Distribution Design System

UNIT 4: CABLE
1.0 INTRODUCTION 1.1. 1.2. 1.3. 1.4. Cable is a mean or tool for which electrical energy is being distributed from one place to others. Cable also means to prevent any person from direct contact with the live conductors. The conductor has to be covered with a layer of insulating material, called cable insulation. To prevent any person from direct contact with the live conductors, a cable can be defined as a length of insulated single conductor or two or more conductors with its own insulation which are laid up together. The insulated conductor or conductors may or may not be provided with overall covering for mechanical protection. Where mechanical protection is required, a second insulating layer known as sheath is wrapped around the first layer of insulation. For stronger protection, a layer of steel wire known as armour is wound around the first layer. A sheath usually PVC is then placed over the armour.

1.5.

2.0 CONDUCTORS 2.1. 2.2. 2.3. The most common conductors used in cables are copper (Cu) and aluminum (Al). The resistance of copper at 70oC is 0.017/mm2/m and aluminum 0.0283/mm2/m. Aluminum has become a major alternative to copper as the price is cheaper. However, it has poorer conductivity than cooper. Thus, the cross sectional area of aluminum is larger. Example: for the same current rating, 300mm2 Al cable is approximately equivalent to 185mm2. A conductor and its immediate insulation known as core. The conductor is identified by colour code: 2.5.1.1. Red, Yellow and Blue for phase conductors. 2.5.1.2. Black for Neutral. 2.5.1.3. Green/Yellow for CPC. Ground wire.

2.4. 2.5.

A.Aman

BEKP 4783

Distribution Design System

2.6.

Rated Voltage for cable is determined by Vo/V: 2.6.1.1. Vo is voltage between insulated conductor to earth and V is between phase conductor. Example: Low voltage power cable 600/1000V.

2.7.

Conductors can be solid or stranded. Stranded conductors are more flexible and easier to handle. 2.7.1.1. 2.7.1.2. Solid conductor- single wire of the required cross-sectional area is used. Stranded conductor several wires of small cross-sectional are twisted together to form a larger wire of the required sectional area. Stranded conductors are more flexible and easier to handle. Normally 3 to 7 wire twisted to form one conductor.

Figure 1- Cable conductor 2.8. Bare conductors are used in overhead HV transmission cable, earthing system, lighting protection and busbars. Insulated conductors are used in domestic and industrial installation, overhead LV (ABC), underground cable system and submarine cable system. Sizes of conductors are denoted by the cross-sectional area of the conductors for example 6mm2 cable means that the total cross-sectional area of all the strands is 6mm2.

2.9.

2.10. Copper conductor is widely used for the electrical earthing. The use of aluminum as earth electrode or earthing conductor is prohibited. 3.0 INSULATION MATERIALS 3.1. The selection of insulation materials is based on their physical and electrical properties. Materials used as insulation for electrical cable must; 3.1.1.1. Provide safe condition of conductors at it rated voltage. 3.1.1.2. Electrical insulating properties should not deteriorate with time. 3.1.1.3. Have high mechanical strength during installation and operation. 3.1.1.4. Have thermal stability- chemical composition not effect by heat. 3.1.1.5. No environment or surrounding effect like weather or water.

A.Aman

BEKP 4783

Distribution Design System

3.2. Types of insulation material used: a) Butyl rubber can be used in ambient temperature of up to 80oC. b) Silicone rubber suitable for temperature -60oC to 150oC. c) PVC poly-vinyl chloride or thermoplastic. Soften at 80oC. d) Glass fiber Good heat resistance up to 155oC. e) Paper paper impregnated with mineral oil mixed resin. f) Mineral insulating material is magnesium oxide. Withstand very high temperature up to copper melting point. g) XLPE cross-linked polyethylene h) FR fire retardant (specially formulated PVC compound) 4.0 CABLE TYPES AND SPECIFICATIONS 4.1. Cables are named in accordance to: a) Type of insulation b) Mechanical protection c) External sheath Example: XLPE/SWA/PVC XLPE- (cross-linked polyethylene) insulation, SWA steel wire armored (mechanical protection) and PVC external sheath. 4.2. The most common type of cables used in distribution systems are: a) PVC PVC insulated. b) PVC/PVC PVC insulated, PVC sheath c) PVC/SWA/PVC PVC insulated, steel wire armored, PVC sheath. d) FR (Fire Retardant) fire rate equipment e.g. emergency light, KELUAR sign, BOMBA lift. e) MICC Mineral insulated copper covered. f) MICS Mineral insulated copper sheath. g) XLPE/SWA/PVC XLPE insulation, steel wire armored, PVC sheath underground cables. h) PILC Paper Insulated Lead Covered used in HV system. 4.3. The current capacity must be sufficient to cater for the maximum sustained current which normally flows through the cable and the insulation must be adequate with the system voltage. 4.4. In a single line diagram, the type and size of the cable is written as follows: Example: 2x120mm2 4C PVC/SWA/PVC (Al) cable means that 2 set of 120mm2, 4 Core, PVC insulated, steel wire armored, PVC sheath and aluminum conductor.

A.Aman

BEKP 4783

Distribution Design System

4.5. According to BS 6004, all PVC insulated cables are suitable only as long as the conductor temperature does not exceed 70oC and for mineral insulated cables to BS 6207 can be operated up to 135oC. 4.6. A sample of current carrying capacity (ampacity) is shown in TABLE 4D1A (IEE Wiring Regulation BS 7671- Requirement for Electrical Installation) for single core PVC insulated cables, non-armored with or without sheath.

Figure 2- Types of cables 5.0 INSTALLATION 5.1. 5.2. 5.3. Small wiring PVC or FR cables can be installed in conduits or trunkings. The conduits and trunkings are made of steel or PVC. Schedule of methods of installation of cables is shown in TABLE 4A1 of IEE Wiring Regulation BS 7671. Table 4A1 in IEE Wiring Regulations BS 7671 shows the methods of installation of cables and conductors.

A.Aman

BEKP 4783

Distribution Design System

5.4.

There are seven types of wiring systems and there are twenty methods of installations in general wiring or in electrical installation. The using of method of installation is to find the appropriate reference for determining current carrying capacity of the cable. Below are the lists of seven types of wiring system. i. Open and clip direct ii. Cable embedded direct in building material. iii. In conduit iv. In trunking v. In the free air, on cleats, brackets or a ladder vi. Cable in building voids vii. Cable in trenches

5.5. 5.6.

For domestic wiring installation only method 1, method 3 and method 4 have to consider. The method of installation in final circuits wiring installation is importance, where the methods of installations will influence of cable size and selection of rated current of protective devices. Common used of LV cables: a) Non-Armoured PVC cables installed in conduits & trunking for internal wiring. b) Non-Armoured PVC/PVC cables general indoor use in domestic & commercial installation. c) Armoured PVC cables for mains & sub-mains application. d) MICS cables areas of extreme temperature or for circuit supplied to firefighting equipment. e) FR cables used in severe condition (firefighting / flammable equipment)

5.7.

6.0 CABLE SIZING AND CURRENT RATING 6.1. The size of the cable to be used in a circuit depends on: a) The full load current based on design current Ib. b) Ambient temperature Ca factor. c) Maximum allowable conductor temperature. d) Conductor material current ampacity. - Table 4D1A and 4D2A in BS7671 for copper conductor. e) The method of installation. Table 4A1 in BS7671 f) Insulation material. - Table 52B (Regulation 523-1) in BS7671 g) The number of circuits installed together Cg. h) The voltage drop in the cable. - Table 4D1B and 4D2B in BS7671. 6.2. It is a normal practice that the design engineer relies on the tabulated current carrying capacities as shown in Appendix 4 of the IEE Wiring Regulation

A.Aman

BEKP 4783

Distribution Design System

BS 7671. However, it should be noted that the tabulated current ratings are based upon a given set of condition. a) Ambient temperature. b) The heating effect of adjacent cable is not considered. c) The cable is installed according to the rating table being used. d) There is no surrounding thermal installation. 6.3. Therefore, any changes on the above said conditions, the cable rating has to be adjusted according to the appropriate correction factor as follows. a) Ambient temperature Correction Factor (Ca). - Table 4C1 in BS7671 b) Grouping Correction Factor (Cg). - Table 4B1 in BS7671 c) Thermal Insulation Correction Factor (Ci). 6.4. For ambient temperature higher than specified temperature of 30oC, the rated of the heat flow out of the conductor will be lower and thus will increase the conductors operating temperature above permitted value. 6.5. Correction factor of temperature Ca in determining the current carrying capacity of cable are provided in Table 4C1 of IEE Wiring Regulation BS 7671. 6.6. Cables installed in the same enclosure or bunch together will get warm when all are carrying current. Those cables close to the edges of enclosures will be able to release the heat outward but will be restricted in losing heat inwards toward other warm cable. Cable in the centre of the enclosure may find it difficult to lose heat at all and as a result will increase the conductor temperature. 6.7. The correction factor for groups Cg is shown in Table 4B1 of IEE Wiring Regulation BS 7671. 6.8. Many new building are now provided with better thermal insulating material for roofs and cavity walls to reduce the heat lose. As thermal insulation is design to limit heat flow, a cable in contact with it will tend become warmer than the preferred operation conditions. 6.9. IEE Wiring Regulation 523-04 recommends that for a single cable, which is likely to be surrounded by thermally insulated material over a length of more than 0.5m, the thermal insulated Ci is 0.5 times the tabulated current carrying capacity (method 1). Table 52A of IEE Wiring Regulation BS 7671 shows the de-rating factor for cable surrounded by thermal insulation for a length less than 0.5m.

A.Aman

BEKP 4783

Distribution Design System

7.0 DETERMINE THE MINIMUM TABULATED CURRENT RATING 7.1. After considering all the above correction factors, the minimum tabulated current rating for the cable can be determined as recommended in the IEE regulation. 7.2. As an example the related table for copper conductor current carrying capacity 7.3. The formula used is as follows: a) Where overload protection is required: It min In Ca x Cg x Ci b) Where overload protection is not required: It min Ib Ca x Cg x Ci

8.0 VOLTAGE DROP 8.1. The resistance of the conductor increases as the length increases and/or the cross sectional area of cable decreases. 8.2. Associated with an increase resistance is a drop in voltage, which means that a load at the end of long or thin cable will not have the full supply voltage available. 8.3. To ensure the voltage drop from the supply intake to the terminal of any appliance does not exceed the appliance operating tolerance, which is normally 10%. 8.4. IEE Regulation 525-01 specifies that the voltage drop between the origins of installation does not exceed 4% of the nominal voltage of the supply. 8.5. The utility supply regulation normally require that the voltage drop in the circuit does not exceed 2.5% of the nominal voltage, i.e. 6V for single phase 240V supply and 10.4V for a three phase 415V supply. This is also a good practice for a designer since the cable routing on the paper may differ from the actual at site installation. 8.6. Values of voltage drop are tabulated for a current of 1 Amp for a 1 meter run, i.e. for a distance of 1 meter along the route taken by the cables. This Tabulated Voltage Drop constant (TVD) is expressed in m per ampere per meter run mV/A/m. 8.7. Voltage drop formula is as follows:

A.Aman

BEKP 4783

Distribution Design System

Vdrop =

TVDr I b length(l ) for cable 16mm2 or less 1000

Vdrop =

(TVDr cos + TVDx sin ) I b length


1000

8.1.1 VOLTAGE DROP CALCULATION 8.1.1.1 TEMPERATURE CORRECTION ON RESISTIVE VALUE

8.1.1.2 In relevant standards and manufacturer specifications, the value of conductor resistance is usually given at 20oC of conductor temperature. This conductor resistance value will increase according to the resistance temperature coefficient when conductor temperature increases due to load current. 8.1.1.3 The coefficient is approximately equal to 0.004 per oC at 20oC for both copper and aluminium conductor. The value of conductor resistance is zero mathematically at a conductor temperature of 230oC.

Figure 3: Calculation of resistance value at various 8.1.1.4 The conductor resistance value at other temperature such as 115 can be calculated as: 115 = 20 230 + 115 230 + 20 = 20 x 1.38

A.Aman

BEKP 4783

Distribution Design System

8.1.1.2 CONDUCTOR TEMPERATURE ON VOLTAGE DROP (TVDr)

8.1.2.3 The TVDr value is based on the resistance of conductor at rated temperature (i.e. 70oC for PVC-insulated Cu conductor) corresponding to the conductor carrying its rated current. 8.1.2.4 If design current is significantly less than the rated current, the actual value of TVDr will be lower due to lower conductor temperature. Thus, the new value of TVDr at other temperatures is given by: ( TVDr )40oC = 230 70 230 + 40 x ( TVDr )70oC

8.1.2.5 The value of reactance (TVDx) is not influenced by temperature, therefore the temperature correction does not apply to the reactance values.

Figure 4: Rated conductor temperature

9.0 PROTECTION AGAINST OVERLOAD

9.1 Overload currents may occur in various circuits in an installation where they are carrying more current than their rated capacity. The consequences of overload currents will increase the temperature of conductors and the effectiveness of the insulation and its expected life may be reduced.
9.1.1 REQUIRED CONDITION FOR OVERLOAD PROTECTION

9.1.1.1

To provide an adequate protection for overload, IEE Regulation 43 requires the following conditions to be satisfied: 1) IN IZ 2) I2 1.45 IZ Where IN : current rating of the protective device IZ : current rating of the cable under particular installation methods. I2 : current magnitude causing an effective operation of the protective device.

A.Aman

BEKP 4783

Distribution Design System

9.1.1.2 9.1.1.3

For MCB, the value I2 is 1.45 IN. For MCCB and ACB, the value I2 is 1.3 IN. For fuse, the value I2 is 1.6 IN. The effective operating time is 2 hours (for MCB, MCCB and ACB), except for breaker less than 63A where the effective operating time is reduced to 1 hour. For fuse, the effective operating time is in the range from 1 to 4 hours depending on the current rating. In loading condition (I2 1.45 IZ), the cable is allowed to increase 145% of its rated capacity even though conductor temperature is higher than rated temperature but still below its critical temperature. Critical temperature refers to the temperature that will cause insulation failure.

9.1.1.4

9.1.1.5

To assess whether there is an overload protection and how adequate it is, we define the degree of overload protection as: OL_P_Yes = 1.45 IZ - I2 x 100% 1.45
Z

9.1.1.6

A positive value of (OL_P_Yes) means that the circuit is adequately protected against overload current and a higher percentage indicate that the circuit is more unlikely to be overloaded. The condition is vice versa for negative value of (OL_P_Yes).

9.1.2 SMALL OVERLOADS AND CABLE UTILISATION

9.1.2.1

There is possible to have a range of very small overload which will not be detected by the protective device (i.e. at the range between IZ I I2). In general statement IEE Regulation 433-01-01, it states that every circuit shall be designed so that a small overload of long duration is unlikely to occur. Therefore, we define the existence of small overload as: Sm_OL_No = IZ - I2 x 100% IZ

9.1.2.2

9.1.2.4

A positive value of (Sm_OL_No) indicates no undetected small overload while a negative value means that small overload range exists. Thus, designer should as far as possible minimize the negative percentage (i.e. increase the conductor size will totally eliminate the occurrence of such small overloads).

A.Aman

10

BEKP 4783

Distribution Design System

9.1.2.5

If value of IZ is very close to IN, the un-detected small overloads may occur (under-design) and if the value of IZ is very much higher than IN, then it implies a larger size of cable has been selected which will increase the installation cost and not fully utilized (over-design).

9.1.3 OMISSION OF OVERLOAD PROTECTION

9.1.3.1

There are several circuits in which a break in current (tripping) by the operation protective devices can cause danger. Example; breaking the current of a lifting electromagnet could cause the load to drop, or breaking the current in CT could induce a very high E.M.F (electromagnetive force). So, it can be replaced by an overload alarm instead of overload breaker. For starting current of a motor, the designer has to ensure that the protective device of the motor circuit will not trip during motor starting. If starting current is large, the rated current IN may have to be much higher than the design current IB. Therefore, the current rating of cable, IZ has to be equal to or larger than IN. IN >> IB and IZ >> IB

9.1.3.2

9.1.3.3

9.1.3.4 9.1.3.5

However, if overload protection is not required, the designer can select IZ to be independent of IN, and IZ >> IB. If overload protection is required, the minimum tabulated current rating for the circuit is obtained by: It,min = IN Ca x Cg x Ci

9.1.3.6

If overload protection is not required, the minimum tabulated current rating for the circuit is obtained by: It,min = IB Ca x Cg x Ci

10.0

PROTECTION AGAINST SHORT CIRCUIT

10.1

It is necessary to ensure that the circuits conductor are protected adequately against short-circuit current by interrupting breaker quickly enough to prevent thermal damage to the cable.

A.Aman

11

BEKP 4783

Distribution Design System

10.1 REQUIRED CONDICTIONS FOR SHORT CIRCUIT PROTECTION

10.1.1 During fault conditions up to duration of 5 seconds, the maximum time that the cable can withstand the fault current can be approximately by the following formula: Tcable,max = k2S2 IF 2 Where k : maximum thermal capacity of the conductor for the type of insulation being used S : cross-sectional area of the conductor in mm2 IF : prospective short-circuit current in amperes
(Note: For more than 5 seconds, more complicated formula has to be used)

10.1.2 (Tcable,max) also known as critical time, which is the time taken for temperature of conductors to rise from rated value, Q1 to the critical value, QF. If QF is exceed, the insulation material fails and the whole cable is thermally damage. 10.1.3 To assess whether short-circuit protection is provided and how adequate it is, let us define: SC_P_Yes = ( Tcable,max Tbk,3-phase F ) x 100% Tcable,max

Where Tbk,3-phase F : operating time of the breaker corresponding to a current during 3-phase fault at the cable. 10.1.4 A positive percentage (SC_P_Yes) indicates that the circuit meets the requirement for shor-circuit protection and higher percentage implies a higher margin of short-circuit protection. A negative percentage (SC_P_Yes) is vice versa.

A.Aman

12

BEKP 4783

Distribution Design System

Figure 5: Values of k for calculation of the effects of fault current

10.2 FORMULA FOR SHORT-CIRCUIT CURRENT

10.2.1 Three Phase Fault: the current magnitude in each phase is identical except that the angle is shifted by 120o in each phase. Thus the current in each phase can be calculated as: IF,3 = VLL / 3 (RS + R1)2 + (Xs + X1)2 10.2.2 Line-to-Neutral Fault : IF,LN = VLL / 3 (RS + R1 + RN)2 + (Xs + X1 + XN)2 10.2.3 Line-to-Line Fault : IF,LL = VLL (2RS + 2R1)2 + (2Xs + 2X1)2

Where

RS : Resistance value of supply source (per phase) XS : Reactance value of supply source (per phase) R1 : Resistance value of phase conductor (per phase)

A.Aman

13

BEKP 4783

Distribution Design System

X1 : Reactance value of phase conductor (per phase) RN : Resistance value of the neutral conductor RN : Reactance value of the neutral conductor VLL : Line-to-Line voltage.

A.Aman

14

BEKP 4783

Distribution Design System

11.0

TABLES AND FIGURES (FROM IEE WIRING REGULATIONS)

11.1.

Conductors Temperature

11.2.

Cable Ampacity

A.Aman

15

BEKP 4783

Distribution Design System

Table 4D1A Single-core Copper Conductor Current Capacity

A.Aman

16

BEKP 4783

Distribution Design System

Table 4D2A Multi-core Copper Conductor Current Capacity


A.Aman 17 BEKP 4783

Distribution Design System

11.3.

Voltage Drop

A.Aman

18

BEKP 4783

Distribution Design System

Table 4D1B Single-core Copper Conductor Voltage Drop

Table 4D2B Multi-core Copper Conductor Voltage Drop

A.Aman

19

BEKP 4783

Distribution Design System

11.4.

Ambient Temperature Correction Factor, Ca

Table 4C1 Correction factor for ambient temperature. 11.5. Grouping Correction Factor, Cg

Table 4B1 Correction factor for group

A.Aman

20

BEKP 4783

Distribution Design System

11.6.

Schedule of Methods of Installation

Table 4A1 An example of methods of insallation

A.Aman

21

BEKP 4783

Distribution Design System

Example 1:

If four cores PVC insulated cable enclosed in trunking has tabulated current capacity 80A. If the ambient temperature 50C, the current rating of cable reduced 80A x 0.71 = 56.8A. The ambient temperature is refers to the temperature of the cable surrounding media and does not temperature of equipment. * 0.71 refers to Table 4C1 temperature correction factor IEE Wiring Regulation. * Tabulated current refers to Table 4D2A
Example 2:

A heater rated at 230V, 3kW is to be installed using twin-with-earth PVC insulated and sheathed cable clip direct in a roof space which has an ambient temperature of 40C. The circuit is protected by 15A MCB. The cable is bunched with four other-twin-earth cables for a short distance as shown in Figure 1. Determine the minimum tabulated current rating of the circuit and the size of the conductor.

Figure Example1
Solution

The design current is

3000 = 13 A 230 and the current rating f the protective device is IN=15A. IB = From table 4C1 the temperature correction factor at 40C is: Ca = 0.87 From table 4B1 the grouping correction factor of five circuits is: Cg = 0.6 The minimum tabulated current rating Iz,min for the circuit is
I z ,min = IN 15 = = 28.74 A C a C g 0.87 0.6

Referring Table 4D2A of IEE Wiring Regulation, column 6, a 4mm2 which tabulated current rating of 36A is selected. Although the design current is only 13A, a 4mm2 cable rated 36A is selected. Without correction factor of Ca and

A.Aman

22

BEKP 4783

Distribution Design System

Cg under same 13A operating conditions a 1mm2 cable rated at 15A is sufficient. Example 3:
The voltage drop on a circuit supplied from a 240V source by 16mm2 two-core copper cable 23m long, clipped direct and carrying a design current 33A, will be;

Solution:
Using formula Vdrop =
TVDr I b length(l ) due to less than 16mm2 1000

TVDr = 2.8mV - From Column 3 Table 4D2B, cable size 16mm2 two core cable single phase. Ib = 33A Length = 23m
Vdrop = mV I b length(l ) 1000

2.8 33 23 = 2.125V 1000

The maximum voltage drop for 240V installation less than 4% from the IEE Regulation is 9.6V, so the voltage drop fulfills the IEE Regulation requirement. The maximum cable length of installation with these parameters could be determined.

MaxLengh =

Vdrop 1000 mV I b 9.6 1000 = 149m 2.8 23

Example 4:

A 3 phase motor with full load current of 102A, and PF of 0.8 is to be fed by single core, PVC insulated, copper conductor, non-armoured cables, clipped direct on non metallic surface at 75 meter rub shown in Figure Example 2. Determine the size of conductor if the permissible voltage drop is 2%.

A.Aman

23

BEKP 4783

Distribution Design System

Figure Example 2

Solution: Let the design current Ib is the motor full load current. From table 4D1A, column 7, a 25mm2 cable with rated current of 104A is initially selected and the voltage drop is calculated as:
Vdrop =

(TVDr cos + TVD x sin ) I b length


1000

(1.5 0.8 + 0.175 0.6) 102 75 =


1000 = 9.983V . 9.983 are 2.40% of 415V which exceeds 2% of 415V. Thus the next higher size of 35mm2 is selected and Vdrop is re-calculated: =

(1.1 0.8 + 0.17 0.6) 102 75


1000

= 7.512V . 7.512V are 1.81% of 415V, thus in order to fulfill the requirement of Vdrop less than 2% a 35mm2 cable is selected.

A.Aman

24

BEKP 4783