Professional Documents
Culture Documents
Received 12 September 2005; received in revised form 17 February 2006; accepted 17 February 2006
Available online 17 April 2006
Abstract
This work presents a detailed investigation on the performance characteristics of vector surge relays used to detect islanding of distributed
synchronous generators. A detection time versus active power imbalance curve is proposed to evaluate the relay performance. Computer simulations
are used to obtain the performance curves. The concept of critical active power imbalance is introduced based on these curves. Main factors affecting
the performance of the relays are analyzed. The factors investigated are voltage-dependent loads, load power factor, inertia constant of the generator,
generator excitation system control mode, feeder length and R/X ratio as well as multi-distributed generators. The results are a useful guideline to
evaluate the effectiveness of anti-island schemes based on vector surge relays for distributed generation applications.
© 2006 Elsevier B.V. All rights reserved.
Keywords: Distributed generation; Islanding detection; Synchronous generators; Vector surge relays; Vector shift relays
1. Introduction common devices used for this purpose are the modified ver-
sions of the under/over voltage and under/over frequency relays.
Distributed generation has recently gained a lot of momentum Among them, devices based on variations of frequency have
in the power industry due to market deregulation, technologi- been recognized as the most reliable option by the industry so
cal advances, governmental incentives and environment impact far. Representative examples of such relays are the rate of change
concerns [1–3]. An important requirement for the connection of of frequency relay (ROCOF) and the vector surge relay (VSR),
synchronous generators to distribution networks is the protec- which is also known as vector shift or voltage jump relay [1–3].
tion system capability of islanding detection. Islanding occurs However, it has been well recognized that such relays tend to
when a portion of the distribution system becomes electrically fail when the mismatch or imbalance between the generation
isolated from the remainder of the power system, yet continues and the load in the islanded system is small. As more and more
to be energized by distributed generators. This is also known as distributed generators are added to utility systems, it has become
loss of mains or loss of grid [3]. Failure to trip islanded gen- clear that a good understanding on the operating characteristics
erators can lead to a number of problems to the generator and of these relays is important. The results can be very useful for
the connected loads. The current industry practice is to discon- utility engineers to evaluate the reliability and robustness of a
nect all distributed generators immediately after the occurrence given distributed generation anti-islanding scheme.
of islands [4,5]. Typically, a distributed generator should be dis- The objective of this paper is to present our investigation
connected within 200–400 ms after loss of main supply. In order results on this subject. The concepts of detection time versus
to achieve such a goal, each distributed synchronous genera- active power imbalance curve and critical active power imbal-
tor must be equipped with an islanding detection device. The ance are proposed to characterize the relay performance. Since
vector surge relays have been widely used by the industry, it is
selected as the study subject in this paper. However, the proposed
∗ Corresponding author. Tel.: +55 19 37883740; fax: +55 19 32891395. method can be applied to other types of anti-islanding relays as
E-mail address: walmir@dsee.fee.unicamp.br (W. Freitas). well.
0378-7796/$ – see front matter © 2006 Elsevier B.V. All rights reserved.
doi:10.1016/j.epsr.2006.02.011
W. Freitas et al. / Electric Power Systems Research 77 (2007) 170–180 171
This paper is organized as follows. The principle of vector Fig. 3. Voltage vector surge and vector surge relay cycle-by-cycle measure-
ments.
surges relays is explained in Section 2. The detection time versus
active power imbalance curves and the concept of critical active
power imbalance are discussed in Section 3. The main factors the cycle duration also changes. Vector surge relays are based
affecting the performance of vector surge relays are investigated on such phenomena [3].
in Section 4. The factors investigated are voltage-dependent Vector surge relays available in the market measure the dura-
loads, load power factor, inertia constant of the generator, gener- tion time of an electrical cycle and start a new measurement at
ator excitation system control mode, feeder length and R/X ratio each zero rising crossings of the terminal voltage. The current
as well as multi-distributed generators. Finally, in Section 5, the cycle duration (measured waveform) is compared with the last
main conclusions are analyzed. one (reference cycle). In an islanding situation, the cycle dura-
tion is either shorter or longer, depending on if there is excess or
2. Principle of vector surge relays deficit of power in the islanded system, as shown in Fig. 3. This
variation of the cycle duration results in a proportional variation
When a synchronous generator is operating in parallel with of the terminal voltage angle θ, which is the input parameter of
a distribution network, as depicted in Fig. 1, there is a voltage vector surge relays. If the variation of the terminal voltage angle
drop V between the terminal voltage VT and the generator exceeds a pre-determined threshold α, a trip signal is imme-
internal voltage EI due to the generator current ISG passing diately sent to the circuit breaker. Usually, vector surge relays
through the generator reactance Xd . Consequently, there is a allow this threshold to be adjusted in the range from 2◦ to 20◦
displacement angle between the terminal voltage and the gen- [3]. Another important characteristic available in these relays is
erator internal voltage, whose phasor diagram is presented in a block function by minimum terminal voltage. If the terminal
Fig. 2(a). In Fig. 1, if the circuit breaker CB opens, due to a fault voltage drops below an adjustable level threshold Vmin , the trip
for example, the system composed by the generator and the load signal from the vector surge relay is blocked. This is to avoid, for
L becomes islanded. At this instant, the synchronous machine example, the actuation of the vector surge relay during generator
begins to feed a larger load (or smaller) because the current ISYS start-up or short-circuits.
provided by (or injected into) the power grid is abruptly inter-
rupted. Consequently, the angular difference between VT and EI 3. Determination and analysis of the performance
is suddenly increased (or decreased) and the terminal voltage curves
phasor changes its direction, as shown in Fig. 2(b). Analyzing
such phenomenon in the time-domain, the instantaneous value In this section, the determination and analysis of the detection
of the terminal voltage jumps to another value and the phase time versus active power imbalance curves, i.e. the performance
position changes, as depicted in Fig. 3, where the point A indi- curves, are discussed. In this paper, the performance curves
cates the islanding instant. This behavior of the terminal voltage are obtained by using repeated dynamic simulations. The pre-
is called vector surge or vector shift. It is possible to verify that islanding active power imbalance is gradually varied from 1 to
0 pu, referred to the MVA rating of the generator, by chang-
ing the generation–load profile in the islanded system. For each
active power imbalance level, dynamic simulation is conducted,
the detection time is determined once that the relay activation
criterion is met and then the curves are plotted.
In this work, the network components were represented by
three-phase models. Distribution feeders were modeled as series
RL impedances. Transformers were modeled using T circuit. The
synchronous generators were represented by a sixth-order three-
phase model in the dq rotor reference frame [6]. The generators
were considered equipped with an automatic voltage regulator,
Fig. 2. Internal and terminal voltage phasors: (a) before the opening of circuit which was represented by the IEEE-Type 1 model. The mechan-
breaker and (b) after the opening of circuit breaker. ical power was considered constant, i.e. the primer mover and
172 W. Freitas et al. / Electric Power Systems Research 77 (2007) 170–180
Fig. 5. Single-line diagram of the test system 1. Fig. 7. Concept of critical active power imbalance level.
W. Freitas et al. / Electric Power Systems Research 77 (2007) 170–180 173
Fig. 9. Most optimistic cases vs. most conservative cases—case with deficit of
reactive power in the islanded system.
assumes the lowest value, is obtained when the loads are con-
stant impedance type and there is excess of active power in the
islanded system. In the case of constant power loads, there is
no difference between the cases with deficit and excess of active
power. The critical active power imbalances for the most conser-
vative and optimistic cases and different relay settings are shown
in Fig. 9, which were obtained considering that the required
detection time is 200 ms. It can be observed that if the loads
are impedance constant type and the relay setting is 2◦ , then
the critical active power imbalance will vary from 2.5 to 18.0%.
The cases with excess of reactive power in the islanded system
are presented in Fig. 8(b). In these cases, the generator exciter
was controlled to keep the generator working at 0.90 capacitive
power factor. The situations of excess and deficit of active power
were simulated as discussed in the previous cases. The results
are contrary to the previous cases, i.e. the most conservative case
can be related to the situation with excess of active power and
Fig. 10. Dynamic behavior of the active power load during islanding: (a) deficit
the most optimistic case is related to the situation with deficit of reactive power and (b) excess of reactive power.
of active power. The impact of voltage-dependent loads on the
performance of vector surge relays is explained in the sequence.
The dynamic behavior of the total active power load of the 24 MW and the generator is injecting 30 MW into the network.
system shown in Fig. 5 considering different types of loads In this case, the generator exciter is controlled to force the gener-
and sceneries of pre-islanding reactive power imbalance is pre- ator to operate at 0.90 capacitive power factor. Thus, before the
sented in Fig. 10. In this figure, the system becomes islanded islanding, the generator is injecting 14.5 MVAr into the network
at t = 0.25 s. In Fig. 10(a), the total active power load before the and the substation is consuming 3.4 MVAr. Therefore, there is
islanding is 30 MW and the generator is injecting 20 MW into the excess of reactive power in the islanded system. Consequently,
network. In this case, the generator exciter is controlled to keep the nodal voltages increase after the islanding; as a result, in
terminal voltage constant at 1 pu. Thus, the generator is injecting the case of constant current and constant impedance loads, the
7.9 MVAr into the network and the rest of the reactive power con- total active power load in the islanded system increases after the
sumed by the system is supplied by the substation (3.9 MVAr). In islanding. Again, the largest variation can be related to constant
this situation, after the islanding, the nodal voltages decrease due impedance loads. The impacts of the possible combinations of
to lack of reactive power, although the generator increases the active and reactive power in the islanded system (Cases a–d) on
reactive power injected after islanding. Consequently, in the case the relay performance are discussed below.
of constant current and constant impedance loads, the total active In the case of active and reactive power deficit (Case a),
power load in the islanded system decreases after islanding. The the total active power load decreases after islanding due to
largest variation can be related to constant impedance loads. In nodal voltage reduction and such fact decreases the active power
Fig. 10(b), the total active power load before the islanding is imbalance in the islanded system. Consequently, vector surge
W. Freitas et al. / Electric Power Systems Research 77 (2007) 170–180 175
Fig. 13. Critical power imbalance as affected by the inertia constant of the Fig. 15. Dynamic behavior of total active power load during islanding consider-
generator. ing different excitation system control modes (synchronous generator injecting
20 MW).
in Fig. 13. The results show that vector surge relays are more
effective when employed to protect small generators.
loads under distinct control modes. The dynamic behavior of
the active power load for different control modes is shown in
4.4. Excitation system control mode
Fig. 15 when the generator is injecting 20 MW. It can be seen
that the load reduction is larger when the generator is operated
A distributed synchronous generator typically has different
at unitary power factor. As a result, the active power imbalance
modes of controlling its excitation system. One is to maintain
reduction in this case is larger too, becoming more difficult to
constant terminal voltage (voltage control mode) and another
detect the islanding situation. For the same reason, the case in
one is to maintain constant power factor (power factor control
which there is excess of active power and deficit of reactive
mode) [3]. In the power factor control mode, in this section,
power after islanding showed that the critical power imbalance
the generator was controlled to keep unitary power factor oper-
is smaller in power factor control mode than that obtained in
ation. The performance curves for the two control modes are
the voltage control mode. It was also found that if the load is
compared in Fig. 14. In these cases, there is deficit of reac-
modeled as constant power load, there is no difference between
tive and active power in the islanded system. It is found that
the two control modes.
the critical power imbalance is larger if the excitation system is
controlled by power factor rather than by voltage. This is due
to the different dynamic behavior of the constant current active 4.5. Feeder length and X/R ratio
is not affected. This is because both relays have the same set-
ting. Consequently, there is almost no interference between the
relays. The conclusion drawn from the results is the following:
if there is a deficit of reactive and active power in the islanded
system, a tight setting for one relay can reduce the critical power
imbalance level related to the other relay. This occurs because
the trip of the first generator will increase the power imbalance
level in the islanded system, leading to the other relay to operate
in a shorter time.
For the case in which there is excess of active power after
islanding, the simulation was conducted by maintaining con-
stant power for both generators at 6 and 4.5 MW. Then, the total
system active power load was varied from 10.5 to approximately
0 MW to create different power imbalance scenarios. The results
are shown in Fig. 20, where only the performance curves related
to VSR1 are presented. The results also suggest that there is inter-
ference between the two relays when VSR1 setting is greater
Fig. 21. Influence of multi-vector surge relays on the critical power imbalance:
Fig. 20. Relay performance curves as affected by multi-distributed generators (a) deficit of reactive and active power and (b) deficit of reactive power and
(deficit of reactive power and excess of active power). excess of active power.
W. Freitas et al. / Electric Power Systems Research 77 (2007) 170–180 179
Table 1
Summary of the investigations concerning the vector surge relay performance
Case investigated Load model Description Results
The influence of Constant power, constant current and Four cases were investigate for each Voltage-dependent loads have huge
voltage-dependent loads constant impedance load model: influence on the relay performance
• Case (a): deficit of active and Most conservative cases:
reactive power
• Case (b): excess of active power • Case (a) and constant impedance
and deficit of reactive power loads
• Case (c): excess of active and • Case (c) and constant impedance
reactive power loads
• Case (d): deficit of active power Most optimistic cases:
and excess of reactive power
• Case (b) and constant impedance
loads
• Case (d) and constant impedance
loads
The influence of load power factor Active component: constant current Deficit of active and reactive power Load power factor has little influence
type has been considered on the relay performance
Reactive component: constant Load power factors tested: 0.80, 0.90
impedance type and 0.95
The influence of the inertia Active component: constant current Deficit of active and reactive power The inertia constant of the generator
constant of the generator type has been considered has huge influence on the relay
Reactive component: constant Values of the inertia constant of the performance. In fact, the larger the
impedance type generator: 0.5, 1 and 1.5 inertia constant, the larger the critical
power imbalance
The influence of the Active component: constant current Deficit of active and reactive power The control mode of the excitation
excitation system control type has been considered and two control system has huge influence on the
modes modes of the excitation system were relay performance. Under power
investigated: factor control mode, the critical
Reactive component: constant • Voltage control: set point equal power imbalances are larger than
impedance type to 1 pu those obtained under voltage control
• Power factor control: set point mode
equal to 1
The influence of the feeder Active component: constant current Deficit of active and reactive power Variations on the feeder length have
length type has been considered. The feeder little influence on the relay
Reactive component: constant length has been multiplied by 0.5, 1 performance
impedance type and 2
The influence of X/R ratio Active component: constant current Deficit of active and reactive power The ration X/R has little influence on
type has been considered. The feeder X/R the relay performance
Reactive component: constant ration length has assumed the
impedance type following values: 4.3, 2.1 (by halving
X) and 2.1 (by doubling R)
presence of the second relay can decrease or increase the critical • The relay performance can be quite different depending on
power imbalance of the first relay. if there is excess or deficit of active and reactive power
in the islanded system. The basic factor behind the differ-
ent responses is the voltage-dependent characteristics of the
5. Conclusions loads. These important results show that utility engineers
must analyze the most conservative cases during studies of
This paper has presented an extensive investigation on the vector surge relays. Typically, such cases are characterized
performance characteristics of the vector surge relays employed by:
to detect islanding of distributed synchronous generators. The - There is deficit of active and reactive power in the islanded
proposed detection time versus active power imbalance curves system and loads are constant impedance type.
proved to be a useful tool to assist the evaluation of the relay - There is excess of active and reactive power in the
performance. The investigation on the relay performance has islanded system and loads are constant impedance
been done through the analysis of various cases, which can be type.
summarized in Tables 1 and 2, as well as the main results. • The main factors affecting the performance of vector surge
Based on the results of the investigation, the main conclusions relays are inertia constant of the generator, load type and
are summarized below: the excitation system control mode. The excitation control
180 W. Freitas et al. / Electric Power Systems Research 77 (2007) 170–180
Table 2
Influence of multiple distributed generators on the vector surge relay performance (see Section 4.6)
Case investigated Load model VSR2 setting (◦ ) VSR1 setting (◦ ) Results
Deficit of active and reactive power Constant impedance 5 5 No interferences between the relays
10 After VSR2 operation, the disconnection of SG2 causes
the active power imbalance rising and, consequently,
accelerates the VSR1 operation
15 After VSR2 operation, the disconnection of SG2 causes
the active power imbalance rising and, consequently,
accelerates the VSR1 operation
Excess of active and deficit of Constant impedance 5 5 No interferences between the relays
reactive power 10 After VSR2 operation, the disturbances cause large
transients that provoke VSR1 actuation
15 After VSR2 operation, the disconnection of SG2 causes
the active power imbalance reduction and, consequently,
delays the VSR1 operation