Technical Specifications
Output

Product Overview

Documentation

Software & Firmware

Options

Compare Models

Ratings and Reviews

Output Power Capacity Max Configurable Power Nominal Output Voltage Output Voltage Distortion Output Frequency (sync to mains) Waveform Type Output Connections

865 Watts / 1500 VA 865 Watts / 1500 VA 230V Less than 5% at full load 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal Stepped approximation to a sinewave (4) IEC 320 C13 (2) IEC Jumpers

Input

Nominal Input Voltage Input Frequency Input Connections

230V 50/60 Hz +/- 3 Hz (auto sensing) IEC-320 C14

1 de 4

21/09/2011 11:01 a.m.

APC Smart-UPS SC 1500VA 230V - 2U Rackmount/Tower

http://www.apc.com/products/resource/include/techspec_index.cfm?base...

Cord Length Input voltage range for main operations

1.83 meters 186 - 284V

Input voltage adjustable range 175 - 297V for mains operation


Batteries & Runtime

Battery Type Typical recharge time Replacement Battery RBC Quantity Runtime Graph

Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof 8 hour(s) RBC59 1

2 de 4

21/09/2011 11:01 a.m.

APC Smart-UPS SC 1500VA 230V - 2U Rackmount/Tower

http://www.apc.com/products/resource/include/techspec_index.cfm?base...

Hover over the line on the graph above to view the runtime at any desired load Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output. View Enlarged Graph
Communications & Management

View Runtime Chart

Interface Port(s) Control panel Audible Alarm

DB-9 RS-232 LED status display with On Line : On Battery : Replace Battery and Overload indicators Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm

Surge Protection and Filtering

Surge energy rating Filtering Data Line Protection

445 Joules Full time multi-pole noise filtering : 5% IEEE surge let-through : zero clamping response time : meets UL 1449 RJ-45 Modem/Fax/DSL/10-100 Base-T protection

3 de 4

21/09/2011 11:01 a.m.

APC Smart-UPS SC 1500VA 230V - 2U Rackmount/Tower

http://www.apc.com/products/resource/include/techspec_index.cfm?base...

Physical

Maximum Height Maximum Width Maximum Depth Rack Height Net Weight Shipping Weight Shipping Height Shipping Width Shipping Depth Master Carton Units Color Units per Pallet
Environmental

89.00 mm 432.00 mm 463.00 mm 2U 21.36 KG 24.55 KG 254.00 mm 610.00 mm 610.00 mm 1.00 Grey 10.00

Operating Environment

0 - 40 C

Operating Relative Humidity 0 - 95% Operating Elevation Storage Temperature Storage Relative Humidity Storage Elevation 0-3000 meters -5 - 45 C 0 - 95% 0-15000 meters

Audible noise at 1 meter from 45.00 dBA surface of unit Online Thermal Dissipation
Conformance

180.00 BTU/hr

Regulatory Approvals Standard Warranty Environmental Compliance

C-tick,CE,GOST,VDE 2 years repair or replace RoHS 7b Exemption,China RoHS

**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.