Type PM, 550 kV, up to 80 kA Power Circuit Breaker

Standard features - Dead tank design, with each tank containing two serially connected, 2-cycle puffer interrupters (three interrupters for 80 kA) on separate galvanized steel frames - National Board certification of interrupter tanks per the ASME Pressure Vessel and Boiler Code - Certified per ANSI C37.04, C37.06, and C37.09 Standards - Each pole is independently driven by a maintenance-free HMB-8 class spring-hydraulic mechanism - Free standing NEMA-3R steel control cabinet protected with TGIC polyester powdercoat finish - Gas density monitor and pressure gauge directly-mounted to each tank - Porcelain or silicone rubber composite bushings - Continuous current ratings through 4000 A - Pole units, less bushings and support structures, are shipped complete with interrupters, mechanism, current transformers, and CT terminal cabinets - High seismic designs Options and accessories - Condition monitoring with the Circuit Breaker Sentinel (CBS) - Tank heaters for operation in ambient temperatures below -30C - Plug-and-play connectors for control wiring can save 6-8 days installation time - Pre-insertion resistors, 425 ohms per pole, to reduce transients from switching operations

With a large installed base and proven track record, the PM breaker offers unequalled performance and reliability. ABB advantages - Interrupting performance through 63 kA without shunt capacitors for short line fault performance, saves cost and simplifies engineering - High performance interrupters for definite purpose breaker reduce potential for overvoltages caused by restrikes during capacitor bank switching - One-piece, two-break interrupter assembly (three-break at 80 kA) simplifies field change-out whenever end of life is reached by eliminating need for internal tank mounting of separate parts and alignment - Fully-integrated spring-hydraulic operating mechanisms are self lubricating and self-damping. They are also hermetically sealed to the atmosphere, which eliminates corrosion and helps provide maintenance-free performance with long term stability - Externally accessible current transformers enable simple field change-out without degassing breaker and bushing removal - Extensive range of available field services, from technical assistance to turn-key installation, can dramatically reduce construction costs and speed time to commercial operation

HMB-8 mechanism The moving contacts of each pole are driven by a type HMB-8 class spring-hydraulic mechanism. Mechanical energy in each is stored in a stack of compression disk springs and is translated hydraulically to the poles operating shaft. Spring charge is automatically maintained by the operation of a universal motor and hydraulic pump. Each fully -integrated mechanism is self-lubricating, hermetically sealed to the atmosphere and weather protected, affording excellent reliability and long term stability.

PHASE TO PHASE

300 (7620)

PHASE TO PHASE

300 (7620)

289 3/4" (7360)


METAL TO METAL

289 3/4" (7360)


METAL TO METAL

*270 9/16 (6872) *224 3/16 (5694) *210 5/8 (5351)


METAL TO METAL HEIGHT REQUIRED TO REMOVE BUSHING

304 1/4 (7727)

280 5/8 (7128)


INSTALLED HEIGHT

RUPTURE DISK CONTROL CABINET POLE CABINET

66 (1676)

RECOMMENDED

192 (4877)

109 5/8 (2784)


40 20 60 PSIG 80 DENSITY

30 (762)
DENSITY MONITOR

67 (1704)

27 1/2" (700)

30 (762)

RUPTURE DISK (FAR SIDE)

PRESSURE GAUGE

82 5/8 (2098)

*258 (6555)

* Add 45.27 (1150 mm) for 80 kA

Rated capabilities
Circuit Breaker Type 550PM40-20 550PM40-30 550PM40-40 550PM50-20 550PM50-30 550PM50-40 550PM63-20 550PM63-30 550PM63-40 550PM80-20 550PM80-30 550PM80-40 Rated Maximum Voltage (kV, rms) 550 550 550 550 550 550 550 550 550 550 550 550 Short Circuit and Short Time Current (kA, rms) 40 40 40 50 50 50 63 63 63 80* 80* 80* Maximum Continuous Current (A, rms) 2000 3000 4000 2000 3000 4000 2000 3000 4000 2000 3000 4000 Rated Interrupting Time (Cycles) 2 2 2 2 2 2 2 2 2 2 2 2 Full Wave Withstand Voltage (kV, Peak) 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 1800 Power Frequency Insulation Withstand Voltage (kV, rms) 860 860 860 860 860 860 860 860 860 860 860 860 2 -sec Chopped Wave Impulse Voltage (kV, rms) 2320 2320 2320 2320 2320 2320 2320 2320 2320 2320 2320 2320 Closing and Latching Current (kA, Peak) 104 104 104 130 130 130 164 164 164 208 208 208

* 13-nF load-side shunt capacitors required for 90% short line fault interrupting performance

For more information please contact: ABB Inc. High Voltage Products Westmoreland Distribution Park East 100 Distribution Circle Mount Pleasant, Pennsylvania, USA Phone: +1 (724) 696-1500 Fax: +1 (724) 696-1502 www.abb.com/highvoltage

Document Number - 2GNM110012 / May 2009

MINIMUM CLEARANCE NEEDED TO PULL INTERRUPTER METAL TO METAL

156 (3962)

41" (1047)

HOUSING MOUNTED ON FAR SIDE

269 1/2 (6844)


LIVE PARTS

100

MONITOR

120

140