Contents Description
Description ______________________________________ Construction Dimensions _________________________ Materials ________________________________________ Installation _______________________________________ Nomenclature ____________________________________ Performance Overview Technical Data _____________ Order Details ____________________________________ 2 3 3 4 5 6 8 Function

Supply Air Linear grille or roll down grille

Secondary air

Water coil

Primary air

Induction nozzles

TROX Floor Induction Unit Type BID with roll down grille

TROX Floor Induction Unit Type BID TROX Floor Induction Unit Type BID with linear grille

Description
TROX type BID floor induction units are used in air-water based air conditioning systems. They can help in exploiting the energyeconomy benefits of load dissipation (heating/cooling) through the medium of water; even in buildings where rooms have full height glazing without false ceilings and hence have smaller floor slab to slab heights. The external primary air volume flow required for ventilation enters a spigot into the primary air plenum and is discharged through nozzles. The secondary air is taken in from the room, passing through coils where it is heated or cooled, as appropriate. The secondary air is mixed with the primary air in the BIDs mixing zone and then supplied to the room via a linear grille or roll down grille in the floor area adjacent to the faade. BID diffusers may be used for cooling or for heating. When used for heating, BID units prevent discomfort caused by cold air downdraughts at the faade, when used for cooling, BID units minimise the thermal load and thermal radiation from the faade into the room. Because of their low height design, type BID floor induction units are particularly suited for use where floor slab to slab heights or false floor voids are small. The type BID unit is thus well suited for use in new buildings, but also in refurbishment projects and provides maximum architectural freedom, as neither a perimeter sill nor a suspended ceiling is required. If connected appropriately, the units can be used both for servicing individual rooms and for servicing zones with multiple units. The unit casing is sized so that control valves including actuators can be built in and thus remain easily accessible. A row of nozzles is stamped into a plate at the primary air plenum opposite the supply air spigot. Three different nozzle variants are available, depending on the required air volume flow rate. The linear grille or roll down grille can easily be removed for cleaning purposes. Caution! The cold water supply temperature must be selected such that it never falls below room dew point. Max. pressure: for 2-pipe and 4-pipe system 6 bar at 90C 7 bar at 20C Other operating pressures available on request!

Constuction Dimensions
Construction
TROX Type BID floor induction units consist of a load-bearing casing with a primary air duct and integral nozzles with various nozzle free areas for optimum induction at low sound power levels and pressure losses. The primary air side is connected via a centrally mounted spigot with a lip seal. The coils may be designed either for cooling or heating operation as a 2-pipe system or for cooling and heating operation as a 4-pipe system with copper pipe connections ( 12 x 1 mm), alternatively with a 1/2 external thread and with optional air venting. In addition, the units have a mixing chamber and a discharge area for supply air. The height of the unit may be altered by means of the adjustable feet. The grille ledge is suitable for: AFN-0-A aluminium linear floor grille (blades parallel to the faade, grille height 23 mm) ARR 20 aluminium roll down grille (bars perpendicular to the faade, grille height 20 mm) Combination with other grille options on request.

Materials
Casing and primary air duct are made of galvanised steel sheet. The coil consists of copper pipes with formed aluminium fins. The lip seal is made of rubber. The surfaces are untreated. On request, the casing and/or the coil can be powder-coated to RAL 9005 (black).

Dimensions in mm
L1
1100...1249 1250...1399 1400...1549 1550...1699 1700...1849

LN
900 1050 1200 1350 1500

A
895 1045 1195 1345 1495

B
875 1025 1175 1325 1475

30

Linear floor grille type AFN-0-A or aluminium roll down grille type ARR20 (order separately) Coil Primary air plenum with integral discharge nozzles Primary air connection spigot with lip seal Casing Water connection Cu-pipe 12 x 1 mm, on request R1/2 external thread Height-adjustable feet

View B

403 34

191

Detail X (rotated 90 degrees) Individual unit with perimeter frame


Gitterauflage Grille ledge

361

*D either 98 or 123

X
L1

A
34

D*

151

45

L2 (LN + 170)

Detail X (rotated 90 degrees) Unit for linear assembly (open-end)


Grille ledge Gitterauflage 10

View A-A
A

34

120

Installation
Once the BID unit has been lined up with the faade, the height-adjustable feet can be used to compensate for building tolerances. Care should be taken to ensure horizontal installation is achieved. Once this is complete, it is possible to secure or bolt the unit to the floor using the pre-stamped slots (11 x 30 mm). The grille or roll down grille selected is then laid on the BIDs grille ledge. In a continuous grille core installation the core must be suitably supported if its length is greater than the L1 dimension selected.

False Floor

Height adjustment feet

Pre-stamped slots (11 x 30 mm) for securing the unit to the building slab Floor slab

Single unit installation, e.g. with the AFN-0-A linear grille


Air entry spigot Primary air plenum Grille L1 + 1*

Continuous installation, e.g. with the ARR 20 roll down grille


Air entry spigot Primary air plenum Grille Supports (supplied by others)

* Floor opening required

405*

405*

Nomenclature

1,5 1.5 m

WK

tWRH WH

WH

tWVK WK

tWRK

tWVH

Secondary air L tL Primary air Pr


Pr

tPr

Nomenclature
tL tPr tW tRWV pt in K: Temp. diff. between room air tR and core tL in K: Temp. diff. between room air and primary air in K: Temp. diff. between water flow and return in K: Temp. diff. between room air and water flow temperature in Pa: Primary air pressure drop

pW in kPa: Water pressure drop tR tAN tWVK tWRK tWVH tWRH tPr FW
WH WK ges Pr S

in C: Room temperature in C: Induced secondary air temperature in C: Water flow temperature cooling in C: Water return temperature cooling in C: Water flow temperature heating in C: Water return temperature heating in C: Primary air temperature : Correction factor water volume flow rate in W: Water heating capacity in W: Water cooling capacity in W: Total cooling/heating capacity
Pr

in W: Primary air cooling/heating capacity in W: Secondary air cooling/heating capacity (for cooling S = WK /for heating S = WH ) in W: Convective heating capacity in l/h: Water volume flow rate cooling in l/h: Water volume flow rate heating in l/s: Primary air volume flow rate in m/s: Max. time average air velocity

HK

WK WH Pr L

LWA in dB(A): A-weighted sound power level LN L1 in mm: Nominal length in mm: Total length of casing 5

0,10 m 0.10 m

Performance Overview Technical Data


with 2-pipe / 4-pipe system
Reference values cooling
tR tAN FW tWVK WK tPr tRWV = = = = = = = 26 C 24.5 C 1.0 tPr = 16 C 110 l/h tPr tR = 10 K tWVK tR = 10 K

Reference values heating


tR = FW = tWVH = WH = tRWV = tAN = tPr = 22 C 1.0 50 C 50 l/h tWVH tR = 28 K

Room height: 3 m
Connecting spigot 98 123
LN Nozzle type l/s . V Pr m3/h LWA dB(A) LWA dB(A) Pt Pa vL m/s tL K

Cooling
2- and 4-pipe system
. Q Pr (air) Watt . QS (water) Watt . Q ges Watt tW K

Heating
2-pipe system
. . PW QS = Qges (water) (water) kPa Watt tW K

Heating
4-pipe system
tW K PW (water) kPa . . PW QS = Qges (water) (water) kPa Watt

4 6 9 8 12 17 15 20 30 4 8 11 10 15 20 15 25 35 5 9 12 10 15 24 16 24 36 5 10 13 10 15 25 17 25 40 6 11 15 14 22 28 20 33 40

14 22 32 29 43 61 54 72 108 14 29 40 36 54 72 54 90 126 18 32 43 36 54 86 58 86 130 18 36 47 36 54 90 61 90 144 22 40 54 50 79 101 72 119 144

<20 <20 27 <20 23 33 22 30 42 <20 20 29 <20 27 35 20 35 44 <20 21 29 <20 24 38 21 32 44 <20 21 29 <20 22 37 22 33 46 <20 21 30 <20 31 38 27 41 46

<20 <20 23 <20 <20 28 <20 23 35 <20 <20 25 <20 21 30 <20 27 36 <20 <20 25 <20 <20 32 <20 23 35 <20 <20 24 <20 <20 30 <20 23 36 <20 <20 26 <20 25 32 <20 29 35

52 117 264 54 122 244 64 144 256 38 151 285 62 138 246 47 131 256 45 145 257 47 105 269 41 93 208 35 140 237 37 83 230 37 80 205 41 137 254 59 144 234 42 115 169

0.07 0.10 0.15 0.09 0.13 0.19 0.12 0.16 0.24 0.06 0.12 0.17 0.10 0.15 0.20 0.11 0.18 0.25 0.07 0.13 0.17 0.09 0.14 0.22 0.11 0.16 0.24 0.07 0.13 0.17 0.09 0.13 0.22 0.11 0.15 0.25 0.08 0.14 0.19 0.11 0.18 0.23 0.12 0.19 0.23

1.82 1.59 1.39 1.96 1.75 1.58 2.03 1.89 1.71 1.98 1.57 1.41 1.99 1.76 1.62 2.18 1.92 1.76 1.98 1.62 1.47 2.13 1.88 1.63 2.29 2.06 1.85 2.11 1.67 1.52 2.26 1.99 1.70 2.38 2.15 1.90 2.10 1.70 1.53 2.15 1.86 1.73 2.39 2.09 1.98

48 72 109 96 145 205 181 241 362 48 96 133 121 181 241 181 301 422 60 109 145 121 181 289 193 289 434 60 121 157 121 181 301 205 301 482 72 133 181 169 265 338 241 398 482

181 230 291 228 290 355 276 328 417 190 285 341 272 345 405 287 389 471 226 317 372 282 357 463 308 392 493 234 348 401 292 369 487 330 413 536 269 378 445 365 468 531 372 495 549

229 303 400 324 435 560 457 570 778 238 381 474 393 526 646 468 691 893 286 425 516 403 538 752 501 682 927 295 468 558 412 550 789 535 715 1018 341 510 626 534 733 868 614 893 1031

1.4 1.8 2.3 1.8 2.3 2.8 2.2 2.6 3.3 1.5 2.2 2.7 2.1 2.7 3.2 2.2 3.0 3.7 1.8 2.5 2.9 2.2 2.8 3.6 2.4 3.1 3.9 1.8 2.7 3.1 2.3 2.9 3.8 2.6 3.2 4.2 2.1 3.0 3.5 2.9 3.7 4.1 2.9 3.9 4.3 4.5 4.2 3.8 3.5 3.1

454 569 704 563 703 842 671 785 968 475 691 812 663 820 945 695 912 1076 559 761 876 685 846 1061 742 919 1119 578 826 937 706 870 1108 788 962 1201 656 889 1026 862 1070 1191 878 1122 1224

7.8 9.8 12.1 9.7 12.1 14.5 11.5 13.5 16.7 8.2 11.9 14.0 11.4 14.1 16.3 12.0 15.7 18.5 9.6 13.1 15.1 11.8 14.6 18.2 12.8 15.8 19.3 9.9 14.2 16.1 12.1 15.0 19.1 13.5 16.5 20.7 11.3 15.3 17.6 14.8 18.4 20.5 15.1 19.3 21.1 0.93 0.86 0.79 0.72 0.64

244 311 395 308 394 483 374 446 569 256 387 468 375 466 533 391 513 647 306 431 506 383 486 634 419 535 676 317 473 547 396 502 668 448 564 736 365 515 609 497 640 729 507 678 754

4.2 5.4 6.8 5.3 6.8 8.3 6.4 7.7 9.8 4.4 6.6 8.0 6.4 8.0 9.5 6.7 9.0 11.1 5.3 7.4 8.7 6.6 8.4 10.9 7.2 9.2 11.6 5.5 8.1 9.4 6.8 8.6 11.5 7.7 9.7 12.7 6.3 8.9 10.5 8.5 11.0 12.5 8.7 11.7 13.0 0.33 0.31 0.29 0.26 0.24

900

1050

1200

1350

1500

Technical Data
Convective heating capacity, related to water flow only (without primary air)
tRWV in K
10 15 20 25 30 35 40 45 50

LN in mm 900
84 114 145 177 210 242 276 309 343

1050
98 133 170 207 245 283 322 361 400

1200 . QHK in W
112 152 194 236 280 323 368 412 458

1350
126 172 218 266 314 364 414 464 515

1500
140 191 242 295 349 404 459 515 572

17 50 l/h 60 70 80 90 100 110 l/h 30 16 15 14 13 12 160 11 10 9 200 8 7 250 6 5 4 3 Water volume flow rate WK / WH in l/h 2 1 0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 Water-side thermal capacity WK / WH in W

Diff. between flow and return water temp. tW in K

20 18 Water pressure drop pW in kPa 16 14 12 10 8 6 4 2 0 40 60


4-pipe system Heating 2-pipe system Heating 2- and 4-pipe system Cooling

1500 1500 1200 1200 900 900

1500 1200 900 LN

80 100 120 140 160 180 200 220 240 260 Water volume flow rate WK / WH in l/h

Correction factors (FW) water volume flow rate Cooling WK in l/h 100 110 0.98 1.00 Heating WH in l/h 80 90 1.09 1.12

50 0.86

60 0.89

70 0.92

80 0.94

90 0.96

120 1.02

140 1.04

160 1.06

200 1.08

250 1.09

30 0.92

40 0.97

50 1.00

60 1.03

70 1.07

100 1.14

110 1.16

120 1.19

140 1.21

160 1.23

See also our selection programme for air-water systems on the internet at www.trox.de

Order Details

Specification Text
Modular floor induction units for air-water air conditioning systems, in 5 nominal sizes, for ventilating rooms requiring high levels of comfort, for load dissipation (heating/cooling) at the faade using water as the medium, for installation in false floors and cavity flooring. Comprising: load bearing casing with installation space for the incorporation of control valves and actuators, side fixed brackets with height-adjustable feet and slotted holes for securing to the structure, flange-mounted, interchangeable primary air duct with integral, non-flammable induction nozzles and primary air duct spigot with lip seal, three nozzle variants with varying free cross-sections, circular, deburred stamped nozzles with a projection height of 2 4 mm depending on the nozzle variant, optimised for high induction performance at minimum sound power levels and pressure losses, for adapting to room layout changes nozzles can be individually closed with plugs, easy-to-clean coils complying with VDI 6022, optional as a 2-pipe version for heating or cooling, and as a 4-pipe version for heating and cooling, copper 12 x 1 mm water connections with the option of right or left hand, optional with bleed valves and/or pipe connections with 1/2 external thread, a grille ledge for a linear grille or roll down grille. Materials Casing and primary air duct of galvanised sheet steel, coils with copper pipes and pressed aluminium fins, untreated surface, rubber lip seal. Casing option powder-coated to RAL 9005 (black) and/or coils black, RAL 9005.

Order Code
BID - 2 - M - R - E /

These codes do not need to be completed for standard products 1197 x 900 x 98 / 0 Not used / K00 / P1 / RAL 9005 State colour 0 Coil untreated G3 Coil RAL 9005, black / G3

Water coil Two-pipe Four-pipe

-2 -4

I E E O E P I E E E O E E E P I E E O E P

1100...1249 x 900 1250 ... 1399 x 1050 1400 ... 1549 x 1200 1550 ... 1699 x 1350 1700 ... 1849 x 1500 L1 x LN1) (mm)
1) Total length x nominal length

Nozzle options

M G U

98 123 D2) (mm)

Design changes reserved All rights reserved TROX GmbH (5/2008)

Casing arrangement Right hand R Left hand L

2) Diameter of connecting spigot on request 98 or 123

E Individual unit B Linear assembly

Standard Connections Cu-pipe 12 x 1 mm E00 Air vent valve for heating and/or cooling circuit A00 Connections R1/2 external thread K00 Combination of E and A

Order example
Make: TROX Type: BID - 2 - M - R - E / 1197 x 900 x 98 / K00 / P1 / G3

Please order separately linear grille or roll down grille: Aluminium roll down grille (ARR20) see product information leaflet PI/T1.1/2/EN/... Aluminium linear grille (AFN-0-A) see product information leaflet PI/T1.1/3/EN/...

I E E E E E E O E E E E E E E E E E P I E E E E E E O E E E E E E E E E E E P

Standard galvanised finish

P1 Casing powder-coated RAL 9005, black

I E E E O E E E P