Kamin Dave Manager Marketing & Protection Applications

DOBLE ENGINEERING COMPANY, INDIA

kdave@doble.com

Protection Relay Testing:

Testing of Generator Protection Relay type SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Under & Over Voltage Protection (27/59) Negative sequence Protection (46) Reverse & Low Forward Power Protection (32) Over Excitation Protection (24) Over & Under Freq. Protection (81O/81U) Under Impedance Protection (21) Loss of Excitation Protection (40G) 100% Stator E/F Protection (27TN/64G2)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Out of Step Protection (78) Voltage Restrained O/C Protection (51VR) Voltage Controlled O/C Protection (51VC) Rotor E/F Protection (64R) Breaker Failure Protection Generator Differential Protection (87D) Ground differential Protection (87N) 95% Stator E/F Protection (59GN/64G1)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Primary & Backup Protection


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Rotor Earth Fault Protection


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Zone2 Reach Zone1 Reach

Load Encroachment characteristic plotted

Characteristic plotted in F6TEST2.21 software for testing


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Select D from List

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

GCB Status Close Input

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Breaker close input & VT fuse fail input

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Characteristic selection

VT fuse fail Status Input

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


V/Hz Curve1

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


V/Hz Curve2

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


V/Hz Curve3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Selection of Curve

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Set as a Low Forward Power threshold range

Set as a Reverse Power threshold range


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Set as Reverse Power function

VT Fuse fail Input

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Relay Logic for Reverse Power Function

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Zone1 Offset reactance for Zone1 Zone2 Offset reactance for Zone2 Directional Angle for Zone2

VT fuse fail Status Input Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Directional Angle for Zone2

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Relay Logic for Loss of Excitation Function

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Enter Setting of NPS Threshold

Enter Time Dial Setting

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Relay Logic for Negative Sequence current Function

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Select function V

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Threshold value Curve selection C1 VT fuse fail status input

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

K = 0.25 Normal Inverse Curve

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Select function C

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Threshold value Curve selection C1 VT fuse fail status input

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

K = 0.2 Normal Inverse Curve

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


0-95% SEF 100% SEF

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Relay Details: SEL300G


Under Freq. function

Under Freq. function

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Equipment Make : DOBLE

Model : F6150

Software F6TesT Version 2.21-1165

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

F6150 Connections:
PT Connections CT Connections

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300 Connections:
CT Connections PT Connections

Connections of 4th Voltage for 100% SEF


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Over Excitation Function (24)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit: Over Excitation Function Test


Source Configurations: 3V X 3I

CT Inputs

VA
SEL

I1

VB

I2

VC

I3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Inverse Time Curve Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use VFChar Module for Characteristic Search Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Curve3 selection Enter Time Dial

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Curve3 for Testing

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Expected Curve
Actual Curve from relay

Phasor
Relay settings: V/Hz = 1PU Curve = 3 Time Dial = 1
SM

Select ABC Fault for testing


Knowledge Is Power
Apparatus Maintenance and Power Management for Energy Delivery

Testing of Reverse Power Function (32)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example1


Failed Prime-mover Gen Set

GT D Y

MVAR

TL Line
CB1 CB3

MW
GCB

G
E
Gen Set

CB5

GT D Y

MVAR

TL Line
CB2 CB4

MW

G
E
Healthy Prime-mover

GCB

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example2


Failed Prime-mover Gen Set

GT D Y

MVAR

TL Line
CB1 CB3

MW
GCB

G
E
Gen Set

CB5

GT D Y

MVAR

TL Line
CB2 CB4

MW

G
E
Healthy Prime-mover

GCB

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example3


Failed Prime-mover Gen Set

Grid

MW

GT D Y

MVAR

TL Line
CB1 CB3

MW
GCB

G
E

MW
CB5

Grid

MW

Active Power Import from Grid sources


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Reverse Power Protection (32R): Example4


Failed Prime-mover Gen Set
MVAR
CB1

CB2

G
E

GCB

CB3

D
M

CB4

CB5

CB6

Only Reactive Power Export to Loads


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Loads

TR2

Loads

TR1

Test Circuit: Reverse Power Function Test


Source Configurations: 3V X 3I

CT Inputs

VA
SEL

I1

VB

I2

VC

I3

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Pickup Test Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use RAMP Module for Pickup Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ Unity PF:


MVAR
MVAR

- MW
Watts = VA = 952.87W

MW

- MW

MW

IExpected = 1A

- MVAR

- MVAR

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ Unity PF:


Vn = 110V In = 5A PF = 1 (Unity) PN = (1.7325*0.11*1000*5) = 952.87watts %PSet = 20% of PN PSet = (952.87 * 20)/(PF*100) = 190.5watts IExpected = (190.5)/(1.7325*0.11*1000*PF) = 1A

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup

IA@180o

Actual Operating Values Enter Expected Value = 1A


Enter Action details
SM

Knowledge Is Power

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ 0.8 lag PF:

MVAR
VA = 952. 87

MVAR

VA

- MW

MW

- MW Watts = 762.3W

MW IExpected = 1.15A

- MVAR

- MVAR

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup

IA@150o

Actual Operating Values Enter Expected Value = 1.15A


Enter Action details
SM

Knowledge Is Power

Apparatus Maintenance and Power Management for Energy Delivery

Pickup Test @ 0.8 lead PF:

MVAR

MVAR

Watts = 762.3W - MW
V 7V A 52.8 A=9

- MW

MW

MW IExpected = 1.15A

- MVAR

- MVAR

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Pickup

IA@210o

Actual Operating Values Enter Expected Value = 1.15A


Enter Action details
SM

Knowledge Is Power

Apparatus Maintenance and Power Management for Energy Delivery

Use SSIMUL Module for Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

TAct = 262ms TExp = 200ms

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Loss of Excitation Function (40G)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit: Field Failure Function Test


3V Source Configurations: 3V & 3I

3I
IA
SEL

VA VB

IB

VC

IC

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Characteristic Search Test Characteristic Time Test RCA (MTA) Test


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Use ZChar Module for Characteristic Search Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Zone1 setting = 20.4Ohms

Zone2 setting = 30.5Ohms

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Blue color shows expected characteristic and pink color shows actual tested characteristic

Show Phasors: fault voltage & current of ABC fault

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Click on Oscillograph: Shows, voltage & current waveform of ABC fault Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Zone1 setting = 20.4Ohms

Zone2 setting = 30.5Ohms Offset = -3.5 Ohms

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Blue color shows expected characteristic and pink color shows actual tested characteristic

Show Phasors: fault voltage & current of ABC fault

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use ZTime Module for Characteristic Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Show Phasors: fault voltage & current of ABC fault Results Table shows; Zone1 time is 0.1s & Zone2 time is 0.4s
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: Field Failure Function Testing

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: Field Failure Function Testing

LED Indicator operated Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use ZMTA Module for Characteristic MTA (RCA) Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Angle Boundary (Theta1) Angle Boundary (Theta2)

Fault type ABC selected for testing

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: Field Failure Function Testing

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Negative Sequence Function (46)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Negative Sequence Protection (46) Sequence Components


Ic Ia Ib +VE Seq. Ic -VE Seq. Zero Seq. Ib Ia Ib Ia Ic

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Negative Sequence Protection (46)

Gen Set
MVAR

GT
MW

MVAR

MW
GCB

G
E

F1

46 Operate: I2Measure>I2Set
Knowledge Is Power
SM

Sys

Apparatus Maintenance and Power Management for Energy Delivery

Negative Sequence Protection (46)

Gen Set

GT D Y
GCB

G
IB @ 240O

F1

46 Operate: I2Measure>I2Set
IY @ 120O

IR @ 0o

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit: Negative Phase Seq. Function Testing


Source Configurations: 3I

3I
I1@0o
SEL

I2@120o I3@240o

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Inverse Time Curve Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use IChar Module for Characteristic Search Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Curve selection Enter Time Dial

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Inverse Curve for Testing

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Phasors shows symmetrical components value (i.e. I1, I0 & I2) Blue color line shows Expected curve & Knowledge Is Power Pink color line shows Actual tested curve

SM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Voltage Controlled Over Current Function (51VC)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Voltage Dependent Over Current Protection (51V)


Voltage Controlled over current function (51VC): Normally Protection applied for Directly connected Generators where system voltage collapse drastically falls below set value (VSet) during faults.
6.37 MVA 11KV PF = 0.8, Xd=36.4%, Xd=26% Xd = 231% 1.5MVA, 11KV/0.415KV, %Z = 4.9%

F2

CB1

Y F1

G
Y
VT

GCB

51

CB2

3
51

1.5MVA, 11KV/0.415KV, %Z = 4.9%

51VC

Y CB2

Knowledge Is Power

SM

Motpro

Apparatus Maintenance and Power Management for Energy Delivery

Voltage Dependent Over Current Protection (51V)

51V-Voltage Controlled
I*/ [I>]
1.0

Vmeasured > Vset Ipickup = (Iset) T = (0.14*T) / ((Ipickup)0.02-1) Vmeasured < Vset Ipickup = (k*Iset) T = (0.14*T) / ((Ipickup)0.02-1)
0.2 0.8

0.2

V/Vs

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit: Voltage Controlled O/C Function Testing


3V Source Configurations: 3V & 3I

3I
IA
SEL

VA VB

IB

VC

IC

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Inverse Time Curve Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use IChar Module for Characteristic Search Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Curve selection Enter Time Dial

Relay Settings: I> = 0.5*In Curve = C1 Time Dial = 1 V1 = 50VL-N V2 = 25VL-N

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for testing

Relay Settings: I> = 0.5*In Curve = C1 Time Dial = 1 V1 = 50VL-N V2 = 25VL-N

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Injected Voltage to relay

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Blue color shows expected characteristic and pink color shows actual tested characteristic

Display Phasors Right click on check box to enable voltage O/P


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Voltage Restrained Over Current Function (51VR)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Voltage Dependent Over Current Protection (51V)


Voltage Restrained over current function (51VR): Normally Protection is applicable when Generator is connected to system through GT.
F2
CB1

Y F1

3
51

G
Y
VT

GCB

Y
CB2

51

51VC

Y CB2

Motpro

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit: Voltage Restrained O/C Function Testing


3V Source Configurations: 3V & 3I

3I
IA
SEL

VA VB

IB

VC

IC

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Voltage Dependent Over Current Protection (51V)

I*/ [I>]
1.0

51V-Voltage restrained

Vmeasured > Vset2 Ipickup = (Iset)

Sl
0.2 0.2

pe

re

o gi

Vset1 < Vmeasured < Vset2 Vmeasured < Vset1 Ipickup = (k*Iset)
0.8

V/Vs

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Inverse Time Curve Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use IChar Module for Characteristic Search Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Curve selection

Enter Time Dial

Relay Settings: I> = 1*In Curve = C1 Time Dial = 1 V1 = 50VL-N V2 = 25VL-N

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Characteristic created for testing

Relay Settings: I> = 1*In Curve = C1 Time Dial = 1 V1 = 50VL-N V2 = 25VL-N

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Injected Voltage to relay

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Blue color shows expected characteristic and pink color shows actual tested characteristic

Display Phasors Right click on check box to enable voltage O/P


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of 0-95% Stator Earth Fault Function (64R1/59GN)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (59GN): Resistor Ground


VLN = 21000/1.7325 PTR = 21000/240V CTR = 20/1A

IF
100 Ohms, 10s

IF

Maximum Ground Fault Amps = (Line to Neutral Voltage) ------------------------------------(NGR Resistance)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (59GN): Impedance Ground (NGT)


IF

VLN = 21000/1.7325 KVPri = 21kV KVSec = 0.240kV KVA = 70KVA R = 0.913 Ohms Full Load current in Primary wdg = 3.33A Ground Fault Impedance = 3640.004 Ohms
Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit: 0-95% SEF Function Testing


3V Source Configurations: 4V

4th V@50Hz
VN
SEL

VA VB

VC

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Pickup Test Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use RAMP Module for Pickup Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Action details for Voltage Ramp

Pickup Value = 5V

4th Voltage used

Expected value = 5V Actual value = 5.3V


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Use SSIMUL Module for Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Ground Fault condition Display Phasor


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

4th Voltage

Ground Fault condition Display Waveforms (Analogue & Digital Channels)


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 1s

Relay Output (Open to Close contact)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of 100% Stator Earth Fault Function (64R2/27TN)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (27TN)


3rd Harmonic Current circulate

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Stator Ground Fault Protection (27TN): 3RD Harmonic Under Voltage Method
3rd Harmonic Under voltage relay

3rd harmonic voltage drop Because capacitance Is shorted

IF

IF
3rd Harmonic Voltage at Neutral End reduced

3rd Harmonic Voltage at Neutral End reduced

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit: 100% SEF Function Test


3V Source Configurations: 4V

4th V@150Hz
VN
SEL

VA VB

VC

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Pickup Test Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use RAMP Module for Pickup Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Action details for Voltage Ramp

Pickup Value = 1.2V

4th Voltage used @ 150Hz Freq.

Expected value = 1V Actual value = 1.2V


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Use SSIMUL Module for Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Ground Fault condition close to Neutral

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 0.55s

Relay Output (Open to Close contact)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: 100%SEF Function Testing

LED Indicator operated Knowledge Is Power


SM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Under Frequency Function (81UF)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit: Under Freq. Function Test


3V Source Configurations: 3V & 3I

3I
IA
SEL

VA VB

IB

VC

IC

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Pickup Test Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use RAMP Module for Pickup Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Action details for Freq. Ramp

Pickup Value = 48.5Hz

Freq. of Voltage sources

Expected value = 48.5Hz Actual value = 48.498Hz


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Use SSIMUL Module for Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Under Frequency condition (48Hz Freq. for Voltage sources)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 0.33s

Relay Output (Open to Close contact)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Testing of Over Frequency Function (81O/F)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Test Circuit: Over Freq. Function Test


3V Source Configurations: 3V & 3I

3I
IA
SEL

VA VB

IB

VC

IC

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Tests conducted:

Pickup Test Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Use RAMP Module for Pickup Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Action details for Freq. Ramp

Pickup Value = 51.0002Hz

Freq. of Voltage sources

Expected value = 51Hz Actual value = 51.0002Hz


Knowledge Is Power
SM

Apparatus Maintenance and Power Management for Energy Delivery

Use SSIMUL Module for Time Test

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Over Frequency condition (51Hz Freq. of Voltage sources)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Actual trip time = 93.9ms

Relay Output (Open to Close contact)

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

SEL300G: 100%SEF Function Testing

LED Indicator operated

Knowledge Is Power

SM

Apparatus Maintenance and Power Management for Energy Delivery

Training to L&T Power at Doble Training Center