Professional Documents
Culture Documents
http://www.apc.com/products/resource/include/techspec_index.cfm?base...
You are here: Home > Products > Uninterruptible Power Supply (UPS) > Smart-UPS
Technical Specifications
Output
Product Overview
Documentation
Options
Compare Models
Output Power Capacity Max Configurable Power Nominal Output Voltage Output Voltage Distortion Output Frequency (sync to mains) Waveform Type Output Connections
865 Watts / 1500 VA 865 Watts / 1500 VA 230V Less than 5% at full load 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal Stepped approximation to a sinewave (4) IEC 320 C13 (2) IEC Jumpers
Input
1 de 4
http://www.apc.com/products/resource/include/techspec_index.cfm?base...
Battery Type Typical recharge time Replacement Battery RBC Quantity Runtime Graph
Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof 8 hour(s) RBC59 1
2 de 4
http://www.apc.com/products/resource/include/techspec_index.cfm?base...
Hover over the line on the graph above to view the runtime at any desired load Curve fit to measured runtime data. All measurements taken with new, fully charged batteries, at typical environmental conditions, with no electrical input and balanced resistive load (PF = 1.0) output. View Enlarged Graph
Communications & Management
DB-9 RS-232 LED status display with On Line : On Battery : Replace Battery and Overload indicators Alarm when on battery : distinctive low battery alarm : overload continuous tone alarm
445 Joules Full time multi-pole noise filtering : 5% IEEE surge let-through : zero clamping response time : meets UL 1449 RJ-45 Modem/Fax/DSL/10-100 Base-T protection
3 de 4
http://www.apc.com/products/resource/include/techspec_index.cfm?base...
Physical
Maximum Height Maximum Width Maximum Depth Rack Height Net Weight Shipping Weight Shipping Height Shipping Width Shipping Depth Master Carton Units Color Units per Pallet
Environmental
89.00 mm 432.00 mm 463.00 mm 2U 21.36 KG 24.55 KG 254.00 mm 610.00 mm 610.00 mm 1.00 Grey 10.00
Operating Environment
0 - 40 C
Operating Relative Humidity 0 - 95% Operating Elevation Storage Temperature Storage Relative Humidity Storage Elevation 0-3000 meters -5 - 45 C 0 - 95% 0-15000 meters
Audible noise at 1 meter from 45.00 dBA surface of unit Online Thermal Dissipation
Conformance
180.00 BTU/hr
**The time to recharge to 90% of full battery capacity following a discharge to shutdown using a load rated for 1/2 the full load rating of the UPS.
4 de 4