Measurement of electrical characteristics

This document is a translation from German. In case of doubt, the German text shall prevail. Document published in electronic form. Signed original at Central Engineering/ENS. Nordex Energy GmbH, Bornbarch 2, D-22848 Norderstedt All rights reserved. Observe protection notice ISO 16016.

Enclosure A:

Excerpt of the report WICO 115NV505/02

Measurements of power quality characteristics of grid connected Wind Turbine Generator System (WTGS) Nordex N90/2500 LS
according to IEC 61400-21

Page 1/5

WICO 115NV505/02, 2005-12-02, Enclosure A

REPORT ON RESULTS OF WIND TURBINE POWER QUALITY TESTS

The reported characteristics are valid for the specific configuration of the assessed wind turbine only. Other configurations, including altered control parameters, that cause the wind turbine to behave differently with respect to power quality, require separate assessment. Name of test organisation WIND-consult GmbH Reuterstrae 9 D-18211 Bargeshagen WICO 115NV505/02 N90/2500 LS Nordex Energy GmbH Bornbarch 2 D-22848 Norderstedt 8047

Report Number Wind Turbine type designation Wind Turbine manufacturer

Serial number of wind turbine tested

The wind turbine identified above has been tested in accordance with IEC 61400-21. This test report is accompanied by the documents specified below. Type of information Description of the tested wind turbine, Including settings of control parameters Description of test site and grid connection Description of test equipment Description of test conditions Note of exceptions to IEC 61400-21 Author Inspection Date of issue Document name and date Manufacturers certificate, 2005-11-30 WICO 115NV505/02, 2005-12-02 WICO 115NV505/02, 2005-12-02 WICO 115NV505/02, 2005-12-02 WICO 115NV505/02, 2005-12-02 Dipl.-Ing. M. Hickisch Dipl.-Ing. D. Wstenberg 2005-12-02

Characteristic parameters that are determined otherwise than outlined in IEC 61400-21 are marked. This includes parameters that are calculated instead of measured. The document(s) with exceptions to IEC 61400-21 describes the alternative procedure(s) that have been applied. The resulting characteristic parameters are stated below. Author Inspection

Dipl.-Ing. M. Hickisch

Dipl.-Ing. D. Wstenberg Bargeshagen, 2005-12-02

(This document is signed electronically.)


No part of this form may be reproduced in any means without permission of the publisher.

Page 2/5

WICO 115NV505/02, 2005-12-02, Enclosure A

1.

General data horizontal 3 90 Pitch 9,6 16,9 asynchronous, 2500 IGBT

Wind turbine type (horizontal/vertical axis) Number of blades Rotor diameter (m) Blade control Speed control (rpm) Generator type and ratings (kW) Frequency converter type

2.

Rated data 2500 14 2500 2187 660

Rated power, Pn (kW) Rated wind speed, vn (m/s) Rated apparent power, Sn (kVA) Rated current, In (A) Rated voltage, Un (V)

3.

Maximum permitted power 2750 1.10

Assessed value, Pmc (kW) * Normalised value, pmc = Pmc/ Pn *


*30 second average value

4. Maximum measured power 4.1 60-second-average value Measured value, P60 (kW) Normalised value, p60 = P60/ Pn 2516 1.01

4.2 0,2-second-average value Measured value, P0,2 (kW) Normalised value, p0,2 = P0,2/ Pn 2637 1.05

No part of this form may be reproduced in any means without permission of the publisher.

Page 3/5

WICO 115NV505/02, 2005-12-02, Enclosure A

5.

Reactive power Output power (kW)


0.0 250.0 500.0 750.0 1000.0 1250.0 1500.0 1750.0 2000.0 2250.0 2500.0

Output power (% of Pn) 0 10 20 30 40 50 60 70 80 90 100

Reactive power (kVAr)


6.3 6.7 6.6 5.7 4.7 4.5 3.8 3.4 3.5 3.4 1.6

Assessed reactive power at Pmc (kVAr) Assessed reactive power at P60 (kVAr) Assessed reactive power at P0,2 (kVAr)

0.8 2.8 -0.4

6. 6.1

Voltage fluctuations Continuous operations 30 3 3 3 3 50 70 Flicker coefficient, c( 3 2 3 2 3 2 3 2 85


ks

Network impedance phase angle, k (deg.) Annual average wind speed, va (m/s) 6,0 7,5 8,5 10,0

va) 2 2 2 2

6.2

Switching operations Start-up at cut-in wind speed 1 10 30 50 70 85 0.1 0.1 0.1 0.1 0.2 0.1 0.1 0.0

Case of switching operation Max. number of switching operations, N10* Max. number of switching operations, N120* Network impedance phase angle, k (deg.) Flicker step factor, Kf ( k) Voltage change factor, Ku ( k)

Case of switching operation Max. number of switching operations, N10* Max. number of switching operations, N120* Network impedance phase angle, k (deg.) Flicker step factor, Kf ( k) Voltage change factor, Ku ( k) * Note:

Start-up at rated wind speed 1 1 30 50 70 85 0.1 0.1 0.1 0.1 0.9 0.7 0.4 0.1

The maximum number of switching operations, N10 and N120, is based on manufacturers information.
No part of this form may be reproduced in any means without permission of the publisher.

Page 4/5

WICO 115NV505/02, 2005-12-02, Enclosure A

7.

Harmonics

Order 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26

Output power (kW) 1174 301 959 2506 2500 2506 2527 1361 1128 1641 1650

Harmonic Order current (% of In) 0.45 27 0.29 28 0.70 29 1.22 30 0.32 31 0.24 32 0.16 33 0.11 34 0.15 35 1.51 36 < 0,1 37 0.45 38 < 0,1 39 < 0,1 40 < 0,1 41 < 0,1 42 < 0,1 43 < 0,1 44 < 0,1 45 < 0,1 46 < 0,1 47 < 0,1 48 < 0,1 49 < 0,1 50 < 0,1

Output power (kW)

789

Harmonic current (% of In) < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 < 0,1 0.13 < 0,1 < 0,1

Maximum total harmonic current distortion (% of In) Output power at maximum total harmonic current distortion (kW)

1.38 1704

No part of this form may be reproduced in any means without permission of the publisher.

Page 5/5