You are on page 1of 36

General product cataloge

ABB Medium Voltage Products Outdoor apparatus

Contents

Introduction 04 This is ABB 05 The one-shop service for all your medium voltage needs Outdoor dead tank circuit breakers 06 R-MAG magnetically actuated outdoor vacuum circuit breaker Outdoor live tank circuit breakers 07 OVB-SDB outdoor vacuum circuit breaker 08 OVB-VBF outdoor vacuum circuit breaker 09 10 11 12 Reclosers OVR-1 single-phase solid dielectric recloser OVR-3 three-phase solid dielectric recloser OVR-3SP three-phase solid dielectric recloser PCD control for OVR-3 and OVR-3SP three-phase solid dielectric recloser

Pole mounted circuit breaker 13 PVB pole mounted vacuum circuit breaker Outdoor three-phase air switches 14 NPS modular outdoor switch disconnectors 15 GridGuard three-phase outdoor air switch

2 Contents | ABB Medium Voltage Products

Outdoor three-phase load break switches 16 SECTOS 24kV NXB and NXBD SF6 load break switch 18 SECTOS 36kV NXA SF6 load break switch Electronic sectionalizers 20 AutoLink single-phase electronic sectionalizer 21 AutoLink three-phase electronic sectionalizer 22 AutoLink loadbreak electronic sectionalizer 23 24 25 26 27 Single-phase switches DCD single-phase disconnect switch SID single-phase disconnect switch LSID single-phase load break disconnect switch RBD single-phase bypass disconnect switch ITD inline tension disconnect switch

Fuse cutouts 28 ICX interchangeable fuse cutout 29 NCX fuse cutout 30 LBU-II loadbreak fuse cutout Instrument transformers 31 Outdoor ANSI medium voltage instrument transformers 32 Outdoor IEC medium voltage instrument transformers Service 33 Reliable, trouble-free and efficient operation

ABB Medium Voltage Products | Contents 3

Introduction This is ABB

ABB is a global leader in power and automation technologies that enable utility and industry customers to improve their performance while lowering environmental impact.
Our group comprises five main divisions: Power Products Power Systems Discrete Automation and Motion Low Voltage Products Process Automation

Sustainability Sustainability is integral to all aspects of ABBs business so we aim to balance economic success, environmental stewardship and social progress to benefit all our stakeholders. Sustainability considerations cover how we design and manufacture products, what we offer customers, how we engage suppliers, how we assess risks and opportunities, and how we behave in the communities where we operate and towards one another. We also strive for excellence in health and safety performance. Technology Technology plays a key role for ABB. We have nine research centers, 6,000 scientists and 70 university collaborations across the world all working to develop unique technologies that make our customers more competitive and efficient while minimizing impact on the environment. Where to find us ABB operates in more than 100 countries and we have offices in 87 of those countries to provide the support our global and local customers need to develop and conduct their business successfully.

4 Introduction | ABB Medium Voltage Products

Introduction The one-shop service for all your medium voltage needs

With ABB, you can meet all your requirements for medium voltage products and systems from a single supplier. We have over 100 years of experience in the design, development, manufacturing and through-life service support of medium voltage switchgear, and the largest installed base of any manufacturer worldwide. Whatever your application utility, industrial, transportation or commercial we can provide the perfect, coordinated solution that delivers maximum efficiency, reliability and safety. Our comprehensive medium voltage portfolio covers switchgear, apparatus, modular packages and distribution automation. Thanks to ABBs global service network, we support our products and systems through a comprehensive range of services that ensure optimum performance throughout their life from installation and commissioning through routine maintenance, retrofit and upgrades to eventual decommissioning. Quality systems ABB operates the very highest global, national and industry-specific quality standards including ISO 9001. Our environmental management systems conform to ISO 14001 and our health and safety management system conforms to OHSAS 18001.

A wide range of applications ABBs medium voltage equipment serves a wide variety of applications throughout the world including: Utility generation Utility transmission Utility distribution Transportation Heavy industrial process plant Mining and mineral processing Light industrial parks Hospitals Product portfolio ABB offers a wide range of medium voltage products for primary and secondary distribution applications, conforming to IEC standards as well as those of the major industrialized countries, including: Circuit breakers Switch disconnectors Contactors Fixed parts and enclosures Distribution switchgear Protection relays and control systems Substation automation Electrical distribution substations A comprehensive range of accessories

ABB Medium Voltage Products | Introduction 5

Outdoor dead tank circuit breakers R-MAG magnetically actuated outdoor vacuum circuit breaker

Reduced maintenance costs 10,000 mechanical operations (five times ANSI requirements) Maintenance free magnetic actuator Eliminates need to replace motors, trip and close coils Vacuum interruption Definite purpose capacitor switching in accordance with ANSI C37.06 15.5 27 kV, up to 3700 A, 25 kA 38 kV, up to 2000 A, 31.5 kA
Technical data Rated maximum voltage Continuous current Operating temperature Voltage range factor K

R-MAG kV A 15.5 800/1250 15.5 15.5 27 1250 27 27 38 800/1250/ 800/1250/2000/ 2000 3000 1/37002 1 20 50/60 50 45 110 142 3 2 6 0.3 20 32 52 20 3 29 1 25 50/60 50 45 110 142 3 2 6 0.3 25 40 65 25 3 29 1250/2000 1250/2000 1250/2000

-50 C and 70 C per IEC 62271-1003 1 kA Hz kV kV kV kV cycles cycles sec cycles sec kA kA kA kA sec kV A A A A A 3 2 6 0.3 12.5 20 32.5 12.5 3 29 600/800/ 1250 100 600 600 600 12.5 50/60 50 45 110 142 1 12.5 50/60 60 50 125/150 194 3 2 6 0.3 12.5 20 32.5 12.5 3 51 1250 100 400 600 600 C1* A Hz 20 4240 20 4240 20 4240 20 4240 1 20 50/60 60 50 125/150 194 3 2 6 0.3 20 32 52 20 3 51 1 25 50/60 60 50 125/150 194 3 2 6 0.3 25 40 65 25 3 51 1 31.5 50/60 80 75 200 258 3 2 6 0.3 31.5 50.4 81.9 31.5 2 71.7

Short circuit interrupting current (at contact part) kA, RMS, Sym Frequency Power frequency withstand dry 60 Hz for 1 min Power frequency withstand wet 60 Hz for 10 sec Lightning impulse withstand (BIL) Chopped wave withstand (kV peak) Operating duty (standard duty cycle) Maximum interrupting time Permissible tripping delay Y Closing time Reclosing time Short circuit interrupting current (at contact part) kA, RMS, Sym Close and latch (initial current loop) kA, RMS, Asym Close and latch (kA peak) Short time current (3 sec) kA, RMS, Sym Rated duration of short-circuit @ short-time current Transient recovery voltage (kV Peak) Load current switching capability Wire line charging current Isolated cable charging current Isolated capacitor bank switching current (A RMS) Back-to-back shunt capacitor bank switching current (A RMS) Transient overvoltage factor Transient inrush current (kA peak) back-to-back Transient inrush frequency (Hz) back-to-back Grounding of system and capacitor bank system Capacitor bank Mechanical life (no load operations)
1 2 3

Exceeds ANSI standard O-0.3 sec-CO-3 min-CO

600/800/ 600/800/1250/ 1250/2000 2000/3000 100 600 600 600 100 600 600 600

1250/2000 1250/2000 1250/2000 100 400 600 600 C1* 20 4240 100 400 600 600 C1* 20 4240 100 600 600 600 C1* 20 4240

Grounded or ungrounded Grounded or ungrounded 10000 10000 10000 10000 10000

10000

10000

Up to 3000 A standard breaker. 3700 A forced air cooled breaker. Above 40C breaker derated per ANSI C37.010. * Per C37.09a restrike category. For 150 kV BIL full-wave rating only. Interrupter life rated for 30,000 operations when interrupting loads are less than 1 kA.

6 Outdoor dead tank circuit breakers | ABB Medium Voltage Products

Outdoor live tank circuit breakers OVB-SDB outdoor vacuum circuit breaker

Long life and less maintenance Available with simple spring mechanism or magnetic actuator: Spring mechanism certified for 10,000 mechanical operations Magnetic actuator rated for 10,000 mechanical operation: eliminates need to replace motors, trip and close coils Reliability and safe operation Long electrical life with proven ABB vacuum interrupters that utilize excellent arc quenching properties Simple and reliable spring mechanism ensures longer life; tested for 10,000 mechanical operations Optional magnetic actuator eliminates maintenance on operating mechanism

Availability and certifications Suitable for auto reclosing duty cycle and capacitor switching duty: type tested as per latest IEC 62271-100, M2 and C2 Class Ease of installation and commissioning with telescopic mounting structure Various accessories available to meet most applications

Technical data Rated voltage Power frequency withstand voltage Impulse withstand voltage Rated frequency Creepage distance to earth Rated normal current Rated breaking current Rated short time withstand current Rated making current First pole to clear factor Duty cycle No. of breaks per pole Weight (approx.)
Standard tested to: IEC 62271-100. * 95 kV (peak) available on request. ** Higher creepage distance available on request.

OVB-SDB 12.08.13 kV kV rms kV (peak) Hz mm A kA kA for 3 sec kA peak 12 28 75* 50 450** 800 13.1 13.1 33 1.5 O-0.3 sec CO 3 min CO/ CO 15 sec CO 1 kg 500

OVB-SDB 12.12.20 12 28 75* 50 450** 1250 20 20 50 1.5 O-0.3 sec CO 3 min CO/ CO 15 sec CO 1 500

OVB-SDB 12.20.25 15 35 95 50 450** 2000 26.3 26.3 65.75 1.5 O-0.3 sec CO 3 min CO/ CO 15 sec CO 1 500

ABB Medium Voltage Products | Outdoor live tank circuit breakers 7

Outdoor live tank circuit breakers OVB-VBF outdoor vacuum circuit breaker

Long life and less maintenance Vacuum switching for higher short circuit operations Simple spring mechanism certified for 10,000 mechanical operations Reliability and safe operation Long electrical life with proven ABB vacuum interrupters that utilize excellent arc quenching properties Simple and reliable spring mechanism ensures longer life: tested for 10,000 mechanical operations Availability and certifications Suitable for auto reclosing duty cycle and capacitor switching duty; type tested as per latest IEC 62271-100, M2 and C2 Class Ease of installation and commissioning with telescopic mounting structure Various accessories available to meet most applications

Technical data Rated voltage Power frequency withstand voltage Impulse withstand voltage Rated frequency Creepage distance to earth Rated normal current Rated breaking current Rated short time withstand current Rated making current First pole to clear factor Duty cycle No. of breaks per pole Weight (approx.)
Standard tested to IEC 62271-100. * 200 kV (peak) available on request. ** Higher creepage distance available on request.

OVB-VBF 36.20.25 kV kV rms kV (peak) Hz mm A kA kA for 3 sec kA peak 36 70 170* 50 900** 2000 26.3 26.3 65.75 1.5 O-0.3 sec CO 3 min CO/ CO 15 sec CO 1 kg 850

OVB-VBF 40.25.32 40.5 95 195* 50/60 1116 2500 31.5 31.5 82 1.5 O-0.3 sec CO 3 min CO/ CO 15 sec CO 1 900

8 Outdoor live tank circuit breakers | ABB Medium Voltage Products

Reclosers OVR-1 single-phase solid dielectric recloser

Solid dielectric recloser utilizing ABB vacuum interrupters Long life and low maintenance with 10,000 operations No electronics in pole assembly provides increased reliability and less maintenance Solid dielectric insulation with HCEP for enhanced reliability and increased life expectancy Electromechanical counter is standard ICD single phase recloser control AC powered electronic control eliminates battery maintenance Optional battery backup available Available under voltage trip/restore function reduces the effects of cold load pick-ups Zone sequence coordination Allows for seamless communication integration with SCADA, modem and radio systems

Technical data Nominal operating voltage Rated maximum voltage Rated power frequency 50/60 50/60 50/60 Hz Rated continuous current Rated symmetrical interrupting current Rated lightning impulse withstand (BIL) Dry withstand 60 Hz 1 min. Wet withstand 60 Hz 10 sec. Phase spacing External creep distance, H2-ground Minimum external strike distance Maximum interrupting time Maximum closing time Operating temperature Control voltage
Standard tested to: ANSI C37.60 2003 and IEC dual log status 62271-111.

OVR-1 kV kV Hz A kV kV kV mm (inch) mm (inch) mm (inch) sec sec C V 2.4 14.4 15.5 50/60 630/800 10 110/125 50 45 394 (15.5) 960 (38.00) 240 (9.50) 0.04 0.06 -40 + 70 (-40 F to + 158 F) 120/240 VAC 24.9 27 50/60 630/800 12 125 60 50 394 (15.5) 960 (38.00) 240 (9.50) 0.03 0.055

ABB Medium Voltage Products | Reclosers 9

Reclosers OVR-3 three-phase solid dielectric recloser

Advanced technology Solid dielectric recloser ABB vacuum interrupters and sensors embedded in each recloser pole HCEP insulation material ensures improved reliability and life expectancy Modular pole and actuator assembly allows easy removal in the field Magnetic actuator per phase allows for single phase tripping capability Reduced maintenance costs No electronics in high voltage recloser cabinet reduced maintenance costs Modular PCD control ability to replace and upgrade individual control cards without removing the relay Reliability and increased life Superior life rated for 10,000 operations Grade 304 stainless steel cabinet 3 year warranty

Technical data Nominal operating voltage Rated maximum voltage Rated power frequency 50/60 50/60 50/60 Hz Rated continuous current Rated symmetrical interrupting current Rated lightning impulse withstand (BIL) Dry withstand 60 Hz 1 min. Wet withstand 60 Hz 10 sec. Phase spacing External creep distance, H2-ground External creep distance, H1-H2 Minimum external strike distance Maximum interrupting time Maximum closing time Operating temperature Control voltage
Standard tested to: ANSI C37.60 2003 and IEC dual log status 62271-111.

OVR-3 kV kV Hz A kA kV kV kV mm (inch) mm (inch) mm (inch) mm (inch) sec sec C V 2.4-14.4 15.5 50/60 630/800/1200 12.5 110/125 50 45 394 (15.5) 960 (38) 1160 (45) 240 (9.5) 0.03 0.055 24.9 27 50/60 630/800/1200 12.5 125 60 50 394 (15.5) 960 (38) 1160 (45) 240 (9.5) 0.03 0.055 -40 70 (-40 F to 158 F) 90 265 VAC / 125 DC 34.5 38 50/60 630/800/1200 16 150/170 70 60 394 (15.5) 1288 (50.70) 1260 (49.80) 367 (14.4) 0.03 0.044

10 Reclosers | ABB Medium Voltage Products

Reclosers OVR-3SP three-phase solid dielectric recloser

Advanced technology Individual pole design allows flexible mounting arrangements Phase-over-phase/Wrap-around/Cross arm Substation replacement of small profile devices Seamless transition for replacement of three hydraulic units One PCD control operates all three recloser poles Available in rack mount design for substation mounting or in standard cabinet Solid dielectric recloser ABB vacuum interrupters and sensors embedded in each recloser pole HCEP insulation material ensures improved reliability and life expectancy Modular pole and actuator assembly allows easy removal in the field Magnetic actuator per phase allows for single phase tripping capability Reduced maintenance costs No electronics in high voltage recloser reduced maintenance costs Modular PCD control ability to replace and upgrade individual control cards without removing the relay

Reliability and increased life Superior life rated for 10,000 operations Grade 304 stainless steel control cabinet 3 year warranty

Technical data Nominal operating voltage Rated maximum voltage Rated power frequency 50/60 50/60 50/60 Hz Rated continuous current Rated symmetrical interrupting current Rated lightning impulse withstand (BIL) Dry withstand 60 Hz 1 min. Wet withstand 60 Hz 10 sec. Phase spacing External creep distance, H2-ground External creep distance, H1-H2 Minimum external strike distance Maximum interrupting time Maximum closing time Operating temperature Control voltage
Standard tested to: ANSI C37.60 2003 and IEC dual log status 62271-111.

OVR-3 kV kV Hz A kA kV kV kV mm (inch) mm (inch) mm (inch) mm (inch) sec sec C V 2.4 14.4 15.5 50/60 630/800/1200 12.5 110/125 50 45 394 (15.5) 960 (38.00) 1160 (45.00) 240 (9.50) 0.03 0.055 24.9 27 50/60 630/800/1200 12.5 125 60 50 394 (15.5) 960 (38.00) 1160 (45.00) 240 (9.50) 0.03 0.055 -40 70 (-40 F to 158 F) 90 265 VAC / 125 DC 34.5 38 50/60 630/800/1200 16 150/170 70 60 394 (15.5) 1288 (50.70) 1260 (49.80) 367 (14.4) 0.03 0.044

ABB Medium Voltage Products | Reclosers 11

Reclosers PCD control for OVR-3 and OVR-3SP three-phase solid dielectric recloser

Protection Phase and ground overcurrent protection, sensitive earth fault (SEF), directional phase and ground current protection, under overvoltage protection, frequency protection, breaker failure protection, cold load supervision. Control features Local programming from HMI; Remote control from SCADA using Modbus ASCII and RTU, DNP 3.0, IEC 60870-101 protocols Modular PCD control design allows for easy upgrades and simple, fast troubleshooting by replacing any of the six backwards compatible cards no need to replace entire control Up to 48-hour backup power during loss of source power with ability to operate on AC only without battery assistance Recloser up to 4 automatic shots Condition monitoring Monitors individual pole operations and battery condition Recloser counters for each reclose shot KSI sum for each phase: counters based on how much fault is interrupted for each recloser trip Metering Measures kW and kVARh, power factor, demand Watts and VARs, and frequency to 2% accuracy Power quality such as sag, swell

Data capture Fault summary and operations record: PCD provides a summary for the last 128 faults including tripping element, date and time, phase and neutral currents, active setting group when fault occurred and captures the last 1024 operations Load profile records: PCD has a load profile that stores historical load data such as kW on each phase, kVAR on each phase, voltages and currents on each phase, power factor Reliability improvements Single phase tripping reduces unnecessary three-phase interruptions and outages due to single-phase faults Voltage based loop control schemes to coordinate multiple reclosers to sectionalize or remove faulted sections from a distribution system Allows an OVR recloser to act as a sectionalizer, midpoint, or tie without physical connections to other reclosers Remote communication capability licensed and unlicensed radios, Web IP radios, GSM/Cellular and digital packet data

12 Reclosers | ABB Medium Voltage Products

Pole mounted circuit breaker PVB pole mounted vacuum circuit breaker

Solid dielectric breaker ABB vacuum interrupters embedded in each pole HCEP insulation material ensures improved reliability and life expectancy Long creepage distance (392 mm) suitable for highly polluted environments Spring operating mechanism with anti-pumping function modular design and maintenance free Reflective position and charge indicators are easily visible from ground, even at night Easily upgraded from manual operated to motor operated and remote control Mounting flexibility various mounting brackets are available for customer application requirements Superior life rated for 10,000 operations Three options of protection and control unit MFC: Provides overcurrent protection, no extra power required REF615: Provides overcurrent protection and earth fault protection, with optional recloser function PCD: Provides full protection for current and voltage faults, with advanced measurement, recloser and communication

Technical data Nominal operating voltage Rated maximum voltage Rated power frequency Rated continuous current Rated symmetrical interrupting current Rated lightning impulse withstand (BIL) Dry withstand 50/60 Hz 1 min. Wet withstand 50/60 Hz 10 sec. Phase spacing External creep distance, H2-ground External creep distance, H1-H2 Minimum external strike distance Rated standard operating duty Maximum interrupting time Maximum closing time Operating temperature Control voltage
Standard tested to: GB 1984-2003 and IEC 62271-100. * For motor operation.

PVB kV kV Hz A kA kV kV kV mm (inch) mm (inch) mm (inch) mm (inch) sec sec C V 10 12 50/60 630 20 75 42 34 280 (11.02) 392 (15.43) 392 (15.43) 230 (9.05) O 0.3s C O 15s C O* 0.08 0.08 -40 (-25 if motor operated) to +40 110 220 VAC / 24 220 VDC

ABB Medium Voltage Products | Pole mounted circuit breaker 13

Outdoor three-phase air switches NPS modular outdoor switch disconnectors

Modular and flexible design adapts to various pole types for mounting Robust, light weight makes installation easier and safer Wide range of accessories for various applications Easy to upgrade from manual switch to remote controlled/ automated switch Simple design provides reliable operation

Technical data Rated maximum voltage Rated frequency Rated continuous current Rated short time withstand current (1 sec) Rated short time withstand current (3 sec) Rated peak withstand current Rated short circuit making current Mainly active load breaking current with standard whip (at 12/24/36kV) with chamber K4 fitted (at 24kV) with chamber K5 fitted (at 24 kv) kV Hz A kA kA kA kA A A A kV kV kV mm (inch) mm (inch) C V 24 50/60 630 16 10 40 5 251 250 630 125 75 55 Epoxy 740 (29.10)2 200 (7.90) -50+40 24 50/60 630 16 10 40 5 251 630 125 75 55 Silicon 715 (28.15)3 255 (10.00) -40+40 24 50/60 630 20 16 50 5 251 630 125 75 55 Silicon 760 (29.90)3 260 (10.20) -40+40 REC523 or REC5014 36 50/60 630 21 16 52 7.5 16 200 88 80 Silicon 1205 (47.41)3 380 (14.95) -40+40 36 50/60 630 21 16 52 7.5 16 200 88 80 Silicon 1365 (53.70)3 385 (15.15) -40+40

Rated lightning impulse withstand (BIL) Rated power frequency across the isolating distance withstand voltage, wet to earth and between phases Insulators Creepage distance to earth Arcing distance Ambient temperature limits Control voltage for motor drive (if fitted) Standard type of control unit used in motor drives
Standard tested to: IEC 60694 , 60129, 60265-1. 1) 40 A for 12 kV. 2) Epoxy insulators version. 3) Silicon insulators version. 4) For the details about REC523 control unit used in motor drives see page 17.

24, 48, 110, 220 VDC 110, 230 VAC

1 NPS cabinet | 2 GridGuard TM cabinet (page 15) 1 2

14 Outdoor three-phase air switches | ABB Medium Voltage Products

Outdoor three-phase air switches GridGuard three-phase outdoor air switch

Robust construction Resilient, higher BIL silicone rubber insulators (porcelain available) Steel phase base construction (") meets Federal Specification BR-C-271 Reverse loop silver plated copper jaw contacts All ferrous components are hot dip galvanized Tinned copper terminal pads Standard quality features include " phase base boxframe construction, 3/8" dead-end connectors, stainless steel brass bearing rotating shafts, silver-plated copper reverse loop contacts and busbar grade copper blades that contribute to an extended life, even in harsh environments Reliable design Looped contact design improves contact integrity Interrupter contact operating speed is independent of switch operating speed, ensuring full loadbreak capability All copper construction is grade C110, providing high conductivity and strength Self-resetting interrupter Advanced shunt design eliminates contact pitting Unitized construction: aluminium, steel, or fibre glass Visible break allows for safe operation and maintenance Maintenance-free stainless steel and brass bearing mechanism RUS approved Application Line switching: load splitting (parallel or loop switching), load dropping, and associated charging currents Transformer switching: load dropping, including associated magnetizing currents Cable switching: load switching (parallel or loop switching), load dropping, and associated charging currents

Technical data Nominal voltage 14.4 21 34.5 kV Maximum voltage 17 29 38 BIL 110 150 200 Continuous current kV kV

15 kV 14.4 17 110

27 kV 21 29 150 600 A (ANSI), 900 A (IEEE)* 900 A (ANSI) 1200 A (ANSI)**

38 kV 34.5 38 200

15 kA rms-asym: 5 x manual operation Fault close 20 kA rms-asym: 3 x manual operation 30 kA rms-asym: 2 x manual operation 600 A: 40,000 A-rms 10 cycles/25,000 A-rms 3 sec Momentary current 900 A: 51,000 A-rms 10 cycles/32,000 A-rms 3 sec 1200 A: 70,000 A-rms 10 cycles/44,000 A-rms 3 sec Insulator type Interrupter type Crossarm type Silicone Porcelain Expulsion tube: 2,500 open and close operations Vacuum bottle: 5,000 open and close operations Galvanized steel: 2,000 lbs/phase Fibreglass: 1,000 lbs/phase Horizontal (upright, extra clearance, or underarm) Mounting configurations Vertical (phase over phase) Riser (vertical) Delta (pole top) Hookstick Control mechanism Reciprocating control rod Torsional control rod Motor operator
*Ice breaking " (manual operation). **Mechanical Tested up to 5,000 cycles (open/close).

ABB Medium Voltage Products | Outdoor three-phase air switches 15

Outdoor three-phase load break switches SECTOS 24kV NXB and NXBD SF6 load break switch

Full options for sectionalizer: current and voltage based logic ABB patent spiral spring operation mechanism with clear indication Reliable, stable gas density switch and gauge with temperature compensation Gas-low locking device/manual locking device as options Completely sealed stainless steel tank Easily upgraded from manual operated to motor operated and remote control Safe, compact design Sensor solution with wide dynamic range Integrated earthing switch for increased safety during maintenance NXBD is a 3-way switch with 1 input + 2 outputs or 2 inputs + 1 output: useful for the loop power supply

Technical data Nominal operating voltage Power frequency withstand voltage, 50 Hz Lightning impulse withstand voltage Rated power frequency Rated normal current Mainly active load breaking current Number of breaking operations CO Line-charging breaking current Cable-charging breaking current Earth fault breaking current Cable-charging breaking current under earth fault conditions No-load transformer breaking current Short-time withstand current (4 sec) Peak withstand current Short-circuit making current main switch 50 kA (CL E2) Number of making operations CO Creepage distance Operating temperature Mechanical endurance (no. of close-open operation) Filling pressure (+20 Celsius) Alarm pressure (+20 Celsius) Weight
Standard tested to: ANSI C37.63 and 37.71 and IEC 60129, IEC 60265-1 and IEC 60694.

SECTOS NXB and NXBD kV to earth and between phases across the isolating distance to earth and between phases across the isolating distance kV kV kV kV Hz A A n A A A A A kA kA kA n n n n mm C main switch earthing switch density switch density gauge low gas lock-out mechanism n n bar (abs) bar (abs) bar (abs) bar (abs) kg 82 main switch 31.5 kA (CL E3) earthing switch 50 kA (CL E2) earthing switch 31.5 kA (CL E3) 12 28 32 75 85 50/60 630 630 100 50 50 50 28 6.3 20 50 50 5 10 3 5 620 -40 +60 5000 2000 1.5 1.2 1.2 1.1 141 24 65 79 125 145

16 Outdoor three-phase load break switches | ABB Medium Voltage Products

Outdoor three-phase load break switches SECTOS 24kV NXB and NXBD SF6 load break switch

REC 523 control features Remote monitoring and control from SCADA using SPA, LON, IEC870-101, Modbus and DNP 3.0 protocols with one RS-485, two RS-232 serial and fibre optic communication ports Provides 15 digital inputs and 9 digital outputs including two power outputs 9 analog inputs 9 sensors CTs and VTs 12V DC for powering communication devices 21 freely configurable LEDs Reclosing functionality Metering Phase currents and phase to phase voltages Residual current and voltage Active and reactive power Active and reactive energy Demand values of current and power Frequency Power factor Harmonics Disturbance and event recording Condition monitoring Control circuit supervision Circuit breaker/disconnector condition monitoring SF6 pressure of primary equipment Battery condition monitoring Battery deep discharge protection Operations counter for primary equipment Internal self-supervision of the unit

Protection and fault indication capabilities Directional earth-fault protection; two stages (low-set and high-set) Three-phase directional overcurrent protection, two stages (low-set and high-set) Three-phase transformer inrush and motor startup current detector Non-directional earth-fault protection; two stages (low-set and high-set) Three-phase non-directional overcurrent protection, two stages (low-set and high-set) Three-phase under voltage protection; two stages (low-set and high-set) Circuit breaker failure protection

ABB Medium Voltage Products | Outdoor three-phase load break switches 17

Outdoor three-phase load break switches SECTOS 36kV NXA SF6 load break switch

Full options for sectionalizer: current and voltage based logic ABB patent spiral spring operation mechanism with clear indication Reliable, stable gas density switch and gauge with temperature compensation Gas-low locking device/manual locking device as options Completely sealed stainless steel tank Easily upgraded from manual operated to motor operated and remote control

Technical data Nominal operating voltage Power frequency withstand voltage, 50 Hz to earth and between phases Power frequency withstand voltage, 50 Hz across the isolating distance Lightning impulse withstand voltage to earth and between phases Lightning impulse withstand voltage across the isolating distance Rated power frequency Rated normal current Mainly active load breaking current Number of breaking operations CO Line-charging breaking current Cable-charging breaking current Earth fault breaking current Cable-charging breaking current under earth fault conditions No-load transformer breaking current Short-time withstand current (3 sec) Peak withstand current Short-circuit making current Number of making operations CO main switch 31,5 kA (CL E3) Creepage distance Operating temperature Mechanical endurance (number of close-open operation) main switch Filling pressure (+20 Celsius) Alarm pressure (+20 Celsius) density switch Alarm pressure (+20 Celsius) density gauge Alarm pressure (+20 Celsius) low gas lock-out mechanism Weight
Standard tested to: ANSI C37.63 and 37.71 and IEC 60129, IEC 60265-1 and IEC 60694.

NXA kV kV kV kV kV Hz A A n A A A A A kA kA kA n mm celsius n bar (abs) bar (abs) bar (abs) bar (abs) kg 36 70 80 170 195 50/60 630 630/400 50/400 40 40 175 80 20 12.5 31.5 31.5 5 960/1440 -40 +60 5000 1.5 1.2 1.2 1.1 117

18 Outdoor three-phase load break switches | ABB Medium Voltage Products

Outdoor three-phase load break switches SECTOS 36kV NXA SF6 load break switch

REC 523 control features: Remote monitoring and control from SCADA using SPA, LON, IEC870-101, Modbus and DNP 3.0 protocols with one RS-485 and two RS-232 serial communication ports Provides 15 digital inputs and 9 digital outputs including two power outputs 12V DC for powering communication devices 21 freely configurable LEDs Reclosing functionality Metering Phase currents and phase to phase voltages Residual current and voltage Active and reactive power Active and reactive energy Demand values of current and power Frequency Power factor Harmonics Disturbance and event recording Condition monitoring Control circuit supervision Circuit breaker/disconnector condition monitoring SF6 pressure of primary equipment Battery condition monitoring Battery deep discharge protection Operations counter for primary equipment Internal self-supervision of the unit Protection and fault indication capabilities Directional earth-fault protection; two stages (low-set and high-set) Three-phase directional overcurrent protection, two stages (low-set and high-set) Three-phase transformer inrush and motor startup current detector Non-directional earth-fault protection; two stages (low-set and high-set) Three-phase non-directional overcurrent protection, two stages (low-set and high-set) Three-phase under voltage protection; two stages (low-set and high-set) Circuit breaker failure protection

ABB Medium Voltage Products | Outdoor three-phase load break switches 19

Electronic sectionalizers AutoLink single-phase electronic sectionalizer

Prevents temporary faults from causing outages Reduces replacement of fuses Coordinates perfectly with reclosers, reducing operating costs and improving system reliability Minimizes inventory as only one model is needed per voltage rating Fits on an interchangeable type cutout body Field resettable as many times as needed between 6 and 215 A, and from 1 to 4 counts Detects and discriminates inrush current Trip arm is reset with no tools required Does not require any power sources

Technical data Model Rated voltage Insulation level (BIL) Insulator material Rated frequency Nominal current Actuating current Number of counts before operation Short time current, 1 sec (effective) Asymmetrical initial (peak) Dead line detection Maximum memory time with dead line Memory reset
Standard tested to: ANSI (IEEE) C37.63.

Single-phase AutoLink AL11 kV kV Hz A A kA kA mA min sec 15 110 Silicone/porcelain 50/60 200 6 215 14 4 10 < 200 3.5 30 AL12 27 125 Silicone/porcelain 50/60 200 6 215 14 4 10 < 200 3.5 30 AL14/15 27/33 150 Silicone/porcelain 50/60 200 6 215 14 4 10 < 200 3.5 30 AL17 38 170 Porcelain 50/60 200 6 215 14 4 10 < 200 3.5 30

20 Electronic sectionalizers | ABB Medium Voltage Products

Electronic sectionalizers AutoLink three-phase electronic sectionalizer

Prevents temporary faults from causing outages Automatic three-phase opening for overhead line isolation and protection One simple pole mounting arrangement Field resettable as many times as needed between 6 and 215 A, and from 1 to 4 counts Visible isolation on the lines High level of operating safety Maintenance-free Does not require any power sources

Technical data Model Rated voltage Insulation level (BIL) Insulator material Rated frequency Nominal current Actuating current Number of counts before operation Short time current, 1 sec (effective) Asymmetrical initial (peak) Dead line detection Maximum memory time with dead line Memory reset
Standard tested to: ANSI (IEEE) C37.63.

Three-phase AutoLink AL32 kV kV Hz A A kA kA mA min sec 27 125 Porcelain 50/60 200 6 215 14 4 10 < 200 3.5 30 AL34 27 150 Porcelain 50/60 200 6 215 14 4 10 < 200 3.5 30

ABB Medium Voltage Products | Electronic sectionalizers 21

Electronic sectionalizers AutoLink loadbreak electronic sectionalizer

Improves network reliability Isolates temporary faults preventing extended outages Reduces replacement of fuses Reduces operating costs Field configurable as many times as needed between 6 and 215 A, and from 1 to 4 counts Detects inrush current Does not require hookstick with loadbreak accessory Does not require an auxiliary power source

Technical data Model Rated voltage Insulation level (BIL) Insulator material Rated frequency Nominal current Manual opening current Actuating current Number of counts before operation Short time current, 1 sec (effective) Asymmetrical initial (peak) Dead line detection Maximum memory time with dead line Memory reset kA rms kA mA min sec Hz A A A kV kV AL41 15 110 Porcelain/silicone 50/60 200 200 6 215 14 4 10 < 200 3,5 30

Loadbreak AutoLink AL42 15/27 125 Silicone 50/60 200 200 6 215 14 4 10 < 200 3,5 30 AL44 15/27 150 Porcelain 50/60 200 200 6 215 14 4 10 < 200 3,5 30

Standard tested to: ANSI (IEEE) C37.63. The 15/27 kV version is applicable on systems of up to 15 kV phase-phase or 27kV phase-earth.

22 Electronic sectionalizers | ABB Medium Voltage Products

Single-phase switches DCD single-phase disconnect switch

Double insulator single-phase disconnect switch 15 kV 38 kV, 600 or 900 A continuous loads with a 40 kA momentary rating Loadbreak tool-operated switch used for sectionalizing or isolating equipment on electrical distribution systems up to 38 kV Can be mounted vertically or underhung, or on a single or double crossarm Porcelain or silicone rubber insulator (110 150 kV BIL) 90 or 160 blade stop available Mounting kit available

Technical data Voltage class BIL Porcelain creep Silicone creep Porcelain strike Silicone strike Continuous current Peak withstand current Silicone weight Porcelain weight kA Asym lb [kg] lb [kg] kV kV mm (inch) mm (inch) mm (inch) mm (inch) 15 110 441 (17.6) 496 (19.53) 196 (7.71) 198 (7.79) 600/900 65 21 (900 A) [9.5] 40 (600 A) [18]

DCD 27 125 583 (22.95) 719 (28.3) 217 (8.55) 234 (9.26) 600/900 65 23 (600 A) [10] 42 (600 A) [19] 38 150 606 (23.87) 1003 (39.52) 249 (9.81) 270 (10.62) 600/900 65 26 (900 A) [12] 44 (600 A) [20]

All testing is in accordance with IEEE C37.34.

ABB Medium Voltage Products | Single-phase switches 23

Single-phase switches SID single-phase disconnect switch

Single insulator disconnect with a double blade door and two 2-hole extended NEMA pad terminals 15 kV 38 kV, 600 or 900 A continuous load with a 40 kA momentary rating Single-phase disconnect on overhead distribution feeders and in outdoor distribution substations Can be mounted like a standard cutout Porcelain, polymer concrete, or silicone rubber insulator (110 170 kV BIL) Mounting kit available 90 or 160 blade stop available

Technical data Voltage class BIL Porcelain creep Silicone creep Polymer concrete creep Momentary withstand current Continuous current Silicone weight Porcelain weight Polymer concrete weight
All testing is in accordance with IEEE C37.34.

SID kV kV mm (inch) mm (inch) mm (inch) kA Asym 600 lb [kg] lb [kg] lb [kg] 10.9 [4.9] 14.7 [6.7] 14.1 [6.4] 15.5 110 231 (9.1) 380 (15) 231 (9.1) 40 900 12 [5.4] 15.6 [7.1] 15 [6.8] 600 13.1 [5.9] 18.4 [8.3] 17.6 [8.0] 27 125 325 (12.8) 480 (18.9) 325 (12.8) 40 900 14 [6.4] 19.3 [8.8] 18.5 [8.4] 600 19.9 [9.0] 25.2 [11.4] 40 900 20.8 [9.4] 26.1 [11.8] 38 150 432 (17) 600 (23.6)

24 Single-phase switches | ABB Medium Voltage Products

Single-phase switches LSID single-phase load break disconnect switch

Loadbreak single insulator disconnect with self-contained loadbreak capabilities, a double blade door, and two 2-hole NEMA pad terminals 15.5 kV 15/27 kV, 600 A continuous and loadbreak with a 40 kA momentary rating Single-phase disconnect on overhead distribution feeders and in outdoor distribution substations Self-contained loadbreak enables utility personnel to interrupt load current with a hookstick Can be mounted like a standard cutout Porcelain, polymer concrete, or silicone rubber insulator (110 170 kV BIL) Mounting kit available 90 or 160 blade stop available

Technical data Voltage class BIL Porcelain creep Silicone creep Polymer concrete creep Momentary withstand current Continuous current Silicone weight Porcelain weight Polymer concrete weight
All testing is in accordance with IEEE C37.34.

LSID kV kV mm (inch) mm (inch) mm (inch) kA Asym 600 lb [kg] lb [kg] lb [kg] 12.8 [5.8] 16.7 [7.6] 15.8 [7.2] 15.5 110 231 (9.1) 380 (15) 231 (9.1) 40 900 13.7 [6.2] 17.6 [8.0] 16.7 [7.6] 600 15.1 [6.8] 20.4 [9.3] 19.6 [8.9] 125 325 (12.8) 480 (18.9) 325 (12.8) 40 900 16 [7.3] 21.3 [9.7] 20.5 [9.3] 600 21.9 [9.9] 27.2 [12.3] 15/27 150 432 (17) 600 (23.6) 40 900 22.8 [10.3] 28.1 [12.7]

ABB Medium Voltage Products | Single-phase switches 25

Single-phase switches RBD single phase bypass disconnect switch

Single-phase bypass disconnect switch 15 kV 38 kV, 600 or 900 A continuous loads with a 40 kA momentary rating Provides a means for bypassing and disconnecting reclosers or voltage regulators, allowing maintenance on equipment without service interruption Can be mounted in the following configurations: vertical or underhung, pole-mounted, or single or double crossarm Porcelain or silicone rubber insulator (110 150 kV BIL) 90 or 160 blade stop available Mounting kit available

Technical data Voltage class BIL Porcelain creep Silicone creep Porcelain strike Silicone strike Continuous current Peak withstand current Silicone weight Porcelain weight
All testing is in accordance with IEEE C37.34.

RBD kV kV mm (inch) mm (inch) mm (inch) mm (inch) kA Asym lb [kg] lb [kg] 15 110 441 (17.6) 496 (19.53) 196 (7.71) 198 (7.79) 600/900 65 54 [24] 91 [41] 27 125 583 (22.95) 719 (28.3) 217 (8.55) 234 (9.26) 600/900 65 55 [25] 99 [45] 38 150 606 (23.87) 1003 (39.52) 249 (9.81) 270 (10.62) 600/900 65 57 [26] 103 [47]

26 Single-phase switches | ABB Medium Voltage Products

Single-phase switches ITD Inline tension disconnect switch

Single-phase, non-loadbreak, inline tension disconnect switch with silicone insulator Maximum voltage ratings: 15 kV (150 kV BIL), 27 kV (150 kV BIL), or 38 kV (200 kV BIL) Continuous current rating of 600 A or 900 A Used for manual switching of parallel or de-energized circuits on overhead distribution lines rated 15-38 kV Loadbreak hooks allow for operation with a portable loadbreak tool 90 or 160 blade stop available

Technical data Voltage class BIL Silicone creep Continuous current Peak withstand current Silicone weight
All testing is in accordance with IEEE C37.34.

ITD kV kV mm (inch) kA Asym lb [kg] 15 and 27 150 590 (23.23) 600/900 65 11 [5] 27 and 38 200 991 (39) 600/900 65 14 [6]

ABB Medium Voltage Products | Single-phase switches 27

Fuse cutouts ICX interchangeable fuse cutout

Distribution cutout for use on overhead distribution system to provide overcurrent protection Fusetube interchangeable with S&C type XS, Cooper Type L, and AB Chance type C cutouts 15 kV 38 kV, up to 16 kAIC Provides visible indication of fuse operation and a visible break sectionalizing point for maintenance personnel Can function as a loadbreak switch when used in conjunction with a portable loadbreak tool Porcelain, silicone rubber (110 170 kV BIL), or polymer concrete insulator (110 and 125 kV BIL) Stainless steel seacoast design Cutout/arrester combination 100 and 200 A fuse available 300 A disconnect blade Kickout spring (100 A only)

Technical data Voltage class Maximum BIL Continuous current Maximum interrupting rating (disconnect blade) Porcelain creep Silicone creep Porcelain weight Silicone weight
All testing is in accordance with IEEE C37.41.

ICX kV kV A kA mm (inch) mm (inch) lbs [kg] lbs [kg] 15 110 100 A/200 A/300 A 16/12 231 (9.1) 380 (14.96) 14 [6.4] 9.3 [4.2] 27 150 100 A/200 A/300 A 8/12 432 (17.0) 480 (18.90) 26.5 [12] 10.2 [4.6] 38 170 100 A/300 A 10 665 (26.2) n/a 35.5 [16.1] n/a

28 Fuse cutouts | ABB Medium Voltage Products

Fuse cutouts NCX fuse cutout

Distribution cutout for overcurrent protection on overhead distribution systems 15 kV 38 kV, up to 20 kAIC Provides visible indication of fuse operation and a visible break sectionalizing point for maintenance personnel Can function as a loadbreak switch when used in conjunction with a portable loadbreak tool Porcelain, silicone rubber (110 150 kV BIL), or polymer concrete insulator (110 and 125 kV BIL) Cutout/arrester combination 100 and 200 A fuse available 300 A disconnect blade

Technical data Voltage class Maximum BIL Continuous current Maximum interrupting rating (disconnect blade) Porcelain creep Silicone creep Porcelain weight Silicone weight
All testing is in accordance with IEEE C37.41.

NCX kV kV kA mm (inch) mm (inch) lbs [kg] lbs [kg] 7.8/15 110 12/20 231 (9.1) 380 (14.96) 13.1[5.91] 10.1 [4.60] 15 110 16/12 231 (9.1) 380 (14.96) 13.1[5.91] 10.1 [4.60] 15/27 125 16/10 325 (12.8) 480 (18.90) 16.5 [7.5] 11.1 [5.03] 20/34.5 150 100 A/300 A 12 432 (17.0) 480 (18.90) 24.3 [11.00] 11.1 [5.03] 27 150 100 A/300 A 12 432 (17.0) 480 (18.90) 24.3 [11.00] 11.1 [5.03]

A 100 A/200 A/300 A 100 A/200 A/300 A 100 A/200 A/300 A

ABB Medium Voltage Products | Fuse cutouts 29

Fuse cutouts LBU-II loadbreak fuse cutout

Distribution cutout for use on overhead distribution system to provide overcurrent protection Loadbreak interruption is accomplished by means of a selfcontained loadbreak arc chute, which confines the arc and provides a deionizing action 15, 27, or 20/34.5 kV, up to 20 kAIC Provides overcurrent protection for capacitor banks and gives visible indication that the equipment is energized Used for switching the magnetizing currents of single and three-phase transformer banks and switching capacitive currents associated with underground feeder cable at the riser pole Porcelain, silicone rubber (110 150 kV BIL), or polymer concrete insulator (110 and 125 kV BIL) Cutout/arrester combination 100 and 200 A fuse available 300 A disconnect blade

Technical data Voltage class Maximum BIL Continuous current Maximum interrupting rating (disconnect blade) Porcelain creep Silicone creep Porcelain weight Silicone weight
All testing is in accordance with IEEE C37.41.

LBU-II kV kV kA mm (inch) mm (inch) lbs [kg] lbs [kg] 7.8/15 110 12/20 231 (9.1) 380 (14.96) 13.1[5.91] 10.1 [4.60] 15 110 16/12 231 (9.1) 380 (14.96) 13.1[5.91] 10.1 [4.60] 15/27 125 16/10 325 (12.8) 480 (18.90) 16.5 [7.5] 11.1 [5.03] 20/34.5 150 100 A/300 A 12 432 (17.0) 480 (18.90) 24.3 [11.00] 11.1 [5.03] 27 150 100 A/300 A 12 432 (17.0) 480 (18.90) 24.3 [11.00] 11.1 [5.03]

A 100 A/200 A/300 A 100 A/200 A/300 A 100 A/200 A/300 A

30 Fuse cutouts | ABB Medium Voltage Products

Instrument transformers Outdoor ANSI medium voltage instrument transformers

Encapsulated in hydrophobic cycloaliphatic epoxy (HCEP) Current and voltage instrument transformers, 46 kV through 52 kV Reduced contamination-related leakage currents Reduced probability of flashover Improved water beading and runoff Improved life expectancy due to reduced insulation Improved quality and system reliability Increased creep distance Improved performance in cold climates (-50C) High accuracy/extended range offering 15 through 34.5 kV 0.15 accuracy to 1% 200:5 and 1000:5 ratios with rating factor of 1.5 Exceeds IEEE C57.13.6 improved accuracy standards

Technical data Insulation voltage Impulse withstand voltage Rated frequency Rated primary Dynamic resistance Thermal resistance Rating factor Accuracy/burden class
*Higher accuracies available - 48/52 kV units available in HCEP or CEP (cycloaliphatic epoxy) material - 69 kV units available in CEP material only - CEP units available in US and Canada markets only

Outdoor MV current transformers kV kV Hz 5 69 60 350 50 60 5 5000 A 180 x rated current 80 x rated current x 1s 1.0 up to 3.0 0.3B 1.8*

Outdoor MV voltage transformers 5 69 60 350 50 60 2400 46000 V up to 3000 VA 0.3W 0.3ZZ and 0.15Y

1 VOZZ 25 | 2 VOZZ 25G | 3 KOTD 250 1 2 3

ABB Medium Voltage Products | Instrument transformers 31

Instrument transformers Outdoor IEC medium voltage instrument transformers

IEC product portfolio is encapsulated in hydrophobic cycloaliphatic epoxy (HCEP) ensuring correct operation in heavily polluted conditions. Reduced contamination-related leakage currents Reduced probability of flashover Improved water beading and runoff Improved life expectancy Improved quality and system reliability Improved performance in cold climate Our product offering Multi-core current transformers Single pole (line ground) insulated voltage transformers Double pole (line line) insulated voltage transformers Current transformer for NPS three-phase outdoor switch disconnector

Technical data Insulation voltage Impulse withstand voltage Rated frequency Rated primary Dynamic resistance Thermal resistance Rating factor Burden class kA kV kV Hz

Outdoor medium voltage current transformers 7.2 40.5 60 200 50 60 10 2500 A up to 125 up to 50kA/1s as per IEC as per IEC

Outdoor medium voltage transformers 7.2 40.5 60 200 50 60 10 000/3 35 000/3 10 000 22 000 V 750 VA 1.9 for 8h as per IEC

1 TDO | 2 TJO | 3 TPO 1 2 3

32 Instrument transformers | ABB Medium Voltage Products

Service Reliable, trouble-free and efficient operation

ABB ensures that customers enjoy reliable, trouble-free and efficient operation over a full service life. Diagnosis Inspection and analysis to improve operating efficiencies and extend asset life. Environmental services Plant, equipment, PCB disposal, pollution prevention/control, waste minimization. Installation and commissioning Cold and hot commissioning including protection and control systems. Migration and upgrades Services and products to evolve or upgrade to the next generation of hardware and software. Retrofit Exchange of worn parts or outdated components while maintaining original configuration. Support and remote services On demand expert support for ABB equipment using telephone consultations, online knowledge management and remote equipment monitoring services.

Engineering and consulting Identify opportunities and implementing solutions to improve performance, processes and compliance. Extension Expansions and extensions to installed systems by adding new equipment or functionality. Maintenance and field services Preventative, predictive and corrective services to maximize the performance, reliability and availability of equipment. Repair and refurbish Factory approved repair, partial or complete reconditioning of products or systems. Spare parts Spare parts, emergency support, repair and exchange, inventory management and logistics solutions. Training Training for personnel including supervisors, engineers, technicians, operators, programmers, maintenance personnel on all aspects of ABB products, systems, processes and technology.

ABBs wide range of world class medium voltage outdoor apparatus products come with unrivalled service support that covers every requirement from installation and commissioning to through-life preventive and corrective maintenance.

ABB Medium Voltage Products | Service 33

34 ABB Medium Voltage Products

ABBs Medium Voltage Products business unit provides utility, industrial and commercial customers with safe, reliable and smart technologies for the distribution of electricity. The extensive global offering includes distribution automation products, switching, limiting, measuring and sensing devices, switchgear, modular substation packages and related services.

ABB Medium Voltage Products 35

Contact us

More product information: www.abb.com/productguide

No part of this publication may be reproduced or transmitted in any form or by means, electronic, mechanical, photocopying, recording or otherwise without prior written permission of ABB. Copyright 2011 ABB. All rights reserved.

Document ID 2NAA000019 ABB Medium Voltage Products. General product cataloge. 01.2011

Your sales contact: www.abb.com/contacts

The data and illustrations are not binding. We reserve the right to modify the contents of this document on the basis of technical development of the products, without prior notice.

You might also like