Regional Office, 1st Floor, Shankar Shopping Complex,Krishna Nagar Main Road, Kurnool – 518 002
To
The Sr. Environmental Engineer(CFO) The Joint Chief Environmental Scientist (HWM)
A.P.Pollution Control Board, A.P.Pollution Control Board,
Board Office, Hyderabad Board Office, Hyderabad
Sir ,
The details of the industry and inspection report are submitted as below:
General Details:
1 Name and Address of the industry M/s Bharat Petroleum Corporation Ltd.
N.H-7, LPG filling plant, 217/6,
K.M. stone, P.B.No.10,
With Tel. No, B.Camp (Post), Kurnool 518 002.
E-mail.
5 Status of E.C
I Line of Activity as per EIA Notification. LPG Filling
II Environmental Clearance order No. ---
and date
(Copy shall be enclosed).
III Violations of EIA Notification, If any. ---
6 I Inspection conducted by A.E.E
II Representative of Industry present Sri J.Mahendra Reddy, Teritory Manager
III Date of Inspection 29-02-2008
CFO Details
7 Raw materials / Fuels required for production at Consented capacity per Day / Month.
Note : Should not be mentioned as “ enclosed with the application “
S.No Name of the Major Raw material / (Per / Month ) for each product
material used in the Activity
1 L.P.G. 100 TPD
9 Water consumption.
I Source of water supply Borewell
(River / Bore wells / Public supply)
S. Purpose Quantity
no in KLD
1. Process / Scrubbing --
2. Washings (Hydraulic testing) 1.0
3. Boiler Feed ---
4 Cooling (Makeup) / Humidification / ---
Water spraying).
5 Fire Fighting mock drills 5.0
6 Domestic 3.0
Total: 9.0
II. Status of Functioning of Water Meters Not provided
iii. For Domestic waste water: Septic tank followed by soak pit
13 Water Cess
I Returns filed upto (Month & Year) 31-01-2008
II Assessment issued upto (Month & 30-06-2006
Year)
III Assessment paid upto (Month & Year) 30-06-2006
IV Assessment amount due (In Rs.) ---
14 Air pollution:
15. Emissions from chimneys – as per CFE / CFO order dt. 01-07-2006
16 Compliance of the industry on CFE (Schedule- A & B) Conditions for Fresh CFO
/ Schedule – B conditions for renewal.
CFO Order No. APPCB/KNL/KNL/330/HO/W&A/2006 -585, dt: 01-07-2006
S.
Condition Compliance
No.
1 The effluent discharged shall not contain : The industry is not generating any
constituents in excess of the tolerance limits industrial effluents. The domestic
mentioned below: effluents are being treated in septic
tank followed by soak pit.
Outlet Parameter No. Limiting standard
mg/l except for pH
1 pH 5.50-9.00
Total Suspended 200.00 mg/l
Solids (TSS at 103
– 1050C
Oil & grease 10 mg/l
BOD 100.00mg/l
S.
Condition Compliance
No.
--- ---
S.
Condition Compliance
No.
--- ---
S.
CREP Recommendations Compliance
No.
--- ---
Common TSDF –
Common HW Incinerator –
For recycle / reused -
viii) Whether industry has submitted annual N.A
returns, date of latest submission.
ix) Whether industry has installed incinerator or Not submitted
sending to common HW Incinerator
x) Particular of own incinerator (if applicable) ---
xi) Whether log books are maintained for ---
incinerator. (if applicable)
xii) Whether industry has taken adequate steps to ---
prevent contaminated runoff from storage
areas of Hazardous Waste.
xiii) Steps taken by industry towards waste ---
minimization and cleaner production.
xiv) Future plan for waste minimization. ---
xv) Facilities available with, industry for waste ---
characterization.
xvi) Overall House Keeping within the factory ---
premises.
xviii) Details of disposal of lead acid batteries along ---
with nos and agencies to whom they are
disposed
22 Compliance of the industry on previous Hazardous Waste Authorisation conditions. :
S.
Condition Compliance
No.
1 Industry shall give top priority for waste minimization : Complied
and cleaner production practices
2 The industry shall lift the hazardous waste i.e., paint : The industry has stored within the
Sludge to TSDF, Dindigal, Rangareddy District premises in HDPE barrels and
regularly proposed to transport to TSDF,
Dindigal as and when the sufficient
quantity is accumulated
3 Industry shall dispose / sell the hazardous wastes to : ---
only industries / agencies authorized by State
Pollution Control Boards. They shall verify the
authorization of the board given to the party before
disposing their wastes to the external party
4 Industry shall maintain 6 copy manifest system for : ---
transportation of waste generated and a copy shall
be submitted to Board Office and concerned
Regional Office
5 Industry should maintain good house keeping & : Complied
maintain proper records for hazardous wastes
stated in Authorisation (Form-II)
6 The unit shall submit the condition wise compliance : Complied
report of the conditions stipulated in Schedule-B and
Schedule C of this order o half yearly basis to Board
Office, Hyderabad and concerned Regional Office
7 The industry shall check the certificate / : ---
authorization / order of MoEF issued to the re-user /
recycler unit while disposing the waste oil
8 The industry shall take all practical steps to : ---
preventing of oil spillages and carry over of oil from
the premises.
This is a LPG Bottling Plant. The industry is having total area of 27.12 acres out
of which 18.45 acres built up area and the remaining 8.67 acres land, they have
developed greenbelt. The industry has provided 3 bullets of capacity 125T each above
the ground level. The industry had provided fire fighting system consisting of sufficient
number of fire hydrant and water monitors (i.e., fire fightings – 70 Nos, hydrants – 29
Nos, water monitors – 15Nos). the industry is having two fire water storage tanks of
capacity, 2,733 KLs each above the ground level. The industry is having 3 X 610
KL/hr. fire water pumps for sprinklers and 2 x 272 KL/hr. fire water pumps for hydrants
and monitors.
The unit is using the water for Cylinder Washing, Cylinder leakage testings
(hydraulic test), Mock drills, Compressor cooling and for Domestic purposes. The water
used for cylinders testing is let out once in a week or 10 days fro green belt
development within the factory premises. The domestic waste water is being treated in
septic tank and the canteen water has been utilized for greenbelt development. The
industry had also provided water meter for assessing water consumption. The industry
has taken all safety measures as per OISD recommendations.
The issue of renewal of CFO of the Board may be considered to this units for the
period of 3years i.e., valid upto 31-03-2011 duly stipulating necessary conditions.
I Maintenance of ETP / APC : ---
II Records Maintained
• ETP Log Book.
• Stack Monitoring Report.
• Ambient Air Quality Monitoring report.
• Energy consumption records.
• Water meter readings.
This is submitted for favour of kind information and taking necessary action.
Yours faithfully,
ENVIRONMENTAL ENGINEER
- Copy submitted to the JCEE (Cess & Planning) APPCB, Board Office, Hyderabad for favour of kind
information and for taking necessary action.
- Copy submitted to the GIS Section, APPCB, Board Office, Hyderabad for favour of kind information and
for taking necessary action.