Job Name Job Location Engineer Approval Contractor Approval Contractors P.O. No. Representative

LEAD FREE* Series LF757DCDA, LF757NDCDA


Sizes: 21/2" 10"

Double Check Detector Assemblies


Series LF757DCDA, LF757NDCDA Double Check Detector Assemblies are used to prevent backflow of non-health hazard pollutants that are objectionable but not toxic, from entering the potable water supply system. The LF757DCDA, LF757NDCDA may be installed under continuous pressure service and may be subjected to backpressure and backsiphonage. Series LF757DCDA, LF757NDCDA is used primarily on fire line sprinkler systems when it is necessary to monitor unauthorized use of water.

LF757DCDAOSY

Features
Lead Free* construction Extremely compact design 70% lighter than traditional designs 304 (Schedule 40) stainless steel housing & sleeve Groove fittings allow integral pipeline adjustment Unique tri-link spring check provides lowest pressure loss Unmatched ease of serviceability Available with grooved butterfly valve shutoffs May be used for horizontal, vertical or N pattern installations Replaceable check disc rubber

LF757DCDABFG

Specifications
The Lead Free* Double Check Detector Assembly shall consist of two independent tri-link check modules within a single housing, sleeve access port, four test cocks and two drip tight shutoff valves. Tri-link checks shall be removable and serviceable, without the use of special tools. The housing shall be constructed of 304 Schedule 40 stainless steel pipe with groove end connections. Tri-link checks shall have reversible elastomer discs and in operation shall produce drip tight closure against reverse flow caused by backpressure or backsiphonage. The bypass assembly shall consist of a meter, which registers in either gallon or cubic measurement, a double check backflow assembly and required test cocks. Assembly shall be a Watts Series LF757DCDA, LF757NDCDA.

LF757NDCDAOSY

*The wetted surface of this product contacted by consumable water contains less than 0.25% of lead by weight.

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold.

Available Models
Suffix: OSY BFG UL/FM outside stem and yoke resilient seated gate valves UL/FM grooved gear operated butterfly valves with tamper switch

Materials
Housing & Sleeve: 304 (Schedule 40) Stainless Steel Elastomers: EPDM, Silicone and Buna-N Tri-link Checks: Noryl, Stainless Steel Check Discs: Reversible Silicone or EPDM Test Cocks: Lead Free* Bronze Body Nickel Plated Pins & Fasteners: 300 Series Stainless Steel Springs: Stainless Steel

**OSY FxG  Flanged inlet gate connection and grooved outlet gate connection **OSY GxF  Grooved inlet gate connection and flanged outlet gate connection **OSY GxG  Grooved inlet gate connection and grooved outlet gate connection Available with grooved NRS gate valves - consult factory** Post indicator plate and operating nut available - consult factory** **Consult factory for dimensions

Pressure Temperature
Temperature Range: 33F 140F (0.5C 60C) Maximum Working Pressure: 175psi (12.1 bar)

Approvals

Dimensions Weight
1048 B64.5 (BFG & OSY only)

C (open)

J I

D A

H G P

LF757DCDA , LF757NDCDA
Size A in. in. mm C (OSY) in. mm D in. mm in. G mm in. dimensions H mm in. I mm in. J mm in. P mm weight LF757DCDA lbs. kgs. LF757NDCDA lbs. kgs.

212 3 4 6 8 10

3012 3138 3312 44 50 5612

775 797 851 1118 1270 1435

1638 1878 2234 3018 3734 4534

416 479 578 765 959 1162

312 31116 4 512 61116 8316

89 94 102 140 170 208

29116 3014 33 4434 5418 66

738 768 838 1137 1375 1676

2112 2214 2312 3334 4058 50

546 565 597 857 1032 1270

1512 1718 1812 23316 27716 3212

393 435 470 589 697 826

81316 9316 91516 13116 151116 17516

223 233 252 332 399 440

13316 1412 15316 19 21316 24

335 368 386 483 538 610

139 159 175 309 494 795

63 72 79 140 224 361

147 172 198 350 569 965

67 78 90 159 258 438

C D A H G
dimensions A C D G H I J

LF757DCDABFG , LF757NDCDABFG
Size

WEIGHT P LF757DCDABFG LF757NDCDA BFG

in. 212 3 4 6 8

in. 2712 28 2834 37 4312

mm 698 711 730 940 1105

in. 8 8516 81516 10 1214

mm 203 211 227 254 311

in. 312 31116 31116 5 612

mm 89 94 94 127 165

in. 2978 301116 311516 43316 51116

mm 759 779 811 1097 1297

in. 2112 2214 2312 3334 4058

mm 546 565 597 857 1032

in. 141516 15716 1614 191116 23516

mm 379 392 412 500 592

in. 81316 9316 91516 13116 151116

mm 223 233 252 332 399

in. 13 1312 14 1412 18316

mm 330 343 356 368 462

lbs. 70 68 75 131 275

kgs. 32 31 34 59 125

lbs. 78 81 98 171 351

kgs. 35 37 44 78 159

Noryl is a registered trademark of General Electric Company.

Capacity
Series LF757DCDA flow curves as tested by Underwriters Laboratory per UL 1469, 1996. Flow characteristics collected using butterfly shutoff valves

* = Rated flow ** = UL Rated flow Horizontal Vertical N - Pattern

Pa k 96 83 69 55 41 28 14 0

psi 14 12 10 8 6 4 2 0

212"

**
N V H

0 50 100 150 200 250 300 350 gpm 0 190 380 570 760 950 1140 1330 lpm 15 fps 4.6 mps

Pa psi k 83 12 69 10 55 8 41 6 28 4 14 2 0 0

6"

**N

H V

0 300 600 900 1200 1500 gpm 0 1140 2280 3420 4560 5700 lpm 15 fps 4.6 mps

Pa psi k 83 12 69 10 55 8 41 6 28 4 14 2 0 0

3"

**
H N V

0 100 200 300 400 500 gpm 0 380 760 1140 1520 1900 lpm 15 fps 4.6 mps

Pa psi k * ** N 83 12 H 69 10 V 55 8 41 6 28 4 14 2 0 0 0 500 1000 1500 2000 2500 gpm 0 1900 3800 5700 7600 9500 lpm 15 fps 4.6 mps

8"

Pa k 165 138 110 83 55 28 0

psi * ** 24 N 20 V 16 H 12 8 4 0 0 100 200 300 400 500 600 700 800 gpm 0 380 760 1140 1520 1900 2280 2660 3040 lpm 15 fps 4.6 mps

4"

Pa psi k 83 12 69 10 55 8 41 6 28 4 14 2 0 0

10"

**
N H V

0 500 1000 1500 2000 2500 3000 3500 gpm 0 1900 3800 5700 7600 9500 11400 13300 lpm fps mps

Inquire with governing authorities for local installation requirements

NOTICE