You are on page 1of 98

The New VLT® AQUA Drive FC202

The new VLT® AQUA Drive


Sets new benchmarks in water and
waste water business

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


2
Compatibility

The new VLT® Aqua Drive


is 1:1 compatible with
VLT® 8000...

All you have in


VLT® 8000
you will have in
VLT® Aqua Drive
…and even more.

Award-winning user
friendliness

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


3
Supply and power range

One drive for full


voltage range
Lower need for
training, less confuse

200 – 240Vac, 0,25 – 45kW


200 – 240Vac, 2,2 – 22kW, 1Ø - 3Ø

380 – 480Vac, 0,37 – 90kW


380 – 480Vac, 7,5 – 37kW, 1Ø - 3Ø

380 – 480Vac, 110 – 1000kW


525 – 600Vac, 0,75 – 90kW
525 – 690Vac, 11 – 1,2MW

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


4
Flexible mechanical design

Common mechanical
concept
•Backwards compatible
with footprint of VLT 2800
+ VLT 8000

Flexible mounting
•Horizontal
•Vertical
•True side-by-side

Global labelling
•CE marked according to:
•C-tick approval
•UL and cUL approvals

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


5
Flexible mounting

Quick and easy


replacement of old
drives

Less installation time

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


6
Compact design

True side by side


mounting saves
space and time

Less panel space


– Less cost

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


7
The smallest IP20

Saves considerably
Space in panels

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


8
The smallest IP20

Footprint:
- up to 57 % smaller Former width

New width,

Volume B5

New IP20 height


- up to 60 % smaller

New IP21 Height


Former IP21 Height
FP54%
FP 54%
VL60%
VL 60%

FP 15%
VL 11%

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


9
VLT AQUA Drive - High Power
Integrated options

• Disconnect switch

• Fast acting fuses

• Built in filters comply with


EN61000-6-4 and EN61000-3
• Class A2 filter as standard
• Optional class A1 (150 m cable)

• Also available as field installable


kits for later upgrade

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


10
Innovative Cooling Back channel
exhaust air
Back Channel Cooling
Internal
• Separate cooling path for power components exhaust air
• Removes 85% of losses using drive main fan
• Main airflow away from control electronics
• Separate cooling for control components
•IP54 seal between power and control
cooling air
• Reduced air volume inside the enclosure
• Less contaminants enter the enclosure
• Small door fans Internal
inlet air

Details Back channel


inlet air
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


11
Innovative cooling by design

§ Two cooling possibilities


Upper exhaust
§ Back cooling –
Air ducted in and out the back
Heat sink Back exhaust § Duct work cooling –
Air ducted in the bottom, out the top
Heat sink fan
§ 85% of the cooling air volume
never enters the controls area
IP54 Seal
§ Separate path makes heat sink
cleaning easy
Back inlet

Bottom § Pre-engineered, thermally tested


inlet cooling kits available
Details for IP00 enclosures

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


12
IP00 enclosure with back channel kits

Back channel
exhaust air

Internal Internal
exhaust air exhaust air

Back channel
exhaust air

IP54 Seal

Internal Internal
inlet air inlet air
Back channel
Back channel inlet air
inlet air
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


13
The reliable VLT® AQUA Drive

Designed for maximum


uptime and long life
• High ambient temp
• High IP-rating
• Robust housing
• Maintenance free

Value

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


14
Value of high ambient temp, IP
and robust housing

Panel builder: End user:

•Less need for panel cooling •Reduced installation cost.


•Increased lifetime •Increased drive lifetime.
•Stabile and reliable system •Usable in harsh environments
•Possible mounting outside panel •Reliable system

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


15
VLT® Aqua Drive cooling system

Fan controlled by
internal temperature
Energy saved
Less acoustic noise

Minimum ambient air passes


the electronic components in
IP20 and no in IP21/55
Optimizes the lifetime

Cold Plate option


Heat sink outside the panel
Less need for panel cooling
Picture shows IP20 unit
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


16
Conformal Coated PCB’s
For harsh
environments
Water applications:
Chlorine etc.
Wastewater applications:
Hydrogen sulphide,
Amonium etc.

Protects against
pollution, moisture,
and dust
Increase drive lifetime

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


17
Large variety of options

• Only pay for


what you need
• Flexible specification
• Reduced total installed
system costs
• Easy Mounting
– plug and play

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


18
Large variety of options

• Relay option
+ 3 relay outputs

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


19
Large variety of options

• Relay option
• General purpose I/O
+ 3 digital inputs
+ 2 digital outputs
+ 2 analogue inputs
+ 1 analogue output

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


20
Large variety of options

• Relay option
• General purpose I/O
• Aqua I/O option
+ 3 PT/NI 1000
analogue input
+ 3 analogue output

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


21
Large variety of options

• Relay option
• General purpose I/O
• Aqua I/O option
• Fieldbusses
– Modbus RTU (Standard)
– Profibus
– Device net
– Ethernet (April 2007)
– Modbus TCP (late 2007)

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


22
Large variety of options

• Relay option
• General purpose I/O
• Aqua I/O option
• Fieldbusses
• Cascade control
– Extended 5 relays
– Advanced 8 relays

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


23
Large variety of options

• Relay option
• General purpose I/O
• Aqua I/O option
• Fieldbusses
• Cascade control

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


24
Large variety of options

• Relay option
• General purpose I/O
• Aqua I/O option
• Fieldbusses
• Cascade control
• Real Time Clock with
24V backup

Value

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


25
Value of a large variety of options?

Panel builder: End user:


,
• Only pay for the needed • Only pay for the needed
• Easy to upgrade a system • Easy retrofit
• Flexibility in project planning • Saves money
• Saves cost

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


26
Tested – ready for operation

Customized units
assembled and
tested in the factory

• Reliability
• Quick and low cost
installation

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


27
Same user interfaces for whole range

Option of 2 Displays
(graphical and numerical)
“Blind cover” available

• Award winning
graphical display
• Easy navigation and
troubleshooting
• Quick learning

Value
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


28
Value of only one user interface
for the whole range?
Panel builder: End user:
• No need for display • Very easy
in all drives commissioning
• Easy commissioning • Saves time and money.
• Saves time and money
• Possible cost optimized user
interface.

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


29
The new VLT® AQUA Drive

Excellent electronic performance


Best built-in EMC performance

3 levels filtering
available, complies IEC
61800-3

Screened Cable length


up to 150m and 300m
unscreened
Flexibility to meet
different requirements
Eliminates interference
with other installed
equipment

Value

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


31
Value of the EMC performance?

Panel builder: End user:


Onboard filter saves:
• panel space • Lower installation cost
• cost of an external filter • Compliance with EMC norms
• time for mounting of • Easy replacement
external filter
3 Different RFI filters: Screened
H1 Class A1/A2 150m
H1 Class B 50m
H2 Class A2 Up to 25m (Size depended)
H3 Class A1 (reduced) 50m
H3 Class B (reduced) Up to 20m (Size depended)

Unscreened up to 300m

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


32
Up to 150 m screened motor cable / 300 m
unscreened

Flexibility in
project planning

No need for
external filters

Saves space and money

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


33
Optimum harmonic performance

DC-coils are
built-in standard
• Reduced installation cost

• Smaller transformer
and cables

Value

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


34
Value of the Harmonic performance?

Panel builder: End user:


• Total Harmonic Distortion • Lower installation cost
(THiD) current • Lower kVar Penalty
lower than 48% • Lower need for power Factor
correction
• No need for • Less cooling
external input filter
• Saves space, time
and money

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


35
The new VLT® AQUA Drive

Use less energy


Energy optimization
Automatic Energy
Optimization (AEO)
Voltage
• Better system efficiency
• Optimize energy savings
• Quicker Start-up
• Optimizes motor
magnetization voltage based
on load dynamics
• Can be used both in VT and Speed
CT torque mode

Value Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


37
Value of Automatic Energy
Optimization (AEO)
Only one parameter that
saves a significant
amount of energy

Decrease the payback time

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


38
Energy optimization

Automatic Motor
Adaptation (AMA)

• Optimizes motor
performance
• Higher system efficiency
• Simple and optimum
commissioning

Value
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


39
Value of Automatic Motor
Adaption (AMA)?

• Easy to fit the drive to the • Compensate for voltage drop


motor. because of long motor cables
• Ensure optimized motor for submersible pumps.
performance. • Submersible pump motors are
• Saves cost because of lower often differencing from
commissioning time standard motor data.
AMA compensate for this.

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


40
Energy optimization

Voltage Vector Control


(VVCplus)

• Full voltage at full speed


• No motor derating
• No overheat at full load
• Improved dynamic and stability

Value
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


41
Value of VVCPlus

Panel builder: End user:

• Full motor power at rated • Optimized motor


speed - No need for motor performance
derating • Dynamic, stabile and
• Cost optimized drive and reliable system
motor system • Minimize drive internal
• Minimize drive internal energy consumption
energy consumption • 60° PWM compensate for
• Reduces the need for panel weak supply grids. Up to
cooling 115% mains voltage

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


42
Energy monitoring

Built-in energy
measurement tool

• Helps user to track


record of the system
• Identifies energy
improvement
possibilities within
water systems

Value
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


43
Value of energy monitoring?

Panel builder: End user:

• Easy process optimization. • Easy to control and


optimize the system.
• Easy to track energy
consumption
• Easy to compare the
actual conditions with the
estimated.

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


44
The new VLT® AQUA Drive

Protects applications and motors


Effective motor and drive protection

• No extra heating due to


switching pattern
• Electronic Thermal Relay
function (ETR)
• Direct thermistor
connection
• Current limit protection
• Motor DC brake function at
stand still. (Motor preheat)
• Switching on output
• Low du/dt and Upeak

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


46
Effective system protection

Automated
skip frequencies
Preventive maintenance
• Reduces system stress
• Reduces
commissioning time
• Easy to avoid
system resonance
• Quick setup of the
frequency bands

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


47
The new VLT® AQUA Drive

Water operation Child’s play


AQUA specific menus

• Quick setup menu


• AQUA application menu Quick Menu

• AQUA function menu My Personal


Menu

• Personal menu
can be customised Quick Setup

• Very easy and quick Function Setup

commissioning Changes Made

Analog
reference

Closed loop
Settings

Menu Structure
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


49
Status Quick menu Main menu Alarm log

Spin Motor/ Prove


System

My Personal Menu

Quick Setup

General
General Clock settings
Function Setup settings LCP Display settings
settings
Analogue outputs
Relays
Changes Made Openloop
loop
Open Digital Reference
settings
settings Analog Reference
Loggings
Closedloop
loop
Closed Feedback Settings
settings
settings PID Settings

Application Fan functions


Application
settings Pump functions
settings
1/1
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


50
2-level password

Protects personal and


main menus

• Allows controlled access


to drive settings
• Reliable water and
waste water systems

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


51
Info key

Provides access to
”Onboard Manual”
Available “on-site”

• No need for
a printed manual
• It’s ”always there”

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


52
Programmable display

Up to 5 variables…
• User-defined Display
• Display values with units
(kPa, Bar, mmHq, kWh and…)

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


53
Graphical display

• Simple monitoring of
logged data
• Graphs and bars
• Multiple font size
• Icons
• International letters,
numbers and signs

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


54
Display features

Alarm messages/log:
Full text messages
Customised texts
Customised display:
Text and values
Easy and improved
monitoring/fault finding
Graphical data log
Undo-function:
Resets latest change
Hand-Off-Auto on keypad

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


55
USB port

Plug and play


connection of a PC
Easy use of
• VLT® Set-up Software
MCT 10
• VLT® Energy Box

Saves time and money

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


56
Drive communicates with other devices

Standard RS-485
• MODBUS RTU
• Danfoss FC
Optional
• Profibus
• DeviceNet
• Ethernet
• Modbus TCP

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


57
Drive communicates with operator

Clear text message

• Many languages are


available in the display
and documentation

• Chinese, Mandarin, Cyril,


Greek etc. characters

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


58
The new VLT® AQUA Drive

Installation is Child's play


Power terminals

Standard cable-glands

Pluggable terminals
(up to 7,5kW)

Screwed terminals
(11 – 90kW)

• Easy cable access


• No need for EMC glands
• Saves money

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


60
Optional mains disconnect switch

• No need for extra


switch
• Easy installation
• Reduced installation
time and cost

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


61
Control terminals

• Spring loaded
connections
• Pluggable terminals
– Quick installation
– Reliable system
– Vibration proof
– loop connection

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


62
The new VLT® AQUA Drive

Built-in Intelligence
Advanced process control

4 x PID controllers
• 1 controller for the drive
• 3 controllers for other
process equipment
• Eliminates need for
secondary controllers
• Provides flexibility
for SCADA

• Can be used for Chemical


feed pumps, valve control,
Aeration with diff. levels

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


64
Advanced process control

Auto tuning of all PI-s


• Easy system
commissioning
• Makes PID control simple
• Saves installation and
labour cost

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


65
PI Auto Tune

1. PI Auto Tune enabled.


2. Monitors the feedback.
3. Manuel adjust the speed to
approximately set point is
reached.
4. Press OK
PID tuning ! 1(2)
5. Drive runs in closed loop 33,7 Hz 1035 rpm 1.6 A

Step 1 of 4

Auto Remote Running

Stabilize with fixed speed 3 acceptable curve periods Drive runs in closed loop

Example
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


66
Scope from MCT10 software

Speed

Feedback

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


67
Advanced process control

3-zone feedback

• Increased control
flexibility

• Improves system by
using the average of
feedbacks

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


68
Real Time Clock

20 actions can
be triggered
• Eliminates need
for external timers
• Increased flexibility

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


69
Preventive Maintenance

20 actions items
can be scheduled

• Helps planned
system maintenance
• More reliable water and
waste water system

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


70
Smart Logic Controller

Offers a wide range of


PLC functions
Automated sequence
actions can be
programmed
• No need for
external controllers
• Saves cost

Example

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


71
Smart Logic Controller
Start command

Condition
Control off

Pump
Operation
Shut off

Stop command

Less than
Start pump Pressure
Setpoint

Pipe
Compare pressure

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


72
Flying start

• Catch motor
in both directions
• Maintains pressure in
case of short voltage
drop-out

Prevent damage and trip if for


instance a Check Valve is defect.

Defect Check valve

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


73
VLT® AQUA Drive

Dedicated pump features


Pump dedicated functions

End of curve monitoring


in case of a leakage
•Provides warning
or an alarm
•Extends life time
of pump
•Shut down of Pump
•Prevent damaging of the
pump

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


75
Pump dedicated functions

Cascade Controller
built-in as standard
• Staging / destaging
• Possible alternation
• Pump Cycling
• Pump Interlocking

Efficient Pump operation

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


76
Cascade Controller

Basic Standard Cascade


2 relays
Alternation of 2 pumps (1 relay/pump)
Extended Cascade – B option
2 + 3 relays
Alternation of 2 pumps
Unequal sized pumps
Master / slave

Advanced Cascade – C option


8 relays
Alternation of 4 pumps
Unequal sized pumps
Master / slave
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


77
Cascade CTL and setpoint

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


78
Master/Slave control mode

• Master Drive contains


the cascade CTL
• Slave units are
standard drives
• All motors operate at
the same frequency
when in use
• Maximum performance
• Maximum energy saving

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


79
Pump dedicated functions

Dry pump detection


No-flow/low-flow
monitoring
• Based on Speed and power
• Semi Automatic setup

• Avoid dry-running and


pump overheat
• Prevent damaging of the
pump
• Saves energy
• Less cost for sensors
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


80
Pump dedicated functions

Sleep Mode
• Based on low flow
• Boost function
• Internal or external
signal to enter sleep
mode
• Maximizes energy
savings
• Reduces wear on
equipment

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


81
Pump dedicated functions

Initial / Final Ramp


• Independent ramp from
zero to minimum freq
• User programmable time
period

• Protects bearings and


other equipment
• Reduces maintenance

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


82
Pump dedicated functions

Check Valve ramp time

• Used when ramping down


from min. speed.
• Slow ramp rate at ramping
down from min. speed
• Protect check valves
• Prevent water hammering

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


83
Pump dedicated functions
Pipe fill mode
-For vertical and horizontal pipe
systems

• Eliminates Water Hammer


Programmable fill rate in
units/second
• Normal ramp from fill
pressure to operating
pressure
• Increase system
performance
• Prevent water hammering
Pipe Fill Example

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


84
Pipe Fill, vertical pipes

PID ramp the


pressure at a user specified
rate units/sec.

Time

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


85
Pipe Fill, horizontal pipes

Constant speed for a set


time.

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


86
Pump dedicated functions

Flow compensation
at setpoint
• Simplifies sensor
installation
• Mount the pressure sensor
close to the pump
• Easy installation
• Reliable system
• Saves money
• Saves energy

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


87
Automatic Flow compensation

1. Program the system


curve
2. Closed loop PID
decrease the speed
depending on pressure
3. Flow compensation
decrease the setpoint

• Flow resistance decreases


with reduced flow
• Saves significantly amount
of energy

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


88
Automatic Flow compensation

1. Program the system


curve
2. Closed loop PID
decrease the speed
depending on pressure
3. Flow compensation
decrease the set point

• Also useable with


Cascade CTL.
• Saves significantly
amount of energy
Flow comp. and cascade CTL
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


89
VLT® AQUA Drive

VLT Software
VLT® Set-up Software MCT 10

Easy to use on/off-line commissioning tool


Planned:
- Profi-Safe option SW.
- Wizards Framework Builder
- Remote access.
- Alarm collection.
More functionality:
- Full Scope & graph
- Alarm history in saved
Free of charge projects.
- Option configuration
- Project files (max 4) - MCO305
- Scope & Graph (max 2)
- View Alarm history

2/2
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


91
Cascade CTL configuration tool

•Set up feedback

•Set up Setpoint

Cascade CTL
configuration tool

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


92
Cascade CTL configuration tool

•Set up cascade

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


93
VLT® Energy Box

• PC tool to calculate Return on


Investment, Payback Time
• Communicate and withdraw
energy data from the Drive
• Easy way to follow up your
energy bill

1/2
Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


94
VLT®Energy Box

PC tool to
calculate
Return on
Investment,
Payback Time

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


95
VLT®Energy Box

Generated
Reports:

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


96
VLT®Energy Box
Generated Reports for documentation

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


97
Local Service – Globally

Dedicated Water and


Waste Water sales
organisation
world-wide with
skilled specialists

• Spare parts
• Hotline support
• Preventative service
• Service
around-the-clock
• Global service network

Confidential / Property of 9 August, 2008

Danfoss Drives A/S Name/department


98