TheNYCDepartmentofBuildingsisaregisteredProviderwithThe AmericanInstituteofArchitectsContinuingEducationSystems(AIA/ CES).Creditearnedoncompletionofthisprogramwillbereportedto AIA/CESforAIAmembers.CertificatesofCompletionforboth membersandnonAIAmembersareavailableuponrequest. ThisprogramisregisteredwiththeAIA/CESforcontinuing professionaleducation.Assuch,itdoesnotincludecontentthatmay bedeemedorconstructedtobeanapprovalorendorsementbythe AIAofanymaterialofconstructionoranymethodormannerof handling,using,distributing,ordealinginanymaterialorproduct. Questionsrelatedtospecificmaterials,methods,andserviceswillbe addressedattheconclusionofthispresentation.
CourseObjectives
Participantswillbeabletolearnfireprotection requirementsforhighrisebuildings Participantswillbeabletoassessspecial requirementsforegressinhighrisebuildings Participantswillbeabletonavigatethecodewith respecttospecialuseandoccupancies Participantswillunderstandrecentlyenactedlocal lawsthataffectsafetyduringhighriseconstruction ofhighrisebuildings
TodaysAgenda
Participantswillbeabletounderstandthespecialfire protectionsystemsrequiredforhighrisebuildings Participantswillbeabletoidentifytheegress provisionsofthecodeforhighrisebuildings Participantswillbeabletoapplythestructural integrityprovisionsforhighrisebuildingsbasedupon occupancyandseismicimportance Participantswillbeableunderstandthechangesto theInternationalCodesforhighrisebuildingsand therelationshipbetweentheNewYorkCitycodeand theInternationalCode
InternationalCodeCouncil
NYChasadoptedtheInternationalCode Councilbodyofconstructioncodes NYCisanactiveparticipantinthecode developmentprocess
HighRiseBuildings SpecificallyaddressedinsectionBC403
Definedashavingoccupiedfloorslocated morethan75feetabovethelowestlevel offiredepartmentvehicleaccess
HighRiseBuildings
AverageCurbElevation LowestLevelofFDVehicleAccess
75ft
75ft
75ft
1968Code: 2008Code:X
1968Code: 2008Code:
75ft
AutomaticSprinklerSystems
Requiredinallbuildingswithfloors>55feetin heightandwithanoccupantload>30 Requiredinallhighrisebuildingsregardlessof occupantload(asdefinedinBC403)
FireDetection&FireAlarms
Highrisebuildingsarerequiredtobe providedwith: Automaticfiredetectionconnectedto automaticfirealarmsystem Emergencyvoice/alarm communicationsystem
VoiceCommunicationSystems
VoiceCommunicationSystems
FireCommandCenter
RequiredinALL highriseoccupanciesinthe lobbyontheentrancefloorforFire Departmentoperations
EmergencyPowerSystems
Requiredinhighrisebuildingsand residentialbuildings>125feettoprovide backuppowerforemergencysystems
ElevatorLobbies
Whenelevatorsopenontoafireresistance ratedcorridor
OR
WhenelevatorsserveaGroupBoccupancy withfourormorestories
Elevator
FireRatedCorridor
ElevatorLobby
SmokePartition
ImpactResistantStairs/Elevators
Stairandelevatorenclosuresinhighrise buildingsmustbeconstructedofimpact resistantwalls
StairDesign
WiderStairwayWidth 44 min.stairwaywidthrequiredinALL occupanciesexcept: Stairwaysthathandle50persons cumulativeforallstories R2occupanciesnotmorethan125 highand eachstairwayserves<30occupantsper floor
StairDesign
EaseofStep 7 max.risersand11 min.treadsrequiredin ALLoccupanciesexcept:
o R2occupancies o R2dwellingunits o R3residentialoccupancies
SmokeProofEnclosures
OpenExteriorBalcony FireRated Enclosure 44 Openingto Exterior
ExteriorWall
FireRated Enclosure
72
Exterior Wall
PostFireSmokePurgeSystems
Requiredinallhighrisebuildingsandother buildingslistedinsectionBC912 Intendedforthetimelyrestorationof operationsandoverhaulactivitiesonceafireis extinguished
ElevatorsasMeansofEgress
Maybeusedasacomponentofaccessiblemeans ofegress,exceptin: 1. Residentialbuildings> 125feetinheight 1. Inotheroccupancieswheretheoccupied flooris> 75 abovethelowestleveloffire departmentaccess
SuperHighRiseBuildings
Buildingstallerthan300feet: Redundantautomaticandgravityfedwater supplies Largertanksizesforonsitestorageofwaterfor firefightingpurposes DedicatedexpressSiameseriser Zonedsystem Onsitesecondarywatersupplyrequiredatbuildings tallerthan300feetandinSeismicDesignCategory CorD
StructuralDesign
ProposedStructuralIntegrityProvisions Applicabletoallbuildings o VehicularImpactDesignLoadrequirement,Section1625.5 o HighpressureGasexplosionDesignLoadrequirement,Section1625.6 o ContinuityandTiesrequirements Requiringadditionalstrengthanddetailing ofmembersandtheirconnections SteelConstructionSection2213 StructuralSteelMembers CompositeConcreteSlabsonMetalDeck ConcreteConstructionSection1917 CastInPlaceConcrete PrecastConcrete MasonryConstruction Section2114 Bearingwalls Piers&Columns
StructuralDesign
StructuralIntegrity KeyElementAnalysis KeyElementAnalysis Section1626 TwoOptions: o AlternateLoadPathMethod Designto preventadisproportionatecollapseassuminga KeyElement willfailduetoanextremeevent o SpecificLocalResistanceMethod Designkey elementsforcodeprescribedloads
StructuralDesign(cont)
KeyElementAnalysisrequiredfor: Buildingsmorethan600feet(183m)tallormorethan1,000,000 square feet(92903m2) EssentialFacilitieslargerthan50,000squarefeet(4645m2) BuildingwithanAspectRatiogreaterthan7 Buildingstallerthan7storieswhereonestructuralmembersupports morethan15%oftheaggregatebuildingarea Buildingsdesignedusingnonlineartimehistoryanalysisorutilizing specialseismicenergydissipationsystems(BaseIsolationorDampers) StructuralPeerReviewbyaqualifiedindependentstructuralengineeralso required Section1627
BuildingUnderConstruction
StandpipeAirPressurizedAlarms LocalLaw64of2009 Airpressurizedalarmsonstandpipesystemsat: o Newbuildings75feet+ o FullDemolitions Required: o Drawingsofalarmsystem o Alteration2StandpipeApplication&Permit Testing
BuildingsUnderConstruction
StandpipeHydrostaticPressureTesting LocalLaw63of2009 Hydrostaticpressuretestsmustbeperformedonstandpipes at: o Newbuildings75feet+ o FullDemolitions o Certainalterationwork Required: o Alteration2StandpipeApplication&Permit Testing
WhereDoWeGofromHere?
WhatsHappeningOutsideNYC?
ChangestotheICC
ICCnowrequiresimpactresistantstairand elevatorenclosures ICCnowrequiresphotoluminescent exitpath markings Fireserviceelevatorandoccupantevacuation elevators
WhatsHappeningOutsideNYC?
ChangestotheICC Buildingstallerthan420feet: Two sprinklerrisersservingeachsprinklerzone Three exitstairs oExceptionforR2(residential)buildings oExceptionforbuildingswithoccupant evacuationelevator