Packaged Cooling with

Electric Heat Rooftop Units


Voyager
3 through 25Tons - 60 HZ

May 2000

RT-PRC002-EN

Introduction

SM

VoyagerTM . . . One of the most


complete lines of packaged units
on the market today. Built to
provide not only ultimate indoor
comfort, but also comfort in knowing
that our packaged units are easy to
install and maintain.

Trane was the first to introduce the


Micro and has continued to improve its
performance. Together the Voyager
and the Micro provide the highest
standards in quality and reliability,
comfort, ease of service, and the
performance ofTrane light commercial
products.

Trane Quality and Reliability. . .


Building a superior packaged unit
means not only knowing what to put in
-- but also what to leave out. We
designed the Voyager unit leaving in
the tried and true components. We left
out those parts and components that
cause failures and require service.

To increase their ability to win jobs,


contractors want a unit that saves time
and money. Engineers want a unit that
meets their design criteria and covers
special applications. Voyager delivers
all of this and more!

American Standard Inc. 2000

RP-PRC002-EN

Contents

Introduction

Features and Benefits

Application Considerations

9
10
11

Selection Procedure
Model Number Description

General Data

12

Performance Data

Controls

20
20
35
54
56

Electric Power

57

Dimension and Weights

78

Mechanical Specifications

98

Cooling Performance
Fan Performance
Heat Performance

RP-PRC002-EN

Features and
Benefits

Compressors
Voyager contains the best
compressor technology available, in
order to achieve the highest
performance possible. Our
compressor line includesTrane built
Climatuff, Model H and 3-D
Scrolls, along with Copeland
Compressors.
Our Compressor designs are tested
inTranes SEET (System Extreme
EnvironmentalTest) facility inTyler,
Texas where five years of operation
are simulated in a sixteen week test.

The dual compressors in the 7-25

The Micro improves quality and


reliability through the use of timetested micro-processor controls and
logic. The Micro now:
prevents the unit from short cycling,
considerably improving compressor life.
ensures that the compressor will run
for a specific amount of time which
allows oil to return for better lubrication,
enhancing the reliability of the
compressor.

The Voyager with the Micro reduces


the number of components required to
operate the unit, thereby reducing
possibilities for component failure.

ton units provide system back-up.

Quality is improved in the Micro units


due to built-in reliability
enhancements. Features like time
delay relay and anti-short cycle timers
are built into the circuit board on all
Voyager Micro units.
Micro

For many yearsTrane has worked


with micro-processor controls in the
applied equipment markets. These
designs provided the technology for
Voyager with micro-processor
controls.

The Micro provides unit control for


heating, cooling and ventilating
utilizing input from sensors that
measure outdoor and indoor
temperature.

Weather Tight Top And Cabinet

Voyager units incorporate either a one


piece top or theTrane-Tite-Top (T3).
Each part of the top (either two or three
pieces) overlaps in such a way that
water cannot leak into the unit.These
overlapped edges are gasketed and
sealed to ensure superior water
integrity.

Quick-Sess (3-7 tons) and QuickAccess (8-25 tons) panels reduce the
number of possiblewater entry points.

For added water integrity, Voyager has


a raised 11/8" lip around the supply and
return of the downflow units to
prevent water blowing into the
ductwork, in the event water should
get into the unit.

Quality And Reliability Testing

The fan and

idler arm assembly


designs have been tested to over
300,000 cycles each. Our combined
cycle testing is now over 7,000,000
cycles.

All of Voyagers designs were


rigorously rain tested at the factory to
ensure water integrity.

Actual shipping tests are performed to


determine packaging requirements.
Units are test shipped around the
country to determine the best
packaging. Factory shake and drop
tests are used as part of the package
design process to help assure that the
unit will arrive at your job site in top
condition.

Rigging tests include lifting a unit into


the air and letting it drop one foot,
assuring that the lifting lugs and rails
hold up under stress.

All parts are inspected at the point of


final assembly. Substandard parts are
identified and rejected immediately.

We perform a 100% coil leak test at the


factory.The evaporator and condenser
coils are leak tested at 200 psig and
pressure tested to 450 psig.

Every unit receives a 100% unit run test


before leaving the production line to
make sure it lives up to rigorousTrane
requirements.

Our designs are tested at the


factory, not on the jobsite!

RT-PRC002-EN

Features and
Benefits

Ease Of Installation

Micro

Contractors look for lower installation


(jobsite) costs. Voyagers conversionless
units provide many time and money
saving features.

The function of the Micro replaces the


need for field installed anti-short-cycle
timer and time delay relays.The Micro
ensures that the controls are integral to
the unit.The contractor no longer has to
purchase these options and pay to have
them installed.

Conversionless Units
The dedicated design units are either
downflow or horizontal and require no
panel removal and alteration time to
convert in the field a major cost
savings during installation.
Horizontal units come complete with
duct flanges so the contractor doesnt
have to field fabricate them.These duct
flanges are a time and cost saver.
Improved Airflow
U-shaped airflow allows for improved
static capabilities.
Single Side Access
Access to all of Voyagers components is
accomplished through the Quick-Sess
and Quick-Access panels. No more than
three screws must be removed to
access components.

Easy Access Low Voltage Terminal Board


Voyagers low voltage terminal board
is external to the electrical control
cabinet. It is extremely easy to locate
and attach the thermostat wire.This is
another cost and time-saving
installation feature.
The wiring of the low voltage to the
unit and the zone sensors is as easy as
1-1, 2-2, and 3-3.
Tranes Idler Arm Assembly
Our idler pulley provides quickadjustment for belt or motor sheaves on
8 - 25 ton units. No longer does the
contractor have to adjust the motor to
tighten the belt or change the motor
sheave setting. A real time-saver in
servicing and installing.
Single Point Power
A single electrical connection powers
the unit.

RT-PRC002-EN

Features and
Benefits

Serviceability
Todays owners are more conscious of
the cost of service and maintenance.
Voyager was designed with input from
service contractors.Their information
helped us design a unit that would get
the serviceman off the job quicker and
save the owner money. Here is why
Voyager can save money in service.
Single-Side Service
Single-side service is standard on all
Voyager units.
Quick-Sess 3-7 ton and Quick-Access
Panels 8-25 Ton Units
Remove three or fewer screws for access
to the standardized internal components
and wiring.
Micro

The

Micro unit requires no special


tools to run the Voyager unit through its
paces. Simply place a jumper between
Test 1 andTest 2 on the Low Voltage
Terminal Board and the unit will walk
through its operational steps
automatically.

The unit automatically returns control to


the zone sensor after stepping through
the test mode a single time, even if the
jumper is left on the unit.

As long as the unit has power and the


LED is lit, the Micro is operational.The
light indicates that the Micro is
functioning properly.

One Zone Sensor option has central


control panel lights which indicate the
mode the unit is in and possible
diagnostic information (dirty filters for
example).
Voyagers Simpler Design

The Voyager design uses up to 42%


fewer parts than previous units. Since
it is simpler in design, it is easier to
diagnose.

The Micro units built-in diagnostics


help the serviceman to identify any
problem quickly.
Standardized Components

Components are placed in the same


location for all Voyager units.
Familiarize yourself with one Voyager
and you are familiar with all Voyager
units.

One single Micro board is used on all


Voyager Packaged Gas/Electrics,
Cooling with Electric Heat, and Heat
Pump models.This provides
standardization of parts for the
contractors. Less money is tied up in
inventory using the Micro.

Quick-Adjust Idler Arm


On all 8-25 ton units, the belt and
sheaves can be quickly adjusted without
moving the mounted fan motor.This is
done with our idler arm pulley.The
Quick-Adjust Idler Arm is a major savings
of time and money.

Contractors/owners can stock fewer


parts due to standardized components
throughout the Voyager product line.
Colored And Numbered Wiring
You save time and money tracing wires
and diagnosing the unit.

The Micro features expanded


diagnostic capabilities when utilized
withTranes Integrated ComfortTM
Systems.

Standardized
Components
Colored and
Numbered Wiring
Easy Access Low Voltage
Terminal Board
6

RT-PRC002-EN

Features and
Benefits
Voyager Helps Win Jobs And Engineer
Specifications
The Voyager units are built utilizing
important input from our consulting
engineers. Engineers want a unit that
performs to their rigorous standards in a
variety of applications. They want a unit
that lives up to their customers
expectations after giving their stamp of
approval. Here is how Voyager performs
to that standard.

Micro

Capacity Modulation

Flexible Applications

Voyager features dual compressors on


units 7 thru 25 tons. The dual
compressor models are outstanding for
humidity control, light load cooling
conditions and system back-up
applications.

Only five factory-built roof curbs for the

Trane
Communication
Interface

entire Voyager line. . .simplifies curb


selection.

Airflow is outstanding.The Voyager


can replace an older machine with old
ductwork and, in some cases, improve
the comfort through better air
distribution.

Factory Installed Options (FIOPs). .


wide variety of options available.
Micro

Some of the benefits of the Micro are


the built-in anti-short-cycle timer, the
time delay relay and the minimum
on time controls.These controls are
functions of the Micro and are factory
tested to assure proper operation.

RT-PRC002-EN

As an energy benefit, the Micro softens


electrical spikes by staging on fans,
compressors and heaters.

Another benefit is the Intelligent


Fallback or Adaptive Control.This is a
benefit to the occupant if a component
goes astray, the unit will continue to
operate at pre-determined temperature
set point.

Intelligent Anticipation is a standard


feature of the Micro. It occurs
constantly as the Micro and the zone
sensor work together in harmony to
provide tighter comfort control than
conventional electro-mechanical
thermostats.

Features and
Benefits

VariTrac

Central Control Panel

TIME
CLOCK

INPUT/
STATUS
PANEL

EDIT
TERMINAL

VariTrac

High Static Drive Accessory

One Of Our Finest Assets:

Tranes outstanding changeover VAV


System for light commercial
applications. When coupled with
Voyager, it provides the latest in
technological advances in comfort
management systems and can allow
thermostat control in every zone
served by VariTrac.

Available on some models, the high


static drive accessory allows for the
optimization of the standard motor.
Avoid expensive motors and operation
costs by installing this optimized sheave
accessory.

Trane Sales Representatives are a


Support group that can assist you with:

Trane Communication Interface or


TCI is available factory or field installed.
This module when applied with the
Micro easily interfaces withTranes
Integrated ComfortTM System.

Training

Factory built roof curbs are available


for the downflow units.
An assortment of zone sensors from
programmable to automatic and manual
are available.

Voyager has the features and benefits


that make it second to none. It was
designed with input from contractors
and engineers in the field.The U-shaped
airflow performance is outstanding.

The following options round-out the


complete line of Voyager accessories:

If all of your customers knew about


Voyager, all would insist on it.

0 - 25% manual outside air hood

Voyager 3 - 25 tons . . .

Motorized outside air for 6-25 ton

SIMPLY THE BEST VALUE!!!!

Low Ambient Cooling


All 3-25 ton units have cooling
capabilities down to 0 F as standard.
Power Exhaust Option
This option offered byTrane is
available on the 6-25 ton downflow
units. It provides exhaust of the
return air when using a downflow
economizer to maintain proper
building pressurization. Great for
relieving most building
overpressurization problems.
Downflow And Horizontal
Economizers

Product
Application
Service
Special Applications
Specifications
Computer Programs and much more

The economizers come with three


control options dry bulb is
standard, enthalpy and differential
enthalpy are field installed options.

RT-PRC002-EN

Application
Considerations

Application of this product should be


wivhin the cataloged airflow and
cooling considerations.The UPG
Computer Performance Program will
simulate product performance for a set
of given conditions. It is recommended
that the program be run for the worst
design scenario for a particular unit. For
more information on the UPG
Computer Product Performance
program contact your localTrane
Representative.
Low Ambient Cooling
This Voyager line features, as standard,
low ambient cooling down to 0F.
Contact your localTrane Representative
for more assistance with low ambient
cooling applications.
Barometric Relief
This product line offers an optional
barometric relief damper included in the
downflow economizer accessory.This
accessory consists of gravity dampers
which open with increased pressure. As
the building air pressure increases, the
pressure in the unit return air section
also increases, opening the dampers
and relieving the conditioned space.

Power Exhaust Accessory


The power exhaust accessory is
available on all 6-25 ton downflow
units.This accessory can be field
installed and will assist the barometric
relief damper in relieving building
pressurization.
Condensate Trap
The evaporator is a draw-thru
configuration. A trap must be field
provided prior to start-up on the cooling
cycle.
Clearance Requirements
The recommended clearances identified
with unit dimensions should be
maintained to assure adequate
serviceability, maximum capacity and
peak operating efficiency. Actual
clearances which appear inadequate
should be reviewed with the localTrane
sales personnel.
Unit Pitch
These units have sloped condensate
drain pans. Units must be installed level,
any unit slope must be toward access
side of unit.

NOTE:THE EFFECTIVENESS OF
BAROMETRIC RELIEF DAMPER
DURING ECONOMIZING OPERATION
IS SYSTEM RELATED.
PRESSURE DROP OFTHE RETURN AIR
SYSTEM SHOULD BE CONSIDEREDTO
CONTROL BUILDING PRESSURIZATION.

RT-PRC002-EN

Selection
Procedure

Cooling Capacity
Step 1
Calculate the buildings total and sensible
cooling loads at design conditions. Use
theTrane calculation methods or any
other standard accepted method.
Factors used in unit selection:
A
Total Cooling Load: 85 MBh
B
Sensible Cooling Load: 60 MBh
C
Airflow: 3000 cfm
D
Electrical Characteristics: 460/60/3
E
Summer Design Conditions: Entering
Evaporator Coil: 80 DB, 67 WB Outdoor
Ambient: 95
F
External Static Pressure: 0.52 in. wg
G
Rooftop - downflow configuration
H
Accessories
Roof curb
Economizer
Electric Heat
I
Heating
Capacity 70 MBh
460 volt/3 phase Electric Heat 3000
cfm
Step 2
As a starting point, a rough
determination must be made of the size
of the unit.The final selection will be
made after examining the performance
at the given conditions. Divide the total
cooling load by nominal BTUH per ton
(12 MBh per ton); then round up to the
nearest unit size.
85 MBh / 12 MBh = 7.08Tons or 7Tons
Step 3
Table PD-7 shows that aTCD090C4 has a
gross cooling capacity of 90 MBh and
65.0 MBh sensible capacity at 3000 cfm
and 95 DB outdoor ambient with 80 DB,
67 WB air entering the evaporator.

10

To Find Capacity at Intermediate


Conditions Not in the Table
When the design conditions are
between two numbers that are in the
capacity table, interpolation is required
to approximate the capacity. Note:
Extrapolation outside of the table
conditions is not recommended.
Step 4
In order to select the correct unit which
meets the buildings requirements, the
fan motor heat must be deducted from
the gross cooling capacity.The amount
of heat that the fan motor generates is
dependent on the effort by the motor cfm and static pressure.To determine the
total unit static pressure:
External Static (duct system)
0.52 wg
Standard Filter 1 in.
fromTable PD-57

0.10 wg

Economizer

0.03 wg

(100% Return Air) fromTable PD-57


Electric Heater Size 36 kw 0.05 wg
fromTable PD-57
Total Static Pressure

0.70 wg

Note:The Evaporator Fan Performance


Table PD-31 has deducted the pressure
drop for a 1 in. filter already in the unit
(see note belowTable PD-31).Therefore,
the actual total static pressure is 0.70 0.10 (from Table PD-57) = 0.60 wg.

Now subtract the fan motor heat from


the gross cooling capacity of the unit:
NetTotal Cooling Capacity
= 90 MBH - 5.01 = 84.99 MBH.
Net Sensible Cooling Capacity
= 64.9 MBH - 5.01 = 59.89 MBH.
Step 5
If the performance will not meet the
required load of the building -total or
sensible cooling load, try a selection at
the next higher size unit.
Heating Capacity
Step 1
Calculate the building heating load
using theTrane calculation form or other
standard accepted method.
Step 2
Size the system heating capacity to
match the calculated building heating
load.The following are building heating
requirements:
A
Total heating load of 70.0 MBH
B
3000 cfm
C
460 volt/3 phase Power Supply
The electric heat accessory capacities
are listed inTable PD-58. From the table,
a 27 kw heater will deliver 92.1 MBH at
480 volts. In order to determine capacity
at 460 volts, the heater voltage
correction factor fromTable PD-59 must
be used.Therefore, 92.1 MBH x .92
(voltage correction factor) = 84.73 MBH.
Air Delivery Selection

With 3000 cfm and 0.60 wg.


Table PD-31 shows 1.42 bhp for this unit.
Note below the table gives a formula to
calculate Fan Motor Heat,
3.53 x bhp = MBH.
3.53 x 1.42 = 5.01 MBH.

External static pressure drop through


the air distribution system has been
calculated to be 0.60 inches of water.
FromTable PD-57 static pressure drop
through the economizer is 0.03 and the
36 kw heater is 0.05 inches of water
(0.52 + 0.03 + 0.05). EnterTable PD-31 for
aTCD090C4 at 3000 cfm and 0.60 static
pressure.The standard motor at 1015
rpm will give the desired airflow at a
rated bhp of 1.42.

RT-PRC002-EN

Model
Number
Description

Packaged Cooling with Electric Heat Unit Typical Model Nomenclature


T

10

11

12

Digits 1, 2 - Product Type


TC = Packaged Cooling, Electric
Heat
Digit 3 - Airflow Configuration
D = Downflow
H = Horizontal

Digits 4, 5, 6 - Nominal Gross Cooling


Capacity (MBh)
036
037
048
049
060
061
074
075
086
090
091
102
103
120
121
150
151
180
181
210
211
240
241
300
301

RT-PRC002-EN

=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=

3Tons Standard Efficiency


3Tons High Efficiency
4Tons Standard Efficiency
4Tons High Efficiency
5Tons Standard Efficiency
5Tons High Efficiency
6 Tons High Efficiency
6 Tons Standard Efficiency
7Tons High Efficiency
7 Tons Standard Efficiency
7 Tons High Efficiency
8 Tons Standard Efficiency
8 Tons High Efficiency
10Tons Standard Efficiency
10Tons High Efficiency
12Tons Standard Efficiency
12 Tons High Efficiency
15Tons Standard Efficiency
15Tons High Efficiency
17Tons Standard Efficiency
17 Tons High Efficiency
20Tons Standard Efficiency
20Tons High Efficiency
25Tons Standard Efficiency
25Tons High Efficiency

Digit 7- Major Development Sequence


Digit 8 - Electrical Characteristics
1 = 208-230/60/1
3 = 208-230/60/3
4 = 460/60/3
W = 575/60/3

Digit 10 - Factory-Installed Options


0
A
B
C

=
=
=
=

No Factory-installed Options
Factory-installed Economizer
Oversized Motor
Downflow Economizer and Oversized
Motor
F = Trane Communications Interface (TCI)
G = Downflow Economizer and TCI

Digit 11- Minor Design Sequence


Digit 12- Service Digit

11

General
Data

(3, 4 , 5Ton)
Standard Efficiency

Table GD-1 General Data


3 Ton Downflow Units
TCD036C1, C3, C4
Cooling Performance1
Gross Cooling Capacity
SEER2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
System Power (KW)
Compressor
No./Type
Sound Rating (BELS)3
Outdoor Coil Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Indoor Coil Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan Type
No. Used
Diameter x Width (in.)
Drive Type/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM
(Standard/Oversized)
Motor Frame Size
(Standard/Oversized)
Filters Type/Furnished?
(No.) Size Recommended (in.)
Refrigerant Charge (Lbs of R-22)4

4Ton Downflow and Horizontal Units


TCR048C1
TCR048C3, C4, CW

5Ton Downflow and Horizontal Units


TCR060C1
TCR060C3, C4, CW

37,400
10.00
1,200/1,200
36,000
4.016

49,900
10.007
1,600/1,600
48,000
5.34

48,900
10.007
1,600/1,600
47,000
5.26

64,000
9.85
2,000/2,000
61,500
6.95

62,500
10.00
2,000/2,000
60,000
6.71

1/Climatuff
8.2
Hi-Performance
.375
5.87
2/16
Hi-Performance
.375
3.67
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
3,150
1/.25
850
FC Centrifugal
1
9x9
Direct/2
1
.33/.40

1/Climatuff
8.6
Hi-Performance
.375
7.43
2/16
Hi-Performance
.375
4.83
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
3,940
1/.33
850
FC Centrifugal
1
12 x 9
Direct/2
1
.50/.75

1/Climatuff
8.6
Hi-Performance
.375
5.83
2/16
Hi-Performance
.375
4.83
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
3,630
1/.33
1,075
FC Centrifugal
1
12 x 9
Direct/2
1
.50/.75

1/Climatuff
8.6
Hi-Performance
.375
11.32
2/16
Hi-Performance
.375
6.33
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,900
1/.50
975
FC Centrifugal
1
12 x 9
Direct/2
1
.60/.75

1/Climatuff
8.6
Hi-Performance
.375
9.76
2/16
Hi-Performance
.375
6.33
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,270
1/.40
1,075
FC Centrifugal
1
12 x 9
Direct/2
1
.60/.75

1075/1400

850/1040

850/1040

850/1040

850/1040

48/48
Throwaway/Yes
(2) 20 x 25 x 1
5.6

48/48
Throwaway/Yes
(2) 20 x 25 x 15
6.6

48/48
Throwaway/Yes
(2) 20 x 25 x 15
5.6

48/48
Throwaway/Yes
(2) 20 x 25 x 1
8.4

48/48
Throwaway/Yes
(2) 20 x 25 x 1
7.9

NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Air-Conditioner Equipment
certification program, which is based on ARI Standard 210/240.
2. SEER is rated at ARI conditions and in accordance with DOE test procedures.
3. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
5. TCH048 models require (2) 16 x 25 x 1 filters
6. TCD036C3, C4 system power KW 3.99.
6. Hoizontal models have 8.95 SEER.

Indicates both downflow and horizontal units.

12

RT-PRC002-EN

General
Data

(6, 7 Ton)
Standard Efficiency

Table GD-2 General Data


6 Ton Downflow and Horizontal Units
TCR075C3, C4, CW
Cooling Performance1
Gross Cooling Capacity
EER2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part Load Value3
System Power (KW)
Compressor
No./Type
Sound Rating (BELS)4
Outdoor Coil Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Indoor Coil Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan Type
No. Used
Diameter x Width (in.)
Drive Type/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters Type/Furnished?
(No.) Size Recommended (in.)
Refrigerant Charge (Lbs of R-22)5

7 Ton Downflow and Horizontal Units


Single Compressor
Dual Compressor
TCR090C3, C4, CW
TCR090D3, D4, DW

75,000
9.00
2,500/2,188
72,000

8.00

92,000
9.00
3,000/2,625
88,000

9.78

90,000
9.00
3,000/2,625
86,000
9.40
9.56

1/Climatuff
8.8
Hi-Performance
.375
11.32
2/16
Hi-Performance
.375
7.00
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,870
1/.50
1,075
FC Centrifugal
1
12 x 9
Belt/1
1
1.0/2.0
1,725/1,725
56/56
Throwaway/Yes
(3) 16 x 25 x 1
9.1

1/Trane H
8.8
Hi-Performance
.375
12.09
2/16
Hi-Performance
.375
7.88
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
5,450
1/.50
1,075
FC Centrifugal
1
12 x 9
Belt/1
1
1.0/2.0
1,725/1,725
56/56
Throwaway/Yes
(3) 16 x 25 x 1
10.6

2/Climatuff
8.8
Hi-Performance
.375
14.00
2/16
Hi-Performance
.375
7.88
2/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
5,620
1/.50
1,075
FC Centrifugal
1
12 x 9
Belt/1
1
1.0/2.0
1,725/1,725
56/56
Throwaway/Yes
(3) 16 x 25 x 1
6.3/Circuit

NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at
ARI
rated cfm.
4. Sound Rating shownis tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

Indicates both downflow and horizontal units.

RT-PRC002-EN

13

General
Data

(8, 10Ton)
Standard Efficiency

Table GD-3 General Data


8 Ton Downflow and Horizontal Units
TCR102C3, C4, CW
Cooling Performance1
Gross Cooling Capacity
EER2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part Load Value3
System Power (KW)
Compressor
No./Type
Sound Rating (BELS)4
Outdoor Coil Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Indoor Coil Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan Type
No. Used
Diameter x Width (in.)
Drive Type/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters Type/Furnished?
(No.) Size Recommended (in.)
Downflow
Horizontal
Refrigerant Charge (Lbs of R-22)5

10Ton Downflow and Horizontal Units


TCR120C3, C4, CW

107,000
9.2
3,400/3,000
102,000
9.4
11.09

125,000
9.26
4,000/3,500
118,000
9.16
12.836

2/Climatuff
9.2
Hi-Performance
.375
16.03
2/16
Hi-Performance
.375
10.50
2/15
Short Orifice
1/0.75 PVC
Propeller
1/26
Direct/1
7,000
1/1.0
1,125
FC Centrifugal
1
15 x 11
Belt/1
1
2.0/3.0
1,740/1,740
145T/145T
Throwaway/Yes

2/Climatuff
9.2
Hi-Performance
.375
18.67
2/16
Hi-Performance
.375
10.50
3/15
Short Orifice
1/0.75 PVC
Propeller
1/26
Direct/1
7,700
1/1.0
1,125
FC Centrifugal
1
15 x 11
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway/Yes

(2) 20 x 20 x 2, (2) 16 x 20 x 2
(2) 20 x 25 x 2, (2) 16 x 25 x 2
7.1/Circuit

(2) 20 x 20 x 2, (2) 16 x 20 x 2
(2) 20 x 25 x 2, (2) 16 x 25 x 2
8.5/Circuit

NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at
ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models EER 9.4, IPLV 9.3, system power KW 12.55.

Indicates both downflow and horizontal units.

14

RT-PRC002-EN

General
Data

(12, 15 Ton)
Standard Efficiency

Table GD-4 General Data


12Ton Downflow and Horizontal Units
TCR150C3, C4, CW
Cooling Performance1
Gross Cooling Capacity
EER2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part Load Value3
System Power (KW)
Compressor
No./Type
Sound Rating (BELS)4
Outdoor Coil Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Indoor Coil Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan Type
No. Used
Diameter x Width (in.)
Drive Type/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM (Standard/Oversized)
Motor Frame Size (Standard/Oversized)
Filters Type/Furnished?
(No.) Size Recommended (in.)
Downflow
Horizontal
Refrigerant Charge (Lbs of R-22)5
Downflow
Horizontal

15 Ton Downflow and Horizontal Units


TCR180B3, B4, BW

150,000
9.2
5,000/4,400
142,000
8.9
15.44

180,000
9.06
6,000/5,300
170,000
8.9
18.906

2/Climatuff Scroll
9.2
Hi-Performance
.375
23.93
2/16
Hi-Performance
.375
12.637
3/15
Short Orifice
1/1.00 NPT
Propeller
1/26
Direct/1
7,800
1/1.00
1,125
FC Centrifugal
1
15 x 15
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway/Yes

2/Trane 3-D Scroll/Climatuff Scroll


9.2
Hi-Performance
.375
24.18
2/16
Hi-Performance
.375
17.50
2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
10,800
2/.50
1,100
FC Centrifugal
1
15 x 15
Belt/1
1
3.0/5.0
1,740/3,450
145T/145T
Throwaway/Yes

(3) 20 x 20 x 2, (3) 16 x 20 x 2
(4) 20 x 25 x 2

(2) 20 x 20 x 2, (4) 20 x 25 x 2
(2) 20 x 20 x 2, (4) 20 x 25 x 2

8.4/9.1/Circuit
8.6/Circuit

13.4/7.7/Circuit
13.4/7.7/Circuit

NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at
ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models EER 9.1, system power KW 18.68.
7. Face area for Indoor Coil on horizontal models is 12.36.

Indicates both downflow and horizontal units.

RT-PRC002-EN

15

General
Data

(17, 20, 25Ton)


Standard Efficiency

Table GD-5 General Data


17Ton
Downflow and Horizontal Units
TCR210C3, C4, CW
Cooling Performance1
Gross Cooling Capacity
208,000
EER2
8.8
Nominal CFM / ARI Rated CFM
7,000/5,800
ARI Net Cooling Capacity
192,000
Integrated Part Load Value3
8.5
System Power (KW)
21.81
Compressor
No./Type
2/Trane 3-D Scroll/Climatuff Scroll
Sound Rating (BELS)4
9.4
Outdoor Coil Type
Hi-Performance
Tube Size (in.) O.D.
.375
Face Area (sq ft)
28.21
Rows/FPI
2/16
Indoor Coil Type
Hi-Performance
Tube Size (in.)
.375
Face Area (sq ft)
17.50
Rows/FPI
3/15
Refrigerant Control
Short Orifice
Drain Connection No./Size (in.)
1/1.00 NPT
Outdoor Fan Type
Propeller
No. Used/Diameter (in.)
2/26
Drive Type/No. Speeds
Direct/1
CFM
14,100
No. Motors/HP
2/1.0
Motor RPM
1,125
Indoor Fan Type
FC Centrifugal
No. Used
1
Diameter x Width (in.)
15 x 15
DriveType/No. Speeds
Belt / 1
No. Motors
1
Motor HP (Standard/Oversized)
5.0/7.5
Motor RPM (Standard/Oversized)
3,450/3,470
Motor Frame Size (Standard/Oversized)
145T/184T
Filters Type/Furnished?
Throwaway/Yes
(No.) Size Recommended (in.)
Downflow
(2) 20 x 20 x 2, (4) 20 x 25 x 2
Horizontal
(2) 20 x 20 x 2, (4) 20 x 25 x 2
14.0/8.5/Circuit6
Refrigerant Charge (Lbs of R-22)5

20 Ton
Downflow and Horizontal Units
TCR240B3, B4, BW

25 Ton
Downflow and Horizontal Units
TCR300B3, B4, BW

246,000
9.2
8,000/7,000
232,000
9.3
25.22

290,000
9.7
10,000/8,750
272,000
9.8
28.05

2/Trane 3-DScroll
9.4
Hi-Performance
.375
32.57
2/16
Hi-Performance
.375
26.00
2/15
Short Orifice
1/1.00 NPT
Propeller
2/26
Direct/1
14,800
2/1.0
1,125
FC Centrifugal
1
18 x 18
Belt / 1
1
5.0/7.5
3,450/3,470
145T/184T
Throwaway/Yes

2/Trane 3-D Scroll


9.4
Hi-Performance
.375
36.43
2/16
Hi-Performance
.375
26.00
3/15
Short Orifice
1/1.00 NPT
Propeller
2/28
Direct/1
16,700
2/1.0
1,125
FC Centrifugal
1
18 x 18
Belt / 1
1
7.5/NA
3,470/NA
184T/NA
Throwaway/Yes

(4) 20 x 20 x 2, (4) 20 x 25 x 2
(8) 20 x 25 x 2
13.8/Circuit

(4) 20 x 20 x 2, (4) 20 x 25 x 2
(8) 20 x 25 x 2
17.0/Circuit

NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. 17 and 20 ton model ratings shown are certified in accordance
with the Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI
Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with ARI Standard 210/240 or 360.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80 F ambient, 80 F entering dry bulb, and 67 F entering wet bulb at
ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Refrigerant charge for horizontal models is 14.4/8.7 per circuit.

Indicates both downflow and horizontal units.

16

RT-PRC002-EN

General
Data

(3, 4, 5, 6, 7Ton)
High Efficiency

Table GD-6 General Data


3 Ton
Downflow Units
TCR037C3,C4
Cooling Performance1
Gross Cooling Capacity
SEER / EER2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
System Power (KW)
Compressor
No./Type
Sound Rating (BELS)3
Outdoor Coil Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Indoor Coil Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan Type
No. Used
Diameter x Width (in.)
Drive Type/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM
(Standard/Oversized)
Motor Frame Size
(Standard/Oversized)
Filters Type/Furnished?
(No.) Size Recommended (in.)
Refrigerant Charge (Lbs of R-22)4

4 Ton
5 Ton
Downflow and Horizontal Units
TCR049C3,C4
TCR061C3,C4

6 Ton
7 Ton
Downflow and Horizontal Units
TCR074C3,C4
TCR086C3,C4

42,400
12.00/
1,200/1,200
41,000
3.78

51,400
12.00/
1,600/1,600
49,500
4.61

60,500
12.00/
2,000/2,000
58,000
5.38

72,000
/10.00
2,500/2,188
68,000
6.80

82,000
/9.50
2,500/2,188
78,000
8.21

1/Climatuff
8.2
Hi-Performance
0.375
11.32
2/16
Hi-Performance
0.375
6.33
2/15
Short Orifice
1 / PVC
Propeller
1/24
Direct/1
4,100
1/.25
850
FC Centrifugal
1
9x9
Direct/2
1
.33/.40

1/Climatuff
8.2
Hi-Performance
0 .375
11.32
2/16
Hi-Performance
0.375
6.33
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,100
1/.25
850
FC Centrifugal
1
12 x 9
Direct/2
1
.50/.75

1/Climatuff
8.2
Hi-Performance
0 .375
12.09
2/16
Hi-Performance
0.375
7.00
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,150
1/.25
850
FC Centrifugal
1
12x 9
Direct/2
1
.60/.75

1/Climatuff
8.2
Hi-Performance
0.375
11.32
2/16
Hi-Performance
0.375
7.88
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
4,100
1/.25
850
FC Centrifugal
1
12 x 9
BELT/1
1
1.0/2.0

1/Climatuff
8.8
Hi-Performance
0.375
14.00
2/16
Hi-Performance
0.375
7.88
3/15
Short Orifice
1/ PVC
Propeller
1/24
Direct/1
5,620
1/.50
1,075
FC Centrifugal
1
12 x 9
BELT/1
1
1.0/2.0

1075/1400

850/1040

850/1040

1725/1725

1725/1725

48/48
Throwaway/Yes
(2) 20 x 25 x 1
8.3

48/48
Throwaway/Yes
(2) 20 x 25 x 1
8.9

48/48
Throwaway/Yes
(3) 16 X 25 X 1
10.2

56/56
Throwaway/Yes
(3)16 X 25 X 1
10.0

56/56
Throwaway/Yes
(3) 16 X 25 X 1
11.6

NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. 3 - 5 ton models are certified in accordance with the Unitary AirConditioner Equipment certification program, which is based on ARI Standard 210/240. 6 and 7 ton models are certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER and SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
4. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

Indicates both downflow and horizontal units.

RT-PRC002-EN

17

General
Data

(7, 8, 10, 12,Ton)


High Efficiency

Table GD-7 General Data


7 Ton
8 Ton
Downflow and Horizontal Models
TCR091D3, D4
TCR103C3,C4,CW
Cooling Performance1
Gross Cooling Capacity
EER 2
Nominal CFM / ARI Rated CFM
ARI Net Cooling Capacity
Integrated Part Load Value 3
System Power KW
Compressor
No./Type
Sound Rating (BELS)4
Outdoor Coil Type
Tube Size (in.) O.D.
Face Area (sq ft)
Rows/FPI
Indoor Coil Type
Tube Size (in.)
Face Area (sq ft)
Rows/FPI
Refrigerant Control
Drain Connection No./Size (in.)
Outdoor Fan Type
No. Used/Diameter (in.)
Drive Type/No. Speeds
CFM
No. Motors/HP
Motor RPM
Indoor Fan Type
No. Used
Diameter x Width (in.)
Drive Type/No. Speeds
No. Motors
Motor HP (Standard/Oversized)
Motor RPM
(Standard/Oversized)
Motor Frame Size
(Standard/Oversized)
Filters Type/Furnished?
(No.) Size Recommended (in.)
Refrigerant Charge (Lbs of R-22) 5/Circuit

10 Ton
12Ton
Downflow and Horizontal Models
TCR121C3,C4,CW
TCR151C3,C4,CW

86,000
10.00
3,000/2,625
81,000
10.10
8.1

106,000
11.00
3,400/3,000
101,000
11.9
9.18

127,000
11.5
4,000/3,500
120,000
12.4
10.43

154,000
11.3
5,000/4,400
147,000
11.5
13.01

2/Climatuff
8.8
Hi-Performance
0.375
14.00
2/16
Hi-Performance
0.375
7.88
3/15
Short Orifice
1 / PVC
Propeller
1/24
Direct/1
5,620
1/.50
1075
FC Centrifugal
1
12 x 9
BELT/1
1
1.0/2.0

2/Copeland Scroll
9.0
Hi-Performance
0 .375
23.93
2/16
Hi-Performance
0.375
12.636
3/15
Short Orifice
1/1.0 NPT
Propeller
1/26
Direct/1
7,100
1/1.00
1125
FC Centrifugal
1
15 x 11
BELT/1
1
2.0/3.0

2/Climatuff
9.2
Hi-Performance
0 .375
28.21
2/16
Hi-Performance
0.375
17.50
3/15
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
10,800
2/.50
1100
FC Centrifugal
1
15 x 15
BELT/1
1
2.0/3.0

2/Copeland Scroll
9.2
Hi-Performance
0.375
27.12
3/16
Hi-Performance
0.375
17.50
3/15
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
10,400
2/.50
1100
FC Centrifugal
1
15 x 15
BELT/1
1
3.0/5.0

1725/1725

1740/1740

1740/1740

1740/3450

56/56
Throwaway/Yes
(3)16 X 25 X 1

145T/145T
Throwaway/Yes
(3)20 X 20 X 2/
(3)16 X 20 X 27
9.1/9.58

145T/145T
Throwaway/Yes
(2)20 X 20 X 2/
(4)20 X 25 X 2
11.0/11.0

145T/145T
Throwaway/Yes
(2)20 X 20 X 2/
(4)20 X 25 X 2
15.0/13.8

6.4/6.4

NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. Certified in accordance with the Unitary Large Equipment
certification program, which is based on ARI Standard 340/360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80F ambient, 80F entering dry bulb, and 67F entering wet bulb
at ARI rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Face area for Indoor Coil on horizontal models is 12.36.
7. Horizontal models have 4 - 20 x 25 x 2 filters.
8. The refrigerant charge for 8 ton horizontal models is 7.8/8.1 per circuit.

Indicates both downflow and horizontal units.

18

RT-PRC002-EN

General
Data

(15, 17, 20, 25 Ton)


High Efficiency

Table GD-8 General Data


15Ton

17 Ton
20 Ton
Downflow and Horizontal Models
TCR211C3,C4,CW
TCR241C3,C4,CW

TCR181C3,C4,CW
Cooling Performance1
Gross Cooling Capacity
189,000
220,000
268,000
EER 2
11.5
11.0
10.6
Nominal CFM / ARI Rated CFM
6,000/5,300
7,000/6,200
8,000/7,000
ARI Net Cooling Capacity
180,000
208,000
250,000
Integrated Part Load Value 3
13.3
12.0
11.2
System Power KW
15.65
18.91
23.58
Compressor
No./Type
2/Trane 3-DScroll/Climatuff Scroll 2/Trane3-D Scroll/Copeland Scroll 2/Trane 3-D Scroll
Sound Rating (BELS)4
9.2
9.4
9.4
Outdoor Coil Type
Hi-Performance
Hi-Performance
Hi-Performance
Tube Size (in.) O.D.
0.375
0 .375
0.375
Face Area (sq ft)
35.30
35.30
35.30
Rows/FPI
3/16
3/16
3/16
Indoor Coil Type
Hi-Performance
Hi-Performance
Hi-Performance
Tube Size (in.)
0.375
0.375
0.375
Face Area (sq ft)
26.00
26.000
26.00
Rows/FPI
3/15
4/15
4/15
Refrigerant Control
Short Orifice
Short Orifice
Short Orifice
Drain Connection No./Size (in.)
1/1.0 NPT
1 /1.0 NPT
1/1.0 NPT
Outdoor Fan Type
Propeller
Propeller
Propeller
No. Used/Diameter (in.)
2/26
2/26
2/26
Drive Type/No. Speeds
Direct/1
Direct/1
Direct/1
CFM
11,000
12,800
13,700
No. Motors/HP
2/.50
2/1.00
2/1.00
Motor RPM
1100
1125
1125
Indoor Fan Type
FC Centrifugal
FC Centrifugal
FC Centrifugal
No. Used
1
1
1
Diameter x Width (in.)
18 x 18
18 x 18
18 x 18
Drive Type/No. Speeds
BELT/1
BELT/1
BELT/1
No. Motors
1
1
1
Motor HP (Standard/Oversized)
3.0/5.0
5.0/7.5
5.0/7.5
Motor RPM
(Standard/Oversized)
1740/3450
3450/3470
3450/3470
Motor Frame Size
(Standard/Oversized)
145T/145T
145T/184T
145T/184T
Filters Type/Furnished?
Throwaway/Yes
Throwaway/Yes
Throwaway/Yes
(No.) Size Recommended (in.)
(4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20 X 20 X 2/20 X 25 X 26 (4/4)20 X 20 X 2/20 X 25 X 26
Refrigerant Charge (Lbs of R-22) 5 / Circuit
25/13
25.7/12.5
21.8/21.8

25 Ton
TCR301C3,C4,CW
300,000
10.4
10,000/8,750
278,000
11.0
26.73
2/Trane 3-D Scroll
9.4
Hi-Performance
0.375
35.30
3/16
Hi-Performance
0.375
26.00
4/15
Short Orifice
1/1.0 NPT
Propeller
2/26
Direct/1
13,700
2/1.00
1125
FC Centrifugal
1
18 x 18
BELT/1
1
7.5/NA
3470/NA
184T/NA
Throwaway/Yes
(4/4)20X20X2/20X25X26
24.5/24.5

NOTES:
1. Cooling Performance is rated at 95 F ambient, 80 F entering dry bulb, 67 F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to 20% of nominal cfm. 15, 17 and 20 ton models are certified in accordance with the
Unitary Large Equipment certification program, which is based on ARI Standard 340/360-93. 25 ton model ratings shown are tested in accordance with ARI Standard 340/
360-93.
2. EER is rated at ARI conditions and in accordance with DOE test procedures.
3. Integrated Part Load Value is based in accordance with ARI Standard 210/240 or 360. Units are rated at 80F ambient, 80F entering dry bulb, and 67F entering wet bulb
at ARI
rated cfm.
4. Sound Rating shown is tested in accordance with ARI Standard 270 or 370.
5. Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
6. Horizontal models have 8 - 20 x 25 x 2 filters.

Indicates both downflow and horizontal units.

RT-PRC002-EN

19

Performance
Data

(3, 4Ton)
Standard Efficiency

Table PD-1 Gross Cooling Capacities (MBH) 3 Ton Single/Three Phase TCD036C1, C3, C4
85

CFM
Airflow

1080

1200

1320

1440

Enter.
Dry
Bulb
61
(F) MBH SHC
75 34.5 26.9
80 34.9 32.0
85 35.9 35.9
90 38.2 38.2
75 35.5 28.5
80 36.0 34.0
85
37.5 37.5
90 39.4 39.4
75 36.3 30.0
80
37.0 36.0
85 38.6 38.6
90 40.4 40.4
75
37.0 31.4
80
37.4 37.4
85 39.5 39.5
90 41.2 41.2

67
MBH SHC
38.8 22.1
39.0 26.1
39.3 30.9
39.6 35.7
39.5 22.1
39.7 27.3
40.0 32.4
40.4 37.5
39.9 22.9
40.2 28.2
40.5 33.7
41.1 39.1
40.3 23.6
40.6 29.1
41.0 34.9
41.6 40.5

73
MBH SHC
41.3 14.6
41.6 19.8
41.9 24.2
42.3 28.5
41.5 14.8
41.9 20.5
42.3 26.0
42.8 29.4
41.8 15.0
42.2 21.2
42.6 27.1
43.2 30.1
41.9 15.2
42.4 21.8
42.9 25.8
43.5 30.8

61
MBH SHC
31.7 25.3
32.2 30.4
33.6 33.6
36.1 36.1
32.6 26.8
33.2 32.4
35.2 35.2
37.5 37.5
33.3 28.2
33.8 33.8
36.5 36.5
38.6 38.6
34.0 29.7
35.0 35.0
37.5 37.5
39.4 39.4

Ambient Temperature (F)


95

105

Entering Wet Bulb (F)


67
73
61
MBH SHC MBH SHC MBH SHC
36.6 20.9 39.7 13.6 28.6 23.5
36.8 24.9 39.9 18.7 29.3 28.7
36.9 29.8 40.2 23.4 31.2 31.2
37.3 34.8 40.5 27.9 33.6 33.6
37.3 20.8 40.0 13.8 29.5 25.1
37.4 26.2 40.3 19.4 30.0 30.0
37.7 31.5 40.7 24.2 32.6 32.6
38.2 36.8 41.1 29.0 35.2 35.2
37.8 21.6 40.3 14.0 30.2 26.5
38.0 27.3 40.7 20.1 31.2 31.2
38.3 33.0 41.0 26.0 33.9 33.9
39.0 38.7 41.5 30.0 36.3 36.3
38.2 22.3 40.5 14.2 30.8 28.0
38.4 28.4 40.9 20.7 32.3 32.3
38.8 34.4 41.3 25.4 35.0 35.0
39.5 39.5 41.8 30.8 37.3 37.3

67
MBH SHC
33.5 19.4
33.7 23.3
33.9 28.3
34.6 33.4
34.5 19.3
34.6 24.7
34.9 30.2
35.3 35.3
35.1 20.1
35.2 26.0
35.6 32.0
36.4 36.4
35.6 20.9
35.7 27.2
36.2 33.5
37.3 37.3

115

73
MBH SHC
37.6 12.4
37.8 17.4
37.9 22.3
38.2 27.1
38.0 12.6
38.2 18.1
38.5 23.3
38.8 28.4
38.3 12.9
38.6 18.8
38.9 24.1
39.2 29.5
38.5 13.1
38.8 19.5
39.2 24.9
39.6 30.5

61
MBH SHC
25.5 21.8
26.2 26.2
28.5 28.5
31.0 31.0
26.2 23.3
27.4 27.4
29.9 29.9
32.5 32.5
26.9 24.8
28.4 28.4
31.1 31.1
33.8 33.8
27.4 26.1
29.4 29.4
32.1 32.1
34.8 34.8

67
MBH SHC
30.1 16.6
30.2 21.5
30.5 26.5
31.1 31.1
30.9 17.5
31.0 22.9
31.4 28.5
32.6 32.6
31.5 18.4
31.6 24.3
32.2 30.3
33.9 33.9
32.0 19.2
32.2 25.5
33.0 32.1
34.9 34.9

73
MBH SHC
34.9 11.1
35.0 16.0
35.2 21.0
35.4 25.9
35.4 11.3
35.5 16.8
35.7 22.1
35.9 27.4
35.8 11.5
35.9 17.4
36.2 23.1
36.5 28.7
36.0 11.7
36.3 18.1
36.5 24.0
36.9 30.0

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-2 Gross Cooling Capacities (MBH) 4 Ton Single Phase TCR048C1
85

CFM
Airflow

1440

1600

1760

1920

Enter.
Dry
Bulb
61
(F) MBH SHC
75 45.9 35.7
80 46.2 42.1
85
47.4 47.4
90 50.3 50.3
75
47.1 37.6
80
47.6 44.7
85 49.4 49.4
90 51.9 51.9
75 48.2 39.5
80 48.8 47.2
85 50.8 50.8
90 53.2 53.2
75 49.0 41.2
80 49.8 49.5
85 51.9 51.9
90 54.2 54.2

67
MBH SHC
51.4 29.9
51.7 34.5
51.9 40.7
52.2 46.9
52.2 29.3
52.5 35.9
52.8 42.5
53.2 49.1
52.8 30.3
53.1 37.1
53.5 44.1
54.0 51.1
53.2 31.2
53.6 38.2
54.1 45.6
54.7 52.8

73
MBH SHC
54.5 19.6
54.9 26.4
55.3 31.9
55.8 37.5
54.9 19.8
55.4 27.2
55.8 34.3
56.5 38.6
55.2 20.1
55.7 28.0
56.2 35.7
57.0 39.5
55.5 20.4
56.0 28.8
56.6 34.0
57.3 40.3

61
MBH SHC
42.5 33.7
42.9 40.2
44.7 44.7
47.8 47.8
43.6 35.7
44.2 42.8
46.6 46.6
49.6 49.6
44.6 37.5
45.4 45.3
48.3 48.3
51.0 51.0
45.4 39.3
46.4 46.4
49.6 49.6
52.1 52.1

Ambient Temperature (F)


95

105

Entering Wet Bulb (F)


67
73
61
MBH SHC MBH SHC MBH SHC
48.8 28.5 52.7 18.4 38.9 31.7
49.0 33.1 53.0 25.1 39.5 38.3
49.2 39.5 53.3 31.0 41.8 41.8
49.5 45.9 53.7 36.8 44.9 44.9
49.7 27.8 53.1 18.7 39.9 33.6
49.9 34.7 53.5 25.9 40.4 40.4
50.1 41.6 53.9 32.0 43.6 43.6
50.6 48.4 54.4 38.2 46.9 46.9
50.3 28.8 53.5 19.0 40.8 35.4
50.6 36.1 53.9 26.8 41.8 41.8
50.8 43.4 54.4 34.4 45.2 45.2
51.5 50.7 55.0 39.4 48.3 48.3
50.9 29.7 53.8 19.3 41.6 37.2
51.1 37.4 54.3 27.5 43.2 43.2
51.5 45.1 54.8 33.6 46.7 46.7
52.1 52.1 55.4 40.4 49.5 49.5

67
MBH SHC
45.2 26.7
45.4 31.3
45.6 37.7
46.2 44.2
46.4 26.1
46.5 33.0
46.7 40.0
47.5 47.2
47.2 27.1
47.3 34.7
47.6 42.2
48.4 48.4
47.8 28.1
47.9 36.1
48.3 44.2
49.5 49.5

115

73
MBH SHC
50.2 17.1
50.4 23.6
50.6 29.8
51.0 35.9
50.7 17.4
51.0 24.5
51.3 31.0
51.7 37.5
51.1 17.7
51.5 25.3
51.8 32.0
52.3 38.9
51.4 17.9
51.8 26.1
52.3 32.9
52.8 40.2

61
MBH SHC
35.0 29.6
35.6 35.6
38.7 38.7
41.8 41.8
36.0 31.5
37.2 37.2
40.4 40.4
43.6 43.6
36.8 33.3
38.6 38.6
41.9 41.9
45.3 45.3
37.5 35.1
39.8 39.8
43.3 43.3
46.5 46.5

67
MBH SHC
41.1 24.8
41.3 29.2
41.5 35.6
41.9 41.9
42.2 24.0
42.3 31.0
42.6 38.0
43.7 43.7
43.0 25.1
43.1 32.6
43.5 40.3
45.4 45.4
43.7 26.1
43.8 34.2
44.4 42.5
46.5 46.5

73
MBH SHC
47.0 15.6
47.2 21.9
47.3 28.3
47.5 34.6
47.6 15.8
47.8 22.8
48.0 29.7
48.3 36.4
48.1 16.1
48.3 23.7
48.6 30.9
48.9 38.0
48.4 16.3
48.7 24.4
49.1 31.9
49.4 39.5

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

20

RT-PRC002-EN

Performance
Data

(4, 5Ton)
Standard Efficiency

Table PD-3 Gross Cooling Capacities (MBH) 4 Ton Three Phase TCR048C3, C4, CW
85

CFM
Airflow

1440

1600

1760

1920

Enter.
Dry
Bulb
61
(F) MBH SHC
75 45.0 35.2
80 45.3 41.7
85 46.7 46.7
90 49.6 49.6
75 46.2 37.2
80 46.7 44.3
85 48.7 48.7
90 51.2 51.2
75
47.2 39.1
80
47.9 46.8
85 50.1 50.1
90 52.5 52.5
75 48.1 40.8
80 48.6 48.6
85 51.2 51.2
90 53.5 53.5

67
MBH SHC
50.6 29.5
50.8 34.2
51.1 40.4
51.4 46.6
51.4 29.0
51.7 35.7
51.9 42.3
52.4 49.0
52.0 29.9
52.3 36.9
52.7 44.0
53.3 51.0
52.5 30.9
52.9 38.0
53.3 45.5
54.0 52.8

73
MBH SHC
54.0 19.4
54.4 26.1
54.7 31.8
55.2 37.4
54.5 19.6
54.9 27.0
55.3 34.0
55.9 38.5
54.8 19.9
55.3 27.8
55.8 35.5
56.4 39.6
55.1 20.2
55.6 28.6
56.2 34.0
56.9 40.5

61
MBH SHC
41.6 33.3
42.1 39.8
44.0 44.0
47.1 47.1
42.7 35.3
43.4 42.5
45.9 45.9
48.9 48.9
43.7 37.1
44.3 44.3
47.6 47.6
50.2 50.2
44.5 38.9
45.7 45.7
48.8 48.8
51.3 51.3

Ambient Temperature (F)


95

105

Entering Wet Bulb (F)


67
73
61
MBH SHC MBH SHC MBH SHC
47.8 28.0 51.9 18.1 38.0 31.4
48.0 32.7 52.2 24.7 38.7 37.9
48.2 39.1 52.4 30.7 41.1 41.1
48.6 45.5 52.8 36.5 44.2 44.2
48.7 27.4 52.3 18.4 39.0 33.3
48.9 34.3 52.7 25.6 39.7 39.7
49.1 41.2 53.1 31.7 42.9 42.9
49.7 48.0 53.6 38.0 46.1 46.1
49.3 28.4 52.7 18.7 39.9 35.1
49.6 35.8 53.2 26.4 41.2 41.2
49.8 43.1 53.6 34.1 44.5 44.5
50.6 50.3 54.1 39.2 47.5 47.5
49.9 29.4 53.0 19.0 40.7 36.8
50.2 37.1 53.5 27.3 42.5 42.5
50.5 44.8 54.0 33.4 45.9 45.9
51.3 51.3 54.6 40.3 48.6 48.6

67
MBH SHC
44.3 26.3
44.5 30.9
44.6 37.3
45.3 43.9
45.3 25.6
45.5 32.6
45.7 39.6
46.2 46.2
46.1 26.7
46.2 34.3
46.5 41.8
47.5 47.5
46.6 27.7
46.8 35.7
47.2 43.8
48.7 48.7

115

73
MBH SHC
49.1 16.7
49.3 23.2
49.6 29.4
49.9 35.5
49.7 17.0
49.9 24.1
50.2 30.6
50.6 37.1
50.1 17.3
50.4 24.9
50.8 31.6
51.2 38.5
50.4 17.5
50.8 25.7
51.2 32.6
51.7 39.8

61
MBH SHC
34.2 29.3
35.0 35.0
38.0 38.0
41.1 41.1
35.1 31.2
36.5 36.5
39.7 39.7
43.0 43.0
35.9 33.0
37.9 37.9
41.2 41.2
44.4 44.4
36.6 34.8
39.1 39.1
42.5 42.5
45.5 45.5

67
MBH SHC
40.2 24.4
40.4 28.9
40.6 35.3
41.2 41.2
41.2 23.6
41.3 30.6
41.7 37.7
43.1 43.1
42.0 24.7
42.1 32.3
42.6 40.0
44.5 44.5
42.7 25.8
42.8 33.9
43.5 42.1
45.6 45.6

73
MBH SHC
45.8 15.2
46.0 21.5
46.2 27.9
46.4 34.1
46.4 15.4
46.6 22.4
46.8 29.2
47.1 35.5
46.9 15.7
47.1 23.3
47.4 30.4
47.7 37.5
47.2 15.9
47.5 24.0
47.9 31.5
48.2 39.0

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-4 Gross Cooling Capacities (MBH) 5 Ton Single Phase TCR060C1
85

CFM
Airflow

1800

2000

2200

2400

Enter.
Dry
Bulb
61
(F) MBH SHC
75 58.9 45.9
80 59.4 54.1
85 60.7 60.7
90 64.2 64.2
75 60.5 48.3
80 61.2 57.4
85 63.2 63.2
90 66.2 66.2
75 61.8 50.7
80 62.6 60.5
85 64.9 64.9
90
67.8 67.8
75 62.8 52.9
80 63.7 63.2
85 66.3 66.3
90 69.0 69.0

67
MBH SHC
65.7 36.5
65.9 44.4
66.2 52.1
66.7 59.9
66.7 37.6
66.9 46.1
67.3 54.4
67.9 62.8
67.4 38.8
67.7 47.6
68.2 56.5
68.9 65.3
67.9 39.7
68.4 49.0
68.9 58.4
69.8 67.5

73
MBH SHC
69.6 25.3
70.1 33.8
70.5 41.0
71.1 48.0
70.2 25.5
70.7 34.9
71.2 42.1
71.9 49.5
70.6 25.9
71.2 35.9
71.8 45.6
72.5 50.7
70.9 26.2
71.6 36.9
72.2 47.3
73.0 51.8

61
MBH SHC
54.8 43.6
55.5 51.9
57.5 57.5
61.4 61.4
56.3 46.1
57.2 55.2
60.0 60.0
63.7 63.7
57.5 48.4
58.7 58.4
62.1 62.1
65.4 65.4
58.6 50.7
59.7 59.7
63.6 63.6
66.8 66.8

Ambient Temperature (F)


95

105

Entering Wet Bulb (F)


67
73
61
MBH SHC MBH SHC MBH SHC
62.8 34.6 67.8 24.0 50.4 41.3
62.9 42.7 68.1 32.4 51.3 49.6
63.0 50.8 68.3 40.2 54.0 54.0
63.6 58.8 68.8 47.6 58.0 58.0
63.8 36.0 68.4 24.4 51.8 43.7
64.0 44.8 68.8 33.5 53.0 52.9
64.2 53.4 69.1 41.5 56.4 56.4
65.0 62.1 69.7 49.4 60.5 60.5
64.6 37.2 68.8 24.8 53.0 46.0
64.8 46.6 69.3 34.6 54.2 54.2
65.2 55.9 69.8 42.6 58.4 58.4
66.2 65.1 70.4 51.0 62.3 62.3
65.3 38.4 69.2 25.1 54.0 48.3
65.6 48.3 69.6 35.0 55.9 55.9
66.1 58.1 70.3 43.6 60.3 60.3
66.8 66.8 71.0 52.4 63.8 63.8

67
MBH SHC
58.4 34.7
58.6 40.6
58.9 48.7
59.7 57.0
59.9 34.0
60.0 42.8
60.3 51.7
61.4 60.8
60.9 35.3
61.0 44.9
61.5 54.5
62.4 62.4
61.6 36.6
61.8 46.8
62.4 57.0
63.8 63.8

115

73
MBH SHC
64.9 22.6
65.1 30.8
65.3 38.9
65.6 46.6
65.6 23.0
65.9 31.9
66.1 40.4
66.6 48.7
66.1 23.3
66.5 33.0
66.8 41.8
67.3 50.6
66.6 23.6
67.0 34.0
67.4 43.0
68.0 52.3

61
MBH SHC
45.8 38.8
46.4 46.4
50.2 50.2
54.1 54.1
47.0 41.2
48.4 48.4
52.4 52.4
56.5 56.5
48.1 43.5
50.1 50.1
54.3 54.3
58.7 58.7
49.0 45.8
51.7 51.7
56.1 56.1
60.3 60.3

67
MBH SHC
53.2 32.4
53.5 38.1
53.9 46.3
55.0 54.7
54.6 31.5
54.8 40.3
55.3 49.3
56.6 56.6
55.7 32.9
55.8 42.5
56.6 52.2
58.8 58.8
56.6 34.2
56.8 `44.5
57.8 55.0
60.4 60.3

73
MBH SHC
61.0 20.8
61.2 28.9
61.4 37.0
61.5 45.0
61.8 21.1
62.0 30.0
62.2 38.8
62.5 47.4
62.5 21.5
62.7 31.1
62.9 40.4
63.3 49.5
63.0 21.8
63.3 32.2
63.6 41.9
64.0 51.6

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.


RT-PRC002-EN

21

Performance
Data

(5, 6Ton)
Standard Efficiency

Table PD-5 Gross Cooling Capacities (MBH) 5 Ton Three Phase TCR060C3, C4, CW
85

CFM
Airflow

1800

2000

2200

2400

Enter.
Dry
Bulb
61
(F) MBH SHC
75
57.5 44.8
80 58.0 52.8
85 59.3 59.3
90 62.7 62.7
75 59.0 47.2
80 59.7 56.0
85 61.7 61.7
90 64.7 64.7
75 60.3 49.5
80 61.2 59.1
85 63.4 63.4
90 66.2 66.2
75 61.3 51.6
80 62.2 61.8
85 64.7 64.7
90
67.4 67.4

67
MBH SHC
64.1 37.4
64.4 43.3
64.6 50.9
65.1 58.5
65.1 36.7
65.3 45.0
65.7 53.2
66.3 61.3
65.8 37.9
66.2 46.5
66.6 55.2
67.3 63.8
66.4 39.1
66.8 47.9
67.3 57.0
68.2 66.0

73
MBH SHC
68.0 24.7
68.5 33.0
68.8 40.1
69.4 46.9
68.5 24.9
69.1 34.1
69.6 42.8
70.2 48.3
68.9 25.3
69.5 35.1
70.1 44.5
70.8 49.5
69.2 25.6
69.9 36.0
70.5 46.2
71.3 50.6

61
MBH SHC
53.5 42.6
54.2 50.7
56.1 56.1
60.0 60.0
54.9 45.0
55.8 53.9
58.5 58.5
62.2 62.2
56.2 47.3
57.3 57.0
60.6 60.6
63.8 63.8
57.2 49.5
58.3 58.3
62.1 62.1
65.2 65.2

Ambient Temperature (F)


95

105

Entering Wet Bulb (F)


67
73
61
MBH SHC MBH SHC MBH SHC
61.2 35.8 66.2 23.5 49.2 40.3
61.4 41.7 66.5 31.6 50.1 48.4
61.6 49.5 66.7 39.3 52.7 52.7
62.1 57.5 67.2 46.5 56.5 56.5
62.3 35.1 66.8 23.8 50.5 42.7
62.5 43.7 67.2 32.7 51.7 51.7
62.7 52.2 67.5 40.5 55.0 55.0
63.5 60.7 68.1 48.2 59.0 59.0
63.1 36.3 67.2 24.2 51.7 44.9
63.3 45.5 67.7 33.7 52.9 52.9
63.7 54.6 68.2 43.2 57.0 57.0
64.6 63.6 68.8 49.8 60.8 60.8
63.8 37.5 67.6 24.5 52.8 47.1
64.1 47.2 68.2 34.7 54.5 54.5
64.5 56.8 68.7 44.8 58.8 58.8
65.2 65.2 69.4 51.2 62.3 62.3

67
MBH SHC
57.0 33.9
57.3 39.6
57.5 47.5
58.3 55.7
58.5 33.2
58.6 41.8
58.9 50.5
59.9 59.4
59.4 34.5
59.6 43.8
60.0 53.2
60.9 60.9
60.2 35.7
60.3 45.7
60.9 55.7
62.3 62.3

115

73
MBH SHC
63.4 22.0
63.5 30.0
63.8 38.0
64.1 45.5
64.1 22.4
64.3 31.1
64.7 39.8
65.0 47.5
64.6 22.7
64.9 32.2
65.3 41.6
65.8 49.4
65.0 23.0
65.4 33.2
65.9 43.3
66.4 51.1

61
MBH SHC
44.7 37.9
45.3 45.3
49.0 49.0
52.8 52.8
45.9 40.2
47.2 47.2
51.1 51.1
55.1 55.1
46.9 42.5
48.9 48.9
53.0 53.0
57.2 57.2
47.9 44.7
50.4 50.4
54.7 54.7
58.9 58.9

67
MBH SHC
52.1 29.3
52.2 37.2
52.6 45.2
53.7 53.4
53.3 30.8
53.5 39.4
54.0 48.1
55.2 55.2
54.3 32.1
54.5 41.5
55.3 51.0
57.3 57.3
55.3 33.4
55.4 43.4
56.4 53.7
58.9 58.9

73
MBH SHC
59.6 20.3
59.8 28.2
59.9 36.1
60.1 43.9
60.4 20.6
60.6 29.3
60.8 38.0
61.0 46.3
61.0 21.0
61.2 30.4
61.5 39.8
61.8 48.4
61.5 21.3
61.8 31.4
62.1 40.9
62.5 50.4

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-6 Gross Cooling Capacities (MBH) 6 Ton Three Phase TCR075C3, C4, CW
85

CFM
Airflow

2250

2500

2750

3000

Enter.
Dry
Bulb
61
(F) MBH SHC
75 70.2 55.7
80 70.8 66.1
85 73.1 73.1
90 76.7 76.7
75 71.8 58.8
80 72.6 70.1
85 75.4 75.4
90 78.8 78.8
75 73.1 61.5
80 74.1 73.7
85
77.1 77.1
90 80.3 80.3
75 74.0 64.1
80 75.0 75.0
85 78.6 78.6
90 81.6 81.6

67
MBH SHC
77.3 45.8
77.7 53.1
78.1 62.8
78.7 72.4
78.3 44.9
78.7 55.1
79.2 65.5
80.0 75.7
79.0 46.5
79.5 56.9
80.1 67.9
81.1 78.6
79.6 47.9
80.2 58.4
80.9 70.0
82.0 81.2

73
MBH SHC
81.3 29.6
81.9 40.2
82.6 48.5
83.4 57.0
81.8 29.8
82.5 41.5
83.2 52.7
84.2 58.6
82.2 30.3
83.0 42.8
83.8 50.6
84.8 60.1
82.5 30.7
83.3 44.0
84.3 51.5
85.3 61.3

61
MBH SHC
65.2 53.0
66.1 63.4
69.2 69.2
73.4 73.4
66.8 56.0
68.0 67.5
71.8 71.8
75.6 75.6
68.1 58.9
69.4 69.4
73.8 73.8
77.3 77.3
69.3 61.7
71.3 71.3
75.3 75.3
78.7 78.7

Ambient Temperature (F)


95

105

Entering Wet Bulb (F)


67
73
61
MBH SHC MBH SHC MBH SHC
73.6 43.9 78.7 28.0 60.0 50.2
73.9 51.4 79.3 38.4 61.1 60.7
74.2 61.4 79.7 47.5 64.9 64.9
74.9 71.4 80.4 56.5 69.5 69.5
74.7 42.9 79.3 28.3 61.5 53.2
75.0 53.7 79.9 39.7 62.8 62.8
75.4 64.5 80.5 48.9 67.6 67.6
76.4 75.2 81.3 58.5 71.8 71.8
75.6 44.5 79.8 28.8 62.7 56.0
75.9 55.9 80.4 41.0 64.9 64.9
76.4 67.3 81.2 50.1 69.7 69.7
77.4 77.4 82.0 60.3 73.6 73.6
76.2 45.7 80.1 29.2 63.8 58.8
76.7 57.8 80.9 42.3 66.8 66.8
77.3 69.9 81.7 51.2 71.4 71.4
78.7 78.7 82.6 61.9 75.1 75.1

67
MBH SHC
68.9 41.6
69.1 49.0
69.4 59.2
70.5 69.6
70.2 40.6
70.4 51.6
70.8 62.8
71.9 71.9
71.1 42.1
71.3 54.1
71.9 66.0
73.7 73.7
71.8 43.6
72.1 56.3
72.9 68.9
75.2 75.2

115

73
MBH SHC
75.2 26.0
75.6 36.3
75.9 46.0
76.5 55.5
75.9 26.5
76.3 37.7
76.8 47.7
77.4 57.9
76.4 26.9
76.9 39.0
77.6 49.3
78.2 60.1
76.8 27.2
77.4 40.3
78.1 50.6
78.8 62.0

61
MBH SHC
54.5 47.3
55.9 55.9
60.4 60.4
65.0 65.0
55.9 50.3
58.2 58.2
62.9 62.9
67.5 67.5
57.0 53.1
60.1 60.1
65.0 65.0
69.4 69.4
58.1 55.8
61.9 61.9
66.8 66.8
70.9 70.9

67
MBH SHC
63.0 38.9
63.3 46.2
63.8 56.5
65.1 65.1
64.5 37.8
64.7 48.9
65.3 60.2
67.6 67.6
65.6 39.5
65.8 51.5
66.6 63.7
69.5 69.5
66.4 41.0
66.6 53.9
67.7 67.1
71.0 71.0

73
MBH SHC
70.8 24.0
71.0 34.1
71.3 44.1
71.6 53.9
71.5 24.3
71.8 35.5
72.2 46.1
72.6 56.7
72.1 24.7
72.5 36.8
72.9 47.9
73.4 59.2
72.6 25.1
72.9 37.7
73.5 49.5
74.1 61.5

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

22

RT-PRC002-EN

Performance
Data

(7Ton)
Standard Efficiency

Table PD-7 Gross Cooling Capacities (MBH) 7 Ton Three Phase TCR090C3, C4, CW
85

CFM
Airflow

2700

3000

3300

3600

Enter.
Dry
Bulb
61
(F) MBH SHC
75 86.3 68.4
80
87.1 81.1
85 89.8 89.8
90 94.3 94.3
75 88.4 72.2
80 89.5 86.1
85 92.7 92.7
90
97.0 97.0
75 90.0 75.6
80 91.3 90.4
85 95.0 95.0
90 99.0 99.0
75 91.3 78.7
80 92.4 92.4
85 96.9 96.9
90 101.0 101.0

67
MBH SHC
95.3 55.9
95.7 65.3
96.3 77.0
97.1 88.8
96.6 55.4
97.1 67.7
97.7 80.3
98.7 92.8
97.5 57.3
98.1 69.8
98.9 83.1
100.0 96.2
98.2 59.2
99.0 71.7
99.9 85.7
101.0 99.3

73
MBH SHC
100.0 36.3
101.0 49.6
102.0 59.5
103.0 69.9
101.0 36.9
102.0 51.3
103.0 65.1
104.0 71.8
102.0 37.5
103.0 53.0
104.0 67.9
105.0 73.5
102.0 38.0
103.0 54.5
104.0 70.6
106.0 75.0

61
MBH SHC
79.3 64.6
80.4 77.4
84.4 84.4
89.8 89.8
81.3 68.4
82.9 82.6
87.9 87.9
92.7 92.7
83.1 72.1
84.8 84.8
90.4 90.4
95.0 95.0
84.7 75.6
87.4 87.4
92.4 92.4
96.8 96.8

Ambient Temperature (F)


95

105

Entering Wet Bulb (F)


67
73
61
MBH SHC MBH SHC MBH SHC
90.2 53.2 96.9 34.3 72.0 60.8
90.6 63.0 97.6 47.2 72.8 72.8
90.9 75.2 98.1 58.3 78.6 78.6
91.8 87.4 99.0 69.4 84.4 84.4
91.7 52.6 97.7 34.8 72.9 64.6
92.0 65.9 98.2 48.5 75.9 75.9
92.5 79.1 99.2 62.7 82.0 82.0
93.8 92.2 100.0 71.8 87.6 87.6
92.8 54.5 98.3 35.4 75.5 68.2
93.2 68.6 99.0 49.4 78.6 78.6
93.9 82.6 100.0 65.5 84.9 84.9
95.0 95.0 101.0 74.0 90.0 90.0
93.7 56.4 98.9 35.9 77.0 71.7
94.2 71.0 99.6 50.2 81.1 81.1
95.1 85.8 101.0 62.9 87.1 87.1
96.8 96.8 102.0 75.9 91.0 92.0

67
MBH SHC
83.7 50.1
84.0 59.7
84.4 72.3
85.8 85.1
85.5 49.5
85.7 63.1
86.2 76.8
87.7 87.7
86.7 51.4
86.9 66.1
87.7 80.8
90.2 90.2
87.6 53.3
87.9 69.0
89.0 84.6
92.1 92.1

115

73
MBH SHC
92.2 31.7
92.7 44.5
93.0 56.5
93.7 68.2
93.1 32.4
93.7 46.2
94.2 58.7
94.9 71.2
93.8 33.0
94.3 47.5
95.2 60.6
96.0 73.9
94.4 33.4
95.0 48.5
95.9 62.3
96.8 76.4

61
MBH SHC
64.7 57.0
66.8 66.8
72.5 72.5
78.3 78.3
66.3 60.7
69.7 69.7
75.7 75.7
81.8 81.8
67.9 64.3
72.2 72.2
78.4 78.4
84.3 84.3
69.3 67.8
74.4 74.4
80.9 80.9
86.4 86.4

67
MBH SHC
75.6 46.5
75.9 55.9
76.6 68.6
78.6 78.6
77.4 45.7
77.6 59.3
78.6 73.2
82.0 82.0
78.8 47.8
79.1 62.6
80.4 77.8
84.5 84.5
80.1 49.8
80.4 65.7
81.2 81.2
86.5 86.5

73
MBH SHC
86.3 29.1
86.6 41.5
86.9 54.1
87.2 66.1
87.4 29.5
87.7 43.3
88.0 56.6
88.5 69.7
88.2 30.1
88.6 45.0
89.0 58.9
89.6 72.9
88.8 30.6
89.2 46.3
89.9 61.1
90.6 75.9

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-8 Gross Cooling Capacities (MBH) 7 Ton Three Phase - Dual Compressor TCR090D3, D4, DW
85

CFM
Airflow

2700

3000

3300

3600

Enter.
Dry
Bulb
61
(F) MBH SHC
75 83.7 66.2
80 84.5 78.3
85
87.0 87.0
90 91.4 91.4
75 85.8 69.8
80 86.9 83.0
85 89.8 89.8
90 93.9 93.9
75
87.4 73.0
80 88.3 86.6
85 92.0 92.0
90 95.8 95.8
75 88.7 76.0
80 90.0 89.3
85 93.8 93.8
90
97.3 97.3

67
MBH SHC
92.5 54.6
92.9 63.2
93.4 74.4
94.2 85.7
93.7 53.7
94.2 65.5
94.8 77.5
95.8 89.4
94.5 55.4
95.2 67.5
95.9 80.3
97.1 92.7
95.2 57.1
96.0 69.3
96.8 82.7
98.1 95.6

73
MBH SHC
97.1 35.5
97.9 48.0
98.6 57.7
99.6 67.6
97.7 35.8
98.5 49.5
99.4 62.7
101.0 69.4
98.1 36.3
99.0 51.0
100.0 62.3
101.0 70.9
98.4 36.7
99.4 52.5
100.0 64.0
102.0 72.3

61
MBH SHC
77.8 62.9
78.9 75.2
82.3 82.3
87.6 87.6
79.8 66.5
80.8 79.3
85.7 85.7
90.3 90.3
81.5 69.9
83.3 82.8
88.2 88.2
92.4 92.4
83.0 73.2
85.2 85.2
90.1 90.1
94.1 94.1

Ambient Temperature (F)


95

105

Entering Wet Bulb (F)


67
73
61
MBH SHC MBH SHC MBH SHC
88.3 52.4 94.3 33.7 71.6 59.6
88.6 61.2 95.0 46.0 72.6 71.3
88.9 72.9 95.5 56.6 77.3 77.3
89.8 84.6 96.4 67.1 82.9 82.9
89.7 51.3 95.0 34.1 73.4 63.2
90.0 64.0 95.8 47.6 75.2 75.0
90.5 76.5 96.5 58.2 80.6 80.6
91.7 89.0 97.4 69.4 85.9 85.9
90.7 53.2 95.5 34.6 75.0 66.5
91.2 66.4 96.4 49.1 77.3 77.3
91.8 79.8 97.2 61.2 83.3 83.3
93.0 91.7 98.3 71.3 88.2 88.2
91.5 54.7 95.9 35.1 76.4 69.8
92.1 68.7 96.8 50.5 79.7 79.7
92.8 82.7 97.8 60.8 85.5 85.5
94.5 94.1 98.9 73.1 90.0 90.0

67
MBH SHC
82.8 49.8
83.1 58.5
83.4 70.4
84.2 82.2
84.4 48.7
84.6 61.6
85.1 74.6
86.6 85.9
85.6 50.5
85.8 64.4
86.5 78.3
88.3 88.3
86.5 52.3
86.8 67.0
87.7 81.7
90.1 90.1

115

73
MBH SHC
90.5 31.7
90.9 43.7
91.3 55.0
91.9 66.1
91.3 32.1
91.8 45.3
92.4 57.0
93.1 68.8
91.8 32.6
92.5 46.8
93.2 58.7
94.0 71.2
92.3 33.1
93.1 48.3
93.9 60.2
94.8 73.4

61
MBH SHC
64.9 56.2
66.4 66.4
71.9 71.9
77.4 77.4
66.6 59.7
69.1 69.1
74.9 74.9
80.7 80.7
68.0 63.0
71.6 71.6
77.6 77.6
83.3 83.3
69.4 66.3
73.8 73.8
80.0 80.0
85.2 85.2

67
MBH SHC
75.7 46.6
76.0 55.2
76.5 67.2
78.4 77.9
77.5 45.4
77.7 58.4
78.5 71.5
80.9 80.9
78.9 47.4
79.1 61.4
80.2 75.8
83.3 83.3
80.1 49.3
80.3 64.3
81.2 79.2
85.2 85.2

73
MBH SHC
85.4 29.3
85.7 41.2
85.9 52.9
86.4 64.3
86.3 29.7
86.7 42.8
87.1 55.2
87.6 67.5
87.0 30.2
87.5 44.3
88.0 57.3
88.6 70.4
87.6 30.6
88.1 45.6
88.7 59.1
89.5 73.0

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.


RT-PRC002-EN

23

Performance
Data

(8, 10Ton)
Standard Efficiency

Table PD-9 Gross Cooling Capacities (MBH) 8 Three Phase TCR102C3, C4, CW
Ambient Temperature
85

CFM
Air Flow
3060

3400

3740

4080

Enter
Dry
Bulb
61
67
73
(F) MBH SHC MBH SHC MBH SHC
75 98.2 78.0 110.0 61.6 115.0 42.2
80 99.0 92.2 110.0 74.7 116.0 57.0
85 102.0 102.0 111.0 87.6 116.0 67.6
90 108.0 108.0 112.0 101.0 118.0 78.7
75 101.0 82.3 111.0 63.6 116.0 42.5
80 102.0 97.9 112.0 77.2 117.0 58.1
85 106.0 106.0 113.0 91.0 117.0 69.3
90 111.0 111.0 114.0 105.0 118.0 80.4
75 103.0 86.4 112.0 65.0 116.0 43.0
80 103.0 103.0 113.0 79.4 117.0 59.0
85 109.0 109.0 114.0 93.9 118.0 70.8
90 113.0 113.0 115.0 108.0 119.0 81.9
75 105.0 90.0 113.0 66.2 116.0 43.5
80 106.0 106.0 114.0 81.2 118.0 59.6
85 111.0 111.0 115.0 96.4 119.0 71.9
90 115.0 115.0 116.0 111.0 120.0 83.3

95

105

Entering Wet Bulb


61
67
73
61
67
73
MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
89.7 73.5 105.0 58.7 112.0 40.3 81.5 69.3 96.8 54.8 108.0 38.0
91.0 87.9 105.0 72.4 113.0 54.4 82.5 82.5 96.9 68.5 108.0 51.9
96.2 96.2 105.0 85.9 113.0 66.7 89.4 89.4 97.2 82.3 109.0 65.1
103.0 103.0 106.0 99.4 114.0 78.6 96.8 96.8 96.8 96.8 109.0 77.7
92.4 77.9 107.0 61.0 113.0 40.7 83.8 73.5 99.5 57.5 109.0 38.6
93.0 93.0 107.0 75.7 114.0 56.2 86.2 86.2 99.6 72.4 110.0 53.8
101.0 101.0 107.0 90.2 115.0 68.4 93.7 93.7 100.0 87.5 110.0 67.4
107.0 107.0 109.0 105.0 116.0 81.0 101.0 101.0 101.0 101.0 111.0 80.8
94.8 82.1 108.0 63.1 114.0 41.3 85.8 77.6 102.0 59.9 110.0 39.3
96.8 96.8 108.0 78.6 114.0 57.0 89.5 89.5 102.0 76.0 111.0 55.5
104.0 104.0 109.0 94.0 115.0 69.9 97.6 97.6 102.0 92.3 111.0 69.3
110.0 110.0 110.0 110.0 117.0 83.0 105.0 105.0 105.0 105.0 112.0 83.4
97.0 86.1 109.0 64.9 114.0 41.9 87.7 81.5 103.0 62.1 110.0 39.8
100.0 100.0 110.0 81.1 115.0 57.8 92.6 92.6 103.0 79.2 111.0 56.3
107.0 107.0 110.0 97.3 116.0 71.0 101.0 101.0 104.0 96.3 112.0 70.9
112.0 112.0 112.0 112.0 117.0 84.7 107.0 107.0 107.0 107.0 113.0 85.7

115

61
MBH SHC
73.5 65.2
76.2 76.2
82.9 82.9
89.9 89.9
75.5 69.4
79.5 79.5
86.8 86.8
94.2 94.2
77.4 73.4
82.6 82.6
90.2 90.2
98.1 98.1
77.6 77.6
85.3 85.3
93.3 93.3
101.0 101.0

67
MBH SHC
87.2 54.4
87.4 64.1
88.0 78.0
90.6 89.9
89.6 53.1
89.7 68.0
90.6 83.2
94.2 94.2
91.6 55.5
91.7 71.6
93.0 88.2
98.0 98.0
93.2 57.8
93.5 75.2
93.3 93.3
101.0 101.0

73
MBH SHC
102.0 35.5
103.0 49.1
103.0 62.7
103.0 75.8
104.0 36.1
104.0 51.0
104.0 65.5
105.0 79.6
104.0 36.6
105.0 52.8
105.0 67.9
106.0 82.8
105.0 37.2
106.0 54.5
106.0 70.0
107.0 85.8

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-10 Gross Cooling Capacities (MBH) 10 Ton Three Phase TCR120C3, C4, CW
85

CFM
Airflow
3600

4000

4400

4800

Ambient Temperature
95

105
115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 115.0 96.2 129.0 74.8 136.0 49.8 106.0 91.1 123.0 70.8 132.0 47.2 95.4 85.9 113.0 66.2 126.0 44.2 85.5 80.9 101.0 63.2 118.0 40.7
80 116.0 116.0 130.0 91.3 137.0 67.8 108.0 107.0 123.0 88.8 133.0 65.8 99.7 99.7 113.0 84.3 127.0 62.4 91.5 91.5 101.0 79.0 119.0 58.8
85 124.0 124.0 130.0 108.0 138.0 81.4 117.0 117.0 124.0 107.0 134.0 81.0 109.0 109.0 114.0 103.0 127.0 79.4 100.0 100.0 103.0 97.4 119.0 76.5
90 130.0 130.0 132.0 125.0 139.0 96.3 124.0 124.0 124.0 124.0 135.0 96.8 117.0 117.0 117.0 117.0 128.0 96.1 109.0 109.0 109.0 109.0 119.0 94.0
75 118.0 102.0 131.0 76.6 137.0 50.5 109.0 96.9 125.0 73.9 133.0 48.0 98.1 91.6 115.0 69.6 127.0 45.0 86.9 86.9 104.0 64.4 120.0 41.7
80 121.0 120.0 132.0 94.8 138.0 69.2 113.0 113.0 125.0 93.3 134.0 67.9 104.0 104.0 116.0 89.4 128.0 64.8 95.6 95.6 104.0 84.2 120.0 61.4
85 128.0 128.0 133.0 113.0 139.0 83.4 122.0 122.0 126.0 113.0 135.0 83.3 114.0 114.0 117.0 110.0 129.0 82.6 105.0 105.0 105.0 105.0 121.0 80.5
90 133.0 133.0 134.0 131.0 141.0 98.9 128.0 128.0 128.0 128.0 136.0 100.0 122.0 122.0 122.0 122.0 130.0 101.0 114.0 114.0 114.0 114.0 121.0 99.3
75 121.0 107.0 132.0 78.6 137.0 51.2 111.0 103.0 126.0 76.8 134.0 48.8 101.0 97.2 117.0 72.8 128.0 45.9 90.0 90.0 106.0 67.7 121.0 42.5
80 124.0 124.0 133.0 97.8 139.0 70.0 117.0 117.0 127.0 97.4 135.0 69.9 108.0 108.0 118.0 94.3 129.0 66.5 99.2 99.2 106.0 89.2 122.0 63.9
85 131.0 131.0 134.0 117.0 140.0 85.1 125.0 125.0 128.0 118.0 136.0 85.6 118.0 118.0 120.0 116.0 130.0 85.4 109.0 109.0 109.0 108.0 122.0 84.0
90 136.0 136.0 136.0 136.0 142.0 101.0 131.0 131.0 131.0 131.0 137.0 103.0 125.0 125.0 125.0 125.0 131.0 104.0 118.0 118.0 118.0 118.0 123.0 104.0
75 123.0 112.0 133.0 80.3 138.0 51.9 114.0 108.0 127.0 79.1 134.0 49.6 102.0 102.0 119.0 75.9 129.0 46.7 92.8 92.8 107.0 70.8 122.0 43.3
80 127.0 127.0 134.0 101.0 139.0 70.7 121.0 121.0 128.0 101.0 136.0 71.2 112.0 112.0 120.0 98.9 130.0 68.0 102.0 102.0 108.0 94.1 122.0 65.9
85 133.0 133.0 135.0 121.0 140.0 86.3 128.0 128.0 130.0 122.0 137.0 87.5 121.0 121.0 121.0 121.0 131.0 87.9 112.0 112.0 112.0 112.0 123.0 87.3
90 137.0 137.0 137.0 137.0 142.0 103.0 133.0 133.0 133.0 133.0 138.0 106.0 128.0 128.0 128.0 128.0 132.0 108.0 120.0 120.0 120.0 120.0 124.0 109.0

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

24

RT-PRC002-EN

Performance
Data

(12, 15Ton)
Standard Efficiency

Table PD-11 Gross Cooling Capacities (MBH) 12 Ton Three Phase TCR150C3, C4, CW
Ambient Temperature
85

CFM
Airflow
4500

5000

5500

6000

Enter
Dry
Bulb
61
(F) MBH SHC
75
139 116
80
141 138
85
148 148
90
156 156
75
142 122
80
144 144
85
153 153
90
159 159
75
145 128
80
149 149
85
156 156
90
162 162
75
147 134
80
152 152
85
159 159
90
164 164

67
MBH SHC
155 89.6
156 110
156 131
158 151
157 92.5
157 114
158 136
160 157
158 94.4
159 118
160 141
162 162
159 96.3
160 121
162 145
164 164

95

73
MBH SHC
161 59.5
162 82.4
163 99.9
165 118
162 60
163 85.7
165 104
167 118
163 60.9
165 83.3
167 102
168 120
164 61.8
165 84.3
167 104
169 122

105

Entering Wet Bulb


61
67
73
MBH SHC MBH SHC MBH SHC
128 110 148 85.5 158 56.9
130 130 148 107 159 78.8
141 141 148 128 160 97.3
149 149 150 150 161 116
132 117 150 89 159 57.6
136 136 151 112 160 82
146 146 152 135 161 101
154 154 153 153 162 120
135 123 152 92.3 159 58.5
141 141 152 117 160 82.8
150 150 153 141 162 102
157 157 157 157 164 123
137 129 153 95 160 59.3
144 144 154 121 161 82.9
153 153 155 146 162 105
159 159 159 159 164 125

MBH
118
122
132
142
121
127
138
147
124
132
142
150
127
136
146
153

61
SHC
105
122
132
142
112
127
138
147
118
132
142
150
124
136
146
153

MBH
138
138
139
142
141
141
142
147
143
143
145
150
144
145
147
153

67
SHC
80.9
103
124
142
84.6
108
132
147
88.1
113
139
150
91.5
118
145
153

115

MBH
152
152
153
154
153
154
155
156
154
155
156
157
155
156
157
159

73
SHC
53.8
75.4
95.5
115
54.7
78.3
98.9
120
55.6
79.9
102
124
56.4
81.4
105
128

MBH
108
114
124
134
111
119
129
139
113
123
134
143
115
127
137
145

61
SHC
99.8
114
124
134
106
119
129
139
113
123
134
143
115
127
137
145

MBH
127
127
129
134
130
130
132
139
132
132
134
143
134
134
137
145

67
SHC
76.1
97.6
119
134
79.9
103
127
139
83.4
109
134
143
86.8
114
137
145

MBH
144
144
145
145
145
146
146
147
146
147
148
149
147
148
149
150

73
SHC
50.2
71.7
92.5
113
51.1
74.6
96.4
118
51.9
77
99.9
123
52.8
78.9
103
127

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-12 Gross Cooling Capacities (MBH) 15 Ton Three Phase TCR180B3, B4, BW
Ambient Temperature
85

CFM
Airflow
5400

6000

6600

7200

Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

61

MBH
164
160
171
181
169
166
177
186
172
175
182
190
175
178
186
193

SHC
131
160
171
181
138
166
177
186
144
167
182
190
150
173
186
193

67
MBH
184
185
185
186
187
187
188
186
188
190
191
190
190
191
193
195

SHC
103
126
148
170
107
131
154
186
110
135
159
190
112
138
164
185

95

73
MBH
195
196
197
199
196
197
199
201
198
199
201
203
199
200
202
204

SHC
71.5
95.9
116
135
72.4
98.3
118
139
73.5
99.8
121
142
74.5
102
124
145

61
MBH
154
155
163
174
158
161
170
180
161
165
175
184
164
170
179
188

SHC
125
146
163
174
132
154
170
180
139
161
175
184
145
168
179
188

67
MBH
177
177
177
174
179
180
180
179
182
182
183
186
183
184
185
189

SHC
99.7
122
145
174
103
128
152
179
107
132
158
178
110
136
163
183

105
Entering Wet Bulb
73
61
MBH
190
191
191
193
191
193
194
195
193
193
195
197
194
195
197
199

SHC
68.9
92.5
114
134
69.7
95.5
117
138
70.7
97.3
119
142
71.7
98.8
122
145

MBH
143
146
154
166
146
151
161
172
150
155
167
176
153
159
171
180

SHC
120
139
154
166
126
147
161
172
133
155
167
176
139
159
171
180

115

67
MBH
167
167
167
169
170
170
171
174
172
173
174
178
174
175
171
181

SHC
94.4
117
140
159
98.3
123
148
167
102
128
155
174
105
133
171
180

73
MBH
183
183
184
185
184
185
186
188
186
186
188
190
187
188
190
191

SHC
65.4
88.6
111
131
66.2
91.6
114
136
67.3
94.2
117
141
68.3
96
120
145

61
MBH
131
135
145
157
135
140
152
163
133
145
157
168
137
149
162
172

SHC
114
133
145
157
120
140
152
163
133
145
157
168
137
149
162
172

67
MBH
155
155
155
159
158
158
159
164
161
161
157
168
163
163
162
172

SHC
88.9
112
135
153
92.9
118
143
162
96.6
123
157
168
100
129
162
172

73
MBH
174
174
174
175
176
176
177
178
177
178
179
180
178
179
180
181

SHC
61.4
84.3
107
128
62.3
87.3
111
134
63.3
90.2
114
139
64.2
92.5
118
145

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.


RT-PRC002-EN

25

Performance
Data

(17, 20Ton)
Standard Efficiency

Table PD-13 Gross Cooling Capacities (MBH) 17 Ton Three Phase TCR210C3, C4, CW
Ambient Temperature
95

85

CFM
Airflow
6300

7000

7700

8400

Enter
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

61

MBH
189
190
196
207
195
196
203
214
199
200
209
219
202
203
214
223

SHC
149
175
196
207
157
185
203
214
164
195
209
219
170
203
214
223

67
MBH
213
213
214
215
216
217
218
219
219
220
221
223
220
222
223
225

SHC
118
144
168
193
122
149
175
201
126
153
181
209
129
157
186
215

73
MBH
227
228
229
231
229
230
232
234
230
231
234
236
231
232
234
238

SHC
82.8
110
133
155
83.6
113
136
159
84.8
117
138
162
86.1
118
143
166

61
MBH
177
177
186
199
181
183
194
206
185
187
201
212
189
193
206
216

SHC
142
168
186
199
150
178
194
206
157
187
201
212
164
193
206
216

Entering Wet Bulb


67
73
MBH
204
204
205
206
208
208
209
210
210
211
212
214
213
214
215
216

SHC
113
139
164
190
117
145
172
199
121
151
179
208
125
155
186
216

MBH
221
222
222
224
223
224
225
227
225
225
228
230
226
227
229
232

SHC
79.3
106
130
153
80.2
109
134
158
81.6
112
137
162
82.9
114
140
166

105

61
MBH
163
165
176
189
168
169
183
197
171
176
190
203
175
181
196
208

SHC
135
161
176
189
142
169
183
197
149
176
190
203
156
181
196
208

115

67
MBH
192
192
192
194
196
197
197
197
200
200
201
203
202
203
204
208

SHC
107
133
159
185
112
140
167
197
116
146
175
203
120
151
183
208

73
MBH
213
213
214
215
215
216
217
218
217
218
219
221
218
219
221
223

SHC
75.1
101
126
150
76.3
105
131
156
77.7
108
135
161
78.7
110
138
166

61
MBH
149
152
165
178
153
158
172
186
157
164
179
193
160
170
185
198

SHC
128
152
165
178
135
158
172
186
142
164
179
193
149
170
185
198

67
MBH
178
178
178
178
182
183
183
186
186
186
187
192
189
189
190
198

73

SHC
100
126
152
178
105
133
161
186
109
139
169
192
113
145
178
198

MBH
202
203
203
204
205
206
206
207
207
208
209
210
209
210
211
213

SHC
70.5
96.1
122
146
71.6
99.6
127
153
72.7
103
131
159
73.8
106
135
164

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-14 Gross Cooling Capacities (MBH) 20 Ton Three Phase TCR240B3, B4, BW
85

CFM
Airflow

7200

8000

8800

9600

Enter.
Dry
Bulb
61
(F) MBH SHC
75
228 183
80
230 216
85
237 237
90
248 248
75
233 192
80
236 228
85
244 244
90
254 254
75
237 200
80
240 238
85
249 249
90
258 258
75
240 208
80
243 243
85
253 253
90
261 261

67
MBH SHC
249 141
250 171
252 201
254 231
251 145
253 177
255 209
258 240
254 148
256 181
258 215
261 248
255 151
258 185
260 220
263 254

73
MBH SHC
260 95.9
263 130
267 149
270 175
262 96.7
265 132
268 159
271 187
264 98.1
267 134
270 162
273 190
265 99.4
268 135
271 164
274 194

61
MBH SHC
209 173
212 207
224 224
240 240
215 183
217 217
234 234
248 248
220 192
225 225
241 241
254 254
224 202
232 232
247 247
259 259

95

Ambient Temperature (F)


105

67
MBH SHC
241 135
242 168
242 201
245 233
246 141
246 177
247 211
250 246
249 146
249 184
251 221
254 254
251 151
252 190
254 229
259 259

Entering Wet Bulb (F)


73
61
67
MBH SHC MBH SHC MBH SHC
260 92.7 190 162 222 126
262 126 193 193 222 159
263 156 208 208 223 192
265 186 224 224 228 226
262 93.9 195 172 227 132
264 131 201 201 228 168
266 161 218 218 229 204
268 192 234 234 234 234
264 95.5 199 182 232 138
265 133 208 208 232 176
268 165 226 226 235 216
270 198 243 243 242 242
266 97.1 203 191 236 143
268 143 215 215 236 185
270 169 233 233 239 227
272 203 249 249 249 249

115

73
MBH SHC
253 87.6
253 120
254 153
254 185
256 89.3
257 125
257 160
258 194
258 90.8
259 130
260 166
262 202
260 92.1
262 134
263 172
264 210

61
MBH SHC
170 152
177 177
192 192
208 208
175 162
184 184
200 200
217 217
179 171
191 191
208 208
225 225
183 180
197 197
214 214
233 233

67
MBH SHC
200 115
200 148
202 181
208 208
204 121
205 157
207 194
217 217
208 127
209 166
212 205
225 225
212 132
212 174
217 217
232 232

73
MBH SHC
235 79.6
235 112
235 145
235 177
239 81.4
240 117
240 153
241 188
243 83.3
244 122
244 160
245 198
246 84.9
247 126
247 167
248 208

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

26

RT-PRC002-EN

Performance
Data

(25 Ton)
Standard Efficiency

Table PD-15 Gross Cooling Capacities (MBH) 25 Ton Three Phase TCR300B3, B4, BW
85

CFM
Airflow

9000

10000

10500

11000

Enter.
Dry
Bulb
61
(F) MBH SHC
75
266 224
80
270 268
85
286 286
90
301 301
75
272 237
80
277 277
85
294 294
90
308 308
75
275 243
80
282 282
85
298 298
90
312 312
75
278 248
80
286 286
85
301 301
90
314 314

67
MBH SHC
299 174
300 215
301 255
304 295
303 180
304 223
306 266
310 309
305 183
306 227
308 272
311 311
306 185
308 231
310 277
314 314

73
MBH SHC
319 118
321 161
323 196
326 232
322 120
324 171
327 208
329 239
323 122
325 174
328 216
330 256
324 123
325 160
327 224
330 266

61
MBH SHC
247 215
252 252
272 272
289 289
253 227
262 262
282 282
297 297
256 233
267 267
286 286
301 301
258 239
271 271
289 289
304 304

95

Ambient Temperature (F)


105

67
MBH SHC
285 167
285 209
286 250
289 289
290 174
290 219
291 263
297 297
291 177
292 223
294 270
301 301
293 181
294 228
296 276
304 304

Entering Wet Bulb (F)


73
61
67
MBH SHC MBH SHC MBH SHC
309 113 228 205 266 172
311 155 237 237 266 200
312 194 256 256 267 242
314 231 275 275 275 275
312 115 234 218 271 165
314 161 246 246 271 211
316 200 266 266 273 257
318 240 284 284 284 284
314 117 236 223 273 188
315 162 250 250 273 216
317 203 270 270 276 264
320 244 288 288 288 288
315 118 239 229 275 172
316 163 254 254 276 221
319 205 274 274 278 271
321 248 291 291 291 291

115

73
MBH SHC
297 108
297 149
298 189
300 229
300 109
301 155
302 197
304 239
301 111
302 157
304 200
306 244
302 113
304 160
305 204
307 249

61
MBH SHC
209 196
221 221
240 240
259 259
214 208
229 229
249 249
268 268
216 214
233 233
253 253
273 273
217 217
237 237
257 257
276 276

67
MBH SHC
244 163
244 190
246 233
259 259
249 156
249 201
253 248
268 268
251 178
251 206
256 255
272 272
253 184
253 212
257 257
276 276

73
MBH SHC
280 99.9
280 142
281 183
282 224
284 102
284 147
285 192
286 235
285 103
286 150
286 196
288 241
286 104
287 153
288 200
289 246

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity
4. Table is for 460 volt capacity. For capacity at 230 volt, multiply table capacity by 101%.

RT-PRC002-EN

27

Performance
Data

(3, 4Ton)
High Efficiency

Table PD-16 Gross Cooling Capacities (MBH) 3 Ton Three Phase TCD037C3, C4
95

Ambient Temperature (F)


105

67
MBH SHC
41.5 22.3
41.6 27.6
41.7 32.8
41.9 38.0
42.3 23.3
42.4 29.0
42.6 34.7
43.0 40.3
43.0 24.2
43.1 30.3
43.3 36.3
43.8 42.4
43.5 25.1
43.7 31.5
44.0 37.9
44.6 44.2

Entering Wet Bulb (F)


73
61
67
MBH SHC MBH SHC MBH SHC
45.1 15.5 32.7 26.3 38.3 21.6
45.3 21.0 33.1 31.7 38.4 25.9
45.5 26.0 35.0 35.0 38.5 31.1
45.8 30.8 37.6 37.6 38.9 36.4
45.6 15.8 33.7 28.0 39.4 21.7
45.9 21.8 34.3 34.0 39.5 27.5
46.2 26.9 36.7 36.7 39.6 33.2
46.6 32.0 39.5 39.5 40.1 39.0
46.0 16.1 34.5 29.6 40.1 22.7
46.4 22.5 35.3 35.3 40.2 28.9
46.7 27.7 38.2 38.2 40.4 35.1
47.2 33.0 40.9 40.9 40.9 40.9
46.1 16.3 35.3 31.2 40.7 23.5
46.5 22.7 36.5 36.5 40.8 30.2
47.0 28.3 39.6 39.6 41.1 36.8
47.6 33.9 42.0 42.0 42.0 42.0

85

CFM
Airflow
1080

1200

1320

1440

Enter.
Dry
Bulb
61
(F) MBH SHC
75 39.0 29.9
80 39.2 35.3
85 40.0 40.0
90 42.5 42.5
75 40.2 31.6
80 40.4 37.5
85 41.8 41.8
90 44.0 44.0
75 41.1 33.3
80 41.5 39.7
85 43.1 43.1
90 45.2 45.2
75
41.9 34.8
80 42.4 41.7
85 44.2 44.2
90 46.1 46.1

67
MBH SHC
43.8 23.8
44.0 29.0
44.2 34.0
44.4 39.1
44.5 24.6
44.7 30.2
45.0 35.6
45.3 41.1
45.0 25.5
45.3 31.1
45.6 37.0
46.0 42.7
45.2 25.9
45.7 32.0
46.1 38.1
46.6 44.1

73
MBH SHC
45.9 16.4
46.3 22.0
46.6 26.5
47.1 30.9
46.3 16.6
46.6 22.9
47.0 27.1
47.6 31.7
46.5 16.9
47.0 23.9
47.5 27.7
48.0 32.4
46.8 17.1
47.3 24.1
48.0 28.3
48.4 33.0

61
MBH SHC
36.0 28.1
36.2 33.5
37.5 37.5
40.2 40.2
37.0 29.9
37.4 35.8
39.3 39.3
42.0 42.0
37.9 31.5
38.5 38.0
40.9 40.9
43.3 43.3
38.7 33.1
39.4 39.4
42.1 42.1
44.3 44.3

115

73
MBH SHC
42.8 14.3
43.0 19.6
43.2 24.8
43.3 29.7
43.4 14.6
43.6 20.4
43.8 25.9
44.1 31.2
43.8 14.9
44.1 21.2
44.4 26.8
44.8 32.5
44.2 15.2
44.5 21.8
44.9 27.6
45.3 33.6

61
67
MBH SHC MBH SHC
29.3 24.4 34.7 19.8
29.9 29.9 34.8 2 4.1
32.3 32.3 35.0 29.3
34.9 34.9 35.5 34.7
30.2 26.1 35.7 19.9
31.1 31.1 35.8 25.6
33.9 33.9 36.0 31.4
36.7 36.7 36.6 36.6
31.0 27.7 36.5 20.9
32.4 32.4 36.6 27.1
35.3 35.3 36.9 33.3
38.2 38.2 38.1 38.1
31.7 29.3 37.2 21.8
33.6 33.6 37.3 28.5
36.6 36.6 37.7 35.3
39.3 39.3 39.3 39.3

73
MBH SHC
39.9 12.9
40.0 18.1
40.2 23.3
40.3 28.4
40.6 13.2
40.7 18.9
40.9 24.5
41.1 30.0
41.0 13.5
41.3 19.7
41.5 25.6
41.7 31.4
41.4 13.7
41.7 20.4
42.0 26.6
42.3 32.8

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-17 Gross Cooling Capacities (MBH) 4 Ton Three Phase TCR049C3, C4
Ambient Temperature
85

CFM
Airflow
1440

1600

1760

1920

Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

61

MBH
47.6
48.1
50.4
52.9
48.8
49.5
52.0
54.3
49.8
50.7
53.3
55.3
50.6
51.9
54.2
56.0

SHC
38.7
46.1
50.4
52.9
40.9
49.2
52.0
54.3
43.1
50.7
53.3
55.3
45.1
51.9
54.2
56.0

95

67
MBH
53.0
53.2
53.5
53.9
53.5
53.9
54.2
54.8
53.9
54.4
54.8
55.5
54.4
54.9
55.4
56.0

SHC
30.0
36.8
43.7
50.5
30.8
38.2
45.6
52.8
31.6
39.3
47.1
54.6
32.3
40.4
48.5
56.0

73
MBH
55.7
56.2
57.0
57.3
56.1
56.7
57.4
57.7
56.5
57.1
57.8
58.2
56.8
57.5
58.2
58.6

SHC
20.2
27.5
33.7
39.2
20.5
28.0
34.3
40.1
20.9
28.5
34.9
41.0
21.2
28.8
35.5
41.9

61
MBH
43.9
44.6
47.5
50.6
45.0
46.0
49.5
52.3
46.0
47.7
51.0
53.6
46.9
49.2
52.2
54.7

SHC
36.6
44.1
47.5
50.6
38.9
46.0
49.5
52.3
41.1
47.7
51.0
53.6
43.2
49.2
52.2
54.7

67
MBH
50.4
50.5
50.7
51.2
51.2
51.4
51.6
52.2
51.9
52.1
52.5
53.6
52.5
52.8
53.2
54.7

SHC
28.4
35.6
42.7
49.9
29.6
37.4
45.1
52.2
30.8
39.1
47.4
53.6
31.9
40.6
49.4
54.7

105
Entering Wet Bulb
73
61
MBH
54.3
54.7
55.0
55.5
54.5
54.9
55.5
56.1
54.9
55.4
55.9
56.5
55.3
55.7
56.3
56.9

SHC
19.1
26.5
32.8
39.3
19.4
27.0
33.7
40.6
19.7
28.9
34.5
41.6
20.1
29.2
35.3
42.7

MBH
40.0
41.0
44.3
47.6
41.0
42.7
46.2
49.5
42.0
44.3
47.9
50.9
42.8
45.7
49.3
52.1

SHC
34.5
41.0
44.3
47.6
36.8
42.7
46.2
49.5
38.9
44.3
47.9
50.9
41.0
45.7
49.3
52.1

115

67
MBH
46.6
46.7
46.9
47.6
47.7
47.8
48.1
49.5
48.5
48.6
49.0
50.9
49.1
49.2
49.8
52.1

SHC
27.6
33.7
40.9
47.6
27.9
35.7
43.6
49.5
29.1
37.6
46.2
50.9
30.2
39.4
48.5
52.1

73
MBH
51.9
52.2
52.3
52.6
52.6
52.8
53.1
53.4
53.1
53.3
53.7
54.1
53.5
53.8
54.3
54.7

SHC
17.8
25.0
31.9
38.6
18.1
26.0
33.3
40.5
18.5
26.8
34.5
42.3
18.9
27.5
35.6
43.8

61
MBH
35.9
37.6
40.9
44.2
36.8
39.2
42.7
46.2
37.7
40.7
44.3
47.7
38.3
42.0
45.8
48.9

SHC
32.3
37.6
40.9
44.2
34.5
39.2
42.7
46.2
36.7
40.7
44.3
47.7
38.3
42.0
45.8
48.9

67
MBH
42.2
42.3
42.6
44.2
43.2
43.3
43.8
46.2
44.0
44.1
44.8
47.7
44.7
44.9
45.8
48.9

73

SHC
25.6
31.5
38.8
44.2
25.7
33.6
41.5
46.2
27.0
35.5
44.2
47.7
28.2
37.4
45.8
48.9

MBH
48.5
48.6
48.7
48.9
49.1
49.3
49.5
49.7
49.7
49.9
50.1
50.4
50.1
50.3
50.7
51.0

SHC
16.1
23.3
30.4
37.3
16.5
24.3
32.0
39.5
16.8
25.4
33.4
41.5
17.2
26.2
34.7
43.3

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

28

Indicates both downflow and horizontal units.

RT-PRC002-EN

Performance
Data

(5, 6Ton)
High Efficiency

Table PD-18 Gross Cooling Capacities (MBH) 5 Ton Three Phase TCR061C3, C4
Ambient Temperature
85

CFM
Airflow
1800

2000

2200

2400

105
115
Enter.
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

56.5
57.0
59.8
62.8
57.8
58.7
61.6
64.5
58.9
60.0
63.1
65.8
59.8
61.3
64.3
66.8

46.0
55.0
59.8
62.8
48.7
58.6
61.6
64.5
51.2
60.0
63.1
65.8
53.5
61.3
64.3
66.8

62.7
63.0
63.3
63.8
63.5
63.9
64.3
65.0
64.2
64.6
65.1
66.0
64.7
65.2
65.8
66.8

35.6
43.9
52.2
60.5
36.8
45.7
54.6
63.5
37.8
47.3
56.8
66.0
38.7
48.7
58.8
66.8

95

66.3
66.8
67.4
68.0
66.8
67.3
68.0
68.8
67.2
67.8
68.7
69.3
67.5
68.2
69.3
69.8

23.9
33.4
39.8
47.1
24.3
34.9
40.8
48.5
24.7
36.0
41.8
49.7
25.0
36.3
42.8
50.8

52.0
52.8
56.3
59.8
53.3
54.5
58.5
61.7
54.3
56.4
60.1
63.2
55.3
58.0
61.4
64.3

43.6
52.6
56.3
59.8
46.2
54.5
58.5
61.7
48.7
56.4
60.1
63.2
51.2
58.0
61.4
64.3

59.3
59.5
59.7
60.4
60.3
60.5
60.8
61.7
61.0
61.3
61.7
63.2
61.6
61.9
62.5
64.3

33.5
42.2
50.8
59.4
35.0
44.3
53.6
61.7
36.3
46.3
56.3
63.2
37.5
48.1
58.6
64.3

64.0
64.4
64.8
65.3
64.5
64.9
65.5
66.1
65.0
65.4
66.1
66.8
65.3
66.1
66.6
67.3

22.4
31.2
39.0
46.8
22.8
32.0
40.2
48.6
23.2
32.7
41.3
50.2
23.6
33.3
42.3
51.6

47.3
48.5
52.4
56.3
48.5
50.5
54.6
58.3
49.5
52.3
56.5
59.9
50.5
53.9
58.0
61.2

41.0
48.5
52.4
56.3
43.6
50.5
54.6
58.3
46.1
52.3
56.5
59.9
48.6
53.9
58.0
61.2

54.6
54.8
55.1
56.2
55.9
56.0
56.5
58.4
56.9
57.0
57.7
60.1
57.7
57.8
58.6
61.5

33.0
39.8
48.5
56.2
32.7
42.2
51.7
58.4
34.2
44.5
54.9
60.1
35.6
46.6
57.8
61.5

61.3
61.5
61.7
62.0
62.0
62.3
62.5
62.9
62.5
62.9
63.3
63.7
63.0
63.3
63.8
64.3

20.8
29.4
37.9
46.2
21.2
30.6
39.7
48.6
21.6
31.8
41.2
50.8
21.9
32.6
42.6
52.7

42.4
44.5
48.3
52.2
43.5
46.3
50.3
54.5
44.5
47.9
52.2
56.1
45.2
49.4
53.8
57.5

38.4
44.5
48.3
52.2
41.0
46.3
50.3
54.5
43.5
47.9
52.2
56.1
45.2
49.4
53.8
57.

49.4
49.7
50.1
52.1
50.6
50.7
51.4
54.3
51.5
51.6
52.6
56.2
52.2
52.5
53.7
5 57.6

30.6
37.3
46.0
52.1
30.2
39.6
49.2
54.3
31.6
41.9
52.4
56.2
33.0
44.1
53.7
57.6

56.8
56.9
57.1
57.3
57.5
57.7
57.9
58.2
58.0
58.3
58.6
59.0
58.5
58.8
59.2
59.6

18.7
27.3
35.8
44.2
19.1
28.5
37.7
46.8
19.5
29.7
39.4
49.2
19.8
30.7
41.0
51.3

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-19 Gross Cooling Capacities (MBH) 6 Ton Three Phase TCR074C3, C4
Ambient Temperature
85

CFM
Airflow
2250

2500

2750

3000

Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

61

MBH
68.1
69.1
72.2
75.5
69.5
70.6
74.1
77.3
70.5
72.3
75.7
78.6
71.4
73.6
76.9
79.7

SHC
57.0
68.4
72.2
75.5
60.2
70.6
74.1
77.3
63.1
72.3
75.7
78.6
65.7
73.6
76.9
79.7

67
MBH
74.7
75.0
75.5
76.3
75.5
76.0
76.5
77.6
76.2
76.8
77.4
78.6
76.8
77.4
78.2
79.6

SHC
43.2
53.4
63.7
73.9
44.5
55.5
66.5
77.3
45.7
57.3
69.0
78.6
46.7
59.0
71.3
79.6

95

73
MBH
78.7
79.4
80.7
80.8
79.3
80.2
81.1
81.6
79.7
80.8
81.6
82.2
80.1
81.0
82.1
82.8

SHC
28.8
43.0
48.8
56.9
29.1
43.9
49.7
58.6
29.7
44.8
50.6
60.0
30.1
45.8
51.5
61.4

61
MBH
62.9
64.0
68.6
72.2
64.3
66.4
70.6
74.1
65.5
68.4
72.3
75.5
66.7
69.9
73.6
76.7

SHC
54.2
64.0
68.6
72.2
57.4
66.4
70.6
74.1
60.5
68.4
72.3
75.5
63.5
69.9
73.6
76.7

67
MBH
70.8
71.0
71.3
72.2
71.7
72.0
72.5
74.0
72.4
72.8
73.5
75.5
73.1
73.5
74.4
76.7

SHC
41.1
51.8
62.5
72.2
42.8
54.3
65.8
74.0
44.3
56.6
68.8
75.5
45.6
58.6
71.6
76.7

105
Entering Wet Bulb
73
61
MBH
75.7
76.1
76.8
77.4
76.3
76.8
77.6
78.3
76.8
77.5
78.2
79.0
77.2
78.3
78.8
79.6

SHC
27.0
37.7
47.1
56.7
27.4
38.6
48.6
58.8
28.0
39.4
49.8
60.6
28.4
40.3
51.0
62.3

MBH
57.3
59.4
64.0
68.2
58.7
61.7
66.3
70.2
59.8
63.6
68.1
71.7
60.9
65.4
69.5
73.0

SHC
51.2
59.4
64.0
68.2
54.4
61.7
66.3
70.2
57.5
63.6
68.1
71.7
60.5
65.4
69.5
73.0

115

67
MBH
65.8
66.0
66.4
68.2
66.8
67.0
67.6
70.2
67.7
67.9
68.7
71.7
68.3
68.6
69.5
73.0

SHC
38.5
49.5
60.4
68.2
40.3
52.3
64.2
70.2
42.0
54.8
67.6
71.7
43.6
57.3
69.5
73.0

73
MBH
71.9
72.3
72.7
73.1
72.5
72.9
73.5
74.1
73.1
73.5
74.2
74.8
73.5
74.0
74.8
75.4

SHC
25.0
35.8
45.9
56.0
25.4
37.0
47.7
58.5
25.8
38.0
49.3
60.8
26.3
38.8
50.8
62.9

61
MBH
51.5
54.5
59.1
63.6
52.7
56.6
61.3
65.7
53.6
58.4
63.3
67.3
55.0
60.0
64.8
68.6

SHC
48.2
54.5
59.1
63.6
51.3
56.6
61.3
65.7
53.6
58.4
63.3
67.3
55.0
60.0
64.8
68.6

67
MBH
59.3
59.5
60.2
63.5
60.5
60.7
61.7
65.8
61.4
61.7
63.1
67.5
62.2
62.6
64.9
68.9

SHC
38.3
46.4
57.5
63.5
37.4
49.3
61.5
65.8
39.2
52.1
63.1
67.5
40.9
54.8
64.9
68.9

73
MBH
67.4
67.6
67.8
68.1
68.2
68.5
68.7
69.1
68.9
69.2
69.5
69.9
69.4
69.7
70.1
70.7

SHC
22.6
33.5
44.3
54.9
23.1
35.0
46.6
58.0
23.6
36.5
48.7
61.0
24.1
37.7
50.7
63.7

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Indicates both downflow and horizontal units.

RT-PRC002-EN

29

Performance
Data

(7, 7Ton)
High Efficiency

Table PD-20 Gross Cooling Capacities (MBH) 7 Ton Three Phase TCR086C3, C4
Ambient Temperature
85

CFM
Airflow
2250

2500

2750

3000

Enter.
Dry
Bulb
61
(F) MBH SHC
75 76.9 60.9
80
77.4 72.1
85 79.7 79.7
90 83.4 83.4
75 78.6 64.1
80 79.3 76.3
85 82.1 82.1
90 85.6 85.6
75 79.8 67.1
80 80.8 80.0
85 84.0 84.0
90
87.4 87.4
75 80.8 69.7
80 81.8 81.8
85 85.6 85.6
90 88.7 88.7

67
MBH SHC
84.3 47.2
84.6 57.6
85.0 67.9
85.6 78.2
85.4 48.9
85.8 59.8
86.3 70.8
87.1 81.7
85.9 49.9
86.7 61.5
87.4 73.3
88.3 84.8
86.4 50.8
87.3 62.9
88.1 75.3
89.2 87.2

95

73
MBH SHC
87.7 32.1
88.5 43.4
89.2 54.3
89.9 60.6
88.3 32.4
89.3 44.2
90.0 61.4
90.8 62.1
88.8 32.9
89.8 44.8
90.9 54.3
91.5 63.5
89.2 33.4
90.3 45.3
91.3 61.4
92.1 64.6

61
MBH SHC
71.6 58.0
72.3 69.2
75.6 75.6
80.0 80.0
73.3 61.3
74.4 73.6
78.5 78.5
82.4 82.4
74.8 64.4
76.0 76.0
80.5 80.5
84.3 84.3
76.1 67.4
78.1 78.1
82.3 82.3
85.9 85.9

67
MBH SHC
80.5 45.0
80.7 55.8
81.0 66.4
81.6 77.1
81.7 46.8
82.0 58.4
82.4 69.8
83.3 81.2
82.7 48.5
83.1 60.6
83.5 72.9
84.3 84.3
83.4 49.8
83.9 62.7
84.5 75.7
85.9 85.9

105
Entering Wet Bulb
73
61
MBH SHC MBH SHC
86.2 30.6 65.9 54.9
86.8 41.8 66.9 66.2
87.2 51.5 71.0 71.0
87.9 61.1 75.9 75.9
86.6 31.0 67.5 58.2
87.1 42.8 68.8 68.8
88.1 52.9 73.9 73.9
88.9 63.2 78.4 78.4
86.8 31.4 68.9 61.3
87.7 45.6 71.2 71.2
88.6 54.0 76.3 76.3
89.6 64.8 80.5 80.5
87.1 31.8 70.2 64.3
88.0 45.9 73.3 73.3
89.0 54.0 78.2 78.2
90.0 66.1 82.2 82.2

67
MBH SHC
75.7 42.4
75.8 53.3
76.0 64.1
76.9 75.2
77.0 44.3
77.2 56.1
77.5 67.9
78.4 78.4
78.0 46.0
78.2 58.7
78.7 71.3
80.4 80.4
78.9 47.6
79.1 61.1
79.8 74.6
82.2 82.2

115

73
MBH SHC
82.6 28.7
82.9 39.6
83.2 50.0
83.7 60.0
83.4 29.2
83.9 41.1
84.3 51.9
84.9 62.6
84.1 29.7
84.5 42.3
85.2 53.5
85.8 65.0
84.7 30.2
85.2 43.2
85.9 55.0
86.6 67.1

61
MBH SHC
60.0 51.7
61.3 61.3
66.1 66.1
71.0 71.0
61.4 55.0
63.8 63.8
68.8 68.8
73.8 73.8
62.8 58.1
66.0 66.0
71.2 71.2
75.9 75.9
64.0 61.1
67.9 67.9
73.3 73.3
77.7 77.7

67
MBH SHC
69.3 42.0
69.6 50.3
69.9 61.1
71.0 71.0
70.9 41.3
71.1 53.2
71.6 65.1
73.8 73.8
72.2 43.2
72.3 56.0
73.1 68.9
75.9 75.9
73.1 44.9
73.3 58.6
74.3 72.6
77.6 77.6

73
MBH SHC
77.8 26.4
78.0 37.2
78.3 47.9
78.5 58.2
78.7 26.9
79.0 38.7
79.3 50.1
79.7 61.2
79.4 27.3
79.8 40.1
80.2 52.0
80.7 64.0
80.1 27.8
80.4 41.3
81.0 53.9
81.5 66.5

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-21 Gross Cooling Capacities (MBH) 7 Ton Three Phase TCR091D3, D4
Ambient Temperature
85

CFM
Airflow
2700

3000

3300

3600

Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

61

MBH
80.5
81.5
85.2
89.3
82.3
83.1
87.7
91.6
83.8
85.3
89.6
93.4
84.9
87.1
91.2
94.7

SHC
66.3
79.1
85.2
89.3
69.9
83.1
87.7
91.6
73.3
85.3
89.6
93.4
76.4
87.1
91.2
94.7

67
MBH
89.2
89.5
89.9
90.8
90.2
90.7
91.3
92.4
91.1
91.8
92.4
93.8
91.8
92.6
93.4
94.7

95

73

SHC MBH
50.9 93.5
62.8 95.0
74.6 95.1
86.3 96.1
52.7 94.1
65.2 95.3
77.8 95.8
90.2 96.8
54.1 94.5
67.3 95.7
80.7 96.6
93.5 97.5
55.3 94.9
69.2 96.1
83.2 97.3
94.7 98.0

SHC
34.3
45.5
56.4
66.6
34.6
46.5
57.6
68.2
35.2
47.6
58.8
69.6
35.7
48.7
60.0
71.0

61
MBH
74.3
75.0
80.6
85.3
76.1
77.9
83.4
87.8
77.6
80.5
85.5
89.7
79.1
82.6
87.3
91.2

SHC
62.9
75.0
80.6
85.3
66.6
77.9
83.4
87.8
70.1
80.5
85.5
89.7
73.4
82.6
87.3
91.2

67
MBH
84.5
84.7
85.0
86.2
85.7
86.0
86.5
87.8
86.7
87.1
87.8
89.7
87.5
88.0
88.9
91.2

105
Entering Wet Bulb
73
61

SHC MBH
48.4 90.8
60.7 91.4
72.9 92.0
85.1 92.7
50.4 91.6
63.6 92.1
76.7 92.9
87.8 93.8
52.3 92.1
66.2 92.7
80.1 93.7
89.7 94.6
53.8 92.4
68.5 93.5
83.2 94.3
91.2 95.3

SHC
32.5
45.0
55.7
66.6
33.0
46.0
57.4
69.0
33.5
46.9
58.9
71.1
34.0
47.5
60.0
72.9

MBH
67.8
69.8
75.3
80.6
69.5
72.5
78.3
83.2
71.0
74.9
80.6
85.2
72.3
77.1
82.5
86.9

SHC
59.5
69.8
75.3
80.6
63.1
72.5
78.3
83.2
66.6
74.9
80.6
85.2
70.0
77.1
82.5
86.9

115

67
MBH
78.5
78.7
79.1
80.6
79.9
80.1
80.7
83.1
81.0
81.2
82.1
85.2
81.9
82.2
83.3
86.8

SHC
45.5
57.9
70.3
80.6
47.5
61.0
74.6
83.1
49.5
64.0
78.4
85.2
51.3
66.7
82.0
86.8

73
MBH
86.3
86.8
87.1
87.7
87.2
87.7
88.2
88.8
87.8
88.3
89.1
89.8
88.4
89.0
89.8
90.6

61

SHC MBH
30.2 61.1
42.5 64.2
54.1 69.7
65.5 75.2
30.7 62.7
44.2 66.7
56.1 72.5
68.4 77.9
31.2 64.1
45.2 69.0
58.0 74.9
70.9 80.0
31.7 64.9
46.2 71.0
59.6 76.9
73.3 81.8

SHC
56.0
64.2
69.7
75.2
59.6
66.7
72.5
77.9
63.1
69.0
74.9
80.0
64.9
71.0
76.9
81.8

67
MBH
71.1
71.4
72.1
75.2
72.7
72.9
74.0
77.9
73.9
74.2
74.9
80.0
75.0
75.3
76.9
81.7

73

SHC MBH
45.7 80.8
54.4 81.0
66.9 81.3
75.2 81.6
44.2 81.7
57.7 82.0
71.4 82.4
77.9 82.8
46.2 82.4
60.8 82.8
74.9 83.3
80.0 83.9
48.1 83.0
63.7 83.4
76.9 84.0
81.7 84.7

SHC
27.5
39.8
51.9
63.7
28.0
41.5
54.3
67.0
28.6
43.1
56.4
70.0
29.0
44.2
58.4
72.8

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

30

Indicates both downflow and horizontal units.

RT-PRC002-EN

Performance
Data

(8Ton)
High Efficiency

Table PD-22 Gross Cooling Capacities (MBH) 8 Ton Three Phase TCD103C3, C4, CW
Ambient Temperature
85

CFM
Air Flow
3060

3400

3740

4080

Enter
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

95

61

67

73

MBH SHC MBH SHC MBH


95.4 82.2 109.0 63.4 115.0
97.6 97.6 109.0 78.7 116.0
105.0 105.0 110.0 94.0 117.0
111.0 111.0 112.0 109.0 119.0
98.3 87.7 110.0 65.6 116.0
102.0 102.0 111.0 82.1 117.0
109.0 109.0 112.0 98.4 118.0
113.0 113.0 113.0 113.0 120.0
101.0 93.0 111.0 67.5 116.0
106.0 106.0 112.0 85.0 117.0
111.0 111.0 113.0 102.0 119.0
115.0 115.0 115.0 115.0 120.0
103.0 98.0 112.0 69.0 117.0
108.0 108.0 113.0 87.5 118.0
113.0 113.0 115.0 105.0 120.0
117.0 117.0 117.0 117.0 121.0

SHC
42.0
57.6
70.5
83.7
42.8
58.5
72.1
85.9
43.5
63.0
73.3
87.8
44.1
65.3
74.5
89.5

61

105
Entering Wet Bulb
67
73

MBH SHC MBH SHC MBH


88.0 78.3 104.0 60.8 112.0
91.7 91.7 104.0 76.8 113.0
99.9 99.9 105.0 92.8 114.0
107.0 107.0 107.0 107.0 115.0
90.8 83.8 106.0 63.7 113.0
96.3 96.3 106.0 81.0 114.0
104.0 104.0 107.0 98.2 115.0
110.0 110.0 110.0 110.0 116.0
93.3 89.1 107.0 66.3 113.0
100.0 100.0 108.0 84.8 115.0
107.0 107.0 109.0 103.0 116.0
112.0 112.0 112.0 112.0 117.0
95.7 94.3 108.0 68.5 114.0
103.0 103.0 109.0 88.2 115.0
110.0 110.0 110.0 107.0 116.0
114.0 114.0 114.0 114.0 118.0

SHC
40.0
56.3
69.4
83.3
40.7
57.6
71.4
86.1
41.4
58.6
73.1
88.6
42.2
59.5
74.7
90.8

115

61

67

73

MBH SHC MBH SHC MBH


80.3 74.3 96.3 57.3 108.0
85.5 85.5 96.5 73.3 109.0
93.7 93.7 97.6 89.7 109.0
102.0 102.0 102.0 102.0 110.0
82.8 79.7 98.7 60.4 109.0
89.7 89.7 99.0 78.1 110.0
98.4 98.4 100.0 96.1 110.0
105.0 105.0 105.0 105.0 111.0
84.5 84.5 101.0 63.3 110.0
93.6 93.6 101.0 82.7 111.0
102.0 102.0 103.0 102.0 111.0
108.0 108.0 108.0 108.0 113.0
87.6 87.6 102.0 66.3 110.0
97.1 97.1 103.0 87.0 112.0
105.0 105.0 105.0 105.0 112.0
110.0 110.0 110.0 110.0 113.0

SHC
37.6
53.9
68.5
83.2
38.4
55.8
71.2
86.9
39.2
57.4
73.4
90.1
39.9
58.8
75.4
92.9

61

67

73

MBH SHC MBH SHC MBH


72.6 70.4 87.3 54.0 103.0
79.2 79.2 87.6 69.2 103.0
87.2 87.2 89.2 85.7 103.0
95.6 95.6 95.6 95.6 104.0
74.8 74.8 89.7 56.4 104.0
83.0 83.0 90.1 74.2 104.0
91.7 91.7 91.7 91.7 105.0
99.9 99.9 99.9 99.9 106.0
77.9 77.9 91.7 59.5 105.0
86.5 86.5 92.4 78.9 105.0
95.7 95.7 95.7 95.7 106.0
103.0 103.0 103.0 103.0 107.0
80.6 80.6 93.4 62.5 105.0
89.8 89.8 94.4 83.6 106.0
99.0 99.0 99.0 99.0 107.0
105.0 105.0 105.0 105.0 108.0

SHC
35.0
51.2
66.8
82.0
35.9
53.6
70.1
86.5
36.6
55.4
73.0
90.5
37.4
57.0
75.6
94.1

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-23 Gross Cooling Capacities (MBH) 8 Ton Three Phase TCH103C3, C4, CW
Ambient Temperature
85

CFM
Airflow
3060

3400

3740

4080

Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

61

67

95

73

MBH SHC MBH SHC MBH


95.7 82.2 108.0 62.8 112.0
97.7 97.7 109.0 77.8 114.0
105.0 105.0 110.0 92.9 115.0
110.0 110.0 111.0 108.0 116.0
98.6 87.6 110.0 64.8 113.0
102.0 102.0 110.0 80.6 114.0
108.0 108.0 111.0 96.7 115.0
112.0 112.0 112.0 112.0 117.0
101.0 92.9 111.0 66.4 113.0
106.0 106.0 111.0 83.0 114.0
110.0 110.0 112.0 99.8 116.0
114.0 114.0 114.0 114.0 117.0
103.0 97.7 111.0 67.7 113.0
108.0 108.0 112.0 85.0 114.0
112.0 112.0 113.0 102.0 116.0
115.0 115.0 115.0 115.0 118.0

SHC
41.4
56.1
68.3
80.6
42.0
56.7
69.3
82.1
42.6
62.3
70.1
83.3
43.2
64.5
70.9
84.4

61

67

105
Entering Wet Bulb
73
61

MBH SHC MBH SHC MBH


88.4 78.3 104.0 60.5 111.0
91.9 91.9 104.0 76.6 112.0
100.0 100.0 105.0 92.5 112.0
107.0 107.0 107.0 107.0 114.0
91.1 83.7 106.0 63.4 111.0
96.3 96.3 106.0 80.6 113.0
104.0 104.0 107.0 97.7 113.0
110.0 110.0 110.0 110.0 115.0
93.5 89.0 107.0 65.7 112.0
100.0 100.0 107.0 84.1 113.0
107.0 107.0 109.0 102.0 114.0
112.0 112.0 112.0 112.0 115.0
95.8 94.1 108.0 67.7 112.0
103.0 103.0 109.0 87.2 113.0
109.0 109.0 110.0 106.0 114.0
113.0 113.0 113.0 113.0 116.0

SHC
39.5
55.5
67.8
81.6
40.3
56.5
69.8
84.0
40.9
57.3
71.1
86.0
41.5
57.8
72.1
87.3

67

115

73

MBH SHC MBH SHC MBH


80.8 74.3 96.6 57.0 107.0
85.8 85.8 96.7 73.1 108.0
93.9 93.9 97.7 89.5 109.0
101.0 101.0 101.0 101.0 110.0
83.4 79.7 98.8 60.1 108.0
89.9 89.9 99.0 77.9 109.0
98.3 98.3 100.0 95.8 110.0
105.0 105.0 105.0 105.0 111.0
85.8 85.0 101.0 63.0 109.0
93.7 93.7 101.0 82.3 110.0
102.0 102.0 103.0 101.0 111.0
108.0 108.0 108.0 108.0 112.0
87.9 87.9 102.0 65.8 109.0
97.0 97.0 102.0 86.3 111.0
104.0 104.0 104.0 104.0 111.0
110.0 110.0 110.0 110.0 113.0

SHC
37.3
53.6
68.0
82.6
38.0
55.0
70.3
85.8
38.7
56.4
72.2
88.6
39.4
57.8
73.9
90.9

61

67

73

MBH SHC MBH SHC MBH


73.0 70.3 87.9 54.0 102.0
79.4 79.4 88.2 69.1 102.0
87.4 87.4 89.6 85.6 103.0
95.5 95.5 95.5 95.5 103.0
75.0 75.0 90.2 56.2 103.0
83.3 83.3 90.6 74.0 104.0
91.9 91.9 91.8 91.8 104.0
99.5 99.5 99.5 99.5 105.0
78.1 78.1 92.1 59.3 104.0
86.8 86.8 92.7 78.7 104.0
95.6 95.6 95.6 95.6 105.0
102.0 102.0 102.0 102.0 106.0
80.8 80.8 93.7 62.2 105.0
90.0 90.0 94.5 83.2 105.0
98.6 98.6 98.5 98.5 106.0
105.0 105.0 105.0 105.0 108.0

SHC
34.5
50.7
66.1
81.3
35.3
53.1
69.2
85.6
36.1
54.7
72.0
89.4
36.9
56.2
74.5
92.8

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Indicates both downflow and horizontal units.

RT-PRC002-EN

31

Performance
Data

(10, 12Ton)
High Efficiency

Table PD-24 Gross Cooling Capacities (MBH) 10 Ton Three Phase TCR121C3, C4, CW
Ambient Temperature
85

CFM
Airflow
3600

4000

4400

4800

95

105
115
Enter
Dry
Entering Wet Bulb
Bulb
61
67
73
61
67
73
61
67
73
61
67
73
(F) MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
75 117.0 99.3 131.0 76.4 137.0 50.5 106.0 93.7 124.0 72.8 134.0 48.0 95.1 88.5 112.0 68.1 129.0 45.0 81.1 81.1 100.0 62.7 120.0 41.5
80 119.0 119.0 131.0 93.6 139.0 68.7 110.0 110.0 125.0 91.9 136.0 67.2 101.0 101.0 113.0 86.6 130.0 64.3 92.6 92.6 101.0 81.2 120.0 60.7
85 127.0 127.0 132.0 111.0 140.0 83.6 120.0 120.0 125.0 111.0 137.0 84.3 110.0 110.0 114.0 106.0 130.0 82.5 101.0 101.0 102.0 101.0 120.0 79.5
90 133.0 133.0 134.0 129.0 142.0 98.8 128.0 128.0 128.0 128.0 138.0 101.0 120.0 120.0 120.0 120.0 131.0 100.0 110.0 110.0 110.0 110.0 121.0 98.4
75 120.0 106.0 132.0 78.6 138.0 51.3 109.0 100.0 127.0 76.2 136.0 48.9 97.8 94.8 116.0 71.5 130.0 45.9 90.6 90.6 102.0 65.8 123.0 42.7
80 124.0 124.0 133.0 97.2 140.0 69.7 115.0 115.0 127.0 96.9 137.0 69.2 106.0 106.0 116.0 92.6 131.0 67.2 96.7 96.7 103.0 87.0 123.0 63.8
85 130.0 130.0 134.0 116.0 141.0 85.4 125.0 125.0 128.0 117.0 138.0 86.9 116.0 116.0 118.0 114.0 132.0 86.2 106.0 106.0 106.0 106.0 123.0 84.6
90 136.0 136.0 136.0 134.0 143.0 101.0 132.0 132.0 132.0 132.0 140.0 105.0 125.0 125.0 125.0 125.0 133.0 105.0 116.0 116.0 116.0 116.0 124.0 105.0
75 123.0 112.0 134.0 80.8 139.0 52.2 112.0 107.0 128.0 79.5 136.0 49.8 99.9 99.9 118.0 75.3 132.0 46.9 91.1 91.1 104.0 69.4 124.0 43.7
80 127.0 127.0 135.0 100.0 141.0 75.6 120.0 120.0 129.0 102.0 138.0 70.6 110.0 110.0 119.0 98.4 133.0 69.5 100.0 100.0 105.0 92.6 125.0 66.7
85 133.0 133.0 136.0 120.0 142.0 87.0 128.0 128.0 130.0 123.0 139.0 89.2 121.0 121.0 121.0 121.0 133.0 89.3 110.0 110.0 110.0 110.0 125.0 89.0
90 138.0 138.0 138.0 138.0 144.0 104.0 134.0 134.0 134.0 134.0 141.0 108.0 129.0 129.0 129.0 129.0 134.0 110.0 121.0 121.0 121.0 121.0 126.0 111.0
75 125.0 118.0 135.0 82.6 140.0 53.1 115.0 113.0 130.0 82.1 137.0 50.7 103.0 103.0 120.0 78.9 132.0 47.8 94.0 94.0 106.0 72.9 125.0 44.5
80 130.0 130.0 136.0 103.0 141.0 78.3 124.0 124.0 130.0 106.0 139.0 71.7 114.0 114.0 121.0 104.0 134.0 71.4 104.0 104.0 108.0 98.2 126.0 69.3
85 135.0 135.0 137.0 124.0 143.0 88.4 131.0 131.0 132.0 129.0 140.0 91.2 125.0 125.0 125.0 125.0 134.0 92.2 115.0 115.0 115.0 115.0 126.0 92.9
90 139.0 139.0 139.0 139.0 145.0 106.0 137.0 137.0 137.0 137.0 142.0 111.0 132.0 132.0 132.0 132.0 136.0 114.0 125.0 125.0 125.0 125.0 128.0 116.0

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

Table PD-25 Gross Cooling Capacities (MBH) 12 Ton Three Phase TCR151C3, C4, CW
85

CFM
Airflow
4500

5000

5500

6000

Enter
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

61

Ambient Temperature
105

95

67

73

61

67

Entering Wet Bulb


73
61

67

115

73

61

67

73

MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
137.0 116.0 157.0 90.2 166.0 60.8 127.0 110.0 151.0 87.1 163.0 58.5 116.0 105.0 140.0 82.3 158.0 55.8 106.0 99.7 128.0 80.6 152.0 52.8
140.0 139.0 158.0 111.0 167.0 82.9 130.0 130.0 151.0 109.0 164.0 80.8 122.0 122.0 141.0 104.0 159.0 77.8 114.0 114.0 128.0 98.5 152.0 74.6
149.0 149.0 158.0 132.0 169.0 100.0 142.0 142.0 151.0 131.0 165.0 99.4 133.0 133.0 141.0 126.0 159.0 98.2 125.0 125.0 130.0 121.0 152.0 96.0
158.0 158.0 160.0 153.0 170.0 118.0 152.0 152.0 154.0 152.0 166.0 118.0 145.0 145.0 145.0 145.0 160.0 118.0 137.0 137.0 137.0 137.0 153.0 117.0
141.0 123.0 159.0 93.4 167.0 61.6 131.0 117.0 154.0 90.9 164.0 59.4 120.0 112.0 144.0 86.6 159.0 56.8 109.0 107.0 132.0 81.0 153.0 53.7
145.0 145.0 160.0 116.0 168.0 84.1 136.0 136.0 154.0 114.0 165.0 82.4 128.0 128.0 144.0 110.0 161.0 80.9 119.0 119.0 132.0 105.0 154.0 77.5
155.0 155.0 161.0 138.0 170.0 103.0 148.0 148.0 155.0 138.0 166.0 102.0 140.0 140.0 145.0 135.0 161.0 102.0 131.0 131.0 134.0 129.0 154.0 100.0
162.0 162.0 163.0 160.0 172.0 121.0 157.0 157.0 157.0 157.0 168.0 122.0 151.0 151.0 151.0 151.0 163.0 123.0 143.0 143.0 143.0 143.0 155.0 122.0
145.0 129.0 161.0 95.8 168.0 62.6 134.0 124.0 156.0 94.4 165.0 60.4 123.0 119.0 147.0 90.4 161.0 57.8 112.0 112.0 135.0 85.1 154.0 54.6
150.0 150.0 162.0 119.0 169.0 85.2 142.0 142.0 156.0 119.0 167.0 84.0 133.0 133.0 147.0 116.0 162.0 82.4 124.0 124.0 135.0 111.0 155.0 80.1
158.0 158.0 163.0 143.0 172.0 104.0 153.0 153.0 157.0 144.0 168.0 104.0 146.0 146.0 149.0 143.0 163.0 105.0 137.0 137.0 137.0 137.0 156.0 104.0
165.0 165.0 165.0 165.0 173.0 123.0 161.0 161.0 161.0 161.0 170.0 126.0 156.0 156.0 156.0 156.0 164.0 127.0 149.0 149.0 149.0 149.0 157.0 127.0
148.0 136.0 162.0 97.9 168.0 63.5 137.0 131.0 157.0 97.1 166.0 61.4 126.0 125.0 150.0 94.3 162.0 58.9 116.0 116.0 138.0 89.0 155.0 55.6
154.0 154.0 163.0 123.0 170.0 86.2 147.0 147.0 158.0 124.0 168.0 85.8 138.0 138.0 150.0 122.0 162.0 83.3 128.0 128.0 138.0 117.0 156.0 82.2
161.0 161.0 165.0 147.0 172.0 106.0 157.0 157.0 160.0 150.0 169.0 106.0 151.0 151.0 152.0 150.0 164.0 107.0 142.0 142.0 142.0 142.0 158.0 107.0
167.0 167.0 167.0 167.0 174.0 126.0 164.0 164.0 164.0 164.0 171.0 128.0 159.0 159.0 159.0 159.0 166.0 131.0 153.0 153.0 153.0 153.0 159.0 132.0

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

32

RT-PRC002-EN

(15, 17Ton)
High Efficiency
Table PD-26 Gross Cooling Capacities (MBH) 15 Ton Three Phase TCR181C3, C4, CW
Ambient Temperature
85

CFM
Airflow
5400

6000

6600

7200

Enter.
Dry
Bulb
61
(F) MBH SHC
75
172 144
80
175 169
85
185 185
90
195 195
75
177 153
80
181 180
85
192 192
90
201 201
75
181 162
80
186 186
85
197 197
90
204 204
75
184 170
80
191 191
85
200 200
90
207 207

67
MBH SHC
194 112
195 138
196 164
195 195
197 116
198 144
199 172
200 200
198 123
200 151
202 179
205 202
200 127
202 153
204 185
208 207

95

73
MBH SHC
205 75.2
207 103
209 126
211 149
207 76
209 105
211 129
214 153
208 76.6
210 107
213 131
215 157
209 79.1
211 108
214 134
217 160

61
MBH SHC
159 138
164 162
176 176
188 188
164 147
170 170
183 183
194 194
168 155
177 177
189 189
199 199
168 168
182 182
194 194
203 203

67
MBH SHC
185 107
186 134
186 161
190 184
189 112
189 142
190 171
195 194
191 117
192 148
194 180
199 199
193 121
194 154
194 194
203 203

105
Entering Wet Bulb
73
61
MBH SHC MBH SHC
200 71.9 147 131
202 99.7 153 153
203 124 165 165
204 148 178 178
202 73.2 151 140
204 103 159 159
206 129 173 173
208 155 185 185
204 74.4 152 152
206 105 166 166
208 132 179 179
209 159 191 191
206 76.4 156 156
207 107 171 171
209 136 185 185
211 163 195 195

67
MBH SHC
172 101
173 128
174 156
179 179
176 106
177 136
173 173
185 185
180 111
180 144
183 173
191 191
182 116
183 151
187 181
195 195

115

73
MBH SHC
193 68
194 95.4
195 122
196 147
195 69.3
196 99.4
197 127
199 154
197 70.6
198 102
199 132
201 160
198 71.9
199 105
201 135
203 166

61
MBH SHC
130 130
142 142
155 155
168 168
138 131
148 148
162 162
175 175
142 139
154 154
168 168
181 181
145 145
159 159
174 174
186 186

67
MBH SHC
158 97
158 122
155 155
167 167
162 99.8
162 130
162 162
175 175
165 105
166 137
170 166
181 181
168 110
169 145
174 174
186 186

73
MBH SHC
183 63.4
183 90.5
184 117
184 144
185 64.8
186 94.6
186 124
187 152
187 66.2
188 98.6
189 129
190 160
189 67.4
190 102
191 134
192 167

NOTES:
1 All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-27 Gross Cooling Capacities (MBH)17 Ton Three Phase TCR211C3, C4, CW
Ambient Temperature
85

CFM
Airflow
6300

7000

7700

8400

Enter
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

61

67

95

73

61

67

105
Entering Wet Bulb
73
61

67

115

73

61

67

73

MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC MBH SHC
200.0 169.0 224.0 130.0 233.0 86.2 184.0 162.0 215.0 125.0 231.0 83.3 169.0 154.0 199.0 118.0 226.0 79.3 147.0 147.0 180.0 113.0 214.0 74.2
202.0 202.0 225.0 161.0 236.0 118.0 190.0 190.0 216.0 158.0 234.0 117.0 177.0 177.0 200.0 151.0 227.0 112.0 164.0 164.0 181.0 142.0 214.0 107.0
216.0 216.0 227.0 191.0 239.0 143.0 206.0 206.0 217.0 190.0 236.0 146.0 193.0 193.0 202.0 184.0 228.0 144.0 180.0 180.0 185.0 176.0 215.0 139.0
227.0 227.0 230.0 221.0 242.0 169.0 220.0 220.0 220.0 220.0 239.0 175.0 209.0 209.0 209.0 209.0 229.0 174.0 196.0 196.0 195.0 195.0 217.0 171.0
205.0 180.0 226.0 134.0 234.0 87.6 190.0 172.0 219.0 131.0 233.0 84.8 174.0 164.0 204.0 124.0 228.0 80.8 155.0 155.0 184.0 116.0 218.0 76.0
210.0 210.0 228.0 167.0 237.0 119.0 198.0 198.0 220.0 167.0 236.0 120.0 185.0 185.0 205.0 160.0 229.0 117.0 171.0 171.0 186.0 152.0 218.0 112.0
223.0 223.0 230.0 199.0 241.0 145.0 215.0 215.0 222.0 202.0 238.0 150.0 202.0 202.0 209.0 197.0 231.0 150.0 188.0 188.0 191.0 189.0 219.0 147.0
232.0 232.0 233.0 230.0 244.0 173.0 227.0 227.0 227.0 227.0 241.0 180.0 218.0 218.0 218.0 218.0 232.0 182.0 205.0 205.0 204.0 204.0 221.0 181.0
210.0 190.0 228.0 138.0 235.0 88.9 195.0 183.0 222.0 137.0 234.0 86.0 179.0 175.0 208.0 130.0 229.0 82.4 161.0 161.0 188.0 122.0 220.0 77.7
217.0 217.0 231.0 173.0 239.0 120.0 206.0 206.0 223.0 174.0 237.0 121.0 192.0 192.0 209.0 169.0 231.0 121.0 178.0 178.0 190.0 161.0 221.0 116.0
228.0 228.0 232.0 206.0 242.0 148.0 221.0 221.0 226.0 211.0 240.0 153.0 210.0 210.0 214.0 209.0 234.0 156.0 196.0 196.0 195.0 195.0 222.0 154.0
235.0 235.0 235.0 235.0 245.0 176.0 232.0 232.0 232.0 232.0 243.0 185.0 224.0 224.0 224.0 224.0 235.0 189.0 213.0 213.0 212.0 212.0 224.0 191.0
214.0 200.0 230.0 141.0 236.0 90.3 200.0 193.0 224.0 141.0 235.0 87.4 181.0 181.0 211.0 136.0 230.0 83.8 166.0 166.0 191.0 128.0 222.0 79.2
222.0 222.0 232.0 177.0 239.0 133.0 213.0 213.0 226.0 181.0 238.0 123.0 199.0 199.0 213.0 178.0 233.0 124.0 184.0 184.0 194.0 170.0 223.0 121.0
231.0 231.0 234.0 211.0 243.0 149.0 226.0 226.0 229.0 220.0 241.0 155.0 216.0 216.0 216.0 216.0 235.0 161.0 203.0 203.0 202.0 202.0 224.0 162.0
238.0 238.0 238.0 238.0 246.0 178.0 235.0 235.0 235.0 235.0 244.0 189.0 229.0 229.0 229.0 229.0 237.0 195.0 219.0 219.0 219.0 219.0 227.0 199.0

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Cooling Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.


RT-PRC002-EN

33

Performance
Data

(20, 25 Ton)
High Efficiency

Table PD-28 Gross Cooling Capacities (MBH) 20 Ton Three Phase TCR241C3, C4, CW
95

Ambient Temperature (F)


105

67
MBH SHC
263 152
264 190
265 228
268 265
267 159
268 199
270 240
274 274
270 164
271 208
274 250
280 280
273 169
274 215
277 260
284 284

Entering Wet Bulb (F)


73
61
67
MBH SHC MBH SHC MBH SHC
280 101 208 186 246 145
283 141 216 216 246 183
285 173 236 236 248 221
288 206 254 254 254 254
282 103 214 199 252 152
285 143 227 227 252 194
288 177 247 247 255 237
291 212 264 264 264 264
284 105 219 211 256 159
287 145 236 236 257 205
290 181 256 256 260 251
293 217 271 271 271 271
285 106 225 223 260 166
288 147 245 245 261 215
291 184 263 263 265 263
294 222 276 276 276 276

85

CFM
Airflow
7200

8000

8800

9600

Enter.
Dry
Bulb
61
(F) MBH SHC
75
246 205
80
250 245
85
263 263
90
274 274
75
253 218
80
257 257
85
270 270
90
280 280
75
258 230
80
264 264
85
276 276
90
285 285
75
262 240
80
270 270
85
280 280
90
288 288

67
MBH SHC
273 158
274 192
275 227
278 262
275 163
277 199
279 236
282 273
278 167
280 204
282 244
286 281
280 169
282 209
284 250
288 288

73
MBH SHC
284 105
287 142
290 171
293 201
285 107
289 144
292 174
295 205
287 109
290 155
293 177
297 209
288 110
291 161
295 179
298 212

61
MBH SHC
228 196
232 232
251 251
266 266
234 209
243 243
261 261
274 274
240 221
252 252
268 268
280 280
246 233
260 260
274 274
284 284

115

73
MBH SHC
273 96.5
274 135
275 170
277 205
275 98.3
277 140
278 177
280 214
277 100
279 144
281 182
283 221
278 102
281 147
282 186
285 228

61
MBH SHC
191 176
201 201
219 219
239 239
194 189
210 210
230 230
250 250
199 199
218 218
240 240
258 258
205 205
226 226
248 248
264 264

67
MBH SHC
222 136
223 172
225 211
237 237
228 142
228 184
232 226
248 248
232 149
233 195
238 238
258 258
236 156
237 205
246 246
265 265

73
MBH SHC
261 91.5
261 130
262 168
262 205
266 93.6
266 136
266 177
267 218
269 95.5
269 141
269 185
271 229
271 97.1
271 146
272 193
275 240

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

Table PD-29 Gross Cooling Capacities (MBH)25 Ton Three PhaseTCR301C3, C4, CW
85

CFM
Airflow
9000

10000

10500

11000

Enter.
Dry
Bulb
(F)
75
80
85
90
75
80
85
90
75
80
85
90
75
80
85
90

61

MBH
277
284
300
312
284
294
307
318
286
297
310
320
289
300
312
322

SHC
243
284
300
312
258
294
307
318
265
297
310
320
272
300
312
322

Ambient Temperature (F)


105

95

67
MBH
306
307
309
313
310
310
313
318
311
312
315
320
312
313
316
321

SHC
187
225
269
312
188
233
280
318
190
237
285
320
192
240
289
321

73
MBH
316
321
325
329
319
323
327
331
320
324
328
332
321
324
329
332

SHC
117
169
198
236
121
175
202
241
122
178
204
244
123
181
205
246

61
MBH
258
269
289
305
264
280
298
312
267
285
302
314
270
289
305
317

SHC
234
269
289
305
249
280
298
312
256
285
302
314
264
289
305
317

67
MBH
295
295
298
305
299
300
303
312
300
302
305
314
302
304
307
317

SHC
178
225
271
305
185
236
286
312
189
241
293
314
192
246
299
317

Entering Wet Bulb (F)


73
61
MBH
314
317
320
321
316
319
322
324
316
320
323
325
317
321
324
326

SHC
115
161
202
240
117
170
207
248
118
174
210
251
119
177
212
255

MBH
238
252
273
293
244
263
284
301
247
267
289
305
249
272
293
308

SHC
224
252
273
293
239
263
284
301
246
267
289
305
249
272
293
308

115

67

MBH
276
277
280
293
282
283
287
301
284
285
289
305
286
287
293
308

SHC
169
217
266
293
178
230
284
301
182
237
289
305
186
243
293
308

73
MBH
305
307
308
310
308
309
312
314
309
310
313
316
309
311
314
317

SHC
110
158
201
245
112
163
208
255
113
165
212
260
114
170
215
265

61
MBH
218
235
256
277
224
245
267
287
228
249
272
292
231
253
276
295

SHC
214
235
256
277
224
245
267
287
228
249
272
292
231
253
276
295

67
MBH
253
254
259
277
259
260
267
287
261
262
272
292
263
265
276
295

73

SHC
163
207
256
277
168
221
267
287
172
227
272
292
176
234
276
295

MBH
292
293
293
295
295
296
297
299
296
298
299
301
297
299
300
303

SHC
104
151
198
244
106
158
208
257
107
162
213
264
108
165
217
270

NOTES:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain net cooling subtract indoor fan heat.
2. MBH = Total Gross Capacity
3. SHC = Sensible Heat Capacity

RIndicates both downflow and horizontal units.

34

RT-PRC002-EN

Performance
Data

(3, 4, 5Ton)
Standard Efficiency

Table PD-30 Evaporator Fan Performance 3, 4 and 5 Ton TCD036C,TCR048C,TCR060C


External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor
Oversized Motor

Tons

Unit
Model No.

TCD036C1

TCD048C1

TCH048C1

TCD060C1

TCH060C1

High Speed

Low Speed

CFM

ESP

BHP

ESP

BHP

ESP

BHP

1000
1100
1200
1300
1400
1500
1300
1400
1500
1600
1700
1800
1900
2000
1300
1400
1500
1600
1700
1800
1900
2000
1700
1800
1900
2000
2100
2200
2300
2400
1700
1800
1900
2000
2100
2200
2300
2400

.72
.63
.56
.49
.38
.27
.85
.83
.80
.75
.71
.65
.60
.55
.82
.78
.73
.69
.64
.60
.53
.47
.80
.75
.70
.65
.60
.53
.47
.40
.75
.71
.66
.60
.56
.48
.40
.33

.30
.32
.34
.36
.38
.40
.49
.50
.52
.54
.56
.58
.60
.62
.46
.48
.49
.50
.52
.54
.56
.58
.59
.61
.63
.66
.69
.71
.73
.76
.59
.62
.64
.66
.68
.70
.73
.76

.60
.52
.40
.25

.77
.70
.63
.55
.42

.70
.65
.60
.52
.44
.32
.16

.72
.66
.60
.52
.45
.35
.23

.68
.60
.57
.48
.40
.29
.17

.28
.30
.33
.38

.37
.39
.42
.44
.49

.34
.36
.39
.41
.43
.47
.52

.48
.50
.52
.55
.59
.62
.67

.48
.50
.52
.56
.59
.63
.67

1.48
1.34
1.16
.97
.75
.50
1.62
1.53
1.46
1.39
1.31
1.23
1.16
1.08
1.59
1.52
1.45
1.38
1.31
1.23
1.16
1.08
1.40
1.32
1.25
1.19
1.12
1.03
.92
.78
1.36
1.28
1.21
1.14
1.07
.98
.85
.71

.61
.63
.66
.69
.73
.77
.74
.77
.80
.83
.86
.90
.93
.97
.77
.79
.81
.83
.86
.90
.93
.96
.86
.90
.93
.96
1.01
1.05
1.09
1.13
.86
.90
.93
.97
1.01
1.05
1.09
1.13

Fan motor heat (MBH) = 4.39 x Fan Bhp.


Tranes factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed
and tested to operate reliably and continuously at all cataloged conditions.
Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our products war ranty will not be affected.
NOTE:
1. Data includes pressure drop due to wet coil and filters.

RIndicates both downflow and horizontal units.

RT-PRC002-EN

35

Performance
Data

(6-7 Ton)
Standard Efficiency

Table PD-31 Evaporator Fan Performance 6 And 7 Ton TCR075C,TCR090C,D

Tons

Unit
Model No.

TCD075C
TCH075C

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.25
1.50
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1 HP Standard Motor & Field
Supplied Low Static Drive1
2000 597 .39 646 .44 692 .50
2250 659 .53 705 .59 745 .65
2500 723 .71 765 .78 802 .85
2750 789 .93 826 1.01 862 1.08
3000 855 1.19 887 1.27 922 1.36

739
787
839
895
953

.55
.72
.92
1.15
1.44

782
829
877
928
983

1 HP Standard Motor & Sheaves


.60 825 .66 868 .71 907 .76 947 .81 986 .86 1082 .98
.78 867 .84 905 .90 944 .96 982 1.02 1017 1.08 1104 1.22 1190 1.35
.99 914 1.05 950 1.12 984 1.19 1019 1.26 1054 1.32 1134 1.49 1213 1.64
1.23 963 1.31 997 1.38 1030 1.45 1061 1.53 1092 1.60 1171 1.79 1244 1.97
1.52 1014 1.60 1046 1.68 1078 1.76 1108 1.85 1137 1.93 1209 2.13
2 HP Oversized Motor & Sheaves

1 HP Standard Motor & Sheaves


7

TCD090C
TCH090C

2400
2700
3000
3300
3600

721
802
884
966
1048

.62
.86
1.17
1.54
1.98

760
836
915
994
1075

.66
.92
1.23
1.60
2.06

801
872
946
1022
1101

.71 840 .76 879 .80 916 .85


.97 908 1.03 943 1.08 977 1.13
1.29 979 1.35 1011 1.41 1042 1.47
1.67 1051 1.73 1081 1.80 1111 1.87
2.12 1126 2.20 1153 2.27 1181 2.34
2 HP Oversized Motor & Sheaves

952
1011
1073
1139
1208

.89
1.17
1.52
1.93
2.42

988
1043
1104
1167
1234

.92
1.22
1.57
1.99
2.49

1025
1075
1134
1195
1260

.96
1.27
1.63
2.05
2.55

1058
1108
1163
1223

.99 1142 1.05 1226 1.10


1.31 1186 1.40 1259 1.47
1.68 1236 1.80

2.11

1 HP Standard Motor & Field


Supplied Low Static Drive1
1 HP Standard Motor & Sheaves
2400 698 0.59 739 0.64 779 0.69 819 0.74 857 0.78 895 0.82 931 0.86 967 0.90 1004 0.94 1039 0.97 1121 1.04 1203 1.09
7

TCD090D
TCH090D

2700
3000
3300
3600

775
853
932
1011

0.82
1.11
1.46
1.88

813
888
963
1040

0.88
1.18
1.53
1.96

848
920
994
1069

0.93
1.24
1.60
2.04

884
952
1023
1096

0.99
1.30
1.67
2.11

919
984
1052
1122

1.04
1.36
1.74
2.18

953
1016
1081
1148

1.09
1.42
1.80
2.26

987
1047
1110
1176

1.14
1.47
1.87
2.33

1020
1077
1138
1203

1.19
1.53
1.93
2.40

1052
1108
1166
1229

1.23
1.58
1.99
2.47

1084
1137
1194
1254

1.28 1164 1.38 1237 1.45


1.63 1209 1.76

2.05 1261 2.20

2.54

2 HP Oversize Motor & Sheaves


Data includes pressure drop due to filters and wet coil.
Fan motor heat (MBH) = 3.53 x Fan Bhp.
NOTE:
1. Requires a field supplied Browning sheave AL74 and Belt A48.

Tranes factory supplied motors, in commercial equipment, are definite purpose motors,
specifically designed and tested to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan motors as shown in our tabular
data will not result in nuisance tripping or premature motor failure. Our products
warranty will not be affected.

RIndicates both downflow and horizontal units.

36

RT-PRC002-EN

Performance
Data

(8Ton)
Standard Efficiency

Table PD-32 Evaporator Fan Performance 8 Ton TCD102C

CFM

2720
3060
3400
3740
4080

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Field Supplied Low
2 HP Standard Motor & Drive
Static Drive (1)
553 0.61 586 0.68 623 0.77 658 0.86 690 0.95 721 1.04 752 1.14 781 1.24 809 1.35 836 1.45 863 1.57
614 0.84 643 0.92 675 1.01 707 1.11 738 1.21 767 1.31 795 1.42 823 1.52 849 1.63 875 1.75 900 1.87
676 1.13 703 1.22 729 1.31 758 1.41 787 1.53 815 1.64 842 1.76 868 1.87 893 1.98 917 2.10 941 2.22
738 1.49 763 1.58 787 1.67 812 1.78 838 1.90 865 2.03 890 2.15 915 2.28 939 2.40 962 2.52 984 2.65
800 1.91 823 2.01 846 2.11 868 2.2 891 2.34 916 2.47 940 2.61
3 HP Oversized Motor
& Field Supplied Drive (2)

963 2.75

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and
filters
1. Field Supplied Fan Sheave AK94 Required. Field
Supplied Belt may be necessary.
Table PD-32 Continued
2. 3 HP Motor with Field Supplied Motor Sheave
IVP44 required.

889
925
964
1007

1.68
1.99
2.35
2.78

914
949
987
1028

1.79
2.11
2.48
2.91

986 2.88 1009 3.02 1030 3.15 1051 3.29 1072 3.43
3 HP Oversized Motor & Drive

Tranes factory supplied motors, in commercial equipment, are definite


purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range
of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our products warranty will not be
affected.

2720

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor
& High Static Drive
Accessory
3 HP Oversized Motor & Drive
938 1.91 962 2.02 986 2.14 1009 2.26 1031 2.38 1053 2.5 1075 2.62

3060
3400
3740
4080

973 2.24 996 2.36


1010 2.61 1032 2.75
1050 3.05 1071 3.19

CFM

RIndicates both downflow and horizontal units.

1.20
1.30
RPM BHP RPM BHP

1018 2.49 1040 2.62 1062 2.75


1053 2.89 1075 3.03 1095 3.17
1092 3.34

1083 2.88 1104 3.01


1116 3.31 1136 3.45

Table PD-33 Evaporator Fan Performance 8 Ton TCH102C


CFM

2720
3060
3400
3740
4080

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard
2 HP Standard Motor & Field
2 HP Standard Motor & Drive
Motor & High Static
Supplied Low Static Drive (1)
Drive Accessory
490 0.45 531 0.53 572 0.61 612 0.70 649 0.78 684 0.87 718 0.97 749 1.07 780 1.17 809 1.27 837 1.37 865 1.48 891 1.59
542 0.62 578 0.70 615 0.79 651 0.89 686 0.98 719 1.08 751 1.18 782 1.28 811 1.39 840 1.50 867 1.61 893 1.73 919 1.84
594 0.83 627 0.91 660 1.01 693 1.11 725 1.22 757 1.33 787 1.44 817 1.55 845 1.66 872 1.77 899 1.89 924 2.01 949 2.14
647 1.08 677 1.17 707 1.27 737 1.38 767 1.50 797 1.62 825 1.74 853 1.85 880 1.97 907 2.10 932 2.22 957 2.35 981 2.48
700 1.38 728 1.48 756 1.59 783 1.70 811 1.82 838 1.95 865 2.08 892 2.21 917 2.34 943 2.47 967 2.60 991 2.73 1015 2.87
3 HP Oversized Motor & Field
3 HP Oversized
2 HP Standard Motor & Drive
Supplied Drive (2)
Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and
filters
1. Field Supplied Fan Sheave AK94 Required. Field
Supplied Belt may be necessary.
2. 3 HP Motor with Field Supplied Motor Sheave
IVP44 required.

Table PD-33 Continued


CFM
2720
3060
3400
3740
4080

RT-PRC002-EN

Tranes factory supplied motors, in commercial equipment, are definite


purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range
of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our products warranty will not be
affected.

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & High Static Drive Accessory
917 1.70 942 1.81 967 1.92 991 2.03 1014 2.14 1037 2.26
944 1.96 968 2.08 992 2.20 1015 2.32 1038 2.45 1061 2.57
973 2.26 997 2.39 1020 2.52 1043 2.65 1065 2.78 1086 2.92
1005 2.61 1028 2.74 1050 2.88 1072 3.02 1093 3.16 1114 3.30
1038 3.01 1060 3.15 1082 3.29 1103 3.44 1124

3 HP Oversized Motor & Drive

2.00
RPM BHP
1059
1082
1108
1135

2.37
2.70
3.05
3.45

37

(10 Ton)

Performance
Data

Standard

Efficiency

Table PD-34 Evaporator Fan Performance 10 Ton TCD120C


CFM
3200
3600
4000
4400
4800

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static Drive (1)
3 HP Standard Motor & Drive
649 0.93 681 1.02 713 1.12 742 1.23 769 1.31 794 1.40 820 1.49 847 1.59 873 1.7 899 1.81 924 1.92
723 1.30 751 1.40 780 1.51 807 1.62 833 1.74 857 1.84 880 1.93 903 2.03 926 2.13 950 2.25 973 2.37
798 1.76 822 1.86 848 1.98 874 2.11 898 2.24 922 2.36 944 2.48 965 2.59 985 2.69 1006 2.79 1027 2.91
873 2.32 895 2.43 918 2.55 942 2.69 965 2.83 987 2.97 1008 3.11 1029 3.24 1048 3.36 1067 3.48 1086 3.59
948 2.99 969 3.11 989 3.24 1011 3.38 1033 3.53 1054 3.68 1074 3.83 1094 3.99 1113 4.14 1131 4.28 1149 4.40
3 HP Standard Motor & Drive
5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTE:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and
filters
1. Field Supplied Fan Sheave BK90 Required. Field
Supplied Belt may be necessary.

1.20
1.30
RPM BHP RPM BHP
948
996
1048
1104
1166

2.03
2.49
3.04
3.71
4.53

972
1019
1069
1123
1183

2.13
2.62
3.17
3.83
4.65

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

Table PD-34 Continued


CFM

3200
3600
4000
4400
4800

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & High
3 HP Standard Motor & Drive
Static Drive Accessory
995 2.24 1017 2.35 1039 2.46 1061 2.58 1082 2.69 1103 2.81 1124 2.94
1041 2.74 1062 2.86 1084 2.98 1104 3.10 1125 3.23 1145 3.35 1164 3.47
1090 3.31 1111 3.45 1131 3.59 1151 3.72 1170 3.85 1190 3.99 1209 4.12
1142 3.97 1162 4.11 1181 4.26 1200 4.41 1219 4.56 1238 4.72 1256 4.87
1200 4.78 1217 4.91 1235 5.05 1252 5.21 1270 5.36 1287 5.52 1305 5.69
5 HP Oversize Motor & Drive

Table PD-35 Evaporator Fan Performance 10 Ton TCH120C

CFM

3200
3600
4000
4400
4800

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static Dr. (1)
3 HP Standard Motor & Drive

640
704
768
833

1.04
1.39
1.82
2.34

676
736
798
860

1.15
1.52
1.96
2.48

651
708
767
827
887

0.95 684 1.04 718 1.14 750 1.25


1.26 738 1.37 768 1.47 798 1.59
1.64 795 1.76 822 1.88 849 2.00
2.10 853 2.23 878 2.36 903 2.49
2.64 913 2.79 936 2.93 959 3.07
3 HP Standard Motor & Drive

782
827
876
927
982

1.35
1.70
2.12
2.62
3.21

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTE:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary.

812
856
902
952
1004

1.47
1.82
2.25
2.76
3.36

842
883
928
976
1027

1.58
1.94
2.38
2.90
3.50

870 1.69 897 1.81 923 1.93


910 2.07 937 2.20 962 2.32
954 2.51 979 2.65 1003 2.79
1000 3.04 1024 3.18 1047 3.33
1049 3.65 1071 3.80 1093 3.96
5 HP Oversize Motor & Drive

949
987
1027
1070
1115

2.04
2.45
2.93
3.48
4.11

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

Table PD-35 Continued


CFM

3200
3600
4000
4400
4800

38

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor &
3 HP Standard Motor & Drive
High Static Drive
Accessory
974 2.16 998 2.28 1021 2.40 1043 2.52 1066 2.65 1087 2.77 1108 2.90
1011 2.58 1035 2.71 1057 2.85 1079 2.98 1101 3.11 1123 3.25 1143 3.38
1051 3.07 1073 3.21 1096 3.36 1117 3.50 1139 3.65 1160 3.79 1180 3.94
1092 3.63 1114 3.78 1136 3.94 1157 4.09 1178 4.25 1198 4.41 1218 4.57
1136 4.27 1157 4.44 1178 4.60 1198 4.77 1218 4.94 1238 5.10 1258 5.28
5 HP Oversize Motor & Drive

RT-PRC002-EN

Performance
Data
Table PD-36 Evaporator Fan Performance

CFM

4000
4500
5000
5500
6000

12 1/2 Ton

(12 Ton)
Standard

Efficiency

TCD150C

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor &
3 HP Standard Motor & Drive
Field Supplied Low Static
591 1.09 628 1.23 663 1.4 698 1.52 732 1.68 764 1.84 796 2.00 827 2.16 857 2.33 886 2.50 914 2.67 942 2.85
655 1.51 689 1.67 721 1.8 753 1.98 783 2.15 813 2.32 843 2.50 871 2.69 899 2.87 927 3.05 953 3.24 980 3.43
721 2.03 752 2.20 781 2.4 810 2.55 838 2.73 866 2.91 893 3.11 920 3.31 946 3.51 971 3.71 997 3.91 1021 4.11
786 2.65 815 2.85 842 3 869 3.23 895 3.42 920 3.62 946 3.82 971 4.03 995 4.25 1019 4.47 1043 4.69 1066 4.91
853 3.40 879 3.62 905 3.8 930 4.03 954 4.24 977 4.45 1001 4.66 1024 4.88 1047 5.11 1070 5.35 1092 5.58

5 HP Oversize Motor & Drive

4000
4500
5000
5500
6000

12 1/2 Ton

969
1005
1046
1089

3.04
3.62
4.32
5.13

Table PD-36 Continued


CFM

Table PD-37 Evaporator Fan Performance

(2)

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK90 Required. Field Supplied
Belt may be necessary.
2. Field Supplied Motor Sheave IVP44 Required. Field
Supplied Belt may be necessary.
3. Field Supplied Motor Sheave IVP50 Required. Field
Supplied Belt may be necessary.

1.30
RPM BHP

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field
5 HP Oversize Motor & Drive
Supplied High Static Drive (2)
995 3.23 1021 3.43 1046 3.63 1071 3.84 1095 4.05 1118 4.27 1141 4.48
1030 3.82 1055 4.02 1079 4.23 1103 4.45 1126 4.66 1149 4.89 1171 5.11
1069 4.53 1093 4.74 1116 4.96 1138 5.18 1161 5.40 1183 5.63

1112 5.36 1134 5.58


5 HP Motor & High Static Drive (3)

TCH150C

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor &
Field Supplied Low Static
3 HP Standard Motor & Drive
Drive (1)
4000 576 1.19 613 1.34 649 1.49 684 1.65 717 1.83 750 2.00 781 2.19 812 2.38 842 2.58
4500 597 1.46 630 1.61 664 1.77 697 1.93 728 2.11 759 2.29 789 2.48 819 2.68 847 2.88 875 3.09
5000 656 1.96 686 2.13 717 2.30 747 2.48 776 2.66 804 2.86 832 3.06 860 3.27 886 3.48 913 3.70
5500 715 2.57 743 2.75 771 2.94 798 3.13 826 3.33 852 3.53 878 3.74 904 3.96 929 4.19 953 4.42
6000 776 3.29 801 3.49 826 3.70 852 3.90 877 4.11 902 4.33 926 4.55 950 4.78 974 5.02 997 5.26
5 HP Oversize
5 HP Oversize Motor & Drive
Motor & Hi Drive
(2)
For Standard Evaporator Fan Speed (RPM), reference Table PD-53.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK90 Required. Field Supplied Belt may be necessary.
2. 5 HP Oversize Motor with Field Supplied Motor Sheave IVL40 Required. Field
Supplied Belt may be necessary.

1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP

872
903
939
978
1020

2.78
3.30
3.92
4.66
5.51

901
930
964
1002

2.99
3.52
4.15
4.90

929
957
989
1025

3.21
3.75
4.39
5.14

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

Table PD-37 Continued


External Static Pressure (Inches of Water)
1.40
1.50
1.60
1.70
1.80
1.90
2.00
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Oversize Motor & Drive
4000 956 3.43 984 3.65 1010 3.88 1036 4.11 1061 4.35 1086 4.59 1110 4.83
4500 983 3.98 1008 4.21 1034 4.45 1058 4.70 1083 4.95 1107 5.20 1130 5.46
5000 1014 4.63 1038 4.88 1062 5.13 1085 5.38 1108 5.64

5500 1049 5.40 1071 5.65

6000

RT-PRC002-EN

39

(15 and 17Ton)

Performance
Data

Table PD-38 Evaporator Fan Performance

CFM

4800
5400
6000
6600
7200

15 Ton

Standard Efficiency

TCR180B

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field
3 HP Standard Motor & Drive
Supplied Low Static Drive (1)
563 1.17 596 1.29 626 1.41 656 1.52 685 1.63 714 1.76 742 1.90 768 2.04 794 2.18 819 2.30
585 1.47 618 1.60 648 1.72 676 1.86 703 1.99 729 2.12 756 2.25 782 2.38 807 2.52 832 2.68 855 2.84
643 1.99 673 2.12 701 2.26 727 2.41 752 2.56 777 2.71 801 2.85 825 2.99 848 3.13 871 3.27 894 3.43
701 2.61 729 2.76 755 2.91 780 3.07 804 3.23 827 3.39 849 3.56 871 3.72 892 3.88 914 4.03 935 4.18
760 3.35 786 3.52 810 3.69 834 3.85 856 4.02 878 4.20 899 4.38 919 4.56 939 4.74 959 4.91 979 5.08
(2)
5 HP Oversize Motor & Drive

1.20
1.30
RPM BHP RPM BHP

844
878
916
956
999

2.43 871
3.00 901
3.61 938
4.34 977
5.25 1018

2.57
3.15
3.79
4.51
5.41

Tranes factory supplied motors, in commercial equipment, are


For Standard Evaporator Fan Speed (RPM), reference Table PD-53.
definite purpose motors, specifically designed and tested to
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
operate reliably and continuously at all cataloged conditions.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
Using the full horsepower range of our fan motors as shown in our
NOTES:
tabular data will not result in nuisance tripping or premature motor
Fan motor heat (MBH) = 3.15 x Fan BHP
failure. Our products warranty will not be affected.
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK105 Required. Field Supplied Belt
may be necessary.
2. 5 HP Oversize Motor with Field Supplied Fan Sheave BK160
Required.
Table PD-38 Continued
Field Supplied Belt may be necessary.
3. 5 HP Oversize Motor with Field Supplied Motor Sheave IVP50
External Static Pressure (Inches of Water)
Required. Field Supplied Belt may be necessary.
1.40
1.50
1.60
1.70
1.80
1.90
2.00

CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & High Static Drive Accessory
4800 898 2.70 923 2.83 946 2.96 970 3.09 994 3.23 1018 3.39 1041 3.54
5400 923 3.29 945 3.43 969 3.58 993 3.73 1016 3.88 1038 4.03 1060 4.17
6000 959 3.97 980 4.15 1000 4.31 1019 4.46 1040 4.62 1061 4.78 1082 4.95

6600 997 4.70 1018 4.90 1037 5.10 1056 5.30 1075 5.49 1093 5.67
7200 1038 5.58 1057 5.77

5 HP Oversize Motor &


5 HP OS Motor & Field Supplied Drive (3)
Drive

Table PD-39 Evaporator Fan Performance 17 Ton TCR210C


CFM
5600
6300
7000
7700
8400

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor with Low Static Drive Accessory
718 2.26 742 2.38 765 2.50 789 2.63 813 2.78 836 2.92 857 3.06
745 2.84 768 2.98 791 3.11 812 3.24 833 3.37 854 3.51 875 3.65 897 3.82 918 3.98
822 3.86 843 4.01 864 4.16 884 4.31 904 4.46 923 4.60 941 4.75 960 4.90 979 5.08
900 5.11 920 5.27 939 5.44 957 5.60 976 5.77 993 5.93 1010 6.09 1027 6.24 1044 6.41
979 6.59 997 6.78 1014 6.96 1031 7.14 1048 7.32 1065 7.49 1081 7.67 1097 7.84 1113 8.02
7.5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & Low Static Drive Accessory Fan Speed (RPM), reference Table PD-56.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTE:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters

1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive
879 3.21 903 3.37 927 3.53 949 3.70
937 4.14 957 4.30 976 4.46 997 4.63
999 5.26 1018 5.44 1036 5.61 1053 5.79
1061 6.59 1079 6.78 1097 6.98 1114 7.18
1128 8.19 1143 8.37 1159 8.57

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

Table PD-39 Continued


CFM
5600
6300
7000
7700
8400

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Drive
971 3.88 993 4.06 1014 4.24 1036 4.42 1058 4.60 1079 4.79
1018 4.81 1039 4.99 1059 5.19 1079 5.38 1098 5.58 1117 5.78
1070 5.97 1088 6.15 1106 6.34 1125 6.54 1144 6.74 1163 6.95
1131 7.37 1147 7.56 1163 7.76 1179 7.95 1194 8.15 1211 8.36

7.5 HP Oversize Motor & Drive

2.00
RPM BHP
1101
1136
1181
1228

4.97
5.98
7.17
8.58

RIndicates both downflow and horizontal units.

40

RT-PRC002-EN

Performance
Data

(20Ton)
Standard Efficiency

Table PD-40 Evaporator Fan Performance 20 Ton TCR240B


CFM

6400
7200
8000
8800
9600

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Field Supplied
5 HP Standard Motor & Drive
Low Static Drive (1)
514 1.69 546 1.88 574 2.05 599 2.21 624 2.37 648 2.54 671 2.71 695 2.90 720 3.11 744 3.32 768 3.52 790 3.72
527 2.08 562 2.29 592 2.50 619 2.71 644 2.91 667 3.09 689 3.26 711 3.45 732 3.64 752 3.83 773 4.04 795 4.27 817 4.50
578 2.79 610 3.03 639 3.26 666 3.50 690 3.73 712 3.96 733 4.16 753 4.35 773 4.55 792 4.75 811 4.96 830 5.18 848 5.40
629 3.65 659 3.93 687 4.18 712 4.43 736 4.69 758 4.96 778 5.20 797 5.43 816 5.65 834 5.86 852 6.08 869 6.30 887 6.53
681 4.67 709 4.99 735 5.27 759 5.54 782 5.82 804 6.11 824 6.39 843 6.67 861 6.92 878 7.16 895 7.40 911 7.63 928 7.86
(2)
5 HP Standard Motor & Drive
7.5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.

Tranes factory supplied motors, in commercial equipment, are definite


purpose motors, specifically designed and tested to operate reliably and
continuously at all cataloged conditions. Using the full horsepower range
of our fan motors as shown in our tabular data will not result in nuisance
tripping or premature motor failure. Our products warranty will not be
affected.

NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may be
necessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave IVP50 Required.
Field Supplied Belt may be necessary.
Table PD-40 Continued

CFM

6400
7200
8000
8800
9600

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP
Standard
5 HP Standard Motor & High Static Drive Accessory
Motor & Drive
811 3.91 833 4.13 855 4.36 877 4.59 897 4.82 917 5.05 936 5.29
839 4.74 860 4.96 880 5.19 898 5.41 917 5.64 937 5.88 957 6.14
867 5.64 887 5.90 907 6.16 927 6.42 946 6.68 964 6.93 982 7.18
904 6.77 921 7.01 938 7.26 955 7.52 973 7.81 991 8.09
944 8.11 960 8.36 976 8.61
7.5 HP Oversize Motor &
Drive

RIndicates both downflow and horizontal units.


RT-PRC002-EN

41

Performance
Data

(25Ton)
Standard Efficiency

Table PD-41 Evaporator Fan Performance 25 Ton TCQ300B


CFM

7000
7500
8000
8500
9000
9500
10000
10500
11000

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
RPM BHP RPM BHP RPM BHP RPM BHPRPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Low Static Drive Accy
7.5 HP Standard
Motor & Drive
593 2.42 619 2.62 643 2.80 667 2.98 690 3.16 712 3.35 733 3.53 754 3.73
595 2.66 624 2.88 649 3.10 673 3.31 695 3.50 717 3.68 738 3.88 759 4.08 779 4.28
595 2.92 627 3.16 655 3.39 679 3.63 702 3.86 724 4.07 745 4.28 766 4.48 786 4.68 805 4.90
628 3.47 659 3.73 686 3.97 710 4.23 732 4.47 754 4.71 774 4.94 794 5.15 813 5.36 832 5.58
661 4.08 691 4.36 717 4.62 741 4.89 763 5.15 784 5.41 803 5.66 822 5.89 841 6.12 859 6.35
695 4.76 723 5.06 749 5.34 772 5.62 794 5.90 814 6.18 833 6.45 852 6.71 870 6.95 887 7.19
729 5.52 755 5.84 781 6.13 804 6.42 825 6.72 844 7.01 863 7.31 881 7.59 899 7.86 916 8.11
762 6.35 788 6.69 812 7.00 835 7.31 856 7.62 875 7.93 894 8.24 911 8.54
796 7.27 821 7.63 844 7.96 867 8.3 887 8.60

7.5 HP Standard Motor & High Static Drive
7.5 HP Standard Motor & Drive
Accessory

For Standard Evaporator Fan Speed (RPM), reference Table PD-53. Tranes factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
For Standard Motor & High Static Drive Accessory Fan Speed
reliably and continuously at all cataloged conditions. Using the full
(RPM), reference Table PD-54.
horsepower range of our fan motors as shown in our tabular data
For Standard Motor & Low Static Drive Accessory Fan Speed
will not result in nuisance tripping or premature motor failure. Our
(RPM), reference Table PD-56.
products warranty will not
NOTES:
be affected.
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and
Table PD-41 Continued
filters

CFM
7000
7500
8000
8500
9000
9500
10000
10500
11000

External Static Pressure (Inches of Water)


1.10
1.20
1.30
1.40
1.50
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Drive
776 3.95 798 4.18 820 4.40 841 4.62 862 4.84
798 4.48 818 4.71 839 4.95 860 5.19 880 5.42
824 5.11 842 5.32 860 5.55 880 5.80 899 6.06
850 5.81 868 6.03 885 6.26 902 6.49 920 6.74
877 6.58 894 6.81 911 7.05 928 7.29 944 7.53
904 7.43 921 7.67 938 7.92 954 8.17 970 8.42

933 8.36 949 8.62




7.5 HP Standard Motor & High Static Drive
Accessory

RIndicates both downflow and horizontal units.

42

RT-PRC002-EN

Performance
Data

(3, 4, 5Ton)
High Efficiency

Table PD-42 Evaporator Fan Performance 3, 4 And 5 Ton TCD037C,TCR049C,TCR061C


External Static Pressure (Inches of Water) & Motor Power (Bhp)1
Standard Motor
Oversized Motor

Tons

Unit
Model No.

High Speed

Low Speed

CFM

ESP

BHP

ESP

BHP

ESP

BHP

900
1000
1100
1200
1300
1400
1500

0.83
0.78
0.72
0.65
0.59
0.50
0.40

0.28
0.30
0.32
0.34
0.36
0.38
0.40

0.74
0.67
0.61
0.50
0.36

0.26
0.28
0.30
0.33
0.38

1.57
1.43
1.26
1.08
0.88
0.63

0.61
0.63
0.66
0.69
0.73
0.77

TCD049C*

1200
1300
1400
1500
1600
1700
1800
1900
2000

0.91
0.88
0.85
0.83
0.78
0.74
0.69
0.64
0.60

0.48
0.49
0.50
0.52
0.54
0.56
0.58
0.60
0.62

0.83
0.77
0.72
0.65
0.58
0.45

0.35
0.37
0.39
0.42
0.44
0.49

1.63
1.55
1.48
1.41
1.34
1.27
1.20
1.12

0.74
0.77
0.80
0.83
0.86
0.90
0.93
0.97

TCH049C*

1200
1300
1400
1500
1600
1700
1800
1900
2000

0.88
0.84
0.80
0.76
0.72
0.68
0.64
0.57
0.51

0.45
0.46
0.48
0.49
0.50
0.52
0.54
0.56
0.58

0.77
0.72
0.68
0.64
0.55
0.47
0.36
0.20

0.32
0.34
0.36
0.39
0.41
0.43
0.47
0.52

1.68
1.61
1.55
1.47
1.42
1.34
1.27
1.20
1.13

0.75
0.77
0.79
0.81
0.83
0.86
0.90
0.93
0.96

TCD061C*

1600
1700
1800
1900
2000
2100
2200
2300
2400

0.77
0.72
0.67
0.61
0.55
0.48
0.40
0.31
0.23

0.58
0.59
0.61
0.63
0.66
0.69
0.71
0.73
0.76

0.70
0.64
0.56
0.48
0.39
0.29
0.16

0.46
0.48
0.50
0.52
0.55
0.59
0.62
0.67

1.42
1.35
1.29
1.23
1.18
1.09
1.01
0.88
0.78

0.82
0.86
0.90
0.93
0.96
1.01
1.05
1.09
1.13

1600
1700
1800
1900
2000
2100
2200
2300
2400

0.79
0.75
0.71
0.66
0.61
0.55
0.48
0.40
0.31

0.58
0.59
0.62
0.64
0.66
0.68
0.70
0.73
0.76

0.73
0.68
0.63
0.58
0.50
0.42
0.31
0.19

0.46
0.48
0.50
0.52
0.56
0.59
0.63
0.67

1.46
1.42
1.37
1.31
1.25
1.18
1.10
1.00
0.90

0.83
0.86
0.90
0.93
0.97
1.01
1.05
1.09
1.13

TCD037C*

TCH061C*

Fan motor heat (MBH) = 4.39 x Fan Bhp.


Tranes factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and
tested to operate reliably and continuously at all cataloged conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in nuisance tripping or premature motor failure. Our products
warranty will not be affected.
NOTE:
1. Data includes pressure drop due to wet coil and filters.

RT-PRC002-EN

Indicates both downflow and horizontal units.

43

Performance
Data
Table PD-43 Evaporator Fan Performance

(6 - 7Ton)
High Efficiency

6-7 Ton TCR074C - 086C,TCR091D

External Static Pressure (Inches of Water)


Unit
.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.25
1.50
Model No. CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1 HP Standard Motor & Field Supplied
Low Static Drive1
2000 615 0.37 663 0.41 710 0.45 756 0.49 799
2250 681 0.52 723 0.56 766 0.61 807 0.65 848
TCD074C
2500 748 0.69 785 0.74 824 0.79 862 0.84 899
TCH074C
2750 816 0.91 849 0.96 884 1.02 920 1.08 954
3000 884 1.17 915 1.23 946 1.29 979 1.35 1011
1 HP Standard Motor & Sheaves

TCD086
TCH086

1 HP Standard Motor & Field Supplied


Low Static Drive1
2000 615 0.37 663 0.41 710 0.45
2250 681 0.52 723 0.56 766 0.61
2500 748 0.69 785 0.74 824 0.79
2750 816 0.91 849 0.96 884 1.02
3000 884 1.17 915 1.23 946 1.29

2400
2700
TCD091D
3000
TCH091D
3000
3600

721
802
884
966
1048

0.62
0.86
1.17
1.54
1.98

760
836
915
994
1075

0.52 843 0.55 884 0.58


0.69 886 0.73 925 0.76
0.89 936 0.93 971 0.98
1.13 988 1.18 1021 1.23
1.41 1042 1.47 1073 1.52

756 0.49 799 0.52 843 0.55 884


807 0.65 848 0.69 886 0.73 925
862 0.84 899 0.89 936 0.93 971
920 1.08 954 1.13 988 1.18 1021
979 1.35 1011 1.41 1042 1.47 1073
1 HP Standard Motor & Sheaves

1 HP Standard Motor & Sheaves


0.66 801 0.71 840 0.76 879 0.80 916
0.92 872 0.97 908 1.03 943 1.08 977
1.23 946 1.29 979 1.35 1011 1.41 1042
1.60 1022 1.67 1051 1.73 1081 1.80 1111
2.06 1101 2.12 1126 2.20 1153 2.27 1181
2 HP Oversize Motor & Sheaves

Data includes pressure drop due to filters and wet coil.


Fan motor heat (MBH) = 3.53 x Fan Bhp.
NOTE:
1. Requires a field supplied Browning sheave AL74 and Belt A48.

0.85
1.13
1.47
1.87
2.34

952
1011
1073
1139
1208

924 0.60 965 0.62 1006 0.63


964 0.79 1000 0.82 1035 0.84 1126
1005 1.02 1041 1.06 1075 1.09 1154
1053 1.28 1084 1.32 1116 1.37 1195
1104 1.57 1134 1.63 1163 1.68 1236
2 HP Oversize Motor & Sheaves

0.58
0.76
0.98
1.23
1.52

924
964
1005
1053
1104

0.60
0.79
1.02
1.28
1.57

965
1000
1041
1084
1134

0.89
1.17
1.52
1.93
2.42

988
1043
1104
1167
1234

0.92
1.22
1.57
1.99
2.49

1025 0.96
1075 1.27
1134 1.63
1195 2.05
1260

0.90 1209 0.92


1.16 1237 1.22
1.46 1266 1.54
1.80

0.62 1006 0.63

0.82 1035 0.84 1126 0.90 1209 0.92


1.06 1075 1.09 1154 1.16 1237 1.22
1.32 1116 1.37 1195 1.46 1266 1.54
1.63 1163 1.68 1236 1.80

2 HP Oversize Motor & Sheaves


1058
1108
1163
1223

0.99
1.31
1.68
2.11

1142
1186
1236
1289

1.05 1226 1.10


1.40 1259 1.47
1.80

2.26

Tranes factory supplied motors, in commercial equipment, are definite purpose


motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown
in our tabular data will not result in nuisance tripping or premature motor failure.
Our products warranty will not be affected.

RIndicates both downflow and horizontal units.

44

RT-PRC002-EN

Performance
Data

Table PD-44 Evaporator Fan Performance

CFM

.10
RPM BHP

2720
3060
3400
3740
4080

494
540
587
634

0.61
0.81
1.06
1.35

(8Ton)
High Efficiency

8 Ton TCR103C

External Static Pressure (Inches of Water)


.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & Field
Supplied Low Static Drive (1)
2 HP Standard Motor & Drive
497 0.52 534 0.59 572 0.67 612 0.75 645 0.82 677 0.90 709 0.98 741 1.1 772 1.17 801 1.27 829 1.37 855 1.47
537 0.70 575 0.78 607 0.86 642 0.94 677 1.03 708 1.12 737 1.20 765 1.3 794 1.38 823 1.49 851 1.60 877 1.70
578 0.91 616 1.00 648 1.09 677 1.18 707 1.27 740 1.37 770 1.47 796 1.6 822 1.66 848 1.75 874 1.86 899 1.97
621 1.17 657 1.27 689 1.37 717 1.47 743 1.56 771 1.67 800 1.78 829 1.9 855 1.99 879 2.09 902 2.19 925 2.30
666 1.47 698 1.59 730 1.70 759 1.80 784 1.91 807 2.01 832 2.12 859 2.2 886 2.36 911 2.48 935 2.59 957 2.71
3 HP Oversized Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTE:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave AK89 Required. Field Supplied Belt
may be necessary.

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

Table PD-44 Continued

CFM

2720
3060
3400
3740
4080

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor 2 HP Standard Motor & High Static Drive
& Drive
Accessory
881 1.58 906 1.69 932 1.80 956 1.92 981 2.05 1005 2.18
903 1.81 928 1.92 952 2.04 975 2.15 998 2.28 1020 2.40
925 2.09 950 2.21 974 2.33 997 2.45 1020 2.57 1041 2.70
949 2.41 972 2.53 996 2.65 1019 2.79 1041 2.92 1063 3.05
978 2.81 999 2.92 1021 3.04 1042 3.17 1064 3.30

3 HP Oversized Motor & Drive

2.00
RPM BHP

1028 2.31
1042 2.53
1063 2.82

RIndicates both downflow and horizontal units.


RT-PRC002-EN

45

Performance
Data

Table PD-45 Evaporator Fan Performance

CFM

3200
3600
4000
4400
4800

(10Ton)
High Efficiency

10 Ton TCD121C

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor &
2 HP Standard Motor &
Field Supplied Low
Drive
Static Drive (1)
444 0.48 500 0.60 549 0.72 592 0.84 632 0.95 669 1.06 703 1.17 735 1.28
402 0.44 469 0.60 524 0.75 572 0.88 615 1.02 654 1.15 690 1.28 725 1.40 757 1.53
430 0.56 495 0.74 549 0.91 596 1.07 638 1.22 677 1.37 713 1.52 746 1.66 778 1.80
459 0.71 521 0.91 574 1.10 620 1.27 662 1.45 700 1.62 735 1.78 769 1.94 801 2.10
488 0.87 548 1.10 599 1.31 645 1.51 686 1.70 723 1.89 759 2.07 792 2.25 823 2.43
2 HP Standard Motor & Drive

1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & High
Static Drive Accessory
766 1.38 795 1.48 823 1.61 851 1.73
787 1.65 816 1.77 844 1.89 871 2.00
809 1.94 838 2.08 865 2.21 892 2.35
831 2.26 859 2.41 887 2.56 913 2.71
853 2.60 881 2.78 909 2.95 935 3.11
3 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


Tranes factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
definite purpose motors, specifically designed and tested to operate
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
NOTES:
will not result in nuisance tripping or premature motor failure. Our
Fan motor heat (MBH) = 3.15 x Fan BHP
products warranty will not be affected.
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave AK89 Required. Field Supplied Belt may
be necessary.
2. 3 HP Oversize Motor with Field Supplied Motor Sheave BK85 Required.
Table PD-45 Continued
Field Supplied Belt may be necessary.

CFM

3200
3600
4000
4400
4800

Table PD-46 Evaporator Fan Performance

CFM

3200
3600
4000
4400
4800

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & High
3 HP Oversize Motor & Drive
Static Drive Accessory
879 1.85 906 1.98 932 2.13 956 2.28 980 2.44 1004 2.60 1026 2.75
897 2.12 922 2.26 946 2.40 971 2.54 996 2.68 1020 2.83 1043 2.99
918 2.48 943 2.61 967 2.73 990 2.87 1013 3.01 1035 3.17 1057 3.33
939 2.86 964 3.01 988 3.16 1011 3.31 1033 3.45

961 3.28 985 3.45

10 Ton TCH121C

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

406
442
479
515

0.58
0.76
0.98
1.25

2 HP Standard Motor & Field


Supplied Low Static Drive (1)
411 0.51 450 0.61 487 0.71
444 0.67 479 0.78 513 0.88
477 0.87 510 0.98 541 1.10
512 1.10 542 1.22 572 1.35
548 1.39 576 1.51 603 1.64

2 HP Standard Motor & Drive


523
546
572
600
630

0.82
1.00
1.22
1.48
1.79

558
578
602
628
656

0.93
1.12
1.35
1.61
1.93

591
609
631
655
682

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave AK89 Required. Field Supplied Belt may
be necessary.
2. 3 HP Oversize Motor with Field Supplied Fan Sheave BK85 Required
Field Supplied belt may be necessary.

623
640
659
682
707

1.18
1.38
1.62
1.90
2.22

653
669
687
708
731

1.31
1.52
1.76
2.05
2.38

682 1.43 710 1.57 737 1.70


697 1.66 724 1.80 750 1.95
714 1.91 740 2.07 766 2.23
733 2.20 758 2.36 783 2.53
755 2.54 779 2.70 802 2.87
3 HP Oversize Motor & Drive

763
775
791
807
825

1.85
2.09
2.38
2.70
3.05

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

Table PD-46 Continued

CFM

3200
3600
4000
4400
4800

46

1.06
1.25
1.48
1.75
2.07

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP Standard Motor & High
3 HP Oversize Motor & Drive
Static Drive Accessory
789 2.00 814 2.15 838 2.31 862 2.47 884 2.63 906 2.79 927 2.95
800 2.24 824 2.40 848 2.56 871 2.72 894 2.89 916 3.06 938 3.24
814 2.54 838 2.70 860 2.86 883 3.02 905 3.19 926 3.37
831 2.87 853 3.04 876 3.21 897 3.39
848 3.23 870 3.42
RT-PRC002-EN

Performance
Data
Table PD-47 Evaporator Fan Performance

CFM

4000
4500
5000
5500
6000

(12 Ton)
High

Efficiency

12 Ton TCD151C

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Stnd Motor &
3 HP Standard Motor & Field
3 HP Standard Motor & Drive
High Static Drive
Supplied Low Static Drive (1)
Accessory
549 0.91 596 1.07 638 1.22 677 1.37 713 1.52 746 1.66 778 1.80 809 1.94 838 2.08 865 2.21 892 2.35
528
0.95
580
1.15
626
1.33
668
1.51
706
1.68
741
1.85
775
2.02
806
2.18
836
2.34
865
2.50
892
2.66 919 2.81

503 0.96 562 1.20 613 1.42 657 1.63 698 1.83 735 2.03 770 2.23 803 2.42 835 2.60 864 2.79 893 2.97 920 3.15 946 3.32
540 1.22 597 1.49 646 1.74 689 1.98 729 2.21 766 2.43 800 2.65 833 2.86 864 3.07 893 3.28 921 3.49 948 3.69 974 3.89
578 1.53 633 1.82 680 2.10 722 2.37 761 2.62 797 2.87 831 3.12 863 3.36 893 3.59 922 3.82 950 4.05 977 4.28 1002 4.50
5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


Tranes factory supplied motors, in commercial equipment, are
For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
definite purpose motors, specifically designed and tested to operate
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
NOTE:
not result in nuisance tripping or premature motor failure. Our
Fan motor heat (MBH) = 3.15 x Fan BHP
products warranty will not be affected.
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK115 Required. Field Supplied
Belt may be necessary.
Table PD-47 Continued

CFM

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

4000
4500
5000
5500
6000

918
944
971
999
1027

3 HP Standard Motor & High Static Drive Accessory

Table PD-48 Evaporator Fan Performance


CFM

.10
.20
RPM BHP RPM BHP

4000
4500
5000
5500
6000

521 1.17
534 1.40 566 1.54
581 1.83 611 1.99
628 2.34 657 2.51

2.48
2.97
3.50
4.09
4.72

1013
1039
1065
1092
1120

3.01
3.57
4.19
4.86
5.59

1035
1061
1087
1114

3.17
3.72
4.36
5.05

1057
1082
1108
1135

3.33
3.85
4.52
5.24

12 Ton TCH151C

External Static Pressure (Inches of Water)


.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & Field Supplied Low Static
3 HP Standard Motor & Drive
Drive (1)
510 0.98 541 1.10 572 1.22 602 1.35 631 1.48 659 1.62 687 1.76 714 1.91 740 2.07 766 2.23
551 1.29 579 1.42 607 1.56 635 1.68 662 1.82 688 1.98 713 2.13 738 2.28 763 2.44 787 2.61
593 1.67 620 1.81 645 1.95 671 2.11 696 2.25 720 2.40 744 2.56 767 2.73 790 2.90 812 3.07
637 2.13 661 2.28 685 2.43 709 2.59 732 2.76 754 2.92 777 3.08 799 3.25 820 3.43 842 3.61
682 2.68 704 2.83 727 3.00 749 3.16 770 3.33 791 3.52 812 3.70 833 3.87 853 4.04 874 4.23
5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTE:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK115 Required. Field Supplied Belt
may be necessary.

1.30
RPM BHP

791
811
835
862
893

2.38
2.78
3.24
3.80
4.43

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

Table PD-48 Continued


CFM

4000
4500
5000
5500
6000

RT-PRC002-EN

943 2.61 967 2.73 990 2.87


969 3.12 993 3.27 1016 3.42
996 3.67 1020 3.85 1043 4.02
1023 4.28 1047 4.48 1070 4.67
1051 4.94 1075 5.16 1098 5.38
5 HP Oversize Motor & Drive

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard
3 HP Standard Motor & High Static
Motor & Drive
Drive Accessory
814 2.54 838 2.70 860 2.86 883 3.02 905 3.19 926 3.37 948 3.55
835 2.96 858 3.13 880 3.31 901 3.48 922 3.66 943 3.84 963 4.02
857 3.42 879 3.61 901 3.81 922 4.00 942 4.20 962 4.39 982 4.59
883 3.98 904 4.17 924 4.37 944 4.57 964 4.78 984 4.99 1003 5.20
913 4.63 932 4.83 951 5.03 970 5.24 988 5.45 1007 5.66

5 HP Oversize Motor & Drive

47

Performance
Data
Table PD-49 Evaporator Fan Performance

CFM

4800
5400
6000
6600
7200

(15, 17 Ton)

High

Efficiency

15 Ton TCR181C

External Static Pressure (Inches of Water)


.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
1.30
.10
.20
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP

445
479
519
560

1.04
1.38
1.79
2.28

3 HP Standard Motor & Field


Supplied Low Static Drive (1)
444 0.84 472 0.99 503 1.14 535 1.29 566
474 1.19 506 1.33 536 1.47 564 1.62 592
513 1.55 543 1.72 571 1.87 597 2.03 623
552 1.98 580 2.17 606 2.35 632 2.52 656
591 2.49 618 2.70 643 2.91 667 3.09 690
3 HP Standard Motor & Drive

3 HP Standard Motor & Drive


1.44
1.78
2.19
2.69
3.27

598
621
648
679
712

1.60
1.95
2.36
2.87
3.46

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTE:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK120 Required. Field Supplied Belt may
be necessary. Field Supplied Belt may be necessary.

Field Supplied Belt may be necessary.

629
648
673
702
734

1.77
2.12
2.55
3.05
3.65

658
676
699
725
755

1.94 684 2.11 710 2.29 735 2.48


2.30 704 2.49 730 2.68 755 2.88
2.74 723 2.93 749 3.13 774 3.34
3.25 748 3.46 771 3.7 794 3.88
3.85 776 4.06 797 4.29 818 4.51
5 HP Oversize Motor & Drive

760
778
798
816
839

2.68
3.07
3.56
4.09
4.74

3 HP Standard Motor & High


Static Drive Accessory
Tranes factory supplied motors, in commercial equipment, are
definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data will
not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

Table PD-49 Continued


CFM

4800
5400
6000
6600
7200

Table PD-50 Evaporator Fan Performance


CFM

.10
.20
RPM BHP RPM BHP

5600
6300
7000
7700
8400

532 1.76
546 2.11 578 2.31
594 2.75 625 2.98
642 3.52 671 3.78

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
3 HP Standard Motor & High
Static Drive Accessory
5 HP Oversize Motor & Drive
785 2.88 809 3.09 832 3.29 854 3.49 876 3.69 898 3.90 919 4.10
800 3.28 823 3.49 845 3.71 867 3.94 889 4.17 910 4.40 931 4.62
821 3.77 842 3.99 863 4.20 884 4.43 904 4.66 924 4.90 944 5.15
839 4.32 862 4.56 884 4.80 904 5.03 924 5.27 943 5.51 961 5.75
860 4.96 881 5.20 902 5.45 923 5.70

5 HP Oversize Motor & Drive

17 Ton TCR211C

External Static Pressure (Inches of Water)


.30
.40
.50
.60
.70
.80
.90
1.00
1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard M otor & Field
5 HP Standard M otor & Drive
Supplied Low Static Drive (1)
518 1.45 547 1.60 575 1.75 602 1.91 629 2.08 656 2.26 683 2.43 710 2.63 736 2.83 761 3.03 785 3.23
561 1.94 588 2.10 614 2.26 639 2.43 663 2.60 687 2.79 711 2.99 735 3.19 759 3.38 783 3.59 807 3.82
606 2.52 631 2.71 655 2.89 678 3.07 701 3.25 723 3.44 744 3.64 766 3.85 788 4.07 810 4.29 831 4.51
651 3.21 675 3.43 698 3.64 720 3.84 741 4.03 761 4.23 782 4.44 801 4.65 821 4.87 841 5.10 861 5.34
697 4.03 720 4.27 741 4.51 762 4.73 782 4.95 802 5.16 821 5.38 840 5.60 858 5.82 876 6.06 894 6.30
5 HP Standard M otor & High
5 HP Standard Motor & Drive
7.5 HP Oversize M otor & Drive
Static Drive Accessory

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTE:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK190 Required. Field
Supplied Belt may be necessary.

Table PD-50 Continued


CFM

Indicates
bothboth
downflow
andand
horizontal
units
. .
Indicates
downflow
horizontal
units

48

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
products warranty will not be affected.

5600
6300
7000
7700
8400

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard
5 HP Standard Motor & High Static Drive
M otor & Drive
Accessory
807 3.43 829 3.64 851 3.86 872 4.09 893 4.32 914 4.56 935 4.80
830 4.04 853 4.27 874 4.49 894 4.72 913 4.95 933 5.19 952 5.43
852 4.74 874 4.97 895 5.22 917 5.47 937 5.72 957 5.97 975 6.22
881 5.59 900 5.83 919 6.07 939 6.32 958 6.58 978 6.85 997 7.12
912 6.55 930 6.81 949 7.08 967 7.34 984 7.60 1002 7.87

7.5 HP Oversize Motor & Drive

RT-PRC002-EN

Performance
Data

Table PD-51 Evaporator Fan Performance


CFM

6400
7200
8000
8800
9600

(20Ton)
High Efficiency

20 Ton TCR241C

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & Field
5 HP Standard Motor & Drive
Supplied Low Static Drive (1)
506 1.64 540 1.84 570 2.03 595 2.19 620 2.34 644 2.51 669 2.69 693 2.89 717 3.09 741 3.29
560 2.28 592 2.50 620 2.72 646 2.92 668 3.10 690 3.27 711 3.45 733 3.65 755 3.86 777 4.08
616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.03
671 4.04 698 4.29 724 4.55 747 4.83 769 5.10 790 5.34 808 5.56 826 5.77 844 5.98 861 6.20
728 5.19 753 5.46 776 5.74 799 6.04 820 6.34 840 6.63 859 6.90 876 7.14 893 7.37 909 7.59
(2)
7.5 HP Oversize Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed (RPM), reference Table PD-54.
For Oversize Evaporator Fan Speed (RPM), reference Table PD-55.
NOTES:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and filters
1. Field Supplied Fan Sheave BK190 Required. Field Supplied Belt may
be necessary.
2. 7.5 HP Standard Motor with Field Supplied Motor Sheave 1VP50
Required. Field Supplied Belt may be necessary.

Table 45-2

Evaporator Fan

Table 45-1

1.10
1.20
1.30
RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & High
Static Drive Accessory
765 3.49 788 3.70 810 3.91
799 4.31 820 4.53 841 4.76
837 5.26 857 5.51 876 5.76
879 6.43 897 6.67 915 6.93
925 7.83 941 8.07 958 8.32

Tranes factory supplied motors, in commercial equipment, are


definite purpose motors, specifically designed and tested to operate
reliably and continuously at all cataloged conditions. Using the full
horsepower range of our fan motors as shown in our tabular data
will not result in nuisance tripping or premature motor failure. Our
Continued
products warranty will not be affected.

Table PD-51 Continued

External Static Pressure (Inches of Water)


1.40
1.50
1.60
1.70
1.80
1.90
2.00
Performance
25BHP
Ton
CFM RPM
RPMTC
BHP 301C
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
5 HP Standard Motor & High Static Drive Accessory
6400 832 4.12 854 4.34 875 4.57 896 4.80 916 5.04 936 5.29 955 5.54
7200 862 4.99 883 5.22 902 5.46 922 5.69 942 5.94 961 6.19 980 6.44

8000 896 6.01 915 6.26 934 6.52 953 6.77 971 7.03 989 7.29
8800 933 7.19 951 7.46 969 7.74 986 8.01

9600 974 8.58

7.5 HP Oversize Motor & Drive

RIndicates both downflow and horizontal units.


RT-PRC002-EN

49

Performance
Data

Table PD-52 Evaporator Fan Performance

CFM
7000
7500
8000
8500
9000
9500
10000
10500
11000

(25Ton)
High Efficiency

25 Ton TCR301C

External Static Pressure (Inches of Water)


.10
.20
.30
.40
.50
.60
.70
.80
.90
1.00
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Drive
7.5
HPHP
Std
Mtr & Low
Static
Drive
7.5
Standard
Motor
& Low

608 2.54 633 2.73 656 2.89 678 3.06 700 3.25 723 3.44 745 3.65 768 3.87

611 2.78 640 3.02 665 3.24 687 3.43 708 3.61 729 3.79 749 3.98 770 4.19 792 4.41
616 3.07 645 3.31 672 3.56 696 3.80 719 4.02 739 4.22 759 4.41 778 4.60 797 4.81 817 5.03
650 3.66 678 3.90 704 4.16 728 4.43 750 4.68 771 4.90 790 5.10 808 5.31 826 5.52 844 5.74
685 4.31 712 4.56 737 4.83 760 5.12 782 5.39 802 5.65 821 5.88 839 6.09 856 6.30 873 6.53
721 5.04 746 5.30 770 5.58 792 5.88 814 6.18 834 6.46 853 6.72 870 6.96 887 7.18 903 7.41
756 5.85 780 6.12 803 6.41 825 6.72 846 7.04 866 7.35 884 7.64 902 7.90 918 8.14 934 8.38
791 6.74 814 7.03 836 7.33 858 7.64 878 7.98 898 8.31 916 8.62


827 7.71 849 8.02 870 8.33 891 8.63


7.5 HP Standard Motor & Drive

For Standard Evaporator Fan Speed (RPM), reference Table PD-53.


For Standard Motor & High Static Drive Accessory Fan Speed
(RPM), reference Table PD-54.
For Standard Motor & Low Static Drive Accessory Fan Speed
(RPM), reference Table PD-56.
NOTE:
Fan motor heat (MBH) = 3.15 x Fan BHP
Data includes pressure drop due to wet coils and
filters
Tranes factory supplied motors, in commercial equipment,
are definite purpose motors, specifically designed and tested
to operate reliably and continuously at all cataloged
conditions. Using the full horsepower range of our fan
motors as shown in our tabular data will not result in
nuisance tripping or premature motor failure. Our products
warranty will not be affected.

7.5 HP Standard Motor & High Static Drive

Table PD-52 Continued


External Static Pressure (Inches of Water)
1.10
1.20
1.30
1.40
CFM RPM BHP RPM BHP RPM BHP RPM BHP
7.5 HP Standard Motor & Drive
7000 790 4.09 812 4.31 833 4.53 854 4.76
7500 813 4.65 833 4.88 854 5.12 874 5.36
8000 837 5.26 857 5.51 876 5.76 896 6.01
8500 863 5.97 881 6.21 900 6.46 919 6.73
9000 890 6.76 908 7.00 925 7.25 943 7.52
9500 919 7.64 936 7.88 952 8.13 969 8.40
10000 949 8.62

10500

11000

1.50
RPM BHP
875
894
915
937
961
985

4.99
5.59
6.26
6.99
7.79
8.67

7.5 HP Standard Motor & High Static Drive

Indicates both downflow and horizontal units.

50

RT-PRC002-EN

Performance
Data

(6-25Ton)

Table PD-53 Standard Motor & Sheave/Fan Speed (RPM)1


Tons

Unit
Model No.

6 Turns
Open

5 Turns
Open

4 Turns
Open

3 Turns
Open

2 Turns
Open

1 Turn
Open

6, 6
7, 7

Closed

TCR074,075
TCR086,090,091

N/A
N/A

735
722

805
791

875
860

945
929

1015
998

1085
1066

TCD102
TCH102
TCR103

N/A
N/A
N/A

725
604
649

773
652
701

822
701
753

870
749
805

919
798
857

967
846
909

TCR120
TCR121
TCR150
TCR151

807
N/A
706
640

857
519
756
680

908
571
807
720

958
623
857
760

1009
675
908
800

1059
779
958
840

N/A
N/A
N/A
N/A

15

TCR180
TCR181

679
560

721
600

764
640

806
680

849
720

891
760

N/A
N/A

17

TCR210
TCR211

869
615

923
659

978
703

1032
747

1087
791

1141
835

N/A
N/A

20

TCR240,TCR241

615

659

703

747

791

835

N/A

25

TCR300,TCR301

705

742

779

817

854

891

N/A

10
12

Table PD-54 Standard Motor & High Static Drive Accessory Fan Speed (RPM)
Tons
8
10

Unit
Model No.
TCR102
TCR103
TCR120
TCR121

6 Turns
Open

5 Turns
Open

4 Turns
Open

3 Turns
Open

2 Turns
Open

1 Turn
Open

Closed

N/A
N/A
958
N/A

870
779
1008
779

918
831
1059
831

967
883
1109
883

1015
935
1160
935

1064
987
1210
987

1112
1039
N/A
1039

12

TCR151

807

857

908

958

1009

1059

N/A

15

TCR180
TCR181
TCR211
TCR240/TCR241

806
640
835
835

849
680
879
879

891
720
923
923

934
760
967
967

976
800
1011
1011

1019
840
1055
1055

N/A
N/A
N/A
N/A

TCR300/TCR301
816
853
890
928
Table PD-55 Oversize Motor & Sheave/Fan Speed (RPM)

965

1002

N/A

17
20
25

Tons

Unit
Model No.

6 Turns
Open

5 Turns
Open

4 Turns
Open

3 Turns
Open

2 Turns
Open

1 Turn
Open

6, 6,7
7

Closed

TCR074,075,086
TCR090,TCR091

N/A
N/A

923
923

992
992

1060
1060

1129
1129

1197
1197

1265
1265

TCR102
TCR103

958
807

1008
857

1059
908

1109
958

1160
1009

1210
1059

N/A
N/A

10

TCR120
TCR121

1032
807

1086
857

1141
908

1195
958

1250
1009

1304
1059

N/A
N/A

12

TCR150
TCR151

869
869

923
923

978
978

1032
1032

1087
1087

1141
1141

N/A
N/A

15

TCR180
TCR181

806
705

856
755

907
806

957
856

1008
907

1058
957

N/A
N/A

17

TCR210
TCR211

949
816

1008
853

1068
890

1127
928

1187
965

1246
1002

N/A
N/A

928

965

1002

N/A

TCR240,TCR241
816
853
890
Table PD-56 Standard Motor & Low Static Fan Drive
20

NOTE:
1. Factory set at 3 turns open.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

Tons

Unit
Model No.

17
25

TCR210
TCR300/TCR301

6 Turns
Open

5 Turns
Open

4 Turns
Open

3 Turns
Open

2 Turns
Open

1 Turn
Open

Closed

705
594

755
631

806
668

856
705

907
742

957
779

N/A
N/A

51

Performance
Data

(3-17Ton)

Table PD-57 Static Pressure Drops Through Accessories (Inches Water Column)

Unit
Model No.

Economizer with
OA/RA Dampers2

Electric Heater
Accessory (KW)3

CFM

Standard
Filters1

100% OA

100% RA

5-12

14-23

TCR036C
TCR037C

960
1200
1440

.03
.04
.04

.05
.06
.07

.01
.01
.01

.01
.01
.02

.01
.02
.03

TCR048C
TCR049C

1280
1600
1920

.04
.06
.09

.06
.02
.10

.01
.08
.03

.01
.02
.03

.02
.04
.06

TCR060C

1600
2000
2400

.04
.06
.08

.08
.10
.12

.02
.03
.06

.02
.03
.05

.04
.07
0.11

TCR061C

1600
2000
2400

.02
.04
.06

.08
.10
.12

.01
.01
.02

.01
.01
.01

.01
.01
.02

6, 6, 7

TCR075C
TCR074C
TCR086C

2000
2500
3000

.04
.07
0.10

.10
.13
.15

.01
.02
.03

.01
.02
.03

.02
.04
.05

TCR090C, D
TCR091D

2400
3000
3600

.06
.10
.15

.12
.15
.20

.02
.03
.03

.02
.03
.04

.03
.05
.07

TCD/TCH102C

2720
3400
4080

.08/.05
.13/.08
.18/.12

.13
.16
.19

.07/.03
.11/.04
.16/.07

.06/.05
.08
.11

.07
.11/.12
.15/.16

TCD/TCH103C

2720
3400
4080

.04/.04
.06/.07
.08/.09

.13
.16
.19

.04
.06
.08

.02
.03
.04

.03
.04
.06

TCD/TCH120C

3200
4000
4800

.11/.07
.17/.11
.25/.16

.15
.19
.22

.10/.04
.15/.06
.22/.10

.07/.08
.11
.14/.18

0.10
.15/.16
.19/.23

TCR121C

3200
4000
4800

.03
.05
.07

.13
.19
.25

.01
.02
.03

.03
.04
.06

.03
.05
.07

.04
.06
.09

TCD/TCH150C

4000
5000
6000

.08/.09
.12/.14
.17/.20

.19
.23
.28

.07
.12
.17

.07/.05
.10/.08
.14/.11

.09/.07
.13/.11
.18/.15

0.11/.08
0.16/0.13
.22/.19

TCR151C

4000
5000
6000

.05
.07
.10

.19
.26
.33

.02
.03
.04

.03
.04
.06

.03
.05
.07

.04
.06
.09

TCR180B

4800
6000
7200

.07
.10
.15

.25
.33
.40

.03
.04
.05

.04
.06
.09

.04
.07
.10

.05
.08
.12

TCD/TCH181C

4800
6000
7200

.04/.03
.06/.05
.09/.07

.14
.20
.27

.03
.04
.05

04
06
09

.04
.07
.10

.05
.08
.12

TCR210C

5600
7000
8400

.09
.14
.20

.30
.39
.47

.04
.05
.06

.06
.10
.15

.07
.11
.17

TCD/TCH211C

5600
7000
8400

.06/.05
.09/.07
.12/.10

.18
.26
.35

.04
.04
.06

.05
.08
.12

.06
.09
.13

.07
.11
.16

Tons

10

12

15

17

36

54

72

.03
.05
.07

NOTES:
1. Tested with: 1" filters 3-7 tons, 2" filters 8-25 tons
2. OA = Outside Air and RA = Return Air.
3. Nominal KW ratings at 240, 480, 600 volts.

RIndicates both downflow and horizontal units.

52

RT-PRC002-EN

Performance
Data

(20, 25Ton)

Table PD-57 Static Pressure Drops Through Accessories (Inches Water Column) Continued

Tons

Unit
Model No.

Economizer with
OA/RA Dampers2

Electric Heater
Accessory (KW)3

CFM

Standard
Filters1

100% OA

100% RA

TCD240B
TCD241C

6400
8000
9600

.07
.11
.16

.22
.32
.44

.04
.05
.07

.06
.10
.14

.08
.12
.17

.09
.14
.20

TCH240B
TCH241C

6400
8000
9600

.06
.09
.13

.22
.32
.44

.04
.05
.07

.06
.10
.14

.08
.12
.17

.09
.14
.20

TCD300B
TCD301C

7000
9000
11000

.09
.14
.21

.26
.40
.57

.04
.07
.10

.08
.13
.18

.10
.15
.22

.11
.18
.26

TCH300B
TCH301C

7000
9000
11000

.07
.11
.17

.26
.40
.60

.04
.07
.10

.08
.13
.18

.10
.15
.22

.11
.18
.26

20

25

5-12

14-23

36

54

72

NOTES:
1. Tested with: 1" filters 3-7 tons, 2" filters 8-25 tons
2. OA = Outside Air and RA = Return Air.
3. Nominal KW ratings at 240, 480, 600 volts.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

53

Performance
Data

(3-25Ton)

Table PD-58 Auxiliary Electric Heat Capacity


Total2
Tons

Unit
Model No.

KW
Input1

MBH
Output1

No. of
Stages

TCD036C1

5.00
10.00
13.80

17.07
34.14
47.10

TCD036C3, C4
TCD037C3, C4

6.00
12.00
17.40
5.00
10.00
13.80
17.60
6.00
12.00
17.40
23.00

TCR048, 060C1
4, 5

Stage1

TCR048, 060C3, C4, CW


TCR049C3, C4

Stage 2

KW
Input1

MBH
Output1

KW
Input1

MBH
Output1

1
2
2

5.00
5.00
8.80

17.07
17.07
30.03

5.00
5.00

17.07
17.07

20.48
40.96
59.39

1
2
2

6.00
6.00
8.70

20.48
20.48
29.69

6.00
8.70

20.48
29.69

17.07
34.14
47.10
60.07
20.48
40.96
59.39
78.50

1
2
2
2
1
2
2
2

5.00
5.00
8.80
8.80
6.00
6.00
8.70
14.30

17.07
17.07
30.03
30.03
20.48
20.48
29.69
48.81

5.00
5.00
8.80

17.07
17.07
30.03

6.00
8.70
8.70

20.48
29.69
29.69

5,6, 6, 7, 7

TCR061C3,C4
TCR074, 75C3, C4, CW
TCR090C3, D3, C4, D4, CW, DW
TCR086C,TCR091D

9.003
17.303, 4
18.00
27.004
36.003, 4

30.72
59.04
61.43
92.15
122.87

1
1
1
2
2

9.00
17.30
18.00
18.00
18.00

30.7
59.0
61.4
61.4
61.4

9.00
18.00

TCR102, 120, 150C3, C4, CW


TCR180B3, B4, BW
TCR103, 121, 151 or 181C3, C4,CW

18.00
36.00
54.005

61.47
122.94
184.41

1
2
2

18.00
18.00
36.00

61.47
61.47
122.94

18.00
18.00

8-15

17, 20, 25

TCR210C3, C4, CW,


240, 300B3, B4, BW
TCR211, 241, 301C3,C4,CW

36.00
54.00
72.006

122.94
184.41
245.88

2
2
2

18.00
36.00
36.00

61.47
122.94
122.94

18.00
18.00
36.00

61.47
61.47
122.94

NOTES:
1. Does not include indoor fan power or heat.
2. Heaters are rated at 240v, 480v. and 600v. For other than rated voltage, CAP =
3. Not available for TCR075, 090CW.
4. Not available for TCR061C3,C4.
5. Not available on TCR102, 120C.
6. Not available on TCR210C.

Voltage
Rated Voltage

30.7
61.4
61.47
61.47

x rated cap.

Table PD-59 Electric Heater Voltage


Correction Factors (Applicable to Auxiliary
Heat Capacity)
Nominal
Voltage

Distribution
Voltage

Capacity
Multiplier

240

208
230
240

0.75
0.92
1.00

480

440
460
480

0.84
0.94
1.00

600

540
575
600

0.81
0.92
1.00

RIndicates both downflow and horizontal units.

54

RT-PRC002-EN

Performance
Data

(3-25Ton)

Table PD-60 Air Temperature Rise Across Electric Heaters (Degree F)


3 Ton
1200 CFM
Single Phase
KW
5.00
6.00
10.00
12.00
13.80
17.40
17.60
23.00

Stages

TCD036C1

1
1
2
2
2
2
2
2

13.2

26.4

36.4

4 Ton
1600 CFM

Three Phase
TCD036C3, C4
TCD037C3, C4

Single Phase

15.8

31.6

45.9

5 Ton
2000 CFM
Single Phase

TCR048C1

Three Phase
TCR048C3,C4
TCR049C3,C4

9.9

19.8

27.3

34.8

11.9

23.7

34.4

45.5

7.9

15.8

21.8

27.8

Three Phase
TCR060C3, C4
TCR061C3, C4

TCR060C1

9.5

19.0

27.5

36.4

For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
Temp. Rise across Elect. Htr =

KW x 3413
1.08 x CFM

NOTE:
1. TCR061C3,C4, 23 KW not available.

Table PD-60 Continued


6 Ton
2500 CFM

KW
9.00
17.30
18.00
27.00
36.00
54.001
72.002

Stages
1
1
1
2
2
2
2

7 Ton
3000 CFM

8 Ton
3400 CFM

Three Phase Three Phase Three Phase


TCR075
TCR090
TCR102
TCR074C
TCR086C,91D
TCR103
11.4
21.9
22.8
34.2
45.5

9.5
18.2
19.0
28.5
37.9

17.8

35.6
53.4

10 Ton
4000 CFM

12 Ton
5000 CFM

15 Ton
6000 CFM

17 Ton
7000 CFM

20 Ton
8000 CFM

25 Ton
9000 CFM

Three Phase
TCR120
TCR121

Three Phase
TCR150
TCR151

Three Phase
TCR180
TCR181

Three Phase
TCR210
TCR211

Three Phase
TCR240
TCR241

Three Phase
TCR300
TCR301

14.2

28.5
42.7

11.4

9.5

22.8
34.1

19.0
28.5

16.3
24.4

32.5

14.2
21.3
28.5

12.6
19.0
25.3

For minimum design airflow, see airflow performance table for each unit.
To calculate temp rise at different air flow, use following formula:
KW x 3413
Temp. Rise across Elect. Htr =
1.08 x CFM
NOTES:
1. Not available on TCR102, 120 models.
2. Not available on TCR210 model.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

55

Controls

Field Installed Control Options


Zone Sensors are the building
occupants comfort control devices.They
replace the conventional electromechanical thermostats.The following
zone sensor options are available for
Voyager units with the Micro control:
Manual Changeover Heat, Cool or
Off System Switch. Fan Auto or Off
Switch. One
temperature
setpoint lever.

Manual/Automatic Changeover
Auto, Heat, Cool or Off System Switch.
Fan Auto or Off
Switch.Two
temperature
setpoint
levers. Optional
Status Indication
LED lights,
System On,
Heat, Cool, or
Service.

Remote Sensor Sensor(s) available


for all zone sensors to provide
remote sensing
capabilities.

Programmable Night Setback


Auto or manual changeover with
seven-day programming. Keyboard
selection of Heat, Cool, Fan, Auto, or On.
All programmable
sensors have
System
On, Heat, Cool,
Service LED/
indicators as
standard.
Night
Setback
Sensors
have one
(1) Occupied,
one (1)
Unoccuped,
and two (2)
Override
programs per
day.

Differential Enthalpy Replaces the


standard dry bulb control with two
enthalpy sensors that compare total heat
content of the indoor air and outdoor air
to determine the most efficient air
source.This control option offers the
highest level of comfort control, plus
energy efficiency, available.

Integrated ComfortTM System


Sensor(s) available with optional
temperature
adjustment and
override buttons
to provide
central control
through aTrane
Integrated
ComfortTM
system.

Differential Pressure Switches


This factory or field-installed option
allows individual fan failure and dirty
filter indication. The fan failure switch
will disable all unit functions and flash
the Service LED on the zone sensor. The
dirty filter switch will light the Service
LED on the zone sensor and will allow
continued unit operation.

Economizer
Controls The
standard
equipment
offering is a fixed
dry bulb
changeover
control. In addition, there are two
optional controls, Enthalpy and
Differential Enthalpy Control.
Enthalpy Control Replaces the dry
bulb control with a wet bulb changeover
controller which has a fully adjustable
set point. Enthalpy control offers a
higher level of comfort control, along
with energy savings potential, than the
standard dry bulb control. This is due to
the additional wet bulb sensing
capability.

56

Remote Potentiometer Minimum


position setting of economizer can be
remotely adjusted with this accessory.
Trane Communication Interface
(TCI) This factory or field-installed
micro-processor interface allows the unit
to communicate toTranes Integrated
ComfortTM system.
Conventional Thermostat Interface
(CTI) This factory or field-installed
option will allow the Micro units to
interface with most conventional electromechanical thermostats.

Input / Output Expansion Accessory


This factory or field-installed option
allows Integrated ComfortTM Sytems to
read Supply AirTemperature, Return Air
Temperature, Return Air Humidity, and
direct indication of fan failure without
the use of an economizer or motorized
outside air accessory.
Electronic Time Clock This field
installed accessory allows up to 4 units
night set-back and unoccupied functions
when using a standard (Dual Setpoint)
zone sensor module.

RT-PRC002-EN

Electrical
Data

Table ED-1 Unit Wiring Standard Efficiency


Standard Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size Or Maximum
Ampacity2
Circuit Breaker1

Oversize Indoor Fan Motor


Minimum
Maximum Fuse
Circuit
Size Or Maximum
Ampacity2
Circuit Breaker1

Unit
Model No.

Unit
Operating
Voltage Range

TCD036C1
TCD036C3
TCD036C4

187-253
187-253
414-506

27.1
18.6
9.4

40
25
15

28.3
19.8
9.7

45
30
15

TCR048C1
TCR048C3
TCR048C4
TCR048CW

187-253
187-253
414-506
517-633

36.3
24.8
11.9
9.5

60
35
15
15

38.7
27.2
13.0
10.3

60
40
20
15

TCR060C1
TCR060C3
TCR060C4
TCR060CW

187-253
187-253
414-506
517-633

46.5
31.3
16.3
11.9

60
45
25
15

47.8
32.6
16.9
12.0

60
50
25
15

TCR075C3
TCR075C4
TCR075CW

187-253
414-506
517-633

36.6
17.7
14.2

50
25
20

39.5
18.9
14.7

60
25
20

TCR090C3 / D3
TCR090C4 / D4
TCR090CW / DW

187-253
414-506
517-633

43.1/41.7
20.9/20.8
16.7/16.0

60/50
30/25
25/20

46.0/44.6
22.1/22.0
17.2/16.5

60/50
30/25
25/20

TCR102C3
TCR102C4
TCR102CW

187-253
414-506
517-633

49
29
19

60
35
20

53
31
20

60
40
25

10

TCR120C3
TCR120C4
TCR120CW

187-253
414-506
517-633

55
31
22

60
40
25

59
34
24

70
40
30

12

TCR150C3
TCR150C4
TCR150CW

187-253
414-506
518-633

71
32
25

80
40
30

77
35
27

90
45
35

15

TCR180B3
TCR180B4
TCR180BW

187-253
414-506
517-633

85
38
31

100
50
40

91
41
34

100
50
45

17

TCR210C3
TCR210C4
TCR210CW

187-253
414-506
517-633

101
45
37

125
60
45

109
49
40

125
60
50

20

TCR240B3
TCR240B4
TCR240BW

187-253
414-506
517-633

123
53
42

150
60
50

130
57
45

150
70
50

25

TCR300B3
TCR300B4
TCR300BW

187-253
414-506
517-633

132
57
45

150
70
50

N/A
N/A
N/A

N/A
N/A
N/A

Tons

NOTE:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

57

Electrical
Data

Table ED-2 Unit Wiring High Efficiency


Standard Indoor Fan Motor
Minimum
Maximum Fuse
Circuit
Size Or Maximum
Ampacity2
Circuit Breaker1

Oversize Indoor Fan Motor


Minimum
Maximum Fuse
Circuit
Size Or Maximum
Ampacity2
Circuit Breaker1

Unit
Model No.

Unit
Operating
Voltage Range

TCD037C3
TCD037C4

187-253
414-506

19.6
9.9

30
15

20.8
10.2

30
15

TCR049C3
TCR049C4

187-253
414-506

24.7
11.8

35
15

27.1
12.9

40
15

TCR061C3
TCR061C4

187-253
414-506

30.6
15.9

45
25

31.9
16.5

50
25

TCR074C3
TCR074C4

187-253
414-506

35.2
16.6

50
25

38.1
17.8

50
25

TCR086C3
TCR086C4

187-253
414-506

38.1
18.1

60
25

41.0
19.3

60
25

TCR091D3
TCR091D4

187-253
414-506

41.7
21.6

50
25

44.6
22.8

50
25

TCR103C3
TCR103C4
TCR103CW

187-253
414-506
517-633

45
24
19

50
30
20

48
25
20

60
30
25

TCR121C3
TCR121C4
TCR121CW

187-253
414-506
517-633

49
30
22

60
35
25

52
31
23

60
40
25

TCR151C3
TCR151C4
TCR151CW

187-253
414-506
517-633

61
31
25

80
40
30

67
34
27

80
40
30

TCR181C3
TCR181C4
TCR181CW

187-253
414-506
517-633

81
38
30

100
50
40

87
40
33

100
50
45

TCR211C3
TCR211C4
TCR211CW

187-253
414-506
517-633

94
46
36

110
60
45

102
49
39

125
60
50

TCR241C3
TCR241C4
TCR241CW
TCR301C3
TCR301C4
TCR301CW

187-253
414-506
517-633
187-253
414-506
517-633

123
53
42
130
56
45

150
60
50
150
70
50

130
56
45
N/A
N/A
N/A

150
70
50
N/A
N/A
N/A

Tons

10

12

15

17

20

25

NOTE:
1. HACR breaker per NEC.
2. Values do not include power exhaust accessory.

RIndicates both downflow and horizontal units.

58

RT-PRC002-EN

Electrical
Data

Table ED-3 Electrical Characteristics Power Exhaust Accessory

Tons

6, 6, 7, 7

Accessory
Model Number

Accessory
Operating
Voltage

Phase

HP

RPM

FLA

LRA

BAYPWRX013

208-230

.75

1100

6.6

13.5

BAYPWRX015

460

.75

1100

3.1

6.4

BAYPWRX014

575

.75

1100

2.4

5.2

BAYPWRX016

208-230

3/4

1040

6.6

13.5

460

3/4

1040

3.2

8.4

8, 101, 121 BAYPWRX017

102, 122

Amps

BAYPWRX018

575

3/4

1040

2.1

5.2

BAYPWRX019

208-230

3/4

1040

6.6

13.5

15, 17

BAYPWRX020

460

3/4

1040

3.2

8.4

20, 25

BAYPWRX021

575

3/4

1040

2.1

5.2

NOTES:
1. 10 and 12 Ton Standard Unit.
2. 10 and 12 Ton High Efficiency Unit.

Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency
Standard Indoor Motor
Tons

To Use
With

Heater
Model No.

Heater
KW Rating1

Control
Stages

MCA

Max Fuse Size Or


Max Circuit Breaker2

Oversize Indoor Motor


MCA

Max Fuse Size Or


Max Circuit Breaker2

208/230 Volts Single Phase


3

TCD036C1

BAYHTRP105A
BAYHTRP110A
BAYHTRP114A

3.7/5.0
7.5/10.0
10.3/13.8

1
2
2

27.1/29.3
48.3/55.3
65.5/75.1

40/40
50/60
70/80

28.3/30.8
49.9/56.8
67.0/76.6

45/45
50/60
70/80

TCR048C1

BAYHTRP105A
BAYHTRP110A
BAYHTRP114A
BAYHTRP118A

3.7/5.0
7.5/10.0
10.3/13.8
13.2/17.6

1
2
2
2

36.3/36.3
50.4/57.3
67.5/77.1
84.7/96.9

60/60
60/60
70/80
90/100

38.7/38.7
53.4/60.3
70.5/80.1
87.7/99.9

60/60
60/70
80/90
90/100

TCR060C1

BAYHTRP105A
BAYHTRP110A
BAYHTRP114A
BAYHTRP118A

3.7/5.0
7.5/10.0
10.3/13.8
13.2/17.6

1
2
2
2

46.5/46.5
51.8/58.7
68.9/78.5
86.1/98.3

60/60
60/60
70/80
90/100

47.8/47.8
53.4/60.3
70.5/80.1
87.7/99.9

60/60
60/70
80/90
90/100

208/230 Volts Three Phase


3

TCD036C3

BAYHTRP306A
BAYHTRP312A
BAYHTRP318A

4.5/6.0
9.0/12.0
13.0/17.4

1
2
2

18.9/21.3
34.5/39.3
48.6/55.6

25/25
35/40
50/60

20.4/22.8
36.0/40.8
50.1/57.1

30/30
40/45
60/60

TCR048C3

BAYHTRP306A
BAYHTRP312A
BAYHTRP318A
BAYHTRP323A

4.5/6.0
9.0/12.0
13.0/17.4
17.2/23.0

1
2
2
2

24.8/24.8
36.5/41.3
50.6/57.6
65.2/74.4

35/35
40/45
60/60
70/80

27.2/27.2
39.5/44.3
53.6/60.6
68.2/77.4

40/40
40/45
60/70
70/80

BAYHTRP306A
BAYHTRP312A
BAYHTRP318A
BAYHTRP323A

4.5/6.0
9.0/12.0
13.0/17.4
17.2/22.0

1
2
2
2

31.3/31.3
37.9/42.7
52.0/59.0
66.6/75.8

45/45
45/45
60/60
70/80

32.6/32.6
39.5/44.3
53.6/60.6
68.2/77.4

50/50
50/50
60/70
70/80

AYRHTRA309BA
AYRHTRA318BA
AYRHTRA327BA
AYRHTRA336BA

6.75/9.0
12.9/17.3
20.2/27.0
27.0/36.0

1
1
2
2

36.6/36.6
52.5/59.4
77.7/88.6
101.2/115.6

50/50
60/60
80/90
110/125

39.5/39.5
56.1/63.0
81.4/92.2
104.8/119.3

60/60
60/70
90/100
110/125

TCR060C3

TCR075C3

NOTES:
1. Heater kw ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

59

Electrical
Data

Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency Continued
Standard Indoor Motor
Tons

To Use
With

Heater
Model No.

Heater
KW Rating1

Control
Stages

MCA

Max Fuse Size Or


Max Circuit Breaker2

Oversize Indoor Motor


MCA

Max Fuse Size Or


Max Circuit Breaker2

208/230 Volts Three Phase


TCR090C3

AYRHTRA309BA
AYRHTRA318BA
AYRHTRA327BA
AYRHTRA336BA

6.75/9.0
12.9/17.3
20.2/27.0
27.0/36.0

1
1
2
2

43.1/43.1
52.5/59.4
77.7/88.6
101.2/115.6

60/60
60/60
80/90
110/125

46.0/46.0
56.1/63.0
81.4/92.2
104.8/119.3

60/60
60/70
90/100
110/125

TCR090D3

AYRHTRA309BA
AYRHTRA318BA
AYRHTRA327BA
AYRHTRA336BA

6.75/9.0
12.9/17.3
20.2/27.0
27.0/36.0

1
1
2
2

41.7/41.7
52.5/59.4
77.7/88.6
101.2/115.6

50/50
60/60
80/90
110/125

44.6/44.6
56.1/63.0
81.4/92.2
104.8/119.3

50/50
60/70
90/100
110/125

TCR102C3

AYRHTRJ318A
AYRHTRJ336A

13.5/18.0
27.0/36.0

1
2

57/64
104/118

60/70
110/125

61/68
108/122

70/70
110/125

10

TCR120C3

AYRHTRJ318A
AYRHTRJ336A3

13.5/18.0
27.0/36.0

1
2

59/66
106/121

60/70
110/125

64/71
N/A

70/80
N/A

12

TCR150C3

AYRHTRF318A
AYRHTRF336A
AYRHTRF354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

71/71
108/122
154/176

80/80
110/125
175/200

77/77
115/130
162/184

90/90
125/150
175/200

15

TCR180B3

AYRHTRF318A
AYRHTRF336A
AYRHTRF354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

85/85
108/122
154/176

100/100
110/125
175/200

91/91
115/130
162/184

100/100
125/150
175/200

17

TCR210C3

AYRHTRH336A
AYRHTRH354A

27.0/36.0
40.5/54.0

2
2

115/130
162/184

125/150
175/200

125/139
171/193

125/150
175/200

20

TCR240B3

AYRHTRH336A
AYRHTRH354A
AYRHTRH372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

123/130
162/184
209/238

150/150
175/200
225/250

130/139
171/193
218/247

150/150
175/200
225/250

25

TCR300B3

AYRHTRH336A
AYRHTRH354A
AYRHTRH372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

130/139
171/193
218/247

150/150
175/200
225/250

460 Volts Three Phase


3

TCD036C4

BAYHTRP406A
BAYHTRP412A
BAYHTRP418A

6.0
12.0
17.4

1
2
2

11.0
20.0
28.2

15
25
30

11.4
20.4
28.5

15
25
30

TCR048C4

BAYHTRP406A
BAYHTRP412A
BAYHTRP418A
BAYHTRP423A

6.0
12.0
17.4
23.0

1
2
2
2

11.9
20.5
28.7
37.1

15
25
30
40

13.0
21.9
30.0
38.5

20
25
35
40

TCR060C4

BAYHTRP406A
BAYHTRP412A
BAYHTRP418A
BAYHTRP423A

6.0
12.0
17.4
23.0

1
2
2
2

16.3
21.2
29.3
37.7

25
25
30
40

16.9
21.9
30.0
38.5

25
25
35
40

TCR075C4

AYRHTRA409BA
AYRHTRA418BA
AYRHTRA427BA
AYRHTRA436BA

9.0
18.0
27.0
36.0

1
1
2
2

17.7
31.1
44.6
58.1

25
35
45
60

19.0
32.6
46.1
59.6

25
35
50
60

NOTES:
1. Heater kw ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.
3. Do not use in conjunction with oversized motor.

RIndicates both downflow and horizontal units.

60

RT-PRC002-EN

Electrical
Data
Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency Continued
Standard Indoor Motor
Tons

To Use
With

Heater
Model No.

Heater
KW Rating1

Control
Stages

MCA

Oversize Indoor Motor

Max Fuse Size Or


Max Circuit Breaker2

MCA

Max Fuse Size Or


Max Circuit Breaker2

460 Volts Three Phase


TCR090C4

AYRHTRA409BA
AYRHTRA418BA
AYRHTRA427BA
AYRHTRA436BA

9.0
18.0
27.0
36.0

1
1
2
2

20.9
31.1
44.6
58.1

30
35
45
60

22.1
32.6
46.1
59.6

30
35
50
60

TCR090D4

AYRHTRA409BA
AYRHTRA418BA
AYRHTRA427BA
AYRHTRA436BA

9.0
18.0
27.0
36.0

1
1
2
2

20.8
31.1
44.6
58.1

25
35
45
60

22.0
32.6
46.1
59.6

25
35
50
60

TCR102C4

AYRHTRJ418A
AYRHTRJ436A

18.0
36.0

1
2

32
59

35
60

34
61

40
70

10

TCR120C4

AYRHTRJ418A
AYRHTRJ436A

18.0
36.0

1
2

34
61

40
70

37
64

40
70

12

TCR150C4

AYRHTRE418A3
AYRHTRE436A
AYRHTRE454A

18.0
36.0
54.0

1
2
2

34
61
88

40
70
90

37
64
91

45
70
100

15

TCR180B4

AYRHTRE418A3
AYRHTRE436A
AYRHTRE454A

18.0
36.0
54.0

1
2
2

38
61
88

50
70
90

41
64
91

50
70
100

17

TCR210C4

AYRHTRG436A
AYRHTRG454A

36.0
54.0

2
2

64
91

70
100

68
95

70
100

20

TCR240B4

AYRHTRG436A
AYRHTRG454A
AYRHTRH472A

36.0
54.0
72.0

2
2
2

64
91
118

70
100
125

68
95
123

70
100
125

25

TCR300B4

AYRHTRG436A
AYRHTRG454A
AYRHTRH472A

36.0
54.0
72.0

2
2
2

68
95
123

70
100
125

575 Volts Three Phase


4

TCR048CW

BAYHTRPW06A
BAYHTRPW12A
BAYHTRPW18A
BAYHTRPW23A

6.0
12.0
17.4
23.0

1
2
2
2

9.5
16.6
23.1
29.8

15
20
25
35

10.3
17.6
24.1
30.8

15
20
25
35

TCR060CW

BAYHTRPW06A
BAYHTRPW12A
BAYHTRPW18A
BAYHTRPW23A

6.0
12.0
17.4
23.0

1
2
2
2

11.9
17.4
23.9
30.7

15
20
25
35

12.0
17.6
24.1
30.8

15
20
25
35

TCR075CW

AYRHTRAW18BA
AYRHTRAW27BA

18.0
27.0

1
2

24.9
35.7

25
40

25.5
36.4

30
40

TCR090CW,DW

AYRHTRAW18BA
AYRHTRAW27BA

18.0
27.0

1
2

24.9
35.7

25
40

25.5
36.4

30
40

TCR102CW

AYRHTRJW18A
AYRHTRJW36A

18.0
36.0

1
2

26
48

30
50

27
49

30
50

NOTES:
1. Heater kw ratings are at 480V for 460 unit and 600V for 575V unit.
2. HACR type circuit breaker per NEC.
3. Heater model number for horizontal is AYHHTRC418A.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

61

Electrical
Data
Table ED-4 Unit Wiring With Electric Heat (Single Point Connection) Standard Efficiency Continued
Standard Indoor Motor
Tons

To Use
With

Heater
Model No.

Heater
KW Rating1

Control
Stages

MCA

Oversize Indoor Motor

Max Fuse Size Or


Max Circuit Breaker2

MCA

Max Fuse Size Or


Max Circuit Breaker2

575 Volts Three Phase


10

TCR120CW

AYRHTRJW18A
AYRHTRJW36A

18.0
36.0

1
2

27
49

30
50

30
51

30
60

12

TCR150CW

AYRHTRDW18A4
AYRHTRGW36A4
AYRHTREW54A

18.0
36.0
54.0

1
2
2

27
49
70

30
50
70

30
51
73

35
60
80

15

TCR180BW

AYRHTRDW18A4
AYRHTRGW36A4
AYRHTREW54A

18.0
36.0
54.0

1
2
2

31
49
70

40
50
70

34
51
73

45
60
80

17

TCR210CW

AYRHTRGW36A3
AYRHTRGW54A

36.0
54.0

2
2

51
73

60
80

55
77

60
80

20

TCR240BW

AYRHTRGW36A3
AYRHTRGW54A
AYRHTRHW72A

36.0
54.0
72.0

2
2
2

51
73
95

60
80
100

55
77
98

60
80
100

25

TCR300BW

AYRHTRGW36A3
AYRHTRGW54A
AYRHTRHW72A

36.0
54.0
72.0

2
2
2

55
77
98

60
80
100

NOTES:
1. Heater kw ratings are at 600V for 575V unit
2. HACR type circuit breaker per NEC.
3. The heater model number for horizontal is AYHHTRCW36A.
4. The heater model number for horizontal is AYHHTRCW18A, AYHHTRCW36A.

RIndicates both downflow and horizontal units.

62

RT-PRC002-EN

Electrical
Data

Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) High Efficiency
Standard Indoor Motor
Tons

To Use
With

Heater
Model No.

Heater
KW Rating1

Control
Stages

MCA

Max Fuse Size Or


Max Circuit Breaker2

Oversize Indoor Motor


MCA

Max Fuse Size Or


Max Circuit Breaker2

208/230 Volts Three Phase


3

TCD037C3

BAYHTRP306A
BAYHTRP312A
BAYHTRP318A

4.5/6.0
9.0/12.0
13.0/17.4

1
2
2

19.6/21.3
34.5/39.3
48.5/55.6

30/30
35/40
50/60

20.8/22.8
36.0/40.8
50.1/57.1

30/30
40/45
60/60

TCR049C3

BAYHTRP306A
BAYHTRP312A
BAYHTRP318A
BAYHTRP323A

4.5/6.0
9.0/12.0
13.0/17.4
17.2/23.0

1
2
2
2

24.7/24.7
36.5/41.3
50.6/57.6
65.2/74.4

35/35
40/45
60/60
70/80

27.1/27.1
39.5/44.3
53.6/60.6
68.2/77.4

40/40
40/45
60/70
70/80

TCR061C3

AYRHTRA309B
AYRHTRA318B

6.7/9.0
12.9/17.3

1
1

30.6/33.7
51.7/58.6

45/45
60/60

31.9/35.3
53.3/60.3

50/50
60/70

TCR074C3

AYRHTRA309B
AYRHTRA318B
AYRHTRA327B
AYRHTRA336B

6.7/9.0
12.9/17.3
20.2/27.0
27.0/36.0

1
1
2
2

35.2/35.2
52.5/59.4
77.7/88.6
101.2/115.6

50/50
60/60
80/90
110/125

38.1/38.1
56.1/63.0
81.4/92.2
104.8/119.3

50/50
60/70
90/100
110/125

TCR086C3

AYRHTRA309B
AYRHTRA318B
AYRHTRA327B
AYRHTRA336B

6.7/9.0
12.9/17.3
20.2/27.0
27.0/36.0

1
1
2
2

38.1/38.1
52.5/59.4
77.7/88.6
101.2/115.6

60/60
60/60
80/90
110/125

41.0/41.0
56.1/63.0
81.4/92.2
104.8/119.3

60/60
60/70
90/100
110/125

TCR091D3

AYRHTRA309B
AYRHTRA318B
AYRHTRA327B
AYRHTRA336B

6.7/9.0
12.9/17.3
20.2/27.0
27.0/36.0

1
1
2
2

41.7/41.7
52.5/59.4
77.7/88.6
101.2/115.6

50/50
60/60
80/90
110/125

44.6/44.6
56.1/63.0
81.4/92.2
104.8/119.3

50/50
60/70
90/100
110/125

TCR103C3

AYRHTRD318A
AYRHTRD336A
AYRHTRD354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

57/64
104/118
151/172

60/70
110/125
175/175

61/68
108/122
154/176

70/70
110/125
175/200

10

TCR121C3

AYRHTRD318A
AYRHTRD336A
AYRHTRD354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

57/64
104/118
151/172

60/70
110/125
175/175

61/68
108/122
154/176

70/70
110/125
175/200

12

TCR151C3

AYRHTRF318A
AYRHTRF336A
AYRHTRF354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

72/72
108/122
154/176

80/80
110/125
175/200

78/78
115/130
162/184

90/90
125/150
175/200

15

TCR181C3

AYRHTRF318A
AYRHTRF336A
AYRHTRF354A

13.5/18.0
27.0/36.0
40.5/54.0

1
2
2

81/81
108/122
154/176

100/100
110/125
175/200

87/87
115/130
162/184

100/100
125/150
175/200

17

TCR211C3

AYRHTRH336A
AYRHTRH354A
AYRHTRH372A

27.0/36.0
40.5/54.0
54.0/72.0

2
2
2

115/130
162/184
209/238

125/150
175/200
225/250

125/139
171/193
218/247

125/150
175/200
225/250

20

TCR241C3

25

TCR301C3

AYRHTRH336A
AYRHTRH354A
AYRHTRH372A
AYRHTRH336A
AYRHTRH354A
AYRHTRH372A

27.0/36.0
40.5/54.0
54.0/72.0
27.0/36.0
40.5/54.0
54.0/72.0

2
2
2
2
2
2

123/130
162/184
209/238
132/139
171/193
218/247

150/150
175/200
225/250
150/150
175/200
225/250

130/139
171/193
218/247

150/150
175/200
225/250

NOTES:
1. Heater kw ratings are at 208/240 for 208/230V unit
2. HACR type circuit breaker per NEC.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

63

Electrical
Data

Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) High Efficiency Continued
Standard Indoor Motor
Tons

To Use
With

Heater
Model No.

Heater
KW Rating1

Control
Stages

MCA

Oversize Indoor Motor

Max Fuse Size Or


Max Circuit Breaker2

MCA

Max Fuse Size Or


Max Circuit Breaker12

460 Volts Three Phase


3

TCD037C4

BAYHTRP406A
BAYHTRP412A
BAYHTRP418A

6.0
12.0
17.4

1
2
2

11.0
20.0
28.2

15
25
30

11.4
20.4
28.5

15
25
30

TCR049C4

BAYHTRP406A
BAYHTRP412A
BAYHTRP418A
BAYHTRP423A

6.0
12.0
17.5
23.0

1
2
2
2

11.8
20.5
28.7
37.1

15
25
30
40

12.9
21.9
30.0
38.5

20
25
35
40

TCR061C4

AYRHTRA409B
AYRHTRA418B

9.0
18.0

1
1

16.7
30.2

25
35

17.4
30.9

25
35

TCR074C4

AYRHTRA409B
AYRHTRA418B
AYRHTRA427B
AYRHTRA436B

9.0
18.0
27.0
36.0

1
1
2
2

17.5
31.1
44.6
58.1

25
35
45
60

19.0
32.6
46.1
59.6

25
35
50
60

TCR086C4

AYRHTRA409B
AYRHTRA418B
AYRHTRA427B
AYRHTRA436B

9.0
18.0
27.0
36.0

1
1
2
2

18.1
31.1
44.6
58.1

25
35
45
60

19.3
32.6
46.1
59.6

25
35
50
60

TCR091D4

AYRHTRA409B
AYRHTRA418B
AYRHTRA427B
AYRHTRA436B

9.0
18.0
27.0
36.0

1
1
2
2

21.6
31.1
44.6
58.1

25
35
45
60

22.8
32.6
46.1
59.6

25
35
50
60

TCR103C4

AYRHTRC418A
AYRHTRD436A4
AYRHTRD454A4

18.0
36.0
54.0

1
2
2

32
59
86

35
60
90

34
61
88

35
70
90

10

TCR121C4

AYRHTRC418A
AYRHTRD436A4
AYRHTRD454A4

18.0
36.0
54.0

1
2
2

32
59
86

35
60
90

34
61
88

40
70
90

12

TCR151C4

AYRHTRF418A3
AYRHTRF436A
AYRHTRF454A

18.0
36.0
54.0

1
2
2

34
61
88

40
70
90

37
64
91

45
70
100

15

TCR181C4

AYRHTRE418A3
AYRHTRE436A
AYRHTRE454A

18.0
36.0
54.0

1
2
2

38
61
88

50
70
90

40
64
91

50
70
100

17

TCR211C4

AYRHTRG436A
AYRHTRG454A
AYRHTRH472A

36.0
54.0
72.0

2
2
2

64
91
118

70
100
125

68
95
122

70
100
125

20

TCR241C4
TCR301C4

36.0
54.0
72.0
36.0
54.0
72.0

2
2
2
2
2
2

64
91
118
68
95
122

70
100
125
70
100
125

68
95
122

70
100
125

25

AYRHTRG436A
AYRHTRG454A
AYRHTRH472A
AYRHTRG436A
AYRHTRG454A
AYRHTRH472A

NOTES:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.
3. Horizontal model heater number is AYHHTRC418A.
4. Horizontal model heater numbers are AYHHTRE436A and AYHHTRE454A.

RIndicates both downflow and horizontal units.

64

RT-PRC002-EN

Electrical
Data

Table ED-5 Unit Wiring With Electric Heat (Single Point Connection) High Efficiency Continued
Standard Indoor Motor
Tons

To Use
With

Heater
Model No.

Heater
KW Rating1

Control
Stages

MCA

Oversize Indoor Motor

Max Fuse Size Or


Max Circuit Breaker2

MCA

Max Fuse Size Or


Max Circuit Breaker12

575 Volts Three Phase


8

TCR103CW
TCR103CW
TCD103CW
TCH103CW

AYRHTRCW18A
AYRHTRDW36A
AYDHTRCW54A
AYHHTREW54A

18.0
36.0
54.0
54.0

1
2
2
2

32
48
69
69

35
50
70
70

34
49
70
70

35
50
70
70

10

TCR121CW
TCR121CW
TCD121CW
TCH121CW

AYRHTRCW18A
AYRHTRCW36A
AYDHTRCW54A
AYHHTREW54A

18.0
36.0
54.0
54.0

1
2
2
2

26
48
69
69

30
50
70
70

27
49
70
70

30
50
70
70

12

TCD151CW
TCH151CW
TCD151CW
TCH151CW
TCR151CW

AYDHTRDW18A
AYHHTRCW18A
AYDHTRGW36A
AYHHTRCW36A
AYRHTREW54A

18.0
18.0
36.0
36.0
54.0

1
1
2
2
2

27
27
49
49
70

30
30
50
50
70

30
30
51
51
73

35
35
60
60
80

15

TCD181CW
TCH181CW
TCD181CW
TCH181CW
TCR181CW

AYDHTRDW18A
AYHHTRCW18A
AYDHTRGW36A
AYHHTRCW36A
AYRHTREW54A

18.0
18.0
36.0
36.0
54.0

1
1
2
2
2

30
30
49
49
70

40
40
50
50
70

33
33
51
51
73

45
45
60
60
80

TCD211CW
TCH211CW
TCR211CW
TCR211CW

AYDHTRGW36A
AYHHTRCW36A
AYRHTRGW54A
AYRHTRHW72A

36.0
36.0
54.0
72.0

2
2
2
2

51
51
73
95

60
60
80
100

55
55
77
98

60
60
80
100

TCD241CW
TCH241CW
TCR241CW
TCR241CW

AYDHTRGW36A
AYHHTRCW36A
AYRHTRGW54A
AYRHTRHW72A

36.0
36.0
54.0
72.0

2
2
2
2

51
51
73
95

60
60
80
100

55
55
77
98

60
60
80
100

TCD301CW
TCH301CW
TCR301CW
TCR301CW

AYDHTRGW36A
AYHHTRCW36A
AYRHTRGW54A
AYRHTRHW72A

36.0
36.0
54.0
72.0

2
2
2
2

55
55
77
98

60
60
80
100

17

20

25

NOTE:
1. HACR type circuit breaker per NEC.
2. Values do not include power exhaust accessory.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

65

Electrical
Data

Table ED-6 Electrical Characteristics Evaporator Fan Motor 60 Cycle


Standard Evaporator Fan Motor

Tons

Unit
Model No.

Oversized Evaporator Fan Motor


Amps

Amps

No.

Volts

Phase

HP

FLA

LRA

No.

Volts

Phase

HP

FLA

LRA

TCD036C1
TCD036C3, TCD037C3
TCD036C4, TCD037C4

1
1
1

208-230
208-230
460

1
1
1

.33
.33
.33

2.4
2.4
1.1/1.6

7.2
7.2
2.2

1
1
1

208-230
208-230
460

1
1
1

.40
.40
.40

3.8
3.8
1.9

6.9
6.9
3.1

TCR048C1
TCR048C3, TCR049C3
TCR048C4, TCR049C4
TCR048CW

1
1
1
1

208-230
208-230
460
575

1
1
1
1

.50
.50
.50
.50

4.2
4.2
2.0
1.9

9.2
9.2
4.3
3.4

1
1
1
1

208-230
208-230
460
575

1
1
1
1

.75
.75
.75
.75

6.6
6.6
3.1
2.4

13.5
13.5
6.4
5.2

TCR060C1
TCR060C3, TCR061C3
TCR060C4, TCR061C4
TCR060CW

1
1
1
1

208-230
208-230
460
575

1
1
1
1

.60
.60
.60
.60

5.3
5.3
2.5
2.4

11.1
11.1
5.6
4.7

1
1
1
1

208-230
208-230
460
575

1
1
1
1

.75
.75
.75
.75

6.6
6.6
3.1
2.5

13.5
13.5
6.4
5.2

TCR075C3, TCR074C3
6, 6 TCR075C4, TCR074C4
TCR075CW

1
1
1

208-230
460
575

3
3
3

1.00
1.00
1.00

5.9
3.2
2.6

32.2
16.1
13.2

1
1
1

208-230
460
575

3
3
3

2.00
2.00
2.00

8.8
4.4
3.1

53.0
26.5
18.4

208-230

1.00

5.9

32.2

208-230

2.00

8.8

53.0

1
1

460
575

3
3

1.00
1.00

3.2
2.6

16.1
13.2

1
1

460
575

3
3

2.00
2.00

4.4
3.1

26.5
18.4

TCR102C3, TCR103C3
TCR102C4, TCR103C4
TCR102CW, TCR103CW

1
1
1

208-230
460
575

3
3
3

2.00
2.00
2.00

7.5
3.4
3.0

47.2
23.6
22.8

1
1
1

208-230
460
575

3
3
3

3.00
3.00
3.00

10.6
4.8
3.9

81.0
40.5
31.0

TCR120C3
TCR120C4
TCR120CW
TCR121C3
TCR121C4
TCR121CW

1
1
1
1
1
1

208-230
460
575
208-230
460
575

3
3
3
3
3
3

3.00
3.00
3.00
2.00
2.00
2.00

9.4
4.8
3.9
7.5
3.4
3.0

81.0
40.5
31.0
47.2
23.6
22.8

1
1
1
1
1
1

208-230
460
575
208-230
460
575

3
3
3
3
3
3

5.00
5.00
5.00
3.00
3.00
3.00

13.4
7.6
6.1
10.6
4.8
3.9

109.8
54.9
41.6
81.0
40.5
31.0

12

TCR150C3, TCR151C3
TCR150C4, TCR151C4
TCR150CW, TCR151CW

1
1
1

208-230
460
575

3
3
3

3.00
3.00
3.00

10.6
4.8
3.9

81.0
40.5
31.0

1
1
1

208-230
460
575

3
3
3

5.00
5.00
5.00

16.7
7.6
6.1

109.8
54.9
41.6

15

TCR180B3, TCR181C3
TCR180B4, TCR181C4
TCR180BW, TCR181CW

1
1
1

208-230
460
575

3
3
3

3.00
3.00
3.00

10.6
4.8
3.9

81.0
40.5
31.0

1
1
1

208-230
460
575

3
3
3

5.00
5.00
5.00

16.7
7.6
6.1

109.8
54.9
41.6

17

TCR210C3, TCR211C3
TCR210C4, TCR211C4
TCR210CW, TCR211CW

1
1
1

208-230
460
575

3
3
3

5.00
5.00
5.00

16.7
7.6
6.1

109.8
54.9
41.6

1
1
1

208-230
460
575

3
3
3

7.50
7.50
7.50

17.6
8.6
7.0

120.4
74.0
60.0

20

TCR240B3, TCR241C3
TCR240B4, TCR241C4
TCR240BW, TCR241CW

1
1
1

208-230
460
575

3
3
3

5.00
5.00
5.00

16.7
7.6
6.1

109.8
54.9
41.6

1
1
1

208-230
460
575

3
3
3

7.50
7.50
7.50

17.6
8.6
7.0

120.4
74.0
60.0

25

TCR300B3, TCR301C3
TCR300B4, TCR301C4
TCR 300BW, TCR301CW

1
1
1

208-230
460
575

3
3
3

7.50
7.50
7.50

17.6
8.6
7.0

120.4
74.0
60.0

TCR090C3,D3,
TCR086C3,091D3
7, 7 TCR090C4,D4,
TCR086C4,091D4
TCR090CW,DW
8

10

RIndicates both downflow and horizontal units.

66

RT-PRC002-EN

Electrical
Data

Standard
Efficiency

Table ED-7 Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle Standard Efficiency
Compressor Motors

Condenser Fan Motors


Amps

Unit
Model No.

No.

Volts

TCD036C1
TCD036C3
TCD036C4

1
1
1

208-230
208-230
460

TCR048C1
TCR048C3
TCR048C4
TCR048CW

1
1
1
1

TCR060C1
TCR060C3
TCR060C4
TCR060CW

Amps

Phase

HP

RPM

RLA

LRA

No.

Phase

HP

FLA

LRA

1
3
3

3.00
3.00
3.00

3450
3450
3450

18.0
11.2
5.5

92
101
51

1
1
1

1
1
1

.25
.25
.25

2.0
2.0
.9

5.3
5.3
2.1

208-230
208-230
460
575

1
3
3
3

4.00
4.00
4.00
4.00

3450
3450
3450
3450

24.0
14.8
7.1
5.5

119
101
51
41

1
1
1
1

1
1
1
1

.33
.33
.33
.33

2.1
2.1
1.0
.9

4.8
4.8
2.6
2.1

1
1
1
1

208-230
208-230
460
575

1
3
3
3

5.00
5.00
5.00
5.00

3450
3450
3450
3450

28.8
18.6
10.0
6.7

142
118
71
43

1
1
1
1

1
1
1
1

.50
.40
.40
.40

5.2
2.7
1.3
1.1

6.5
7.8
3.2
2.4

TCR075C3
TCR075C4
TCR075CW

1
1
1

208-230
460
575

3
3
3

6.25
6.25
6.25

3450
3450
3450

21.8
9.7
7.8

124
64
51

1
1
1

1
1
1

.50
.50
.50

3.4
2.4
1.8

10.8
5.4
4.1

TCR090C3
TCR090C4
TCR090CW

1
1
1

208-230
460
575

3
3
3

7.50
7.50
7.50

3450
3450
3450

27.0
12.2
9.8

164
79
63

1
1
1

1
1
1

.50
.50
.50

3.4
2.4
1.8

10.8
5.4
4.1

TCR090D3
TCR090D4
TCR090DW
TCR102C3
TCR102C4
TCR102CW

2
2
2
2
2
2

208-230
460
575
208-230
460
575

3
3
3
3
3
3

4.00/3.50
4.00/3.50
4.00/3.50
4.30/4.30
4.30/4.30
4.30/4.30

3450
3450
3450
3450
3450
3450

14.4
7.1
5.4
16.0
10.0
5.9

101
51
41
118
71
43

1
1
1
1
1
1

1
1
1
1
1
1

.50
.50
.50
1.00
1.00
1.00

3.4
2.4
1.8
5.5
2.9
2.0

10.8
5.4
4.1
18.3
9.3
5.7

TCR120C3
TCR120C4
TCR120CW

2
2
2

208-230
460
575

3
3
3

5.00/4.30 3450 19.0/16.0


5.00/4.30 3450
10.0
5.00/4.30 3450
6.9

118
71
43

1
1
1

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

TCR150C3
TCR150C4
TCR150CW

2
2
2

208-230
460
575

3
3
3

156
70
54

1
1
1

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

15

TCR180B3
TCR180B4
TCR180BW

2
2
2

208-230
460
575

3
3
3

9.30/5.10 3450 38.2/19.5


9.30/5.10 3450 16.6/8.5
9.30/5.10 3450 13.8/7.1

253/128
118/63
97/49

2
2
2

1
1
1

.50
.50
.50

3.2
1.6
1.3

8.8
3.8
3.2

17

TCR210C3
TCR210C4
TCR210CW

2
2
2

208-230
460
575

3
3
3

10.0/6.80 3450 37.4/26.1


10.0/6.80 3450 16.2/11.3
10.0/6.80 3450 13.5/9.4

253/164
118/100
97/72

2
2
2

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

20

TCR240B3
TCR240B4
TCR240BW

2
2
2

208-230
460
575

3
3
3

9.30
9.30
9.30

3450
3450
3450

42.1
17.4
13.9

247
95
76

2
2
2

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

25

TCR300B3
TCR300B4
TCR300BW

2
2
2

208-230
460
575

3
3
3

10.00
10.00
10.00

3450
3450
3450

42.8
17.7
14.2

247
95
76

2
2
2

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

Tons
3

10

12

6.00
6.00
6.00

3450
3450
3450

24.3
10.6
8.4

NOTES:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

67

Electrical
Data

High
Efficiency

Table ED-8 Electrical Characteristics Compressor Motor And Condenser Motor 60 Cycle High Efficiency
Compressor Motors

Condenser Fan Motors


Amps

Unit
Model No.

No.

Volts

TCD037C3
TCD037C4

1
1

208-230
460

TCR049C3
TCR049C4
TCR061C3
TCR061C4

1
1
1
1

TCR074C3
TCR074C4
TCR086C3
TCR086C4
TCR091D3
TCR091D4
TCR103C3
TCR103C4
TCR103CW

Amps

Phase

HP

RPM

RLA

LRA

No.

Phase

FLA

LRA

3
3

3.00
3.00

3450
3450

12.0
5.9

101
51

1
1

1
1

.25
.25

2.0
.9

5.3
2.1

208-230
460
208-230
460

3
3
3
3

3.50
3.50
4.30
4.30

3450
3450
3450
3450

14.8
7.1
18.6
10.0

101
51
118
71

1
1
1
1

1
1
1
1

.25
.25
.25
.25

2.0
.9
2.0
.9

5.3
2.1
5.3
2.1

1
1
1
1
2
2
2
2
2

208-230
460
208-230
460
208-230
460
208-230
460
575

3
3
3
3
3
3
3
3
3

5.00
5.00
6.25
6.25
3.00
3.00
3.80
3.80
3.80

3450
3450
3450
3450
3450
3450
3450
3450
3450

21.0
10.0
23.0
10.0
14.4
7.1
14.0
7.5
5.9

118
71
124
64
101
51
91
46
37

1
1
1
1
1
1
1
1
1

1
1
1
1
1
1
1
1
1

.25
.25
.50
.50
.50
.50
1.00
1.00
1.00

2.0
.9
3.4
2.4
3.4
2.4
5.5
2.9
2.0

5.3
2.1
10.8
5.4
10.8
5.4
18.3
9.3
5.7

TCR121C3
TCR121C4
TCR121CW

2
2
2

208-230
460
575

3
3
3

4.30
4.30
4.30

3450
3450
3450

15.4
10.0
6.9

118
71
43

2
2
2

1
1
1

.50
.50
.50

3.2
1.6
1.3

8.8
3.8
3.2

TCR151C3
TCR151C4
TCR151CW
TCR181C3
TCR181C4
TCR181CW

2
2
2
2
2
2

208-230
460
575
208-230
460
575

3
3
3
3
3
3

5.70
5.70
5.70
9.30/4.50
9.30/4.50
9.30/4.50

3450
19.4
156
3450
10.0
70
3450
7.8
54
3450 37.0/16.9 253/124
3450 17.4/7.4 118/60
3450 13.9/6.1 97/49

2
2
2
2
2
2

1
1
1
1
1
1

.50
.50
.50
.50
.50
.50

3.2
1.6
1.3
3.2
1.6
1.3

8.8
3.8
3.2
8.8
3.8
3.2

17

TCR211C3
TCR211C4
TCR211CW

2
2
2

208-230
460
575

3
3
3

9.30/5.70
9.30/5.70
9.30/5.70

3450 37.0/20.0 253/156


3450 17.4/10.0 118/70
3450 13.9/8.0 97/54

2
2
2

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

20

TCR241C3
TCR241C4
TCR241CW

2
2
2

208-230
460
575

3
3
3

9.30
9.30
9.30

3450
3450
3450

42.1
17.4
13.9

253
118
97

2
2
2

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

25

TCR301C3
TCR301C4
TCR301CW

2
2
2

208-230
460
575

3
3
3

10.00
10.00
10.00

3450
3450
3450

42.1
17.4
13.9

253
118
97

2
2
2

1
1
1

1.00
1.00
1.00

5.5
2.9
2.0

18.3
9.3
5.7

Tons
3
4
5
6
7
7
8

10

12

15

HP

NOTES:
1. Amp draw for each motor; multiply value by numbers of motors to determine total amps.
2. HP for each compressor.

RIndicates both downflow and horizontal units.

68

RT-PRC002-EN

Jobsite
Connections

Zone Sensors Typical Number Of Wires

DISCONNECT
SWITCH
(BY OTHERS)

A Manual Changeover ...................................... 4


Manual/Auto Changeover ............................. 5
Manual/Auto Changeover with
Status Indication LEDs .......................... 10
Programmable Night Setback with
Status Indication LEDs ............................ 7

ZONE SENSORS
ROOFTOP
UNIT

B 3 Power Wires + 1 Ground Wire (three phase)


2 Power Wires + 1 Ground Wire (single phase)

For specific wiring information, see the installation instructions.


All wiring except power wires is low voltage.
All customer supplied wiring to be copper and must conform to NEC or CEC and local electrical codes. Wiring shown dotted is to be furnished and installed by the customer.
NOTE:
1. Conventional Thermostat Interface - CTI is a field or factory-installed accessory and is required to operate all Micro-processor units with a conventional thermostat. For
accurate wiring requirements, refer to the accessory installation instructions.

RT-PRC002-EN

69

Typical
Wiring

70

(3-7Ton)

RT-PRC002-EN

Typical
Wiring

(3-7Ton)

Typical wiring diagram. For specific


wiring, see individual Service Facts.

PRINTED FROM: 2307-0211

RT-PRC002-EN

71

Typical
Wiring

72

(3-7Ton)

RT-PRC002-EN

Typical
Wiring

(3-7Ton)

Typical wiring diagram. For specific


wiring, see individual Service Facts.

PRINTED FROM: 2307-0222

RT-PRC002-EN

73

Typical
Wiring

74

(8-25 Ton)

RT-PRC002-EN

Typical
Wiring

(8-25 Ton)

Typical wiring diagram. For specific


wiring, see individual Service Facts.

PRINTED FROM: 2307-0307

RT-PRC002-EN

75

Typical
Wiring

76

(8-25 Ton)

RT-PRC002-EN

Typical
Wiring

(8-25 Ton)

Typical wiring diagram. For specific


wiring, see individual Service Facts.

PRINTED FROM: 2307-5513

RT-PRC002-EN

77

Dimensional
Data

(3-5Ton) Standard Efficiency


(3-4Ton) High Efficiency

All dimensions are in inches.

See page 94 for condensate


drain size and location

78

RT-PRC002-EN

Dimensional
Data

(3-5Ton) Standard Efficiency


(3-4Ton) High Efficiency

All dimensions are in inches.


Downflow Duct Connections Field Fabricated

Horizontal Unit Supply/Return(4 and 5 Ton Models Only)

See page 94 for condensate


drain size and location

RT-PRC002-EN

79

Dimensional (6, 7Ton) Std. Efficiency


(5-7Ton) High Efficiency
Data
All dimensions are in inches.

&

See page 94 for condensate


drain size and location

80

RT-PRC002-EN

Dimensional (6, 7Ton) Std. Efficiency


(5-7Ton) High Efficiency
Data

All dimensions are in inches.

Downflow Duct Connections Field Fabricated

Horizontal Unit Supply/Return

See page 94 for condensate


drain size and location
RT-PRC002-EN

81

Dimensional (8, 10Ton) Std . Efficiency


Data

All dimensions are in inches.

See page 94 for condensate


drain size and location

82

RT-PRC002-EN

Dimensional (8, 10Ton) Std. Efficiency


Data

All dimensions are in inches.

Downflow Duct Connections Field Fabricated

Horizontal Unit Supply/Return

See page 94 for condensate


drain size and location

RT-PRC002-EN

83

Dimensional
Data

(8Ton) High Efficiency


(12Ton) Std, Efficiency

All dimensions are in inches.

NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges. See recommended duct
dimensions on the next page.

84

RT-PRC002-EN

(8Ton) High Efficiency


(12Ton) Std. Efficiency

Dimensional
Data

1"

All dimensions are in inches.

16 3/16"

Downflow Duct Connections Field Fabricated

51 7/8"
22 5/16"

44 1/2"

1 1\2"
PERIMETER
CURB FLANGE

14 1/16"
7 7/16"

1"

UR

T
RE

LY

P
UP

S
NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges.

Horizontal Unit Supply/Return

RT-PRC002-EN

85

Dimensional (10, 12Ton) High Efficiency


(15, 17Ton) Std. Efficiency
Data

All dimensions are in inches.

NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges. See recommended duct
dimensions on the next page.

86

RT-PRC002-EN

Dimensional (10, 12Ton) High Efficiency


(15, 17Ton) Std. Efficiency
Data

All dimensions are in inches.


1"
Downflow Duct Connections Field Fabricated

17 7/8"
59 7/16"
26 5/16"

52 1/2"

1 1\2"
PERIMETER
CURB FLANGE

14 1/16"
7 7/16"

1"

UR

T
RE

LY

PP

SU

NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges.

Horizontal Unit Supply/Return

RT-PRC002-EN

87

Dimensional (15-25Ton) High Efficiency


(20, 25Ton) Std. Efficiency
Data
All dimensions are in inches.

NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges. See recommended duct
dimensions on the next page.

88

RT-PRC002-EN

Dimensional
Data
All dimensions are in inches.

(15-25Ton) High Efficiency


(20, 25Ton) Std. Efficiency

1"

Downflow Duct Connections Field Fabricated

19 5/16"
73 7/16"
66 1/2"

1"

1 1\2"
PERIMETER
CURB FLANGE

14 1/16"
7 7/16"

26 5/16"

RN
TU
E
R
LY
PP
U
S

NOTE:
Duct flanges mount 7-7/16" down
inside the curb on the 1" curb
flanges.

Horizontal Unit Supply/Return

RT-PRC002-EN

89

Dimensional
Data

(3-7Ton)
Accessories

All dimensions are in inches.

Note:
When applying economizer to horizontal units,
connecting ductwork must be run full size to allow
proper operation of Economizer Damper.

90

RT-PRC002-EN

Dimensional
Data

(8-25 Ton)
Accessories

All dimensions are in inches.

Note:
When applying economizer to horizontal units,
connecting ductwork must be run full size to
allow proper operation of Economizer Damper.

Table DD-1
Unit
Model #

TCR102-120, 150
14 /4
TCR121, 151-180, 210 171/2
TCR181, 211-301
191/2
1

B1

C2

33
53
64

33
36
39

NOTES:
1. Horizontal dimension only. Downflow economizer is
width of end panel.
2. Power exhaust is applied on downflow economizer
only.

RT-PRC002-EN

91

Dimensional
Data

Factory Installed
Options (FIOPS)

All dimensions are in inches.

Table DD-2
Unit
Model #
TCD036-060
TCD061-090
TCD090-091
TCD102, 120

311/4

511/8

25

331/4

531/8

25

32

531/8

287/8

Table DD-3
Unit
Model #

3/
8

TCD103, 150
33
TCD121, 151, 180, 210 423/8
TCD181, 211-301
291/2

92

39 /8
483/8
56

31
31
381/2

RT-PRC002-EN

Dimensional
Data

Factory Installed
Options (FIOPS)

Disconnect Switch
or Circuit Breaker

Fan Failure Switch

Clogged Filter Switch


Powered Or Unpowered
Convenience Outlet

Trane Communication Interface


Hinged Access Door

Hinged Access Door

Black Epoxy Coated


Outdoor Coils

Through the Base


Electrical
High Pressure Cut Out

Supply and/or Return


Smoke Detectors

RT-PRC002-EN

93

(3-25Ton)

Dimensional
Data

Table DD-4 Standard Efficiency Units

Tons

Downflow Only

A
3, 4, 5
6, 7
8, 10
12
15, 17
20, 25

Condensate
Drain Size

3/

13
153/16
153/16
227/16
267/16
267/16
16

3/

22
22
22
14
22
28

16
1/
2
1/
2
1/
2
1/
2
3/
4

C
1/

11
12
12
17
18
19

4
15/
16
15/
16
11/
16
11/
16
15/
16

7/

3/

2
31/4
43/16
41/4
41/4
41/4
8

3
33/8
33/8
41/4
41/4
41/4
8

7/

39
427/8
427/8
5413/16
627/16
765/16
8

1/

Condensate Drain Location


Downflow

32
351/4
351/4
473/16
5411/16
6811/16
4

3/

PVC
PVC
4 PVC
1 NPT
1 NPT
1 NPT

3/

4
4

3/

Horizontal

19
22
23

5/

24
25
26

5/
3/

8
8
4

20

2 3/16
3/
28 16
16
6
5 3/8

Table DD-5 High Efficiency Units

Tons

3, 4
5,6,7,7
8
10, 12
15-25

94

Condensate Drain Location

Condensate
Drain Size

Downflow Only

133/16
153/16
227/16
267/16
267/16

223/16
221/2
141/2
221/2
283/4

111/4
1215/16
1711/16
1811/16
1915/16

27/8
31/4
41/4
41/4
41/4

33/8
33/8
41/4
41/4
41/4

397/8
427/8
5413/16
627/16
765/16

321/4
351/4
473/16
5411/16
6811/16

Downflow

E
3/

PVC
3/
4 PVC
1 NPT
1 NPT
1 NPT
4

19
22

Horizontal

24
25
26

5/
5/
3/

8
8
4

20 3/8
2 3/16
16
6
5 3/8
RT-PRC002-EN

(3-25Ton)

Weights

Table W-1 Accessory Net Weights (Lbs)1, 8


Economizer

Outside Air Damper


Motorized

Power
Exhaust4

High6
Static
Drive

Oversized
Motor
Adder

Roof
Curb4

Low6
Static
Drive

Model No.

Net

Manual

TCR036,048,060C
TCR037,049

40

32

TCR075,090C,090D
TCR061,074,086C,091D,
TCR102C, 120C

40

32

35

65

82

TCD103C
TCD150C

40

32

35

75

165

TCD180B
TCD121,151C, TCD210C

65

32

60

95

205

TCD240B
TCD181,211,241C

80

32

75

95

235

TCD300B.301C

80

32

75

95

TCH103, 150C

35

32

35

TCH180B, 210C
TCH121,151C

50

32

60

TCH240B
TCH181,211,241C

65

32

75

TCH300B,301C

65

32

75

N/A

N/A

80

235

N/A

N/A

Table W-1 Continued


Electric Heaters
Unit
Model No.

All Zone
Sensors

6-23 KW
240/480V2

27-36 KW
240/480V2 3

54 KW
240/480V2

72 KW
240/480V2

TCR036, 048, 060C


TCR037,049

20/20

TCR075, 090C, 090D


TCR061,074,086C,091D, 102C, 120C

26/26

26/265

TCD103, 150C

28/21

31/27

38/32

TCD180B, 210C
TCD121,151,181C

28/217

31/27

38/32

TCD240B
TCD211,241C

TCD300B,301C

TCH103, 121C, 150C

28/21

31/27

38/32

TCH180B, 210C
TCH121,151,181C

28/217

31/27

38/32

TCH240B
TCH211, 241C

33/27

40/32

43/34

TCH300B, 301C

33/27

40/32

43/34

33/27

40/32

43/34

33/27

40/32

43/34

NOTES:
1. Net weight should be added to unit weight when ordering factory installed accessories.
2. For 600V heaters net weights are same as 480V heaters.
3. To estimate shipping weight add 5 lbs to net weight.
4. Downflow only.
5. 27 - 36 KW Heaters not available for TCR061C.
6. Not available on all models (See Fan Performance tables for specific models).
7. 9 - 23 KW Heaters not available for TCR210C.
8. TC102-300 factory installed options for economizers, multiply net capacity x .99, EER x .97. For oversized motors, multiply net capacity x .98, EER x .93.
This is provided in compliance with ARI certification program.

RIndicates both downflow and horizontal units.


RT-PRC002-EN

95

Weights

Table W-3 Maximum Unit And Corner Weights (Lbs) And Center Of Gravity Dimensions (In.)
Corner Weights (Lbs)1

Maximum Weights (Lbs)

Center of Gravity (In.)

Tons

Unit
Model No.

Net

Length

Width

3
4
5
6, 6

TCD036C/TCD037C
TCR048C/TCR049C
TCR060C/TCR061C
TCR075C/TCR074C

702/731
731/765
751/821
819/852

541/571
559/592
579/633
630/663

184/192
190/196
194/284
196/207

137/139
138/147
143/156
162/173

99/107
106/114
109/121
123/130

120/133
123/135
134/152
150/153

36/36
36/37
36/38
39/40

19/20
19/20
20/21
21/21

TCR090C/TCR086C
Single Compressor

878/861

689/673

229/213

177/173

130/130

153/156

39/39

20/21

TCR090D/TCR091D
Dual Compressor

940/953

751/765

264/265

182/188

130/135

175/176

36/37

20/20

TCR102C/TCR103C
TCR120C/TCR121C
TCR150C/TCR151C
TCR180B/TCR181C
TCR210C/TCR211C
TCR240B/TCR241C
TCR300B/ TCR301C

1064/1393
1086/1753
1460/1776
1739/2309
1820/2380
2309/2470
2365/2475

857/1094
879/1385
1161/1408
1371/1850
1452/1921
1850/2011
1906/2016

298/353
302/468
389/474
482/635
500/643
654/692
661/695

217/291
225/357
307/349
350/464
378/495
487/523
507/524

144/203
150/242
205/248
227/317
247/341
303/343
320/343

197/246
202/317
260/337
312/434
327/442
406/453
454/454

37/43
38/46
42/45
45/52
46/53
52/53
53/53

20/26
20/29
26/30
28/35
28/35
33/34
33/34

7, 7

8
10
12
15
17
20
25

Shipping

NOTES:
1. Corner weights are given for information only. 8-25 ton models must be supported continuously by a curb or equivalent frame support.
2. Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.

RIndicates both downflow and horizontal units.

96

RT-PRC002-EN

Weights

Table W-3 Factory Installed Options (FIOPS) Net Weights (Lbs)1,2,3


Accessory
High Efficiency Motors
Hinged Doors
Powered Convenience Outlet
Through the Base Electrical
Unit Mounted Circuit Breaker
Unit Mounted Disconnect

Model
Number
FIYHEMT001,002
FIYHEMT003-005
FIYHEMT006-008
FIYHNGE001,002
FIYHNGE003-009
FIYCOPO101-206
FIYTBUE101-111
FIYTBUE201-216
FIYUCB4015-4150
FIYUCB3175-3250
FIYUDC4150,6100
FIYUDC3250

Weight
15
49
36
10
27
38
16
23
5
10
5
10

NOTES:
1. Weights for FIOP accessories not listed are >5 lbs.
2. Net weight should be added to unit weight when ordering factory installed accessories.
3. See Table W-1 for standard factory installed economizer, electric heater and oversized motor.

RT-PRC002-EN

97

Mechanical
Specifications

General
The units shall be dedicated downflow
or horizontal airflow.The operating
range shall be between 115 F and 0 F in
cooling as standard from the factory for
all units. Cooling performance shall be
rated in accordance with ARI testing
procedures. All units shall be factory
assembled, internally wired, fully
charged with R-22 and 100% run tested
to check cooling operation, fan and
blower rotation and control sequence
before leaving the factory. Wiring
internal to the unit shall be colored and
numbered for simplified identification.
Units shall be UL listed and labeled,
classified in accordance to UL 1995/
CAN/CSA No. 236-M90 for Central
Cooling Air Conditioners. Canadian
units shall be CSA Certified.
Casing
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
All components shall be mounted in a
weather resistant steel cabinet with a
painted exterior. Cabinet construction
shall allow for all maintenance on one
side of the unit. Service panels shall
have lifting handles and shall be
removed and reinstalled by removing
not more than three screws while
providing a water and air tight seal. All
exposed vertical panels and top covers
in the indoor air section shall be
insulated with fire-resistant,
permanent, ordorless glass fiber
material. The base of the downflow
unit is insulated with a foil-faced,
closed-cell material. The downflow
units base pan shall have no
penetrations within the perimeter of
the curb other than the raised 11/8" high
supply/return openings to provide an
added water integrity precaution
should the condensate drain back up.
Each unit has a sloped condensate
drain pan. The base of the unit shall
have provisions for forklift and crane
lifting.

98

Filters
One inch, throwaway filters shall be
standard on all 3-7 ton units. Filter rack
can be converted to two inch capability.
Two inch filters shall be factory supplied
on all units above 7 tons.
Compressors
All 3-10 ton standard, 3-7 and 10 ton
high efficiency units shall have directdrive hermetic, reciprocating type
compressors. The reciprocating type
compressors have a centrifugal oil pump
providing positive lubrication to moving
parts. Motor shall be suction gas-cooled
and shall have a voltage utilization range
of plus or minus 10 percent of unit
nameplate voltage. Crankcase heater,
internal temperature and currentsensitive motor overloads shall be
included for maximum protection. Shall
have internal spring isolation and sound
muffling to minimize vibration
transmission and noise. Low pressure
switches shall be standard.
8 ton high efficiency and 12 to 25 ton
standard and high efficiency units shall
have direct-drive, hermetic, scroll type
compressors with centrifugal type oil
pumps. Motor shall be suction gascooled and shall have a voltage
utilization range of plus or minus 10
percent of unit nameplate voltage.
Internal overloads shall be provided with
the scroll compressors. The scrolls used
on the 12, 15 and 17 ton high
efficiency and 15, 17, and 25 ton
standard efficiency units have crankcase
heaters.

Evaporator and Condenser Coils


Internally finned 3/8" copper tubes
mechanically bonded to configured
aluminum plate fin shall be standard.
Coils shall be leak tested at the factory to
ensure the pressure integrity. The
evaporator coil and condenser coil shall
be leak tested to 200 psig and pressure
tested to 450 psig. On all dual
compressor models, the evaporator coil
shall be intermingled configuration.
Outdoor Fans
The outdoor fan shall be direct-drive,
statically and dynamically balanced,
draw through in the vertical discharge
position. The fan motor(s) shall be
permanently lubricated and have built-in
thermal overload protection.
Indoor Fan
Units 5 and below shall have directdrive, FC, centrifugal fans. Units above 5
tons shall have belt driven, FC,
centrifugal fans with adjustable motor
sheaves. 8-25 ton units shall have an
adjustable idler-arm assembly for quick
adjustment of fan belts and motor
sheaves. All motors shall be thermally
protected. Oversized motors will be
available for high static operations. All
indoor fan motors meet the U.S. Energy
Policy Act of 1992 (EPACT).

Refrigerant Circuits
Each refrigerant circuit shall have
independent fixed orifice expansion
devices, service pressure ports and
refrigerant line filter driers factoryinstalled as standard. An area shall be
provided for replacement suction line
driers.

RT-PRC002-EN

Mechanical
Specifications
Controls
Unit shall be completely factory wired
with necessary controls and contactor
pressure lugs or terminal block for
power wiring. Units shall provide an
external location for mounting fused
disconnect device. Micro-processor
controls shall be provided for all 24 volt
control functions. The resident control
algorithms shall make all heating,
cooling and/or ventilating decisions in
response to electronic signals from
sensors measuring indoor and outdoor
temperatures.The control algorithm
maintains accurate temperature control,
minimizes drift from set point and
provides better building comfort. A
centralized Micro-processor shall provide
anti-short cycle timing and time delay
between compressors to provide a
higher level of machine protection.

Accessories
Electric Heaters Electric heat
modules shall be available for
installation within basic unit. Electric
heater elements shall be constructed of
heavy-duty nickel chromium elements
internally delta connected for 240 volt,
wye connected for 480 and 600 volt.
Staging shall be achieved through the
unitary control processor (UCP). Each
heater package shall have automatically
reset high limit control operating
through heating element contactors. All
heaters shall be individually fused from
factory, where required, and meet all
NEC and CEC requirements when
properly installed. Power assemblies
shall provide single-point connection.
Electric heat modules shall be UL listed
or CSA certified.
Roof Curb - Downflow The roof
curb shall be designed to mate with the
downflow unit and provide support and
a water tight installation when installed
properly. The roof curb design shall
allow field-fabricated rectangular supply/
return ductwork to be connected directly
to the curb. Curb design shall comply
with NRCA requirements. Curb shall
ship knocked down for field assembly
and include wood nailer strips.

RT-PRC002-EN

Economizer - Downflow This


accessory shall be either field or factory
installed. The assembly includes: fully
modulating 0-100 percent motor and
dampers, barometric relief, minimum
position setting, preset linkage, wiring
harness with plug, and fixed dry bulb
control. The barometric relief damper
shall be standard with the downflow
economizer and shall provide a pressure
operated damper that shall be gravity
closing and prohibit entrance of outside
air during the equipment off cycle.
Solid state enthalpy and differential
enthalpy control shall be factory
supplied, field installed option.
Economizer - Horizontal This
accessory shall be field installed only.
The horizontal economizer shall be
available and contain the same features
as the downflow economizer with the
exception of barometric relief.
Remote Potentiometer The
minimum position setting of the
economizer shall be adjusted with this
accessory.
Powered Exhaust Shall be available
on units above 5 tons.The accessory
shall assist the barometric relief damper
in the economizer in relieving building
pressurization.
Manual Outside Air Damper Field
installed rain hood and screen shall
provide up to 25 percent outside air.
Motorized Outside Air Dampers
Manually set outdoor air dampers shall
provide up to 50 percent outside air.
Once set, outdoor air dampers shall
open to set position when indoor fan
starts.The damper shall close to the full
closed position when indoor fan shuts
down.This option shall be available for
the 6-25 ton models.
High Static Drive Field installed
high static drive option shall allow the
standard motor to operate with
improved external static capabilities.
(See Fan Performance tables).

Low Static Drive Field installed low


static drive option shall allow the
standard motor to operate at lower static
performance. (See Fan Performance
tables).
Oversized Motors Factory or field
installed oversized motors shall be
available for high static applications.

Control Options
Trane Communication Interface
(TCI) Shall be provided to interface
with theTrane Integrated ComfortTM
System.
Zone Sensors Shall be provided to
interface with the Micro equipped
Voyagers and shall be available in either
manual, automatic programmable with
night setback, with system malfunction
lights or remote sensor options.
Conventional Thermostat Interface
(CTI) This field installed circuit board
shall provide interface with electromechanical thermostats or automation
systems.
Differential Pressure Switches
This field installed option allows
individual fan failure and dirty filter
indication.The fan failure switch will
disable all unit functions and flash the
Service LED on the zone sensor.The dirty
filter switch will light the Service LED on
the zone sensor and will allow continued
unit operation.
Input/Output Expansion Accessory
This kit allows Integrated Comfort
Systems to read Supply AirTemperature,
Return AirTemperature, Return Air
Humidity, and direct indication of fan
failure without the use of an economizer
or motorized outside air accessory.
Electronic Time Clock This field
installed accessory allows up to 4 units
night set-back and unoccupied functions
when using a standard (Dual Setpoint)
zone sensor module.

99

Mechanical
Specifications

Additional Factory Installed


Options (FIOPS)
Electric Heaters Factory installed
and wired electric heaters are available
for all 3 phase horizontal and downflow
3 - 25 ton models. If ordering the
Through the Base Electrical option with
an Electric Heater, the heater must be
factory installed
Through the Base Electrical With
Disconnect Switch Factory installed
3-pole, molded case disconnect switch
with provisions for through the base
electrical connections are available. The
disconnect switch will be installed in the
unit in a water tight enclosure with
access through a swinging door. Factory
wiring will be provided from the switch
to the unit high voltage terminal block.
The switch will be UL/CSA agency
recognized. Note:The disconnect switch
will be sized per NEC and UL guidelines
but will not be used in place of unit
overcurrent protection.This option is
available on all 3-25 ton downflow
models.
Through the Base Electrical with
Circuit Breaker This option is a
factory installed thermal magnetic,
molded case, HACR Circuit Breaker with
provisions for through the base electrical
connections. The circuit breaker will be
installed in a water tight enclosure in the
unit with access through a swinging
door. Factory wiring will be provided
from the switch to the unit high voltage
terminal block.The circuit breaker will
provide overcurrent protection, be sized
per NEC and UL guidelines, and be
agency recognized by UL/CSA.This
option is available on all 3-25 ton
downflow models.

Powered or Unpowered
Convenience Outlet This option is a
GFCI, 120v/15amp, 2 plug, convenience
outlet, either powered or unpowered.
When the convenience outlet is
powered, a service receptacle disconnect
will be available. The convenience outlet
is powered from the line side of the
disconnect or circuit breaker, and
therefore will not be affected by the
position of the disconnect or circuit
breaker. This option can only be ordered
when theThrough the Base Electrical
with either the Disconnect Switch, or
Circuit Breaker, option is ordered.This
option is available on all 3-25 ton
downflow models.
Clogged Filter/Fan Failure Switch
A dedicated differential pressure switch
is available to achieve active fan failure
indication and/or clogged filter
indication. These indications will be
registered with either a zone sensor with
status indication lights or an Integrated
Comfort System.
Reference or Comparative Enthalpy
Reference or Comparative Enthalpy
option shall be available when a factory
installed Downflow Economizer is
ordered.This option is available on all 325 ton downflow models.
Input/Output Expansion Module
This factory installed option will allow an
Integrated Comfort System to read
Supply AirTemperature, Return Air
Temperature, Return Air Humidity, and
direct indication of fan failure without the
use of an economizer or motorized
outside air accessory.
High Pressure Cutout This option is
offered for units that do not have High
Pressure cutout as standard. The units
WITH High Pressure Cutout as standard
are: TC*090C,TC*180-301B,C
Hinged Access Doors Sheet metal
hinges are available factory installed on
the Filter/Evaporator Access Door and
the Compressor/Control Access Door.
This option is available on all 3-25 ton
downflow models.

100

Trane Communications Interface


(TCI) An option for a factory installed
Trane Communication Interface is
available to allow twisted wire pair
communication with an Integrated
Comfort System. Order this option
when a combination of TCI and
oversized motor is desired.
Discharge Air Sensing Kit Provides
true discharge air sensing in heating
models. This sensor is a status indicator
readable throughTracer orTracker.
Functional only with theTCI and
Economizer orTCI and Generic Input/
Output Module options.
High Efficiency Motors Available
with efficiency ratings from 86.5 up to
91.0. Not available for all models.
Supply and/or Return Air Smoke
Detector With this option installed, if
smoke is detected, all unit operation will
be shut down. Reset will be manual at
the unit. Return Air Smoke Detectors
require minimum allowable airflow
when used with certain models. See the
Installation, Operation, and Maintenance
(IOM) manual for the models affected
and the minimum allowable airflow
required. This option is available on all 325 ton downflow models.
Conventional Thermostat Interface
This option is a circuit board mounted
in the unit control box to the right of the
Unitary Control Processor board. It
allows the unit to be operated by an
electo-mechanical thermostat or through
dry contact closure type controls.
Black Epoxy Coated Condenser Coil
Provides corrosion protection to
condenser coils for seacoast application.
The protection is a factory applied
thermoset vinyl coating, bonded to
normal aluminum fin stock. The uniform
thickness of the bonded vinyl layer
exhibits excellent corrosion protection in
salt spray tests performed in accordance
with ASTM B117.

RT-PRC002-EN

RT-PRC002-EN

The Trane Company


Unitary Products Group
2701 Wilma Rudolph Blvd.
Clarksville, TN 37040
www.trane.com
An American Standard Company

Literature Order Number

RT-PRC002-EN

File Number

PL-UN-RT-TCD/TCH 3-25 TONS-PRC002-EN-05-00

Supersedes

TC-D-5 (22-1352-10, Tab 3)

Stocking Location

Inland-LaCrosse (Printing Inc-Louisville)

Since The Trane Company has a policy of continuous product and product data improvement, it reserves the
right to change design and specifications without notice.