SMC-Flex Selection Guide

New Dimensions in Motor Control

Discover a New Dimension in Motor Control: SMC-Flex


The Allen-Bradley SMC-Flex softstarter, from complete Automation supplier Rockwell Automation, provides integrated features and technology previously unavailable in a softstarter. The flexibility and capabilities of the SMC-Flex make it ideal for virtually any application. The same high-grade quality and functionality found in the original SMC products exist today in the SMC-Flex. And with the available options, functionality, and application capabilities, the SMC-Flex is unmatched in the industry.

SMC-Flex Smart and Compact Soft Starter


The SMC-Flex takes softstarting to new dimensions by reducing both product size and the total cost to the customer. As standard, the SMC-Flex includes electronic overload, integral bypass, modular communication capabilities, motor starting capabilities for both star-delta and standard squirrel-cage induction motors, advanced protection and diagnostics in a compact, maintainable, modular, costeffective package.

Why Use Smart Motor Controllers (SMCs)?


SMC-Flex Provides many features to benefit your system:
Minimize mechanical damage resulting from full-voltage starting of AC induction motors, enabling longer system life Limit line disturbances from inrush currents, resulting in reduced downtime Multiple Start/Stop modes increase functionality Diagnostic monitoring helps prevent problems before they occur Satisfy electrical distribution restrictions by reducing inrush currents

SMC-Flex is ideal for applications where:


Belts, gears, and chains can be damaged by across-the-line starting Materials can be damaged by sudden starts and stops A step change in torque can damage equipment Power company line current restrictions are imposed Space is a premium and enclosure size must be minimized Solid-state starting is needed for a Star-Delta motor application

With SMC Softstarters you benefit from:


Advanced diagnostics, increasing system performance Compact, space-saving footprint Greater product functionality for increased system flexibility Decreased downtime due to advanced protection of motor winding, equipment, and materials Greater system operation accuracy due to improved technology Ease of purchasing, installation, setup and maintenance

SMC-FLEX Size for Size Best Value in the Industry


Current Range Amps
Product Rating
108 135 201 251 317 361 480

Line Current
108 135 201 251 317 361 480

Delta Current
187 234 348 435 549 625 831

The SMC-Flex provides intelligence, unmatched performance, flexibility, diagnostics, and communication in a modular compact design for controlling either a standard squirrel-cage induction motor or a star-delta motor.

Compact Size
The SMC-Flex integrates a bypass to minimize heat generation during run time. The bypass automatically closes when the motor reaches its nominal speed, resulting in a cooler-running component and reduction in enclosure size.

Voltage Range
200 600V AC, 50/60 Hz

Control Voltage
100 240V AC or 24V AC/DC

Starting Modes

Motor Connection

Standard Soft Start Soft Stop Current Limit Full Voltage Kick Start Preset Slow Speed Linear Speed Start and Stop Dual Ramp Pump Start and Stop Smart Motor Braking Accu-Stop Slow Speed with Braking X X X X X X X X

Pump Control X X X X X

Braking Control X X X X X X

Line Connection

1/L1

3/L2

5/L3

X X X X

Features
Overload
Flexibility in Trip Class (10, 15, 20, 30, Off) Reset Operation (Manual or Automatic)

2/T1

4/T2

6/T3

Diagnostics
PTC Line Fault Voltage Imbalance Undervoltage Overtemperature Overload Ground Fault Power Loss Phase Reversal Overvoltage Open Gate Excessive Starts per Hour

Configurable Auxiliary Contacts


Auxiliary #1 Normal, Up-to-speed, External Bypass Fault Contact Alarm Contact Auxiliary #2 Normal (N.O./N.C.)

Delta Connections

1/L1

3/L2

5/L3

Motor Control
Standard Squirrel-Cage Induction Motor Star-Delta Motor

Communication
DeviceNet , ControlNet , EtherNet , Remote I/O, RS-485, Profibus , Interbus

Metering
Three-phase Currents Power in kW Motor Thermal Capacity Usage Elapsed Time of Motor Operation Three-phase Voltages Power Usage in kWH Power Factor of the Running Motor
12/T6 2/T1 8/T4 4/T2 10/T5 6/T3

M
3~

Unsurpassed Advantages
Features
Built-in Overload

Benefits
Multiple overload trip class selection Less products to inventory Ease of selection Ease of setup Reduced footprint Reduced footprint Minimal heat loss Reduced enclosure size Reduced total cost Reduction in inventory Cost savings Flexibility of system configuration No external components to purchase Less product to inventory Built-in power monitoring Takes mystery out of motor operation No additional investment required Minimize panel space Minimal parameters to set up Ease of setup Ease of operation Multilingual for a diverse workforce Ease of maintenance

Integral Bypass

Flexible Communication Option

Configurable Auxiliary Contacts

Full Metering and Diagnostics

LCD Display

Product Modularity

Auxiliary Contact Number


#1 N.O. Fault Alarm #2 Normal

Configurable to:
Normal / Up-To-Speed / External Bypass N.O. / N.C. N.O. / N.C. N.O. / N.C.

Modular by design
for Installation and Commissioning
Fan Assembly

Power Pole Feed-Through Wiring

DPI Communications (same as Powerflex Drives) Programmer and Backlit LCD

Control Terminal Blocks Power Connections for Standard Squirrel-Cage Induction Motor or Star-Delta Motors

Catalog # 150-F251NBD Illustrated

Ease of Maintenance
Modular Power Structure Removable Control Module Changeable Fan Assembly

Control Module

Power Structure

The SMC-Flex has been designed to make customer use easier than ever before. The modular design of the product takes maintenance to a new level of simplicity.
Protection

The modular communication capability makes it the most flexible and advanced product on the market.

Power termination covers

Advanced Diagnostics
PTC Input Ground Fault Detection Additional Current Transformer required Catalog Number 825-CBCT

Communication
The Allen-Bradley family of 20-COMM DPI communication interfaces allows the SMC-Flex to be connected to multiple network types including DeviceNet, ControlNet, EtherNet, Remote I/O, RS-485, Profibus and Interbus. All connections are built into the SMC-Flex so no additional panel space is required.

SMC-Flex Ideal for a Wide Range of Applications


Allen-Bradley SMC-Flex provides innovative starting and stopping solutions for ample design flexibility with minimal control module options meeting the needs of most production applications. To help identify which start and stop profiles, described in the following pages, are included in each control module option, use the following code: STANDARD PUMP CONTROL BRAKING CONTROL

100

Soft Start
By reducing starting torque surges, Soft Start provides smooth, stepless motor acceleration while minimizing damage to gears, couplings and belts.
Start Run

Voltage

Initial Torque

100

Soft Stop
The Soft Stop option extends the stopping time to minimize load shifting or spillage.

Motor Speed

Start

Run

Coast Soft Stop

600

Current Limit Start


Current Limit starting is designed for applications that require the in-rush current to be limited during acceleration.
Note: Selectable Kickstart is also available with the Current
Limit Start.
Start

% of FLC

50

100

Full-Voltage Start
In the Full-Voltage Start mode, the SMC performs like a solid-state contactor, achieving full in-rush current and locked rotor torque.
Run

Voltage

Kick Start with Soft Start


Activate the Selectable Kickstart function to provide an extra pulse of torque. This optional feature is ideal for overcoming stiction wherever high-friction loads are encountered.
Voltage Initial Torque

100

Kickstart
(when selected)

Start

Run

Preset Slow Speed


The Preset Slow Speed option furnishes two jog speeds to facilitate process setup and alignment. These speeds are available in both the forward and reverse direction without a reversing contactor.
Motor Speed

100

Slow Speed Forward

7% or 15%

Stop
10% or 20%

Slow Speed Reverse

Linear Speed Start and Stop


With this type of acceleration mode, a closedloop feedback system maintains the motor acceleration at a constant rate. The required feedback signal is provided by a DC tachometer coupled to the motor (tachometer supplied separately).
Note: This mode is also available with Kickstart.
Motor Speed

100

Start

Run

Linear Stop

Dual Ramp Start


Available exclusively on the SMC Flex controller, Dual Ramp Start allows you to choose between two separate Start profiles with independently adjustable ramp times and torque settings. Its designed for applications with varying loads, two-speed requirements and reversing.
100

Ramp 2 Voltage Ramp 1

Start 1

Start 2

Run

Pump Start and Stop


The SMC controller's unique, interactive Pump Control is designed to reduce fluid surges in pumping systems. It provides closed-loop acceleration and deceleration control of centrifugal pump motors without need for feedback devices.
Motor Speed
100

Pump Start

Run

Pump Stop

100

Smart Motor Braking

SMB Smart Motor Braking


SMB Smart Motor Braking stops a motor quickly for improved operation cycle times and increased productivity. Braking control with automatic zero speed shutoff is fully integrated into the controllers compact design.

Motor Speed Coast to Rest

Start

Run

Stop

Braking
100

Slow Speed Motor Speed


7% or 15%

Accu-Stop Position Control


Accu-Stop position control provides rapid braking to a slow speed and then braking to a stop. This option facilitates cost-effective general positioning control.

Slow Speed Slow Speed Braking/Coast

Slow Speed Start

Start

Run

Accu-Stop

100 7% or 15%

Slow Speed w/Braking


Braking Coast to Rest

Motor Speed

Slow Speed with Braking combines the benefits of SMB Smart Motor Braking and Preset Slow Speed for applications requiring slow setup speeds and braking to a full stop.

Slow Speed

Start

Run

Stop

Additional Products Available Selection Guide Chart


STC Starting Torque Controller SMC-2 Smart Motor Controller SMC PLUS Smart Motor Controller SMC Dialog Plus Controller SMC-3 Controller SMC-Delta Controller

150-SG001A-EN-P

150-SG006B-EN-P

10

Bulletin 150

Smart Motor Controller SMC-Flex


Overview/Modes of Operation Bulletin 150 SMC-Flex Smart Motor Controller
The SMC-Flex controller provides microprocessor controlled starting for standard 3-phase squirrel-cage induction or Star-Delta (6-lead) motors. Seven standard modes of operation are available within a single controller: Soft Start Features Current Limit Start SCR Bypass Dual Ramp Motor Protection Full Voltage Metering Linear Speed Acceleration DPI Communication Preset Slow Speed LCD Display Soft Stop Keypad Programming Options Four Programmable Auxiliary Contacts Pump Control Braking Control The SMC-Flex controller is available for motors rated 108480 A; 200480V AC, or 200600V AC, 50 and 60 Hz. In addition to motors, the SMC-Flex controller can be used to control resistive loads.

Table of Contents
Description of Starting and Stopping Options . . . . . . . . 13 Features. . . . . . . . . . . . . . . . 14 Cat. No. Explanation. . . . . . 15 Product Selection . . . . . . . . 16 Options . . . . . . . . . . . . . . . . 19 Accessories . . . . . . . . . . . . 20 Specifications . . . . . . . . . . . 21 Approx. Dimensions. . . . . . 24

Standards Compliance
UL 508 CSA C22.2 No. 14 EN/IEC 60947-4-2 cULus Listed (Open Type) (File No. E96956) CE Marked (Open Type) per EMC Directive and Low Voltage Directive

Modes of Operation
The SMC-Flex controller provides the following modes of operation as Standard:

Soft Start
This method covers the most general applications. The motor is given an initial torque setting, which is user adjustable from 090% of locked-rotor torque. From the initial torque level, the output voltage to the motor is steplessly increased during the acceleration ramp time, which is user adjustable from 030 seconds. If, during the voltage ramp operation, the SMC-Flex controller senses that the motor has reached an up-to-speed condition, the output voltage will automatically switch to full voltage, and transition over the SCR Bypass contactors. Note: Kickstart is available with this mode.
Percent Voltage 100%

Initial Torque

Start Time (seconds)

Run

Percent Voltage 100%

Kickstart

Selectable Kickstart
The kickstart feature provides a boost at startup to break away loads that may require a pulse of high torque to get started. It is intended to provide a current pulse, user adjustable 090% locked-rotor torque for a selected period of time, 0.02.0 seconds.

Initial Torque

Start Time (seconds)

Run

600%

Current Limit Start


This method provides current limit start and is used when it is necessary to limit the maximum starting current. The starting current is user adjustable from 50600% of full-load amperes. The current limit stating time is user adjustable from 030 seconds. Note: Kickstart is available with this mode.
Percent Full Load Current

50%

Start Time (seconds)

Dual Ramp Start


This starting method is useful on applications with varying loads, starting torque, and start time requirements. Dual Ramp Start offers the user the ability to select between two separate Soft Start profiles with separately adjustable ramp times and initial torque settings. The acceleration ramp times can be programmed from 030 seconds. The initial torque values can be programmed from 090% of locked-rotor torque. Note: Dual Ramp is only available with the standard controller. Note: Kickstart is available with this mode.

Percent Voltage Ramp #2 100%

Initial Torque #2 Ramp #1 Initial Torque #1

Start #1 Start #2 Time (seconds)

Run #1 Run #2

11

Bulletin 150

Smart Motor Controller SMC-Flex


Modes of Operation, Continued

100%

Full Voltage Start


This method is used in applications requiring across-the-line starting. The SMC-Flex controller performs like a solid-state contactor. Full inrush current and locked-rotor torque are realized. The SMC-Flex may be programmed to provide full voltage start in which the output voltage to the motor reaches full voltage in second.
Percent Voltage

Time (seconds)

Percent Speed 100%

Linear Speed Acceleration


With this type of acceleration mode, a closed-loop feedback system maintains the motor acceleration at a constant rate. The required feedback signal is provided by a DC tachometer coupled to the motor (tachometer supplied separately). Note: Kickstart is available with this mode.
Start Run Time (seconds) Stop

100%

Preset Slow Speed


This method can be used on applications that require a slow speed for positioning material. The Preset Slow Speed can be set for either Low, 7% of base speed, or High, 15% of base speed. Reversing is also possible through programming. Speeds provided during reverse operation are Low, 10% of base speed, or High, 20% of base speed.

Motor Speed Forward 15% - High 7% - Low Time (seconds) 10% - Low 20% - High Reverse

Start

Run

Soft Stop
The Soft Stop option can be used in applications requiring an extended coast-to-rest. The voltage ramp down time is use adjustable from 0120 seconds. The Soft Stop time is adjusted independently from the start time. The load will stop when the voltage drops to a point where the load torque is greater than the motor torque.
Not intended to be used as an emergency stop. Refer to the applicable standards for emergency stop requirments.

Percent Voltage Selectable Kickstart 100% Coast-to-rest Soft Stop

Initial Torque

Start

Run Time (seconds)

Soft Stop

Product Selection Page 16 Options Page 19 Accessories Page 20 Specifications Page 21 Approximate Dimensions Page 24

12

Bulletin 150

Smart Motor Controller SMC-Flex


Options Options
The following options are available in the SMC-Flex controller: Pump Control Braking Control

Pump Control

Start and Stop


This option is used to reduce surges during the starting and stopping of a centrifugal pump by smoothly accelerating and decelerating the motor. The microprocessor analyzes the motor variables and generates commands which control the motor and reduce the possibility of surges occurring in the system. The starting time is programmable from 030 seconds and the stopping time is programmable from 0120 seconds.

100%

Motor Speed

Pump Start

Run Time (seconds)

Pump Stop

Braking Control
The following options are all available with the braking option controller. Different setup allows the user to provide the type of braking control required by the application.

SMB Smart Motor Braking


This option provides motor braking for applications that require the motor to stop faster than a coast to rest. Braking control, with automatic zero speed shut off, is fully integrated into the compact design of the SMC-Flex controller. This design facilitates a clean, straightforward installation and eliminates the requirement for additional hardware such as braking contactors, resistors, timers, and speed sensors. The microprocessor based braking system applies braking current to a standard squirrel-cage induction motor. The strength of the braking current is programmable from 150400% of full-load current.
100%
Smart Motor Braking

Motor Speed
Coast-to-rest

Start

Run Time (seconds)

Brake
Automatic Zero Speed Shut-off

Accu-Stop
This option is used in applications requiring controlled position stopping. During stopping, braking torque is applied to the motor until it reaches preset slow speed (7% or 15% of rated speed) and holds the motor at this speed until a stop command is given. Braking torque is then applied until the motor reaches zero speed. Braking current is programmable from 0400% of full-load current. Slow Speed Current is programmable from 0450% of full-load current. Slow speed can be programmed for either 7% (low) or 15% (high).

Slow Speed with Braking


Slow Speed with Braking is used on applications that require slow speed (in the forward direction) for positioning or alignment and also require braking control to stop. Slow speed adjustments are 7% (low) or 15% (high) of rated speed. Slow speed acceleration current is adjustable from 0450%. Slow speed running current is adjustable from 0450% of full-load current. Braking current is adjustable from 0400%.

Not intended to be used as an emergency stop. Refer to the applicable standards for emergency stop requirements.

13

Bulletin 150

Smart Motor Controller SMC-Flex


Description of Features Description of Features
Electronic Motor Overload Protection
The SMC-Flex controller incorporates, as standard, electronic motor overload protection. This overload protection is accomplished electronically with an I2t algorithm. When coordinated with the proper short circuit protection, overload protection is intended to protect the motor, motor controller, and power wiring against overheating caused by excessive overcurrent. The SMC-Flex controller meets applicable requirements as a motor overload protective device. The controllers overload protection is programmable, providing the user with flexibility. The overload trip class can be selected for class 10, 15, 20 or 30 protection. The trip current is programmed by entering the motor full-load current rating, service factor, and selecting the trip class. Thermal memory is included to accurately model motor operating temperature. Ambient insensitivity is inherent in the electronic design of the overload.

Excessive Starts Per Hour


The SMC-Flex controller allows the user to program the allowed number of starts per hour (up to 99). This helps eliminate motor stress caused by repeated starting during a short time period.

Metering
Power monitoring parameters include: 3-phase current 3-phase voltage Power in kW Power usage in kWH Power factor Motor thermal capacity usage Elapsed time Note: The motor thermal capacity usage allows the user to monitor the amount of overload thermal capacity usage before the SMC-Flex controllers built-in electronic overload trips.

Built-in DPI Communication Capabilities


A serial interface port is provided as standard, which allows connection to a Bulletin 20 Human Interface Module and a variety of Bulletin 20-COMM Communication Modules. This includes Allen-Bradley Remote I/O, DeviceNet, ControlNet, Ethernet, ProfiBUS, Interbus, and RS485-DF1.

Stall Protection and Jam Detection


Motors can experience locked-rotor currents and develop high torque levels in the event of a stall or a jam. These conditions can result in winding insulation breakdown or mechanical damage to the connected load. The SMC-Flex controller provides both stall protection and jam detection for enhanced motor and system protection. Stall protection allows the user to program a maximum stall protection delay time from 010 seconds. The stall protection delay time is in addition to the programmed start time and begins only after the start time has timed out. If the controller senses that the motor is stalled, it will shut down after the delay period has expired. Jam detection allows the user to determine the motor jam detection level as a percentage of the motors full-load current rating. To prevent nuisance tripping, a jam detection delay time, from 0.099 seconds, can be programmed. This allows the user to select the time delay required before the SMC-Flex controller will trip on a motor jam condition. The motor current must remain above the jam detection level during the delay time. Jam detection is active only after the motor has reached full speed.

LCD Display
The SMC-Flex controllers three-line 16-character backlit LCD display provides parameter identification using clear, informative text. Controller set up can be performed quickly and easily without the use of a reference manual. Parameters are arranged in an organized four-level menu structure for ease of programming and fast access to parameters.

Keypad Programming
Programming of parameters is accomplished through a five-button keypad on the front of the SMC-Flex controller. The five buttons include up and down arrows, an Enter button, a Select button, and an Escape button. The user needs only to enter the correct sequence of keystrokes for programming the SMC-Flex controller.

Underload Protection
Utilizing the underload protection of the SMC-Flex controller, motor operation can be halted if a drop in current is sensed. The SMC-Flex controller provides an adjustable underload trip setting from 099% of the programmed motor full-load current rating with an adjustable trip delay time of 099 seconds.

Auxiliary Contacts
Four programmable hard contacts are furnished as standard with the SMCFlex controller: Aux #1 N.O. (Normal/Up-to-Speed/External Bypass) Fault N.O./N.C. Alarm N.O./N.C. Aux #2 N.O./N.C. (Normal)

Undervoltage Protection
The SMC-Flex controllers undervoltage protection will halt motor operation if a drop in the incoming line voltage is detected. The undervoltage trip level is adjustable as a percentage of the programmed line voltage, from 099%. To eliminate nuisance trips, a programmable undervoltage trip delay time of 099 seconds can also be programmed. The line voltage must remain below the undervoltage trip level during the programmed delay time.

Ground Fault Input


The SMC-Flex can monitor for ground fault conditions. A Cat. No. 825-CBCT core balance current transformer is required for this function.

PTC Input
A motor PTC input can be monitored by the SMC-Flex. In the event of a fault, the SMC-Flex will shut down and indicate a PTC fault.

Overvoltage Protection
If a rise in the incoming line voltage is detected, the SMC-Flex controllers overvoltage protection will halt motor operation. The overvoltage trip level is adjustable as a percentage of the programmed line voltage, from 0199%. To eliminate nuisance trips, a programmable overvoltage trip delay time of 099 seconds can also be programmed. The line voltage must remain above the overvoltage trip level during the programmed delay time.

Voltage Unbalance Protection


Voltage unbalance is detected by monitoring the 3-phase supply voltage magnitudes in conjunction with the rotational relationship of the three phases. The controller will halt motor operation when the calculated voltage unbalance reaches the user-programmed trip level. The voltage unbalance trip level is programmable from 025% unbalance.

14

Bulletin 150

Smart Motor Controller SMC-Flex


Cat. No. Explanation Open and Non-Combination

150 F135 F B D
Bulletin Number 150 Solid-State Controller

B 8L
Options 8L Line-Mounted Protective Module 8M Load-Mounted Protective Module 8B Line- and Load-Mounted Protective Modules Load-side MOVs not available with Pump and Braking options. MOVs can be field installed for Open type units.

Controller Ratings F108 F135 F201 F251 F317 F361 F480 108 A, 6075 Hp @ 480V AC 135 A, 60100 Hp @ 480V AC 201 A, 75150 Hp @ 480V AC 251 A, 100200 Hp @ 480V AC 317 A, 125250 Hp @ 480V AC 361 A, 150300 Hp @ 480V AC 480 A, 200400 Hp @ 480V AC

Enclosure Type F NEMA Type 4/12 (IP65) N Open Control Voltage D 100240V AC

Options (Select Only One) B Pump Control D Braking Control

Input Line Voltage Open Type B 200480V AC, 3-phase, 50 and 60 Hz C 200600V AC, 3-phase, 50 and 60 Hz Non-Combination Enclosed Only H 200208V AC, 3-phase, 50 and 60 Hz A 230V AC, 3-phase, 50 and 60 Hz B 200480V AC, 3-phase, 50 and 60 Hz C 200600V AC, 3-phase, 50 and 60 Hz

Combination

152H F480
Bulletin Number 152H Solid-State Controller with Fusible Disconnect 153H Solid-State Controller with Circuit Breaker

BD B 52 8B
Options 8L Line-Mounted Protective Module 8M Load-Mounted Protective Module 8B Line- and Load-Mounted Protective Modules Load-side MOVs not available with Pump and Braking options.. Horsepower Cat. No. 39 40 41 42 43 44 45 46 47 48 49 50 51 Hp Rating 5 7.5 10 15 20 25 30 40 50 60 75 100 125 Cat. No. 52 54 56 57 58 59 60 61 62 63 65 67 Hp Rating 150 200 250 300 350 400 450 500 600 700 800 1000

Controller Ratings F108 F135 F201 F251 F317 F361 F480 108 A, 6075 Hp @ 480V AC 135 A, 60100 Hp @ 480V AC 201 A, 75150 Hp @ 480V AC 251 A, 100200 Hp @ 480V AC 317 A, 125250 Hp @ 480V AC 361 A, 150300 Hp @ 480V AC 480 A, 200400 Hp @ 480V AC

Control Options B Pump Control D Braking Control

Line Voltage HD 200208V AC, 3-phase, 50 and 60 Hz AD 230V AC, 3-phase, 50 and 60 Hz BD 400480V AC, 3-phase, 50 and 60 Hz CD 500600V AC, 3-phase, 50 and 60 Hz

Enclosure Type F NEMA Type 4/12 (IP65)

Product Selection Page 16 Options Page 19 Accessories Page 20 Specifications Page 21 Approximate Dimensions Page 24

15

Bulletin 150

Smart Motor Controller SMC-Flex


Product Selection Open Type and Non-Combination Enclosed (IP65, Type 4/12) Line-Connected Controllers
Enclosures other than those listed are available; consult your local Allen-Bradley distributor.
Open Type Line-Connected Motors 100240V AC 50/60 Hz Control Cat. No. 150-F108NBD 150-F135NBD 150-F201NBD 150-F251NBD 150-F317NBD 150-F361NBD 150-F480NBD 150-F108NBD 150-F135NBD 150-F201NBD 150-F251NBD 150-F317NBD 150-F361NBD 150-F480NBD 150-F108NBD 150-F135NBD 150-F201NBD 150-F251NBD 150-F317NBD 150-F361NBD 150-F480NBD 150-F108NCD 150-F135NCD 150-F201NCD 150-F251NCD 150-F317NCD 150-F361NCD 150-F480NCD IP65 (Type 4/12) Enclosed Non-Combination Controllers Cat. No. 150-F108FHD 150-F135FHD 150-F201FHD 150-F251FHD 150-F317FHD 150-F361FHD 150-F480FHD 150-F108FAD 150-F135FAD 150-F201FAD 150-F251FAD 150-F317FAD 150-F361FAD 150-F480FAD 150-F108FBD 150-F135FBD 150-F201FBD 150-F251FBD 150-F317FBD 150-F361FBD 150-F480FBD 150-F108FCD 150-F135FCD 150-F201FCD 150-F251FCD 150-F317FCD 150-F361FCD 150-F480FCD

Rated Voltage [V AC]

Current Rating (A) 108 135 201 251 317 361 480 108 135 201 251 317 361 480 108 135 201 251 317 361 480 108 135 201 251 317 361 480

kW

Hp , 60 Hz 30 40 60 75 100 125 150 40 50 75 100 125 150 200 75 100 150 200 250 300 400 100 125 200 250 300 350 500

208

230

480

600

30 37 55 75 90 110 132 55 75 110 132 160 200 250 75 90 132 160 200 250 315

Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 20 for terminal lug kits. Hp ratings at motor terminal voltages for 200, 230, 480, and 600 line volts, respectively. These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string.

16

Bulletin 150

Smart Motor Controller SMC-Flex


Product Selection, Continued Open Type Delta-Connected Controllers
Rated Voltage [V AC] Current Rating (A) 108 135 201 251 317 361 480 108 135 201 251 317 361 480 108 135 201 251 317 361 480 108 135 201 251 317 361 480 kW 55 75 110 132 160 200 250 90 132 160 250 315 355 450 132 160 250 315 400 450 560 Hp , 60 Hz 50 75 100 150 150 200 300 60 75 125 150 200 250 350 125 150 250 350 450 500 600 150 200 350 400 500 600 800 100240V AC 50/60 Hz Control Cat. No. 150-F108NBD 150-F135NBD 150-F201NBD 150-F251NBD 150-F317NBD 150-F361NBD 150-F480NBD 150-F108NBD 150-F135NBD 150-F201NBD 150-F251NBD 150-F317NBD 150-F361NBD 150-F480NBD 150-F108NBD 150-F135NBD 150-F201NBD 150-F251NBD 150-F317NBD 150-F361NBD 150-F480NBD 150-F108NCD 150-F135NCD 150-F201NCD 150-F251NCD 150-F317NCD 150-F361NCD 150-F480NCD

208

230

480

600

Controllers rated 108 A and greater are not equipped with line and load terminal lugs. See page 20 for terminal lug kits. Hp ratings at motor terminal voltages for 200, 230, 480, and 600 line volts, respectively.

Options Page 19 Accessories Page 20 Specifications Page 21 Approximate Dimensions Page 24

17

Bulletin 150

Smart Motor Controller SMC-Flex


Product Selection, Continued Combination Controllers IP65 (Type 4/12) Enclosed with Fusible Disconnect or Circuit Breaker
These controllers include line and load terminations. Enclosures other than those listed are available; consult your local Allen-Bradley distributor.
Rated Voltage [V AC] Controller Current Rating (A) 108 108 108 135 201 201 251 317 361 480 108 108 108 135 201 201 251 317 361 480 108 108 108 135 201 201 251 317 361 480 480 108 108 135 201 201 251 317 361 480 480 480 IP65 (Type 4/12) Enclosed Combination IP65 (Type 4/12) Enclosed Combination Controllers with Fusible Disconnect Controllers with Circuit Breaker Cat. No. Cat. No. 152H-F108FHD-43 153H-F108FHD-43 152H-F108FHD-44 153H-F108FHD-44 152H-F108FHD-45 153H-F108FHD-45 152H-F135FHD-46 153H-F135FHD-46 152H-F201FHD-47 153H-F201FHD-47 152H-F201FHD-48 153H-F201FHD-48 152H-F251FHD-49 153H-F251FHD-49 152H-F317FHD-50 153H-F317FHD-50 152H-F361FHD-51 153H-F361FHD-51 152H-F480FHD-52 153H-F480FHD-52 152H-F108FAD-44 153H-F108FAD-44 152H-F108FAD-45 153H-F108FAD-45 152H-F108FAD-46 153H-F108FAD-46 152H-F135FAD-47 153H-F135FAD-47 152H-F201FAD-48 153H-F201FAD-48 152H-F201FAD-49 153H-F201FAD-49 152H-F251FAD-50 153H-F251FAD-50 152H-F317FAD-51 153H-F317FAD-51 152H-F361FAD-52 153H-F361FAD-52 152H-F480FAD-54 153H-F480FAD-54 152H-F108FBD-47 153H-F108FBD-47 152H-F108FBD-48 153H-F108FBD-48 152H-F108FBD-49 153H-F108FBD-49 152H-F135FBD-50 153H-F135FBD-50 152H-F201FBD-51 153H-F201FBD-51 152H-F201FBD-52 153H-F201FBD-52 152H-F251FBD-54 153H-F251FBD-54 152H-F317FBD-56 153H-F317FBD-56 152H-F361FBD-57 153H-F361FBD-57 152H-F480FBD-58 153H-F480FBD-58 152H-F480FBD-59 153H-F480FBD-59 152H-F108FCD-49 153H-F108FCD-49 152H-F108FCD-50 153H-F108FCD-50 152H-F135FCD-51 153H-F135FCD-51 152H-F201FCD-52 153H-F201FCD-52 152H-F201FCD-54 153H-F201FCD-54 152H-F251FCD-56 153H-F251FCD-56 152H-F317FCD-57 153H-F317FCD-57 152H-F361FCD-58 153H-F361FCD-58 152H-F480FCD-59 153H-F480FCD-59 152H-F480FCD-60 153H-F480FCD-60 152H-F480FCD-61 153H-F480FCD-61

Hp, 60 Hz 20 25 30 40 50 60 75 100 125 150 25 30 40 50 60 75 100 125 150 200 50 60 75 100 125 150 200 250 300 350 400 75 100 125 150 200 250 300 350 400 450 500

208

230

480

600

These controllers require a separate 100240V, 50/60 Hz single-phase control source. To add a control circuit transformer to the enclosure, add the appropriate option code to the catalog string. The nominal current rating for the combination package may differ from the controller, based on the horsepower. Consult your local Allen-Bradley distributor.

Options Page 19 Accessories Page 20 Specifications Page 21 Approximate Dimensions Page 24

18

Bulletin 150

Smart Motor Controller SMC-Flex


Options Options
Option Description Provides smooth motor acceleration and deceleration, reducing surges caused by the starting and stopping of centrifugal pumps. Starting time is adjustable from 030 seconds, and stopping time is adjustable from 0120 seconds. Provides Smart Motor Braking (SMB), Accu-Stop, and Slow Speed with Braking. Cat. No. Modification

Enclosed Options
Option Description Start-Stop Push Button Start-Stop Push Button with H-O-A Selector Switch Soft Stop Push Button Pump Stop Push Button Slow Speed Push Button Brake Push Button Accu-Stop/Slow Speed Push Button Emergency Stop Fault Reset Hand-Off-Auto Selector Switch SMC-Off-Bypass Selector Switch Transformer Pilot Lights (Red Lens Easy Ship Program) Push-to-Test Pilot Lights Control Circuit Transformer (fused primary and secondary) Additional 100 VA Control Circuit Transformer (fused primary and secondary) 108480 A, 480V Line Side Protective Module 108480 A, 600V Line Side Protective Module 108480 A, 480V Load Side Protective Module 108480 A, 600V Load Side Protective Module 108480 A, 480V Both Line and Load Side Protective Modules 108480 A, 600V Both Line and Load Side Protective Modules Door-mounted programmer only (Type 4/12) Cat. No. Modification -1 -1F -1XA -1XB -1XC -1XD -1XE -1E -FR -3 -3B -4_ -5_ -6P -6PX -8L -8M

Pump Control

B Push Buttons D

Braking Control

Selector Switch Pilot Lights Control Circuit Transformer

Protective Modules

-8B

Human Interface Module

-HC3 -20R -20S -20D -20E -20C -20P

Remote I/O RS-485 Communica- DeviceNet Network tion Module Enhanced Devicenet Control Net ProfiBUS

Add the designated letter to the end of the cat. no. Example: To add the Pump Control option: Cat. No. 150-F361NBDB or Cat. No. 152H-F361FBDB-51. Option push buttons are available only when the corresponding option module is selected. Example: Cat. No. 150-F108FBD-1XA. Specify pilot light lens color. Options: Amber, Blue, Clear, Green, Red, and White. Example: -4R for a red lens.

19

Bulletin 150

Smart Motor Controller SMC-Flex


Accessories Field-Installed Protective Modules
Current Rating (A) Description Field Modification Cat. No. 150-F84L

480V Protective Module 108480 600V Protective Module

150-F86L

The same protective module mounts on the line or load side of the SMC-Flex. For applications requiring both line and load side protection, two protective modules must be ordered.

Terminal Lug Kits (108480 A)


Current Rating (A) Conductor Range Total No. of Line Controller Terminal Lugs Possible Each Side Line Side Load Side 3 #64/0 AWG 201251 6 6 3 3 199-LF1 Pkg. Qty. Cat. No.

108135

317480

#4500MCM AWG

199-LG1

IEC Terminal Covers


Description IEC line or load terminal covers for 108251 A devices. Dead front protection Package Quantity 1 Field Modification Cat. No. 150-TC2

IEC line and load terminal covers for 317480 A devices. Dead front protection

150-TC3

Description LCD Programmer only HIM, Programmer only LCD Human Interface Modules IP66 (Type 4/12) Door Mount Bezel Kit

Cat. No. 20-HIM-A5 20-HIM-A3 20-HIM-C3

1 m Cable Description Remote I/O RS-485/DF1 ProfiBUS Communication Modules ControlNet DeviceNet Ethernet/IP DriveTools Programming Software Personal Computer Bulletin 150 SMC-Flex For Use with

20-HIM-H10 IP30 (Type 1) Cat. No. 20-COMM-R 20-COMM-S 20-COMM-P 20-COMM-C 20-COMM-D 20-COMM-E 1300-DTLS

20

Bulletin 150

Smart Motor Controller SMC-Flex


Specifications/Wiring Diagram
Functional Design Specifications
Power Wiring Standard squirrel-cage induction motor or a Star-Delta, six-lead motor. Installation Control Wiring 2- and 3-wire control for a wide variety of applications. Keypad Front keypad and backlit LCD display. Setup Parameter values can be downloaded to the SMC-Flex Controller with DriveTools programming Software software and the Cat. No. 20-COMM DPI communication module. Communications One DPI provided for connection to optional human interface and communication modules. Soft Start Current Limit Start Dual Ramp Starting Modes Full Voltage Linear Speed Acceleration Preset Slow Speed Soft Stop Power loss, line fault, voltage unbalance, excessive starts/hour, phase reversal, undervoltage, Protection and Diagnostics overvoltage, controller temp, stall, jam, open gate, overload, underload, communication fault. Metering Amps, volts, kW, kWH, elapsed time, power factor, motor thermal capacity usage. Alarm Contact Overload, underload, undervoltage, overvoltage, unbalance, jam, stall, and ground fault Status Indication Stopped, starting, stopping, at speed, alarm, and fault. Contact programmable as normal/up-to-speed/external bypass; one programmable for fault, one Auxiliary Contacts programmable for alarm, and one programmable for N.O./N.C. normal. Helps reduce fluid surges in centrifugal pumping systems during starting and stopping period. Starting Pump Control time is adjustable from 030 seconds. Stopping time is adjustable from 0120 seconds. SMB Smart Provides motor braking without additional equipment for applications that require the motor to stop Motor Braking quickly. Braking current is adjustable from 0400% of the motors full-load current rating. Provides controlled position stopping. During stopping, braking torque is applied to the motor until it reaches preset slow speed (7% or 15% of rated speed) and holds the motor at this speed until a stop Braking Control Accu-Stop command is given. Braking torque is then applied until the motor reaches zero speed. Braking current is programmable from 0450% of full-load current. Slow Speed with Used on applications that require slow speed (in the forward direction) for positioning or alignment and Braking also require braking control to stop.

Standard Features

Optional Features

Wiring Diagram Line Controller


L1/1 3-Phase L2/3 Input Power L3/5 T3/6 T2/4 M T1/2

SMC-Flex Controller

Branch Protection

Fan

Stop
Option Input #1

Start

Option Input #2

11 12 13 14 15 16 17 18 19 20 21 22

SMC-Flex Control Terminals

Aux #1

Not Used Internal Auxillary Contacts

Normal/Up-to-Speed/External Bypass 23 24 25 26 27 28 29 30 31 32 33 34

}
TACH Input

}
Aux #2 Normal

}
PTC Input

Ground Fault

Fault Contact

Alarm Contact

As Required

21

Bulletin 150

Smart Motor Controller SMC-Flex


Specifications, Continued
Electrical Ratings UL/CSA/NEMA Rated Operation Voltage Rated Insulation Voltage Rated Impulse Voltage Dielectric Withstand Power Circuit Repetitive Peak Inverse Voltage Rating Operating Frequency Utilization Category Protection Against Electrical Shock DV/DT Protection Transient Protection SCPD Performance SCPD List 108 135 201 251 317 361 480 IEC 200480V AC 200415V 200600V AC (15%, +10%) 200500V N/A 500V N/A 6000V 2200V AC 2500V 200480V AC: 1400V 200415V: 1400V 200600V AC: 1600V 200500V: 1600V 50/60 Hz 50/60 Hz MG 1 AC-53B N/A IP00 (open device)/Optional IP20 RC Snubber Network Metal Oxide Varistors: 220 Joules Type 1 Maximum Fuse or Circuit Breaker (A): 350 500 600 700 1000 1200 1600 100240V AC 100240V N/A 240V N/A 3000V 1600V AC 2000V 50/60 Hz 50/60 Hz N/A IP20 75 VA 50 VA 1G 2.5 G 167 176 200 218 225 245 290 Electromagnetic relay 1 N.O. AC 3 A @ 120V AC, 1.5 A @ 240V AC 5A 3600/360 AC-15 040 C (32104 F) (open) 040 C (32104 F) (enclosed) 20+75 C 2000 m (6560 ft) 595% (non-condensing) 2

Short Circuit Protection Device Operational Current Rating (A)

Control Circuit

Rated Operational Voltage Rated Insulation Voltage Rated Impulse Voltage Dielectric Withstand Operating Frequency Protection Against Electric Shock Control Module Heatsink Fan(s) (A) Operational Non-Operational 108 135 201 251 317 361 480

Power Requirements

Vibration

Steady State Heat Dissipation (Watts)

Controller Rating (A)

Auxiliary Contacts 19/20 (Normal/Up-toSpeed/External Bypass) 29/30 (Fault) 31/32 (Alarm) 33/34 (Normal)

Type of Control Circuit Number of Contacts Type of Contacts Type of Current Rated Operational Current Conventional Thermal Current Ith Make/Break VA Utilization Category Environmental

Operating Temperature Range Storage and Transportation Temperature Range Altitude Humidity Pollution Degree

For devices rated 108480 A, heatsink fans can be powered by either 110/120V AC or 220/240V AC.

22

Bulletin 150

Smart Motor Controller SMC-Flex


Specifications, Continued
Mechanical Resistance to Vibration Resistance to Shock Operational Non-Operational Operational Non-Operational Power Poles Construction Control Modules Metal Parts Terminals Power Terminals Power Terminal Markings Control Terminals Other EMC Emission Levels Conducted Radio Frequency Emissions Radiated Emissions Electrostatic Discharge Radio Frequency Electromagnetic Field Fast Transient Surge Transient 108 135 201 251 317 361 480 Line 54108 68135 100201 125251 158317 180361 240480 Class A Class A 8 kV Air Discharge Per EN 60947-4-2 Per EN 60947-4-2 Per EN 60947-4-2 Delta 94187 117234 174348 218435 275549 313625 415831 108251 A 317480 A Heatsink hockey puck thyristor modular design 1.0 G Peak, 0.15 mm (0.006 in.) Displacement 2.5 G, 0.38 mm (0.015 in.) Displacement 5.5 G 25 G 108480 A Thermoset and Thermoplastic Moldings Plated Brass, Copper, or Painted Steel Two M10 x 1.5 diameter holes per power pole Two M12 x 1.75 diameter holes per power pole NEMA, CENELEC EN50 012 M 3.5 x 0.6 Pozidriv screw with self-lifting clamp plate

EMC Immunity Levels

Current Range Overload Characteristics

Trip Classes Trip Current Rating Number of Poles Approvals Open Type Controllers

10, 15, 20, and 30 120% of Motor FLC 3 CE Marked Per Low Voltage Directive 73/23/EEC, 93/68/EEC UL Listed (File No. E96956)

23

Bulletin 150

Smart Motor Controller SMC-Flex


Specifications, Continued/ Approximate Dimensions and Shipping Weights Specifications, Continued
Maximum Available Fuse and Fault Current (Open Type)
Current Rating (A) 108 135 201 251 317 361 480 Fuse/Type 1600/Class L 1600/Class L 1600/Class L 1600/Class L 1600/Class L 1600/Class L 1600/Class L Fault Current @ 600V 30000 30000 30000 30000 42000 42000 42000

Approximate Dimensions and Shipping Weights


Open Type Controllers
Dimensions are in millimeters (inches). Dimensions are not intended for manufacturing purposes.
Controller Rating (A) 108251 317480 Height 560 (22.05) 600 (23.62) Width 225 (8.86) 290 (11.42) Depth 253.8 (9.99) 276.5 (10.89) Weight 30.4 kg (67 lbs). 45.8 kg (101 lbs)

Maximum Available Circuit Breaker and Fault Current (Open Type)


Current Rating (A) 108 135 201 251 317 361 480 Inverse Time Circuit Breaker 1200 1200 1200 1200 1200 1200 1200 Fault Current @ 600V 30000 30000 30000 30000 30000 30000 30000

Enclosed Type Line-Connected Controllers


Factory-installed options may affect enclosure size requirements. Exact dimensions can be obtained after order entry. Please consult your local Allen-Bradley distributor.
A C

Controller Rating (A)

IP65 (Type 4/12) B Height A Width C Depth Non-Combination Controller 108 762 (30) 610 (24) 305 (12) 135 762 (30) 610 (24) 305 (12) 201 914 (36) 762 (30) 305 (12) 251 914 (36) 762 (30) 305 (12) 317 1220 (48) 914 (36) 356 (14) 361 1524 (60) 940 (37) 356 (14) 480 1524 (60) 940 (37) 356 (14) Combination Controllers with Fusible Disconnect Combination Controllers with Circuit Breaker

Consult NEC Handbook for proper fuse sizing guidelines. Consult your local Allen-Bradley distributor for the full range of enclosure sizes

Trademark List Accu-Stop, SMC, SMC-2, SMC-Flex, SMC PLUS, SMC Dialog Plus, SMB, and STC are trademarks of Rockwell Automation. DeviceNet and the DeviceNet logo are trademarks of the Open Device Vendors Association (ODVA).