Technical Data
Product Description
The PowerFlex Digital DC drive provides digital control for precise speed and current regulation, easy programmability, extensive diagnostics, non-regenerative and regenerative operation, and is easily interfaced for integration into larger drive systems. PowerFlex DC drives are well suited to a variety of applications including extruding operations, finishing, drawing, and coating processes, applications exhibiting shock loads, high inertia, rapid accel/decel or continuous regeneration, and is an excellent choice for existing DC machinery upgrades. The compact design of this drive includes a fully contained power module and a common control structure for the entire range of horsepower. And, to make connectivity even easier, the PowerFlex DC drive provides a standard DPI interface that is compatible with all PowerFlex DPI communication products. The standard hardware offering consists of an open type enclosure, armature converter, regulated field converter for field weakening or economy applications, an advanced regulator with integrated DPI functionality, DC tachometer and encoder capability.
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Page Standard Drives Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Catalog Number Explanation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Standard Drives Product Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 User Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Installation Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Parameter List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 PowerFlex DC Configured Drives . . . . . . . . . . . . . . . . . . . . . . . . . . 72 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77 Watts Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 Reference Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
PC-based Configuration tools include: - DriveExplorer and DriveExplorer Lite (v5.02 or higher). A simple and flexible On-line tool for monitoring and configuring while connected to a drive. - DriveTools SP (v4.01 or higher is required with a PowerFlex DC drive specific software patch. The patch can be downloaded from http://www.ab.com/support/abdrives/webupdate/). A suite of software tools which provide an intuitive means for programming, troubleshooting and maintaining Allen-Bradley drives, including the PowerFlex DC Drive Start-Up Wizard. Internal Communications allow you to integrate the drive into the manufacturing process. Status indicators for all internal communication options are visible on the cover for easy setup and monitoring of drive communications. You can easily manage information from shop floor to top floor and seamlessly integrate a complete system as you control, configure and collect data. 4
Publication 20P-TD001D-EN-P - January 2010
Description
(Unconnected Messaging) permits other network devices (e.g. PanelView) to communicate directly to a drive without routing the communication through the network scanner. Adapter Routing - Plug PC into one drive and talk to all other Allen-Bradley drives on same network, without being routed through network scanner. Access to 100% of all parameters over the network. AutoBaud capability makes initial connections less problematic. Change of State significantly reduces network traffic by configuring control messages to be sent only upon customer defined states. Very flexible configuration for each node (Example: reference must change by more than 5%). Peer Control provides master-slave type control between drives, where one or more slave drives (consumers) can run based on the status of a master drive (producer), which can also significantly reduce network traffic. ADR (Automatic Device Replacement) saves significant time and effort when replacing a drive, by allowing the scanner to be configured to automatically detect a new drive and download the required parameter settings. Flexible Fault Configuration - Adapters can be programmed to take fault based actions as ramp to stop, coast-to-stop and hold last state, as well as send user configurable logic control and speed reference values. In addition, different actions can be taken based on whether the network experienced a serious problem (broken cable etc.) versus network idle condition (PLC set to Program).
20P
a
4
b
1
c
A
d
D
e
4P1
f
R
g
A
h
0
i
N
j
N
k
N
l
a
Drive Code 20P Type PowerFlex DC 7P0 9P0 1.5 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 Code Hp
f1
230V, 60 Hz Input Armature Amps 7 9 12 20 29 38 55 73 93 110 146 180 218 265 360 434 521 700 875 1050 Frame A A A A A A A A A A B B B B B B C C D D Field Amps 10 10 10 10 10 10 10 14 14 14 20 20 20 20 20 20 20 20 40 40 Code 452 Hp 400 500 600 700 800 900 1000 1100 1250 Code 067 101 135 270 405 540 675 810 1K0 1K2 1K3 1K6 Hp 50 75 100 200 300 400 500 600 800 900 1000 1250
f3
575V, 60 Hz Input Armature Amps 67.5 101.3 135 270 405 504 675 810 1080 1215 1350 1668 Frame B B B B B C C D D D D D Field Amps 20 20 20 20 20 20 20 40 40 40 40 40
b
Motor Operation Code 2 4 Type Two Quadrant Operation Four Quadrant Operation
c
Input Type Code 1 Type 6 Pulse
Frame B & C drives not yet available at this input rating. Consult with factory for availability.
d
Enclosure Code A Enclosure Rating IP20, NEMA/UL Type Open Conform. Coat No
f4
690V, 60 Hz Input Armature Amps 452 565 678 791 904 1017 1130 1243 1413 Frame C C D D D D D D D Field Amps 20 20 40 40 40 40 70 70 70
f2 e
Input Voltage Code B D E Voltage 230V AC 460V AC 600V AC 460V, 60 Hz Input Code 4P1 6P0 010 014 019 027 035 045 052 073 086 100 129 167 207 250 330 412 495 667 830 996 1K1 1K3 1K4 Hp 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 400 500 600 700 800 900 Armature Amps 4.1 6 10 14 19 27 35 45 52 73 86 100 129 167 207 250 330 412 495 667 830 996 1162 1328 1494 Frame A A A A A A A A A A A A A B B B B B C C D D D D D Field Amps 10 10 10 10 10 10 10 10 10 14 14 14 14 20 20 20 20 20 20 20 40 40 70 70 70
1400 1582 D 70 1K5 Frame C drives not yet available at this input rating. Consult with factory for availability.
20P
a
4
b
1
c
A
d
D
e
4P1
f
R
g
A
h
0
i
N
j
N
k
N
l
g
Field Supply Code R Type Single-Phase Regulated Code 0
i
HIM Operator Interface Blank Cover Code N
k
Communication Options Description None
h
Packaging/Documentation Code A Shipping Carton Yes User Manual Yes
Standard - for additional selections, refer to the PowerFlex Digital DC Drive Technical Data, publication 20P-TD001. . .
Standard - for additional selections, refer to the PowerFlex Digital DC Drive Technical Data, publication 20P-TD001. . .
j
I/O Options Code A B C N Control I/O Expansion Card (4 Additional 24V dc Digital Inputs & Outputs, 2 Analog Outputs) 115V ac Conversion Card (8 Digital Inputs & Outputs) I/O Expansion Card + 115V ac Conversion None (8 - 24V dc Digital Inputs & Outputs, 3 Analog Outputs and 2 Analog Inputs are Standard) Code N
l
Cabinet Options Type None
All I/O Options are purchased separately and are user installed.
Non-Regenerative Drives(1) Cat. No. 20P21AB360RA0NNN 20P21AB434RA0NNN 20P21AB521RA0NNN 20P21AB700RA0NNN 20P21AB875RA0NNN 20P21AB1K0RA0NNN
Regenerative Drives Cat. No. 20P41AB360RA0NNN 20P41AB434RA0NNN 20P41AB521RA0NNN 20P41AB700RA0NNN 20P41AB875RA0NNN 20P41AB1K0RA0NNN
Frame Size B B C C D D
Handheld/Local (Drive Mount) Description No HIM (Blank Plate) LCD Display, Full Numeric Keypad LCD Display, Programmer Only Wireless Interface Module Cat. No. 20-HIM-A0 20-HIM-A3 20-HIM-A5 20-WIM-N1
Remote (Panel Mount) IP66, NEMA/UL Type 4x/12 Cat. No. 20-HIM-C3S 20-HIM-C5S 20-WIM-N4S
For indoor use only. Includes a 1202-C30 interface cable (3 meters) for connection to drive.
Includes a 1202-C30 interface cable (3 meters) for connection to drive. Required only when HIM is used as handheld or remote. Required in addition to 20-HIM-H10 for distances up to a total maximum of 10 Meters (32.8 Feet).
PC Programming Software
Cat. No. 20-COMM-B 20-COMM-C 20-COMM-D 20-COMM-E 20-COMM-H 20-COMM-I 20-COMM-P 20-COMM-Q 20-COMM-R 20-COMM-S 20-XCOMMAC-PS1 20-XCOMMDC-BASE 20-XCOMMIO-OPT1 1769-SM1 1203-SNM 1203-SSS 1203-USB DriveTools SP Software DriveExplorer Software (Lite/Full) Pocket DriveExplorer Software Set-up wizards are available for use with DriveTools SP and DriveExplorer (Lite/Full) only. DriveExplorer Lite is available for free download at: http://www.ab.com/drives/driveexplorer/free_download.html See publication 9303-PL002 for ordering/pricing information. Description
ControlNet Communication Adapter (Coax) DeviceNet Communication Adapter EtherNet/IP Communication Adapter HVAC Communication Adapter Interbus Communication Adapter PROFIBUS DP Communication Adapter ControlNet Communication Adapter (Fiber) Remote I/O Communication Adapter RS485 DF1 Communication Adapter External Communications Kit Power Supply DPI External Communications Kit External DPI I/O Option Board Compact I/O to DPI/SCANport Module Serial Null Modem Adapter Smart Self-powered Serial Converter (RS232) includes 1203-SFC and 1202-C10 Cables Universal Serial Bus (USB) Converter includes 2m USB, 20-HIM-H10 & 22-HIM-H10 Cables
For use only with External DPI Communications Kits 20-XCOMM-DCBASE. Only ModBus RTU can be used with Vector Control.
Isolation Transformers
Isolation Transformers are available for installations that have specific types of AC supply configurations or require drive protection due to AC line disturbances.
Three Phase Primary Voltage Three Phase Secondary Voltage 230V AC 460V AC kVA kW (HP) Voltage Catalog Number Catalog Number 5 1.2 - 2.2 230 1321-3TW005-AA 1321-3TW005-AB (1.5 - 3) 460 1321-3TW005-BA 1321-3TW005-BB 575 1321-3TW005-CA 1321-3TW005-CB 7.5 3.7 (5) 230 1321-3TW007-AA 1321-3TW007-AB 460 1321-3TW007-BA 1321-3TW007-BB 575 1321-3TW007-CA 1321-3TW007-CB 11 5.5 (7.5) 230 1321-3TW011-AA 1321-3TW011-AB 460 1321-3TW011-BA 1321-3TW011-BB 575 1321-3TW011-CA 1321-3TW011-CB 14 7.5 (10) 230 1321-3TW014-AA 1321-3TW014-AB 460 1321-3TW014-BA 1321-3TW014-BB 575 1321-3TW014-CA 1321-3TW014-CB 20 11 (15) 230 1321-3TW020-AA 1321-3TW020-AB 460 1321-3TW020-BA 1321-3TW020-BB 575 1321-3TW020-CA 1321-3TW020-CB 27 15 (20) 230 1321-3TW027-AA 1321-3TW027-AB 460 1321-3TW027-BA 1321-3TW027-BB 575 1321-3TW027-CA 1321-3TW027-CB 34 18.5 (25) 230 1321-3TW034-AA 1321-3TW034-AB 460 1321-3TW034-BA 1321-3TW034-BB 575 1321-3TW034-CA 1321-3TW034-CB 575V AC Catalog Number N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A
10
575V AC Catalog Number N/A N/A N/A N/A N/A N/A 1321-3TH063-AC 1321-3TH063-BC 1321-3TH063-CC 1321-3TH075-AC 1321-3TH075-BC 1321-3TH075-CC 1321-3TH093-AC 1321-3TH093-BC 1321-3TH093-CC 1321-3TH118-AC 1321-3TH118-BC 1321-3TH118-CC 1321-3TH145-AC 1321-3TH145-BC 1321-3TH145-CC 1321-3TH175-AC 1321-3TH175-BC 1321-3TH175-CC 1321-3TH220-AC 1321-3TH220-BC 1321-3TH220-CC 1321-3TH275-AC 1321-3TH275-BC 1321-3TH275-CC 1321-3TH330-AC 1321-3TH330-BC 1321-3TH330-CC 1321-3TH440-AC 1321-3TH440-BC 1321-3TH440-CC 1321-3TH550-AC 1321-3TH550-BC 1321-3TH550-CC 1321-3TH660-AC 1321-3TH660-BC 1321-3TH660-CC 1321-3TH770-AC 1321-3TH770-BC 1321-3TH770-CC 1321-3TH880-AC 1321-3TH880-BC 1321-3TH880-CC
11
Regenerative Drive Cat. No. 20P-41AD4P1 20P-41AD6P0 20P-41AD010 20P-41AD014 20P-41AD019 20P-41AD027 20P-41AD035 20P-41AD045 20P-41AD052 20P-41AD073 20P-41AD086 20P-41AD100 20P-41AD129 20P-41AD167 20P-41AD207 20P-41AD250 20P-41AD330 20P-41AD412 20P-41AD495 20P-41AD667 20P-41AD830 20P-41AD996 20P-41AD1K1 20P-41AD1K3 20P-41AD1K4
DC Amps 4.1 6 10 14 19 27 35 45 52 73 86 100 129 167 207 250 330 412 495 667 830 996 1162 1328 1494
AC Line Amps 3.3 4.9 8.2 11.4 15.5 22.1 28.6 36.8 42.5 59.6 70.3 81.7 105.4 136.4 169.1 204.3 269.6 336.6 404.4 544.9 678.1 813.7 949.4 1085.0 1220.6
HP 2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200 250 300 400 500 600 700 800 900
IP00 (Open Style) Line Reactor Cat No. 1321-3R4-A 1321-3R8-A 1321-3R18-B 1321-3R18-B 1321-3R18-B 1321-3R55-B 1321-3R55-B 1321-3R55-B 1321-3R55-B 1321-3R80-B 1321-3R100-B 1321-3R100-B 1321-3R160-B 1321-3R160-B 1321-3RB250-B 1321-3RB250-B 1321-3RB320-B 1321-3RB400-B 1321-3R500-B 1321-3R600-B 1321-3R750-B 1321-3R850-B 1321-3R1000-B
(1) (2)
Line Reactor kW (HP) .55 (.75) .75 (1) 1.5-7.5 (2-10) 1.5-7.5 (2-10) 1.5-7.5 (2-10) 11-22 (15-30) 11-22 (15-30) 11-22 (15-30) 11-22 (15-30) 30 (40) 37-45 (50-60) 37-45 (50-60) 56-75 (75-100) 56-75 (75-100) 93-112 (125-150) 93-112 (125-150) 149 (200) 186.4 (250) 223.7 (300) 298.3 (400) 372.8 (500) 447,4 (600) 552 (700)
AC Input Contactor Cat. No. 100-C12D10 100-C12D10 100-C12D10 100-C12D10 100-C23D10 100-C23D10 100-C30D10 100-C37D10 100-C43D10 100-C60D10 100-C85D10 100-C85D10 100-D110D11 100-D140D11 100-D180D11 100-D210ED11 100-D300ED11 100-D420ED11 100-D420ED11 100-D630ED11 100-D860ED11 100-D860ED11 100-G860KD22 100-G860KD22 100-G1200KD12
No Line Reactor available for this drive rating. Use the recommended Isolation Transformer: 1321-3TH880-BB. No Line Reactor or Isolation Transformer available for this drive rating - must be sourced locally.
12
IP00 (Open Style) Line Reactor Cat No. 1321-3R600-B 1321-3R750-B 1321-3R850-B 1321-3R1000-B
(1)
Line Reactor kW (HP) 447 (600) 597 (800) 671 (900) 746 (1000)
No Line Reactor or Isolation Transformer available for this drive rating - must be sourced locally. No AC Input Contactor available for this drive rating - must be sourced locally.
C D
(1) (2)
(1)
(2)
(2) (2)
Armature Voltage (Volts) 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240 240
DB Resistor Size (ohms) 20 20 15 8.6 6 5 3.5 2.6 2 2 0.7 0.5 0.5 2 1.4 0.5 0.322
DB Resistor Size (Watts) 420 420 420 420 345 330 385 385 330 330 280 365 365 330 290 1458 6221
Brake Amps Required 12.00 12.00 16.00 27.91 40.00 48.00 68.57 92.31 120.00 120.00 342.86 480.00 480.00 120.00 171.43 651 781
DC Loop Contactor Cat. No.(3) 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC110 1370-DC110 1370-DC110 1370-DC180 1370-DC180 1370-DC280 1370-DC280 (1) (1) (1) (1) (1) (1)
DC Contactor Crimp Lugs Cat. No.(4) 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG56 1370-LG92 1370-LG92 1370-LG110 1370-LG160 1370-LG180 1370-LG228 1370-LG268
(5)
Frame
See Alternate Dynamic Brake Resistor Kits and DC Output Contactors Amp on page 15. No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally. (3) Coil voltage = 115V AC, 50/60Hz. (4) See DC Contactor Crimp Lug Kit Specifications Amp on page 14 for more information. (5) Wire and Lug size dependant on enclosure dimensions and local codes.
13
(1) (1)
(2)
Armature Voltage (Volts) 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500 500
DB Resistor Size (ohms) 81 62 45 27 20 12 5 4.5 3.5 2.6 2 2 1 0.7 0.7 0.5 0.7 0.808 0.595 0.542
DB Resistor Size (Watts) 255 245 245 350 420 405 330 330 385 345 345 345 270 280 280 365 280 7292 6069 6439
Brake Amps Required 6.17 8.06 11.11 18.52 25.00 41.67 100.00 111.11 142.86 192.31 250.00 250.00 500.00 714.29 714.29 1000.00 714.29
DC Loop Contactor Cat. No.(3) 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC56 1370-DC110 1370-DC110 1370-DC110 1370-DC180 1370-DC180 1370-DC280 1370-DC280 (1) (1) (1) (1)
(1) (1) (1) (1) (1)
DC Contactor Crimp Lugs Cat. No.(4) 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG40 1370-LG52 1370-LG52 1370-LG92 1370-LG92 1370-LG110 1370-LG140 1370-LG180 1370-LG228 1370-LG268
(5)
Frame
See Alternate Dynamic Brake Resistor Kits and DC Output Contactors Amp on page 15. No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally. Coil voltage = 115V AC, 50/60Hz. (4) See DC Contactor Crimp Lug Kit Specifications Amp on page 14for more information. (5) Wire and Lug size dependant on enclosure dimensions and local codes.
The Rated Motor Armature Current is taken directly from the motor nameplate or motor data. The current listed in this column is the maximum current allowed for the Armature Conductor Size (column 3) and the DC Contactor Rating (column 2). (2) The armature conductors are sized by multiplying the Rated Motor Armature Current by 1.25 as provided for in NEC 420-22 (1987). The DC lug ratings are determined from NEC Table 31016 (1987) for copper conductors, insulation temperature rated at 75 C (167 F) at an ambient temperature of 30 C (86 F). If conditions are other than shown in NEC Table 310-16, then refer to application codes. (3) The dynamic braking (DB) conductors are sized as in footnote 2 above, but at half ampacity due to the short time duration of current flow in these conductors, and has been sized to satisfy NEMA Standard ICS 3-302.62 - Dynamic Braking. If the load inertia is larger than that of the motor, calculations must be made to determine correct conductor sizing and DB resistor wattage per NEMA Standard ICS 3-302.62.
14
PowerFlex DC Technical Data Alternate Dynamic Brake Resistor Kits and DC Output Contactors
The following alternate dynamic brake resistor kits and/or DC output contactors may be used with the corresponding PowerFlex DC drives but must be sourced separately from the drive. 230V AC Input Drives
Drive Current AC Rating DC Line Code Amps Amps HP
360 434 294 355 100 125
DB DC Loop Contactor Cat. No.(2) Armature Resistor Brake Voltage DB Resistor Size Amps Drive w/No Dynamic (Volts) Size (ohms) (Watts) Required Brake Drive w Dynamic Brake
1.4 0.5 290 1458 171.43 651 ABB_EHDB360C2P-1L2S ABB_EHDB520C2P-1L2S ABB_EHDB360C-1L22SS ABB_EHDB520C-1L22SS
B 360 434
Frame
1370-DBL76 240 CUTLER240 HAMMER_G3AP50 (Qty 4 - two in series, two in parallel) HUBBELL_Y139W322GB 240 (1) 240 240 240
0.322
6221
781
(1) (2)
No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally. Coil voltage = 115V AC, 50/60Hz. (3) See DC Contactor Crimp Lug Kit Specifications Amp on page 14 for more information. (4) Wire and Lug size dependant on enclosure dimensions and local codes.
DB DC Loop Contactor Cat. No.(2) Armature Resistor Brake Voltage DB Resistor Size Amps (Volts) Size (ohms) (Watts) Required Drive w/No Dynamic Brake Drive w Dynamic Brake
500 500 500 500 500 500 500 500 0.7 0.808 0.595 0.542 0.463 0.322 0.322 0.255 280 7292 6069 6439 6338 6221 6221 5718 714.29 ABB_EHDB360C-1L22SS ABB_EHDB520C-1L22SS ABB_EHDB520C-1L22SS ABB_EHDB800C-1L22SS ABB_EHDB960C-1L22SS SIEMENS-MFG_14-193-10158-2 (Qty 1) SIEMENS-MFG_14-193-10158-2 (Qty 1) CUTLERHAMMER_6702ED636-2 (Qty 1) CUTLER-HAMMER_6702ED636- CUTLER2 (Qty 2) HAMMER_6702ED636-2 (Qty 1) ABB_EHDB360C2P-1L2S ABB_EHDB520C2P-1L2S ABB_EHDB520C2P-1L2S ABB_EHDB800C2P-1L2S ABB_EHDB960C2P-1L2S SIEMENS-MFG_14-193-101-58-2 (Qty 2) SIEMENS-MFG_14-193-101-58-2 (Qty 2) CUTLER-HAMMER_6702ED6362 (Qty 2)
B C D
Frame
1K4
1494
900
500
0.255
5718
(1) (2)
No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally. Coil voltage = 115V AC, 50/60Hz. (3) See DC Contactor Crimp Lug Kit Specifications Amp on page 14 for more information. (4) Wire and Lug size dependant on enclosure dimensions and local codes.
Dynamic Brake Armature Resistor Voltage DB Resistor Kit Cat. No. (Volts) Size (ohms)
(1)
DB DC Loop Contactor Cat. No.(2) Resistor Brake Size Amps (Watts) Required Drive w/No Dynamic Brake
ABB_EHDB960C2P-1L2S SIEMENS-MFG_14-193-101-58-2 (Qty 2) SIEMENS-MFG_14-193-101-58-2 (Qty 2) CUTLER-HAMMER_6702ED636-2 (Qty 2) CUTLER-HAMMER_6702ED636-2 (Qty 2)
Frame
(1) (2)
No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally. Coil voltage = 115V AC, 50/60Hz. (3) See DC Contactor Crimp Lug Kit Specifications Amp on page 14 for more information. (4) Wire and Lug size dependant on enclosure dimensions and local codes.
15
Dynamic Brake Armature Resistor Kit Voltage DB Resistor Cat. No. (Volts) Size (ohms)
(1)
DB DC Loop Contactor Cat. No.(2) Resistor Brake Size Amps (Watts) Required Drive w/No Dynamic Brake
SIEMENS-MFG_14-193-101-58-2 (Qty 2) SIEMENS-MFG_14-193-101-58-2 (Qty 2) SIEMENS-MFG_14-193-101-58-2 (Qty 2) SIEMENS-MFG_14-193-101-58-2 (Qty 2) SIEMENS-MFG_14-193-101-58-2 (Qty 2) SIEMENS-MFG_14-193-101-58-2 (Qty 2) CUTLER-HAMMER_6702ED636-2 (Qty 2) CUTLER-HAMMER_6702ED636-2 (Qty 2)
Frame
(1) (2)
No Dynamic Brake Resistor kit available for this drive rating - must be sourced locally. Coil voltage = 115V AC, 50/60Hz. (3) See DC Contactor Crimp Lug Kit Specifications Amp on page 14 for more information. (4) Wire and Lug size dependant on enclosure dimensions and local codes.
575
SK-20P-S726171
690
16
Installation Considerations
The PowerFlex Digital DC drive has the following built in protective features to help simplify installation: Ground fault protection during start up and running ensures reliable operation Electronic motor overload protection increases motor life There are many other factors that must be considered for optimal performance in any given application. The block diagram below highlights the primary installation considerations.
Motor Recommendations - See the Allen-Bradley Variable Speed AC/DC Motors Catalog, publication RAPS-1348
17
Note: For frame B and C drives only, a jumper must be placed between terminals SA-SB on the Switching Power Supply circuit board for the control circuits to work with 115V AC input. Refer to SA-SB Terminal Block Location on Frame B Drives on page 34 and SA-SB Terminal Block Location on Frame C Drives on page 35 for terminal block locations. DC Output Voltages The output voltages below take into account an AC input undervoltage within the stated tolerance limits and a voltage drop of 4% due to an AC input line reactor. It is the same as the rated armature voltage suggested for the connected motor. Armature Circuit
AC Input Voltage (Terminals U, V, W) 230V 10 %, 3Ph 400V 10 %, 3Ph 440V 10 %, 3Ph 460V 10 %, 3Ph 480V 10 %, 3Ph 575V 10 %, 3Ph 690V 10 %, 3Ph DC Output Armature Voltage (Terminals C & D) Two Quadrant Drive Four Quadrant Drive 260V 240V 470V 420V 530V 460V 560V 480V 580V 500V 680V 600V 810V 720V
Field Circuit
AC Input Voltage (Terminals U1 & V1) 230V 10 %, 1Ph 400V 10 %, 1Ph 460V 10%, 1Ph
(1)
DC Output Field Voltage(1) (Terminals C1 & D1) Fixed Field Adjustable Field 200V 200V 310V 310V 360V 360V
18
PE 34 (N.O. Relay) M1 AC Contactor C Isolation (2) (2) Transformer Line Reactor 13 L1 L2 L3 W A2 A2 FS2 D C1 FU1 FV1 V1 SA (1) SB U2 V2 35
(8) (8) (1) (6) (4)
FS2
(6)
(3)
(5)
L1 A1
A1
L2
L3 Safety Ground FU FU A1
3 Phase AC line
Field Power Terminal Block U1 F1 These connections must be taken from the primary side of the Isolation Transformer or Line Reactor (clean power). D1
FU
FU
PowerFlex DC Drive
F2
36
(9)
(1) For frame B and C drives only, a jumper is required between terminals SA and SB for 115V AC control input power. See Control Circuit Input Power on page 32 for more information. (2) An Isolation Transformer and/or 35% impedance Line Reactor is required. If the Isolation Transformer provides the required 35% impedance, a Line Reactor is not required. See AC Input Line Reactors and Contactors on page 12 and Isolation Transformers on page 10 for recommendations. (3) AC input fuses for the armature converter are customer supplied for frame A and B drives and are internally mounted on frame C and D drives. See Circuit Protection on page 47 for fuse recommendations. (4) Par 140 [Digital In8 Sel] set to 31 Contactor (5) If using the +24V internal power supply, terminal 18 (24V common) must be jumpered to terminal 35 (digital input common). (6) Customer supplied armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. See Circuit Protection on page 47 for fuse recommendations. Fuses with Trip Indicator Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. Refer to Power Wiring with Armature Output Fuses and Inverting Fault Status on page 22. (7) Optional armature voltage feedback sensing not needed with AC contactor if Fuses with Trip Indicator are used (and wired to Inverting Fault input). See Power Wiring with Armature Output Fuses and Inverting Fault Status on page 22. If regular fuses are used, armature voltage TB can be used for overvoltage fault. (8) Par 1391 [ContactorControl] = 1 AC Cntctr and Par 1392 [Relay Out 1 Sel] = 25 Contactor. Important: Terminal 35 and 36 are on the Control Power / Relay Terminal block, NOT the I/O terminal blocks. See Relay Outputs on page 39 for locations. (9) Frame C & D drives only require an external power supply for the heatsink cooling fan. See Frame C Heatsink Cooling Fans Power Supply Terminals on page 36 and Frame D Heatsink Cooling Fan Power Supply Terminals on page 37 for more information.
19
20
PE 19
FS2 L1 T1 T2 A2 A1 L2 A1
(6)
34
(5)
(4)
Lockable Installation Disconnect Isolation (2) (2) Transformer Line Reactor FS1 FS1 FS1 W Safety Ground FU FU A2 Field Power Terminal Block U1 C1 FU1 FV1 V1 SA (1) SB U2 V2 35 36 U3 V3
(9)
(3)
L1
(3) (3)
U V 1A1
Armature Volt. (7) Fdbk. Term.
L2
PowerFlex DC Drive
A1 1A2
(6)
L3 FU
M
A2 FS2
3 Phase AC line
FU
These connections must be taken from the primary side of the Isolation Transformer or Line Reactor (clean power). F1 D1 F2
(1)
(1) For frame B and C drives only, a jumper is required between terminals SA and SB for 115V AC control input power. See Control Circuit Input Power on page 32 for more information. (2) An Isolation Transformer and/or 35% impedance Line Reactor is required. If the Isolation Transformer provides the required 35% impedance, a Line Reactor is not required. See AC Input Line Reactors and Contactors on page 12 and Isolation Transformers on page 10 for recommendations. (3) AC input fuses for the armature converter are customer supplied for frame A and B drives and are internally mounted on frame C and D drives. See Circuit Protection on page 47 for fuse recommendations. (4) Par 140 [Digital In8 Sel] set to 31 Contactor (5) If using the +24V internal power supply, terminal 18 (24V common) must be jumpered to terminal 35 (digital input common). (6) Customer supplied armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. See Circuit Protection on page 47 for fuse recommendations. Fuses with Trip Indicator Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. Refer to Power Wiring with Armature Output Fuses and Inverting Fault Status on page 22. (7) Optional armature voltage feedback sensing not needed with DC contactor if Fuses with Trip Indicator are used (and wired to Inverting Fault input). See Power Wiring with Armature Output Fuses and Inverting Fault Status on page 22. If regular fuses are used, armature voltage TB can be used for overvoltage fault. (8) Par 1391 [ContactorControl] = 3 DC Cntctr and Par 1392 [Relay Out 1 Sel] = 25 Contactor. Important: Terminal 35 and 36 are on the Control Power / Relay Terminal block, NOT the I/O terminal blocks. See Relay Outputs on page 39 for locations. (9) Frame C & D drives only require an external power supply for the heatsink cooling fan. See Frame C Heatsink Cooling Fans Power Supply Terminals on page 36 and Frame D Heatsink Cooling Fan Power Supply Terminals on page 37 for more information.
(4)
Lockable Installation Disconnect FS1 FS1 FS1 W Safety Ground FU A2 Field Power Terminal Block U1 C1 FU1 FV1 V1 SA (1) SB V2 U2 35 36 U3 V3
(10)
(3)
L1
(3) (3)
U V 1A1
Armature Volt. (7) Fdbk. Term. (N.O. Relay) A1 M1 DC Cntctr
L2
PowerFlex DC Drive
A1 1A2
FS2
(6)
L3 FU FU
3 Phase AC line
FU
M
A2
F1
DB (8) Res.
These connections must be taken from the primary side of the Isolation Transformer or Line Reactor (clean power). D1 F2
FS2
(6)
(1)
(1) For frame B and C drives only, a jumper is required between terminals SA and SB for 115V AC control input power. See Control Circuit Input Power on page 32 for more information. (2) An Isolation Transformer and/or 35% impedance Line Reactor is required. If the Isolation Transformer provides the required 35% impedance, a Line Reactor is not required. See AC Input Line Reactors and Contactors on page 12 and Isolation Transformers on page 10 for recommendations. (3) AC input fuses for the armature converter are customer supplied for frame A and B drives and are internally mounted on frame C and D drives. See Circuit Protection on page 47 for fuse recommendations. (4) Par 140 [Digital In8 Sel] set to 31 Contactor (5) If using the +24V internal power supply, terminal 18 (24V common) must be jumpered to terminal 35 (digital input common). (6) Customer supplied armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. See Circuit Protection on page 47 for fuse recommendations. Fuses with Trip Indicator Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. Refer to Power Wiring with Armature Output Fuses and Inverting Fault Status on page 22. (7) Optional armature voltage feedback sensing not needed with DC contactor if Fuses with Trip Indicator are used (and wired to Inverting Fault input). See Power Wiring with Armature Output Fuses and Inverting Fault Status on page 22. If regular fuses are used, armature voltage TB can be used for overvoltage fault. (8) The Enable input must be removed in order to perform a dynamic braking stop. (9) Par 1391 [ContactorControl] = 3 DC Cntctr and Par 1392 [Relay Out 1 Sel] = 24 ContactorDB. Important: Terminal 35 and 36 are on the Control Power / Relay Terminal block, NOT the I/O terminal blocks. See Relay Outputs on page 39 for locations. (10) Frame C & D drives only require an external power supply for the heatsink cooling fan. See Frame C Heatsink Cooling Fans Power Supply Terminals on page 36 and Frame D Heatsink Cooling Fan Power Supply Terminals on page 37 for more information.
21
FS2 C
(1)
A1
PowerFlex DC Drive
D
M
FS2
(1)
A2
(1)
33
(2)
(2)
Customer supplied armature output fuses are required on four quadrant and are recommended on two quadrant Frame A and B drives. See Circuit Protection on page 47 for fuse recommendations. Fuses with Trip Indicator Switches are recommended for Inverting Fault protection when the motor will be Field Weakened and run above base speed. Par 139 [Digital In7 Sel] set to 64 Invert Flt.
22
Loosen the two screws that secure the power terminal cover to the drive chassis and remove the terminal cover in order to connect the armature power wiring. Front View Note: Front view of drive shown with bottom protective and power terminal covers removed.
PE
ATTENTION: Do not operate the drive with the power terminal cover removed. Operating the drive with the power terminal cover removed may result in a hazardous condition that could cause personal injury and/or equipment damage.
23
PE
PE
Bottom View
24
Top of Drive
Bottom of Drive
PE
25
A B
C All D All
(1)
See Catalog Number Explanation on page 6, positions 8, 9 and 10 for corresponding drive HP rating, armature amp rating and field amp rating.
Important: Certain frame D drives require the use of a terminal adapter kit(s) for terminals U, V, W, C and D. Refer to Frame D Terminal Adapter Kits on page 16 for details.
Wire with an insulation rating of 600V or greater is recommended. See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing information.
26
27
Bottom of Drive
28
U1
V1
C1
D1
U1
V1
C1
D1
29
D1 C1 U1 V1
See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing information.
30
C1
D1
2 AWG
See Catalog Number Explanation on page 6, positions 8, 9 and 10 for corresponding drive HP rating, armature amp rating and field amp rating. (2) See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing information.
31
U2
V2
32
U2
V2
U2
V2
33
U2 V2
Terminals U2, V2 PE
(1)
See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing information.
SA-SB terminals
34
35
Terminals U3, V3
(1)
AWG 2616
See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing information.
U3
V3
36
Frame D Heatsink Cooling Fan Signal Wire Sizes and Terminal Specifications
Wire Size and Type(1) Flexible Multi-core (mm2) (mm2) 0.141.5 0.142.5 Tightening Torque Nm (lbin) AWG 2812 0.50.6 (4.45.3)
See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing information.
32
31
PE V3 U3
37
Terminals 81, 82
(1)
AWG 2616
See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing information.
81
82
38
81 82
Relay Outputs
Terminals 35 and 36 and 75 and 76 are N.O. relay outputs. The relay output between terminals 35 and 36 is configured with parameter 1392 [Relay Out 1 Sel]. The relay output between terminals 75 and 76 is configured with parameter 629 [Relay Out 2 Sel]. Refer to Using Contactors in the PowerFlex Digital DC Drive User Manual, publication 20PUM001, for more information.
39
Note: Terminals 78 and 79 shown with 1k ohm resistor in place of temperature sensor.
78 79 35 36 75 76
78 79 35 36 75 76
40
35 36 75 76 78 79
78 79 35 36 75 76
Recommended Signal Wire Size for Relay Outputs and Thermistor/Thermal Switch Terminals
Wire Size and Type(1) Multi-core Flexible (mm2) (mm2) 0.1401.500 0.1401.500 Tightening Torque Nm (lbin) 0.5 (4.4)
AWG 2614
See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing information.
41
Signal Analog Input 1 (+) Analog Input 1 () Analog Input 2 (+) Analog Input 2 () Analog Input 3 (+) Analog Input 3 ()
7 8 9 10
(1)
Description Isolated (1), bipolar, differential, 10V / 0-20mA, or 4-20mA. Important: 0-20mA or 4-20mA operation requires that switch S9, S10, and S11 on the Control board be in the Off position. Drive damage may occur if the switch is not in the correct position based on the type of input signal. Refer to DIP Switch and Jumper Settings in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001 Max 10V, Max 0.25mA. 2-5k ohm load. Max 10V, Max 10mA. For (+) and () 10V pot references. PE ground to drive chassis.
Related Parameter 70 [Anlg In1 Sel] 75 [Anlg In2 Sel] 80 [Anlg In3 Sel]
Differential Isolation - External source must be maintained at less than 160V with respect to PE. Input provides high common mode immunity.
42
11
12
13
14
15
16
17
18
19
20
Signal Internal 0V Digital Input 1 Digital Input 2 Digital Input 3 Digital Input 4 Digital Input Common(2) Not Used 24V Supply Common +24V DC Supply PE ground
Description Max Volt. +30V, Max Cur. 15V/3.2mA, 24V/5mA, and 30V/6.4mA.
Common for the internal power supply. Drive supplied control input power.
Related Parameter 133 [Digital In1 Sel] 134 [Digital In2 Sel] 135 [Digital In3 Sel] 136 [Digital In4 Sel]
21
22
23
24
25
26
27
28
29
30
Drive supplied power for Digital Outputs. Max. + 30V, Max. 80mA.
31
32
33
34
35
36
Signal Digital Input 5 Digital Input 6 Digital Input 7 Digital Input 8 Digital Input Common
Description Max Volt. +30V, Max Cur. 15V/3.2mA, 24V/5mA, and 30V/6.4mA.
Important: When using the internal +24V DC supply (terminal 19) for digital inputs 5-8, you must connect the digital input common (terminal 35) to the +24V supply common (terminal 18).
Related Parameter 137 [Digital In5 Sel] 138 [Digital In6 Sel] 139 [Digital In7 Sel] 140 [Digital In8 Sel]
3640
Not Used
Recommended Signal Wire Size for Analog I/O and Digital I/O
Terminal Block (Terminals) TB14 (140) Wire Size and Type(1) Multi-core Flexible (mm2) (mm2) 0.1401.500 0.1401.500 Tightening Torque Nm (lbin) 0.4 (3.5)
AWG 2616
See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for cable spacing information.
43
A+
A-
B+
B-
Z+
ZCO M
+V
(1)
Selectable via switch S21 on the Control board. Refer to DIP Switch and Jumper Settings in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for more information. (2) Selectable via switch S20 on the Control board. Refer to DIP Switch and Jumper Settings in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001, for more information.
44
to Shield (1)
to Shield (1)
to Shield (1)
(1)
Shield connection is on the drive Control EMI Shield. Refer to Digital Encoder Terminal Block Location on page 44.
45
(1)
Maximum voltage depends on the configuration of DIP switch S4. Refer to the PowerFlex Digital DC Drive User Manual, publication 20P-UM001 for information on jumper settings.
Nm (lbin)
See Cable and Wiring Recommendations in the PowerFlex Digital DC Drive User Manual, publication 20P-UM001
46
Circuit Protection
The tables on the following pages provide drive ratings and the recommended fuses for protecting the armature and field circuits. Externally mounted fuses (as indicated in the figures below) must be sourced separately when installing the drive. Internally mounted fuses are provided with the drive.
FS1
U1 FS3 C1
V1
C
FS2 = Externally mounted fuses for the armature circuit on the DC side.
D1
FS3 = Internally mounted fuses for the field circuit on the AC input side.
FS2
Drive Current Rating Code A 7P0 9P0 012 020 029 038 055 073 093 110 B 146 180 218 265 360 434 Frame
Ferraz Shawmut (Gould Shawmut) Ferrule A70QS Type A70QS10-14F A70QS16-14F A70QS20-14F A70QS25-14F A70QS40-22F A70QS63-22F A70QS80-22F North American A70P / A70QS Type A70P10-4 A70P15-4 A70P20-4 A70QS25-4 A70QS40-4 A70QS60-4 A70QS80-4 A70QS100-4K A70QS150-4K A70QS175-4K A70QS250-4 A70QS300-4 A70QS350-4 A70QS400-4 A70QS600-4K A70QS600-4
ST38-72612
47
Drive Current Rating Code A 4P1 6P0 010 014 019 027 035 045 052 073 086 100 129 B 167 207 250 330 412 Frame
Ferraz Shawmut (Gould Shawmut) Ferrule A70QS Type A70QS10-14F A70QS10-14F A70QS20-14F A70QS25-14F A70QS25-14F A70QS40-22F A70QS63-22F A70QS80-22F A70QS80-22F North American A70P / A70QS Type A70P10-4 A70P10-4 A70P25-4 A70P25-4 A70P25-4 A70QS40-4 A70QS60-4 A70QS80-4 A70QS80-4 A70QS100-4K A70QS150-4K A70QS175-4K A70QS175-4K A70QS300-4 A70QS350-4 A70QS400-4 A70QS600-4K A70QS600-4
ST38-72612
Drive Current Rating Code A 7P0 9P0 012 020 029 038 055 073 093 110 B 146 180 218 265 360 434 Frame
(1)
Ferraz Shawmut (Gould Shawmut) Ferrule A70QS Type A70QS16-14F A70QS20-14F A70QS25-14F A70QS40-14F A70QS63-22F A70QS80-22F North American A70P / A70QS Type A70P15-4 A70P20-4 A70P25-4 A70QS40-4 A70QS60-4 A70QS80-4 A70QS125-4K A70QS150-4K A70QS200-4K A70QS250-4 A70QS300-4 A70QS350-4 A70QS450-4 A70QS600-4K A70QS700-4 A70P900-4
ST38-72612
Required on four quadrant drives only, highly recommended on two quadrant drives.
48
Drive Current Rating Code A 4P1 6P0 010 014 019 027 035 045 052 073 086 100 129 B 167 207 250 330 412 Frame
(1)
Ferraz Shawmut (Gould Shawmut) Ferrule A70QS Type A70QS10-14F A70QS16-14F A70QS20-14F A70QS32-14F A70QS40-14F A70QS63-22F A70QS80-22F North American A70P / A70QS Type A70P10-4 A70P15-4 A70P20-4 A70P30-4 A70QS40-4 A70QS60-4 A70QS70-4 A70QS90-4 A70QS100-4 A70QS150-4K A70QS175-4K A70QS200-4K A70QS250-4 A70QS350-4 A70QS400-4 A70QS500-4K A70QS700-4 A70QS800-4
ST38-72612
Required on four quadrant drives only, highly recommended on two quadrant drives.
Drive Current Rating Code 7P0 9P0 012 020 029 038 055 073 093 110 146 180 218 265 360 434
Frame
Field Amps 10
Type 6 x 32 mm
14
20
10 x 38 mm
FWC-25A10F
A60Q25-2
60 033 05.25
(1)
49
Drive Current Rating Code 4P1 6P0 010 014 019 027 035 045 052 073 086 100 129 167 207 250 330 412
Frame
Field Amps 10
Type 6 x 32 mm
14
20
10 x 38 mm
FWC-25A10F
A60Q25-2
60 033 05.25
(1)
50
FS4 = Internally mounted fuses for the armature converter on the AC input side.
U FS4 C
U1 FS3 C1
V1
D1
FS3 = Internally mounted fuses for the field circuit on the AC input side.
51
Frame
Field Amps
C D
20 40
22 x 58 mm
FWP-50A22F
A70QS50-22F
5014006.50
Frame
Field Amps
Type
C D
20 40 70
10 x 38 mm 2 22 x 58 mm
Frame D
Drive Current Field Rating Code Amps 810 40 1K0 1K2 1K3 1K6
Type 22 x 58 mm
Qty 2
Frame D
Drive Current Rating Code 678 791 904 1K0 1K1 1K2 1K4 1K5
Field Amps 40
Type 22 x 58 mm
Qty 2
70
FWP-100A22F
A70QS100-22F
5014006.100
52
53
54
AC Line Amps 553 645 738 830 922 1014 1153 1291
Qty 6 6 6 6 12 12 12 12
55
SIBA 20 635 32.800 + switch 28 001 04 20 635 32.1000 + switch 28 001 04 20 635 32.1100 + switch 28 001 04 20 635 32.1250 + switch 28 001 04 20 635 32.1400 + switch 28 001 04
SIBA 20 635 32.800 + switch 28 001 04 20 635 32.1000 + switch 28 001 04 20 635 32.1100 + switch 28 001 04 20 635 32.1250 + switch 28 001 04 20 635 32.800 + switch 28 001 04
56
AC Line Amps 553 645 738 830 922 1014 1153 1291
SIBA 20 635 32.630 + switch 28 001 04 20 635 32.800 + switch 28 001 04 20 635 32.900 + switch 28 001 04 20 635 32.1000 + switch 28 001 04 20 635 32.1100 + switch 28 001 04 20 635 32.1250 + switch 28 001 04 20 635 32.1400 + switch 28 001 04 20 635 32.800 + switch 28 001 04
Qty 6 6 6 6 6 6 6 12
Note: Drive shown with front covers removed and Control EMI shield lowered.
57
Important: Verify the circuit board revision prior to ordering and installing fuses.
Frame A B Circuit Board ID / Revision SW1-31 / H & below SW1-31 / I & above SW2-32 / H & below SW2-32 / I & above C SW3-32 / H & below SW3-32 / I & above D SW1-31 / I & above Designation F1 F1 F1 F2 F1 F2 F1 F2 F1 F2 F1 Fuse (5 x 20 mm) 1 A, 250V, slow 2.5 A, 250V, slow 3.15 A, 250V fast 2.5 A, 250V slow 2.5 A, 250V slow 3.15 A, 250V fast 2.5 A, 250V slow 2.5 A, 250V slow 2.5 A, 250V, slow
58
Fuses are located on the Switching Power Supply circuit board (SW-2) on the back of the Control EMI shield, which holds the Control board.
Switching Power Supply fuse holder The Switching Power Supply circuit board is located on the Control EMI shield.
59
Mounting
Operating Conditions and Temperatures
PowerFlex DC drives are designed to operate at 050 C (32 122 F) surrounding air temperature without derating. The drive must be mounted in a clean, dry location. Contaminants such as oils, corrosive vapors and abrasive debris must be kept out of the enclosure. NEMA/UL Type Open, IP20 enclosures are intended for indoor use primarily to provide a degree of protection against contact with enclosed equipment. These enclosures offer no protection against airborne contaminants.
STS
10 mm (0.4 in.)
10 mm (0.4 in.)
10 mm (0.4 in.)
50 mm (2.0 in.)
Important: Verify that all mounting screws are properly tightened before and after operation.
60
Approximate Dimensions
Frame A Dimensions
A mm (in.) 267 (10.5) B mm (in.) 359 (14.0) C mm (in.) 287 (11.3) A1 mm (in.) 7 (0.3) A2 mm (in.) 250 (9.8) B1 mm (in.) 275 (10.8)
A A1
PORT MOD NET A NET B
STS
B1
A2
Frame A Weights
Drive w/ND Rating Code 230V 460V 7P0 4P1 9P0 6P0 012 010 020 014 019 029 027 038 035 055 045 052 073 073 093 086 110 100 129 Weight Drive kg (lbs.) 8.4 (19.5) Drive & Packaging kg (lbs.) 10.5 (23.1)
8.8 (19.4)
11 (24.3)
10.8 (23.8)
13 (28.7)
61
A A1
STS
B1
A2
A3
Frame B Weights
Drive w/ND Rating Code 230V 460V 146 167 180 218 207 265 250 360 330 434 412 Weight Drive kg (lbs.) 25.5 (56.2) Drive & Packaging kg (lbs.) 27.5 (60.6)
62
A1 B4
B1 B B2
STS
B5
B3
Frame C Weights
Drive w/ND Rating Code 230V 460V 495 521 667 700 Weight - Regenerative Drives Drive Drive & Packaging kg (lb) kg (lb) 61 (134.5) 83 (183.0) 65 (143.3) 87 (191.8) Weight - Non-regenerative Drives Drive Drive & Packaging kg (lb) kg (lb) 57 (125.7) 79 (174.2) 62 (136.7) 84 (185.2)
63
127 (5.0)
127 (5.0)
127 (5.0)
127 (5.0)
Note: Only certain frame D drives require the use of a terminal adapter kit(s) for terminals U, V, W and C, D. These kits are not included with the drive. Refer to Frame D Terminal Adapter Kits on page 16 for details.
101 (4.0)
227.5 (9.0)
792 (31.2) 1230 (48.4) 1438 (56.6) 208 (8.2) 1250 (49.2)
144 (5.7)
157.5 (6.2) 32 (1.3) 10.5 (0.4) 146 (5.7) 60 (2.4) 252.5 (9.9) 37.5 (1.5) 134 (5.3) 134 (5.3)
107 (4.2)
64
Terminal adapter kit (see note) Note: Only certain frame D drives require the use of a terminal adapter kit(s) for terminals U, V, W and C, D. These kits are not included with the drive. Refer to Frame D Terminal Adapter Kits on page 16 for details.
541 (21.3)
531 (20.9)
65
1K4
Drive w/ND Rating Code 678 791 904 1K0 1K1 1K2 1K4 1K5
66
Parameter List
The LCD HIM displays parameters in a FileGroupParameter or Numbered List view order. To switch display mode, access the Main Menu, press ALT, then Sel (View) while the cursor is on the Parameter menu selection. In addition, using Par 211 [Param Access Lvl], you have the option to display the most commonly used parameters (Basic Parameter view) or all parameters (Advanced Parameter View).
FileGroupParameter Order
This simplifies programming by grouping parameters that are used for similar functions. The parameters are organized into files. Each file is divided into groups, and each parameter is an element in a group. By default, the LCD HIM displays parameters by FileGroupParameter view.
Parameters
[Speed Ref A] [Speed Ref A Pct] [Speed Ref B] [Speed Ref B Pct] [Speed Ref Out] [Spd Ref Out Pct] [Ramp In] [Spd Reg Out Pct] [Current Reg In] [Arm Current] [Arm Current Pct] [FaultCode] [AC Line Voltage] [AC Line Freq] 44 47 48 49 385 384 110 236 41 200 199 57 466 588 [Ramp In Pct] [Ramp Out] [Ramp Out Pct] [Speed Draw Out] [Spd Draw Out Pct] [Speed Reg In] [Speed Reg In Pct] [Field Current] [Fld Current Pct] [Cur Lim Pos Out] [Cur Lim Neg Out] [Output Voltage] [Output Power] [Drive Type] 111 113 114 1018 1019 118 117 351 234 10 11 233 1052 300 [Spd Feedback] [Spd Feedback Pct] [Actual Speed] [Encoder Speed] [Tachometer Speed] [Filt TorqCur Pct] [Field Ref Pct] [Drive Size] [Elapsed Lifetime] [Software Version] 122 121 924 420 1408 928 500 465 235 331
Current Meters
Drive Data
67
[Max Ref Speed] [Max Feedback Spd] [Rated Motor Volt] [Field Reg Enable] Field Config [Field Economy En] [Field Econ Delay] [Field Mode Sel] [Max Fld Curr Pct] [Min Fld Curr Pct] [Current Limit] Torq Attributes [Current Lim Pos] [Current Lim Neg] [Torque Ref] [Trim Torque] Speed Feedback [Fdbk Device Type] [Anlg Tach Gain] [Anlg Tach Zero] [Spd Fdbk Control] [SpdReg FB Bypass] [Autotune Cur Lim] Autotune [CurrReg Autotune] [Arm Resistance] [Arm Inductance] [Spd Reg Autotune] [TstGen Output] Test Generator [TstGen Frequency] [Minimum Speed] Speed Command Limits [Min Speed Fwd] Speed Comm and Discrete Speeds [Jog Speed] [Jog Off Delay] [Preset Speed 1] [Preset Speed 2] [Trim Ramp] Speed [Trim Ramp Pct] References [Arm Volt Kp] [Arm Volt Ki] [Spd Reg Kp] [Spd Reg Ki] [Arm Volt Kp Base] [Arm Volt Ki Base] [Spd Reg Kp Base] [Spd Reg Ki Base] [Spd Reg Kp Outpt] [Spd Reg Ki Outpt] [Speed Thresh Pos] [Speed Ramp En] Dynamic Control Ramp Rates [Ramp Type Select] Dynam ic Con trol [Accel Time 1] [Decel Time 1] [Accel Time 2] [Decel Time 2] [MOP Accel Time] [Enable Droop Load Limits [Droop Percent] [Droop Filter] [Fast Stop Time] Stop Modes [Spd 0 Trip Delay] [Start At Powerup] Restart Modes Adaptv Regulator [Adaptive Spd En] [Adaptive Reg Typ] [Adaptive Ref] [Adaptive Spd 1] [Adaptive Spd 2]
Parameters
45 162 175 497 499 1407 469 467 468 7 8 9 39 40 414 562 563 457 458 1048 452 453 454 1027 58 59 1 5 266 1409 154 155 42 378 242 493 494 87 88 495 496 93 94 99 100 101 245 18 660 662 24 32 22 699 696 697 38 627 1344 181 182 183 184 185 [Nom Mtr Arm Amps] [Nom Mtr Fld Amps] [Drv Fld Brdg Cur] [Fld Weaken Ratio] [Fld Reg Kp] [Fld Reg Ki] [Force Min Field] [Out Volt Level] [Fld Reg Kp Base] [Torque Reduction] [Zero Torque] [TrqTpr_Enable] [TrqTpr_Lim0] [TrqTpr_Lim1] [Spd Fdbk Error] [Act Spd Filter] [Encoder PPR] [Encoder Out Sel] [Encoder Err Chk] [Speed Tune Dir] [Speed Tune Kp] [Speed Tune Ki] [Spd Tune Inertia] [SpdTune Friction] [TstGen Amplitude] [Min Speed Rev] [Maximum Speed] [Preset Speed 3] [Preset Speed 4] [Preset Speed 5] [Preset Speed 6] [Trim Speed] [Trim Speed Pct] [Speed Thresh Neg] [Threshold Delay] [At Speed Error] [At Speed Delay] [Ref Zero Level] [Speed Zero Level] [Speed Zero Delay] [Spd Zero I En] [Spd Ref Zero En] [Spd Zero P En] [Spd Zero P Gain] [Lock Speed Integ] [MOP Decel Time] [Jog Ramp Time] [S Curve Time] [S Curve Accel 1] [S Curve Decel 1] [S Curve Accel 2] [S Curve Decel 2] [Droop Limit] [Load Comp] [Torq Red CurLim] [Closing Speed] [Opening Delay] [Powerup Delay] [Adaptive Joint 1] [Adaptive Joint 2] [Adaptive P Gain1] [Adaptive I Gain1] [Adaptive P Gain2] 179 280 374 456 91 92 498 921 97 342 353 750 751 752 455 923 169 1021 652 1029 1032 1033 1030 1031 60 6 2 156 157 158 159 43 379 102 103 104 105 106 107 108 123 124 125 126 348 30 1410 19 665 666 667 668 700 698 13 1262 1263 1345 186 187 188 189 190 [Drive Type Sel] [Fld Reg Ki Base] [Set Fld Curve] [Reset Fld Curve] [Fld Const 40 Pct] [Fld Const 70 Pct] [Fld Const 90 Pct] [TrqTpr_Lim2] [TrqTpr_Lim3] [TrqTpr_Lim4] [TrqTpr_Spd] [Filt Torq Cur] [Z Channel Enable] [Z Capture Pos En] [Z Captured Pos] [I Reg Error] [Inertia C Filter] [Torque Const] [Inertia] [Friction] [TstGen Offset] [Max Speed Fwd] [Max Speed Rev] [Preset Speed 7] [TB Manual Ref] [Speed Ratio] [Flying Start En] [Spd Fdbk Filter] [Spd Up Gain Pct] [Speed Up Base] [Speed Up Filter] [SpdReg Kp Bypass] [SpdReg Ki Bypass] [SpdFuncSelect] [InertiaCompAct] [InertiaCompVar] [Ramp Delay] [Zero Ramp Output] [Zero Ramp Input] [Freeze Ramp] [Acc Dec Filter] [Torq Limit Type] [Ramp In Zero En] [Actuator Delay] [Adaptive I Gain2] [Adaptive P Gain3] [Adaptive I Gain3] 201 98 919 920 916 917 918 753 754 755 756 926 911 912 913 587 1012 1013 1014 1015 61 3 4 160 267 1017 388 444 445 446 447 459 460 1016 1191 1192 20 344 345 373 1212 715 1265 1266 191 192 193
68
Group PI Control
Parameters
769 695 764 765 771 770 421 766 1258 418 731 734 757 758 759 484 485 486 487 488 489 490 491 492 553 554 555 556 557 558 559 560 561 794 795 796 797 798 799 800 1153 1154 1171 1172 1173 1174 1175 1176 1177 1178 1179 1180 1181 1182 1183 1184 1185 [PI Central v1] [PI Central v2] [PI Central v3] [PI Central v sel] [PI Central vs0] [PD Deriv Filter] [PD Prop Gain 1] [PD Prop Gain 2] [PID Setpoint 0] [PID Setpoint 1] [PID Setpoint Sel] [PID Feedback] [PID Output Sign] [PID Output Scale] [PID Output] [Scale3 Input] [Scale3 Output] [Scale3 Mul] [Scale3 Div] [Scale3 In Max] [Scale3 In Min] [Scale3 In Off] [Scale3 Out Off] [Scale3 In Abs] [Scale4 Input] [Scale4 Output] [Scale4 Mul] [Scale4 Div] [Scale4 In Max] [Scale4 In Min] [Scale4 In Off] [Scale4 Out Off] [Scale4 In Abs] [Line Spd Thresh] [Line Spd Gain] [Diameter Reset] [Diam Threshold] [Diameter Reached] [Line Speed Pct] [Diam Calc Dis] [Diameter Filter] [Base Omega] [Line FastStp Pct] [Winder Type] [Torq Current Pct] [Act Ten Ref Pct] [Speed Match] [Spd Match Acc] [Spd Match Dec] [Offs Accel Time] [W Offset] [Spd Match Gain] [Winder Side] [W Gain] [Spd Match Compl] [Line Spd Source] [Close Loop Comp] 776 777 778 779 780 767 768 788 760 761 762 763 772 773 774 1218 1219 1220 1221 1222 1223 1224 1225 1226 1227 1228 1229 1230 1231 1232 1233 1234 1235 1155 1156 1157 1158 1159 1160 1161 1162 1163 1186 1187 1193 1194 1195 1196 1197 1198 1199 1200 1201 1202 1203 1204 1208 [PI Central vs1] [PI integr freeze] [PI Upper Limit] [PI Lower Limit] [PI Init Prop Gn] [PD Deriv Gain 2] [PD Prop Gain 3] [PD Deriv Gain 3] [PID Target] [PID Source] [PID Source Gain] [PID Accel Time] [PID Decel Time] [PID Error Gain] [Scale5 Input] [Scale5 Output] [Scale5 Mul] [Scale5 Div] [Scale5 In Max] [Scale5 In Min] [Scale5 In Off] [Scale5 Out Off] [Scale5 In Abs] [Scale6 Input] [Scale6 Output] [Scale6 Mul] [Scale6 Div] [Scale6 In Max] [Scale6 In Min] [Scale6 In Off] [Scale6 Out Off] [Scale6 In Abs] [Diam Preset 0] [Diam Preset 1] [Diam Preset 2] [Diam Preset 3] [Diam Preset Sel] [Diam Inc Dec En] [Diam init filter [Diam stdy delay] [Torque Winder En] [W Target] [Actual Comp] [Closed Loop En] [Speed Demand En] [Spd match torque] [W Reference] [Jog TW Speed] [Jog TW Enable] [Ref Spd Source] [Ref Speed Gain] [Ref Line Speed] [Static F Zero] 781 783 784 785 793 789 790 791 782 786 787 1046 1047 1254 1236 1237 1238 1239 1240 1241 1242 1243 1244 1245 1246 1247 1248 1249 1250 1251 1252 1253 1164 1165 1166 1167 1168 1205 1206 1207 1209 1210 1213 1214 1215 1216 1217 1255 1256 1284 1285 1286 1287
[Enable PI] [PI Steady Thrsh] [PI Integral Gain] [PI Prop Gain PID] [PI Output] [Enable PD] PD Control [PD Output PID] [PD Deriv Gain 1] [Enable PID] PID Control [Real FF PID] [PID Steady Delay] [PI Init Intgl Gn] [PID Clamp] [Feed Fwd PID] [PID Error] [Scale1 Input] Scale Blocks [Scale1 Output] [Scale1 Mul] [Scale1 Div] [Scale1 In Max] [Scale1 In Min] [Scale1 In Off] [Scale1 Out Off] [Scale1 In Abs] [Scale2 Input] [Scale2 Output] [Scale2 Mul] [Scale2 Div] [Scale2 In Max] [Scale2 In Min] [Scale2 In Off] [Scale2 Out Off] [Scale2 In Abs] [Diameter Calc] Diameter Calc [DncrPosSpd] [Max Deviation] [Gear Box Ratio] [Dancer Constant] [Minimum Diameter] [Diameter Calc St] [Max Diameter] [Roll Diameter] Winder Functions [Variable J Comp] [Constant J Comp] [Materl Width Pct] [Static Friction] [Dynamic Friction] [Taper Enable] [Initial Diameter] [Final Diameter] [Tension Reduct] [Tension Ref] [Tension Scale] [Time AccDec Min] [Int Acc Calc En] [Line Accel Pct] [Line Decel Pct]
69
[Save HIM Ref] [Param Access Lvl] Drive Memory [Drive Status 1] Diagnostics [Drive Status 2] [Last Stop Source] [Start Inhibits] [Drive Logic Rslt] [At Speed] [At Zero Speed] [CurrLimit Active] [Spd Limit Active] [Speed Threshold] [Clear Fault Que] Faults [Fault Clear] [Fault Clr Mode] [Status1 at Fault] [Status2 at Fault] [Fault Arm Amps] [Fault Speed] [Fault Field Amps] [Fault Voltage] [Fault 1 Code] [Drive Alarm 1] Alarms [OverVolt Flt Cfg] [Aux Inp Flt Cfg] [UsrDsplyMult0] User Defined [UsrDsplyDiv0] [UsrValMult1] [UsrValDiv1] [UserDefined0] [UserDefined1] [UserDefined2] [UserDefined3] [UserDefined4] [UserDefined5] [UserDefined6] [UserDefined7] [UserDefined8] [UserDefined9] [UserDefined10] [UserDefined11] [UserDefined12] [UserDefined13] [DPI Baud Rate] Communications Comm Control [DPI Port Sel] Comm unicat ion Masks & Owners [Logic Mask] [Start Mask] [Jog Mask] [Direction Mask] [Reference Mask] [Accel Mask] [Fault Clr Mask] [Data In A1] Datalinks [Data In A2] [Data In B1] [Data In B2] [Data In C1] [Data In C2] [Logic Mask] Security [Logic Mask Act]
Utility
1322 209 211 381 382 1402 1403 1328 394 395 349 372 393 263 1347 1348 1349 1350 1371 1372 1373 1374 1351 1380 203 354 50 51 53 54 503 504 505 506 507 508 509 510 511 512 513 514 515 516 589 590 591 592 593 594 595 596 597 610 611 612 613 614 615 591 1376
[Man Ref Preload] [Save MOP Ref] [Reset Defaults] [Torque Positive] [Torque Negative] [MOP Inc Active] [MOP Dec Active] [Spd Select 0] [Spd Select 1] [Spd Select 2] [Ramp Select 0] [Ramp Select 1] [Encoder State] [Fault 2 Code] [Fault 3 Code] [Fault 4 Code] [Fault 5 Code] [Fault 6 Code] [Fault 7 Code] [Fault 8 Code] [Fault 9 Code] [Fault 10 Code] [Fault 1 Time] [OverTemp Flt Cfg] [FldLoss Flt Cfg] [Spd Loss Flt Cfg] [UserDefined14] [UserDefined15] [UsrDefBitWrdA] [UsrDefBitWrdA0] [UsrDefBitWrdA1] [UsrDefBitWrdA2] [UsrDefBitWrdA3] [UsrDefBitWrdA4] [UsrDefBitWrdA5] [UsrDefBitWrdA6] [UsrDefBitWrdA7] [UsrDefBitWrdA8] [UsrDefBitWrdA9] [UsrDefBitWrdA10] [UsrDefBitWrdA11] [UsrDefBitWrdA12] [UsrDefBitWrdA13] [UsrDefBitWrdA14] [DPI Fdbk Select] [MOP Mask] [Local Mask] [Decel Mask] [Stop Owner] [Start Owner] [Jog Owner] [Direction Owner] [Data In D1] [Data In D2] [Data Out A1] [Data Out A2] [Data Out B1] [Data Out B2] [Write Mask Act] [Write Mask Cfg]
210 249 258 346 347 396 397 400 401 402 403 404 651 1352 1353 1354 1355 1356 1357 1358 1359 1360 1361 365 473 478 517 518 519 520 521 522 523 524 525 526 527 528 529 530 531 532 533 534 1321 598 599 631 600 601 602 603 616 617 618 619 620 621 1377 1378
[MOP Select]
1375
[Accel Status] [Decel Status] [Fast Stop Status] [TestPoint Sel] [TestPoint Data] [TaskLoad 32 ms] [TaskLoad 1 ms] [TaskLoad 2 ms] [TaskLoad 8 ms] [Fault 2 Time] [Fault 3 Time] [Fault 4 Time] [Fault 5 Time] [Fault 6 Time] [Fault 7 Time] [Fault 8 Time] [Fault 9 Time] [Fault 10 Time] [UnderVolt Thresh] [OverCurrent Thr] [UsrDefBitWrdA15] [UsrDefBitWrdB] [UsrDefBitWrdB0] [UsrDefBitWrdB1] [UsrDefBitWrdB2] [UsrDefBitWrdB3] [UsrDefBitWrdB4] [UsrDefBitWrdB5] [UsrDefBitWrdB6] [UsrDefBitWrdB7] [UsrDefBitWrdB8] [UsrDefBitWrdB9] [UsrDefBitWrdB10] [UsrDefBitWrdB11] [UsrDefBitWrdB12] [UsrDefBitWrdB13] [UsrDefBitWrdB14] [UsrDefBitWrdB15] [DPI Port Value] [Reference Owner] [Accel Owner] [Fault Clr Owner] [MOP Owner] [Local Owner] [Decel Owner] [Data Out C1] [Data Out C1] [Data Out D1] [Data Out D2] [Data In Val Sel] [Data In SelData] [Port Mask Act]
1188 1189 1190 1381 1382 1383 1384 1385 1386 1362 1363 1364 1365 1366 1367 1368 1369 1370 481 584 535 536 537 538 539 540 541 542 543 544 545 546 547 548 549 550 551 552 1343 604 605 606 607 608 609 622 623 624 625 1319 1320 1379
70
Parameters
[Anlg In1 Sel] [Anlg In1 Config] [Anlg In1 Scale] [Anlg1 Tune Scale] [Anlg In1 Offset] [Anlg In1 Tune] [Anlg In1 Filter] [Anlg In2 Sel] [Anlg In2 Config] [Anlg In2 Scale] [Anlg Out1 Sel] [Anlg Out2 Sel] [Anlg Out3 Sel] [ContactorControl] [Dig In Status] [Digital In1 Sel] [Digital In2 Sel] [Digital In3 Sel] [Digital In4 Sel] [Digital In5 Sel] [Digital In6 Sel] [Digital In7 Sel] [Digital In8 Sel] [Digital In9 Sel] [Digital In10 Sel] [Digital In11 Sel] [Dig Out Status] [Digital Out1 Sel] [Digital Out2 Sel] [Digital Out3 Sel] [Digital Out4 Sel] [Digital Out5 Sel] [Digital Out6 Sel] [DPI P1 Select] [DPI P2 Select] 70 71 72 73 74 259 792 75 76 77 66 67 68 1391 564 133 134 135 136 137 138 139 140 141 142 143 581 145 146 147 148 149 150 1323 1324 [Anlg2 Tune Scale] [Anlg In2 Offset] [Anlg In2 Tune] [Anlg In3 Sel] [Anlg In3 Config] [Anlg In3 Scale] [Anlg3 Tune Scale] [Anlg In3 Offset] [Anlg In3 Tune] [Anlg In1 Target] [Anlg Out4 Sel] [Analog Out1 Scale] [Analog Out2 Scale] [Digital In12 Sel] [Inversion In 1] [Inversion In 2] [Inversion In 3] [Inversion In 4] [Inversion In 5] [Inversion In 6] [Inversion In 7] [Inversion In 8] [Inversion In 9] [Inversion In 10] [Inversion In 11] [Inversion In 12] [Digital Out7 Sel] [Digital Out8 Sel] [Relay Out 1 Sel] [Relay Out 2 Sel] [Inversion Out 1] [Inversion Out 2] [Inversion Out 3] [DPI P3 Select] [DPI P4 Select] 78 79 260 80 81 82 83 84 261 295 69 62 63 144 1276 1277 1278 1279 1280 1281 1282 1283 1387 1388 1389 1390 151 152 1392 629 1267 1268 1269 1325 1326 [Anlg In2 Target] [Anlg In3 Target] [Anlg In1 Cmp] [Anlg In1 Cmp Err] [Anlg In1 Cmp Dly] [Anlg In1 Cmp Eq] [Analog In1 Value] [Analog In2 Value] [Analog In3 Value] 296 297 1042 1043 1044 1045 1404 1405 1406
[Analog Out3 Scale] 64 [Analog Out4 Scale] 65 [Dig In Term 1] [Dig In Term 2] [Dig In Term 3] [Dig In Term 4] [Dig In Term 5] [Dig In Term 6] [Dig In Term 7] [Dig In Term 8] [Dig In Term 9] [Dig In Term 10] [Dig In Term 11] [Dig In Term 12] [Inversion Out 4] [Inversion Out 5] [Inversion Out 6] [Inversion Out 7] [Inversion Out 8] [Inversion Relay1] [Inversion Relay2] [DPI P5 Select] 565 566 567 568 569 570 571 572 573 574 575 576 1270 1271 1272 1273 1274 1393 1275 1327
Digital Outputs
DPI Inputs
71
Benefits
Simplified installation and start-up by use of common options assembled at the factory. Drive functionality exceeds options offered with a standard drive. Multiple packaging options specific to customer needs. Pre-engineered options for easy order entry, consistent manufacturing, high quality and reduced delivery time. Selectable configurations to meet application requirements.
72
73
Communication Options The PowerFlex Configured DC drives are fully compatible with Allen-Bradley drives wide variety of DPI communication adapters, offering the following options.
Description ControlNet Communication Adapter (Coax) DeviceNet Communication Adapter EtherNet/IP Communication Adapter Interbus Communication Adapter LonWorks Communication Adapter PROFIBUS DP Communication Adapter ControlNet Communication Adapter (Fiber) Remote I/O Communication Adapter None Catalog No. C D E I L P Q R N
Cabinet Options The Configured Drive enclosure can be equipped with a variety of standard user option. These options are predefined as described below. Other options can be ordered through the ETO program.
Description None Start and Stop PBs Local/Remote SS E-Stop PB Jog Blower Motor Starter Options 1 & 2 Options 1 & 3 Options 1 & 4 Options 1 - 3 Options 1 - 4 Options 1 - 5 Options A & 4 Options A & 5 Options B & 4 Options B & 5 Catalog No. N 1 2 3 4 5 A B C D E F G H J K
74
Please contact your local distributor or sales office for product availability. Configured Drives offers Quick Ship and PreEngineered Programs.
Frame 2
JOG
PORT MOD NET A NET B
START
JOG
PORT MOD NET A NET B
START
STS
STS
LOCAL-REMOTE
STOP
LOCAL-REMOTE
STOP
SPEED
EMERG STOP
SPEED
EMERG STOP
75
JOG
PORT MOD NET A NET B
START
STS
LOCAL-REMOTE
STOP
SPEED
EMERG STOP
76
Specifications
Category Agency Certification Specification According to file E59272 for the series of the approved devices. In conformity with the following European Directives: EMC Directive (2004/108/EC) Low Voltage Directive (2006/95/EC) Standards applied: EN 50178: 1997 EN 61800-3: 2004 Australian Communications and Media Authority In conformity with the following: Radio communications Act: 1992 Radio communications Standard: 2008 Radio communications Labelling Notice: 2008 Standards applied: EN 61800-3:2004 The drive is also designed to meet the following specifications: NFPA 70 - US National Electrical Code Category Drive Type Protection Specification Full Wave Regen, 6 Pulse, Regulated Field Supply Heat Sink Thermistor: Monitored by microprocessor overtemp trip Drive Overcurrent Trip Software Overcurrent Trip: 200% of rated current (typical) Hardware Overcurrent Trip: 220-300% of rated current (dependent on drive rating) Line transients: Up to 2000 volts peak per IEC 6100-4-5 Control Logic Noise Immunity: Showering arc transients up to 1500V peak Power Ride-Thru: 15 milliseconds at full load Logic Control Ride-Thru: 0.5 seconds minimum, 2 seconds typical Ground Fault Trip: Phase-to-ground on drive output Short Circuit Trip: Phase-to-phase on drive output Altitude: 1000 m (3300 ft) max. without derating. De-rate output power by 1.2% for every 100 meters (328ft) above 1000 meters (3300ft). Maximum Surrounding Air 050 C (32122 F), typical. Temperature IP20, NEMA Type De-rate 1.25% for every 1 C over 50 C (122 F), to 55 C (131 F). Open: Additional cooling is required for temps. above 55 C. Storage Temp. (all const.): 25 to 55 degrees C (13 to 131 degrees F) Atmosphere: Important: Drive must not be installed in an area where the ambient atmosphere contains volatile or corrosive gas, vapors or dust. If the drive is not going to be installed for a period of time, it must be stored in an area where it will not be exposed to a corrosive atmosphere. Relative Humidity: Operating: 5 to 85% non-condensing Storage: 5 - 95% non-condensing Shock: 15G peak for 11ms duration (1.0 ms) Vibration: 0.152 mm (0.006 in.) displacement, 1G peak
Environment(1)
(1)
77
Control
78
DC Analog Tachometer
Inputs
Analog Inputs
Digital Inputs
Outputs
Analog Outputs
Digital Outputs
Relay Outputs
Type: Incremental, dual channel, two channel optional (with jumper), differential (recommended) or single-ended Input Voltage: Configurable for +2.5V - 5.2V (switch S21 in ENC_5 position) or +5.4V - 15.2V (switch S21 in ENC_12 position) Input Current: 4.5 mA / 6.8 - 10.9 mA each channel Quadrature: 90 27 @ 25 C Duty cycle: 50% 10% Source/Sink capable Pulses Per Revolution: 100 to 32770 Maximum Frequency: 150 kHz Maximum Cable Length: Shielded, 150m (0.75 mm2), 125m (0.5 mm2), 55m (0.22 mm2) Input Voltage: 22.7, 45.4, 90.7, 181.6, & 302.9V max. Input Current: 8 mA full scale Maximum Cable Length: Shielded, depends on the installation, typical 150m. Three configurable, isolated, differential 10V, 0-10V, 0-20mA or 4-20mA. Resolution: 11 Bit + sign Eight standard configurable, four additional configurable with the I/O Expansion circuit board. Max Voltage +30V DC input, 200mA (total current draw is the sum of encoder power, digital outputs and any other loads connected to terminal 19) Two standard configurable, two additional configurable with the I/O Expansion circuit board. Sampling rate 2 ms. 10V, 5mA, bipolar (current is not bipolar) Resolution: 11 Bit + sign Four standard configurable, four additional configurable with the I/O Expansion circuit board. + 30V, 50mA Two configurable, N.O. contacts Max. 250V AC, 1A AC1
79
Watts Loss
Watts loss data shown below is based on the rated current of the drive. Frame A Drives Watts Loss and Fan Capacity
Drive Current Rating Code(1) @ 230 VAC 7P0 9P0 012 020 029 038 055 073 093 110
(1)
@ 460 VAC 4P1 6P0 010 014 019 027 035 045 052 073 086 100 129
Fan Input Voltage (no fan) Rated Current Air Flow Capacity (m3/h)
186 254
80
160
Refer to Catalog Number Explanation on page 6, positions 8-10 for corresponding drive HP rating, armature amp rating and field amp rating.
Fans AC Input Voltage 230 Total Watts Loss 781 939 1038 1693 460 781 939 1038 1248 1693 Input Voltage Rated Current (Internal power supply) Air Flow Capacity (m3/h) 320
680 320
680
Refer to Catalog Number Explanation on page 6, positions 8-10 for corresponding drive HP rating, armature amp rating and field amp rating.
Refer to Catalog Number Explanation on page 6, positions 8-10 for corresponding drive HP rating, armature amp rating and field amp rating. (2) Fans on frames C drives must be powered by an external 230 V AC, 50/60 Hz power supply, connected to terminals U3 and V3.
80
575
690
Total Watts Loss 2694 3284 3200 3568 4189 5229 5117 3122 3819 4679 4879 5720 3174 3582 4028 4064 4509 5368 5543 5886
Refer to Catalog Number Explanation on page 6, positions 8-10 for corresponding drive HP rating, armature amp rating and field amp rating. (2) Fans on frames D drives must be powered by an external 230 V AC, 50/60 Hz power supply, connected to terminals U3 and V3.
81
Reference Materials
For additional PowerFlex DC data and general drive information, refer to the following publications:
Title PowerFlex Digital DC Drive User Manual A Global Reference Guide for Reading Schematic Diagrams Guarding Against Electrostatic Damage Preventive Maintenance of Industrial Control and Drive System Equipment Safety Guidelines for the Application, Installation and Maintenance of Solid State Control Publication Available Online at . . . 20P-UM001 100-2.10 8000-4.5.2 www.rockwellautomation.com/literature DRIVES-TD001 SGI-1.1
www.rockwellautomation.com
Power, Control and Information Solutions Headquarters
Americas: Rockwell Automation, 1201 South Second Street, Milwaukee, WI 53204-2496 USA,Tel: (1) 414.382.2000, Fax: (1) 414.382.4444 Europe/Middle East/Africa: Rockwell Automation, Vorstlaan/Boulevard du Souverain 36, 1170 Brussels, Belgium,Tel: (32) 2 663 0600, Fax: (32) 2 663 0640 Asia Pacific: Rockwell Automation, Level 14, Core F, Cyberport 3, 100 Cyberport Road, Hong Kong,Tel: (852) 2887 4788, Fax: (852) 2508 1846