You are on page 1of 302

Session 1

Review of Basics

Types of Loads
Resistive Inductive Capacitive

Resistive Circuit

Current in Phase with Voltage

Inductive Loads
V

Current Lagging Voltage by 900

Capacitive Loads
I

Current Leading Voltage by 900

Power factor correction Some fundamental thoughts


What is Power factor? Why power factor is important? Why improve power factor? What is the power factor of various loads? What is the origin of power factor? How to improve power factor?

Definition of Power Factor


Power Factor = Active Power (kW)/ Apparent Power (kVA) Power Factor can never be greater than 1.00 Power Factor at best can be equal to 1.00 Usually P.F is always Lag ( Inductive) Some times P.F can be Lead ( Capacitive)

Origin of Low Power Factor


Electrical Equipment need Reactive Power Inductive loads draw Reactive Power Phase difference between current & Voltage reduces Displacement PF. Reactive Power to maintain magnetic fields in Motors. Non-Linear loads reduces Distortion PF. True PF, being product of displacement and distortion PF is lower than both.

Power Factor Improvement Concept


Reactive Power flow analogy Power Triangle analogy Resonance analogy

Reactive Power Flow Analogy


Voltage
Current

+
V Pi

Active power
Reactive power

Inductive Load

Inductive Load

Reactive Power Flow Analogy


Inductive Load Active power

Capacitor
Reactive power

Inductive Load

Power Triangle Analogy


QC S(kVA) S(kVA)

1
P(kW)

Q(kVAr)

1 2
P(kW) -QC

kVA=(kW)2 + (kVAr)2 PF = kW/kVA = Cos 1 Q = P .Tan 1 Uncompensated Load

QC = P (Tan 1 - Tan 2) Cos 1 = Initial Power Factor Cos 2 = Final Power Factor Partially compensated Load

Power Factor Correction

Reactive Current (capacitive) IR(C) 1 Reactive Current (inductive) IR(L) 2

I=Active Current V= Line Voltage

I2

I1

Resonance Analogy-1
Definition:Resonance is defined as a condition where Capacitive Reactance becomes equal to Inductive Reactance in magnitude. The frequency at which this occurs is called the Resonance Frequency.
| XL| = |XC |

Inductor
| XL| = |XC |

Inductor
|Z| = 0

Zeq = Z1 + Z2

|Z| = Zeq = Z1Z2 / (Z1+ Z2)

Series Resonance

Parallel Resonance

Resonance Analogy-2
Uncompensated load
Inductive Load

Compensated Load
Inductive Load

If you make |XL| of Load = |XC| of Capacitor at Fundamental Frequency, then the PF will be Unity due to Parallel resonance b/w capacitor & load inductor.

Inductor

Inductor

Resistor

Resistor

Resistor

Practical Example
40 W Fluorescent Tube Light

Choke P N

P = 40W+10W = 50W Power Factor = 0.6

230 Volts 50 Hz.

Calculation of PF correction based on Power Triangle concept


Active Power = 50 W. ; Power Factor = 0.6

Apparent Power = Active Power/ PF = 83.33 VA. Reactive Pr.= (VA)2-(W)2 = (83.33)2-(50)2 = 66.67 VAr. Capacitive VAr. req. for UPF = 66.67=V2(2f)C Hence Capacitor req. for UPF=106x66.67/2302/100 = 4.01 F.

Calculation of PF correction based on Resonance concept


Equivalent Circuit of Tube Light
R = V2/W = 2302/50 = 1058
Inductor Resistor

230V

XL = V2/VAr = 2302/66.67 = 793.5

L = XL/(2f) = 793.5/100 = 2.526 H. The value of capacitive reactance required to Resonate with the inductive reactance at the R fundamental frequency is given by, |XC| = |XL| = 793.5 = 1/100C C = 106/(793.5x100) = 4.01F.

Inductor

Resistor

230V C

Types of Power Factors


Displacement PF is defined as the cosine of the angle between fundamental voltage and fundamental current of the load. Presence of harmonics increases the RMS current and voltage relative to their respective fundamental values. This increases the kVA of the load. The PF taking into account the effect of harmonics, called True PF, is lower than or at best equal to displacement PF. The factor by which the displacement PF is related to true PF is called the Distortion PF True PF = Displacement PF x Distortion PF Capacitors can only improve displacement PF.

Mathematical expression of PF
Displacement Power factor = P/(V1I1) Where P = watts and V1 and I1 are fundamental voltage and current THDV 2 THDI 2 V = V rms 1 1+ 1+ 100 100 True Power factor = P/ (VrmsIrms) P = THDV 2 V1I1 1 + THDI 2 1+ 100 100 True Power factor = Displacement PF x Distortion PF Irms= I1

(
1+

) (
1

Where Distortion PF =

THDI 100

) 1 + (
2

THDV 100

Effect of harmonics on PF
%THD(V) 0 1 2 3 4 5 %THD(I) 0 20 40 60 80 100 Distortion PF 1.00 0.98 0.93 0.86 0.78 0.71

Three dimensional power triangle


kW kdVA

kVA kVA= kW2+kVAr2+kdVA2 kVAr Displacement PF = kW

kW2+kVAr2

kW True PF = kW2+kVAr2+kdVA2

Electric Power
Apparent Power kVA
wer Po
Po we r Re ac tiv e

tive Ac

Power Triangle
Reactive Power
Ap pa r en tP

kVA =
ow er

kW2 + kVAr2
kW kVA

P.F. =

Active Power

PF of various Industries
Industry
Textiles Chemical Machine shop Arc Welding Arc Furnaces Coreless induction furnaces and heaters Cement plants Garment factories Breweries Steel Plants Collieries Brick Works Cold Storage Foundries Plastic moulding plants Printing Quarries Rolling Mills (i.e. ,Paper, Steel , etc.)

Power Factor
0.65/0.75 0.75/0.85 0.4 / 0.65 0.35/ 0.4 0.7 / 0.9 0.15/0.4 0.78/0.8 0.35/0.6 0.75/0.8 0.6 / 0.85 0.65/0.85 0.6 / 0.75 0.7 / 0.8 0.5 / 0.7 0.6 / 0.75 0.55/0.7 0.5 / 0.7 0.3 / 0.75

Inductive Loads
Induction Motor 0.8 P.F Arc Furnace 0.8 P.F

Floursent Lamp 0.5 P.F. Induction Furnace 0.8 P.F Welding Transformer 0.5 P.F.

Session 2
Benefits of Power factor improvement

Advantages of P.F Correction

Reduction in KVAR Demand

Reduction in Switchgear Rating

Reduction in KVA Demand

Reduction in Transformer Rating

Reduction in Cable / Bus-bar size

Reduction in Line Current

Reduction in Line loss

REDUCTION IN KVA DEMAND


LOAD - 900 KW EXISTING P.F. (COS 1) - 0.6 DESIRED P.F. (COS 2 ) - 0.92 COS. = KVA = kW kVA kW cos . 900 / 0.6 = 1500 900 / 0.92 = 978
KV A

. KW

Reduction in KVA 1500 - 978 = 522

KVA 1 = KVA2 =

REDUCTION IN KVAR DEMAND


KW - 900 KVA1 - 1500 KVA2 - 978 kVA =

KW2 + KVAR2 KVA1 2

KVAR

KV A

KVAR1 = =

KW2

. KW

1500 2 - 900 2 = 1200 978 2 - 900 2 =


382

Reduction in KVAR 1200 - 382 = 818

KVAR 2 =

KVA1 - 1500 KVA2 - 978

REDUCTION IN LINE CURRENT


KVA I I1 = = = =

3 V I
1000 KVA x 1000 3 x 415 1500 x 1000

3 x 415
2087 Amp 978 x 1000

Reduction in Current 2087 - 1361 = 726

I2

= =

3 x 415
1361 Amp

% Rise in Current w.r.t. decrease in Power Factor


% Rise in I n 100
90 80 70 60 50 40 30 20 10 0

0.9

0.8

0.7

0.6

0.5

P.F .

Cable Losses
% of saving in losses =

1-

Cos1 Cos2

X 100

1-

0.6 0.92

X 100

= 57.46

Saving in Cable Losses


80 70 60 50 40 30 20 10 0 0.5

P.F.
1.0 0.95 0.9

0.8
0.6 0.7

0.85

0.8

0.9

Initial P.F.

Transformer Losses
Saving in losses = Wr x K1
1 Cos

1 Cos

Wr = Full load copper loss of the transformer connected load in Kw k1 KVA rating of the transformer

Graph Transformer Losses

Transformer Losses
40000 35000 30000 cu Loss 25000 20000 15000 10000 5000 0 0 500 1000 1500 2000 2500 3000 3500 Transformer KVA

Copper losses

Transformer Losses
Saving in losses = Wr x K1
1 Cos

1 Cos

900 = 18000 x 1500 = 6260 Watts x

1 0.6

1 0.92

Annual Saving = 6260 x 300 x 12 = 22536 KWH 1000

Power Savings
3000 2500 2000
1500 1500 1000 2500 2086 1360 1600

1500 1000 500 0 KVA X'MER


978

CURRENT AT 0.92 PF

AT 0.6 PF

ACB RATNG

Workshop - I
1.

Calculate the pf and kVA demand at the secondary of a 1000kVA, 11/0.44 kVA transformer supplying the following loads:
100kW 150kW 250kW 100kW UPF 0.9 lag 0.8 lag 0.9 lead

2.

A 50HP 440V, 3ph, 50Hz, 1500rpm Induction motor has the following operating conditions: PF = 0.9lag, & efficiency = 90% under full load. PF = 0.6lag, & efficiency = 70% under half load. If a 3ph. 440V capacitor of rating 12.5kVAr is connected at the motor terminals, find the pf of the motor and capacitor combination, under: a) Full load b) Half load.
(Use 1HP = 0.746 kW for HP to kW conversion).

Session 3
Evaluating PF from Electricity Bill

ELECTRICITY TARIFFS - I
In India, there are broadly 4 types of Electricity Tariffs.
Single part tariff
Measurement of kWh only - Energy charges Generally applicable for LT installations only.

Two part tariff


kWh - Energy charges kVA or kW - Maximum demand charges PF Penalty/Incentives - vary from region to region Applicable for HT installations

ELECTRICITY TARIFFS II
Three part tariff
kWh - Energy charges kVArh - Reactive Energy charges kVA or kW - Maximum demand charges PF Penalty- vary from region to region Applicable for HT installations

Time of day tariff


Different charges for the various quantities mentioned above depending on the time of the day Analogous to STD (Telecom) tariff structure

PF PENALTIES
Different structures are followed - Some common features
Minimum monthly PF limit - Varies from 0.85 upwards If PF falls below minimum limit then penalty is levied The penalty is normally calculated as a %age of the Energy charges or the full value of the Electricity Bill. The %age of penalty is normally linked to the difference between actual monthly PF as calculated by Electricity supply authorities and the minimum PF limit specified.
For Ex: Minimum PF limit - 0.90 Actual monthly PF as per calculated by Electricity Supply authorities - 0.82 Penalty is 1% for every 0.01 difference between above PF values Hence penalty will be 8% in this case.

INCENTIVES FOR HIGH PF


Different structures are followed - Some common features
Minimum Upper monthly PF limit - from 0.92 upwards If actual monthly PF exceeds this upper limit, then incentive is offered The incentive is normally calculated as a %age of the Energy charges or the full value of the Electricity Bill. The %age of incentive is linked to the difference between actual monthly PF as calculated by Electricity supply authorities and the minimum Upper PF limit specified.
For Ex: Minimum Upper monthly PF limit - 0.95 Actual monthly PF as per Electricity bill - 0.98 Incentive is 1% for every 0.01 difference between above PF values Hence Incentive will be 3% in this case.

EVALUATING PF FROM ELECTRICITY BILL


The value of monthly PF is normally indicated on the Electricity bill If this value is not shown on the Electricity bill, then the normal procedure is as follows
Note down kWh consumed as given in the bill Note down kVAh consumed as given in the bill Divide kWh by kVAh This value should always be less than 1 This gives the monthly PF as considered by the Electricity Supply authorities.

ESTIMATE kVAr REQUIRED - I


From Electricity bill data Note down the value of maximum demand in kVA as given in the Electricity bill Convert this value to kW by multiplying the maximum demand kVA with the monthly PF
For ex: If maximum demand kVA is 375 and monthly PF is 0.80 then, kW = 375 x 0.80 = 300 kW

Monthly PF should be assumed as Initial PF - 0.80 Fix target PF as Final PF - Let us assume - 0.96 Note down multiplying factor from table 4.2 on Page 6 of RPM catalogue This multiplying factor is 0.458

ESTIMATE kVAr REQUIRED - II


Multiply the kW calculated earlier by this multiplying factor
kVAr = 300 x 0.458 = 137.4 kVAr - rounded off to 150 kVAr, since this is easy to offer

Always recommend fixed compensation for the transformer in the installation - the kVAr required can be estimated from table 4.3 on Page 7 of RPM Catalogue
For ex: If in the above installation the transformer is 500 kVA then fixed compensation required is 6% of 500 kVA which works out to 30 kVAr

Out of 150 kVAr we can now subtract this 30 kVAr i.e., leaving a balance of 120 kVAr

ESTIMATE kVAr REQUIRED - III


Of this 120 kVAr we can recommend additional compensation only for base load. Fixed
If base load is given as 40% of the installation, 40% of the above kVAr can be provided as fixed compensation. Therefore 40% of 120 kVAr = 48 kVAr - about 50 kVAr Consequently, the balance kVAr can be as an APFC This works out to 120 - 50 = 70 kVAr - about 75 kVAr

The final compensation scheme customer can be


Total Compensation - 150 kVAr - of which

Fixed compensation - 75 kVAr APFC - 75 kVAr

This procedure is common to Industrial and Commercial Installations.

Workshop-2
Calculate the kVAr required to improve the pf of an LT installation to 0.95 lag. You have the following details from the Bill. Billing date = 01.07.2001 to 31.07.2001 Units consumed = 13500 kWh. Avg. PF = 0.8 lag. Calculate the kVAr required to improve the pf of an HT installation to 0.97 lag. You have the following details from the Bill. Contract Demand = 300 kVA Recorded Demand = 270 kVA Avg. PF = 0.8 lag. Units consumed = 75600 kWh

Session 4
Evaluating kVAr for new installations

ESTIMATE kVAr REQUIRED for New Electrical Installations - I


Refer the SLD below
500kVA, 11kV/415V, %Impedance = 4.25%

M
30 HP, 415V, 3ph, motor

M
75 HP, Other loads, 415V, total of 25 3ph, kW compressor 50 kVA, 440V, 3ph, UPS

M
75 HP, 415V, 3ph, compressor

Resistive Load 30kW Lighting

20 HP, Load 10kW 415V, 3ph, Pump, PF =0.80 Lag

ESTIMATE kVAr REQUIRED for New Electrical Installations - I


We must draw up a load list of the Maximum operating load (including the supply transformer) & fix the target Power Factor as desired by the Customer. Let us assume the load list as follows Supply transformer - 3 Phase, 500 kVA, 11 kV/415V, 3 Phase, 415 V, Induction motors - Totaling to 200 HP 3 Phase, 415 V, UPS system - 50 kVA Resistive heating load - 30 kW Lighting load (Fluorescent) - 10 kW Miscellaneous loads - 14 kW Let us assume that the target Power Factor as desired by the Customer is 0.95.

ESTIMATE kVAr REQUIRED - for New Electrical Installations - II


The kVAr can be estimated as follows:
The kVAr required for the supply transformer can be estimated from Table 4.3 on pg 7 of RPM Cat.
For 500 kVA transformer kVAr = 30 kVAr

Convert induction motor rating from HP to kW - 200 HP x 0.746 = 150 kW


Assume that initial PF of motors is likely to be around 0.7, because of the fact that motors are generally oversized due to other considerations. Calculate kVAr by using multiplying factor as given in Table 4.2 on Page 6 of RPM Catalogue - Multiplying factor for initial PF of 0.7 and final PF of 0.95 = 0.692. Hence, kVAr = 150 x 0.692 = 104 kVAr

ESTIMATE kVAr REQUIRED - for New Electrical Installations - III


The kVAr can be estimated as follows:
Convert the UPS system kVA to kW by assuming a PF of 0.7 to be on the safer side. Hence, kVAr required for the UPS is 25 kVAr. The resistive heating loads are unity Power Factor loads and hence do not consume Reactive Power. Hence, kVAr compensation is not required. For other loads i.e., fluorescent lighting - 10 kW and miscellaneous loads of 14 kW assume an average PF of 0.7. Hence kVAr works out to about 17 kVAr.

ESTIMATE kVAr REQUIRED - for New Electrical Installations - IV


The total kVAr can be estimated as follows:
Transformer - 30 kVAr , Induction motors - 104 kVAr, UPS - 25 kVAr, Other loads - 17 kVAr: Total kVAr = 176 Round off on the higher side by about 15% since, significant assumptions have been made in the calculation. Hence, total kVAr recommended can be 200 kVAr. Capacitors can be connected at motor terminals.The total kVAr of such Capacitors may be subtracted from the figure of 200 kVAr. For calculating the balance fixed compensation and APFC combination, the procedure given earlier applies.

HOW TO CALCULATE SAVINGS


If Power Factor is improved cash savings arise due to the following : Reduction in kVA demand charges Elimination of Penalties for low Power Factor Incentives for maintaining high Power Factor

Hence, we must calculate the above savings as given in the workshop 3 problems.

Workshop-3
1. In problem 1 of workshop-2, if the PF penalty is 5% of kWh charges, calculate the savings when the PF is improved to 0.95 lag. Unit charges = Rs. 3.5/ kWh. Unit consumed = 13500 kWh. In problem 2 of workshop-2, the penalty clause is as follows: kVA charges = Rs. 180/kVA (if Demand < CD) = Rs. 180 x 3 ( if Demand > CD) Unit charges = Rs. 3.4 / kWh. Units consumed = 56700 kWh PF penalty = 5% on energy consumed

2.

CLAUSES, TERMS & CONDITIONS


All calculations are done on assumptions of certain Electrical loading in the installation. If any changes occur due to modifications/ revisions of load data and characteristics the desired PF may not be achieved This is particularly important in Indian conditions, since data given by the Customer is not always accurate. This issue must be kept in mind when dealing with customers.

Session 5 Methods of improving power factor

Methods of Improving Power Factor


Fixed Compensation
For Steady Loads No load compensation of Motors No load compensation of Transformers

Variable Compensation
For Varying Loads

Selection of Capacitor
1. Individual Compensation 2. Group Compensation 3. Central Compensation

Where to install Power Factor correction Equipment


Individual Compensation Directly at the Load terminals Ex. Motors, Steady loads Gives maximum benefit to user Not recommended for Drives Costly solution

Where to install Power Factor correction Equipment-2


Group Compensation Single compensation for Group of Loads Ex. Group of Motors Gives moderate benefit to user Few Capacitor Banks Relatively easy to maintain

Where to install Power Factor correction Equipment-3


Central Compensation Directly connected at the incomer Improves PF at the metering point Line losses continue to prevail down stream Least beneficial to user Extremely easy to maintain

Central Compensation Providing compensation at the main incomer of the installation is called central compensation (pos. No. 1). This is suitable for installations where the loads are few and situated close to the main supply. (Refer Fig. 3.1) Supply Bus

Transformer Circuit Breaker No 1 M M M Fig. 3.1 M

Central,Group and Individual Compensation


Providing compensation at main incomer bus central compensation. (pos. No 1) At power distribution boards group compensation (pos. No. 2). At individual load terminals individual compensation. (pos. No. 3) This is suitable for installations consisting of main receiving station, substations, several load feeders and a wide variety of loads. (refer fig 3.3)

Supply Bus Transformer Circuit Breaker


No 1 No 2 No 3 M No 3 M No 2 No 3 M No 3 M

Fig. 3.3

Session 6
Selection of capacitors

TYPES OF CAPACITOR TECHNOLOGIES


MPP - METALLISED POLYPROPYLENE MD - MIXED DIELECTRIC FF/ALL PP - FILM - FOIL OR ALL POLY PROPELENE MD -XL - MIXED DIELECTRIC LOW LOSS

METALISED POLYPROPELENE CAPACITOR


MPP - METALLISED
METALLISED LAYER

POLYPROPELENE METALISATION HAS BEEN DONE ON ONE SIDE OF POLY PROPELENE FILM AND USED FOR CAPACITOR WINDING ECNOMICAL AND COMPETITIVE DESIGN MPP-S - NORMAL DUTY MPP-H - MEDIUM DUTY

PP FILM

SELF HEALING
DURING INTERNAL FAULTS

SELF HEALING IS PROTECTIVE FEATURE

AFTER SELF HEALING

PRESSURE SENSITIVE DEVICE


SELF HEALING PRODUCES GASES, WHICH WILL INCREASE THE PRESSURE INSIDE THE CAN. THIS WILL CAUSE THE BELLOWS TO EXPAND. BEYOND A POINT POWER SUPPLY WILL BE CUT-OFF. THUS BURSTING OF CAPACITOR IS PREVENTED.

MIXED DIELECTRIC
MD - MIXED DIELECTRIC
PAPER

PP FILM, FOIL AND PAPER ARE USED TO


PP FILM FOIL

FORM CAPACITOR WINDING

FILM FOIL OR APP


FILM FOIL OR APP PP FILM

ALL POLY PROPELENE METAL LAYER IS PLACED IN - BETWEEN

PP FILM

FOIL

PP FILM TO FORM CAPACITOR WINDING

MIXED DIELECTRIC LOW LOSS


MD-XL - MIXED DIELECTRIC LOW LOSS
DOUBLE SIDE METALLISED PAPER

PP FILM AND DOUBLE SIDED METALISED FILM


PP FILM

ARE USED TO FORM CAPACITOR WINDING

Film foil/APP verses Mixed dielectric comparison


Film foil/APP
low dielectric watt loss Film not impregnable More prone to Self healing Inferior long term stability Moderate harmonic overload capability

Mixed dielectric
High dielectric watt loss Paper impregnable less prone to Self healing Superior long term stability Good harmonic overload capability

Mixed dielectric verses MDXL Comparison


Mixed dielectric
High dielectric watt loss Paper impregnable less prone to Self healing Superior long term stability Good harmonic overload capability

MDXL

Lowest dielectric watt loss Combines plus points of MD and APP types Excellent long term stability Superior harmonic overload capability

Comparison of Technologies
MPP-S Rating MPP-H Long life Rating MD Long life Rating MD-XL Long life Rating FF Long life Rating

Life

Optimum

10

10

10

Non-linear loads Capability

Up to 10 %

Up to 15 %

Up to 25 %

10

Up to 25 %

10

Up to 25 %

10

Initial cost

Lowest

10

Medium

Highest

High

Highest

Operating cost

Lowest

10

Lowest

10

Highest

Lowest

10

high

Total

24

25

22

31

25

Cylindrical verses stand-alone type


Cylindrical Type Stand-alone Type

Compact Size Better heat dissipation Discharge resistor in Minimal internal wires Suitable only for panels MPP-S,MPP-H,MDXL Not repairable

Bulky Inferior heat dissipation Two resistor configuration More Internal wires Robust construction Available in all types Elements can be replaced

Gas filled capacitors


Only made by EPCOS & Electro-Nicon (Germany) Considered to be better heat dissipation than oil Debated by ABB, hence controversial Equivalent to MPP but EPCOS claiming as APP Inferior to MDXL (MKV of EPCOS) SF6 banned for LV application, hence nitrogen Leakage not noticeable and failure is sudden Lighter in weight Generally available in 10 to 25 kVAr. units

Gas filled capacitors from L&T Meher


To fill the Technological gap Design improvement over EPCOS Protective coating on element ensures longer life even after gas leakage. Available in the financial year 2004-05

Launch of Resin filled Capacitors


Jelly Resin has much better di-electric properties compared to Gas. Meher is switching to resin filled capacitors. Oil filled capacitors will also be available on request. However MDXL will continue with oil

Competitive edge of MEHER


Comprehensive test facility in Meher works. Raw materials imported from premium source. Automatic element winding machine. Robot spraying machine. Only Indian capacitor company to transfer technology to Germany. Joint Venture in Capacitor manufacturing in Germany through MKS Technologies ISO revalidated by BVQI from 2004 to 2007. On the verge of getting UL certification for marketing internationally.

Peak current measurement capability at Meher Works

Session 7
Some basic formulae capacitance,capacitor currents

Capacitor Connection
R

Capacitor Rated Current


KVAR = 3. VL IL 1000 KVAR .1000 3 .VL

IL

Change in Current Vs. Change in Voltage


VOLTAGE KVAR CURRENT

440 415 400 380 360

28.10 25.00 23.23 20.96 18.81

36.88 34.78 33.52 31.85 30.17

Capacitance
6 f C VL2 KVAR = C CM = = 10 9 KVAR X 10 9 6f 1.5. C VL2

*
F
C

CM

Calculate Capacitance C and CM for 25 KVAR, 415 V, 50 Hz. capacitor * C in F

and VL in Volts

Peak inrush current of capacitor


Ip = Ir

MVA SC X 103 kVArc

Ip Ir MVAsc kVArc

= Peak inrush Current in Amps = Capacitor Rated Current in Amps. = Short circuit MVA of the System = Capacitor Rating in kVAr.

Fault Level Calculation


Maximum Fault Current =
Transformer % Z = 5 1000 KVA , 22.0kV/415V

1.1 VL 3 ZT 1.1 x 415 3 x 0.00861 30607 Amp

= =

ACB

Transformer = impedance =

%Z x 10 x kV2 kVA 5 x 10 x 0.4152 1000

0.00861 Ohm

Short Circuit MVA of the System


Short circuit MVA of the System = 3 VL Isc 10 6 = 3x 415 x 30607 10 6 = 22.0

Peak Current Calculation


Capacitor Rating = 25 KVAR, 415V, 50 Hz. Ip = Ir . 2

MVA SC X 103 kVARc

Ip= 34.78. 2

22.0 X 103 25

= 1459.1 Amp

Parallel Switching of Capacitor

Ip =

2 3

1 VL

X C XL

Ip = Peak inrush current in Amps. VL = Line to Line Voltage in Volts


XC = Capacitive Reactance in Ohms XL = Inductive Reactance Between the Capacitors in Ohms.

Voltage Rise Due To Capacitor


Q V = S V V = Voltage Rise V = System Voltage Without Capacitors Q = Capacitors Rating in MVAR S = System Fault Level In MVA

Voltage Rise Due To Capacitor


For a 25 kVAr, 415V capacitor & System fault level of 22 MVA.

Q V = S V V = 415 x 0.025 22

= 0.47 volts

Discharge Time

Discharge Time < = 60 sec for LT capacitors < = 10 min for HT capacitors Voltage at the end of Discharge time should be < = 50 volts taking into account the plus side tolerances of the Capacitance value and supply voltage. C

Discharge Time
t R< K C log e
R = t =

Vn.2 VR

Discharge Resistance in M Ohm Discharge Time in Sec. 1/3 or 1 or 3 depending upon discharge resistor Configuration. Capacitance in F Capacitor Rated Voltage Permissible Residual Voltage

K =

C = Vn = VR =

Configuration of Discharge Resistors


R K=1 C C R K=1 R C K=3 R
C

K = 1/3

R C

R C
R

K=3

C K=1

USEFUL FORMULAE AND TABLES 1. Capacitance in parallel C = C1 + C2 + C3 Where C = equivalent capacitance of parallel circuit. 2. Capacitance in Series 1 1 1 1 = + + C C1 C2 C3 Where C = equivalent capacitance of series circuit.

3. Calculation of Capacitor kVAr Required for PowerFactor Improvement

Capacitor kVAr Where 1 2

= kW (tan1 - tan2) = Cos-1(PF1) and = Cos-1(PF2)

PF1 and PF2 are initial and final power factor respectively.

Multiplying Factor Table to Calculate kVAr


Present PF 0.9 0.91 0.92 0.93 0.94 0.4 1.807 1.836 1.865 1.896 1.928 0.45 1.500 1.529 1.559 1.589 1.622 0.5 1.248 1.276 1.306 1.337 1.369 0.55 1.034 1.063 1.092 1.123 1.156 0.6 0.849 0.878 0.907 0.938 0.970 0.65 0.685 0.714 0.743 0.774 0.806 0.7 0.536 0.565 0.594 0.625 0.657 0.75 0.398 0.426 0.456 0.487 0.519 0.8 0.266 0.294 0.324 0.355 0.387 0.85 0.135 0.164 0.194 0.225 0.257 0.9 0.029 0.058 0.089 0.121 0.91 0.030 0.060 0.093 0.92 0.031 0.063 0.93 0.032 0.94 0.95 0.96 0.97 0.98 0.99 Final PF 0.95 1.963 1.656 1.403 1.190 1.005 0.840 0.692 0.553 0.421 0.291 0.156 0.127 0.097 0.067 0.034 0.96 2.000 1.693 1.440 1.227 1.042 0.877 0.729 0.590 0.458 0.328 0.193 0.164 0.134 0.104 0.071 0.037 0.97 2.041 1.734 1.481 1.268 1.083 0.919 0.770 0.631 0.499 0.369 0.234 0.205 0.175 0.145 0.112 0.078 0.041 0.98 2.088 1.781 1.529 1.315 1.130 0.966 0.817 0.679 0.547 0.417 0.281 0.253 0.223 0.192 0.160 0.126 0.089 0.048 0.99 2.149 1.842 1.590 1.376 1.191 1.027 0.878 0.739 0.608 0.477 0.342 0.313 0.284 0.253 0.220 0.186 0.149 0.108 0.061 1.00 2.291 1.985 1.732 1.518 1.333 1.169 1.020 0.882 0.750 0.620 0.484 0.456 0.426 0.395 0.363 0.329 0.292 0.251 0.203 0.142

4. For Single Phase Capacitor


1 lC 2 V

kVAr =

fCV2 109

kVAr . 103 IC = V

XC =

106 2 fC

C XC V kVAr IC

= Measured capacitance across terminals 1 &2 in F = Capacitive Reactance in ohms = Voltage in Volts = Rated output of capacitor = Capacitor Current in Amps.

5. For a Balanced Three Phase Delta Connected Capacitor


1 V 2 3 CM C C V = Vph C Vph CM 1.5 F

CM is the measured capacitance across any two terminals with the other terminal left open circuited.

106 XC / ph = 2fc

2fcV2 X 3 3 phase kVAr = 109

IL =

3ph kVAr X 103 3 V

Where

XC V kVAr IL

= Capacitive Reactance per phase in ohms = Voltage (line to line) in volts = Rated output of capacitor = Line current in Amps

6. For a Balanced Three Phase Star Connected Capacitor


1

IL

>
C
Vph

CM

V C
2 3

Vph = V/ 3 C C= 2CM

CM is the measured capacitance across any two terminals with the other terminal left open circuited.

XC/Ph

106 2fc 2fcV2 109


x3 103

Where XC = Capacitive Reactance per phase in ohms V = Voltage (line to line) in volts kVAr = Rated output of capacitor

3 Ph kVAr =

IL

3 ph kVAr X 3 V

IL = Line current in Amps

7 Inrush transient current 7.1 Switching in single capacitor

Ip = Ir . 2 . Where IP Ir MVASC kVArC

MVAsc . 103 kVArc

= The peak value of Inrush Capacitor current in Amps = The rated capacitor current (rms) in Amps = the short circuit power in MVA at the point where the capacitor is connected = kVAr of the capacitor

7.2 Switching of capacitors in parallel with energized capacitor

IP =

2 . V 3 . XcXL
= the crest value of Capacitors inrush current in Amps = Rated voltage in volts (line to line)

Where IP V

XC = Capacitive reactance per phase in (ohms) XL = the inductive reactance per phase between the capacitors in (ohms)

7.3 Frequency of Inrush Current

fS = fN .

Xc XL

Where fS fN XC XL

= the frequency of inrush current in Hz = the Rated frequency in Hz = Capacitive Reactance per phase in (ohms) = the inductive reactance per phase between the capacitors in (ohms)

Measured verses cell capacitance


Ca Cc C1 C2 Cb C3 1

C1,C2,C3 are the capacitance measured as indicated with the third line open-circuited. Ca,Cb,Cc are the cell capacitance, internal to the three phase capacitor. Using following formulae we can calculate cell capacitance, without opening and de-soldering/cutting the capacitor units.
1

Ca =

1 1 1 + C1 C3 C2

Cb =

1 1 1 + C1 C2 C3

Cc = 1

1 1 - 1 + C2 C3 C1

where
= C1+C2+C3 C1C2C3 1 2

1 1 1 + 2+ 2 C12 C2 C3

These are derived from the following basic relationships. C cC a CaCb C3 = Cb+ C 1 = C c+ C + C C c+ C a a b CbCc C2 = Ca+ Cb+ Cc

Measured verses cell capacitance


1 Ca Cc Ca Cc C2 2 Cb C1 3 Cb 3 2 Cb 2 C3 3 1 Ca Cc 1

C1,C2,C3 are measured capacitances across any line and other two lines short circuited. Full line to line voltages are applied across the cells. C1 = Ca+Cb C2 = Ca+Cc C3 = Cb+Cc 1 (C +C -C ) 2 3 1 2

The individual cell capacitances can be computed as follows.


Ca = 1 (C +C -C ) ; 1 (C +C -C ) ; Cb = 1 3 2 2 1 2 3 2 Cc =

Cost Based Selection


The total cost of using a capacitor is a function of Purchase Cost Operating Cost

While purchase cost is easy to estimate it is necessary to also evaluate operating cost The operating cost of a capacitor is a function of the total losses & the operating time of the capacitor.
Ex: An installation requires 1000 kVAr which will be operated for about 6000 hrs per year. Calculate the operating cost of MD-XL Capacitors verses MD type Capacitors assuming a life expectancy of 15 years for the Capacitors. The total energy consumed by the Capacitors for its on operation is calculated as follows

Calculation of operating cost of capacitors


An installation requires 1000 kVAr which will be operated for about 6000 hrs per year. Calculate the operating cost of MD-XL Capacitors verses MD type Capacitors assuming a life expectancy of 15 years for the Capacitors. The total energy consumed by the Capacitors due to its internal watt loss is calculated as follows.

Cost Based Selection


MD-XL Capacitors
Energy Consumed = (Loss per kVAr x Total kVAr x Operating time)/1000 = (0.5 x 1000 x 6000 x 15) / 1000 = 45,000 kWh

MD Capacitors
Energy Consumed = (Loss per kVAr x Total kVAr x Operating time)/1000 = (1.5 x 1000 x 6000 x 15) / 1000 = 1,35,000 kWh Consequently, the excess energy consumption due to the MD Capacitor shall be = 1,35,000 45,000 = 90,000 kWh This energy consumed can be converted into cost using a weighted average cost of Rs.5 per kWh. Consequently, the extra cost shall be Rs.5 x 90,000 = Rs.4,50,000. On a per kVAr base this can work out to Rs.450/-per kVAr. It is obvious that operating cost must be evaluated carefully before taking the final decision on the type of capacitor to be used. It is also self explanatory that lower the losses, lower will be the operating cost.

Session 8
Automatic Power Factor Correction (APFC)

NEED FOR AUTOMATIC POWER FACTOR CORRECTION


Modern Power networks cater to a wide variety of electrical and power electronic loads, which create a varying power demand on the supply system. In case of such varying loads, the power factor also varies as a function of the load requirements. It therefore becomes practically difficult to maintain a consistent power factor by use of Fixed Compensation i.e. fixed capacitors which shall need to be manually switched to suit the variations of the load. This will lead to situations where the installation can have a low power factor leading to higher demand charges and levy of power factor penalties.

NEED FOR AUTOMATIC POWER FACTOR CORRECTION


The use of fixed compensation can also result in leading power factor under certain load conditions. This is also unhealthy for the installation, as it can result in over voltages, saturation of transformers, mal-operation of diesel generating sets, penalties by electric supply authorities etc. It is therefore necessary to automatically vary, without manual intervention, the compensation to suit the load requirements. This is achieved by using an Automatic Power Factor Correction(APFC) system which can ensure consistently high power factor. In addition, the occurrence of leading power factor will be prevented.

Session 9
Intelligent APFC Relay

POWER FACTOR CONTROL SCHEME R Y B

PFCR
MEASURING UNIT OUTPUT RELAYS CAPACITOR BANKS

TO LOAD

8 STAGE 14 STAGE

1 : 1 : 1 : 1 : 1 : . 1 : 2 : 2 : 2 : 2 : . 1 : 2 : 4 : 4 : 4 : . 1 : 2 : 4 : 8 : 8 : .

Features
Controls power factor Protects capacitor banks Measures & displays various parameters Records

Controls Power Factor


Maintains system power factor at a set value Under varying load conditions Uses microprocessor techniques for measurement of reactive current & system power factor Can control upto 8 capacitor banks

Optimization of Capacitor Banks


Constantly selects right combination of capacitor banks to ensure pf is kept very close to the desired value.

Top-up Facility
Constantly monitors the actual pf & compares with target value. Any spare capacitor bank is utilized to push up the pf to unity even after the target value is met. Ensures reactive power consumption is kept to the minimum. Feature can be enabled or disabled.

Short Time Delay Facility


This is the time delay between the immediate OFF to ON of a capacitor bank. Provides additional delay of 30msec between switching, if enabled Ensures longer life of capacitors

Hunt Free Operation


Capacitor hunting is avoided by providing threshold values.

Automatic Disconnection of Faulty Capacitor Bank


If any capacitor bank is reduced to 60% of its original rating, it treats the bank as defective, after three successive switching

Protection Against Fault Conditions


Switches OFF all capacitor banks & provides a safety lockout period of 60 sec when power interruption occurs Protects against
over voltage, under voltage Under current Harmonic overload By switching of capacitor banks one after another

Provides alarm for fault conditions & for 5th & 7th harmonics

Multi-parameter Display
Voltage Current Reactive power Accurate display of power factor even in presence of harmonics.

Records
Keeps updated (every two hours) records for each bank. Number of times each bank is switched on for pf compensation. Configuration with respect to lowest bank size.

Session 10
Issues in Power Quality

Momentary Voltage Sag

Momentary voltage sag , which is a momentary decrease in voltage outside normal tolerance.

Momentary Voltage Swell

Momentary Voltage swell , which is a corresponding voltage increase often caused by the sudden de energizing of heavy equipment.

Voltage Loss

Voltage Transient / Impulse

Voltage transient or impulse , which is a very short duration voltage, whose amplitude will be in the range of several tens to thousand volts.

Voltage Spike

Voltage Spike ,which can destroy electronic equipment and damage transformer and motor insulation. They also cause failures in capacitors and indicators.

Notch in the Voltage Waveform

Liner Load Characteristics

Voltage Waveform

Current Waveform

Non-linear Load Characteristics

Voltage Waveform

Current Waveform

Scope
Improvement of power quality in LV networks To enhance network reliability To reduce failure of electrical & electronic equipment To increase profitability by saving on energy costs To achieve energy conservation

Power Quality in LV Networks - I


External power quality Conditions arising from incoming power supply source
Voltage fluctuations
Steady state Transients

Frequency variations Interruptions in power supply Import of harmonics

Power Quality in LV Networks - II


Internal power quality
Function of conditions arising due to use of equipment to overcome external power quality problems
On-line UPS systems Voltage regulating devices
AUTO TRANSFORMER, STABILISERS etc.

Back-up power supply


DG Sets Inverters etc.

Power Quality in LV Networks - III


Internal power quality
Is also a function of types of loads connected in the network
Non-linear loads
Rectifiers, converters, drives Battery chargers, UPS systems Modern lighting systems

Rapidly fluctuating loads


Welding machines Plastic extruders High speed presses

Single phase SMPS loads


PCs, Servers, LAN Networks.

Power Quality Issues


Reactive power flow Harmonic currents & voltages Voltage dips Voltage flicker Unbalanced load High neutral current Excessive neutral to earth voltage

Problems ! - I
Reactive power flow
Lower PF & Increased kVA Demand. Overloading of transformers, cables & switchgear. Increased energy consumption due to higher losses. Financial penalties for low PF. Loss of financial incentives for high PF.

PROBLEMS ! - II
Harmonic currents & voltages
Overheating & failure of
Electrical equipment
Motors, transformers, switchgear Capacitors

Power electronic equipment

Malfunction/failure of
Protective relays Control & Automation equipment

Increased energy consumption. Risks of resonance - current amplification extremely dangerous

PROBLEMS ! - III
Voltage dips & flicker
Failure of power electronic equipment Malfunction/failure of
Protective relays Control & Automation equipment

Increased strain on eyes.


Due to fluctuations in intensity of lighting systems.

PROBLEMS ! - IV
Unbalanced loads
Over & under voltage in the network. Increased energy consumption by motors
Due to reduced efficiency.

Failure of power electronic equipment Malfunction/failure of


Protective relays Control & Automation equipment

PROBLEMS ! - V
High neutral current
Overheating of neutral conductors Increased energy consumption If neutral becomes open high voltages will occur, resulting in
Malfunction/failure of
Single phase loads Protective relays Control & Automation equipment

Risk of fire & destruction

Accumulation of 3rd harmonic current in neutral


Three phase system

Wave forms of balanced three phase fundamental currents.


Time.
R - phase.

R-Phase current with its third harmonic component.


Time.
Y - phase.

Y-Phase current with its third harmonic component.


Time.
B - phase.

B-Phase current with its third harmonic component.


Time. Addition of third harmonics in Neutral conductor

Time.

Third harmonic currents of R,Y&B phases are in phase with each other and hence adds up, without cancellation in the neutral conductor.

SOLUTIONS - I
Networks with <20% non linear load Improve PF, reduce voltage dips/flicker by the use of
Power capacitors APFC systems
Contactor switched Thyristor switched
Open loop systems Closed loop systems

SOLUTIONS - II
Networks with >20% non-linear load Improve PF, reduce harmonics & voltage dips/flicker by the use of
Fixed detuned filters Detuned filters + APFC systems
Contactor switched Thyristor switched
Open loop systems Closed loop systems

AHF - Active Harmonic Filters

SOLUTIONS - III
Networks with unbalanced loads. Improve PF, reduce harmonics & voltage dips/flicker by the use of
Phase balancing circuits Electronic VAr Compensation Systems. AHF - Active Harmonic Filters

SOLUTIONS - IV
Networks with high neutral current / excessive neutral to earth voltages
Ensure proper EARTHING quality Oversize all neutral conductors to reduce neutral heating If OVERSIZING is not possible, reduce harmonics by the use of
AHF - active harmonic filters in 4 line configuration

Active filter schematic diagram


Lo ad C u rren t w ith H arm o n ics Sin u so id al Su pp ly C u rren t Su pp ly Sy stem

C o m p ensatin g C u rren t A ctiv e F ilter

+
( T im e Do ma in )

+
( F requ en cy D oma in )

Benefits of POWER QUALITY MANAGEMENT


Improved reliability of installation Reduced energy consumption Reduced fuel consumption Better productivity Improved profitability Enhanced equipment life

Session 11
Dynamic Compensation

Scope
Need for Dynamic Compensation

Applications

Need for DYNAMIC COMPENSATION


When load conditions demand rapidly fluctuating reactive power.
Due to nature of load. Due to process requirements.

When switching transients are to be eliminated. For Optimizing performance & fuel consumption of DG sets.

THYRISTOR SWITCHED APFC


There are certain loads which demand, under certain operating conditions, large amount of reactive power for very short duration of time. Typical examples are: Welding equipment Injection moulding equipment Starting of large induction motors Traction loads such as, lifting cranes, elevators, lifts, etc.

Thyristor Switched APFC


The large demand for reactive power by such loads during operation can cause: Rapid voltage fluctuation System instability Over sizing of electrical installation since kVA capacity will have to be provided for the maximum power demand. Malfunctioning of sensitive electrical and electronic equipment such as relays, PLCs etc. These ill-effects can be overcome by injecting into the network defined amount of reactive power at a very fast rate which can meet the demand of such loads.

RAPIDLY FLUCTUATING LOADS - I


Variations in current are sudden & high Lower PF & voltage dip Examples
Motor starting EOT cranes, lifts Rolling mills Conveyors - Mining etc. Wind electric generators

RAPIDLY FLUCTUATING LOADS - II


Current drawn in repetitive pulses Lower PF & voltage dips / flicker Examples
High speed presses
Metal working Plastic processing

Balanced welding loads

SWITCHING TRANSIENTS
Capacitor switching by contactors results in transients These transients may interfere with operation of modern relays, control & automation equipment
For ex: digital relays, PLCs etc. can malfunction

Thyristor switching is a must for eliminating switching transients Hence, dynamic compensation

DG SET PERFORMANCE & FUEL CONSUMPTION


Use of dynamic compensation systems can
Stabilize DG set output voltage. Reduce DG set rating for a given load. Enable better % loading of the DG set. Reduce fuel consumption. Enhance life of DG set.

APPLICATIONS - I
Industrial networks
Automobile & automobile component Mfrg. Plants Metal working
Fabrication & press shops Rolling mills Forging

Plastic extrusion & Moulding. Mining


Extraction Polishing, Crushing etc.

APPLICATIONS - II
Industrial networks
Paper, wood & particle board Mfrg. plants Plants with CNC machines

Other networks with sensitive loads


Hospitals IT parks Intelligent buildings

DYNAMIC COMPENSATION SYSTEMS


Open loop systems
Suitable for dedicated loads. Fastest Response. (< 15 msec) Unique EPS logic. External signal from load can be used for switching on. On time - externally settable. Integrated protection for
Wrong phase sequence. Phase fall out. Over temperature.

DYNAMIC COMPENSATION SYSTEMS


Closed loop systems
For groups of diverse loads. Use advanced programmable controller. Fast Response. (< 60 msec) EPS logic Desired PF & specified harmonic distortion values are settable. Integrated protection for
Wrong phase sequence. Phase fall out. Over temperature. Harmonic over load.

DYNAMIC COMPENSATION SYSTEMS


Open & closed loop systems
The system consists of
Ergonomic metal enclosure. Incoming switchgear & protection. Modern Copper Busbar System. (upto 80 kA short circuit withstand capacity) Power capacitors. Harmonic Reactors. (if required) Thyristor modules
Firing circuits Electronic control modules Protection fuses

By-pass contactors.

THYRISTORISED SWITCHED APFC


Conventional power factor correction systems using contactors as switching devices cannot be used in sufficient speed of response to meet the reactive power demand imposed by such loads.

It is necessary to use a dynamic power factor correction system in which the switching and controlling devices used have a response time in milliseconds.

DYNAMIC COMPENSATION SYSTEMS : Advantage - I


LOSSES & TEMPRATURE RISE
Thyristor Loss = 2 x In watts
Ex: 3 Phase, 440 V, 50 Hz. 50 kVAr capacitor has In = 65 A.
watt loss/thyristor module= 130 watts. for three phase switching two thyristor modules are required. total watt loss = 260 watts. unit watt loss = 5.2 watts/kVAr. Generally therefore cooling fans are required for each thyristor step. Energy consumption is very high.

INTELLVAr - D : No cooling fans for each Thyristor step.

DYNAMIC COMPENSATION SYSTEMS : Advantage - II


THYRISTOR RELIABILITY
Use of bypass contactors reduces
Operating losses. Utilization time of Thyristors. PIV of Thyristors used = 1800 Volts. In a 415 V, 50 Hz. system
peak to peak voltage = 1174 V Therefore Safety factor > 150% in Voltage

Lower utilization time + high PIV results in enhanced Thyristor reliability.

DYNAMIC COMPENSATION SYSTEMS : Advantage - III


SWITCHING LOGIC
ZERO CROSSOVER SWITCHING DESIGNS
Due to various factors exact zero crossover is not consistently achievable in practice. consequently use of [di/dt] limiting inductors/coils is common in zero crossover switching designs.

EQUI-POTENTIAL SWITCHING - EPS LOGIC


Enables continuous sensing of capacitor & line potential. Switching is done at equi-potential instant. This reduces the [di/dt] to very safe values. Hence no current limiting devices are needed.

EPS LOGIC THUS INCREASES RELIABILITY

Session 12
Power factor improvement of DG sets

Capacitors with Generators

Diesel generator set


G

Prime mover

Alternator

100 KVA 0.8 P.F. 80 kW

Connected load P.F. is 0.6


Case 1 100 kVA Shortfall of P.F. 0.6 20 kW 60 kW

100 kVA P.F. 0.8 80 kW

Case 2

P.F. 0.6 80 kW kVA 133.33

Alternator overloaded by 33.33 %

Load P.F. improved up to 0.98

100 kVA P.F. 0.8 80 kW

100 kVA P.F.0.98 98 kW

Prime mover overloaded

DG Set fundamentals
As load kW (Output) increases, input power from prime mover has to be increased. Diesel engines can be overloaded by 10 %, for half an hour, within a span of 12 hours. Prime movers are matched with alternator to operate at specific P.F. Lagging P.F. weakens the flux which links with alternator stator and leading P.F. strengthens it.

DG Set fundamentals
At low lagging P.F, it is not possible to reach the nominal operating voltage of the alternator, even at low load. With leading P.F, even with low excitation, there could be rise in voltage, causing damages to the connected equipment. At leading P.F. generator becomes unstable. If generator is operated with purely capacitive load voltage increases by 33.33 %

Selection of DG set rating


Connected load and demand factor.

Short duration peak loads like starting of induction motors. Allowance for extra kVA for harmonic generating loads. Allowance for accommodating future additional loads. Hence DG sets are always oversized for a given application and operate at relatively lower percentage loading.

Loading verses Yield curve

Operating at lower % of loading , result in poor yield from DG set.

How to improve % loading in DG


Do not exceed the current rating of Alternator. Do not exceed the BHP/kW rating of the prime mover (Engine). Golden Rules for safe DG set operation : Load the Alternator by Amperes. Load the diesel engine by BHP/kW.

Improve % loading by operating at higher power factor Higher PF reduces current output from DG at a given load. Loads can now be added without violating the Golden Rules. Operating at highest feasible PF, enables higher loading, resulting in better yield from DG set.

PF CORRECTION IN INSTALLATION WITH CAPTIVE GENERATION BY DG SETS


The DG set consists of a diesel engine, which is mechanically coupled to an alternator. The engine supplies the mechanical energy to the alternator and the alternator supplies the electrical energy to the load. The alternator is subjected to certain copper losses, which is proportional to the square of the current delivered by it. The diesel engine has to supply these losses in addition to supplying the load requirements. Thus by reducing the losses in the alternator the diesel consumption of the diesel engine can be brought down.

ALTERNATOR LOSS REDUCTION BY P.F IMPROVEMENT


Reducing the current output from alternator without altering the loading conditions can reduce the alternator losses. Improving the power factor at the output of the alternator can conveniently do this. Hence, improvement in the Power Factor in alternator leads to reduction of fuel consumption in DG sets. DG sets operate at a relatively low power factor of 0.6 to 0.8. Conventionally capacitors are not used along with DG sets.

Effect of PF improvement
OUTPUT CURRENT FROM DG WITH /WITHOUT COMPENSATION 600 500 CURRENT IN AMPS 400 300 200 100 0 1 2 3 4 5 6 7 8 9 10 WITH COMPENSATION

WITHOUT COMPENSATION

TIME IN SECONDS

Alternator loss reduction due to P.F improvement


The following example gives an approximate calculation to show the impact of power factor improvement on reduction of alternator losses and accrued savings in Diesel consumption. Consider a 3 phase, 415V, 50Hz, 500 kVA DG set used in an industry for 6000 hours/year with an average load of approximately 250kW at 0.65 PF. What is the fuel saving if PF is improved to 0.93? The full load copper loss of the alternator is 12kW and average yield of the DG set is 3kWh/litre of fuel (HSD).

Alternator loss reduction by P.F. improvement


Rated Current of Alternator Current at 0.65 PF = 500000/(3 x 415) = 695.60 A = 250000/ 3 x 415 x 0.65 = 535.08 A Copper loss at this current = (535.08)/695.6)2x12kW = 7.1 kW Current at 0.93pf = 250000/ 3 x 415 x 0.93 = 373.98A Copper loss at this current Saving in Copper loss = (373.98/695.6)2x12kW = 3.47kW = 7.1 3.47 kW = 3.63 kW

Alternator loss reduction by P.F. improvement

Energy saved for 6000 hour Generation DG set Yield


Potential savings in HSD fuel

= 3.63 x 6000 kWh = 21780 kWh = 3 kWh / liter of HSD


= 21780/3

= 7260 liters per year Potential savings in Rs @ Rs. 35/liter = 2,54,100 per year

Method of P.F. improvement Conventional fixed capacitors, should not be used with DG sets. This is because, by using fixed capacitors, there is a danger that the PF can become leading under lightly loaded condition, which is highly undesirable in DG set operation. Hence only Automatic Power factor Correction system (APFC) should be used with DG sets. The target power factor can be set to 0.93 to 0.95 for optimum performance.

APFC Selection
The appropriate APFC system can be selected based upon the harmonic content of the load. If the harmonic generating load is less than 20%, the APFC should be used as mentioned in section-8. If the Harmonic load is greater than 20% then reactor protected APFC should be used as mentioned in section 9.5 The rating of the APFC has to be selected depending upon the kW of the load connected and the minimum power factor in the installation.

F I G .3 - B L O C K D I A G R A M O F C O N T A C T O R S W I T C H E D A P F C S Y S T E M
G

C T ..../ 5 A V a r ia b l e L o a d s

F .S .U

F 1 ......F

Pow er F a c to r C o n tr o lle r

K 1 .....K

C 1......C

C 1......C n K 1 ......K n F 1......F n f2 F .S .U G CT

= = = = = = =

N o . o f C a p a c it o r S te p s N o . o f C a p a c it o r S te p C o n ta c to r s C a p a c i to r S t e p P r o te c tio n F u s e s C o n tr o l F u s e s F u s e S w itc h U n it ( O p tio n a l) D i e s e l G e n e r a to r M a in S u p p l y C u r r e n t T r a n s f o r m e r

FIG 5. BLOCK DIAGRAM OF DYNAMIC COMPENSATION SYSTEM IN CLOSED LOOP


G

CT

Variable Load
F.S.U

Reactive Power Controller

f2 F1 F2 Fn

Thy 1

Thy 2

Thy n

S1

Sn

= No. of Steps S 1......S n Thy 1......Thy n = Thyristor Switches = Capacitor Step Protection Fuses F1......F n = Control Fuses f2 = Fuse Switch Unit (Optional) F.S.U = Diesel Generator G CT = Main Supply Current Transformer

Conclusions
The efficiency of the DG set is maximum at UPF. The yield of the DG set is maximum at its peak loading. By proper use of reactive power management the efficiency of DG set can be improved. The loads can be transferred so as to optimize the loading of DG for better yield output. The output voltage of DG set can be stabilized under rapidly fluctuating loads by use of Dynamic compensation systems Saving in fuel is possible resulting in economic benefit to user.

Session 13
Harmonics & Effect of Adding Capacitors in the System

POWER FACTOR CORRECTION IN HARMONIC RICH ENVIRONMENT A harmonic rich environment is said to exist when the percentage of non linear loads in an installation becomes greater than 20% of transformer rating. Power factor correction by the use of capacitors, in such an environment, must therefore be carried out with certain precaution. This is due to the fact that parallel resonance conditions can occur, I.e. the magnitude of the Capacitive reactance of capacitors installed and the inductive reactance of the network can tend to be come equal. If such resonance occurs near to a frequency which is present in the network, current amplification takes place.

POWER FACTOR CORRECTION IN HARMONIC RICH ENVIRONMENT

lh

XC

XL

POWER FACTOR CORRECTION IN HARMONIC RICH ENVIRONMENT This current amplification can lead to overloading of capacitors and an increase of the voltage distortion in the network. Capacitors drawing higher current i.e. more than the rated current at normal operating voltages is a typical indication of presence of harmonics. While it is possible to design the capacitors to withstand the overload conditions, the increase in distortion will cause other ill effects such as : Capacitors installed being subjected to severe harmonic overloading, leading to premature failure

POWER FACTOR CORRECTION IN HARMONIC RICH ENVIRONMENT

Total harmonic distortion in the network increasing beyond the permissible levels, which is harmful to various equipments within the installation. The use of capacitors in the conventional manner is therefore not recommended in such situations.

Technical problems experienced in industry

Case 1
Type of industry - paperboard Manufacturing industry. Brief description of installation. Primary power source = grid supply at 33kv. Distribution voltage = 440V. Load details: The total induction motor load was 800HP.

Case 1
There were no non-linear loads installed in this plant. 300kvar, 3ph, 440V MPP-H capacitor banks were installed for power factor correction. Some capacitors were connected across the motor terminals and remaining used as central compensation.

Problem experienced:
Frequent failure of capacitors.

Case 1- Analysis
The system voltage was around 435 440V. The capacitors installed were subjected to severe and intermittent overload. For ex:- A 25 kVAr, 440V capacitor was drawing a current of 90 - 120A for certain periods of time. Compared to its rated current of 33 amps, the capacitors were subjected to an overload greater than 250%. This abnormal overloading resulted in frequent capacitor failure.

Case 1- Analysis
Following observations were made on the 33kV grid : Only two industries were found to be connected to 33kV line, one of them being the paperboard manufacturing industry and the other was a steel rolling mill. The length of the 33 kV transmission line between the two plants was approximately10kms. The steel rolling mill had installed a high frequency induction furnace.

Case 1- Analysis
It was observed that, whenever the high frequency induction furnace installed in steel rolling mill was operated, the harmonic distortion on the grid abnormally increased and during this period the capacitors were getting severely over loaded.

Case 1- Conclusion
Thus the use of conventional capacitors in the network, where the harmonic voltage distortion at the grid was abnormally high resulted in the following: Over loading of capacitors due to series resonance. Frequent failure of capacitor banks Increased harmonic distortion at the LV bus Inability of the customer to maintain the desired power factor. Financial losses incurred by customer.

Case 2
Type of industry Cement industry Brief description of installation. Primary power source = grid at 220kV. Distribution voltage = 6.6kv and 440V. The LV power factor correction is done as follows: At 440V bus, around 2000 kVAr APFC panels with conventional capacitors were installed.The APFC panels were distributed on several 6.6/0.440 kV distribution transformers installed in the plant.

Case 2
Problem experienced at LV bus: Malfunction of 350kW, 440V DC drive used for kiln motor installed at cement plant substation, when capacitors are connected in the network.

Case 2: Analysis
The cement plant sub station was fed by a 1600kVA, 6.6/0.440 kV transformer. The 350kW, 440V DC drive, was connected to this transformer, consequently the % non-linear load exceeded 22%. A 475kVAr, 440V APFC panel with conventional capacitors, was also connected to this transformer for power factor correction. Other linear loads such as compressors, pumps etc were also connected to this transformer. Malfunctioning of the DC drive was co-related to a situation when specific combination of capacitor steps in the APFC were ON.

Case 2: Conclusion
The use of conventional capacitor in harmonic rich environment led to high total harmonic distortion on the LV bus. As the same distorted sine wave is applied to the 350kW DC drive, sensitive electronic devices used in this drive were mal-functioning.

Case 3
Type of industry Steel rolling mill. Brief description on installation. Primary power source = grid at 33kV. Distribution voltage = 440V. The plant was installed with 2 x 2000 kVA + 1 x 1000 kVA, 33/0.440 kV distribution transformers. At the secondary of one of the 2MVA transformer following loads were connected: 1000HP AC induction motor. 500HP DC drive.

Case 3
Around 900 kVAr of conventional capacitors were connected to this transformer for power factor improvement as shown in the fig.

Case 3
33kV supply from Grid.

2000kVA, 33/0.44 kV Trafo.

Feeder for other 2000kVA Trafo.

Feeder for 1000kVA Trafo. 440V bus

M 1000HP Induction Motor

500HP DC Drive

900kVAr Capacitor

Case 3
Problem experienced: Frequent failure of capacitors installed for power factor correction.

Case 3- Analysis
A team of engineers from MEHER made an analysis at the site. The result of the analysis is as follows: The capacitors installed were drawing more than its rated current. A 50 kVAr, 440V capacitor was drawing a current of 200A against the rated value of 65amps, thus constituting an overload greater than 300%. This abnormal over load resulted in frequent capacitor failure. The total harmonic voltage distortion at the secondary of this 2000 kVA transformer with all the capacitors switched on was more than 25%. This value is higher than acceptable levels.

Case 3- Conclusion
Thus the use of conventional capacitor in harmonic rich environment resulted in: Over loading of capacitors due to parallel resonance. Increased harmonic distortion at the LV bus. Frequent failure of capacitor banks. Inability of the customer to maintain the desired power factor. Financial losses incurred by customer.

What Are Harmonics ?


Distorted sine wave cause harmonics. Distorted current wave cause current harmonics. Distorted voltage wave cause voltage harmonics. Fourier expansion result in integral multiples of fundamental frequency components. Nth order harmonics is of n.Fs frequency. Generally odd harmonics are prevalent because of half wave symmetry.

How Harmonics Are Generated ?


Non-linear loads generate current harmonics. Harmonic currents flow largely through capacitors. Harmonic currents also flows through network. The flow of harmonic currents cause voltage harmonics. Harmonics are thus injected to other linear loads connected in the same bus. Harmonics injected into the network flow towards other users connected to the network.

What Loads Generate Harmonics


Equipment using switched mode power supply - Television - Computers, other IT loads Equipment using power electronic devices - AC & DC drives - Frequency converters - Rectifiers - Arc & induction furnaces - UPS - Compact fluorescent & other discharge lamps

Sources of Harmonics
Following are some of the non-linear loads which generates harmonics: Static Power Converters and Rectifiers, which are used in UPS, Battery chargers, etc. Arc furnaces. Power Electronics for motor controls (AC/DC Drives) Computers. Television receivers Saturated Transformers Fluorescent Lighting with electronic ballast. Telecommunication equipment.

Type of Harmonics
Characteristic harmonics
- Related to circuit configuration. - Fairly predictable frequency spectrum. - Frequency spectrum given by k*p+1 ; k = 1,2,3. - For ex. 5&7 for 6 pulse, 11 & 13 for 12 pulse. - Magnitude inversely proportional to order.

Non-characteristic harmonics
- Caused by frequency converters. - System imbalance (voltage & impedance)

Triplen harmonics
- 3.(2n+1) order n = 0,1,2 i.E 3,9,15,21.. Etc. - Zero sequence in nature. - Accumulates as neutral current.

Harmonic Order & Phase Sequence


Each harmonic order has a particular phase sequence relationship with respect to fundamental. By convention the fundamental is assumed to have positive phase sequence. All higher order harmonics have either positive,negative or zero phase sequence with respect to fundamental.

How to Determine the Phase Sequence of Each Harmonics ?


R

Phase Sequence of RYB (+ Seq.) For Fundamental Component R Fundamental +120o Second Harmonic +240o -120o Y 0o 0o 0o B -120o -240o +120o

Positive Sequence
Y

B B

Negative Sequence
Y

Thus Second Harmonic Behaves As a Negative Sequence Component.


R

How to determine the phase sequence of each harmonics ?


Fundamental Third Harmonic Fundamental
R

R Y +1200 00

B -1200

+3600 00

00 -3600 00 00 Third Harmonics


Zero Sequence
R Y B

Positive Sequence
Y

Thus third harmonic behaves as a zero sequence component.

Accumulation of 3rd harmonic current in the neutral


Three phase system

Wave forms of balanced three phase fundamental currents.


Time.
R - phase.

R-Phase current with its third harmonic component.


Time.
Y - phase.

Y-Phase current with its third harmonic component.


Time.
B - phase.

B-Phase current with its third harmonic component.


Time. Addition of third harmonics in Neutral conductor

Time.

Third harmonic currents of R,Y&B phases are in phase with each other and hence adds up, without cancellation in the neutral conductor.

How to Determine the Phase Sequence of Harmonics ?


Harmonic order Phase Sequence

1 +

2 -

3 0

4 +

5 -

6 0

7 +

8 -

9 0

Positive Sequence Fundamental 4th Harmonic 7th Harmonic 10th Harmonic 3n+1 Div. by 3 Rem. 1

Negative Sequence 2nd Harmonic 5th Harmonic 8th Harmonic 11th Harmonic 3n+2 Div. by 3 Rem. 2

Zero Sequence 3rd Harmonic 6th Harmonic 9th Harmonic 12th Harmonic 3n+3 Divisible by 3

Characteristics of Harmonics
Positive Sequence
Causes over heating due to Skin effect Aids the fundamental Moderate heating Relatively less harmful

Negative Sequence
Causes over heating due to Skin effect Opposes the fundamental Excessive heating Most harmful

Zero Sequence
Causes over heating due to Skin effect Accumulates in the neutral Creates hot neutral Responsible for neutral to earth voltage and open neutral condition.

Skin effect
Cross-section of current carrying conductor

DC current flow

Low frequency AC current flow

High frequency AC current flow

The effective area of the conductor, available for current flow, reduces as the frequency of the AC current increases. Hence, the resistance of the conductor increases, at higher frequencies, as it is inversely proportional to its area of cross-section.

R =

L A

Skin effect explanation


Magnified view of current carrying conductor
Enhanced impedance due to high mutual inductance. Hence least current flow. Moderate impedance due to medium mutual inductance. Hence moderate current flow. Least impedance due to low mutual inductance. Hence max. current flow.

Effect of Harmonics
Type of equipment Rotating machines Effect of harmonics Increased losses, over heating due to skin effect. Pulsating torque Over heating, increased power consumption Mal-operation, nuisance tripping Mal-operation, failure Erratic operation High currents & failure due to overload

Transformer, switch-gear, power cables Protective relays Power electronics Control & automation Power capacitors

Effect of Harmonics on Protective Relays


Mal-operation
Nuisance tripping

Trip level set lower than the fundamental value. The relay should trip as the fundamental value is higher than the trip level. But the presence of harmonics has reduced the peak value. Hence the protective relay will not trip.

Trip level set higher than the fundamental value. The relay should not trip as the fundamental value is lower than the trip level. But the presence of harmonics has increased the peak value. Hence the protective relay will trip.

Circuit configuration of six pulse drive

Current spectrum of six pulse drive for star-star & star-delta configuration

Twelve pulse drive configuration

Current spectrum of twelve pulse drive

How Capacitors & Harmonics Are Related -1


Network behaviour without capacitors Network do not reveal harmonics. Most of the harmonic currents internal to network go to the grid. No resonance at harmonic frequencies. Network power factor is unacceptably low.

Network Without Capacitors


GRID

Harmonic currents flow towards Grid. Min. Import of Harmonics from Grid. No Resonance at harmonic frequencies.

BUS
Non Linear Load

Hence least Harmonic Problem. Power Factor Very Low.

How Capacitors & Harmonics Are Related -2


Network behaviour with capacitors Network start revealing harmonics Internally generated harmonic currents may amplify due to parallel resonance Externally generated harmonics enter capacitors due to series resonance May increase harmonic distortions. Capacitors draw excessive currents & fail Network power factor improves

Network With Capacitors


GRID ZN ZT BUS

Harmonic currents flow towards Capacitors , due to parallel resonance with load ZL Import of Harmonics from Grid towards Capacitors , due to series resonance with network & transformer impedances ZN &ZT Increase of THD(V) in the Bus Harmonic overloading of Capacitors, leading to its failure Improvement in Power Factor With Harmonic overload

M
Non Linear Load

Equivalent Load Impedance ZL

Session 14
Harmonic Filters

Harmonic Mitigation Concept


Fire Triangle Harmonic Triangle

How to Improve Power Factor Without Causing Harmonic Problem ?


Conventional capacitors should not be used.

Capacitors should be replaced by harmonic suppression filters (series combination of suitable series reactor & capacitors) so that,
It offers capacitive reactance at fundamental frequency for necessary power factor correction. It offers inductive reactance at all higher order dominant harmonic frequencies to avoid resonance. Its self series resonance frequency fR do not coincide with predominant harmonics.

Network With Harmonic Filters


GRID ZN ZT BUS L

No resonance at harmonic frequencies as filter is inductive at such frequencies Harmonic currents flow towards Grid , as it offers least impedance compared to filter

M
Non Linear Load

Predominantly fundamental current flows through Capacitors Moderate THD(V) in the Bus No harmonic overloading of Capacitors Improvement in Power Factor without Harmonic overload

Equivalent Load Impedance ZL

Harmonic Filter
Harmonic filter comprises of a reactor (L) in series with a capacitor (C) Such a filter has a unique self series resonance frequency fR at which inductive reactance of reactor equals capacitive reactance of capacitor. Fr = 1/(2LC) Below fR the filter is capacitive Above fR the filter is inductive

Characteristics of Harmonic Filter


Capacitive
Impedance

Inductive

fR= Resonant

Frequency

f < fR - Capacitive f > fR - Inductive


Harmonic filters are classified based upon how close fR is to a Harmonic frequency

fR

Frequency

Classification of Harmonic Filters


Detuned or harmonic suppression filters
Resonance frequency fR< 90% of lowest dominant harmonic frequency.

Tuned or harmonic absorption filters


Resonance frequency fR within 10% of the frequency of the harmonic to be absorbed.

Classification of Harmonic Filters


Harmonic Filters

Passive Harmonic Filters

Active Harmonic Filters

Hybrid Harmonic Filters

Detuned Filters

Tuned Filters

3 3wire 3 4wire Single Phase

7%

14 %

Selection Criteria for Harmonic Filters


Detuned filters
Power factor correction is of paramount importance. If ordinary capacitors draw > 130% of its rated current. Reduction of THD(V) not relevant. To prevent capacitors from harmonic overload Harmonic study not required for installing standard detuned filters.

Selection Criteria for Harmonic Filters


Tuned filters
Power factor correction & reduction of THD(V) are of paramount importance. Ordinary capacitors draw > 130% of its rated current. Harmonic study required for installing tuned filters. Specifically designed for each location. More bulky, since it carries large amount of harmonic currents. Hence expensive.

Standard Detuned Filters-1


Standard detuned filters have a fixed percentage tuning factor p Percentage tuning factor is defined as Reactor reactance at system frequency p = Capacitor reactance at system frequency X 100 % Standard detuned filters are available for 7% tuning factor The resonant frequency of the filter fR is related to tuning factor p by Fr = Fs/ (p/100) = 189 Hz for 7% filter

Standard Detuned Filters-2


Standard 7% detuned filters are suitable for use in majority of installations where the dominant harmonics are higher than 189 Hz like 5th and higher. 7% detuned filters should not be used in installations where predominant 3rd harmonics are present like IT based industries. For IT based industries 14% detuned filters (fR=134 Hz) should be used.

Design Features of Detuned Filter


Detuned filter consists of matched pair of specially designed reactor and capacitor. Detuned filter is designed to provide the rated kVAr at the rated voltage at the bus. The reactor capacitor combination is designed for the rated tuning factor. Standard detuned filters are available for 7% tuning factor rated for 12.5, 25, 50, 75 & 100 kVAr at 440 volts.

Design Features of Detuned Filter


Reactor features. Reactors are specially designed to carry wide spectrum of harmonic and fundamental currents without saturating. They are rated for operation up to 160C through use of class F insulation. Over load thermal cut off provided to protect the reactor.

Design Features of Detuned Filter


Capacitor features Capacitor is specially designed to carry wide spectrum of harmonic and fundamental currents without overloading. It is designed for higher voltage to allow for increased voltage due to introduction of series reactor. The kVAr of the capacitor is suitably designed to deliver the rated kVAr of the filter at the bus.

Calculation to Estimate the Rated Voltage of the Filter Capacitor


I V C L XL= (p/100) XC XC

I = V/ Xeq = V/ (XC (1-p/100))


Voltage across Capacitor VC is given by

VC = I XC = V/ (1-p/100)
Allowing 10% for over voltage, the rated voltage of the capacitor is given by

1.1 VC = 1.1 V/ (1-p/100)


Bus Voltage Percentage Tuning Factor Voltage Rating of Capacitor Voltage Rating Rounded off

415 415

7% 14%

490.86 530.81

500 V 550 V

Note on Capacitor for Detuned Filter Application


It is seen that the voltage rating of the capacitor has to be higher than the system voltage. Hence normal capacitor of 415/440 volts rating should never be used in series with reactor. Any such attempt would be hazardous to the capacitor and the installation.

Analysis of Detuned Filters

CY

CY

Actual connection of Detuned Filter

SLD Representation Star equivalent of Detuned Filter of Detuned Filter

Analysis of Detuned Filters


Analysis of Detuned Filter can be done by analysing its single line diagram representation as shown IL L XL Let the net available kVAr. at Bus = N C Let the System Line Voltage in Volts = V V/ 3 Let the Tuning Factor in % =p XCY Line current of the Filter IL= V/3/(XC - XL) = V/3/XC/(1-p/100) C The 3 phase kVAr. At Bus = 3V IL/1000 i.e NC = V2/ XC/(1-p/100)/1000 The XCY of the star eq. Capacitor = V2/ (NC/1000/(1-p/100)) The XL of the Reactor = XCY p/100 = V2/(NC/1000/(100/p-1)) The kVAr of the Capacitor at its rated voltage VC and the inductance of the reactor can be computed from the above.

Analysis of Detuned Filters


kVAr. of the Capacitor at its rated voltage VC = (VC/V)2 NC (1-p/100) IL L Inductance per phase of the 3 phase Reactor in mH. XL L = V2/N /(100/p-1)/100/ C V/ 3 From these formulae we can calculate the Detuned C XC Filter elements for standard outputs as under. For 7%, 440 Volts Detuned Filters
Available Inductance per Rated Voltage of kVAr.of the Bus kVAr. Phase in mH. the Capacitor VC Capacitor at VC 12.5 25 50 75 100 3.71 1.855 0.928 0.618 0.464 500 500 500 500 500 15.01 30.02 60.05 90.07 120.09

Section 15 Exercise

Parallel Resonance

Description of the Problem


A 500kVA, 415V, 3 phase, 50Hz., 4% impedance drop transformer is feeding a 100kW, 6pulse DC drive. The PF of the DC drive under full load condition is 0.7 lag. Calculate the following :A) Calculate the harmonic current spectrum of 100kW DC drive. B) Calculate the kVAr required to improve the PF of the drive above 0.99 lag. C) Calculate the harmonic voltage distortion and harmonic overload with the following :1) Without any capacitors. 2) With conventional capacitor connected to the network. 3) With de-tuned filter connected to the network.

Harmonic Spectrum
Harmonic spectrum of 100kW, 6 pulse, 0.7 PF DC drive is given by the relation: Ih =i1/h, where h is the harmonic order. Since the drive is 6 pulse, h = 5,7,11,13,17,19. I1 = = 100x1000 / (3 x 415 x 0.7) 200 A (Approx.).

Harmonic Spectrum
h 5 7 11 13 17 19 Ih Amps 40 28.6 18.2 15.4 11.8 10.5

Estimation of kVAr
kVAr required to improve the PF above 0.99 lag. kVAr =kW x (tan (cos-1 (PF1)) - tan (cos-1 (PF2)) =100 x (tan (cos-1 (0.7)) - tan (cos-1 (0.99)) =87.8 kVAr. kVAr =100 kVAr. (standard available)

Network Without Capacitors:


500 kVA

100 kW, 3ph,415V, DC drive

Linear resistive Loads

Network Without Capacitors Equivalent Circuit

XT

Ih

Calculation of Transformer Impedance Xt


We use the following formula. % Z = Transformer Impedance / Base Imp. Base Imp.= Phase voltage / Full load current. Xt = % Z* Phase voltage / Full load current. = 0.04* 415/3/(500*1000/(415*3 )) ohm. = 0.013778 ohm.

Harmonic Simulation Without Capacitors


h 5 7 11 13 17 19 Ih 40 28.6 18.2 15.4 11.8 10.5 Xth = Xt*h 0.0689 0.0964 0.1516 0.1791 0.2342 0.2618 Vh = 3*Ih*Xtotal 4.7728 4.7728 4.7728 4.7728 4.7728 4.7728

Total Harmonic Voltage Distortion % Without Capacitors


Total harmonic voltage distortion THDV% = ((V52+V72+V112+V132+V172+V192) / V1) x 100
= ((4.772+4.772+4.772+4.772+4.772+4.772)/415)*100

THDV% = (11.69/415)*100 THDV% = 2.82%

Network With Capacitors:


Calculation of harmonic voltage distortion and harmonic overload: With conventional capacitor of rating 100 kVAr. Capacitive reactance Xc= V2/ (kVAr x 1000) ohms. = 4152 / (100 x 1000). Xc = 1.72225 ohms. Transformer reactance. Xt = V2 x (%Z / 100 ) / (kVA x 1000) ohms = 4152 x (4 / 100) / (500 x 1000). Xt = 0.013778 ohms.

Network With Capacitors


500 kVA

100 kW, 3ph,415V, DC drive

Linear resistive Loads

100 kVAr, 3ph,415V

Network With Capacitors: Equivalent Circuit

Ih

Xt

XC

Harmonic Simulation With Capacitors


h
5 7 11 13 17 19

Ih
40.0 28.6 18.2 15.4 11.8 10.5

Xth=Xt*h Xch=Xc/h

|Xtotal| = Xth*Xch |(Xth-Xch)|

Vh = 3*Ih*Xtotal

Ic = Vh/(3* Xch)

0.0689 0.0964 0.1516 0.1791 0.2342 0.2618

0.3445 0.2460 0.1566 0.1325 0.1013 0.0906

0.08611 5.9659 0.15863 7.8501 4.73619 149.151 0.50885 13.5593 0.17853 3.6379 0.13866 2.5281

10.00 18.42 549.89 59.08 20.73 16.11

Overloading of Capacitors
Ich = 554 Amps. Ic1 =139 Amps. Iceff=571 Amps. Overload = 411 %

THDV% With Capacitors


THDV% = ((V52+V72+V112+V132+V172+V192) / V1) x 100 =((5.972+7.852+149.152+13.562+3.642+2.532)/415)*100 = (150.16)/415*100

= 36.18%

Calculation With Detuned Filters


500 kVA

XLF 100 kW, 3ph,415V, DC drive

Linear resistive Loads

112.5 kVAr, 3ph,440V,DF

Why 112.5 kVAr


The detuned filters, supplied by L&T/Meher are rated for a bus voltage of 440V. This is mainly done to provide a standardized solution. The kVAr output of a 440V capacitor is reduced if connected to a 415 volts system, given by the relation. = (Vsystem/Vrated)2 * kVAr. = (415/440)2 * 100 kVAr. = 88.9 kVAr. Hence while suggesting a detuned filter for a 415 V system, additional kVAr has to be provided so as to provide the required 100 kVAr at system voltage. .

Why 112.5 kVAr


Hence if the 100 kVAr capacitors have to be supplemented by detuned filter, the detuned filter should be rated for 112.5 kVAr, calculated by the relation = (Vrated/Vsystem)2 * kVAr = (440/415)2 * kVAr = 1.124 * 100 = 112.5 kVAr. (approx.)

Network With Detuned Filters: Equivalent Circuit

Ih

Xt

XLF

XCF

Detuned Filter of 112.5 kVAr, 440V


Capacitive kVAr = = = = XC = XCF = 112.5 * (1 p/100) 112.5* (1-7/100) 112.5 *0.93 104.625 kVAr 4402 / (104.625 x 1000) 1.8504 ohms.

Reactance of reactor XLF = p/100* Xc = 0.07*1.8504 = 0.129528 ohm.

Harmonic Simulation
Transformer reactance. Xt = = Xt = V2 x (%Z / 100 ) / (kVA x 1000) ohms. 4152 x (4 / 100) / (500 x 1000). 0.013778 ohms.

Harmonic Simulation With Detuned Filter


h
5 7 11 13 17 19

Ih
40 28.6 18.2 15.4 11.8 10.5

Xth = Xt*h

XLFH = XLF*h

XCFH = XCF/h

XFilter = XLFH XCFH

Xtotal = Xfilter*Xth
( XFilter+Xth)

Vh = 3*Ih* Xtotal

Ic= Vh/ (3*XFilter)

0.0689 0.6476 0.3701 0.2776 0.0552 3.8238 0.0964 0.9067 0.2643 0.6424 0.0839 4.1498 0.1516 1.4248 0.1682 1.2566 0.1353 4.2591 0.1791 1.6839 0.1423 1.5415 0.1605 4.2760 0.2342 2.2020 0.1088 2.0931 0.2107 4.2925 0.2618 2.4610 0.0974 2.3636 0.2357 4.2969

7.95 3.73 1.96 1.60 1.18 1.05

Overloading of Detuned Filter


Ifh = 9.27 Amps.

If1 =139.12 Amps. Ifeff=139.43 Amps. Overload = Negligible.

THDV% With Detuned Filters


THDV% = ((V52+V72+V112+V132+V172+V192) / V1) x 100 = ((3.822 +4.152+4.262+4.282+4.292+4.302)/415)*100 THDV% = (10.25/415)*100

THDV% = 2.47%

Summary
It is seen that the introduction of capacitors into a network with non-linear loads not only leads to very high overloading of the capacitors but also increases the harmonic voltage distortion in the network due to parallel resonance. If the same capacitors are supplemented with detuned filters, the overloading is prevented and also the voltage distortion in the network is reduced to acceptable limits.

Conclusion

Detuned filter is a safe and proven solution to improve power factor in harmonic rich environment.

Limitations of Passive filters


Sensitive to system frequency change. Sensitive to change in network parameters. Has location limitation when Drives exist in system. Mixing of filters having different tuning factor generally not possible due to risk of resonance. Not immune from harmonic overloading. Generally cannot handle wide harmonic spectrum. kVAr. output of filter variable only in steps.

Session 15
Active Compensation

SCOPE
ACTIVE COMPENSATION NEED PRINCIPLE BENEFITS SOLUTIONS AHF - ACTIVE HARMONIC FILTER INTELLVAr - E Electronic VAr Compensation

Need for Active Compensation - I


In networks where HARMONIC FILTERING is to be done
Independent of PF Improvement

for complex harmonic frequencies for fine control of THD(V): <3%

Need for Active Compensation - II


for Unsymmetrical Reactive Power Compensation (PF improvement)
in REAL TIME MODE in STEPLESS MODE where INFINITE CONTROL is needed

for real time Voltage Support

Principle of Active Compensation


Involves real time CURRENT INJECTION into a network
in Variable AMPLITUDE & PHASE ANGLE in COMPLEX WAVE SHAPES with INFINITE CONTROL at any LOCATION (in shunt)

Active Compensation Benefits


Filtering upto the 50th HARMONIC including Inter-Harmonics Unsymmetrical Compensation of Reactive Power Real time response < 2 msec Independent of network characteristics, voltage & frequency behavior INFINITE CONTROL Compatibility with conventional compensation installations

Active Compensation - BENEFITS


Total PF Control No risk of Resonance

Voltage Stabilty

Extremely Flexible

THD (V) Control

Plug & Play Solution

SOLUTIONS - I
ACTIVE HARMONIC FILTERS - for 3 Phase, 415/440 V, 50 Hz. NETWORKS - In Current Ratings from 32 to 630 Amps - Optional Reactive Power Compensation

SOLUTIONS - II
INTELLVAr - E - Hybrid ELECTRONIC VAr COMPENSATION - for 3 Phase, 415/440 V, 50 Hz. NETWORKS - Output from 50 to 1000 kVAr

Active filter schematic diagram


Load Current with Harm onics

Sinusoidal Supply Current

Supply System

Compensating Current
Active Filter

+
(Time Domain)

+
(Frequency Domain)

Waveform of current without Active filter

Waveform of current with Active filter

Current harmonics without active filter

Current harmonics with active filter

Cost-Technology Pyramid of Harmonic Filters


Active filters Top end solution for wide spectrum of current harmonics & suitable for installations having sensitive equipment

Suitable for installations having high harmonic distortion (cement, sugar & steel plants, etc.)

Hybrid Filters

Tuned Filters

14% Detuned Filters Suitable for installations having 3rd harmonics and above (IT parks, corporate banks & establishments) 7% Detuned Filters Most common, Base end product suitable for majority of industries having 5th and above harmonics

You might also like