Ceiling Duct Type Air Conditioner

SERVICE MANUAL
MODELS: LB-D1861HL/CL/ZL LB-D2461HL/CL/ZL LB-F3061HL/CL LB-F3661HL/CL/ZL LB-F3681HL/CL/ZL LB-F4261HL LB-E4881HL/CL/ZL LB-E6081HL/CL/ZL LB-E4885HL/CL LB-E6085HL/CL

Contents
Functions .................................................................................................................................3 Product Specifications (Cooling & Heating) ..........................................................................5 Dimensions ..............................................................................................................................9 Refrigeration Cycle Diagram ................................................................................................11 Wiring Diagram ......................................................................................................................13 Operation Details ...................................................................................................................20 Installation of Indoor, Outdoor Unit .....................................................................................23 Cycle ........................................................................................................................................37 Cycle Troubleshooting Guide ...............................................................................................40 Electronic Parts Troubleshooting Guide .............................................................................41 Electronic Control Device .....................................................................................................44 Exploded View and Replacement Parts List .......................................................................45

Functions
Indoor Unit
Operation ON/OFF by Remote controller Sensing the Room Temperature Room temperature control Starting Current Control Time Delay Safety Control Indoor Fan Speed Control Soft Dry Operation Mode Auto Restart Room temperature sensor. (Thermistor)

Maintains the room temperature in accordance with the Setting Temp. Indoor fan is delayed for 5 seconds at the starting. Restarting is inhibited for approx. 3 minutes. High, Med, Low Intermittent operation of fan at low speed.

Although the air-conditioner is turned off by a power failure, it is restarted automatically previous operation mode after power supply. The setting temperature and desired operation mode are autoAuto Operation(Auto Change Over) matically set by fuzzy rule. Deice (defrost) control (Heating) Hot-start Control (Heating) High head height Drain pump(Optional) Central Control(Optional) Group Control(Optional Wiring) Both the indoor and outdoor fan stops during defrosting. Hot start after defrost ends. The indoor fan stops until the evaporator piping temperature will be reached at 28C. A standard drain-head height of up to 700mm is possible. It is operating individually or totally by central control function. Each controller can control 16 units and 8 controllers can connect. It operates maximum 16 units by only one wired remote controller and each unit starts random to prevent overcurrent.

Remote Controller
Operation ON/OFF

Operation Mode Selection Cooling Operation Mode ( Heating Operation Mode ( ) ) Soft Dry Operation Mode ( Auto Operation Mode ( ) )

(Cooling (Heating model only) model only)

Fan Speed Selection

LO (Low)
Room Temperature Display : High:39C LOW:11C Temperature Setting Cooling Setting the Timer
Timer Cancel

MED (Med)

HI (High)

AUTO

Down to 18C Up to 30C

Heating

Down to 16C Up to 30C

Weekly Program
Program Week Holiday

SET/CLR Hour Min

Fan Operation Mode

: Fan Operates without cooling & heating

Electric Heater

Product Specifications (Cooling & Heating)


Model
Power Source Cooling Capacity , V, Hz" kcal/h(BTU/h) W Input Heating Capacity W kcal/h(BTU/h) W Input Electric Heater Rated Load Amp. Capacity Cooling Heating Air Volumn Cooling(H/M/L) Heating(H/M/L) Refrigerant(R-22) Drain Hose Main Cable Connecting Cable Remote Control Type Refigerant Control Type Fuction Soft Dry Timer Self Diagnosis Deice Operation Hot Start Zone Control(Optional) Central Control(Optional) Group Control(Optional wiring) Weekly Programning Thermistor Drain Pump(Optional) Auto changeover(Auto Operation: CL) Stand-by Consumption 0 Connecting Pipe Liquid Gas Dimension Indoor Outdoor Net Weight Indoor Outdoor Inch (mm) mm (WxDxH) Kg In. Dia g mm No. X mm2 W Kw A A CMM(m3/min)

LB-D1861HL LB-D1861ZL LB-D1861CL LB-D2461HL LB-D2461ZL LB-D2461CL


1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 4,536(18,000) 4,536(18,000) 4,536(18,000) 6,048(24,000) 6,048(24,000) 6,048(24,000) 5,274 1,950 5,274 1,950 5,274 2,050 9.5 7,033 2,600 7,033 2,600 7,033 2,800 13 -

4,536(18,000) 4,536(18,000) 5,274 1,900 9.4 9 5,274 1,900 1.5 9.4 9

6,048(24,000) 6,048(24,000) 7,033 2,500 12 11 7,033 2,500 3 12 11

16.5/14.5/12.5 16.5/14.5/12.5 16.5/14.5/12.5 16.5/14.5/12.5 16.5/14.5/12.5 16.5/14.5/12.5 16.5/14.5/12.5 16.5/14.5/12.5 1,900 22.6 3*2.5 6*0.75 L.C.D Wired 1,900 22.6 3*2.5 6*0.75 L.C.D Wired 1,400 22.6 3*2.5 4*0.75 L.C.D Wired 16.5/14.5/12.5 16.5/14.5/12.5 2,270 22.6 3*2.5 6*0.75 L.C.D Wired 2,270 22.6 3*2.5 6*0.75 L.C.D Wired 1,500 22.6 3*2.5 4*0.75 L.C.D Wired

Capillary type Capillary type Capillary type Capillary type Capillary type Capillary type Yes Yes Yes Yes Yes Yes

24 Hours On/Off 24 Hours On/Off 24 Hours On/Off 24 Hours On/Off 24 Hours On/Off 24 Hours On/Off Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 1/4(6.35) 5/8(15.88) 880*575*281 870*320*655 42 57 Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 1/4(6.35) 5/8(15.88) 880*575*281 870*320*655 42 57 Yes Optional Optional Yes Yes Yes Optional Yes Yes 1/4(6.35) 5/8(15.88) Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 1/4(6.35) 5/8(15.88) Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 1/4(6.35) 5/8(15.88) 880*575*281 870*320*655 42 60 Yes Optional Optional Yes Yes Yes Optional Yes Yes 1/4(6.35) 5/8(15.88) 880*575*281 870*320*655 42 57

880*575*281 880*575*281 870*320*655 870*320*655 42 55 42 60

Model
Power Source Cooling Capacity , V, Hz" kcal/h(BTU/h) W Input Heating Capacity W kcal/h(BTU/h) W Input Electric Heater Rated Load Amp. Capacity Cooling Heating Air Volumn Cooling(H/M/L) Heating(H/M/L) Refrigerant(R-22) Drain Hose Main Cable Connecting Cable Remote Control Type Refigerant Control Type Fuction Soft Dry Timer Self Diagnosis Deice Operation Hot Start Zone Control(Optional) Central Control(Optional) Group Control(Optional wiring) Weekly Programning Thermistor Drain Pump(Optional) Auto changeover(Auto Operation: CL) Stand-by Consumption 0 Connecting Pipe Liquid Gas Dimension Indoor Outdoor Net Weight Indoor Outdoor Inch (mm) mm (WxDxH) Kg In. Dia g mm No. X mm2 W Kw A A CMM(m3/min)

LB-F3061HL LB-F3061CL LB-F3661HL LB-F3661ZL LB-F3661CL LB-F3681HL LB-F3681ZL


1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 3, 380-415, 50 3, 380-415, 50 7,560(30,000) 7,560(30,000) 9,072(36,000) 9,072(36,000) 9,072(36,000) 9,072(36,000) 9,072(36,000) 8,790 3,000 7,560(30,000) 8,790 2,500 14 12 28/27/25 28/27/25 2,600 22.6 3*3.5 5*1.25 L.C.D Wired 8,790 3,000 14 28/27/25 2,600 22.6 3*3.5 5*1.25 L.C.D Wired 10,548 4,400 10,548 4,400 10,548 4,400 20 28/27/25 2,850 22.6 3*5.5 4*1.25 L.C.D Wired 10,548 4,000 10,548 4,000

9,072(36,000) 9,072(36,000) 10,548 3,600 20 20 28/27/25 28/27/25 2,850 22.6 3*5.5 5*1.25 L.C.D Wired 10,548 3,600 3 20 20 28/27/25 28/27/25 2,850 22.6 3*5.5 5*1.25 L.C.D Wired

9,072(36,000) 9,072(36,000) 10,548 3,400 8 7 28/27/25 28/27/25 2,800 22.6 4*2.5 5*1.25 L.C.D Wired 10,548 3,400 3 8 7 28/27/25 28/27/25 2,800 22.6 4*2.5 5*1.25 L.C.D Wired

Capillary type Capillary type Capillary type Capillary type Capillary type Capillary type Capillary type Yes Yes Yes Yes Yes Yes Yes

24 Hours On/Off 24 Hours On/Off 24 Hours On/Off 24 Hours On/Off 24 Hours On/Off 24 Hours On/Off 24 Hours On/Off Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 5/8(15.88) Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 5/8(15.88) Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 5/8(15.88) Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 5/8(15.88) Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 5/8(15.88) Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 5/8(15.88) Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 5/8(15.88)

1180*600*298 1180*600*298 1180*600*298 1180*600*298 1180*600*298 1180*600*298 1180*600*298 870*320*800 46 55 870*320*800 46 55 790*320*965 46 78 790*320*965 46 78 790*320*965 46 78 790*320*965 46 78 790*320*965 46 78

Model
Power Source Cooling Capacity , V, Hz" kcal/h(BTU/h) W Input Heating Capacity W kcal/h(BTU/h) W Input Electhic Heater Rated Load Amp. Capacity Cooling Heating Air Volumn Cooling(H/M/L) Heating(H/M/L) Refrigerant(R-22) Drain Hose Main Cable Connecting Cable Remote Control Type Refigerant Control Type Fuction Soft Dry Timer Self Diagnosis Deice Operation Hot Start Zone Control(Optional) Central Control(Optional) Group Control(Optional wiring) Weekly Programning Thermistor Drain Pump(Optional) Auto changeover(Auto Operation: CL) Stand-by Consumption 0 Connecting Pipe Liquid Gas Dimension Indoor Outdoor Net Weight Indoor Outdoor Inch (mm) mm (WxDxH) Kg In. Dia g mm No. X mm2 W Kw A A CMM(m3/min)

LB-F3681CL

LB-4261HL

LB-E4881HL LB-E4885HL
12,096(48,000) 14,066 5,500

LB-E4881ZL

LB-E4881CL LB-E4885CL
3, 380-415, 50 12,096(48,000) 14,066 6,000 9.5 40/35/30 3,030 22.6 4*3.5 4*1.25 L.C.D Wired Capillary type Yes 24 Hours On/Off Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 3/4(19.05) 1,230*680*370 900*370*1,220 70 90

3, 380-415, 50 1, 220-240, 50 9,072(36,000) 10,548 4,400 8 28/27/25 2,800 22.6 4*2.5 4*1.25 LCD wired 10,589(42,000) 12,306 4,800

3, 380-415, 50 3, 380-415, 50 12,096(48,000) 14,066 5,500

10,584(42,000) 12,096(48,000) 12,096(48,000) 12,360 4,600 26 26 28/27/25 27/25/23 4,900 22.6 3*8.0 5*1.25 LCD wired 14,066 4,500 9 8 40/35/30 40/35/30 4,250 22.6 4*3.5 5*1.25 L.C.D Wired Capillary type Yes 14,066 4,500 4.5 9 8 40/35/30 40/35/30 4,250 22.6 4*3.5 5*1.25 L.C.D Wired Capillary type Yes

Capillary Type Capillary Type Yes Yes

24 Hours On/Off 24 Hours On/Off 24 Hours On/Off 24 Hours On/Off Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 5/8(15.88) 1,180*600*298 790*320*965 46 78 Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 3/4(19.05) 1,180*600*298 900*370*1,220 50 95 Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 3/4(19.05) 1,230*680*370 900*370*1,220 70 95 Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 3/8(9.52) 3/4(19.05) 1,230*680*370 900*370*1,220 70 95

Model
Power Source Cooling Capacity , V, Hz" kcal/h(BTU/h) W Input Heating Capacity W kcal/h(BTU/h) W Input Electhic Heater Rated Load Amp. Capacity Cooling Heating Air Volumn Cooling(H/M/L) Heating(H/M/L) Refrigerant(R-22) Drain Hose Main Cable Connecting Cable Remote Control Type Refigerant Control Type Fuction Soft Dry Timer Self Diagnosis Deice Operation Hot Start Zone Control(Optional) Central Control(Optional) Group Control(Optional wiring) Weekly Programning Thermistor Drain Pump(Optional) Auto changeover(Auto Operation: CL) Stand-by Consumption 0 Connecting Pipe Liquid Gas Dimension Indoor Outdoor Net Weight Indoor Outdoor Inch (mm) mm (WxDxH) Kg In. Dia g mm No. X mm2 W Kw A A CMM(m3/min)

LB-E6081HL LB-E6085HL
3, 380-415, 50 14,360(57,000) 16,700 6,150 15,120(60,000) 17,580 4,900 10.5 8.5 45.5/39/35 45.5/39/35 6,550 22.6 4*3.5 5*1.25 L.C.D Wired Capillary type Yes 24 Hours On/Off Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 1/2(12.7) 3/4(19.05) 1,230*680*370 900*370*1,220 70 95

LB-E6081ZL
3, 380-415, 50 14,360(57,000) 16,700 6,150 15,120(60,000) 17,580 4,900 4.5 10.5 8.5 45.5/39/35 45.5/39/35 6,550 22.6 4*3.5 5*1.25 L.C.D Wired Capillary type Yes 24 Hours On/Off Yes Yes Yes Optional Optional Yes Yes Yes Optional Yes Yes 1/2(12.7) 3/4(19.05) 1,230*680*370 900*370*1,220 70 95

LB-E6081CL LB-E6085CL
3, 380-415, 50 14,868(59,000) 17,291 6,000 10 45.5/39/35 6,250 22.6 4*3.5 4*1.25 L.C.D Wired Capillary type Yes 24 Hours On/Off Yes Optional Optional Yes Yes Yes Optional Yes Yes 1/2(12.7) 3/4(19.05) 1,230*680*370 900*370*1,220 70 90

Dimensions
(1) Indoor Unit

MODEL DIM W(mm)

18K

24K

30K

36K

42K

48K

60K

880

880

1180

1180

1180

1230

1230

H(mm)

281

281

298

298

298

370

370

D(mm)

575

575

600

600

600

680

680

(2) Outdoor Unit


D W

D W

H
H

(18K/24K/30K)

(36K/42K/48K/60K)

MODEL DIM W(mm)

18K

24K

30K

36K

42K

48K

60K

870

870

870

790

900

900

900

H(mm)

655

655

800

965

1,220

1,220

1,220

D(mm)

320

320

320

320

370

370

370

10

Refrigeration Cycle Diagram


HEAT PUMP (18K/24K/30K/36K/42K/48K/60K)
INDOOR UNIT
CAPILLARY TUBE LIQUID SIDE

OUTDOOR UNIT

HEAT EXCHANGER

HEAT EXCHANGER

GAS SIDE REVERSING VALVE COOLING HEATING

COMPRESSOR

Pipe size(Diameter: ) MODEL Gas 18K 24K 30K 36K 42K 48K 60K 5/8" 5/8" 5/8" 5/8" 3/4" 3/4" 3/4" Liquid 1/4" 1/4" 3/8" 3/8" 3/8" 3/8" 1/2"

Piping length(m) Rated 7.5 7.5 7.5 7.5 7.5 7.5 7.5 Max. 50 50 50 50 50 50 50

Elevation(m) Rated 5 5 5 5 5 5 5 Max. 30 30 30 30 30 30 30

*Additional refrigerant (g/m) 25 30 50 40 50 50 60

Rated performance for refrigerant line length of: 7.5m If 18K Model is installed at a distance of 15m, 188g of refrigerant should be added (15-7.5)x25g=188g

11

COOLING ONLY (18K/24K/30K/36K/42K/48K/60K)


INDOOR UNIT
CAPILLARY TUBE LIQUID SIDE

OUTDOOR UNIT

HEAT EXCHANGER (CONDENSER)

HEAT EXCHANGER (CONDENSER)

GAS SIDE

COMPRESSOR

Pipe size(Diameter: ) MODEL Gas 18/24K 30K 36K 48K 60K 5/8" 5/8" 5/8" 3/4" 3/4" Liquid 1/4" 3/8" 3/8" 3/8" 1/2"

Piping length(m) Rated 7.5 7.5 7.5 7.5 7.5 Max. 50 50 50 50 50

Elevation(m) Rated 5 5 5 5 5 Max. 30 30 30 30 30

*Additional refrigerant (g/m) 25 50 40 50 60

Rated performance for refrigerant line length of: .7.5m If 18K Model is installed at a distance of 15m, 188g of refrigerant should be added (15-7.5)x25g=188g

12

Wiring Diagram
HEAT PUMP
Model : LB-D1861HL/LB-D2461HL/ LB-D2461ZL/LB-D1861ZL
OUTDOOR WIRING DIAGRAM
BL
R

HEAT PUMP
Model : LB-D1861HL/LB-D2461HL

INDOOR WIRING DIAGRAM


TEMP. THERMISTOR

CAPACITOR
H C F

YL OR BK

BR

COMP S
C

RD BR

BL

BL

BR BL GN/YL

FUSE 250V10A

POWER RELAY

4 2

8 6

1 0
RD

TO OUTDOOR UNIT

REVERSING VALVE

OR RD BL BK

BL

FAN MOTOR
3(L) 4(N)

YL

INDOOR MOTOR

DRAIN PUMP

GN/YL

OUT FAN

COMP

BR BR FUSE 5A

BL BL FUSE 5A

TB2 BR BL BK YL GN/YL GN/YL

RD BK

4 WAY

PIPE THERMISTOR

BL

5 6 7

FLOAT S/W

YL

REMOTE CONTROL

1(L)

2(N)
POWER INPUT

3(L)

4(N)

8
TERMINAL BLOCK

TERMINAL BLOCK OPTION

TO INDOOR UNIT

ZONE CONTROL

Model : LB-D2461ZL/LB-D1861ZL

Model : LB-D2461HL(Only Australia)

52H TF2

INDOOR WIRING DIAGRAM


T1 T2 T3 b

OUTDOOR WIRING DIAGRAM


S/CAPACITOR YL
R

1,220-240V~,50Hz POWER SUPPLY

L1 L2 L3 a

EH ROOM. THERMISTOR
TF1

YL CAPACITOR YL OR BK
H C F
WH
3 3 4 4 RY- RYCOMP S/CAPA CN-POWER

BR YL

26S1

INDOOR MOTOR

DRAIN PUMP
BL BL

OR RD BL BK

1 2 3

COMP S
C

RD BR BL

FAN MOTOR

GN/YL

BR BL GN/YL

FUSE 250V10A

BL

3(L) 4(N)

TO OUTDOOR UNIT

POWER RELAY
OUT FAN COMP HEATER 4 WAY

PIPE THERMISTOR

4 2

8 6
BL

1 0

REVERSING VALVE RD

BR BR FUSE 5A

RD

BL BL FUSE 5A

BR BL BL

BK

BK YL

GN/YL

REMOTE CONTROL

TERMINAL BLOCK OPTION T/B

ZONE CONTROL

1(L) 2(N)

3(L) 4(N)

GN/YL

BK

5 6 7

FLOAT S/W

TB2

8
TERMINAL BLOCK

3854A20031Z

POWER INPUT

TO INDOOR UNIT

3854A20119A

13

COOLING ONLY
Model : LB-D1861CL/LB-D2461CL
OUTDOOR WIRING DIAGRAM
BL
R

INDOOR WIRING DIAGRAM


FAN MOTOR
BR YL

COMP S
C

RD BR

OR BK

INDOOR MOTOR

DRAIN PUMP
BL BL

BL

POWER RELAY

4 2

8 6

1 0
TO OUTDOOR UNIT

BR BL GN/YL

FUSE 250V10A

TEMP. THERMISTOR PIPE THERMISTOR FLOAT S/W

CAPACITOR

YL
GN/YL

BR BR FUSE 5A

BL BL FUSE 5A

TB2 BR BL RD YL GN/YL GN/YL

RD

COMP

BL

OR RD BL BK

3(L ) 4 (N ) 5 6 7

REMOTE CONTROL

1(L) 2(N)
POWER INPUT

3(L) 4(N)

8
TERMINAL BLOCK

TERMINAL BLOCK OPTION

ZONE CONTROL

TO INDOOR UNIT

HEAT PUMP
Model : LB-F3061HL
OUTDOOR WIRING DIAGRAM
BL CAPACITOR
R

INDOOR WIRING DIAGRAM


OR
BR YL

YL

COMP S
C

RD BR BL

FAN MOTOR

BL

DEICER PCB HIGH PRESS SWITCH BK

BR BR FUSE 5A BL FUSE 5A SUMP HEATER

TO OUTDOOR UNIT

POWER RELAY

4 2

8 6

1 0

REVERSING VALVE BR

BR BL GN/YL

FUSE 250V10A

BL

BL

OR RD BL BK

BL

OR BK
3(L) 4(N)

INDOOR MOTOR

DRAIN PUMP

TEMP. THERMISTOR PIPE THERMISTOR FLOAT S/W

CAPACITOR

GN/YL

COMP

L3 L2 L1

BK WH BK BK BK TERMINAL BLOCK

BR

BL

RD BK

YL 1 TERMINAL BLOCK

BK

BK

4 WAY

5 6 7

REMOTE CONTROL

TERMINAL BLOCK OPTION

POWER INPUT

TO INDOOR UNIT

ZONE CONTROL

3854AP2708T

3854A30086Q

COOLING ONLY
Model : LB-F3061CL
OUTDOOR WIRING DIAGRAM
BL CAPACITOR
R

INDOOR WIRING DIAGRAM


YL OR
GN/YL YL

BL

BR

BL

BK
8 6 1 0

BK

BR BL

FUSE 250V10A

4 2

TO OUTDOOR UNIT

POWER RELAY

OR RD BL BK

BL

COMP S

RD

FAN OR MOTOR BK

INDOOR MOTOR

DRAIN PUMP

ROOM SENSOR PIPE SENSOR FLOAT S/W

CAPACITOR

BR

GN/YL

3(L) 4(N)

BK

BL

BL

BR FUSE 5A

BL FUSE 5A

RD

BR

BR

BL

GN/YL
7

COMP

5 6

REMOTE CONTROL

TERMINAL BLOCK

TERMINAL BLOCK OPTION

POWER INPUT

TO INDOOR UNIT

3854A20025W

ZONE CONTROL

3854A20166Q

14

HEAT PUMP
Model : LB-F3661HL
OUTDOOR WIRING DIAGRAM
BK BK WH WH GN/YL WH F1 BK BK WH
T/B1

INDOOR WIRING DIAGRAM


D.P TNS
C TH NO NC

BR YL

INDOOR MOTOR

DRAIN PUMP
BL BL

GN/YL

CH1 WH
L1 L2 A2

2 4 6 8

52C
T1 T2 A1

BK

BL

TO OUTDOOR UNIT

ROOM. THERMISTOR

TM 1 L

3 N

63H2

BK WH

3 5

GN/YL

YL

FUSE 250V10A

OR RD BL BK

52F1

BK BR Co OR YL OR

BK BL Co YL PTCR BK
R S

BK WH

220-240V 1, 50Hz POWER SUPPLY

BK

RD BL

4 WAY

WH

COMP

BK

PIPE THERMISTOR

To the indoor unit

Cr
RD WH C

3(L) 4(N)

FLOAT S/W

WH

FMo1 49FMo

FMo2 49FMo

CM

BK
20SV

BK BK GN/YL

BK

1 2 3 4 5 6

BK WH BL RD GN/YL

BR

REMOTE CONTROL

TERMINAL BLOCK

OPTIONAL EXTRA

ZONE CONTROL

Tmo

3854A20025G

3854A20031X

Model : LB-F3661HL(Only Australia)


OUTDOOR WIRING DIAGRAM
BK BK WH WH GN/YL WH TIMER 3 TM N 63H2 F1 BK BK WH CH1 52F1 BK
L1

Model : LB-F3661ZL
INDOOR WIRING DIAGRAM

D.P TNS

C TH
NO NC

52H TF2

WH
L2 A2

2 4 6 8

1 L

BK 52C RD

BK WH

3 5 7

YL

1,220-240V~,50Hz POWER SUPPLY

L1 L2 L3 a

T1 T2 T3 b

EH
TEMP. THERMISTOR
TF1
BR YL OR

FACTORY WIRING FIELD WIRING OPTIONAL WIRING

T1

T2

A1

BK 240V 1, 50Hz POWER SUPPLY WH BK BR Co OR YL OR BK BK Co YL RD WH YL S R FMo1 48FMo FMo2 48FMo CM


20SV

BK

BL
26S1

INDOOR MOTOR
RD BL BK

DRAIN PUMP
BL BL

GN/YL

1 2 3
BK
BR BL COMP FUSE 250V10A

WH

BK

1(L) 2(N)

LOW

MED

BK BK

BK RD Cs Cr

BK WH

TO OUTDOOR UNIT

HI
HEATER

To the Indoor unit

WH BL BK BK BK BK GN/YL

1 2 3 4 5 6 Tmo

RD RD

4 WAY

PIPE THERMISTOR

3 4 5

FLOAT S/W
BL

BK YL BK REACTOR BK
A1 L3 L2

REMOTE CONTROL

TERMINAL BLOCK

GN/YL

GN/YL

ZONE CONTROL

3854A20166J

52S
A2 T3 T2

BK

BK WH

15

COOLING ONLY
Model : LB-F3661CL
OUTDOOR WIRING DIAGRAM
WH BK BK WH WH GN/YL
T/B

INDOOR WIRING DIAGRAM


BR YL

F1

BK

INDOOR MOTOR

DRAIN PUMP
BL BL

CH1
WH 3 N
L1 L2 A2

TM 1 L

BR BL

FUSE 250V10A

52C
T1 T2 A1

TO OUTDOOR UNIT

COMP

TEMP. THERMISTOR PIPE THERMISTOR FLOAT S/W

GN/YL

220-240V 1, 50Hz POWER SUPPLY

WH BK BK BR Co Co YL
PTCR BK
R S

BK BK BL
Cr
RD C WH

RD

BK

To the indoor unit

OR

YL OR

WH

CM
FMo1 FMo2

1 2 3 4 5 6 GN/YL

BK WH BL

OR RD BL BK

GN/YL

TMo

TERMINAL BLOCK OPTION

1 (L ) 2 ( N ) 3 4 5

GN/YL

REMOTE CONTROL

ZONE CONTROL

3854A20025J

3854A20031Y

HEAT PUMP
Model : LB-F3681HL
OUTDOOR WIRING DIAGRAM
BK BK WH WH RD BK WH TM 1 2 3 4 R S T N F1 BK BK WH
T/B1

INDOOR WIRING DIAGRAM


C TH

D.P TNS

BR
NO NC

YL

INDOOR MOTOR

DRAIN PUMP
BL BL

GN/YL

52F1
1 2 4 6

52C
1 3 5 31

WH
B

63H2

5 7

32

TO OUTDOOR UNIT

CH1 BK BK

ROOM. THERMISTOR

BK WH

YL

GN/YL

FUSE 250V10A

OR RD BL BK

COMP

BL

BK

BK BR Co OR YL OR

BK BL Co YL T1 T2 T3 WH

BK WH 1 2 3 4 5 6 GN/YL BK WH BL RD GN/YL

380-415V 3, 50Hz POWER SUPPLY

WH BK

RD BL

4 WAY

PIPE THERMISTOR

3(L) 4(N)

FLOAT S/W

To the indoor unit

BK WH RD

BR

REMOTE CONTROL

TERMINAL BLOCK

CM
FMo1 FMo2

BK
20SV

BK BK

OPTIONAL EXTRA

ZONE CONTROL

BK

TMo

3854A90021F

3854A20031X

Model : LB-F3681ZL
INDOOR WIRING DIAGRAM
52H TF2

3,380V~415V,50Hz POWER SUPPLY

L1 L2 L3 a

T1 T2 T3 b

EH
BR YL OR

26S1

INDOOR MOTOR
RD BK BL

DRAIN PUMP
BL BL

1 2 3
BR BL COMP FUSE 250V10A

LOW

MED

TO OUTDOOR UNIT

HI

HEATER

TEMP. THERMISTOR PIPE THERMISTOR FLOAT S/W

TF1
GN/YL

RD RD BL GN/YL

4 WAY

TERMINAL BLOCK OPTION

1(L) 2(N) 3 4 5

REMOTE CONTROL

ZONE CONTROL

3854A20031M

16

COOLING ONLY
Model : LB-F3681CL
OUTDOOR WIRING DIAGRAM
WH BK BK WH RD WH WH TM 1 2 3 4 R S T N
T/B

INDOOR WIRING DIAGRAM


TEMP. THERMISTOR PIPE THERMISTOR FLOAT S/W

F1

BK
BR YL

INDOOR MOTOR

DRAIN PUMP
BL BL

GN/YL

52C
1 3 5

WH
31

BR BL

FUSE 250V10A

TO OUTDOOR UNIT

32

3, 380V, 50Hz POWER SUPPLY

WH

BK

BK

RD

BK BR Co OR YL OR

BK BL Co YL T1 T2 T3 WH

BK

CM
FMo1 FMo2

1 2 3 4 5 6 GN/YL

BK WH BL

To the indoor unit

BK WH RD

COMP

OR RD BL BK

TERMINAL BLOCK OPTION

1(L) 2(N) 3 4 5

GN/YL

REMOTE CONTROL

GN/YL

ZONE CONTROL

TMo

3854A90010Y

3854A20031Y

HEAT PUMP
Model : LB-F4261HL
OUTDOOR WIRING DIAGRAM
BK BK BR OR WH WH BK WH WH TM L N RD 220-240V 1,50Hz POWER SUPPLY
2 4 6 B 32
T/B2

INDOOR WIRING DIAGRAM


D.P TNS NO NC
C TH

BR
52F1
1 3 2 4 6 8

YL

INDOOR MOTOR

DRAIN PUMP
BL BL

GN/YL

52C

31 A

T/B1

5 7

GN/YL

FUSE 250V10A

OR RD BL BK

TO OUTDOOR UNIT

RD BR Co Co BR WH BK

WH BK

WH

63H2

ROOM. THERMISTOR

COMP

BK

YL

F1

BK

YL YL BK WH BK

BL

BK

RD BL

4 WAY

PIPE THERMISTOR

YL OR

BK YL OR

BK

RD

CH

BK BL RD
20SV

FMo1
49FMo

FMo2
49FMo

CM
GN/YL

RD GN/YL

1 2 3 4 5 6

BK WH BL RD GN/YL

To the indoor unit

WH PTCR BK

WH

3(L) 4(N)

Cr

FLOAT S/W

BR

REMOTE CONTROL

TERMINAL BLOCK

Tmo

OPTIONAL EXTRA

ZONE CONTROL

3854AP2778F

3854A20031X

17

HEAT PUMP
Model : LB-E4881HL/LB-E6081HL
OUTDOOR WIRING DIAGRAM
Fuse
BK BK BK WH RD WH OR
(250V 5A)

INDOOR WIRING DIAGRAM


C TH
NO NC

HIGH PRESSURE S/W


BK WH

Deice PCB
TNS

BR YL

Fuse
(250V 5A)

INDOOR MOTOR

DRAIN PUMP
BL BL

WH BK

R S T N BLOCK

TERMINAL

1 3 5 7

31

OR
T/B1

4 6 8

BR BL

FUSE 250V10A

POWER RELAY POWER SUPPLY


2 4 6

B
32
T/B2

WH

TO OUTDOOR UNIT

COMP

OR RD BL BK

POWER RELAY

4 WAY

TEMP. THERMISTOR PIPE THERMISTOR FLOAT S/W

GN/YL

1(L) 2(N) 3

BK WH BK BK RD WH YL BK

RD BK

CAPACITOR

CAPACITOR

5
GN/YL

YL BK OR

YL BK OR

WH BK

WH

FAN MOTOR

FAN MOTOR

T2 T3

T1

BL
REVERSING VALVE

1 2 3 4 5 6
GN/YL

BR BL BR BL GN/YL

To the indoor unit

BK

RD

REMOTE CONTROL

TERMINAL BLOCK OPTION

ZONE CONTROL

COMP.

BL

TERMINAL BLOCK

Model : LB-4881ZL/LB-E6081ZL
OUTDOOR WIRING DIAGRAM
Fuse
BK BK BK WH RD WH OR
(250V 5A)

INDOOR WIRING DIAGRAM


C TH
NO NC

HIGH PRESSURE S/W


BK WH

Deice PCB
TNS

52H TF2

3,380V~415V,50Hz POWER SUPPLY

L1 L2 L3

T1 T2 T3 b

EH
BR YL OR

(250V 5A)

WH BK

POWER RELAY
1 3 5 7 2 4 6

BL

RD

POWER RELAY POWER SUPPLY


2 4 6

T/B1

B
32
T/B2

WH

LOW

MED

BR BL

FUSE 250V10A HI

TO OUTDOOR UNIT

HEATER

WH BK BK RD

WH

YL BK

RD RD

CAPACITOR

CAPACITOR

4 WAY

BK

COMP

BK

BL

OR

BL

TERMINAL R S T N BLOCK

26S1

INDOOR MOTOR

DRAIN PUMP

31

1 2 3

TEMP. THERMISTOR PIPE THERMISTOR FLOAT S/W

Fuse

TF1
GN/YL

1(L) 2(N) 3 4 5

BL GN/YL

YL BK OR

YL BK OR

WH BK

WH

FAN MOTOR

FAN MOTOR

T2 T3

T1

BL
REVERSING VALVE

1 2 3 4 5 6
GN/YL

BR BL BR BL GN/YL

To the indoor unit

BK

RD

REMOTE CONTROL

TERMINAL BLOCK OPTION

ZONE CONTROL

COMP.

BL

TERMINAL BLOCK

18

HEAT PUMP
Model : LB-E4885HL/LB-E6085HL
OUTDOOR WIRING DIAGRAM
Fuse
BK BK BK WH RD WH OR
(250V 5A)

INDOOR WIRING DIAGRAM


NO NC

HIGH PRESSURE S/W


BK WH

TNS

YL

INDOOR MOTOR

DRAIN PUMP
BL BL

Fuse
(250V 5A)

WH BK

POWER RELAY
1 3 5 7 2 4 6

TERMINAL R S T N BLOCK

BR BL

FUSE 250V10A

31

OR
T/B1

TO OUTDOOR UNIT

POWER SUPPLY

32
T/B2

COMP

POWER RELAY

WH

OR RD BL BK

ROOM SENSOR PIPE SENSOR FLOAT S/W

Deice PCB

C TH

BR

GN/YL

RD BK

BK WH BK BK RD WH YL BK

CAPACITOR

CAPACITOR

4WAY

1( L) 2( N) 3 4 5

YL BK OR

YL BK OR

WH BK

WH

FAN MOTOR

FAN MOTOR

T2 T3

T1

BL
REVERSING VALVE

1 2 3 4 5 6
GN/YL

BR BL BR BL GN/YL

To the indoor unit

BK

RD

GN/YL

REMOTE CONTROL

TERMINAL BLOCK OPTION

COMP.

A/CL UNIT

TELECONTROL/ CENTRAL CONTROL

BL

TERMINAL BLOCK

ZONE CONTROL

3854A20166K

COOLING ONLY
Model : LB-4881CL/LB-E6081CL
OUTDOOR WIRING DIAGRAM
BK BK WH RD WH OR

INDOOR WIRING DIAGRAM


BR YL

F1

INDOOR MOTOR

F1

DRAIN PUMP
BL BL

WH

TM R S T N

52C

31

A B

BR BL

FUSE 250V10A

WH

BK

COMP

BK OR BR BR

TO OUTDOOR UNIT

3, 380-415V, 50Hz POWER SUPPLY

32

TEMP. THERMISTOR PIPE THERMISTOR FLOAT S/W

GN/YL

RD

Co

Co
BK RD WH BL WH

To the indoor unit

YL BK OR

YL BK OR

FMo 49FMo

FMo 49FMo

T2
GN/YL

T1

T3

1 2 3 4 5 6
GN/YL

BK WH BL

OR RD BL BK

1(L) 2(N) 3 4 5

GN/YL

REMOTE CONTROL

GN/YL

TMo

CM

TERMINAL BLOCK OPTION

ZONE CONTROL

Model : LB-4885CL/LB-E6085CL
OUTDOOR WIRING DIAGRAM
BK BK WH RD WH OR

INDOOR WIRING DIAGRAM


YL

F1

F1

INDOOR MOTOR

DRAIN PUMP
BL BL

WH

TM R S T N

52C

31

A B

BR BL

FUSE 250V10A

TO OUTDOOR UNIT

COMP

3, 380-415V, 50Hz POWER SUPPLY


OR BR BR

32

BK

WH

BK

OR RD BL BK

ROOM SENSOR PIPE SENSOR FLOAT S/W

BR

GN/YL

1(L) 2(N) 3

RD

Co

Co
BK RD WH BL WH

YL BK OR

YL BK OR

FMo 49FMo

FMo 49FMo

T2
GN/YL

T1

T3

1 2 3 4 5 6
GN/YL

BK WH BL

To the indoor unit

5
GN/YL

REMOTE CONTROL

GN/YL

TMo

CM

TERMINAL BLOCK OPTION

A/CL UNIT

TELECONTROL/ CENTRAL CONTROL

ZONE CONTROL

3854A20166L

19

Operation Details
(1) The function of main control
1. Time Delay Safety Control
3min The compressor is ceased for 3minutes to balance the pressure in the refrigeration cycle. (Protection of compressor) 5sec Vertical louvers are delayed for 5 secs to be opened to prevent the frictional sound between louver and air flow. 30sec The 4-way valve is ceased for 30sec. to prevent abnormal noise when the Heating operation is OFF or switched to the other operation mode while compress is off. While compressor is running, it takes 3~5 seconds to switch.

2. Auto Swing Control


This function is to swing the louver up and down automatically.

3. Air-Filter Checking Control


'Filter' sign will appear on the remote controller display and main body display when an air-filter is polluted. Then clean the air-filter referring to Owners Manual. 4. Soft-Dry Operation The indoor fan speed is automatically set to the low, and fan speed control is not available because of already being set to the best speed for Dry Operation by Micom Control.

5. Cooling Mode Operation


When selecting the Cooling( ) Mode Operation, the unit will operate according to the setting by the remote controller and the operation diagram is as follows.

Intake Air temp. SET TEMP.+0.5C (COMP. ON) SET TEMP SET TEMP. -0.5C (COMP. OFF) More than 3 minutes INDOOR FAN COMPRESSOR Selected fan speed ON Low OFF Selected fan speed ON More than 3 minutes Low OFF Selected fan speed ON

20

4. Heating Mode Operation (Except Cooling Model)


The unit will operate according to the setting by the remote controller and the operation diagram is shown as following. Intake Air temp. Setting temp.+3C (Compressor OFF)

Setting temp. (Compressor ON)

1min

minimum 10sec.

minimum 1min.

minimum 10sec.

INDOOR FAN COMPRESSOR ON OFF ON

Selecting fan speed OFF

A point; While the indoor Heat-Exchanger temperature is higher than 40C fan operates at low speed, when it becomes lower than 40C fan stops. B point; When the indoor Heat-Exchanger temperature is higher than 51(42)C, fan operates at selected fan speed, when it becomes lower than 48(39)C, the fan operates at low speed.

5. Hot-Start Control
The indoor fan stops until the evaporator piping temperature will be reached to 25C. The operation diagram is as following.

PIPING TEMPERATURE 25C 22C

1min

INDOOR FAN COMPRESSOR

OFF

LOW ON

Selected fan speed

21

6. Defrost Control(30K/36K/42K/48K/60K)
Defrost control is available 45 minutes later since heating mode operation started, and it will not prolong over 10 minutes. Defrost control is carried out when the outdoor pipe temp. falls below -6C for more than 3 minutes after 45 minutes passed from starting of heating operation. Defrost ends after 10 minutes passed from starting of defrost operation or when the outdoor pipe temp. rises over 12C after 5 minutes passed from starting of defrost.
The outdoor piping Temp. 12C OFF More than 45 minutes of heating operation Within More than 45 minutes 9min. 45sec. of heating operation More than 10 min. running of compressor

-6C ON

HOTSTART

INDOOR FAN COMPRESSOR 4-WAY VALVE

ON ON ON OFF

OFF

ON

ON

s Defrost Control (New Type Defrost Control) (18K/24K) While in heating mode operation in order to protect the evaporator pipe of the outdoor unit from freezing, reversed to cooling cycle to defrost the evaporator pipe of the outdoor unit. Defrost control is available 45 min. later since heating mode operation started, and it will not prolong over 10 min. Defrost control is carried out according to the following priority order while in heating mode operation. 1st priority : Defrost control is carried out according to the indoor pipe temp 60 min. later since heating mode operation started. 2nd priority : The temp differences between the indoor pipe temp and the intake air temp 25 min. later(T1) and 45 min. later (T2) since heating mode operation started are measured, then defrost control is carried out according to the dirrerence (T=T1-T2) 3rd priority : Defrost control is carried out according to the temp difference (E=TE1-TE2) between the indoor pipe temperatures of 25 min later(TE1) and 45 min later (TE2) after heating mode operation started. When the indoor pipe temp is 41C or above, defrost control is not carried out even if the condition is one of the defrost conditions above. While in defrost control, the compressor is on and the indoor fan, the outdoor fan, and the 4 way valve are off.

7. Self-diagnosis Function
'CHECK' will flash in the remote controller display when a problem occurs. Then please contact your dealer. Correct the 'FAULT MESSAGES' as shown in the table below before restarting operation. During the normal operation 'CHECK' won't be displayed in the remote controller. Remote controller LCD C 0 H 1 CH 02 CH 03 CH 04(Optional) FAULT MESSAGES Indoor room temperature thermistor error Indoor piping thermistor error Indoor main body / Remote controller unit communication error Water level float switch error 22

Installation of Indoor, Outdoor Unit


1. Selection of the best location
1) Indoor unit
Select location Install the air conditioner in the location that satisfies the following conditions. The place shall easily bear a load exceeding four times the indoor units weight. The place shall be able to inspect the unit as the figure. The place where the unit shall be leveled. The place shall allow easy water drainage.(Suitable dimension H is necessary to get a slope to drain as figure.) The place shall easily connect with the outdoor unit. The place where the unit is not affected by an electrical noise. The place where air circulation in the room will be good . There should not be any heat source or steam near the unit.

Top view
(unit: mm)

Inspection hole (600X600) Control box

600

1000

600

Front

Front view

2) Outdoor unit
If an awning is built over the unit to prevent direct sunlight or rain exposure, be careful that heat radiation from the condenser is not restricted. There should not be any animals or plants which could be affected by hot air discharged. Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
More than 30cm

Su nro of

Fe ob nce sta or cle s

3) Piping length and the elevation


Capacity 18K BTU/h 24K H/P BTU/h C/O 30K BTU/h 36K H/P BTU/h C/O 42K BTU/h 48K BTU/h 60K BTU/h Pipe Size Length A(m) (Diameter: ) Gas Liquid Standard Max. 5/8" 1/4" 7.5 50 1/4" 7.5 50 5/8" 1/4" 7.5 50 5/8" 5/8" 3/8" 7.5 50 5/8" 3/8" 7.5 50 5/8" 3/8" 7.5 50 3/4" 3/8" 7.5 50 3/4'' 3/8" 7.5 50 3/4" 1/2" 7.5 50 Elevation B(m) Standard 5 5 5 5 5 5 5 5 5 Max. 30 30 30 30 30 30 30 30 30 * Additional refrigerant (g/m) 25 30 25 50 40 40 50 50 60

More than 30cm More than 70cm Indoor unit

A B Outdoor unit

If 18K Model is installed at a distance of 15m, 188g of refrigerant should be added (15-7.5) x 25g = 188g Capacity is based on standard length and maximun allowance length is on the basis of reliability. 23

2. Ceiling dimension and hanging bolt location


s Installation of Unit Install the unit above the ceiling correctly.

A B

CASE 1
C E
(G) 87 87 87 87 87 87 H I 750 186 830 186 750 186 830 186 830 186

POSITION OF SUSPENSION BOLT Apply a joint-canvas between the unit and duct to absorb unnecessary vibration. Apply a filter Accessory at air return hole. (Unit:mm)
Dimension Capacity

D 54 54 54 54 54 54

E 575 575 600 600 600 600 760 680 760 680

F 30 30 30 30 30 30

24K BTU/h 942 880 466 30K BTU/h 1242 1180 492 36K BTU/h (LB-C36) 1072 1010 492 36K BTU/h (LB-F36) 1242 1180 492 42K BTU/h 1242 1180 492 48K BTU/h (LB-B48) 48K BTU/h (LB-E48) 60K BTU/h (LB-B60) 60K BTU/h (LB-E60)

H
Drainage hole

1292 1230 650.5 54 1292 1230 570.5 54 1292 1230 650.5 54 1292 1230 570.5 54

30 120 1006 294 30 120 1006 294 30 120 1006 294 30 120 1006 294

M10 Nut

X4

(Local M10 SP. washer X 4 supply) M10 washer X4

Install the unit leaning to a drainage hole side as a figure for easy water drainage.

M10 washer

X4

CASE 2
POSITION OF CONSOLE BOLT A place where the unit will be leveled and that can support the weight of the unit. A place where the unit can withstand its vibration. A place where service can be easily performed.

(Local M10 SP. washer X 4 supply) M10 Nut X4

NOTE:
Throughly study the following installation locations: 1. In such places as restaurants and kitchens, considerable amount of oil steam and flour adhere to the fan, the fin of the heat exchanger, resulting in heat exchange reduction, spraying, dispersing of water drops, etc. In these cases, take the following actions: Make sure that the ventilation fan for smoke-collecting hood on a cooking table has sufficient capacity so that it draws oily steam which should not flow into the suction of the air conditioner. Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oil steam. 2. Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories, etc. 3. Avoid places where inflammable gas is generated, flows in, is stored or vented. 4. Avoid places where sulfurous acid gas or corrosive gas is generated. 5. Avoid places near high frequency generators. 24

1-3 mm

18K BTU/h 942 880 466

750 186

(G)

3. The Indoor Unit Installation


Select and mark the position for fixing bolts. Drill the hole for set anchor on the face of ceiling.

Old building
Insert the set anchor and washer onto the suspension bolts for locking the suspension bolts on the ceiling. Mount the suspension bolts to the set anchor firmly. Secure the installation plates onto the suspension bolts (adjust level roughly) using nuts, washers and spring washers.

New building

1 Set anchor 2 Plate washer 3 Spring washer 4 Nut 5 Suspension bolts


Local supply Set anchor Plate washer Spring washer Nut Suspension bolt

CAUTION Tighten the nut and bolt to prevent unit from falling off.

- M10 - M10 - W3/8 or M10 - W3/8 or M10

4. Remote Controller Installation


Although the room temperature sensor is in the indoor unit, the remote controller should be installed in such places away from direct sunlight and high humidity. Installation of the remote controller Select places that are not splashed with water. Select control position after receiving customer approval. The room temperature sensor is built in the indoor unit. This remote controller equipped with liquid crystal display. If this position is higher or lower, display is difficult to see.(The standard height is 1.2 ~ 1.5m high) Routing of the remote controller cord Keep the remote controller cord away from the refrigerant piping and the drain piping. To protect the remote controller cord from electrical noise, place the cord at least 5cm away from other power cables (audio equipment, television set, etc.) If the remote controller cord is secured to the wall, provide a trap at the top of the cord to prevent water droplets from running to the controller. 25

WIRED REMOTE CONTROL INSTALLATION


DISASSEMBLING
Front case
Th

Separate the under plate from Remote control box.

el

ow er

pa

rt

Lever carefully the box open using a screw driver, etc.

Remote control box body

Fix the under plate on the wall


Face of wall Under plate

Fix the cord clamps on the wall by 3 tapping screws (accessory). Fix the remote control cord.
Cord clamp (accessory)

Screw (accessory)

ELECTRICAL WIRING
(Main board)
CN REMO

Remote controller

Wire and make sure that teminal numbers are matched on unit side and remote controller side. The maximum length of the cord is 100m. If the length of the cord exceeds 50m, 2 use a wire size greater than 0.5mm .

REMOTE CONTROL PREPARATION(OPTIONAL)


HOW TO MOUNT ON A WALL

HOW TO INSERT BATTERIES Remove the battery cover from the remote controller. Slide the cover according to the arrow direction. Insert the two batteries. Be sure that the (+) and (-) directions are correct. Be sure that both batteries are new. Re-attach the cover. Slide it back into position. 26

Do not use rechargeable batteries, such batteries differ from standard dry cells in shape, dimensions, and performance. Romove the batteries from the remote controller if the air conditioner is not going to be used for some long time.

5. Connecting Cables between Indoor Unit and Outdoor Unit


1) Connecting cables to the Indoor Unit
Connect the wires to the terminals on the control board individually according to the outdoor unit connection. Ensure that the color of the wires of outdoor unit and the terminal No. are the same as those of indoor unit respectively (380-415V3N~) (220-240V~) R S T N 1(L) 2(N) 36K/42K/48K/60K Btu Cooling only type
Terminals on the indoor unit Terminals on the outdoor unit 1 1 2 2 3 3 4 4 5
POWER INPUT POWER INPUT

Cooling & Heating type


Terminals on the indoor unit Terminals on the outdoor unit 1 1 2 2 3 3 4 4 5 5

60K Btu(LB-E6082CL) Cooling only type


Terminals on the indoor unit Terminals on the outdoor unit 1 1 2 2 3 3 4 5

18K/24K Btu Cooling only type


Terminals on the indoor unit 3(L) 4(N) 5 6

30K Btu Cooling only type


Terminals on the indoor unit 3(L) 4(N) 5 6 7

Terminals on the outdoor unit 1(L) 2(N)


POWER INPUT

3(L) 4(N) 5

Terminals on the outdoor unit 1


POWER INPUT

Cooling & Heating type


Terminals on the indoor unit 3(L) 4(N) 5 6 7

Cooling & Heating type


Terminals on the indoor unit 3(L) 4(N) 5 6 7

Terminals on the outdoor unit 1(L) 2(N)


POWER INPUT

3(L) 4(N)

Terminals on the outdoor unit 1


POWER INPUT

CAUTION The power cord connected to the outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
NORMAL CROSS-SECTIONAL AREA
Capacity 18K BTU/h 24K BTU/h 30K BTU/h 36K BTU/h 42K BTU/h 48K BTU/h 60K BTU/h 1 Phase 2.5mm2 2.5mm2 3.3mm2 5.5mm2 8.5mm2 3 Phase 2.5mm2 3.5mm2 3.5mm2

The connecting cable connected to the indoor and outdoor unit should be complied with the following specifications (Rubber insulation, type H05RN-F approved by HAR or SAA).
NORMAL CROSS-SECTIONAL AREA 0.75mm2 (18K/24K) 1.25mm2 (30K/36K/42K/48K/60K)
20 mm

GN /YL
20 mm

GN /Y

If the supply cord is damaged, it must be replaced by a special cord or assembly availible from the manufacturer of its service agent.

WARNING
Make sure that the screws of the terminal are free from looseness.

2) Clamping of cables
1) Arrange 2 power cables on the control panel. 2) First, fasten the steel clamp with a screw to the inner boss of control panel. 3) For the cooling model, fix the other side of the clamp with a screw strongly. For the heat pump model, put the 0.75mm2 cable(thinner cable) on the clamp and tighten it with a plastic clamp to the other boss of the control panel. 4) In Australia, the length of power supply cord measured from the entry of the power supply cord to the middle of live pin on the power plug should be over 1.8m.
27

ELECTRICAL WIRING

Perform the electrical wiring work according to the electrical wiring connection.
Circuit Breaker Main power source Switch box

All wiring must comply with local requirements. Select a power source that is capable of supplying the current required by the air conditioner. Use a recognized circuit breaker between the power source and the unit. A disconnection device to adequately disconnect all supply lines must be fitted. Capacity of circuit breaker Capacity 18K BTU/h 24K BTU/h 30K BTU/h 36K BTU/h 42K BTU/h 48K BTU/h 60K BTU/h 1 Phase 20A 25A 25A 35A 40A 3 Phase 25A 25A 25A

Outdoor Indoor

Control terminal board Control box

A view

WIRING CONNECTION

Remote control cord Cord clamper

INDOOR UNIT
Remove the control box cover for electrical connection between the indoor and outdoor unit.(Remove two screws .) Use the cord clamper to fix the cord.
1

Connection cord between the indoor unit and the outdoor unit

Control box cover (On which the Electric Wiring Connection is put)

OUTDOOR UNIT
Remove the control cover for wiring connection. Use the cord clamper to fix the cord. Earthing work Connect the cable of diameter 1.6mm2 or more to the earthing terminal provided in the control box and do earthing. Please check !!

Main terminal board Control terminal board

Cord clamper Cover control

28

6. Connecting Pipes to the Indoor Unit Preparation of Piping


Main cause of gas leakage is defect in flaring work. Carry out correct flaring work in the following procedure.

1) Cutting the pipes and the cable.


s Use the accessory piping kit or the pipes purchased locally. s Measure the distance between the indoor and the outdoor unit. s Cut the pipes a little longer than measured distance. s Cut the cable 1.5m longer than the pipe length.
Copper tube 90 Slanted Uneven Rough

2) Burrs removal
s Completely remove all burrs from the cut cross section of pipe/tube. s Put the end of the copper tube/pipe to downward direction as you remove burrs in order to avoid to let burrs drop in the tubing.

Pipe Reamer

Point down

Flare nut

3) Putting nut on
s Remove flare nuts attached to indoor and outdoor units, than put them on pipe/tube having completed burr removal. (Not possible to put them on after flaring work)
Copper tube

4) Flaring work
s Carry out flaring work using flaring tool as shown below. Capacity 18K BTU/h 24K BTU/h 30K BTU/h 36K BTU/h 42K BTU/h 48K BTU/h 60K BTU/h Outside Diameter Gas Liquid 5/8" 1/4" 5/8" 1/4" 5/8" 3/8" 5/8" 3/8" 3/4" 3/8" 3/4" 3/8" 3/4" 1/2" "A" Gas Liquid 0.8~1.0 0~0.5 0.8~1.0 0~0.5 0.8~1.0 0.5~0.8 0.8~1.0 0.5~0.8 1.0~1.3 0.5~0.8 1.0~1.3 0.5~0.8 1.0~1.3 0.5~0.8
Bar Bar "A" Yoke Cone Copper pipe Clamp handle Red arrow mark Handle

Firmly hold copper tube in a bar(or die) as indicated dimension in the table above.

Smooth all round Inside is shining without scratches.

5) Check
s Compare the flared work with figure below. s If flare is noted to be defective, cut off the flared section and do flaring work again.
Even length all round

= Improper flaring =

Inclined Surface Cracked Uneven damaged thickness

29

Piping Connection
1. Form the piping according to its routing. Avoid bending and bending back the same piping point more than three times. (This will result in hardening of pipe.) 2. After deforming the piping, align centers of the union fitting of the indoor unit and the piping, and tighten them firmly with wrenches. 3. Connect pipe to the service valve or ball valve which is located below the outdoor unit. 4. After completing the piping connection, be sure to check if there is gas leakage in indoor and outdoor connection.
Liquid side Indoor unit
Outdoor unit

Flare connection Gas side Flare connection

Vacuum drying
After completing the piping connection, execute vacuum drying for the connecting piping and the indoor unit. The vacuum drying must be carried out using the service ports of both the liquid and gas side valves. Model 18K, 24K Btu/h 30K Btu/h 36K Btu/h 42K Btu/h 48K Btu/h 60K Btu/h Liquid side piping 1/4" 3/8" 3/8" 3/8" 3/8" 1/2" Gas side piping 5/8" 5/8" 5/8" 3/4" 3/4" 3/4"

CAUTION Use two wrenches and tighten with regular torque. Flare nut fastening torque 1.8kg.m 4.0kg.m 5.5kg.m 6.6kg.m 6.6kg.m

Union

6.35mm 9.52mm 12.7mm 15.88mm 19.05mm

30

CAUTION
1. Install declination of the indoor unit is very important for the drain of the duct type air conditioner. 2. Minimum thickness of the insulation for the connecting pipe shall be 5mm.

Front of view The unit must be horizontal or declined to the drain hose connected when finished installation.

Ceiling
1~3mm
CORRECT

Drainage hole

INCORRECT

Drainage hole

CAUTION FOR GRADIENT OF UNIT AND DRAIN PIPING


Alway lay the drain with downward inclination (1/50 to 1/100). Prevent any upward flow or reverse flow in any part. 5mm or thicker formed thermal insulator shall always be provided for the drain pipe.

Lay the drain hose with a downware inclination so water will drain out.
Thermal insulator (Local supply) Drainage pipe (Local supply)

Unit

Make sure to be closed.

Drainage hole

Upward routing not allowed

CORRECT

INCORRECT Applied U-Trap Dimension


A 70mm B 2C C 2 x SP SP = External Pressure (mmAq) Ex) External Pressure = 10mmAq A 70mm B 40mm C 20mm

Install the P-Trap (or U-Trap) to prevent a water leakage caused by the blocking of intake air filter.

B C U-Trap A

31

Drill the piping hole with 70mm dia, hole core drill. Piping hole should be slightly slant to the outdoor side.

Indoor

WALL

Outdoor

5~7mm

INSULATION, OTHERS
THERMAL INSULATION

Insulate the joint and tubes completely.

All thermal insulation must comply with local requirement.

INDOOR UNIT

Union for liquid pipe Refrigerant pipe and thermal insulator(Local supply) Hose crip for thermal insulator (Local supply) Thermal insulator for refrigerant pipe (Local supply) Union for gas pipe

Thermal insulator for refrigerant pipe (Local supply) Thermal insulator for piping(Local supply)

Overlap with thermal insulator for piping. Hose crip for thermal insulator(Local supply) Make sure that there is no clearance here.

REFRIGERANT PIPE
Insulate and tape both the gas piping and liquid piping.

Connecting cable Liquid pipe Thermal insulator

Tape Gas pipe

32

FORM THE PIPINGS


1. Wrap the connecting portion of indoor unit with the Insulation material and secure it with two Plastic Bands. (for the right pipings) If you want to connect an additional drain hose, the end of the drain-outlet should keep distance from the ground. (Do not dip it into water, and fix it on the wall to avoid swinging in the wind.) In case of the Outdoor unit being installed below position of the Indoor unit. 2. Tape the Pipings, drain hose and Connecting Cable from bottom to top. 3. Form the pipings gathered by taping along the exterior wall and fix it onto the wall by saddle or equivalent.

Seal a small opening around the pipings with gum type sealer.

Drain hose Taping

Pipings Connecting cable Power supply cord

Trap is required to prevent water from entering into electrical parts.

Test running
1) PRECAUTIONS IN TEST RUN
The initial power supply must provide at least 90% of the rated voltage. Otherwise, the air conditioner should not be operated. For test run, carry out the cooling operation first even during winter season. If heating operation is Caution carried out first, it leads to the trouble of compressor. Carry out the test run more than 5 minutes without stopping. (Test run will be cancelled 18 minutes later automatically) The test run is started by pressing the room temperature checking button and down timer button for 3 seconds at the same time. To cancel the test run, press any button.

CHECK THE FOLLOWING ITEMS WHEN INSTALLATION IS COMPLETE


After completing work, be sure to measure and record trial run properties, and store measured data, etc. Measuring data are room temperature, outside temperature, suction temperature, blow out temperature, air velocity, air volume, voltage, current, presence of abnormal vibration and noise, operating pressure, piping temperature. As to the structure and appearance, check following items. Is the circulation of air adequate? Is the drainage OK? Is the heat insulation complete (refrigerant and drain piping)? Is there any leakage of refrigerant? Does the romote controller works properly? Is there any error on wiring? Aren't terminal screws loosened? M4......118N.cm{12kgf.cm} M5......196N.cm{20kgf.cm} M6......245N.cm{25kgf.cm} M8......588N.cm{60kgf.cm}

33

2) Connection of power supply


1. Connect the power supply cord to the independent power supply. Circuit breaker is required. 2. Operate the unit for fifteen minutes or more.

3) Evaluation of the performance


1. Measure the temperature of the intake and discharge air. 2. Ensure the difference between the intake temperature and the discharge one is more than 8C (Cooling) or reversely (Heating).

CAUTION After the confirmation of the above conditions, prepare the wiring as follows: 1) Never fail to have an individual power specialized for the air conditioner. As for the method of wiring, be guided by the circuit diagram pasted on the inside of control box cover. 2) Provide a circuit breaker switch between power source and the unit. 3) The screw which fasten the wiring in the casing of electrical fittings are liable to come loose from vibrations to which the unit is subjected during the course of transportation. Check them and make sure that they are all tightly fastened. (If they are loose, it could give rise to burn-out of the wires.) 4) Specification of power source 5) Confirm that electrical capacity is sufficient. 6) Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate. 7) Confirm that the cable thickness is as specified in the power sources specification. (Particularly note the relation between cable length and thickness.) 8) Never fail to equip a leakage breaker where it is wet or moist. 9) The following troubles would be caused by voltage drop-down. Vibration of a magnetic switch, damage on the contact point there of, fuse breaking, disturbance to the normal function of a overload protection device. Proper starting power is not given to the compressor.

HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual (air filter cleaning, temperature control, etc.).

34

Optional Operation
1) Two Thermistor System
(1) Open the rear cover of the wired remote-controller to set the mode. (2) Select one of three selectable modes as follows. Position 1: The room temperature is controlled by the thermistor of the main body. Position 2: The room themperature is controlled by the thermistor of the wired remote-controller, control the temperature according to the position of wired remote-controller. Position 3: The room temperature is controlled by lower temperature between the temperature of main body and of remote-controller sensor. (3) Move the slide switch to set position.
Room Temp. sensor Slide switch for 2 Thermistor
TH R13H R12H CO1H OP5R16H OP4 R14H OP3 SW TH OP2 OP1 R19H R11H R15H

Position 2 Position 1 Position 3

REMO MAIN 2TH


SW

REMO MAIN 2TH R17H

OP7 R18H OP6

LO STAND HI

C070 R03S R04S R02S R01S

HIGH

(4) Close the rear cover and check if it works normally. CAUTION Select the position after counselling with a customer. In case of cooling mode, room temperature is controlled by the main body sensor. To control the room temperature by a wired remote controller, install controller(room temp. sensor) to sense the temperature more accurately. Maunfactured in the position 1.

35

2) Group Control(Optional Wiring)


You can use a group control operation after connecting the brown and yellow wire of each air-conditioner. Move slide switch #2 to the "GROUP" position. It operates maximum 16 Units by only one Wired Remote Controller, and each Unit starts sequentially to prevent overcurrent.

Wiring design
Indoor Unit 1
Terminal(Local Supply) Block Connector
RED(12V) YL(SIGNAL) BR(GND) RED(12V) YL(SIGNAL) BR(GND)

Main PCB
Indoor Unit 2
Terminal(Local Supply) Block Connector
YL(SIGNAL) BR(GND) YL(SIGNAL) BR(GND)

Indoor Unit 16
Terminal(Local Supply) Block Connector

Main PCB #1

Main PCB #2

....

YL(SIGNAL) BR(GND)

YL(SIGNAL) BR(GND)

Main PCB #16

....

Connecting Cable(Local Supply)

AUTO SWING

OPERATION

SET TEMP
Room Temp

FAN SPEED HI MED LO


ZONE

SUB FUNCTION

Time Timer
Operation unit
03 05 07

AUTO Heater Preheat JET Defrost Humidify Filter Out door 1 2 3 4


19 21 23

Slide Switch

Program set
09 11 13 15 17

On Off Set no. Time 01

Wired Remote Controller

OP7 Remote Controller PCB

Features
Use Only One Wired Remote Controller with several air conditioners(max. 16 Units) Random starting to prevent overcurrent. CAUTION
Be careful not to exchange the color of wires. The maximum length of connecting wire should be below 200m(25) on connecting each units. Use a wire more than 0.5mm2

36

Cycle
1. Installation (Connecting the piping between indoor and outdoor unit)
Indoor unit Liquid side Outdoor unit

Gas side

Gas cylinder

Lo

R22
Purge the air

Installation
(1) Connect the piping between the indoor and outdoor unit firmly. Incorrect connection may cause the leakage and incomplete vacuuming. (2) Attach the charging hose (manifold gage) to the service port. Charging hose is necessary to check the pressure and to inject N2 for leakage test. The valve of charging hose must be closed before being connected. (3) Inject the 100~300g N2 through the charging hose opening the valve. (4) Check the joint part using a gas detector or soapy water for leakage. On checking, the service valve of main service port must be closed, this test is only for checking whether pipe connection is ok or not. (5) If there is no leakage, discharge N 2 in piping completely into tank for retrieving. Complete discharge is needed for vacuuming. If leakage is found, please fasten the joint more tightly. (6) After closing the valve of charging hose, disconnect the tank and connect the vacuum pump to charging hose and open the valve again for vacuuming. (7) Turn on the vacuum pump until the pressure drops below 0kg/cm2. (8) After vacuuming, disconnect the vacuum pump and open the spindle of service port (liquid-side) slightly for 30 sec and then open the spindle of (gas side) with hexagonal wrench. (9) Open the liquid side completely first and then the gas side fully in order.

37

2. Disconnection (on moving)

Indoor unit

Liquid side Outdoor unit

Gas side

Retrieving Tank

Lo

Disconnection
(1) Attach the charging hose (manifold gage) to the service port. Connect the manifold gage once to the service port not stopping. Stopping in the middle of process may cause the leakage. (2) Purge the air in hose into special device such as retrieving tank opening the valve of charging- hose (gas side) slightly and then close it tightly. (3) Operate the air conditioner for 10~15 min until cycle is stabilized. (4) Close the spindle of service port (liquid sidehigh pressure) and wait till pressure of gas side (low pressure) drops below 0kgf/cm2. (5) After the needle of gage indicates below 0 kgf/cm2, close the valve of gas side quickly and turn off the power. (6) Disconnect the piping between indoor and outdoor unit and then put on service cap to the service port.

38

3. Gas Charging
(After Evacuation)

Indoor unit

Liquid side 2-Way valve

Open

Outdoor unit

Gas side

Open
Check valve 3-Way valve

Charging cylinder Lo
(1) OPEN CLOSE

Procedure
\

(1) Connect the charge hose to the charging cylinder. Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If you are using a gas cylinder, also use a scale and reverse the cylinder so that the system can be charged in liquid state. (2) Purge the air from the charge hose. Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air. (Be careful of the liquid refrigerant). The procedure is the same if using a gas cylinder. (3) Open the valve (Lo side on the charge set and charge the system with liquid refrigerant. If the system can not be charged with the specified amount of refrigerant, it can be charged with a little at a time (approximately 150g each time) while operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.

This is different from previous procedures. Because you are charging with liquid refrigerant from the gas side, absolutely do not attempt to charge with larger amounts of liquid refrigerant while operating the air conditioner. (4) Immediately disconnect the charge hose from the 3-way valves service port. Stopping partway will allow the gas to be discharged. If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose. (5) Mount the valve stem nuts and the service port nut. Use torque wrench to tighten the service port nut to a torque of 1.8 kg.m. Be sure to check for gas leakage.

39

Cycle Troubleshooting Guide


Trouble analysis
1. Check temperature difference between intake and discharge air and operating current. Temp. difference Current : approx. 0C : less than 80% of rated current All amount of refrigerant leaked out Check refrigeration cycle

Temp. Difference

Temp. difference Current

: approx. 8C : less than 80% of rated current

Refrigerant leakege Clog of refrigeration cycle Defective compressor

Operating Current

Temp. difference Current

: less than 8C : over the rated current

Excessive amount of refrigerant

Temp. difference

: over 8C

Normal

Notice : Temperature difference between intake and discharge air depends on room air humidity. When the room air humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower temperature difference is larger. 2. Check temperature and pressure of refrigeration cycle. Suction pressure (Compared with the normal value) Temperature (Compared with the normal value) High Higher Normal

Cause of Trouble Defective compressor Defective 4-way reverse valve Excessive amount of refrigerant Insufficient amount of refrigerant (Leakage) Clogging

Description Current is low High pressure does not quickly rise at the beginning of operation Current is low Current is low

Lower

Higher

Notice : 1. The suction pressure is usually 4.5~6.0 kg/cm2G at normal condition. 2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with putty.

40

Electronic Parts Troubleshooting Guide


Possible Trouble 1
: The unit does not operate.

Is the input voltage AC230V? YES Is the input voltage of IC03D about AC12V? YES

NO

Check the FUSE and the wiring diagram.

NO

Check the main P.C.B pattern.

Is the output voltage of IC03D DC5V? YES

NO

Exchange IC03D.

Is the PIN 49,58 of MICOM. DC5V? YES Exchange MICOM.

NO

Check the 5V P.C.B pattern.

41

Possible Trouble 2
Is it the HOT START mode? NO

: The indoor fan does not operate.

YES

It is normal operation.

Is IC01M operated normally? YES Is the each Relay any problem? NO Check the fan motor and connector.(CN-MOTOR)

NO

Exchange IC01M.

YES

Exchange Relay.

Possible Trouble 3

: Ineffective Heating

Is it Heating Mode? YES Does the temperature set all right? YES

NO

Adjust operation mode.

NO

Adjust set temperature.

Is IC01M operated normally? YES

NO

Change IC01M.

Is 4way-valve operated? YES Check the connector. (CN-OUT)

NO

Check RY-4Way.

42

Possible Trouble 4

: Wired remote controller does not operate.

Is the LCD operated normally? NO

YES

Check the parts of communication.

Is the terminal of wired Remocon T2 DC12V? YES

NO

Connector CN-Remo, and terminals of wired Remocon exactly.

Is the pin 39, 40 of Micom DC 5V? YES Change the wired Remocon.

NO

Check the wired Remocon PCB and DC 12V pattern.

43

Electronic control device


s MAIN P.C.B ASM

44

Exploded View and Replacement Parts List


1. Indoor Unit
Model: LB-D1861ZL/HL/CL, LB-D2461ZL/HL/CL, LB-F3061HL/CL, LB-F3661HL/CL/ZL, LB-F3681HL/CL/ZL, LB-F4261HL, LB-E4881HL/CL/ZL, LB-E4885HL/CL, LB-E6081HL/CL/ZL, LB-E6085HL/CL
267110-2 336610-2 152302 267110-1 35211C-2 35211C-1 263230-2 263230-1 359012-2 249951

336610-1

359012-1

346810

354210

W0CZZ

268714

330860

45

753000

Parts List
18K/24K
Part No. LOCATION No. 152302 249951 263230-1 263230-2 267110-1 267110-2 268714 330860 336610-1 336610-2 346810 35211C-1 35211C-2 354210 359012-1 359012-2 W0CZZ 753000 DESCRIPTION FILTER(MECH), A/C CONTROL BOX ASSY, INDOOR THERMISTOR ASSY THERMISTOR ASSY REMOTE CONTROLLER ASSY REMOTE CONTROLLER ASSY PWB(PCB) ASSY, MAIN DRAIN PAN HOUSING ASSY(MECH) HOUSING ASSY(MECH) MOTOR ASSY, INDOOR TUBE ASSY, DISCHARGE TUBE ASSY, DISCHARGE EVAPORATOR ASSY FAN ASSY, BLOWER FAN ASSY, BLOWER CAPACITOR, DRAWING HEATER, ELECTRIC LB-D1861HL LB-D1861CL LB-D1861ZL LB-D2461HL LB-D2461CL LB-D2461ZL 5230A30001D 5230A30001D 5230A30001D 5230A30001D 5230A30001D 5230A30001D 4995A20011Q 4995A20011R 4995A20011X 4995A20011Q 4995A20011R 4995A20011X 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6711A10002D 6711A10002C 6711A10002V 6711A10002D 6711A10002C 6711A10002V 6711A20041E 6711A20041D 6711A20041F 6711A20041E 6711A20041D 6711A20041F 6871A10008B 6871A10008D 6871A10038Y 6871A10008B 6871A10008D 6871A10038Y 3086A30001F 3086A30001F 3086A30001F 3086A30001F 3086A30001F 3086A30001F 3661A10009A 3661A10009A 3661A10009A 3661A10009A 3661A10009A 3661A10009A 3661A10009B 3661A10009B 3661A10009B 3661A10009B 3661A10009B 3661A10009B 4681A20005L 4681A20005L 4681A20005L 4681A20005L 4681A20005L 4681A20005L 5211A30094A 5211A30094A 5211A30094A 5211A30094A 5211A30094A 5211A30094A 5211A30094C 5211A30094C 5211A30094C 5211A30094C 5211A30094C 5211A30094C 5421A20008G 5421A20008G 5421A20008G 5421A20008G 5421A20008G 5421A20008G 5901A10015A 5901A10015A 5901A10015A 5901A10015A 5901A10015A 5901A10015A 5901A10015B 5901A10015B 5901A10015B 5901A10015B 5901A10015B 5901A10015B 2H00841C 2H00841C 2H00841C 5300A20004A 2H00841C 2H00841C 2H00841C 5300A20004A R R R R R R R R R R R R R R R R R R REMARKS

46

Parts List
30K
Part No. LOCATION No. 152302 249951 263230-1 263230-2 267110-1 267110-2 268714 330860 336610-1 336610-2 346810 35211C-1 35211C-2 354210 359012-1 359012-2 W0CZZ DESCRIPTION FILTER(MECH), A/C CONTROL BOX ASSY, INDOOR THERMISTOR ASSY THERMISTOR ASSY REMOTE CONTROLLER ASSY REMOTE CONTROLLER ASSY PWB(PCB) ASSY, MAIN DRAIN PAN HOUSING ASSY(MECH) HOUSING ASSY(MECH) MOTOR ASSY, INDOOR TUBE ASSY, DISCHARGE TUBE ASSY, DISCHARGE EVAPORATOR ASSY FAN ASSY, BLOWER FAN ASSY, BLOWER CAPACITOR, DRAWING LB-F3061HL 5230A30001F 4995A20011V 6323AQ3214Q 6323AQ3226G 6711A10002D 6711A20041E 6871A10008C 3086A30001F 3661A10009C 3661A10009D 4681A20005M 5211A30094A 5211A30094B 5421A20008D 5901A10015C 5901A10015D 2H00841C LB-F3061CL 5230A30001F 4995A20164P 6323AQ3214Q 6323AQ3226G 6711A10002C 6711A20041D 6871A10008D 3086A30001F 3661A10009C 3661A10009D 4681A20005M 5211A30094A 5211A30094B 5421A20008D 5901A10015C 5901A10015D 2H00841C R R R R R R R R R R R R R R R R R REMARKS

47

Parts List
36K
Part No. LOCATION No. 152302 249951 263230-1 263230-2 267110-1 267110-2 268714 330860 336610-1 336610-2 346810 35211C-1 35211C-2 354210 359012-1 359012-2 W0CZZ 753000 DESCRIPTION FILTER(MECH), A/C CONTROL BOX ASSY, INDOOR THERMISTOR ASSY THERMISTOR ASSY REMOTE CONTROLLER ASSY REMOTE CONTROLLER ASSY PWB(PCB) ASSY, MAIN DRAIN PAN HOUSING ASSY(MECH) HOUSING ASSY(MECH) MOTOR ASSY, INDOOR TUBE ASSY, DISCHARGE TUBE ASSY, DISCHARGE EVAPORATOR ASSY FAN ASSY, BLOWER FAN ASSY, BLOWER CAPACITOR, DRAWING HEATER, ELECTRIC LB-F3661HL LB-F3661CL LB-F3661ZL LB-F3681HL LB-F3681CL LB-F3681ZL 5230A30001F 5230A30001F 5230A30001F 5230A30001F 5230A30001F 5230A30001F 4995A20011S 4995A20011T 4995A20011U 4995A20011S 4995A20011T 4995A20011U 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6711A10002D 6711A10002C 6711A10002V 6711A10002D 6711A10002C 6711A10002V 6711A20041E 6711A20041D 6711A20041F 6711A20041E 6711A20041D 6711A20041F 6871A10008C 6871A10008D 6871A10008Z 6871A10008C 6871A10008D 6871A10008Z 3086A30001K 3086A30001K 3086A30001K 3086A30001K 3086A30001K 3086A30001K 3661A10009C 3661A10009C 3661A10009C 3661A10009C 3661A10009C 3661A10009C 3661A10009D 3661A10009D 3661A10009D 3661A10009D 3661A10009D 3661A10009D 4681A20005M 4681A20005M 4681A20005M 4681A20005M 4681A20005M 4681A20005M 5211A30094A 5211A30094A 5211A30094A 5211A30094A 5211A30094A 5211A30094A 5211A30094B 5211A30094B 5211A30094B 5211A30094B 5211A30094B 5211A30094B 5421A20008D 5421A20008D 5421A20008D 5421A20008D 5421A20008D 5421A20008D 5901A10015C 5901A10015C 5901A10015C 5901A10015C 5901A10015C 5901A10015C 5901A10015D 5901A10015D 5901A10015D 5901A10015D 5901A10015D 5901A10015D 2H00841C 2H00841C 2H00841C 5300A20004C 2H00841C 2H00841C 2H00841C 5300A20004B R R R R R R R R R R R R R R R R R R REMARKS

48

Parts List
42K/48K
Part No. LOCATION No. 152302 249951 263230-1 263230-2 267110-1 267110-2 268714 330860 336610-1 336610-2 346810 35211C-1 35211C-2 354210 359012-1 359012-2 W0CZZ 753000 DESCRIPTION FILTER(MECH), A/C CONTROL BOX ASSY, INDOOR THERMISTOR ASSY THERMISTOR ASSY REMOTE CONTROLLER ASSY REMOTE CONTROLLER ASSY PWB(PCB) ASSY, MAIN DRAIN PAN HOUSING ASSY(MECH) HOUSING ASSY(MECH) MOTOR ASSY, INDOOR TUBE ASSY, DISCHARGE TUBE ASSY, DISCHARGE EVAPORATOR ASSY FAN ASSY, BLOWER FAN ASSY, BLOWER CAPACITOR, DRAWING HEATER, ELECTRIC LB-F4261HL LB-E4881HL LB-E4881CL LB-E4881ZL LB-E4885HL LB-E4885CL 5230A30001F 5230A30001A 5230A30001A 5230A30001A 5230A30001A 5230A30001A 4995A20011S 4995A20011S 4995A20011T 4995A20011U 4995A20164J 4995A20164K 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6711A10002D 6711A10002D 6711A10002C 6711A10002V 6711A20043D 6711A20043E 6711A20041E 6711A20041E 6711A20041D 6711A20041F 6711A20041E 6711A20041D 6871A10008C 6871A10008C 6871A10008D 6871A10008Z 6871A10040M 6871A10040N 3086A30001K 3086A30001H 3086A30001H 3086A30001H 3086A30001H 3086A30001H 3661A10009C 3661A10009E 3661A10009E 3661A10009E 3661A10009E 3661A10009E 3661A10009D 3661A10009F 3661A10009F 3661A10009F 3661A10009F 3661A10009F 4681A20005M 4681A20005K 4681A20005K 4681A20005K 4681A20005K 4681A20005K 5211A30077A 5211A30077A 5211A30077A 5211A30077A 5211A30077A 5211A30077A 5211A30094B 5211A30094B 5211A30094B 5211A30094B 5211A30094B 5211A30094B 5421A20008F 5421A20008A 5421A20008A 5421A20008A 5421A20008A 5421A20008A 5901A10015C 5901A10015E 5901A10015E 5901A10015E 5901A10015E 5901A10015E 5901A10015D 5901A10015F 5901A10015F 5901A10015F 5901A10015F 5901A10015F 2H00841C 0CZZA20001C 0CZZA20001C 0CZZA20001C 0CZZA20001C 0CZZA20001C 5300A10001C R R R R R R R R R R R R R R R R R R REMARKS

49

Parts List
60K
Part No. LOCATION No. 152302 249951 263230-1 263230-2 267110-1 267110-2 268714 330860 336610-1 336610-2 346810 35211C-1 35211C-2 354210 359012-1 359012-2 W0CZZ 753000 DESCRIPTION FILTER(MECH), A/C THERMISTOR ASSY THERMISTOR ASSY LB-E6081HL LB-E6081CL LB-E6081ZL LB-E6085HL LB-E6085CL 5230A30001A 5230A30001A 5230A30001A 5230A30001A 5230A30001A 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3214Q 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G 6323AQ3226G R R R R R R R R R R R R R R R R R R REMARKS

CONTROL BOX ASSY, INDOOR 4995A20011S 4995A20011T 4995A20011U 4995A20164J 4995A20164K

REMOTE CONTROLLER ASSY 6711A10002D 6711A10002C 6711A10002V 6711A20043D 6711A20043E REMOTE CONTROLLER ASSY 6711A20041E 6711A20041D 6711A20041F 6711A20041E 6711A20041D PWB(PCB) ASSY, MAIN DRAIN PAN HOUSING ASSY(MECH) HOUSING ASSY(MECH) MOTOR ASSY, INDOOR TUBE ASSY, DISCHARGE TUBE ASSY, DISCHARGE EVAPORATOR ASSY FAN ASSY, BLOWER FAN ASSY, BLOWER CAPACITOR, DRAWING HEATER, ELECTRIC 6871A10008C 6871A10008D 6871A10008Z 6871A10040M 6871A10040N 3086A30001H 3086A30001H 3086A30001H 3086A30001H 3086A30001H 3661A10009E 3661A10009E 3661A10009E 3661A10009E 3661A10009E 3661A10009F 3661A10009F 3661A10009F 3661A10009F 3661A10009F 4681A20005Q 4681A20005Q 4681A20005Q 4681A20005Q 4681A20005Q 5211A30077A 5211A30077A 5211A30077A 5211A30077A 5211A30077A 5211A30094B 5211A30094B 5211A30094B 5211A30094B 5211A30094B 5421A20008E 5421A20008E 5421A20008E 5421A20008E 5421A20008E 5901A10015E 5901A10015E 5901A10015E 5901A10015E 5901A10015E 5901A10015F 5901A10015F 5901A10015F 5901A10015F 5901A10015F 0CZZA20001B 0CZZA20001B 0CZZA20001B 0CZZA20001B 0CZZA20001B 5300A10001C -

50

554031 437212

2. Outdoor Unit

435512

546810 W0CZZ-2 559010

W6920 437210 W0CZZ-1

Model: LB-D1861HL/CL/ZL, LB-D2461HL/CL/ZL

51
CS R 561410

649950

435301 268713 W0CZZ-3 552202

554160

349490

552203-1

552203-2

435512 263230 137213

2. Outdoor Unit

Model: LB-F3061HL/CL

554031 435300

546810 W0CZZ-1 559010 W6920 W0CZZ-2 552201

437210

52
561410 CS R

268712

349490

649950

435301 552202 566000

554160

552203-1

552203-2

Parts List
18K/24K/30K
Part No. LOCATION No. 137213 263230 268712 349490 435300 435301 435512 437210 437212 546810 552201 552202 552203-1 552203-2 554031 554160 559010 561410 566000 649950 W6920 W0CZZ-1 W0CZZ-2 268713 W0CZZ-3 DESCRIPTION PANEL ASSY, SIDE THERMISTOR ASSY PWB(PCB) ASSY, DEICER ORIFICE GRILLE, REAR GRILLE, DISCHARGE COVER ASSY, TOP PANEL ASSY, FRONT SUB PANEL ASSY, REAR MOTOR ASSY, OUTDOOR VALVE, CHECK VALVE, REVERSING VALVE, SERVICE VALVE, SERVICE CONDENSER ASSY, BENT COMPRESSOR ASSY, FINAL FAN ASSY, PROPELLER COIL ASSY, REVERSING VALVE SWITCH, PRESSURE CONTROL BOX ASSY, OUTDOOR RELAY CAPACITOR, DRAWING CAPACITOR, DRAWING PCB, SOFT START CAPACITOR REMARKS LB-D1861HL LB-D2461HL LB-D1861CL LB-D2461CL LB-F3061HL LB-F3061CL LB-D1861ZL LB-D2461ZL 1A00202C 1A00202C R 3H03266N 3H03266N 3H03266N 3H03266N 3Q35015G 6871A20015R 1A00208D 2A00915F 1A00197C 3A01020H 3A02027B 2A00392E 2A00393Q 2A01032A 1A00195B 3A02028Y 3A02524A 2A00986A 2A00986D 2A00986A 2A00986D 1A00208D 2A00915F 1A00197C 3A01020H 3A02027B 2A00392E 2A00393Q 2A01032A 1A00195B 3A02524A R R R R R R R R R R R R R R R R R R Only Australia R R R Only Australia Only Australia

4948AP2527A 4948AP2527A 4948AP2527A 4948AP2527A 4948AP2527A 4948AP2527A 3530AP2289V 3530AP2289V 3530AP2289V 3530AP2289V 3530A20007B 3530A20007B 3721A20005J 3721A20005J 3721A20005J 3721A20005J 3720AP0003D 3720AP0003D 3720AP0003D 3720AP0003D 3A02027A 2A00392E 2H02479B 2A00392E 2H02479B 3A02027A 2A00392E 2H02479B 2A00392E 2H02479B

4681A20013A 4681A20013A 4681A20013A 4681A20013A 4681A20008N 4681A20008N

5402AR2347B 5402AR2347H 5402AR2347B 5402AR2347H 6140AP2096Q 6140AP2096Q 5416A20016A 5416A20016A 5416A20016B 5416A20016B 1A00195B 3A02028Y 1A00195B 1A00195B 3A02028Y 4995A10040C 1A00195B -

4995A20014C 4995A20014D 4995A20014C 4995A20014D 4995A20167A 4995A20027S 6920AP3400A 6920AP3400A 6920AP3400A 6920AP3400A 6920AP3400A 6920AP3400A 6120AR2194K 6120AR2194K 6120AR2194K 6120AR2194K 6871A20052B 0CZZAP3478C -

53

137213 435512

2. Outdoor Unit

437212

554031-1

554031-2 552201

Model: LB-F3661HL/CL/ZL, LB-F3681HL/CL/ZL

54
437210 567490 546810 W0CZZ-1 559010 W0CZZ-3 W0CZZ-2 263230 649950 268711 W6920 566001

552202 561410

566000

548490 552203-1

435301

554160

552203-2

Parts List
36K
Part No. LOCATION No. 137213 263230 268711 435301 435512 437210 437212 546810 548490 552201 552202 552203-1 552203-2 554031-1 554031-2 554160 559010 561410 566000 567490 649950 566001 W6920 W0CZZ-1 W0CZZ-3 W0CZZ-2 DESCRIPTION PANEL ASSY, SIDE THERMISTOR ASSY PWB(PCB) ASSY, DEICER GRILLE, DISCHARGE COVER ASSY, TOP PANEL ASSY, FRONT SUB RANEL ASSY, REAR MOTOR ASSY, OUTDOOR ACCUMULATOR ASSY VALVE, CHECK VALVE, REVERSING VALVE, SERVICE VALVE, SERVICE CONDENSER ASSY, BENT CONDENSER ASSY, BENT COMPRESSOR ASSY, FINAL FAN ASSY, PROPELLER COIL ASSY, REVERSING VALVE SWITCH, PRESSURE P.T.C ASSY CONTROL BOX ASSY, OUTDOOR SWITCH, MAGNET RELAY CAPACITOR, DRAWING CAPACITOR CAPACITOR LB-F3661HL LB-F3661ZL 3A01055Z 3Q35015H 6871A20015N 2A00144Y 3A01040Y 3A00426X 2A00252Z 2H00430X 4849A20001Q 3A01020H 3A02027B 2A00392A 2A00393A 5403A20006A 5403A20006G 5417A90001F 1H00156B 3A02028Y 3A02524A 3A01911B LB-F3661CL 3A01055Z 2A00144Y 3A01040Y 3A00426X 2A00252Z 2H00430X 4849A20001Q 3A02027B 2A00392A 2A00393A 5403A20006A 5403A20006G 5417A90001F 1H00156B 3A01911B LB-F3681HL LB-F3681ZL 3A01055Z 3Q35015H 6871A20015U 2A00144Y 3A01040Y 3A00426X 2A00252Z 2H00430X 4849A20001Q 3A01020H 3A02027B 2A00392A 2A00393A 5403A20006A 5403A20006G 5417A90001E 1H00156B 3A02028Y 3A02524A LB-F3681CL 3A01055Z 2A00144Y 3A01040Y 3A00426X 2A00252Z 2H00430X 4849A20001Q 3A02027B 2A00392A 2A00393A 5403A20006A 5403A20006G 5417A90001E 1H00156B REMARKS R R R R R R R R R R R R R R R R R R R R

4995AZ20003X 4995AZ20003R 4995AZ20003W 4995AP1089J 4995A10041B 2A00771D 3A00261C 0CZZA20001D 0CZZAP3478E 3A02157A 2A00771D 3A00261C 2A00986X 3A02157A 2A01031A 3A00261C 3A02157A 2A01031A 3A02157A Only Australia R R R Only Australia

55

554031-1

2. Outdoor Unit

435512

546810

554031-2 649950 566001 W0CZZ 268711 437212

559010

435301

Model: LB-F4261HL/CL, LB-E4881HL/CL/ZL, LB-E4885HL/CL, LB-E6081HL/CL/ZL, LB-E6085HL/CL

56
263230 W6920 561410 137213 566000 548490 552202 554160

437210 552115

552201 552203-1

552203-2

Parts List
42K/48K/60K

Part No. LOCATION No. 137213 263230 268711 435301 435512 437210 437212 546810 548490 552115 552201 552202 552203-1 552203-2 554031-1 554031-2 554160 559010 561410 566000 649950 566001 W6920 W0CZZ DESCRIPTION LB-F4261HL PANEL ASSY, SIDE THERMISTOR ASSY PWB(PCB) ASSY, DEICER GRILLE, DISCHARGE COVER ASSY, TOP PANEL ASSY, FRONT SUB RNAEL ASSY, REAR MOTOR ASSY, OUTDOOR ACCUMULATOR ASSY TUBE ASSY, MANIFOLD VALVE, CHECK VALVE, REVERSING VALVE, SERVICE VALVE, SERVICE CONDENSER ASSY, BENT CONDENSER ASSY, BENT COMPRESSOR ASSY, FINAL FAN ASSY, PROPELLER COIL ASSY, REVERSING VALVE SWITCH, PRESSURE SWITCH, MAGNET RELAY CAPACITOR, DRAWING LB-E4881HL/ZL LB-E4881CL LB-E6081HL/ZL LB-E6081CL REMARKS LB-E4885HL LB-E4885CL LB-E6085HL LB-E6085CL R R R R R R R R R R R R R R R R R R R R R R R R 3Q35015E 3Q35015E 6871A20015N -

3720AP1215B 3720AP1215B 3720AP1215B 3720AP1215B 3720AP1215B 3Q35015E 6871A20015U 6871A20015N

3530AP1225B 3530AP1225B 3530AP1225B 3530AP1225B 3530AP1225B 3550AP1213B 3550AP1213B 3550AP1213A 3550AP1213B 3550AP1213A 3720AP1212B 3720AP1212B 3720AP1212B 3720AP1212B 3720AP1212B 3720AP1202C 3720AP1202C 3720AP1202C 3720AP1202C 3720AP1202C 4680AP2135M 4681A20008R 4681A20008P 4681A20008P 4681A20008P 3A01020H 3A02080A 2A00393Q 2A00499A 4849A20001H 4849A20001J 4849A20001K 4849A20001K 5211AP3988A 5211A30124B 5211AP3988A 5211AP3988A 4A00322A 3A02080A 2A00393Q 2A00499A 2A00393Q 2A00499A 4A00322A 3A02080A 2H0189G 2A00499A 2H0189G 2A00499A

5403AP2378K 5403AP2378D 5403A20001H 5403AP2378D 5403A20003M 5403AP2378Z 5403AP2378F 5403A20001H 5403AP2378F 5403A20003P 5416A10001A 5417A30002A 5417A30002A 5417A20008G 5417A20008G 1A00195B 3A02028B 3A01100A 2A01031C 3A00261C 2A00986D 1A00195B 3A02028B 3A01100A 2A01031A 3A00261C 2A00986D 1A00195B 2A01031C 2A00986D 1A00195B 3A02028B 3A01100A 2A01031A 3A00261C 2A00986D 1A00195B 2A01031C 2A00986D

CONTROL BOX ASSY, OUTDOOR 4995A20167B 6615AP2772Y 6615AP2772Z 6615AP2772Y 6615AP2772Z

57

Memo

58

P/No.: 3828A30023K P/No.: 3828A20050E

March, 2002 December, 2000 Printed in Korea Printed in Korea