You are on page 1of 22

C Sl.

No C DSR NO

INTERNAL ELECTRIFICATION WORKS Rate Description of Items total Qty Unit DSR NDSR DSR NDSR Amount (TOTAL)

HEAD: ELECTRICAL WORKS ELECTRICAL y, pp PANELS , g Non-sch commissioning of free standing, floor mounted indoor type, air insulated, totally enclosed vermin proof, dead front, compartmentalised, cubicle type, 2 mm thick sheet steel enclosure panel suitable for use on 415 V, 3 Ph.,4 wire, 50 Hz. A.C. system, incoming circuit breaker/ S F unit, high conductivity TP & N Aluminium bus bars, bus bar, risers, extended bus bars for cable connection, outgoing circuit breakers instrumental panel, C.Ts, outgoing feeder terminals and incoming cable compartment. The incoming and outgoing functional units shall be arranged in multi tier formation to provide a compact panel. Each unit shall be accommodated in a totally separate compartment having gasketted hinged door

C1

ELECTRICAL: Page 1

Sl. No

DSR NO

Description of Items total Qty with locking arrangement. The Panel shall be complete with switches/circuit breakers of following ratings, interconnection, G.I. earth bus bar of adequate size covering the total length of switch board with drilled holes, G.I. bolts, nuts, washers etc. The cubicle should be painted with two (2) coats of light grey synthetic enamel paint over two coats of zinc chromate primer. The complete fabrication, construction shall be done as per the detailed specification and conforming to the relevant IS. Short circuit interrupting current of all MCBs should be of 10 KA minimum. Name plate of Panels/DBs Danger Board, incoming and outgoing feeders with Ampere rating of switches/ MCCB/ MCB etc. are to be fixed up on front door above or below the respective switches. Approval of Manufacturer's drawings from Consultant/Employer is required before commencing manufacture and panel should be tested in the presence of Consultant/ Employer's engineer at Unit DSR NDSR DSR NDSR

ELECTRICAL: Page 2

Sl. No

DSR NO

Description of Items total Qty Unit DSR NDSR DSR NDSR

C1a

manufacturer's premises before dispatch to site. Non-sch MAIN POWER DISTRIBUTION BOARD Incoming : 415 V400 A 50 KA 4pole MCCB (Relay range 320-400 A) : 1 no. Multifunction meter to observe voltage/current/PF etc with sets of 400/5A CT's ete. As reqd 3 Nos. Phase Indicating lamp, 230 V 3nos. protective fuse : PVC SLEEVED TPN ALUMINIUM BUS BAR : 100 mm x 8 mm for phases & 50 mm x 6 mm for neutral. GI EARTH BUS BAR 25 mm x 6 mm covering the total length of panel. Outgoing : 4 Nos.415 V 200 A, 35KA 4 pole MCCB with relay range 160-200A. 1 Nos.415 V 100 A, 25KA 4 pole MCCB with relay range 80-100A. 4 Nos.415 V 63 A, 25KA 4 pole MCCB with relay range 50-63A.

0.00 1.00 No 350,000.00

350,000.00

C1a

Non-sch MAIN POWER DISTRIBUTION BOARD Incoming : 415 V400 A 50 KA 4pole MCCB (Relay range 250-320 A) : 1 no. Multifunction meter to observe voltage/current/PF etc with sets of 300/5A CT's ete. As reqd 3 Nos. Phase Indicating lamp, 230 V 3nos. protective fuse :

ELECTRICAL: Page 3

Sl. No

DSR NO

Description of Items total Qty PVC SLEEVED TPN ALUMINIUM BUS BAR : 75 mm x 8 mm for phases & 50 mm x 6 mm for neutral. GI EARTH BUS BAR 25 mm x 6 mm covering the total length of panel. Outgoing : 4 Nos.415 V 125 A, 35KA 4 pole MCCB with relay range 100-125A. Unit DSR NDSR DSR NDSR

0.00 1.00 208,600.00

208,600.00

C1b

Non-sch MAIN LIGHT DISTRIBUTION BOARD Incoming : 415 V100 A25 KA 4pole MCCB (Relay range 80-100 A) : 1 no. 125A 4 pole 415V on load change over switch-1no Multifunction meter to observe voltage/current/PF etc with sets of 100/5A CT's ete. As reqd 3 Nos. Phase Indicating lamp, 230 V 3nos. protective fuse : PVC SLEEVED TPN ALUMINIUM BUS BAR : 40 mm x 6 mm for phases & 25 mm x 6 mm for neutral. GI EARTH BUS BAR 25 mm x 6 mm covering the total length of panel. Outgoing : 9 Nos.415 V 63 A, 10KA 4 pole MCB 1 Nos.415 V 32 A, 10KA 4 pole MCB

1.00

No

108,000.00

0.00

108,000.00

ELECTRICAL: Page 4

Sl. No C1c

DSR NO

Description of Items total Qty Unit DSR NDSR DSR NDSR

Non-sch SUB MAIN POWER DISTRIBUTION BOARD (SMPDB) Incoming : 415 V 200 A 35 KA 4pole MCCB (Relay range 160-200 A) : 1 no. Multifunction meter to observe voltage/current/PF etc with sets of 200/5A CT's ete. As reqd 3 Nos. Phase Indicating lamp, 230 V 3nos. protective fuse : PVC SLEEVED TPN ALUMINIUM BUS BAR : 50 mm x 8 mm for phases & 25 mm x 6 mm for neutral. GI EARTH BUS BAR 25 mm x 6 mm covering the total length of panel. Outgoing : 5 Nos.415 V 100 A, 25KA 4 pole MCCB with relay range 125-160A. 1 Nos.415 V 63 A, 25KA 4 pole MCCB with relay range 50-63A.

0.00 3.00 No 169,000.00

507,000.00

C1b

Non-sch Area Lighting DB The Road Lighting DB consists of the following : Incoming : 1 no. 32A TPN MCB Outgoing : 6 no. 16A/20A SP MCB 1 no. time switch.( DAILY) 1 no. 3 pole power contactor 40A 1 set 4 pole 60A Al Bus Bar complete with all interconnection

1.00

No

21,584.00

0.00

21,584.00

ELECTRICAL: Page 5

Sl. No C2

DSR NO

Description of Items total Qty Unit DSR NDSR DSR NDSR

a b

SUPPLYgAND FIXING OF TPNgMCB DB pp y g y 2.33 sheet steel MCB distribution board, 415V TPMCB on surface/ recessed, complete with DB tinned copper Bus bar, neutral link, earth bar, din bar, detachable grand plate, interconnections, phosphatized powder painted including earthing etc. as required.(but without MCB/ RCCB/ Isolator) 2.33.1 4 way (4+12, single door horizontal type) 2.33.2 6 way (4+18, single door horizontal type) 2.35 Suppling, installation, testing and VTTPM commissioning of surface/ recessed CBDB mounting, vertical type, 415V, TPNMCB Distribution board of sheet steel, dust protected, duly phophatised and powder painted, inclussive of 200A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's, detachable gland/ Knock out plate, and with 100A 10Ka MCCB as incomer, interconnection between incomer MCCB and Busbars of following ways (but with out MCBs) as required. 2.35.2 8 way with 100A MCCB as incommer SUPPLY AND FIXING CONSUMER UNIT OF SPN 1.00 nos 959.00 8.00 nos 820.00

6,560.00 959.00

0.00 0.00

56,848.00 16.00 no 3,553.00

0.00

ELECTRICAL: Page 6

Sl. No C3

DSR NO

Description of Items total Qty Unit DSR NDSR DSR NDSR

a b

C4

Supplying and fixing of following way SPN 2.32 SPMCB sheet steel MCB distribution board DBCO consumer unit, 240V on surface/ recessed, complete with tinned copper Bus bar, neutral link, earth bar, din bar, hinged front acrylic cover for the MCB knobs, detachable grand plate, interconnections, phosphatized and powder painted including painting, earthing etc. as required.(but without MCB, RCCB, Isolator). 2.32.1 2+4 way 2.32.2 2+8 wat SUPPLY AND FIXING OF 5A to 32A L series MCB: 2.52 MCBC Supplying and fixing 5amps to 32 amps rating 240V, 'C' series, MCB suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Category B) 2.52.1 2.52.3 Single Pole Triple pole

1.00 4.00

each each

559.00 654.00

559.00 2,616.00

0.00 0.00

a B

342.00 74.00

each each

94.00 383.00

32,148.00 28,342.00

0.00 0.00

C5

S/F DP MCB ISOLATOR 2.54 MCBDP Supply and fixing following rating double IS pole 240V, isolator in the existing MCB DB complete with connections, testing and commissioning etc as required. 2.54.1 40A

5.00

each

166.00

830.00

0.00

ELECTRICAL: Page 7

Sl. No C6

DSR NO

Description of Items total Qty Unit DSR NDSR DSR NDSR

2.55 MCBTP S/F TP MCB ISOLATOR IS Supply and fixing following rating 4 pole 400V, isolator in the existing MCB DB complete with connections, testing and commissioning etc as required. 63 A

2.55.2 C7

12.00

each

362.00

4,344.00

0.00

a b c

nonProviding and fixing G.I. pipes complete schedul with G.I. fittings if required including e trenching and refilling etc.for cable protection 50 mm dia. Nominal bore 100 mm dia. Nominal bore 150 mm dia. Nominal bore DISTRIBUTION CABLE : SUPPLYING OF CABLE : Supplying, Transportation & handling of nonschedul 1.1 KV grade XLPE insulated and PVC sheathed armoured aluminium conductor e cable of following size conforming of IS:1554 (Part-I) : 2 core 10 sq.mm. PVCA Al. Cable. 4 core 16 sq.mm. PVCA Al. Cable. 4 core 10 sq.mm. PVCA Al. Cable. 3.5 core 300 sq.mm. PVCA Al. Cable. 3.5 core 35 sq.mm. PVCA Al. Cable. 3.5 core 150 sq.mm. PVCA Al. Cable. 3.5 core 70 sq.mm. PVCA Al. Cable. 3.5 core 50 sq.mm. PVCA Al. Cable.

8.00 8.00 26.00

meter meter meter

450.00 1,100.00 1,600.00

0.00 0.00 0.00

3,600.00 8,800.00 41,600.00

C8

a b c d e f g

100.00 100.00 90.00 60.00 300.00 40.00 60.00 150.00

meter meter meter meter meter meter meter meter

215.00 330.00 263.00 2,890.00 497.00 1,490.00 827.00 697.00

0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

21,500.00 33,000.00 23,670.00 173,400.00 149,100.00 59,600.00 49,620.00 104,550.00

ELECTRICAL: Page 8

Sl. No C9

DSR NO

Description of Items total Qty Unit DSR NDSR DSR NDSR

1.1 MVCBG MV Cable Laying upto 25sqmm in ground: R25 10,200.00 Laying of 1 no. PVC insul and PVC sheathed / XLPE cable of 1.1 KV grade size not exceeding 25sqmm, direct in ground including excavation, sand cousioning, protective covering and refilling the treanch etc as required. 120.00 0.00

meter

85.00

C10

C11

1.2 MVCBG MV Cable Laying upto 120 sqmm in ground: R120 Laying of 1 no. PVC insul and PVC sheathed / XLPE cable of 1.1 KV grade size exceeding 25sqmm but not exceeding 120 sqmm, direct in ground including excavation, sand cousioning, protective covering and refilling the treanch etc as required. MV Cable Laying upto 400 sqmm in ground: 1.3 Laying of 1 no. PVC insul and PVC MVCBG sheathed / XLPE cable of 1.1 KV grade R400 size exceeding 120sqmm but not exceeding 400 sqmm, direct in ground including excavation, sand cousioning, protective covering and refilling the treanch etc as required.

6,825.00

0.00

75.00

meter

91.00

5,820.00

0.00

60.00

meter

97.00 0.00 5,890.00 0.00 0.00

Laying and fixing of 1 no PVC insulated 1.11 and PVC sheathed/ XLPE aluminium MVCBS conductor cable of 1.1 KV grade of size UR 25 not exceeding 25sqmm on surface as required. 190.00

meter

31.00

ELECTRICAL: Page 9

Sl. No

DSR NO

Description of Items total Qty Unit DSR NDSR DSR 25,665.00 NDSR 0.00

1.12 Laying and fixing of 1 no PVC insulated MVCBS and PVC sheathed/ XLPE aluminium UR 120 conductor cable of 1.1 KV grade of size exceeding 25sqmm but not exceeding 120sqmm on surface as required. 435.00 1.13 Laying and fixing of 1 no PVC insulated MVCBS and PVC sheathed/ XLPE aluminium UR 400 conductor cable of 1.1 KV grade of size exceeding 120sqmm but not exceeding 400sqmm on surface as required. BASS COMPRESSION GRAND C12 4.1 MVET S/M LV/MV cable end termination Supplying and making end termination with brass compression grand and aluminium lugs for following sizes of PVC insulated and PVC sheathed/ XLPE aluminium conductor cable of 1.1 KV grade as required. 2 x 10 sqmm 4 x 10 sqmm 4 x 16 sqmm 3.5 x 150 sqmm 3.5 x 300 sqmm 3.5 x 35 sqmm 3.5 x 70 sqmm 3.5 x 50 sqmm

meter

59.00 2,440.00 0.00

40.00

meter

61.00

a b C12 d e

C14

4.1.2 4.1.32 4.1.33 4.1.26 4.1.30 4.1.21 4.1.23 4.1.22 1.5 WGSTL Power Plug wiring in steel conduit (2 x 4 sqmm) PP2

14.00 16.00 10.00 6.00 2.00 26.00 2.00 9.00

each each each each each each each each

76.00 104.00 196.00 278.00 508.00 137.00 168.00 146.00

1,064.00 1,664.00 1,960.00 1,668.00 1,016.00 3,562.00 336.00 1,314.00

0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00

ELECTRICAL: Page 10

Sl. No

DSR NO

Description of Items total Qty Wiring for light/ power plug with 2x4sqmm FRPVC insulated copper conductor single core cable in surface/ recessed steel conduit along with 1 no 4sqmm FRPVC insulated copper conductor single core cable for loop earthing as required. 2600.00 (For Lab equipment power plug wiring) Unit DSR NDSR DSR 353,600.00 NDSR 0.00

meter

136.00

C15

1.14 WGPV Circuit/ submain wiring in PVC conduit CSB Wiring for circuit / submain wiring along with earth wire with the following sizes of FRPVC insulated copper conductor, single core cable in surface/ recessed in conduit as required. 1900.00 1.14.1 2 x1.5 sqmm + 1x 1.5sqmm earth wire (Circuit wiring) 750.00 1.14.1 2 x1.5 sqmm + 1x 1.5sqmm earth wire (6amp plug wiring) 1500.00 1.14.3 2 x4 sqmm + 1x 4sqmm earth wire 10.00 1.14.4 2 x6 sqmm + 1x 6sqmm earth wire 5.00 1.14.9 4 x 4 sqmm + 2x 4 sqmm earth wire 5.00 1.14.10 4 x 6 sqmm + 2x 6 sqmm earth wire 1.7 WGSTL Circuit/ submain wiring in Steel conduit SB Wiring for circuit / submain wiring along with bearth wire with the following sizes of FRPVC insulated copper conductor, single core cable in surface/ recessed in conduit as required. 4 x 4 sqmm + 2x 4 sqmm earth wire 1250.00 1.7.9 (For Lab equipment power plug wiring)

a b c d e f C15

meter meter meter meter meter meter

71.00 71.00 97.00 127.00 148.00 207.00

134,900.00 53,250.00 145,500.00 1,270.00 740.00 1,035.00

0.00 0.00 0.00 0.00 0.00 0.00

meter

190.00

237,500.00

0.00

ELECTRICAL: Page 11

Sl. No a b

DSR NO 1.7.1 1.7.1 1.7.10

Description of Items total Qty 300.00 350.00 550.00 Unit meter meter meter DSR 109.00 109.00 258.00 NDSR DSR 32,700.00 38,150.00 141,900.00 NDSR 0.00 0.00 0.00

2 x1.5 sqmm + 1x 1.5sqmm earth wire (Circuit wiring) 2 x1.5 sqmm + 1x 1.5sqmm earth wire (6amp plug wiring) 4 x 6 sqmm + 2x 6 sqmm earth wire

10 A LIGHT PLUG POINT WIRING ON BOARD C16 nonschedul Wiring for 10 A light plug point on board with 1100 e volt grade single core 3 Nos.1.5 sq. mm (1 green colour for earth) PVC insulated flexible copper conductor cable (IS:694) complete with providing and fixing of 10 A 3 pin socket on switch board and 10 A switch, earthing the 3rd pin, etc. as required With Modular Switch and approved coloured plate 97.00 POINT WIRING FOR LIGHT, FAN, ETC. : nonWiring for light/ ceiling fan / exhaust fan/ schedul call bell point with 2x 1.5 sq.mm PVC e insulated copper conductor cable in surface/ recessed PVC conduit as required. With 10A Modular Switch and approved colour plate (primary point) 500.00 300.00 Secondary point without switch

0.00 Point 698.00

67,706.00

C17

a b

0.00 Point Point 895.00 666.00 0.00

447,500.00 199,800.00

ELECTRICAL: Page 12

Sl. No C17

DSR NO

Description of Items total Qty Unit DSR NDSR DSR NDSR

a b

nonWiring for light/ ceiling fan / exhaust fan/ schedul call bell point with 2x 1.5 sq.mm PVC e insulated copper conductor cable in surface/ recessed steel conduit as required. With 10A Modular Switch and approved colour plate (primary point) 100.00 55.00 Secondary point without switch 2.62 MCBDP Supply and fixing 20A 240V SPN SOC20 Industrial type, socket outlet, with 2 pole and earth metal enclosed plug top along with 20A C series SPMCB, in sheet steel enclosure, on surface or in recessed, with chained metal cover for the socket outlet and complete with connection, testing and commissioning etc as required. 2.64 MCBTP Supply and fixing 30A, 415V , TPN SOC30 Industrial type, socket outlet, with 4 pole and earth metal enclosed plug top along with 30A C series TPMCB, in sheet steel enclosure, on surface or in recessed, with chained metal cover for the socket outlet and complete with connection, testing and commissioning etc as required. nonSupply and fixing power unit consisting schedul 20A starter, 25A socket, 25A plug top with e 4 module plate and box complete as required. SUPPLY & FIXING OF 16 A SOCKET OUTLET & SWITCH :

0.00 Point Point 996.00 767.00 0.00 7,800.00

99,600.00 42,185.00 0.00

15.00

each

520.00 23,292.00 0.00

18.00

each

1,294.00 0.00 16,100.00

14.00

each

1,150.00

ELECTRICAL: Page 13

Sl. No C18

DSR NO

Description of Items total Qty Unit DSR NDSR DSR NDSR

C19

Supply and fixing of 16 A socket outlet nonwith 16A controlling switch, mounting box schedul and front cover on wall surface or e recessed in wall complete with chase cutting, making good all damages to original finish, interconnection, painting, etc. as required to be completed in all respect. With Modular Switch/ socket and approved coloured plate. 30.00 SUPPLY & FIXING OF 10/6 A SOCKET OUTLET & SWITCH : nonschedul Supply and fixing of 10/6 A socket outlet with e controlling switch, mounting box and front cover on wall surface or recessed in wall complete with chase cutting, making good all damages to original finish, interconnection, painting, etc. as required to be completed in all respect. With Modular Switch/ socket and approved coloured plate. 132.00

0.00 No. 941.00

28,230.00

0.00 No. 711.00

93,852.00

ELECTRICAL: Page 14

Sl. No C20

DSR NO

Description of Items total Qty Unit DSR NDSR DSR NDSR

nonSupply and fixing of 16/13/10 A combined schedul socket outlet with the following i.e. (a) 1no e 16A controlling switch with 16/10A socket, (b) 1no 16A switch & 1no 13A universal socket and ( c) 1no 10A switch & 10A socket outlet, in single modular mounting box and front cover on wall/ table surface or recessed in wall complete with chase cutting, making good all damages to original. finish, interconnection, painting, etc. as required to be completed in all respect. With Modular Switch/ socket and approved coloured plate. Supplying & Installation of surface nonschedul mounted Industrial type luminior with stove enamelled reflector 2x36W T8 eqv e WIPRO cat no WCF 26236 SWG, suspended with required length of 2x 20mm dia painted MS conduit complete with clamping arrangement as required, . nonschedul Supplying & Installation of recessed type integral low bay luminiar simillar to e WIPRO cat no WHH91070 with 1x 70W MHL (double ended) fixed in metal false ceiling/ cladding complete as required. .

0.00 54.00 no 2,109.00 0.00

113,886.00

C21

322,470.00

90.00

nos

3,583.00 0.00 95,650.00

C21

10.00

nos

9,565.00 0.00 438,496.00

C21

Supplying & Installation of surface nonmounted mirror optic luminior with schedul 2x14wT5 eqv. PHILIPS cat no TCS e 350/214 MI HF. 142.00

nos

3,088.00

ELECTRICAL: Page 15

Sl. No C22

DSR NO

Description of Items total Qty Unit DSR NDSR DSR 0.00 82.00 nos 3,697.00 0.00 104,400.00 NDSR 303,154.00

C25

C26

C27

C28

C29

C30

C31

C32

C33

Supplying & Installation of surface nonmounted mirror optic luminior with 2xTL5 schedul 28W PHILIPS cat no TCS 350/228 MI e HF. nonSupplying & Installation of surface schedul mounted mirror optic lumeniar with e paralite P5 louvers complete with 2x36w CFL eqv. WIPRO cat no. WVP 44236. Supplying & Installation of recessed nonschedul mounted mirror optic lumeniar with paralite P5 louvers complete with 2x36w e CFL eqv. WIPRO cat no. WVP 24236. Supplying & Installation of wall mounted nonschedul decorative lumeniar with cylindrical diffuser including 1x8W CFL eqv. cat e no.CITY-1 of Havells wall mounting range. Supplying & Installation of recessed nonschedul mounted ceiling decorative lumeniar with diffuser including 1x55 W 2D lamp eqv. e cat no.CASPER of Havells. Supplying & Installation of recessed nonlight low depth schedul mounted ceiling downlighter with fresnel lens and 2 x 18W e CFL eqv. WIPRO WCP 28218. Supplying & Installation of slim energy nonschedul saving tube fitting with 1x 28W FTL(T5) eqv. WIPRO cat no. WIF 21128 SWG e Supplying & Installation of slim energy nonschedul saving tube fitting with 2x 28W FTL(T5) eqv. WIPRO cat no. WIF 21228 APF e Supplying & Installation of bulk head fitting nonschedul with 1x 9W PL-S Lamp eqv. Philips FXC/101. e Supplying & Installation of decobattens nonschedul with 1x 14 w(T5) TLS eqv. Philips TWG 207 1x14w TLSHF e

18.00

nos

5,800.00 0.00 199,800.00

36.00

nos

5,550.00 0.00 5,610.00

6.00

nos

935.00 0.00 23,070.00

2.00

nos

11,535.00 0.00 123,240.00

65.00

nos

1,896.00 0.00 120,770.00

65.00

nos

1,858.00 0.00 46,900.00

14.00

nos

3,350.00 0.00 2,380.00

2.00

nos

1,190.00 0.00 955.00

1.00

nos

955.00

ELECTRICAL: Page 16

Sl. No C34

DSR NO nonschedul e nonschedul e

Description of Items total Qty Unit DSR NDSR DSR 0.00 1.00 nos 1,200.00 0.00 410,970.00 NDSR 1,200.00

Supplying & Installation of decobattens with 1x 28 w(T5) TLS eqv. Philips TWG 207 1xTLS28wHF Supplying & Installation of decorative surface mounted circular fitting with 2 x 18W CFL ( THORN cat no. ORBITLITE S CORS 218 (E) or equivant. Supplying & Installation of Out door nonschedul luminiar suitable for 70W (I) HPSV lamp integral Translucent of KLITE ID 6831 with e 10' long Colombia pole complete with all asseccories of Metal Coat ID No. 6005. Supplying & Installation Emergency light nonschedul with 8W PL lamp and one hour battery backup Cat no. 617 31/617 87 G5NM of e Legrand 1.42 ITC fluroscent fitting with down rods and ITCFFD copper wiring: Installation, testing and commissioning of prewired, flourescent R fittings of all types complete with all accessories and tube etc. including supply and fixing ball and socket arrangement, 2nos. down rods of 20mm dia x 1.6mm thick steel conduit upto 30cm. length painting and wiring the down rod and connection with 1.5sqmmfFR PVC insulated Cu conducter single core cable and earthing etc. as required.

70.00

nos

5,871.00 0.00 199,200.00

12.00

16,600.00 0.00 86,020.00

11.00

nos

7,820.00 25,200.00 0.00

C38

200.00

Each

126.00

ELECTRICAL: Page 17

Sl. No C39

DSR NO

Description of Items total Qty Unit DSR NDSR DSR 1,075.00 NDSR 0.00

C40

1.41 ITC fluroscent fitting directly on surface ITCFFS with copper wiring: Installation, testing and UR commissioning of prewired, flourescent fittings of all types complete with all accessories and tube etc. directly on ceiling/wall including connections with 1.5 sq.mm FR PVC insulated, copper conductor, single core cable and earthing etc. as required 25.00 1.43 P/F extra down rod with copper wiring: EXTDR Providing and fixing extra conduit down rod of 20 mm dia. 2 X 10 cm length with 2 X 1.5 sq.mm FR PVC insulated , copper conductor , single core cable including painting etc. as required (Note: more than 5 cm length shall be rounded to the nearest 10 cm. and 5 cm. or less shall be 250.00 ignored) nonschedul e nonschedul e nonschedul e nonschedul e nonschedul e Supply of 1200 AC ceiling fan of Delux model quality, complete as required.

Each

43.00 4,250.00 0.00

Each

17.00 0.00 92,988.00

C41

42.00

no

2,214.00 0.00 595,200.00

Supply of 1400 AC ceiling fan of Delux model quality, complete as required. 248.00 Supply of 300mm dia Metal body Exhaust fan with louvers. Supply of 450mm dia Metal body heavy duty Exhaust fan with louvers. Supply and installing 400mm dia with rotating head wall bracket fan suitable for 240 V AC supply.

no

2,400.00 0.00 97,152.00

C42

32.00

no

3,036.00 0.00 56,160.00

12.00

no

4,680.00 0.00 27,950.00

C43

13.00

no

2,150.00

ELECTRICAL: Page 18

Sl. No C44

DSR NO nonschedul e 1.44 ITCCF

Description of Items total Qty Unit DSR NDSR DSR 0.00 no 500.00 13,050.00 0.00 NDSR 145,000.00

C45

C46

C47

Supply and fixing 2 module ceiling fan regulator in the existing switch plate as required. 290.00 I T C of ceiling fan including wiring the down rods of standard length (upto 30cm) with 1.5 sqmm FRPVC insulated copper conductor single core cable etc as required, upto 450mm sweep in the existing opening, including making the hole to suit the size of the above fan, making good the damage, connections, testing, commissioning etc. as required. 290.00 1.52 Installation of exhaust fan upto 450mm ITCEF4 sweep in the existing opening, including making the hole to suit the size of the 50 above fan, making good the damage, connections, testing, commissioning etc. as required. 44.00 1.54 Fixing louvres /shutters for exhaust LOUSH fan:Extra for fixing the louvres /shutters complete with frames for exhaust fans of EF all sizes 44.00

Each

45.00 9,812.00 0.00

Each

223.00 2,860.00 0.00

Each

65.00 3,888.00 0.00

C48

C49

Providing and fixing of lightning conductor 4.2 LCFGI finial, made of 25mm dia, 300mm long GI tube, having single prong at top, with 85mm dia 6mm thick GI base plate including holes etc. complete as required. 16.00 Providing and fixing GI tape 20mm x3mm 4.7 LCGITS thick on parapet or surface of wall for URH lightning conductors as required ( for horizontal run) 500.00

each

243.00 15,500.00 0.00

meter

31.00

ELECTRICAL: Page 19

Sl. No C50

DSR NO

Description of Items total Qty Unit DSR NDSR DSR 8,600.00 NDSR 0.00

C51

C52

C53

Providing and fixing GI tape 20mm x3mm 4.8 LCGITS thick on parapet or surface of wall for URV lightning conductors as required ( for verticall run) 200.00 4.12 Providing and fixing testing joints, made of LCTJGI 20mm x 3mm thick GI strip, 125mm long with 4 Nos of GI bolts nuts check nuts and spring washer complete as required. 8.00 GI Earth Plate Electrode : Earthing with GI 3.5 EARGIP plate 600mm x 600mm x 6mm thick including accessories and providing L masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal or coke and 14.00 salt complete) as required. Salt /charcoal for plate earth electrode: 3.7 EARCH Extra for using charcoal and salt for G.I. copper plate earth electrode as required ARPL 14.00 3.10 Supply & Laying of 6 SWG GI wire at EAR6G 0.5meter below ground level / along cable GIWR thru pipe for conductor earth electrode including soldering etc s required. 400.00

meter

43.00 296.00 0.00

each

37.00 22,190.00 0.00

set

1,585.00 8,442.00 0.00

set

603.00 6,400.00 0.00

meter

16.00

ELECTRICAL: Page 20

Sl. No

DSR NO

Description of Items total Qty Unit DSR NDSR DSR 0.00 NDSR 2,070,000.00

Providing, Installation, Testing and Commissioning of Otis or equivalent make Electric Traction Passenger Elevator of 10 person (680 Kgs) capacity Elevators, traveling from ground floor to third floor (4 stops, 4 opening,) stopped at all floor and opening on the same side, 1 m/s speed, AC varable voltage variable frequency ( with close loop) controlled, simplex full collective, automatic with ACVVVF door operator & multi-ray door detector system, stainless steel hair finished car and car door, etc complete ( Otis model code No. OPTIMUS-7C10A-7-18M) as per specification and instruction of Engineer in charge. The work also include all building/ structural works for supporting arrangement system, necessary scaffolding required for erection of the complete system, necessary wiring and installation of lighting for lift well and lift pit, providing ladder in the lift pit etc. as C55 NonSupply, installation, testing & schedule commissioning of Hi wall split unit with outdoor unit, Indoor Unit, refrigeration pipe of required length (with insulation as required), PVC drainout pipes of required length, electrical starter unit with necessary wiring etc. complete as per instruction of engineer-in-charge. The rate shall be inclussive of the cost of supporting system of the outdoor unit. a 2.0 TR

1.00

each

2,070,000.00

12.00

each

45,000.00

0.00

540,000.00

ELECTRICAL: Page 21

Sl. No b

DSR NO 1.5 TR

Description of Items total Qty 2.00 Unit each DSR NDSR 42,000.00 DSR 0.00 Rs. 1,495,830.00 Rs. 2,587,785.90 Rs. 9,165,218.00 NDSR 84,000.00

SUB-TOTAL (DSR)
Cost after index

SUB-TOTAL (NON-SCH)

ELECTRICAL: Page 22