 3-1 Fault Codes Error Code Fault Source(s) Fault Type H=Hardware S=Software Fault Description Actions Troubleshooting 36 975-0582-01-01
0017 Phase Error S The calculated frequency is negative indicating the phase rotation of the grid is incorrect. The correct rotation is L1, L2, L3 Contact your Distributor / Reseller, or Customer Service. 0018 AC Contactor Circuit Fault S Xantrex GT500 E GI and Xantrex GT630 E GI only: An Auxiliary contact is used to determine the state of -K1. This fault indicates the Xantrex GT500 E GI and Xantrex GT630 E GI has detected the contactor is not in the correct state. Contact your Distributor / Reseller, or Customer Service. 0019 PV Over-I Positive H This fault indicates that the Xantrex inverter has detected a DC current in the Positive connection to the Unit greater than the maximum allowed of 1300 amps Contact your Distributor / Reseller, or Customer Service. 0020 PV Over-I Negative H This fault indicates that the Xantrex inverter has detected a DC current in the negative connection to the Unit greater than the maximum allowed of 1300 amps. Contact your Distributor / Reseller, or Customer Service. 0021 PV Over-Voltage S This fault indicates that the Xantrex inverter has detected a DC input voltage of greater than the maximum allowed value of 1100 Vdc. Often this is caused by a lightning strike to the utility. Allow the Xantrex inverter to auto-clear the fault once the condition corrects itself. If the fault does not auto-clear, contact your Distributor / Reseller, or Customer Service. 0023 Bus Voltage High H This fault indicates that the Xantrex inverter has detected that the DC bus voltage has exceeded the maximum allowed value of 1020 Vdc. Often this is caused by a lightning strike to the utility. Allow the Xantrex inverter to auto-clear the fault once the condition corrects itself. If the fault does not auto-clear, contact your Distributor / Reseller, or Customer Service. Table 3-1 Fault Codes Error Code Fault Source(s) Fault Type H=Hardware S=Software Fault Description Actions Fault Code Descriptions 975-0582-01-01 37
XX30 Matrix Over- Current H This fault indicates that the Xantrex inverter has detected that the AC current on one or more phases of the inverter output has exceeded the maximum allowed value of 2000A pk . The first two digits of the fault code indicate the particular phase where the over-current occurred as follow: 0130 - Matrix over-current in phase A 0230 - Matrix over-current in phase B 0430 - Matrix over-current in phase C If more than one phase faults simultaneously, the two first digits are added in hexadecimal form to indicate an over-current condition in more than one phase, thus the error code contains the summation of the faulted phases. Contact your Distributor / Reseller, or Customer Service. 0033 Ground Over- Current S This fault indicates that the Xantrex inverter has detected that the ground fault current has exceeded the setting of Max Gnd Flt I:. Contact your Distributor / Reseller, or Customer Service. XX34 Unused Matrix Over-I H This fault indicates that the inverter has detected a control unit board failure. Contact your Distributor / Reseller, or Customer Service. 0035 Fault Class 35 S The Bender relay has detected the impedance between ground and the PV array has dropped below the setting of the Bender relay or the enclosure temperature is too low and humidity is too high. Contact your Distributor / Reseller, or Customer Service. Table 3-1 Fault Codes Error Code Fault Source(s) Fault Type H=Hardware S=Software Fault Description Actions Troubleshooting 38 975-0582-01-01
0040 Programming Software S This code indicates that the Xantrex inverter has detected that the system is in Programming mode. This fault does not indicate any malfunction with the Xantrex inverter, but is merely an indication that the system software is in the process of being downloaded into the EEPROMs of the control unit. 0041 State Invalid S The state machine implemented within the control unit system software governs the operation of the Xantrex inverter. This fault indicates that the Xantrex inverter has detected an unknown system variable and has encountered an invalid state. Contact your Distributor / Reseller, or Customer Service. 0042 Serial EEPROM Write Error S This fault indicates that the Xantrex inverter has detected a serial EEPROM write error. The control unit controller board performs a verification check of data written to ROM compared to what is read back. Contact your Distributor / Reseller, or Customer Service. 0043 Serial EEPROM Timeout S This fault indicates that the Xantrex inverter has detected that when writing data to the serial EEPROM, a confirmation timer of 300mS has expired. Contact your Distributor / Reseller, or Customer Service. 0044 Bad NOVRAM Memory S This fault indicates that the Xantrex inverter has detected that one of the two non-volatile memory banks on the control unit controller board has failed. The control unit performs a series of tests to confirm the validity of the NOVRAM, and one of the two banks has produced errors. Contact your Distributor / Reseller, or Customer Service. Table 3-1 Fault Codes Error Code Fault Source(s) Fault Type H=Hardware S=Software Fault Description Actions Fault Code Descriptions 975-0582-01-01 39
0045 Interrupt 2 Timeout S This fault indicates that the Xantrex inverter has detected that an interrupt 2 timeout has occurred. The control unit controller board performs a conversion validation of analog- to-digital data within the A to D converters. If validation of the conversion is not performed within 500mS, an interrupt 2 timeout fault occurs. Contact your Distributor / Reseller, or Customer Service. 0047 Software Test S This fault indicates that the Xantrex inverter has detected that a software test fault has occurred. This is a simulated fault used for debugging purposes. 0048 Bad Memory S This fault indicates that the Xantrex inverter has detected that the SRAM DIMM on the control unit controller board has failed. The control unit performs a series of tests to confirm the validity of the SRAM, and the memory module has produced errors. Contact your Distributor / Reseller, or Customer Service. 0049 Control Voltage Low S This fault indicates the Xantrex GT500 E GI and Xantrex GT630 E GI has detected the 230 Vac auxiliary AC voltage has dropped below 165 Vrms for 2 consecutive cycles. Contact your Distributor / Reseller, or Customer Service. 0054 Control Voltage High S This fault indicates the Xantrex GT500 E GI and Xantrex GT630 E GI has detected the 230 Vac auxiliary AC voltage has exceeded 270 Vrms for 2 consecutive cycles. Contact your Distributor / Reseller, or Customer Service. 0062 Matrix Temperature S This fault indicates that the Xantrex inverter has detected that the temperature of the IGBT matrix aluminium heatsink has exceeded the maximum allowed value of 95 C. Contact your Distributor / Reseller, or Customer Service. Table 3-1 Fault Codes Error Code Fault Source(s) Fault Type H=Hardware S=Software Fault Description Actions Troubleshooting 310 975-0582-01-01
0072 Local E-Stop S Control unit has detected a loss of 15 VDC at terminal J2-1. Contact your Distributor / Reseller, or Customer Service. 0073 Remote E-Stop S Control unit has detected a loss of 15 VDC at terminal J2-5. Contact your Distributor / Reseller, or Customer Service. 0075 Shutdown Remotely S This fault indicates that the Xantrex inverter has detected that the system was commanded via the GUI to transition to the Shutdown State. This fault is not indicative of a failure or malfunction, but primarily used to disable the system remotely. 0082 Matrix Not ON S This fault indicates that the Xantrex inverter has detected that the IGBT matrix (FPGA) was not enabled after having sent a command for it to turn on. The control unit sends an acknowledge bit to confirm the command is received. This fault is primarily a watch-dog between software and hardware to ensure control of the IGBT matrix (FPGA). Contact your Distributor / Reseller, or Customer Service. 0083 Matrix Not OFF S This fault indicates that the Xantrex inverter has detected that the IGBT matrix (FPGA) was not disabled after having sent a command for it to turn off. The control unit sends an acknowledge bit to confirm the command is received. This fault is primarily a watch-dog between software and hardware to ensure control of the IGBT matrix (FPGA). Contact your Distributor / Reseller, or Customer Service. Table 3-1 Fault Codes Error Code Fault Source(s) Fault Type H=Hardware S=Software Fault Description Actions Fault Code Descriptions 975-0582-01-01 311
Control Unit Disconnect Errors These errors cause the inverter to disconnect from the grid and shut down. Errors are reported to the control unit. In all of these situations, contact your Distributor / Reseller, or Customer Service. Fault 0152 IGBT Over-current Cause: The current has exceeded 2000 Arms. Fault 0252 Switch Fault Cause: An IGBT was activated, but no feedback signal was received confirming activation. Fault 0452 Over-temperature Cause: The AC current converters cooling element temperature has exceeded 80C. The temperature is displayed in the display. Fault 0852 Over-voltage DC Bus Cause: The intermediate circuit voltage has exceeded 950 Vdc. If the inverter has the 1000 Vdc option, then this fault only applies while the inverter is producing power. Before it starts, the DC voltage can reach 1000 Vdc. Fault 1052 Earth Fault Cause: The PV array exceeds the differential current limit of the PV terminals; the difference in current between PV+ and PV- exceeds the predefined limit. Fault 2052 Under-voltage 24V Converter Cause: The power semiconductors control voltage is below 20 V. Fault 0153 DC Over-current Cause: The DC bus current has exceeded 1250 A average. Fault 0853 Too Cold or Internal Voltage not in Range Causes: The internal temperature sensor is reporting temperature below 0C. The internal control circuit supply voltage or clock have malfunctioned. 312
4 Preventative Maintenance Chapter 4, Preventative Maintenance contains information for site maintenance personnel on when to book an appointment with qualified personnel for preventative maintenance on the Xantrex inverter. WARNING: Risk of electric shock, explosion, and arc flash All installation, service, and maintenance must be performed by qualified personnel as defined on page iii and must follow the Lock-out and Tag-out and other Safety instructions found in the Xantrex GT500 E and Xantrex GT630 E Grid-Tied Photovoltaic Inverter Planning and Installation Manual (Part #: 975-0581-01-01). Failure to follow these instructions will result in death or serious injury. Preventative Maintenance 42 975-0582-01-01
Maintenance Intervals Maintenance intervals must be adhered to in order to ensure that the Xantrex inverter continues to operate in a way that is as safe and reliable as possible. The basis for these maintenance intervals is installation in an environment with an average annual ambient temperature of +20 C, with cooling air maintained within the temperature limits stated in the Specifications. Customers should follow the maintenance intervals at a minimum, however the environmental degree of pollution at the installation may mean that maintenance needs to be performed more frequently. Schneider Electric recommends that the following preventative maintenance procedures be carried out on the Xantrex inverter. Monthly Intervals or As Required Visually inspect the intake air ducts and external cooling fans for accumulation of dirt and debris. Accumulation of dirt and debris within the cooling fans will decrease their ability to move air and thus transfer heat away from the IGBT bridge heatsink and inductor, which may cause the Xantrex inverter to enter a Fault state based upon an over-temperature alarm. If there is any dirt or debris blocking the air intake or exhaust clear the debris using a vacuum cleaner or similar tool. Enclosure doors must remain closed at all times, even during debris-clearing. Electrical switchgear will need to be maintained as per the manufacturer's recommendation. Six Month Intervals Contact Customer Service to book an appointment with qualified personnel to perform the following preventative maintenance tasks on a six-month basis or as required. Enclosure Seals Electrical Connections Transformer and Inductor Enclosure 5 year Interval Contact Customer Service to book an appointment with qualified personnel to perform the following preventative maintenance tasks on a five-year basis or as required. PV Fuses 10 year Interval Facilities will be maintained after ten years. Contact Customer Service to book an appointment with qualified personnel to perform the following preventative maintenance tasks: Interior Fans Power Element Fans
A Specifications Appendix A provides the environmental and electrical specifications for the Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters. WARNING: Risk of electric shock, explosion, and arc flash. Risk of equipment damage Unsafe conditions and damage to the inverter may result if the instructions, and electrical, physical, and environmental installation specifications in this manual are not obeyed. Specifications A2 975-0582-01-01
System Specifications The Xantrex inverter has been designed for photovoltaic power systems, which operate within the following specifications. Electrical Specifications Table A-1 Electrical Specifications Specification Xantrex GT500 E Xantrex GT630 E Nominal AC Output Voltage (see Table A-4) 315 V (requires custom MV transformer) 375 V (requires custom MV transformer) Maximum AC Output Current with no options with Optional VAR Control 920 A 1040 A 965 A 1040 A Nominal AC Output Frequency (see Table A-4) 50 Hz (60 Hz auto-detect) AC Output Voltage 315 V 5% 375 V 5% Max. Reactive Power (only with Optional VAR Control) 200 kVar 250 kVar Phase Angle (only with Optional VAR Control) 22 degrees 22 degrees Line Power Factor with Optional VAR Control > 0.99 (above 20% rated power) 0.93 leading to 0.93 lagging AC Current Distortion < 3% THD at rated power < 3% THD at rated power Rated Current AC Output with no options with Optional VAR Control 920 A 1040 A 965 A 1040 A Output Power 500.0 kW 630.0 kW Suggested PV Array Power 560 kWp 705 kWp Maximum Open Circuit PV Voltage with no options with Optional 1000 Vdc Input 930 V 930 V 1000 V Maximum DC Input Current 1120 A 1120 A DC Input with no options with Optional VAR Control with Optional 1000 Vdc Input 450 to 930 V 495 to 930 V 575 to 930 V 575 to 930 V 575 to 1000 V MPP Range with no options with Optional VAR Control 450 to 880 V a 495 to 880 V a a. reduced current above 820 V 575 to 880 V a 575 to 880 V a Efficiency without Transformer 97.9 % (European weighted efficiency at 495 Vdc and 315 Vac) 98.2 % (European weighted efficiency at 575 Vdc and 375 Vac) External Auxiliary Supply Voltage 230/315/375/400 VA External Auxiliary Supply Power Required 2500 VA 2500 VA Inverters Capacitance to Earth approx. 15 F approx. 15 F System Specifications 975-0582-01-01 A3
Physical and Environmental Specifications Table A-3 shows the allowable environmental classifications for the inverter, based on the EN60721 series of standards. WARNING: Risk of electric shock, explosion, and arc flash. Risk of equipment damage Unsafe conditions and damage to the inverter may result if the inverter is energized with condensation present inside the unit. Storage, transportation, and operational conditions must ensure that internal condensation is not created, or that the inverter is dry before energizing. Obey the environmental specifications and classifications in Table A-2 and Table A-3. Table A-2 Physical and Environmental Specifications Specification Value Dimensions 2112 mm H x 2406 mm W x 605 mm D (83 in. H x 94 in. W x 24 in. D) Weight 1770 kg (3902 lbs) Allowable Ambient Temperature and Humidity Ranges Operating: EN60721 class 3K3: -10 C to 45 C Maximum (14 F to 113 F) Max 95% relative humidity, non-condensing Transport: EN60721 class 2K2: -25 C to 55 C Maximum (-13 F to 131 F) Max 95% relative humidity, non-condensing Storage: EN60721 class 1K2: -25 C to 55 C Maximum (-13 F to 131 F) Max 95% relative humidity, non-condensing Maximum Elevation 1500 m Storage Air Pressure 700 to 1060 mbar Ingress Protection Class IP20 Matrix Heatsink Cooling Fans 2700 m/h temperature threshold 68 C Cooling Air Power Cabinet (+H1) 4200m/h, fan starting temperature: 30 C for roof fans 65C for heat sink fans Cooling Air AC/DC Cabinet (+H2, +H0) 700m/h, fan starting temperature: 30C Total Cooling Air 5600m/h Clearance (ventilation and serviceability) Top: 100 mm Front: 600 mm (door clearance) plus local safety standards Table A-3 Environmental Classifications (EN60721 series of standards) Storage (1 prefix) EN60721-3-1 Transport (2 prefix) EN60721-3-2 Operation (3 prefix) EN60721-3-3 Classification of Climatic Conditions 1K2 2K2 3K3 Classification of Special Climatic Conditions 1Z1 2Z1 3Z1 Classification of Biological Conditions 1B1 2B1 3B1 Classification of Chemically Active Substances 1C1 2C1 3C1 Classification of Mechanically Active Substances 1S1 2S1 3S1 Classification of Mechanical Conditions 1M1 2M1 3M1 Specifications A4 975-0582-01-01
Regulatory Specifications Regulatory specifications for the Xantrex inverter are as follows: CE marked for the Low Voltage Directive per EN50178 CE marked for the EMC Directive per EN61000-6-4 (emissions) and EN61000-6-2 (immunity) Complies with RD1663/2000 and 661/2007 (Spain) Complies with Decree from 23 April 2008; Art du 23 Avril 2008 (France) Low voltage ride-through version complies with BDEW medium voltage grid connection requirement; "Technische Richtlinie - Erzeugungsanlagen am Mittelspannungsnetz, BDEW, June 2008" (Germany) Bureau Veritas certificate for DK5940 (Italy) Over Voltage, Under Voltage and Frequency Ranges Table A-4 provides the over-voltage, under-voltage, over-frequency, and under- frequency detection limits for the Xantrex inverter. These detection limits have been tested and are in compliance with requirements given under Regulatory Specifications above. Table A-4 Over/Under-Voltage and Over/Under-Frequency Ranges AC Voltage Condition (% of Nominal) Xantrex GT500 E Xantrex GT630 E Low Range 85% Vac 105% 5% Vac 105% a a.values are for all units with the optional low voltage ride-through capability installed 267.75 Vac 330.75 15.75 Vac 330.75 318.75 Vac 393.75 18.75 Vac 393.75 Low Default 90% = Vac Vac = 283.5 Vac = 337.5 High Range 97% Vac 115% 305.55 Vac < 362.25 363.75 Vac 431.25 High Default 110% = Vac Vac = 346.5 Vac = 412.5 50 Hz Low Range -3.0 Hz f +0.5 Hz 47.0 f 50.5 47.0 f 50.5 50 Hz Low Default f = 49.0 f = 49.0 50 Hz High Range -0.5 Hz f +3.0 Hz 49.5 f 53.0 49.5 f 53.0 50 Hz High Default f = 51.0 f = 51.0 60 Hz Low Range -5.0 Hz f +0.5 Hz 55.0 f 60.5 55.0 f 60.5 60 Hz Low Default f = 59.5 f = 59.5 60 Hz High Range -0.5 Hz f +5.0 Hz 59.5 f 65.0 59.5 f 65.0 60 Hz High Default f = 60.5 f = 60.5 System Specifications 975-0582-01-01 A5
Bolt Sizes and Torque Requirements Table A-5 provides acceptable bolt sizes and torque values for AC terminal connections. Table A-6 provides acceptable bolt sizes and torque values to be connected to the Xantrex inverters DC terminal connections. Uninterrupted Power Supply UPS If you have a Xantrex GT500 E or Xantrex GT630 E with optional ride-through capability you need to install a UPS for operation. You can order an appropriate UPS from Schneider Electric (part number: 820-0031-01-01) if you are using 230 Vac auxiliary supply voltage in your installation, or you can use any UPS which meets the requirements in Table A-7 on page A5 and matches the auxiliary supply voltage for your installation. Table A-5 AC Terminal Bolt Size, and Torque Values AC Terminal Connections Max. # of Conductors per Terminal Bolt (Hardware) Size Torque Requirements PE (Enclosure Ground) 2 1/M12 75 Nm (55 lb ft) L1, L2, L3 6 3/M12 75 Nm (55 lb ft) -X2:L1, -X2:L2 to AC aux input transformer 1 cable cross section 0.5 - 10 mm use appropriate ferrules 0.6 0.8 Nm (5.3 7.1 lb ft) -X2:23 and -X2:25 to UPS input, -X2:24 and -X2:26 to UPS output 1 cable cross section 0.5 - 10 mm use appropriate ferrules 0.5 0.6 Nm (4.4 lb ft 5.3 lb ft) X2:6 and X2:7 (external interlock) 1 cable cross section: 0.14 - 2.5 mm use appropriate ferrules X2:20 and X2:22 (external voltage) 1 cable cross section 0.5 - 10 mm use appropriate ferrules Table A-6 DC Terminal Bolt Size, and Torque Values DC Terminal Connections Max. # of Conductors per Terminal Bolt (Hardware) Size Torque Requirements PV+, PV- 8 8/M12 75 Nm (55 lb ft) Table A-7 Minimum UPS Specifications Power 500 VA AC Input must match auxiliary supply voltage provided by the installer (230, 315, or 400 Vac) AC Outputs 230 V Use UPS in bypass operation: Cross-over Time < 10 msec Support Time > 5 sec Specifications A6 975-0582-01-01
Dimensions Figure A-1 Xantrex inverter Dimensions TM A 597 597 1197 1197 3 597 597 3 A 568 568 .G1.SP +H1K10 605 2406 2 0 0 2 +H2 +H1 +H0 KHLLUFT/ COOLING AIR SK3326.100 SK3326.100 SK3326.100 SK3326.100 SK3326.100 SK3326.100 SK3326.100 SK3326.100 8 8 Xantrex GT500 E -A22 -S3 -S2 Dimensions in mm 975-0582-01-01 WA1 Warranty and Return Information Warranty What does this warranty cover and how long does it last? This Limited Warranty is provided by Xantrex Technology Inc. ("Xantrex") and covers defects in workmanship and materials in your Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid- Tied Photovoltaic Inverters. This warranty period lasts for 5 years starting three months from the date of purchase at the point of sale to you, the original end user customer, unless otherwise agreed in writing (the Warranty Period). You will be required to demonstrate proof of purchase to make warranty claims. This Limited Warranty is transferable to subsequent owners but only for the unexpired portion of the Warranty Period. Subsequent owners also require original proof of purchase as described in "What proof of purchase is required?" What will Xantrex do? During the Warranty Period Xantrex will, at its option, repair the product (if economically feasible) or replace the defective product free of charge, provided that you notify Xantrex of the product defect within the Warranty Period, and provided that Xantrex through inspection establishes the existence of such a defect and that it is covered by this Limited Warranty. Xantrex will, at its option, use new and/or reconditioned parts in performing warranty repair and building replacement products. Xantrex reserves the right to use parts or products of original or improved design in the repair or replacement. If Xantrex repairs or replaces a product, its warranty continues for the remaining portion of the original Warranty Period or 90 days from the date of the return shipment to the customer, whichever is greater. All replaced products and all parts removed from repaired products become the property of Xantrex. Xantrex covers both parts and labor necessary to repair the product, and return shipment to the customer via a Xantrex- selected non-expedited surface freight within the contiguous United States and Canada. Alaska, Hawaii and outside of the United States and Canada are excluded. Contact Xantrex Customer Service for details on freight policy for return shipments from excluded areas. How do you get service? If your product requires troubleshooting or warranty service, contact your merchant. If you are unable to contact your merchant, or the merchant is unable to provide service, contact Xantrex directly at: www.schneider-electric.com Direct returns may be performed according to the Xantrex Return Material Authorization Policy described in your product manual. For some products, Xantrex maintains a network of regional Authorized Service Centers. Call Xantrex or check our website to see if your product can be repaired at one of these facilities. What proof of purchase is required? In any warranty claim, dated proof of purchase must accompany the product and the product must not have been disassembled or modified without prior written authorization by Xantrex. Proof of purchase may be in any one of the following forms: The dated purchase receipt from the original purchase of the product at point of sale to the end user; or The dated dealer invoice or purchase receipt showing original equipment manufacturer (OEM) status; or The dated invoice or purchase receipt showing the product exchanged under warranty.
North America 1 408 987 6255 1 925 245 1022 re.techsupport@schneider-electric.com La France +0825012999 fr-re-techsupport@fr.schneider-electric.com Deutschland +49 (0) 180 575 6575 +49 (0) 2102 404 7101 solarservice@de.schneider-electric.com Espaa +34 93 498 7466 +34 93 305 5026 re.techsupport@es.schneider-electric.com L'Italia +39 035 4151111 +39 035415 3200 IT-pronto-contatto@it.schneider-electric.com For other country details please contact your local Schneider Electric Sales Representative or visit our website at: http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page Warranty and Return Information WA2 975-0582-01-01 What does this warranty not cover? Claims are limited to repair and replacement, or if in Xantrex's discretion that is not possible, reimbursement up to the purchase price paid for the product. Xantrex will be liable to you only for direct damages suffered by you and only up to a maximum amount equal to the purchase price of the product. This Limited Warranty does not warrant uninterrupted or error-free operation of the product or cover normal wear and tear of the product or costs related to the removal, installation, or troubleshooting of the customer's electrical systems. This warranty does not apply to and Xantrex will not be responsible for any defect in or damage to: a) the product if it has been misused, neglected, improperly installed, physically damaged or altered, either internally or externally, or damaged from improper use or use in an unsuitable environment; b) the product if it has been subjected to fire, water, generalized corrosion, biological infestations, or input voltage that creates operating conditions beyond the maximum or minimum limits listed in the Xantrex product specifications including, but not limited to, high input voltage from generators and lightning strikes; c) the product if repairs have been done to it other than by Xantrex or its authorized service centers (hereafter "ASCs"); d) the product if it is used as a component part of a product expressly warranted by another manufacturer; e) component parts or monitoring systems supplied by you or purchased by Xantrex at your direction for incorporation into the product; f) the product if its original identification (trade-mark, serial number) markings have been defaced, altered, or removed; g) the product if it is located outside of the country where it was purchased; and h) any consequential losses that are attributable to the product losing power whether by product malfunction, installation error or misuse. Disclaimer Product THIS LIMITED WARRANTY IS THE SOLE AND EXCLUSIVE WARRANTY PROVIDED BY XANTREX IN CONNECTION WITH YOUR XANTREX PRODUCT AND IS, WHERE PERMITTED BY LAW, IN LIEU OF ALL OTHER WARRANTIES, CONDITIONS, GUARANTEES, REPRESENTATIONS, OBLIGATIONS AND LIABILITIES, EXPRESS OR IMPLIED, STATUTORY OR OTHERWISE IN CONNECTION WITH THE PRODUCT, HOWEVER ARISING (WHETHER BY CONTRACT, TORT, NEGLIGENCE, PRINCIPLES OF MANUFACTURER'S LIABILITY, OPERATION OF LAW, CONDUCT, STATEMENT OR OTHERWISE), INCLUDING WITHOUT RESTRICTION ANY IMPLIED WARRANTY OR CONDITION OF QUALITY, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE TO THE EXTENT REQUIRED UNDER APPLICABLE LAW TO APPLY TO THE PRODUCT SHALL BE LIMITED IN DURATION TO THE PERIOD STIPULATED UNDER THIS LIMITED WARRANTY. IN NO EVENT WILL XANTREX BE LIABLE FOR: (A) ANY SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING LOST PROFITS, LOST REVENUES, FAILURE TO REALIZE EXPECTED SAVINGS, OR OTHER COMMERCIAL OR ECONOMIC LOSSES OF ANY KIND, EVEN IF XANTREX HAS BEEN ADVISED, OR HAD REASON TO KNOW, OF THE POSSIBILITY OF SUCH DAMAGE; (B) ANY LIABILITY ARISING IN TORT, WHETHER OR NOT ARISING OUT OF XANTREX'S NEGLIGENCE, AND ALL LOSSES OR DAMAGES TO ANY PROPERTY OR FOR ANY PERSONAL INJURY OR ECONOMIC LOSS OR DAMAGE CAUSED BY THE CONNECTION OF A PRODUCT TO ANY OTHER DEVICE OR SYSTEM; AND (C) ANY DAMAGE OR INJURY ARISING FROM OR AS A RESULT OF MISUSE OR ABUSE, OR THE INCORRECT INSTALLATION, INTEGRATION OR OPERATION OF THE PRODUCT BY PERSONS NOT AUTHORIZED BY XANTREX. CONSUMERS IN THE EUROPEAN UNION: IF YOU ARE A CONSUMER (RATHER THAN A PURCHASER OF THE PRODUCT IN THE COURSE OF A BUSINESS) AND PURCHASED THE PRODUCT IN A MEMBER STATE OF THE EUROPEAN UNION, THIS LIMITED WARRANTY SHALL BE SUBJECT TO YOUR STATUTORY RIGHTS AS A CONSUMER UNDER THE EUROPEAN UNION PRODUCT WARRANTY DIRECTIVE 1999/44/EC AND AS SUCH DIRECTIVE HAS BEEN IMPLEMENTED IN THE EUROPEAN UNION MEMBER STATE WHERE YOU PURCHASED THE PRODUCT. FURTHER, WHILE THIS LIMITED WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, YOU MAY HAVE OTHER RIGHTS WHICH MAY VARY FROM EU MEMBER STATE TO EU MEMBER STATE OR, IF YOU DID NOT PURCHASE THE PRODUCT IN AN EU MEMBER STATE, IN THE COUNTRY YOU PURCHASED THE PRODUCT WHICH MAY VARY FROM COUNTRY TO COUNTRY AND JURISDICTION TO JURISDICTION. CONSUMERS IN THE REST OF THE WORLD: Exclusions If this product is a consumer product, federal law does not allow an exclusion of implied warranties. To the extent you are entitled to implied warranties under federal law, to the extent permitted by applicable law they are limited to the duration of this Limited Warranty. Some states, provinces and jurisdictions do not allow limitations or exclusions on implied warranties or on the duration of an implied warranty or on the limitation or exclusion of incidental or consequential damages, so the above limitation(s) or exclusion(s) may not apply to you. This Limited Warranty gives you specific legal rights. You may have other rights which may vary from state to state, province to province or jurisdiction to jurisdiction. 975-0582-01-01 WA3 Return Material Authorization Policy For those products that are not being repaired in the field and are being returned to Xantrex, before returning a product directly to Xantrex you must obtain a Return Material Authorization (RMA) number and the correct factory "Ship To" address. Products must also be shipped prepaid. Product shipments will be refused and returned at your expense if they are unauthorized, returned without an RMA number clearly marked on the outside of the shipping box, if they are shipped collect, or if they are shipped to the wrong location. When you contact Xantrex to obtain service, please have your instruction manual ready for reference and be prepared to supply: The serial number of your product Information about the installation and use of the unit Information about the failure and/or reason for the return A copy of your dated proof of purchase Record these details in Information About Your System. Return Procedure Package the unit safely, preferably using the original box and packing materials. Please ensure that your product is shipped fully insured in the original packaging or equivalent. This warranty will not apply where the product is damaged due to improper packaging. Include the following: The RMA number supplied by Xantrex Technology Inc. clearly marked on the outside of the box. A return address where the unit can be shipped. Post office boxes are not acceptable. A contact telephone number where you can be reached during work hours. A brief description of the problem. Ship the unit prepaid to the address provided by your Xantrex customer service representative. If you are returning a product from outside of the USA or Canada In addition to the above, you MUST include return freight funds and are fully responsible for all documents, duties, tariffs, and deposits. If you are returning a product to a Xantrex Authorized Service Center (ASC) A Xantrex return material authorization (RMA) number is not required. However, you must contact the ASC prior to returning the product or presenting the unit to verify any return procedures that may apply to that particular facility and that the ASC repairs this particular Xantrex product. Out of Warranty Service If the warranty period for your product has expired, if the unit was damaged by misuse or incorrect installation, if other conditions of the warranty have not been met, or if no dated proof of purchase is available, your unit may be serviced or replaced for a flat fee. To return your product for out of warranty service, contact Xantrex Customer Service for a Return Material Authorization (RMA) number and follow the other steps outlined in "Return Procedure". Payment options such as credit card or money order will be explained by the Customer Service Representative. In cases where the minimum flat fee does not apply, as with incomplete units or units with excessive damage, an additional fee will be charged. If applicable, you will be contacted by Customer Service once your unit has been received. Information About Your System As soon as you open your Xantrex GT500 E 500 kW & Xantrex GT630 E 630 kW Grid-Tied Photovoltaic Inverters package, record the following information and be sure to keep your proof of purchase. Serial Number _________________________________ Purchased From _________________________________ Purchase Date _________________________________ WA4 975-0582-01-01 WA5 Product Registration To ensure the fastest possible service, please ensure your system information submitted to Xantrex. Please fill the required information in and send a copy of this page to Xantrex Technology Inc. Fax number: 1 925 245 1022 Mail to: Xantrex Technology Inc. 161-G South Vasco Road Livermore, CA 94551 Attention: Customer Service USA Customer Company Name: __________________________________ Project Name: __________________________________ System Location Information: Street __________________________________ City __________________________________ Country __________________________________ Xantrex Inverter Model: __________________________________ Serial Number of Inverter: __________________________________ Name of Distributor (if applicable): __________________________________ __________________________________________ __________________________________________ Xantrex Authorized Signature Customer Authorized Signature Date: Date: WA6 975-0582-01-01 Schneider Electric www.schneider-electric.com
North America 1 408 987 6255 1 925 245 1022 re.techsupport@schneider-electric.com La France +0825012999 fr-re-techsupport@fr.schneider-electric.com Deutschland +49 (0) 180 575 6575 +49 (0) 2102 404 7101 solarservice@de.schneider-electric.com Espaa +34 93 498 7466 +34 93 305 5026 re.techsupport@es.schneider-electric.com L'Italia +39 035 4151111 +39 035415 3200 IT-pronto-contatto@it.schneider-electric.com For other country details please contact your local Schneider Electric Sales Representative or visit our website at: http://www.schneider-electric.com/sites/corporate/en/support/operations/local-operations/local-operations.page Printed in Germany
Evaluation of Some Websites that Offer Virtual Phone Numbers for SMS Reception and Websites to Obtain Virtual Debit/Credit Cards for Online Accounts Verifications
Hacking: A Beginners Guide To Your First Computer Hack; Learn To Crack A Wireless Network, Basic Security Penetration Made Easy and Step By Step Kali Linux
Cybersecurity: A Simple Beginner’s Guide to Cybersecurity, Computer Networks and Protecting Oneself from Hacking in the Form of Phishing, Malware, Ransomware, and Social Engineering
Palo Alto Networks: The Ultimate Guide To Quickly Pass All The Exams And Getting Certified. Real Practice Test With Detailed Screenshots, Answers And Explanations