Heating

Technical Data
Daikin Altherma

EEDEN10-721

Heating

Technical Data
Daikin Altherma

EEDEN10-721

Indoor Unit EKHVMYD-A

TABLE OF CONTENTS EKHVMYD-A

1 2

Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Technical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Electrical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3 4

Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Dimensional Drawings
............................................... 5

Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Piping Diagrams
..................................................... 7

Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Wiring Diagrams
..................................................... 8

External connection diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .


External Connection Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

13 13

Sound data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Sound Power Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sound Pressure Spectrum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
14 15

Hydraulic performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Static Pressure Drop Unit
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

1
t h i t n l UA - g Drn n Y oi i M ok tV di aH naKe ID HE

Features
High temperature application: up to 80C without electric heater Possible to choose between low temperature and high temperature heat emitters Cost effective alternative to a fossil fuel boiler Low energy bills and low CO2 emissions Heating and cooling in one system

1
1

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

Specifications
EKHVMYD50AAV1 EKHVMYD80AAV1

2-1 Technical Specifications


Casing Dimensions Colour Material Unit Height Width Depth Packed unit Height Width Depth Weight Packing Pump Unit Packed unit Material Weight Type Nr of speeds Nominal ESP unit Expansion vessel Heating Cooling Max. water pressure Pre pressure Sound pressure level Operation range Nom. Night quiet mode Heating Level 1 Ambient Min. Max. Water side Cooling Min. Max. Max. Water side Domestic hot water Min. Max. Max. Water side Refrigerant Refrigerant circuit Type Charge Gas side diameter Suction side diameter Liquid side diameter High pressure side Water circuit Piping Safety valve Manometer Drain valve / fill valve Shut off valve Air purge valve Heating water system Refrigerant oil Refrigerant side heat exchanger Type Charged volume Type Quantity Plates Material Insulation material Quantity l Water volume Min. Max. l l Design pressure Piping connections diameter kg mm mm mm bar inch inch bar Min. Max. Heating Volume Volume kPa l l bar bar dBA dBA C C C C CDB CDB C C CDB CDB C C kg mm mm mm mm mm mm kg kg

3 1
2

Metallic grey Precoated sheet metal 705 600 695 860 680 800 120 135 EPSCardboard + MDFWood (pallet) + Metal 8.75 DC motor Inverter controlled 83.7 7 2 3 1 40 (4) + 43 (5) 38 -15 20 25 80 10 43 5 (10) 20 (10) -15 35 45 75 R-134a 2 12.7 15.9 9.52 38 G 1" (female) 1" 3 Yes Yes Yes Yes 20 200 FVC50K 0.75 Plate heat exchanger 1 66 AISI 316 Felt type 42 (4) + 43 (5) 58.8

Ambient Min.

Ambient Min.

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

Specifications
EKHVMYD50AAV1 EKHVMYD80AAV1

2-1 Technical Specifications


Water side Heat exchanger Water flow rate Min. Heating Cooling Heating Type Quantity Plates Material Water volume Insulation material Cooling Type Quantity Plates Material Water volume Insulation material Water filter Cascade compressor Diameter perforations Material Quantity Motor Installation place Type Starting method mm l Quantity l Quantity Nom. Nom. l/min l/min l/min

5 16.1 14.3 Plate heat exchanger 1 72 AISI 316 2.2 Felt type Plate heat exchanger 1 42 AISI 316 0.82 EPDM type 1 Brass 1 Hermetically sealed swing compressor Direct on line Indoor 25.8 22.9

1
2

2-2 Electrical Specifications


Power supply Name Phase Frequency Voltage Voltage range Current Zmax Minimum Ssc value Maximum running current Recommended fuses Wiring connections For power supply Benefit kWh rate power supply installations For power supply multi tenant For connection with outdoor unit Power supply intake Notes Multi tenant Power supply Voltage Voltage range Current Min. Max. V % % A A Quantity Type of wires Quantity Type of wires Quantity Remark Quantity Remark Heating Min. Max. Text kVa A A Hz V % %

EKHVMYD50AAV1

EKHVMYD80AAV1

V1 1~ 50 220-240 -10 6 0.46 1,459 16.5 20 2G Select diameter and type according to national and local regulations 2G+2G Select diameter and type according to national and local regulations 2G Select diameter and type according to national and local regulations 2 F1 + F2 Both indoor and outdoor unit Cooling leaving water temperature depends on indoor unit operation status and other setpoints 24 -20 20 1 3

Maximum running current Recommended fuses

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

3
3-1

Dimensional drawings
Dimensional Drawings

EKHVMYD50-80A
left installation right installation upwiring

3 1
3

Screw fixation of top plate (Both sides)

Min. 500

Model EKHVMYD*

A 340

B 290

C 315

Min. 600

Space required for switch box removal)

3TW59914-1A

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

3
3-1

Dimensional drawings
Dimensional Drawings
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Suction/gas pipe connection J15.9 Solder (R410A) Discharge/gas pipe connection J12.7 Solder (R410A) Liquid pipe connection J9.5 Solder (R410A) R1340 Service ports 5/16 flare (2x) Pressure gauge Blow off valve (2x) Drain water circuit 5/16 SAE (2x) Air purge (2x) Shut-off valves (2x) Water filter Water in connection G 1 (Female) Water out connection G 1 (Female) Control wiring intake (Knock out hole J37) Power supply wiring intake (Knock out hole J37) Knock-out holes for refrigerant piping and water piping Levelling feet Remote controller (delivered as accessory) Installation location is outside the unit Suction/gas stop valve J15.9 Solder (R410A) Discharge/gas stop valve J12.7 Solder (R410A) Liquid stop valve J9.5 Solder (R410A)

EKHVMYD50-80A

1
3

Detail A Scale 1/3


If required (e.g. Wall fixation) Pressure gauge can be removed from waterfilter, maximum distance between waterfilter and pressure gauge +/- 600mm

left installation

right installation

Detail A

3TW59914-1A

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

4
4-1

Piping diagrams
Piping Diagrams

EKHVMYD50-80AAV1
Outdoor unit
Flowswitch

3
Heating Cooling
Shut off valve G 1 Female

Refrigerant side
Field piping J 12.7 C 1220T-0 Field piping J 9.52 C 1220T-0 Field piping J 15.9 C 1220T-0

Water outlet Option domestic hot water tank

1
4

Check valve Expansion vessel Muffler Heating heat exchanger R134a Air purge Filter Air purge

Filter Filter

3 way valve

Shut off valve G 1 Female

Water inlet
Drain port Blow off

Blow off

Filter
Plate heat exchanger R410A/R134a

Safety valve

Expansion vessel

Pressure gauge

Accumulator
R11T R10T R9T R7T R6T R5T R4T R3T S1PH B1PL B1PH K3E K2E K1E K3S K2S K1S Q2L M1C M1P Suction thermistor R410A Liquid thermistor R410A Cooling Leaving water cooling thermistor Liquid thermistor R134a Discharge thermistor Leaving water heating thermistor Returning water thermistor Liquid thermistor R410A High pressure switch Low pressure sensor Electronic expansion valve Electronic expansion valve Electronic expansion valve Solenoid valve 3 way valve (Cooling/Heating) 3 way valve Thermistor protector waterpiping Compressor DC invertor pump High pressure sensor

Safety valve

Filter

Cooling heat exchanger R410A

Field installation (delivered with Option domestic hot water tank) 3 way valve

Standard

Drain port

Service port 5/16

Service port 5/16

3TW59915-1A
Flare connection Screw connection Flange connection Pinched pipe Spinned pipe

Check valve

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

5
5-1

Wiring diagrams
Wiring Diagrams
NOTES TO GO THROUGH BEFORE STARTING THE UNIT X1M X2M X3M C F : Main terminal : Field wiring terminal for high voltage : Field wiring terminal for low voltage : Earth wiring : Field supply : Option
* #

Legend
: included in option kit : field supplied

1
5

: Wiring depending on model

: Not mounted in switchbox

: PCB X**/12.2 : Connection ** continues on page 12 column 2 : Several wiring possibilities

User installed: *KHTS* *KRTW* *KRTR* *KRTETS *KRUAHT *KRP1HB* *KRP1AHT* = Domestic hot water tank = Room thermostat (Wired) = Room thermostat (Wireless) = External temperature sensor for *KRTR* = Remote user interface = Digital I/O PCB = Demand PCB

A1P : Main PCB A2P : User interface PCB A3P : control PCB A4P : Inverter PCB A5P : QA PCB A6P : Filter PCB A7P * : Digital I/O PCB A8P * : Demand PCB A9P : Multi tenant PCB A10P * : Thermostat PCB A11P * : Receiver PCB B1PH : High pressure sensor B1PL : Low pressure sensor C1-C3 : Filter capacitor C1-C3 (ASP) : PCB Capacitor DS1 (A*P) : Dipswitch F1U : Fuse (T,3.2A, 250V) F1U (A1P,A3P,A9P) : Fuse (T, 3.15A, 250V) F1U (A6P) : Fuse (T, 6.3A, 250V) F1U-F2U (A7P) : Fuse (5A, 250V) F3U-F4U (A*P) : Fuse (T, 6.3A, 250V) HAP (A*P) : PCB LED IPMI : Integrated power module K1A-K3A : Interface relay K1E-K3E : Electronic expansion valve K*R (A*P) : PCB Relay K1S * : 3 way valve K2S : 3 way valve K3S : 2 way valve K4S # : 2 way valve M1C : Compressor M1F : Switchbox cooling fan M1P-M2P : DC inverter pump PC (A11P) * : Power circuit PHC1 : Optocoupler input circuit PS (A*P) : Switching power supply Q1DI-Q2DI # : Earth leakage protector Q2L : Thermal protector water piping R1-R2 (A4P) : Resistance R1L : Reactor R1H (A10P) * : Humidity sensor R1T (A10P) * : Ambient sensor R2T * : Domestic hot water tank Thermistor R2T * : External sensor (floor or ambient) R3T : Liquid thermistor R410A R4T : Returning water thermistor R5T : Leaving water thermistor (heating) R6T : Discharge thermistor R7T : Liquid thermistor R134a R8T : Fin thermistor R9T : Leaving water thermistor (cooling) R10T : Liquid thermistor (cooling) R11T : Suction thermistor (cooling) RC (A*P) : Receiver circuit S1PH : High pressure switch S1S # : benefit kWh rate power supply contact S3S # : Input multiple setpoint S4S # : Input multiple setpoint SS1 (A1P) : Selector switch (emergency) SS1 (A2P) : Selector switch (master slave) SS1 (A7P) * : Selector switch TC (A*P) : Transmitter circuit T1R-T2R (A*P) : Diode bridge T3R : Power module V1C-V8C : Ferrite core noise filter X1M-X3M : Terminal strip X*M (A*P) * : PCB terminal strip X1Y-X4Y : Connector Z1F-Z5F (A*P) : Noise filter

4TW59916-1A

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

5
5-1

Wiring diagrams
Wiring Diagrams

EKHVMYD50-80

3
Power supply (Only for benefit kWh rate power supply installation)
150Hz 220-240 VAC Power supply 150Hz 220-240 VAC Normal kWh rate power supply 150Hz 24V AC Multi tenant power supply (Refer to manual for more details) 150Hz 220-240 VAC benefit kWh rate power supply contact

Compressor circuit

Power supply (Only for normal power supply installation)

150Hz 24V AC Multi tenant power supply (Refer to manual for more details)

1
5
Only for *KHVMYD*

**: Remove 2 wire bridges on X2M terminal positions 8-10 and 9-11. See page 6 for installation of the benefit KWh rate power supply contact. (see installation manual)

Only for *KHVMYD*

Only for *KHVMYD*

4TW59916-1A

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

5
5-1

Wiring diagrams
Wiring Diagrams

EKHVMYD50-80A

1
5

CONTROL CIRCUIT

Only for *KHTS*

Only for *KHVMYD*

Only for *KRTW*

Only for *KHTS*

Only for benefit kWh rate power supply installation

Only for *KHVMYD* Only for *KHVMYD*

Only for *KRTR*

Only for *KRTETS

Only for *KRP1AHT*

Transmission wiring: Indoor/outdoor unit wiring (Refer to manual for more details)

Unit heating/cooling on/off output

Alarm output

220-240 VAC Output Maximum load: 0.3 A

Only for *KRUAHT*

220-240 VAC Output Maximum load: 0.3A Only for *KHVMYD*

Cooling mode on/off output

Remote user interface

Maximum load: 0.3 A - 250 VAC Minimum load: 20 mA - 5VDC

DHW mode on/off output

User interface

4TW59916-1A

10

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

5
5-1

Wiring diagrams
Wiring Diagrams
Indoor unit Common BUH step 1 (3kW) BUH step 2 (6kW)

EKBUH-AA6V3
Power supply 1N~230V 50Hz

3
Option demand PCB

1
5

Switch box layout

Part number A8P E1H, E2H F1B, F2B F1U F1T K1A K1M, K2M K5M, K6M
*: optional #: eld supplied

Description Demand PCB (Indoor unit option) Backup heater elements Fuse backup heater (20A 400V) Fuse (5A T 250V) Thermal fuse backup heater Time relay (on-delay) Contactor backup heater step Contactor for backup heater (all pole disconnection)

Part number S1L Q1DI Q1L Q2L R1 X1M,X2M X801M #

Description Flowswitch Earth leakage protector Thermal protector backup heater (manual reset) Thermal protector inlet water (automatic reset) Inline resistor for flowswitch Terminal strip PCB terminal strip

4TW59726-1
NOTES

: Main terminal : Field wiring terminal : Earth wiring : Wire number 15 : Field supply : Several wiring possibilities

: Option

: Not mounted in switch box

: Wiring depending on model

: PCB

Heating Daikin Altherma

11

Indoor Unit EKHVMYD-A

5
5-1

Wiring diagrams
Wiring Diagrams
Power supply 3N~400V 50Hz

EKBUH-AA6W1
Indoor unit Common BUH step 1 (3kW) BUH step 2 (6kW)

1
5

Option demand PCB

Switch box layout

Part number A8P E1H, E2H, E3H F1B F1U F1T K1A K2A K1M, K2M
*: optional #: eld supplied

Description Demand PCB (Indoor unit option) Backup heater elements Fuse backup heater (20A 400V) Fuse (5A T 250V) Thermal fuse backup heater Time relay (on-delay) Auxilary relay Contactor backup heater step

Part number K5M S1L Q1DI Q1L Q2L R1 X1M,X2M X801M #

Description Contactor for backup heater (all pole disconnection) Flowswitch Earth leakage protector Thermal protector backup heater (manual reset) Thermal protector inlet water (automatic reset) Inline resistor for flowswitch Terminal strip PCB terminal strip

4TW59726-2
NOTES

: Main terminal : Field wiring terminal : Earth wiring : Wire number 15 : Field supply : Several wiring possibilities

: Option

: Not mounted in switch box

: Wiring depending on model

: PCB

12

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

6
6-1
EKHVMYD

External connection diagrams


External Connection Diagrams
Electrical connection diagram Daikin Altherma
Standard parts
Outdoor unit power supply (benet kWh rate power supply is NOT allowed) 380V - 415V + earth 5 core
X1M: L1-L2-L3-N-earth

Please check unit wiring diagram for more details Outdoor unit

3 1
6

Indoor unit 2
communication 2 core

Indoor unit n (2n8)

2 core communication

2 core communication only for EKRP1HBAA

2 core communication

Indoor unit 1
Indoor unit power supply Possibility 1: Only for normal power supply installation 220V - 240V + earth 3 core
L-N-earth

2 core
DHW mode on/off output

Field supply

1 core Possibility 2: Only for benet kWh rate power supply installation Benet kWh rate power supply: 3 core 220V - 240V + earth Normal kWh rate power supply: 220V - 240V + earth 3 core 2 core signal 2 core signal 2 core Backup heater Indoor unit multi-tenant power supply: Ensure correct multi-tenant operation, if not installed, the outdoor unit will stop and display an error when one or more tenants cut off the indoor unit power supply 2 core signal 3 core signal 2 core signal Room thermostat Possibility 1 2 core
Input multiple setpoint 1

2 core 1 core
L-N-earth
Cooling/heating mode on/ off output

Optional power supply: cooling/heating on/off output

1 core 2 core 1 core


Alarm output

* remove wire bridges

Optional power supply: alarm output

Benet kWh rate power supply contact

Input multiple setpoint 2

only for *KBUH*


L1-L2-L3-earth or L-N-earth

5 or 3 core

Optional power supply: 380V-415V or 220V-240V + earth only for EKRP1AHTA

Optional parts
2 core signal Only for EKHVMYD* 2 core only for EKRTW (wired room thermostat)

Field supply
Only for EKHVMYD*
Cooling mode on/ off output

Optional parts
Only for EKHTS* Possibility 2 2 core signal Only for EKHVMYD* 2 core 2 core signal 3 core 2 core 2 core (3m included) signal
R2T External sensor (oor or ambient)

only for EKRTR (wireless room thermostat)

only for EKRTETS

Domestic hot water tank


R2T - Thermistor water temperature

3 way valve
K1S (When EKHTS* is installed) selection domestic hot water - heating

Only for EKRAUHT* 2 core communication

User interface

User interface

communication

2 core

3TW59919-4A
NOTE

In case of signal cable or communication cable, keep minimum distance to power cables > 25mm

Heating Daikin Altherma

13

Indoor Unit EKHVMYD-A

7
7-1

Sound data
Sound Power Spectrum

EKHVMYD50-80A
Sound power Lw per Octave band (dB) 500 1000 2000 49 47 41 51 45 45 Total (dBA) LwA 54 55

1
7

EKHVMYD50AAV1 EKHVMYD80AAV1

125 38 39

250 49 50

4000 41 43

8000 39 41

Notes - Measured according to ISO3744 - Reference acoustic pressure 0dB = 10E-6W/m_ - dBA=A-weighted sound power level - Unit condition: Ta=7/6C - Heating setpoint 55/65C - Maximum compressor frequency - If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Choose the installation location carefully and do not install in a sound sensitive environment (e.g. living room, bedroom, . . .)

3TW59917-2

14

Heating Daikin Altherma

Indoor Unit EKHVMYD-A

7
7-2

Sound data
Sound Pressure Spectrum
Position of microphones
Back

EKHVMYD50-80A

3 1
7

Left

Right

Front

= Microphone

Sound levels

Notes - The above data is valid in free field condition, because it is measured in a semi-anechoic room. If sound is measured under actual installation conditions, the measured value will be higher due to environmental noise and sound reflections. Choose the installation location carefully and do not install in a sound sensitive environment (e.g. living room, bedroom, . . .) - dB(A) = A-weighted sound pressure level (A-scale according to IEC) - EW = Entering water temperature - LW = Leaving water temperature - Reference acoustic pressure 0dB = 20Pa - Sound pressure level of low sound mode n2 and n3 is lower than n1 - (*) Does not occur simultanuously on all sides.

Sound pressure [dBA] EKHVMYD [EW/LW 55/65C] Front Left / Right / Back (*) [EW/LW 70/80C] Front Left / Right / Back (*) [EW/LW 55/65C] - Low sound mode n1 FrontRight (*) 50 40 40 40 40 38 80 42 41 43 42 38

3TW59917-1

Heating Daikin Altherma

15

Indoor Unit EKHVMYD-A

8
8-1

Hydraulic performance
Static Pressure Drop Unit
Unit ESP
unit ESP without DHW 3way valve unit ESP including DHW 3way valve
max. ESP if _T = 10C (heating) max. ESP if _T = 5C (heating) max. ESP if _T = 5C (cooling)

EKHVMYD50-80A

1
8
ESP [kPa]

Note: In case of stand alone tank, available ESP during DHW mode: to be confirmed

Flow [l/min]
1. The ESP curves are the maximum ESP curves for different DT types (pump rpm=4000 for _T=5C; pump rpm=3600 for _T=10C) The pump of the indoor module is inverter controlled and controls to have a fixed _T between return and leaving water temperature. 2. In case of installing a domestic hot water tank there is an additional pressure drop over the three way valve (delivered as accessory with the tank) ESP: External static pressure Flow: waterflow through the unit Warning 1. Selecting a flow outside the curves can cause damage to or malfunction of the unit. See also minimum and maximum allowed water flowrange in the technical specifications. 2. Water quality must be according to EN directive EC 98/83 EC.

3TW59919-5

16

Heating Daikin Altherma

Daikins unique position as a manufacturer of air conditioning equipment, compressors and refrigerants has led to its close involvement in environmental issues. For several years Daikin has had the intention to become a leader in the provision of products that have limited impact on the environment. This challenge demands the eco design and development of a wide range of products and an energy management system, resulting in energy conservation and a reduction of waste.

The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.

Daikin products are distributed by:

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory. Multi units are Eurovent certified for combinations up to 2 indoor units.

Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende

EEDEN10-721 CD 08/10 Copyright Daikin The present publication supersedes EEDEN09-721 Printed in Belgium by Lannoo (www.lannooprint.be), a company whose concern for the environmont is set in the EMAS and ISO 14001 systems. Responsible Editor: Daikin Europe N.V., Zandvoordestraat 300, B-8400 Oostende