Professional Documents
Culture Documents
· · ··
Socket Outlets Busbar Systems Measuring devices and
E-counters Monitoring devices Software
Switchboards and Distribution Systems LV 10.2 Switchboards · SIVACON 8PS busbar trunking systems ·
Order No.: SIVACON 8MC, 8MF Cubicle Systems · SIVACON 8MR, 8ME
E86060-K8260-A101-A1-7600 Cubicle Air-Conditioning · Distribution Boards · Terminal
blocks
· · · ··
air-conditioning Load management Safety Quick-assem-
bly systems Gateways, interface converters Physical
·
sensors Control and automation devices System products · ·
· ·
System accessories Counters Radio system - GAMMA wave
·
KNX-Radio Radio system - EnOcean
SIVACON S4 LV 56 ·
Power distribution boards Standard configurations Cubi- ·
Power Distribution Boards cles, supporting structure and enclosures Busbar system· ·
Order No.:
· ·
Assembly kits for switching devices Covers, modular doors,
mounting plates, 19" rack Internal separation Air-condition- ·
E80003-A10-R112-X-7600
·
ing products Accessories
SIVACON 8PS
Busbar Trunking Systems
LV 70 Busbar Trunking Systems, Overview CD-L System
·
(25 A ... 40 A) BD 01 System (40 A ... 160 A)
· ·
CD-L, BD01, BD2 up to 1250 A BD2 System (160 A ... 1250 A)
Order No.:
E86060-K1870-A101-A5-7600
Catalog PDF All catalogs for low-voltage power distribution and electrical
Internet: installation technology can be downloaded as PDF files.
www.siemens.com/lowvoltage/infomaterial
© Siemens AG 2010
SIVACON 8PS Busbar Trunking Systems
15
Catalog LV 10.2 · 2011
Innovation is the key to success Energy-efficiency and environmental Customer focus as USP
protection is our business principle
We continue to invest heavily in the re- And this business principle applies cross- This is not just a soundbite, we make ev-
search and development of new technolo- company and to each and every em- ery effort to ensure close customer rela-
gies. We have our own experimental and ployee: We are committed to environmen- tions. We have in-depth knowledge of
test laboratories where we carry out in- tal protection and the careful use of re- their business and involve them in the de-
tensive basic research on the climate in sources. Since 1994, we have been velopment of our innovations. Our skills
buildings and on fire, gas and explosion involved in more than 1300 energy effi- make us an expert provider of industry-
protection. This gives us the experience ciency projects, which have jointly con- specific solutions and services, a preferred
and the opportunity to create solutions tributed to the saving of around 1.5 billion partner during the life cycle of a building -
that continuously flow into our new prod- euro in energy costs and reduced the an- and allow us to enjoy mutual growth with
ucts and systems. At special test premises, nual CO2 burden on the environment by our customers.
such as airport buildings and hospital approx. 700 000 t. So, as you can see, in-
premises, we test the interoperability of telligent solutions in technical infrastruc-
the individual systems. This empirical data tures benefit not only the owners and op-
is incorporated into industry-specific solu- erators of buildings, but also those who
tions that continually set new standards have nothing to do with them.
and underscore our claim to technological
leadership.
customers.
Total Building Solutions means more in- • Low-voltage power distribution • Fire protection
novation from a single source for en- Switchboards, busbar trunking Fire alarms, alerting, evacuation, ex-
hanced functionality under one roof. systems, distribution boards, tinction and complete fire protection
When it comes to delivering turnkey build- circuit breakers, switch disconnectors, solutions
ings equipped with cutting edge power low-voltage circuit protection, building
distribution, building automation and management systems, switches and Take a closer look at all the options avail-
safety and fire-protection equipment from socket outlets able from Siemens. Check out the oppor-
a single source, Siemens is in a league of • Building automation tunities our products provide and discover
its own. And just to show that we are Heating, ventilation and air-condition- how we can help you sustainably enhance
more than just the sum of our parts, our ing controls, overall energy solutions your competitive edge.
portfolio includes: offering guaranteed savings
• Safety solutions
Access control, video monitoring, bur-
glar protection, alarm control centers,
operation of alarm control centers
reason, you need products and systems which cope with every
eventuality and always keep you on the safe side. Our portfolio is
to socket outlets.
Making efficient use of energy Excellent support Top quality standards world-wide
The consistent concept behind the As a competent and reliable partner we Opting for us puts you on the safe side:
communication-capable components of offer you comprehensive support – from Whether it is our workmanship, the
our low-voltage power distribution range initial information, planning, configura- materials we use or the operability and
forms a sound basis for the measurement, tion and ordering through to commission- functionality of our products –
indication, evaluation and optimization of ing, operation and technical support. We we guarantee top standards of quality
power flows, thus enabling professional know the requirements to be met in your world-wide.
energy management for more cost-effec- area of work and day-to-day business. On
tiveness. At the same time our intelligent this basis we provide you with the type of
building management systems, e.g. for flexible and efficient help that allows you
lighting and heating, help to remarkably to concentrate fully on your customers
reduce power consumption. and their needs.
New developments
5SL miniature circuit breakers → page 3/6 Auxiliary switches and fault signal contacts with TEST button for miniature
circuit breakers → page 3/31
Busbar system according to UL 508 → page 3/45 Auxiliary switches for miniature circuit breakers according to UL 489
→ page 3/52
Selective main miniature circuit breaker, SHU → page 3/56 SIQUENCE residual current protective devices, Type B+ → page 4/9
Compact fuse holders for motor starter combinations → page 5/24 Photovoltaic fuses → page 5/64
3NJ62 switch disconnectors with fuses - fuse monitoring, EFM10 and EFM20/25 electronic fuse monitors
DC version → page 7/64 → page 7/65
3NP1 fuse switch disconnectors → page 7/89 Light indicators with LEDs → page 8/14
SENTRON PAC 4200 → page 11/28 SENTRON PAC 4DI/2DO expansion modules → page 11/31
ALPHA SELECT V6.1project management software → page 13/7 SENTRON Powermanager → page13/16
With our basic and advanced courses, you can lay the founda- Visit us on the Internet. You will find comprehensive informa-
tions for your business success. Expert lecturers provide you tion on our products – SIVACON switchboards, busbar trunk-
with the necessary theoretical and practical knowledge in our ing systems, ALPHA distribution boards, SENTRON circuit
modern training center in Regensburg. Dynamic and easy-to- breakers and switch disconnectors, BETA low-voltage circuit
understand training with multimedia teaching equipment and protection, GAMMA building management systems and
many practical examples. Available in German and English. If DELTA switches and socket outlets – at:
required, we also provide training in-house or in one of our lo- www.siemens.com/lowvoltage
cal Siemens branches.
Comprehensive support
1/2 Introduction
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical specifications
under Entry List:
- Updates
- Downloads
- FAQ
- Manuals
- Characteristic curves
- Certificates
and at
www.siemens.com/lowvoltage/
configurators
- Configurators
Introduction
■ Overview
Degree of protection
With cover IP55 IP55
Without cover IP41 IP41
(with door sealing frame)
Dimensions 3-/4-pole
B T W mm 320/410 460/590 704/914 460/590
Fixed H mm 434 434 434 434
H
NSE0_01111a
Rating Plug
Introduction
Switching capacity
Size I II III
Type 3WL11 3WL12 3WL13
Switching capacity class N S N S H H C C
N S N S H H C C
3-pole 4-pole
Short-circuit breaking capacity
Rated operational voltage Ue
up to 415 V AC
Icu kA 55 66 66 80 100 100 150 130
Ics kA 55 66 66 80 100 100 150 130
Icm kA 121 145 145 176 220 220 330 286
Rated operational voltage Ue
up to 500 V AC
Icu kA 55 66 66 80 100 100 150 130
Ics kA 55 66 66 80 100 100 150 130
Icm kA 121 145 145 176 220 220 330 286
Rated operational voltage Ue
up to 690 V AC
Icu kA 42 50 50 75 85 85 150 130
Ics kA 42 50 50 75 85 85 150 130
Icm kA 88 105 105 165 187 187 330 286
Rated operational voltage Ue
up to 1000 V/1150 V AC
Icu kA -- -- -- -- 50 50 704) 704)
Ics kA -- -- -- -- 50 50 704) 704)
Icm kA -- -- -- -- 105 105 1544) 1544)
Rated short-time withstand current Icw
of the circuit breakers3)
0.5 s kA 55 66 66 80 100 100 100 100
1s kA 42 50 55 66 80 100 100 100
2s kA 29.5 35 39 46 651)/702) 80 80 80
3s kA 24 29 32 37 501)/652) 65 65 65
Short-circuit breaking capacity Icc
of the non-automatic air circuit breakers
Up to 500 V AC kA 55 66 66 80 100 100 100 100
Up to 690 V AC kA 42 50 50 75 85 85 100 100
Up to 1000 V /1150 V AC kA -- -- -- -- 504) 504) 704) 704)
Size II
DC
Type 3WL12
Switching capacity class DC
Short-circuit breaking capacity
Up to 220 V DC Icc kA 35
Up to 300 V DC Icc kA 30
Up to 600 V DC Icc kA 25
Up to 1000 V DC Icc kA 20
Rated short-time withstand current Icw
0.5 s kA --
1s kA 355)/306)/257)/208)
2s kA --
3s kA --
1)
Size II with In max ≤ 2500 A.
N
Circuit breaker with ECO switching capacity N 2)
Size II with In max = 3200 A and In max = 4000 A.
3)
At a rated voltage of ≥ 690 V the Icw value of the circuit breaker cannot be
S
Circuit breaker with standard switching capacity S greater than the Icu or Ics value at 690 V.
4)
Rated operational voltage Ue = 1150 V.
Circuit breaker with high switching capacity H 5)
H At Ue = 220 V DC.
6)
At Ue = 300 V DC.
7)
C
Circuit breakers with very high switching capacity C At Ue = 600 V DC.
8)
At Ue = 1000 V DC.
DC
Non-automatic air circuit breakers with DC switching
capacity
These breaking capacities are indicated in the corre-
sponding tables by the symbols shown on orange back-
grounds.
Introduction
SENTRON 3WL:
Superior individual products integrated into uniform power dis-
tribution systems - up to and including industry-specific indus-
trial and infrastructure solutions
7
2
3 8
5
4
9
1
25
21
10
19
22 11
23
12
24 18 13
17
14 NSE0_01887b
20
16
15
$ Guide frame (pages 1/30 to 1/33) 4 Operating cycles counter (pages 1/25 and 1/38)
% Main circuit connection front, flange, horizontal, vertical 5 Breaker status sensor (BSS) (pages 1/26 and 1/44)
(pages 1/28, 1/45 and 1/46) 6 Protective device with device holder, electronic release (ETU)
& Position signaling switch (pages 1/26 and 1/38) (page 1/34)
( Grounding contact, leading (page 1/42) 7 Remote reset solenoid (pages 1/25 and 1/35)
& Shutters (pages 1/26 and 1/41) 8 Breaker data adapter (BDA) (page 1/43)
* COM15 PROFIBUS module or COM16 MODBUS module 9 4-line display (page 1/34)
(pages 1/26 and 1/44) : Ground-fault protection module (page 1/34)
+ External CubicleBUS module (page 1/43) ; Rated current module (pages 1/24 and 1/34)
, Closing solenoid, auxiliary release (pages 1/23, 1/25 and 1/40) < Measurement function module (pages 1/26 and 1/34)
$ Auxiliary cable connection system (pages 1/27 and 1/39) = Circuit breaker (pages 1/7 to 1/22)
- Auxiliary switching block (pages 1/23 and 1/40)
/ Door sealing frame (pages 1/25 and 1/41)
0 Interlocking set for mechanical ON/OFF (page 1/35)
1 Transparent panel, function insert (page 1/35)
2 EMERGENCY-STOP pushbutton, key operated (page 1/38)
3 Motorized operating mechanism (pages 1/25 and 1/40)
Introduction
Communication-capable circuit breakers (with ETU45B or ETU76B electronic release)
21
Ethernet
19
20
PROFIBUS
4 5 22 14 15 16 17 18 7
8 6
CubicleBUS
10
11 9
1 1
12
13
2 3
NSE0_01105i
1 SENTRON 3VL 12 Electronic ETU release
2 Electronic LCD ETU release 13 Measurement function Plus
3 Electronic ETU release 14 ZSI module
4 COM10 PROFIBUS module complete with ZSI 15 Digital output module with relay contacts
5 COM20 PROFIBUS module1) complete with ZSI 16 Digital output module with relay contacts, configurable
6 Breaker Data Adapter (BDA) 17 Analog output module
7 BDA Plus with Ethernet interface 18 Digital input module
8 Browser-capable input and output device (e.g. notebook) 19 Switch ES Power on PC
9 SENTRON 3WL 20 PLC e.g. SIMATIC S7
10 COM15 PROFIBUS module2) 21 SIMATIC powerrate
11 Breaker Status Sensor (BSS) 22 SENTRON PAC
Features
• Coordinated communication concept using the PROFIBUS DP Communication:
or MODBUS, ranging from 16 A to 6300 A with SENTRON 3VL • For air circuit breakers with optional communication function
and SENTRON 3WL (ETU45B or ETU76B electronic release) see pages 1/7 to 1/22.
• The high level of modularity of circuit breakers and accessories • For accessories see pages 1/43 and 1/44.
allows easy retrofitting of all communication components
• For more information see also chapters "Measuring Instru-
• Significant additional benefits for the switchboard due to the ments and E-Counters" and "Software".
possibility of linking up external input and output modules to
the circuit breaker-internal CubicleBUS of the SENTRON 3WL
• Innovative software products for parameterization, operation,
monitoring, and diagnostics of SENTRON circuit breakers,
both locally or via PROFIBUS DP, MODBUS or Ethernet/
Intranet/Internet
• Complete integration of the SENTRON circuit breakers into the
Totally Integrated Power and Totally Integrated Automation
solutions
Conductor cross-sections
Size I II
Type Up to 3WL11 12 3WL11 16 3WL12 08 3WL12 10 3WL12 12 3WL12 16 3WL12 20
3WL11 10
Permissible load • Up to 55 °C (Cu bare) A 1000 1250 1600 800 1000 1250 1600 2000
At rear horizontal main • Up to 60 °C (Cu bare)1) A 1000 1250 1600 800 1000 1250 1600 2000
connections • Up to 70 °C (Cu black A 1000 1210 1490 800 1000 1250 1600 2000
painted)1)
Main conductor • Copper bars, Unit(s) 1 × 2× 2× 1× 1× 2× 2× 3×
minimum bare mm2 60 × 10 40 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10 50 × 10
cross-sections Unit(s) 1 × 2× 2× 1× 1× 2× 2× 3×
• Copper bars,
painted black mm2 60 × 10 40 × 10 50 × 10 50 × 10 60 × 10 40 × 10 50 × 10 50 × 10
Size II III
Type 3WL12 25 3WL12 32 3WL12 40 3WL13 40 3WL13 50 3WL13 63
Permissible load • Up to 55 °C (Cu bare) A 2500 3200 3950 4000 5000 5920
• Up to 60 °C (Cu bare)1) A 2500 3020 3810 4000 5000 5810
• Up to 70 °C (Cu black A 2280 2870 3600 4000 5000 5500
painted)1)
Main conductor • Copper bars, Unit(s) 2 × 3× 4× 4x 6x 6x
minimum bare mm2 100 × 10 100 × 10 120 × 10 100 x 10 100 x 10 120 x 10
cross-sections • Copper bars, Unit(s) 2 × 3× 4× 4× 6× 6×
painted black mm2 100 × 10 100 × 10 100 × 102) 100 × 10 100 × 10 120 × 10
1)
ETU76B with graphics display can be used up to max. 55 °C.
2)
Minimum main conductor cross-sections for 4-pole withdrawable circuit
breakers: 4 × 120 × 10 mm.
Size Max. rated circuit breaker Rated current1) Icu up to 66/80 kA at 500 V, PU PS*/ PG Weight
current In standard switching capacity S S (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
For Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Horizontal main circuit connection
I 630 630 66 B 3WL11 06-3@@32-.... 1 1 unit 103 43.000
I 800 800 66 B 3WL11 08-3@@32-.... 1 1 unit 103 43.000
I 1000 1000 66 B 3WL11 10-3@@32-.... 1 1 unit 103 43.000
I 1250 1250 66 B 3WL11 12-3@@32-.... 1 1 unit 103 43.000
I 1600 1600 66 B 3WL11 16-3@@32-.... 1 1 unit 103 43.000
II 800 800 80 B 3WL12 08-3@@32-.... 1 1 unit 103 56.000
II 1000 1000 80 B 3WL12 10-3@@32-.... 1 1 unit 103 56.000
II 1250 1250 80 B 3WL12 12-3@@32-.... 1 1 unit 103 56.000
II 1600 1600 80 B 3WL12 16-3@@32-.... 1 1 unit 103 56.000
II 2000 2000 80 B 3WL12 20-3@@32-.... 1 1 unit 103 56.000
II 2500 2500 80 B 3WL12 25-3@@32-.... 1 1 unit 103 59.000
II 3200 3200 80 B 3WL12 32-3@@32-.... 1 1 unit 103 64.000
Vertical main circuit connection
I 630 630 66 B 3WL11 06-3@@31-.... 1 1 unit 103 43.000
I 800 800 66 B 3WL11 08-3@@31-.... 1 1 unit 103 43.000
I 1000 1000 66 B 3WL11 10-3@@31-.... 1 1 unit 103 43.000
I 1250 1250 66 B 3WL11 12-3@@31-.... 1 1 unit 103 43.000
I 1600 1600 66 B 3WL11 16-3@@31-.... 1 1 unit 103 43.000
II 800 800 80 B 3WL12 08-3@@31-.... 1 1 unit 103 56.000
II 1000 1000 80 B 3WL12 10-3@@31-.... 1 1 unit 103 56.000
II 1250 1250 80 B 3WL12 12-3@@31-.... 1 1 unit 103 56.000
II 1600 1600 80 B 3WL12 16-3@@31-.... 1 1 unit 103 56.000
II 2000 2000 80 B 3WL12 20-3@@31-.... 1 1 unit 103 56.000
II 2500 2500 80 B 3WL12 25-3@@31-.... 1 1 unit 103 59.000
II 3200 3200 80 B 3WL12 32-3@@31-.... 1 1 unit 103 64.000
II 4000 4000 80 B 3WL12 40-3@@31-.... 1 1 unit 103 85.000
Front main circuit connection, single hole
I 630 630 66 B 3WL11 06-3@@33-.... 1 1 unit 103 43.000
I 800 800 66 B 3WL11 08-3@@33-.... 1 1 unit 103 43.000
I 1000 1000 66 B 3WL11 10-3@@33-.... 1 1 unit 103 43.000
I 1250 1250 66 B 3WL11 12-3@@33-.... 1 1 unit 103 43.000
I 1600 1600 66 B 3WL11 16-3@@33-.... 1 1 unit 103 43.000
II 800 800 80 B 3WL12 08-3@@33-.... 1 1 unit 103 56.000
II 1000 1000 80 B 3WL12 10-3@@33-.... 1 1 unit 103 56.000
II 1250 1250 80 B 3WL12 12-3@@33-.... 1 1 unit 103 56.000
II 1600 1600 80 B 3WL12 16-3@@33-.... 1 1 unit 103 56.000
II 2000 2000 80 B 3WL12 20-3@@33-.... 1 1 unit 103 56.000
II 2500 2500 80 B 3WL12 25-3@@33-.... 1 1 unit 103 59.000
II 3200 3200 80 B 3WL12 32-3@@33-.... 1 1 unit 103 64.000
Front main circuit connection, double hole
I 630 630 66 B 3WL11 06-3@@34-.... 1 1 unit 103 43.000
I 800 800 66 B 3WL11 08-3@@34-.... 1 1 unit 103 43.000
I 1000 1000 66 B 3WL11 10-3@@34-.... 1 1 unit 103 43.000
I 1250 1250 66 B 3WL11 12-3@@34-.... 1 1 unit 103 43.000
I 1600 1600 66 B 3WL11 16-3@@34-.... 1 1 unit 103 43.000
II 800 800 80 B 3WL12 08-3@@34-.... 1 1 unit 103 56.000
II 1000 1000 80 B 3WL12 10-3@@34-.... 1 1 unit 103 56.000
II 1250 1250 80 B 3WL12 12-3@@34-.... 1 1 unit 103 56.000
II 1600 1600 80 B 3WL12 16-3@@34-.... 1 1 unit 103 56.000
II 2000 2000 80 B 3WL12 20-3@@34-.... 1 1 unit 103 56.000
II 2500 2500 80 B 3WL12 25-3@@34-.... 1 1 unit 103 59.000
II 3200 3200 80 B 3WL12 32-3@@34-.... 1 1 unit 103 64.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
For footnotes see page 1/10.
Size Max. rated circuit breaker Rated current1) Icu up to 100 kA at 500 V, PU PS*/ PG Weight
current In high switching capacity H H (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Horizontal main circuit connection
II 800 800 100 B 3WL12 08-4@@32-.... 1 1 unit 103 56.000
II 1000 1000 100 B 3WL12 10-4@@32-.... 1 1 unit 103 56.000
II 1250 1250 100 B 3WL12 12-4@@32-.... 1 1 unit 103 56.000
II 1600 1600 100 B 3WL12 16-4@@32-.... 1 1 unit 103 56.000
II 2000 2000 100 B 3WL12 20-4@@32-.... 1 1 unit 103 56.000
II 2500 2500 100 B 3WL12 25-4@@32-.... 1 1 unit 103 59.000
II 3200 3200 100 B 3WL12 32-4@@32-.... 1 1 unit 103 64.000
III 4000 4000 100 B 3WL13 40-4@@32-.... 1 1 unit 103 82.000
III 5000 5000 100 B 3WL13 50-4@@32-.... 1 1 unit 103 82.000
Vertical main circuit connection
II 800 800 100 B 3WL12 08-4@@31-.... 1 1 unit 103 56.000
II 1000 1000 100 B 3WL12 10-4@@31-.... 1 1 unit 103 56.000
II 1250 1250 100 B 3WL12 12-4@@31-.... 1 1 unit 103 56.000
II 1600 1600 100 B 3WL12 16-4@@31-.... 1 1 unit 103 56.000
II 2000 2000 100 B 3WL12 20-4@@31-.... 1 1 unit 103 56.000
II 2500 2500 100 B 3WL12 25-4@@31-.... 1 1 unit 103 59.000
II 3200 3200 100 B 3WL12 32-4@@31-.... 1 1 unit 103 64.000
II 4000 4000 100 B 3WL12 40-4@@31-.... 1 1 unit 103 85.000
III 4000 4000 100 B 3WL13 40-4@@31-.... 1 1 unit 103 82.000
III 5000 5000 100 B 3WL13 50-4@@31-.... 1 1 unit 103 82.000
III 6300 6300 100 B 3WL13 63-4@@31-.... 1 1 unit 103 90.000
Front main circuit connection, single hole
II 800 800 100 B 3WL12 08-4@@33-.... 1 1 unit 103 56.000
II 1000 1000 100 B 3WL12 10-4@@33-.... 1 1 unit 103 56.000
II 1250 1250 100 B 3WL12 12-4@@33-.... 1 1 unit 103 56.000
II 1600 1600 100 B 3WL12 16-4@@33-.... 1 1 unit 103 56.000
II 2000 2000 100 B 3WL12 20-4@@33-.... 1 1 unit 103 56.000
II 2500 2500 100 B 3WL12 25-4@@33-.... 1 1 unit 103 59.000
II 3200 3200 100 B 3WL12 32-4@@33-.... 1 1 unit 103 64.000
III 4000 4000 100 B 3WL13 40-4@@33-.... 1 1 unit 103 82.000
Front main circuit connection, double hole
II 800 800 100 B 3WL12 08-4@@34-.... 1 1 unit 103 56.000
II 1000 1000 100 B 3WL12 10-4@@34-.... 1 1 unit 103 56.000
II 1250 1250 100 B 3WL12 12-4@@34-.... 1 1 unit 103 56.000
II 1600 1600 100 B 3WL12 16-4@@34-.... 1 1 unit 103 56.000
II 2000 2000 100 B 3WL12 20-4@@34-.... 1 1 unit 103 56.000
II 2500 2500 100 B 3WL12 25-4@@34-.... 1 1 unit 103 59.000
II 3200 3200 100 B 3WL12 32-4@@34-.... 1 1 unit 103 64.000
III 4000 4000 100 B 3WL13 40-4@@34-.... 1 1 unit 103 82.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
For footnotes see page 1/10.
Size Max. rated circuit breaker Rated current1) Icu up to 150 kA at 500 V, PU PS*/ PG Weight
current In very high switching capacity C C (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Horizontal main circuit connection
III 4000 4000 150 B 3WL13 40-5@@32-.... 1 1 unit 103 82.000
III 5000 5000 150 B 3WL13 50-5@@32-.... 1 1 unit 103 82.000
Vertical main circuit connection
III 4000 4000 150 B 3WL13 40-5@@31-.... 1 1 unit 103 82.000
III 5000 5000 150 B 3WL13 50-5@@31-.... 1 1 unit 103 82.000
III 6300 6300 150 B 3WL13 63-5@@31-.... 1 1 unit 103 90.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
Footnotes for pages 1/7 to 1/10:
1) 3)
The rated current is determined by the rated current module. For the stan- Current transformers for protection of the N conductor and current trans-
dard version, the supplied module is equal to the maximum rated current. formers for detection of the ground-fault current in the grounded neutral
If a lower rated current is required, adaptation by order code on page 1/24. point of the transformer are to be ordered separately, see page 1/34.
2) 4)
For permissible rated short-time current Icc and rated short-circuit making Current transformers for protection of the N conductor are to be ordered
capacity Icm for non-automatic air circuit breakers see page 1/3. separately, see page 1/34.
5)
ETU45B and ETU76B with ground-fault protection module GFM AT (alarm
and tripping), see page 1/34.
6)
ETU15B cannot be used with 3WL circuit breakers, size III.
Size Max. rated circuit breaker Rated current1) Icu up to 66/80 kA at 500 V, PU PS*/ PG Weight
current In standard switching capacity S S (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
For Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Without guide frames
(for guide frames, see page 1/30 to 1/33)
I 630 630 66 B 3WL11 06-3@@35-.... 1 1 unit 103 45.000
I 800 800 66 B 3WL11 08-3@@35-.... 1 1 unit 103 45.000
I 1000 1000 66 B 3WL11 10-3@@35-.... 1 1 unit 103 45.000
I 1250 1250 66 B 3WL11 12-3@@35-.... 1 1 unit 103 45.000
I 1600 1600 66 B 3WL11 16-3@@35-.... 1 1 unit 103 45.000
II 800 800 80 B 3WL12 08-3@@35-.... 1 1 unit 103 60.000
II 1000 1000 80 B 3WL12 10-3@@35-.... 1 1 unit 103 60.000
II 1250 1250 80 B 3WL12 12-3@@35-.... 1 1 unit 103 60.000
II 1600 1600 80 B 3WL12 16-3@@35-.... 1 1 unit 103 60.000
II 2000 2000 80 B 3WL12 20-3@@35-.... 1 1 unit 103 60.000
II 2500 2500 80 B 3WL12 25-3@@35-.... 1 1 unit 103 63.000
II 3200 3200 80 B 3WL12 32-3@@35-.... 1 1 unit 103 68.000
With guide frames, horizontal main circuit connection
I 630 630 66 B 3WL11 06-3@@36-.... 1 1 unit 103 70.000
I 800 800 66 B 3WL11 08-3@@36-.... 1 1 unit 103 70.000
I 1000 1000 66 B 3WL11 10-3@@36-.... 1 1 unit 103 70.000
I 1250 1250 66 B 3WL11 12-3@@36-.... 1 1 unit 103 70.000
I 1600 1600 66 B 3WL11 16-3@@36-.... 1 1 unit 103 70.000
II 800 800 80 B 3WL12 08-3@@36-.... 1 1 unit 103 91.000
II 1000 1000 80 B 3WL12 10-3@@36-.... 1 1 unit 103 91.000
II 1250 1250 80 B 3WL12 12-3@@36-.... 1 1 unit 103 91.000
II 1600 1600 80 B 3WL12 16-3@@36-.... 1 1 unit 103 91.000
II 2000 2000 80 B 3WL12 20-3@@36-.... 1 1 unit 103 91.000
II 2500 2500 80 B 3WL12 25-3@@36-.... 1 1 unit 103 102.000
II 3200 3200 80 B 3WL12 32-3@@36-.... 1 1 unit 103 113.000
With guide frames, vertical main circuit connection
I 630 630 66 B 3WL11 06-3@@37-.... 1 1 unit 103 70.000
I 800 800 66 B 3WL11 08-3@@37-.... 1 1 unit 103 70.000
I 1000 1000 66 B 3WL11 10-3@@37-.... 1 1 unit 103 70.000
I 1250 1250 66 B 3WL11 12-3@@37-.... 1 1 unit 103 70.000
I 1600 1600 66 B 3WL11 16-3@@37-.... 1 1 unit 103 70.000
II 800 800 80 B 3WL12 08-3@@37-.... 1 1 unit 103 91.000
II 1000 1000 80 B 3WL12 10-3@@37-.... 1 1 unit 103 91.000
II 1250 1250 80 B 3WL12 12-3@@37-.... 1 1 unit 103 91.000
II 1600 1600 80 B 3WL12 16-3@@37-.... 1 1 unit 103 91.000
II 2000 2000 80 B 3WL12 20-3@@37-.... 1 1 unit 103 91.000
II 2500 2500 80 B 3WL12 25-3@@37-.... 1 1 unit 103 102.000
II 3200 3200 80 B 3WL12 32-3@@37-.... 1 1 unit 103 113.000
II 4000 4000 80 B 3WL12 40-3@@37-.... 1 1 unit 103 121.000
With guide frames, connecting flanges
I 630 630 66 B 3WL11 06-3@@38-.... 1 1 unit 103 70.000
I 800 800 66 B 3WL11 08-3@@38-.... 1 1 unit 103 70.000
I 1000 1000 66 B 3WL11 10-3@@38-.... 1 1 unit 103 70.000
I 1250 1250 66 B 3WL11 12-3@@38-.... 1 1 unit 103 70.000
I 1600 1600 66 B 3WL11 16-3@@38-.... 1 1 unit 103 70.000
II 800 800 80 B 3WL12 08-3@@38-.... 1 1 unit 103 91.000
II 1000 1000 80 B 3WL12 10-3@@38-.... 1 1 unit 103 91.000
II 1250 1250 80 B 3WL12 12-3@@38-.... 1 1 unit 103 91.000
II 1600 1600 80 B 3WL12 16-3@@38-.... 1 1 unit 103 91.000
II 2000 2000 80 B 3WL12 20-3@@38-.... 1 1 unit 103 91.000
II 2500 2500 80 B 3WL12 25-3@@38-.... 1 1 unit 103 102.000
II 3200 3200 80 B 3WL12 32-3@@38-.... 1 1 unit 103 113.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
For footnotes see page 1/14.
Size Max. rated circuit breaker Rated current1) Icu up to 100 kA at 500 V, PU PS*/ PG Weight
current In high switching capacity H H (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Without guide frames
(for guide frames, see page 1/30 to 1/33)
II 800 800 100 B 3WL12 08-4@@35-.... 1 1 unit 103 60.000
II 1000 1000 100 B 3WL12 10-4@@35-.... 1 1 unit 103 60.000
II 1250 1250 100 B 3WL12 12-4@@35-.... 1 1 unit 103 60.000
II 1600 1600 100 B 3WL12 16-4@@35-.... 1 1 unit 103 60.000
II 2000 2000 100 B 3WL12 20-4@@35-.... 1 1 unit 103 60.000
II 2500 2500 100 B 3WL12 25-4@@35-.... 1 1 unit 103 63.000
II 3200 3200 100 B 3WL12 32-4@@35-.... 1 1 unit 103 68.000
III 4000 4000 100 B 3WL13 40-4@@35-.... 1 1 unit 103 88.000
III 5000 5000 100 B 3WL13 50-4@@35-.... 1 1 unit 103 88.000
III 6300 6300 100 B 3WL13 63-4@@35-.... 1 1 unit 103 96.000
With guide frames, horizontal main circuit connection
II 800 800 100 B 3WL12 08-4@@36-.... 1 1 unit 103 91.000
II 1000 1000 100 B 3WL12 10-4@@36-.... 1 1 unit 103 91.000
II 1250 1250 100 B 3WL12 12-4@@36-.... 1 1 unit 103 91.000
II 1600 1600 100 B 3WL12 16-4@@36-.... 1 1 unit 103 91.000
II 2000 2000 100 B 3WL12 20-4@@36-.... 1 1 unit 103 91.000
II 2500 2500 100 B 3WL12 25-4@@36-.... 1 1 unit 103 102.000
II 3200 3200 100 B 3WL12 32-4@@36-.... 1 1 unit 103 113.000
III 4000 4000 100 B 3WL13 40-4@@36-.... 1 1 unit 103 148.000
III 5000 5000 100 B 3WL13 50-4@@36-.... 1 1 unit 103 148.000
With guide frames, vertical main circuit connection
II 800 800 100 B 3WL12 08-4@@37-.... 1 1 unit 103 91.000
II 1000 1000 100 B 3WL12 10-4@@37-.... 1 1 unit 103 91.000
II 1250 1250 100 B 3WL12 12-4@@37-.... 1 1 unit 103 91.000
II 1600 1600 100 B 3WL12 16-4@@37-.... 1 1 unit 103 91.000
II 2000 2000 100 B 3WL12 20-4@@37-.... 1 1 unit 103 91.000
II 2500 2500 100 B 3WL12 25-4@@37-.... 1 1 unit 103 102.000
II 3200 3200 100 B 3WL12 32-4@@37-.... 1 1 unit 103 113.000
II 4000 4000 100 B 3WL12 40-4@@37-.... 1 1 unit 103 121.000
III 4000 4000 100 B 3WL13 40-4@@37-.... 1 1 unit 103 148.000
III 5000 5000 100 B 3WL13 50-4@@37-.... 1 1 unit 103 148.000
III 6300 6300 100 B 3WL13 63-4@@37-.... 1 1 unit 103 166.000
With guide frames, connecting flanges
II 800 800 100 B 3WL12 08-4@@38-.... 1 1 unit 103 91.000
II 1000 1000 100 B 3WL12 10-4@@38-.... 1 1 unit 103 91.000
II 1250 1250 100 B 3WL12 12-4@@38-.... 1 1 unit 103 91.000
II 1600 1600 100 B 3WL12 16-4@@38-.... 1 1 unit 103 91.000
II 2000 2000 100 B 3WL12 20-4@@38-.... 1 1 unit 103 91.000
II 2500 2500 100 B 3WL12 25-4@@38-.... 1 1 unit 103 102.000
II 3200 3200 100 B 3WL12 32-4@@38-.... 1 1 unit 103 113.000
III 4000 4000 100 B 3WL13 40-4@@38-.... 1 1 unit 103 148.000
Non-automatic air circuit breakers 2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
For footnotes see page 1/14.
Size Max. rated circuit breaker Rated current1) Icu up to 150 kA at 500 V, PU PS*/ PG Weight
current In very high switching capacity C C (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Without guide frames
(for guide frames, see page 1/30 to 1/33)
III 4000 4000 150 B 3WL13 40-5@@35-.... 1 1 unit 103 88.000
III 5000 5000 150 B 3WL13 50-5@@35-.... 1 1 unit 103 88.000
III 6300 6300 150 B 3WL13 63-5@@35-.... 1 1 unit 103 96.000
With guide frames, horizontal main circuit connection
III 4000 4000 150 B 3WL13 40-5@@36-.... 1 1 unit 103 148.000
III 5000 5000 150 B 3WL13 50-5@@36-.... 1 1 unit 103 148.000
With guide frames, vertical main circuit connection
III 4000 4000 150 B 3WL13 40-5@@37-.... 1 1 unit 103 148.000
III 5000 5000 150 B 3WL13 50-5@@37-.... 1 1 unit 103 148.000
III 6300 6300 150 B 3WL13 63-5@@37-.... 1 1 unit 103 166.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
Footnotes for pages 1/11 to 1/14:
1) The rated current is determined by the rated current module. For the stan- 3) Current transformers for protection of the N conductor and current trans-
dard version, the supplied module is equal to the maximum rated current. formers for detection of the ground-fault current in the grounded neutral
If a lower rated current is required, adaptation by order code on page 1/24. point of the transformer are to be ordered separately, see page 1/34.
2) For permissible rated short-time current Icc and rated short-circuit making 4) Current transformers for protection of the N conductor are to be ordered
capacity Icm for non-automatic air circuit breakers see page 1/3. separately, see page 1/34.
5) ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
and tripping), see page 1/34.
6) ETU15B cannot be used with 3WL circuit breakers, size III.
Size Max. rated circuit breaker Rated current1) Icu up to 66/80 kA at 500 V, PU PS*/ PG Weight
current In standard switching capacity S S (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Horizontal main circuit connection
I 630 630 66 B 3WL11 06-3@@42-.... 1 1 unit 103 50.000
I 800 800 66 B 3WL11 08-3@@42-.... 1 1 unit 103 50.000
I 1000 1000 66 B 3WL11 10-3@@42-.... 1 1 unit 103 50.000
I 1250 1250 66 B 3WL11 12-3@@42-.... 1 1 unit 103 50.000
I 1600 1600 66 B 3WL11 16-3@@42-.... 1 1 unit 103 50.000
II 800 800 80 B 3WL12 08-3@@42-.... 1 1 unit 103 67.000
II 1000 1000 80 B 3WL12 10-3@@42-.... 1 1 unit 103 67.000
II 1250 1250 80 B 3WL12 12-3@@42-.... 1 1 unit 103 67.000
II 1600 1600 80 B 3WL12 16-3@@42-.... 1 1 unit 103 67.000
II 2000 2000 80 B 3WL12 20-3@@42-.... 1 1 unit 103 67.000
II 2500 2500 80 B 3WL12 25-3@@42-.... 1 1 unit 103 71.000
II 3200 3200 80 B 3WL12 32-3@@42-.... 1 1 unit 103 77.000
Vertical main circuit connection
I 630 630 66 B 3WL11 06-3@@41-.... 1 1 unit 103 50.000
I 800 800 66 B 3WL11 08-3@@41-.... 1 1 unit 103 50.000
I 1000 1000 66 B 3WL11 10-3@@41-.... 1 1 unit 103 50.000
I 1250 1250 66 B 3WL11 12-3@@41-.... 1 1 unit 103 50.000
I 1600 1600 66 B 3WL11 16-3@@41-.... 1 1 unit 103 50.000
II 800 800 80 B 3WL12 08-3@@41-.... 1 1 unit 103 67.000
II 1000 1000 80 B 3WL12 10-3@@41-.... 1 1 unit 103 67.000
II 1250 1250 80 B 3WL12 12-3@@41-.... 1 1 unit 103 67.000
II 1600 1600 80 B 3WL12 16-3@@41-.... 1 1 unit 103 67.000
II 2000 2000 80 B 3WL12 20-3@@41-.... 1 1 unit 103 67.000
II 2500 2500 80 B 3WL12 25-3@@41-.... 1 1 unit 103 71.000
II 3200 3200 80 B 3WL12 32-3@@41-.... 1 1 unit 103 77.000
II 4000 4000 80 B 3WL12 40-3@@41-.... 1 1 unit 103 103.000
Front main circuit connection, single hole
I 630 630 66 B 3WL11 06-3@@43-.... 1 1 unit 103 50.000
I 800 800 66 B 3WL11 08-3@@43-.... 1 1 unit 103 50.000
I 1000 1000 66 B 3WL11 10-3@@43-.... 1 1 unit 103 50.000
I 1250 1250 66 B 3WL11 12-3@@43-.... 1 1 unit 103 50.000
I 1600 1600 66 B 3WL11 16-3@@43-.... 1 1 unit 103 50.000
II 800 800 80 B 3WL12 08-3@@43-.... 1 1 unit 103 67.000
II 1000 1000 80 B 3WL12 10-3@@43-.... 1 1 unit 103 67.000
II 1250 1250 80 B 3WL12 12-3@@43-.... 1 1 unit 103 67.000
II 1600 1600 80 B 3WL12 16-3@@43-.... 1 1 unit 103 67.000
II 2000 2000 80 B 3WL12 20-3@@43-.... 1 1 unit 103 67.000
II 2500 2500 80 B 3WL12 25-3@@43-.... 1 1 unit 103 71.000
II 3200 3200 80 B 3WL12 32-3@@43-.... 1 1 unit 103 77.000
Front main circuit connection, double hole
I 630 630 66 B 3WL11 06-3@@44-.... 1 1 unit 103 50.000
I 800 800 66 B 3WL11 08-3@@44-.... 1 1 unit 103 50.000
I 1000 1000 66 B 3WL11 10-3@@44-.... 1 1 unit 103 50.000
I 1250 1250 66 B 3WL11 12-3@@44-.... 1 1 unit 103 50.000
I 1600 1600 66 B 3WL11 16-3@@44-.... 1 1 unit 103 50.000
II 800 800 80 B 3WL12 08-3@@44-.... 1 1 unit 103 67.000
II 1000 1000 80 B 3WL12 10-3@@44-.... 1 1 unit 103 67.000
II 1250 1250 80 B 3WL12 12-3@@44-.... 1 1 unit 103 67.000
II 1600 1600 80 B 3WL12 16-3@@44-.... 1 1 unit 103 67.000
II 2000 2000 80 B 3WL12 20-3@@44-.... 1 1 unit 103 67.000
II 2500 2500 80 B 3WL12 25-3@@44-.... 1 1 unit 103 71.000
II 3200 3200 80 B 3WL12 32-3@@44-.... 1 1 unit 103 77.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
For footnotes see page 1/18.
Size Max. rated circuit breaker Rated current1) Icu up to 100 kA at 500 V, PU PS*/ PG Weight
current In high switching capacity H H (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Horizontal main circuit connection
II 800 800 100 B 3WL12 08-4@@42-.... 1 1 unit 103 67.000
II 1000 1000 100 B 3WL12 10-4@@42-.... 1 1 unit 103 67.000
II 1250 1250 100 B 3WL12 12-4@@42-.... 1 1 unit 103 67.000
II 1600 1600 100 B 3WL12 16-4@@42-.... 1 1 unit 103 67.000
II 2000 2000 100 B 3WL12 20-4@@42-.... 1 1 unit 103 67.000
II 2500 2500 100 B 3WL12 25-4@@42-.... 1 1 unit 103 71.000
II 3200 3200 100 B 3WL12 32-4@@42-.... 1 1 unit 103 77.000
III 4000 4000 100 B 3WL13 40-4@@42-.... 1 1 unit 103 99.000
III 5000 5000 100 B 3WL13 50-4@@42-.... 1 1 unit 103 99.000
Vertical main circuit connection
II 800 800 100 B 3WL12 08-4@@41-.... 1 1 unit 103 67.000
II 1000 1000 100 B 3WL12 10-4@@41-.... 1 1 unit 103 67.000
II 1250 1250 100 B 3WL12 12-4@@41-.... 1 1 unit 103 67.000
II 1600 1600 100 B 3WL12 16-4@@41-.... 1 1 unit 103 67.000
II 2000 2000 100 B 3WL12 20-4@@41-.... 1 1 unit 103 67.000
II 2500 2500 100 B 3WL12 25-4@@41-.... 1 1 unit 103 71.000
II 3200 3200 100 B 3WL12 32-4@@41-.... 1 1 unit 103 77.000
II 4000 4000 100 B 3WL12 40-4@@41-.... 1 1 unit 103 103.000
III 4000 4000 100 B 3WL13 40-4@@41-.... 1 1 unit 103 99.000
III 5000 5000 100 B 3WL13 50-4@@41-.... 1 1 unit 103 99.000
III 6300 6300 100 B 3WL13 63-4@@41-.... 1 1 unit 103 108.000
Front main circuit connection, single hole
II 800 800 100 B 3WL12 08-4@@43-.... 1 1 unit 103 67.000
II 1000 1000 100 B 3WL12 10-4@@43-.... 1 1 unit 103 67.000
II 1250 1250 100 B 3WL12 12-4@@43-.... 1 1 unit 103 67.000
II 1600 1600 100 B 3WL12 16-4@@43-.... 1 1 unit 103 67.000
II 2000 2000 100 B 3WL12 20-4@@43-.... 1 1 unit 103 67.000
II 2500 2500 100 B 3WL12 25-4@@43-.... 1 1 unit 103 71.000
II 3200 3200 100 B 3WL12 32-4@@43-.... 1 1 unit 103 77.000
III 4000 4000 100 B 3WL13 40-4@@43-.... 1 1 unit 103 99.000
Front main circuit connection, double hole
II 800 800 100 B 3WL12 08-4@@44-.... 1 1 unit 103 67.000
II 1000 1000 100 B 3WL12 10-4@@44-.... 1 1 unit 103 67.000
II 1250 1250 100 B 3WL12 12-4@@44-.... 1 1 unit 103 67.000
II 1600 1600 100 B 3WL12 16-4@@44-.... 1 1 unit 103 67.000
II 2000 2000 100 B 3WL12 20-4@@44-.... 1 1 unit 103 67.000
II 2500 2500 100 B 3WL12 25-4@@44-.... 1 1 unit 103 71.000
II 3200 3200 100 B 3WL12 32-4@@44-.... 1 1 unit 103 77.000
III 4000 4000 100 B 3WL13 40-4@@44-.... 1 1 unit 103 99.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
For footnotes see page 1/18.
Size Max. rated circuit breaker Rated current1) Icu up to 130 kA at 500 V, PU PS*/ PG Weight
current In very high switching capacity C C (UNIT, P. unit per PU
In max. Order No. Basic SET, M) approx.
Order No. supplements, price
see page 1/23 per PU
A A kA DT kg
Horizontal main circuit connection
III 4000 4000 130 B 3WL13 40-5@@42-.... 1 1 unit 103 99.000
III 5000 5000 130 B 3WL13 50-5@@42-.... 1 1 unit 103 99.000
Vertical main circuit connection
III 4000 4000 130 B 3WL13 40-5@@41-.... 1 1 unit 103 99.000
III 5000 5000 130 B 3WL13 50-5@@41-.... 1 1 unit 103 99.000
III 6300 6300 130 B 3WL13 63-5@@41-.... 1 1 unit 103 108.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
Footnotes for pages 1/15 to 1/18:
1) 3)
The rated current is determined by the rated current module. For the stan- Current transformers for protection of the N conductor and current trans-
dard version, the supplied module is equal to the maximum rated current. formers for detection of the ground-fault current in the grounded neutral
If a lower rated current is required, adaptation by order code on page 1/24. point of the transformer are to be ordered separately, see page 1/34. The
2)
For permissible rated short-time current Icc and rated short-circuit making internal current transformers for N conductors can be ordered by adding
capacity Icm for non-automatic air circuit breakers see page 1/3. the supplement "–Z" and the order code "F23", see page 1/26.
4)
Current transformers for protection of the N conductor are to be ordered
separately, see page 1/34.
5)
ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
and tripping), see page 1/34.
6)
ETU15B cannot be used with 3WL circuit breakers, size III.
Size Max. rated circuit breaker Rated current1) Icu up to 66/80 kA at 500 V, PU PS*/ PG Weight
current In standard switching capacity S S (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Without guide frames
(for guide frames, see page 1/30 to 1/33)
I 630 630 66 B 3WL11 06-3@@45-.... 1 1 unit 103 54.000
I 800 800 66 B 3WL11 08-3@@45-.... 1 1 unit 103 54.000
I 1000 1000 66 B 3WL11 10-3@@45-.... 1 1 unit 103 54.000
I 1250 1250 66 B 3WL11 12-3@@45-.... 1 1 unit 103 54.000
I 1600 1600 66 B 3WL11 16-3@@45-.... 1 1 unit 103 54.000
II 800 800 80 B 3WL12 08-3@@45-.... 1 1 unit 103 72.000
II 1000 1000 80 B 3WL12 10-3@@45-.... 1 1 unit 103 72.000
II 1250 1250 80 B 3WL12 12-3@@45-.... 1 1 unit 103 72.000
II 1600 1600 80 B 3WL12 16-3@@45-.... 1 1 unit 103 72.000
II 2000 2000 80 B 3WL12 20-3@@45-.... 1 1 unit 103 72.000
II 2500 2500 80 B 3WL12 25-3@@45-.... 1 1 unit 103 76.000
II 3200 3200 80 B 3WL12 32-3@@45-.... 1 1 unit 103 82.000
With guide frames, horizontal main circuit connection
I 630 630 66 B 3WL11 06-3@@46-.... 1 1 unit 103 84.000
I 800 800 66 B 3WL11 08-3@@46-.... 1 1 unit 103 84.000
I 1000 1000 66 B 3WL11 10-3@@46-.... 1 1 unit 103 84.000
I 1250 1250 66 B 3WL11 12-3@@46-.... 1 1 unit 103 84.000
I 1600 1600 66 B 3WL11 16-3@@46-.... 1 1 unit 103 84.000
II 800 800 80 B 3WL12 08-3@@46-.... 1 1 unit 103 109.000
II 1000 1000 80 B 3WL12 10-3@@46-.... 1 1 unit 103 109.000
II 1250 1250 80 B 3WL12 12-3@@46-.... 1 1 unit 103 109.000
II 1600 1600 80 B 3WL12 16-3@@46-.... 1 1 unit 103 109.000
II 2000 2000 80 B 3WL12 20-3@@46-.... 1 1 unit 103 109.000
II 2500 2500 80 B 3WL12 25-3@@46-.... 1 1 unit 103 123.000
II 3200 3200 80 B 3WL12 32-3@@46-.... 1 1 unit 103 136.000
With guide frames, vertical main circuit connection
I 630 630 66 B 3WL11 06-3@@47-.... 1 1 unit 103 84.000
I 800 800 66 B 3WL11 08-3@@47-.... 1 1 unit 103 84.000
I 1000 1000 66 B 3WL11 10-3@@47-.... 1 1 unit 103 84.000
I 1250 1250 66 B 3WL11 12-3@@47-.... 1 1 unit 103 84.000
I 1600 1600 66 B 3WL11 16-3@@47-.... 1 1 unit 103 84.000
II 800 800 80 B 3WL12 08-3@@47-.... 1 1 unit 103 109.000
II 1000 1000 80 B 3WL12 10-3@@47-.... 1 1 unit 103 109.000
II 1250 1250 80 B 3WL12 12-3@@47-.... 1 1 unit 103 109.000
II 1600 1600 80 B 3WL12 16-3@@47-.... 1 1 unit 103 109.000
II 2000 2000 80 B 3WL12 20-3@@47-.... 1 1 unit 103 109.000
II 2500 2500 80 B 3WL12 25-3@@47-.... 1 1 unit 103 123.000
II 3200 3200 80 B 3WL12 32-3@@47-.... 1 1 unit 103 136.000
II 4000 4000 80 B 3WL12 40-3@@47-.... 1 1 unit 103 146.000
With guide frames, connecting flanges
I 630 630 66 B 3WL11 06-3@@48-.... 1 1 unit 103 84.000
I 800 800 66 B 3WL11 08-3@@48-.... 1 1 unit 103 84.000
I 1000 1000 66 B 3WL11 10-3@@48-.... 1 1 unit 103 84.000
I 1250 1250 66 B 3WL11 12-3@@48-.... 1 1 unit 103 84.000
I 1600 1600 66 B 3WL11 16-3@@48-.... 1 1 unit 103 84.000
II 800 800 80 B 3WL12 08-3@@48-.... 1 1 unit 103 109.000
II 1000 1000 80 B 3WL12 10-3@@48-.... 1 1 unit 103 109.000
II 1250 1250 80 B 3WL12 12-3@@48-.... 1 1 unit 103 109.000
II 1600 1600 80 B 3WL12 16-3@@48-.... 1 1 unit 103 109.000
II 2000 2000 80 B 3WL12 20-3@@48-.... 1 1 unit 103 109.000
II 2500 2500 80 B 3WL12 25-3@@48-.... 1 1 unit 103 123.000
II 3200 3200 80 B 3WL12 32-3@@48-.... 1 1 unit 103 136.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
For footnotes see page 1/22.
Size Max. rated circuit breaker Rated current1) Icu up to 100 kA at 500 V, PU PS*/ PG Weight
current In high switching capacity H H (UNIT, P. unit per PU
In max. Order No. Basic SET, approx.
Order No. supplements, price M)
see page 1/23 per PU
A A kA DT kg
Without guide frames
(for guide frames, see page 1/30 to 1/33)
II 800 800 100 B 3WL12 08-4@@45-.... 1 1 unit 103 72.000
II 1000 1000 100 B 3WL12 10-4@@45-.... 1 1 unit 103 72.000
II 1250 1250 100 B 3WL12 12-4@@45-.... 1 1 unit 103 72.000
II 1600 1600 100 B 3WL12 16-4@@45-.... 1 1 unit 103 72.000
II 2000 2000 100 B 3WL12 20-4@@45-.... 1 1 unit 103 72.000
II 2500 2500 100 B 3WL12 25-4@@45-.... 1 1 unit 103 76.000
II 3200 3200 100 B 3WL12 32-4@@45-.... 1 1 unit 103 82.000
III 4000 4000 100 B 3WL13 40-4@@45-.... 1 1 unit 103 106.000
III 5000 5000 100 B 3WL13 50-4@@45-.... 1 1 unit 103 106.000
III 6300 6300 100 B 3WL13 63-4@@45-.... 1 1 unit 103 108.000
With guide frames, horizontal main circuit connection
II 800 800 100 B 3WL12 08-4@@46-.... 1 1 unit 103 109.000
II 1000 1000 100 B 3WL12 10-4@@46-.... 1 1 unit 103 109.000
II 1250 1250 100 B 3WL12 12-4@@46-.... 1 1 unit 103 109.000
II 1600 1600 100 B 3WL12 16-4@@46-.... 1 1 unit 103 109.000
II 2000 2000 100 B 3WL12 20-4@@46-.... 1 1 unit 103 109.000
II 2500 2500 100 B 3WL12 25-4@@46-.... 1 1 unit 103 123.000
II 3200 3200 100 B 3WL12 32-4@@46-.... 1 1 unit 103 136.000
III 4000 4000 100 B 3WL13 40-4@@46-.... 1 1 unit 103 190.000
III 5000 5000 100 B 3WL13 50-4@@46-.... 1 1 unit 103 190.000
With guide frames, vertical main circuit connection
II 800 800 100 B 3WL12 08-4@@47-.... 1 1 unit 103 109.000
II 1000 1000 100 B 3WL12 10-4@@47-.... 1 1 unit 103 109.000
II 1250 1250 100 B 3WL12 12-4@@47-.... 1 1 unit 103 109.000
II 1600 1600 100 B 3WL12 16-4@@47-.... 1 1 unit 103 109.000
II 2000 2000 100 B 3WL12 20-4@@47-.... 1 1 unit 103 109.000
II 2500 2500 100 B 3WL12 25-4@@47-.... 1 1 unit 103 123.000
II 3200 3200 100 B 3WL12 32-4@@47-.... 1 1 unit 103 136.000
II 4000 4000 100 B 3WL12 40-4@@47-.... 1 1 unit 103 146.000
III 4000 4000 100 B 3WL13 40-4@@47-.... 1 1 unit 103 190.000
III 5000 5000 100 B 3WL13 50-4@@47-.... 1 1 unit 103 190.000
III 6300 6300 100 B 3WL13 63-4@@47-.... 1 1 unit 103 227.000
With guide frames, connecting flanges
II 800 800 100 B 3WL12 08-4@@48-.... 1 1 unit 103 109.000
II 1000 1000 100 B 3WL12 10-4@@48-.... 1 1 unit 103 109.000
II 1250 1250 100 B 3WL12 12-4@@48-.... 1 1 unit 103 109.000
II 1600 1600 100 B 3WL12 16-4@@48-.... 1 1 unit 103 109.000
II 2000 2000 100 B 3WL12 20-4@@48-.... 1 1 unit 103 109.000
II 2500 2500 100 B 3WL12 25-4@@48-.... 1 1 unit 103 123.000
II 3200 3200 100 B 3WL12 32-4@@48-.... 1 1 unit 103 136.000
III 4000 4000 100 B 3WL13 40-4@@48-.... 1 1 unit 103 190.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU15B: Protection functions LI6) BB ✓
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
For footnotes see page 1/22.
Size Max. rated circuit breaker Rated current1) Icu up to 130 kA at 500 V, PU PS*/ PG Weight
current In very high switching capacity C C (UNIT, P. unit per PU
In max. Order No. Basic SET, M) approx.
Order No. supplements, price
see page 1/23 per PU
A A kA DT kg
Without guide frames
(for guide frames, see page 1/30 to 1/33)
III 4000 4000 130 B 3WL13 40-5@@45-.... 1 1 unit 103 115.000
III 5000 5000 130 B 3WL13 50-5@@45-.... 1 1 unit 103 106.000
III 6300 6300 130 B 3WL13 63-5@@45-.... 1 1 unit 103 108.000
With guide frames, horizontal main circuit connection
III 4000 4000 130 B 3WL13 40-5@@46-.... 1 1 unit 103 190.000
III 5000 5000 130 B 3WL13 50-5@@46-.... 1 1 unit 103 190.000
With guide frames, vertical main circuit connection
III 4000 4000 130 B 3WL13 40-5@@47-.... 1 1 unit 103 190.000
III 5000 5000 130 B 3WL13 50-5@@47-.... 1 1 unit 103 190.000
III 6300 6300 130 B 3WL13 63-5@@47-.... 1 1 unit 103 227.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Electronic releases
Versions without ground-fault protection
ETU25B: Protection functions LSI CB ✓
ETU45B: Protection functions LSIN3) EB ✓
ETU45B: Protection functions LSIN3) with 4-line display FB ✓
ETU76B: Protection functions LSIN3) with pixel graphics display NB ✓
Versions with ground-fault protection
ETU27B: Protection functions LSING4) DG ✓
ETU45B: Protection functions LSING3)5) EG ✓
ETU45B: Protection functions LSING3)5) with 4-line display FG ✓
ETU76B: Protection functions LSING3)5) with pixel graphics display NG ✓
Standard Order No. supplements (for further Order No. supplements for circuit breakers and guide frames, see page 1/23)
Manual operating mechanism with mechanical closing
Without 1st and 2nd auxiliary releases; auxiliary switch 2 NC + 2 NO 1AA2 None
✓ Additional price
Footnotes for pages 1/19 to 1/22:
1) 3)
The rated current is determined by the rated current module. For the stan- Current transformers for protection of the N conductor and current trans-
dard version, the supplied module is equal to the maximum rated current. formers for detection of the ground-fault current in the grounded neutral
If a lower rated current is required, adaptation by order code on page 1/24. point of the transformer are to be ordered separately, see page 1/34. The
2)
For permissible rated short-time current Icc and rated short-circuit making internal current transformers for N conductors can be ordered by adding
capacity Icm for non-automatic air circuit breakers see page 1/3. the supplement "–Z" and the order code "F23", see page 1/26.
4)
Current transformers for protection of the N conductor are to be ordered
separately, see page 1/34.
5)
ETU45B to ETU76B with ground-fault protection module GFM AT (alarm
and tripping), see page 1/34.
6)
ETU15B cannot be used with 3WL circuit breakers, size III.
Add "–Z" to the complete Order No. and Order No. with "–Z" Additional price
indicate the appropriate order code(s). 1234 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . - . . . . . - . . . . - Z
and additional order code(s)
@@@+ . . . + . . .
Code for
"Further versions" -Z
Operating manuals
Printed version
In scope of supply of circuit breaker) French/Italian A 1 1 ✓
In scope of supply of circuit breaker) Spanish/Portuguese A 1 2 ✓
Rated voltage 1000 V AC/DC Add. Add.
Only for circuit breakers with high switching capacity H price price
(8th digit of the Order No. is a "4") 3-pole 4-pole
Cannot be combined with "Rated voltage 1150 V AC order code "A15".
Size II1) Up to 2000 A A 0 5 ✓ ✓
2500 A A 0 5 ✓ ✓
3200 A A 0 5 ✓ ✓
Size III1)2) 4000 A A 0 5 ✓ ✓
5000 A A 0 5 ✓ ✓
6300 A A 0 5 ✓ ✓
Rated voltage 1150 V AC
Only for circuit breakers with high switching capacity H
(8th digit of the Order No. is a "4")
Cannot be combined with "Rated voltage 1000 V AC order code "A05".
Size II Up to 2000 A A 1 5 ✓ ✓
2500 A A 1 5 ✓ ✓
3200 A A 1 5 ✓ ✓
4000 A A 1 5 ✓ ✓
For size III select a circuit breaker with very high switching capacity C,
which can be used as standard up to 1150 V AC.
Tinned version of the customer's connections
on the guide frame3)4)
Only for circuit breakers in withdrawable version with horizontal connection or
flange connection. The normal delivery time increases to 15 work days.
Size I A 0 8 ✓ ✓
Size II A 0 8 ✓ ✓
Size III A 0 8 ✓ ✓
Special packaging (moisture protection) Additional price
Special packaging for extended technical requirements
Cardboard packaging with water-repellent coating on corrugated cardboard A 6 1 ✓
(moisture protection)
Rated current modules / Rating plugs Additional price
Rated
current In
A
Only one module is possible per For size I, II 250 B 0 2 None
circuit breaker (not in conjunction 315 B 0 3 None
with electronic release ETU15B).
As standard the overcurrent 400 B 0 4 None
releases are equipped with a 500 B 0 5 None
rated current module which is
equal to the maximum rated cir- 630 B 0 6 None
cuit breaker current (In max). The 800 B 0 8 None
rated current of the selected
1000 B 1 0 None
rated current module must be
smaller than In max. For size I, II, III 1250 B 1 2 None
1600 B 1 6 None
For size II, III 2000 B 2 0 None
2500 B 2 5 None
3200 B 3 2 None
4000 B 4 0 None
For size III 5000 B 5 0 None
6300 B 6 3 None
✓ Additional price
1) If ordering withdrawable circuit breaker and guide frame separately,
specify order code "A05" for withdrawable circuit breaker and guide frame.
2) Not necessary for circuit breakers with very high switching capacity C as
these circuit breakers can be used as standard up to 1150 V AC.
3)
Front connections are tinned as standard.
4)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
Add "–Z" to the complete Order No. and Order No. with "–Z" Additional price
indicate the appropriate order code(s). 1234 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . - . . . . . - . . . . - Z
and additional order code(s)
@@@+. . . + . . .
Code for
"Further versions" -Z
Indication/operator control elements, door sealing frames
5-digit mechanical operating cycles counter1) C 0 1 ✓
Electrical ON button in the operator Button with sealing cap C 1 1 ✓
panel2) Key operation with lock CES C 1 2 ✓
Possible only for circuit breakers
with closing solenoid.
Storage status signaling switch 2) 1 NO contact C 2 0 ✓
(S21)
Ready-to-close signaling switch (S20) 1 NO contact C 2 2 ✓
Signaling switches2) For the first auxiliary release (S22) C 2 6 ✓
For the second auxiliary release (S23) C 2 7 ✓
Motor shutdown switch in the operator panel3) S 2 5 ✓
EMERGENCY-STOP pushbuttons Mushroom pushbutton instead of S 2 4 ✓
the mechanical OFF pushbutton
Door sealing frames T 4 0 ✓
Reclosing lockout and remote resets
Automatic reset of the reclosing lockout K 0 1 ✓
Tripped signaling switch2)4) 1 CO K 0 7 ✓
Remote reset solenoid for displays and reset buttons
including automatic reset of the reclosing lockout
50/60 Hz V AC V DC
-- 24 K 1 0 ✓
-- 48 K 1 1 ✓
120 125 K 1 2 ✓
208 ... 250 208 ... 250 K 1 3 ✓
Motorized operating mechanisms and closing/opening solenoids
Motorized operating mechanisms
Only possible if the 13th digit of the Order No. = "1"
Motor
50/60 Hz V AC V DC
-- 24 ... 30 M 0 1 ✓
-- 48 ... 60 M 0 3 ✓
110 ... 127 110 ... 125 M 0 5 ✓
208 ... 240 220 ... 250 M 0 6 ✓
Closing solenoid suitable for uninterrupted duty, 100 % duty ratio
Only possible if the 13th digit of the Order No. = "1"
Activation solenoids
50/60 Hz V AC V DC
-- 24 M2 1 ✓
-- 30 M2 2 ✓
-- 48 M2 3 ✓
-- 60 M2 4 ✓
110 110 M2 5 ✓
230 220 M2 6 ✓
Closing solenoids5) unsuitable for uninterrupted duty, 5 % duty ratio,
synchronizable
Only possible if the 13th digit of the Order No. = "1"
Activation solenoids
50/60 Hz V AC V DC
-- 24 M 3 1 ✓
-- 48 M 3 3 ✓
110 ... 127 110 ... 125 M 3 5 ✓
208 ... 240 220 ... 250 M 3 6 ✓
Opening solenoids (shunt release)6)7)
Not suitable for uninterrupted duty, 5% duty ratio, synchronizable
Activation solenoids
50/60 Hz V AC V DC
-- 24 M 4 1 ✓
-- 48 M 4 3 ✓
110 ... 127 110 ... 125 M 4 5 ✓
208 ... 240 220 ... 250 M 4 6 ✓
4)
✓ Additional price Not available for non-automatic air circuit breakers.
5)
1)
Only possible with motorized operating mechanism. Overexcited, i.e. opening time 50 ms (standard > 80 ms).
2) 6) Only possible if the 14th position of the Order No. for the circuit breaker is
Not possible with communications interface option, order code "F02" or "F12".
3) Only for circuit breakers with motorized operating mechanism, not possible "A", i.e. "without 1st auxiliary release".
7)
with order codes "C11", "C12". Overexcited, i.e. opening time 50 ms (standard > 80 ms).
Add "–Z" to the complete Order No. and Order No. mit "-Z" Additional
indicate the appropriate order code(s). 1234 5 6 7 8 9 10 11 12 13 14 15 16 price
3WL . . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@ + . . . + . . .
Code for
"Further versions" -Z
Order code Order code
for fixed- for with-
mounted drawable
version version
Interlocks, covers, position signaling switches @@@ @@@
Mutual mechanical
interlockings Fixed-mounted circuit breakers S 5 5 -- -- -- ✓
(interlocking module
with Bowden wire 2 m) For withdrawable circuit breakers -- R 5 5 ✓
with guide frame
1 CO 1 CO 1 CO -- R 1 5 ✓
3 CO 2 CO 1 CO -- R 1 6 ✓
Add "–Z" to the complete Order No. and Order No. with "–Z" Additional
indicate the appropriate order code(s). 1234 5 6 7 8 9 10 11 12 13 14 15 16 price
3WL . . . . - . . . . . - . . . . - Z
and additional order code(s)
@@@ +. . . + . . .
Code for
"Further versions" -Z
Communication and measurement functions
Breaker status sensor (BSS) F 0 1 ✓
PROFIBUS communications interface2) Including COM15 and breaker F 0 2 ✓
status sensor (BSS)
MODBUS communications interface2) Including COM16 and breaker F 1 2 ✓
status sensor (BSS)
Measurement function Plus (without PROFIBUS/MODBUS F 0 5 ✓
communications interface)3)
Overload and short-circuit protection for neutral conductors
Internal current transformers for Size I F 2 3 ✓
N conductors Size II F 2 3 ✓
Only possible with 4-pole circuit breakers
with ETU27B to ETU76B Size III F 2 3 ✓
EMC filters
EMC filters Common-mode interference F 3 1 ✓
suppressor filters (e.g. in IT net-
works, caused by frequency con-
verters)
Insertion loss (asymmetric) in the
range 40 kHz to 10 MHz >40 dB.
3)
✓ Additional price Additional voltage transformers are required for connection of the mea-
1)
Padlocks not included in scope of supply. surement function Plus, see page 1/43.
2)
If ordering withdrawable circuit breaker and guide frame separately, spec-
ify order code "F02" or "F12" for withdrawable circuit breaker only.
Add "–Z" to the complete Order No. Order No. mit "-Z"
and indicate the appropriate order code(s). 1234 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@ + . . . + . . .
Code for
"Further versions" -Z
Order code Add. price Order code Add. price
for fixed- for fixed- for with- for withdraw-
mounted mounted drawable able version
version version version
Locking devices @@@ @@@
To prevent movement -- R 5 0 ✓
with the cabinet door open
Connection methods for auxiliary conductors
Connections for screwless N 6 1 ✓ P 6 1 ✓
terminals (tension spring)
✓ Additional price
1)
Locks must be ordered from the manufacturer.
2)
Padlock not included in the scope of supply.
Add "–Z" to the complete Order No. and Order No. mit "-Z"
indicate the appropriate order code(s). 1234 5 6 7 8 9 10 11 12 13 14 15 16
3WL . . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@
+. . . + . . .
Code for
"Further versions" -Z
For withdrawable circuit breakers with guide frames Additional Additional
or for guide frames1) price price
3-pole 4-pole
To select this connection method the 12th
digit of the Order No. for the
circuit breaker must be a "6"
Connection methods for main connections
Top and bottom: Size I, up to 1600 A P 0 0 ✓ ✓
accessible from front, Size II, up to 2000 A P 0 0 ✓ ✓
single hole Size II, up to 2500 A P 0 0 ✓ ✓
Size II, up to 3200 A P 0 0 ✓ ✓
Size III, up to 4000 A P 0 0 ✓ ✓
Top and bottom: Size I, up to 1600 A P 0 1 ✓ ✓
accessible from front, Size II, up to 2000 A P 0 1 ✓ ✓
double hole Size II, up to 2500 A P 0 1 ✓ ✓
Size II, up to 3200 A P 0 1 ✓ ✓
Size III, up to 4000 A P 0 1 ✓ ✓
Top: Size I, up to 1600 A P 0 7 ✓ ✓
horizontal, Size II, up to 2000 A P 0 7 ✓ ✓
double hole Size II, up to 2500 A P 0 7 ✓ ✓
Bottom: Size II, up to 3200 A P 0 7 ✓ ✓
accessible from front, Size III, up to 4000 A P 0 7 ✓ ✓
single hole
Top: Size I, up to 1600 A P 1 8 ✓ ✓
vertical Size II, up to 2000 A P 1 8 ✓ ✓
Bottom: Size II, up to 2500 A P 1 8 ✓ ✓
horizontal Size II, up to 3200 A P 1 8 ✓ ✓
Size III, up to 4000 A P 1 8 ✓ ✓
Size III, up to 5000 A P 1 8 ✓ ✓
Top: Size I, up to 1600 A P 1 9 ✓ ✓
connecting flange Size II, up to 2000 A P 1 9 ✓ ✓
Bottom: Size II, up to 2500 A P 1 9 ✓ ✓
horizontal Size II, up to 3200 A P 1 9 ✓ ✓
Size III, up to 4000 A P 1 9 ✓ ✓
Top: Size I, up to 1600 A P 2 3 ✓ ✓
horizontal Size II, up to 2000 A P 2 3 ✓ ✓
Bottom: Size II, up to 2500 A P 2 3 ✓ ✓
vertical Size II, up to 3200 A P 2 3 ✓ ✓
Size III, up to 4000 A P 2 3 ✓ ✓
Size III, up to 5000 A P 2 3 ✓ ✓
For fixed-mounted circuit breakers Additional Additional
To select this connection method the 12th price price
digit of the Order No. for the 3-pole 4-pole
circuit breaker must be a "2"
Connection methods for main connections
Top: Size I, up to 1600 A N 1 1 ✓ ✓
horizontal Size II, up to 2000 A N 1 1 ✓ ✓
Bottom: Size II, up to 2500 A N 1 1 ✓ ✓
accessible from front, Size II, up to 3200 A N 1 1 ✓ ✓
single hole Size III, up to 4000 A N 1 1 ✓ ✓
Top: Size I, up to 1600 A N 2 0 ✓ ✓
vertical Size II, up to 2000 A N 2 0 ✓ ✓
Bottom: Size II, up to 2500 A N 2 0 ✓ ✓
horizontal Size II, up to 3200 A N 2 0 ✓ ✓
Size III, up to 4000 A N 2 0 ✓ ✓
Size III, up to 5000 A N 2 0 ✓ ✓
Top: Size I, up to 1600 A N 2 4 ✓ ✓
horizontal Size II, up to 2000 A N 2 4 ✓ ✓
Bottom: Size II, up to 2500 A N 2 4 ✓ ✓
vertical Size II, up to 3200 A N 2 4 ✓ ✓
Size III, up to 4000 A N 2 4 ✓ ✓
Size III, up to 5000 A N 2 4 ✓ ✓
✓ Additional price
1)
Only horizontal connection and vertical connection are available for circuit
breakers with very high switching capacity C.
■ Overview
Determination of the number of auxiliary supply connectors required
This selection is only required if the guide frame is ordered under a The required number of auxiliary supply connectors
separate Order No. depends on:
• Operating mechanism type
X6 X5 • Electronic release with/without current transformer
X7
• Type and number of auxiliary releases
NSE0_01104
Number of Terminal
auxiliary supply
connectors
a First auxiliary supply connector X6 always required. 1 X6
b Operating mechanisms
b1 Manual operating mechanism with stored-energy feature with mechanical closing 0
b2 Manual operating mechanism with stored-energy feature with mechanical and electrical closing 0 X6
b3 Manual/motorized operating mechanism with stored-energy feature with mechanical and electrical closing +1 X5
c Electronic releases
c1 Electronic releases ETU15B, ETU25B, ETU27B 0
c2 Electronic releases ETU45B, ETU76B (internal CubicleBUS) +1 X8
Connections for external current transformers for overload protection in the N conductor and ground-fault protection
c3 Current transformer installed in the N conductor (required with 3-pole circuit breakers if c2 is not selected) +1 X8
c4 Current transformer in the neutral point of the transformer (required if c2 or c3 is not selected) +1 X8
d Auxiliary releases
d1 With/without 1st auxiliary release (shunt release F1) 0 X6
d2 2nd auxiliary release (shunt release F2, undervoltage release F3, delayable undervoltage release F4) +1 X5
e Auxiliary switch blocks
e1 1st auxiliary switch block 2 NO + 2 NC 0 X6
e2 1st and 2nd auxiliary switch block 4 NO + 4 NC or 6 NO + 2 NC or 5 NO + 3 NC (required if b3 or d2 is not selected) +1 X5
f Communication modules
f1 Without communication module COM15/COM16 0
f2 With communication module COM15/COM16 – +1 X7
occupies the entire terminal strip X7, making the following options no longer possible:
• Tripped signal switch S24
• Stored-energy status indication S21
• Electrical ON button S10
• Signaling switch on first and second auxiliary release S22 + S23
g Optional signals/accessories
g1 Tripped signaling switch S24 (only when f2 not selected) +1 X7
g2 Stored energy status signaling switch S21 (only when f2 not selected, required if g1 not selected) +1 X7
g3 Electric ON button S10 (only when f2 not selected, required if g1 or g2 not selected) +1 X7
g4 Signaling switch at first auxiliary release S22 (only when f2 not selected, required if g1, g2 or g3 not selected) +1 X7
g5 Signaling switch at second auxiliary release S23 (only when f2 not selected, required if g1, g2, g3 or g4 not selected) +1 X7
g6 Switch on readiness signal switch S20 0 X6
g7 Motor shutdown switch S12 (only if motorized operating mechanism selected) 0 X5
g8 Remote reset solenoid F7 (required if c2 not selected) +1 X8
h Total number of auxiliary supply connectors (max. 4)
For ordering the auxiliary supply connectors see under "Accessories and Spare Parts, Guide Frames for AC Circuit Breakers/
Non-Automatic Air Circuit Breakers", pages 1/30 to 1/33 and under "Accessories and Spare Parts, Auxiliary Conductor Connections,
Auxiliary Supply Connectors", page 1/39.
Size Max. rated circuit breaker Switching DT Guide frames for 3-pole circuit breakers/ PU PS*/ PG Weight
current capacity non-automatic air circuit breakers (UNIT, P. unit per PU
In max. Icu Order No. Basic SET, approx.
(Order No. supplements price M)
required acc. to table below) per PU
A kA kg
Vertical main circuit connection
I 1000 ... 66 B 3WL9 211-1AD@@-@@A1 1 1 unit 103 25.000
I 1600 ... 66 B 3WL9 211-2AD@@-@@A1 1 1 unit 103 25.000
II 2000 ... 100 B 3WL9 212-3AD@@-@@A1 1 1 unit 103 31.000
II 2500 ... 100 B 3WL9 212-4AD@@-@@A1 1 1 unit 103 39.000
II 3200 ... 100 B 3WL9 212-5AD@@-@@A1 1 1 unit 103 45.000
II 4000 ... 100 B 3WL9 212-6AD@@-@@A1 1 1 unit 103 52.000
III 4000 ... 100 B 3WL9 213-6AD@@-@@A1 1 1 unit 103 60.000
III 5000 ... 100 B 3WL9 213-7AD@@-@@A1 1 1 unit 103 60.000
III 6300 ... 100 B 3WL9 213-8AD@@-@@A1 1 1 unit 103 70.000
III 4000 ... 150 B 3WL9 213-6AD@@-@@C1 1 1 unit 103 63.000
III 5000 ... 150 B 3WL9 213-7AD@@-@@C1 1 1 unit 103 63.000
III 6300 ... 150 B 3WL9 213-8AD@@-@@C1 1 1 unit 103 74.000
Main circuit connection connecting flanges
I 1000 ... 66 B 3WL9 211-1AE@@-@@A1 1 1 unit 103 25.000
I 1600 ... 66 B 3WL9 211-2AE@@-@@A1 1 1 unit 103 25.000
II 2000 ... 100 B 3WL9 212-3AE@@-@@A1 1 1 unit 103 31.000
II 2500 ... 100 B 3WL9 212-4AE@@-@@A1 1 1 unit 103 39.000
II 3200 ... 100 B 3WL9 212-5AE@@-@@A1 1 1 unit 103 45.000
III 4000 ... 100 B 3WL9 213-6AE@@-@@A1 1 1 unit 103 60.000
Number of auxiliary supply connectors Order No. supplements Add. price
Without 0 None
1 connector 1 ✓
2 connectors 2 ✓
3 connectors 3 ✓
4 connectors 4 ✓
For required number of auxiliary supply connectors,
see table on page 1/29
Type of auxiliary circuit connections
Without 0 None
With screw connection (SIGUT, standard) 1 ✓
With screwless connection method (tension spring) 2 ✓
Position signaling switches
Without 0 None
Option 1 Connected position 1 CO, 1 ✓
test position 1 CO,
disconnected position 1 CO
Option 2 Connected position 3 CO, 2 ✓
test position 2 CO,
disconnected position 1 CO
Shutters
Without A None
With shutter, Size I B ✓
2-part, Size II ✓
lockable Size III ✓
1234 5 6 7 8 9 10 11 12 13 14 15 16
Add "–Z" to the complete Order No. Order No. with "–Z" Additional
and indicate the appropriate order code(s). and additional order code 3WL9 2 1 . – . . . . . – . . . . –Z price
@@@
Rated voltage 1000 V AC
Size II, except 4000 A (switching capacity H) A05 ✓
Size III, not necessary with circuit breakers with very high switching capacity A 0 5 ✓
Rated voltage 1150 V AC
Size II, except 4000 A (switching capacity H) A15 ✓
Tinned version of the customer's connections on the guide frame1)2)
Only for guide frames with horizontal connection or flange connection
Size I A08 ✓
Size II A08 ✓
Size III A08 ✓
For main circuit connection front, single hole, main circuit connection front, double hole, and main circuit connection horizontal see
the previous page.
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see pages 1/24 to 1/28.
✓ Additional price
1)
Front connections are tinned as standard.
2)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
Size Max. rated circuit breaker Switching DT Guide frames for 4-pole circuit breakers/ PU PS*/ PG Weight
current capacity non-automatic air circuit breakers (UNIT, P. unit per PU
In max. Icu Order No. Basic SET, approx.
(Order No. supplements price M)
required acc. to table below) per PU
A kA kg
Front main circuit connection, single hole
I 1000 ... 66 B 3WL9 211-1BA@@-@@A1 1 1 unit 103 30.000
I 1600 ... 66 B 3WL9 211-2BA@@-@@A1 1 1 unit 103 30.000
II 2000 ... 100 B 3WL9 212-3BA@@-@@A1 1 1 unit 103 37.000
II 2500 ... 100 B 3WL9 212-4BA@@-@@A1 1 1 unit 103 47.000
II 3200 ... 100 B 3WL9 212-5BA@@-@@A1 1 1 unit 103 54.000
III 4000 ... 100 B 3WL9 213-6BA@@-@@A1 1 1 unit 103 84.000
Front main circuit connection, double hole
I 1000 ... 66 B 3WL9 211-1BB@@-@@A1 1 1 unit 103 30.000
I 1600 ... 66 B 3WL9 211-2BB@@-@@A1 1 1 unit 103 30.000
II 2000 ... 100 B 3WL9 212-3BB@@-@@A1 1 1 unit 103 37.000
II 2500 ... 100 B 3WL9 212-4BB@@-@@A1 1 1 unit 103 47.000
II 3200 ... 100 B 3WL9 212-5BB@@-@@A1 1 1 unit 103 54.000
III 4000 ... 100 B 3WL9 213-6BB@@-@@A1 1 1 unit 103 84.000
Horizontal main circuit connection
I 1000 ... 66 B 3WL9 211-1BC@@-@@A1 1 1 unit 103 30.000
I 1600 ... 66 B 3WL9 211-2BC@@-@@A1 1 1 unit 103 30.000
II 2000 ... 100 B 3WL9 212-3BC@@-@@A1 1 1 unit 103 37.000
II 2500 ... 100 B 3WL9 212-4BC@@-@@A1 1 1 unit 103 47.000
II 3200 ... 100 B 3WL9 212-5BC@@-@@A1 1 1 unit 103 54.000
III 4000 ... 100 B 3WL9 213-6BC@@-@@A1 1 1 unit 103 84.000
III 5000 ... 100 B 3WL9 213-7BC@@-@@A1 1 1 unit 103 84.000
III 4000 ... 130 B 3WL9 213-6BC@@-@@C1 1 1 unit 103 87.000
III 5000 ... 130 B 3WL9 213-7BC@@-@@C1 1 1 unit 103 87.000
Number of auxiliary supply connectors Order No. supplements Add. price
Without 0 None
1 connector 1 ✓
2 connectors 2 ✓
3 connectors 3 ✓
4 connectors 4 ✓
For required number of auxiliary supply connectors,
see table on page 1/29
Type of auxiliary circuit connections
Without 0 None
With screw connection (SIGUT, standard) 1 ✓
With screwless connection method (tension spring) 2 ✓
Position signaling switches
Without 0 None
Option 1 Connected position 1 CO, 1 ✓
test position 1 CO,
disconnected position 1 CO
Option 2 Connected position 3 CO, 2 ✓
test position 2 CO,
disconnected position 1 CO
Shutters
Without A None
With shutter, Size I B ✓
2-part, Size II ✓
lockable Size III ✓
1234 5 6 7 8 9 10 11 12 13 14 15 16
Add "–Z" to the complete Order No. Order No. with "–Z" Additional
and indicate the appropriate order code(s). and additional order code 3WL9 2 1 . – . . . . . – . . . . –Z price
@@@
Rated voltage 1000 V AC
Size II, except 4000 A (switching capacity H) A05 ✓
Size III, not necessary with circuit breakers with very high switching capacity A 0 5 ✓
Rated voltage 1150 V AC
Size II, except 4000 A (switching capacity H) A15 ✓
Tinned version of the customer's connections on the guide frame1)2)
Only for guide frames with horizontal connection or flange connection
Size I A08 ✓
Size II A08 ✓
Size III A08 ✓
For main circuit connection vertical and main circuit connecting flange see the following page.
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see pages 1/24 to 1/28.
✓ Additional price
1)
Front connections are tinned as standard.
2)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
Size Max. rated circuit breaker Switching DT Guide frames for 4-pole circuit breakers/ PU PS*/ PG Weight
current capacity non-automatic air circuit breakers (UNIT, P. unit per PU
In max. Icu Order No. Basic SET, approx.
(Order No. supplements price M)
A kA required acc. to per PU kg
table below)
Vertical main circuit connection
I 1000 ... 66 B 3WL9 211-1BD@@-@@A1 1 1 unit 103 30.000
I 1600 ... 66 B 3WL9 211-2BD@@-@@A1 1 1 unit 103 30.000
II 2000 ... 100 B 3WL9 212-3BD@@-@@A1 1 1 unit 103 37.000
II 2500 ... 100 B 3WL9 212-4BD@@-@@A1 1 1 unit 103 47.000
II 3200 ... 100 B 3WL9 212-5BD@@-@@A1 1 1 unit 103 54.000
II 4000 ... 100 B 3WL9 212-6BD@@-@@A1 1 1 unit 103 62.000
III 4000 ... 100 B 3WL9 213-6BD@@-@@A1 1 1 unit 103 84.000
III 5000 ... 100 B 3WL9 213-7BD@@-@@A1 1 1 unit 103 84.000
III 6300 ... 100 B 3WL9 213-8BD@@-@@A1 1 1 unit 103 119.000
III 4000 ... 130 B 3WL9 213-6BD@@-@@C1 1 1 unit 103 88.000
III 5000 ... 130 B 3WL9 213-7BD@@-@@C1 1 1 unit 103 88.000
III 6300 ... 130 B 3WL9 213-8BD@@-@@C1 1 1 unit 103 124.000
Main circuit connection connecting flanges
I 1000 ... 66 B 3WL9 211-1BE@@-@@A1 1 1 unit 103 30.000
I 1600 ... 66 B 3WL9 211-2BE@@-@@A1 1 1 unit 103 30.000
II 2000 ... 100 B 3WL9 212-3BE@@-@@A1 1 1 unit 103 37.000
II 2500 ... 100 B 3WL9 212-4BE@@-@@A1 1 1 unit 103 47.000
II 3200 ... 100 B 3WL9 212-5BE@@-@@A1 1 1 unit 103 54.000
III 4000 ... 100 B 3WL9 213-6BE@@-@@A1 1 1 unit 103 84.000
Number of auxiliary supply connectors Order No. supplements Add. price
Without 0 None
1 connector 1 ✓
2 connectors 2 ✓
3 connectors 3 ✓
4 connectors 4 ✓
For required number of auxiliary supply connectors,
see table on page 1/29
Type of auxiliary circuit connections
Without 0 None
With screw connection (SIGUT, standard) 1 ✓
With screwless connection method (tension spring) 2 ✓
Position signaling switches
Without 0 None
Option 1 Connected position 1 CO, 1 ✓
test position 1 CO,
disconnected position 1 CO
Option 2 Connected position 3 CO, 2 ✓
test position 2 CO,
disconnected position 1 CO
Shutters
Without A None
With shutter, Size I B ✓
2-part, Size II ✓
lockable Size III ✓
1234 5 6 7 8 9 10 11 12 13 14 15 16
Add "–Z" to the complete Order No. Order No. with "–Z" Additional
and indicate the appropriate order code(s). and additional order code 3WL9 2 1 . – . . . . . – . . . . –Z price
@@@
Rated voltage 1000 V AC
Size II, except 4000 A (switching capacity H) A05 ✓
Size III, not necessary with circuit breakers with very high switching capacity A 0 5 ✓
Rated voltage 1150 V AC
Size II, except 4000 A (switching capacity H) A15 ✓
Tinned version of the customer's connections on the guide frame1)2)
Only for guide frames with horizontal connection or flange connection
Size I A08 ✓
Size II A08 ✓
Size III A08 ✓
For main circuit connection front, single hole, main circuit connection front, double hole, and main circuit connection horizontal see
the previous page.
All other accessory parts must be ordered by specifying "–Z" and the corresponding order code, see pages 1/24 to 1/28.
✓ Additional price
1)
Front connections are tinned as standard.
2)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
function Plus
ETU76B LSIN(G) Without C 3WL9 317-6AA00-0AA2 1 1 unit 103 0.720
With measurement B 3WL9 317-6AA20-0AA2 1 1 unit 103 0.720
3WL9 31.-.AA.0-0AA1 function Plus
Rated current modules / Rating plugs2)
For size Rated current In (A)
= 3 2 0 0 A
I, II 250 B 3WL9 111-0AA51-0AA0 1 1 unit 103 0.010
n
315 B 3WL9 111-0AA52-0AA0 1 1 unit 103 0.010
N S E 0 _ 0 0 9 9 2 b
400 B 3WL9 111-0AA53-0AA0 1 1 unit 103 0.010
500 B 3WL9 111-0AA54-0AA0 1 1 unit 103 0.010
3WL9 111-0AA64-0AA0
630 B 3WL9 111-0AA55-0AA0 1 1 unit 103 0.010
800 B 3WL9 111-0AA56-0AA0 1 1 unit 103 0.010
1000 B 3WL9 111-0AA57-0AA0 1 1 unit 103 0.010
I, II, III 1250 B 3WL9 111-0AA58-0AA0 1 1 unit 103 0.010
1600 B 3WL9 111-0AA61-0AA0 1 1 unit 103 0.010
II, III 2000 B 3WL9 111-0AA62-0AA0 1 1 unit 103 0.010
2500 B 3WL9 111-0AA63-0AA0 1 1 unit 103 0.010
3200 B 3WL9 111-0AA64-0AA0 1 1 unit 103 0.010
4000 B 3WL9 111-0AA65-0AA0 1 1 unit 103 0.010
III 5000 B 3WL9 111-0AA66-0AA0 1 1 unit 103 0.010
6300 B 3WL9 111-0AA67-0AA0 1 1 unit 103 0.010
Ground-fault modules3)
S I
G F M A T 4 5 B GFM AT 45B (only for ETU45B) alarm and tripping B 3WL9 111-0AT53-0AA0 1 1 unit 103 0.030
g T R IP A L A R M A L A R M t g (s ) I 2 tg
G A
B
C T R IP
.5
.4
.3
.1
.2
.3
GFM AT 55B–76B (only for ETU76B) alarm and tripping B 3WL9 111-0AT56-0AA0 1 1 unit 103 0.030
D .2 .4
O F F E .1 .5
N S E 0 _ 0 1 0 2 7 a
3WL9 111-0AT53-0AA0
Displays
4-line displays for ETU45B B 3WL9 111-0AT81-0AA0 1 1 unit 103 0.060
N S E 0 _ 0 1 6 0 9
3WL9 111-0AT81-0AA0
Current transformers for N conductor protection
Internal transformers for N conductors Size I B 3WL9 111-0AA11-0AA0 1 1 unit 103 0.200
(not for ETU Release 2) Size II B 3WL9 111-0AA12-0AA0 1 1 unit 103 0.280
Including wiring kit Size III B 3WL9 111-0AA13-0AA0 1 1 unit 103 0.500
Internal transformers for N conductors Size I B 3WL9 111-0AA14-0AA0 1 1 unit 103 0.200
Only for ETU Release 2 Size II B 3WL9 111-0AA15-0AA0 1 1 unit 103 0.280
N S E 0 _ 0 0 9 9 0 a Including wiring kit Size III B 3WL9 111-0AA16-0AA0 1 1 unit 103 0.500
3WL9 111-0AA2.-0AA0 External transformers for N conductors Size I B 3WL9 111-0AA21-0AA0 1 1 unit 103 0.300
(for T5, "Measurement Method" function Size II B 3WL9 111-0AA22-0AA0 1 1 unit 103 0.380
see Technical Information at Size III B 3WL9 111-0AA23-0AA0 1 1 unit 103 0.680
www.siemens.com/lowvoltage/support.
External transformers for N conductors Size I B 3WL9 111-0AA31-0AA0 1 1 unit 103 1.600
with copper connection pieces Size II B 3WL9 111-0AA32-0AA0 1 1 unit 103 4.260
(for T5, "Measurement Method" function Size III B 3WL9 111-0AA33-0AA0 1 1 unit 103 8.500
N S E 0 _ 0 0 9 9 1 a
see Technical Information at
3WL9 111-0AA3.-0AA0 www.siemens.com/lowvoltage/support.
EMC filters
EMC filters Not for B 3WL9 111-0AK32-0AA0 1 1 unit 103 0.280
Common-mode interference suppressor ETU Release 2
filters (e.g. in IT networks, caused by fre- Only for ETU B 3WL9 111-0AK34-0AA0 1 1 unit 103 0.280
quency converters) Release 2
Insertion loss (asymmetric) in the range
40 kHz to 10 MHz >40 dB.
1) 3)
For replacement in existing circuit breakers please specify the circuit For direct measurement of the ground-fault current, e.g. in the neutral point
breaker ID No. when ordering. of the transformer, a 1200 A/1 A current transformer, class 1, is required.
2)
With the rated current module selected, the maximum rated The internal load of the SENTRON 3WL is 0.11 m. If the ground-fault cur-
current In max of the circuit breaker must not be exceeded. rent is to be determined using the vectorial sum of the phases, a current
The following applies In ≤ In max. transformer must be installed in the neutral conductor.
ETU45B
For ETU76 B 3WL9 111-0AT46-0AA0 1 1 unit 103 0.050
ETU25B Automatic reset of the reclosing lockout B 3WL9 111-0AK21-0AA0 1 1 unit 103 0.050
Spare part for option K01, see "-Z" + order code, page 1/25.
Remote reset solenoids1) 24 V DC B 3WL9 111-0AK03-0AA0 1 1 unit 103 0.200
For mechanical tripped indicator 48 V DC B 3WL9 111-0AK04-0AA0 1 1 unit 103 0.200
Spare part for option K10 to K13, 120 V AC/ B 3WL9 111-0AK05-0AA0 1 1 unit 103 0.200
see "-Z" + order code, page 1/25. 125 V DC
208-250 V AC/ B 3WL9 111-0AK06-0AA0 1 1 unit 103 0.200
3WL9 111-0AT45-0AA0 208-250 V DC
F 7 Retrofittable internal CubicleBUS For ETU45B and B 3WL9 111-0AK30-0AA0 1 1 unit 103 0.150
wiring for connection to terminal X8 ETU76B
(without male connector2))
Retrofittable internal wiring for connection of the D 3WL9 111-0AK31-0AA0 1 1 unit 103 0.020
external N- and G-transformers to terminal X8
(without male connector, not for ETU Release 2)
Retrofittable internal wiring for connection of the D 3WL9 111-0AK33-0AA0 1 1 unit 103 0.020
N S E 0 _ 0 0 9 9 9 a
external N- and G-transformers to terminal X8
3WL9 111-0AK0.-0AA0 for ETU Release 2 (without male connector)
Locking devices
Interlocking set for Without safety B 3WL9 111-0BA21-0AA0 1 1 unit 103 0.100
mechanical ON/OFF lock
Consisting of 2 transparent covers each Made by CES B 3WL9 111-0BA22-0AA0 1 1 unit 103 0.300
for sealing or for attaching padlocks4),
cover with 6.35 mm hole (for tool actua- Made by IKON B 3WL9 111-0BA24-0AA0 1 1 unit 103 0.300
tion), lock mount for safety lock for key
operation
NSE00980
Locking devices against Assembly kit B 3WL9 111-0BA31-0AA0 1 1 unit 103 0.200
unauthorized closing, FORTRESS or
in the operator panels CASTELL3)
3WL9 111-0BA22-0AA0
The disconnector unit fulfills the ■ Made by Ronis B 3WL9 111-0BA33-0AA0 1 1 unit 103 0.400
requirements for main circuit breakers Made by KIRK- B 3WL9 111-0BA34-0AA0 1 1 unit 103 0.270
acc. to EN 60204-1 Key3)
Spare part for option S01 to S09, Made by Profalux B 3WL9 111-0BA35-0AA0 1 1 unit 103 0.250
see "-Z" + order code, page 1/27. Made by CES B 3WL9 111-0BA36-0AA0 1 1 unit 103 0.200
Made by IKON B 3WL9 111-0BA38-0AA0 1 1 unit 103 0.200
Assembly kit for B 3WL9 111-0BA41-0AA0
NSE00981 padlocks4) 1 1 unit 103 0.360
Locking devices against Made by CES B 3WL9 111-0BA51-0AA0 1 1 unit 103 0.300
unauthorized closing, Made by IKON B 3WL9 111-0BA53-0AA0 1 1 unit 103 0.300
for withdrawable circuit breakers ■ Made by KIRK- B 3WL9 111-0BA57-0AA0 1 1 unit 103 0.300
3WL9 111-0BA31-0AA0 The disconnector unit fulfills the require- Key3)
ments for main circuit breakers acc. to Made by Ronis B 3WL9 111-0BA58-0AA0 1 1 unit 103 0.300
EN 60204-1 consisting of lock in the Made by Profalux B 3WL9 111-0BA50-0AA0 1 1 unit 103 0.227
cabinet door, active in connected
position; function is retained when circuit
breaker is replaced
NSE0_00982
Spare part for option R60, R61, R68,
3WL9 111-0BA53-0AA0 see "-Z" + order code, page 1/27.
Locking devices for operating mecha- B 3WL9 111-0BA71-0AA0 1 1 unit 103 0.080
nism handle with padlock4)
Spare part for option S33,
see "-Z" + order code, page 1/27.
Locking devices against movement of Made by CES B 3WL9 111-0BA73-0AA0 1 1 unit 103 0.300
the withdrawable circuit breakers Made by IKON B 3WL9 111-0BA75-0AA0 1 1 unit 103 0.200
Safety lock for mounting on the circuit Made by Profalux B 3WL9 111-0BA76-0AA0 1 1 unit 103 0.300
breaker. Made by Ronis B 3WL9 111-0BA77-0AA0 1 1 unit 103 0.300
Spare part for option S71, S75, S76, ■ Made by KIRK- B 3WL9 111-0BA80-0AA0 1 1 unit 103 0.400
NSE00984 see "-Z" + order code, page 1/27. Key3)
3WL9 111-0BA71-0AA0 Interlocking systems Made by CES B 3WL9 111-0BA43-0AA0 1 1 unit 103 0.360
2 of the same keys for 3 circuit breakers,
locking device OFF position,
key-operated switch on operator panel.
A maximum of 2 circuit breakers can be
switched on.
NSE0_00986
3WL9 111-0BA76-0AA0
1) 3)
Can only be used in conjunction with "automatic reset of the reclosing lock- Locks, cylinders and keys must be ordered from the manufacturer.
4)
out", e.g. "–Z" + "K01", 3WL9 111-0AK21-0AA0. Padlock not included in the scope of supply.
2)
Required if communication is retrofitted. ■ Start of delivery on request.
NSE00985
3WL9 111-0BA72-0AA0
1) 3)
Not possible with communications interface option, order code "F02" or Only in conjunction with motorized operating mechanism.
"F12". 4)
Not possible with motor shutdown switch.
2)
X7 manual connector required for circuit breakers or guide frames. If this is 5)
Not possible with electrical ON button.
not already available, please order additionally
(see pages 1/29 and 1/39).
Extension for the 1000 V male connector B 3WL9 111-0AB02-0AA0 1 1 unit 103 0.150
versions
(male connector must be ordered separately)
3WL9 111-0AB01-0AA0
Male connectors and extension for 1000 V B 3WL9 111-0AB10-0AA0 1 1 unit 103 1.000
N S E 0 _ 0 1 2 6 8
Auxiliary supply connec- Screw connection B 3WL9 111-0AB03-0AA0 1 1 unit 103 0.070
tors for circuit breakers or (SIGUT)
guide frames % Screwless connec- B 3WL9 111-0AB04-0AA0 1 1 unit 103 0.070
3WL9 111-0AB03-0AA0 tion method (tension
spring)
N S E 0 _ 0 1 2 6 9
3WL9 111-0AB04-0AA0
Coding kits for fixed-mounted version (X5 to X8) B 3WL9 111-0AB07-0AA0 1 1 unit 103 0.020
&
NSE00974
3WL9 111-0AB07-0AA0
Sliding contact modules for guide frames ( B 3WL9 111-0AB08-0AA0 1 1 unit 103 0.100
7 a
9 7
0 0
E 0 _
N S
3WL9 111-0AB08-0AA0
One-part sliding contact modules for guide B 3WL9 111-0AB18-0AA0 1 1 unit 103 0.120
frames Screw connection (SIGUT) )
NSE0_01586
3WL9 111-0AB18-0AA0
Blanking blocks for circuit breakers B 3WL9 111-0AB12-0AA0 1 1 unit 103 0.030
110 ... 125 V DC/110 ... 127 V AC B 3WL9 111-0AF03-0AA0 1 1 unit 103 1.510
220 ... 250 V DC/208 ... 240 V AC B 3WL9 111-0AF04-0AA0 1 1 unit 103 1.510
N S E 0 _ 0 1 0 0 3 a
3WL9 111-0AF0.-0AA0
Auxiliary contacts
Auxiliary switch blocks 2 NO + 2 NC B 3WL9 111-0AG01-0AA0 1 1 unit 103 0.180
2 NO B 3WL9 111-0AG02-0AA0 1 1 unit 103 0.080
1 NO + 1 NC B 3WL9 111-0AG03-0AA0 1 1 unit 103 0.070
NSE0_01004
3WL9 111-0AG03-0AA0
1)
Overexcited, i.e. opening time 50 ms (standard > 80 ms).
2)
X7 manual connector required for circuit breakers or guide frames. If this is
not already available, please order additionally (see pages 1/29 and 1/39).
3WL9 111-0AP0.-0AA0
Arc chute
Arc chute
690 V Size I B 3WL9 111-0AS01-0AA0 1 1 unit 103 1.110
Size II B 3WL9 111-0AS02-0AA0 1 1 unit 103 1.680
Size III B 3WL9 111-0AS03-0AA0 1 1 unit 103 2.980
NSE0_01007
NSE0_01009
3WL9 111-0AR12-0AA0
1)
Not available for
- 1000-V version (order code "A05"),
- 1150-V version (order code "A15"),
- DC version,
- 4000 A size II,
- circuit breaker with very high switching capacity C.
3WL9 111-0BB50-0AA0
1)
For 60 kA ground short-circuit current, order 2.
2)
Can also be used for size II, 4000 A.
N S E 0 _ 0 1 0 2 3 a
3WL9 111-0AT23-0AA0
Parameterization systems
Breaker Data Parameterization, operation, monitoring and B 3WL9 111-0AT28-0AA0 1 1 unit 103 0.900
Adapters diagnostics of SENTRON circuit breakers
(BDA)2) using the local interface; Breaker Data
Adapter, connection cable to the SENTRON
3WL circuit breaker and to the programming
device (e.g. notebook); can be run with
Internet Explorer with JAVA2 VM 1.4.0-01 and
higher
BDA Plus2)3) Same as BDA, but with additional Ethernet B 3WL9 111-0AT33-0AA0 1 1 unit 103 1.200
interface for connection to Ethernet/Intranet/
Internet
Connection Connection cable for connection of BDA Plus B 3WL9 111-0BC21-0AA0 1 1 unit 103 0.350
N S E 0 _ 0 1 0 2 4 a
cables for to terminal X8 of the SENTRON 3WL circuit
BDA Plus breaker. Required if neither COM15 nor
3WL9 111-0AT28-0AA0 COM16 nor other external CubicleBUS
modules are available, length 2 m.
Switch ES Calibration, operation, monitoring, and diag- A 3ZS2 311-0CC10-0YA0 1 1 unit 133 0.200
Power nostics of SENTRON circuit breakers via
parameter- PROFIBUS DP; runs under Windows 95,
ization Windows 98, Windows NT, Windows 2000 and
software Windows XP Professional, requires additional
PROFIBUS card e.g. CP5613
Accessories for communications
Preassem- 0.2 m long, for connection to SENTRON 3WL B 3WL9 111-0BC04-0AA0 1 1 unit 103 0.020
bled with COM15/COM16
cables for 1 m long, for connection to SENTRON 3WL B 3WL9 111-0BC02-0AA0 1 1 unit 103 0.050
CubicleBUS with COM15/COM16
modules
2 m long, for connection to SENTRON 3WL B 3WL9 111-0BC03-0AA0 1 1 unit 103 0.060
with COM15/COM16
2 m long, for connection to SENTRON 3WL B 3WL9 111-0BC05-0AA0 1 1 unit 103 0.070
without COM15/COM16
SENTRON Detailed description of the communication
manuals for functions for SENTRON circuit breakers.
communica- Installation, connection, commissioning, data
tion solu- transmission to the PLC, including description
tions of Switch ES Power and BDA.
PROFIBUS, German, token fee A5E0151347
PROFIBUS, English, token fee A5E0151353
MODBUS, German, token fee
MODBUS, English, token fee Z 3ZX10 12-0WL10-1AB1
3ZX10 12-0WL10-1AC1
Free download from:
www.siemens.com/lowvoltage/manuals
Voltage 380 ... 690 V/100 V, class 0.5 B 3WL9 111-0BB68-0AA0 1 1 unit 103 2.600
transformers,
3-pole, for
SENTRON
3WL with
measurement
function
Plus4)
All communication components, CubicleBUS modules and measurement functions are available for the ETU45B and ETU76B releases.
1) 3)
Each CubicleBUS module is supplied with a 0.2 m factory-fitted cable to Operation under Windows Vista and Windows 7 on request.
connect the modules with each other. A longer factory-fitted cable is 4)
Is required for operation of the measurement function Plus.
required for connection to the circuit breaker.
2)
A 24 V DC power supply unit is required.
All communication components, CubicleBUS modules and measurement functions are available for the ETU45B and ETU76B releases.
1)
A measuring accuracy of 3 % is reached if retrofitted.
3WL9 111-0AM03-0AA0
1)
In the case of vertical connection size I, up to 1000 A
one 3WL9 111–0AM01-0AA0 vertical connection is required,
up to 1600 A two 3WL9 111-0AM01-0AA0 vertical connections are
required.
2)
In the case of vertical connection size II, up to 2500 A
one 3WL9 111–0AM02-0AA0 vertical connection is required,
up to 3200 A two 3WL9 111-0AM02-0AA0 vertical connections are
required.
3WL9 111-0AN14-0AA0
Supports
for front and DIN
connecting bars
3-pole for 3 bars Size I B 3WL9 111-0AN41-0AA0 1 1 unit 103 0.700
Size II B 3WL9 111-0AN42-0AA0 1 1 unit 103 1.350
Size III B 3WL9 111-0AN43-0AA0 1 1 unit 103 2.420
Schematics in as-supplied state Version Size DT Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
SET, approx.
M)
kg
Withdrawable short-circuiting, grounding and bridging units
Top and 3-pole
bottom
NSE0_01118
Up to 1600 A I C 3WL9 111-0BD01-0AA0 1 1 unit 103 30.000
parts of
system are Up to 3200 A II C 3WL9 111-0BD03-0AA0 1 1 unit 103 40.500
L1 L2 L3 short- Up to 6300 A III C 3WL9 111-0BD05-0AA0 1 1 unit 103 65.000
circuited
and
NSE0_01113
grounded 4-pole
Up to 1600 A I C 3WL9 111-0BD02-0AA0 1 1 unit 103 35.000
NSE0_01119
(as-supplied state)
Up to 3200 A II C 3WL9 111-0BD04-0AA0 1 1 unit 103 46.000
Up to 6300 A III C 3WL9 111-0BD06-0AA0 1 1 unit 103 70.000
N L1 L2 L3
L1 L2 L3 L1 L2 L3
NSE0_01116
NSE0_01113 NSE0_01112
NSE0_01119
N L1 L2 L3 N L1 L2 L3
NSE0_01117
Top and bottom parts of system are short-circuited and grounded Top part of system is short-circuited and grounded,
(as-supplied state) infeed from bottom
NSE0_01120
NSE0_01122a
L1 L2 L3
NSE0_01115 NSE0_01114
NSE0_01121
NSE0_01123a
N L1 L2 L3
Withdrawable bridging unit, infeed and outgoing terminals are permanently Bottom part of system is short-circuited and grounded,
connected to each other infeed from top
■ Options
Structure of the Order No.
3WL1 Ô Ô Ò – ÖéâÕÓ– ÓáÜÔ An important prerequisite for
computer-based order process-
Example
>>> >>>>> >>>> ing is that order numbers must
be structured according to stan-
5. position: Size Size II Ô dardized criteria.
They are used as an unambigu-
6. and 7th posi- Max. rated circuit In max = 2000 A ÔÒ ous means of communication for
tions: breaker current various purposes:
In max
• Offer processing
8. position: Switching capacity High breaking capacity Ö Selection and configuration
class "H": 100 kA • Order processing
Orders
9. position: Electronic release ETU76B with pixel graphics é Order confirmation
display ... Processing of products for stor-
10. position: Electronic release ... with ground-fault protection â age
supplement Order processing in supply lo-
cations
11. position: Number of poles Three-pole Õ Supply and dispatch
• Reporting and planning
12. position: Installation type Fixed mounting, main connec- Ó • Service and warranty
tions on rear, vertical The standardized structure
ensures that only one Order No.
13. position: Operating mecha- Manual operating mechanism Ó
has to be administered for one
nism with mechanical closing
device.
This saves time and effort during
14. position: 1. Auxiliary release Shunt release á
planning, configuring, ordering
50/60 Hz 110 V AC
and stock keeping, and conse-
15. position: 2. Auxiliary release Without 2nd auxiliary release Ü quently above all it saves costs.
The example opposite explains
16. position: Auxiliary switches 2 NO contact + 2 NC contact Ô the various positions within an
Order No.
Documentation
Operating manual German/English Order No. 3ZX18 12-0WL00-0AN1 Delivery time class C
Complete set French/Italian Order No. 3ZX18 12-0WL00-0AJ1 On request
Spanish/Portuguese Order No. 3ZX18 12-0WL00-0AL1 On request
Manuals German Order No. A5E0151347
Communication English Order No. A5E0151353
■ More information
Up-to-date information on the Internet at:
www.siemens.com/sentron
Size Max. rated circuit breaker DT 4-pole non-automatic air circuit PU PS*/ PG Weight
current breakers DC (UNIT, P. unit per PU
In max. SET, approx.
Order No. Price
M)
A For Order No. supplements, per PU kg
see page 1/23
Horizontal main circuit connection
II 1000 B 3WL12 10-8@@42-.... 1 1 unit 103 67.000
II 2000 B 3WL12 20-8@@42-.... 1 1 unit 103 67.000
II 40001) B 3WL12 40-8@@42-.... 1 1 unit 103 77.000
Vertical main circuit connection
II 1000 B 3WL12 10-8@@41-.... 1 1 unit 103 75.000
II 2000 B 3WL12 20-8@@41-.... 1 1 unit 103 75.000
II 40001) B 3WL12 40-8@@41-.... 1 1 unit 103 103.000
Front main circuit connection, single hole
II 1000 B 3WL12 10-8@@43-.... 1 1 unit 103 67.000
II 2000 B 3WL12 20-8@@43-.... 1 1 unit 103 67.000
Front main circuit connection, double hole
II 1000 B 3WL12 10-8@@44-.... 1 1 unit 103 67.000
II 2000 B 3WL12 20-8@@44-.... 1 1 unit 103 67.000
Non-automatic air circuit breakers2) Order No. supplements Add. price
Without electronic release AA None
Standard Order No. supplements (for further Order No. supplements, see page 1/23)
Manual operating mechanism with mechanical closing 1AA2 None
1234 5 6 7 8 9 10 11 12 13 14 15 16
Add "–Z" to the complete Order No. Order No. with "–Z" Additional price
and indicate the appropriate order code(s). and additional order code 3WL1 2 . 0 – 8 . . . . – . . . . –Z
@@@
3-pole 4-pole
Rated voltage 1000 V DC
Size II Up to 2000 A A05 ✓ ✓
Size II Up to 4000 A A05 ✓ ✓
Note:
For voltages over 600 V use the version for 1000 V DC rated An external overload and short-circuit protection device is avail-
voltage: Order with "-Z" and order code "A05". able from the company "mat" for the SENTRON 3WL non-auto-
matic air circuit breakers.
All other accessory parts must be ordered by specifying "–Z" Available only directly from the company mat – Maschinen- und
and the corresponding order code, see "3WL Air circuit Anlagentechnik (for address see page 1/52).
breakers/non-automatic air circuit breakers up to 6300 A (AC)",
"Options", page 1/24 onwards.
✓ Additional price
1) Provisions to dissipate heat must be made on the line side.
2) For permissible rated short-time current Icw and short-circuit switching
capacity Icc for non-automatic air circuit breakers see page 1/3.
1234 5 6 7 8 9 10 11 12 13 14 15 16
Add "–Z" to the complete Order No. Order No. with "–Z" Additional price
and indicate the appropriate order code(s). and additional order code 3WL1 2 . 0 – 8 . . 3 . – . . . . –Z
@@@
3-pole
Rated voltage 1000 V DC
Size II4) Up to 2000 A A05 ✓
Size II4) Up to 4000 A A05 ✓
Tinned version of the customer's connections on the guide frame3)
Only for circuit breakers in withdrawable version with horizontal connection or flange connection.
The normal delivery time increases to 15 work days.
Size II A08 ✓
Note:
For voltages over 600 V use the version for 1000 V DC rated An external overload and short-circuit protection device is avail-
voltage; order with "-Z" and order code "A05". able from the company "mat" for the SENTRON 3WL non-auto-
matic air circuit breakers.
All other accessory parts must be ordered by specifying "–Z" Available only directly from the company mat – Maschinen- und
and the corresponding order code, see "3WL Air circuit Anlagentechnik (for address see page 1/52).
breakers/non-automatic air circuit breakers up to 6300 A (AC)",
"Options", page 1/24 onwards.
✓ Additional price
1)
Provisions to dissipate heat must be made on the line side.
2)
For permissible rated short-time current Icw and short-circuit switching
capacity Icc for non-automatic air circuit breakers see page 1/3.
3)
The permissible temperature-rise limits according to IEC 60947-2 are 5 K
lower for a tin surface than for a silver surface.
4)
If ordering withdrawable circuit breaker and guide frame separately, spec-
ify order code "A05" for withdrawable circuit breaker and guide frame.
Note:
For voltages over 600 V use the version for 1000 V DC rated An external overload and short-circuit protection device is avail-
voltage; order with "-Z" and order code "A05". able from the company "mat" for the SENTRON 3WL non-auto-
matic air circuit breakers.
All other accessory parts must be ordered by specifying "–Z" Available only directly from the company mat – Maschinen- und
and the corresponding order code, see "3WL Air circuit Anlagentechnik5).
breakers/non-automatic air circuit breakers up to 6300 A (AC)",
"Options", page 1/24 onwards.
Size Max. rated circuit breaker current DT For 4-pole non-automatic air circuit breakers PU PS*/ PG Weight
In max Order No. Price (UNIT, P. unit per PU
(Order No. supplements per PU SET, approx.
A required acc. to table below) M) kg
Front main circuit connection, single hole
II 2000 B 3WL9 212-3EA@@-@@A1 1 1 unit 103 37.000
Front main circuit connection, double hole
II 2000 B 3WL9 212-3EB@@-@@A1 1 1 unit 103 37.000
Horizontal main circuit connection
II 2000 B 3WL9 212-3EC@@-@@A1 1 1 unit 103 37.000
II 4000 B 3WL9 212-6EC@@-@@A1 1 1 unit 103 84.000
Vertical main circuit connection
II 2000 B 3WL9 212-3ED@@-@@A1 1 1 unit 103 37.000
II 4000 B 3WL9 212-6ED@@-@@A1 1 1 unit 103 84.000
Main circuit connection connecting flanges
II 2000 B 3WL9 212-3EE@@-@@A1 1 1 unit 103 37.000
II 4000 B 3WL9 212-6EE@@-@@A1 1 1 unit 103 84.000
Order No. supplements Add. price
Number of auxiliary supply connectors 4-pole
Without 0 None
1 connector 1 ✓
2 connectors 2 ✓
3 connectors 3 ✓
4 connectors 4 ✓
For required number of auxiliary supply connectors,
see table on page 1/29
Type of auxiliary circuit connections
Without 0 None
With screw connection (SIGUT, standard) 1 ✓
With screwless connection method (tension spring) 2 ✓
Position signaling switches
Without 0 None
Option 1 Connected 1 CO contact, 1 ✓
test 1 CO contacts,
disconnected 1 CO contact
Option 2 Connected 3 CO contacts, 2 ✓
test 2 CO contacts,
disconnected 1 CO contact
Shutters
Without A None
With shutter, 2 parts, lockable B ✓
1234 5 6 7 8 9 10 11 12 13 14 15 16
Add "–Z" to the complete Order No. Order No. with "–Z" Add.
and indicate the appropriate order code(s). and additional order code 3WL9 2 1 2 – . . . . . – . . A1 –Z price
@@@
2/2 Introduction
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical specifications
under Entry List:
- Updates
- Downloads
- FAQ
- Manuals
- Characteristic curves
- Certificates
and at
www.siemens.com/lowvoltage/
configurators
- Configurators
■ Overview
Rated current In A 16 ... 160 50 ... 160 200 ... 250 200 ... 400
at 50 °C ambient temperature
Number of poles 3 4 3 4 3 4 3 4
Rated operational voltage Ue
50/60 Hz AC V 690 690 690 690 690 690 690 690
DC1) V 500 500 600 600 600 600 600 600
Electronic releases
Thermal-magnetic ✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
Electronic LCD ETU/ETU -- -- ✓ ✓ ✓ ✓ ✓ ✓
Replaceable -- -- ✓ ✓ ✓ ✓ ✓ ✓
PROFIBUS module COM20 -- -- ✓ ✓ ✓ ✓ ✓ ✓
Dimensions
D A mm 105 139 105 139 105 139 139 183
A C B mm 157 157 175 175 175 175 279 279
N S E 0 _ 0 1 1 5 9
C mm 81 81 81 81 81 81 102 102
D mm 107 107 107 107 107 107 138 138
B
Introduction
2
3 4 3 4 3 4 3 4
✓ ✓ -- -- -- -- -- --
✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
✓ ✓ ✓ ✓ ✓ ✓ ✓ ✓
25 25 25 25
20 20 20 20
50 50 50 50
30 30 30 30
65 65 65 65
35 35 35 35
2) 4)
At 240 V AC, 415 V AC and 525 V AC max. 5 % overvoltage, The maximum permitted DC voltage for each conducting path needs to be taken
at 440 V AC, 500 V AC and 690 V AC max. 10 % overvoltage, into account for DC switching applications; see Technical Information at
at 250/500/600 V DC max. 5 % overvoltage. www.siemens.com/lowvoltage/support; time constant t = 15 ms.
3) Rated current I ≥ 25 A. 5) The NEMA breaking capacity can be found on the rating plate of each IEC circuit
n
breaker.
10
10
11
12
13
NSE0_02087b
$ Withdrawable/plug-in bases (pages 2/70 to 2/75)
% Side panels for withdrawable version (pages 2/70 to 2/75)
& Phase barriers (pages 2/77 to 2/82)
( Flared front busbar connecting bars (pages 2/77 to 2/82)
) Straight connecting bars (pages 2/77 to 2/82)
* Circular conductor terminals for Al/Cu (pages 2/77 to 2/79)
+ Box terminals for Cu (pages 2/77 to 2/82)
, Extended connection covers (terminal covers) (pages 2/77 to 2/82)
- Standard connection covers (terminal covers) (pages 2/77 to 2/82)
. Masking frames/cover frames for door cutout (pages 2/94 to 2/97)
/ Motorized operating mechanisms with stored energy mechanism (pages 2/66)
0 Front-operated rotary operating mechanisms (pages 2/62 to 2/65)
1 Door-coupling rotary operating mechanisms (pages 2/62 to 2/65)
2 SENTRON 3VL circuit breakers (pages 2/10 to 2/53)
3 Internal accessories (pages 2/55, 2/56, 2/59 to 2/61)
4 Electronic overcurrent releases LCD ETU (pages 2/20, 2/24, 2/28, 2/44 and 2/46)
5 Electronic releases with communication function (pages 2/12 to 2/28, 2/40 to 2/50)
6 Thermal/magnetic overcurrent releases (pages 2/10 to 2/12, 2/30, 2/34 to 2/38, 2/52)
7 RCD modules (page 2/76)
8 Rear terminals – flat and round (pages 2/77 to 2/82)
9 COM20 communication modules to the PROFIBUS DP (page 2/98)
: Battery power supplies with test function for electronic releases (pages 2/84 to 2/88)
Introduction
2
8
7
2
6
5 3
15
14
18
22
16
19
17
7
21
6
NSE0_02087b
9
4
8
20
Measured values are the basis for efficient load management, These switching capacities are indicated in the corre-
for drawing up power demand profiles and for assigning power sponding tables by the symbols shown on orange back-
to cost centers. grounds.
Communication: Standards and specifications
• For molded case circuit breakers with communication function
see pages 2/12 to 2/28 and 2/40 to 2/50. SENTRON 3VL circuit breakers comply with:
• For accessories, see page 2/98. IEC 60947-1, EN 60947-1,
IEC 60947-2, EN 60947-2.
• For more information see also chapters "Measuring Devices Isolating features according to IEC 60947-2, EN 60947-2.
and E-Counters" and "Software".
Disconnecting features (main control switches) according to
■ Applications EN 60204.
The SENTRON 3VL circuit breakers comply in addition with re-
The different versions of SENTRON 3VL circuit breakers are suit- quirements for "disconnector units with features for stopping and
able for the following applications: switching off in an emergency" (EMERGENCY-STOP switches) in
• Incoming and outgoing circuit breakers in distribution systems conjunction with lockable rotary operating mechanisms (red-yel-
low) and terminal covers.
• Switching and protection devices for motors, transformers
and capacitors Please contact Siemens for details of other standards.
• Disconnector units with features for stopping and switching off The electronic releases of the circuit breakers for motor
in an emergency (main control switches and EMERGENCY- protection also fulfill IEC 60947-4-1, EN 60947-2.
STOP switches) in conjunction with lockable rotary operating
mechanisms and terminal covers. VL160X to VL400 circuit breakers can be equipped with a
SENTRON 3VL RCD module. They then comply with
The SENTRON 3VL circuit breakers are available in the following IEC 60947-2 Appendix B.
versions:
The SENTRON 3VL RCD module complies with IEC 61000-4-2 to
1. For system protection (in 3- and 4-pole versions) IEC 61000-4-6, IEC 61000-4-11 and EN 55011, Class B (equiva-
The overload and short-circuit releases are designed for the lent to CISPR 11) with regard to electromagnetic compatibility.
protection of cables, leads and non-motor loads.
2. For motor protection (in 3-pole version) Operating conditions
The overload and short-circuit releases are designed for opti- The SENTRON 3VL circuit breakers are designed for operation
mized protection and direct-on-line starting of induction squir- in enclosed areas.
rel-cage motors. The circuit breakers for motor protection are
susceptible to phase failure and feature an adjustable trip Suitable enclosures must be provided for operation in areas with
class. The electronic releases operate with a microprocessor. severe ambient conditions (such as dust, caustic vapors, haz-
ardous gases).
Introduction
2
RCD modules
The RCD module is designed for retrofitting to the circuit breaker. Protection of plant and equipment against overload or damage
It can also be retrofitted by the customer. by ground faults (ground-fault protection).
The combination of SENTRON 3VL circuit breaker and RCD The RCD module trips the circuit breaker through vectorial sum-
module can be fed from the top or bottom. mation current formation for all phase currents if the vectorial
sum of the currents in the poles (= the ground fault current) over-
All SENTRON 3VL circuit breakers with RCD modules are avail- shoots the pre-set response and delay time values. AC currents
able with auxiliary switches, alarm switches, undervoltage and and pulsating DC currents are measured (CBR, design A
shunt releases. according to EN 60947-2).
Main connections, basic equipment and options
NSE0_00701 NSE0_00702
NSE0_00700 NSE0_01541
Box terminal Connection with screw terminal Connection to front busbar connecting Circular conductor terminals
(for copper cables or solid/ (available with direct cable lug connec- bars (screw terminal required) multiple feed-in terminal
flexible busbars) tion on VL160X, VL160, VL250, VL400) (for Al/Cu terminal)
Conductor cross-sections
Type VL160X VL160 VL250 VL400 VL630 VL800 VL1250 VL1600
3VL1 3VL2 3VL3 3VL4 3VL5 3VL6 3VL7 3VL8
Conductor cross-sections
Box terminals1)
• Solid or stranded cable Copper only mm2 2.5 ... 95 2.5 ... 95 25 ... 185 50 ... 300 -- -- -- --
• Finely stranded with end sleeve mm2 2.5 ... 50 2.5 ... 50 25 ... 120 50 ... 240 -- -- -- --
• Flexible busbar mm 12 × 10 12 × 10 17 × 10 25 × 10 -- -- -- --
Connecting terminal plate for flexible busbar2) mm -- -- -- -- 2 units -- -- --
10 × 32
Circular conductor terminal for cable1)
• Solid or stranded cable Cu or Al mm2 16 ... 70 16 ... 70 25 ... 185 50 ... 300 -- -- -- --
- With terminal cover Cu or Al mm2 16 ... 150 16 ... 150 120 ... 240 -- -- -- -- --
• Finely stranded with end sleeve mm2 10 ... 50 10 ... 50 25 ... 120 50 ... 240 -- -- -- --
Multiple feed-in terminal1)
• Solid or stranded cable Cu or Al mm2 -- -- -- 2 units 2 units 3 units 4 units --
50 ... 120 50 ... 240 50 ... 240 50 ... 240
- With terminal cover Cu or Al mm2 -- -- -- 2 units -- -- -- --
70 ... 300
2
• Finely stranded with end sleeve mm -- -- -- 2 units 2 units 3 units 4 units --
50 ... 95 50 ... 185 50 ... 185 50 ... 185
• Direct connection of busbars Cu or Al mm 17 × 7 22 × 7 24 × 7 32 × 10 40 × 10 2 × 40 × 10 2 × 50 × 10 3 × 60 × 10
• Screw for connection with screw terminal M6 M6 M8 M8 M6 M8 M8 --
Conductor cross-sections for control circuits with
terminal connection
Screw terminals
• Solid mm2 0.75 ... 1.5 0.75 ... 1.5 0.75 ... 1.5 0.75 ... 1.5 0.75 ... 1.5 0.75 ... 1.5 0.75 ... 1.5 0.75 ... 1.5
• Finely stranded with end sleeve mm2 0.75 ... 1.0 0.75 ... 1.0 0.75 ... 1.0 0.75 ... 1.0 0.75 ... 1.0 0.75 ... 1.0 0.75 ... 1.0 0.75 ... 1.0
For details see Mounting Instruction.
1)
Cross-sections according to IEC 60999.
2)
Not for 690 V AC/600 V DC.
System/generator protection
System protection Setting options
Starter protection
Motor protection
circuit breakers
Non-automatic
L S1) I1) G
supplement
Releases
Function
protection protection (short- protection (instan-
time delayed) taneous)
Ir = × In Isd = × Ir tsd [s] Ii = × In Ig = × In tg [s]
DK M -- -- -- ✓ -- I -- -- -- 7 ... 15 -- --
DE M -- -- -- -- ✓ I -- -- -- 8 ... 18 -- --
EE M -- -- -- -- ✓ I -- -- -- 8 ... 18 -- --
DA TM 2) ✓ -- -- -- -- LI 1 -- -- 9 ... 184) -- --
DD TM 2) ✓ -- -- -- -- LI 0.8 ... 1 -- -- 9 ... 184) -- --
DC TM 2) ✓ -- -- -- -- LI 0.8 ... 1 -- -- 5 ... 10 -- --
EH TM 2) ✓ -- -- -- -- LI 1 -- -- 9 ... 184) -- --
EJ TM 2) ✓ -- -- -- -- LI 0.8 ... 1 -- -- 5 ... 10 -- --
EA TM 2) ✓ -- -- -- -- LIN 1 -- -- 9 ... 184) -- --
EC TM 2) ✓ -- -- -- -- LIN 0.8 ... 1 -- -- 5 ... 10 -- --
EM TM 2) ✓ -- -- -- -- LIN 0.8 ... 1 -- -- 5 ... 10 -- --
SP ETU10M3) -- -- ✓ -- -- LI 0.4 ... 1 -- -- 1.25 ... 11 -- --
MP ETU10M3) -- -- ✓ -- -- LI 0.4 ... 1 -- -- 1.25 ... 11 -- --
SB ETU10 ✓ -- -- -- -- LI 0.4 ... 1 -- -- 1.25 ... 11 -- --
MB ETU10 ✓ -- -- -- -- LI 0.4 ... 1 -- -- 1.25 ... 11 -- --
LB ETU10 ✓ -- -- -- -- LI 0.4 ... 1 -- -- 1.25 ... 11 -- --
TA ETU10 ✓ -- -- -- -- LIN 0.4 ... 1 -- -- 1.25 ... 11 -- --
NA ETU10 ✓ -- -- -- -- LIN 0.4 ... 1 -- -- 1.25 ... 11 -- --
LA ETU10 ✓ -- -- -- -- LIN 0.4 ... 1 -- -- 1.25 ... 11 -- --
TB ETU10 ✓ -- -- -- -- LI 0.4 ... 1 -- -- 1.25 ... 11 -- --
NB ETU10 ✓ -- -- -- -- LI 0.4 ... 1 -- -- 1.25 ... 11 -- --
SL ETU12 ✓ -- -- -- -- LIG 0.4 ... 1 -- -- 1.25 ... 11 0.6 ... 1, OFF 0.1 ... 0.3
ML ETU12 ✓ -- -- -- -- LIG 0.4 ... 1 -- -- 1.25 ... 11 0.6 ... 1, OFF 0.1 ... 0.3
SF ETU12 ✓ -- -- -- -- LIG 0.4 ... 1 -- -- 1.25 ... 11 0.6 ... 1, OFF 0.1 ... 0.3
MF ETU12 ✓ -- -- -- -- LIG 0.4 ... 1 -- -- 1.25 ... 11 0.6 ... 1, OFF 0.1 ... 0.3
TN ETU12 ✓ -- -- -- -- LING 0.4 ... 1 -- -- 1.25 ... 11 0.6 ... 1, OFF 0.1 ... 0.3
NN ETU12 ✓ -- -- -- -- LING 0.4 ... 1 -- -- 1.25 ... 11 0.6 ... 1, OFF 0.1 ... 0.3
SE ETU20 -- ✓ -- -- -- LSI 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 -- --
ME ETU20 -- ✓ -- -- -- LSI 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 -- --
LE ETU20 -- ✓ -- -- -- LSI 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 -- --
TE ETU20 -- ✓ -- -- -- LSI 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 -- --
NE ETU20 -- ✓ -- -- -- LSI 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 -- --
TF ETU20 -- ✓ -- -- -- LSIN 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 -- --
NF ETU20 -- ✓ -- -- -- LSIN 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 -- --
LF ETU20 -- ✓ -- -- -- LSIN 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 -- --
SG ETU22 -- ✓ -- -- -- LSIG 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 0.6 ... 1, OFF 0.1 ... 0.3
MG ETU22 -- ✓ -- -- -- LSIG 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 0.6 ... 1, OFF 0.1 ... 0.3
SH ETU22 -- ✓ -- -- -- LSIG 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 0.6 ... 1, OFF 0.1 ... 0.3
MH ETU22 -- ✓ -- -- -- LSIG 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 0.6 ... 1, OFF 0.1 ... 0.3
TH ETU22 -- ✓ -- -- -- LSING 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 0.6 ... 1, OFF 0.1 ... 0.3
NH ETU22 -- ✓ -- -- -- LSING 0.4 ... 1 1.5 ... 10 0 ... 0.5 11 0.6 ... 1, OFF 0.1 ... 0.3
SS ETU30M3) -- -- ✓ -- -- LI 0.4 ... 1 -- -- 6/8/11 -- --
MS ETU30M3) -- -- ✓ -- -- LI 0.4 ... 1 -- -- 6/8/11 -- --
LS ETU30M3) -- -- ✓ -- -- LI 0.4 ... 1 -- -- 6/8/11 -- --
CP LCD ETU40M3) -- -- ✓ -- -- LI 0.4 ... 1 -- -- 1.25 ... 11 -- --
CH LCD ETU40 -- ✓ -- -- -- LI, LS, LSI 0.4 ... 1 1.5 ... 10 0 ... 0.5 1.25 ... 11 -- --
CJ LCD ETU40 -- ✓ -- -- -- LI, LSI, LIN, 0.4 ... 1 1.5 ... 10 0 ... 0.5 1.25 ... 11 -- --
LSIN
CL LCD ETU42 -- ✓ -- -- -- LSIG 0.4 ... 1 1.5 ... 10 0 ... 0.5 1.25 ... 11 0.4 ... 1 0.1 ... 0.5
CM LCD ETU42 -- ✓ -- -- -- LSIG 0.4 ... 1 1.5 ... 10 0 ... 0.5 1.25 ... 11 0.4 ... 1 0.1 ... 0.5
CN LCD ETU42 -- ✓ -- -- -- LSIG, LSING 0.4 ... 1 1.5 ... 10 0 ... 0.5 1.25 ... 11 0.4 ... 1 0.1 ... 0.5
✓ Function is available.
-- Function not available
1) Size dependent.
2) TM up to In = 630 A.
3) Motor protection up to In = 500 A.
4) Non-adjustable.
Introduction
2
Thermal-magnetic releases
Communication-capable
Ground-fault protection
N pole protected1)
Electronic release
Number of poles
Thermal image
I2t (ON/OFF)
LCD display
supplement
Order No.
Magnetic
Releases
releases
DK M -- -- -- -- 3 -- -- -- -- -- ✓ -- --
DE M -- -- -- -- 3 -- -- -- -- -- ✓ -- --
EE M -- -- -- -- 4 -- -- -- -- -- ✓ -- --
DA TM 2) ✓ -- -- -- 3 -- -- -- -- ✓ -- -- --
DD TM 2) ✓ -- -- -- 3 -- -- -- -- ✓ -- -- --
DC TM 2) ✓ -- -- -- 3 -- -- -- -- ✓ -- -- --
EH TM 2) ✓ -- -- -- 4 -- -- -- -- ✓ -- -- --
EJ TM 2) ✓ -- -- -- 4 -- -- -- -- ✓ -- -- --
EA TM 2) ✓ -- -- -- 4 100 % -- -- -- ✓ -- -- --
EC TM 2) ✓ -- -- -- 4 60 % -- -- -- ✓ -- -- --
EM TM 2) ✓ -- -- -- 4 100 % -- -- -- ✓ -- -- --
SP ETU10M3) ✓ 40 % IR -- -- 3 -- -- 10 -- -- -- ✓ --
MP ETU10M3) ✓ 40 % IR ✓4) -- 3 -- -- 10 -- -- -- ✓ --
SB ETU10 ✓ -- -- -- 3 -- -- -- 2.5 ... 30 -- -- ✓ --
MB ETU10 ✓ -- ✓4) -- 3 -- -- -- 2.5 ... 30 -- -- ✓ --
LB ETU10 ✓ -- -- -- 3 -- -- -- 2.5 ... 30 -- -- ✓ --
TA ETU10 ✓ -- -- -- 4 50/100 % -- -- 2.5 ... 30 -- -- ✓ --
NA ETU10 ✓ -- ✓4) -- 4 50/100 % -- -- 2.5 ... 30 -- -- ✓ --
LA ETU10 ✓ -- -- -- 4 50/100 % -- -- 2.5 ... 30 -- -- ✓ --
TB ETU10 ✓ -- -- -- 4 -- -- -- 2.5 ... 30 -- -- ✓ --
NB ETU10 ✓ -- ✓4) -- 4 -- -- -- 2.5 ... 30 -- -- ✓ --
SL ETU12 ✓ -- -- $ 3 -- -- -- 2.5 ... 30 -- -- ✓ --
ML ETU12 ✓ -- ✓4) $ 3 -- -- -- 2.5 ... 30 -- -- ✓ --
SF ETU12 ✓ -- -- % 3 -- -- -- 2.5 ... 30 -- -- ✓ --
MF ETU12 ✓ -- ✓4) % 3 -- -- -- 2.5 ... 30 -- -- ✓ --
TN ETU12 ✓ -- -- % 4 50/100 % -- -- 2.5 ... 30 -- -- ✓ --
NN ETU12 ✓ -- ✓4) % 4 50/100 % -- -- 2.5 ... 30 -- -- ✓ --
SE ETU20 ✓ -- -- -- 3 -- ✓ -- -- -- -- ✓ --
ME ETU20 ✓ -- ✓4) -- 3 -- ✓ -- -- -- -- ✓ --
LE ETU20 ✓ -- -- -- 3 -- ✓ -- -- -- -- ✓ --
TE ETU20 ✓ -- -- -- 4 -- ✓ -- -- -- -- ✓ --
NE ETU20 ✓ -- ✓4) -- 4 -- ✓ -- -- -- -- ✓ --
TF ETU20 ✓ -- -- -- 4 50/100 % ✓ -- -- -- -- ✓ --
NF ETU20 ✓ -- ✓4) -- 4 50/100 % ✓ -- -- -- -- ✓ --
LF ETU20 ✓ -- -- -- 4 50/100 % ✓ -- -- -- -- ✓ --
SG ETU22 ✓ -- -- $ 3 -- ✓ -- -- -- -- ✓ --
MG ETU22 ✓ -- ✓4) $ 3 -- ✓ -- -- -- -- ✓ --
SH ETU22 ✓ -- -- % 3 -- ✓ -- -- -- -- ✓ --
MH ETU22 ✓ -- ✓4) % 3 -- ✓ -- -- -- -- ✓ --
TH ETU22 ✓ -- -- % 4 50/100 % ✓ -- -- -- -- ✓ --
NH ETU22 ✓ -- ✓4) % 4 50/100 % ✓ -- -- -- -- ✓ --
SS ETU30M3) ✓ 40 % IR -- -- 3 -- -- 10, 20, 30 -- -- -- ✓ --
MS ETU30M3) ✓ 40 % IR ✓4) -- 3 -- -- 10, 20, 30 -- -- -- ✓ --
LS ETU30M3) ✓ 40 % IR -- -- 3 -- -- 10, 20, 30 -- -- -- ✓ --
CP LCD ETU40M3) ✓ 5 ... 50 % IR -- -- 3 -- -- 5, 10, 15, 20, 30 -- -- -- ✓ ✓
CH LCD ETU40 ✓ -- -- -- 3 -- ✓ -- 2.5 ... 30 -- -- ✓ ✓
CJ LCD ETU40 ✓ -- -- -- 4 50 ... 100 %, OFF ✓ -- 2.5 ... 30 -- -- ✓ ✓
NSE0_00695
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal not in conjunction with RCD module 6
NSE0_00540a
OFF
TM ~=
63A
50° C
CAT.A
1.0 .8
xI n IR
NSE0_00703
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal not in conjunction with RCD module 6
** Delivery time class A for Order No. supplement "0AA0", see page 2/57.
>
3
6
>
3
6
** Delivery time class A for Order No. supplement "0AA0", see page 2/57.
Type Rated Current setting of the Operating current of the DT Icu up to 55 kA at 415 V, standard switching capacity N
N
current inverse-time delayed instantaneous See "Overview".
In overcurrent releases short-circuit releases "I" Order No. Basic price PU PS*/ PG Weight
"L" Ii per PU (UNIT, P. unit per PU
IR Order No. supplement
required, See also SET, M) approx.
A A A see page 2/57 page 2/32 kg
3-pole, fixed-mounted, for system protection, 50 A to 630 A,
thermal-magnetic releases LI
NSE0_-00541a
Ii I 16 DC
R
1.0
I n =160A
I
L 7 8
50 C
6 9 xI I I
R i
n ~ .8
I 5 10
TM = CAT.A xI n
NSE0_00691
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 200 160 ... 200 1000 ... 2000 B 3VL47 20-1DC36-.... 1 1 unit 113 5.700
250 200 ... 250 1250 ... 2500 B 3VL47 25-1DC36-.... 1 1 unit 113 5.700
315 250 ... 315 1575 ... 3150 B 3VL47 31-1DC36-.... 1 1 unit 113 5.700
400 320 ... 400 2000 ... 4000 B 3VL47 40-1DC36-.... 1 1 unit 113 5.700
VL630/3VL5 315 250 ... 315 1575 ... 3150 B 3VL57 31-1DC36-.... 1 1 unit 113 9.000
400 320 ... 400 2000 ... 4000 B 3VL57 40-1DC36-.... 1 1 unit 113 9.000
500 400 ... 500 2500 ... 5000 B 3VL57 50-1DC36-.... 1 1 unit 113 9.000
630 500 ... 630 3150 ... 6300 B 3VL57 63-1DC36-.... 1 1 unit 113 9.000
3-pole, fixed-mounted, for system protection, 63 A to 1600 A,
electronic releases LI
NSE0_02119
ETU10, LI function
With adjustable overcurrent releases, adjustable short-circuit releases
VL160/3VL2 63 25 ... 63 1.25 ... 11 × In B 3VL27 06-1@@3@-.... 1 1 unit 113 2.400
100 40 ... 100 1.25 ... 11 × In B 3VL27 10-1@@3@-.... 1 1 unit 113 2.400
160 64 ... 160 1.25 ... 11 × In B 3VL27 16-1@@3@-.... 1 1 unit 113 2.400
VL250/3VL3 200 80 ... 200 1.25 ... 11 × In B 3VL37 20-1@@3@-.... 1 1 unit 113 2.500
250 100 ... 250 1.25 ... 11 × In B 3VL37 25-1@@3@-.... 1 1 unit 113 2.500
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In B 3VL47 31-1@@36-.... 1 1 unit 113 5.900
400 160 ... 400 1.25 ... 11 × In B 3VL47 40-1@@36-.... 1 1 unit 113 5.900
VL630/3VL5 630 525 ... 630 1.25 ... 10 × In B 3VL57 63-1@@36-.... 1 1 unit 113 9.300
VL800/3VL6 800 320 ... 800 1.25 ... 8 × In B 3VL67 80-1@@36-.... 1 1 unit 113 16.000
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 × In B 3VL77 10-1@@36-.... 1 1 unit 113 25.000
1250 500 ... 1250 1.25 ... 11 × In B 3VL77 12-1@@36-.... 1 1 unit 113 25.000
VL1600/3VL81) 1600 640 ... 1600 1.25 ... 9 × In B 3VL87 16-1@@30-.... 1 1 unit 113 31.300
B 3VL27 05-2DC3@-.... 1 1 unit 113 2.200 B 3VL27 05-3DC3@-.... 1 1 unit 113 2.200
B 3VL27 06-2DC3@-.... 1 1 unit 113 2.200 B 3VL27 06-3DC3@-.... 1 1 unit 113 2.200
B 3VL27 08-2DC3@-.... 1 1 unit 113 2.200 B 3VL27 08-3DC3@-.... 1 1 unit 113 2.200
B 3VL27 10-2DC3@-.... 1 1 unit 113 2.200 B 3VL27 10-3DC3@-.... 1 1 unit 113 2.200
B 3VL27 12-2DC3@-.... 1 1 unit 113 2.200 B 3VL27 12-3DC3@-.... 1 1 unit 113 2.200
B 3VL27 16-2DC3@-.... 1 1 unit 113 2.200 B 3VL27 16-3DC3@-.... 1 1 unit 113 2.200
B 3VL37 20-2DC3@-.... 1 1 unit 113 2.300 B 3VL37 20-3DC3@-.... 1 1 unit 113 2.300
B 3VL37 25-2DC3@-.... 1 1 unit 113 2.300 B 3VL37 25-3DC3@-.... 1 1 unit 113 2.300
> >
3 3
6 6
B 3VL47 20-2DC36-.... 1 1 unit 113 5.700 B 3VL47 20-3DC36-.... 1 1 unit 113 5.700
B 3VL47 25-2DC36-.... 1 1 unit 113 5.700 B 3VL47 25-3DC36-.... 1 1 unit 113 5.700
B 3VL47 31-2DC36-.... 1 1 unit 113 5.700 B 3VL47 31-3DC36-.... 1 1 unit 113 5.700
B 3VL47 40-2DC36-.... 1 1 unit 113 5.700 B 3VL47 40-3DC36-.... 1 1 unit 113 5.700
B 3VL57 31-2DC36-.... 1 1 unit 113 9.000 B 3VL57 31-3DC36-.... 1 1 unit 113 9.000
B 3VL57 40-2DC36-.... 1 1 unit 113 9.000 B 3VL57 40-3DC36-.... 1 1 unit 113 9.000
B 3VL57 50-2DC36-.... 1 1 unit 113 9.000 B 3VL57 50-3DC36-.... 1 1 unit 113 9.000
B 3VL57 63-2DC36-.... 1 1 unit 113 9.000 B 3VL57 63-3DC36-.... 1 1 unit 113 9.000
B 3VL27 06-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 06-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 10-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 10-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 16-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 16-3@@3@-.... 1 1 unit 113 2.400
B 3VL37 20-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 20-3@@3@-.... 1 1 unit 113 2.500
B 3VL37 25-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 25-3@@3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2@@36-.... 1 1 unit 113 5.900 B 3VL47 31-3@@36-.... 1 1 unit 113 5.900
B 3VL47 40-2@@36-.... 1 1 unit 113 5.900 B 3VL47 40-3@@36-.... 1 1 unit 113 5.900
B 3VL57 63-2@@36-.... 1 1 unit 113 9.300 B 3VL57 63-3@@36-.... 1 1 unit 113 9.300
B 3VL67 80-2@@36-.... 1 1 unit 113 16.000 B 3VL67 80-3@@36-.... 1 1 unit 113 16.000
B 3VL77 10-2@@36-.... 1 1 unit 113 25.000 B 3VL77 10-3@@36-.... 1 1 unit 113 25.000
B 3VL77 12-2@@36-.... 1 1 unit 113 25.000 B 3VL77 12-3@@36-.... 1 1 unit 113 25.000
B 3VL87 16-2@@30-.... 1 1 unit 113 31.300 B 3VL87 16-3@@30-.... 1 1 unit 113 31.300
>
SB
MB
>
SB
MB
LB LB
Type Rated Current Operating Ground-fault DT Icu up to 55 kA at 415 V, standard switching capacity N
N
current setting of the current of the protection "G" See "Overview".
In inverse-time instantaneous Ig Order No. For price PU PS*/ PG Weight
delayed short-circuit see page (UNIT, P. unit per PU
overcurrent releases "I" 2/32 SET, M) approx.
releases "L" Ii
IR Order No. supplement
required,
A A A A see page 2/57 kg
3-pole, fixed-mounted, for system protection, 63 A to 1600 A,
electronic releases LIG
NSE0_02118
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL47 31-1@@36-.... 1 1 unit 113 5.900
400 160 ... 400 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL47 40-1@@36-.... 1 1 unit 113 5.900
VL630/3VL5 630 252 ... 630 1.25 ... 10 × In 0.6 ... 1 × In, OFF B 3VL57 63-1@@36-.... 1 1 unit 113 9.300
VL800/3VL6 800 320 ... 800 1.25 ... 8 × In 0.6 ... 1 × In, OFF B 3VL67 80-1@@36-.... 1 1 unit 113 16.000
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL77 10-1@@36-.... 1 1 unit 113 25.000
1250 500 ... 1250 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL77 12-1@@36-.... 1 1 unit 113 25.000
VL1600/3VL81) 1600 640 ... 1600 1.25 ... 9 × In 0.6 ... 1 × In, OFF B 3VL87 16-1@@30-.... 1 1 unit 113 31.300
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL47 31-1@@36-.... 1 1 unit 113 5.900
400 160 ... 400 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL47 40-1@@36-.... 1 1 unit 113 5.900
VL630/3VL5 630 252 ... 630 1.25 ... 10 × In 0.6 ... 1 × In, OFF B 3VL57 63-1@@36-.... 1 1 unit 113 9.300
VL800/3VL6 800 320 ... 800 1.25 ... 8 × In 0.6 ... 1 × In, OFF B 3VL67 80-1@@36-.... 1 1 unit 113 16.000
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL77 10-1@@36-.... 1 1 unit 113 25.000
1250 500 ... 1250 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL77 12-1@@36-.... 1 1 unit 113 25.000
VL1600/3VL81) 1600 640 ... 1600 1.25 ... 9 × In 0.6 ... 1 × In, OFF B 3VL87 16-1@@30-.... 1 1 unit 113 31.300
kg kg
B 3VL27 06-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 06-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 10-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 10-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 16-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 16-3@@3@-.... 1 1 unit 113 2.400
B 3VL37 20-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 20-3@@3@-.... 1 1 unit 113 2.500
B 3VL37 25-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 25-3@@3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2@@36-.... 1 1 unit 113 5.900 B 3VL47 31-3@@36-.... 1 1 unit 113 5.900
B 3VL47 40-2@@36-.... 1 1 unit 113 5.900 B 3VL47 40-3@@36-.... 1 1 unit 113 5.900
B 3VL57 63-2@@36-.... 1 1 unit 113 9.300 B 3VL57 63-3@@36-.... 1 1 unit 113 9.300
B 3VL67 80-2@@36-.... 1 1 unit 113 16.000 B 3VL67 80-3@@36-.... 1 1 unit 113 16.000
B 3VL77 10-2@@36-.... 1 1 unit 113 25.000 B 3VL77 10-3@@36-.... 1 1 unit 113 25.000
B 3VL77 12-2@@36-.... 1 1 unit 113 25.000 B 3VL77 12-3@@36-.... 1 1 unit 113 25.000
B 3VL87 16-2@@30-.... 1 1 unit 113 31.300 B 3VL87 16-3@@30-.... 1 1 unit 113 31.300
>
SL
ML
>
SL
ML
B 3VL27 06-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 06-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 10-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 10-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 16-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 16-3@@3@-.... 1 1 unit 113 2.400
B 3VL37 20-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 20-3@@3@-.... 1 1 unit 113 2.500
B 3VL37 25-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 25-3@@3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2@@36-.... 1 1 unit 113 5.900 B 3VL47 31-3@@36-.... 1 1 unit 113 5.900
B 3VL47 40-2@@36-.... 1 1 unit 113 5.900 B 3VL47 40-3@@36-.... 1 1 unit 113 5.900
B 3VL57 63-2@@36-.... 1 1 unit 113 9.300 B 3VL57 63-3@@36-.... 1 1 unit 113 9.300
B 3VL67 80-2@@36-.... 1 1 unit 113 16.000 B 3VL67 80-3@@36-.... 1 1 unit 113 16.000
B 3VL77 10-2@@36-.... 1 1 unit 113 25.000 B 3VL77 10-3@@36-.... 1 1 unit 113 25.000
B 3VL77 12-2@@36-.... 1 1 unit 113 25.000 B 3VL77 12-3@@36-.... 1 1 unit 113 25.000
B 3VL87 16-2@@30-.... 1 1 unit 113 31.300 B 3VL87 16-3@@30-.... 1 1 unit 113 31.300
>
SF
MF
>
SF
MF
Communication: • For more information see also chapters "Measuring Devices and
•For accessories, see page 2/98. E-Counters" and "Software".
S .9 .5 7 2.5 .2 .2
2 Active
.3 I t
2
I X3 .8 .6 6 3 I t .1
x I n .7 .63 5 4 x I R ON .5 .4 OFF
NSE0_00692
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 0.4 ... 1.0 × In 11 × In 1.5 ... 10xIR B 3VL47 31-1@@36-.... 1 1 unit 113 5.900
400 0.4 ... 1.0 × In 11 × In 1.5 ... 10xIR B 3VL47 40-1@@36-.... 1 1 unit 113 5.900
VL630/3VL5 630 0.4 ... 1.0 × In 10 × In 1.5 ... 9xIR B 3VL57 63-1@@36-.... 1 1 unit 113 9.300
VL800/3VL6 800 0.4 ... 1.0 × In 8 × In 1.5 ... 7xIR B 3VL67 80-1@@36-.... 1 1 unit 113 16.000
VL1250/3VL7 1000 0.4 ... 1.0 × In 11 × In 1.5 ... 10xIR B 3VL77 10-1@@36-.... 1 1 unit 113 25.000
1250 0.4 ... 1.0 × In 11 × In 1.5 ... 10xIR B 3VL77 12-1@@36-.... 1 1 unit 113 25.000
VL1600/3VL81) 1600 0.4 ... 1.0 × In 9 × In 1.5 ... 8xIR B 3VL87 16-1@@30-.... 1 1 unit 113 31.300
Order No. For price PU PS*/ PG Weight Order No. For price PU PS*/ PG Weight
Order No. supplement see page (UNIT, P. unit per PU Order No. supplement see page (UNIT, P. unit per PU
required, 2/32 SET, approx. required, 2/32 SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 06-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 10-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 10-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 16-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 16-3@@3@-.... 1 1 unit 113 2.400
B 3VL37 20-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 20-3@@3@-.... 1 1 unit 113 2.500
B 3VL37 25-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 25-3@@3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2@@36-.... 1 1 unit 113 5.900 B 3VL47 31-3@@36-.... 1 1 unit 113 5.900
B 3VL47 40-2@@36-.... 1 1 unit 113 5.900 B 3VL47 40-3@@36-.... 1 1 unit 113 5.900
B 3VL57 63-2@@36-.... 1 1 unit 113 9.300 B 3VL57 63-3@@36-.... 1 1 unit 113 9.300
B 3VL67 80-2@@36-.... 1 1 unit 113 16.000 B 3VL67 80-3@@36-.... 1 1 unit 113 16.000
B 3VL77 10-2@@36-.... 1 1 unit 113 25.000 B 3VL77 10-3@@36-.... 1 1 unit 113 25.000
B 3VL77 12-2@@36-.... 1 1 unit 113 25.000 B 3VL77 12-3@@36-.... 1 1 unit 113 25.000
B 3VL87 16-2@@30-.... 1 1 unit 113 31.300 B 3VL87 16-3@@30-.... 1 1 unit 113 31.300
>
SE
ME
>
SE
ME
LE LE
ETU22, LSIG function for 3-wire three-phase systems and time-based discrimination
With adjustable overcurrent releases, non-adjustable short-circuit releases,
ground fault delay tg = 0.1 ... 0.3 s, short-circuit delay tsd = 0 ... 0.5 s, ground-fault protection (G) can be switched off
VL160/3VL2 63 25 ... 63 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL27 06-1@@3@-.... 1 1 unit 113 2.400
100 40 ... 100 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL27 10-1@@3@-.... 1 1 unit 113 2.400
160 64 ... 160 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL27 16-1@@3@-.... 1 1 unit 113 2.400
VL250/3VL3 200 80 ... 200 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL37 20-1@@3@-.... 1 1 unit 113 2.500
250 100 ... 250 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL37 25-1@@3@-.... 1 1 unit 113 2.500
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL47 31-1@@36-.... 1 1 unit 113 5.900
400 160 ... 400 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL47 40-1@@36-.... 1 1 unit 113 5.900
VL630/3VL5 630 252 ... 630 10 × In 1.5 ... 9xIR 0.6 ... 1 × In, OFF B 3VL57 63-1@@36-.... 1 1 unit 113 9.300
VL800/3VL6 800 320 ... 800 8 × In 1.5 ... 7xIR 0.6 ... 1 × In, OFF B 3VL67 80-1@@36-.... 1 1 unit 113 16.000
VL1250/3VL7 1000 400 ... 1000 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL77 10-1@@36-.... 1 1 unit 113 25.000
1250 500 ... 1250 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL77 12-1@@36-.... 1 1 unit 113 25.000
VL1600/3VL81) 1600 640 ... 1600 9 × In 1.5 ... 8xIR 0.6 ... 1 × In, OFF B 3VL87 16-1@@30-.... 1 1 unit 113 31.300
Order No. For price PU PS*/ PG Weight Order No. For price PU PS*/ PG Weight
Order No. supplement see page (UNIT, P. unit per PU Order No. supplement see page (UNIT, P. unit per PU
required, 2/32 SET, approx. required, 2/32 SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 06-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 10-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 10-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 16-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 16-3@@3@-.... 1 1 unit 113 2.400
B 3VL37 20-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 20-3@@3@-.... 1 1 unit 113 2.500
B 3VL37 25-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 25-3@@3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2@@36-.... 1 1 unit 113 5.900 B 3VL47 31-3@@36-.... 1 1 unit 113 5.900
B 3VL47 40-2@@36-.... 1 1 unit 113 5.900 B 3VL47 40-3@@36-.... 1 1 unit 113 5.900
B 3VL57 63-2@@36-.... 1 1 unit 113 9.300 B 3VL57 63-3@@36-.... 1 1 unit 113 9.300
B 3VL67 80-2@@36-.... 1 1 unit 113 16.000 B 3VL67 80-3@@36-.... 1 1 unit 113 16.000
B 3VL77 10-2@@36-.... 1 1 unit 113 25.000 B 3VL77 10-3@@36-.... 1 1 unit 113 25.000
B 3VL77 12-2@@36-.... 1 1 unit 113 25.000 B 3VL77 12-3@@36-.... 1 1 unit 113 25.000
B 3VL87 16-2@@30-.... 1 1 unit 113 31.300 B 3VL87 16-3@@30-.... 1 1 unit 113 31.300
>
SG
MG
>
SG
MG
CAT.A n=250 A~ 25 CL
LCD-ETU42, LSIG function for 3-wire three-phase systems and time-based discrimination
With adjustable overcurrent releases, adjustable short-circuit releases
Vectorial summation current, ground fault delay tg = 0.1 ... 0.5 s, short-circuit delay tsd = 0 ... 0.5 s
VL160/3VL2 63 25 ... 63 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL27 06-1CL3@-.... 1 1 unit 113 2.400
100 40 ... 100 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL27 10-1CL3@-.... 1 1 unit 113 2.400
160 64 ... 160 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL27 16-1CL3@-.... 1 1 unit 113 2.400
VL250/3VL3 200 80 ... 200 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL37 20-1CL3@-.... 1 1 unit 113 2.500
250 100 ... 250 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL37 25-1CL3@-.... 1 1 unit 113 2.500
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL47 31-1CL36-.... 1 1 unit 113 5.900
400 160 ... 400 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL47 40-1CL36-.... 1 1 unit 113 5.900
VL630/3VL5 630 252 ... 630 10 × In 1.5 ... 9xIR 0.4 ... 1 × In B 3VL57 63-1CL36-.... 1 1 unit 113 9.300
VL800/3VL6 800 320 ... 800 8 × In 1.5 ... 7xIR 0.4 ... 1 × In B 3VL67 80-1CL36-.... 1 1 unit 113 16.000
VL1250/3VL7 1000 400 ... 1000 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL77 10-1CL36-.... 1 1 unit 113 25.000
1250 500 ... 1250 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL77 12-1CL36-.... 1 1 unit 113 25.000
VL1600/3VL81) 1600 640 ... 1600 9 × In 1.5 ... 8xIR 0.4 ... 1 × In B 3VL87 16-1CL30-.... 1 1 unit 113 31.300
NSE-00547a
L
ESC
S L1=178; L2=181
G I
L3=179; N=0
NSE0_00697
CAT.A n=250 A~ 25 CL
LCD-ETU42, LSIG function for 4-wire three-phase systems and time-based discrimination
With adjustable overcurrent releases, adjustable short-circuit releases. External current transformer required in addition, see pages 2/90.
Vectorial summation current, ground fault delay tg = 0.1 ... 0.5 s, short-circuit delay tsd = 0 ... 0.5 s
VL160/3VL2 63 25 ... 63 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL27 06-1CM3@-.... 1 1 unit 113 2.400
100 40 ... 100 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL27 10-1CM3@-.... 1 1 unit 113 2.400
160 64 ... 160 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL27 16-1CM3@-.... 1 1 unit 113 2.400
VL250/3VL3 200 80 ... 200 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL37 20-1CM3@-.... 1 1 unit 113 2.500
250 100 ... 250 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL37 25-1CM3@-.... 1 1 unit 113 2.500
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL47 31-1CM36-.... 1 1 unit 113 5.900
400 160 ... 400 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL47 40-1CM36-.... 1 1 unit 113 5.900
VL630/3VL5 630 252 ... 630 10 × In 1.5 ... 9xIR 0.4 ... 1 × In B 3VL57 63-1CM36-.... 1 1 unit 113 9.300
VL800/3VL6 800 320 ... 800 8 × In 1.5 ... 7xIR 0.4 ... 1 × In B 3VL67 80-1CM36-.... 1 1 unit 113 16.000
VL1250/3VL7 1000 400 ... 1000 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL77 10-1CM36-.... 1 1 unit 113 25.000
1250 500 ... 1250 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL77 12-1CM36-.... 1 1 unit 113 25.000
VL1600/3VL81) 1600 640 ... 1600 9 × In 1.5 ... 8xIR 0.4 ... 1 × In B 3VL87 16-1CM30-.... 1 1 unit 113 31.300
1)
Front busbar connection pieces are included in the scope of supply
and are to be fitted by the customer.
Order No. Basic price PU PS*/ PG Weight Order No. Basic price PU PS*/ PG Weight
Order No. supplement per PU (UNIT, P. unit per PU Order No. supplement per PU (UNIT, P. unit per PU
required, SET, approx. required, SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2CL3@-.... 1 1 unit 113 2.400 B 3VL27 06-3CL3@-.... 1 1 unit 113 2.400
B 3VL27 10-2CL3@-.... 1 1 unit 113 2.400 B 3VL27 10-3CL3@-.... 1 1 unit 113 2.400
B 3VL27 16-2CL3@-.... 1 1 unit 113 2.400 B 3VL27 16-3CL3@-.... 1 1 unit 113 2.400
B 3VL37 20-2CL3@-.... 1 1 unit 113 2.500 B 3VL37 20-3CL3@-.... 1 1 unit 113 2.500
B 3VL37 25-2CL3@-.... 1 1 unit 113 2.500 B 3VL37 25-3CL3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2CL36-.... 1 1 unit 113 5.900 B 3VL47 31-3CL36-.... 1 1 unit 113 5.900
B 3VL47 40-2CL36-.... 1 1 unit 113 5.900 B 3VL47 40-3CL36-.... 1 1 unit 113 5.900
B 3VL57 63-2CL36-.... 1 1 unit 113 9.300 B 3VL57 63-3CL36-.... 1 1 unit 113 9.300
B 3VL67 80-2CL36-.... 1 1 unit 113 16.000 B 3VL67 80-3CL36-.... 1 1 unit 113 16.000
B 3VL77 10-2CL36-.... 1 1 unit 113 25.000 B 3VL77 10-3CL36-.... 1 1 unit 113 25.000
B 3VL77 12-2CL36-.... 1 1 unit 113 25.000 B 3VL77 12-3CL36-.... 1 1 unit 113 25.000
B 3VL87 16-2CL30-.... 1 1 unit 113 31.300 B 3VL87 16-3CL30-.... 1 1 unit 113 31.300
B 3VL27 06-2CM3@-.... 1 1 unit 113 2.400 B 3VL27 06-3CM3@-.... 1 1 unit 113 2.400
B 3VL27 10-2CM3@-.... 1 1 unit 113 2.400 B 3VL27 10-3CM3@-.... 1 1 unit 113 2.400
B 3VL27 16-2CM3@-.... 1 1 unit 113 2.400 B 3VL27 16-3CM3@-.... 1 1 unit 113 2.400
B 3VL37 20-2CM3@-.... 1 1 unit 113 2.500 B 3VL37 20-3CM3@-.... 1 1 unit 113 2.500
B 3VL37 25-2CM3@-.... 1 1 unit 113 2.500 B 3VL37 25-3CM3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2CM36-.... 1 1 unit 113 5.900 B 3VL47 31-3CM36-.... 1 1 unit 113 5.900
B 3VL47 40-2CM36-.... 1 1 unit 113 5.900 B 3VL47 40-3CM36-.... 1 1 unit 113 5.900
B 3VL57 63-2CM36-.... 1 1 unit 113 9.300 B 3VL57 63-3CM36-.... 1 1 unit 113 9.300
B 3VL67 80-2CM36-.... 1 1 unit 113 16.000 B 3VL67 80-3CM36-.... 1 1 unit 113 16.000
B 3VL77 10-2CM36-.... 1 1 unit 113 25.000 B 3VL77 10-3CM36-.... 1 1 unit 113 25.000
B 3VL77 12-2CM36-.... 1 1 unit 113 25.000 B 3VL77 12-3CM36-.... 1 1 unit 113 25.000
B 3VL87 16-2CM30-.... 1 1 unit 113 31.300 B 3VL87 16-3CM30-.... 1 1 unit 113 31.300
ETU22, LSIG function for 4-wire three-phase systems and time-based discrimination
With adjustable overcurrent releases, non-adjustable short-circuit releases, external current transformers required in addition, see page 2/90.
Ground fault delay tg = 0.1 ... 0.3 s, short-circuit delay tsd = 0 ... 0.5 s, ground fault function (G) can be switched off.
VL160/3VL2 63 25 ... 63 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL27 06-1@@3@-.... 1 1 unit 113 2.400
100 40 ... 100 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL27 10-1@@3@-.... 1 1 unit 113 2.400
160 64 ... 160 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL27 16-1@@3@-.... 1 1 unit 113 2.400
VL250/3VL3 200 80 ... 200 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL37 20-1@@3@-.... 1 1 unit 113 2.500
250 100 ... 250 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL37 25-1@@3@-.... 1 1 unit 113 2.500
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL47 31-1@@36-.... 1 1 unit 113 5.900
400 160 ... 400 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL47 40-1@@36-.... 1 1 unit 113 5.900
VL630/3VL5 630 252 ... 630 10 × In 1.5 ... 9xIR 0.6 ... 1 × In, OFF B 3VL57 63-1@@36-.... 1 1 unit 113 9.300
VL800/3VL6 800 320 ... 800 8 × In 1.5 ... 7xIR 0.6 ... 1 × In, OFF B 3VL67 80-1@@36-.... 1 1 unit 113 16.000
VL1250/3VL7 1000 400 ... 1000 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL77 10-1@@36-.... 1 1 unit 113 25.000
1250 500 ... 1250 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL77 12-1@@36-.... 1 1 unit 113 25.000
VL1600/3VL81) 1600 640 ... 1600 9 × In 1.5 ... 8xIR 0.6 ... 1 × In, OFF B 3VL87 16-1@@30-.... 1 1 unit 113 31.300
Order No. For price PU PS*/ PG Weight Order No. For price PU PS*/ PG Weight
Order No. supplement see page (UNIT, P. unit per PU Order No. supplement see page (UNIT, P. unit per PU
required, 2/32 SET, approx. required, 2/32 SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 06-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 10-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 10-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 16-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 16-3@@3@-.... 1 1 unit 113 2.400
B 3VL37 20-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 20-3@@3@-.... 1 1 unit 113 2.500
B 3VL37 25-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 25-3@@3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2@@36-.... 1 1 unit 113 5.900 B 3VL47 31-3@@36-.... 1 1 unit 113 5.900
B 3VL47 40-2@@36-.... 1 1 unit 113 5.900 B 3VL47 40-3@@36-.... 1 1 unit 113 5.900
B 3VL57 63-2@@36-.... 1 1 unit 113 9.300 B 3VL57 63-3@@36-.... 1 1 unit 113 9.300
B 3VL67 80-2@@36-.... 1 1 unit 113 16.000 B 3VL67 80-3@@36-.... 1 1 unit 113 16.000
B 3VL77 10-2@@36-.... 1 1 unit 113 25.000 B 3VL77 10-3@@36-.... 1 1 unit 113 25.000
B 3VL77 12-2@@36-.... 1 1 unit 113 25.000 B 3VL77 12-3@@36-.... 1 1 unit 113 25.000
B 3VL87 16-2@@30-.... 1 1 unit 113 31.300 B 3VL87 16-3@@30-.... 1 1 unit 113 31.300
>
SH
MH
>
SH
MH
CAT.A n=250 A~ 25 CL
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In 1.5 ... 10xIR B 3VL47 31-1CH36-.... 1 1 unit 113 5.900
400 160 ... 400 1.25 ... 11 × In 1.5 ... 10xIR B 3VL47 40-1CH36-.... 1 1 unit 113 5.900
VL630/3VL5 630 252 ... 630 1.25 ... 10 × In 1.5 ... 9xIR B 3VL57 63-1CH36-.... 1 1 unit 113 9.300
VL800/3VL6 800 320 ... 800 1.25 ... 8 × In 1.5 ... 7xIR B 3VL67 80-1CH36-.... 1 1 unit 113 16.000
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 × In 1.5 ... 10xIR B 3VL77 10-1CH36-.... 1 1 unit 113 25.000
1250 500 ... 1250 1.25 ... 11 × In 1.5 ... 10xIR B 3VL77 12-1CH36-.... 1 1 unit 113 25.000
VL1600/3VL81) 1600 640 ... 1600 1.25 ... 9 × In 1.5 ... 8xIR B 3VL87 16-1CH30-.... 1 1 unit 113 31.300
1)
Front busbar connection pieces are included in the scope of supply
and are to be fitted by the customer.
Order No. Basic price PU PS*/ PG Weight Order No. Basic price PU PS*/ PG Weight
Order No. supplement per PU (UNIT, P. unit per PU Order No. supplement per PU (UNIT, P. unit per PU
required, SET, approx. required, SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2CH3@-.... 1 1 unit 113 2.400 B 3VL27 06-3CH3@-.... 1 1 unit 113 2.400
B 3VL27 10-2CH3@-.... 1 1 unit 113 2.400 B 3VL27 10-3CH3@-.... 1 1 unit 113 2.400
B 3VL27 16-2CH3@-.... 1 1 unit 113 2.400 B 3VL27 16-3CH3@-.... 1 1 unit 113 2.400
B 3VL37 20-2CH3@-.... 1 1 unit 113 2.500 B 3VL37 20-3CH3@-.... 1 1 unit 113 2.500
B 3VL37 25-2CH3@-.... 1 1 unit 113 2.500 B 3VL37 25-3CH3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2CH36-.... 1 1 unit 113 5.900 B 3VL47 31-3CH36-.... 1 1 unit 113 5.900
B 3VL47 40-2CH36-.... 1 1 unit 113 5.900 B 3VL47 40-3CH36-.... 1 1 unit 113 5.900
B 3VL57 63-2CH36-.... 1 1 unit 113 9.300 B 3VL57 63-3CH36-.... 1 1 unit 113 9.300
B 3VL67 80-2CH36-.... 1 1 unit 113 16.000 B 3VL67 80-3CH36-.... 1 1 unit 113 16.000
B 3VL77 10-2CH36-.... 1 1 unit 113 25.000 B 3VL77 10-3CH36-.... 1 1 unit 113 25.000
B 3VL77 12-2CH36-.... 1 1 unit 113 25.000 B 3VL77 12-3CH36-.... 1 1 unit 113 25.000
B 3VL87 16-2CH30-.... 1 1 unit 113 31.300 B 3VL87 16-3CH30-.... 1 1 unit 113 31.300
ETU10M, LI function
With thermal image, with non-adjustable trip class tC = 10, with phase failure sensitivity 40 % IR
VL160/3VL2 63 25 ... 63 1.25 ... 11 × In B 3VL27 06-1@@3@-.... 1 1 unit 113 2.400
100 40 ... 100 1.25 ... 11 × In B 3VL27 10-1@@3@-.... 1 1 unit 113 2.400
160 64 ... 160 1.25 ... 11 × In B 3VL27 16-1@@3@-.... 1 1 unit 113 2.400
VL250/3VL3 200 80 ... 200 1.25 ... 11 × In B 3VL37 20-1@@3@-.... 1 1 unit 113 2.500
250 100 ... 250 1.25 ... 11 × In B 3VL37 25-1@@3@-.... 1 1 unit 113 2.500
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 125 ... 315 1.25 ... 11 × In B 3VL47 31-1@@36-.... 1 1 unit 113 5.900
VL630/3VL5 500 200 ... 500 1.25 ... 12.5 × In B 3VL57 50-1@@36-.... 1 1 unit 113 9.300
NSE0_02082
L
.4 .4 IR .10 .01 Ii =11x In 30 10 TC Alarm
.4 .09 .02 >1.05
.4 20 20 =6x
Ii In
.4 .5 + .08 .03 10 30
Active
I X3 .9 .6 .07 .04 Test 10
.8 .7 xI n .06 .05 30 20 Ii =8x In
NSE0_01419
ETU30M, LI function
With thermal image, with adjustable trip class tC = 10, 20, 30, with phase failure sensitivity 40 % IR
VL160/3VL2 63 25 ... 63 6/8/11 × In B 3VL27 06-1@@3@-.... 1 1 unit 113 2.400
100 40 ... 100 6/8/11 × In B 3VL27 10-1@@3@-.... 1 1 unit 113 2.400
160 64 ... 160 6/8/11 × In B 3VL27 16-1@@3@-.... 1 1 unit 113 2.400
VL250/3VL3 200 80 ... 200 6/8/11 × In B 3VL37 20-1@@3@-.... 1 1 unit 113 2.500
250 100 ... 250 6/8/11 × In B 3VL37 25-1@@3@-.... 1 1 unit 113 2.500
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 125 ... 315 6/8/11 × In B 3VL47 31-1@@36-.... 1 1 unit 113 5.900
VL630/3VL5 500 200 ... 500 6/8/12.5 × In B 3VL57 50-1@@36-.... 1 1 unit 113 9.300
Communication:
• For accessories, see page 2/98.
• For more information see also chapters "Measuring Devices
and E-Counters" and "Software".
Order No. For price PU PS*/ PG Weight Order No. For price PU PS*/ PG Weight
Order No. supplement see page (UNIT, P. unit per PU Order No. supplement see page (UNIT, P. unit per PU
required, 2/32 SET, approx. required, 2/32 SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 06-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 10-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 10-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 16-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 16-3@@3@-.... 1 1 unit 113 2.400
B 3VL37 20-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 20-3@@3@-.... 1 1 unit 113 2.500
B 3VL37 25-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 25-3@@3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2@@36-.... 1 1 unit 113 5.900 B 3VL47 31-3@@36-.... 1 1 unit 113 5.900
B 3VL57 50-2@@36-.... 1 1 unit 113 9.300 B 3VL57 50-3@@36-.... 1 1 unit 113 9.300
>
SP
MP
>
SP
MP
B 3VL27 06-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 06-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 10-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 10-3@@3@-.... 1 1 unit 113 2.400
B 3VL27 16-2@@3@-.... 1 1 unit 113 2.400 B 3VL27 16-3@@3@-.... 1 1 unit 113 2.400
B 3VL37 20-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 20-3@@3@-.... 1 1 unit 113 2.500
B 3VL37 25-2@@3@-.... 1 1 unit 113 2.500 B 3VL37 25-3@@3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2@@36-.... 1 1 unit 113 5.900 B 3VL47 31-3@@36-.... 1 1 unit 113 5.900
B 3VL57 50-2@@36-.... 1 1 unit 113 9.300 B 3VL57 50-3@@36-.... 1 1 unit 113 9.300
>
SS
MS
>
SS
MS
LS LS
CAT.A n=250 A~ 25 CL
LCD-ETU40M, LI function
With thermal image, with adjustable trip class tC = 5, 10, 15, 20, 30, phase failure sensitivity adjustable in steps 5 ... 50 % IR
VL160/3VL2 63 25 ... 63 1.25 ... 11 × In B 3VL27 06-1CP3@-.... 1 1 unit 113 2.400
100 40 ... 100 1.25 ... 11 × In B 3VL27 10-1CP3@-.... 1 1 unit 113 2.400
160 64 ... 160 1.25 ... 11 × In B 3VL27 16-1CP3@-.... 1 1 unit 113 2.400
VL250/3VL3 200 80 ... 200 1.25 ... 11 × In B 3VL37 20-1CP3@-.... 1 1 unit 113 2.500
250 100 ... 250 1.25 ... 11 × In B 3VL37 25-1CP3@-.... 1 1 unit 113 2.500
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In B 3VL47 31-1CP36-.... 1 1 unit 113 5.900
VL630/3VL5 500 250 ... 500 1.25 ... 11 × In B 3VL57 50-1CP36-.... 1 1 unit 113 9.300
Order No. Basic price PU PS*/ PG Weight Order No. Basic price PU PS*/ PG Weight
Order No. supplement per PU (UNIT, P. unit per PU Order No. supplement per PU (UNIT, P. unit per PU
required, SET, approx. required, SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2CP3@-.... 1 1 unit 113 2.400 B 3VL27 06-3CP3@-.... 1 1 unit 113 2.400
B 3VL27 10-2CP3@-.... 1 1 unit 113 2.400 B 3VL27 10-3CP3@-.... 1 1 unit 113 2.400
B 3VL27 16-2CP3@-.... 1 1 unit 113 2.400 B 3VL27 16-3CP3@-.... 1 1 unit 113 2.400
B 3VL37 20-2CP3@-.... 1 1 unit 113 2.500 B 3VL37 20-3CP3@-.... 1 1 unit 113 2.500
B 3VL37 25-2CP3@-.... 1 1 unit 113 2.500 B 3VL37 25-3CP3@-.... 1 1 unit 113 2.500
> >
3 3
6 6
B 3VL47 31-2CP36-.... 1 1 unit 113 5.900 B 3VL47 31-3CP36-.... 1 1 unit 113 5.900
B 3VL57 50-2CP36-.... 1 1 unit 113 9.300 B 3VL57 50-3CP36-.... 1 1 unit 113 9.300
i
CAT.A
1250 2500
NSE0_00707
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 200 1250 ... 2500 B 3VL47 20-1DK36-.... 1 1 unit 113 5.700
250 2000 ... 4000 B 3VL47 25-1DK36-.... 1 1 unit 113 5.700
315 2000 ... 4000 B 3VL47 31-1DK36-.... 1 1 unit 113 5.700
VL630/3VL5 315 2000 ... 4000 B 3VL57 31-1DK36-.... 1 1 unit 113 9.000
500 3250 ... 6300 B 3VL57 50-1DK36-.... 1 1 unit 113 9.000
3-pole, fixed-mounted, for safe disconnection,
100 A to 1600 A, magnetic releases I
NSE0_00708
Connection type can be selected by assignment of the 12th position of the Order >
• Connection with box terminal 3
• Connection with screw terminal not in conjunction with RCD module at 3VL1 6
Order No. Basic price PU PS*/ PG Weight Order No. Basic price PU PS*/ PG Weight
Order No. supplement per PU (UNIT, P. unit per PU Order No. supplement per PU (UNIT, P. unit per PU
required, SET, approx. required, SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2DK3@-.... 1 1 unit 113 2.200 B 3VL27 06-3DK3@-.... 1 1 unit 113 2.200
B 3VL27 10-2DK3@-.... 1 1 unit 113 2.200 B 3VL27 10-3DK3@-.... 1 1 unit 113 2.200
B 3VL27 16-2DK3@-.... 1 1 unit 113 2.200 B 3VL27 16-3DK3@-.... 1 1 unit 113 2.200
B 3VL37 25-2DK3@-.... 1 1 unit 113 2.300 B 3VL37 25-3DK3@-.... 1 1 unit 113 2.300
> >
3 3
6 6
B 3VL47 20-2DK36-.... 1 1 unit 113 5.700 B 3VL47 20-3DK36-.... 1 1 unit 113 5.700
B 3VL47 25-2DK36-.... 1 1 unit 113 5.700 B 3VL47 25-3DK36-.... 1 1 unit 113 5.700
B 3VL47 31-2DK36-.... 1 1 unit 113 5.700 B 3VL47 31-3DK36-.... 1 1 unit 113 5.700
B 3VL57 31-2DK36-.... 1 1 unit 113 9.000 B 3VL57 31-3DK36-.... 1 1 unit 113 9.000
B 3VL57 50-2DK36-.... 1 1 unit 113 9.000 B 3VL57 50-3DK36-.... 1 1 unit 113 9.000
> >
3 3
6 6
B 3VL47 40-2DE36-.... 1 1 unit 113 5.700 B 3VL47 40-3DE36-.... 1 1 unit 113 5.700
B 3VL57 63-2DE36-.... 1 1 unit 113 9.000 B 3VL57 63-3DE36-.... 1 1 unit 113 9.000
B 3VL67 80-2DE36-.... 1 1 unit 113 15.700 B 3VL67 80-3DE36-.... 1 1 unit 113 15.700
B 3VL77 12-2DE36-.... 1 1 unit 113 23.500 B 3VL77 12-3DE36-.... 1 1 unit 113 23.500
B 3VL87 16-2DE30-.... 1 1 unit 113 29.800 B 3VL87 16-3DE30-.... 1 1 unit 113 29.800
Releases 63 A 100 A 160 A 200 A 250 A 315 A 400 A 500 A 630 A 800 A 1000 A 1250 A 1600 A
Price
ETU10 SB N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU10 MB N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU10 LB N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU12 SL N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU12 ML N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU12 SF N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU12 MF N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU20 SE N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU20 ME N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU20 LE N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU22 SG N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU22 MG N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU42 CL N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU42 CM N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU22 SH N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU22 MH N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
ETU40 CH N ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
H ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
L ✓ ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ ✓ ✓ ✓ ✓
✓ Available
-- Not available
Releases 63 A 100 A 160 A 200 A 250 A 315 A 400 A 500 A 630 A 800 A 1000 A 1250 A 1600 A
Price
ETU10M S P N ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
H ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
L ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
ETU10M M P N ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
H ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
L ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
ETU30M S S N ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
H ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
L ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
ETU30M M S N ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
H ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
L ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
ETU30M L S N ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
H ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
L ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
ETU40M C P N ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
H ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
L ✓ ✓ ✓ ✓ ✓ ✓ -- ✓ -- -- -- -- --
✓ Available
-- Not available
NSE0_00695
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal not in conjunction with RCD module 6
NSE0_-00541a
Ii I 16 DC
R
1.0
I n =160A
I
7 8
50 C
6 9 xI I I
R i
n ~ .8
TM = CAT.A xI n
5 10
NSE0_00704
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 200 160 ... 200 1000 ... 2000 B 3VL47 20-1EJ46-.... 1 1 unit 113 7.400
250 200 ... 250 1250 ... 2500 B 3VL47 25-1EJ46-.... 1 1 unit 113 7.400
315 250 ... 315 1575 ... 3150 B 3VL47 31-1EJ46-.... 1 1 unit 113 7.400
400 320 ... 400 2000 ... 4000 B 3VL47 40-1EJ46-.... 1 1 unit 113 7.400
VL630/3VL5 315 250 ... 315 1575 ... 3150 B 3VL57 31-1EJ46-.... 1 1 unit 113 11.200
400 320 ... 400 2000 ... 4000 B 3VL57 40-1EJ46-.... 1 1 unit 113 11.200
500 400 ... 500 2500 ... 5000 B 3VL57 50-1EJ46-.... 1 1 unit 113 11.200
630 500 ... 630 3150 ... 6300 B 3VL57 63-1EJ46-.... 1 1 unit 113 11.200
** Delivery time class A for Order No. supplement "0AA0", see page 2/57.
>
3
6
B 3VL27 05-2EJ4@-.... 1 1 unit 113 3.000 B 3VL27 05-3EJ4@-.... 1 1 unit 113 3.000
B 3VL27 06-2EJ4@-.... 1 1 unit 113 3.000 B 3VL27 06-3EJ4@-.... 1 1 unit 113 3.000
B 3VL27 08-2EJ4@-.... 1 1 unit 113 3.000 B 3VL27 08-3EJ4@-.... 1 1 unit 113 3.000
B 3VL27 10-2EJ4@-.... 1 1 unit 113 3.000 B 3VL27 10-3EJ4@-.... 1 1 unit 113 3.000
B 3VL27 12-2EJ4@-.... 1 1 unit 113 3.000 B 3VL27 12-3EJ4@-.... 1 1 unit 113 3.000
B 3VL27 16-2EJ4@-.... 1 1 unit 113 3.000 B 3VL27 16-3EJ4@-.... 1 1 unit 113 3.000
B 3VL37 20-2EJ4@-.... 1 1 unit 113 3.200 B 3VL37 20-3EJ4@-.... 1 1 unit 113 3.200
B 3VL37 25-2EJ4@-.... 1 1 unit 113 3.200 B 3VL37 25-3EJ4@-.... 1 1 unit 113 3.200
> >
3 3
6 6
B 3VL47 20-2EJ46-.... 1 1 unit 113 7.400 B 3VL47 20-3EJ46-.... 1 1 unit 113 7.400
B 3VL47 25-2EJ46-.... 1 1 unit 113 7.400 B 3VL47 25-3EJ46-.... 1 1 unit 113 7.400
B 3VL47 31-2EJ46-.... 1 1 unit 113 7.400 B 3VL47 31-3EJ46-.... 1 1 unit 113 7.400
B 3VL47 40-2EJ46-.... 1 1 unit 113 7.400 B 3VL47 40-3EJ46-.... 1 1 unit 113 7.400
B 3VL57 31-2EJ46-.... 1 1 unit 113 11.200 B 3VL57 31-3EJ46-.... 1 1 unit 113 11.200
B 3VL57 40-2EJ46-.... 1 1 unit 113 11.200 B 3VL57 40-3EJ46-.... 1 1 unit 113 11.200
B 3VL57 50-2EJ46-.... 1 1 unit 113 11.200 B 3VL57 50-3EJ46-.... 1 1 unit 113 11.200
B 3VL57 63-2EJ46-.... 1 1 unit 113 11.200 B 3VL57 63-3EJ46-.... 1 1 unit 113 11.200
** Delivery time class A for Order No. supplement "0AA0", see page 2/57.
Type Rated Current setting of the Operating current of the DT Icu up to 55 kA at 415 V, standard switching capacity N
N
current inverse-time delayed instantaneous ** See "Overview".
In overcurrent releases short-circuit releases "I" Order No. Basic price PU PS*/ PG Weight
"L" Ii per PU (UNIT, P. unit per PU
IR Order No. supplement
required, SET, M) approx.
A A A see page 2/57 kg
4-pole, fixed-mounted, for system protection, 16 A to 160 A,
thermal-magnetic releases LIN
NSE0_00539a
OFF
TM ~=
63A
50° C
CAT.A
NSE0_00695
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal not in conjunction with RCD module 6
NSE0_00539a
OFF
TM ~=
63A
50° C
CAT.A
NSE0_00695
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal not in conjunction with RCD module 6
** Delivery time class A for Order No. supplement "0AA0", see page 2/57.
>
3
6
>
3
6
** Delivery time class A for Order No. supplement "0AA0", see page 2/57.
Type Rated Current setting of the Operating current of the DT Icu up to 55 kA at 415 V, standard switching capacity N
N
current inverse-time delayed instantaneous See "Overview".
In overcurrent releases short-circuit releases "I" Order No. Basic price PU PS*/ PG Weight
"L" Ii per PU (UNIT, P. unit per PU
IR Order No. supplement
required, SET, M) approx.
A A A see page 2/57 kg
4-pole, fixed-mounted, for system protection, 16 A to 630 A,
thermal-magnetic releases LIN
NSE0_-00541a
Ii I 16 DC
R
1.0
I n =160A
I
L 7 8
50 C
6 9 xI I I
R i
n ~ .8
I 5 10
TM = CAT.A xI n
NSE0_00691
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 200 160 ... 200 1000 ... 2000 B 3VL47 20-1EM46-.... 1 1 unit 113 7.400
250 200 ... 250 1250 ... 2500 B 3VL47 25-1EM46-.... 1 1 unit 113 7.400
315 250 ... 315 1575 ... 3150 B 3VL47 31-1EM46-.... 1 1 unit 113 7.400
400 320 ... 400 2000 ... 4000 B 3VL47 40-1EM46-.... 1 1 unit 113 7.400
VL630/3VL5 315 250 ... 315 1575 ... 3150 B 3VL57 31-1EM46-.... 1 1 unit 113 11.200
400 320 ... 400 2000 ... 4000 B 3VL57 40-1EM46-.... 1 1 unit 113 11.200
500 400 ... 500 2500 ... 5000 B 3VL57 50-1EM46-.... 1 1 unit 113 11.200
630 500 ... 630 3150 ... 6300 B 3VL57 63-1EM46-.... 1 1 unit 113 11.200
NSE0_-00541a
Ii I 16 DC
R
1.0
I n =160A
I
L 7 8
50 C
6 9 xI I I
R i
n ~ .8
I 5 10
TM = CAT.A xI n
NSE0_00691
2 4 6
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 200 160 ... 200 1000 ... 2000 B 3VL47 20-1EC46-.... 1 1 unit 113 7.400
250 200 ... 250 1250 ... 2500 B 3VL47 25-1EC46-.... 1 1 unit 113 7.400
315 250 ... 315 1575 ... 3150 B 3VL47 31-1EC46-.... 1 1 unit 113 7.400
400 320 ... 400 2000 ... 4000 B 3VL47 40-1EC46-.... 1 1 unit 113 7.400
VL630/3VL5 315 250 ... 315 1575 ... 3150 B 3VL57 31-1EC46-.... 1 1 unit 113 11.200
400 320 ... 400 2000 ... 4000 B 3VL57 40-1EC46-.... 1 1 unit 113 11.200
500 400 ... 500 2500 ... 5000 B 3VL57 50-1EC46-.... 1 1 unit 113 11.200
630 500 ... 630 3150 ... 6300 B 3VL57 63-1EC46-.... 1 1 unit 113 11.200
B 3VL27 05-2EM4@-.... 1 1 unit 113 3.000 B 3VL27 05-3EM4@-.... 1 1 unit 113 3.000
B 3VL27 06-2EM4@-.... 1 1 unit 113 3.000 B 3VL27 06-3EM4@-.... 1 1 unit 113 3.000
B 3VL27 08-2EM4@-.... 1 1 unit 113 3.000 B 3VL27 08-3EM4@-.... 1 1 unit 113 3.000
B 3VL27 10-2EM4@-.... 1 1 unit 113 3.000 B 3VL27 10-3EM4@-.... 1 1 unit 113 3.000
B 3VL27 12-2EM4@-.... 1 1 unit 113 3.000 B 3VL27 12-3EM4@-.... 1 1 unit 113 3.000
B 3VL27 16-2EM4@-.... 1 1 unit 113 3.000 B 3VL27 16-3EM4@-.... 1 1 unit 113 3.000
B 3VL37 20-2EM4@-.... 1 1 unit 113 3.200 B 3VL37 20-3EM4@-.... 1 1 unit 113 3.200
B 3VL37 25-2EM4@-.... 1 1 unit 113 3.200 B 3VL37 25-3EM4@-.... 1 1 unit 113 3.200
> >
3 3
6 6
B 3VL47 20-2EM46-.... 1 1 unit 113 7.400 B 3VL47 20-3EM46-.... 1 1 unit 113 7.400
B 3VL47 25-2EM46-.... 1 1 unit 113 7.400 B 3VL47 25-3EM46-.... 1 1 unit 113 7.400
B 3VL47 31-2EM46-.... 1 1 unit 113 7.400 B 3VL47 31-3EM46-.... 1 1 unit 113 7.400
B 3VL47 40-2EM46-.... 1 1 unit 113 7.400 B 3VL47 40-3EM46-.... 1 1 unit 113 7.400
B 3VL57 31-2EM46-.... 1 1 unit 113 11.200 B 3VL57 31-3EM46-.... 1 1 unit 113 11.200
B 3VL57 40-2EM46-.... 1 1 unit 113 11.200 B 3VL57 40-3EM46-.... 1 1 unit 113 11.200
B 3VL57 50-2EM46-.... 1 1 unit 113 11.200 B 3VL57 50-3EM46-.... 1 1 unit 113 11.200
B 3VL57 63-2EM46-.... 1 1 unit 113 11.200 B 3VL57 63-3EM46-.... 1 1 unit 113 11.200
B 3VL27 12-2EC4@-.... 1 1 unit 113 3.000 B 3VL27 12-3EC4@-.... 1 1 unit 113 3.000
B 3VL27 16-2EC4@-.... 1 1 unit 113 3.000 B 3VL27 16-3EC4@-.... 1 1 unit 113 3.000
B 3VL37 20-2EC4@-.... 1 1 unit 113 3.200 B 3VL37 20-3EC4@-.... 1 1 unit 113 3.200
B 3VL37 25-2EC4@-.... 1 1 unit 113 3.200 B 3VL37 25-3EC4@-.... 1 1 unit 113 3.200
> >
3 3
6 6
B 3VL47 20-2EC46-.... 1 1 unit 113 7.400 B 3VL47 20-3EC46-.... 1 1 unit 113 7.400
B 3VL47 25-2EC46-.... 1 1 unit 113 7.400 B 3VL47 25-3EC46-.... 1 1 unit 113 7.400
B 3VL47 31-2EC46-.... 1 1 unit 113 7.400 B 3VL47 31-3EC46-.... 1 1 unit 113 7.400
B 3VL47 40-2EC46-.... 1 1 unit 113 7.400 B 3VL47 40-3EC46-.... 1 1 unit 113 7.400
B 3VL57 31-2EC46-.... 1 1 unit 113 11.200 B 3VL57 31-3EC46-.... 1 1 unit 113 11.200
B 3VL57 40-2EC46-.... 1 1 unit 113 11.200 B 3VL57 40-3EC46-.... 1 1 unit 113 11.200
B 3VL57 50-2EC46-.... 1 1 unit 113 11.200 B 3VL57 50-3EC46-.... 1 1 unit 113 11.200
B 3VL57 63-2EC46-.... 1 1 unit 113 11.200 B 3VL57 63-3EC46-.... 1 1 unit 113 11.200
ETU10, LI function
With adjustable overcurrent releases, adjustable short-circuit releases
VL160/3VL2 63 25 ... 63 1.25 ... 11 × In B 3VL27 06-1@@4@-.... 1 1 unit 113 3.100
100 40 ... 100 1.25 ... 11 × In B 3VL27 10-1@@4@-.... 1 1 unit 113 3.100
160 64 ... 160 1.25 ... 11 × In B 3VL27 16-1@@4@-.... 1 1 unit 113 3.100
VL250/3VL3 200 80 ... 200 1.25 ... 11 × In B 3VL37 20-1@@4@-.... 1 1 unit 113 3.300
250 100 ... 250 1.25 ... 11 × In B 3VL37 25-1@@4@-.... 1 1 unit 113 3.300
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In B 3VL47 31-1@@46-.... 1 1 unit 113 7.600
400 160 ... 400 1.25 ... 11 × In B 3VL47 40-1@@46-.... 1 1 unit 113 7.600
VL630/3VL5 630 252 ... 630 1.25 ... 10 × In B 3VL57 63-1@@46-.... 1 1 unit 113 11.700
VL800/3VL6 800 320 ... 800 1.25 ... 8 × In B 3VL67 80-1@@46-.... 1 1 unit 113 20.500
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 × In B 3VL77 10-1@@46-.... 1 1 unit 113 33.500
1250 500 ... 1250 1.25 ... 11 × In B 3VL77 12-1@@46-.... 1 1 unit 113 33.500
VL1600/3VL81) 1600 640 ... 1600 1.25 ... 9 × In B 3VL87 16-1@@40-.... 1 1 unit 113 40.800
NSE0_00691
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In B 3VL47 31-1@@46-.... 1 1 unit 113 7.600
400 160 ... 400 1.25 ... 11 × In B 3VL47 40-1@@46-.... 1 1 unit 113 7.600
VL630/3VL5 630 252 ... 630 1.25 ... 10 × In B 3VL57 63-1@@46-.... 1 1 unit 113 11.700
VL800/3VL6 800 320 ... 800 1.25 ... 8 × In B 3VL67 80-1@@46-.... 1 1 unit 113 20.500
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 × In B 3VL77 10-1@@46-.... 1 1 unit 113 33.500
1250 500 ... 1250 1.25 ... 11 × In B 3VL77 12-1@@46-.... 1 1 unit 113 33.500
VL1600/3VL81) 1600 640 ... 1600 1.25 ... 9 × In B 3VL87 16-1@@40-.... 1 1 unit 113 40.800
Order No. For price PU PS*/ PG Weight Order No. For price PU PS*/ PG Weight
Order No. supplement see page (UNIT, P. unit per PU Order No. supplement see page (UNIT, P. unit per PU
required, 2/54 SET, approx. required, 2/54 SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 06-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 10-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 10-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 16-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 16-3@@4@-.... 1 1 unit 113 3.100
B 3VL37 20-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 20-3@@4@-.... 1 1 unit 113 3.300
B 3VL37 25-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 25-3@@4@-.... 1 1 unit 113 3.300
> >
3 3
6 6
B 3VL47 31-2@@46-.... 1 1 unit 113 7.600 B 3VL47 31-3@@46-.... 1 1 unit 113 7.600
B 3VL47 40-2@@46-.... 1 1 unit 113 7.600 B 3VL47 40-3@@46-.... 1 1 unit 113 7.600
B 3VL57 63-2@@46-.... 1 1 unit 113 11.700 B 3VL57 63-3@@46-.... 1 1 unit 113 11.700
B 3VL67 80-2@@46-.... 1 1 unit 113 20.500 B 3VL67 80-3@@46-.... 1 1 unit 113 20.500
B 3VL77 10-2@@46-.... 1 1 unit 113 33.500 B 3VL77 10-3@@46-.... 1 1 unit 113 33.500
B 3VL77 12-2@@46-.... 1 1 unit 113 33.500 B 3VL77 12-3@@46-.... 1 1 unit 113 33.500
B 3VL87 16-2@@40-.... 1 1 unit 113 40.800 B 3VL87 16-3@@40-.... 1 1 unit 113 40.800
>
TB
NB
>
TB
NB
B 3VL27 06-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 06-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 10-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 10-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 16-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 16-3@@4@-.... 1 1 unit 113 3.100
B 3VL37 20-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 20-3@@4@-.... 1 1 unit 113 3.300
B 3VL37 25-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 25-3@@4@-.... 1 1 unit 113 3.300
> >
3 3
6 6
B 3VL47 31-2@@46-.... 1 1 unit 113 7.600 B 3VL47 31-3@@46-.... 1 1 unit 113 7.600
B 3VL47 40-2@@46-.... 1 1 unit 113 7.600 B 3VL47 40-3@@46-.... 1 1 unit 113 7.600
B 3VL57 63-2@@46-.... 1 1 unit 113 11.700 B 3VL57 63-3@@46-.... 1 1 unit 113 11.700
B 3VL67 80-2@@46-.... 1 1 unit 113 20.500 B 3VL67 80-3@@46-.... 1 1 unit 113 20.500
B 3VL77 10-2@@46-.... 1 1 unit 113 33.500 B 3VL77 10-3@@46-.... 1 1 unit 113 33.500
B 3VL77 12-2@@46-.... 1 1 unit 113 33.500 B 3VL77 12-3@@46-.... 1 1 unit 113 33.500
B 3VL87 16-2@@40-.... 1 1 unit 113 40.800 B 3VL87 16-3@@40-.... 1 1 unit 113 40.800
>
TA
NA
>
TA
NA
LA LA
Communication: • For more information see also chapters "Measuring Devices and
•For accessories, see page 2/98. E-Counters" and "Software".
Type Rated Current Operating Ground-fault DT Icu up to 55 kA at 415 V, standard switching capacity N
N
current setting of the current of the protection "G" See "Overview".
In inverse-time instantaneous Ig Order No. For price PU PS*/ PG Weight
delayed short-circuit see page (UNIT, P. unit per PU
overcurrent releases "I" Order No. supplement
required, 2/54 SET, M) approx.
releases "L" Ii
IR see page 2/57
A A A A kg
4-pole, fixed-mounted, for system protection, 63 A to 1600 A,
electronic releases LING
NSE0_02079
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL47 31-1@@46-.... 1 1 unit 113 7.600
400 160 ... 400 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL47 40-1@@46-.... 1 1 unit 113 7.600
VL630/3VL5 630 252 ... 630 1.25 ... 10 × In 0.6 ... 1 × In, OFF B 3VL57 63-1@@46-.... 1 1 unit 113 11.700
VL800/3VL6 800 320 ... 800 1.25 ... 8 × In 0.6 ... 1 × In, OFF B 3VL67 80-1@@46-.... 1 1 unit 113 20.500
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL77 10-1@@46-.... 1 1 unit 113 33.500
1250 500 ... 1250 1.25 ... 11 × In 0.6 ... 1 × In, OFF B 3VL77 12-1@@46-.... 1 1 unit 113 33.500
VL1600/3VL81) 1600 640 ... 1600 1.25 ... 9 × In 0.6 ... 1 × In, OFF B 3VL87 16-1@@40-.... 1 1 unit 113 40.800
B 3VL27 06-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 06-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 10-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 10-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 16-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 16-3@@4@-.... 1 1 unit 113 3.100
B 3VL37 20-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 20-3@@4@-.... 1 1 unit 113 3.300
B 3VL37 25-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 25-3@@4@-.... 1 1 unit 113 3.300
> >
3 3
6 6
B 3VL47 31-2@@46-.... 1 1 unit 113 7.600 B 3VL47 31-3@@46-.... 1 1 unit 113 7.600
B 3VL47 40-2@@46-.... 1 1 unit 113 7.600 B 3VL47 40-3@@46-.... 1 1 unit 113 7.600
B 3VL57 63-2@@46-.... 1 1 unit 113 11.700 B 3VL57 63-3@@46-.... 1 1 unit 113 11.700
B 3VL67 80-2@@46-.... 1 1 unit 113 20.500 B 3VL67 80-3@@46-.... 1 1 unit 113 20.500
B 3VL77 10-2@@46-.... 1 1 unit 113 33.500 B 3VL77 10-3@@46-.... 1 1 unit 113 33.500
B 3VL77 12-2@@46-.... 1 1 unit 113 33.500 B 3VL77 12-3@@46-.... 1 1 unit 113 33.500
B 3VL87 16-2@@40-.... 1 1 unit 113 40.800 B 3VL87 16-3@@40-.... 1 1 unit 113 40.800
>
TN
NN
>
TN
NN
Type Rated Current setting of Operating current S function short- DT Icu up to 55 kA at 415 V,
N
current the inverse-time of the instanta- circuit protection standard switching capacity N
In delayed over- neous short-circuit (short-time see "Overview"
current releases releases "I" delayed) Order No. Basic price PU PS*/ PG Weight
"L" Ii S per PU (UNIT, P. unit per PU
IR Order No. supple-
ment required, SET, M) approx.
see page 2/57
A A A A kg
4-pole, fixed-mounted, for system protection - generator protection,
63 A to 1600 A, electronic releases LI, LSI, LIN, LSIN
NSE-00547a
L
ESC
S L1=178; L2=181
I
L3=179; N=0
NSE0_00696
CAT.A n=250 A~ 25 CL
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In 1.5 ... 10xIR B 3VL47 31-1CJ46-.... 1 1 unit 113 7.600
400 160 ... 400 1.25 ... 11 × In 1.5 ... 10xIR B 3VL47 40-1CJ46-.... 1 1 unit 113 7.600
VL630/3VL5 630 252 ... 630 1.25 ... 10 × In 1.5 ... 9xIR B 3VL57 63-1CJ46-.... 1 1 unit 113 11.700
VL800/3VL6 800 320 ... 800 1.25 ... 8 × In 1.5 ... 7xIR B 3VL67 80-1CJ46-.... 1 1 unit 113 20.500
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 × In 1.5 ... 10xIR B 3VL77 10-1CJ46-.... 1 1 unit 113 33.500
1250 500 ... 1250 1.25 ... 11 × In 1.5 ... 10xIR B 3VL77 12-1CJ46-.... 1 1 unit 113 33.500
VL1600/3VL81) 1600 640 ... 1600 1.25 ... 9 × In 1.5 ... 8xIR B 3VL87 16-1CJ40-.... 1 1 unit 113 40.800
Order No. Basic price PU PS*/ PG Weight Order No. Basic price PU PS*/ PG Weight
Order No. supplement per PU (UNIT, P. unit per PU Order No. supplement per PU (UNIT, P. unit per PU
required, SET, approx. required, SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2CJ4@-.... 1 1 unit 113 3.100 B 3VL27 06-3CJ4@-.... 1 1 unit 113 3.100
B 3VL27 10-2CJ4@-.... 1 1 unit 113 3.100 B 3VL27 10-3CJ4@-.... 1 1 unit 113 3.100
B 3VL27 16-2CJ4@-.... 1 1 unit 113 3.100 B 3VL27 16-3CJ4@-.... 1 1 unit 113 3.100
B 3VL37 20-2CJ4@-.... 1 1 unit 113 3.300 B 3VL37 20-3CJ4@-.... 1 1 unit 113 3.300
B 3VL37 25-2CJ4@-.... 1 1 unit 113 3.300 B 3VL37 25-3CJ4@-.... 1 1 unit 113 3.300
> >
3 3
6 6
B 3VL47 31-2CJ46-.... 1 1 unit 113 7.600 B 3VL47 31-3CJ46-.... 1 1 unit 113 7.600
B 3VL47 40-2CJ46-.... 1 1 unit 113 7.600 B 3VL47 40-3CJ46-.... 1 1 unit 113 7.600
B 3VL57 63-2CJ46-.... 1 1 unit 113 11.700 B 3VL57 63-3CJ46-.... 1 1 unit 113 11.700
B 3VL67 80-2CJ46-.... 1 1 unit 113 20.500 B 3VL67 80-3CJ46-.... 1 1 unit 113 20.500
B 3VL77 10-2CJ46-.... 1 1 unit 113 33.500 B 3VL77 10-3CJ46-.... 1 1 unit 113 33.500
B 3VL77 12-2CJ46-.... 1 1 unit 113 33.500 B 3VL77 12-3CJ46-.... 1 1 unit 113 33.500
B 3VL87 16-2CJ40-.... 1 1 unit 113 40.800 B 3VL87 16-3CJ40-.... 1 1 unit 113 40.800
CAT.A n=250 A~ 25 CL
LCD-ETU42, LSIG/LSING function for 4-wire three-phase systems and time-based discrimination
With adjustable overcurrent releases, adjustable short-circuit releases
Ground fault delay tg = 0.1 ... 0.5 s, short-circuit delay tsd = 0 ... 0.3 s
with overcurrent and short-circuit release in 4th pole (N), N protection = 50 ... 100 %, OFF
VL160/3VL2 63 25 ... 63 1.25 ... 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL27 06-1CN4@-.... 1 1 unit 113 3.100
100 40 ... 100 1.25 ... 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL27 10-1CN4@-.... 1 1 unit 113 3.100
160 64 ... 160 1.25 ... 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL27 16-1CN4@-.... 1 1 unit 113 3.100
VL250/3VL3 200 80 ... 200 1.25 ... 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL37 20-1CN4@-.... 1 1 unit 113 3.300
250 100 ... 250 1.25 ... 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL37 25-1CN4@-.... 1 1 unit 113 3.300
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 1.25 ... 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL47 31-1CN46-.... 1 1 unit 113 7.600
400 160 ... 400 1.25 ... 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL47 40-1CN46-.... 1 1 unit 113 7.600
VL630/3VL5 630 252 ... 630 1.25 ... 10 × In 1.5 ... 9xIR 0.4 ... 1 × In B 3VL57 63-1CN46-.... 1 1 unit 113 11.700
VL800/3VL6 800 320 ... 800 1.25 ... 8 × In 1.5 ... 7xIR 0.4 ... 1 × In B 3VL67 80-1CN46-.... 1 1 unit 113 20.500
VL1250/3VL7 1000 400 ... 1000 1.25 ... 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL77 10-1CN46-.... 1 1 unit 113 33.500
1250 500 ... 1250 1.25 ... 11 × In 1.5 ... 10xIR 0.4 ... 1 × In B 3VL77 12-1CN46-.... 1 1 unit 113 33.500
VL1600/3VL81) 1600 640 ... 1600 1.25 ... 9 × In 1.5 ... 8xIR 0.4 ... 1 × In B 3VL87 16-1CN40-.... 1 1 unit 113 40.800
Order No. Basic price PU PS*/ PG Weight Order No. Basic price PU PS*/ PG Weight
Order No. supplement per PU (UNIT, P. unit per PU Order No. supplement per PU (UNIT, P. unit per PU
required, SET, approx. required, SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2CN4@-.... 1 1 unit 113 3.100 B 3VL27 06-3CN4@-.... 1 1 unit 113 3.100
B 3VL27 10-2CN4@-.... 1 1 unit 113 3.100 B 3VL27 10-3CN4@-.... 1 1 unit 113 3.100
B 3VL27 16-2CN4@-.... 1 1 unit 113 3.100 B 3VL27 16-3CN4@-.... 1 1 unit 113 3.100
B 3VL37 20-2CN4@-.... 1 1 unit 113 3.300 B 3VL37 20-3CN4@-.... 1 1 unit 113 3.300
B 3VL37 25-2CN4@-.... 1 1 unit 113 3.300 B 3VL37 25-3CN4@-.... 1 1 unit 113 3.300
> >
3 3
6 6
B 3VL47 31-2CN46-.... 1 1 unit 113 7.600 B 3VL47 31-3CN46-.... 1 1 unit 113 7.600
B 3VL47 40-2CN46-.... 1 1 unit 113 7.600 B 3VL47 40-3CN46-.... 1 1 unit 113 7.600
B 3VL57 63-2CN46-.... 1 1 unit 113 11.700 B 3VL57 63-3CN46-.... 1 1 unit 113 11.700
B 3VL67 80-2CN46-.... 1 1 unit 113 20.500 B 3VL67 80-3CN46-.... 1 1 unit 113 20.500
B 3VL77 10-2CN46-.... 1 1 unit 113 33.500 B 3VL77 10-3CN46-.... 1 1 unit 113 33.500
B 3VL77 12-2CN46-.... 1 1 unit 113 33.500 B 3VL77 12-3CN46-.... 1 1 unit 113 33.500
B 3VL87 16-2CN40-.... 1 1 unit 113 40.800 B 3VL87 16-3CN40-.... 1 1 unit 113 40.800
S .9 .5 7 2.5 .2 .2
2 Active
.3 I t
2
I X3 .8 .6 6 3 I t .1
x I n .7 .63 5 4 x I R ON .5 .4 OFF
NSE0_00692
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 11 × In 1.5 ... 10xIR B 3VL47 31-1@@46-.... 1 1 unit 113 7.600
400 160 ... 400 11 × In 1.5 ... 10xIR B 3VL47 40-1@@46-.... 1 1 unit 113 7.600
VL630/3VL5 630 252 ... 630 10 × In 1.5 ... 9xIR B 3VL57 63-1@@46-.... 1 1 unit 113 11.700
VL800/3VL6 800 320 ... 800 8 × In 1.5 ... 7xIR B 3VL67 80-1@@46-.... 1 1 unit 113 20.500
VL1250/3VL7 1000 400 ... 1000 11 × In 1.5 ... 10xIR B 3VL77 10-1@@46-.... 1 1 unit 113 33.500
1250 500 ... 1250 11 × In 1.5 ... 10xIR B 3VL77 12-1@@46-.... 1 1 unit 113 33.500
VL1600/3VL81) 1600 640 ... 1600 9 × In 1.5 ... 8xIR B 3VL87 16-1@@40-.... 1 1 unit 113 40.800
S .9 .5 7 2.5 .2 .2
2 Active
.3 I t IN
2
I X3 .8 .6 6 3 I t .1 IN
x I n .7 .63 5 4 x I R ON .5 .4 OFF 100% 50%
NSE0_00692
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 0.4 ...1.0 × In 11 × In 1.5 ... 10xIR B 3VL47 31-1@@46-.... 1 1 unit 113 7.600
400 0.4 ...1.0 × In 11 × In 1.5 ... 10xIR B 3VL47 40-1@@46-.... 1 1 unit 113 7.600
VL630/3VL5 630 0.4 ...1.0 × In 10 × In 1.5 ... 9xIR B 3VL57 63-1@@46-.... 1 1 unit 113 11.700
VL800/3VL6 800 0.4 ...1.0 × In 8 × In 1.5 ... 7xIR B 3VL67 80-1@@46-.... 1 1 unit 113 20.500
VL1250/3VL7 1000 0.4 ...1.0 × In 11 × In 1.5 ... 10xIR B 3VL77 10-1@@46-.... 1 1 unit 113 33.500
1250 0.4 ...1.0 × In 11 × In 1.5 ... 10xIR B 3VL77 12-1@@46-.... 1 1 unit 113 33.500
VL1600/3VL81) 1600 0.4 ...1.0 × In 9 × In 1.5 ... 8xIR B 3VL87 16-1@@40-.... 1 1 unit 113 40.800
Front busbar connection pieces are included in the scope of supply • For accessories, see page 2/98.
and are to be fitted by the customer.
• For more information see also chapters "Measuring Devices
Communication: and E-Counters" and "Software".
Order No. For price PU PS*/ PG Weight Order No. For price PU PS*/ PG Weight
Order No. supplement see page (UNIT, P. unit per PU Order No. supplement see page (UNIT, P. unit per PU
required, 2/54 SET, approx. required, 2/54 SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 06-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 10-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 10-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 16-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 16-3@@4@-.... 1 1 unit 113 3.100
B 3VL37 20-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 20-3@@4@-.... 1 1 unit 113 3.300
B 3VL37 25-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 25-3@@4@-.... 1 1 unit 113 3.300
> >
3 3
6 6
B 3VL47 31-2@@46-.... 1 1 unit 113 7.600 B 3VL47 31-3@@46-.... 1 1 unit 113 7.600
B 3VL47 40-2@@46-.... 1 1 unit 113 7.600 B 3VL47 40-3@@46-.... 1 1 unit 113 7.600
B 3VL57 63-2@@46-.... 1 1 unit 113 11.700 B 3VL57 63-3@@46-.... 1 1 unit 113 11.700
B 3VL67 80-2@@46-.... 1 1 unit 113 20.500 B 3VL67 80-3@@46-.... 1 1 unit 113 20.500
B 3VL77 10-2@@46-.... 1 1 unit 113 33.500 B 3VL77 10-3@@46-.... 1 1 unit 113 33.500
B 3VL77 12-2@@46-.... 1 1 unit 113 33.500 B 3VL77 12-3@@46-.... 1 1 unit 113 33.500
B 3VL87 16-2@@40-.... 1 1 unit 113 40.800 B 3VL87 16-3@@40-.... 1 1 unit 113 40.800
>
TE
NE
>
TE
NE
B 3VL27 06-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 06-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 10-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 10-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 16-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 16-3@@4@-.... 1 1 unit 113 3.100
B 3VL37 20-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 20-3@@4@-.... 1 1 unit 113 3.300
B 3VL37 25-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 25-3@@4@-.... 1 1 unit 113 3.300
> >
3 3
6 6
B 3VL47 31-2@@46-.... 1 1 unit 113 7.600 B 3VL47 31-3@@46-.... 1 1 unit 113 7.600
B 3VL47 40-2@@46-.... 1 1 unit 113 7.600 B 3VL47 40-3@@46-.... 1 1 unit 113 7.600
B 3VL57 63-2@@46-.... 1 1 unit 113 11.700 B 3VL57 63-3@@46-.... 1 1 unit 113 11.700
B 3VL67 80-2@@46-.... 1 1 unit 113 20.500 B 3VL67 80-3@@46-.... 1 1 unit 113 20.500
B 3VL77 10-2@@46-.... 1 1 unit 113 33.500 B 3VL77 10-3@@46-.... 1 1 unit 113 33.500
B 3VL77 12-2@@46-.... 1 1 unit 113 33.500 B 3VL77 12-3@@46-.... 1 1 unit 113 33.500
B 3VL87 16-2@@40-.... 1 1 unit 113 40.800 B 3VL87 16-3@@40-.... 1 1 unit 113 40.800
>
TF
NF
>
TF
NF
LF LF
ETU22, LSING function for 4-wire three-phase systems and time-based discrimination
With adjustable overcurrent releases, adjustable short-circuit releases,
ground fault delay tg = 0.1 ... 0.3 s, ground-fault protection (G) can be switched off, short-circuit delay tsd = 0 ... 0.5 s
with overcurrent and short-circuit release in 4th pole (N), N protection = 50 ... 100 %, OFF
VL160/3VL2 63 25 ... 63 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL27 06-1@@4@-.... 1 1 unit 113 3.100
100 40 ... 100 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL27 10-1@@4@-.... 1 1 unit 113 3.100
160 64 ... 160 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL27 16-1@@4@-.... 1 1 unit 113 3.100
VL250/3VL3 200 80 ... 200 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL37 20-1@@4@-.... 1 1 unit 113 3.300
250 100 ... 250 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL37 25-1@@4@-.... 1 1 unit 113 3.300
Connection type can be selected by assignment of the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal 6
VL400/3VL4 315 128 ... 315 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL47 31-1@@46-.... 1 1 unit 113 7.600
400 160 ... 400 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL47 40-1@@46-.... 1 1 unit 113 7.600
VL630/3VL5 630 252 ... 630 10 × In 1.5 ... 9xIR 0.6 ... 1 × In, OFF B 3VL57 63-1@@46-.... 1 1 unit 113 11.700
VL800/3VL6 800 320 ... 800 8 × In 1.5 ... 7xIR 0.6 ... 1 × In, OFF B 3VL67 80-1@@46-.... 1 1 unit 113 20.500
VL1250/3VL7 1000 400 ... 1000 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL77 10-1@@46-.... 1 1 unit 113 33.500
1250 500 ... 1250 11 × In 1.5 ... 10xIR 0.6 ... 1 × In, OFF B 3VL77 12-1@@46-.... 1 1 unit 113 33.500
VL1600/3VL81) 1600 640 ... 1600 9 × In 1.5 ... 8xIR 0.6 ... 1 × In, OFF B 3VL87 16-1@@40-.... 1 1 unit 113 40.800
Order No. For price PU PS*/ PG Weight Order No. For price PU PS*/ PG Weight
Order No. supplement see page (UNIT, P. unit per PU Order No. supplement see page (UNIT, P. unit per PU
required, 2/54 SET, approx. required, 2/54 SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
B 3VL27 06-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 06-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 10-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 10-3@@4@-.... 1 1 unit 113 3.100
B 3VL27 16-2@@4@-.... 1 1 unit 113 3.100 B 3VL27 16-3@@4@-.... 1 1 unit 113 3.100
B 3VL37 20-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 20-3@@4@-.... 1 1 unit 113 3.300
B 3VL37 25-2@@4@-.... 1 1 unit 113 3.300 B 3VL37 25-3@@4@-.... 1 1 unit 113 3.300
> >
3 3
6 6
B 3VL47 31-2@@46-.... 1 1 unit 113 7.600 B 3VL47 31-3@@46-.... 1 1 unit 113 7.600
B 3VL47 40-2@@46-.... 1 1 unit 113 7.600 B 3VL47 40-3@@46-.... 1 1 unit 113 7.600
B 3VL57 63-2@@46-.... 1 1 unit 113 11.700 B 3VL57 63-3@@46-.... 1 1 unit 113 11.700
B 3VL67 80-2@@46-.... 1 1 unit 113 20.500 B 3VL67 80-3@@46-.... 1 1 unit 113 20.500
B 3VL77 10-2@@46-.... 1 1 unit 113 33.500 B 3VL77 10-3@@46-.... 1 1 unit 113 33.500
B 3VL77 12-2@@46-.... 1 1 unit 113 33.500 B 3VL77 12-3@@46-.... 1 1 unit 113 33.500
B 3VL87 16-2@@40-.... 1 1 unit 113 40.800 B 3VL87 16-3@@40-.... 1 1 unit 113 40.800
>
TH
NH
>
TH
NH
NSE0_00708
Connection type can be selected through the 12th position of the Order No. >
• Connection with box terminal 3
• Connection with screw terminal not in conjunction with RCD module at 3VL1 6
VL400/3VL4 400 4000 B 3VL47 40-1EE46-.... 1 1 unit 113 7.400
VL630/3VL5 630 6300 B 3VL57 63-1EE46-.... 1 1 unit 113 11.200
VL800/3VL6 800 6500 B 3VL67 80-1EE46-.... 1 1 unit 113 19.900
VL1250/3VL7 1250 12000 B 3VL77 12-1EE46-.... 1 1 unit 113 31.000
VL1600/3VL82) 1600 14400 B 3VL87 16-1EE40-.... 1 1 unit 113 38.300
1) See also "Switch Disconnectors" chapter. 3K. switch disconnectors are
also available with rear-mounting operating mechanism and leading
contacts.
2)
Front busbar connection pieces are included in the scope of supply
and are to be fitted by the customer.
Order No. Basic price PU PS*/ PG Weight Order No. Basic price PU PS*/ PG Weight
Order No. supplement per PU (UNIT, P. unit per PU Order No. supplement per PU (UNIT, P. unit per PU
required, SET, approx. required, SET, approx.
see page 2/57 M) see page 2/57 M)
kg kg
> >
3 3
6 6
B 3VL47 40-2EE46-.... 1 1 unit 113 7.400 B 3VL47 40-3EE46-.... 1 1 unit 113 7.400
B 3VL57 63-2EE46-.... 1 1 unit 113 11.200 B 3VL57 63-3EE46-.... 1 1 unit 113 11.200
B 3VL67 80-2EE46-.... 1 1 unit 113 19.900 B 3VL67 80-3EE46-.... 1 1 unit 113 19.900
B 3VL77 12-2EE46-.... 1 1 unit 113 31.000 B 3VL77 12-3EE46-.... 1 1 unit 113 31.000
B 3VL87 16-2EE40-.... 1 1 unit 113 38.300 B 3VL87 16-3EE40-.... 1 1 unit 113 38.300
✓ Available
When ordering, add "-Z" to the complete Order No. and add the Order No. with "-Z" Additional
relevant order code(s). 1234 5 6 7 8 9 10 11 12 13 14 15 16 price
3VL . . . . - . . . . . - . . . . -Z
and additional order code(s)
@@@ +...+...
Code for
further versions -Z
For fixed-mounted circuit breakers (wired in factory)
Pre-mounted motorised operating mechanisms
(24 V DC) on circuit breaker,
not synchronizable
Available with
VL160X
(3VL1)
M2 5
N ✓
✓ Additional price
-- Not available
1)
Except for installing in the left accessory compartment of the SENTRON
VL160X circuit breakers with RCD module.
2)
With mounting adapter up to 3 HS.
3)
With mounting adapter up to 2 HS + 2 AS.
4)
Not feasible for use of SENTRON VL160 and VL250 with LCD ETU or
marine engineering ETU and additional use of shunt and undervoltage
releases.
When using a communication-capable ETU, the accessory compartment
X2 is fitted with an auxiliary switch and an alarm switch. The combination of
1st and 2nd Order No. supplement is only possible with restrictions. It is
recommended to use the configurator in the Mall for selection purposes.
5)
Not possible when using a communication-capable ETU.
NSE0_02116a
Max. Max.
VL1250 Max. Max. VL1600 Max. Max. U<
Max.
2 HS + U< 2 HS+
3VL7 4 HS 4 HS 3VL8 4 HS 4 HS 2 AS 4 HS
2 AS
NSE0_02114a
3-pole circuit breakers with communication preparation 4-pole circuit breakers with communication preparation
Note:
Before ordering, use the tables above to check whether the
required combination of shunt releases, undervoltage releases
and auxiliary/alarm switches is feasible.
V AC V DC Mounting side
-- 12 Right pole only A 3VL9 400-1UN00 1 1 unit 113 0.075
-- 24 Right pole only A 3VL9 400-1UP00 1 1 unit 113 0.075
-- 48 Right pole only A 3VL9 400-1UU00 1 1 unit 113 0.075
-- 60 Right pole only A 3VL9 400-1UV00 1 1 unit 113 0.075
3VL9 400-1S.00, 24 -- Right pole only A 3VL9 400-1UD00 1 1 unit 113 0.075
3VL9 400-1U.00 110 ... 127 -- Right pole only A 3VL9 400-1UG00 1 1 unit 113 0.075
-- 110 ... 127 Right pole only A 3VL9 400-1UR00 1 1 unit 113 0.075
208 -- Right pole only A 3VL9 400-1UM00 1 1 unit 113 0.075
220 ... 250 -- Right pole only A 3VL9 400-1UH00 1 1 unit 113 0.075
-- 220 ... 250 Right pole only A 3VL9 400-1US00 1 1 unit 113 0.075
277 -- Right pole only A 3VL9 400-1UQ00 1 1 unit 113 0.075
380 ... 415 -- Right pole only A 3VL9 400-1UJ00 1 1 unit 113 0.075
440 ... 480 -- Right pole only A 3VL9 400-1UK00 1 1 unit 113 0.075
500 ... 525 -- Right pole only A 3VL9 400-1UL00 1 1 unit 113 0.075
Time-delay devices for undervoltage releases
(220 ... 250 V DC)
Rated control supply voltage Us
220 ... 250 V AC
Delay time > 200 ms A 3TX4 701-0AN1 1 1 unit 101 0.170
Storage devices for shunt releases
(208 ... 277 V AC/220 ... 250 V DC)
Rated control supply voltage Us
220 ... 240 V AC/ 220 ... 250 V DC
Storage time 5 min B 3WL9 111-0BA14-0AA0 1 1 unit 103 0.520
1) Except for installing in the left accessory compartment of the SENTRON
VL160X (3VL1) circuit breakers with RCD module and SENTRON
VL160/250 with LCD ETU.
2) Shunt releases with disconnection contact (3SB3 for ON/OFF position)
not floating (see Technical Information at
www.siemens.com/lowvoltage/support).
3) In the case of VL400 (3VL4):
Unsuitable for mounting in the right-hand accessory compartment.
The 3VL9 400-2AB00 assembly kit with auxiliary switches only is recom-
mended.
V AC V DC Mounting side
-- 12 Right pole only A 3VL9 800-1UN00 1 1 unit 113 0.088
-- 24 Right pole only A 3VL9 800-1UP00 1 1 unit 113 0.088
-- 48 Right pole only A 3VL9 800-1UU00 1 1 unit 113 0.088
-- 60 Right pole only A 3VL9 800-1UV00 1 1 unit 113 0.088
24 -- Right pole only A 3VL9 800-1UD00 1 1 unit 113 0.088
3VL9 800-1S.00, 110 ... 127 -- Right pole only A 3VL9 800-1UG00 1 1 unit 113 0.088
3VL9 800-1U.00 -- 110 ... 127 Right pole only A 3VL9 800-1UR00 1 1 unit 113 0.088
208 -- Right pole only A 3VL9 800-1UM00 1 1 unit 113 0.088
220 ... 250 -- Right pole only A 3VL9 800-1UH00 1 1 unit 113 0.088
-- 220 ... 250 Right pole only A 3VL9 800-1US00 1 1 unit 113 0.088
277 -- Right pole only A 3VL9 800-1UQ00 1 1 unit 113 0.088
380 ... 415 -- Right pole only A 3VL9 800-1UJ00 1 1 unit 113 0.088
440 ... 480 -- Right pole only A 3VL9 800-1UK00 1 1 unit 113 0.088
500 ... 525 -- Right pole only A 3VL9 800-1UL00 1 1 unit 113 0.088
Time-delay devices for undervoltage releases
(220 ... 250 V DC)
Rated control supply voltage Us
220 ... 250 V AC
Delay time > 200 ms A 3TX4 701-0AN1 1 1 unit 101 0.170
Storage devices for shunt releases
(208 ... 277 V AC/220 ... 250 V DC)
Rated control supply voltage Us
220 ... 240 V AC/ 220 ... 250 V DC
Storage time 5 min B 3WL9 111-0BA14-0AA0 1 1 unit 103 0.520
1)
Shunt releases with disconnection contact (3SB3 for ON/OFF position)
not floating (see Technical Information at
www.siemens.com/lowvoltage/support).
NSE0_00684
A 3VL9 400-3HA00 1 1 unit 113 0.725 A 3VL9 600-3HA00 1 1 unit 113 0.834
A 3VL9 400-3HC00 1 1 unit 113 0.725 A 3VL9 600-3HC00 1 1 unit 113 0.834
A 3VL9 400-3HE00 1 1 unit 113 0.267 A 3VL9 600-3HE00 1 1 unit 113 0.755
A 3VL9 400-3HF05 1 1 unit 113 0.970 A 3VL9 600-3HF05 1 1 unit 113 2.465
A 3VL9 400-3HG05 1 1 unit 113 1.100 A 3VL9 600-3HG05 1 1 unit 113 2.460
A 3VL9 400-3AS10 1 1 unit 113 0.080 A 3VL9 600-3AS10 1 1 unit 113 0.080
A 3VL9 400-3AT10 1 1 unit 113 0.130 A 3VL9 600-3AT10 1 1 unit 113 0.130
A 3VL9 400-3AU10 1 1 unit 113 0.080 A 3VL9 600-3AU10 1 1 unit 113 0.080
A 3VL9 400-3AW10 1 1 unit 113 0.130 A 3VL9 600-3AW10 1 1 unit 113 0.130
A 3VL9 400-3HR10 1 1 unit 113 2.000 A 3VL9 500-3HR10 1 1 unit 113 2.400
A 3VL9 400-3HR20 1 1 unit 113 2.000 A 3VL9 500-3HR20 1 1 unit 113 2.400
A 3VL9 400-3HR30 1 1 unit 113 2.000 A 3VL9 500-3HR30 1 1 unit 113 2.400
A 3VL9 400-3HR11 1 1 unit 113 2.000 A 3VL9 500-3HR11 1 1 unit 113 2.400
A 3VL9 400-3HR21 1 1 unit 113 2.000 A 3VL9 500-3HR21 1 1 unit 113 2.400
A 3VL9 400-3HR31 1 1 unit 113 2.000 A 3VL9 500-3HR31 1 1 unit 113 2.400
A 3VL9 400-3HP00 1 1 unit 113 0.379 A 3VL9 600-3HP00 1 1 unit 113 0.437
-- --
operating mechanism
Standard or EMERGENCY-STOP version
"OFF after ON"
Leading auxiliary switches when switching on
3VL9 .00-3A.10
1 changeover contact with 1.5 m long cables A 3VL9 600-3AS10 1 1 unit 113 0.080
2 changeover contacts with 1.5 m long cables A 3VL9 600-3AT10 1 1 unit 113 0.130
"ON after OFF"
Leading auxiliary switches when switching off
1 changeover contact with 1.5 m long cables A 3VL9 600-3AU10 1 1 unit 113 0.080
2 changeover contacts with 1.5 m long cables A 3VL9 600-3AW10 1 1 unit 113 0.130
Retaining brackets
suitable for matching door-coupling rotary
operating mechanisms, complete
Retaining bracket is mounted on the operating A 3VL9 600-3HP00 1 1 unit 113 0.437
mechanism, recommended for extension shafts
>250 mm, with locking device for max. 3 pad-
locks
1)
Additional accessories and components for door-coupling ro- IP40 with additional masking frame mounted on the door cutout.
tary operating mechanism, see 2/67 and 2/69.
50/60 Hz V AC V DC
-- 24 A 3VL9 300-3MJ00 1 1 unit 113 2.140
42 ... 48 42 ... 48 A 3VL9 300-3ML00 1 1 unit 113 2.140
60 60 A 3VL9 300-3MS00 1 1 unit 113 2.140
110 ... 127 110 ... 127 A 3VL9 300-3MN00 1 1 unit 113 2.140
3VL9 .00-3M.00 220 ... 250 220 ... 250 A 3VL9 300-3MQ00 1 1 unit 113 2.140
• Toggle handle extensions --
For VL400 (3VL4)
50/60 Hz V AC V DC
-- 24 A 3VL9 400-3MJ00 1 1 unit 113 3.910
42 ... 48 42 ... 48 A 3VL9 400-3ML00 1 1 unit 113 3.910
60 60 A 3VL9 400-3MS00 1 1 unit 113 3.910
110 ... 127 110 ... 127 A 3VL9 400-3MN00 1 1 unit 113 3.910
220 ... 250 220 ... 250 A 3VL9 400-3MQ00 1 1 unit 113 3.910
• Toggle handle extensions A 3VL9 400-3HN00 1 1 unit 113 0.100
For VL630 to VL800
(3VL5 to 3VL6)
50/60 Hz V AC V DC
-- 24 A 3VL9 600-3MJ00 1 1 unit 113 4.800
42 ... 48 42 ... 48 A 3VL9 600-3ML00 1 1 unit 113 4.800
60 60 A 3VL9 600-3MS00 1 1 unit 113 4.800
110 ... 127 110 ... 127 A 3VL9 600-3MN00 1 1 unit 113 4.800
220 ... 250 220 ... 250 A 3VL9 600-3MQ00 1 1 unit 113 4.800
• Toggle handle extensions C 3VL9 600-3HN00 1 1 unit 113 0.140
Motorized operating mechanisms2)
Degree of protection IP30, with locking
device for 3 padlocks
N For VL160X (3VL1)
50/60 Hz V AC V DC
16(B
50/60 Hz V AC V DC
-- 24 B 3VL9 800-3MA10 1 1 unit 113 1.000
42 ... 60 42 ... 60 B 3VL9 800-3MC10 1 1 unit 113 1.000
110 ... 127 110 ... 127 B 3VL9 800-3MD10 1 1 unit 113 1.000
220 ... 250 220 ... 250 B 3VL9 800-3ME10 1 1 unit 113 1.000
1)
Not possible on VL160X with RCD module.
2)
For safety lock as an assembly kit for retrofitting see pages 2/84 to 2/88.
8UC72 10-6BD
3VL7, 8UC73 3 12 × 12 Standard C 8UC73 10-6BD 1 1 unit 103 0.200
3VL8 EMER- C 8UC73 20-8BD 1 1 unit 103 0.200
GENCY-
STOP
8UC73 10-1BB
Rotary operating mechanisms Cross-section DT Individual parts for 8UC6 PU PS*/ PG Weight
of the actuat- door-coupling rotary operating (UNIT, P. unit per PU
ing shaft mechanisms SET, approx.
M)
Order No. Price
Type mm × mm per PU kg
Individual parts for 8UC door-coupling rotary operating mechanisms
Coupling drivers for 3VL
8UC71 (plastic) 6×6 C 8UC70 11-2AA 1 1 unit 103 0.200
8UC71/8UC722) (die cast) 8×8 A 8UC60 17-2AA 1 1 unit 103 0.047
8UC73/74 (die cast) 12 × 12 B 8UC60 14 1 1 unit 103 0.253
nse0_00372 Rivet
8UC60 14
Extension shafts 300 mm long
8UC71 6×6 B 8UC60 31 1 1 unit 103 0.068
8UC71/8UC72 8×8 B 8UC60 32 1 1 unit 103 0.132
NSE0_00373
8UC73 10 × 10 C 8UC60 33 1 1 unit 103 0.217
Groove 8UC73/74 12 × 12 B 8UC60 34 1 1 unit 103 0.315
8UC60 31
Extension shafts 600 mm long
8UC71 6×6 B 8UC60 81 1 1 unit 103 0.136
8UC71/8UC72 8×8 B 8UC60 82 1 1 unit 103 0.265
NSE0_00373
8UC73 10 × 10 B 8UC60 83 1 1 unit 103 0.430
Groove 8UC73/74 12 × 12 B 8UC60 84 1 1 unit 103 0.640
8UC60 81
Shaft couplings
8UC71 6×6 B 8UC60 21 1 1 unit 103 0.031
8UC72 8×8 B 8UC60 22 1 1 unit 103 0.023
8UC73 10 × 10 B 8UC60 23 1 1 unit 103 0.085
nse0_00374 8UC73/74 12 × 12 B 8UC60 24 1 1 unit 103 0.077
Lug Rivet
8UC60 21 to 8UC60 24
Reducers
8UC71 8 × 8 to 6 × 6 C 8UC70 58 1 1 unit 103 0.200
8UC72 12 × 12 to C 8UC70 50 1 1 unit 103 0.200
8×8
44
02
_0
g0
ns
8UC70 58
1) Non-interchangeability features.
2) Shortened coupling driver with reduced tolerance compensation.
3) Standard: Ti-grey handle, light-gray masking plate;
EMERGENCY-STOP: Red handle, yellow masking plate.
Type A mm Nm Size
8UC Door-Coupling Rotary Operating Mechanisms
8UC71 - 3VL circuit breakers
3VL1 16 ... 160 6×6 4 1 75
3VL2 50 ... 160 6×6 4
Tripped
6×6
NSE00362
3VL3 200... 250 4
Reset
36
8×8
NSE00362
3VL3 200... 250 4
Reset
(Supplied with door coupling rotary operating mechanism,
complete 3VL9 300-3H.05)
36
NSE00363
Reset
62
Reset
140
1) Requires in addition a front-operated rotary operating mechanism with
shaft stub for direct mounting to the circuit breaker. For ordering the
complete operating mechanism see pages 2/62 to 2/65.
@ 6 mm @ 6 mm @ 8 mm by 6 mm
Standard C 8UC71 11-6BD15 1 1 unit 103 0.200 8UC71 10-6BD 8UC70 11-2AA 8UC60 31 8UC70 58
EMERGENCY- C 8UC71 21-8BD15 1 1 unit 103 0.200 8UC71 20-8BD 8UC70 11-2AA 8UC60 31 8UC70 58
STOP
(coupling driver
made of plastic)
@ 8 mm @ 8 mm @ 8 mm by 8 mm
Standard C 8UC71 62-6BD22 1 1 unit 103 0.200 8UC71 10-6BD 8UC60 17-2AA 8UC60 32 8UC60 22
EMERGENCY- C 8UC71 72-8BD22 1 1 unit 103 0.200 8UC71 20-8BD 8UC60 17-2AA 8UC60 32 8UC60 22
STOP
(Die-cast
coupling driver
with reduced
tolerance
compensation)
@ 8 mm @ 8 mm @ 12 mm by 8 mm
Standard C 8UC72 62-6BD26 1 1 unit 103 0.200 8UC72 10-6BD 8UC60 17-2AA 8UC60 32 8UC70 50
EMERGENCY- C 8UC72 62-8BD26 1 1 unit 103 0.200 8UC72 20-8BD 8UC60 17-2AA 8UC60 32 8UC70 50
STOP
(Die-cast
coupling driver
with reduced
tolerance
compensation)
@ 12 mm @ 12 mm @ 12 mm by 12 mm
Standard C 8UC73 14-6BD44 1 1 unit 103 0.200 8UC73 10-6BD 8UC60 14 8UC60 34 8UC60 24
EMERGENCY- C 8UC73 24-8BD44 1 1 unit 103 0.200 8UC73 20-8BD 8UC60 14 8UC60 34 8UC60 24
STOP
(Die-cast
coupling driver)
3VL9 .00-4PE30
Withdrawable version assembly kits
Upgrade of the plug-in base assembly kit to
Withdrawable version 3-pole --
including side panels 3-pole with RCD --
and racking mecha- 4-pole --
nism. 4-pole with RCD --
Withdrawable version
NSE0_00719
Blade contacts
As replacement for converting fixed-mounted
circuit breakers into plug-in/withdrawable circuit
3VL9 .00-4WA30 breakers, including trip pin
1 set = 6 units 3-pole A 3VL9 100-4PS30 1 1 unit 113 0.226
1 set = 8 units 4-pole A 3VL9 100-4PS40 1 1 unit 113 0.295
Trip pins and springs
As replacement for plug-in/withdrawable A 3VL9 100-4PF00 1 1 unit 113 0.012
circuit breaker
Auxiliary circuit plug connections for plug-in
bases
Accessory connections for plug-in circuit break-
ers (factory-wired connectors) and for plug-in
bases or withdrawable version (coupling with
1)
screw terminal)
8 terminals A 3VL9 300-4PJ00 1 1 unit 113 0.134
Position signaling switches
(connected/disconnected position)
For plug-in/withdrawable base, 1 CO,
max. 2 signaling switches possible A 3VL9 000-4WL00 1 1 unit 113 0.019
1)
It is recommended to use a maximum of 2 auxiliary circuit plug-in systems
per circuit breaker (16 terminals).
A 3VL9 200-4PA30 1 1 unit 113 2.170 A 3VL9 300-4PA30 1 1 unit 113 2.280
A 3VL9 200-4PB30 1 1 unit 113 2.460 A 3VL9 300-4PB30 1 1 unit 113 2.570
A 3VL9 200-4PA40 1 1 unit 113 2.850 A 3VL9 300-4PA40 1 1 unit 113 3.000
A 3VL9 200-4PB40 1 1 unit 113 3.200 A 3VL9 300-4PB40 1 1 unit 113 3.330
A 3VL9 300-4PE30 1 1 unit 113 0.375 A 3VL9 300-4PE30 1 1 unit 113 0.375
A 3VL9 300-4PE40 1 1 unit 113 0.500 A 3VL9 300-4PE40 1 1 unit 113 0.500
A 3VL9 200-4PC30 1 1 unit 113 1.980 A 3VL9 300-4PC30 1 1 unit 113 2.090
A 3VL9 200-4PD30 1 1 unit 113 2.260 A 3VL9 300-4PD30 1 1 unit 113 2.370
A 3VL9 200-4PC40 1 1 unit 113 2.620 A 3VL9 300-4PC40 1 1 unit 113 2.770
A 3VL9 200-4PD40 1 1 unit 113 2.960 A 3VL9 300-4PD40 1 1 unit 113 3.070
A 3VL9 300-4WF30 1 1 unit 113 1.260 A 3VL9 300-4WF30 1 1 unit 113 1.260
A 3VL9 300-4WG30 1 1 unit 113 2.031 A 3VL9 300-4WG30 1 1 unit 113 2.031
A 3VL9 300-4WF40 1 1 unit 113 1.280 A 3VL9 300-4WF40 1 1 unit 113 1.280
A 3VL9 300-4WG40 1 1 unit 113 2.050 A 3VL9 300-4WG40 1 1 unit 113 2.050
A 3VL9 200-4WA30 1 1 unit 113 3.430 A 3VL9 300-4WA30 1 1 unit 113 3.540
A 3VL9 200-4WB30 1 1 unit 113 4.000 A 3VL9 300-4WB30 1 1 unit 113 4.601
A 3VL9 200-4WA40 1 1 unit 113 4.130 A 3VL9 300-4WA40 1 1 unit 113 4.280
A 3VL9 200-4WB40 1 1 unit 113 4.940 A 3VL9 300-4WB40 1 1 unit 113 5.361
A 3VL9 200-4WC30 1 1 unit 113 3.240 A 3VL9 300-4WC30 1 1 unit 113 3.350
A 3VL9 200-4WD30 1 1 unit 113 3.810 A 3VL9 300-4WD30 1 1 unit 113 4.398
A 3VL9 200-4WC40 1 1 unit 113 3.940 A 3VL9 300-4WC40 1 1 unit 113 4.050
A 3VL9 200-4WD40 1 1 unit 113 4.710 A 3VL9 300-4WD40 1 1 unit 113 5.158
A 3VL9 200-4PS30 1 1 unit 113 0.248 A 3VL9 300-4PS30 1 1 unit 113 0.342
A 3VL9 200-4PS40 1 1 unit 113 0.330 A 3VL9 300-4PS40 1 1 unit 113 0.426
A 3VL9 300-4PF00 1 1 unit 113 0.013 A 3VL9 300-4PF00 1 1 unit 113 0.013
1) 1)
A 3VL9 300-4PJ00 1 1 unit 113 0.134 A 3VL9 300-4PJ00 1 1 unit 113 0.134
A 3VL9 000-4WL00 1 1 unit 113 0.019 A 3VL9 000-4WL00 1 1 unit 113 0.019
kg
Plug-in versions/withdrawable versions
3- or 4-pole
Plug-in base assembly kits
Base, blade contacts for circuit breakers, termi-
nal covers for degree of protection IP20, fixing
screws, trip pin
Rear terminals
NSE0_00717
3VL9 .00-4PE30
Withdrawable version assembly kits
Upgrade of the plug-in base assembly kit to
Withdrawable version 3-pole A 3VL9 400-4WF30 1 1 unit 113 3.400
including side panels 3-pole with RCD --1)
and racking mecha- 4-pole A 3VL9 400-4WF40 1 1 unit 113 3.600
nism. 4-pole with RCD A 3VL9 400-4WG40 1 1 unit 113 3.800
Withdrawable version
NSE0_00719
Blade contacts
As replacement for converting fixed-mounted
circuit breakers into plug-in/withdrawable circuit
3VL9 .00-4WA30 breakers, including trip pin
1 set = 6 units 3-pole A 3VL9 400-4PS30 1 1 unit 113 0.720
1 set = 8 units 4-pole A 3VL9 400-4PS40 1 1 unit 113 0.960
Trip pins and springs
As replacement for plug-in/withdrawable A 3VL9 400-4PF00 1 1 unit 113 0.015
circuit breaker
Auxiliary circuit plug connections for plug-in
bases
Accessory connections for plug-in circuit break-
ers (factory-wired connectors) and for plug-in
bases or withdrawable version (coupling with
2)
screw terminal)
8 terminals A 3VL9 400-4PJ00 1 1 unit 113 0.144
Position signaling switches A 3VL9 000-4WL00 1 1 unit 113 0.019
(connected/disconnected position)
For plug-in/withdrawable base, 1 CO,
max. 2 signaling switches possible
1)
For 3-pole applications please use 4-pole withdrawable version
with 4-pole RCD module and 4-pole circuit breaker.
2)
It is recommended to use a maximum of 3 auxiliary circuit plug-in systems
per circuit breaker (24 terminals).
3) With VL800 (3VL6) to VL1600 (3VL8) as vertical connection.
-- --
-- --
A 3VL9 500-4WA30 1 1 unit 113 11.000 A 3VL9 600-4WA30 1 1 unit 113 40.104
-- --
A 3VL9 500-4WA40 1 1 unit 113 15.000 A 3VL9 600-4WA40 1 1 unit 113 48.060
-- --
A 3VL9 500-4WC30 1 1 unit 113 10.300 A 3VL9 600-4WC30 1 1 unit 113 40.716
-- --
A 3VL9 500-4WC40 1 1 unit 113 13.400 A 3VL9 600-4WC40 1 1 unit 113 48.876
-- --
A 3VL9 500-4PS30 1 1 unit 113 1.260 A 3VL9 600-4PS30 1 1 unit 113 1.500
A 3VL9 500-4PS40 1 1 unit 113 1.680 A 3VL9 600-4PS40 1 1 unit 113 2.000
A 3VL9 500-4PF00 1 1 unit 113 0.018 A 3VL9 600-4PF00 1 1 unit 113 0.025
2) 2)
A 3VL9 600-4PJ00 1 1 unit 113 0.144 A 3VL9 600-4PJ00 1 1 unit 113 0.144
A 3VL9 000-4WL00 1 1 unit 113 0.019 A 3VL9 000-4WL00 1 1 unit 113 0.019
3-pole --
3-pole with RCD module --
4-pole --
3VL9 .00-4PA30 4-pole with RCD module --
90° angle connecting adapters
For rear connection, 3-pole --
For rear connection, 4-pole --
Front-accessible terminals
3-pole --
3-pole with RCD module --
4-pole --
4-pole with RCD module --
NSE00581
3VL9 .00-4PE30
Withdrawable version assembly kits
Upgrade of the plug-in base assembly kit to
Withdrawable version 3-pole --
including side panels 3-pole with RCD --
and racking mecha- 4-pole --
nism. 4-pole with RCD --
Withdrawable version
NSE0_00719
Blade contacts
As replacement for converting fixed-mounted
circuit breakers into plug-in/withdrawable circuit
3VL9 .00-4WA30 breakers, including trip pin
1 set = 6 units 3-pole A 3VL9 800-4PS30 1 1 unit 113 2.000
1 set = 8 units 4-pole A 3VL9 800-4PS40 1 1 unit 113 2.660
Trip pins and springs
As replacement for plug-in/withdrawable A 3VL9 800-4PF00 1 1 unit 113 0.030
circuit breaker
Auxiliary circuit plug connections for plug-in
bases
Accessory connections for plug-in circuit break-
ers (factory-wired connectors) and for plug-in
bases or withdrawable version (coupling with
2)
screw terminal)
8 terminals A 3VL9 800-4PJ00 1 1 unit 113 0.144
Position signaling switches A 3VL9 000-4WL00 1 1 unit 113 0.019
(connected/disconnected position)
For plug-in/withdrawable base, 1 CO,
max. 2 signaling switches possible
1) With VL800 (3VL6) to VL1600 (3VL8) as vertical connection.
2) It is recommended to use a maximum of 3 auxiliary circuit plug-in systems
per circuit breaker (24 terminals).
--
--
--
--
--
--
--
--
--
--
--
--
--
--
2)
Circuit breakers Rated Residual Delay time td Rated DT Order No. Price PU PS*/ PG Weight
for system pro- current currents I adjustable operational per PU (UNIT, P. unit per PU
tection, only for In adjust- voltage Ue SET, M) approx.
TM, starters, able
disconnectors
A A s V AC kg
RCD modules
3-pole
VL160X (3VL1) 0.03 Instantaneous
Bottom 160 0.10 0.06 127 ... 480 A 3VL9 112-5GA30 1 1 unit 113 1.340
mounting1)3) 0.30 0.10
NSE0_00582
Mounting kit for 0.50 0.25 A 3VL9 112-5GB30 1 1 unit 113 1.525
left side,
without 1.00 0.50
SENTRON VL160X RCD1)2)3) 3.00 1.00
with RCD module VL160 (3VL2) 160 127 ... 480 A 3VL9 216-5GC30 1 1 unit 113 1.320
mounted laterally on
the circuit breaker 230 ... 690 A 3VL9 216-5GD30 1 1 unit 113 1.320
(on left side) VL250 (3VL3) 250 127 ... 480 A 3VL9 325-5GE30 1 1 unit 113 1.400
230 ... 690 A 3VL9 325-5GF30 1 1 unit 113 1.400
VL400 (3VL4) 400 127 ... 480 --
230 ... 690 --
4-pole
VL160X (3VL1) 0.03 Instantaneous
Bottom 160 0.10 0.06 127 ... 480 A 3VL9 112-5GA40 1 1 unit 113 1.590
mounting1)3) 0.30 0.10
Mounting kit for 0.50 0.25 A 3VL9 112-5GB40 1 1 unit 113 1.824
left side,
without 1.00 0.50
RCD1)2)3) 3.00 1.00
NSE0_00583
VL160 (3VL2) 160 127 ... 480 A 3VL9 216-5GC40 1 1 unit 113 1.570
230 ... 690 A 3VL9 216-5GD40 1 1 unit 113 1.570
VL250 (3VL3) 250 127 ... 480 A 3VL9 325-5GE40 1 1 unit 113 1.650
SENTRON VL160X 230 ... 690 A 3VL9 325-5GF40 1 1 unit 113 1.650
up to VL400 with
VL400 (3VL4) 400 127 ... 480 A 3VL9 440-5GG40 1 1 unit 113 2.980
RCD module
mounted below the 230 ... 690 A 3VL9 440-5GH40 1 1 unit 113 2.980
circuit breaker
Circuit breakers Rated Residual Delay time td Rated 3-pole 4-pole
for system pro- current currents I adjustable operational circuit breakers circuit breakers
tection, only for In adjust- voltage Ue
TM, starters, able
disconnectors
Order No. with "-Z" Addi- Order No. with "-Z" Addi-
3VL. . . . - . D . . . - . . . . -Z tional 3VL. . . . - . E . . . - . . . . -Z tional
price price
and additional and additional
order code order code
@@@ Code for further @@@ Code for further
A A s V AC versions -Z versions -Z
Circuit breakers with RCD module
3 and 4-pole
VL160X (3VL1) 0.03 Instantaneous
(Bottom 160 0.10 0.06 127 ... 480 A 0 1 1)3) ✓ A 0 1 1)3) ✓
mounting) 0.30 0.10
0.50 0.25
VL160 (3VL2) 160 1.00 0.50 127 ... 480 A 0 1 ✓ A 0 1 ✓
3.00 1.00 230 ... 690 A 0 2 ✓ A 0 2 ✓
3VL9 .00-4TD.0
Circular conductor terminal with terminal
covers for cable (Al or Cu) N
1 set = 3 units B 3VL9 115-4TD30 1 1 unit 113 0.150
1 set = 4 units B 3VL9 115-4TD40 1 1 unit 113 0.150
Auxiliary conductor terminals A 3VL9 200-3TN00 1 1 unit 113 0.130
For box terminals/circular conductor terminals
1 set = 10 units
Terminals with screw connection -
metric thread
With insulator (for rear) for use with busbars and cable
lugs, see Technical Information at
NSE0_00701
www.siemens.com/lowvoltage/support.
3VL9 .00-4TA.0
1 set = 3 units A 3VL9 116-4TA30 1 1 unit 113 0.055
1 set = 4 units A 3VL9 116-4TA40 1 1 unit 113 0.070
Connection covers
(terminal covers) for circuit breakers
Degree of protection IP30 for main connections
1 set = 2 units
Extended 3-pole A 3VL9 300-8CA30 1 1 unit 113 0.204
NSE0_00730
Standard 3-pole A 3VL9 300-8CB30 1 1 unit 113 0.053
3VL9 .00-3CB.0 Extended 4-pole A 3VL9 300-8CA40 1 1 unit 113 0.264
Standard 4-pole A 3VL9 300-8CB40 1 1 unit 113 0.071
Phase barriers for circuit breakers, fixed-mounted,
plug-in or withdrawable versions
NSE0_00731 1 set = 2 units A 3VL9 300-8CE00 1 1 unit 113 0.023
3VL9 .00-8CE00
1)
Screw terminal connections are required for SENTRON VL160X and VL160 (3VL1 and 3VL2) circuit breakers,
see Technical Information at www.siemens.com/lowvoltage/support.
3VL9 .00-4TD.0
Circular conductor terminal with terminal
covers for cable (Al or Cu) N
1 set = 3 units A 3VL9 215-4TD30 1 1 unit 113 0.150
1 set = 4 units B 3VL9 215-4TD40 1 1 unit 113 0.150
Multiple feed-in terminals
N S E 0 _ 0 1 5 4 2 N S E 0 _ 0 1 5 4 3
3 units --
3VL9 .00-4TF.0 4 units --
Multiple feed-in terminal
with terminal covers N
3 units (2 × 70 ... 300) --
4 units (2 × 70 ... 300) --
Auxiliary conductor terminals A 3VL9 200-3TN00 1 1 unit 113 0.130
For box terminals/circular conductor termi-
nals/multiple feed-in terminals
1 set = 10 units
Terminals with screw connection -
metric thread
NSE0_00701
With insulator (for rear) for use with busbars and
cable lugs, see Technical Information at
3VL9 .00-4TA.0
www.siemens.com/lowvoltage/support.
1 set = 3 units A 3VL9 216-4TA30 1 1 unit 113 0.055
1 set = 4 units A 3VL9 216-4TA40 1 1 unit 113 0.070
Connection covers
(terminal covers) for circuit breakers
Degree of protection IP30 for main connections
NSE0_00730
1 set = 2 units
3VL9 .00-3CB.0
Extended 3-pole A 3VL9 300-8CA30 1 1 unit 113 0.204
Standard 3-pole A 3VL9 300-8CB30 1 1 unit 113 0.053
Extended 4-pole A 3VL9 300-8CA40 1 1 unit 113 0.264
Standard 4-pole A 3VL9 300-8CB40 1 1 unit 113 0.071
Phase barriers for circuit breakers, fixed-mounted,
NSE0_00731 plug-in or withdrawable versions
3VL9 .00-8CE00 1 set = 2 units A 3VL9 300-8CE00 1 1 unit 113 0.023
1)
Screw terminal connections are required for SENTRON VL160X and VL160 (3VL1 and 3VL2) circuit breakers,
see Technical Information at www.siemens.com/lowvoltage/support.
A 3VL9 300-4EC30 1 1 unit 113 0.256 A 3VL9 400-4EC30 1 1 unit 113 0.889
A 3VL9 300-4EC40 1 1 unit 113 0.345 A 3VL9 400-4EC40 1 1 unit 113 1.193
A 3VL9 300-4ED30 1 1 unit 113 0.256 A 3VL9 400-4ED30 1 1 unit 113 0.916
A 3VL9 300-4ED40 1 1 unit 113 0.345 A 3VL9 400-4ED40 1 1 unit 113 1.229
A 3VL9 300-4RA00 1 1 unit 113 0.126 A 3VL9 400-4RA00 1 1 unit 113 0.219
A 3VL9 300-4RB00 1 1 unit 113 0.229 A 3VL9 400-4RB00 1 1 unit 113 0.377
A 3VL9 300-4RC30 1 1 unit 113 0.481 A 3VL9 400-4RC30 1 1 unit 113 0.816
A 3VL9 300-4RF40 1 1 unit 113 0.711 A 3VL9 400-4RF40 1 1 unit 113 1.192
A 3VL9 300-4RK00 1 1 unit 113 0.104 A 3VL9 400-4RK00 1 1 unit 113 0.343
A 3VL9 300-4RL00 1 1 unit 113 0.200 A 3VL9 400-4RL00 1 1 unit 113 0.502
A 3VL9 300-4RM30 1 1 unit 113 0.408 A 3VL9 400-4RM30 1 1 unit 113 1.190
A 3VL9 300-4RN40 1 1 unit 113 0.608 A 3VL9 400-4RN40 1 1 unit 113 1.690
A 3VL9 300-4TC30 1 1 unit 113 0.192 A 3VL9 400-4TC30 1 1 unit 113 0.423
A 3VL9 300-4TC40 1 1 unit 113 0.256 A 3VL9 400-4TC40 1 1 unit 113 0.573
C 3VL9 300-4TD30 1 1 unit 113 0.159 C 3VL9 400-4TD30 1 1 unit 113 0.260
C 3VL9 300-4TD40 1 1 unit 113 0.212 C 3VL9 400-4TD40 1 1 unit 113 0.340
A 3VL9 300-4TA30 1 1 unit 113 0.090 A 3VL9 400-4TA30 1 1 unit 113 0.112
A 3VL9 300-4TA40 1 1 unit 113 0.120 A 3VL9 400-4TA40 1 1 unit 113 0.149
A 3VL9 300-8CA30 1 1 unit 113 0.204 A 3VL9 400-8CA30 1 1 unit 113 0.450
A 3VL9 300-8CB30 1 1 unit 113 0.053 A 3VL9 400-8CB30 1 1 unit 113 0.120
A 3VL9 300-8CA40 1 1 unit 113 0.264 A 3VL9 400-8CA40 1 1 unit 113 0.594
A 3VL9 300-8CB40 1 1 unit 113 0.071 A 3VL9 400-8CB40 1 1 unit 113 0.164
A 3VL9 300-8CE00 1 1 unit 113 0.023 A 3VL9 600-8CE00 1 1 unit 113 0.042
3VL9 .00-4RK00, Flat connecting bar (1 unit) A 3VL9 500-4RG00 1 1 unit 113 0.358
3VL9 .00-4RL00 Flat connecting bar
Set = 3 units, 3-pole A 3VL9 500-4RH30 1 1 unit 113 1.075
NSE0_00725
NSE0_00731
3VL9 .00-8CE00
1)
Front connecting bars included in scope of supply; not for 690 V AC/600 V DC.
A 3VL9 600-4EC30 1 1 unit 113 1.602 C 3VL9 800-4EC30 1 1 unit 113 3.313
A 3VL9 600-4EC40 1 1 unit 113 2.136 C 3VL9 800-4EC40 1 1 unit 113 4.438
-- --
-- --
-- --
-- --
-- --
-- --
-- --
-- --
A 3VL9 600-4RG00 1 1 unit 113 1.604 A 3VL9 700-4RG00 1 1 unit 113 1.604
A 3VL9 600-4RH30 1 1 unit 113 4.812 A 3VL9 700-4RH30 1 1 unit 113 4.812
A 3VL9 600-4RH40 1 1 unit 113 6.416 A 3VL9 700-4RH40 1 1 unit 113 6.416
C 3VL9 600-4TG30 1 1 unit 113 0.918 C 3VL9 700-4TG30 1 1 unit 113 2.175
C 3VL9 600-4TG40 1 1 unit 113 1.224 C 3VL9 700-4TG40 1 1 unit 113 2.900
A 3VL9 400-3TN00 1 1 unit 113 0.140 A 3VL9 400-3TN00 1 1 unit 113 0.140
-- --
-- --
C 3VL9 600-4TA30 1 1 unit 113 0.289 C 3VL9 800-4TA30 1 1 unit 113 0.319
C 3VL9 600-4TA40 1 1 unit 113 0.386 C 3VL9 800-4TA40 1 1 unit 113 0.426
A 3VL9 600-8CA30 1 1 unit 113 0.696 A 3VL9 800-8CA30 1 1 unit 113 1.060
A 3VL9 600-8CB30 1 1 unit 113 0.210 A 3VL9 800-8CB30 1 1 unit 113 0.360
A 3VL9 600-8CA40 1 1 unit 113 0.960 A 3VL9 800-8CA40 1 1 unit 113 1.326
A 3VL9 600-8CB40 1 1 unit 113 0.270 A 3VL9 800-8CB40 1 1 unit 113 0.470
A 3VL9 600-8CE00 1 1 unit 113 0.042 C 3VL9 800-8CE00 1 1 unit 113 0.130
NSE0_00733
Interlocking modules for Bowden wire Combination with next size up possible
interlocking 1) (see Order No.)
3VL9 .00-8L.00 For the mechanical interlocking of two circuit
breakers.
C 3VL9 300-8LA00 1 1 unit 113 0.174
Interlocking module for one circuit breaker
3VL9 .00-8LA00
Safety lock assembly kits
Key can be removed with the circuit breaker in the
"OFF" position
For front-operated rotary operating mechanisms
Lock types
Ronis A 3VL9 715-8HA00 1 1 unit 113 0.309
NSE0_00680 For motorized operating mechanism with stored
energy mechanism
Lock types
Ronis --
Filli Giussani A 3VL9 321-8HA00 1 1 unit 113 0.053
Sets of fixing screws
3VL9 ...-8HA00 (metric thread)
Including the screws, washers and nuts required to
secure a 3- or 4-pole circuit breaker to a prepared
surface
Set with 4 screws A 3VL9 300-8SA40 1 1 unit 113 0.030
Transparent covers for releases, sealable
To prevent access by unqualified personnel and
unauthorized changes to settings (seal not included)
Electronic releases --
Thermal-magnetic A 3VL9 300-8BM00 1 1 unit 113 0.015
Battery power supply for activating/ --
parameterizing the LCD ETU release, with test
function for all IEC and UL ETUs
(two 9 V blocks are required in addition)
NSE0_01531a
3VL9 000-8AP01
1) Two interlocking modules and one Bowden wire are required. Cannot be
used in conjunction with motorized operating mechanism and withdraw-
able version.
Interlocking modules for Bowden wire Combinations with next size up/down possible
NSE0_00733
interlocking 1) (see Order No.)
For the mechanical interlocking of two circuit
3VL9 .00-8L.00 breakers.
Interlocking module for one circuit breaker C 3VL9 300-8LA00 1 1 unit 113 0.174
3VL9 000-8AP01
1) Two interlocking modules and one Bowden wire are required. Cannot be
used in conjunction with motorized operating mechanism and withdraw-
able version.
C 3VL9 300-3HL00 1 1 unit 113 0.052 C 3VL9 400-3HL00 1 1 unit 113 0.122
C 3VL9 300-8LC00 1 1 unit 113 0.215 C 3VL9 400-8LC00 1 1 unit 113 0.386
C 3VL9 300-8LD00 1 1 unit 113 0.223 C 3VL9 400-8LD00 1 1 unit 113 0.436
C 3VL9 300-8LA00 1 1 unit 113 0.174 C 3VL9 400-8LA00 1 1 unit 113 0.196
A 3VL9 715-8HA00 1 1 unit 113 0.309 A 3VL9 715-8HA00 1 1 unit 113 0.309
A 3VL9 300-8SA40 1 1 unit 113 0.030 C 3VL9 500-8SA40 1 1 unit 113 0.090
C 3VL9 700-8BL00 1 1 unit 113 0.002 C 3VL9 700-8BL00 1 1 unit 113 0.002
A 3VL9 300-8BM00 1 1 unit 113 0.015 A 3VL9 400-8BM00 1 1 unit 113 0.017
B 3VL9 000-8AP01 1 1 unit 113 0.605 B 3VL9 000-8AP01 1 1 unit 113 0.605
Interlocking modules for Bowden wire Combinations with next size up/down possible
interlocking 1) (see Order No.)
NSE0_00733
For the mechanical interlocking of two circuit
breakers.
3VL9 .00-8L.00
Interlocking module for one circuit breaker C 3VL9 600-8LA00 1 1 unit 113 0.244
3VL9 000-8AP01
1)
Two interlocking modules and one Bowden wire are required.
Cannot be used in conjunction with motorized operating mechanism and
withdrawable version.
C 3VL9 600-3HL00 1 1 unit 113 0.130 C 3VL9 800-3HL00 1 1 unit 113 0.238
C 3VL9 600-8LC00 1 1 unit 113 1.499 C 3VL9 800-8LC00 1 1 unit 113 2.935
C 3VL9 600-8LD00 1 1 unit 113 5.076 C 3VL9 800-8LD00 1 1 unit 113 3.825
C 3VL9 600-8LA00 1 1 unit 113 0.244 C 3VL9 800-8LA00 1 1 unit 113 0.283
-- --
C 3VL9 000-8LH20 1 1 unit 113 0.298 --
C 3VL9 000-8LH30 1 1 unit 113 0.412 C 3VL9 000-8LH30 1 1 unit 113 0.412
A 3VL9 715-8HA00 1 1 unit 113 0.309 A 3VL9 715-8HA00 1 1 unit 113 0.309
A 3VL9 715-8HA00 1 1 unit 113 0.309 A 3VL9 715-8HA00 1 1 unit 113 0.309
-- --
A 3VL9 600-8SA40 1 1 unit 113 0.090 A 3VL9 800-8SA40 1 1 unit 113 0.090
C 3VL9 700-8BL00 1 1 unit 113 0.002 C 3VL9 700-8BL00 1 1 unit 113 0.002
-- --
B 3VL9 000-8AP01 1 1 unit 113 0.605 B 3VL9 000-8AP01 1 1 unit 113 0.605
3VL9 000-8AP01
1)
Mounting plate not included in scope of supply.
2)
Two interlocking modules and one Bowden wire are required.
Cannot be used in conjunction with motorized operating mechanism and
withdrawable version.
Busbar adapter systems with 40 mm or 60 mm busbar center-to-center spacing with components for busbar runs, adapters and switching device holders for
individual equipment possibilities, devices with an integrated adapter, as well as accessories and flat copper profiles. Observe the short-circuit strength of the
busbar system. Short-circuit strength greater than 50 kA on request.
See also "Busbar Systems" chapter.
1)
For degree of protection IP30, the terminal covers from page 2/77 to 2/82
should be ordered.
2)
Usable only for 3VL circuit breakers with line-side box terminals.
8US12 11–4SL01
Up to 400 A
Busbar adapters, length 320 mm
With threaded inserts M4, M6 and M8
For various types of switching devices, 3-pole
Without connecting cables,
with M10 terminal screws at top and bottom1)
Adapter 185 mm wide A 8US12 10-4AF00 1 1 unit 143 2.769
Mounting plates for 8US12 10–4AF00
For VL400 (3VL4) circuit breakers A 8US19 27-4AF01 1 1 unit 143 0.575
(also for VL160X+RCD, VL160, VL250 circuit
breakers (3VL1 + RCD, 3VL2, 3VL3))
For VL630 (3VL5) circuit breakers A 8US12 13-4AF00 1 1 unit 143 2.880
(In max = 580 V)
The connecting cable between adapter and switch-
ing device should be manufactured in accordance
with the rated current as a round cable,
e.g. H07V-R, with a cable lug or as a flat conductor
8US12 10–4AF00 for bolt-type connection M10 (adapter).
1) For degree of protection IP30, the terminal covers from page 2/77 to 2/82 2) Usable only for 3VL circuit breakers with line-side box terminals.
should be ordered.
Standards EN 60044-1
Window-type current transformers The conductor to be measured (busbar or cable) is passed through the window opening and constitutes the
primary circuit of the window-type current transformer.
Pin-wound transformers: An economical solution especially for small primary currents of 5 ... 75 A is achieved
when the conductor to be measured is pin-wound several times.
Rated primary current Ipn Current transformers can be continuously loaded with 1.3 times the rated primary current (Ipn).
Rated secondary current Isn
1A Particularly suitable for longer measuring leads. Cable losses of only 4 % in contrast to 5 A current transformers.
5A 5 A current transformers generate 25 times the power losses on measuring leads as compared with 1 A current
transformers. These stray losses result in higher power in the case of long cables. Only recommended for use
with short measuring leads.
Accuracy class
Class 1 Operation measurement, internal metering
Current error ±1 % at 1 x Ipn and 1.2 x Ipn
Class 3 Coarse measurement
Current error ±3 % at 0.5 x Ipn and 1.2 x Ipn
Rated power Pn The rated power of transformers is specified in VA. The actual load rating should be similar to the rated power;
a lower actual load rating (underburden) increases the overcurrent factor and measuring devices may be dam-
aged in case of a short-circuit, a higher actual load rating (overburden) has a negative effect on the accuracy.
With a frequency of 60 Hz the rated power increases to 1.2 times. With 162/3Hz the output power decreases to
1
/3 of the rated power.
Maximum voltage for equipment Um This is the rms value of the maximum voltage between the conductors of a system. For this voltage the insula-
tion must be rated at normal operating conditions.
4NC5 current transformers are suitable for 720 V.
Overcurrent limiting factor FS The overcurrent limiting factor is expressed using the characters FS and a factor, e.g. FS5 or FS10.
When a short-circuit current flows through the primary winding of a current transformer, the load on the measur-
ing devices connected to the current transformer is the lower the smaller the overcurrent limiting factor is.
Rated short-time thermal current Ith The rated short-time thermal current Ith is the rms value of the primary current with a duration of one second,
whose heat effect the current transformer can resist without being damaged in the event of a short-circuited
secondary winding.
Rated impulse current Idyn The rated impulse current Idyn is the highest instantaneous value of the current after a short-circuit whose force
the current transformer can resist without being damaged.
The rated impulse current is specified as peak value.
Class 1
• For circular conductors with max. diameter 17.5 mm
• For 1 busbar up to max. 12 mm × 10 mm
100 2.5 A 4NC51 17-0CC20 1 1 unit 103 0.335
150 2.5 A 4NC51 21-0CC20 1 1 unit 103 0.327
200 5 A 4NC51 22-0CE20 1 1 unit 103 0.356
4NC51 17-0CC20 250 5 A 4NC51 23-0CE20 1 1 unit 103 0.352
4NC53 25-0CE20
4NC54 31-0CH20
Class 1
• For circular conductors with max. diameter 17.5 mm
• For 1 busbar up to max. 12 mm × 10 mm
100 2.5 A 4NC51 17-2CC20 1 1 unit 103 0.340
150 2.5 A 4NC51 21-2CC20 1 1 unit 103 0.327
200 5 A 4NC51 22-2CE20 1 1 unit 103 0.339
4NC51 17-2CC20 250 5 A 4NC51 23-2CE20 1 1 unit 103 0.345
4NC53 25-2CE20
4NC54 31-2CH20
4NC51 window-type current transformers, used as pin-wound transformers, Classes 1 and 3, from 5 A to 75 A
Pin-winding increases the primary current of the current trans-
former. Consequently, window-type current transformers can
also be used for low primary currents.
Masking frame C
A 3VL9 300-8BC00 1 1 unit 113 0.038 A 3VL9 300-8BC00 1 1 unit 113 0.038
A 3VL9 300-8BG00 1 1 unit 113 0.099 A 3VL9 300-8BG00 1 1 unit 113 0.099
A 3VL9 300-8BH00 1 1 unit 113 0.267 A 3VL9 300-8BH00 1 1 unit 113 0.267
A 3VL9 300-8BD00 1 1 unit 113 0.034 A 3VL9 300-8BD00 1 1 unit 113 0.034
A 3VL9 300-8BD00 1 1 unit 113 0.034 A 3VL9 300-8BD00 1 1 unit 113 0.034
A 3VL9 300-8BH00 1 1 unit 113 0.267 A 3VL9 300-8BH00 1 1 unit 113 0.267
A 3VL9 300-8BJ00 1 1 unit 113 0.230 A 3VL9 300-8BJ00 1 1 unit 113 0.230
DT For VL630 (3VL5) PU PS*/ PG Weight DT For VL800 (3VL6) PU PS*/ PG Weight
Order No. Price (UNIT, P. unit per PU Order No. Price (UNIT, P. unit per PU
per PU SET, M) approx. per PU SET, M) approx.
kg kg
A 3VL9 600-8BC00 1 1 unit 113 0.055 A 3VL9 600-8BC00 1 1 unit 113 0.055
A 3VL9 600-8BG00 1 1 unit 113 0.177 A 3VL9 600-8BG00 1 1 unit 113 0.177
A 3VL9 600-8BH00 1 1 unit 113 0.575 A 3VL9 600-8BH00 1 1 unit 113 0.575
-- --
-- --
-- --
-- --
NSE-00574
Masking frame A
B1) Fixed-mounted, plug-in or withdrawable
IP40 circuit breaker with front-operated rotary
operating mechanism or
motorized operating mechanism A 3VL9 800-8BG00 1 1 unit 113 0.192
NSE-00575
Masking frame B
C Withdrawable circuit breaker with toggle
IP20 lever actuation. Assembly kit contains
masking frame and extended escutcheon
(cannot be used together with a motorized
operating mechanism/rotary operating
mechanism) A 3VL9 800-8BH00 1 1 unit 113 0.531
Masking frame C
D Fixed-mounted circuit breaker or
IP40 plug-in circuit breaker
RCD circuit breaker masking frame --
RCD masking frame --
NSE-00577
Masking frame D
E1) Circuit breaker with RCD module and
IP40 front-operated rotary operating mechanism.
Assembly kit contains masking frame and
extended escutcheon --
Circuit breaker with RCD module and
motorized operating mechanism.
Assembly kit contains masking frame and
NSE-00578 extended escutcheon --
Masking frame E
1) For withdrawable version IP20.
--
--
--
--
■ More information
Manual for the SENTRON 3VL circuit breakers SENTRON manual for communication solutions
This manual contains additional technical information, covering Free download from www.siemens.com/lowvoltage/manuals
a product description, mode of operation, electrical wiring sys-
tem and retrofitting. See also "3WL Air Circuit Breakers/Non-Automatic Air Circuit
Breakers up to 6300 A (AC)", "Accessories and spare parts".
The manual and operating instructions are available in PDF for-
mat at: www.siemens.com/lowvoltage/manuals
3/2 Introduction 3
5SL Miniature Circuit Breakers
3/4 6000 A N
Busbars
3/37 Standard 5ST3 6, 5ST3 7
3/43 According to UL 508, 5ST3 7. .-.HG
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical specifications
under Entry List:
- Updates
- Downloads
- FAQ
- Manuals
- Characteristic curves
- Certificates
and at
www.siemens.com/lowvoltage/
configurators
- Configurators
Introduction
■ Overview
3 Devices Page Field of application Standards Used in
Non-residential
Residential
buildings
buildings
Industry
5SL miniature circuit breakers, 3/4 For all 0.3 to 63 A applications with B EN 60898-1 ✓ ✓ ✓
6000 A and C tripping characteristics with
6000 A rated switching capacity acc. to
EN 60898-1.
5SY and 5SP miniature circuit 3/8 For all applications from 0.3 to 125 A EN 60898-1/2; ✓ ✓ ✓
breakers with a rated switching capacity of EN 60947-2
10000 A and 15000 A acc. to
EN 60898-1. Applications for universal
current and from 0.3 to 63 A,
Version 25 kA, acc. to EN 60947-2.
5SJ6 . . .-.KS miniature circuit 3/23 For socket outlet and lighting circuits in EN 60898-1 ✓ ✓ ✓
breakers with plug-in terminals all building installations.
The plug-in terminals offer easy front
connection for manual insertion of con-
ductors, which considerably reduces
mounting times.
5SY6 0 miniature circuit breakers, 3/26 For socket outlet and lighting circuits in EN 60898-1 ✓ ✓ ✓
1+N in 1 MW all building installations where a switch-
able neutral conductor is required.
The miniature circuit breaker 1+N saves
space in the distribution board.
5SJ4 . . .-.HG miniature circuit 3/46 Miniature circuit breakers can be used UL 489 ✓ ✓ ✓
breakers and accessories, as "branch circuit protection" and are
acc. to UL 489 and IEC approved for the connection type "same
polarity" and "opposite polarity" in the
characteristics B, C and D acc. to
UL 489, from 0.3 to 63 A.
Introduction
3
Devices Page Field of application Standards Used in
Non-residential
Residential
buildings
buildings
Industry
5SP3 main miniature circuit breakers, 3/55 Voltage-independent selective main DIN VDE 0641-21 ✓ ✓ --
SHU miniature circuit breakers (SHU) in the
precounter sector support downstream
miniature circuit breakers by providing
better current limitation.
5SK9 circuit breaker terminals 3/58 Circuit breaker terminals are used for -- -- ✓
short-circuit protection or for protection
against overload and short circuits in
auxiliary and control circuits down-
stream of control transformers.
■ Benefits
• Attractive device design • Ergonomic handle and enclosure for user-friendly switching.
• Easily recognizable, color-coded switching position indication
integrated in the handle.
• Square terminal version for joint accommodation of pin bus- • Easy-to-mount busbar assembly
bars with cables. • Consistent bus-mounting concept throughout the Siemens
miniature circuit breaker range.
• Effective touch protection when grasping and manually oper- • Terminal for the accommodation of 2 cables of the same
ating the latching slide with latch-down option. cross-section (solid up to 2 x 10 mm2, finely stranded with end
sleeve, up to 2 x 4 mm2).
• Individual devices can be removed from the bus-mounted as- • The 5SL miniature circuit breakers are ideal for the quick and
sembly without the use of tools. easy mounting of auxiliary switches and fault signal contacts.
■ Technical specifications
5SL6
Standards EN 60898-1
Approvals See annex, chapter 20
Tripping characteristic B, C
Rated voltage Un V AC 230/400
Operational voltage
• Min. V AC/DC 24
• Max. V AC 250/440
• Max. V DC/pole 601)
Rated switching capacity Icn Acc. to EN 60898-1 kA AC 6
Insulation coordination
• Rated insulation voltage V AC 250/440
• Pollution degree for overvoltage category 2/III
Touch protection Acc. to EN 50274 Yes
Handle end position, sealable Yes
Degree of protection IP20, with connected conductors
CFC and silicone-free Yes
Conductor cross-sections
• Solid and stranded mm2 0.75 ... 35
• Finely stranded with end sleeve mm2 0.75 ... 25
Terminals
• Terminal tightening torque Nm 2.5 ... 3
Mounting position Any
Service life, on average, with rated load 20000 actuations
Ambient temperature °C -25 ... +45, occasionally +55, max. 95 % humidity,
storage temperature: -40 ... +75
Resistance to climate Acc. to IEC 60068-2-30 6 cycles
Resistance to vibrations Acc. to IEC 60068-2-6 m/s2 50 at 25 ... 150 Hz and 60 at 35 Hz (4 sec)
1) The operational voltage 60 V DC/pole takes into account a battery charg-
ing voltage with a peak value of 72 V.
3
6 000 Characteristic B Characteristic C
3 In Mount- DT Order No. Price PG DT Order No. Price PU PS*/ PG Weight
ing per PU per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW1) kg
MCBs 6000 A
3P, 400 V AC
0.3 3 -- A 5SL6 314-7 1 1 unit 003 0.465
0.5 -- A 5SL6 305-7 1 1 unit 003 0.465
1 -- A 5SL6 301-7 1 1 unit 003 0.465
1.6 -- A 5SL6 315-7 1 1 unit 003 0.465
2 -- A 5SL6 302-7 1 1 unit 003 0.465
3 -- A 5SL6 303-7 1 1 unit 003 0.465
4 -- A 5SL6 304-7 1 1 unit 003 0.465
6 A 5SL6 306-6 002 A 5SL6 306-7 1 1 unit 003 0.465
8 -- A 5SL6 308-7 1 1 unit 003 0.465
10 A 5SL6 310-6 002 A 5SL6 310-7 1 1 unit 003 0.465
13 A 5SL6 313-6 002 A 5SL6 313-7 1 1 unit 003 0.465
16 A 5SL6 316-6 002 A 5SL6 316-7 1 1 unit 003 0.360
20 A 5SL6 320-6 002 A 5SL6 320-7 1 1 unit 003 0.465
25 A 5SL6 325-6 002 A 5SL6 325-7 1 1 unit 003 0.465
32 A 5SL6 332-6 002 A 5SL6 332-7 1 1 unit 003 0.465
40 A 5SL6 340-6 002 A 5SL6 340-7 1 1 unit 003 0.465
50 A 5SL6 350-6 002 A 5SL6 350-7 1 1 unit 003 0.465
63 A 5SL6 363-6 002 A 5SL6 363-7 1 1 unit 003 0.465
3P+N, 400 V AC
0.3 4 -- A 5SL6 614-7 1 1 unit 003 0.660
0.5 -- A 5SL6 605-7 1 1 unit 003 0.660
1 -- A 5SL6 601-7 1 1 unit 003 0.660
1.6 -- A 5SL6 615-7 1 1 unit 003 0.660
2 -- A 5SL6 602-7 1 1 unit 003 0.660
3 -- A 5SL6 603-7 1 1 unit 003 0.660
4 -- A 5SL6 604-7 1 1 unit 003 0.660
6 A 5SL6 606-6 002 A 5SL6 606-7 1 1 unit 003 0.660
8 -- A 5SL6 608-7 1 1 unit 003 0.660
10 A 5SL6 610-6 002 A 5SL6 610-7 1 1 unit 003 0.660
13 A 5SL6 613-6 002 A 5SL6 613-7 1 1 unit 003 0.660
16 A 5SL6 616-6 002 A 5SL6 616-7 1 1 unit 003 0.660
20 A 5SL6 620-6 002 A 5SL6 620-7 1 1 unit 003 0.660
25 A 5SL6 625-6 002 A 5SL6 625-7 1 1 unit 003 0.660
32 A 5SL6 632-6 002 A 5SL6 632-7 1 1 unit 003 0.660
40 A 5SL6 640-6 002 A 5SL6 640-7 1 1 unit 003 0.660
50 A 5SL6 650-6 002 A 5SL6 650-7 1 1 unit 003 0.660
63 A 5SL6 663-6 002 A 5SL6 663-7 1 1 unit 003 0.660
4P, 400 V AC
0.3 4 -- A 5SL6 414-7 1 1 unit 003 0.660
0.5 -- A 5SL6 405-7 1 1 unit 003 0.660
1 -- A 5SL6 401-7 1 1 unit 003 0.660
1.6 -- A 5SL6 415-7 1 1 unit 003 0.660
2 -- A 5SL6 402-7 1 1 unit 003 0.660
3 -- A 5SL6 403-7 1 1 unit 003 0.660
4 -- A 5SL6 404-7 1 1 unit 003 0.660
6 A 5SL6 406-6 002 A 5SL6 406-7 1 1 unit 003 0.660
8 -- A 5SL6 408-7 1 1 unit 003 0.660
10 A 5SL6 410-6 002 A 5SL6 410-7 1 1 unit 003 0.660
13 A 5SL6 413-6 002 A 5SL6 413-7 1 1 unit 003 0.660
16 A 5SL6 416-6 002 A 5SL6 416-7 1 1 unit 003 0.660
20 A 5SL6 420-6 002 A 5SL6 420-7 1 1 unit 003 0.660
25 A 5SL6 425-6 002 A 5SL6 425-7 1 1 unit 003 0.660
32 A 5SL6 432-6 002 A 5SL6 432-7 1 1 unit 003 0.660
40 A 5SL6 440-6 002 A 5SL6 440-7 1 1 unit 003 0.660
50 A 5SL6 450-6 002 A 5SL6 450-7 1 1 unit 003 0.660
63 A 5SL6 463-6 002 A 5SL6 463-7 1 1 unit 003 0.660
1)
1 MW (modular width) = 18 mm.
■ Overview
3 MCBs are used to protect plants in buildings and for industrial The devices are approved for worldwide use according to IEC
applications. The devices can be used as main control switches standards for systems up to 250/440 V AC. 60 V DC per pole is
for the disconnection or isolation of plants. permitted in DC systems.
Used in industrial applications and plant engineering, miniature For North America, we also have additional certification to
circuit breakers can be supplemented with additional compo- UL 1077 for use as "supplementary protectors" in systems up to
nents, such as auxiliary switches, fault signal contacts, shunt 480Y/277 V AC. For use in ship building, the devices also have
trips, undervoltage releases, remote controls and RC units. numerous certifications according to shipping classifications;
BV, DNV, GL and LRS. References to this can be found in the
annex, chapter 20.
■ Benefits
• Optional top or bottom infeed as the terminals are identical • Integrated movable terminal covers located at the cable en-
• Clear and visible conductor connection in front of the busbar tries ensure the terminals are fully insulated when the screws
facilitates controls are tightened
• The conductor is easily inserted into the terminal thanks to the • The effective touch protection when grasping the device con-
large and easily accessible wiring space. siderably exceeds the requirements of VBG 4/BGV A3.
• Manual snap-on fixing and release systems that require no • Quick and easy manual removal of MCBs from the busbar as-
tools enable fast assembly and disassembly of MCBs sembly if e. g. connections need to be changed
• Marked labeling field on all modular installation devices for • Time-saving replacement of parts as busbars no longer need
uniform, quick and easy identification. to be freed from adjacent devices.
• Duplicate terminal clamps allow 2 conductors with different • The 5SY miniature circuit breakers are ideal for the quick and
cross-sections (cross-section combinations upon request) to easy mounting of auxiliary switches and fault signal contacts.
be fitted. Captive metal brackets on additional components ensure the
quick and easy mounting of devices on the miniature circuit
breakers without the need for tools.
■ Technical specifications
3 5SY4 5SY5 5SY7 5SY8 5SP4 5SP5
Standards EN 60898-1; EN 60898-2; EN 60898-1; EN 60947-2 EN 60898-1; EN 60898-2
EN 60947-2 EN 60947-2 EN 60947-2
Approvals See annex, chapter 20
Operational voltage V AC 230/400 230/400 230/400 230/400 230/400 230/400
V DC -- 220/440/880 -- -- -- 220/440
Min. V AC/DC 24 24 24 24 24 24
Acc. to EN 60898-1/-2 and EN 60947-2 Max. V DC/pole 601) 250 601) 601) 601) 250
Max. V AC 250/440 250/440 250/440 250/440 250/440 250/440
Acc. to UL 1077 and CSA C22.2 No.235 Max. V AC 480Y/277 -- 480Y/277 480Y/277 480Y/277 --
V DC/pole 60 -- 60 60 60 --
Rated switching capacity2)
• Icn acc. to IEC/EN 60898-1 kA AC 10 10 15 -- 10 3
• Icn acc. to IEC/EN 60898-2 kA DC 10 10 15 -- 10 10
• Icu acc. to IEC/EN 60947-2 kA AC -- -- -- 25 -- --
kA DC -- 15 -- 15 -- 15
• Acc. to UL1077 and CSA C22.2 No.235 kA AC 5 -- 5 5 5 --
Insulation coordination
• Rated insulation voltage V AC 250/440
V DC/pole -- 250 -- -- -- 250
Pollution degree for overvoltage category 3/III
Touch protection Acc. to EN 50274 Yes
Main switch characteristics according to EN 60204 Yes
Handle end position, sealable Yes
Degree of protection Acc. to EN 60529 IP20, with connected conductors
CFC and silicone-free Yes
Mounting
• Snap-on fixing system Yes --
• Standard mounting rail and screw fixing -- Yes
Terminals
• Tunnel terminals at both ends -- Yes
• Combined terminals at both ends Yes --
• Terminal tightening torque Nm 2.5 ... 3 2.5 ... 3.5
lb. in 22 ... 26 22 ... 31
Conductor cross-sections
• Solid and stranded mm2 0.75 ... 35 0.75 ... 50
• Finely stranded, with end sleeve mm2 0.75 ... 25 0.75 ... 35
• AWG cables AWG 14 ... 4 14 ... 2
Mains connection
• AC Any
• DC Any 3) Any 3)
1)
The operational voltage 60 V DC/pole takes into account a battery charg-
ing voltage with a peak value of 72 V.
2)
For detailed information, see engineering manual at:
www.siemens.com/lowvoltage/manuals.
3)
Ensure compliance with the specified polarity when connecting DC.
3
10 000 Mount- DT Characteristic C PG DT Characteristic D PU PS*/ PG Weight
In ing Order No. Price Order No. Price (UNIT, P. unit per PU
3 width SET, approx.
per PU per PU
M)
A MW1) kg
MCBs 10000 A
1P, 230/400 V AC
0.3 1 B 5SY4 114-7 003 C 5SY4 114-8 1 1 unit 004 0.167
0.5 } 5SY4 105-7 003 B 5SY4 105-8 1 1 unit 004 0.166
1 } 5SY4 101-7 003 } 5SY4 101-8 1 1 unit 004 0.165
1.6 A 5SY4 115-7 003 B 5SY4 115-8 1 1 unit 004 0.163
2 } 5SY4 102-7 003 } 5SY4 102-8 1 1/12 units 004 0.155
3 } 5SY4 103-7 003 } 5SY4 103-8 1 1 unit 004 0.160
4 } 5SY4 104-7 003 } 5SY4 104-8 1 1/12 units 004 0.158
5 C 5SY4 111-7 003 -- 1 1 unit 0.149
6 } 5SY4 106-7 003 } 5SY4 106-8 1 1 unit 004 0.159
8 } 5SY4 108-7 003 A 5SY4 108-8 1 1 unit 004 0.156
10 } 5SY4 110-7 003 } 5SY4 110-8 1 1/12 units 004 0.155
13 } 5SY4 113-7 003 B 5SY4 113-8 1 1 unit 004 0.156
15 C 5SY4 118-7 003 -- 1 1 unit 0.151
16 } 5SY4 116-7 003 } 5SY4 116-8 1 1 unit 004 0.156
20 C 5SY4 120-7 003 A 5SY4 120-8 1 1 unit 004 0.162
25 } 5SY4 125-7 003 B 5SY4 125-8 1 1 unit 004 0.161
30 C 5SY4 130-7 003 -- 1 1 unit 0.148
32 } 5SY4 132-7 003 B 5SY4 132-8 1 1 unit 004 0.165
35 B 5SY4 135-7 003 -- 1 1 unit 0.180
40 } 5SY4 140-7 003 B 5SY4 140-8 1 1 unit 004 0.166
45 B 5SY4 145-7 003 -- 1 1 unit 0.160
50 A 5SY4 150-7 003 B 5SY4 150-8 1 1 unit 004 0.164
60 B 5SY4 160-7 003 -- 1 1 unit 0.160
63 B 5SY4 163-7 003 B 5SY4 163-8 1 1 unit 004 0.166
80 B 5SY4 180-7 003 -- 1 1 unit 0.160
1P+N, 230 V AC
0.3 2 C 5SY4 514-7 003 C 5SY4 514-8 1 1 unit 004 0.323
0.5 B 5SY4 505-7 003 C 5SY4 505-8 1 1 unit 004 0.316
1 } 5SY4 501-7 003 B 5SY4 501-8 1 1 unit 004 0.303
1.6 C 5SY4 515-7 003 C 5SY4 515-8 1 1 unit 004 0.319
2 } 5SY4 502-7 003 A 5SY4 502-8 1 1 unit 004 0.320
3 A 5SY4 503-7 003 B 5SY4 503-8 1 1 unit 004 0.314
4 } 5SY4 504-7 003 B 5SY4 504-8 1 1 unit 004 0.310
6 } 5SY4 506-7 003 A 5SY4 506-8 1 1 unit 004 0.311
8 B 5SY4 508-7 003 C 5SY4 508-8 1 1 unit 004 0.305
10 } 5SY4 510-7 003 } 5SY4 510-8 1 1 unit 004 0.305
13 } 5SY4 513-7 003 B 5SY4 513-8 1 1 unit 004 0.304
16 } 5SY4 516-7 003 A 5SY4 516-8 1 1 unit 004 0.306
20 } 5SY4 520-7 003 B 5SY4 520-8 1 1 unit 004 0.309
25 A 5SY4 525-7 003 B 5SY4 525-8 1 1 unit 004 0.309
32 A 5SY4 532-7 003 B 5SY4 532-8 1 1 unit 004 0.320
40 B 5SY4 540-7 003 C 5SY4 540-8 1 1 unit 004 0.312
50 C 5SY4 550-7 003 C 5SY4 550-8 1 1 unit 004 0.322
63 C 5SY4 563-7 003 C 5SY4 563-8 1 1 unit 004 0.332
80 C 5SY4 580-7 003 -- 1 1 unit 0.321
2P, 400 V AC
0.3 2 A 5SY4 214-7 003 B 5SY4 214-8 1 1 unit 004 0.325
0.5 } 5SY4 205-7 003 A 5SY4 205-8 1 1 unit 004 0.325
1 } 5SY4 201-7 003 } 5SY4 201-8 1 1 unit 004 0.320
1.6 } 5SY4 215-7 003 A 5SY4 215-8 1 1 unit 004 0.319
2 } 5SY4 202-7 003 } 5SY4 202-8 1 1 unit 004 0.318
3 } 5SY4 203-7 003 } 5SY4 203-8 1 1 unit 004 0.313
4 } 5SY4 204-7 003 } 5SY4 204-8 1 1 unit 004 0.309
5 C 5SY4 211-7 003 -- 1 1 unit 0.297
6 } 5SY4 206-7 003 } 5SY4 206-8 1 1 unit 004 0.312
8 } 5SY4 208-7 003 A 5SY4 208-8 1 1 unit 004 0.305
10 } 5SY4 210-7 003 } 5SY4 210-8 1 1 unit 004 0.303
13 } 5SY4 213-7 003 A 5SY4 213-8 1 1 unit 004 0.304
15 C 5SY4 218-7 003 -- 1 1 unit 0.294
16 } 5SY4 216-7 003 } 5SY4 216-8 1 1 unit 004 0.305
20 } 5SY4 220-7 003 } 5SY4 220-8 1 1 unit 004 0.317
25 } 5SY4 225-7 003 A 5SY4 225-8 1 1 unit 004 0.318
30 B 5SY4 230-7 003 -- 1 1 unit 0.300
32 } 5SY4 232-7 003 A 5SY4 232-8 1 1 unit 004 0.324
35 B 5SY4 235-7 003 -- 1 1 unit 0.298
40 } 5SY4 240-7 003 A 5SY4 240-8 1 1 unit 004 0.326
45 B 5SY4 245-7 003 -- 1 1 unit 0.312
50 A 5SY4 250-7 003 B 5SY4 250-8 1 1 unit 004 0.324
60 B 5SY4 260-7 003 -- 1 1 unit 0.322
63 A 5SY4 263-7 003 B 5SY4 263-8 1 1 unit 004 0.325
80 B 5SY4 280-7 003 -- 1 1/6 units 0.313
* You can order this quantity or a multiple thereof.
Siemens LV 10.1 · 2011 3/13
© Siemens AG 2010
2P, 400 V AC
80 3 C 5SP4 280-6 1 1 unit 002 0.532
100 C 5SP4 291-6 1 1 unit 002 0.527
125 C 5SP4 292-6 1 1 unit 002 0.534
3P, 400 V AC
80 4.5 B 5SP4 380-6 1 1 unit 002 0.800
100 B 5SP4 391-6 1 1 unit 002 0.787
125 C 5SP4 392-6 1 1 unit 002 0.793
4P, 400 V AC
80 6 B 5SP4 480-6 1 1 unit 002 1.046
100 C 5SP4 491-6 1 1 unit 002 1.038
125 C 5SP4 492-6 1 1 unit 002 1.062
2P, 400 V AC
80 3 A 5SP4 280-7 003 C 5SP4 280-8 1 1 unit 004 0.505
100 A 5SP4 291-7 003 C 5SP4 291-8 1 1 unit 004 0.515
125 A 5SP4 292-7 003 -- 1 1 unit 0.521
3P, 400 V AC
80 4.5 } 5SP4 380-7 003 A 5SP4 380-8 1 1 unit 004 0.762
100 } 5SP4 391-7 003 A 5SP4 391-8 1 1 unit 004 0.783
125 A 5SP4 392-7 003 -- 1 1 unit 0.787
4P, 400 V AC
80 6 A 5SP4 480-7 003 A 5SP4 480-8 1 1 unit 004 1.031
100 A 5SP4 491-7 003 C 5SP4 491-8 1 1 unit 004 1.033
125 A 5SP4 492-7 003 -- 1 1 unit 1.031
1)
1 MW (modular width) = 18 mm.
3
10 000 Characteristic B Characteristic C
3 In Mount- DT Order No. Price PG DT Order No. Price PU PS*/ PG Weight
ing per PU per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW1) kg
MCBs 10000 A, UC
4P, 400 V AC, 880 V DC
0.3 1 -- C 5SY5 414-7 1 1 unit 003 0.660
0.5 -- C 5SY5 405-7 1 1 unit 003 0.660
1 -- C 5SY5 401-7 1 1 unit 003 0.660
1.6 -- C 5SY5 415-7 1 1 unit 003 0.660
2 -- C 5SY5 402-7 1 1 unit 003 0.660
3 -- C 5SY5 403-7 1 1 unit 003 0.660
4 -- C 5SY5 404-7 1 1 unit 003 0.660
6 C 5SY5 406-6 002 C 5SY5 406-7 1 1 unit 003 0.660
8 -- C 5SY5 408-7 1 1 unit 003 0.660
10 C 5SY5 410-6 002 C 5SY5 410-7 1 1 unit 003 0.660
13 C 5SY5 413-6 002 C 5SY5 413-7 1 1 unit 003 0.660
16 C 5SY5 416-6 002 C 5SY5 416-7 1 1 unit 003 0.660
20 C 5SY5 420-6 002 C 5SY5 420-7 1 1 unit 003 0.660
25 C 5SY5 425-6 002 C 5SY5 425-7 1 1 unit 003 0.660
32 C 5SY5 432-6 002 C 5SY5 432-7 1 1 unit 003 0.660
40 C 5SY5 440-6 002 C 5SY5 440-7 1 1 unit 003 0.660
50 C 5SY5 450-6 002 C 5SY5 450-7 1 1 unit 003 0.660
63 C 5SY5 463-6 002 C 5SY5 463-7 1 1 unit 003 0.660
3
15 000 Characteristic C Characteristic D
In Mount- DT Order No. Price PG DT Order No. Price PU PS*/ PG Weight
ing per PU per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW1) kg
MCBs 15000 A
1P, 230/400 V AC
0.3 1 B 5SY7 114-7 003 C 5SY7 114-8 1 1 unit 004 0.160
0.5 B 5SY7 105-7 003 C 5SY7 105-8 1 1 unit 004 0.153
1 A 5SY7 101-7 003 C 5SY7 101-8 1 1 unit 004 0.180
1.6 B 5SY7 115-7 003 C 5SY7 115-8 1 1 unit 004 0.165
2 } 5SY7 102-7 003 C 5SY7 102-8 1 1 unit 004 0.162
3 A 5SY7 103-7 003 C 5SY7 103-8 1 1 unit 004 0.161
4 } 5SY7 104-7 003 B 5SY7 104-8 1 1 unit 004 0.158
6 } 5SY7 106-7 003 B 5SY7 106-8 1 1 unit 004 0.160
8 B 5SY7 108-7 003 C 5SY7 108-8 1 1 unit 004 0.154
10 } 5SY7 110-7 003 B 5SY7 110-8 1 1 unit 004 0.156
13 B 5SY7 113-7 003 C 5SY7 113-8 1 1 unit 004 0.156
16 } 5SY7 116-7 003 B 5SY7 116-8 1 1 unit 004 0.156
20 } 5SY7 120-7 003 C 5SY7 120-8 1 1 unit 004 0.141
25 B 5SY7 125-7 003 C 5SY7 125-8 1 1 unit 004 0.162
32 B 5SY7 132-7 003 C 5SY7 132-8 1 1 unit 004 0.166
40 B 5SY7 140-7 003 C 5SY7 140-8 1 1 unit 004 0.166
50 C 5SY7 150-7 003 C 5SY7 150-8 1 1 unit 004 0.167
63 B 5SY7 163-7 003 C 5SY7 163-8 1 1 unit 004 0.165
1P+N, 230 V AC
0.3 2 C 5SY7 514-7 003 C 5SY7 514-8 1 1 unit 004 0.323
0.5 C 5SY7 505-7 003 C 5SY7 505-8 1 1 unit 004 0.312
1 B 5SY7 501-7 003 C 5SY7 501-8 1 1 unit 004 0.320
1.6 C 5SY7 515-7 003 C 5SY7 515-8 1 1 unit 004 0.319
2 B 5SY7 502-7 003 C 5SY7 502-8 1 1 unit 004 0.319
3 B 5SY7 503-7 003 C 5SY7 503-8 1 1 unit 004 0.298
4 B 5SY7 504-7 003 B 5SY7 504-8 1 1 unit 004 0.310
6 A 5SY7 506-7 003 C 5SY7 506-8 1 1 unit 004 0.326
8 C 5SY7 508-7 003 C 5SY7 508-8 1 1 unit 004 0.286
10 } 5SY7 510-7 003 C 5SY7 510-8 1 1 unit 004 0.305
13 B 5SY7 513-7 003 C 5SY7 513-8 1 1 unit 004 0.304
16 } 5SY7 516-7 003 B 5SY7 516-8 1 1 unit 004 0.293
20 B 5SY7 520-7 003 C 5SY7 520-8 1 1 unit 004 0.317
25 B 5SY7 525-7 003 C 5SY7 525-8 1 1 unit 004 0.313
32 B 5SY7 532-7 003 C 5SY7 532-8 1 1 unit 004 0.325
40 C 5SY7 540-7 003 C 5SY7 540-8 1 1 unit 004 0.308
50 C 5SY7 550-7 003 C 5SY7 550-8 1 1 unit 004 0.330
63 C 5SY7 563-7 003 C 5SY7 563-8 1 1 unit 004 0.308
2P, 400 V AC
0.3 2 C 5SY7 214-7 003 C 5SY7 214-8 1 1 unit 004 0.322
0.5 B 5SY7 205-7 003 C 5SY7 205-8 1 1 unit 004 0.325
1 } 5SY7 201-7 003 B 5SY7 201-8 1 1 unit 004 0.313
1.6 C 5SY7 215-7 003 C 5SY7 215-8 1 1 unit 004 0.359
2 } 5SY7 202-7 003 A 5SY7 202-8 1 1 unit 004 0.318
3 A 5SY7 203-7 003 B 5SY7 203-8 1 1 unit 004 0.314
4 } 5SY7 204-7 003 A 5SY7 204-8 1 1 unit 004 0.310
6 } 5SY7 206-7 003 A 5SY7 206-8 1 1 unit 004 0.312
8 B 5SY7 208-7 003 B 5SY7 208-8 1 1 unit 004 0.302
10 } 5SY7 210-7 003 A 5SY7 210-8 1 1 unit 004 0.306
13 B 5SY7 213-7 003 C 5SY7 213-8 1 1 unit 004 0.287
16 } 5SY7 216-7 003 } 5SY7 216-8 1 1 unit 004 0.304
20 } 5SY7 220-7 003 B 5SY7 220-8 1 1 unit 004 0.314
25 } 5SY7 225-7 003 B 5SY7 225-8 1 1 unit 004 0.313
32 } 5SY7 232-7 003 C 5SY7 232-8 1 1 unit 004 0.328
40 A 5SY7 240-7 003 C 5SY7 240-8 1 1 unit 004 0.325
50 B 5SY7 250-7 003 C 5SY7 250-8 1 1 unit 004 0.308
63 B 5SY7 263-7 003 C 5SY7 263-8 1 1 unit 004 0.326
1)
1 MW (modular width) = 18 mm.
3
Characteristic C Characteristic D
In Mount- DT Order No. Price PG DT Order No. Price PU PS*/ PG Weight
ing per PU per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW1) kg
MCBs 25 kA
3P, 400 V AC
0.3 3 C 5SY8 314-7 003 C 5SY8 314-8 1 1 unit 004 0.495
0.5 C 5SY8 305-7 003 C 5SY8 305-8 1 1 unit 004 0.482
1 A 5SY8 301-7 003 C 5SY8 301-8 1 1 unit 004 0.478
1.6 C 5SY8 315-7 003 C 5SY8 315-8 1 1 unit 004 0.495
2 C 5SY8 302-7 003 C 5SY8 302-8 1 1 unit 004 0.471
3 C 5SY8 303-7 003 C 5SY8 303-8 1 1 unit 004 0.467
4 C 5SY8 304-7 003 C 5SY8 304-8 1 1 unit 004 0.460
6 B 5SY8 306-7 003 C 5SY8 306-8 1 1 unit 004 0.442
8 C 5SY8 308-7 003 C 5SY8 308-8 1 1 unit 004 0.495
10 B 5SY8 310-7 003 C 5SY8 310-8 1 1 unit 004 0.455
13 C 5SY8 313-7 003 C 5SY8 313-8 1 1 unit 004 0.487
16 } 5SY8 316-7 003 C 5SY8 316-8 1 1 unit 004 0.449
20 C 5SY8 320-7 003 C 5SY8 320-8 1 1 unit 004 0.452
25 } 5SY8 325-7 003 B 5SY8 325-8 1 1 unit 004 0.472
32 A 5SY8 332-7 003 B 5SY8 332-8 1 1 unit 004 0.482
40 B 5SY8 340-7 003 C 5SY8 340-8 1 1 unit 004 0.464
50 B 5SY8 350-7 003 B 5SY8 350-8 1 1 unit 004 0.465
63 B 5SY8 363-7 003 C 5SY8 363-8 1 1 unit 004 0.467
3P+N, 400 V AC
0.3 4 C 5SY8 614-7 003 C 5SY8 614-8 1 1 unit 004 0.660
0.5 C 5SY8 605-7 003 C 5SY8 605-8 1 1 unit 004 0.660
1 C 5SY8 601-7 003 C 5SY8 601-8 1 1 unit 004 0.660
1.6 C 5SY8 615-7 003 C 5SY8 615-8 1 1 unit 004 0.660
2 C 5SY8 602-7 003 C 5SY8 602-8 1 1 unit 004 0.631
3 C 5SY8 603-7 003 C 5SY8 603-8 1 1 unit 004 0.621
4 C 5SY8 604-7 003 C 5SY8 604-8 1 1 unit 004 0.660
6 C 5SY8 606-7 003 C 5SY8 606-8 1 1 unit 004 0.660
8 C 5SY8 608-7 003 C 5SY8 608-8 1 1 unit 004 0.660
10 C 5SY8 610-7 003 C 5SY8 610-8 1 1 unit 004 0.571
13 C 5SY8 613-7 003 C 5SY8 613-8 1 1 unit 004 0.609
16 B 5SY8 616-7 003 C 5SY8 616-8 1 1 unit 004 0.602
20 C 5SY8 620-7 003 C 5SY8 620-8 1 1 unit 004 0.596
25 C 5SY8 625-7 003 C 5SY8 625-8 1 1 unit 004 0.601
32 B 5SY8 632-7 003 C 5SY8 632-8 1 1 unit 004 0.611
40 C 5SY8 640-7 003 C 5SY8 640-8 1 1 unit 004 0.617
50 C 5SY8 650-7 003 C 5SY8 650-8 1 1 unit 004 0.650
63 A 5SY8 663-7 003 C 5SY8 663-8 1 1 unit 004 0.625
4P, 400 V AC
0.3 4 C 5SY8 414-7 003 C 5SY8 414-8 1 1 unit 004 0.660
0.5 C 5SY8 405-7 003 C 5SY8 405-8 1 1 unit 004 0.660
1 C 5SY8 401-7 003 C 5SY8 401-8 1 1 unit 004 0.636
1.6 C 5SY8 415-7 003 C 5SY8 415-8 1 1 unit 004 0.660
2 C 5SY8 402-7 003 C 5SY8 402-8 1 1 unit 004 0.681
3 C 5SY8 403-7 003 C 5SY8 403-8 1 1 unit 004 0.660
4 C 5SY8 404-7 003 C 5SY8 404-8 1 1 unit 004 0.660
6 C 5SY8 406-7 003 C 5SY8 406-8 1 1 unit 004 0.660
8 C 5SY8 408-7 003 C 5SY8 408-8 1 1 unit 004 0.598
10 B 5SY8 410-7 003 C 5SY8 410-8 1 1 unit 004 0.597
13 C 5SY8 413-7 003 C 5SY8 413-8 1 1 unit 004 0.660
16 } 5SY8 416-7 003 C 5SY8 416-8 1 1 unit 004 0.601
20 A 5SY8 420-7 003 C 5SY8 420-8 1 1 unit 004 0.627
25 } 5SY8 425-7 003 C 5SY8 425-8 1 1 unit 004 0.627
32 } 5SY8 432-7 003 C 5SY8 432-8 1 1 unit 004 0.641
40 } 5SY8 440-7 003 C 5SY8 440-8 1 1 unit 004 0.647
50 } 5SY8 450-7 003 C 5SY8 450-8 1 1 unit 004 0.646
63 } 5SY8 463-7 003 C 5SY8 463-8 1 1 unit 004 0.644
1)
1 MW (modular width) = 18 mm.
■ Overview
Miniature circuit breakers with plug-in terminals are used for the
3
protection of socket outlets and lighting circuits with the most
common rated currents of 10 to 20 A.
■ Benefits
• Double, self-contained, screwless outgoing terminals for fast • The plug-in terminal, offering easily accessible and angled ca-
connection of conductors. ble entries for manual insertion, saves mounting time
• Removal of individual conductors requires no tools and en-
sures high operating safety
• No end sleeves required for finely stranded conductors. This
saves mounting time.
■ Technical specifications
3 5SJ6 . . .-.KS
Standards EN 60898-1
Approvals See annex, chapter 20
Operational voltage V AC 230/400
• Min. V AC/DC 24
• Max. V AC 250/440
• Max. V DC/pole 601)
Rated switching capacity Acc. to EN 60898-1 kA AC 6
Insulation coordination
• Rated insulation voltage V AC 250/440
• Pollution degree for overvoltage category 2/III
Touch protection Acc. to EN 50274 Yes
Handle end position, sealable Yes
Degree of protection Acc. to EN 60529 IP20, with connected conductors
CFC and silicone-free Yes
Terminals Screwless terminals on the outgoing terminals for 1.5 ... 4 mm2
Conductor cross-sections
• Top, plug-in terminals
- Solid, stranded and finely stranded, without end sleeve mm2 1.5 ... 4
- Finely stranded, with end sleeve mm2 1.5 ... 2.5
• Bottom, tunnel terminal
- Solid, stranded or finely stranded, with end sleeve mm2 0.75 ... 25
Mounting position Any
Service life,
on average, with rated load 20000 actuations
Ambient temperature °C -25 ... +45, occasionally +55, max. 95 % humidity,
storage temperature: -40 ... +75
Resistance to climate Acc. to IEC 60068-2-30 6 cycles
Resistance to vibrations Acc. to IEC 60068-2-6 m/s2 50 at 25 ... 150 Hz and 60 at 35 Hz (4 sec)
1) The operational voltage 60 V DC/pole takes into account a battery charg-
ing voltage with a peak value of 72 V.
1P+N
10 2 B 5SJ6 510-6KS 002 B 5SJ6 510-7KS 1 1/6 units 003 0.209
13 B 5SJ6 513-6KS 002 B 5SJ6 513-7KS 1 1/6 units 003 0.210
16 B 5SJ6 516-6KS 002 B 5SJ6 516-7KS 1 1/6 units 003 0.208
20 B 5SJ6 520-6KS 002 B 5SJ6 520-7KS 1 1/6 units 003 0.209
2P
10 2 B 5SJ6 210-6KS 002 B 5SJ6 210-7KS 1 1/6 units 003 0.229
13 B 5SJ6 213-6KS 002 B 5SJ6 213-7KS 1 1/6 units 003 0.228
16 B 5SJ6 216-6KS 002 B 5SJ6 216-7KS 1 1/6 units 003 0.226
20 B 5SJ6 220-6KS 002 B 5SJ6 220-7KS 1 1/6 units 003 0.226
3P
10 3 B 5SJ6 310-6KS 002 B 5SJ6 310-7KS 1 1/4 units 003 0.353
13 B 5SJ6 313-6KS 002 B 5SJ6 313-7KS 1 1/4 units 003 0.357
16 B 5SJ6 316-6KS 002 B 5SJ6 316-7KS 1 1/4 units 003 0.358
20 B 5SJ6 320-6KS 002 B 5SJ6 320-7KS 1 1/4 units 003 0.354
1)
1 MW (modular width) = 18 mm.
■ Overview
3 These miniature circuit breakers are used for the protection of The devices are approved for worldwide use according to IEC
plants with switched neutral conductors in distribution boards standards for systems up to 250 V AC. 60 V DC per pole is per-
with little space. They are just a single modular width. mitted in DC systems according to IEC standards.
Compact busbars facilitate installation in space saving distribu-
tion boards.
■ Benefits
• Auxiliary switches and fault signal contacts from the high- • For 3-pole busbars, the 5ST3 6 busbar system is used –
capacity range can be freely mounted on these miniature a universal system suitable for all miniature circuit breakers.
circuit breakers. This increases availability and cuts down on
logistics.
• By actuating the latching slide, the miniature circuit breakers • The infeed can be implemented either from the top or the
can be quickly and easily removed from the assembly. bottom. Additional terminals with lateral cable entry facilitate
mounting when using large conductor cross-sections.
■ Technical specifications
5SY6 0..
3
Standards EN 60898-1
Approvals See annex, chapter 20
Rated voltage Un V AC 230
Operational voltage
• Min. V AC/DC 24
• Max. V AC 250
• Max. V DC/pole 601)
Rated switching capacity Icn kA AC 6
Insulation coordination
• Rated insulation voltage V AC 250
• Pollution degree for overvoltage category 2/III
Touch protection Acc. to EN 50274 Yes
Handle end position, sealable Yes
Degree of protection IP20, with connected conductors
CFC and silicone-free Yes
Terminals
• Solid and stranded, mm2 0.75 ... 16
top and bottom terminal
• Finely stranded, with end sleeve, mm2 0.75 ... 10
top and bottom terminal
• Terminal tightening torque Nm 2.0 ... 2.5
Mounting position Any
Service life
On average, with rated load 20000 actuations
at 2 A/4 A and 40 A: 8000 actuations
Ambient temperature °C -25 ... +45, occasionally +55, max. 95 % humidity,
storage temperature: -40 ... +75
Resistance to climate Acc. to IEC 60068-2-30 6 cycles
Resistance to vibrations Acc. to IEC 60068-2-6 m/s2 50 at 25 ... 150 Hz and 60 at 35 Hz (4 sec)
1)
The operational voltage 60 V DC/pole takes into account a battery charg-
ing voltage with a peak value of 72 V.
Single-phase
For 12 MCBs 1+N, gray 1 216 A 5ST3 762 1 10 units 027 0.022
For 12 MCBs 1+N, blue 216 A 5ST3 763 1 10 units 027 0.001
Single-phase
For MCBs 1+N, gray 1 1016 A 5ST3 764 1 10 units 027 0.134
For MCBs 1+N, blue 1016 A 5ST3 765 1 10 units 027 0.134
1)
1 MW (modular width) = 18 mm.
Additional components
■ Overview
The Siemens mounting concept supports the combination of all Shunt trips (ST)
3
5ST3 additional components with Siemens 5SY and 5SP minia-
ture circuit breakers and with 5SU1 RCBOs. Shunt trips are used for the remote tripping of miniature circuit
breakers.
5SL and 5SY6 0. . miniature circuit breakers are suitable for
mounting auxiliary switches and fault signal contacts. Auxiliary Undervoltage releases (UR)
switches can also be mounted on 5TE8 flush-mounting circuit Undervoltage releases are integrated (e.g. in EMERGENCY
breakers and 5SG7 1 MINIZED switch disconnectors. STOP loops), thus ensuring that the MCB trips in the event of an
Auxiliary switches (AS) emergency, which, in turn, ensures disconnection of the control
circuit according to EN 60204. In the event that the voltage is in-
The auxiliary switch (AS) always signals the contact position of terrupted or too low, it also trips, i.e. prevents activation of the
the miniature circuit breaker, regardless of whether the miniature MCB.
circuit breaker was tripped manually or as the result of a fault. An
additional version is also available for the switching of small cur- Remote controlled mechanisms (RC)
rents and voltages for the control of programmable control sys- Remote controlled mechanisms are used for the remote ON/OFF
tems (PLCs) acc. to EN 61131-2. The auxiliary switch with test switching of miniature circuit breakers and the remote ON
button enables the testing of control circuits without the need to switching of RC units, as well as the local manual switching of
switch the miniature circuit breaker. these devices. A blocking function permits maintenance work. In
Fault signal contacts (FC) the event that a miniature circuit breaker or RC unit is tripped, an
acknowledgment must be carried out prior to switching back on.
The fault signal contact (FC) signals the automatic tripping of the The remote controlled mechanism has an operating mode selec-
miniature circuit breaker in the event of a fault, such as an over- tor switch with the functions: "Locked", "Manual" and "Remote
load or a short circuit. If the fault signal contact is activated, the Switching". The mechanism can be mechanically latched and
contact position does not change if the miniature circuit breaker locked, which serves to protect personnel during maintenance
is tripped manually. Fault signal contacts with TEST and RESET work.
buttons enable the testing of control circuits without the need to
trip the miniature circuit breaker. The red RESET button inte- RC units
grated in the handle also indicates the automatic tripping of the RC units can be combined with miniature circuit breakers of
MCB. The signal can be acknowledged manually using the characteristic A, B, C and D. They then form a combination of
RESET button. RCCB and MCB for personnel, fire and line protection. The com-
binations can be tailored to meet individual requirements.
For information on RC units, please refer to the section "Residual
current protective devices".
■ Benefits
Can be universally retrofitted with all additional components
• The 5SL, 5SY and 5SP miniature circuit breakers are ideal for • Fault signal contacts with TEST and RESET button enable the
the quick and easy mounting of auxiliary switches and fault simple testing of auxiliary circuits and, in the event of a fault,
signal contacts. acknowledgement of the fault over the RESET button, without
Captive metal brackets on additional components ensure the the need to switch the miniature circuit breakers.
quick and easy mounting of devices on the miniature circuit
breakers without the need for tools.
Additional components
The auxiliary switches with TEST button enable the simple man-
ual testing of control circuits during operation of the entire plant
without the need to switch the miniature circuit breakers.
■ Technical specifications
Auxiliary switches (AS) Fault signal contacts (FC)
5ST3 010, 5ST3 010-2 5ST3 013 5ST3 020, 5ST3 020-2
5ST3 011, 5ST3 011-2 5ST3 014 5ST3 021, 5ST3 021-2
5ST3 012, 5ST3 012-2 5ST3 015 5ST3 022, 5ST3 022-2
Standards EN 62019; IEC/EN 60947-5-1; UL 1077; CSA C22.2 No. 235
Approvals See annex, chapter 20
Short-circuit protection Miniature circuit breaker or gG 6 A fuse
Contact load
• Min. 50 mA, 24 V 1 mA/5 V DC 50 mA, 24 V
• Max. -- 50 mA/30 V DC --
• 400 V AC, AC-14, NO A 2 -- 2
• 230 V AC, AC-14, NO A 6 -- 6
• 400 V AC, AC-13, NC A 2 -- 2
• 230 V AC, AC-13, NC A 6 -- 6
• 220 V DC, DC-13, NO+NC A 1 -- 1
• 110 V DC, DC-13, NO+NC A 1 -- 1
• 60 V DC, DC-13, NO+NC A 3 -- 3
• 24 V DC, DC-13, NO+NC A 6 -- 6
Service life, on average, with rated load 20000 actuations 20000 actuations 20000 actuations
Conductor cross-sections mm2 0.5 ... 2.5 0.5 ... 2.5 0.5 ... 2.5
AWG 22 ... 14 22 ... 14 22 ... 14
Terminals
• Terminal tightening torque Nm 0.5 0.5 0.5
lb/in 4.5 4.5 4.5
Additional components
1)
1 MW (modular width) = 18 mm.
Additional components
3
Rated residual Rated current Mount- DT Order No. Price PU PS*/ PG Weight
current ing per PU (UNIT, P. unit per PU
width SET, approx.
M)
IΔn In
mA A MW1) kg
RC units, type A, instantaneous tripping
For 5SY miniature circuit breakers,
not suitable for use with 5SY5, 5SY8, 5SY6 0..
and 5SL,
2P, 230 ... 400 V AC, 50 ... 60 Hz
10 0.3 ... 16 2 B 5SM2 121-6 1 1 unit 007 0.207
30 0.3 ... 40 } 5SM2 322-6 1 1 unit 007 0.209
300 A 5SM2 622-6 1 1 unit 007 0.199
30 0.3 ... 63 A 5SM2 325-6 1 1 unit 007 0.215
100 B 5SM2 425-6 1 1 unit 007 0.211
300 B 5SM2 625-6 1 1 unit 007 0.203
500 B 5SM2 725-6 1 1 unit 007 0.198
For 5SY miniature circuit breakers,
not suitable for use with 5SY5, 5SY8, 5SY6 0..
and 5SL,
3P, 230 ... 400 V AC, 50 ... 60 Hz
30 0.3 ... 40 3 A 5SM2 332-6 1 1 unit 007 0.314
300 A 5SM2 632-6 1 1 unit 007 0.295
30 0.3 ... 63 B 5SM2 335-6 1 1 unit 007 0.359
100 B 5SM2 435-6 1 1 unit 007 0.327
300 B 5SM2 635-6 1 1 unit 007 0.298
500 B 5SM2 735-6 1 1 unit 007 0.322
For 5SY miniature circuit breakers,
not suitable for use with 5SY5, 5SY8, 5SY6 0..
and 5SL,
4P, 230 ... 400 V AC, 50 ... 60 Hz
30 0.3 ... 40 3 } 5SM2 342-6 1 1 unit 007 0.337
300 } 5SM2 642-6 1 1 unit 007 0.326
30 0.3 ... 63 A 5SM2 345-6 1 1 unit 007 0.397
100 B 5SM2 445-6 1 1 unit 007 0.357
300 A 5SM2 645-6 1 1 unit 007 0.328
500 A 5SM2 745-6 1 1 unit 007 0.326
1)
1 MW (modular width) = 18 mm.
Additional components
3
Rated residual Rated current Mount- DT Order No. Price PU PS*/ PG Weight
current ing per PU (UNIT, P. unit per PU
width SET, approx.
IΔn In M)
mA A MW1) kg
RC units, type A, super resistant æ
For 5SY miniature circuit breakers,
not suitable for use with 5SY5, 5SY8, 5SY6 0..
and 5SL,
2P, 230 ... 400 V AC, 50 ... 60 Hz
30 0.3 ... 40 2 B 5SM2 322-6KK01 1 1 unit 007 0.215
30 0.3 ... 63 B 5SM2 325-6KK01 1 1 unit 007 0.214
1)
1 MW (modular width) = 18 mm.
Additional components
3
Version Mount- DT Order No. Price PU PS*/ PG Weight
ing per PU (UNIT, P. unit per PU
width SET, approx.
MW1) M) kg
Terminal covers
For miniature circuit breakers, not suitable for
use with 5SY6 0. .,
For additional covering of the screw openings B 5ST3 800 1 10 units 027 0.002
per pole, sealable. In the case of 5SY, also
prevents removal of device from the standard
mounting rail.
For 5SL miniature circuit breakers A 5ST3 806 1 5 units 027 0.007
For padlock with 3 ... 6 mm shackle
Padlocks
For 5ST3 801 and 5ST3 806 handle locking devices } 5ST3 802 1 1 unit 027 0.031
Locking devices
For 5SP and 5SY miniature circuit breakers B 5ST3 803 1 1 set 027 0.041
comprising 5ST3 801 handle locking device
and 5ST3 802 padlock
Locking devices
For 5SL miniature circuit breakers, N A 5ST3 807 1 1 set 027 0.034
comprising 5ST3 806 handle locking device
and 5ST3 802 padlock
Spacers
Can be placed on either side of the standard 0.5 } 5TG8 240 1 2 units 027 0.010
mounting rail. Two spacers allow for conve-
nient cable routing
Fixing parts
Made of plastic, for use on a mounting plate B 5ST2 201 1 1 unit 027 0.013
Inscription labels
15 mm x 9 mm, 3 frames à 44 labels, can be B 5ST2 173 1 1 set 027 0.049
mounted on casing collar, white, self-adhesive
Labeling system
Inscription on self-adhesive labels for a uniform and tidy appearance in electrical power distribution.
The labeling program can be downloaded to your PC free of charge at:
www.siemens.com/labeling-tool
Recommended ELAT-3-747 labels for printing out on Brady GmbH
normal printers can be ordered at: Otto-Hahn-Str. 5-7
D-63222 Langen
Tel: +49 (0) 61 03/75 98-660
* You can order this quantity or a multiple thereof.
3/34 Siemens LV 10.1 · 2011
© Siemens AG 2010
Additional components
3
Version DT Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
SET, approx.
M)
kg
Terminal covers, gray
For surface mounting, degree of protection IP40,
sealable, with 35 mm standard mounting rail
• Up to 2.5 MW B 5SW3 004 1 1 unit 008 0.091
• Up to 4.5 MW B 5SW3 005 1 1 unit 008 0.171
Covers
Can be assembled as mini distribution board,
suitable for all devices, cover parts prepared for rail
mounting of conventional label caps, comprising:
• End plates (for snapping onto standard mounting } 5ST2 134 1 10 units 027 0.021
rail)
• Angled profile (approx. 1 m long) A 5ST2 135 1 5 units 027 0.288
• Alternative flat profiles B 5ST2 136 1 5 units 027 0.239
(as a cover between the rows of devices length
approx. 1 m)
Holders for front panel installation
Universal application for devices from 1 to 6 MW
Cutout dimensions:
Height 45+0.5 mm
Width: 23, 41, 59, 77, 95 or 113 mm B 7LF9 006 1 1 unit 027 0.070
Additional components
■ More information
3 The Siemens mounting concept supports the combination of all The chart shows which additional components can be mounted
5ST3 additional components with miniature circuit breakers of on either the right or the left.
the 5SY and 5SP series and RCBOs of the 5SU1 series.
5SL and 5SY6 0.. miniature circuit breakers are suitable for
mounting auxiliary switches and fault signal contacts. Auxiliary
switches can also be mounted on 5TE8 flush-mounting circuit
breakers and 5SG7 1 MINIZED switch disconnectors.
or or or
I2_18123a
RC-Unit MCB RC AS FC AS AS AS FC
FC FC FC AS
5SU1
or or or
RCBO RC ST AS FC AS AS AS FC
FC FC FC AS
For further information on the mounting concept for RCBOs, please refer to the chapter, "Residual Current Protective Devices".
■ Overview
The busbar system with pin-type connections can be used for all Any free pins on the busbars can be made safe by covering with
3
5SL6 and 5SJ6 . . .-.KS miniature circuit breakers and 5SY min- touch protection.
iature circuit breakers with or without mounted auxiliary switch
(AS) or fault signal contact (FC). For further information on bus-mounting miniature circuit break-
ers with residual current operated circuit breakers, please refer
Busbars in 10 mm2 and 16 mm2 versions are available. to the chapter "Residual current protective devices".
The 5ST3 7 busbar system with bars that can be cut to length
can be tailored to any requirements.
The extremely flexible 5ST3 6 busbar system with fixed lengths
also enables installation in any length as the busbars can be
overlapped.
No further need for time-consuming tasks, such as cutting, cut-
ting to length, deburring, cleaning of cut surfaces and mounting
of end caps.
■ Benefits
• Between the devices, the busbar, located at the bottom and • The ability to overlap the busbar mounting enables a cross-
behind the conductor, provides an optimum wiring space with section enlargement of up to 32 mm2 using the respective
easy view of the inserted conductor. This enables easy control components, 10 mm2 and 16 mm2.
of connections.
• By overlapping the busbars with fixed lengths, it is possible to • The fact that the connection of the conductor is always clearly
achieve device combinations with any number of devices. visible facilitates control and insertion of conductors of all pole
types and considerably reduces mounting times.
■ Technical specifications
3 5ST3
Standards EN 60439-1 (VDE 0660-500): 2005-01
Busbar material SF-Cu F 24
Partition material Plastic, Cycoloy 3600
heat-resistant over 90 °C
flame-retardant and
self-extinguishing,
dioxin and halogen-free
Rated operational voltage Uc V AC 400
Rated current In
• Cross-section 10 mm2 A 63
• Cross-section 16 mm2 A 80
Rated impulse withstand voltage Uimp kV 4
Test pulse voltage (1.2/50) kV 6.2
Rated conditional short-circuit current Icc kA 25
Resistance to climate
• Constant atmosphere Acc. to DIN 50015 23/83; 40/92; 55/20
• Humid heat Acc. to IEC 60068-2-30 28 cycles
Insulation coordination
• Overvoltage category III
• Pollution degree 2
Maximum busbar current IS/phase
• Infeed at the start of the busbar
- Cross-section 10 mm2 A 63
- Cross-section 16 mm2 A 80
• Infeed at the center of the busbar
- Cross-section 10 mm2 A 100
- Cross-section 16 mm2 A 130
Infeed at the start or end of the busbar Infeed along the busbar or midpoint infeed
3 2 1 1 2 3
I201_13755 I201_13754a
S S S
The sum of the output current per branch (1, 2, 3 ... n) must not be greater
than the max. busbar current IS/phase.
Three-phase
For 2 MCBs 3P 1 102 A 5ST3 613 1 10 units 027 0.030
For 3 MCBs 3P 157.5 A 5ST3 614 1 10 units 027 0.056
For 4 MCBs 3P 210 } 5ST3 615 1 10 units 027 0.075
Three-phase,
for MCBs with AS or FC
For 2 MCBs 3P 1+1+1.5 115 A 5ST3 616 1 10 units 027 0.038
For 4 MCBs 3P 237 A 5ST3 617 1 10 units 027 0.090
For 6 MCBs 1P 1.5 125 A 5ST3 618 1 10 units 027 0.046
For 9 MCBs 1P 229 A 5ST3 620 1 10 units 027 0.075
Three-phase
For 1 RCCB 4P N right
and 8 MCBs 1P 1 210 A 5ST3 624 1 10 units 027 0.077
For 1 RCCB 4P N left
and 8 MCBs 1P 1 192 A 5ST3 667 1 10 units 027 0.061
4-phase
For 2 MCBs 4P or 3P+N 1 145 A 5ST3 621 1 10 units 027 0.055
For 3 MCBs 4P or 3P+N 215 A 5ST3 622 1 10 units 027 0.093
For 6 MCBs 2P or 1P+N 215 A 5ST3 623 1 10 units 027 0.087
5ST3 6 busbars, 16 mm2,
for MCBs, fixed lengths,
cannot be cut, fully insulated
Single-phase
For 2 MCBs 1P 1 33 A 5ST3 630 1 10 units 027 0.007
For 6 MCBs 1P 105 A 5ST3 631 1 10 units 027 0.025
For 12 MCBs 1P 210 A 5ST3 632 1 10 units 027 0.048
Single-phase,
for MCBs with AS or FC
For 2 MCBs 1P 1.5 40 A 5ST3 633 1 10 units 027 0.010
For 6 MCBs 1P 156.5 A 5ST3 634 1 10 units 027 0.029
For 9 MCBs 1P 237 A 5ST3 635 1 10 units 027 0.052
2-phase
For 2 MCBs 2P 1 75.5 A 5ST3 636 1 10 units 027 0.012
For 3 MCBs 2P 105 A 5ST3 637 1 10 units 027 0.037
For 6 MCBs 2P 210 A 5ST3 638 1 10 units 027 0.089
2-phase,
for MCBs with AS or FC
For 2 MCBs 2P 1 + 1.5 75.5 A 5ST3 640 1 10 units 027 0.024
For 3 MCBs 2P 120.5 A 5ST3 641 1 10 units 027 0.048
For 5 MCBs 2P 210 A 5ST3 642 1 10 units 027 0.081
1) 1 MW (modular width) = 18 mm.
3
Pin Length DT Order No. Price PU PS*/ PG Weight
spacing per PU (UNIT, P. unit per PU
SET, approx.
M)
MW1) mm kg
2
5ST3 6 busbars, 16 mm ,
for MCBs, fixed lengths,
cannot be cut, fully insulated
Three-phase
For 2 MCBs 3P 1 102.5 A 5ST3 643 1 10 units 027 0.047
For 3 MCBs 3P 157.5 A 5ST3 644 1 10 units 027 0.085
For 4 MCBs 3P 210 } 5ST3 645 1 10 units 027 0.119
Three-phase,
for MCBs with AS or FC
For 2 MCBs 3P 1+1+1.5 115 A 5ST3 646 1 10 units 027 0.052
For 4 MCBs 3P 237 A 5ST3 647 1 10 units 027 0.126
For 6 MCBs 1P 1.5 156 A 5ST3 648 1 10 units 027 0.067
For 9 MCBs 1P 245 A 5ST3 650 1 10 units 027 0.110
Three-phase,
For 1 RCCB 4P N right
and 8 MCBs 1P 1 210 A 5ST3 654 1 10 units 027 0.108
For 1 RCCB 4P N left
and 8 MCBs 1P 1 210 A 5ST3 668 1 10 units 027 0.099
4-phase
For 2 MCBs 4P or 3P+N 1 A 5ST3 651 1 10 units 027 0.071
For 3 MCBs 4P or 3P+N A 5ST3 652 1 10 units 027 0.130
For 6 MCBs 2P or 1P+N A 5ST3 653 1 10 units 027 0.118
Touch protection
For free connections, yellow (RAL 1004) A 5ST3 655 1 10 units 027 0.003
5 x 1 pin
Range
10 mm2
20 × 5ST3 613 + 10 × 5ST3 614 + A 5ST3 656 1 1 set 027 5.460
50 × 5ST3 615 + 50 × 5ST3 655
16 mm2
20 × 5ST3 643 + 10 × 5ST3 644 + A 5ST3 657 1 1 set 027 7.650
50 × 5ST3 645 + 50 × 5ST3 655
5ST3 7 busbar systems, 10 mm2 12 MW,
for MCBs,
can be cut, with end caps
Single-phase, angled
For 12 MCBs 1P 1 214 A 5ST3 730 1 1 unit 027 0.032
For 9 MCBs 1P with AS or FC 1.5 A 5ST3 732 1 1 unit 027 0.034
2-phase
For 6 MCBs 2P 1 A 5ST3 734 1 1 unit 027 0.070
For 4 MCBs 2P with AS or FC 1+1.5 A 5ST3 736 1 1 unit 027 0.072
Three-phase
For 4 MCBs 3P 1 } 5ST3 738 1 1 unit 027 0.084
for 3 MCBs 3P with AS or FC 1+1+1.5 A 5ST3 741 1 1 unit 027 0.078
For 3 MCBs 1P with AS or FC 1.5 A 5ST3 743 1 1 unit 027 0.075
4-phase
For 3 MCBs 4P or 3P+N 1 A 5ST3 745 1 1 unit 027 0.119
5ST3 7 busbar systems, 10 mm2 56 MW,
for MCBs,
can be cut, without end caps
Single-phase, angled
For MCBs 1P 1 1016 A 5ST3 731 1 1 unit 027 0.153
For MCBs 1P with AS or FC 1.5 A 5ST3 733 1 1 unit 027 0.157
2-phase
For MCBs 2P 1 A 5ST3 735 1 1 unit 027 0.343
For MCBs 2P with AS or FC 1+1.5 A 5ST3 737 1 1 unit 027 0.327
Three-phase
For MCBs 3P 1 } 5ST3 740 1 1 unit 027 0.440
For MCBs 3P with AS or FC 1+1+1.5 A 5ST3 742 1 1 unit 027 0.421
For MCBs 1P with AS or FC 1.5 A 5ST3 744 1 1 unit 027 0.420
4-phase
For MCBs 4P or 3P+N 1 A 5ST3 746 1 1 unit 027 0.600
1)
1 MW (modular width) = 18 mm.
3
Pin Length DT Order No. Price PU PS*/ PG Weight
spacing per PU (UNIT, P. unit per PU
SET, approx.
M)
MW1) mm kg
2
5ST3 7 busbar systems, 16 mm 12 MW,
for MCBs,
can be cut, with end caps
Single-phase, angled
For MCBs 1P 1 214 } 5ST3 700 1 1 unit 027 0.039
For MCBs 1P with AS or FC 1.5 A 5ST3 702 1 1 unit 027 0.040
2-phase
For MCBs 2P 1 } 5ST3 704 1 1 unit 027 0.092
For MCBs 2P with AS or FC 1+1.5 A 5ST3 706 1 1 unit 027 0.090
Three-phase
For MCBs 3P 1 } 5ST3 708 1 1 unit 027 0.116
For MCBs 3P with AS or FC 1+1+1.5 A 5ST3 711 1 1 unit 027 0.098
For MCBs 1P with AS or FC 1.5 A 5ST3 713 1 1 unit 027 0.098
4-phase
For MCBs 4P or 3P+N 1 A 5ST3 715 1 1 unit 027 0.142
5ST3 7 busbar systems, 16 mm2 56 MW,
for MCBs,
can be cut, without end caps
Single-phase, angled
For MCBs 1P 1 1016 } 5ST3 701 1 1 unit 027 0.196
For MCBs 1P with AS or FC 1.5 } 5ST3 703 1 1 unit 027 0.185
2-phase
For MCBs 2P 1 } 5ST3 705 1 1 unit 027 0.452
For MCBs 2P with AS or FC 1+1.5 } 5ST3 707 1 1 unit 027 0.446
Three-phase
For MCBs 3P 1 } 5ST3 710 1 1 unit 027 0.610
For MCBs 3P with AS or FC 1+1+1.5 } 5ST3 712 1 1 unit 027 0.580
For MCBs 1P with AS or FC 1.5 } 5ST3 714 1 1 unit 027 0.540
4-phase
For MCBs 4P or 3P+N 1 } 5ST3 716 1 1 unit 027 0.798
5ST3 7 busbar systems, 10 mm2 56 MW
can be cut, with end caps, with touch protection
4-phase
For MCBs 2P and RCBOs 1P+N 1 1008 A 5ST3 770-2 1 10 units 027 0.400
5ST3 7 busbar systems, 16 mm2 56 MW
can be cut, with end caps, with touch protection
4-phase
For MCBs 2P and RCBOs 1P+N 1 1008 A 5ST3 770-3 1 10 units 027 0.550
5ST3 7 busbar systems, 10 mm2 16 MW
can be cut, with end caps, with touch protection
4-phase
For 6 MCBs 1P+N and 1 288 A 5ST3 770-4 1 10 units 027 0.100
RCCBs 4P, N connection, right
5ST3 7 busbar systems, 16 mm2 16 MW
can be cut, with end caps, with touch protection
4-phase
For 6 MCBs 1P+N and 1 288 A 5ST3 770-5 1 10 units 027 0.160
RCCBs 4P, N connection, right
End caps for 5ST3 7, can be cut
For single-phase busbars A 5ST3 748 1 10 units 027 0.001
For two-phase and three-phase busbars } 5ST3 750 1 10 units 027 0.001
For 4-phase busbars A 5ST3 718 1 10 units 027 0.001
3
Pin Length DT Order No. Price PU PS*/ PG Weight
spacing per PU (UNIT, P. unit per PU
SET, approx.
M)
MW1) mm kg
2
5ST3 7 busbar systems, 10 mm 12 MW,
for MCBs 1+N in 1 MW of the compact range,
can be cut, with end caps
Single-phase
For 12 MCBs 1+N, gray 1 216 A 5ST3 762 1 10 units 027 0.022
For 12 MCBs 1+N, blue 1 A 5ST3 763 1 10 units 027 0.001
Single-phase
For MCBs 1+N, gray 1 1016 A 5ST3 764 1 10 units 027 0.134
For MCBs 1+N, blue 1 A 5ST3 765 1 10 units 027 0.134
1)
1 MW (modular width) = 18 mm.
■ Overview
Products according to UL standards are used in North America, The busbars are available in single-, two- and three-phase ver-
3
but also in several other countries. This is important in particular sion with different pin spacings and with two cross-sections
for exporting machines or electrical switchgear and equipment 18 mm² and 25 mm². Infeed can be directly into the terminals of
to the USA. Acceptance and delivery are possible only if the rel- the miniature circuit breaker or through connection terminals.
evant UL standards are satisfied.
The connection terminals are available in two versions – for di-
The 5ST3 7 busbar system according to UL 508 and CSA is suit- rect infeed at the busbar or for infeed directly at the miniature cir-
able for both universal use worldwide with all 5SY and 5SP min- cuit breaker/fuse holder. Pins that are not required can be cov-
iature circuit breakers for Supplementary Protection certified ac- ered with touch protection covers.
cording to UL 1077 and for 3NW and 3NC fuse holders certified
according to UL 512.
■ Benefits
• Bus-mounting with infeed through a connection terminal di- • Infeed directly on the miniature circuit breaker up to a cross-
rectly on the miniature circuit breaker up to a conductor cross- section of 35 mm² and connection terminal for connection
section of 35 mm² directly on the busbar up to a conductor cross-section of
50 mm²
• Suitable for universal use according to both IEC and UL stan-
dards
• Can be used for 5SY, 5SP miniature circuit breakers and for
Class CC, cylindrical and SITOR fuse holders
• UL-tested combination – device and busbar
• Different cross-sections 18 mm² and 25 mm².
■ Technical specifications
3 5ST3 7. .-0HG 5ST3 7. .-2HG 5ST3 770-0HG 5ST3 770-1HG
Standards UL 508, CSA C22.2 No. 14-M 95
Approvals UL 508 File No. E328403
CSA
Operational voltage
• Acc. to IEC V AC 690
• Acc. to UL 508 V AC 600
Rated conditional short-circuit current kA 10
• Dielectric strength kV/mm 25
• Surge strength kV > 9.5
Rated current A -- -- 115
Maximum busbar current IS/phase
• Infeed at the start of the busbar A 80 100 -- --
• Infeed at the center of the busbar A 160 200 -- --
Insulation coordination
• Overvoltage category III
• Pollution degree 2
2
Busbar cross-section mm Cu 18 25 -- --
Infeed Any
Conductor cross-sections AWG -- -- 10 ... 1/0 14 ... 1
mm2 -- -- 6 ... 35 6 ... 50
Terminals
• Terminal tightening torque Nm -- -- 5 3.5
lbs/in -- -- 50 35
Infeed at the start or end of the busbar Infeed along the busbar or midpoint infeed
3 2 1 1 2 3
I201_13755 I201_13754a
S S S
The sum of the output current per branch (1, 2, 3 ... n) must not be greater
than the max. busbar current IS/phase.
Infeed to busbar
• 50 mm2 A 5ST3 770-1HG 1 10 units 012 0.035
■ Overview
3 UL standards are used in North America as well as in several The key difference between the three device series is their appli-
other countries. This is of particular importance to European ex- cation in different power supply systems.
porters of electrical switchgear equipment for machines who ex- • 5SJ4 …-.HG40: 240/120 V AC, 1-pole, "same polarity only",
port to the USA, as their products will only be accepted if they • 5SJ4 …-.HG41: 240 V AC, 1-, 2- and 3-pole,
meet the relevant UL standards. • 5SJ4 …-.HG42: 480Y/277 V AC, 1-, 2- and 3-pole.
A wide range of low-voltage circuit protection devices from The terminals are suitable for "field wiring". This means that the
Siemens comply with UL standards and are therefore suitable for devices can be installed not only in factory-finished distribution
implementation worldwide in both IEC/EN and UL applications boards and control cabinets, but also on-site in a customer sys-
within the framework of their specified use. tem.
Miniature circuit breakers certified to UL 489 permit use as an Using this mounting concept, all additional 5ST3 . . .-.HG com-
all-round solution for protection tasks in distribution boards, con- ponents can be combined with miniature circuit breakers of the
trol cabinets and control systems to UL 508A as "branch protec- 5SJ4 …-.HG range. The auxiliary switch (AS) signals the contact
tors". In particular, they are also approved for the protection of position. In the event of a fault, the fault signal contact (FC) sig-
electrical circuits in heating, ventilating and cooling systems nals the automatic tripping of the MCB as well as the contact po-
(HVAC), as well as for DC applications up to 60 V/125 V. sition. Shunt trips (ST) are used for the remote tripping of minia-
This covers a wide range of protection tasks, in residential and ture circuit breakers. Captive metal brackets on the additional
non-residential buildings, as well as in industry. The tripping components ensure fast mounting on the devices.
characteristics B, C and D to EN/IEC 60898-1 have been Single-, two- and three-phase busbars in 3 lengths with 6, 12 or
adapted so that they fall in the permissible tripping range ac- 18 pins are available as accessories for all device series. The in-
cording to UL 489, as well as for applications at 25 °C and 40 °C. feed is via connection terminals, which are available in two ver-
This means that the devices are approved for use according to sions, for direct infeed at either the busbar or the miniature cir-
both standards. The enclosure dimensions of the devices corre- cuit breakers. Pins that are not required can be covered with
spond to DIN format. This means that the device series are suit- touch protection covers.
able for universal use worldwide according to IEC or UL stan-
dards.
■ Benefits
• Can be used globally for all applications in residential, non-
residential and industrial buildings. This facilitates the plan-
ning of plants and enhances export opportunities
• The devices can be used according to IEC/EN 60898-1 and
UL 489, which means these devices can be installed any-
where in the world
• Miniature circuit breakers with 480Y/277 V up to 40 A, with
240/120 V and 240 V up to 63 A
• Can be used for both AC voltage and DC voltage up to 125 V
• Rated switching capacity up to 14 kA in acc with UL 489 and
up to 15 kA in acc. with IEC 60947-2
• Fast mounting with busbars up to 115 A and feeder terminals
up to 50 mm2.
• Bus mounting with central infeed directly on the busbar up to • Accessories: Auxiliary switches, fault signal contacts and
conductor cross-section of 50 mm2 shunt trips up to 480 V can be easily mounted onto the minia-
ture circuit breaker.
■ Technical specifications
5SJ4 . . .-.HG40 5SJ4 . . .-.HG41 5SJ4 . . .-.HG42
3
Standards EN 60898-1; EN 60947-2; UL 489; UL-File E243414; CSA C22.2 No. 5-02
Approvals See annex, chapter 20
Tripping characteristic B, C, D C, D
Operational voltage Min. V AC/DC 24
• Acc. to IEC 60898-1 Max. V DC/pole 60
Max. V AC 250/440
• Acc. to UL 489 and CSA C22.2 No.5-02 Max. V AC 240/120 240 480Y/277
DC V/1P 60 60 60
DC V/2P -- 125 125
Rated breaking capacity
• Icn acc. to IEC 60898-1 kA AC 10
• Icu acc. to IEC 60947-2 kA AC 15
• Acc. to UL 489 and CSA C22.2 No.5-02 kA AC 14/101) 14/101) 101)
Insulation coordination
• Rated insulation voltage V AC 250 250/440
• Pollution degree for overvoltage category 3/III
Touch protection according to EN 50274 Yes
Handle end position, sealable Yes
Degree of protection to EN 60529 IP20, with connected conductors
CFC and silicone-free Yes
Mounting On standard mounting rail
Terminals
• Combined terminals at both ends Yes
• Terminal tightening torque, only for Cu, 60/75 °C Nm 3.5
lb. in 31
Conductor cross-sections
• Solid and stranded, acc. to UL489 and CSA C22.2 No.5-02 AWG 14 ... 4
• Solid and stranded, according to IEC 60898-1 mm2 0.75 ... 35
• Finely stranded, with end sleeve mm2 0.75 ... 25
Mains connection Any
Mounting position Any
Service life, on average, with rated load 20000 actuations
EMC environment
• Acc. to EN 60947-2 Suitable for environment "B" (immunity to interference not applicable)
Ambient temperature °C -25 ... +45, occasionally +55, max. 95 % humidity,
storage temperature: -40 ... +75
Resistance to climate acc. to IEC 60068-2-30 6 cycles
Resistance to vibrations acc. to IEC 60068-2-6 m/s2 50 at 25 ... 150 Hz and 60 at 35 Hz (4 sec)
1)
For detailed information about the rated switching capacity, see engineering manual at: www.siemens.com/lowvoltage/manuals.
Additional components Auxiliary switches Fault signal contacts Shunt trips (ST)
(AS) (FC)
5ST3 010-0HG 5ST3 020-0HG 5ST3 030-0HG 5ST3 031-0HG
5ST3 011-0HG 5ST3 021-0HG
5ST3 012-0HG 5ST3 022-0HG
Standards UL 489, UL-File E243414;
CSA 22.2 No. 5-02
IEC/EN 62019, IEC/EN 60947-5-1 IEC/EN 60947-1
Operational voltage/operational current (load)
• Acc. to IEC V AC 400 230 110 ... 415 24 ... 60
A AC 2 6 (NC: AC13, S: AC14) -- --
V DC 220 110 60 24 -- 24 ... 60
A DC 1 1 3 6 (DC13) -- --
• Acc. to UL V AC 480 277 240 120 110 ... 480 24 ... 60
A AC 1.5 3 4 6 -- --
V DC 125 60 -- 24 ... 60
A DC 1 3 -- --
Short-circuit protection Miniature circuit breaker or 6 A fuse
Minimum contact load 50 mA, 24 V
Tripping operations -- -- max. 2000
Service life, on average, with rated load 12000 actuations
Primary operating range x Un -- 0.7 ... 1.1
Conductor cross-sections AWG 22 ... 14 22 ... 14
mm2 0.5 ... 2.5 0.5 ... 2.5
Terminals
• Terminal tightening torque Nm 0.5 0.8
lb/in 4.5 6.8
3
Version Busbars Terminals
Type 5ST3 663-.HG 5ST3 666-0HG 5ST3 666-2HG
5ST3 664-.HG
5ST3 665-.HG
Standards UL 489;
UL File No. E243414
Operational voltage
• Acc. to IEC V AC 690
• Acc. to UL 489 V AC 480Y/277 and 240
Rated conditional short-circuit current kA 15 (with NH3 355A gL/gG 500 V)
• Dielectric strength kV/mm 30
• Surge strength kV > 9.5
Rated current at 40 °C ambient temperature A 115
Insulation coordination
• Pollution degree 2
• Overvoltage category III
Busbar cross-section (Cu) mm2 16
Infeed Any
Conductor cross-sections
• AWG cables AWG -- 14 ... 2 14 ... 1
• Solid and stranded mm2 -- 1.5 ... 35 1.5 ... 50
Terminals
• Terminal tightening torque Nm -- 3.3 3.3
lb. in -- 30 30
Temperature resistance °C 200 – UL 94-V0/0.4 mm
3
Characteristic C Characteristic D
In Mount- DT Order No. Price PG DT Order No. Price PU PS*/ PG Weight
ing per PU per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW1) kg
MCBs
"same polarity only"
1P, 240 V AC
0.3 1 C 5SJ4 114-7HG40 012 C 5SJ4 114-8HG40 1 1 unit 012 0.152
0.5 C 5SJ4 105-7HG40 012 C 5SJ4 105-8HG40 1 1 unit 012 0.152
1 B 5SJ4 101-7HG40 012 C 5SJ4 101-8HG40 1 1 unit 012 0.156
1.6 C 5SJ4 115-7HG40 012 C 5SJ4 115-8HG40 1 1 unit 012 0.151
2 B 5SJ4 102-7HG40 012 C 5SJ4 102-8HG40 1 1 unit 012 0.151
3 B 5SJ4 103-7HG40 012 C 5SJ4 103-8HG40 1 1 unit 012 0.139
4 B 5SJ4 104-7HG40 012 C 5SJ4 104-8HG40 1 1 unit 012 0.153
5 C 5SJ4 111-7HG40 012 C 5SJ4 111-8HG40 1 1 unit 012 0.150
6 B 5SJ4 106-7HG40 012 C 5SJ4 106-8HG40 1 1 unit 012 0.150
8 B 5SJ4 108-7HG40 012 C 5SJ4 108-8HG40 1 1 unit 012 0.152
10 B 5SJ4 110-7HG40 012 C 5SJ4 110-8HG40 1 1 unit 012 0.151
13 C 5SJ4 113-7HG40 012 C 5SJ4 113-8HG40 1 1 unit 012 0.147
15 C 5SJ4 118-7HG40 012 C 5SJ4 118-8HG40 1 1 unit 012 0.153
16 B 5SJ4 116-7HG40 012 C 5SJ4 116-8HG40 1 1 unit 012 0.152
20 B 5SJ4 120-7HG40 012 C 5SJ4 120-8HG40 1 1 unit 012 0.152
25 B 5SJ4 125-7HG40 012 C 5SJ4 125-8HG40 1 1 unit 012 0.152
30 C 5SJ4 130-7HG40 012 C 5SJ4 130-8HG40 1 1 unit 012 0.158
32 C 5SJ4 132-7HG40 012 C 5SJ4 132-8HG40 1 1 unit 012 0.156
35 C 5SJ4 135-7HG40 012 C 5SJ4 135-8HG40 1 1 unit 012 0.161
40 C 5SJ4 140-7HG40 012 C 5SJ4 140-8HG40 1 1 unit 012 0.156
45 C 5SJ4 145-7HG40 012 C 5SJ4 145-8HG40 1 1 unit 012 0.159
50 C 5SJ4 150-7HG40 012 C 5SJ4 150-8HG40 1 1 unit 012 0.159
60 C 5SJ4 160-7HG40 012 C 5SJ4 160-8HG40 1 1 unit 012 0.157
63 C 5SJ4 163-7HG40 012 C 5SJ4 163-8HG40 1 1 unit 012 0.157
MCBs
1P, 240 V AC
0.3 1 C 5SJ4 114-7HG41 012 C 5SJ4 114-8HG41 1 1 unit 012 0.155
0.5 C 5SJ4 105-7HG41 012 C 5SJ4 105-8HG41 1 1 unit 012 0.155
1 C 5SJ4 101-7HG41 012 C 5SJ4 101-8HG41 1 1 unit 012 0.175
1.6 C 5SJ4 115-7HG41 012 C 5SJ4 115-8HG41 1 1 unit 012 0.155
2 C 5SJ4 102-7HG41 012 C 5SJ4 102-8HG41 1 1 unit 012 0.168
3 C 5SJ4 103-7HG41 012 C 5SJ4 103-8HG41 1 1 unit 012 0.171
4 C 5SJ4 104-7HG41 012 C 5SJ4 104-8HG41 1 1 unit 012 0.170
5 C 5SJ4 111-7HG41 012 C 5SJ4 111-8HG41 1 1 unit 012 0.155
6 C 5SJ4 106-7HG41 012 C 5SJ4 106-8HG41 1 1 unit 012 0.169
8 C 5SJ4 108-7HG41 012 C 5SJ4 108-8HG41 1 1 unit 012 0.172
10 C 5SJ4 110-7HG41 012 C 5SJ4 110-8HG41 1 1 unit 012 0.173
13 C 5SJ4 113-7HG41 012 C 5SJ4 113-8HG41 1 1 unit 012 0.172
15 C 5SJ4 118-7HG41 012 C 5SJ4 118-8HG41 1 1 unit 012 0.155
16 C 5SJ4 116-7HG41 012 C 5SJ4 116-8HG41 1 1 unit 012 0.172
20 C 5SJ4 120-7HG41 012 C 5SJ4 120-8HG41 1 1 unit 012 0.171
25 C 5SJ4 125-7HG41 012 C 5SJ4 125-8HG41 1 1 unit 012 0.172
30 C 5SJ4 130-7HG41 012 C 5SJ4 130-8HG41 1 1 unit 012 0.155
32 C 5SJ4 132-7HG41 012 C 5SJ4 132-8HG41 1 1 unit 012 0.155
35 C 5SJ4 135-7HG41 012 C 5SJ4 135-8HG41 1 1 unit 012 0.155
40 C 5SJ4 140-7HG41 012 C 5SJ4 140-8HG41 1 1 unit 012 0.175
45 C 5SJ4 145-7HG41 012 C 5SJ4 145-8HG41 1 1 unit 012 0.155
50 C 5SJ4 150-7HG41 012 C 5SJ4 150-8HG41 1 1 unit 012 0.155
60 C 5SJ4 160-7HG41 012 C 5SJ4 160-8HG41 1 1 unit 012 0.155
63 C 5SJ4 163-7HG41 012 C 5SJ4 163-8HG41 1 1 unit 012 0.155
1)
1 MW (modular width) = 18 mm.
3
Characteristic C Characteristic D
In Mount- DT Order No. Price PG DT Order No. Price PU PS*/ PG Weight
ing per PU per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW1) kg
MCBs
2P, 240 V AC
0.3 2 C 5SJ4 214-7HG41 012 C 5SJ4 214-8HG41 1 1 unit 012 0.310
0.5 C 5SJ4 205-7HG41 012 C 5SJ4 205-8HG41 1 1 unit 012 0.341
1 C 5SJ4 201-7HG41 012 C 5SJ4 201-8HG41 1 1 unit 012 0.337
1.6 C 5SJ4 215-7HG41 012 C 5SJ4 215-8HG41 1 1 unit 012 0.332
2 C 5SJ4 202-7HG41 012 C 5SJ4 202-8HG41 1 1 unit 012 0.332
3 C 5SJ4 203-7HG41 012 C 5SJ4 203-8HG41 1 1 unit 012 0.329
4 C 5SJ4 204-7HG41 012 C 5SJ4 204-8HG41 1 1 unit 012 0.329
5 C 5SJ4 211-7HG41 012 C 5SJ4 211-8HG41 1 1 unit 012 0.310
6 C 5SJ4 206-7HG41 012 C 5SJ4 206-8HG41 1 1 unit 012 0.335
8 C 5SJ4 208-7HG41 012 C 5SJ4 208-8HG41 1 1 unit 012 0.337
10 C 5SJ4 210-7HG41 012 C 5SJ4 210-8HG41 1 1 unit 012 0.332
13 C 5SJ4 213-7HG41 012 C 5SJ4 213-8HG41 1 1 unit 012 0.332
15 C 5SJ4 218-7HG41 012 C 5SJ4 218-8HG41 1 1 unit 012 0.310
16 C 5SJ4 216-7HG41 012 C 5SJ4 216-8HG41 1 1 unit 012 0.335
20 C 5SJ4 220-7HG41 012 C 5SJ4 220-8HG41 1 1 unit 012 0.334
25 C 5SJ4 225-7HG41 012 C 5SJ4 225-8HG41 1 1 unit 012 0.333
30 C 5SJ4 230-7HG41 012 C 5SJ4 230-8HG41 1 1 unit 012 0.336
32 C 5SJ4 232-7HG41 012 C 5SJ4 232-8HG41 1 1 unit 012 0.342
35 C 5SJ4 235-7HG41 012 C 5SJ4 235-8HG41 1 1 unit 012 0.310
40 C 5SJ4 240-7HG41 012 C 5SJ4 240-8HG41 1 1 unit 012 0.343
45 C 5SJ4 245-7HG41 012 C 5SJ4 245-8HG41 1 1 unit 012 0.310
50 C 5SJ4 250-7HG41 012 C 5SJ4 250-8HG41 1 1 unit 012 0.343
60 C 5SJ4 260-7HG41 012 C 5SJ4 260-8HG41 1 1 unit 012 0.310
63 C 5SJ4 263-7HG41 012 C 5SJ4 263-8HG41 1 1 unit 012 0.310
MCBs
3P, 240 V AC
0.3 3 C 5SJ4 314-7HG41 012 C 5SJ4 314-8HG41 1 1 unit 012 0.465
0.5 C 5SJ4 305-7HG41 012 C 5SJ4 305-8HG41 1 1 unit 012 0.465
1 C 5SJ4 301-7HG41 012 C 5SJ4 301-8HG41 1 1 unit 012 0.465
1.6 C 5SJ4 315-7HG41 012 C 5SJ4 315-8HG41 1 1 unit 012 0.465
2 C 5SJ4 302-7HG41 012 C 5SJ4 302-8HG41 1 1 unit 012 0.488
3 C 5SJ4 303-7HG41 012 C 5SJ4 303-8HG41 1 1 unit 012 0.486
4 C 5SJ4 304-7HG41 012 C 5SJ4 304-8HG41 1 1 unit 012 0.484
5 C 5SJ4 311-7HG41 012 C 5SJ4 311-8HG41 1 1 unit 012 0.465
6 C 5SJ4 306-7HG41 012 C 5SJ4 306-8HG41 1 1 unit 012 0.489
8 C 5SJ4 308-7HG41 012 C 5SJ4 308-8HG41 1 1 unit 012 0.498
10 C 5SJ4 310-7HG41 012 C 5SJ4 310-8HG41 1 1 unit 012 0.492
13 C 5SJ4 313-7HG41 012 C 5SJ4 313-8HG41 1 1 unit 012 0.494
15 C 5SJ4 318-7HG41 012 C 5SJ4 318-8HG41 1 1 unit 012 0.499
16 C 5SJ4 316-7HG41 012 C 5SJ4 316-8HG41 1 1 unit 012 0.506
20 C 5SJ4 320-7HG41 012 C 5SJ4 320-8HG41 1 1 unit 012 0.495
25 C 5SJ4 325-7HG41 012 C 5SJ4 325-8HG41 1 1 unit 012 0.494
30 C 5SJ4 330-7HG41 012 C 5SJ4 330-8HG41 1 1 unit 012 0.504
32 C 5SJ4 332-7HG41 012 C 5SJ4 332-8HG41 1 1 unit 012 0.504
35 C 5SJ4 335-7HG41 012 C 5SJ4 335-8HG41 1 1 unit 012 0.465
40 C 5SJ4 340-7HG41 012 C 5SJ4 340-8HG41 1 1 unit 012 0.505
45 C 5SJ4 345-7HG41 012 C 5SJ4 345-8HG41 1 1 unit 012 0.465
50 C 5SJ4 350-7HG41 012 C 5SJ4 350-8HG41 1 1 unit 012 0.499
60 C 5SJ4 360-7HG41 012 C 5SJ4 360-8HG41 1 1 unit 012 0.465
63 C 5SJ4 363-7HG41 012 C 5SJ4 363-8HG41 1 1 unit 012 0.465
1)
1 MW (modular width) = 18 mm.
3
Characteristic C Characteristic D
In Mount- DT Order No. Price PG DT Order No. Price PU PS*/ PG Weight
ing per PU per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW1) kg
MCBs
1P,
480Y/277 V AC
0.3 1 C 5SJ4 114-7HG42 012 C 5SJ4 114-8HG42 1 1 unit 012 0.155
0.5 C 5SJ4 105-7HG42 012 C 5SJ4 105-8HG42 1 1 unit 012 0.155
1 C 5SJ4 101-7HG42 012 C 5SJ4 101-8HG42 1 1 unit 012 0.155
1.6 C 5SJ4 115-7HG42 012 C 5SJ4 115-8HG42 1 1 unit 012 0.155
2 C 5SJ4 102-7HG42 012 C 5SJ4 102-8HG42 1 1 unit 012 0.155
3 C 5SJ4 103-7HG42 012 C 5SJ4 103-8HG42 1 1 unit 012 0.155
4 C 5SJ4 104-7HG42 012 C 5SJ4 104-8HG42 1 1 unit 012 0.155
5 C 5SJ4 111-7HG42 012 C 5SJ4 111-8HG42 1 1 unit 012 0.155
6 C 5SJ4 106-7HG42 012 C 5SJ4 106-8HG42 1 1 unit 012 0.155
8 C 5SJ4 108-7HG42 012 C 5SJ4 108-8HG42 1 1 unit 012 0.155
10 C 5SJ4 110-7HG42 012 C 5SJ4 110-8HG42 1 1 unit 012 0.155
13 C 5SJ4 113-7HG42 012 C 5SJ4 113-8HG42 1 1 unit 012 0.155
15 C 5SJ4 118-7HG42 012 C 5SJ4 118-8HG42 1 1 unit 012 0.155
16 C 5SJ4 116-7HG42 012 C 5SJ4 116-8HG42 1 1 unit 012 0.155
20 C 5SJ4 120-7HG42 012 C 5SJ4 120-8HG42 1 1 unit 012 0.155
25 C 5SJ4 125-7HG42 012 C 5SJ4 125-8HG42 1 1 unit 012 0.155
30 C 5SJ4 130-7HG42 012 C 5SJ4 130-8HG42 1 1 unit 012 0.155
32 C 5SJ4 132-7HG42 012 C 5SJ4 132-8HG42 1 1 unit 012 0.155
35 C 5SJ4 135-7HG42 012 -- 1 1 unit 0.155
40 C 5SJ4 140-7HG42 012 -- 1 1 unit 0.155
MCBs
2P,
480Y/277 V AC
0.3 2 C 5SJ4 214-7HG42 012 C 5SJ4 214-8HG42 1 1 unit 012 0.310
0.5 C 5SJ4 205-7HG42 012 C 5SJ4 205-8HG42 1 1 unit 012 0.310
1 C 5SJ4 201-7HG42 012 C 5SJ4 201-8HG42 1 1 unit 012 0.310
1.6 C 5SJ4 215-7HG42 012 C 5SJ4 215-8HG42 1 1 unit 012 0.310
2 C 5SJ4 202-7HG42 012 C 5SJ4 202-8HG42 1 1 unit 012 0.310
3 C 5SJ4 203-7HG42 012 C 5SJ4 203-8HG42 1 1 unit 012 0.310
4 C 5SJ4 204-7HG42 012 C 5SJ4 204-8HG42 1 1 unit 012 0.310
5 C 5SJ4 211-7HG42 012 C 5SJ4 211-8HG42 1 1 unit 012 0.310
6 C 5SJ4 206-7HG42 012 C 5SJ4 206-8HG42 1 1 unit 012 0.310
8 C 5SJ4 208-7HG42 012 C 5SJ4 208-8HG42 1 1 unit 012 0.310
10 C 5SJ4 210-7HG42 012 C 5SJ4 210-8HG42 1 1 unit 012 0.310
13 C 5SJ4 213-7HG42 012 C 5SJ4 213-8HG42 1 1 unit 012 0.310
15 C 5SJ4 218-7HG42 012 C 5SJ4 218-8HG42 1 1 unit 012 0.310
16 C 5SJ4 216-7HG42 012 C 5SJ4 216-8HG42 1 1 unit 012 0.310
20 C 5SJ4 220-7HG42 012 C 5SJ4 220-8HG42 1 1 unit 012 0.310
25 C 5SJ4 225-7HG42 012 C 5SJ4 225-8HG42 1 1 unit 012 0.310
30 C 5SJ4 230-7HG42 012 C 5SJ4 230-8HG42 1 1 unit 012 0.310
32 C 5SJ4 232-7HG42 012 C 5SJ4 232-8HG42 1 1 unit 012 0.310
35 C 5SJ4 235-7HG42 012 -- 1 1 unit 0.310
40 C 5SJ4 240-7HG42 012 -- 1 1 unit 0.310
1)
1 MW (modular width) = 18 mm.
3
Characteristic C Characteristic D
In Mount- DT Order No. Price PG DT Order No. Price PU PS*/ PG Weight
ing per PU per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW1) kg
MCBs
3P,
480Y/277 V AC
0.3 3 C 5SJ4 314-7HG42 012 C 5SJ4 314-8HG42 1 1 unit 012 0.465
0.5 C 5SJ4 305-7HG42 012 C 5SJ4 305-8HG42 1 1 unit 012 0.465
1 C 5SJ4 301-7HG42 012 C 5SJ4 301-8HG42 1 1 unit 012 0.465
1.6 C 5SJ4 315-7HG42 012 C 5SJ4 315-8HG42 1 1 unit 012 0.465
2 C 5SJ4 302-7HG42 012 C 5SJ4 302-8HG42 1 1 unit 012 0.465
3 C 5SJ4 303-7HG42 012 C 5SJ4 303-8HG42 1 1 unit 012 0.465
4 C 5SJ4 304-7HG42 012 C 5SJ4 304-8HG42 1 1 unit 012 0.465
5 C 5SJ4 311-7HG42 012 C 5SJ4 311-8HG42 1 1 unit 012 0.465
6 C 5SJ4 306-7HG42 012 C 5SJ4 306-8HG42 1 1 unit 012 0.465
8 C 5SJ4 308-7HG42 012 C 5SJ4 308-8HG42 1 1 unit 012 0.465
10 C 5SJ4 310-7HG42 012 C 5SJ4 310-8HG42 1 1 unit 012 0.465
13 C 5SJ4 313-7HG42 012 C 5SJ4 313-8HG42 1 1 unit 012 0.465
15 C 5SJ4 318-7HG42 012 C 5SJ4 318-8HG42 1 1 unit 012 0.465
16 C 5SJ4 316-7HG42 012 C 5SJ4 316-8HG42 1 1 unit 012 0.465
20 C 5SJ4 320-7HG42 012 C 5SJ4 320-8HG42 1 1 unit 012 0.465
25 C 5SJ4 325-7HG42 012 C 5SJ4 325-8HG42 1 1 unit 012 0.465
30 C 5SJ4 330-7HG42 012 C 5SJ4 330-8HG42 1 1 unit 012 0.465
32 C 5SJ4 332-7HG42 012 C 5SJ4 332-8HG42 1 1 unit 012 0.465
35 C 5SJ4 335-7HG42 012 -- 1 1 unit 0.465
40 C 5SJ4 340-7HG42 012 -- 1 1 unit 0.465
■ Accessories
Pin spacing Length DT Order No. Price PU PS*/ PG Weight
3
per PU (UNIT, P. unit per PU
SET, approx.
M)
MW1) mm kg
Busbars according to UL 489
specially for 5SJ4 ... -.HG.. MCBs,
fixed length, cannot be cut2)
UL-File E321559
Single-phase
For 6 MCBs 1P 1 100 A 5ST3 663-0HG 1 10 units 012 0.056
For 12 MCBs 1P 205 A 5ST3 663-1HG 1 10 units 012 0.112
For 18 MCBs 1P 310 A 5ST3 663-2HG 1 10 units 012 0.170
2-phase
For 3 MCBs 2P 1 100 A 5ST3 664-0HG 1 10 units 012 0.065
For 6 MCBs 2P 205 A 5ST3 664-1HG 1 10 units 012 0.137
For 9 MCBs 2P 310 A 5ST3 664-2HG 1 10 units 012 0.211
Three-phase
For 2 MCBs 3P 1 100 A 5ST3 665-0HG 1 10 units 012 0.067
For 4 MCBs 3P 205 A 5ST3 665-1HG 1 10 units 012 0.155
For 6 MCBs 3P 310 A 5ST3 665-2HG 1 10 units 012 0.243
Terminals according to UL 489
specially for 5SJ4 ... -.HG.. MCBs
Infeed at the miniature circuit breaker
Max. 35 mm2 A 5ST3 666-0HG 1 10 units 012 0.033
Handle locking devices according to UL, A 5ST3 801 1 1 unit 027 0.012
UL-File E321559
Can be sealed against unwanted manual ON/OFF switch-
ing, padlock with max. 3 mm shackle
1)
1 MW (modular width) = 18 mm.
2)
All unassigned pins of the busbar must be covered with 5ST3 666-1HG
touch protection covers.
■ More information
3 Mounting concept for mounting 5ST3 0. .-0HG accessories on
5SJ4 . . .-.HG miniature circuit breakers
The diagram shows which additional components can be
mounted on the right.
5SJ4 ...-.HG.. or or or
AS FC AS AS AS FC
FC FC FC AS
I2_18121
CB
or or or
ST AS FC AS AS AS FC
FC FC FC AS
Max. 1 shunt trip (ST) can be mounted on the right of the
miniature circuit breaker (CB). 2 auxiliary switches (AS)
or fault signal contacts (FC) can also be mounted to the
right of the ST in any combination
■ Overview ■ Benefits
Selective main miniature circuit breakers are used as circuit • Quick and easy installation due to direct bus-mounting 3
breakers at meter panels and provide an optimum solution. • Space saving field installation due to reduced mounting width
Characteristic E is adapted to the special application require- • Tool-free connection of meter cable
ments for cascade circuits between melting fuses and miniature • Reliable and high selectivity
circuit breakers in distributor circuits.
• Optimum availability of customer system
An integrated adapter enables quick and easy mounting of the
• Voltage-independent operation of selective main miniature cir-
devices on 40-mm busbars. The reduced width of 1.5 MW cre-
cuit breakers
ates lots of additional space in the meter cabinet.
The screwless outgoing terminal provides optimum user-friend- • Practical locking options
liness. • Excellent current limitation characteristics increase plant pro-
Used in conjunction with the downstream miniature circuit tection, thanks to the selective main miniature circuit breakers
breaker, selective main miniature circuit breakers ensure effec- supporting downstream miniature circuit breakers.
tive protection and optimum availability of the system. • High and safe selectivity between sub-distribution and meter
panel ensures the continued supply of the unaffected circuits
in the event of a fault, thus improving plant availability
• The selective main miniature circuit breaker prevents the
affected circuit from being reconnected until the fault is elimi-
nated. Greater safety during operation
• No previous knowledge required for operation of the selective
main miniature circuit breakers. This ensures fast and safe dis-
connection and reconnection of loads.
• Complies with all the requirements of TAB 2007.
■ Technical specifications
5SP3 7. ., 5SP3 7. .-1 5SP3 7. .-2, 5SP3 8. .-2
5SP3 7. .-2KK0.
Standards DIN VDE 0645 E DIN VDE 0641-21
Rated voltage Un
• 1-pole V AC 230/400 --
• 3 x 1-pole V AC 400 -- 400
Operational voltage Min. V AC 110
Max. V AC 440
Rated frequency Hz 50 ... 60
Rated current In A 16 ... 100 16 ... 63
Rated insulation voltage Ui V AC 690
Rated switching capacity Icn A 25000
Insulation coordination
• Overvoltage category IV
• Pollution degree 3
Surge strength Uimp kV 6
Impact resistance 30 g, at least 3 impacts, impact duration 11 ms
Resistance to vibrations 2 g, 20 frequency cycles 5 ... 150 ... 15 Hz
Switching position indication OFF = green, ON = red
Main conductor characteristics Acc. to EN 60204-1 Yes
Handle end position, sealable Yes
Cutoff ON/OFF -- Locking slide with lock, additional wire seal, cable
ties and Antilux
Device depth mm 92
Degree of protection IP20, with connected conductors
Mains connection Any
Mounting position Any
Mounting On standard mounting rail Direct tool-free mounting on the busbar system
or interface adapter
Service life, on average, with rated load Actuations 20000
Conductor connections Saddle terminals at both
ends
• Top Screwless spring terminal for flexible cables,
in particular for meter connecting cables acc. to
DIN 43870-3
• Bottom Box terminal, also for infeed of the busbar system,
up to 100 A input terminal current
3
5SP3 7. ., 5SP3 7. .-1 5SP3 7. .-2, 5SP3 8. .-2
5SP3 7. .-2KK0.
Conductor cross-sections
• Top and bottom, solid and stranded mm2 2.5 ... 70 --
• Top and bottom, finely stranded mm2 2.5 ... 50 --
• Top, finely stranded mm2 -- 2.5 ... 16
2
• Bottom, solid, stranded and finely stranded, with end sleeve mm -- 2.5 ... 50
Storage temperature °C -40 ... +70
Ambient temperature °C -25 ... +55
3
In Mount- DT Order No. Price PU PS*/ PG Weight
ing per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW1) kg
Main miniature circuit breakers, 1P
For mounting on standard mounting rail, busbar (spacing:
40 mm, with 5ST1 busbar adapter), or for screw fixing
16 2 C 5SP3 716 1 1 unit 005 0.474
20 C 5SP3 720 1 1 unit 005 0.461
25 C 5SP3 725 1 1 unit 005 0.497
32 C 5SP3 732 1 1 unit 005 0.465
35 C 5SP3 735 1 1 unit 005 0.497
40 C 5SP3 740 1 1 unit 005 0.461
50 C 5SP3 750 1 1 unit 005 0.501
63 C 5SP3 763 1 1 unit 005 0.517
80 C 5SP3 780 1 1 unit 005 0.512
100 C 5SP3 791 1 1 unit 005 0.487
Main miniature circuit breakers, 3 x 1P
Premounted on 5ST1 324 busbar adapter; can be clipped
onto busbars (spacing: 40 mm); including three 5ST1 323
transparent operating protective covers
80 6 C 5SP3 780-1 1 1 set 005 1.827
100 C 5SP3 791-1 1 1 set 005 1.855
Mounting plates
For mounting on standard mounting rails accord-
ing to EN 50022
For 1 or 2 standard mounting rails, universal appli- } 5ST1 322 1 10 units 005 0.025
cation, tier spacing 125 mm
■ Overview ■ Benefits
3 Circuit breaker terminals are used for short-circuit protection or • Integration of line protection switching function in the terminal
for protection against overloading and short-circuiting in auxil- technology of control cabinets in compact 12 mm design
iary and control circuits after control transformers. All terminals • Display of switching position or the "Tripped" state for the fast
are designed for 2 wires. The terminal block labeling accesso- detection of faults
ries are used for inscription.
• Switching/isolating function facilitates fault locating
• Device versions with integrated auxiliary switch (AS) signal
the contact position
• Device versions with floating through-type connection parallel
to the switching contacts facilitate line connection
These devices are listed as "Supplementary Protectors" accord-
ing to UL 1077 (UL Recognized Components) and CSA 235
(CSA Component Accepted).
■ Technical specifications
5SK9 011-1KK2., 5SK9 011-4KK2.,
5SK9 011-2KK2. 5SK9 011-6KK2.,
5SK9 011-8KK2.
Standards DIN VDE 0660-101, IEC/EN 60947-2, UL 1077
Rated operational voltage Max. AC 250 V at 50/60 Hz
DC 60 V
Operational voltage Min. V AC/DC 24
Power loss Max. W 1
Rated impulse withstand voltage kV 4
Pollution degree Acc. to EN 60664-1 3
Rated current of through-type connection A 16
Rated operational current of auxiliary switch A 1
Mechanical service life Actuations 16000
Electrical service life, on average, with rated load Actuations 8000
Polarity with direct current Any
Mounting position Any
Resistance to vibrations 10 g at ≤ 70 Hz
Enclosures With thermoplastic insulating body
Screw connection at both ends for 2 conductors each
Enclosed on both sides
Touch protection Acc. to EN 50274-1 Yes
Terminal size mm2 1.5 2.5
Terminal tightening torque, recommended Nm 0.8
Conductor cross-sections
• Solid mm2 1 or 2 × (0.75 ... 1.5)
• Finely stranded, with end sleeve mm2 1 or 2 × (1 ... 2.5)
• UAWG 14-12 Yes --
• sAWG 14 Yes --
Stripped length mm 10
Notes
Residual Current
Protective Devices
4/2 Introduction
4/23 Busbars
4/27 Accessories
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical specifications
under Entry List:
- Updates
- Downloads
- FAQ
- Manuals
- Characteristic curves
- Certificates
and at
www.siemens.com/lowvoltage/
configurators
- Configurators
Introduction
■ Overview
Devices Page Field of application Standards Used in
Non-residential
4
Residential
buildings
buildings
Industry
5SM3 RCCBs, type A 4/3 Personnel, material and fire protection, IEC/EN 61008 ✓ ✓ ✓
as well as protection against direct con-
tact. SIGRES with active condensation
protection for use in harsh environ-
ments. Super resistant and selective
versions
SIQUENCE 5SM3 and 5SU1 universal 4/9 SIQUENCE, the technology of universal VDE 0664-100 ✓ -- ✓
current-sensitive RCCBs, type B and current-sensitive residual current pro- VDE 0664-200
type B+ tective devices VDE V 0664-110
5SM2 RC units, type A 4/15 The freely selectable combination of RC IEC/EN 61009 ✓ -- ✓
units with miniature circuit breakers per-
mits the flexible configuration of RCBO
combinations
5SU1 RCBOs, type A 4/18 The ideal protection combination for all IEC/EN 61009 ✓ ✓ ✓
electrical circuits due to the compact
device versions of RCCBs and minia-
ture circuit breakers in a single device
5SM1 and 5SZ9 RCCB socket outlets 4/26 For retrofitting in existing installations VDE 0664 ✓ ✓ ✓
5SV8 residual current monitors Ch. 12 Monitoring of residual currents in elec- IEC 62020 ✓ -- ✓
trical plants with indication if a specified EN 62020
limit value is exceeded.
see chapter: "Monitoring Devices
––> Monitoring Devices for Electrical
Values ––> Residual current monitors"
■ Overview ■ Benefits
RCCBs of type A are used in all systems up to 240/415 V AC. • Instantaneous RCCBs with the N connection on the left-hand
They trip in the event of both sinusoidal AC residual currents and side enable simple bus mounting with standard pin busbars
pulsating DC residual currents. with miniature circuit breakers installed on the right-hand side
RCCBs with a rated residual current of maximum 30 mA are
used for personnel, material and fire protection, as well as for
• Instantaneous RCCBs with the N connection on the right-hand
side can be bus-mounted with miniature circuit breakers using 4
protection against direct contact. RCCBs with a rated residual a special pin busbar
current of 10 mA are primarily used in areas that represent an in- • Instantaneous devices have a surge current withstand capa-
creased risk for personnel. bility with current waveform 8/20 μs of > 1 kA, super resistant
of > 3 kA and selective of > 5 kA. This ensures safe operation
Since DIN VDE 0100-410 came into effect in June 2007, all
socket outlet current circuits up to 20 A must now also be fitted • SIGRES has an extremely long service life due to patented ac-
with residual current protective devices with a rated residual cur- tive condensation protection and the same dimensions for the
rent of max. 30 mA. This also applies to outdoor electrical cir- quick and easy replacement of instantaneous RCCBs already
cuits up to 32 A for the connection of portable equipment. installed
Devices with a rated residual current of maximum 300 mA are • Super resistant devices increase plant availability, as unnec-
used as preventative fire protection in case of insulation faults. essary tripping is prevented in systems with short-time
RCCBs with a rated residual current of 100 mA are primarily glitches
used outside Europe. • Selective RCCBs increase plant availability, as in the event of
a fault, a staggered tripping time enables the selective trip-
SIGRES ping of RCCBs connected in series
SIGRES RCCBs were developed for use in harsh ambient con- • Auxiliary switches or remote controlled mechanisms are also
ditions, such as swimming baths as protection against chlorine available as additional components
and ozone, in the agricultural sector (ammonia), on building • The operating handle and the test button can be locked by
sites and in the chemical industry (nitrogen oxide, sulfur dioxide, means of a handle locking device.
solvents), in the food processing industry (hydrogen sulfide) and
in unheated rooms (dampness). The patented active condensa-
tion protection requires a continuous power supply and bottom Design Selection
infeed if the RCCB is switched off. criterion
By use in ambient conditions in acc. with product standard RCCB RCBO RC unit
EN 61008-1, the operation interval for pressing the test button
can be extended to 1x a year.
Super resistant æ Type B Equipment Circuit,
B+ load current,
Super resistant (short-time delayed) RCCBs meet the maximum AC A residual current
permissible break times for instantaneous devices. However, by
implementing a short-time delay they prevent unnecessary trip-
pings, and thus plant faults, when pulse-shaped leakage cur- Version System, equipment,
rents occur - as is the case when capacitors are switched on. ambient conditions
K S SIGRES 500 V 50- 400 Hz
Selective î
Can be used as upstream group switch for selective tripping Number of poles
contrary to a downstream, instantaneous or super resistant Equipment
RCCB. 1+N 2 3 3+N 4
Note:
Rated residual current I∆n
You will find further information on the subject of residual current protection objective Installation
protective devices in the technology primer "Residual current residual current protection regulation
protective devices", I∆n > 30mA VDE 0100-410
Order No.: E10003-E38-9T-B3011 and in the Additional Trip conditions Fire
-530
Technology Manual under: -7xx
protection limited I∆n protection
www.siemens.com/lowvoltage/manuals. -482
I∆n ≤ 30 mA I∆n ≤ 300 mA VDS 3501
Selection aid for finding the suitable residual current protective device
■ Technical specifications
Instantaneous SIGRES Super resistant Selective
Standards IEC/EN 61008-1 (VDE 0664-10), IEC/EN 61008-2-1 (VDE 0664-11);
IEC/EN 61543 (VDE 0664-30)
4 Approvals
Surge current withstand capability
IEC 61008-1, IEC 61008-2-1; EN 61008-1, EN 61008-2-1
with current waveform 8/20 µs Acc. to DIN VDE 0432-2 kA >1 >3 >5
Minimum operational voltage for test function operation V AC 100
Insulation coordination
• Overvoltage category III
Terminal conductor cross-sections
• For 2 MW At In = 16 A, 25 A, 40 A mm2 1.0 ... 16
At In = 100 A, 125 A mm2 1.5 ... 50 -- -- --
• For 2.5 MW At In = 63 A, 80 A mm2 1.5 ... 25
• For 4 MW At In = 25 A, 40 A, 63 A, 80 A mm2 1.5 ... 25
At In = 125 A mm2 2.5 ... 50 -- -- 2.5 ... 50
Terminal tightening torque
• Up to In 80 A Nm 2.5 ... 3.0
• At In = 100 A, 125 A Nm 3.0 ... 3.5 -- -- 3.0 ... 3.5
Mains connection Top or bottom Bottom Top or bottom
Mounting position Any
Degree of protection Acc. to EN 60529 IP20, if the distribution board is installed, with connected conductors
(VDE 0470-1)
Touch protection Acc. to EN 50274 Finger and back-of-hand safe
(VDE 0660-514)
Service life Test cycle acc. to IEC/EN 61008 Switching > 10000
cycles
Storage temperature °C -40 ... +75
Ambient temperature °C -25 ... +45,
marked with -25
Resistance to climate Acc. to IEC 60068-2-30 28 cycles (55 °C; 95 % rel. air humidity)
CFC and silicone-free Yes
-25
O Residual Current Protective Devices
(Type AC)
■ Applications
• Personnel and fire protection • Un 230/400 V; 50 to 60 Hz; can be used in systems up to:
- IΔn ≤ 30 mA: additional protection in case of direct contact 240/415 V AC
- IΔn ≤ 300 mA: preventative fire protection in the case of • â G type: at least 10 ms trip delayed.
4
ground fault currents High surge current withstand capability: > 3 kA.
• Product standards: ÖVE/ÖNORM EN 61008; ÖVE/ÖNORM E
8601
mA A A MW kg
RCCBs, type AC
instantaneous
2P; 125 ... 230 V AC, 50 ... 60 Hz
30 25 63 2 X 5SM3 312-0LB 1 1 unit 006 0.230
40 X 5SM3 314-0LB 1 1 unit 006 0.230
401) X 5SM3 314-0LA 1 1 unit 006 0.280
100 25 X 5SM3 412-0LB 1 1 unit 006 0.230
40 X 5SM3 414-0LB 1 1 unit 006 0.230
RCCBs, type AC
short-time delayed â
2P; 125 ... 230 V AC, 50 ... 60 Hz
30 401) 63 2 X 5SM3 314-0LA01 1 1 unit 006 0.280
1)
Thermal overload protection according to ÖVE/ÖNORM E 8001 possible
up to rated current of the RCCB.
4
series fuse M)
IΔn In 10 000
mA A A MW kg
RCCBs, type A
Instantaneous
1P+N; 125 ... 230 V AC; 50 ... 60 Hz
N connection, right
10 16 63 2 A 5SM3 111-6 1 1 unit 007 0.251
30 16 63 2 A 5SM3 311-6 1 1 unit 007 0.248
25 } 5SM3 312-6 1 1 unit 007 0.248
40 } 5SM3 314-6 1 1 unit 007 0.247
63 100 2.5 A 5SM3 316-6 1 1 unit 007 0.328
80 B 5SM3 317-6 1 1 unit 007 0.330
Up to 40 A 100 2 B 5SM3 318-6KK 1 1 unit 007 0.272
125 B 5SM3 315-6KK 1 1 unit 007 0.269
100 25 63 2 B 5SM3 412-6 1 1 unit 007 0.240
40 B 5SM3 414-6 1 1 unit 007 0.240
63 100 2.5 B 5SM3 416-6 1 1 unit 007 0.315
80 B 5SM3 417-6 1 1 unit 007 0.324
100 125 2 B 5SM3 418-6KK 1 1 unit 007 0.272
125 B 5SM3 415-6KK 1 1 unit 007 0.273
300 25 63 2 A 5SM3 612-6 1 1 unit 007 0.231
40 A 5SM3 614-6 1 1 unit 007 0.233
63 A and 80 A 63 100 2.5 B 5SM3 616-6 1 1 unit 007 0.299
80 B 5SM3 617-6 1 1 unit 007 0.320
100 125 2 B 5SM3 618-6KK 1 1 unit 007 0.256
125 B 5SM3 615-6KK 1 1 unit 007 0.255
N connection, left
10 16 63 2 B 5SM3 111-6KL 1 1 unit 007 0.280
30 16 63 2 C 5SM3 311-6KL 1 1 unit 007 0.280
25 B 5SM3 312-6KL 1 1 unit 007 0.251
40 B 5SM3 314-6KL 1 1 unit 007 0.249
100 A and 125 A 63 100 2.5 C 5SM3 316-6KL 1 1 unit 007 0.327
100 40 63 2 C 5SM3 414-6KL 1 1 unit 007 0.280
63 100 2.5 C 5SM3 416-6KL 1 1 unit 007 0.310
300 25 63 2 B 5SM3 612-6KL 1 1 unit 007 0.234
40 B 5SM3 614-6KL 1 1 unit 007 0.235
63 100 2.5 B 5SM3 616-6KL 1 1 unit 007 0.313
Rated residual Rated current Max. Mount- DT Order No. Price PU PS*/ PG Weight
current permissible ing per PU (UNIT, P. unit per PU
short-circuit width SET, approx.
series fuse M)
IΔn In 10 000
mA
RCCBs, type A
A A MW kg
4
Instantaneous
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
N connection, left
30 25 100 4 B 5SM3 342-6KL 1 1 unit 007 0.494
40 } 5SM3 344-6KL 1 1 unit 007 0.495
63 B 5SM3 346-6KL 1 1 unit 007 0.527
80 B 5SM3 347-6KL 1 1 unit 007 0.532
300 25 100 4 B 5SM3 642-6KL 1 1 unit 007 0.458
40 B 5SM3 644-6KL 1 1 unit 007 0.463
63 B 5SM3 646-6KL 1 1 unit 007 0.464
80 B 5SM3 647-6KL 1 1 unit 007 0.454
500 63 100 4 A 5SM3 746-6KL 1 1 unit 007 0.460
RCCBs, type A
Instantaneous, special versions
1P+N; 24 ... 125 V AC; 50 ... 60 Hz
30 16 63 2 B 5SM3 311-6KK13 1 1 unit 007 0.248
RCCBs, type A
SIGRES instantaneous
1P+N; 125 ... 230 V AC; 50 ... 60 Hz
30 25 63 2 B 5SM3 312-6KK12 1 1 unit 007 0.248
40 C 5SM3 314-6KK12 1 1 unit 007 0.251
63 100 2.5 B 5SM3 316-6KK12 1 1 unit 007 0.330
80 B 5SM3 317-6KK12 1 1 unit 007 0.331
Rated residual Rated current Max. Mount- DT Order No. Price PU PS*/ PG Weight
current permissible ing per PU (UNIT, P. unit per PU
short-circuit width SET, approx.
series fuse M)
IΔn In 10 000
4 mA
RCCBs, type A
A A MW kg
SIGRES, selective î
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
300 63 100 4 B 5SM3 646-8KK12 1 1 unit 007 0.506
RCCBs, type A
Super resistant æ
1P+N; 125 ... 230 V AC; 50 ... 60 Hz
30 25 63 2 B 5SM3 312-6KK01 1 1 unit 007 0.250
40 B 5SM3 314-6KK01 1 1 unit 007 0.247
63 100 2.5 B 5SM3 316-6KK01 1 1 unit 007 0.329
300 63 100 2.5 B 5SM3 616-6KK01 1 1 unit 007 0.314
RCCBs, type A
Selective î
1P+N; 125 ... 230 V AC; 50 ... 60 Hz
100 63 100 2.5 B 5SM3 416-8 1 1 unit 007 0.325
300 40 63 2 B 5SM3 614-8 1 1 unit 007 0.248
63 100 2.5 A 5SM3 616-8 1 1 unit 007 0.314
80 100 B 5SM3 617-8 1 1 unit 007 0.314
■ Overview ■ Benefits
Frequency converters, medical devices and UPS systems are • Universal current-sensitive residual current protective devices
seeing increasing use in industry. Smooth DC residual currents detect not only AC residual currents and pulsating DC residual
or currents with low residual ripple may occur in the event of currents, but also smooth DC residual currents, thus ensuring
4
faults on these devices. the desired protective function with all types of residual cur-
rent.
Type A residual current protective devices are unable to detect
these smooth DC residual currents. Furthermore, such smooth • With Type B, the tripping characteristic is adapted to the in-
DC residual currents make Type A devices increasingly insensi- crease of leakage currents at higher frequencies in systems
tive to AC residual currents and pulsating DC residual currents. with capacitive impedances and results in increased operat-
If a fault occurs, there is therefore no tripping and the desired ing safety
protective function is no longer assured. • Type B+ versions offer enhanced preventative fire protection
and correspond to the prestandards DIN V VDE V 0664-110
UC-sensitive residual current protective devices of Types B and
and/or DIN V VDE V 0664-210 and VdS Directive 3501
B+ have an additional transformer which is supplied with a con-
trol signal. This enables an evaluation of the change of the trans- • The RCBO is a compact device for up to 125 A. It provides not
former's operating range caused by smooth DC residual cur- only personnel, property and fire protection but also overload
rents, thus ensuring the desired protective function. and short-circuit protection for cables. Wiring and mounting
outlay is reduced as a result
The residual current protective devices of type B are suitable for
use in three-phase current systems before input circuits with rec- • The RCBOs offer external remote tripping over terminals
tifiers. They are not intended for use in DC systems and in net- Y1/Y2. This supports implementation of central OFF circuits.
works with operating frequencies other than 50 Hz or 60 Hz.
The devices in this series are designed as residual current oper-
ated circuit breakers (RCCBs) up to 80 A and as residual current
circuit breakers with integral overcurrent protection (RCBOs) for
100 A or 125 A in Characteristics C or D.
Type B+ residual current protective devices also offer enhanced,
preventative fire protection. In these versions, the tripping value
is limited to a maximum of 420 mA up to 20 kHz.
■ Technical specifications
SIQUENCE, RCCBs SIQUENCE RCBOs
Type B and type B+ Type B and type B+
5SM3 5SU1
Standards IEC/EN 61008-1 (VDE 0664-10); IEC/EN 61009-1 (VDE 0664-20);
VDE 0664-100; VDE 0664-200;
IEC/EN 61543 (VDE 0664-30); IEC/EN 61543 (VDE 0664-30);
IEC 62423 IEC 62423
And in addition for type B+:
DIN V VDE V 0664-110
Versions 1P+N 3P+N 4P
Tripping characteristic -- -- C, D
Surge current withstand capability with
current waveform 8/20 μs
acc. to DIN VDE 0432-2
• Super resistant kA >3 >3 >3
• Selective kA -- >5 >5
Minimum operational voltage for test V AC 150 150 150
function operation
Rated voltages Un V AC 230 400 400, 480
Rated frequency fn Hz 50 ... 60
Rated currents In A 16, 25, 40, 63 25, 40, 63, 80 100, 125
Rated residual currents IΔn mA 30, 300 30, 300, 500 30, 300
Rated switching capacity
• Im A 800 --
• Icn kA -- 10
Insulation coordination
• Overvoltage category III
Conductor cross-sections
• Solid and stranded mm2 1.5 ... 25 6 ... 50
• Finely stranded, with end sleeve mm2 1.5 ... 16 6 ... 35
Terminal tightening torques for all devices Nm 2.5 ... 3.0 3.0 ... 3.5
Mains connection Either top or bottom
Mounting position Any
Degree of protection IP20, if the distribution board is installed, with connected conductors
acc. to EN 60529 (VDE 0470-1)
Touch protection Finger and back-of-hand safe
acc. to EN 50274 (VDE 0660-514)
4 Storage temperature
Ambient temperature
°C
°C
-40 ... +75
-25 ... +45,
-25
marked with
Resistance to climate acc. to IEC 60068-2-30 28 cycles (55 °C; 95 % rel. air humidity)
CFC and silicone-free Yes
2
I t characteristic curves, see Technology Manual under:
www.siemens.com/lowvoltage/manuals.
mA A A MW kg
SIQUENCE RCCBs, type B
Super resistant æ
1P+N; 230 V AC; 50 ... 60 Hz
30 16 100 4 A 5SM3 321-4 1 1 unit 015 0.590
25 A 5SM3 322-4 1 1 unit 015 0.590
40 A 5SM3 324-4 1 1 unit 015 0.588
63 A 5SM3 326-4 1 1 unit 015 0.591
300 16 100 4 A 5SM3 621-4 1 1 unit 015 0.600
25 A 5SM3 622-4 1 1 unit 015 0.600
40 A 5SM3 624-4 1 1 unit 015 0.591
63 A 5SM3 626-4 1 1 unit 015 0.586
Rated Rated current Max. permissible Mount- DT Order No. Price PU PS*/ PG Weight
residual short-circuit ing per PU (UNIT, P. unit per PU
current series fuse width SET, approx.
M)
IΔn In 10 000
mA A
SIQUENCE RCCBs, type B+
A MW kg
4
Super resistant æ
3P+N; 230 ... 400 V AC; 50 ... 60 Hz
30 25 100 4 C 5SM3 342-4KK14 1 1 unit 015 0.600
40 C 5SM3 344-4KK14 1 1 unit 015 0.600
63 C 5SM3 346-4KK14 1 1 unit 015 0.600
80 C 5SM3 347-4KK14 1 1 unit 015 0.600
300 25 100 4 C 5SM3 642-4KK14 1 1 unit 015 0.600
40 C 5SM3 644-4KK14 1 1 unit 015 0.600
63 C 5SM3 646-4KK14 1 1 unit 015 0.600
80 C 5SM3 647-4KK14 1 1 unit 015 0.600
Rated Rated current Max. permissible Mount- DT Order No. Price PU PS*/ PG Weight
residual short-circuit ing per PU (UNIT, P. unit per PU
current series fuse width SET, approx.
M)
IΔn In 10 000
4 mA A
SIQUENCE RCBOs, Type B+
A MW kg
Selective î,
rated switching capacity 10 kA
4P; 400 V AC; 50 ... 60 Hz
Characteristic C
300 125 11 C 5SU1 674-7EK82 1 1 unit 017 2.082
Characteristic D
300 100 11 C 5SU1 674-8EK81 1 1 unit 017 2.078
Additional components
■ Overview ■ Benefits
Auxiliary switches (AS) signal the contact position of the • Using captive brackets, the remote-controlled operating
RCCB. mechanism can be attached (or retroffitted) to the right-hand
side of the basic device without the need for tools
Remote controlled mechanisms are used for the remote ON/OFF
switching of RCCBs. They also enable local manual switching.
A blocking function permits maintenance work. A tripped RCCB
• Bus systems, such as instabus KNX, AS-Interface bus or
PROFIBUS, can be integrated in the communication over 4
must be acknowledged prior to switching back on. binary inputs
• The leakage current measurement device enables the sys-
The leakage current measurement device detects the leakage
tematic selection of the rated residual current, thus preventing
currents - like the circuit breaker - thus providing a direct state-
the inadvertent tripping of RCCBs.
ment as to the current loading of the RCCB. It is used to measure
leakage currents up to 300 mA. This requires a voltmeter with an
internal resistance > 1 MΩ/V and a measuring range for AC volt-
ages of Ueff = 1 mV to 2 V. For the fault-free operation of an
RCCB, the measured leakage current should be no greater than
1/3 of the rated residual current.
■ Technical specifications
Auxiliary switches (AS) Auxiliary switches (AS)
5SW3 30. 5SW3 330
Standards IEC/EN 60947-5-1
Approvals DIN VDE 0660-200
Terminals
• Conductor cross-section mm2 0.75 ... 2.5
• Tightening torques Nm 0.6 ... 0.8
Short-circuit protection B6 or C6 or gL/gG 6 A fuse
Min. contact load 50 mA/24 V
Max. contact load
• 230 V AC, AC-12 A 6 5
• 230 V AC, AC-14 A 3.6 --
• 220 V DC, DC-12 A 1 0.5
Additional components
4
M)
MW kg
Auxiliary switches (AS)
for 5SM3 RCCBs up to 80 A
1 NO + 1 NC 0.5 } 5SW3 300 1 1/10 units 008 0.050
2 NC 0.5 C 5SW3 301 1 1/10 units 008 0.049
2 NO 0.5 A 5SW3 302 1 1/10 units 008 0.050
Locking devices
For RCCBs up to 80 A, sealable and lockable
4.5 mm lock hasp diameter B 5SW3 303 1 10 units 008 0.009
Padlocks
For 5SW3 303 locking device } 5ST3 802 1 1 unit 027 0.031
(Type A)
-25 Residual Current Protective Devices
■ Overview ■ Benefits
RC units of type A can be used in all systems up to • Our wide variety of RC unit types and comprehensive range of
240/415 V AC. They trip in the event of both sinusoidal AC fault miniature circuit breakers offer a huge spectrum of combina-
currents and pulsating residual currents. tions for all applications
RCCBs with a rated residual current of maximum 30 mA are
used for personnel, material and fire protection, as well as for
• All devices have surge current withstand capability of more
than 1 kA, thus ensuring safe and reliable operation 4
protection against direct contact. • All additional components for miniature circuit breakers can
be retrofitted on the right-hand side
Devices with a rated residual current of maximum 300 mA are
used as preventative fire protection in case of insulation faults. • All 100 A and 125 A RC units offer external remote tripping
over terminals Y1/Y2. This supports implementation of central
RC units are combined with miniature circuit breakers with char- OFF circuits.
acteristics A, B, C and D, provided that these are available in the
MCB range. The two components are simply plugged together • Both components can be simply plugged into each other and
without the need for any tools. secured with captive metal brackets - no tools required. This
saves considerable time when mounting.
They then form a combination of RCCB and MCB for personnel,
fire and line protection.
Super resistant æ
Super resistant (short-time delayed) RC units satisfy the maxi-
mum permissible break times for instantaneous devices. How-
ever, by implementing a short-time delay they prevent unneces-
sary trippings, and thus plant faults, when pulse-shaped
leakage currents occur - as is the case when capacitors are
switched on.
Selective î
Can be used as upstream group switch for selective tripping
contrary to a downstream, instantaneous or super resistant
RCCB.
The dimensioning of the rated residual current depends on the
size of the plant.
■ Technical specifications
5SM2
Standards IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-2-1 (VDE 0664-21),
IEC/EN 61543 (VDE 0664-30)
Approvals EN 61009-1, EN 61009-2-1; IEC 61009-1, IEC 61009-2-1
Surge current withstand capability
With current waveform 8/20 µs Acc. to DIN VDE 0432-2
• Instantaneous kA >1
• Super resistant kA >3
• Selective kA >5
Minimum operational voltage for test function operation
• Up to In = 63 A, 2 and 3-pole V AC 195
• Up to In = 63 A, 4-pole V AC 100
• At In = 80 ... 100 A V AC 100
Rated voltage Un V AC 230 ... 400
Rated frequency fn Hz 50 ... 60
Rated currents In A 0.3 ... 16; 0.3 ... 40; 0.3 ... 63; 80 ... 100
Rated residual currents IΔn mA 10, 30, 100, 300, 500, 1000
Insulation coordination
• Overvoltage category III
Terminal conductor cross-sections
• Up to In 63 A mm2 1.5 ... 25
• At In = 80 ... 100 A mm2 6.0 ... 50
Terminal tightening torque Nm 2.5 ... 3.0
Mains connection Either top or bottom
Mounting position Any
Degree of protection Acc. to EN 60529 (VDE 0470-1) IP20, if the distribution board is installed, with connected conductors
Touch protection Acc. to EN 50274 (VDE 0660-514) Finger and back-of-hand safe
Service life Test cycle acc. to DIN/EN 61009 > 10 000 switching cycles
Storage temperature °C -40 ... +75
Ambient temperature °C -25 ... +45,
-25
marked with
Resistance to climate Acc. to IEC 60068-2-30 28 cycles (55 °C; 95 % rel. air humidity)
CFC and silicone-free Yes
4 IΔn In M)
mA A MW kg
RC units, type A
Instantaneous
For 5SY miniature circuit breakers,
not suitable for use with 5SY5, 5SY8 and 5SY6 0. .,
2P, 230 ... 400 V AC, 50 ... 60 Hz
10 0.3 ... 16 2 B 5SM2 121-6 1 1 unit 007 0.207
30 0.3 ... 40 } 5SM2 322-6 1 1 unit 007 0.209
300 A 5SM2 622-6 1 1 unit 007 0.199
30 0.3 ... 63 A 5SM2 325-6 1 1 unit 007 0.215
100 B 5SM2 425-6 1 1 unit 007 0.211
300 B 5SM2 625-6 1 1 unit 007 0.203
500 B 5SM2 725-6 1 1 unit 007 0.198
(Type A)
-25 Residual Current Protective Devices
Rated residual Rated current Mount- DT Order No. Price PU PS*/ PG Weight
current ing per PU (UNIT, P. unit per PU
width SET, approx.
IΔn In M)
mA A MW kg
RC units, type A
Super resistant æ 4
For 5SY miniature circuit breakers,
not suitable for use with 5SY5, 5SY8 and 5SY6 0. .,
2P, 230 ... 400 V AC, 50 ... 60 Hz
30 0.3 ... 40 2 B 5SM2 322-6KK01 1 1 unit 007 0.215
30 0.3 ... 63 B 5SM2 325-6KK01 1 1 unit 007 0.214
RC units, type A
Selective î
For 5SY miniature circuit breakers,
not suitable for use with 5SY5, 5SY8 and 5SY6 0. .,
2P, 230 ... 400 V AC, 50 ... 60 Hz
300 0.3 ... 40 2 A 5SM2 622-8 1 1 unit 007 0.210
300 0.3 ... 63 B 5SM2 625-8 1 1 unit 007 0.210
■ Overview
RCBOs are a combination of an RCCB and a miniature circuit In order to implement this protection, we recommend the na-
breaker in a compact design for personnel, fire and line protec- tional use of RCBOs with 30 mA.
tion. For personnel and fire protection, the residual current part
Assignment to each individual branch circuit helps prevent the
4 of the type A trips in the event of sinusoidal AC residual currents
and pulsating DC residual currents. unwanted tripping of fault-free circuits induced by the accumu-
lation of operation-related leakage currents or by transient cur-
RCBOs with a rated residual current of maximum 30 mA are rent pulses during switching operations.
used for personnel, material and fire protection, as well as for
protection against direct contact. RCBOs with a rated residual Additional components of the 5SY miniature circuit breakers can
current of 10 mA are primarily used in areas that represent an in- be mounted at the side and carry out additional functions.
creased risk for personnel and the outdoor installations of resi- For further details on additional components, please refer to the
dential buildings. chapter "Miniature Circuit Breakers".
Devices with a rated residual current of maximum 300 mA are RCBOs comprise one part for fault-current detection and one
used as preventative fire protection in case of insulation faults. part for overcurrent detection. They are equipped with a delayed
The MCB part of the RCBO protects lines against overload and overload/time-dependent thermal release (thermal bimetal) for
short circuits and is available in characteristics B and C. low overcurrents and with an instantaneous electromagnetic re-
lease for higher overload and short-circuit currents.
Since DIN VDE 0100-410 came into effect in June 2007, all
socket outlet current circuits up to 20 A must now also be fitted The special contact materials used guarantee a long service life
with residual current protective devices with a rated residual cur- and offer a high degree of protection against contact welding.
rent of max. 30 mA. This also applies to outdoor electrical cir-
cuits up to 32 A for the connection of portable equipment.
■ Benefits
■ Technical specifications
Up to 40 A 125 A
Standards IEC/EN 61009-1 (VDE 0664-20), IEC/EN 61009-2-1 (VDE 0664-21)
IEC/EN 61543; VDE 0664-30
Approvals
Rated voltages Un V AC
IEC 61009-1, IEC 61009-2-1; EN 61009-1, EN 61009-2-1
125 ... 230 400
4
Rated frequency fn Hz 50 ... 60
Rated currents In A 6, 8, 10, 13, 16, 20, 25, 32, 40 125
Rated residual currents IΔn mA 10, 30, 300 30, 300, 1000
Rated switching capacity kA 6, 10 10
Energy limitation class 3 --
Surge current withstand capability
With current waveform 8/20 µs Acc. to DIN VDE 0432-2
• Instantaneous kA >1
• Super resistant kA >3 --
• Selective kA >5
Minimum voltage for operation of the test equipment V AC 100
Insulation coordination
• Overvoltage category III
Terminal conductor cross-sections
• Solid and stranded mm2 0.75 ... 35 6 ... 50
• Finely stranded with end sleeve mm2 0.75 ... 25 6 ... 35
Terminal tightening torque Nm 2.5 ... 3.0 3.0 ... 3.5
Mains connection Top or bottom
Mounting position Any
Degree of protection Acc. to EN 60529 IP20, if the distribution board is installed, with connected conductors
(VDE 0470-1)
Touch protection Acc. to EN 50274 Finger and back-of-hand safe
(VDE 0660-514)
Service life Test cycle acc. to Switching > 10000
IEC/EN 61009 cycles
Storage temperature °C -40 ... +75
Ambient temperature °C -25 ... +45,
-25
marked with
Resistance to climate Acc. to IEC 60068-2-30 28 cycles (55 °C; 95 % rel. air humidity)
CFC and silicone-free Yes
4 mA A
RCBOs, type AC
MW kg
Instantaneous
1P+N; 230 V AC; 50 ... 60 Hz
10 000
3
RCBOs, type AC
short-time delayed â
2P (1P+N); AC 230 V;
50 ... 60 Hz
10 000
3
RCBOs, type A
RCBOs, type A
Instantaneous
1P+N; 230 V AC; 50 ... 60 Hz
6 000
3
30 125 6.5 B 5SU1 324-6KK82 011 B 5SU1 324-7KK82 1 1 unit 011 1.212
300 125 B 5SU1 624-6KK82 011 B 5SU1 624-7KK82 1 1 unit 011 0.930
4 mA A
RCBOs, type A
MW kg
Super resistant æ
1P+N; 230 V AC; 50 ... 60 Hz
10 000
3
RCBOs, type A
Selective î
2P; 400 V AC; 50 ... 60 Hz
10 000
300 125 6.5 B 5SU1 624-6WK82 011 B 5SU1 624-7WK82 1 1 unit 011 0.930
300 125 11 B 5SU1 644-6WK82 011 B 5SU1 644-7WK82 1 1 unit 011 2.018
5ST3
or or or
AS FC AS AS AS FC
FC FC FC AS
5SU1
or or or
I2_13658b
RCBO RC ST AS FC AS AS AS FC
FC FC FC AS
Busbars
■ Overview
4-pole 5SM3 RCCBs are bus-mounted either together or in com- No further need for time-consuming tasks, such as cutting, cut-
bination with miniature circuit breakers. RCCBs with an N wire ting to length, deburring, cleaning of cut surfaces and mounting
connection on the left-hand side facilitate installation because of end caps.
standard busbars are used, as those used for mounting minia-
ture circuit breakers. Any free pins on the busbars can be made safe by covering with
touch protection.
4
2 2
Busbars in 10 mm and 16 mm versions are available.
If several RCBOs are bus-mounted together, this is implemented
The extremely flexible 5ST3 6 busbar system with fixed lengths with two-phase busbars, which are used as 1+N busbars.
enables installation in any length as the busbars can be over-
lapped.
■ Benefits
• Connection of miniature circuit breakers to 4-pole RCCBs with • Connection of miniature circuit breakers to 4-pole RCCBs with
N connection right and three-phase busbar, using busbar N connection left, with three-phase busbar that can be cut. No
specially designed for this application. No cutting or end caps additional items to be stored and busbars that are always
required. available.
• Connection of 1P+N RCBOs with two-phase busbar. No cut- • Bus-mounting of RCCBs on busbar (3-phase +N) that can be
ting or end caps required. cut. A proven and frequently used application.
Busbars
■ Technical specifications
5ST3, 5ST2
Standards EN 60439-1 (VDE 0660-500): 2005-01
4
Busbar material SF-Cu F 24
Partition material Plastic, Cycoloy 3600
Heat-resistant over 90 °C
flame-retardant and
self-extinguishing,
dioxin and halogen-free
Rated operational voltage Ue V AC 400
Rated current In
• Cross-section 10 mm2 A 63
• Cross-section 16 mm2 A 80
Rated impulse withstand voltage Uimp kV 4
Test pulse voltage (1.2/50) kV 6.2
Rated conditional short-circuit current Icc kA 25
Resistance to climate
• Constant atmosphere Acc. to DIN 50015 23/83; 40/92; 55/20
• Humid heat Acc. to IEC 68-2-30 28 cycles
Insulation coordination Acc. to IEC 664 (VDE 0110-1)
• Overvoltage category III
• Pollution degree 2
Maximum busbar current IS/phase
• Infeed at the start of the busbar
- Cross-section 10 mm2 A 63
- Cross-section 16 mm2 A 80
• Infeed at the center of the busbar
- Cross-section 10 mm2 A 100
- Cross-section 16 mm2 A 130
Infeed at the start or end of the busbar Infeed along the busbar or midpoint infeed
3 2 1 1 2 3
I201_13755 I201_13754a
S S S
The sum of the output current per branch (1, 2, 3 ... n) must not be greater
than the max. busbar current IS/phase.
Busbars
■ Overview
Number of Rated Rated residual
poles current In current IΔn
A mA (Type A)
■ Application
RCCB protective socket outlets • Rated voltage: 230 V AC, 50 Hz to 60 Hz
• Molded-plastic enclosure equipped with RCCB and flush-type • For outdoor connection of gardening equipment and socket
SCHUKO® socket outlet or flush-type SCHUKO® double outlets in workshops or for agricultural purposes
socket outlet • Degree of protection IP21 (5SM1 920-.),
• For electric devices where there is a risk of accidental contact degree of protection IP54 (5SZ9 2.6).
with live parts in the event of damage
Accessories
■ Accessories
Version DT Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
SET, approx.
4
M)
kg
Terminal covers, gray
For surface mounting, degree of protection IP40,
sealable, with 35 mm standard mounting rail
• Up to 2.5 MW B 5SW3 004 1 1 unit 008 0.091
• Up to 4.5 MW B 5SW3 005 1 1 unit 008 0.171
Covers
Can be assembled as mini distribution board, suitable
for all devices, cover parts prepared for rail mounting of
conventional label caps,
comprising:
• End plates (for snapping onto standard mounting rail) } 5ST2 134 1 10 units 027 0.021
• Angled profile (approx. 1 m long) A 5ST2 135 1 5 units 027 0.288
• Alternative flat profiles B 5ST2 136 1 5 units 027 0.239
(as a cover between the rows of devices length
approx. 1 m)
Touch protection
For RCCBs up to 80 A A 5SW3 313 1 1 set 008 0.012
1 set contains 12 units
Fixing parts
Plastic B 5ST2 201 1 1 unit 027 0.013
4 MW
Labeling systems
Inscription on self-adhesive labels for a uniform and tidy appearance in electrical power distribution.
The labeling program can be downloaded to your PC free of charge at:
www.siemens.com/beta
Recommended ELAT-3-747 labels for printing
out on normal printers can be ordered at: Brady GmbH
Otto-Hahn-Str. 5-7
D-63222 Langen
Tel.: +49 (0) 61 03/75 98-660
■ Application
Standards1) Field of application Required IΔn Recommended Siemens residual current
protective devices
[mA] 5SM. 5SM3 5SM3 . . .-6KK12
4 (Type A)
SIQUENCE
(Type B/type B+)
SIGRES
DIN VDE 0100-410 Sockets ≤ 20 A and end current circuits in the outdoor area ≤ 30 ✓ -- --
≤ 32 A
DIN VDE 0100-482 Fire protection for particular risks or safety hazard 30, 300 ✓ ✓ --
DIN VDE 0100-551 Low-voltage generating sets ≤ 30 ✓ -- --
DIN VDE 0100-559 Luminaires and lighting installations, display stands for lights ≤ 30 ✓ -- --
DIN VDE 0100-701 Rooms with baths or showers, socket outlets in zone 3 ≤ 30 ✓ -- --
DIN VDE 0100-702 Swimming pools, zone 1 and 2 ≤ 30 ✓ -- ✓
DIN VDE 0100-704 Construction and demolition site installations, socket outlet ≤ 30 ✓ -- ✓
current circuits (single-phase operation) up to 32 A
and for hand-held equipment ✓ ✓ ✓
DIN VDE 0100-705 Agricultural and general horticultural premises ≤ 500 ✓ -- ✓
Socket outlet current circuits ≤ 30 ✓ -- ✓
DIN VDE 0100-706 Conductive areas with limited freedom of movement ≤ 30 ✓ -- --
DIN VDE 0100-708 Feeding points for caravan parking spaces, camping sites ≤ 30 ✓ -- --
DIN VDE 0100-710 Medical premises, depending on application group 1 or 2 and ≤ 30 or ✓ ✓ --
equipment ≤ 300 ✓ ✓ --
DIN VDE 0100-722 Portable buildings, vehicles, mobile homes for fairgrounds ≤ 500 -- -- ✓
DIN VDE 0100-723 Classrooms with experiment equipment ≤ 30 -- ✓ --
DIN VDE 0100-738 Fountains zone 2, general ≤ 500 ✓ -- ✓
Socket outlets in zone 2 ≤ 30 ✓ -- ✓
Zones 0 and 1 ≤ 30 ✓ -- ✓
DIN VDE 0100-739 Additional protection against direct contact in homes ≤ 30 ✓ -- --
DIN VDE 0118-100 Mining plants ≤ 500 ✓ -- ✓
DIN EN 50178 Fitting of power installations with electronic equipment General requirements ✓ ✓ --
(VDE 0160) for correct selection
when using res. current
protection
DIN VDE 0832-100 Traffic signals
• Class T1 ≤ 300 ✓ -- ✓
• Class U1 ≤ 30 ✓ -- ✓
BG FE Selection and operation of electrical equipment on worksites
BGI 608 General:
• Socket circuits ≤ 32 A ≤ 30 ✓ ✓ ✓
• Socket circuits > 32 A ≤ 500 ✓ ✓ ✓
Frequency-controlled equipment:
• With plug-and-socket device ≤ 32 A ≤ 30 -- ✓ --
• With plug-and-socket device > 32 A ≤ 500 -- ✓ --
Chemical industry and food processing industries 30 (recommended) ✓ ✓ ✓
1)
The standards of the range DIN VDE 0100-4.., -5.., -7.. essentially
correspond to the IEC standards of the range IEC 60364-4, -5, -7;
they have, however, been modified.
Note:
For reasons of basic fire protection, we recommend a maximum
rated residual current of 300 mA for residual current protective
devices.
Fuse Systems
5/2 Introduction
Photovoltaic Fuses
5/63 Cylindrical fuse design N
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical specifications
under Entry List:
- Updates
- Downloads
- FAQ
- Manuals
- Characteristic curves
- Certificates
and at
www.siemens.com/lowvoltage/
configurators
- Configurators
Fuse Systems
Introduction
■ Overview
Devices Page Field of application Standards Used in
Non-residential
Residential
buildings
buildings
Industry
5 NEOZED fuse systems 5/4 MINIZED switch disconnectors, bases, Fuse system:
fuse links from 2 A to 63 A of opera- IEC 60269-3;
✓ ✓ ✓
DIAZED fuse systems 5/12 Fuse links from 2 A to 100 A in various IEC 60269-3; ✓ ✓ ✓
operational classes, base versions with DIN VDE 0635;
classic screw base connections. DIN VDE 0636-3;
A widely used fuse system. CEE 16
Compact fuse holders for motor 5/22 For installing fused loaded motor starter IEC 60947-4 ✓ -- ✓
starter combinations combinations.
Class CC fuse systems 5/25 These comply with American standard Fuse holders: ✓ ✓ ✓
and have UL and SCA approval, for UL 512; CSA 22.2
customers exporting OEM products
and mechanical engineers. Fuse links:
Modern design with touch protection UL 248-4; CSA 22.2
acc. to BGV A3 for use in "branch cir-
cuit protection".
Fuse Systems
Introduction
Non-residential
Residential
buildings
buildings
Industry
LV HRC fuse systems
LV HRC fuse links 5/33 Fuse links from 2 A to 1250 A for selec- IEC 60269-1, -2;
tive line protection and plant protection EN 60269-1;
in non-residential buildings, industry DIN VDE 0636-2
✓ ✓ ✓
5
and power supply companies.
LV HRC sockets and accessories 5/44 Fuse bases for screw or snap-on IEC 60269-1, -2; ✓ ✓ ✓
mounting onto standard mounting rails, EN 60269-1;
available as 1-pole or 3-pole version DIN VDE 0636-2
SITOR, cylindrical fuse design 5/58 Fuse sets, fuse holders – usable as fuse -- -- ✓
switch disconnectors and fuse bases
up to 600/690 V AC and 400/700 V DC
from 1 A to 100 A in the sizes
10 mm × 38 mm, 14 mm × 51 mm and
22 mm × 58 mm.
NEOZED and DIAZED design, 5/61 NEOZED fuse links for 400 V AC and -- -- ✓
SILIZED 250 V DC and DIAZED for 500 V AC
and 500 V DC.
Photovoltaic fuses
Cylindrical fuse design 5/63 Fuses with a rated voltage of IEC 60269-6 (draft) ✓ ✓ ✓
1000 V DC and operational class gPV
for the protection of photovoltaic mod-
ules and their connecting cables.
Fuse Systems
NEOZED Fuse Systems
Introduction
■ Overview
The NEOZED fuse system is primarily used in distribution tech- Due to its small footprint, the MINIZED D01 fuse switch discon-
nology and industrial switchgear assemblies. The system is easy nector is primarily used in control engineering.
to use and is also approved for domestic installation.
The NEOZED fuse bases are the most cost-effective solution for
The MINIZED switch disconnectors are primarily used in switch- the application of NEOZED fuses. All NEOZED bases must be
gear assemblies and control engineering. They are approved for fed from the bottom to ensure that the threaded ring is insulated
switching loads as well as for safe switching in the event of short during removal of the fuse link. The terminals of the NEOZED
circuits. The MINIZED D02 is also suitable for use in the pre- bases are available in different versions and designs to support
5 counter sector in household applications in compliance with the
recommendations of the VDEW according to TAB 2007.
the various installation methods.
■ Benefits
Fuse Systems
NEOZED Fuse Systems
Introduction
■ Technical specifications
NEOZED fuse links
5SE2
Standards IEC 60269-3; DIN VDE 0636-3
Operational class gG
Rated voltage Un V AC 400
V DC 250
5
Rated current In A 2 ... 100
Rated breaking capacity kA AC 50
kA DC 8
Non-interchangeability Using adapter sleeves
Resistance to climate °C Up to 45 at 95 % rel. humidity
Ambient temperature °C -5 ... +40, humidity 90 % at 20
Fuse Systems
NEOZED Fuse Systems
Introduction
■ More information
Fuse bases D01 with terminal version BB Fuse bases D02, with terminal version KS
• Incoming feeders, clamp-type terminal B • Incoming feeders, screw head contact K
• Outgoing feeders, clamp-type terminal B • Outgoing feeders, saddle terminal S
Fuse Systems
NEOZED Fuse Systems
NEOZED fuse links
5
operational class gG
D01 2 Pink } 5SE2 302 1 10 units 016 0.005
4 Brown } 5SE2 304 1 10 units 016 0.013
6 Green } 5SE2 306 1 10/500 units 016 0.009
10 Red } 5SE2 310 1 10/500 units 016 0.007
13 Black A 5SE2 013-2A 1 10 units 016 0.006
16 Gray } 5SE2 316 1 10/500 units 016 0.005
D02 20 Blue } 5SE2 320 1 10 units 016 0.011
25 Yellow } 5SE2 325 1 10 units 016 0.010
32 Black B 5SE2 332 1 10 units 016 0.013
35 Black } 5SE2 335 1 10 units 016 0.011
40 Black B 5SE2 340 1 10 units 016 0.015
50 White } 5SE2 350 1 10 units 016 0.013
63 Copper } 5SE2 363 1 10 units 016 0.015
D03 80 Blue } 5SE2 280 1 10 units 016 0.035
100 Red } 5SE2 300 1 10 units 016 0.042
Fuse Systems
NEOZED Fuse Systems
MINIZED switch disconnectors and
MINIZED fuse switch disconnectors
5 D02 1P
1P+N
63
63
1.5
3
}
B
5SG7 113
5SG7 153
1
1
1 unit
1 unit
016
016
0.141
0.259
2P 63 3 B 5SG7 123 1 1 unit 016 0.276
3P 63 4.5 } 5SG7 133 1 1 unit 016 0.411
3P+N 63 6 B 5SG7 163 1 1 unit 016 0.524
Versions for Austria only,
with permanently fitted adapter sleeves,
incl. fuse set
D02 3P 25 4.5 B 5SG7 133-8BA25 1 1 unit 016 0.450
35 B 5SG7 133-8BA35 1 1 unit 016 0.448
50 B 5SG7 133-8BA50 1 1 unit 016 0.455
Locking caps
In D02 MINIZED switch disconnectors C 5SH5 532 1 1 unit 016 0.012
for applications in the precounter sector
Reducers
For fuse links D01 C 5SH5 527 1 10/100 units 016 0.001
in MINIZED switch disconnectors D02
Fuse Systems
NEOZED Fuse Systems
NEOZED fuse bases and accessories
5
D01 1P 16 -- 1.5 } 5SG1 301 1 3 units 016 0.114
D02 63 -- } 5SG1 701 1 3 units 016 0.116
1) 2)
Covers in parentheses are included in delivery. For terminal versions, see page 5/6.
Covers without parentheses are not included in delivery.
Fuse Systems
NEOZED Fuse Systems
NEOZED fuse bases and accessories
Sizes Num- In Matching Terminals2) Mount- DT Order No. Price PU PS*/ PG Weight
ber of cover ing per PU (UNIT, P. unit per PU
poles width SET, approx.
M)
A MW kg
NEOZED fuse bases made of ceramic1)
For snap-on mounting on standard mounting rails,
without cover
D01 3P 16 A5 BB 4.5 B 5SG5 555 1 2 units 016 0.188
5 D02
D02
63 A11
63 A11
SS
KS
4.5
4.5
B
B
5SG5 655
5SG5 695
1
1
2 units
2 units
016
016
0.260
0.240
NEOZED covers2)
Made of molded plastic, plug-in,
for fuse base made of molded plastic
D01, A1 1.5 C 5SH5 244 1 15 units 016 0.002
D02
Screw-on
D03 A6 2.5 B 5SH5 233 1 20 units 016 0.019
NEOZED caps
Made of molded plastic, plug-in
D01, D02 A8 B 5SH5 235 1 5 units 016 0.021
Screw-on
D03 A9 C 5SH5 234 1 10 units 016 0.065
Fuse Systems
NEOZED Fuse Systems
NEOZED fuse bases and accessories
Sizes For fuse links Identification Mount- DT Order No. Price PU PS*/ PG Weight
color ing per PU (UNIT, P. unit per PU
width SET, approx.
M)
A MW kg
NEOZED screw caps
Molded plastic, with inspection hole
D01 } 5SH4 116 1 10/1000 units 016 0.007
D02 } 5SH4 163 1 10/200 units 016 0.009
Ceramic 5
D01, sealable A 5SH4 316 1 10 units 016 0.017
D02, sealable A 5SH4 363 1 10 units 016 0.022
D03 A 5SH4 100 1 3 units 016 0.074
1)
This spring enables the use of NEOZED fuses in DL fuse bases, e.g. in unrenovated prefabricated buildings.
Fuse Systems
■ Overview
The DIAZED fuse system is one of the oldest fuse systems in the The terminals of the DIAZED bases are available in different ver-
world. It was developed by Siemens as far back as 1906. It is still sions and designs to support the various installation methods.
the standard fuse system in many countries to this day. It is par-
ticularly widely used in the harsh environments of industrial ap- The high-performing EZR bus-mounting system for screw con-
plications. nection is an outstanding feature. The busbars, which are partic-
ularly suited for bus-mounting bases, have a load capacity of up
The series is available with rated voltages from 500 A to 750 V. to 150 A with lateral infeed.
5
All DIAZED bases must be fed from the bottom to ensure an in- DIAZED stands for Diametral gestuftes zweiteiliges Sicherungs-
sulated threaded ring when the fuse link is being removed. Reli- system mit Edisongewinde (diametral two-step fuse system with
able contact of the fuse links is only ensured when used together Edison screw).
with DIAZED screw adapters.
■ Benefits
DIAZED fuse systems are a result of a well-designed modular
system which enables the components to be combined in any
way to meet the various requirements and to facilitate different
4
installation methods.
$ DIAZED base
% DIAZED cover
1 3
& DIAZED cover ring
( DIAZED cap
10
7 ) DIAZED fuse link, DII
* DIAZED fuse link, NDz
5
2 + DIAZED screw adapter
, DIAZED adapter sleeve
9 - DIAZED screw cap
6
. Busbar, oblong hole, single-phase
11 / Terminal, fork-type terminal, non-insulated
8
I201_16013a
■ Technical specifications
5SA, 5SB, 5SC, 5SD
Standards IEC 60269-3; DIN VDE 0635; DIN VDE 0636-3; CEE 16
Operational class Acc. to IEC 60269; DIN VDE 0636 gG
Characteristic Acc. to DIN VDE 0635 Slow and quick
Rated voltage Un V AC 500, 690, 750
V DC 500, 600, 750
Rated current In A 2 ... 100
Rated breaking capacity kA AC 50, 40 at E16
kA DC 8, 1.6 at E16
Mounting position Any, but preferably vertical
Non-interchangeability Using screw adapter or adapter sleeves
Degree of protection Acc. to IEC 60529 IP20, with connected conductors
Resistance to climate °C Up to 45, at 95 % rel. humidity
Ambient temperature °C -5 ... +40, humidity 90 % at 20
Terminal version
B K S R
Size DII DIII NDz DII DIII DIII DIV DII DIII
Conductor cross-sections
• Rigid, min. mm2 1.5 2.5 1.0 1.5 2.5 2.5 10 1.5 1.5
• Rigid, max. mm2 10 25 6 10 25 25 50 35 35
• Flexible, with end sleeve mm2 10 25 6 10 25 25 50 35 35
Tightening torques
• Screw M4 Nm 1.2 --
• Screw M5 Nm 2.0 --
• Screw M6 Nm 2.5 4
• Screw M8 Nm 3.5 --
Fuse Systems
Characteristic: slow
TNDz 500/500 2 Pink E16 B 5SA2 11 1 10 units 016 0.011
4 Brown B 5SA2 21 1 10 units 016 0.020
6 Green B 5SA2 31 1 10 units 016 0.015
10 Red B 5SA2 51 1 10 units 016 0.012
16 Gray B 5SA2 61 1 10 units 016 0.013
20 Blue B 5SA2 71 1 10 units 016 0.014
25 Yellow B 5SA2 81 1 10 units 016 0.030
Characteristic: quick
NDz 500/500 2 Pink E16 B 5SA1 11 1 10 units 016 0.011
4 Brown B 5SA1 21 1 10 units 016 0.011
6 Green B 5SA1 31 1 10 units 016 0.015
10 Red B 5SA1 51 1 10 units 016 0.012
16 Gray B 5SA1 61 1 10 units 016 0.014
20 Blue B 5SA1 71 1 10 units 016 0.014
25 Yellow B 5SA1 81 1 10 units 016 0.016
Fuse Systems
3P
DII 500/500 3 × 25 E27 } 5SF5 068 1 1/36 units 016 0.475
DIII 3 × 63 E33 } 5SF5 268 1 1/44 units 016 0.595
Fuse Systems
Ceramic
DIV 500/500 100 R1¼" C 5SH1 141 1 1 unit 016 0.223
Fuse Systems
5 10
16
C
C
5SH3 06
5SH3 07
1
1
20 units
20 units
016
016
0.003
0.002
Also for 5SF2 30 to 750 V
DII E27 2 } 5SH3 10 1 25/1500 units 016 0.014
4 } 5SH3 11 1 25/1500 units 016 0.009
6 } 5SH3 12 1 25/1500 units 016 0.015
10 } 5SH3 13 1 25/1500 units 016 0.021
16 } 5SH3 14 1 25/1500 units 016 0.008
20 } 5SH3 15 1 25/1500 units 016 0.013
25 } 5SH3 16 1 25/1500 units 016 0.012
Also for 5SF2 30 to 750 V
DIII E33 35 } 5SH3 17 1 25/850 units 016 0.025
50 } 5SH3 18 1 25/850 units 016 0.018
63 } 5SH3 20 1 25/850 units 016 0.019
For DII fuse links in DIII base B 5SH3 02 1 10 units 016 0.012
DIAZED covers
Made of molded plastic
Not for SILIZED fuse links
DII 5 bases = 12 MW E27 } 5SH2 032 1 10/620 units 016 0.016
DIII 4 bases = 12 MW E33 } 5SH2 232 1 10/620 units 016 0.020
DIAZED caps
Made of molded plastic
NDz E16 A 5SH2 01 1 5 units 016 0.044
DII E27 A 5SH2 02 1 5 units 016 0.249
DIII E33 A 5SH2 22 1 5 units 016 0.049
Fuse Systems
5
Made of molded plastic, also for EZR bus-mounting base
DII E27 A 5SH3 401 1 5/60 units 016 0.014
DIII E33 A 5SH3 411 1 5/60 units 016 0.020
■ More information
DIII fuse bases with terminal version BS NDz fuse bases with terminal version KK
• Outgoing feeders (top), saddle terminal S • Outgoing feeders (top), screw head contact K
• Incoming feeders (bottom), clamp-type terminal B • Incoming feeders (bottom), screw head contact K
DIII fuse bases with terminal version BB DII fuse bases with terminal version SS
• Outgoing feeders (top), clamp-type terminal B • Outgoing feeders (top), saddle terminal S
• Incoming feeders (bottom), clamp-type terminal B • Incoming feeders (bottom), saddle terminal S
Fuse Systems
Cylindrical Fuse Systems
Cylindrical fuse sets and
cylindrical fuse holders
■ Overview ■ Benefits
Cylindrical fuses are standard in Europe. There are a range of • Devices with pole number 1P+N are available in a single
different cylindrical fuse links and holders that comply with the modular width. This reduces the footprint by 50 %.
standards IEC 60269-1, -2 and -3, and which are suitable for use • The sliding catch for type ranges 8 x 32 mm and 10 x 38 mm
in industrial applications. In South West Europe they are also enables the removal of individual devices from the assembly.
approved for use in residential buildings.
• Space for a spare fuse in the plug-in module enables the fast
The cylindrical fuse holders are also approved to UL 512. replacement of fuses. This saves time and money and
The cylindrical fuse holders are tested and approved as fuse increases plant availability.
5 disconnectors according to the switching device standard
IEC 60947-3. They are not suitable for switching loads.
• A flashing LED signals that a fuse link has been tripped. This
enables fast detection during runtime.
Cylindrical fuse holders can be supplied with or without signal
detectors. In the case of devices with signal detector, a small
electronic device with LED is located behind an inspection
window in the plug-in module. If the inserted fuse link is tripped,
this is indicated by the LED flashing.
The switching state of the fuse holder can be signaled over a
side-mounted auxiliary switch, which enables the integration of
the fuses in the automation process.
■ Technical specifications
Cylindrical fuse links
3NW6 3.. 3NW6 0.. 3NW6 1.. 3NW6 2.. 3NW8 0.. 3NW8 1.. 3NW8 2..
Sizes mm × mm 8 × 32 10 × 38 14 × 51 22 × 58 10 × 38 14 × 51 22 × 58
Standards IEC 60269-1, -2, -3; NF C 60-200; NF C 63-210, -211; NBN C 63269-2, CEI 32-4, -12
Operational class gG aM
Rated voltages Un V AC 400 or 500
Rated current In A 2 ... 20 2 ... 32 4 ... 50 8 ... 100 0.5 ... 25 2 ... 50 10 ... 100
Rated breaking capacity
• 500 V version kA AC 100
• 400 V version kA AC 20
Mounting position Any, but preferably vertical
Fuse Systems
Cylindrical Fuse Systems
Cylindrical fuse sets and
cylindrical fuse holders
Fuse Systems
Cylindrical Fuse Systems
Cylindrical fuse sets and
cylindrical fuse holders
5
25 B 3NW8 210-1 1 10 units 018 0.040
32 B 3NW8 212-1 1 10 units 018 0.052
40 B 3NW8 217-1 1 10 units 018 0.047
50 B 3NW8 220-1 1 10 units 018 0.049
63 B 3NW8 222-1 1 10 units 018 0.046
80 B 3NW8 224-1 1 10 units 018 0.054
100 400 B 3NW8 230-1 1 10 units 018 0.050
Number of In For fuse links Mount- DT Order No. Price PU PS*/ PG Weight
poles of size ing per PU (UNIT, P. unit per PU
width SET, approx.
M)
A mm × mm MW kg
Cylindrical fuse holders with signal detector
1P
20 8 × 32 1 C 3NW7 314 1 1 unit 018 0.067
32 10 × 38 1 A 3NW7 014 1 1 unit 018 0.066
50 14 × 51 1.5 B 3NW7 112 1 1 unit 018 0.100
100 22 × 58 2 B 3NW7 212 1 1 unit 018 0.150
1P+N
20 8 × 32 1 C 3NW7 354 1 1 unit 018 0.082
32 10 × 38 1 A 3NW7 054 1 1 unit 018 0.080
50 14 × 51 3 B 3NW7 152 1 1 unit 018 0.224
100 22 × 58 4 B 3NW7 252 1 1 unit 018 0.359
2P
20 8 × 32 2 C 3NW7 324 1 1 unit 018 0.135
32 10 × 38 2 A 3NW7 024 1 1 unit 018 0.134
50 14 × 51 3 B 3NW7 122 1 1 unit 018 0.217
100 22 × 58 4 B 3NW7 222 1 1 unit 018 0.328
3P
20 8 × 32 3 C 3NW7 334 1 1 unit 018 0.198
32 10 × 38 3 A 3NW7 034 1 1 unit 018 0.199
50 14 × 51 4.5 B 3NW7 132 1 1 unit 018 0.327
100 22 × 58 6 B 3NW7 232 1 1 unit 018 0.495
3P+N
20 8 × 32 3 C 3NW7 364 1 1 unit 018 0.216
32 10 × 38 3 A 3NW7 064 1 1 unit 018 0.215
50 14 × 51 6 B 3NW7 162 1 1 unit 018 0.444
100 22 × 58 8 B 3NW7 262 1 1 unit 018 0.681
Cylindrical fuse holders without signal detector
1P
20 8 × 32 1 A 3NW7 313 1 1 unit 018 0.066
32 10 × 38 1 } 3NW7 013 1 1/12 018 0.076
units
50 14 × 51 1.5 } 3NW7 111 1 1 unit 018 0.108
100 22 × 58 2 } 3NW7 211 1 1 unit 018 0.165
1P+N
20 8 × 32 1 A 3NW7 353 1 1 unit 018 0.080
32 10 × 38 1 } 3NW7 053 1 1 unit 018 0.078
50 14 × 51 3 B 3NW7 151 1 1 unit 018 0.237
100 22 × 58 4 B 3NW7 251 1 1 unit 018 0.362
2P
20 8 × 32 2 A 3NW7 323 1 1 unit 018 0.133
32 10 × 38 2 } 3NW7 023 1 1/6 units 018 0.132
50 14 × 51 3 } 3NW7 121 1 1 unit 018 0.217
100 22 × 58 4 } 3NW7 221 1 1 unit 018 0.326
Fuse Systems
Cylindrical Fuse Systems
Cylindrical fuse sets and
cylindrical fuse holders
Number of In For fuse links Mount- DT Order No. Price PU PS*/ PG Weight
poles of size ing per PU (UNIT, P. unit per PU
width SET, approx.
M)
A mm × mm MW kg
Cylindrical fuse holders without signal detector
3P
20 8 × 32 3 A 3NW7 333 1 1 unit 018 0.194
32 10 × 38 3 } 3NW7 033 1 1/4 units 018 0.194
50
100
14 × 51
22 × 58
4.5
6
}
}
3NW7 131
3NW7 231
1
1
1 unit
1 unit
018
018
0.324
0.488 5
3P+N
20 8 × 32 3 A 3NW7 363 1 1 unit 018 0.208
32 10 × 38 3 } 3NW7 063 1 1 unit 018 0.205
50 14 × 51 6 A 3NW7 161 1 1 unit 018 0.452
100 22 × 58 8 A 3NW7 261 1 1 unit 018 0.685
Auxiliary switches
For indicating disconnection of the fuse link, solely for
application of striker fuse links.
For retrofitting using the factory-fitted brackets.
Contact: 250 V AC, 5 A,
Minimum contact load: 12 V, 25 mA
For fuse bases 14 × 51 0.5 B 3NW7 901 1 1 unit 018 0.048
For fuse bases 22 × 58 B 3NW7 902 1 1 unit 018 0.048
■ More information
Mounting
Fuse holders, sizes 8 mm x 32 mm and 10 mm x 38 mm, have a
sliding catch that enables the removal of individual devices from
the assembly.
The infeed can be from the top or the bottom. Because the cylin-
drical fuse holders are fitted with the same anti-slip terminals at
the top and the bottom, the devices can also be rail-mounted at
the top or the bottom.
Auxiliary switches
Auxiliary switches are available for the cylindrical fuse holders.
These are simply clipped onto the base using the factory-fitted
brackets.
Sizes 8 mm × 32 mm and 10 mm × 38 mm:
The auxiliary switches support the remote display of the switch-
ing state ON or OFF of the fuse holder.
Sizes 14 mm × 51 mm and 22 mm × 58 mm:
The auxiliary switches support the remote display of fuse failure.
However, fuse links with strikers are required for this function.
When the fuse is tripped, a small striking pin - the striker - shoots
out of the front of the fuse. Over an armature link in the auxiliary
switch, the kinetic energy of this striker is used to switch a mini
switch, which then initializes this signal over a floating contact.
Fuse Systems
Cylindrical Fuse Systems
Compact fuse holders for
motor starter combinations N
■ Overview
Fused motor starter combinations can be configured with the The accessories are generally UL-certified.
fuse holders. The contactor and the fuse holder can be mounted
directly next to each other. Customers can mount an auxiliary switch which signals the
switching state or prevents the fuse holder from switching off
The strong current-limiting fuses ensure a type 2 protection level under load by interrupting the contactor control, thus increasing
(coordination according to IEC 60947-4, no damage protection) safety for the operator and process.
for the contactor.
Busbars and a matching three-phase feeder terminals complete
5
The UL version has an SCCR value of 200 kA. the product range.
Cylindrical fuse holder Class CC with signal detector and mounted aux- Installation configuration of a cylindrical fuse holder and a SIRIUS con-
iliary switch tactor on busbar adapter for the 60 mm busbar system.
■ Technical specifications
Cylindrical fuse holders
3NW7 0. .-1 3NW7 5. .-1HG
Sizes mm × mm 10 × 38 Class CC
Standards IEC 60269; UL 512; CSA UL 512; CSA
Approvals
• Acc. to UL U, UL File Number E171267 u, UL File Number E171267
• Acc. to CSA s s
Rated voltage Un V AC 690 600
Rated current In A AC 32 30
Rated short-circuit strength kA 120 (at 500 V) 200
80 (at 690 V)
Switching capacity
• Utilization category AC-20B (switching without load) --
Rated impulse withstand voltage kV 6
Overvoltage category III
Pollution degree 2
Max. power dissipation of the fuse link W 3
No-voltage changing of fuse links Yes
Sealable when installed Yes
Lockable with padlock Yes
Mounting position Any, but preferably vertical
Current direction Any
Degree of protection acc. to IEC 60529 IP20, with connected conductors
Terminals with touch protection according to BGV A3 Yes
at incoming and outgoing feeder
Ambient temperature °C -5 ... +40, humidity 90 % at +20
Conductor cross-sections
2
• Finely stranded, with end sleeve mm 1 ... 4
• AWG cables (American Wire Gauge) AWG 18 ... 10
Tightening torques Nm 1.5
lb. in 13
• Terminal screws PZ2
Fuse Systems
Cylindrical Fuse Systems
N Compact fuse holders for
motor starter combinations
Auxiliary switches
3NW7 903-1
Standards IEC 60947
Approvals U, s, UL 508, UL File Number E334003
Utilization category AC-12 DC-13 AC-15 Acc. to UL
Rated voltage Un V AC 250 -- -- -- 24 120 240 240
V DC -- 24 120 240 -- -- -- --
Rated current In A 2 0.5 0.25 4 3 1.5 5
5
Busbars
5ST2 60.
For cylindrical fuse holders 3NW7 0. .-1 3NW7 5. .-1HG
Pin spacing mm 15
Standards DIN EN 60974-1, VDE 0660 part 100, IEC 60947-1:2004, UL 508, CSA 22.2
Approvals u, UL 4248-1, UL File Number E337131
Busbar material E-Cu 58 F25
Partition material PA66-V0
Lamp wire resistance /1.5 mm2 °C 960
Insulation coordination Overvoltage category III, degree of pollution 2
Rated voltage Un
• Acc. to UL V AC -- 600
• Acc. to IEC V AC 690 --
Maximum busbar current In
• Acc. to UL A -- 65
• Acc. to IEC A 80 --
Terminal
5ST2 600
For cylindrical fuse holders 3NW7 0. .-1 3NW7 5. .-1HG
Pin spacing mm 15
Standards IEC 60999:2000, UL 508
Approvals u, UL 4248-1, UL File Number E337131
Enclosure/cover material PA66-V0
Lamp wire resistance /1 mm2 °C 960
Temperature resistance PA66-V0, HDT B ISO 179, °C 200
UL 94-V0/1.5
Insulation coordination Overvoltage category III, degree of pollution 2
Max. operational voltage Umax
• Acc. to UL V AC -- 600
• Acc. to IEC V AC 690 --
Maximum electrical load Imax
• Acc. to UL A -- 65
• Acc. to IEC A 80 --
Rated current In A 63
Conductor cross-sections
• Solid/stranded mm2 2.5 ... 35
• Finely stranded, with end sleeve mm2 2.5 ... 25
Tightening torque of clamping screw Nm 2.5 ... 3.5
Fuse Systems
Cylindrical Fuse Systems
Compact fuse holders for
motor starter combinations N
■ Selection and ordering data
Number of In For fuse links of size Mount- DT Order No. Price PU PS*/ PG Weight
poles ing per PU (UNIT, P. unit per PU
width SET, approx.
M)
A mm x mm MW kg
3NW7 cylindrical fuse holders
Cylindrical fuse holders U
5 3P 32
Without signal detectors
10 x 38 2.5
B 3NW7 033-1 1 1 unit 017 7.700
With signal detector B 3NW7 034-1 1 1 unit 017 0.190
Cylindrical fuse holders class CC u
3P 30 class CC 2.5
Without signal detectors B 3NW7 533-1HG 1 1 unit 018 0.181
With signal detector B 3NW7 534-1HG 1 1 unit 018 0.200
Accessories
Auxiliary switches u
AC-12, 5 A, max. 250 V, 1 NO, 1 NC 2.5 B 3NW7 903-1 1 1 unit 017 0.010
Accessories
Terminals u
For conductor cross-section 2.5 mm2 ... 35 mm2 B 5ST2 600 1 10 units 027 0.500
Accessories
Mounting rails for busbar device adapter u
For assembly of additional devices 45 A 8US19 98-7CB45 1 10 units 143 0.009
1)
Further device adapters and accessories, see chapter "Busbar Systems".
Fuse Systems
■ Technical specifications
Class CC fuse holders
3NW7 5.3-0HG
Standards UL 512; CSA C22.2
Approvals UL512; UL File No. E171267; CSA C22.2
Rated voltage V AC 600
Rated current In A 30
Max. power dissipation of fuse links
• With cable, 6 mm2 W 3
• With cable, 10 mm2 W 4.3
Conductor cross-sections
• Solid and stranded mm2 1.5 ... 25
• AWG Conductor cross-section, solid and stranded AWG 18 ... 4
Fuse Systems
5
2P 600 30 2 C 3NW7 523-0HG 1 6 units 018 0.139
3P 600 30 3 C 3NW7 533-0HG 1 4 units 018 0.208
Characteristic: slow,
current limiting
In1) DT Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
SET, approx.
M)
A kg
Class CC fuse links
0.6 (6/10) --
0.8 (8/10) --
1 C 3NW3 010-0HG 1 10 units 018 0.017
1.5 (1 ½) --
2 C 3NW3 020-0HG 1 10 units 018 0.017
3 C 3NW3 030-0HG 1 10 units 018 0.009
4 C 3NW3 040-0HG 1 10 units 018 0.008
5 C 3NW3 050-0HG 1 10 units 018 0.009
6 C 3NW3 060-0HG 1 10 units 018 0.009
8 C 3NW3 080-0HG 1 10 units 018 0.009
10 C 3NW3 100-0HG 1 10 units 018 0.001
12 C 3NW3 120-0HG 1 10 units 018 0.008
15 C 3NW3 150-0HG 1 10 units 018 0.008
20 C 3NW3 200-0HG 1 10 units 018 0.007
25 C 3NW3 250-0HG 1 10 units 018 0.006
30 C 3NW3 300-0HG 1 10 units 018 0.008
1)
Values in brackets, American English Wording
Fuse Systems
Busbar systems
■ Overview
Busbars with pin-type connections can be used for NEOZED Busbars with fork plugs are used for the most frequently used
safety switching devices and fuse bases. Busbars in 10 mm2 NEOZED fuse bases made of ceramic.
and 16 mm2 versions are available.
■ Benefits
• Clear and visible conductor connection that can be easily • Bus-mounting of NEOZED fuse bases made of molded plastic
checked when using NEOZED comfort base D02. This facili- on three-phase busbar with fork plug, which can be cut to
tates cable entry and saves time. length. Frequently used.
• Bus-mounting of NEOZED fuse bases made of ceramic on • Bus-mounting of MINIZED fuse switch disconnectors D01 with
three-phase busbar with fork plug, which can be cut to length. three-phase pin busbar, which can be cut to length with fork
Most common application. plug. Tried and tested.
• Clear and visible conductor connection that can be easily • Bus-mounting of cylindrical fuse holders 8 mm × 32 mm and
checked when using MINIZED switch disconnectors D02. 10 mm × 38 mm with three-phase pin busbar which can be
This facilitates cable entry and saves time. cut to length.
Fuse Systems
Busbar systems
• Bus-mounting of SITOR cylindrical fuse holders • Bus mounting with infeed through a connection terminal
10 mm x 38 mm with the same terminal connection as directly on the fuse holder up to a conductor cross-section of
Class CC fuse holders with three-phase pin busbar which can 35 mm²
be cut to length.
■ Technical specifications
5ST, 5SH
Standards EN 60439-1: 2005-01
Busbar material SF-Cu F 24
Partition material Plastic, Cycoloy 3600
heat-resistant over 90 °C
flame-retardant and
self-extinguishing,
dioxin and halogen-free
Rated operational voltage Uc V AC 400
Rated current In
• Cross-section 10 mm2 A 63
• Cross-section 16 mm2 A 80
Rated impulse withstand voltage Uimp kV 4
Test pulse voltage (1.2/50) kV 6.2
Rated conditional short-circuit current Icc kA 25
Resistance to climate
• Constant atmosphere Acc. to DIN 50015 23/83; 40/92; 55/20
• Humid heat Acc. to IEC 60068-2-30 28 cycles
Insulation coordination
• Overvoltage category III
• Pollution degree 2
Maximum busbar current IS/phase
• Infeed at the start of the busbar
- Cross-section 10 mm2 A 63
- Cross-section 16 mm2 A 80
• Infeed at the center of the busbar
- Cross-section 10 mm2 A 100
- Cross-section 16 mm2 A 130
Fuse Systems
Busbar systems
5ST3 7 . . - . HG busbars acc. to UL 508
5ST3 7. .-0HG 5ST3 7. .-2HG 5ST3 770-0HG 5ST3 770-1HG
Standards UL 508, CSA C22.2 No. 14-M 95
Approvals UL 508 File No. E328403
CSA
Operational voltage
• Acc. to IEC V AC 690
• Acc. to UL 489 V AC 600
5
Rated conditional short-circuit current kA 10 (RMS symmetrical 600 V for three cycles)
• Dielectric strength kV/mm 25
• Surge strength kV > 9.5
Rated current A -- -- 115
Maximum busbar current IS/phase
• Infeed at the start of the busbar A 80 100 -- --
• Infeed at the center of the busbar A 160 200 -- --
Insulation coordination
• Overvoltage category III
• Pollution degree 2
Busbar cross-section mm2 Cu 18 25 -- --
Infeed Any
Conductor cross-sections AWG -- -- 10 ... 1/0 14 ... 1
mm2 -- -- 6 ... 35 1.5 ... 50
Terminals
• Terminal tightening torque Nm -- -- 5 3.5
lbs/in -- -- 50 35
Infeed at the start of the busbar Infeed along the busbar or midpoint infeed
3 2 1 1 2 3
I201_13755 I201_13754a
S S S
The sum of the output current per branch must not be greater than the bus-
bar current IS1.2 / phase.
Fuse Systems
Busbar systems
Phases Conductor Load Pin Length DT Order No. Price PU PS*/ PG Weight
cross- capacity spacing per PU (UNIT, P. unit per PU
section up to SET, approx.
M)
mm2 A MW mm kg
For MINIZED fuse switch disconnectors D01
Can be cut to length, without end caps
Single- 16 120 1 1000 B 5ST2 190 1 1 unit 027 0.222
phase
5 Two-
phase
B 5ST2 191 1 1 unit 027 0.448
For two-phase and three-phase 5ST3 7 busbars and } 5ST3 750 1 10 units 027 0.001
for three-phase 5SH5 320 busbars
Fuse Systems
Busbar systems
Phases Conductor Load capacity Length DT Order No. Price PU PS*/ PG Weight
cross- up to per PU (UNIT, P. unit per PU
section SET, approx.
M)
mm2 A mm kg
Touch protection for free connection of
pin busbars
Yellow, (RAL1004) A 5ST3 655 1 10 units 027 0.003
5 x 1 pin
Terminals
5
For NEOZED fuse bases D01/D02 made of ceramic
For DIAZED fuse bases DII/DIII made of ceramic
Terminal version S
For con- 2 ... 25 A 5SH5 327 1 10/300 units 016 0.011
ductors
Busbars
For 1-pole DIAZED fuse bases made of ceramic
with terminal versions BB and BS
Size DII, for 19 bases
Single- 24 80 1000 A 5SH3 500 1 1/25 units 016 0.120
phase
Busbars
For DIAZED bus-mounting bases/EZR
with thread for screw adapters
For size DII, 42 5SF6 005 bases
Single- 48 150 2000 C 5SH3 54 1 5 units 016 0.700
phase
Fuse Systems
Busbar systems
5ST3 7 . . - . HG busbars acc. to UL 508
Pin Length DT Order No. Price PU PS*/ PG Weight
spacing per PU (UNIT, P. unit per PU
SET, approx.
M)
MW mm kg
5ST3 7. .-.HG busbars according to UL 508, 18 mm2,
can be cut, without end caps
Single-phase
• For fuse holders 14 x 51 1.5 1000 A 5ST3 703-0HG 1 10 units 012 0.330
(3NC1 491, 3NW7 111) or
MCB 1P (5SY, 5SP) with AS or FC
Two-phase
• For fuse holder 10 x 38/class CC 1 1000 A 5ST3 705-0HG 1 10 units 012 0.700
(3NC1 092, 3NW7 523-0HG) or
MCB 2P (5SY)
Three-phase
• For fuse holder 10 x 38/class CC 1 1000 A 5ST3 710-0HG 1 10 units 012 0.850
(3NC1 093, 3NW7 533-0HG) or
MCB 3P (5SY)
• For fuse holders 14 x 51 1.5 1000 A 5ST3 714-0HG 1 10 units 012 0.850
(3NC1 493, 3NW7 131) or
MCB 1P (5SY, 5SP) with AS or FC
5ST3 7. .-.HG busbars according to UL 508, 25 mm2,
can be cut, without end caps
Single-phase
• For fuse holders 14 x 51 1.5 1000 A 5ST3 701-2HG 1 10 units 012 0.340
(3NC1 491, 3NW7 111) or
MCB 1P (5SP)
Two-phase
• For fuse holder 14 x 51 1.5 1000 A 5ST3 705-2HG 1 10 units 012 0.800
(3NC1 492, 3NW7 121) or
MCB 2P (5SP)
Three-phase
• For fuse holder 14 x 51 1.5 1000 A 5ST3 710-2HG 1 10 units 012 1.090
(3NC1 493, 3NW7 131) or
MCB 3P (5SP)
End caps for 5ST3 7. .-.HG
• For single-phase busbars A 5ST3 748-0HG 1 10 units 012 0.001
• For two- and three-phase busbars A 5ST3 750-0HG 1 10 units 012 0.002
Infeed to busbar
• 50 mm2 A 5ST3 770-1HG 1 10 units 012 0.035
Fuse Systems
LV HRC Fuse Systems
LV HRC fuse links
■ Overview
LV HRC fuse systems (NH type) are used for installation systems LV HRC fuse links are available in the following operational
in non-residential, commercial and industrial buildings as well as classes:
in systems of power supply companies. They therefore protect • gG for cable and line protection
essential building parts and installations.
• aM for the short-circuit protection of switching devices in
LV HRC fuse systems (NH type) are fuse systems designed for motor circuits
operation by experts. There are no constructional requirements • gR or aR for the protection of power semiconductors
for non-interchangeability of rated current and touch protection.
The components and auxiliary equipment are designed in such
a way as to ensure the safe replacement of NH type fuses or iso-
• gS: The new operational class gS combines cable and line
protection with semiconductor protection. 5
lation of systems. LV HRC fuse links of size 000 can also be used in
LV HRC fuse bases, LV HRC fuse switch disconnectors,
LV HRC fuse links are available in the sizes 000, 00, 0, 1, 2, 3, 4 LV HRC fuse strips as well as LV HRC in-line fuse switch discon-
and 4a. nectors of size 00.
The fuse links 300 A, 355 A and 425 A comply with the standard
but do not have the VDE mark.
LV HRC components
5
$ LV HRC fuse base from the SR60 busbar system
4 % LV HRC fuse base for busbar mounting
3
2 & LV HRC fuse base, 3P
6
( LV HRC fuse base, 1P
7 ) LV HRC contact cover
* LV HRC fuse link
+ LV HRC signal detector
8 , LV HRC partition
1
9 - LV HRC protective cover
LV HRC fuse base with swivel mechanism
. - For screw fixing on mounting plates
/ - For screw fixing on busbar systems
14 0 - For claw fixing on busbars
10 11 12 13 1 LV HRC protective cover for LV HRC fuse bases with swivel
mechanism
2 LV HRC swivel mechanism
3 LV HRC fuse base cover
4 LV HRC isolating link with insulated grip lugs
5 LV HRC isolating link with non-insulated grip lugs
15 16 17 18 19
6 LV HRC fuse puller with sleeve
I2_13743 7 LV HRC fuse puller
Fuse Systems
LV HRC Fuse Systems
LV HRC fuse links
■ Benefits
• LV HRC fuse links with combination alarm signal the tripping • In the standard series with front indicator, the front-mounted
of a fuse by a clear color change from red to white. This en- red indicator signals the tripping of a fuse.
ables fast identification and replacement of the tripped fuse • LV HRC fuse links are always equipped with silver-plated con-
links. This increases plant availability tact pins. This means that they are non-corroding and have
• The insulated grip lugs made of metal are integrated in the top less contact resistance. This ensures the long-term opera-
and bottom covers of the fuse link in molded plastic and pro- tional safety of the plant.
vide greater safety during replacement. The mark shown
below indicates that the grip lugs are insulated
■ Technical specifications
LV HRC fuse links
Operational class Operational
class
gG aM
3NA6 ...-4 3NA6 ... 3NA3 ... 3NA6 ...-6 3NA3 ...-6 3ND1
3NA6 ...-4KK 3NA6 ...-7 3NA3 ...-7 3NA7 ...-6 3ND2
3NA3 83.-8 3NA7 ...
3NA7 ...-7
Standards IEC 60269-1, -2; EN 60269-1; DIN VDE 0636
Approvals DIN VDE 0636-2; CSA 22.2 No.106, File Number 016325_0_00 (CSA approval of fuses 500 V for 600 V)
Rated voltage Un
• Sizes 000 and 00 V AC 400 500 500 690 690 500
V DC -- 250 250 250 250 --
• Sizes 1 and 2 V AC 400 500 500 690 690 690
V DC -- 440 440 440 440 --
• Size 3 V AC 500 690 690
V DC 440 440
• Sizes 4 and 4a (IEC design) V AC 500 --
V DC 400 --
Rated current In A 10 ... 400 2 ... 400 2 ... 1250 2 ... 315 2 ... 500 6 ... 630
Rated breaking capacity kA AC 120
kA DC -- 25 --
Contact pins Non-corroding, silver-plated
Resistance to climate °C -20 ... +50 at 95 % relative humidity
Fuse Systems
LV HRC Fuse Systems
LV HRC fuse links
5
operational class gG
000 21 10 400/-- B 3NA6 803-4 1 3 units 013 0.127
16 B 3NA6 805-4 1 3 units 013 0.128
20 B 3NA6 807-4 1 3 units 013 0.128
25 B 3NA6 810-4 1 3 units 013 0.128
32 B 3NA6 812-4 1 3 units 013 0.128
35 B 3NA6 814-4 1 3 units 013 0.123
40 B 3NA6 817-4 1 3 units 013 0.113
50 B 3NA6 820-4 1 3 units 013 0.125
63 B 3NA6 822-4 1 3 units 013 0.126
80 B 3NA6 824-4 1 3 units 013 0.124
100 B 3NA6 830-4 1 3 units 013 0.120
00 30 80 400/-- B 3NA6 824-4KK 1 3 units 013 0.201
100 B 3NA6 830-4KK 1 3 units 013 0.204
125 B 3NA6 832-4 1 3 units 013 0.193
160 B 3NA6 836-4 1 3 units 013 0.206
Fuse Systems
LV HRC Fuse Systems
LV HRC fuse links
5
combination alarm,
operational class gG
000 21 2 500/ B 3NA7 802 013 B 3NA6 802 1 3 units 013 0.130
4 250 B 3NA7 804 013 B 3NA6 804 1 3 units 013 0.126
6 B 3NA7 801 013 B 3NA6 801 1 3 units 013 0.116
10 B 3NA7 803 013 B 3NA6 803 1 3 units 013 0.128
16 } 3NA7 805 013 } 3NA6 805 1 3 units 013 0.129
20 } 3NA7 807 013 } 3NA6 807 1 3 units 013 0.128
25 } 3NA7 810 013 } 3NA6 810 1 3 units 013 0.121
32 B 3NA7 812 013 B 3NA6 812 1 3 units 013 0.129
35 } 3NA7 814 013 } 3NA6 814 1 3 units 013 0.129
40 B 3NA7 817 013 B 3NA6 817 1 3 units 013 0.123
50 } 3NA7 820 013 } 3NA6 820 1 3 units 013 0.124
63 } 3NA7 822 013 } 3NA6 822 1 3 units 013 0.125
80 } 3NA7 824 013 } 3NA6 824 1 3 units 013 0.128
100 } 3NA7 830 013 } 3NA6 830 1 3 units 013 0.124
00 30 80 500/ B 3NA7 824-7 013 B 3NA6 824-7 1 3 units 013 0.182
100 250 B 3NA7 830-7 013 B 3NA6 830-7 1 3 units 013 0.202
125 } 3NA7 832 013 } 3NA6 832 1 3 units 013 0.206
160 } 3NA7 836 013 A 3NA6 836 1 3 units 013 0.194
Fuse Systems
LV HRC Fuse Systems
LV HRC fuse links
Non-insulated
grip lugs
Sizes Mounting In Un DT Order No. Price PU PS*/ PG Weight
width per PU (UNIT, P. unit per PU
SET, approx.
M)
mm A V AC/V DC kg
LV HRC fuse links with front indicator,
operational class gG
000 21 2
4
6
500/250 }
}
}
3NA3 802
3NA3 804
3NA3 801
1
1
1
3 units
3 units
3 units
013
013
013
0.122
0.125
0.121
5
10 } 3NA3 803 1 3 units 013 0.130
16 } 3NA3 805 1 3 units 013 0.123
20 } 3NA3 807 1 3 units 013 0.120
25 } 3NA3 810 1 3 units 013 0.123
32 } 3NA3 812 1 3 units 013 0.124
35 } 3NA3 814 1 3/90 units 013 0.129
40 } 3NA3 817 1 3 units 013 0.127
50 } 3NA3 820 1 3/90 units 013 0.122
63 } 3NA3 822 1 3/90 units 013 0.124
80 } 3NA3 824 1 3/90 units 013 0.128
100 } 3NA3 830 1 3/90 units 013 0.124
125 400/250 } 3NA3 832-8 1 3/60 units 013 0.120
160 } 3NA3 836-8 1 3/60 units 013 0.160
00 30 35 500/250 B 3NA3 814-7 1 3 units 013 0.190
50 B 3NA3 820-7 1 3 units 013 0.189
63 B 3NA3 822-7 1 3 units 013 0.190
80 B 3NA3 824-7 1 3 units 013 0.198
100 B 3NA3 830-7 1 3 units 013 0.191
125 } 3NA3 832 1 3 units 013 0.192
160 } 3NA3 836 1 3 units 013 0.189
Fuse Systems
LV HRC Fuse Systems
LV HRC fuse links
Non-insulated
grip lugs
Sizes Mounting In Un DT Order No. Price PU PS*/ PG Weight
width per PU (UNIT, P. unit per PU
SET, approx.
M)
mm A V AC/V DC kg
LV HRC fuse links with front indicator,
operational class gG
5 2 47.2 35
50
63
500/440 B
B
A
3NA3 214
3NA3 220
3NA3 222
1 3 units
1 3 units
1 3 units
013
013
013
0.454
0.420
0.433
80 A 3NA3 224 1 3 units 013 0.431
100 A 3NA3 230 1 3 units 013 0.430
125 A 3NA3 232 1 3 units 013 0.429
160 } 3NA3 236 1 3 units 013 0.432
200 } 3NA3 240 1 3 units 013 0.427
224 } 3NA3 242 1 3 units 013 0.432
250 } 3NA3 244 1 3 units 013 0.440
57.8 300 A 3NA3 250 1 3 units 013 0.626
315 } 3NA3 252 1 3 units 013 0.625
355 } 3NA3 254 1 3 units 013 0.617
400 } 3NA3 260 1 3 units 013 0.624
3 57.8 200 500/440 B 3NA3 340 1 3 units 013 0.629
224 B 3NA3 342 1 3 units 013 0.625
250 A 3NA3 344 1 3 units 013 0.632
300 B 3NA3 350 1 3 units 013 0.626
315 } 3NA3 352 1 3 units 013 0.632
355 A 3NA3 354 1 3 units 013 0.666
400 } 3NA3 360 1 3 units 013 0.677
71.2 425 A 3NA3 362 1 3 units 013 0.892
500 } 3NA3 365 1 3 units 013 0.880
630 } 3NA3 372 1 3 units 013 0.885
Fuse Systems
LV HRC Fuse Systems
LV HRC fuse links
5
combination alarm,
operational class gG
000 21 2 690/ B 3NA7 802-6 013 B 3NA6 802-6 1 3 units 013 0.122
4 250 B 3NA7 804-6 013 B 3NA6 804-6 1 3 units 013 0.130
6 B 3NA7 801-6 013 B 3NA6 801-6 1 3 units 013 0.122
10 B 3NA7 803-6 013 B 3NA6 803-6 1 3 units 013 0.124
16 B 3NA7 805-6 013 B 3NA6 805-6 1 3 units 013 0.123
20 B 3NA7 807-6 013 B 3NA6 807-6 1 3 units 013 0.128
25 B 3NA7 810-6 013 B 3NA6 810-6 1 3 units 013 0.120
32 B 3NA7 812-6 013 B 3NA6 812-6 1 3 units 013 0.128
35 B 3NA7 814-6 013 B 3NA6 814-6 1 3 units 013 0.129
00 30 40 690/ B 3NA7 817-6 013 B 3NA6 817-6 1 3 units 013 0.203
50 250 B 3NA7 820-6 013 B 3NA6 820-6 1 3 units 013 0.196
63 B 3NA7 822-6 013 B 3NA6 822-6 1 3 units 013 0.202
80 B 3NA7 824-6 013 B 3NA6 824-6 1 3 units 013 0.187
100 B 3NA7 830-6 013 B 3NA6 830-6 1 3 units 013 0.202
2 47.2 80 690/ B 3NA7 224-6 013 B 3NA6 224-6 1 3 units 013 0.460
100 440 B 3NA7 230-6 013 B 3NA6 230-6 1 3 units 013 0.462
125 B 3NA7 232-6 013 B 3NA6 232-6 1 3 units 013 0.436
160 B 3NA7 236-6 013 B 3NA6 236-6 1 3 units 013 0.439
200 B 3NA7 240-6 013 B 3NA6 240-6 1 3 units 013 0.455
57.8 224 B 3NA7 242-6 013 B 3NA6 242-6 1 3 units 013 0.656
250 B 3NA7 244-6 013 B 3NA6 244-6 1 3 units 013 0.658
300 B 3NA7 250-6 013 B 3NA6 250-6 1 3 units 013 0.661
315 B 3NA7 252-6 013 B 3NA6 252-6 1 3 units 013 0.627
Fuse Systems
LV HRC Fuse Systems
LV HRC fuse links
Non-insulated
grip lugs
Sizes Mounting In Un DT Order No. Price PU PS*/ PG Weight
width per PU (UNIT, P. unit per PU
SET, approx.
M)
mm A V AC/V DC kg
LV HRC fuse links with front indicator,
operational class gG
5 000 21 2
4
6
690/250 }
}
}
3NA3 802-6
3NA3 804-6
3NA3 801-6
1 3 units
1 3 units
1 3 units
013
013
013
0.127
0.128
0.123
10 } 3NA3 803-6 1 3 units 013 0.123
16 } 3NA3 805-6 1 3 units 013 0.126
20 } 3NA3 807-6 1 3 units 013 0.133
25 } 3NA3 810-6 1 3 units 013 0.126
32 B 3NA3 812-6 1 3 units 013 0.121
35 } 3NA3 814-6 1 3 units 013 0.128
00 30 40 690/250 B 3NA3 817-6 1 3 units 013 0.190
50 } 3NA3 820-6 1 3 units 013 0.191
63 } 3NA3 822-6 1 3 units 013 0.191
80 } 3NA3 824-6 1 3 units 013 0.195
100 } 3NA3 830-6 1 3 units 013 0.200
Fuse Systems
LV HRC Fuse Systems
LV HRC fuse links
Non-insulated
grip lugs
Sizes Mounting In Un DT Order No. Price PU PS*/ PG Weight
width per PU (UNIT, P. unit per PU
SET, approx.
M)
mm A V AC/V DC kg
LV HRC fuse links with front indicator,
operational class aM
000 21 6
10
16
500/-- B
B
B
3ND1 801
3ND1 803
3ND1 805
1 3 units
1 3 units
1 3 units
014
014
014
0.114
0.127
0.129
5
20 B 3ND1 807 1 3 units 014 0.128
25 B 3ND1 810 1 3 units 014 0.122
32 B 3ND1 812 1 3 units 014 0.130
35 B 3ND1 814 1 3 units 014 0.123
40 B 3ND1 817 1 3 units 014 0.123
50 B 3ND1 820 1 3 units 014 0.134
63 B 3ND1 822 1 3 units 014 0.122
80 B 3ND1 824 1 3 units 014 0.129
00 30 100 500/-- B 3ND1 830 1 3 units 014 0.177
125 B 3ND1 832 1 3 units 014 0.189
160 B 3ND1 836 1 3 units 014 0.199
Fuse Systems
LV HRC Fuse Systems
LV HRC signal detectors
■ Overview
LV HRC signal detectors are used for remotely indicating that the • 3NX1 024 signal detector top
LV HRC fuse links have been tripped. 3 different solutions are The signal detector top can be used with LV HRC fuse links,
available: sizes 000, 00, 1 and 2, which are equipped with non-insulated
• 3NX1 021 signal detectors with signal detector link grip lugs and have a front indicator or combination alarm. It is
The LV HRC signal detectors with signal detector link support simply plugged into the grip lugs
monitoring of LV HRC fuse links with non-insulated grip lugs of • 5TT3 170 fuse monitors
sizes 000 to 4 at 10 A or more. The signal detector link is con- If a fuse is tripped, the front indicator springs open and
■ Benefits
Uniform solution for all sizes
LV HRC signal detectors reliably indicate when a fuse has The LV HRC signal detector top is a cost-effective solution for the
tripped. Tripped fuses are quickly located. This saves time and monitoring of Siemens LV HRC fuse links of sizes 000, 00, 1 and
increases plant availability. 2.
$ LV HRC fuse links
$ LV HRC fuse links
% LV HRC signal detectors % Front indicator
I2_13744
6
& Microswitch & Signal detector tops
( Spring contact ( Rocker/lever arm
) Hinged lid
%
* Signal detector links 1
$
5
(
4
2
3
&
Fuse Systems
LV HRC Fuse Systems
LV HRC signal detectors
Fuse Systems
LV HRC Fuse Systems
LV HRC sockets and accessories
■ Overview
Terminals for all applications
Terminals are as different as the requirements of individual sys-
tems.
Flat terminals with screws are suitable for connecting busbars or The modern box terminal ensures efficient and reliable connec-
cable lugs. They have a torsion-proof screw connection with tion to the conductors. They support connection of conductors
shim, spring washer and nut. When tightening the nut, always with or without end sleeves.
ensure compliance with the specified torque due to the consid-
erable leverage effect.
The double busbar terminal differs from the flat connection in
that it supports connection of two busbars, one on the top and
one at the bottom of the flat connection.
With the flat connection with nut, terminal lug of the nut is torsion- Up to three conductors can be clamped to the terminal strip.
proof. When tightening the nut, the torque must be observed
because of the considerable leverage effect.
The plug-in terminal is equipped for connecting two conductors. One conductor can be clamped to the saddle-type terminal.
Fuse Systems
LV HRC Fuse Systems
LV HRC sockets and accessories
■ Benefits
• The silver-plated Lyra contact provides a large contact area
for the pin of the LV HRC fuse link. This improves heat trans-
mission and lowers the temperature. It also minimizes the ag-
ing of the fuse link in the maximum load range, in particular
when using SITOR fuses
• The large contact area also facilitates replacement of
LV HRC fuse links
• The spring washer tensioning the contact is mechanically
galvanized. This will prevent hydrogen embrittlement. The 5
contact is resistant to aging and there will be no dreaded an-
nealing of contacts, which considerably improves operating
safety.
■ Technical specifications
LV HRC fuse bases, LV HRC bus-mounting bases
Size 000/00 0 1 2 3 4
Standards IEC 60269-1, -2; EN 60269-1; DIN VDE 0636-2
Rated current In A 160 160 250 400 630 1250
Rated voltage Un V AC 6901) 6901) 690
V DC 250 440 440
Rated short-circuit strength kA AC 120
kA DC 25
Flat terminal
Screw M8 M10 M12
Nut M8 --
Max. tightening torque Nm 14 38 65
Plug-in terminal
Conductor cross-section mm2 2.5 ... 50 --
Saddle-type terminal
Conductor cross-section mm2 6 ... 70 --
Box terminals
Conductor cross-section mm2 2.5 ... 50
Terminal strips
Conductor cross-section, 3-wire mm2 1.5 ... 16 --
Max. torque Nm 2 2.5 --
for attachment of LV HRC fuse base
1)
Extended rated voltage up to 1000 V (except LV HRC bus-mounting bases).
Fuse Systems
LV HRC Fuse Systems
LV HRC sockets and accessories
5 000/00
160
1P
With flat terminals, screw
With saddle-type terminals
}
}
3NH3 051
3NH3 052
1 1/10 units
1 1/10 units
014
014
0.149
0.010
125 With box terminal, up to 50 mm2 } 3NH3 053 1 1/10 units 014 0.118
Made of ceramic for screw fixing
000/00 160 1P
With flat terminals, screw } 3NH3 030 1 3 units 014 0.217
With plug-in terminals B 3NH3 031 1 3 units 014 0.260
With saddle-type terminals } 3NH3 032 1 3 units 014 0.204
With flat terminals and terminal strip B 3NH3 035 1 3 units 014 0.229
With flat terminals, nut B 3NH3 038 1 3 units 014 0.177
With flat and saddle-type terminals B 3NH3 050 1 3 units 014 0.217
Fuse Systems
LV HRC Fuse Systems
LV HRC sockets and accessories
5
With flat terminals A 3NH3 530 1 1 unit 014 3.116
1 250 1P
With screw fixing for mounting plate A 3NH7 230 1 1 unit 014 1.086
With claw fixing for non-perforated B 3NH7 231 1 1 unit 014 1.501
busbar
With screw fixing for perforated B 3NH7 232 1 1 unit 014 1.212
busbar
Fuse Systems
LV HRC Fuse Systems
LV HRC sockets and accessories
LV HRC covers
000/00 For plugging into IP2X LV HRC protective B 3NX3 116 1 10 units 014 0.014
covers
Fuse Systems
LV HRC Fuse Systems
LV HRC sockets and accessories
Fuse-base covers
For LV HRC fuse bases, red,
with inscription "Trennstelle" (isolating point)
000/00 C 3NX1 003 1 3 units 014 0.013
1, 2, 3 C 3NX1 004 1 3 units 014 0.087
Fuse pullers
000 ... 4 For LV HRC fuse links
Without sleeve } 3NX1 013 1 1 unit 014 0.301
With sleeve } 3NX1 014 1 1 unit 014 0.558
Isolating links
For LV HRC fuse bases and
fuse switch disconnectors
With insulated grip lugs
000/00 Silver-plated } 3NG1 002 1 3/30 units 014 0.066
0 C 3NG1 102 1 1/10 units 014 0.116
1 } 3NG1 202 1 1/10 units 014 0.159
2 } 3NG1 302 1 1/5 units 014 0.228
3 } 3NG1 402 1 1/5 units 014 0.281
With non-insulated grip lugs
4 Tinned B 3NG1 503 1 3 units 014 0.679
4a Nickel-plated B 3NG1 505 1 1/5 units 014 0.701
Fuse Systems
SITOR Semiconductor Fuses
SITOR LV HRC design
■ Overview ■ Benefits
SITOR fuses protect power semiconductors from the effects of • SITOR fuses have a high varying load factor, which ensures a
short circuits because the super quick disconnect characteristic high level of operating safety and plant availability - even
is far quicker than with conventional LV HRC fuses (NH type). when subject to constant load change.
They protect expensive devices and system components, such • The use of SITOR fuses in LV HRC bases or Siemens switch
as converters with fuses in the input and the DC link, UPS sys- disconnectors has been tested with regard to heat dissipation
tems and soft starters for motors. and maximum current loading. This makes planning and
Panel mounting requirements have given rise to various connec- dimensioning easier and prevents consequential damage.
Fuse Systems
SITOR Semiconductor Fuses
SITOR LV HRC design
5
dimension: 110 mm, or for installation in LV HRC fuse
bases or switch disconnectors
3 150 500 gR 33 000 35 0.85 B 3NC2 423-3C 1 3 units 047 0.940
200 64 000 40 0.85 B 3NC2 425-3C 1 3 units 047 0.940
250 99 000 50 0.85 B 3NC2 427-3C 1 3 units 047 0.940
300 132 000 65 0.85 B 3NC2 428-3C 1 3 units 047 0.940
350 aR 249 000 60 0.85 B 3NC2 431-3C 1 3 units 047 0.940
400 390 000 50 0.85 B 3NC2 432-3C 1 3 units 047 0.940
Fuse Systems
SITOR Semiconductor Fuses
SITOR LV HRC design
Sizes Ie Ue Opera- Breaking Power Vary- DT Order No. Price PU PS*/ PG Weight
tional I2t value loss ing per PU (UNIT, P. unit per PU
classes load SET, approx.
factor M)
A V AC A2s W WL kg
SITOR LV HRC design
With slotted blade contacts for M12 screw fixing, mounting
dimension: 110 mm, or for installation in LV HRC fuse bases
or switch disconnectors
5 3 560
630
670
690 gR 890 000 60
1 390 000 62
1 640 000 65
1.0
1.0
1.0
D
D
D
3NE1 435-3
3NE1 436-3
3NE1 447-3
1 3 units
1 3 units
1 3 units
047
047
047
1.150
1.150
1.150
710 1 818 000 72 1.0 D 3NE1 437-3 1 3 units 047 1.150
800 2 475 000 82 1.0 D 3NE1 438-3 1 3 units 047 1.150
850 3 640 000 76 1.0 D 3NE1 448-3 1 3 units 047 1.150
With slotted blade contacts with two M10 oblong slots for
screw fixing, or for installation in LV HRC fuse bases or switch
disconnectors
3 150 690 gR 17 600 40 0.85 B 3NC8 423-0C 1 3 units 047 0.940
200 38 400 55 0.85 B 3NC8 425-0C 1 3 units 047 0.940
250 70 400 72 0.85 B 3NC8 427-0C 1 3 units 047 0.940
350 176 000 95 0.85 B 3NC8 431-0C 1 3 units 047 0.940
500 448 000 130 0.85 B 3NC8 434-0C 1 3 units 047 0.940
Size Ie Ue Opera- Breaking Power Vary- DT Order No. Price PU PS*/ PG Weight
tional I2t value loss ing per PU (UNIT, P. unit per PU
classes load SET, approx.
factor M)
A V AC/ A2s W WL kg
V DC
SITOR LV HRC design
With M8 bolt-on links, mounting dimension: 80 mm,
for screwing onto busbars
000 20 690/ gR 83 7 0.9 B 3NE8 714-1 1 10 units 047 0.128
7001)
25 140 9 0.9 B 3NE8 715-1 1 10 units 047 0.130
32 285 10 0.9 A 3NE8 701-1 1 10 units 047 0.110
40 490 12 0.9 A 3NE8 702-1 1 10 units 047 0.122
50 815 15 0.9 A 3NE8 717-1 1 10 units 047 0.131
63 aR 1 550 16 0.95 A 3NE8 718-1 1 10 units 047 0.130
80 2 700 18 0.9 } 3NE8 720-1 1 10 units 047 0.132
100 4 950 19 0.95 } 3NE8 721-1 1 10 units 047 0.123
125 9 100 23 0.95 } 3NE8 722-1 1 10 units 047 0.130
160 17 000 31 0.9 } 3NE8 724-1 1 10 units 047 0.122
200 30 000 36 0.9 } 3NE8 725-1 1 10 units 047 0.117
250 55 000 42 0.9 } 3NE8 727-1 1 10 units 047 0.132
315 85 500 54 0.85 } 3NE8 731-1 1 10 units 047 0.127
1) DC voltage acc. to UL.
Fuse Systems
SITOR Semiconductor Fuses
SITOR LV HRC design
Sizes Ie Ue Opera- Breaking Power Vary- DT Order No. Price PU PS*/ PG Weight
tional I2t value loss ing per PU (UNIT, P. unit per PU
classes load SET, approx.
factor M)
A V AC A 2s W WL kg
SITOR LV HRC design
With blade contacts for mounting in LV HRC fuse bases or
switch disconnectors
000 16 690 gS 200 3.0 1.0 } 3NE1 813-0 1 3 units 047 0.133
20
25
430 3.5
780 4.0
1.0
1.0
}
}
3NE1 814-0
3NE1 815-0
1 3 units
1 3 units
047
047
0.124
0.127 5
35 1 700 5.0 1.0 } 3NE1 803-0 1 3 units 047 0.128
40 3 000 5.0 1.0 } 3NE1 802-0 1 3 units 047 0.126
50 4 400 6.0 1.0 } 3NE1 817-0 1 3 units 047 0.129
63 9 000 7.0 1.0 } 3NE1 818-0 1 3 units 047 0.126
80 18 000 8.0 1.0 } 3NE1 820-0 1 3 units 047 0.124
00 100 690 gS 33 000 10 1.0 } 3NE1 021-0 1 3 units 047 0.204
125 63 000 11 1.0 } 3NE1 022-0 1 3 units 047 0.195
1 160 690 gS 60 000 24 1.0 } 3NE1 224-0 1 3 units 047 0.522
200 100 000 27 1.0 } 3NE1 225-0 1 3 units 047 0.518
250 200 000 30 1.0 } 3NE1 227-0 1 3 units 047 0.515
315 310 000 38 1.0 A 3NE1 230-0 1 3 units 047 0.519
2 350 690 gS 430 000 42 1.0 } 3NE1 331-0 1 3 units 047 0.687
400 590 000 45 1.0 } 3NE1 332-0 1 3 units 047 0.519
450 750 000 53 1.0 A 3NE1 333-0 1 3 units 047 0.689
500 950 000 56 1.0 A 3NE1 334-0 1 3 units 047 0.765
3 560 690 gS 1 700 000 50 1.0 A 3NE1 435-0 1 3 units 047 1.000
630 2 350 000 55 1.0 A 3NE1 436-0 1 3 units 047 1.113
710 3 400 000 60 1.0 A 3NE1 437-0 1 3 units 047 1.045
800 5 000 000 59 1.0 A 3NE1 438-0 1 3 units 047 1.560
00 80 690 gR 5 800 10.5 1.0 A 3NE1 020-2 1 3 units 047 0.200
100 11 000 11.5 1.0 A 3NE1 021-2 1 3 units 047 0.197
125 23 000 13.5 1.0 A 3NE1 022-2 1 3 units 047 0.195
3 560 690 gR 890 000 60 1.0 A 3NE1 435-2 1 3 units 047 1.098
630 1 390 000 62 1.0 A 3NE1 436-2 1 3 units 047 1.038
670 1 640 000 65 1.0 A 3NE1 447-2 1 3 units 047 1.044
710 1 818 000 72 1.0 B 3NE1 437-2 1 3 units 047 1.031
800 2 475 000 82 1.0 A 3NE1 438-2 1 3 units 047 1.067
850 3 640 000 76 1.0 A 3NE1 448-2 1 3 units 047 1.048
Fuse Systems
SITOR Semiconductor Fuses
SITOR LV HRC design
Sizes Ie Ue Opera- Breaking Power Vary- DT Order No. Price PU PS*/ PG Weight
tional I2t value loss ing per PU (UNIT, P. unit per PU
classes load SET, approx.
factor M)
A V AC A2s W WL kg
SITOR LV HRC design
With blade contacts for mounting in LV HRC fuse bases or
switch disconnectors (contd.)
00 25 690 gR 180 7 0.95 } 3NE8 015-1 1 3 units 047 0.193
5 35
50
400 9
700 14
0.95
0.95
}
}
3NE8 003-1
3NE8 017-1
1 3 units
1 3 units
047
047
0.195
0.614
63 1 400 16 0.95 } 3NE8 018-1 1 3 units 047 0.196
80 aR 2 400 19 0.95 } 3NE8 020-1 1 3 units 047 0.206
100 4 200 22 0.95 } 3NE8 021-1 1 3 units 047 0.207
125 6 500 28 0.95 } 3NE8 022-1 1 3 units 047 0.195
160 13 000 38 0.95 } 3NE8 024-1 1 3 units 047 0.195
Fuse Systems
SITOR Semiconductor Fuses
SITOR LV HRC design
Sizes Ie Ue Opera- Breaking Power Vary- DT Order No. Price PU PS*/ PG Weight
tional I2t value loss ing per PU (UNIT, P. unit per PU
classes load SET, approx.
factor M)
A V AC A2s W WL kg
SITOR LV HRC design
With slotted blade contacts for M10 screw fixing, mounting
dimension: 110 mm, or for installation in LV HRC fuse bases
or switch disconnectors
1 100 1 000 aR
125
160
4 800 28
7 200 36
13 000 42
0.95
0.95
0.95
A
A
}
3NE3 221
3NE3 222
3NE3 224
1 3 units
1 3 units
1 3 units
047
047
047
0.510
0.506
0.513
5
200 30 000 42 0.95 } 3NE3 225 1 3 units 047 0.586
250 48 000 50 0.95 } 3NE3 227 1 3 units 047 0.580
315 80 000 65 0.95 } 3NE3 230-0B 1 3 units 047 0.513
350 100 000 75 0.9 A 3NE3 231 1 3 units 047 0.515
400 135 000 85 0.9 A 3NE3 232-0B 1 3 units 047 0.520
450 175 000 95 0.9 } 3NE3 233 1 3 units 047 0.580
2 400 1 000 aR 135 000 85 1.0 A 3NE3 332-0B 1 3 units 047 0.683
450 175 000 90 1.0 A 3NE3 333 1 3 units 047 0.687
500 260 000 90 1.0 } 3NE3 334-0B 1 3 units 047 0.697
560 360 000 95 1.0 } 3NE3 335 1 3 units 047 0.692
630 600 000 100 1.0 } 3NE3 336 1 3 units 047 0.810
710 900 aR 800 000 105 1.0 } 3NE3 337-8 1 3 units 047 0.687
800 800 850 000 130 0.95 } 3NE3 338-8 1 3 units 047 0.686
900 690 920 000 165 0.95 } 3NE3 340-8 1 3 units 047 0.657
Fuse Systems
SITOR Semiconductor Fuses
SITOR LV HRC design
Sizes Ie Ue Opera- Breaking Power Vary- DT Order No. Price PU PS*/ PG Weight
tional I2t value loss ing per PU (UNIT, P. unit per PU
classes load SET, approx.
factor M)
A V AC A2s W WL kg
SITOR LV HRC design
With M12 female thread at both ends for direct busbar
mounting
3 630 1 000 aR 418 000 130 0.90 C 3NC3 336-6 1 3 units 047 0.980
5 710
800
900
569 000
819 000
1 160 000
140
150
160
0.90
0.90
0.95
D
C
D
3NC3 337-6
3NC3 338-6
3NC3 340-6
1
1
1
3 units
3 units
3 units
047
047
047
0.980
0.980
0.980
1 000 1 670 000 165 0.95 C 3NC3 341-6 1 3 units 047 0.980
1 100 800 1 910 000 175 0.95 D 3NC3 342-6 1 3 units 047 0.980
1 250 2 600 000 185 0.95 C 3NC3 343-6 1 3 units 047 0.980
With slotted blade contacts for M12 screw fixing,
mounting dimension: 110 mm
3 315 1 250 aR 72 500 80 0.95 D 3NC3 430-1 1 3 units 047 1.010
400 163 000 95 0.95 D 3NC3 432-1 1 3 units 047 1.010
500 290 000 115 0.90 D 3NC3 434-1 1 3 units 047 1.010
630 650 000 120 0.95 D 3NC3 436-1 1 3 units 047 1.010
800 1 100 985 000 145 0.90 D 3NC3 438-1 1 3 units 047 1.150
Fuse Systems
SITOR Semiconductor Fuses
SITOR LV HRC design
Sizes Ie Ue Opera- Breaking Power Vary- DT Order No. Price PU PS*/ PG Weight
tional I2t value loss ing per PU (UNIT, P. unit per PU
classes load SET, approx.
factor M)
A V AC A2s W WL kg
SITOR LV HRC design
With slotted blade contacts for M12 screw fixing, mounting
dimension: 260 mm
3 125 2 500 aR 34 500 78 1.0 D 3NE9 622-1C 1 1 unit 047 2.500
400
500
630
620 000 250
1 270 000 235
2 800 000 275
1.0
1.0
1.0
D
D
D
3NE9 632-1C
3NE9 634-1C
3NE9 636-1C
1
1
1
1 unit
1 unit
1 unit
047
047
047
2.350
2.350
2.350
5
710 900 620 000 150 0.9 D 3NE6 437-7 1 3 units 047 1.062
1 250 600 2 480 000 210 0.9 D 3NE9 450-7 1 3 units 047 1.072
1)
Special design
Fuse Systems
SITOR Semiconductor Fuses
SITOR, cylindrical fuse design
■ Overview ■ Benefits
SITOR cylindrical fuses protect power semiconductors from the • Cylindrical fuses have an extremely compact design and a
effects of short-circuits because the super quick disconnect correspondingly small footprint
characteristic is far quicker than that of conventional fuses. They • The cylindrical fuses have IEC and UL approval and are suit-
protect expensive devices and system components such as able for universal use worldwide.
solid-state contactors, electronic relays (solid state), converters
with fuses in the input and in the DC link, UPS systems and soft • The use of SITOR cylindrical fuses in the cylindrical fuse hold-
starters for motors up to 100 A. ers and bases has been tested with regard to heat dissipation
and maximum current loading. This makes planning and
5 The cylindrical design is approved for industrial applications.
The cylindrical fuse links comply with IEC 60269.
dimensioning easier and prevents consequential damage.
• The use of fuse holders as switch disconnectors expands the
Cylindrical fuse holders also comply with IEC 60269 and area of application of these devices and increases operating
UL 512. The cylindrical fuse holders for 10 x 38 mm and safety.
14 x 51 mm have been tested and approved as fuse switch dis-
connectors and the cylindrical fuse holders for 22 x 58 mm as
fuse disconnectors according to the switching device standard
IEC 60947-3. The utilization category and the tested current and
voltage values are specified in the Table "Technical Specifica-
tions".
The cylindrical fuse holders have been specially developed for
the application of SITOR fuse links with regard to heat tolerance
and heat dissipation and are therefore not recommended for
standard applications.
Cylindrical fuse bases do not offer the same comprehensive
touch protection as the fuse holders, but have better heat dissi-
pation. The single-pole cylindrical fuse bases for 14 x 51 mm
and 22 x 58 mm allow modular expansion to multipole bases.
■ Technical specifications
Sizes mm × mm 10 × 38 14 × 51 22 × 58
Cylindrical fuse links
3NC1 0, 3NC1 4, 3NC2 2
Standards IEC 60269-4; UL 248-13; CSA C22.2 No. 248.13
Approvals UL 248-13; UL File No. E167357; CSA C22.2 No. 248.13
Fuse holders, fuse bases
3NC1, 3NC2
Standards IEC 60269-2; EN 60947-3; UL 512; CSA C22.2 No. 39-M
Approvals UL 512; UL File No. E220063; CSA C22.2 No. 39-M
Rated voltage V AC 690
Rated current In A 32 50 100
Max. power dissipation of fuse links W 3 (6 mm2) 5 (10 mm2) 9.5 (35 mm2)
(conductor cross-section used) 4.3 (10 mm2) 6.5 (25 mm2) 11 (50 mm2)
Feeder terminals mm2 1.5 ... 25 1.5 ... 35 4 ... 50
Conductor cross-sections
• Solid and stranded mm2 1.5 ... 25 1.5 ... 35 4 ... 50
• AWG Conductor cross-section, solid and stranded AWG 18 ... 4 14 ... 2 10 ... 1/0
Utilization category Acc. to IEC 60947-3 22B/32 A/400 V AC 22B/50 A/400 V AC 20B/690 V AC
22B/10 A/690 V AC 22B/20 A/690 V AC
Rated conditional short-circuit current
• At 400 V kA 50 (32 A gG) 100 (50 A gG) 100 (100 A gG)
80 (80 A gG)
Fuse Systems
SITOR Semiconductor Fuses
SITOR, cylindrical fuse design
5
10 × 38 3 600/400 8 1.2 A 3NC1 003 1 10 units 047 0.008
6 20 1.5 } 3NC1 006 1 10 units 047 0.008
8 30 2 B 3NC1 008 1 10 units 047 0.006
10 60 2.5 } 3NC1 010 1 10 units 047 0.007
12 110 3 B 3NC1 012 1 10 units 047 0.006
16 150 3.5 } 3NC1 016 1 10 units 047 0.009
20 200 4.8 } 3NC1 020 1 10 units 047 0.016
25 250 6 } 3NC1 025 1 10 units 047 0.008
32 500 7.5 } 3NC1 032 1 10 units 047 0.010
14 × 51 1 660/7001) 1.2 5 B 3NC1 401 1 10 units 047 0.018
2 10 3 } 3NC1 402 1 10 units 047 0.020
3 15 2.5 B 3NC1 403 1 10 units 047 0.018
4 25 3 } 3NC1 404 1 10 units 047 0.018
5 690/7001) 9 1.5 B 3NC1 405 1 10 units 047 0.021
6 12 1.5 } 3NC1 406 1 10 units 047 0.022
10 20 4 } 3NC1 410 1 10 units 047 0.019
15 75 5.5 } 3NC1 415 1 10 units 047 0.020
20 120 6 } 3NC1 420 1 10 units 047 0.020
25 250 7 } 3NC1 425 1 10 units 047 0.020
30 300 9 B 3NC1 430 1 10 units 047 0.020
32 700 7.6 } 3NC1 432 1 10 units 047 0.028
40 900 8 } 3NC1 440 1 10 units 047 0.020
50 1 800 9 } 3NC1 450 1 10 units 047 0.001
22 × 58 20 690/7001) 220 4.6 B 3NC2 220 1 5 units 047 0.056
25 300 5.6 B 3NC2 225 1 5 units 047 0.053
32 450 7 B 3NC2 232 1 5 units 047 0.055
40 700 8.5 B 3NC2 240 1 5 units 047 0.055
50 1 350 9.5 } 3NC2 250 1 5 units 047 0.056
63 2 600 11 } 3NC2 263 1 5 units 047 0.051
80 5 500 13.5 } 3NC2 280 1 5 units 047 0.055
1)
100 600/700 8 000 16 } 3NC2 200 1 5 units 047 0.052
Cylindrical fuse links with striking pin,
operational class aR
14 × 51 10 690/7001) 90 4 B 3NC1 410-5 1 10 units 047 0.001
15 100 5.5 B 3NC1 415-5 1 10 units 047 0.001
20 500 6 B 3NC1 420-5 1 10 units 047 0.020
25 400 7 C 3NC1 425-5 1 10 units 047 0.001
30 500 9 C 3NC1 430-5 1 10 units 047 0.020
32 600 7.6 B 3NC1 432-5 1 10 units 047 0.022
40 900 8 B 3NC1 440-5 1 10 units 047 0.020
50 2 000 9 B 3NC1 450-5 1 10 units 047 0.020
Fuse Systems
SITOR Semiconductor Fuses
SITOR, cylindrical fuse design
5
3P } 3NC1 093 1 4 units 047 0.200
14 × 51 1P } 3NC1 491 1 6 units 047 0.102
2P } 3NC1 492 1 3 units 047 0.203
3P B 3NC1 493 1 2 units 047 0.279
22 × 58 1P } 3NC2 291 1 1 unit 047 0.204
2P } 3NC2 292 1 3 units 047 0.358
3P B 3NC2 293 1 2 units 047 0.512
Cylindrical fuse holders
Can be used as fuse switch disconnectors,
with alarm switches for fuse links with striking pin1)
14 × 51 1P 690 B 3NC1 491-5 1 6 units 047 0.130
22 × 58 1P B 3NC2 291-5 1 6 units 047 0.181
1)
Please observe the utilization category and current/voltage values speci-
fied in the "Technical specifications" table.
Fuse Systems
SITOR Semiconductor Fuses
NEOZED and DIAZED design, SILIZED
■ Overview ■ Benefits
SILIZED is the brand name of the NEOZED fuses (D0 fuses) and • SILIZED fuses have an extremely compact design. This
the DIAZED fuses (D fuses) with super quick characteristic for means they have a very small footprint – particularly the
semiconductor protection. The fuses are used in combination NEOZED version.
with fuse bases, fuse screw caps and accessory parts of the • The rugged and well-known DIAZED design complies with
standard fuse system. IEC 60269-3. It is globally renowned and can be used in many
SILIZED fuses protect power semiconductors from the effects of countries.
short-circuits because the super quick disconnect characteristic • A huge range of fuse bases and accessories are available for
is far quicker than that of conventional fuses. They protect ex-
pensive devices and system components, such as semiconduc-
the NEOZED and DIAZED versions of the SILIZED fuses. This
increases the application options in many devices. 5
tor contactors, static relays, converters with fuses in the input
and in the DC link, UPS systems and soft starters for motors
up to 100 A.
When using fuse bases and fuse screw caps made of molded
plastic, always heed the maximum permissible power loss
values due to the high power loss (power dissipation) of the
SILIZED fuses. When using these components, the following
maximum permissible power loss applies:
• NEOZED D02: 5.5 W
• DIAZED DII: 4.5 W
• DIAZED DIII: 7.0 W
For this reason, sometimes a thermal permanent load of only
50 % is possible.
The DIAZED screw adapter DII for 25 A is used for the 30 A fuse
link.
■ Technical specifications
SILIZED fuse links, SILIZED fuse links,
NEOZED design DIAZED design
5SE1 3 5SD4
Standards DIN VDE 0636-3; IEC 60269-3;
DIN VDE 0636-4; IEC 60269-4
Operational class gR
Characteristic Super quick
Rated voltage Un V AC 400 500
V DC 250 500
Rated current In A 10 ... 63 16 ... 100
Rated breaking capacity kA AC 50
kA DC 8
Mounting position Any, but preferably vertical
Non-interchangeability Using adapter sleeves Using screw adapter or adapter sleeves
Resistance to climate °C up to 45 at 95 % rel. humidity
Ambient temperature °C -5 ... +40, humidity 90 % at 20
Fuse Systems
SITOR Semiconductor Fuses
NEOZED and DIAZED design, SILIZED
5 D01 10
16
400/250 73
120
6.9
6.2
B
B
5SE1 310
5SE1 316
1 10 units
1 10 units
016
016
0.007
0.007
Fuse Systems
Photovoltaic fuses
N Cylindrical fuse design
There is still no uniform international or European standard for PV
■ Overview fuses and fuse holders, but work on integrating the special re-
In spite of the lack of uniform international and European stan- quirements of these fuses in the IEC 60269 set of standards is in
dards, cylindrical fuses for photovoltaic applications are already progress. UL approval for the international market will be avail-
being deployed in many European countries. able soon.
The fuse inserts have a rated voltage of 1000 V and a high oper- The correct selection and dimensioning of these fuses must take
ational class of gPV for the protection of PV modules and their account of the specific operating conditions as well as the data
connecting cables. of the PV modules when calculating the voltage and the current.
The cylindrical fuse holders can be supplied in single-pole and
■ Benefits
two-pole versions with and without signal detectors. In the case
of devices with signal detector, a small electronic device with • Protection of the module connection leads and the modules in
5
LED is located behind an inspection window in the plug-in mod- case of reverse currents
ule. If the inserted fuse link is tripped, this is indicated by the LED • Safe disconnection in case of fault currents reduces the risk of
flashing. fire due to DC electric arcs
The fuse holders size 10 mm x 38 mm have a sliding catch that • Safe isolation when the fuse holder is open
enables the removal of individual devices from the assembly. • A flashing LED on the fuse holder indicates when the fuse link
The infeed can be from the top or the bottom. Because the cylin- disconnects. This enables fast detection during runtime.
drical fuse holders are fitted with the same anti-slip terminals at
the top and the bottom, the devices can also be rail-mounted at
the top or the bottom.
The PV cylindrical fuse holders comply with IEC 60269-2 and are
regarded as fuse disconnectors in the sense of the switching
device standard IEC 60947. Under no circumstances are they
suitable for switching loads.
■ Technical specifications
Cylindrical fuse holders Cylindrical fuse links
3NW7 0. .-4 cylindrical fuse 3NW6 0.. -4 cylindrical fuse links
holders Size mm x mm 10 x 38
Size mm x mm 10 x 38 Standards IEC 60269-6 (draft)
Standards IEC 60269, IEC 60269-6 (draft), Approvals UL 248-13 (available soon)
IEC 60947
Operational class gPV
Approvals UL 712 (available soon)
Rated voltage Un V DC 1000 at time constant (L/R) 3 ms
Rated voltage Un V DC 1000
Rated current In A DC 4 ... 16
Rated current In A DC 25
Rated breaking capacity
Rated short-circuit strength kA DC 30
kA 30
Mounting position Any, but preferably vertical
Switching capacity
• Utilization category AC-20B, DC-20B Ambient temperature °C -5 ... +40,
(switching without load) Humidity 90 % at +20
Max. power dissipation of
the fuse link W 3.4
Rated impulse withstand
voltage kV 6
Overvoltage category II
Pollution degree 2
No-voltage changing of fuse links
Yes
Sealable when installed
Yes
Mounting position Any, but preferably vertical
Current direction Any (signal detector with antipar-
allel LED)
Degree of protection acc. to IP20, with connected conductors
IEC 60529
Terminals are touch-protected accord-
ing to BGVA3 at the incoming and out- Yes
going feeder
Ambient temperature °C -5 ... +40,
Humidity 90 % at +20
Conductor cross-sections
• finely stranded, with end sleeve mm2 0.75 ... 25
• AWG (American Wire Gauge) 18 ... 4
Tightening torques Nm 1.2
Fuse Systems
Photovoltaic fuses
Cylindrical fuse design N
■ Selection and ordering data
Sizes In Un Pv DT Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
SET, approx.
M)
mm x mm A DC V DC W kg
Cylindrical fuse links, operational class gPV
10 x 38 4 1000 1.4 B 3NW6 004-4 1 10 units 018 0.008
5
6 2.0 B 3NW6 001-4 1 10 units 018 0.010
8 1.8 B 3NW6 008-4 1 10 units 018 0.008
10 2.5 B 3NW6 003-4 1 10 units 018 0.010
12 2.0 B 3NW6 006-4 1 10 units 018 0.010
16 2.7 B 3NW6 005-4 1 10 units 018 0.010
Number of In For fuse links of size Mount- DT Order No. Price PU PS*/ PG Weight
poles ing per PU (UNIT, P. unit per PU
width SET, approx.
M)
A DC mm x mm MW kg
Cylindrical fuse holders with signal detector
1P 25 10 x 38 1 B 3NW7 014-4 1 12 units 018 0.007
2P 25 10 x 38 2 B 3NW7 024-4 1 6 units 018 0.014
Overvoltage Protection
Devices
6/2 Introduction
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical specifications
under Entry List:
- Updates
- Downloads
- FAQ
- Manuals
- Characteristic curves
- Certificates
and at
www.siemens.com/lowvoltage/
configurators
- Configurators
Introduction
■ Overview
Devices Page Field of application Standards Used in
Non-residential
Residential
buildings
buildings
Industry
Lightning arresters, type 1 6/3 With plug-in protective modules for EN 61643-11 ✓ ✓ ✓
TN-C, TN-S and TT systems
Rated voltage 350 V AC for lightning
currents from 25 kA to 100 kA.
6
All versions with remote signaling
contact.
Surge arresters, type 2 6/7 With plug-in protective modules for EN 61643-11 ✓ ✓ ✓
TN-C, TN-S and TT systems
Rated voltage 350 V AC, rated
discharge surge current 20 kA and
discharge surge current 40 kA.
For installation in sub-distribution
boards.
Surge arresters, type 3 6/11 With plug-in protective modules for EN 61643-11 ✓ ✓ ✓
single-phase and three-phase systems.
Rated voltage, single-phase
24 V AC/DC, 60 V, 120 V, 230 V and
three-phase 230/400 V AC.
For installation as close as possible
upstream from the terminal equipment.
Accessories for surge arresters 6/12 Plug-in parts for lightning and surge EN 61643-11 ✓ ✓ ✓
arresters and through-type terminals for
installation.
Surge arresters for measuring and 6/16 With plug-in protective modules for EN 61643-21 ✓ -- ✓
control technology measuring and control technology for
installation in signal circuits.
■ Overview ■ Benefits
Lightning arresters type 1 protect low-voltage systems against • The rated arrester voltage is a uniform 350 V AC. This in-
any overvoltage or high impulse currents that may be triggered creases safety in systems with extended voltage overshoots.
by a direct or indirect lightning strike. • All lightning arresters are fitted with a mechanical fault indica-
The protection level is lowered to 1.5 kV by the lightning arrester. tion, which does not require an extra power supply. This
means they can be installed in the precounter area, where
The lightning arresters are enclosed and are suitable for installa- electrical plants can be protected particularly effectively.
tion in the precounter area.
• The protective modules are plug-in versions. No dismantling
All spark gaps are tripped. For this reason, decoupling reactors of electrical wires required when replacing the protective
are no longer required for the installation of overvoltage protec- modules. When taking insulation measurements, the protec-
tion devices. tive modules are simply removed in order to ensure discon-
nection from the power supply.
The lightning arresters are tested using a wave-shaped 25 kA to
100 kA lightning impulse current with waveform 10/350 µs. • All lightning arresters have a remote signaling contact, which
signals if the device fails. 6
■ Technical specifications
5SD7 411-1 5SD7 412-1 5SD7 413-1 5SD7 414-1
Standards IEC 61643-11; EN 61643-11
Approvals -- UL/cUL UL/cUL UL/cUL
Rated voltage UN V AC 240 240/415
Rated arrester voltage UC
• L/N, N/PE, L/PEN V AC 350
Lightning impulse current Iimp (10/350 μs)
• L/N or L/PEN, 1P/3P kA 25 25 25/75 25/75
• N/PE kA -- 100 -- 100
Rated discharge surge current In (8/20 μs)
• L/N or L/PEN, 1P/3P kA 25 25 25/75 25/75
• N/PE kA -- 100 -- 100
Protection level Up
• L/N, N/PE, L/PEN kV ≤ 1.5
Follow current discharge capacity Ifi (AC)
• L/N or L/PEN for 264 V/350 V kA 50/25 50/25 50/25 50/25
• N/PE A -- 100 -- 100
Response time tA
• L/N or L/PEN ns ≤ 100 ≤ 100 ≤ 100 ≤ 100
• L-(N)-PE ns -- ≤ 100 -- ≤ 100
Max. back-up fuse Acc. to IEC 61643-11
• For parallel connection A 315 gL/gG
• For series connection A 125 gL/gG
Short-circuit strength with max. back-up fuse kArms 50
Temperature range °C -40 ... +80
Degree of protection IP20, with connected conductors
Conductor cross-section
• Finely stranded mm2 2.5 ... 25
• Solid mm2 2.5 ... 35
Mounting width Acc. to DIN 43880 MW 2 4 6 8
Remote signaling (RS) Yes
• Contact type Floating CO contact (plug-in)
• Operational voltage, max. V AC 250
V DC 125
• Operational current, max.
- Resistive/inductive load A AC 1/1
- Resistive/inductive load mA DC 200/30
• Conductor cross-section
- Finely stranded mm2 1.5
- Solid mm2 1.5
■ Overview ■ Benefits
Combination surge arresters type 1 and type 2 protect low- • The rated arrester voltage is a uniform 350 V AC. This in-
voltage systems against the overvoltages and high currents creases safety in systems with extended voltage overshoots.
triggered by direct lightning strikes. They are tested by wave- • All combination surge arresters are fitted with a mechanical
shaped lightning impulse, 25 KA to 100 kA with waveform fault indication, which does not require an extra power supply.
10/350 µs.
• The protective modules are plug-in versions. No dismantling
The protection level is lowered to 1.5 kV by the combination of electrical wires required when replacing the protective
surge arresters. modules. When taking insulation measurements, the protec-
tive modules are simply removed in order to ensure discon-
A thermal isolating arrester disconnector offers a high degree of
nection from the power supply.
protection against overload.
• The same type 2 overvoltage protective modules are used as
All spark gaps are tripped. For this reason, decoupling reactors for the slim version of the surge arresters (5SD7 42.). This
6
are no longer required for the installation of overvoltage protec- simplifies stock-keeping.
tion devices.
• All combination surge arresters have a remote signaling
contact, which signals if the device fails.
■ Technical specifications
5SD7 441-1 5SD7 442-1 5SD7 443-1 5SD7 444-1
Standards IEC 61643-11; EN 61643-11
Approvals -- KEMA, UL/cUL KEMA, UL/cUL KEMA, UL/cUL
Rated voltage UN V AC 240 240/415
Rated arrester voltage UC
• L/N, N/PE, L/PEN V AC 350
Lightning impulse current Iimp (10/350 μs)
• L/N or L/PEN, 1P/3P kA 25 25 25/75 25/75
• N/PE kA -- 100 -- 100
Rated discharge surge current In (8/20 μs)
• L/N or L/PEN, 1P/3P kA 25 25 25/75 25/75
• N/PE kA -- 100 -- 100
Protection level Up
• L/N, N/PE, L/PEN kV ≤ 1.5
Follow current discharge capacity Ifi (AC)
• L/N or L/PEN kA 25 25 25 25
• N/PE kA -- 100 -- 100
Response time tA
• L/N or L/PEN ns ≤ 25 ≤ 100 ≤ 100 ≤ 100
• L-(N)-PE ns -- ≤ 100 -- ≤ 100
Max. back-up fuse Acc. to IEC 61643-11
• For parallel connection A 315 gL/gG
• For series connection A 125 gL/gG
Short-circuit strength with max. back-up fuse kArms 25
Temperature range °C -40 ... +80
Degree of protection IP20, with connected conductors
Conductor cross-section
• Finely stranded mm2 2.5 ... 25
• Solid mm2 2.5 ... 35
Mounting width Acc. to DIN 43880 MW 2 4 6 8
Visual function/fault indication Yes
Remote signaling (RS) Yes
• Contact type Floating CO contact (plug-in)
• Operational voltage, max. V AC 250
V DC 125
• Operational current, max.
- Resistive/inductive load A AC 1/1
- Resistive/inductive load mA DC 200/30
• Conductor cross-section
- Finely stranded mm2 1.5
- Solid mm2 1.5
■ Overview ■ Benefits
Surge arresters type 2 are used downstream of lightning arrest- • The rated arrester voltage is a uniform 350 V AC. This in-
ers type 1 in main distribution boards or sub-distribution boards. creases safety in systems with extended voltage overshoots.
They protect low-voltage systems against transient overvol- • All type 2 surge arresters are fitted with a mechanical fault
tages. indication, which does not require an extra power supply.
The type 2 surge arrester lowers the protection level to • A thermal isolating arrester installed in each device offers a
1.4 / 1.5 kV. A remote signaling contact signals whether a high degree of protection. In the event of overload, the surge
protective module has been disconnected from the network arrester is disconnected from the mains - the plant continues
by the thermal arrester disconnector or whether it is just not running
plugged in. • The protective modules are plug-in versions. No dismantling
All spark gaps are tripped. For this reason, decoupling reactors of electrical wires required when replacing the protective
are no longer required for the installation of overvoltage protec- modules. When taking insulation measurements, the protec-
tion devices.
To ensure fault-free operation of photovoltaic systems, it is
tive modules are simply removed in order to ensure discon-
nection from the power supply. 6
essential to have standardized protection against lightning and • All surge arresters are available with a remote signaling
overvoltages. SPDs (5SD7 483-.) on the DC side protect the contact, which signals if the device fails.
photovoltaic generator and the inverter against overvoltages.
The SPDs 5SD7 473-. and 5SD7 485-. are especially available
for protecting IT systems.
■ Technical specifications
Surge arresters, standard design
N/PE Single-pole Multipole
Plug-in Plug-in 3P 4P 3P 4P 3P
5SD7 481-0 5SD7 461-. 5SD7 463-. 5SD7 464-. 5SD7 473-. 5SD7 485-. 5SD7 483-.
Standards IEC 61643-11; EN 61643-11
Approvals KEMA --
Rated voltage UN V AC 240 240 240/415 240/415 500 240/415 --
Rated arrester voltage UC
• L/N V AC -- 350 -- -- -- -- --
• L/N or L/PEN V -- -- 350 AC 350 AC 580 AC 440 AC 1000 DC
• N/PE V AC 260 -- -- 260 -- -- --
Rated discharge surge current In (8/20 μs)
• L/N kA -- 20 -- -- -- -- --
• L/N or L/PEN, 1P kA -- -- 20 20 15 20 15
• N/PE kA 20 -- -- 20 -- -- --
Max. discharge surge current Imax (8/20 μs)
• L/N kA -- 40 -- -- -- -- --
• L/N or L/PEN, 1P kA -- -- 40 40 -- -- 30
• L/N or L/PEN, 1P/multipole kA -- -- -- -- 30 40 --
• N/PE kA 40 -- -- 40 -- -- --
Lightning impulse current Iimp (10/350 μs) kA 12 --
Protection level Up
• L/N or L/PEN kV -- ≤ 1.4 ≤ 1.4 ≤ 1.4 ≤ 2.5 ≤ 2.2 ≤5
• N/PE kV ≤ 1.5 -- -- ≤ 1.5 -- -- --
Response time tA
• L/N or L/PEN ns -- ≤ 25 ≤ 25 ≤ 25 ≤ 25 ≤ 25 ≤ 25
• N/PE ns ≤ 100 -- -- ≤ 100 -- -- --
Max. back-up fuse Acc. to IEC 61643-11
• For parallel connection A 125 gL/gG
• For series connection A 63 gL/gG
Short-circuit strength kArms 25
with max. back-up fuse
Temperature range °C -40 ... +80
Degree of protection IP20, with connected conductors
Conductor cross-section
• Finely stranded mm2 1.5 ... 25
• Solid mm2 1.5 ... 35
Mounting width according to DIN 43880 MW 1 1 3 4 3 4 3
Visual function/fault indication Yes
• 3P, plug-in
For protecting the DC part of the photovoltaic
systems up to 1000 V DC acc. to IEC 60364-7-712
- Without remote signaling 15/30 3 A 5SD7 483-0 1 1 unit 008 0.344
- With remote signaling 15/30 3 A 5SD7 483-1 1 1/44 units 008 0.352
6
• 4P, plug-in, 4+0 circuit
For IT systems with N-conductor incorporated in the
cable
- Without remote signaling 20/40 4 A 5SD7 485-0 1 1/44 units 008 0.445
- With remote signaling 20/40 4 A 5SD7 485-1 1 1 unit 008 0.455
• 3P
For TN-C systems
- Without remote signaling 20/40 36 (2) A 5SD7 423-0 1 1 unit 008 0.320
- With remote signaling 20/40 36 (2) B 5SD7 423-1 1 1 unit 008 0.317
• 4P
For TN-S and TT systems
- Without remote signaling 20/40 48 (2 2/3) A 5SD7 424-0 1 1 unit 008 0.407
- With remote signaling 20/40 48 (2 2/3) A 5SD7 424-1 1 1 unit 008 0.423
■ Overview ■ Benefits
Type 3 surge arresters are installed after the type 2 surge arrest- • The protective modules are plug-in versions. No mounting
ers in sub-distribution boards close to the loads in single or work required when replacing the protective modules
multiphase systems and further limit the overvoltage in order to • All type 3 surge arresters are fitted with a fault indication,
protect the connected loads. which does not require an extra power supply
• In the event of a power failure, a remote signaling is output
over an optocoupler with open collector output.
■ Technical specifications
Multipole surge arresters, plug-in
2P
5SD7 432-1 5SD7 432-2 5SD7 432-3 5SD7 432-4
4P
5SD7 434-1
6
Standards IEC 61643-11; EN 61643-11
Approvals KEMA -- KEMA
Rated voltage UN V AC 230 120 60 24 230/400
Rated load current IL (at 30 °C) A 26 26 26 26 3 × 26
Rated arrester voltage UC V AC 253 150 100 34 335
Rated discharge surge current In (8/20 μs) kA 3 2.5 2.5 1 1.5
Max. discharge surge current Imax (8/20 μs) kA 10 10 6.5 2 4.5
Combined surge Uoc kV 6 6 4 2 4
Protection level Up L–N/L(N)–PE V ≤ 1500/≤ 600 ≤ 850/≤ 350 ≤ 700/≤ 250 ≤ 550/≤ 100 ≤ 1200
Response time tA ns ≤ 100 ≤ 100 ≤ 100 ≤ 100 ≤ 100
Required back-up fuse, max. A 25 gL/gG 25 gL/gG 25 gL/gG 25 gL/gG 25 gL/gG
Temperature range °C -40 ... +85
Degree of protection IP20, with connected conductors
Conductor cross-section
• Finely stranded mm2 0.2 ... 4
• Solid mm2 0.2 ... 2.5
Mounting width Acc. to DIN 43880 MW 1 1 1 1 2
Visual function/fault indication Yes
Remote signaling (RS) Yes
• Contact type NC contacts
• Operational voltage, max. V AC 250
• Operational current, max. 3
• 4P
With remote signaling 230/400 2 A 5SD7 434-1 1 1 unit 008 0.135
Link rails
■ Overview ■ Benefits
Link rails let you combine 1-pole surge arresters to create These link rails allow cable lengths to be reduced to a minimum
complete solutions for multiphase systems. and save time during mounting.
■ Technical specifications
Link rails
5SD7 490-2, 5SD7 490-3, 5SD7 490-4
Standards EN 60439-1
Busbar material SF-Cu F 24
Partition material
Busbar cross-section mm2
Plastic, cycolor 3600 temperature resistant ≥ 90 °C
16
6
Rated operational voltage Uc V AC 400
Rated current In
• Cross-section 16 mm2 A 80
Rated impulse withstand voltage Uimp kV 4
Test pulse voltage (1.2/50) kV 6.2
Rated conditional short-circuit current Icc kA 25
Resistance to climate
• Constant atmosphere acc. to DIN 50015 23/83; 40/92; 55/20
• Humid heat (acc. to IEC 68, Part 2-30) 28 cycles
Insulation coordination according to IEC 60664-1
• Overvoltage category III
• Pollution degree 2
Maximum busbar current Is/phase
• Cross-section 16 mm2 A 80
Maximum current in the arm IE/phase
• Cross-section 16 mm2 A 130
Configuration
■ More information
Selection of overvoltage protection devices
Situation Systems Basic protection
Which type of building do you For installation upstream of counters in main distribution boards
want to protect? or in combined main/sub-distribution boards
Generally speaking, all our
devices are suitable for resi-
dential buildings, office build-
ings, industrial and commercial
buildings.
Low risk buildings TN-S and TT systems Surge arresters, type 2
Narrow design
5SD7 424-0, 5SD7 424-1
6 Wide design
5SD7 464-0, 5SD7 464-1
With or without remote signaling
IT systems
with N-conductor incorporated in the
cable
Configuration
Only required if the distance between the main and sub-distribution boards is > 10 m
Only required if the distance between the main and sub-distribution boards is > 10 m
Only required if the distance between the main and sub-distribution boards is > 10 m
■ Overview ■ Benefits
The surge arresters for measuring and control technology are • The two-component design offers users maximum mainte-
overvoltage protection modules that comprise two parts, a basic nance convenience. The basic element is always a fixed inte-
element and a plug-in part. Their application area is the protec- gral part of the installation. There are therefore no laborious
tion of signal circuits. access problems during repair work, etc.
The cable shields of basic elements can be either directly or in- • The benefits:
directly grounded. - Two-part design comprising plug-in part and basic element
- Interruption-free and impedance neutral plugging in and
The mounting width of the new surge arrester is 1 MW. pulling out of the plug-in part
Through the number of integrated paths, it is possible to protect - Reverse polarity protection through mechanical encoding
up to four signal cores or two double cores against overvoltages. - An electric surge voltage resistant connection is made auto-
matically when it is snapped onto the standard mounting
rail – no laborious wiring of ground.
6 • The arrangement of suppressor diodes between signal cores
achieves a fine protection in connection with a fast response.
The low-limiting coupling of the suppressor diodes to the sig-
nal cores supports fast data transmission rates.
• The use of gas-filled surge arresters ensures a high discharge
capacity.
■ Technical specifications
5SD7 502-0 5SD7 520-1 5SD7 522-7 5SD7 530-3 5SD7 541-7 5SD7 550-4
IEC category/EN type C1/C2/C3/D1 C1/C2/C3/ C1/C2/C3/D1 C1/C2/C3/D1 C1/C2/C3/D1 C1/C2/C3/D1
D1/B2
Max. continuous voltage UC
• Direct voltage V DC 68 185 40 5.2 40 14
• AC voltage V AC 48 130 28 3.6 28 9.8
Rated current IN mA 2000 450 450 450 300 450
Lightning test current Iimp 10/350 μs Per path kA 5 -- 2.5 2.5 2.5 2.5
Rated discharge current In 8/20 μs
• Core - Core kA -- 10 10 10 -- 10
• Core - Ground kA 20 10 10 10 10 10
Total surge current IN 8/20 μs kA 40 10 20 20 20 20
Output voltage limit at 1 kV/μs
• Core - Core V -- ≤ 300 ≤ 55 ≤ 15 -- ≤ 25
• Core - Ground V ≤ 600 ≤ 300 ≤ 450 ≤ 15 ≤ 55 ≤ 25
Residual voltage at In
• Core - Core V -- ≤ 160 ≤ 55 ≤ 15 -- ≤ 25
(C2/5 kA)
• Core - Ground V -- ≤ 160 -- ≤ 30 ≤ 55 ≤ 40
(C2/5 kA)
Response time tA
• Core - Core ns -- ≤ 500 ≤1 ≤ 500 -- ≤ 500
• Core - Ground ns ≤ 100 ≤ 500 ≤ 100 ≤ 500 ≤1 ≤ 500
Insertion loss A E
• Symmetrical in the 50-Ω system dB -- -- Typ. 0.5 -- -- --
(1.5 MHz)
• Asymmetrical in the 50-Ω system dB 0.1 (1 MHz) -- -- -- 0.5 (1.5 MHz) --
• Symmetrical in the 100-Ω system dB -- Typ. 0.2 -- 0.2 (5 MHz) -- 0.2 (5 MHz)
(5 MHz)
Limit frequency fG (3 dB)
• Symmetrical in the 50-Ω system MHz -- -- Typ. 8 -- -- --
• Asymmetrical in the 50-Ω system MHz -- -- -- -- Typ. 8 --
• Symmetrical in the 100-Ω system MHz -- Typ. 70 -- Typ. 70 -- Typ. 70
Resistor per path Ω -- -- 2.2 2.2 4.7 2.2
Temperature range °C -40 ... +85
Degree of protection acc. to IEC 60529/EN 60529 IP20
Flammability class acc. to UL 94 V0
Test standards EN 61643-21 IEC 61643-21 EN 61643-21 IEC 61643-21 EN 61643-21 IEC 61643-21
• For plug-in parts with protection circuit for a 1 B 5SD7 522-0 1 1 unit 008 0.057
2-wire ungrounded signal circuit
• Gas arrester between terminals 3/4 (GND) and 9/10
• For 5SD7 522-1 and 5SD7 550-4 plug-in parts
• For plug-in parts with protection circuit for four con- 1 B 5SD7 541-1 1 1 unit 008 0.056
ductors single-sided grounded signal circuit
• Jumper between terminals 3/4 (GND) and 9/10
• For 5SD7 541-7 plug-in parts
• Jumper between terminals 3/4 (GND) and 9/10 1 B 5SD7 500-0 1 1 unit 008 0.050
• For 5SD7 502-0 plug-in parts
Plug-in parts - PROFIBUS 1 B 5SD7 530-3 1 1 unit 008 0.020
• Protection for 2 signal cores with shared reference
potential
• For 5SD7 512-1 basic element
Plug-in parts for analog telecommunication 1 B 5SD7 520-1 1 1 unit 008 0.020
interfaces
• Protection for 2-wire Telecom cable
(Uk0 or T-DSL)
• For 5SD7 512-1 basic element
Plug-in parts, 24 V AC 1 B 5SD7 522-7 1 1 unit 008 0.024
• Protection for 2-wire ungrounded signal circuit.
• Miniature protection element between the connected
cores
• For 5SD7 522-0 and 5SD7 522-1 basic elements
Plug-in parts, 12 V DC 1 B 5SD7 550-4 1 1 unit 008 0.026
• Protection for field bus systems and signal circuits in
3- or 4-wire method
• For 5SD7 522-0 and 5SD7 522-1 basic elements
Plug-in parts, 24 V DC 1 B 5SD7 541-7 1 1 unit 008 0.026
• Protection for 4 signal cores with shared reference
potential
• For 5SD7 541-1 basic element
Plug-in parts, 2-wire 1 B 5SD7 502-0 1 1 unit 008 0.020
• Coarse protection for 2 single-sided signal leads
• For 5SD7 500-0 basic element
Notes
Switch Disconnectors
7/26
up to 200 A
Introduction
7/110 With fuse monitoring 7
7/114 Accessories
7/27 General data 7/117 Assembly kits for distribution systems
SENTRON 3KA, 3KE Switch
SENTRON 3NJ4, 3NJ5 In-Line Fuse
Disconnectors up to 1000 A
Switch Disconnectors up to 2000 A
7/31 Introduction
7/118 Introduction
7/34 Floor mounting
7/121 1-pole switchable
7/39 Molded-plastic enclosures
7/122 3-pole switchable
7/40 Accessories
7/123 Accessories
SENTRON 3KL Switch
Disconnectors with Fuses
up to 800 A
Technical Information
7/43 Introduction
can be found at
7/45 Floor mounting
www.siemens.com/lowvoltage/support
7/47 Front mounting
7/48 Accessories under Product List:
- Technical Specifications
SENTRON 3KM Switch under Entry List:
Disconnectors with Fuses and - Updates
Isolating Plug Connector - Download
- FAQ
up to 400 A - Manuals
7/52 Introduction - Characteristic curves
7/54 For snapping onto busbars - Certificates
7/55 Accessories and at
www.siemens.com/lowvoltage/configurators
8UC Door-Coupling Rotary - Configurators
Operating Mechanisms
7/57 For 3K switch disconnectors
7/62 Individual parts
7/63 Operating mechanisms for fixed
mounting
Switch Disconnectors
Introduction
■ Overview
Order No. Page
Switch disconnectors
Main and EMERGENCY-STOP switches 16 A to 250 A 3LD 7/3
• Devices for front mounting, floor mounting with door-coupling rotary operating
mechanism, distribution board mounting or in molded-plastic enclosures
• Front mounting with four-hole and center hole arrangement
• 3-, 4- and 6-pole versions
3LD • 3- and 4-pole load transfer switches
• Solar plant isolators 800 V DC
7 5TE1
In-line switch disconnectors with fuses, plug-in type, up to 630 A 3NJ62 7/64
• 2-, 3- and 4-pole versions
• Suitable for NH and BS 88 fuse systems
• Manually operated or with motorized operating mechanism
3NJ62
• Optionally with integrated current transformers, auxiliary switches and electronic
fuse monitoring
3NP1
In-line fuse switch disconnectors up to 2000 A 3NJ4, 3NJ5 7/118
• 1- and 3-pole switchable versions
• Versions for secondary-side fusing of transformers
• In-line incoming versions up to 2000 A with isolating links
• Connection components are available for flat connection, stud bolt connection, sad-
dle terminal connection, prism terminal connection and box terminal connection
• Versions with/without integratable current transformer
• Versions with/without electronic fuse monitoring
3NJ4/3NJ5
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Introduction
■ Overview
7
3
7
6
3
1
5
NSG0_00112a
3 Auxiliary switch 1 NO + 1 NC
The 3LD main and EMERGENCY-STOP switches are manually The 3LD switches for 16 to 250 A are approved according to
operated switch disconnectors according to IEC 60947-3/ UL 508 and can be used as "manual motor controllers" and
EN 60947-3 and comply with the conditions for switch discon- "motor disconnects".
nectors.
Maintenance personnel can protect themselves against unau-
In EN 60204-1, main control switches are called "disconnector thorized startup with padlocks (up to three can be fitted).
units", while EMERGENCY-STOP switches are termed "devices
for emergency shutdown". The 3LD switches can be used in any mounting position.
■ Application
The 3LD switches are used for switching main and auxiliary cir- They can be used as:
cuits, but also for switching induction motors and other loads • ON-OFF switches
during maintenance and repair work.
• EMERGENCY-STOP switches
• Main control switches according to EN 60204-1.
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Introduction
■ Design
Construction of the contacts
Each switch has three adjacent contact elements1). A fourth
leading contact for switching the N conductor, a continuous
PE terminal, an auxiliary switch (1 NO + 1 NC) can be fitted to
each side of the switch. The auxiliary switches operate as lead-
ing contacts on opening. On opening, the NO contact opens be-
fore the main contacts, so that a contactor carries the switching
capacity in the circuit and the maintenance or safety switch
switches at zero current. On closing, the auxiliary switch
switches later than or at the same time as the main contacts. 3LD2 704-0TK53 switch 3LD2 222-0TK1 switch
for front mounting for front mounting
Construction of rotary operating mechanisms with rotary operating mechanism with knob
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Introduction
■ Technical specifications
Standards IEC 60947-3
Switches Type 3LD2 0 3LD2 1 3LD2 2 3LD2 5 3LD2 7 3LD2 8 3LD2 3 3LD2 4
Rated insulation voltage Ui V 690
Rated operational voltage Ue V AC 690
Rated frequency Hz 50 ... 60
Rated impulse withstand voltage Uimp V 690 690 690 690 690 690 690 690
Rated short-time withstand current (1 s current, rms value) A 340 640 640 1260 2000 2000 4000 4000
Short-circuit protection, max. back-up fuse (gG) A 20 25 40 63 100 125 160 250
Rated conditional short-circuit current with upstream fuses kArms 50 50 50 50 50 20 50 50
at AC 50/60Hz, 690V
Permissible let-through current of the fuse kA 3 3.5 4.5 6 10 10 15 15
Rated uninterrupted current Iu A 16 25 32 63 100 125 160 250
AC-21A load-break switch Rated operational current Ie A 16 25 32 63 100 125 160 250
AC-3 motor load switches Rating
In-service switching
of individual motors
At 220 ... 240 V
At 380 ... 440 V
At 660/690 V
kW
kW
kW
3.0
5.5
5.5
4.0
7.5
7.5
5.5
9.5
9.5
11.0
18.5
15.0
18.5
30.0
22.0
22.0
37.0
30.0
35.0
50.0
37.0
55.0
110.0
45.0
7
AC-23A main control switch Rating
Repair switch At 220 ... 240 V kW 4.0 5.0 6.0 11.0 18.5 22.0 45.0 75.0
frequent, but not in-service switching At 380 ... 440 V kW 7.5 9.5 11.5 22.0 37.0 45.0 75.0 132.0
of individual motors At 660/690 V kW 7.5 9.5 11.5 18.5 30.0 37.0 45.0 55.0
Power loss per conducting path at Ie W 0.5 1.1 1.8 4.5 7.5 12.0 36.0 36.0
Endurance mechanical Switching cycles 100 000
Switching frequency 1/h 50
Permissible ambient temperature °C -25 ... +55
Isolating features Up to max. V 690
Conductor cross-sections for main conductors 1)
Solid or stranded mm2 1 ... 6 1.5 ... 16 1.5 ... 16 2.5 ... 35 4 ... 50 4 ... 50 16 ...185 16 ... 185
Finely stranded with end sleeve (max.) mm2 4 10 10 16 35 35 150 150
Conductor cross-sections Copper cable AWG 18 ... 10 14 ... 8 14 ... 8 14 ... 6 12 ... 1 12 ... 1
Torque for terminal Nm 1.5 ... 2 2 ... 2.5 2 ... 2.5 2.5 ... 3 2.5 ... 3 2.5 ... 3 9.5 ... 10 9.5 ... 10
Touch protection acc. to EN 50274 Yes
Auxiliary switches
Rated insulation voltage Ui V 500
Rated operational voltage Ue V AC 500
Rated uninterrupted current Iu A 10
Rated operational current Ie, AC-15 At 120 V A 6
At 220 ... 240 V A 3
At 380 ... 415 V A 1.8
At 500 V A 1.4
Short-circuit protection, auxiliary switch, A 10
max. back-up fuse (gG)
Conductor cross-sections for auxiliary conductors
Connection type Terminals
Solid or stranded mm2 2 × (0.75 ... 2.5). 1 × 4
Finely stranded with end sleeve mm2 2 × (0.75 ... 1.5) 1 x 2.5
Torque for terminal Nm 0.8
Rated operational voltage Ue V AC 600 600 600 600 600 600 600 600
Rated uninterrupted current Iu A 10 20 30 60 100 125 160 250
Current rating A 600 A 600 A 600 -- -- -- -- --
Pilot duty P 600 P 600 P 600 -- -- -- -- --
Conventional thermal current Ith A 16 25 32 63 100 125 160 250
Maximum rated power (AC-3) 3 ∼ 120 V HP 1 3 3 5 10 15 -- --
Alternating current operating 240 V HP 3 7.5 10 15 30 40 40 50
mechanisms 40 ... 60 Hz 480 V HP 7.5 10 20 40 60 75 75 100
600 V HP 10 15 30 50 75 100 75 75
1 ∼ 120 V HP 0.5 2 2 3 -- -- -- --
240 V HP 1.5 3 3 10 -- -- -- --
Conductor cross-sections Cu cable AWG 18 ... 10 14 ... 8 14 ... 8 14 ... 6 12 ... 1 12 ... 1 1 ... MCM400
Torque Nm 1.5 ... 2 2 ... 2.5 2 ... 2.5 2.5 ... 3 2.5 ... 3 2.5 ... 3 10 10
1)
Depending on the cable infeed, only small cross-sections are possible with
devices in molded-plastic enclosures
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Front mounting
7 7.5
9.5
18.5
9.5
11.5
22.0
25
32
63
}
}
}
3LD2 103-0TK5@
3LD2 203-0TK5@
3LD2 504-0TK5@
1
1
1
1 unit
1 unit
1 unit
103
103
103
0.206
0.206
0.424
30 37.0 100 } 3LD2 704-0TK5@ 1 1 unit 103 0.501
37 45.0 125 A 3LD2 804-0TK5@ 1 1 unit 103 0.503
50 75.0 160 A 3LD2 305-0TK1@ 1 1 unit 103 2.100
110 132.0 250 A 3LD2 405-0TK1@ 1 1 unit 103 2.100
3+N -- 5.5 7.5 16 } 3LD2 003-1TL5@ 1 1 unit 103 0.217
3LD2 203-0TK51 7.5 9.5 25 A 3LD2 103-1TL5@ 1 1 unit 103 0.243
9.5 11.5 32 A 3LD2 203-1TL5@ 1 1 unit 103 0.243
18.5 22.0 63 A 3LD2 504-1TL5@ 1 1 unit 103 0.424
30.0 37.0 100 } 3LD2 704-0TK5@ 1 1 unit 103 0.501
+1)
} 3LD9 280-0B 1 1 unit 103 0.101
37.0 45.0 125 A 3LD2 804-0TK5@ 1 1 unit 103 0.503
+1)
} 3LD9 280-0B 1 1 unit 103 0.101
50 75.0 160 A 3LD2 305-1TL1@ 1 1 unit 103 2.600
110 132.0 250 A 3LD2 405-1TL1@ 1 1 unit 103 2.600
3LD2 704-0TK53 3 1 NO + 1 NC 5.5 7.5 16 A 3LD2 003-1TP5@ 1 1 unit 103 0.250
7.5 9.5 25 A 3LD2 103-1TP5@ 1 1 unit 103 0.249
9.5 11.5 32 A 3LD2 203-1TP5@ 1 1 unit 103 0.206
18.5 22.0 63 A 3LD2 504-1TP5@ 1 1 unit 103 0.424
30.0 37.0 100 A 3LD2 704-1TP5@ 1 1 unit 103 0.503
37 45.0 125 A 3LD2 804-1TP5@ 1 1 unit 103 0.503
50.0 75.0 160 A 3LD2 305-0TK1@ 1 1 unit 103 2.100
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
110.0 132.0 250 A 3LD2 405-0TK1@ 1 1 unit 103 2.100
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
3+N 1 NO + 1 NC 5.5 7.5 16 A 3LD2 003-2EP5@ 1 1 unit 103 0.272
7.5 9.5 25 A 3LD2 103-2EP5@ 1 1 unit 103 0.287
9.5 11.5 32 A 3LD2 203-1TL5@ 1 1 unit 103 0.243
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
18.5 22.0 63 A 3LD2 504-1TP5@ 1 1 unit 103 0.424
+1)
} 3LD9 250-0BA 1 1 unit 103 0.079
30.0 37.0 100 } 3LD2 704-0TK5@ 1 1 unit 103 0.501
+1)
} 3LD9 280-0B 1 1 unit 103 0.101
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
37.0 45.0 125 A 3LD2 804-0TK5@ 1 1 unit 103 0.503
+1)
} 3LD9 280-0B 1 1 unit 103 0.101
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
50.0 75.0 160 A 3LD2 305-1TL1@ 1 1 unit 103 2.600
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
110.0 132.0 250 A 3LD2 405-1TL1@ 1 1 unit 103 2.600
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1) 2)
4. Contact element as N conductor to be ordered separately, Auxiliary switches 1 NO + 1 NC to be ordered separately,
see "Accessories". see "Accessories".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Front mounting
Number and version of the Rated data at DT Order No. Price PU PS*/ PG Weight
contacts 50 ... 60 Hz, 380 ... 440 V per PU (UNIT, P. unit per PU
SET, approx.
Main contact Auxiliary P/AC-3 P/AC-23A Iu/ M)
elements contact AC-21A
elements
kW kW A kg
Main and EMERGENCY-STOP switches with rotary
operating mechanism/knob-operated mechanism
• Lockable in 0 position with up to 3 padlocks
• Degree of protection at front side IP65
• All versions with rotary operating mechanism
Exception: 3LD2 3 and 3LD2 4 with knob-operated mecha-
nism
• Including terminal cover for the infeed side
• Front plate
- 3LD2 0, 3LD2 1, 3LD2 2: 67 mm × 67 mm
- 3LD2 5 to 3LD2 8: 90 mm × 90 mm
- 3LD2 3 to 3LD2 4: 96 mm × 96 mm
Center-hole mounting Ø 22.5 mm
7
3 -- 5.5 7.5 16 A 3LD2 054-0TK5@ 1 1 unit 103 0.215
7.5 9.5 25 A 3LD2 154-0TK5@ 1 1 unit 103 0.215
9.5 11.5 32 A 3LD2 254-0TK5@ 1 1 unit 103 0.214
18.5 22 63 A 3LD2 555-0TK5@ 1 1 unit 103 0.443
3+N -- 5.5 7.5 16 A 3LD2 054-1TL5@ 1 1 unit 103 0.230
7.5 9.5 25 A 3LD2 154-1TL5@ 1 1 unit 103 0.256
9.5 11.5 32 A 3LD2 254-1TL5@ 1 1 unit 103 0.260
18.5 22 63 A 3LD2 555-0TK5@ 1 1 unit 103 0.443
3LD2 254-0TK53 +1)
} 3LD9 250-0BA 1 1 unit 103 0.079
3 1 NO + 5.5 7.5 16 A 3LD2 054-1TP5@ 1 1 unit 103 0.261
1 NC 7.5 9.5 25 A 3LD2 154-1TP5@ 1 1 unit 103 0.257
9.5 11.5 32 A 3LD2 254-0TK5@ 1 1 unit 103 0.214
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
18.5 22 63 A 3LD2 555-0TK5@ 1 1 unit 103 0.443
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
3+N 1 NO + 5.5 7.5 16 A 3LD2 054-2EP5@ 1 1 unit 103 0.276
1 NC 7.5 9.5 25 C 3LD2 154-2EP5@ 1 1 unit 103 0.304
9.5 11.5 32 A 3LD2 254-1TL5@ 1 1 unit 103 0.260
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
18.5 22 63 A 3LD2 555-0TK5@ 1 1 unit 103 0.443
+1)
} 3LD9 250-0BA 1 1 unit 103 0.079
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1) 4. Contact element as N conductor to be ordered separately,
see "Accessories".
2) Auxiliary switches 1 NO + 1 NC to be ordered separately,
see "Accessories".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Front mounting
Number and version Rated data at DT Order No. Price PU PS*/ PG Weight
of the contacts 50 ... 60 Hz, 380 ... 440 V per PU (UNIT, P. unit per PU
SET, M) approx.
Main contact Auxiliary P/AC-23A Iu
elements contact
elements
kW A kg
Main and EMERGENCY-STOP switches
with knob-operated mechanism
• Lockable in 0 position (can be modified to I position) with
max. 2 padlocks
• Degree of protection at front side IP65
• Including terminal cover for the infeed side
• Front plate
- 48 mm × 48 mm
Four-hole mounting
3 -- 7.5 16 A 3LD2 022-0TK1@ 1 1 unit 103 0.186
7 9.5
11.5
25
32
A
A
3LD2 122-0TK1@
3LD2 222-0TK1@
1
1
1 unit
1 unit
103
103
0.181
0.182
3+N -- 7.5 16 A 3LD2 022-1TL1@ 1 1 unit 103 0.206
9.5 25 A 3LD2 122-1TL1@ 1 1 unit 103 0.180
11.5 32 A 3LD2 222-0TK1@ 1 1 unit 103 0.182
+1)
} 3LD9 220-0B 1 1 unit 103 0.039
3 1 NO + 1 NC 7.5 16 A 3LD2 022-0TK1@ 1 1 unit 103 0.186
3LD2 222-0TK11 +2)
} 3LD9 200-5B 1 1 unit 103 0.046
9.5 25 A 3LD2 122-0TK1@ 1 1 unit 103 0.181
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
11.5 32 A 3LD2 222-0TK1@ 1 1 unit 103 0.182
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
3+N 1 NO + 1 NC 7.5 16 A 3LD2 022-1TL1@ 1 1 unit 103 0.206
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
9.5 25 A 3LD2 122-1TL1@ 1 1 unit 103 0.180
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
11.5 32 A 3LD2 222-0TK1@ 1 1 unit 103 0.182
+1)
} 3LD9 220-0B 1 1 unit 103 0.039
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1) 4. Contact element as N conductor to be ordered separately,
see "Accessories".
2) Auxiliary switches 1 NO + 1 NC to be ordered separately,
see "Accessories".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Front mounting
Number and version Rated data at DT Order No. Price PU PS*/ PG Weight
of the contacts 50 ... 60 Hz, 380 ... 440 V per PU (UNIT, P. unit per PU
SET, M) approx.
Main Auxiliary P/AC-23A Iu
contact contact
elements elements
kW A kg
Main and EMERGENCY-STOP switches
with knob-operated mechanism
• Lockable in 0 position (can be modified to I position)
with max. 2 padlocks
• Degree of protection at front side IP65
• Including terminal cover for the infeed side
• Front plate: 48 mm × 48 mm
Center-hole mounting Ø 22.5 mm
3 -- 7.5 16 A 3LD2 050-0TK1@ 1 1 unit 103 0.197
9.5 25 A 3LD2 150-0TK1@ 1 1 unit 103 0.191
3+N --
11.5
7.5
32
16
A
A
3LD2 250-0TK1@
3LD2 050-1TL1@
1
1
1 unit
1 unit
103
103
0.192
0.215
7
9.5 25 A 3LD2 150-0TK1@ 1 1 unit 103 0.191
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
11.5 32 A 3LD2 250-0TK1@ 1 1 unit 103 0.192
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
3LD2 150-0TK13
3 1 NO + 7.5 16 A 3LD2 050-0TK1@ 1 1 unit 103 0.197
1 NC +2)
} 3LD9 200-5B 1 1 unit 103 0.046
9.5 25 A 3LD2 150-0TK1@ 1 1 unit 103 0.191
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
11.5 32 A 3LD2 250-0TK1@ 1 1 unit 103 0.192
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
3+N 1 NO + 7.5 16 A 3LD2 050-1TL1@ 1 1 unit 103 0.215
1 NC +2)
} 3LD9 200-5B 1 1 unit 103 0.046
9.5 25 A 3LD2 150-0TK1@ 1 1 unit 103 0.191
+1)
} 3LD9 220-0B 1 1 unit 103 0.039
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
11.5 32 A 3LD2 250-0TK1@ 1 1 unit 103 0.192
+1)
} 3LD9 220-0B 1 1 unit 103 0.039
+2)
} 3LD9 200-5B 1 1 unit 103 0.046
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1) 4. Contact element as N conductor to be ordered separately,
see "Accessories".
2) Auxiliary switches 1 NO + 1 NC to be ordered separately,
see "Accessories".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Front mounting
Number and version of Rated data at DT Order No. Price PU PS*/ PG Weight
the contacts 50 ... 60 Hz, 380 ... 440 V per PU (UNIT, P. unit per PU
SET, approx.
M)
Main Auxiliary P/AC-3 P/AC-23A Iu
contact contact
elements elements
kW kW A kg
Main and EMERGENCY-STOP switches
with rotary operating mechanism/
knob-operated mechanism (6-pole)
• Lockable in 0 position with up to 3 padlocks
• Degree of protection at front side IP65
• All versions with rotary operating mechanism
Exception: 3LD2 3 and 3LD2 4 with knob-operated mecha-
nism
• Including terminal cover for the infeed side
• Front plate
7 - 3LD2 0, 3LD2 1, 3LD2 2: 67 mm × 67 mm
- 3LD2 5: 90 mm × 90 mm
- 3LD2 3 to 3LD2 4: 96 mm × 96 mm
Four-hole mounting
6 -- 7.5 9.5 25 A 3LD2 103-3VK5@ 1 1 unit 103 0.380
9.5 11.5 32 A 3LD2 203-3VK5@ 1 1 unit 103 0.381
18.5 22.0 63 A 3LD2 504-3VK5@ 1 1 unit 103 0.854
50 75 160 A 3LD2 305-3VK1@ 1 1 unit 103 3.900
110 132 250 A 3LD2 405-3VK1@ 1 1 unit 103 3.900
3LD2 103-3VK53 6 1 NO + 7.5 9.5 25 A 3LD2 103-4VP5@ 1 1 unit 103 0.432
1 NC
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
Number and version of Rated data at DT Order No. Price PU PS*/ PG Weight
the contacts 50 ... 60 Hz, 380 ... 440 V per PU (UNIT, P. unit per PU
SET, approx.
M)
Main Auxiliary P/AC-3 P/AC-23A Iu
contact contact
elements elements
kW kW A kg
Changeover switches
with knob-operated mechanism
• Black actuator
• Knob-operated mechanism on 3LD2 3 and 3LD2 4 is lockable,
on all other versions it is non-lockable
• Degree of protection at front side IP65
Four-hole mounting
3 -- 7.5 9.5 25 A 3LD2 123-7UK01 1 1 unit 103 0.374
9.5 11.5 32 A 3LD2 223-7UK01 1 1 unit 103 0.378
18.5 22.0 63 A 3LD2 524-7UK01 1 1 unit 103 0.841
30.0 37.0 100 A 3LD2 724-7UK01 1 1 unit 103 1.061
50 75 160 A 3LD2 305-7UK01 1 1 unit 103 4.300
3LD2 123-7UK01 110 132 250 A 3LD2 405-7UK01 1 1 unit 103 4.400
3+N 50 75 160 A 3LD2 305-7UL01 1 1 unit 103 5.700
110 132 250 A 3LD2 405-7UL01 1 1 unit 103 5.700
3LD2 405-7UL01
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Floor mounting
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1)
4. Contact element as N conductor to be ordered separately,
see "Accessories".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Floor mounting
Number and version Rated data at DT Order No. Price PU PS*/ PG Weight
of the contacts 50 ... 60 Hz, 380 ... 440 V per PU (UNIT, P. unit per PU
SET, approx.
M)
Main Auxiliary P/AC-23A Iu
contact contact
elements elements
kW A kg
Four-hole mounting (continued)
3 1 NO + 7.5 16 } 3LD2 013-0TK5@ 1 1 unit 103 0.412
1 NC +2)
} 3LD9 200-5C 1 1 unit 103 0.046
9.5 25 } 3LD2 113-0TK5@ 1 1 unit 103 0.407
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
11.5 32 } 3LD2 213-0TK5@ 1 1 unit 103 0.405
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
7
22 63 } 3LD2 514-0TK5@ 1 1 unit 103 0.655
+2)
3LD2 213-0TK53 } 3LD9 200-5C 1 1 unit 103 0.046
37 100 } 3LD2 714-0TK5@ 1 1 unit 103 0.765
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
45 125 A 3LD2 814-0TK5@ 1 1 unit 103 0.766
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
75 160 A 3LD2 318-0TK1@ 1 1 unit 103 2.400
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
132 250 A 3LD2 418-0TK1@ 1 1 unit 103 2.700
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
3+N 1 NO + 7.5 16 } 3LD2 013-1TL5@ 1 1 unit 103 0.412
1 NC +2)
} 3LD9 200-5C 1 1 unit 103 0.046
9.5 25 A 3LD2 113-1TL5@ 1 1 unit 103 0.450
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
11.5 32 A 3LD2 213-1TL5@ 1 1 unit 103 0.446
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
22 63 A 3LD2 514-1TL5@ 1 1 unit 103 0.720
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
37 100 } 3LD2 714-0TK5@ 1 1 unit 103 0.765
+1)
} 3LD9 280-0C 1 1 unit 103 0.102
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
45 125 A 3LD2 814-0TK5@ 1 1 unit 103 0.766
+1)
} 3LD9 280-0C 1 1 unit 103 0.102
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
75 160 A 3LD2 318-1TL1@ 1 1 unit 103 2.900
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
132 250 A 3LD2 418-1TL1@ 1 1 unit 103 3.200
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1)
4. Contact element as N conductor to be ordered separately,
see "Accessories".
2) Auxiliary switches 1 NO + 1 NC to be ordered separately,
see "Accessories".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Floor mounting
Number and version Rated data at DT Order No. Price PU PS*/ PG Weight
of the contacts 50 ... 60 Hz, 380 ... 440 V per PU (UNIT, P. unit per PU
SET, approx.
M)
Main Auxiliary P/AC-23A Iu
contact contact
elements elements
kW A kg
Main and EMERGENCY-STOP switches
with door-coupling rotary operating mechanism
• With shaft
• Lockable in 0 position with up to 3 padlocks
• Degree of protection at front side IP65
• Door-coupling rotary operating mechanism with inte-
grated tolerance compensation (16 A to 125 A)
• All versions with rotary operating mechanism
• Exception: 3LD2 3 and 3LD2 4 with knob-operated
7
mechanism
• Mounting using screws or snap-on mounting on 35 mm
standard mounting rail (16 A to 125 A)
• Including terminal cover for the infeed side
• Front plate
- 3LD2 0, 3LD2 1, 3LD2 2: 67 mm x 67 mm
- 3LD2 5 to 3LD2 8: 90 mm x 90 mm
- 3LD2 3 to 3LD2 4: 96 mm x 96 mm
• Mounting dimensions
- 3LD2 0, 3LD2 1, 3LD2 2: 380 mm
- 3LD2 5 to 3LD2 8: 390 mm
- 3LD2 3 to 3LD2 4: 600 mm
Center-hole mounting Ø 22.5 mm
3 -- 7.5 16 A 3LD2 044-0TK5@ 1 1 unit 103 0.430
9.5 25 A 3LD2 144-0TK5@ 1 1 unit 103 0.426
11.5 32 A 3LD2 244-0TK5@ 1 1 unit 103 0.427
22 63 A 3LD2 545-0TK5@ 1 1 unit 103 0.710
3+N -- 7.5 16 A 3LD2 044-1TL5@ 1 1 unit 103 0.433
9.5 25 A 3LD2 144-1TL5@ 1 1 unit 103 0.461
11.5 32 A 3LD2 244-1TL5@ 1 1 unit 103 0.465
22 63 A 3LD2 545-0TK5@ 1 1 unit 103 0.710
3LD2 144-0TK53 +1)
} 3LD9 250-0CA 1 1 unit 103 0.080
3 1 NO + 7.5 16 A 3LD2 044-0TK5@ 1 1 unit 103 0.430
1 NC +2)
} 3LD9 200-5C 1 1 unit 103 0.046
9.5 25 A 3LD2 144-0TK5@ 1 1 unit 103 0.426
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
11.5 32 A 3LD2 244-0TK5@ 1 1 unit 103 0.427
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
22 63 A 3LD2 545-0TK5@ 1 1 unit 103 0.710
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
3+N 1 NO + 7.5 16 A 3LD2 044-1TL5@ 1 1 unit 103 0.433
1 NC +2)
} 3LD9 200-5C 1 1 unit 103 0.046
9.5 25 A 3LD2 144-1TL5@ 1 1 unit 103 0.461
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
11.5 32 A 3LD2 244-1TL5@ 1 1 unit 103 0.465
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
22 63 A 3LD2 545-0TK5@ 1 1 unit 103 0.710
+1)
} 3LD9 250-0CA 1 1 unit 103 0.080
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1) 4. Contact element as N conductor to be ordered separately,
see "Accessories".
2) Auxiliary switches 1 NO + 1 NC to be ordered separately,
see "Accessories".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Floor mounting
Number and version of Rated data at DT Order No. Price PU PS*/ PG Weight
the contacts 50 ... 60 Hz, 380 V ... 440 V per PU (UNIT, P. unit per PU
SET, approx.
M)
Main Auxiliary P/AC-3 P/AC-23A Iu
contact contact
elements elements
kW kW A kg
Main and EMERGENCY-STOP switches with
door-coupling rotary operating mechanism (6-pole)
• Lockable in 0 position with up to 3 padlocks
• Degree of protection at front side IP65
• Door-coupling rotary operating mechanism with integrated
tolerance compensation (for 3LD21)
• All versions with rotary operating mechanism
Exception: 3LD2 3 and 3LD2 4 with door-coupling rotary
operating mechanism as selector switch
• Mounting using screws or snap-on mounting on 35 mm
3LD2 113-3VK51
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
Number and version of Rated data at DT Order No. Price PU PS*/ PG Weight
the contacts 50 ... 60 Hz, 380 V ... 440 V per PU (UNIT, P. unit per PU
SET, approx.
M)
Main Auxiliary P/AC-3 P/AC-23A Iu
contact contact
elements elements
kW kW A kg
Changeover switches
with door-coupling rotary operating mechanism
• Lockable in 0 position with up to 3 padlocks
• Handle and cover black
• Door-coupling rotary operating mechanisms as selector
switch
• Degree of protection at front side IP65
Four-hole mounting
3 50 75 160 A 3LD2 318-7UK01 1 1 unit 103 5.000
3 110 132 250 A 3LD2 418-7UK01 1 1 unit 103 5.000
3+N 50 75 160 A 3LD2 318-7UL01 1 1 unit 103 6.400
3+N 110 132 250 A 3LD2 418-7UL01 1 1 unit 103 6.400
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Floor mounting
Number and version of Rated data at DT Order No. Price PU PS*/ PG Weight
the contacts 50 ... 60 Hz, 380 ... 440 V per PU (UNIT, P. unit per PU
SET, approx.
M)
Main Auxiliary P/AC-23A Iu
contact contact
elements elements
kW A kg
Main and EMERGENCY-STOP switches
with defeatable door-coupling rotary operating
mechanism
The SENTRON 3LD main and EMERGENCY-STOP switch
with defeatable door-coupling rotary operating mecha-
nism enables you to conduct repairs, maintenance work
or tests on electrical plants and machines without having
to interrupt their operation. With the help of the defeat-
able door-coupling rotary operating mechanism, an elec-
trician can bypass the interlock in ON position and open
the control cabinet door with the plant activated.
SENTRON 3LD main and EMERGENCY-STOP switches
with defeatable door-coupling rotary operating mecha-
nism are approved according to UL508.
7
• With 300 mm switch shaft
• Lockable in 0 position with up to 3 padlocks
• Degree of protection at front side IP65
• Door-coupling rotary operating mechanism with inte-
grated tolerance compensation
• Mounting using screws or snap-on mounting on 35 mm
standard mounting rail
• Including terminal cover for the infeed side
• Front plate 65 mm × 65 mm
Four-hole mounting
3 -- 7.5 16 C 3LD2 017-0TK1@ 1 1 unit 103 0.412
11.5 32 C 3LD2 217-0TK1@ 1 1 unit 103 0.412
22 63 C 3LD2 517-0TK1@ 1 1 unit 103 0.412
3+N -- 7.5 16 C 3LD2 017-1TL1@ 1 1 unit 103 0.412
11.5 32 C 3LD2 217-1TL1@ 1 1 unit 103 0.412
22 63 C 3LD2 517-1TL1@ 1 1 unit 103 0.412
3LD2 017-0TK..
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Distribution board mounting
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1) 4. contact element as N conductor to be ordered separately;
see "Accessories for floor mounting".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Distribution board mounting
Number and version of Rated data at DT Order No. Price PU PS*/ PG Weight
the contacts 50 ... 60 Hz, 380 ... 440 V per PU (UNIT, P. unit per PU
SET, approx.
M)
Main Auxiliary P/AC-23A Iu
contact contact
elements elements
kW A kg
3 1 NO + 7.5 16 A 3LD2 030-0TK1@ 1 1 unit 103 0.169
1 NC +2)
} 3LD9 200-5C 1 1 unit 103 0.046
9.5 25 A 3LD2 130-0TK1@ 1 1 unit 103 0.171
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
3LD2 530-0TK11 11.5 32 A 3LD2 230-0TK1@ 1 1 unit 103 0.168
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
22 63 A 3LD2 530-0TK1@ 1 1 unit 103 0.311
+2)
37 100
}
A
3LD9 200-5C
3LD2 730-0TK1@
1
1
1 unit
1 unit
103
103
0.046
0.379
7
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
45 125 A 3LD2 830-0TK1@ 1 1 unit 103 0.379
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
75 160 A 3LD2 330-0TK1@ 1 1 unit 103 2.000
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
132 250 A 3LD2 430-0TK1@ 1 1 unit 103 2.000
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
3+N 1 NO + 7.5 16 A 3LD2 030-1TL1@ 1 1 unit 103 0.183
1 NC +2)
} 3LD9 200-5C 1 1 unit 103 0.046
9.5 25 A 3LD2 130-0TK1@ 1 1 unit 103 0.171
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
+1)
} 3LD9 220-0C 1 1 unit 103 0.039
11.5 32 A 3LD2 230-0TK1@ 1 1 unit 103 0.168
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
+1)
} 3LD9 220-0C 1 1 unit 103 0.039
22 63 A 3LD2 530-0TK1@ 1 1 unit 103 0.311
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
+1)
} 3LD9 250-0CA 1 1 unit 103 0.080
37 100 A 3LD2 730-0TK1@ 1 1 unit 103 0.379
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
+1)
} 3LD9 280-0C 1 1 unit 103 0.102
45 125 A 3LD2 830-0TK1@ 1 1 unit 103 0.379
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
+1)
} 3LD9 280-0C 1 1 unit 103 0.102
75 160 A 3LD2 330-0TK1@ 1 1 unit 103 2.000
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
+1)
} 3LD9 240-0C 1 1 unit 103 0.500
132 250 A 3LD2 430-0TK1@ 1 1 unit 103 2.000
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
+1)
} 3LD9 240-0C 1 1 unit 103 0.500
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1) 4. contact element as N conductor to be ordered separately;
see "Accessories for floor mounting".
2) Auxiliary switches 1 NO + 1 NC to be ordered separately,
see "Accessories".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Molded-plastic enclosures
7
• Metric screwed glands
3 -- PE + N 7.5 16 A 3LD2 064-0TB5@ 1 1 unit 103 0.463
PE + N 9.5 25 A 3LD2 164-0TB5@ 1 1 unit 103 0.463
PE + N 11.5 32 A 3LD2 264-0TB5@ 1 1 unit 103 0.465
PE + N 22 63 A 3LD2 565-0TB5@ 1 1 unit 103 0.906
PE + N 37 100 A 3LD2 766-0TB5@ 1 1 unit 103 1.890
PE + N 45 125 A 3LD2 866-0TB5@ 1 1 unit 103 1.890
3+N -- PE 7.5 16 A 3LD2 064-1TC5@ 1 1 unit 103 0.453
PE 9.5 25 A 3LD2 164-1TC5@ 1 1 unit 103 0.487
PE 11.5 32 C 3LD2 264-1TC5@ 1 1 unit 103 0.500
PE 22 63 C 3LD2 565-1TC5@ 1 1 unit 103 0.960
PE + N 37 100 A 3LD2 766-0TB5@ 1 1 unit 103 1.890
3LD2 164-0TB53 +1)
} 3LD9 280-0C 1 1 unit 103 0.102
PE + N 45 125 A 3LD2 866-0TB5@ 1 1 unit 103 1.890
+1)
} 3LD9 280-0C 1 1 unit 103 0.102
3 1 NO + N 7.5 16 A 3LD2 064-1GP5@ 1 1 unit 103 0.507
1 NC N 9.5 25 A 3LD2 164-1GP5@ 1 1 unit 103 0.501
N 11.5 32 A 3LD2 264-1GP5@ 1 1 unit 103 0.488
N 22 63 A 3LD2 565-1GP5@ 1 1 unit 103 0.935
N 37 100 A 3LD2 766-1GP5@ 1 1 unit 103 1.838
N 45 125 A 3LD2 866-1GP5@ 1 1 unit 103 1.843
3+N 1 NO + PE 7.5 16 A 3LD2 064-1TC5@ 1 1 unit 103 0.453
1 NC +2)
} 3LD9 200-5C 1 1 unit 103 0.046
PE 9.5 25 A 3LD2 164-1TC5@ 1 1 unit 103 0.487
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
PE 11.5 32 C 3LD2 264-1TC5@ 1 1 unit 103 0.500
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
PE 22 63 C 3LD2 565-1TC5@ 1 1 unit 103 0.960
+2)
} 3LD9 200-5C 1 1 unit 103 0.046
N 37 100 A 3LD2 766-1GP5@ 1 1 unit 103 1.838
+1)
} 3LD9 280-0C 1 1 unit 103 0.102
N 45 125 A 3LD2 866-1GP5@ 1 1 unit 103 1.843
+1)
} 3LD9 280-0C 1 1 unit 103 0.102
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
1)
4. contact element as N conductor to be ordered separately;
see "Accessories for floor mounting".
2)
Auxiliary switches 1 NO + 1 NC to be ordered separately,
see "Accessories".
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Molded-plastic enclosures
Number and version Base Rated data at DT Order No. Price PU PS*/ PG Weight
of the contacts terminal 50 ... 60 Hz, per PU (UNIT, P. unit per PU
380 ... 440 V SET, approx.
M)
Main Auxiliary P/AC-3 P/AC-23A Iu
contact contact
elements elements
kW kW A kg
Main and EMERGENCY-STOP switches
with rotary operating mechanism (6-pole)
• With N- and/or PE-/ground base terminals
• Degree of protection IP65
• Metric screwed glands
6 -- PE + N 7.5 9.5 25 A 3LD2 165-3VB5@ 1 1 unit 103 0.880
PE + N 9.5 11.5 32 A 3LD2 265-3VB5@ 1 1 unit 103 0.878
PE + N 18.5 22.0 63 A 3LD2 566-3VB5@ 1 1 unit 103 2.105
6 1 NO + N 7.5 9.5 25 A 3LD2 165-4VD5@ 1 1 unit 103 0.914
1 NC N 9.5
PE + N 18.5
11.5
22.0
32
63
A
A
3LD2 265-4VD5@
3LD2 566-4VD5@
1
1
1 unit
1 unit
103
103
0.910
2.084
7
3LD2 165-3VB53
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
Number and version Base Rated data at DT Order No. Price PU PS*/ PG Weight
of the contacts terminal 50 ... 60 Hz, per PU (UNIT, P. unit per PU
380 ... 440 V SET, approx.
M)
Main Auxiliary P/AC-3 P/AC-23A Iu
contact contact
elements elements
kW kW A kg
Changeover switches
with knob-operated mechanism
• With N- and/or PE-/ground base terminals
• Black actuator
• Lockable in 0 position with up to 3 padlocks (25 A and 32 A)
• Metric screwed glands
• Degree of protection IP65
3 -- PE + N 7.5 9.5 25 A 3LD2 165-7UB01 1 1 unit 103 0.888
PE + N 9.5 11.5 32 A 3LD2 265-7UB01 1 1 unit 103 0.888
PE + N 18.5 22.0 63 A 3LD2 566-7UB01 1 1 unit 103 2.105
PE + N 30.0 37.0 100 A 3LD2 766-7UB01 1 1 unit 103 2.335
3LD2 165-7UB01
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
DC applications
3LD2 265-8VQ5.-0AF6
Actuator color
Black
>
1
Red/yellow (EMERGENCY-STOP) 3
3LD2 265-8VQ11-0AF6
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Accessories
3LD9 200-2B
Auxiliary switches
For mounting on the left and/or right, lagging switch-on,
leading switch-off
• 1 NO + 1 NC
For mounting on the left and/or right, lagging switch-on,
with gold-plate contacts for SIMATIC request, leading
} 3LD9 200-5B 1 1 unit 103 0.046
7
switch-off
3LD9 200-5B • 1 NO + 1 NC C 3LD9 200-5BF 1 1 unit 103 0.028
For floor mounting, distribution board mounting or molded-plastic
enclosures
N or PE terminals } 3LD9 200-2C 1 1 unit 103 0.032
Through-type
3LD9 200-2C
Auxiliary switches
For mounting on the left and/or right, lagging switch-on,
leading switch-off
• 1 NO + 1 NC } 3LD9 200-5C 1 1 unit 103 0.046
• 2 NO } 3LD9 200-6C 1 1 unit 103 0.046
For mounting on the left and/or right, lagging switch-on,
3LD9 200-5C (left) with gold-plate contacts for SIMATIC request, leading
3LD9 200-6C (right) switch-off
• 1 NO + 1 NC C 3LD9 200-5CF 1 1 unit 103 0.028
For front and floor mounting
Rotary operating mechanisms
Lockable in 0 position with up to 3 padlocks
• For four-hole mounting, including seal
- Black A 3LD9 224-1B 1 1 unit 103 0.072
- Red/Yellow A 3LD9 224-3B 1 1 unit 103 0.075
3LD9 224-1B • For center-hole mounting, including seal and nut
- Black A 3LD9 224-1D 1 1 unit 103 0.080
- Red/Yellow A 3LD9 224-3D 1 1 unit 103 0.081
3LD9 224-3D
Assembly tools
For center-hole mounting with nut A 3LD9 256-0A 1 5 units 103 0.027
3LD9 256-0A
Switching shafts 6 x 6 mm
Length 300 mm C 3LD9 205-0C 1 5 units 103 0.476
Length 600 mm C 3LD9 205-2C 1 5 units 103 0.476
Inscription labels
With English/German inscription A 3LD9 286-1A 1 10 units 103 0.005
(MAIN SWITCH/HAUPTSCHALTER)
3LD9 286-1A Without inscription A 3LD9 286-4A 1 10 units 103 0.054
Terminal covers as additional touch protection
(also for distribution board mounting)
Can be snapped on at top and bottom
• 1-pole A 3LD9 201-2A 100 4 units 103 0.200
3LD9 201-2A
• 3-/4-pole A 3LD9 201-1A 1 4 units 103 0.007
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Accessories
7
For mounting on the left and/or right, lagging switch-on,
leading switch-off, with gold-plate contacts for SIMATIC
request
3LD9 200-5B • 1 NO + 1 NC C 3LD9 200-5BF 1 1 unit 103 0.028
For floor mounting, distribution board mounting or molded-plastic
enclosures
4. contact (N conductor) } 3LD9 220-0C 1 1 unit 103 0.039
Leading switch-on, lagging switch-off
3LD9 220-0C
N or PE terminals } 3LD9 220-2C 1 1 unit 103 0.037
Through-type
Auxiliary switches
For mounting on the left and/or right, lagging switch-on,
leading switch-off
• 1 NO + 1 NC } 3LD9 200-5C 1 1 unit 103 0.046
• 2 NO } 3LD9 200-6C 1 1 unit 103 0.046
For mounting on the left and/or right, lagging switch-on,
leading switch-off, with gold-plate contacts for SIMATIC
3LD9 200-5C (left) request
3LD9 200-6C (right) • 1 NO + 1 NC C 3LD9 200-5CF 1 1 unit 103 0.028
For front and floor mounting
Rotary operating mechanisms
Lockable in 0 position with up to 3 padlocks
• For four-hole mounting
- Black A 3LD9 224-1B 1 1 unit 103 0.072
- Red/Yellow A 3LD9 224-3B 1 1 unit 103 0.075
3LD9 224-1B
• For center-hole mounting, including seal and nut
- Black A 3LD9 224-1D 1 1 unit 103 0.080
- Red/Yellow A 3LD9 224-3D 1 1 unit 103 0.081
3LD9 224-3D
Assembly tools
For center-hole mounting with nut A 3LD9 256-0A 1 5 units 103 0.027
3LD9 256-0A
Switching shafts 6 x 6 mm
Length 300 mm C 3LD9 205-0C 1 5 units 103 0.476
Length 600 mm C 3LD9 205-2C 1 5 units 103 0.476
Inscription labels
With English/German inscription A 3LD9 286-1A 1 10 units 103 0.005
(MAIN SWITCH/HAUPTSCHALTER)
3LD9 286-1A Without inscription A 3LD9 286-4A 1 10 units 103 0.054
Terminal covers as additional touch protection
(also for distribution board mounting)
Can be snapped on at top and bottom
• 1-pole A 3LD9 221-2A 100 4 units 103 0.100
3LD9 221-2A (left) • 3-pole A 3LD9 221-0A 1 4 units 103 0.007
3LD9 221-0A (right)
* You can order this quantity or a multiple thereof.
7/22 Siemens LV 10.1 · 2011
© Siemens AG 2010
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Accessories
3LD9 242-4F
4. contact (N conductor) } 3LD9 240-0C 1 1 unit 103 0.500
Leading switch-on, lagging switch-off
N or PE terminals } 3LD9 240-2C 1 1 unit 103 0.450
Through-type
3LD9 200-5C (left) For mounting on the left and/or right, lagging switch-on,
3LD9 200-6C (right) leading switch-off, with gold-plate contacts for SIMATIC
request
• 1 NO + 1 NC C 3LD9 200-5CF 1 1 unit 103 0.028
For front and floor mounting
Knob-operated mechanism
Lockable in 0 position with up to 3 padlocks
• For four-hole mounting, including seal
- Black A 3LD9 243-1B 1 1 unit 103 0.154
3LD9 243-1B - Red/Yellow A 3LD9 243-3B 1 1 unit 103 0.154
Switching shafts 8 x 8 mm
Length 300 mm C 3LD9 245-0C 1 5 units 103 0.476
Length 600 mm C 3LD9 245-2C 1 5 units 103 0.476
Inscription labels
With English/German inscription A 3LD9 286-1A 1 10 units 103 0.005
(MAIN SWITCH/HAUPTSCHALTER)
3LD9 286-1A Without inscription A 3LD9 286-4A 1 10 units 103 0.054
Terminal covers as additional touch protection
(also for distribution board mounting)
Can be snapped on at top and bottom
• 1-pole A 3LD9 241-2A 1 4 units 103 0.010
3LD9 241-2A
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Accessories
3LD9 284-3D
Assembly tools
For center-hole mounting with nut A 3LD9 256-0A 1 5 units 103 0.027
3LD9 256-0A
Switching shafts 6 x 6 mm
Length 300 mm C 3LD9 205-0C 1 5 units 103 0.476
Length 600 mm C 3LD9 205-2C 1 5 units 103 0.476
Inscription labels
With English/German inscription A 3LD9 286-1A 1 10 units 103 0.005
(MAIN SWITCH/HAUPTSCHALTER)
3LD9 286-1A Without inscription A 3LD9 286-4A 1 10 units 103 0.054
Terminal covers as additional touch protection
(also for distribution board mounting)
Can be snapped on at top and bottom
• 1-pole A 3LD9 251-2A 100 4 units 103 0.100
3LD9 251-2A (left)
3LD9 251-0A (right) • 3-pole A 3LD9 251-0A 1 4 units 103 0.009
Switch Disconnectors
SENTRON 3LD Main and EMERGENCY-STOP Switches up to 250 A
Accessories
7
• 1 NO + 1 NC } 3LD9 200-5B 1 1 unit 103 0.046
For mounting on the left and/or right, lagging switch-on,
leading switch-off, with gold-plate contacts for SIMATIC re-
3LD9 200-5B quest
• 1 NO + 1 NC C 3LD9 200-5BF 1 1 unit 103 0.028
For floor mounting, distribution board mounting or molded-plastic
enclosures
4. contact (N conductor) } 3LD9 280-0C 1 1 unit 103 0.102
Leading switch-on, lagging switch-off
N or PE terminals } 3LD9 280-2C 1 1 unit 103 0.093
Through-type
Switch Disconnectors
5TE1 Switch Disconnectors up to 200 A
Introduction
■ Overview ■ Benefits
The 5TE1 switch disconnectors are available from 100 A to • Transparent enclosures ensure that the contact position is
200 A in 3 and 4-pole versions and can be used as main always visible
switches, repair switches, outgoing feeder switches and emer- • Contacts with double breaks ensure reliable insulation char-
gency system interrupters. acteristics
The series corresponds to the requirements of IEC/EN 60947-3 • Can be locked in the OFF position to allow for maintenance
and its key features are its compact and robust design, high work.
short-circuit strength, high DC switching capacity and compre- • With a red knob and yellow cap, it can also be used as an
hensive accessories. emergency system interrupter.
Its small footprint means it is easy to install in all types of enclo-
sures, distribution boards and control cabinets.
The devices are approved to UL 508 and KEMA certified.
■ Technical specifications
7
5TE1 .1 5TE1 .2 5TE1 .3 5TE1 .4
Standards IEC/EN 60947-3, UL 508
Approvals UL 508 for the following types: 5TE1 320, 5TE1 330,
5TE1 340, 5TE1 420, 5TE1 430 and 5TE1 440.
UL File No. E302554
Rated operational current Ie Per conducting path At Ue= 400 V A 100 125 160 200
With utilization category AC-21A 415 V A 100 125 160 200
500 V A 100 125 160 200
690 V A 100 125 160 200
Rated operational current Ie Per conducting path At Ue= 400 V A 100 125 160 200
With utilization category AC-22A 415 V A 100 125 160 200
500 V A 100 100 160 200
690 V A 63 63 160 200
Rated operational current Ie Per conducting path At Ue= 400 V A 80 125 160
With utilization category AC-23A 415 V A 80 125 160
500 V A 50 125 125
690 V A 40 63 80
Rated operational current Ie 2 poles in series 110 V A 100 160
With utilization category DC-23A 2 poles in series 220 V A -- 100
4 poles in series 220 V A 100 160
Rated operational voltage Ue V AC Acc. to UL: 480, acc. to IEC: 690
Rated insulation voltage Ui V AC 690
Rated impulse withstand voltage Uimp 2000 m kV 8
Impulse test voltage At sea level kV 12.3
Max. rated operational power At Ue= 400 V kW 44 69 88
With utilization category AC-23A 415 V kW 46 72 92
500 V kW 35 86 86
690 V kW 36 60 76
Rated thermal current Ith At 40 °C, 50 °C and 60 °C A 100 125 160 200
Rated making capacity At 415 V AC-23A A 1875 3200 4000
Rated breaking capacity At 415 V AC-23A A 1000 1920 2400
Rated ultimate short-circuit breaking capacity Icm Per conducting path At Ue= 400 V kA 10
415 V kA 10
500 V kA 6.7
690 V kA 6.7
Rated short-time withstand current Icw Per conducting path 0.25 s kA 5 6
(peak value) 1s kA 2.5 3
Rated conditional short-circuit current At Ue= 400 V kA 50
With back-up protection with back-up fuse 415 V kA 50
With identical rated current 500 V kA 50
690 V kA 33 33 20 18
Capacitive load At 400 V kVar 50 60 77 97
Number of poles 2/3/4
Rated power dissipation Pv Per pole VA 2.9 4.5 6.5 10
Frequency Hz 50/60
Conductor cross-sections
• Solid and stranded mm2 6 ... 50 --
• AWG cables AWG 10 ... 1/0 8
• Copper busbars mm2 -- max. 20 × 6
Endurance Electrical Switching 1500 1000
Mechanical cycles 20000 10000
According to UL 508 In A -- 80 100 125
UL 508 General Use 480 V FLA (Full load amperes) A -- 28 34 40
UL 508 Manual motor controller 230 V Rating hp -- 10 25 30
UL 508 Manual motor controller 480 V Rating hp -- 20 15 15
UL 508 Short-circuit at 480 V With Class H or K5 fuses kA -- 10
With J fuses kA -- 50
Switch Disconnectors
5TE1 Switch Disconnectors up to 200 A
General data
4 NO
200 B 5TE1 340 1 1 unit 027 0.697
7
100 690 5 B 5TE1 410 1 1 unit 027 0.602
125 B 5TE1 420 1 1 unit 027 0.591
160 8 B 5TE1 430 1 1 unit 027 0.774
200 B 5TE1 440 1 1 unit 027 0.794
3 NO with N-conductor through-type terminal
100 690 5 B 5TE1 610 1 1 unit 027 0.592
125 B 5TE1 620 1 1 unit 027 0.606
160 8 B 5TE1 630 1 1 unit 027 0.791
200 B 5TE1 640 1 1 unit 027 0.789
Switch disconnectors with red knob and yellow cap,
can be used as emergency mains switching off device
acc. to IEC 60204-1, EN 60204-1 if switch is easily
accessible, mounting depth 92 mm
3 NO
100 690 5 B 5TE1 315 1 1 unit 027 0.545
125 B 5TE1 325 1 1 unit 027 0.550
160 8 B 5TE1 335 1 1 unit 027 0.693
200 B 5TE1 345 1 1 unit 027 0.722
4 NO
100 690 5 B 5TE1 415 1 1 unit 027 0.596
125 B 5TE1 425 1 1 unit 027 0.609
160 8 B 5TE1 435 1 1 unit 027 0.803
200 B 5TE1 445 1 1 unit 027 0.806
Switch Disconnectors
5TE1 Switch Disconnectors up to 200 A
General data
■ Accessories
Version Ie Ue DT Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
SET, approx.
M)
A AC V AC kg
Terminal covers
Sealable
For 100 A and 125 A load disconnect switches B 5TE9 000 1 1 unit 027 0.043
For 160 A and 200 A load disconnect switches B 5TE9 001 1 1 unit 027 0.037
Locking units
For up to three padlocks with max. ∅ 8 mm B 5TE9 014 1 1 unit 027 0.017
Switch Disconnectors
5TE1 Switch Disconnectors up to 200 A
General data
■ Dimensional drawings
5TE1 switch disconnectors, 100 A and 125 A 5TE9 auxiliary switches
73
44
45
90
44
90
75
45
I2_07111c
I2_07109a
9 42
7
90 6 92,5 73
5TE1 210 5TE1 310 5TE1 410 5TE1 610 5TE9 005
5TE1 220 5TE1 315 5TE1 415 5TE1 620 5TE9 006
5TE1 320 5TE1 420
5TE1 325 5TE1 425
5TE1 switch disconnectors, 160 A and 200 A 5TE9 014 locking units
73 1x 2x 3x
5,5
35 35 35 44 max. 8 mm
I2_07112a
13
ON
45
80
70
90
OFF
I2_07110a
70 6 92,5
144
5TE1 230 5TE1 330 5TE1 430 5TE1 630
5TE1 240 5TE1 335 5TE1 435 5TE1 640
5TE1 340 5TE1 440
5TE1 345 5TE1 445
73 19 H 165/365 65 73 19 H 165/365 65
79 53,5 79 53,5
H+35 L H+100 H+35 L H+100
H-7 2,5
H-7 2,5
SW16
SW16
6
I2_07205b
0 37,5
6
32
I2_07206b
With switch disconnectors 100 A and 125 A With switch disconnectors 160 A and 200 A
5TE9 010, 5TE9 011, 5TE9 010, 5TE9 011,
5TE9 012, 5TE9 013 5TE9 012, 5TE9 013
It is possible to open the door in a disconnected state. It is possible to open the door in a disconnected state.
Switch Disconnectors
5TE1 Switch Disconnectors up to 200 A
General data
■ Schematics
Diagram 5TE9 auxiliary switches
1 3 1 3 5 1 3 5 7 1 2 1 2 3 4
2 4 2 4 6 2 4 6 8 L L1 L2
5TE1 210 5TE1 310 5TE1 410 5TE9 005 5TE9 006
5TE1 220 5TE1 320 5TE1 420
5TE1 230 5TE1 330 5TE1 430
5TE1 240 5TE1 340 5TE1 440
1 3 5 N 1 3 5 1 3 5 7
2 4 6 2 4 6 2 4 6 8
5TE1 610 5TE1 315 5TE1 415
5TE1 620 5TE1 325 5TE1 425
5TE1 630 5TE1 335 5TE1 435
5TE1 640 5TE1 345 5TE1 445
7 ■ More information
Connection of 5TE1 3 and 5TE1 4 switches, 160 and 200 A Design
• From 160 A: supplied with one terminal cover
10-12
• 160 A and 200 A: version for connection with cable lug
• Screw fixing on base plate
I2_08070a
• Installation on standard mounting rail to EN 60715, which is
raised at least 5 mm from the base plate.
max. 12 Nm SW 5
SW 13
10-12
Ø8,5
max. 6
5TE9 003
5TE9 004
20 max.
SW 5
max. Ø14
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Introduction
■ Overview
1 2
NSE0_01931b
4
For the 3KA switch disconnectors, complete kits for standard An operating linkage permits simultaneous switching of two 3KE
and EMERGENCY-STOP application are available for installation switch disconnectors with identical or different rated operational
in the side and rear panels of control cabinets. currents.
A changeover operating mechanism is available for the use of Identical accessories for 3KA switch disconnectors and for 3KL
2 switch disconnectors in the 3KE series as load changeover and 3KM switch disconnectors with fuses simplify stock keep-
switches. ing.
■ Application
3KA and 3KE switch disconnectors are used as main, All 3K switch disconnectors are climate-proof and meet the
EMERGENCY-STOP, maintenance and transfer switches in dis- requirements of IEC 60947-1 and IEC 60947-3. Switch discon-
tribution boards for residential and non-residential buildings as nectors in the type-tested 8HP molded-plastic distribution board
well as industrial switchboards. As three and four-pole versions, enclosure (degree of protection IP65) are available for use as
they ensure activation and deactivation of the specified rated safety switches.
current under load. At the same time, they constitute a safety iso-
lating function and isolating distance in all low-voltage circuits. Additional data, see catalog LV 10.2, chapter 18
"Distribution Boards" and chapter 19 "Terminal Blocks".
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Introduction
■ Technical specifications
Standards IEC 60947-1, IEC 60947-3
Type 3KA50 3KA51 3KA521) 3KA531) 3KA551) 3KA571) 3KA581)
Rated uninterrupted current Iu A 63 80 125 160 250 400 6303)
Conventional free-air thermal current Ith 2)
A 63 80 125 160 250 400 6303)
Rated insulation voltage Ui V 690 690 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp kV 6 6 8 8 8 8 8
Rated operational voltage Ue
50/60 Hz AC V 690
DC V 440 (3 conducting paths series-connected)
V 220 (2 conducting paths series-connected)
V 110 (1 conducting path)
Rated short-circuit making capacity Icm kA 220 220 220 220 176 176 105
with upstream fuses4)
At 50/60 Hz 690 V AC, peak value
Rated conditional short-circuit current with upstream kA 100 100 100 100 80 80 50
7 fuses4)
At 50/60 Hz 690 V AC, rms value
Max. rated current In of the fuses A 63 80 160 160 400 400 630
Permissible let-through current of the fuses kA 8 10 17 17 305) 305) 405)
Maximum permissible let-through I2t value kA2s 55 55 223 223 1000 1000 2600
Permissible let-through current of an upstream circuit kA 7 8 8 15 25 25 32
breaker
At 50/60 Hz 690 V AC, peak value
Rated short-circuit making capacity without fuses kA 7 7 7 9 20 25 35
At AC 50 Hz/60 Hz 690 V, peak value
Switching capacity (infeed from the top or bottom)
At 400 V AC
• Breaking current Ic (at p.f. = 0.35, rms value) A 500 650 1000 1280 2000 3200 5040
• Rated operational current Ie at
- AC-21A, AC-22A, AC-23A A 63 80 125 160 250 400 6306)
• Motor switching capacity AC-23A kW 30 40 65 80 132 200 350
At 500 V AC
• Breaking current Ic (at p.f. = 0.35, rms value) A 500 640 1000 1280 2000 3200 3200
• Rated operational current Ie at
- AC-21A, AC-22A A 63 80 125 160 250 400 630
- AC-23A A 63 80 125 160 250 400 400
• Motor switching capacity AC-23A kW 40 50 90 110 185 280 280
At 690 V AC
• Breaking current Ic (at p.f. = 0.35, rms value) A 500 500 1000 1280 2000 3200 3200
• Rated operational current Ie at
- AC-21A, AC-22A A 63 80 125 160 250 400 630
- AC-23A A 63 63 125 160 250 400 400
• Motor switching capacity AC-23A kW 50 50 110 150 220 375 375
At 440 V DC (3 conducting paths series-connected)7)
• Breaking current Ic (L/R = 15 ms) A 250 260 500 640 10008) 1600 1600
• Rated operational current Ie at DC-23A A 63 63 125 160 2509) 400 400
Rated short-time current Icw kA 2.5 2.5 3.2 3.2 8 11 15
(1 s current, rms value)
3)
Permissible ambient temperature °C -25 ... +55 for operation
°C -50 ... +80 when stored
Mechanical endurance, operating cycles 15 000 15 000 15000 15 000 12 000 12 000 12 000
Degree of protection IP00/IP20 (from the operator side, with busbar and terminal covers)
Power loss of the switch disconnector at Ith W 7 12 22 22 33 72 170
Main conductor connections
Busbar systems, max. dimensions (w x t) mm 25 x 9 25 x 9 45 x 10 45 x 10 40 x 12 40 x 12 40 x 15
Cable lug, max. conductor cross-section (stranded) mm2 35 35 70 120 150 2 x 150 or 1 2 x 240
x 240
Tightening torque Nm 6 ... 7.5 6 ... 7.5 7 ... 10 18 ... 22 35 ... 45 35 ... 45 35 ... 45
Terminal screws M6 M6 M6 M8 M10 M10 M10
Protective conductor connections
Flat bars mm -- -- -- -- 20 x 2.5 20 x 2.5 20 x 2.5
Cable lug, max. conductor cross-section (stranded) mm2 -- -- -- -- 70 120 120
1) 5)
Technical specifications for approval on request. 3ND1 switchgear protection fuse.
2) 6)
Configuring note: Max. permissible operating temperature at connections AC-23B.
100 °C. 7)
220 V DC (L1 and L3 series-connected) or 110 V DC
3)
With 3KA58 for operation -25 °C ... +35 °C, 570 A at 55 °C. (one conducting path) at DC-23A.
4) 8)
Only available with fuses 3NA3 8, 3NA3 2 or 3ND1 8, 3ND1 2 At 440 V L/R = 4 ms, at 220 V L/R = 15 ms.
(otherwise only 105 kA/50 kA). 9)
At 440 V DC-22A, at 220 V DC-23A.
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Introduction
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Floor mounting
■ Applications
3KA switch disconnectors are implemented as main switches Main and EMERGENCY-STOP switches are manually operated
and EMERGENCY-STOP switches for normal switching duty and switch disconnectors according to IEC 60947-3 and
isolation of main circuits and auxiliary circuits. Another field of EN 60947-3 and comply with the conditions for switch discon-
application is the switching of induction motors and other loads nectors and the requirements of the machinery directive
in the event of maintenance and repair. EN 60204-1.
7
mechanism (black handle)
3-pole for motor loads and for power distribution
63 B 3KA50 30-1GE01 1 1 unit 103 1.444
80 B 3KA51 30-1GE01 1 1 unit 103 1.403
125 B 3KA52 30-1GE01 1 1 unit 103 2.383
160 B 3KA53 30-1GE01 1 1 unit 103 2.426
250 B 3KA55 30-1GE01 1 1 unit 103 5.475
400 B 3KA57 30-1GE01 1 1 unit 103 5.556
630 B 3KA58 30-1GE01 1 1 unit 103 6.128
4-pole1) for power distribution
63 B 3KA50 40-1GE01 1 1 unit 103 2.498
80 B 3KA51 40-1GE01 1 1 unit 103 2.540
125 B 3KA52 40-1GE01 1 1 unit 103 2.490
160 B 3KA53 40-1GE01 1 1 unit 103 2.458
250 B 3KA55 40-1GE01 1 1 unit 103 6.038
400 B 3KA57 40-1GE01 1 1 unit 103 5.154
630 B 3KA58 40-1GE01 1 1 unit 103 6.595
Basic switch versions without handle
3-pole for motor loads and for power distribution
63 B 3KA50 30-1AE01 1 1 unit 103 0.946
80 B 3KA51 30-1AE01 1 1 unit 103 0.918
125 B 3KA52 30-1AE01 1 1 unit 103 1.880
160 } 3KA53 30-1AE01 1 1 unit 103 2.028
250 B 3KA55 30-1AE01 1 1 unit 103 4.514
400 B 3KA57 30-1AE01 1 1 unit 103 4.630
3KA53 30-1AE01 630 B 3KA58 30-1AE01 1 1 unit 103 5.151
4-pole1) for power distribution
63 B 3KA50 40-1AE01 1 1 unit 103 2.100
80 B 3KA51 40-1AE01 1 1 unit 103 2.112
125 B 3KA52 40-1AE01 1 1 unit 103 2.090
160 B 3KA53 40-1AE01 1 1 unit 103 2.240
250 C 3KA55 40-1AE01 1 1 unit 103 5.042
400 B 3KA57 40-1AE01 1 1 unit 103 5.195
630 B 3KA58 40-1AE01 1 1 unit 103 5.740
3KA53 40-1AE01
8UC7 EMERGENCY-STOP door-coupling rotary operating
mechanisms (red handle, yellow indicator plate) for basic switch
versions without handle
3-pole for motor loads and for power distribution
63 B 8UC71 21-3BB10 1 1 unit 103 0.200
80 B 8UC71 21-3BB10 1 1 unit 103 0.200
125 B 8UC72 22-3BB20 1 1 unit 103 0.200
160 B 8UC72 22-3BB20 1 1 unit 103 0.200
250 B 8UC73 23-3BB30 1 1 unit 103 0.200
400 B 8UC73 23-3BB30 1 1 unit 103 0.200
630 B 8UC73 23-3BB30 1 1 unit 103 0.200
8UC71 21-3BB10
4-pole1) for power distribution
63 B 8UC72 22-3BB20 1 1 unit 103 0.200
80 B 8UC72 22-3BB20 1 1 unit 103 0.200
125 B 8UC72 22-3BB20 1 1 unit 103 0.200
160 B 8UC72 22-3BB20 1 1 unit 103 0.200
250 B 8UC73 23-3BB30 1 1 unit 103 0.200
400 B 8UC73 23-3BB30 1 1 unit 103 0.200
630 B 8UC73 23-3BB30 1 1 unit 103 0.200
1)
Rated values reduced in the event of strong harmonics caused by fre- For 8UC7 EMERGENCY-STOP door-coupling rotary operating
quency converter operation. mechanisms (red handle, yellow indicator plate),
see Accessories.
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Floor mounting
Rated uninterrupted current Iu DT 3-pole, assembly kits for mounting PU PS*/ PG Weight
in control cabinet side panels (UNIT, P. unit per PU
SET, M) approx.
Assembly kits (IP40 from front)
Comprising: Lockable handle and
three terminal covers for the infeed
side
Order No. Price
A per PU kg
Black handle
63 B 3KX3 516-2AA 1 1 unit 103 0.591
80 B 3KX3 516-2AA 1 1 unit 103 0.591
125 B 3KX3 536-2AA 1 1 unit 103 0.843
160 B 3KX3 536-2AA 1 1 unit 103 0.843
250 B 3KX3 556-2AA 1 1 unit 103 1.560
400 B 3KX3 556-2AA 1 1 unit 103 1.560
630 B 3KX3 556-2AA 1 1 unit 103 1.560
7
3KA53 30-1AE01 with
3KX3 536-2AA
EMERGENCY-STOP red handle
63 B 3KX3 516-2BA 1 1 unit 103 0.584
80 B 3KX3 516-2BA 1 1 unit 103 0.584
125 B 3KX3 536-2BA 1 1 unit 103 0.860
160 B 3KX3 536-2BA 1 1 unit 103 0.860
250 B 3KX3 556-2BA 1 1 unit 103 1.590
400 B 3KX3 556-2BA 1 1 unit 103 1.590
630 B 3KX3 556-2BA 1 1 unit 103 1.590
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Floor mounting
All switch disconnectors with degree of protection IP00
With high speed closing and opening
Conductor connecting screws are generally included in the scope of supply
Rated uninterrupted current Iu DT 3-pole, operating mechanism and PU PS*/ PG Weight
actuation from the front (UNIT, P. unit per PU
Direct operating mechanisms SET, M) approx.
Order No. Price
A per PU kg
Complete versions with black handle
250 B 3KE42 30-0BA 1 1 unit 103 4.210
400 B 3KE43 30-0BA 1 1 unit 103 4.178
630 B 3KE44 30-0BA 1 1 unit 103 7.184
1000 B 3KE45 30-0BA 1 1 unit 103 7.838
3KE43 30-0BA
7
Basic switch versions without handle
250 B 3KE42 30-0AA 1 1 unit 103 3.879
400 B 3KE43 30-0AA 1 1 unit 103 3.870
630 B 3KE44 30-0AA 1 1 unit 103 6.915
1000 B 3KE45 30-0AA 1 1 unit 103 7.427
EMERGENCY-STOP red handles + coupling sockets
for basic switch versions without handle
250 B 8UC93 71 1 1 unit 103 0.146
+
B 3KX2 210-0H 1 1 unit 103 0.236
400 B 8UC93 71 1 1 unit 103 0.146
+
B 3KX2 210-0H 1 1 unit 103 0.236
630 B 8UC93 75 1 1 unit 103 0.165
+
B 3KX2 210-0H 1 1 unit 103 0.236
1000 B 8UC93 75 1 1 unit 103 0.165
+
B 3KX2 210-0H 1 1 unit 103 0.236
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Floor mounting
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Floor mounting
7 A
+
8UB95 30
+
1 1 unit 103 0.028
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Molded-plastic enclosures
■ Benefits
• Lockable with 3 padlocks • Maintenance-free
• Generous terminal compartment • Easy mounting
• Degree of protection IP65
■ Application
Our master and EMERGENCY-STOP switches provide absolute building and industrial installations as well as the food and
safety, even during maintenance and repair work. All-round chemical industry. Even with the enclosure open, they comply
safety for people and machines. with protection class 2. IP20 is the minimum!
With their high degree of protection IP65, they can even with-
stand dust and water spray, providing unparalleled safety in the
7
at At 660/
elements 380 ... 690 V conductor/PEN SET, approx.
400 V M)
kW kW A mm2 kg
Main control switches complete with rotary operating mechanism, black1)
3 -- 65 110 125 35/352) C 8HP2 707 1 1 unit 046 5.240
80 150 160 120/702) C 8HP2 711 1 1 unit 046 8.039
132 220 250 150/702) C 8HP2 712 1 1 unit 046 12.242
200 375 400 2 × 150 or C 8HP2 717 1 1 unit 046 12.378
1 × 240/120
350 375 630 2 × 240/120 C 8HP2 718 1 1 unit 046 13.050
315 315 8003)
2 × 240/240 C 8HP2 738 1 1 unit 046 14.290
8HP2 7..
EMERGENCY-STOP switches complete with rotary operating mechanism,
red/yellow1)
3 -- 65 110 125 35/352) C 8HP2 747 1 1 unit 046 5.217
80 150 160 120/702) C 8HP2 748 1 1 unit 046 7.992
132 220 250 150/702) C 8HP2 761 1 1 unit 046 12.340
200 375 400 2 × 150 or C 8HP2 762 1 1 unit 046 12.354
1 × 240/120
350 375 630 2 × 240/120 C 8HP2 763 1 1 unit 046 12.875
315 315 8003)
2 × 240/240 C 8HP2 758 1 1 unit 046 14.329
1)
With PE/ground or N terminal.
2)
For a fifth conductor, the same terminal can be fitted additionally.
3)
At ambient temperatures up to 35 °C.
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Accessories
3SB14 00-0A
3KA50 40/3KA51 40/3KA52/3KA53
Terminal covers
For 3-pole 3KA52 devices (1set = 6 units) } 3KX3 552-3DA01 1 1 unit 103 0.077
For 4-pole 3KA52 devices (1set = 8 units) B 3KX3 552-3DB01 1 1 unit 103 0.102
3KX3 552-3DA01
For 3KA53 B 3KX3 553-3DB01 1 1 unit 103 0.170
Door-coupling rotary operating mechanisms
IP65
Black handle, shaft 300 mm C 8UC72 12-1BB20 1 1 unit 103 0.200
EMERGENCY-STOP (yellow/red), B 8UC72 22-3BB20 1 1 unit 103 0.200
square shaft 300 mm
Operating mechanisms for fixed mounting } 3KX3 536-1AA 1 1 unit 103 0.155
Black handle, shaft 250 mm
8UC72 12-1BB20 Extension shaft 300 mm long B 8UC60 32 1 1 unit 103 0.132
Extension shaft 600 mm long B 8UC60 82 1 1 unit 103 0.265
Shaft connecting pieces B 8UC60 22 1 1 unit 103 0.023
Auxiliary switches
1 NO + 1 NC B 3SB14 00-0A 1 1 unit 102 0.020
2 NO B 3SB14 00-0G 1 1 unit 102 0.020
2 NC B 3SB14 00-0H 1 1 unit 102 0.020
1 NO + 1 NC, 20 ms leading B 3KX3 552-3EA01 1 1 unit 103 0.019
3SB14 00-0A
3KA55/3KA57/3KA58
Terminal covers
For 3-pole devices (1set = 6 units) } 3KX3 557-3DA01 1 1 unit 103 0.277
For 4-pole devices (1set = 8 units) B 3KX3 557-3DB01 1 1 unit 103 0.362
Door-coupling rotary operating mechanisms
IP65
Black handle, shaft 300 mm C 8UC73 13-1BB30 1 1 unit 103 0.200
EMERGENCY-STOP (yellow/red), B 8UC73 23-3BB30 1 1 unit 103 0.200
square shaft 300 mm
Operating mechanisms for fixed mounting } 3KX3 176-1E 1 1 unit 103 0.285
Black handle, shaft 250 mm
Extension shaft 300 mm long C 8UC60 33 1 1 unit 103 0.217
Extension shaft 600 mm long B 8UC60 83 1 1 unit 103 0.430
3KX3 176-1E Shaft connecting pieces B 8UC60 23 1 1 unit 103 0.085
Auxiliary switches
1 NO + 1 NC B 3SB14 00-0A 1 1 unit 102 0.020
2 NO B 3SB14 00-0G 1 1 unit 102 0.020
2 NC B 3SB14 00-0H 1 1 unit 102 0.020
1 NO + 1 NC, 20 ms leading B 3KX3 552-3EA01 1 1 unit 103 0.019
3SB14 00-0A
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Accessories
3KX2 210-0D
Door-coupling rotary operating C 8UC74 14-1BF44 1 1 unit 103 0.200
mechanisms IP65
Handle (black), shaft 300 mm
Direct operating mechanisms
Twin handle (black) for fixed mounting
B 8UC93 81 1 1 unit 103 0.264
7
Changeover switches without interruption
Switch I ON – Switch II OFF B 3KX2 210-0E 1 1 unit 103 2.448
Switch I ON – Switch II ON
Switch I ON – Switch II ON
Door-coupling rotary operating
mechanisms IP65
Handle (black), shaft 300 mm C 8UC74 14-1FG44 1 1 unit 103 0.200
Direct operating mechanisms B 8UC93 81 1 1 unit 103 0.264
Twin handle (black) for fixed mounting
Parallel switches
Switch I ON – Switch II ON C 3KX2 250-1A 1 1 unit 103 0.750
Switch I OFF – Switch II OFF
Door-coupling rotary operating C 8UC74 14-1BB44 1 1 unit 103 0.200
mechanisms IP65
Handle (black), shaft 300 mm
EMERGENCY-STOP door-coupling rotary B 8UC74 24-3BB44 1 1 unit 103 0.200
operating mechanisms IP65
Twin handle (red), shaft 300 mm
Direct operating mechanisms B 8UC93 81 1 1 unit 103 0.264
Handle (black) for fixed mounting
Further accessories
Terminal covers } 3KX3 557-3DA01 1 1 unit 103 0.277
(1 set = 6 units)
3KX3 557-3DA01
Door-coupling rotary operating
mechanisms IP65
Black handle, shaft 300 mm C 8UC73 14-1BB44 1 1 unit 103 0.200
EMERGENCY-STOP (yellow/red), B 8UC73 24-3BB44 1 1 unit 103 0.200
square shaft 300 mm
Extension shaft 300 mm long B 8UC60 34 1 1 unit 103 0.315
Extension shaft 600 mm long B 8UC60 84 1 1 unit 103 0.640
Auxiliary switches with switching cam B 3KX2 231-1A 1 1 unit 103 0.049
1 NO + 1 NC (complete mounting kit)
3KX2 231-1A
Grounding brackets B 3KX2 252-1A 1 1 unit 103 0.049
Arc chute B 3KY2 202-0B 1 1 unit 103 0.640
(spare part with 3 arc-splitter assemblies)
Arcing contacts B 3KY2 204-0A 1 1 unit 103 0.202
(spare part with 3 fixed and 3 movable con-
tacts)
3KY2 204-0A
Switch Disconnectors
SENTRON 3KA, 3KE Switch Disconnectors up to 1000 A
Accessories
Switch I ON – Switch II ON
Door-coupling rotary operating C 8UC74 14-1FG44 1 1 unit 103 0.200
mechanisms IP65
Handle (black) for changeover switches
without interruption, shaft 300 mm
Direct operating mechanisms B 8UC93 81 1 1 unit 103 0.264
Twin handle (black) for fixed mounting
Parallel switches
Switch I ON – Switch II ON C 3KX2 250-1A 1 1 unit 103 0.750
Switch I OFF – Switch II OFF
Door-coupling rotary operating C 8UC74 14-1BB44 1 1 unit 103 0.200
mechanisms IP65
Handle (black), shaft 300 mm
EMERGENCY-STOP door-coupling rotary B 8UC74 24-3BB44 1 1 unit 103 0.200
operating mechanisms IP65
Twin handle (red), shaft 300 mm
Direct operating mechanisms B 8UC93 81 1 1 unit 103 0.264
Handle (black) for fixed mounting
Further accessories
Terminal covers B 3KX2 252-0C 1 1 unit 103 0.424
(top and bottom)
Door-coupling rotary operating
mechanisms IP65
Black handle, shaft 300 mm C 8UC73 14-1BB44 1 1 unit 103 0.200
EMERGENCY-STOP (yellow/red), square B 8UC73 24-3BB44 1 1 unit 103 0.200
shaft 300 mm
Extension shaft 300 mm long B 8UC60 34 1 1 unit 103 0.315
Extension shaft 600 mm long B 8UC60 84 1 1 unit 103 0.640
Auxiliary switches B 3KX2 231-1A 1 1 unit 103 0.049
3KX2 231-1A 1 NO + 1 NC (complete mounting kit)
Grounding brackets B 3KX2 252-1A 1 1 unit 103 0.049
Arc chute B 3KY2 232-0A 1 1 unit 103 1.040
(spare part with 3 arc-splitter assemblies)
Arcing contacts B 3KY2 234-0A 1 1 unit 103 0.105
Spare part with 3 fixed and 3 movable con-
tacts
3KY2 232-0A
Switch Disconnectors
SENTRON 3KL Switch Disconnectors with Fuses up to 800 A
Introduction
■ Overview
NSE0_01557b
1
4
7
6
3
3KL or 3KM basic device
Plug-in contact strip for 3KM Optional
3 Fuses, optionally BS-88 or LV HRC fuses 8UC9 knob for fixed mounting in standard version (black) or
EMERGENCY-STOP version (red), or
Terminal cover, IP20 (vertical to operator side) 9 8UC7 door-coupling rotary operating mechanism in standard
Coupling driver with extension shaft version (ti-grey) or EMERGENCY-STOP version (red/yellow)
All switch disconnectors feature double contact interruption and Identical accessories for 3KA load disconnectors and 3KL and
an isolating distance. As a result, the fuses of the switch discon- 3KM load disconnectors with fuses simplifies inventory.
nectors are de-energized in the OFF position. Please inquire about a special variant with reduced values that
Generally all 3K.5 switch disconnectors can can be secured to is particularly resistant to atmospheres high in sulfur, e.g. in the
the shaft with padlock against unauthorized reclosing. paper and cellulose processing industries.
■ Application
3KL switch disconnectors with fuses protect against overload All 3K switch disconnectors are climate-proof and meet the
and short-circuits as main and EMERGENCY-STOP switches of requirements of IEC 60947-1 and IEC 60947-3.
switch boards, distribution boards, power supply and motor out-
going feeders.
In conjunction with Siemens SITOR semiconductor fuses, they
are also used in UPS systems, frequency converters and capac-
itor control systems.
Switch Disconnectors
SENTRON 3KL Switch Disconnectors with Fuses up to 800 A
Introduction
■ Technical specifications
Standards IEC 60947-1, IEC 60947-3
Type 3KL50 3KL521) 3KL531) 3KL551) 3KL571) 3KL611) 3KL621)
Rated uninterrupted current Iu A 63 125 160 250 400 630 800
For fuse links acc. to DIN 43620, Size 00 and 00 and 00 and 1 and 2 1 and 2 3 and 2 3 and 2
(when SITOR semiconductor fuses are used, 000 000 000
a reduction of rated current is necessary,
see reference to technical information at start of chapter)
Conventional free-air thermal current Ith2) A 63 125 160 250 400 630 800
Rated insulation voltage Ui V 690 1000 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp kV 6 8 8 8 8 8 8
Rated operational voltage Ue
50/60 Hz AC V 690
DC V 440 (3 conducting paths series-connected)
220 (2 conducting paths series-connected) 3)
Rated short-circuit making capacity with fuses kA 220 220 220 176 176 105 105
peak value at 50/60 Hz 690 V AC
Max. rated current In of the fuses A 80 160 160 400 400 6304) 800
Max. permissible power loss of the installed fuse
• NH W 6 9 11.5 32 45 48 62
• BS W 8 (A2/A3) 11.5 (A4) 11.5 32 45 48 60.5
Permissible let-through current of the fuses kA 8 17 17 305) 305) 50 50
Maximum permissible let-through I2t value kA2s 55 223 223 1000 1000 5400 10500
Switching capacity (infeed from the top or bottom)
At 400 V AC
• Breaking current Ic (at p.f. = 0.35, rms) A 500 1000 1280 2000 3200 5100 6400
• Rated operational current Ie with AC-21A, AC-22A, AC-23A A 63 125 160 250 400 6306) 8006)
• Motor switching capacity AC-23A kW 30 65 80 132 200 335 400
At 500 V AC
• Breaking current Ic (at p.f. = 0.35, rms) A 500 1000 1280 2000 3200 5100 6400
• Rated operational current Ie with AC-21A, AC-22A, AC-23A A 63 125 160 250 400 6306) 8006)
• Motor switching capacity AC-23A kW 40 90 110 185 280 425 500
At 690 V AC
• Breaking current Ic (at p.f. = 0.35, rms) A 500 1000 1280 2000 3200 5100 6400
• Rated operational current Ie with AC-21A, AC-22A, AC-23A A 63 125 160 250 400 6305) 8005)
• Motor switching capacity AC-23A kW 50 110 150 220 375 560 700
At 440 V DC (3 conducting paths series-connected)7)
• Breaking current Ic (L/R = 15 ms) A 250 500 640 10008) 1600 25209) 25209)
• Rated operational current Ie at DC-23A A 63 125 160 25010) 400 63010) 63010)
Rated short-time current Icw (1 s current, rms value) kA 2.5 3.2 3.2 8 11 32 32
Permissible ambient temperature °C -25 ... +55 for operation4),
°C -50 ... +80 when stored
Mechanical endurance, operating cycles 15000 15000 15000 12000 12000 3000 3000
Degree of protection IP00/IP20 (from the operator side, with fuse and terminal covers)
Power loss of the switch disconnector at Ith W 8.5 22 36 33 86 140 225
(plus power loss of the fuses)
Main conductor connections
Busbar systems, max. dimensions (w x t) mm 25 x 9 45 x 10 45 x 10 40 x 12 40 x 15 40 x 17 40 x 17
Cable lug, max. conductor cross-section (stranded) mm2 35 70 120 150 2 x 150 or 2 x 240 2 x 240
1 x 240
Tightening torque Nm 6 ... 7.5 7 ... 10 18 ... 22 35 ... 45 35 ... 45 56 56
Terminal screws M6 M6 M8 M10 M10 M12 M12
Protective conductor connections
Flat bars mm -- -- -- 20 x 2.5 20 x 2.5 -- --
Cable lug, max. conductor cross-section (stranded) mm2 -- -- -- 70 120 -- --
1)
Technical specifications for approval on request. Note:
2)
Configuring note: Max. permissible operating temperature for fuse blades
135 °C, for connections 100 °C. For the 3KL switch disconnectors, complete kits for standard
3) and EMERGENCY-STOP application are available for installation
110 V (one conducting path).
4)
in the side and rear panels of control cabinets.
With 3KL61 for operation -25 °C ... +35 °C, at +55 °C: Ith = 570 A.
5)
With 3ND1 switchgear protection fuse.
6)
AC-23B.
7)
220 V DC (L1 and L3 series-connected) or 110 V DC
(one conducting path) at DC-23A.
8)
At 440 V L/R = 4 ms, at 220 V L/R = 15 ms.
9)
Only DC-22A (L/R = 2.5 ms)
10)
At 440 V DC-22A, at 220 V DC-23A.
Switch Disconnectors
SENTRON 3KL Switch Disconnectors with Fuses up to 800 A
Floor mounting
7
400 2 and 1 gG, aM B 3KL57 30-1GB01 1 1 unit 103 6.067
630 3 and 2 gG, aM B 3KL61 30-1GB00 1 1 unit 113 18.070
6303) 3 and 23) gG, aM3) D 3KL61 30-1GB02 1 1 unit 113 15.200
8003) 3 and 23) gG, aM3) C 3KL62 30-1GB02 1 1 unit 113 15.200
4-pole for NH fuse systems
63 00 and 000 gG, aM B 3KL50 40-1GB01 1 1 unit 103 2.542
125 00 and 000 gG, aM B 3KL52 40-1GB01 1 1 unit 103 2.623
160 00 and 000 gG, aM C 3KL53 40-1GB01 1 1 unit 103 2.776
250 1 and 2 gG, aM B 3KL55 40-1GB01 1 1 unit 103 6.642
400 2 and 1 gG, aM B 3KL57 40-1GB01 1 1 unit 103 6.886
630 3 and 2 gG, aM B 3KL61 40-1GB00 1 1 unit 113 16.690
3-pole for fuses acc. to BS 88
63 Form A2/A3 B 3KL50 30-1GG01 1 1 unit 103 1.455
125 Form A2/A3 B 3KL52 30-1GG01 1 1 unit 103 2.360
125 Form A4 B 3KL52 30-1GJ01 1 1 unit 103 2.406
160 Form A4 B 3KL53 30-1GJ01 1 1 unit 103 2.575
250 Form B1-B3 B 3KL55 30-1GG01 1 1 unit 103 6.115
400 Form B1-B3 B 3KL57 30-1GG01 1 1 unit 103 6.582
630 Form C1-C3 C 3KL61 30-1GG00 1 1 unit 113 16.278
800 Form C1-C3 D 3KL62 30-1GG00 1 1 unit 113 15.400
4-pole for fuses acc. to BS 88
63 Form A2/A3 B 3KL50 40-1GG01 1 1 unit 103 2.563
125 Form A2/A3 B 3KL52 40-1GG01 1 1 unit 103 2.560
125 Form A4 B 3KL52 40-1GJ01 1 1 unit 103 2.614
160 Form A4 B 3KL53 40-1GJ01 1 1 unit 103 2.780
250 Form B1-B3 B 3KL55 40-1GG01 1 1 unit 103 6.639
400 Form B1-B3 B 3KL57 40-1GG01 1 1 unit 103 7.148
630 Form C1-C3 C 3KL61 40-1GG00 1 1 unit 113 16.996
Basic switch versions without handle
3-pole for NH fuse systems
63 00 and 000 gG, aM } 3KL50 30-1AB01 1 1 unit 103 1.055
125 00 and 000 gG, aM } 3KL52 30-1AB01 1 1 unit 103 1.989
160 00 and 000 gG, aM } 3KL53 30-1AB01 1 1 unit 103 2.200
250 1 and 2 gG, aM } 3KL55 30-1AB01 1 1 unit 103 5.715
400 2 and 1 gG, aM } 3KL57 30-1AB01 1 1 unit 103 5.400
630 3 and 2 gG, aM A 3KL61 30-1AB0 1 1 unit 113 17.696
3KL52 30-1AB01 6303) 3 and 23) gG, aM3) A 3KL61 30-1AB02 1 1 unit 113 14.000
8003) 3 and 23) gG, aM3) A 3KL62 30-1AB02 1 1 unit 113 15.200
4-pole for NH fuse systems
63 00 and 000 gG, aM B 3KL50 40-1AB01 1 1 unit 103 2.219
125 00 and 000 gG, aM B 3KL52 40-1AB01 1 1 unit 103 2.195
160 00 and 000 gG, aM B 3KL53 40-1AB01 1 1 unit 103 2.344
250 1 and 2 gG, aM B 3KL55 40-1AB01 1 1 unit 103 5.577
400 2 and 1 gG, aM B 3KL57 40-1AB01 1 1 unit 103 5.670
630 3 and 2 gG, aM A 3KL61 40-1AB00 1 1 unit 113 15.423
3KL52 40-1AB01
3-pole for fuses acc. to BS 88
63 Form A2/A3 B 3KL50 30-1AG01 1 1 unit 103 0.993
125 Form A2/A3 B 3KL52 30-1AG01 1 1 unit 103 1.939
125 Form A4 B 3KL52 30-1AJ01 1 1 unit 103 2.033
160 Form A4 B 3KL53 30-1AJ01 1 1 unit 103 2.170
250 Form B1-B3 B 3KL55 30-1AG01 1 1 unit 103 5.145
400 Form B1-B3 B 3KL57 30-1AG01 1 1 unit 103 5.666
3KL52 30-1AJ01
630 Form C1-C3 A 3KL61 30-1AG00 1 1 unit 113 15.075
800 Form C1-C3 C 3KL62 30-1AG00 1 1 unit 113 14.200
Fuse monitoring through 5TT3 170 safety monitor with a floating For footnotes, see page 7/46.
1 NO signaling contact, see chapter 5 "Fuse Systems".
* You can order this quantity or a multiple thereof.
Siemens LV 10.1 · 2011 7/45
© Siemens AG 2010
Switch Disconnectors
SENTRON 3KL Switch Disconnectors with Fuses up to 800 A
Floor mounting
Rated uninterrupted LV HRC fuse links1) DT Order No. Price PU PS*/ PG Weight
current Iu acc. to DIN 436202) per PU (UNIT, P. unit per PU
SET, approx.
M)
Size Operational
class
A kg
4-pole for fuses acc. to BS 88
63 Form A2/A3 B 3KL50 40-1AG01 1 1 unit 103 2.145
125 Form A2/A3 B 3KL52 40-1AG01 1 1 unit 103 2.161
125 Form A4 B 3KL52 40-1AJ01 1 1 unit 103 2.120
160 Form A4 B 3KL53 40-1AJ01 1 1 unit 103 2.230
250 Form B1-B3 B 3KL55 40-1AG01 1 1 unit 103 5.666
400 Form B1-B3 B 3KL57 40-1AG01 1 1 unit 103 6.441
3KL52 40-1AJ01
with fuses 630 Form C1-C3 C 3KL61 40-1AG00 1 1 unit 113 15.708
8UC7 EMERGENCY-STOP door-coupling rotary operating mechanisms
(red handle, yellow indicator plate)
for basic switch versions without handle
7 3-pole for NH fuse systems
63 00 and 000 gG, aM B 8UC71 21-3BB10 1 1 unit 103 0.200
125 00 and 000 gG, aM B 8UC72 22-3BB20 1 1 unit 103 0.200
160 00 and 000 gG, aM B 8UC72 22-3BB20 1 1 unit 103 0.200
250 1 and 2 gG, aM B 8UC73 23-3BB30 1 1 unit 103 0.200
400 2 and 1 gG, aM B 8UC73 23-3BB30 1 1 unit 103 0.200
630 3 and 2 gG, aM B 8UC74 24-3BB44 1 1 unit 103 0.200
+
8UC71 21-3BB10
} 8UC92 53 1 1 unit 103 0.115
800 3 and 2 gG, aM B 8UC74 24-3BB44 1 1 unit 103 0.200
+
} 8UC92 53 1 1 unit 103 0.115
4-pole for NH fuse systems
63 00 and 000 gG, aM B 8UC72 22-3BB20 1 1 unit 103 0.200
125 00 and 000 gG, aM B 8UC72 22-3BB20 1 1 unit 103 0.200
160 00 and 000 gG, aM B 8UC72 22-3BB20 1 1 unit 103 0.200
250 1 and 2 gG, aM B 8UC73 23-3BB30 1 1 unit 103 0.200
400 2 and 1 gG, aM B 8UC73 23-3BB30 1 1 unit 103 0.200
630 3 and 2 gG, aM B 8UC74 24-3BB44 1 1 unit 103 0.200
+
} 8UC92 53 1 1 unit 103 0.115
3-pole for fuses acc. to BS 88
63 Form A2/A3 B 8UC71 21-3BB10 1 1 unit 103 0.200
125 Form A2/A3 B 8UC72 22-3BB20 1 1 unit 103 0.200
125 Form A4 B 8UC72 22-3BB20 1 1 unit 103 0.200
160 Form A4 B 8UC72 22-3BB20 1 1 unit 103 0.200
250 Form B1-B3 B 8UC73 23-3BB30 1 1 unit 103 0.200
400 Form B1-B3 B 8UC73 23-3BB30 1 1 unit 103 0.200
630 Form C1-C3 B 8UC74 24-3BB44 1 1 unit 103 0.200
+
} 8UC92 53 1 1 unit 103 0.115
800 Form C1-C3 B 8UC74 24-3BB44 1 1 unit 103 0.200
+
} 8UC92 53 1 1 unit 103 0.115
4-pole for fuses acc. to BS 88
63 Form A2/A3 B 8UC72 22-3BB20 1 1 unit 103 0.200
125 Form A2/A3 B 8UC72 22-3BB20 1 1 unit 103 0.200
125 Form A4 B 8UC72 22-3BB20 1 1 unit 103 0.200
160 Form A4 B 8UC72 22-3BB20 1 1 unit 103 0.200
250 Form B1-B3 B 8UC73 23-3BB30 1 1 unit 103 0.200
400 Form B1-B3 B 8UC73 23-3BB30 1 1 unit 103 0.200
630 Form C1-C3 B 8UC74 24-3BB44 1 1 unit 103 0.200
+
} 8UC92 53 1 1 unit 103 0.115
Switch Disconnectors
SENTRON 3KL Switch Disconnectors with Fuses up to 800 A
Front mounting
7
63 00 gG, aM B 3KX3 516-3AA 1 1 unit 103 0.626
125 00 gG, aM B 3KX3 526-3AA 1 1 unit 103 0.820
160 00 gG, aM B 3KX3 536-3AA 1 1 unit 103 0.880
250 1 and 2 gG, aM B 3KX3 556-3AA 1 1 unit 103 1.720
400 2 and 1 gG, aM B 3KX3 556-3AA 1 1 unit 103 1.720
• EMERGENCY-STOP red handle
63 00 gG, aM B 3KX3 516-3BA 1 1 unit 103 0.625
125 00 gG, aM B 3KX3 526-3BA 1 1 unit 103 0.846
160 00 gG, aM B 3KX3 536-3BA 1 1 unit 103 0.883
250 1 and 2 gG, aM B 3KX3 556-3BA 1 1 unit 103 1.690
400 2 and 1 gG, aM B 3KX3 556-3BA 1 1 unit 103 1.690
Switch Disconnectors
SENTRON 3KL Switch Disconnectors with Fuses up to 800 A
Accessories
3KX3 5.7-3AA
7
Cover IP20 } 3KX3 507-0CA02 1 1 unit 103 0.400
For 3-pole devices
Fuse partitions } 3KX3 507-0AA01 1 1 unit 103 0.044
(1 set = 5 units)
Lyre-shaped fuse covers B 3KX3 507-0BA01 1 1 unit 103 0.033
(1 set = 6 units)
3KX3 507-0BA01
Door-coupling rotary operating mechanisms IP65
Black handle, shaft 300 mm C 8UC71 11-1BB10 1 1 unit 103 0.200
EMERGENCY-STOP (yellow/red), square shaft 300 mm B 8UC71 21-3BB10 1 1 unit 103 0.200
Operating mechanisms for fixed mounting } 3KX3 516-1AA 1 1 unit 103 0.088
Black handle, shaft 250 mm
Extension shaft 300 mm long B 8UC60 31 1 1 unit 103 0.068
Extension shaft 600 mm long B 8UC60 81 1 1 unit 103 0.136
Shaft connecting pieces B 8UC60 21 1 1 unit 103 0.031
Auxiliary switches
1 NO + 1 NC B 3SB14 00-0A 1 1 unit 102 0.020
2 NO B 3SB14 00-0G 11.90 1 1 unit 102 0.020
2 NC B 3SB14 00-0H 11.90 1 1 unit 102 0.020
3SB14 00-0A
Fuse monitor connections B 3KX3 505-0AA 1 1 unit 103 0.014
(1 set = 6 units)
3KL50 40/3KL52/3KL53
Terminal covers
For 3-pole devices (1 set = 6 units)
3KX3 552-3DA01 • 3KL52 } 3KX3 552-3DA01 1 1 unit 103 0.077
• 3KL53 } 3KX3 553-3DA01 1 1 unit 103 0.147
For 4-pole devices (1set = 8 units)
• 3KL50 40, 3KL52 B 3KX3 552-3DB01 1 1 unit 103 0.102
• 3KL53 B 3KX3 553-3DB01 1 1 unit 103 0.170
Fuse covers1) } 3KX3 527-3AA 1 1 unit 103 0.071
(interlock only detachable in the OFF position)
3KX3 5.7-3AA
Cover IP20 } 3KX3 527-0CA02 1 1 unit 103 0.765
For 3KL52 3-pole devices
Cover IP20 } 3KX3 537-0CA02 1 1 unit 103 0.765
For 3KL53 3-pole devices
Fuse partitions } 3KX3 507-0AA01 1 1 unit 103 0.044
(1 set = 5 units)
Lyre-shaped fuse covers B 3KX3 507-0BA01 1 1 unit 103 0.033
(1 set = 6 units)
3KX3 507-0BA01
1) For 3KX3 527-3AA: Not suitable for use with type A4 BS fuses.
Switch Disconnectors
SENTRON 3KL Switch Disconnectors with Fuses up to 800 A
Accessories
3SB14 00-0A
1 NO + 1 NC, 20 ms leading B 3KX3 552-3EA01 1 1 unit 103 0.019 7
Fuse monitor connections B 3KX3 505-0AA 1 1 unit 103 0.014
(1 set = 6 units)
3KL55/3KL57
Terminal covers
For 3-pole devices (1set = 6 units) } 3KX3 557-3DA01 1 1 unit 103 0.277
For 4-pole devices (1set = 8 units) B 3KX3 557-3DB01 1 1 unit 103 0.362
Fuse covers } 3KX3 557-3AA 1 1 unit 103 0.212
(interlock only detachable in the OFF position)
3KX3 5.7-3AA
Cover IP20 } 3KX3 557-0CA02 1 1 unit 103 1.235
For 3-pole devices
Fuse partitions } 3KX3 557-0AA01 1 1 unit 103 0.162
(1 set = 5 units)
Door-coupling rotary operating mechanisms IP65
Black handle, shaft 300 mm C 8UC73 13-1BB30 1 1 unit 103 0.200
EMERGENCY-STOP (yellow/red), square shaft 300 mm B 8UC73 23-3BB30 1 1 unit 103 0.200
Operating mechanisms for fixed mounting, size 3 } 3KX3 176-1E 1 1 unit 103 0.285
Black handle, shaft 250 mm
3KX3 176-1E
Extension shaft 300 mm long C 8UC60 33 1 1 unit 103 0.217
Extension shaft 600 mm long B 8UC60 83 1 1 unit 103 0.430
Shaft connecting pieces B 8UC60 23 1 1 unit 103 0.085
Auxiliary switches
1 NO + 1 NC B 3SB14 00-0A 1 1 unit 102 0.020
2 NO B 3SB14 00-0G 1 1 unit 102 0.020
2 NC B 3SB14 00-0H 1 1 unit 102 0.020
1 NO + 1 NC, 20 ms leading B 3KX3 552-3EA01 1 1 unit 103 0.019
3SB14 00-0A
Fuse monitor connections B 3KX3 505-0AA 1 1 unit 103 0.014
(1 set = 6 units)
Switch Disconnectors
SENTRON 3KL Switch Disconnectors with Fuses up to 800 A
Accessories
7
} 8UC92 53 1 1 unit 103 0.115
Operating mechanisms for fixed mounting, size 5 } 3KX3 616-1A 1 1 unit 103 0.490
Black handle, shaft 250 mm
Extension shaft 300 mm long B 8UC60 34 1 1 unit 103 0.315
Extension shaft 600 mm long B 8UC60 84 1 1 unit 103 0.640
Shaft connecting pieces B 8UC60 24 1 1 unit 103 0.077
Auxiliary switches2)
1 NO + 1 NC C 3KX3 612-1B 1 1 unit 113 0.201
1) 2)
Only for NH fuse systems. For more 3SB34 00-0. contact blocks with other contact types, see
catalog IC 10, chapter 10 "Pushbutton Units and Indicator Lights".
SITOR fuses for 3KL and KM fuse switch disconnectors: Assignment table
For switch disconnectors SITOR fuses Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
Type 3KL Permissible Required Size Opera- Rated Rated DT SET, M) approx.
(Type 3KM) load current1) conductor tional current voltage
cross- class
section
Cu
A mm 2 A V kg
SITOR 3NE1 fuses for 3KL5, 3KL6 and 3 KM5
3KL50 30 16 1.5 000 1) gR/gS 16 690 } 3NE1 813-0 1 3 units 047 0.133
(3KM50 30) 20 2.5 000 1) gR/gS 20 690 } 3NE1 814-0 1 3 units 047 0.124
25 4 000 1) gR/gS 25 690 } 3NE1 815-0 1 3 units 047 0.127
35 6 000 1) gR/gS 35 690 } 3NE1 803-0 1 3 units 047 0.128
40 10 000 1) gR/gS 40 690 } 3NE1 802-0 1 3 units 047 0.126
50 10 000 1) gR/gS 50 690 } 3NE1 817-0 1 3 units 047 0.129
63 16 000 1) gR/gS 63 690 } 3NE1 818-0 1 3 units 047 0.126
3KL52 30 80 25 000 1) gR/gS 80 690 } 3NE1 820-0 1 3 units 047 0.124
(3KM52 30) 100 35 00 gR/gS 100 690 } 3NE1 021-0 1 3 units 047 0.204
125 50 00 gR/gS 125 690 } 3NE1 022-0 1 3 units 047 0.195
125 50 00 gR 125 690 A 3NE1 022-2 1 3 units 047 0.195
3KL55 30 160 70 1 gR/gS 160 690 } 3NE1 224-0 1 3 units 047 0.522
(3KM55 30) 160 70 1 gR 160 690 A 3NE1 224-2 1 3 units 047 0.535
200 95 1 gR/gS 200 690 } 3NE1 225-0 1 3 units 047 0.518
200 95 1 gR 200 690 A 3NE1 225-2 1 3 units 047 0.508
250 120 1 gR/gS 250 690 } 3NE1 227-0 1 3 units 047 0.515
245 120 1 gR 250 690 A 3NE1 227-2 1 3 units 047 0.533
3KL57 30 315 2 × 70 1 gR/gS 315 690 A 3NE1 230-0 1 3 units 047 0.519
(3KM57 30) 280 2 × 70 1 gR 315 690 A 3NE1 230-2 1 3 units 047 0.519
3KL57 350 (330)2) 2 × 95 2 gR/gS 350 690 } 3NE1 331-0 1 3 units 047 0.687
3KL61 30 350 (300)2) 2 × 95 2 gR 400 690 A 3NE1 331-2 1 3 units 047 0.684
(3KM57 30) 400 (375) 2) 2 × 95 2 gR/gS 400 690 } 3NE1 332-0 1 3 units 047 0.519
3KL61 30 450 (400) 2) 2 × 120 2 gR/gS 450 690 A 3NE1 333-0 1 3 units 047 0.689
(3KM57 30) 450 (325) 2) 2 × 120 2 gR 450 690 A 3NE1 333-2 1 3 units 047 0.691
500 (400) 2) 2 × 120 2 gR/gS 500 690 A 3NE1 334-0 1 3 units 047 0.765
500 (350) 2) 2 × 120 2 gR 500 690 A 3NE1 334-2 1 3 units 047 0.695
1)
Permissible load current in the switch disconnector.
In the case of cyclic loads, the currents may have to be reduced again
(precise values on request).
2)
Values in blue in brackets apply to 3KM switch disconnectors.
Switch Disconnectors
SENTRON 3KL Switch Disconnectors with Fuses up to 800 A
Accessories
For switch disconnectors SITOR fuses Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
Type 3KL Permissible Required Size Opera- Rated Rated DT SET, M) approx.
(Type 3KM) load current1) conductor tional current voltage
cross- class
section
Cu
A mm 2 A V kg
3KL61 30 630 (710)3) 2 x (40 x 5) 3 gR/gS 710 690 A 3NE1 437-0 1 3 units 047 1.045
(3KL62) 630 (710)3) 2 x (40 x 5) 3 gR 710 600 D 3NE1 437-1 1 3 units 047 1.179
630 (700)3) 2 x (40 x 5) 3 gR 710 690 B 3NE1 437-2 1 3 units 047 1.031
630 (800)3) 2 x (50 x 5) 3 gR/gS 800 690 A 3NE1 438-0 1 3 units 047 1.560
630 (800)3) 2 x (50 x 5) 3 gR 800 600 B 3NE1 438-1 1 3 units 047 1.100
630 (760)3) 2 x (50 x 5) gR 800 690 A 3NE1 438-2 1 3 units 047 1.067
630 (670)3) 2 x (40 x 5) 3 gR 670 690 A 3NE1 447-2 1 3 units 047 1.044
630 (790)3) 2 x (40 x 8) 3 gR 850 690 A 3NE1 448-2 1 3 units 047 1.048
SITOR fuses 3NE3 ... 3NE8, 3NC2 for 3KL5, 3KL6 and 3KM5
3KL50 25 4 00 gR 25 690 } 3NE8 015-1 1 3 units 047 0.193
(3KM50) 33 6 00 gR 35 690 } 3NE8 003-1 1 3 units 047 0.195
45
54
10
16
00
00
gR
gR
50
63
690
690
}
}
3NE8 017-1
3NE8 018-1
1
1
3 units
3 units
047
047
0.614
0.196 7
3KL52 68 25 00 aR 80 690 } 3NE8 020-1 1 3 units 047 0.206
(3KM52) 89 35 00 aR 100 690 } 3NE8 021-1 1 3 units 047 0.207
106 50 00 aR 125 690 } 3NE8 022-1 1 3 units 047 0.195
130 70 00 aR 160 690 } 3NE8 024-1 1 3 units 047 0.195
3KL552) 32 6 0 gR 32 1000 } 3NE4 101 1 3 units 047 0.824
(3KM55)2) 40 10 0 gR 40 1000 } 3NE4 102 1 3 units 047 0.258
50 10 0 gR 50 1000 } 3NE4 117 1 3 units 047 0.274
63 16 0 gR 63 1000 } 3NE4 118 1 3 units 047 0.257
80 25 0 aR 80 1000 } 3NE4 120 1 3 units 047 0.261
95 35 0 aR 100 1000 } 3NE4 121 1 3 units 047 0.260
120 50 0 aR 125 1000 } 3NE4 122 1 3 units 047 0.265
150 70 0 aR 160 1000 } 3NE4 124 1 3 units 047 0.274
90 35 1 aR 100 1000 A 3NE3 221 1 3 units 047 0.510
110 50 1 aR 125 1000 A 3NE3 222 1 3 units 047 0.506
140 70 1 aR 160 1000 } 3NE3 224 1 3 units 047 0.513
175 95 1 aR 200 1000 } 3NE3 225 1 3 units 047 0.586
210 120 1 aR 250 1000 } 3NE3 227 1 3 units 047 0.580
3KL57 240 185 1 aR 315 1000 } 3NE3 230-0B 1 3 units 047 0.513
(3KM57) 265 240 1 aR 350 1000 A 3NE3 231 1 3 units 047 0.515
290 240 1 aR 400 1000 A 3NE3 232-0B 1 3 units 047 0.520
320 2 × 150 1 aR 450 1000 } 3NE3 233 1 3 units 047 0.580
3KL61 340 (360)3) (290)4) 240 2 aR 400 1000 A 3NE3 332-0B 1 3 units 047 0.683
(3KL62) 380 (400)3) (320) 4) 2 × 150 2 aR 450 1000 A 3NE3 333 1 3 units 047 0.687
(3KM57) 440 (470)3) (360)4) 2 × 150 2 aR 500 1000 } 3NE3 334-0B 1 3 units 047 0.697
500 (530)3) (400)4) 2 × 185 2 aR 560 1000 } 3NE3 335 1 3 units 047 0.692
540 (580)3) (400)4) 2 × 185 2 aR 630 1000 } 3NE3 336 1 3 units 047 0.810
600 (640)3) (400)4) 2 × 200 2 aR 710 900 } 3NE3 337-8 1 3 units 047 0.687
630 (720)3) (400)4) 2 × 200 2 aR 800 800 } 3NE3 338-8 1 3 units 047 0.686
630 (800)3) (400)4) 2 × 200 2 aR 900 690 } 3NE3 340-8 1 3 units 047 0.657
200 (200)3) (175)4) 120 2 aR 250 800 } 3NE4 327-0B 1 3 units 047 0.780
260 (260)3) (230)4) 240 2 aR 315 800 } 3NE4 330-0B 1 3 units 047 1.539
370 (370)3) (340)4) 2 x (30 x 5) 2 aR 450 800 } 3NE4 333-0B 1 3 units 047 0.682
425 (450)3) (380)4) 2 x (30 x 5) 2 aR 500 800 } 3NE4 334-0B 1 3 units 047 0.683
600 (630)3) (400)4) 2 x (40 x 5) 2 aR 710 800 } 3NE4 337 1 3 units 047 0.689
3KL61 145 (150)3) 70 3 gR 150 500 B 3NC2 423-3C 1 3 units 047 0.940
(3KL62) 180 (190)3) 95 3 gR 200 500 B 3NC2 425-3C 1 3 units 047 0.940
225 (240)3) 120 3 gR 250 500 B 3NC2 427-3C 1 3 units 047 0.940
255 (270)3) 185 3 gR 300 500 B 3NC2 428-3C 1 3 units 047 0.940
330 (345)3) 240 3 gR 350 500 B 3NC2 431-3C 1 3 units 047 0.940
400 (400)3) 240 3 gR 400 500 B 3NC2 432-3C 1 3 units 047 0.940
135 (140)3) 70 3 gR 150 660 B 3NC8 423-3C 1 3 units 047 0.940
180 (190)3) 95 3 gR 200 660 B 3NC8 425-3C 1 3 units 047 0.940
225 (240)3) 120 3 gR 250 660 B 3NC8 427-3C 1 3 units 047 0.940
300 (315)3) 240 3 gR 350 660 B 3NC8 431-3C 1 3 units 047 0.940
425 (450)3) 2 × 150 3 gR 500 660 B 3NC8 434-3C 1 3 units 047 0.940
630 (800)3) 2 × (60 x 6) 3 aR 1000 600 C 3NC8 444-3C 1 3 units 047 0.940
1)
Permissible load current in the switch disconnector.
In the case of cyclic loads, the currents may have to be reduced again
(precise values on request).
2)
Due to the mechanical stress on the relatively long fuse blades,
SITOR 3NE4 1 fuses should be switchable only occasionally and
only at zero current.
3)
Values in black in brackets apply to 3KL62 switch disconnectors.
4)
Values in blue in brackets apply to 3KM switch disconnectors.
For technical specifications and dimensional drawings of the
SITOR fuses, see chapter 5 "Fuse Systems"
Switch Disconnectors
SENTRON 3KM Switch Disconnectors with Fuses and Isolating Plug Connector up to 400 A
Introduction
■ Overview
NSE0_01557b
1
4
7
6
3
3KL or 3KM basic device
Plug-in contact strip for 3KM Optional
3 Fuses, optionally BS-88 or LV HRC fuses 8UC9 knob for fixed mounting in standard version (black) or
EMERGENCY-STOP version (red), or
Terminal cover, IP20 (vertical to operator side) 9 8UC7 door-coupling rotary operating mechanism in standard
Coupling driver with extension shaft version (ti-grey) or EMERGENCY-STOP version (red/yellow)
All switch disconnectors feature double contact interruption and be secured to the shaft with padlock against unauthorized re-
an isolating distance. As a result, the fuses are de-energized closing.
when the switch disconnectors are in the disconnected position.
Identical accessories for 3KA switch disconnectors and for 3KL
The 3KM switch disconnectors with fuses also feature an isolat- and 3KM switch disconnectors with fuses simplify stock keep-
ing plug connector. This facilitates mounting and contact estab- ing. Please inquire about a special variant with reduced values
lishment in motor control centers (MCCs) in conjunction with ver- that is particularly resistant to atmospheres high in sulfur, e. g. in
tical busbars. Generally all 3K.5 switch disconnectors can can the paper and cellulose processing industries.
■ Application
3KM switch disconnectors with fuses protect against overload All 3K switch disconnectors are climate-proof and meet the
and short-circuits as main and EMERGENCY-STOP switches of requirements of IEC 60947-1 and IEC 60947-3.
switch boards, distribution boards, power supply and motor out-
going feeders. In conjunction with Siemens SITOR semiconduc-
tor fuses, they are also used in UPS systems, frequency
converters and capacitor control systems.
Switch Disconnectors
SENTRON 3KM Switch Disconnectors with Fuses and Isolating Plug Connector up to 400 A
Introduction
■ Technical specifications
Standards IEC 60947-1, IEC 60947-3
Type 3KM50 3KM52 3KM53 3KM55 3KM57
Rated uninterrupted current Iu A 63 125 160 250 400
For fuse links acc. to DIN 43620, Size 00 and 000 00 and 000 00 and 000 1 and 2 1 and 2
(when SITOR semiconductor fuses are used,
a reduction of rated current is necessary,
see reference to technical information at start of chapter)
Conventional free-air thermal current Ith1) A 63 125 160 250 400
Rated insulation voltage Ui V 690 1000 1000 1000 1000
Rated impulse withstand voltage Uimp kV 6 8 8 8 8
Rated operational voltage Ue
50/60 Hz AC V 690
DC V 440 (3 conducting paths series-connected)
V 220 (2 conducting paths series-connected) 2)
Rated short-circuit making capacity with fuses kA 220 220 220 176 176
7
(peak value, at 50/60 Hz 690 V AC)
Rated conditional short-circuit current with fuses kA 100 100 100 80 80
At 50/60 Hz 690 V AC (rms value)
Max. rated current In of the fuses A 80 160 160 400 400
Max. permissible power loss of the installed fuse
• NH W 6 9 11.5 32 45
• BS W 8 (A2/A3) 11.5 (A4) 11.5 32 45
Permissible let-through current of the fuses kA 8 17 17 303) 303)
Maximum permissible let-through I2t value kA2s 55 223 223 1000 1000
Switching capacity (infeed from the top or bottom)
At 400 V AC
• Breaking current Ic (at p.f. = 0.35, rms) A 500 1000 1280 2000 3200
• Rated operational current Ie with AC-21A, AC-22A, AC-23A A 63 125 160 250 400
• Motor switching capacity AC-23A kW 30 65 80 132 200
At 500 V AC
• Breaking current Ic (at p.f. = 0.35, rms) A 500 1000 1280 2000 3200
• Rated operational current Ie with AC-21A, AC-22A, AC-23A A 63 125 160 250 400
• Motor switching capacity AC-23A kW 40 90 110 185 280
At 690 V AC
• Breaking current Ic (at p.f. = 0.35, rms) A 500 1000 1280 2000 3200
• Rated operational current Ie with AC-21A, AC-22A, AC-23A A 63 125 160 250 400
• Motor switching capacity AC-23A kW 50 110 150 220 375
At 440 V DC (3 conducting paths series-connected)4)
• Breaking current Ic (L/R = 15 ms) A 250 500 640 10004) 1600
• Rated operational current Ie at DC-23A A 63 125 160 2505) 400
Rated short-time current (1 s current), rms value kA 2.5 3.2 3.2 8 11
Permissible ambient temperature °C -25 ... +55 for operation6)
°C -50 ... +80 when stored
Mechanical endurance, operating cycles 15000 15000 15000 12000 12000
Degree of protection IP00/IP20 (from the operator side, with fuse and terminal covers)
Power loss of the switch disconnector at Ith W 8.5 22 36 33 86
(plus power loss of the fuses)
Main conductor connections
Busbar systems, max. dimensions (w × t) mm 25 × 9 45 × 10 45 × 10 40 × 12 40 × 15
Cable lug, max. conductor cross-section (stranded) mm2 35 70 120 150 2 ∞ 150 or
1 × 240
Busbar systems, max. dimensions (w × t) mm 25 × 9 45 × 10 45 × 10 40 × 12 40 × 15
Tightening torque Nm 6 ... 7.5 7 ... 10 18 ... 22 35 ... 45 35 ... 45
Terminal screws M6 M6 M8 M10 M10
Protective conductor connections
Flat bars mm -- -- -- 20 × 2.5 20 × 2.5
Cable lug, max. conductor cross-section (stranded) mm2 -- -- -- 70 120
1)
Configuring note: Max. permissible operating temperature for fuse blades
135 °C, for connections 100 °C.
2)
110 V (one conducting path).
3)
220 V DC (L1 and L3 series-connected) or 110 V DC
(one conducting path) at DC-23A.
4)
At 440 V L/R = 4 ms, at 220 V L/R = 15 ms.
5)
At 440 V DC-22A, at 220 V DC-23A.
6)
3ND1 switchgear protection fuse.
Switch Disconnectors
SENTRON 3KM Switch Disconnectors with Fuses and Isolating Plug Connector up to 400 A
For snapping onto busbars
7
125 00 and 000 gG, aM B 3KM52 30-1GB01 1 1 unit 103 2.860
160 00 and 000 gG, aM B 3KM53 30-1GB01 1 1 unit 103 2.935
250 1 and 2 gG, aM B 3KM55 30-1GB01 1 1 unit 103 5.670
400 2 and 1 gG, aM B 3KM57 30-1GB01 1 1 unit 103 6.938
3-pole for fuses acc. to BS 88
• Complete versions with 8UC7 door-coupling rotary
operating mechanism (black handle)
125 Form A2/A3 C 3KM52 30-1GG01 1 1 unit 103 2.785
125 Form A4 C 3KM52 30-1GJ01 1 1 unit 103 2.340
160 Form A4 C 3KM53 30-1GJ01 1 1 unit 103 2.926
250 Form B1-B3 C 3KM55 30-1GG01 1 1 unit 103 6.651
400 Form B1-B3 C 3KM57 30-1GG01 1 1 unit 103 7.175
Basic switch versions without handle
3-pole for NH fuse systems
63 00 and 000 gG, aM B 3KM50 30-1AB01 1 1 unit 103 1.515
125 00 and 000 gG, aM B 3KM52 30-1AB01 1 1 unit 103 2.450
160 00 and 000 gG, aM C 3KM53 30-1AB01 1 1 unit 103 2.516
250 1 and 2 gG, aM B 3KM55 30-1AB01 1 1 unit 103 5.698
400 2 and 1 gG, aM B 3KM57 30-1AB01 1 1 unit 103 5.966
3KM53 30-1AB01
with fuses
3-pole for fuses acc. to BS 88
63 Form A2/A3 C 3KM50 30-1AG01 1 1 unit 103 1.450
125 Form A2/A3 C 3KM52 30-1AG01 1 1 unit 103 2.405
125 Form A4 C 3KM52 30-1AJ01 1 1 unit 103 2.430
160 Form A4 C 3KM53 30-1AJ01 1 1 unit 103 2.520
250 Form B1-B3 C 3KM55 30-1AG01 1 1 unit 103 5.689
400 Form B1-B3 C 3KM57 30-1AG01 1 1 unit 103 6.250
3KM55 30-1AG01
with fuses
8UC7 EMERGENCY-STOP door-coupling rotary operating mechanisms
(red handle, yellow indicator plate)
for basic switch versions without handle
63 00 and 000 gG, aM B 8UC71 21-3BB10 1 1 unit 103 0.200
125 00 and 000 gG, aM B 8UC72 22-3BB20 1 1 unit 103 0.200
160 00 and 000 gG, aM B 8UC72 22-3BB20 1 1 unit 103 0.200
250 1 and 2 gG, aM B 8UC73 23-3BB30 1 1 unit 103 0.200
400 2 and 1 gG, aM B 8UC73 23-3BB30 1 1 unit 103 0.200
• 8UC7 EMERGENCY-STOP door-coupling rotary operating
mechanisms (red handle, yellow indicator plate)
8UC71 21-3BB10
Switch Disconnectors
SENTRON 3KM Switch Disconnectors with Fuses and Isolating Plug Connector up to 400 A
Accessories
3KX3 5.7-3AA
Fuse partitions } 3KX3 507-0AA01 1 1 unit 103 0.044
(1 set = 5 units)
Lyre-shaped fuse covers B 3KX3 507-0BA01 1 1 unit 103 0.033
7
(1 set = 6 units)
3KX3 507-0BA01
Door-coupling rotary operating mechanisms IP65
Black handle, shaft 300 mm C 8UC71 11-1BB10 1 1 unit 103 0.200
EMERGENCY-STOP (yellow/red), square shaft 300 mm B 8UC71 21-3BB10 1 1 unit 103 0.200
Operating mechanisms for fixed mounting } 3KX3 516-1AA 1 1 unit 103 0.088
Black handle, shaft 250 mm
Extension shaft 300 mm long B 8UC60 31 1 1 unit 103 0.068
Extension shaft 600 mm long B 8UC60 81 1 1 unit 103 0.136
Shaft connecting pieces B 8UC60 21 1 1 unit 103 0.031
Auxiliary switches
1 NO + 1 NC B 3SB14 00-0A 1 1 unit 102 0.020
2 NO B 3SB14 00-0G 1 1 unit 102 0.020
2 NC B 3SB14 00-0H 1 1 unit 102 0.020
3SB14 00-0A
Fuse monitor connections B 3KX3 505-0AA 1 1 unit 103 0.014
(1 set = 6 units)
3KM52/3KM53
Terminal covers
For 3-pole devices (1set = 6 units) 3KM52 } 3KX3 552-3DA01 1 1 unit 103 0.077
3KM53 } 3KX3 553-3DA01 1 1 unit 103 0.147
For 4-pole devices (1set = 8 units) 3KM52 B 3KX3 552-3DB01 1 1 unit 103 0.102
3KM53 B 3KX3 553-3DB01 1 1 unit 103 0.170
Fuse covers1) } 3KX3 527-3AA 1 1 unit 103 0.071
(interlock only detachable in the OFF position)
3KX3 5.7-3AA
Fuse partitions } 3KX3 507-0AA01 1 1 unit 103 0.044
(1 set = 5 units)
Lyre-shaped fuse covers B 3KX3 507-0BA01 1 1 unit 103 0.033
(1 set = 6 units)
3KX3 507-0BA01
Door-coupling rotary operating mechanisms IP65
Black handle, shaft 300 mm C 8UC72 12-1BB20 1 1 unit 103 0.200
EMERGENCY-STOP (yellow/red), square shaft 300 mm B 8UC72 22-3BB20 1 1 unit 103 0.200
Operating mechanisms for fixed mounting } 3KX3 536-1AA 1 1 unit 103 0.155
Black handle, shaft 250 mm
1)
For 3KX3 527-3AA: Not suitable for use with type A4 BS fuses.
Switch Disconnectors
SENTRON 3KM Switch Disconnectors with Fuses and Isolating Plug Connector up to 400 A
Accessories
3KX3 5.7-3AA
Fuse partitions } 3KX3 557-0AA01 1 1 unit 103 0.162
(1 set = 5 units)
3KX3 557-0AA01
Door-coupling rotary operating mechanisms IP65
Black handle, shaft 300 mm C 8UC73 13-1BB30 1 1 unit 103 0.200
EMERGENCY-STOP (yellow/red), square shaft 300 mm B 8UC73 23-3BB30 1 1 unit 103 0.200
Operating mechanisms for fixed mounting, size 3 } 3KX3 176-1E 1 1 unit 103 0.285
Black handle, shaft 250 mm
3KX3 176-1E
Extension shaft 300 mm long C 8UC60 33 1 1 unit 103 0.217
Extension shaft 600 mm long B 8UC60 83 1 1 unit 103 0.430
Shaft connecting pieces B 8UC60 23 1 1 unit 103 0.085
Auxiliary switches
1 NO + 1 NC B 3SB14 00-0A 1 1 unit 102 0.020
2 NO B 3SB14 00-0G 1 1 unit 102 0.020
2 NC B 3SB14 00-0H 1 1 unit 102 0.020
1 NO + 1 NC, 20 ms leading B 3KX3 552-3EA01 1 1 unit 103 0.019
3SB14 00-0A
Fuse monitor connections B 3KX3 505-0AA 1 1 unit 103 0.014
(1 set = 6 units)
Switch Disconnectors
8UC Door-Coupling Rotary Operating Mechanisms
For 3K switch disconnectors
■ Overview
Available sizes
Rotary Size Rated Shaft profile Masking plate
operating torque1)
mecha-
nisms
Nm mm x mm mm x mm
8UC71 1 4 6x6 75 x 75
8UC72 2 9 8x8 75 x 75
8UC73 3 25 10 x 10 or 12 x 12 100 x 100
8UC74 4 40/552) 12 x 12 100 x 100
1)
Operating mechanisms tested with triple torque (according to
EN 60947-3). They are therefore also suitable for applications in this area.
2)
Operation with two hands.
Degree of protection
Degree of protection when installed is IP65. 7
Standards
8UC7 door-coupling rotary operating mechanisms are in line
with for example the following standards:
8UC7 rotary operating mechanism in STANDARD version (left) and Standard Title
EMERGENCY-STOP version (right) IEC 60204-1, EN 60204-1 Safety of machinery; Electrical equipment
of machines
With door-coupling rotary operating mechanisms it is also possi-
ble to operate switch disconnectors from the outside with the IEC 60439-1, EN 60439-1 Low-voltage switchgear and controlgear
assemblies
control cabinet doors closed
IEC 60947-3, EN 60947-3 Low-voltage switchgear and controlgear;
The rotary operating mechanisms are available in "STANDARD" Switches, disconnectors, switch discon-
and "EMERGENCY-STOP" versions with the following differ- nectors and fuse-combination units
ences:
• STANDARD version: Masking plates in light-gray with black
inscription, handles in ti-grey.
• EMERGENCY-STOP version: Masking plates in yellow with
black inscription, handles in red.
Switch Disconnectors
8UC Door-Coupling Rotary Operating Mechanisms
For 3K switch disconnectors
■ Benefits ■ Application
Can be locked 8UC7 door-coupling rotary operating mechanisms can be used
in electrical controls, distribution boards and switchboards in
The retractable locking device integrated in the handles is suit-
cases where switches have to be mounted behind covers, end
able for padlocks with shackle diameters of 4.5 mm to 8.5 mm
plates and doors that must be opened and where they are to be
(locks according to DIN 7465).
operated manually from outside.
Up to three padlocks with a shackle diameter of 8.5 mm and up
to five padlocks with a shackle diameter of 6 mm can be fitted Interlocking conditions
simultaneously. The basic versions of the rotary operating mechanisms comply
with the following interlocking conditions:
Non-interchangeability
• Operating mechanism and switch in "0" (OFF) position:
In order to ensure that, when installing switches and door-cou- The control cabinet door can be opened. With padlocks fitted,
pling operating mechanisms, all components are assembled in the control cabinet door remains locked however.
the correct position with respect to one another, the components
are provided with non-interchangeability features (rivel and lug). • Operating mechanism and switch in "I" (ON) position:
The control cabinet door cannot be opened in this position.
Stops However, the interlock can be overridden and the control cab-
inet door opened by trained personnel for performing checks.
7 Stops are used to prevent damage occuring as the result of ex-
cessive torque. These stops are supplied loose with the rotary
No padlocks can be fitted in "I" position.
operating mechanisms and can be fitted as required. Stops are Other interlocking conditions:
fitted at the factory to size 1 and 2 rotary operating mechanisms • If no door interlock is required, the user can remove the door
with a 90° operating angle (exception: 3RV motor starter protec- interlocking plate of the rotary operating mechanism.
tors/circuit breakers).
• It is easy for the user to fit padlocks to the rotary operating
Tolerance compensation mechanisms in the "I" position as well. In this case the door
cannot be opened, the operating mechanism cannot be actu-
8UC7 rotary operating mechanisms are capable of taking up a ated and the door interlock cannot be overridden.
radial eccentricity of max. 3 mm between the actuating shaft of
the switching device and the door-coupling rotary operating Operating conditions and ambient conditions
mechanism. Supporting the extension shaft is recommended
with greater tolerances. The temperature range for operation of the rotary operating
mechanisms is between -25 °C and +60 °C.
a
_0
09
45
Coupling a b Shaft Thanks to the use of glass fiber-reinforced molded plastic for
E0
NS drivers length handles and masking plates as well as metal components with
With tolerance +3 ±5 x surface protection, the rotary operating mechanisms are suit-
compensation able for rough conditions, high air humidity and aggressive at-
Without +1.5 ±2.5 x+23.5 mospheres.
tolerance
compensation
Switch Disconnectors
8UC Door-Coupling Rotary Operating Mechanisms
For 3K switch disconnectors
■ Design
Components Switch position
The rotary operating mechanisms consist of a masking plate In order to ensure compliance with locking and interlocking con-
with handle, including seal and fixing screws for door installa- ditions, the controls and operating mechanisms must be in-
tion, an extension shaft (300 mm) and a coupling driver to be stalled such that, with two-position switches the "0" position lies
mounted onto the switch shaft. at 9 o'clock and the "I" position at 12 o'clock.
Operating mechanisms for 3KA / 3KL / 3KM switch disconnec-
tors do not have a shaft coupling since the extension shaft is fit- 1
ted directly into the switch. Extension shafts with a length of 90°
600 mm are also available.
0°
2
7
NSE0_00352a
5
6 1 12 o'clock position
2 9 o'clock position
7
4
3
2 Positions for two-position switches with 90° operating angle
10
1
8
9
NSE0_00022a
Switch Disconnectors
8UC Door-Coupling Rotary Operating Mechanisms
For 3K switch disconnectors
Type A mm Nm Size
8UC71
For switch disconnectors with or without fuses 75
3KL501), 3KM501) 63 6x6 3 1
63 6x6 3
NSE00355
3KA501)
3KA511) 80 6x6 3
36
8UC72
For switch disconnectors with or without fuses
7
75
3KL52, 3KM52 125 8x8 7.5 2
NSE00356
3KL53, 3KM53 160 8x8 7.5
3KA52 125 8x8 7.5
3KA53 160 8x8 7.5 62
8UC73
For switch disconnectors with or without fuses 100
3KL55, 3KM55 250 10 x 10 16 3
3KL57, 3KM57 400 10 x 10 16
NSE00357
3KA55 250 10 x 10 16
3KA57 400 10 x 10 16
140
3KA58 630 10 x 10 16
NSE00357
3KE44 630 12 x 12 24
3KE45 1000 12 x 12 24
140
8UC74
For switch disconnectors with fuses 100
3KL612) 630 12 x 12 30 4
3KL622) 800 12 x 12 30
NSE00358
200
1) 3)
Valid only for 3-pole switching devices. For 4-pole switching devices, an The door interlocking plate must be removed.
operating mechanism with 8 x 8 mm actuating shaft must be used, 4)
With shortened 8UC60 16/8UC60 17 coupling driver and reduced toler-
see lower level for 3KA52, 3KL52 or 3KM52. ance compensation, see "Dimensional Drawings".
2)
Additionally required for 3KL61: 1 shaft coupling, order no. 8UC92 53,
see individual parts, table, page 7/62.
Switch Disconnectors
8UC Door-Coupling Rotary Operating Mechanisms
For 3K switch disconnectors
Individual parts
Version DT Rotary operating mechanisms, PU PS*/ PG Weight Handle with Coupling Extension shaft Shaft couplings
complete (UNIT, P. unit per PU masking plate drivers Length 300 mm
SET, M) approx.
Order No. Price Order No. Order No. Order No. Order No.
per PU kg
@ 6 mm @ 6 mm @ 6 mm by 6 mm
Standard C 8UC71 11-1BB10 1 1 unit 103 0.200 8UC71 10-1BB 8UC60 11 8UC60 31 Not required
Standard4) C 8UC71 61-1BB10 1 1 unit 103 0.200 8UC71 10-1BB 8UC60 16 8UC60 31 Not required
EMER- B 8UC71 21-3BB10 1 1 unit 103 0.200 8UC71 20-3BB 8UC60 11 8UC60 31 Not required
GENCY-
STOP
@ 8 mm @ 8 mm @ 8 mm by 8 mm
Standard C
Standard4) C
8UC72 12-1BB20
8UC72 62-1BB20
1
1
1 unit
1 unit
103
103
0.200 8UC72 10-1BB
0.200 8UC72 10-1BB
8UC60 12
8UC60 17
8UC60 32
8UC60 32
Not required
Not required
7
EMER- B 8UC72 22-3BB20 1 1 unit 103 0.200 8UC72 20-3BB 8UC60 12 8UC60 32 Not required
GENCY-
STOP
@ 10 mm @ 10 mm @ 10 mm by 10 mm
Standard C 8UC73 13-1BB30 1 1 unit 103 0.200 8UC73 10-1BB 8UC60 13 8UC60 33 Not required
EMER- B 8UC73 23-3BB30 1 1 unit 103 0.200 8UC73 20-3BB 8UC60 13 8UC60 33 Not required
GENCY-
STOP
@ 12 mm @ 12 mm @ 12 mm by 12 mm
Standard C 8UC73 14-1BB44 1 1 unit 103 0.200 8UC73 10-1BB 8UC60 14 8UC60 34 8UC60 24
EMER- B 8UC73 24-3BB44 1 1 unit 103 0.200 8UC73 20-3BB 8UC60 14 8UC60 34 8UC60 24
GENCY-
STOP
@ 12 mm @ 12 mm @ 12 mm by 12 mm
Standard C 8UC74 14-1BB44 1 1 unit 103 0.200 8UC74 10-1BB 8UC60 14 8UC60 34 8UC60 24
EMER- B 8UC74 24-3BB44 1 1 unit 103 0.200 8UC74 20-3BB 8UC60 14 8UC60 34 8UC60 24
GENCY-
STOP
@ 12 mm @ 12 mm @ 12 mm by 12 mm
Standard C 8UC74 14-1BF44 1 1 unit 103 0.200 8UC74 10-1BF 8UC60 14 8UC60 34 8UC60 24
@ 12 mm @ 12 mm @ 12 mm by 12 mm
Standard C 8UC74 14-1FG44 1 1 unit 103 0.200 8UC74 10-1FG 8UC60 14 8UC60 34 8UC60 24
@ 12 mm @ 12 mm @ 12 mm by 12 mm
Standard C 8UC74 14-1BB44 1 1 unit 103 0.200 8UC74 10-1BB 8UC60 14 8UC60 34 8UC60 24
Switch Disconnectors
8UC Door-Coupling Rotary Operating Mechanisms
Individual parts
8UC71
3KL52, 3KM52, 8UC72 2 8×8 Standard C 8UC72 10-1BB 1 1 unit 103 0.200
3KL53, 3KM53, EMER- C 8UC72 20-3BB 1 1 unit 103 0.200
3KA52, 3KA53 GENCY-
7
STOP
8UC72
3KL55, 3KM55, 8UC73 3 10 × 10 Standard C 8UC73 10-1BB 1 1 unit 103 0.200
3KL57, 3KM57, or EMER- C 8UC73 20-3BB 1 1 unit 103 0.200
3KA55, 3KA57, 12 x 12 GENCY-
3KE42, 3KE43, STOP
3KE44, 3KE45
8UC73
3KL61, 3KL62 8UC74 4 12 × 12 Standard C 8UC74 10-1BB 1 1 unit 103 0.200
EMER- C 8UC74 20-3BB 1 1 unit 103 0.200
GENCY-
STOP
3KE42, 3KE43, 8UC743) 4 12 × 12 Standard C 8UC74 10-1BF 1 1 unit 103 0.200
8UC74 3KE44, 3KE45 Standard C 8UC74 10-1FG 1 1 unit 103 0.200
Standard C 8UC74 10-1BB 1 1 unit 103 0.200
Rotary operating Cross-section of the DT Individual parts for 8UC6 PU PS*/ PG Weight
mechanisms actuating shaft door-coupling rotary (UNIT, P. unit per PU
operating mechanisms SET, M) approx.
Order No. Price
Type mm × mm per PU kg
Coupling drivers, extension shafts, shaft couplings and reducers
Coupling drivers for 3K
8UC71 6×6 B 8UC60 11 1 1 unit 103 0.078
8UC712) 6×6 A 8UC60 16 1 1 unit 103 0.070
8UC72 8×8 B 8UC60 12 1 1 unit 103 0.075
8UC722) 8×8 A 8UC60 17 1 1 unit 103 0.043
8UC73 10 × 10 B 8UC60 13 1 1 unit 103 0.251
8UC60 11 8UC73/74 12 × 12 B 8UC60 14 1 1 unit 103 0.253
Extension shafts 300 mm long
8UC71 6×6 B 8UC60 31 1 1 unit 103 0.068
8UC72 8×8 B 8UC60 32 1 1 unit 103 0.132
NSE0_00373 8UC73 10 × 10 C 8UC60 33 1 1 unit 103 0.217
Nut 8UC73/74 12 × 12 B 8UC60 34 1 1 unit 103 0.315
8UC60 31 ... 34
Extension shafts 600 mm long
8UC71 6×6 B 8UC60 81 1 1 unit 103 0.136
8UC72 8×8 B 8UC60 82 1 1 unit 103 0.265
NSE0_00373 8UC73 10 × 10 B 8UC60 83 1 1 unit 103 0.430
Nut 8UC73/74 12 × 12 B 8UC60 84 1 1 unit 103 0.640
8UC60 81 ... 84
Shaft couplings
8UC71 6×6 B 8UC60 21 1 1 unit 103 0.031
8UC72 8×8 B 8UC60 22 1 1 unit 103 0.023
NSE00374 8UC73 10 × 10 B 8UC60 23 1 1 unit 103 0.085
Steg 1) Niet 1) 8UC73/74 12 × 12 B 8UC60 24 1 1 unit 103 0.077
8UC60 21 to 8UC6024 8UC74 (3KL61) 12 × 12 } 8UC92 53 1 1 unit 103 0.115
Reducers
8UC71 8 × 8 to 6 × 6 C 8UC70 58 1 1 unit 103 0.200
8UC72 12 × 12 to 8 × 8 C 8UC70 50 1 1 unit 103 0.200
4
0 24
_0 45
g0 02
ns _0
g0
ns
8UC70 58 8UC70 50
1) 4)
Non-interchangeability features. Standard: Ti-grey handle, light-gray masking plate;
2)
Shortened coupling driver with reduced tolerance compensation. EMERGENCY-STOP: Red handle, yellow masking plate.
3)
For switch disconnectors as changeover switches in various versions,
see table on page 7/60
Switch Disconnectors
8UC Door-Coupling Rotary Operating Mechanisms
Operating mechanisms for fixed mounting
8UC93 60
3KA52 8×8 7.5 2 Black B 8UC93 62 1 1 unit 103 0.041
3KA53,
3KL52,
3KM52,
3KL53,
7
3KM53
Red B 8UC93 63 1 1 unit 103 0.044
3KL55, 10 × 10 16 3 Black B 8UC93 65 1 1 unit 103 0.138
3KM55,
3KL57,
8UC93 65 3KM57
3KA55, Red B 8UC93 66 1 1 unit 103 0.160
3KA57,
3KA58
3KE42, 12 × 12 16 3 Black 3) B 8UC93 70 1 1 unit 103 0.128
3KE43
3)
Red B 8UC93 71 1 1 unit 103 0.146
3KE44, 12 × 12 30 4 Black 3)
B 8UC93 74 1 1 unit 103 0.145
3KE45
Red 3) B 8UC93 75 1 1 unit 103 0.165
8UC93 74
3KL61 12 × 12 55 5 Black B 8UC93 81 1 1 unit 103 0.264
Red B 8UC93 82 1 1 unit 103 0.273
8UC93 81
1)
Operating mechanisms were tested with triple torque (EN 60947-3). They
are therefore qualified for use in all controls, especially for disconnectors.
2)
Red handle available on request.
3)
Also required: 3KX2 210-0H coupling socket.
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
Introduction
■ Overview
All key product features at a glance
• In-line
• Type-tested according to IEC EN 60947-3
• Voltage levels up to 690 V AC/440 V DC
• 160 A to 630 A for LV HRC and BS 88 fuse links, according to
IEC 60269-1/EN 60269-1
• 2-, 3- and 4-pole versions available
• 185 mm phase center distance of plug-in contacts
• Manually operated or with motorized operating mechanism
• Electronic fuse monitoring (EFM)
• Developed for switchgears in plug-in design
• Horizontal or vertical mounting position
• Front panel locked in ON position
,B
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
Introduction
■ Benefits ■ Function
Key advantages for switchgear manufacturers due to the Fuse monitoring
following:
Fuse monitoring is used to detect, indicate and report faults.
• Compact, modular design The electronic fuse monitors are available in 2 versions.
• Simple and efficient mounting due to incoming plug-in contact EFM10 electronic fuse monitor:
• High packing density in the field • For use up to 690 V AC
• Cable connection with cable clamps or cable lugs • Operational voltage < 20 V
• Can be mounted in different control cabinet depths • Display: ready-to-run
• Comprehensive range of accessories • Individual fault display per phase
The advantages for users are: • 1 CO contact as centralized fault signaling unit
• Conversion, retrofitting and replacement without switching off EFM20/25 electronic fuse monitor and line monitor:
the switchgear
• EFM20 for use up to 690 V AC, EFM25 for use up to 440 V DC
• Dead-state fuse replacement
• Operational voltage < 13 V (EFM20) < 20 V (EFM25)
7
• Maintenance free
• Test function
• High personal safety
• Closed-circuit principle or open-circuit principle
• Operating handle can be locked in OFF position
• 2 CO contacts as centralized fault signaling unit incl. line mon-
• Clear and unambiguous switch position indicator itoring functions with phase failure detection (EFM20), under-
voltage/overvoltage detection
■ Application
The plug-in 3NJ6 switch disconnectors with fuses are installed
in low-voltage distribution boards where a minimum amount of
space is available for a maximum number of cable ducts to the
power distribution. They can be easily fitted in all common con-
trol cabinets (minimum depth: 400 mm).
The plug-in 3NJ62 switch disconnectors with fuses are available
for rated uninterrupted currents from 160 A to 630 A.
LV HRC fuse links according to IEC 60269-1/EN 60269-1 (sizes
NH 00 to NH 3) or BS fuse links according to BS 88 provide over-
load and short-circuit protection up to 690 V AC.
The switch disconnectors can be retrofitted at any time with aux-
iliary switches, an ammeter (48 mm x 48 mm) and current trans-
formers, with no extra space required. For installation in control
cabinets of > 400 mm depth, the mounting depth of the discon- EFM10 electronic fuse monitor N
nectors can be increased by 200 mm using a contact extension.
Further installation accessories, such as guide rails and blank-
ing covers, complete the product range.
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
Introduction
■ Technical specifications
Main devices of sizes 00 and 1
Switching capacity H H H S H H S H
Rated insulation voltage Ui V 1000
Rated impulse withstand voltage Uimp V 8000
Rated operational current Ie A 63 100 160 -- 160 125 160 125 250
For LV HRC fuse links (NH type) -- -- 00 and 000 1
For BS fuse links acc. to BS 88 A3 A3 00T1) B2
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
Introduction
Main devices of sizes 2 and 3
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
Introduction
Auxiliary switches Electronic fuse monitor, DC-version (EFM 25)
Acc. to IEC 60947-5-1 Size 00 1 2/3
Rated insulation voltage Ui V 690 Blind power uptake VA S approx. 2.5
Rated impulse withstand voltage Uimp V 8000 Internal resistance of measurement MΩ Rin > 6
Rated operational current Ie circuit
• At AC15, Ue = 120 V A 8 Storage temperature °C - 20 ... + 80
• At AC15, Ue = 230 V A 6 Operating temperature °C - 5 ... + 55
• At AC15, Ue = 400 V A 4 Operating temperature °C - 5 ... + 35
• At AC15, Ue = 690 V A 2 (500 V and/or 500 A)
Protection rating in closed in-line IP40
Electronic fuse monitor AC-version (EFM 10) connector
Rated operating voltage of the main V DC 220 ... 440
Size 00 1 2/3 switching devices
Blind power uptake VA S approx. 2.5 Voltage limits % ±15
Internal resistance of measurement circuit MΩ Rin > 6 Undervoltage V 200
Storage temperature °C - 20 ... + 80 Overvoltage V 240
Operating temperature °C - 5 ... + 55 Voltage drop for faulty fuses V > 20
Operating temperature (500 V or 500 A) °C - 5 ... + 35
7
Delay time s 0.1
Protection rating in closed in-line IP40
connector Relay 2 as relay 1
(fuse
Rated operating voltage of the main V AC 230 ... 690 monitor)
switching devices Hz 50/60
Storage function Off
Voltage limits % ±15
Open/closed-circuit principle Closed-circuit principle
Signaling relay acc. to IEC 60947-5-1 A Ith = 1.5
kV Uimp = 4 Mode Run mode
V Ui = 250 Menu option Display of
Load capacity of the signaling relay voltage values/
signals
• Ue V 24 125 240
• DC - 13; Ie A 1 0.2 0.1 Signaling relay acc. to IEC 60947-5-1 A Ith = 1.5
• AC - 15; Ie A 1.5 kV Uimp = 4
V Ui = 250
Short-circuit protection Max. fuse protection
Diazed 2 A gG Signaling relay 1 1 changeover for fuse
monitoring
Electronic fuse monitor, AC-version (EFM 20) Signaling relay 2 1 changeover as output
for central fault
Size 00 1 2/3 OR as signaling relay 1
(presetting)
Blind power uptake VA S approx. 2.5
Load capacity of the signaling relay
Internal resistance of measurement circuit MΩ Rin > 6
• Ue V 24 125 240
Storage temperature °C - 20 ... + 80 • DC - 13; Ie A 1 0.2 0.1
Operating temperature °C - 5 ... + 55 • AC - 15; Ie A 1.5
Operating temperature (500 V or 500 A) °C - 5 ... + 35
Short-circuit protection Max. fuse protection
Protection rating in closed in-line IP40 Diazed 2 A gG
connector
Rated operating volatge of the main V AC 230 ... 690 Ammeters
switching devices Hz 50/60
Voltage limits % ±15
Inputs x/1 A or x/5 A
Undervoltage V 375
Overvoltage V 425 Overload
Voltage drop for faulty fuses V > 13 • Moving-iron measuring instruments 1.2 times
• Bi-metal measuring instruments 2 times
Delay time s 0.1
Relay 2 as relay 1 Slave pointer
(fuse • Moving-iron measuring instruments min --
monitor) • Bi-metal measuring instruments 15
min
Storage function Off
Power consumption
Open/closed-circuit principle Closed-circuit principle
• Moving-iron measuring instruments VA 0.6
Mode Run mode • Bi-metal measuring instruments 1
VA
Menu option Display of
voltage values/ Motorized operating mechanisms
signals
Signaling relay acc. to IEC 60947-5-1 A Ith = 1.5 Size 00 1 2/3
kV Uimp = 4 Control supply voltage V DC 24 ± 2
V Ui = 250
Power consumption A 1.1 1.3 2.8
Signaling relay 1 1 changeover for fuse
monitoring Service life (no limitation of circuit
Signaling relay 2 1 changeover as output breaker acc. to IEC 60947-3)
for central fault Operating cycles total 1600
OR as signaling relay 1 200
(presetting) Switch cycles under load
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC fuse links
7
160 00 C 3NJ62 02-4AA0@-0AA0 1 1 unit 143 3.630
250 1 C 3NJ62 12-4AA0@-0AA0 1 1 unit 143 6.750
400 2 C 3NJ62 22-4AA0@-0AA0 1 1 unit 143 15.000
630 3 C 3NJ62 32-4AA0@-0AA0 1 1 unit 143 15.360
Motorized operating mechanisms, EFM 25 N
160 00 C 3NJ62 02-4AE0@-0AA0 1 1 unit 143 7.450
250 1 C 3NJ62 12-4AE0@-0AA0 1 1 unit 143 7.450
400 2 C 3NJ62 22-4AE0@-0AA0 1 1 unit 143 15.700
630 3 C 3NJ62 32-4AE0@-0AA0 1 1 unit 143 16.060
3-pole, standard switching capacity S
Manually operated N
160 00 A 3NJ62 03-1AA0@-@@@@ 1 1 unit 143 3.630
250 1 A 3NJ62 13-1AA0@-@@@@ 1 1 unit 143 6.750
400 2 A 3NJ62 23-1AA0@-@@@@ 1 1 unit 143 15.000
630 3 A 3NJ62 33-1AA0@-@@@@ 1 1 unit 143 15.360
Manually operated, EFM 10 N
160 00 B 3NJ62 03-1AB0@-@@@@ 1 1 unit 143 3.830
250 1 B 3NJ62 13-1AB0@-@@@@ 1 1 unit 143 6.950
400 2 B 3NJ62 23-1AB0@-@@@@ 1 1 unit 143 15.200
630 3 B 3NJ62 33-1AB0@-@@@@ 1 1 unit 143 15.560
Manually operated, EFM 20 N
160 00 B 3NJ62 03-1AC0@-@@@@ 1 1 unit 143 3.830
250 1 B 3NJ62 13-1AC0@-@@@@ 1 1 unit 143 6.950
400 2 B 3NJ62 23-1AC0@-@@@@ 1 1 unit 143 15.200
630 3 B 3NJ62 33-1AC0@-@@@@ 1 1 unit 143 15.560
3-pole, high switching capacity H
Manually operated
160 00 A 3NJ62 03-3AA0@-@@@@ 1 1 unit 143 3.630
250 1 A 3NJ62 13-3AA0@-@@@@ 1 1 unit 143 6.750
400 2 A 3NJ62 23-3AA0@-@@@@ 1 1 unit 143 15.000
630 3 A 3NJ62 33-3AA0@-@@@@ 1 1 unit 143 15.360
Manually operated, EFM 10 N
160 00 B 3NJ62 03-3AB0@-@@@@ 1 1 unit 143 3.830
250 1 B 3NJ62 13-3AB0@-@@@@ 1 1 unit 143 6.950
400 2 B 3NJ62 23-3AB0@-@@@@ 1 1 unit 143 15.200
630 3 B 3NJ62 33-3AB0@-@@@@ 1 1 unit 143 15.560
Manually operated, EFM 20 N
160 00 B 3NJ62 03-3AC0@-@@@@ 1 1 unit 143 3.830
250 1 B 3NJ62 13-3AC0@-@@@@ 1 1 unit 143 6.950
400 2 B 3NJ62 23-3AC0@-@@@@ 1 1 unit 143 15.200
630 3 B 3NJ62 33-3AC0@-@@@@ 1 1 unit 143 15.560
Motorized operating mechanisms
160 00 C 3NJ62 03-4AA0@-@@@@ 1 1 unit 143 3.630
250 1 C 3NJ62 13-4AA0@-@@@@ 1 1 unit 143 6.750
400 2 C 3NJ62 23-4AA0@-@@@@ 1 1 unit 143 15.000
630 3 C 3NJ62 33-4AA0@-@@@@ 1 1 unit 143 15.360
Motorized operating mechanisms, EFM 10 N
160 00 C 3NJ62 03-4AB0@-@@@@ 1 1 unit 143 4.330
250 1 C 3NJ62 13-4AB0@-@@@@ 1 1 unit 143 7.450
400 2 C 3NJ62 23-4AB0@-@@@@ 1 1 unit 143 15.700
630 3 C 3NJ62 33-4AB0@-@@@@ 1 1 unit 143 16.060
Motorized operating mechanisms, EFM 20 N
160 00 C 3NJ62 03-4AC0@-@@@@ 1 1 unit 143 4.330
250 1 C 3NJ62 13-4AC0@-@@@@ 1 1 unit 143 7.450
400 2 C 3NJ62 23-4AC0@-@@@@ 1 1 unit 143 15.700
630 3 C 3NJ62 33-4AC0@-@@@@ 1 1 unit 143 16.060
Order No. supplement Add. price
Standard Order No. supplement
(more Order No. supplements from page 7/73 onwards)
Without auxiliary switches, ammeters, current transformers } 0 0AA0 None
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC fuse links
7
630 3 B 3NJ62 34-1AC0@-@@@@ 1 1 unit 143 18.560
Motorized operating mechanisms N
160 00 C 3NJ62 04-2AA0@-@@@@ 1 1 unit 143 6.160
250 1 C 3NJ62 14-2AA0@-@@@@ 1 1 unit 143 10.380
400 2 C 3NJ62 24-2AA0@-@@@@ 1 1 unit 143 18.900
630 3 C 3NJ62 34-2AA0@-@@@@ 1 1 unit 143 20.000
Motorized operating mechanisms, EFM 10 N
160 00 C 3NJ62 04-2AB0@-@@@@ 1 1 unit 143 7.330
250 1 C 3NJ62 14-2AB0@-@@@@ 1 1 unit 143 10.450
400 2 C 3NJ62 24-2AB0@-@@@@ 1 1 unit 143 18.700
630 3 C 3NJ62 34-2AB0@-@@@@ 1 1 unit 143 19.060
Motorized operating mechanisms, EFM 20 N
160 00 C 3NJ62 04-2AC0@-@@@@ 1 1 unit 143 7.330
250 1 C 3NJ62 14-2AC0@-@@@@ 1 1 unit 143 10.450
400 2 C 3NJ62 24-2AC0@-@@@@ 1 1 unit 143 18.700
630 3 C 3NJ62 34-2AC0@-@@@@ 1 1 unit 143 19.060
Order No. supplement Add. price
Standard Order No. supplement
(more Order No. supplements from page 7/73 onwards)
Without auxiliary switches, ammeters, current transformers } 0 0AA0 None
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For BS fuse links
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For BS fuse links
7
630 3T1) C 3NJ62 94-1AC0@-@@@@ 1 1 unit 143 18.560
Motorized operating mechanisms
160 00T1) C 3NJ62 64-2AA0@-@@@@ 1 1 unit 143 6.160
250 B2 C 3NJ62 74-2AA0@-@@@@ 1 1 unit 143 10.380
400 B4 C 3NJ62 84-2AA0@-@@@@ 1 1 unit 143 18.900
630 3T1) C 3NJ62 94-2AA0@-@@@@ 1 1 unit 143 20.000
Motorized operating mechanisms, EFM 10 N
160 00T1) C 3NJ62 64-2AB0@-@@@@ 1 1 unit 143 7.330
250 B2 C 3NJ62 74-2AB0@-@@@@ 1 1 unit 143 10.450
400 B4 C 3NJ62 84-2AB0@-@@@@ 1 1 unit 143 18.700
630 3T1) C 3NJ62 94-2AB0@-@@@@ 1 1 unit 143 19.060
Motorized operating mechanisms, EFM 20 N
160 00T1) C 3NJ62 64-2AC0@-@@@@ 1 1 unit 143 7.330
250 B2 C 3NJ62 74-2AC0@-@@@@ 1 1 unit 143 10.450
400 B4 C 3NJ62 84-2AC0@-@@@@ 1 1 unit 143 18.700
630 3T1) C 3NJ62 94-2AC0@-@@@@ 1 1 unit 143 19.060
Order No. supplement Add. price
Standard Order No. supplement
(more Order No. supplements from page 7/73 onwards)
Without auxiliary switches, ammeters, current transformers } 0 0AA0 None
1)
The fuse is available from Lawson fuses (UK) and
does not correspond to BS 88.
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC and BS fuse links
■ Options
1. Order No. supplement:
Auxiliary switch wired to multi-function plug
1 NC contact B 2 ✓ 1 unit
T1
Without 100 1 0.5 calibrated D 0 B D3 ✓ 1 unit
Without 100 5 1 B 0BD4 ✓ 1 unit
Without 100 5 0.5 B 0BD5 ✓ 1 unit
Without 100 5 0.5 calibrated D 0BD6 ✓ 1 unit
Without 150 1 1 B 0BE1 ✓ 1 unit
Without 150 1 0.5 B 0BE2 ✓ 1 unit
Without 150 1 0.5 calibrated D 0BE3 ✓ 1 unit
Without 150 5 1 B 0BE4 ✓ 1 unit
Without 150 5 0.5 B 0BE5 ✓ 1 unit
Without 150 5 0.5 calibrated D 0BE6 ✓ 1 unit
3 current transformers to multi-function plug
Without 50 1 1 B 0CB1 ✓ 1 unit
Without 50 5 1 B 0CB4 ✓ 1 unit
T1
Without 100 1 1 B 0CD1 ✓ 1 unit
Without 100 1 0.5 B 0CD2 ✓ 1 unit
NSE0_01968
T2
Without 100 1 0.5 calibrated D 0CD3 ✓ 1 unit
Without 100 5 1 B 0CD4 ✓ 1 unit
T3
Without 100 5 0.5 B 0CD5 ✓ 1 unit
Without 100 5 0.5 calibrated D 0CD6 ✓ 1 unit
Without 150 1 1 B 0CE1 ✓ 1 unit
Without 150 1 0.5 B 0CE2 ✓ 1 unit
Without 150 1 0.5 calibrated D 0CE3 ✓ 1 unit
Without 150 5 1 B 0CE4 ✓ 1 unit
Without 150 5 0.5 B 0CE5 ✓ 1 unit
Without 150 5 0.5 calibrated D 0CE6 ✓ 1 unit
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC and BS fuse links
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC and BS fuse links
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC and BS fuse links
7
Moving iron 200 5 1 B 1EF4 ✓ 1 unit
Moving iron 200 5 0.5 B 1EF5 ✓ 1 unit
Moving iron 250 1 1 B 1EG1 ✓ 1 unit
Moving iron 250 1 0.5 B 1EG2 ✓ 1 unit
Moving iron 250 5 1 B 1EG4 ✓ 1 unit
Moving iron 250 5 0.5 B 1EG5 ✓ 1 unit
Bi-metal 50 1 1 B 2EB1 ✓ 1 unit
Bi-metal 50 5 1 B 2EB4 ✓ 1 unit
Bi-metal 100 1 1 B 2ED1 ✓ 1 unit
Bi-metal 100 1 0.5 B 2E D2 ✓ 1 unit
Bi-metal 100 5 1 B 2E D4 ✓ 1 unit
Bi-metal 100 5 0.5 B 2E D5 ✓ 1 unit
Bi-metal 150 1 1 B 2 EE1 ✓ 1 unit
Bi-metal 150 1 0.5 B 2EE2 ✓ 1 unit
Bi-metal 150 5 1 B 2EE4 ✓ 1 unit
Bi-metal 150 5 0.5 B 2EE5 ✓ 1 unit
Bi-metal 200 1 1 B 2 EF1 ✓ 1 unit
Bi-metal 200 1 0.5 B 2EF2 ✓ 1 unit
Bi-metal 200 5 1 B 2EF4 ✓ 1 unit
Bi-metal 200 5 0.5 B 2EF5 ✓ 1 unit
Bi-metal 250 1 1 B 2 EG 1 ✓ 1 unit
Bi-metal 250 1 0.5 B 2 EG 2 ✓ 1 unit
Bi-metal 250 5 1 B 2 EG 4 ✓ 1 unit
Bi-metal 250 5 0.5 B 2 EG 5 ✓ 1 unit
3 current transformers to 1 ammeter and multi-function plug
Moving iron 50 1 1 B 1FB1 ✓ 1 unit
Moving iron 50 5 1 B 1FB4 ✓ 1 unit
T1 Moving iron 100 1 1 B 1FD1 ✓ 1 unit
A
Moving iron 100 1 0.5 B 1FD2 ✓ 1 unit
T2 Moving iron 100 5 1 B 1FD4 ✓ 1 unit
Moving iron 100 5 0.5 B 1FD5 ✓ 1 unit
NSE0_01923
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC and BS fuse links
T1
Without 300 5 1 B 0BH4 ✓ 1 unit
Without 300 5 0.5 B 0BH5 ✓ 1 unit
Without 300 5 0.5 calibrated D 0BH6 ✓ 1 unit
Without 400 1 1 B 0BJ1 ✓ 1 unit
Without 400 1 0.5 B 0BJ2 ✓ 1 unit
Without 400 1 0.5 calibrated D 0BJ3 ✓ 1 unit
Without 400 5 1 B 0BJ4 ✓ 1 unit
Without 400 5 0.5 B 0BJ5 ✓ 1 unit
Without 400 5 0.5 calibrated D 0BJ6 ✓ 1 unit
3 current transformers to multi-function plug
Without 300 1 1 B 0CH1 ✓ 1 unit
Without 300 1 0.5 B 0CH2 ✓ 1 unit
Without 300 1 0.5 calibrated D 0 C H3 ✓ 1 unit
Without 300 5 1 B 0CH4 ✓ 1 unit
T1 Without 300 5 0.5 B 0CH5 ✓ 1 unit
Without 300 5 0.5 calibrated D 0CH6 ✓ 1 unit
NSE0_01968
T2
Without 400 1 1 B 0CJ1 ✓ 1 unit
T3 Without 400 1 0.5 B 0CJ2 ✓ 1 unit
Without 400 1 0.5 calibrated D 0CJ3 ✓ 1 unit
Without 400 5 1 B 0CJ4 ✓ 1 unit
Without 400 5 0.5 B 0CJ5 ✓ 1 unit
Without 400 5 0.5 calibrated D 0CJ6 ✓ 1 unit
1 current transformer to 1 ammeter and multi-function plug
Moving iron 300 1 1 B 1EH1 ✓ 1 unit
Moving iron 300 1 0.5 B 1EH2 ✓ 1 unit
NSE0_01924
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC and BS fuse links
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC and BS fuse links
T2
Without 400 1 1 B 0CJ1 ✓ 1 unit
T3 Without 400 1 0.5 B 0CJ2 ✓ 1 unit
Without 400 1 0.5 calibrated D 0CJ3 ✓ 1 unit
Without 400 5 1 B 0CJ4 ✓ 1 unit
Without 400 5 0.5 B 0CJ5 ✓ 1 unit
Without 400 5 0.5 calibrated D 0CJ6 ✓ 1 unit
Without 500 1 1 B 0CK1 ✓ 1 unit
Without 500 1 0.5 B 0CK2 ✓ 1 unit
Without 500 1 0.5 calibrated D 0CK3 ✓ 1 unit
Without 500 5 1 B 0CK4 ✓ 1 unit
Without 500 5 0.5 B 0CK5 ✓ 1 unit
Without 500 5 0.5 calibrated D 0CK6 ✓ 1 unit
Without 600 1 1 B 0CL1 ✓ 1 unit
Without 600 1 0.5 B 0CL2 ✓ 1 unit
Without 600 1 0.5 calibrated D 0CL3 ✓ 1 unit
Without 600 5 1 B 0CL4 ✓ 1 unit
Without 600 5 0.5 B 0CL5 ✓ 1 unit
Without 600 5 0.5 calibrated D 0CL6 ✓ 1 unit
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC and BS fuse links
Switch Disconnectors
SENTRON 3NJ62 In-line Switch Disconnectors with Fuses up to 630 A
For LV HRC and BS fuse links
Switch Disconnectors
SENTRON 3NJ62 in-line switch disconnectors with fuses up to 630 A
Accessories
7 3NJ69 23-1DA00
Contact extensions
3-pole A 3NJ69 23-1EB00 1 1 unit 143 1.700
4-pole A 3NJ69 24-1EB00 1 1 unit 143 2.000
3NJ69 23-1EB00
Electronic fuse monitor and line monitor N
EFM 10 – electronic fuse monitoring for AC networks A 3NJ69 20-3FB00 1 1 unit 143 0.400
EFM 20 – electronic fuse monitoring for AC networks A 3NJ69 20-3FC00 1 1 unit 143 0.450
EFM 25 – electronic fuse monitoring for DC networks A 3NJ69 20-3FE00 1 1 unit 143 0.450
3NJ69 23-3FB00
3NJ69 23-3FC00
Auxiliary switches
1 NO contact (1 NO) with cover A 3NJ69 20-2BB00 1 1 unit 143 0.080
1 NO contact (1 NO) A 3NJ69 00-2BC00 1 1 unit 143 0.020
1 NC contact (1 NC) with cover A 3NJ69 20-2CB00 1 1 unit 143 0.080
3NJ69 20-2BB00
1 NC contact (1 NC) A 3NJ69 00-2CC00 1 1 unit 143 0.020
3NJ69 00-2BC00
Current transformers for main devices and contact
extensions
∅ = Feed-through opening diameter
50 A / 1 A Class 1 1 VA, ∅ 21 mm A 3NJ69 20-3BB11 1 1 unit 143 0.160
50 A / 5 A Class 1 1 VA, ∅ 21 mm A 3NJ69 20-3BB21 1 1 unit 143 0.160
3NJ69 20-3BD11 100 A / 1 A Class 1 2.5 VA, ∅ 21 mm A 3NJ69 20-3BD11 1 1 unit 143 0.160
100 A / 1 A Class 0.5 1.5 VA, ∅ 21 mm A 3NJ69 20-3BD12 1 1 unit 143 0.160
100 A / 1 A Class 0.5 calibrated 1.5 VA, ∅ 14 mm D 3NJ69 20-3BD13 1 1 unit 143 0.160
100 A / 5 A Class 1 2.5 VA, ∅ 21 mm A 3NJ69 20-3BD21 1 1 unit 143 0.160
100 A / 5 A Class 0.5 1.5 VA, ∅ 21 mm A 3NJ69 20-3BD22 1 1 unit 143 0.160
100 A / 5 A Class 0.5 calibrated 1.5 VA, ∅ 14mm D 3NJ69 20-3BD23 1 1 unit 143 0.160
150 A / 1 A Class 1 2.5 VA, ∅ 21 mm A 3NJ69 20-3BE11 1 1 unit 143 0.170
150 A / 1 A Class 0.5 1.5 VA, ∅ 21 mm A 3NJ69 20-3BE12 1 1 unit 143 0.170
150 A / 1 A Class 0.5 calibrated 2.5 VA, ∅ 14 mm D 3NJ69 20-3BE13 1 1 unit 143 0.170
150 A / 5 A Class 1 1.5 VA, ∅ 21 mm A 3NJ69 20-3BE21 1 1 unit 143 0.170
150 A / 5 A Class 0.5 1.5 VA, ∅ 21 mm A 3NJ69 20-3BE22 1 1 unit 143 0.170
150 A / 5 A Class 0.5 calibrated 2.5 VA, ∅ 14 mm D 3NJ69 20-3BE23 1 1 unit 143 0.170
Switch Disconnectors
SENTRON 3NJ62 in-line switch disconnectors with fuses up to 630 A
Accessories
3NJ69 20-3DD00
Holders for ammeters A 3NJ69 00-4GA00 1 1 unit 143 0.040 7
For sizes 00, 1, 2, 3
3NJ69 00-4GA00
Ammeters
Moving-iron measuring instruments for measure-
ments on transformer x/1A with double overload
50 A / 1 A 0.6 VA A 3NJ69 00-4HB11 1 1 unit 143 0.100
100 A / 1 A 0.6 VA A 3NJ69 00-4HD11 1 1 unit 143 0.100
150 A / 1 A 0.6 VA A 3NJ69 00-4HE11 1 1 unit 143 0.100
3NJ69 00-4H... Moving-iron measuring instruments for measure-
ments on transformer x/5A with double overload
50 A / 5 A 0.6 VA A 3NJ69 00-4HB21 1 1 unit 143 0.100
100 A / 5 A 0.6 VA A 3NJ69 00-4HD21 1 1 unit 143 0.100
150 A / 5 A 0.6 VA A 3NJ69 00-4HE21 1 1 unit 143 0.100
Bi-metal measuring instruments for measurements
on transformer x/1A with 1.2-times the overload
50 A / 1 A 1 VA A 3NJ69 00-4HB12 1 1 unit 143 0.100
100 A / 1 A 1 VA A 3NJ69 00-4HD12 1 1 unit 143 0.100
150 A / 1 A 1 VA A 3NJ69 00-4HE12 1 1 unit 143 0.100
Bi-metal measuring instruments for measurements
on transformer x/5A with 1.2-times the overload
3NJ69 00-4H... 50 A / 5 A 1 VA A 3NJ69 00-4HB22 1 1 unit 143 0.100
100 A / 5 A 1 VA A 3NJ69 00-4HD22 1 1 unit 143 0.100
150 A / 5 A 1 VA A 3NJ69 00-4HE22 1 1 unit 143 0.100
Multi-function plugs
6 x 2.5 mm2, with fixing screws A 3NJ69 20-3EB00 1 1 unit 143 0.047
8 x 2.5 mm2, without fixing screws A 3NJ69 20-3ED00 1 1 unit 143 0.047
10 x 1.5 mm2 and 8 x 2.5 mm2, A 3NJ69 20-3EE00 1 1 unit 143 0.070
without fixing screws
3NJ69 20-3EB00
3NJ69 20-3ED00
3NJ69 20-3EE00
Front panel
3NJ69 23-4BB00 For NH: 3NJ62 03-1AA... and 3NJ62 03-3AA... A 3NJ69 23-4BB00 1 1 unit 143 0.400
without/with EFM
For BS: 3NJ62 03-1AA... and 3NJ62 03-3AA... A 3NJ69 23-4BC00 1 1 unit 143 0.400
without/with EFM
1)
Not available in combination with multi-function plug
Switch Disconnectors
SENTRON 3NJ62 in-line switch disconnectors with fuses up to 630 A
Accessories
3NJ69 33-1BA00 Single terminal for 4-pole devices, 16 ... 300 mm2 A 3NJ69 34-1BA00 1 1 unit 143 0.310
(1 set = 4 units)
Terminal covers
For 2-/3-pole devices A 3NJ69 33-1DA00 1 1 unit 143 0.146
Internal terminal covers for 2-/3-pole devices A 3NJ69 33-1DB00 1 1 unit 143 0.020
Only for 4th pole A 3NJ69 04-1DA00 1 1 unit 143 0.070
7
3NJ69 33-1DA00
3NJ69 33-1DB00
Contact extensions
3-pole A 3NJ69 33-1EB00 1 1 unit 143 2.400
4-pole A 3NJ69 34-1EB00 1 1 unit 143 2.800
3NJ69 33-1EB00
Electronic fuse monitor and line monitor N
EFM 10 – electronic fuse monitoring for AC networks A 3NJ69 30-3FB00 1 1 unit 143 0.400
EFM 20 – electronic fuse monitoring for AC networks A 3NJ69 30-3FC00 1 1 unit 143 0.450
EFM 25 – electronic fuse monitoring for DC networks A 3NJ69 30-3FE00 1 1 unit 143 0.450
3NJ69 23-3FB00
3NJ69 23-3FC00
Auxiliary switches
1 NO contact (1 NO) with cover A 3NJ69 30-2BB00 1 1 unit 143 0.050
1 NO contact (1 NO) A 3NJ69 00-2BC00 1 1 unit 143 0.020
1 NC contact (1 NC) with cover A 3NJ69 30-2CB00 1 1 unit 143 0.050
1 NC contact (1 NC) A 3NJ69 00-2CC00 1 1 unit 143 0.020
3NJ69 30-2BB00
3NJ69 00-2BC00
Current transformers
For main devices and contact extensions
∅ = Feed-through opening diameter
50 A / 1 A Class 1 1 VA, ∅ 21 mm A 3NJ69 20-3BB11 1 1 unit 143 0.160
50 A / 5 A Class 1 1 VA, ∅ 21 mm A 3NJ69 20-3BB21 1 1 unit 143 0.160
3NJ69 20-3BD11 100 A / 1 A Class 1 2.5 VA, ∅ 21 mm A 3NJ69 20-3BD11 1 1 unit 143 0.160
100 A / 1 A Class 0.5 1.5 VA, ∅ 21 mm A 3NJ69 20-3BD12 1 1 unit 143 0.160
100 A / 5 A Class 1 2.5 VA, ∅ 21 mm A 3NJ69 20-3BD21 1 1 unit 143 0.160
100 A / 5 A Class 0.5 1.5 VA, ∅ 21 mm A 3NJ69 20-3BD22 1 1 unit 143 0.160
150 A / 1 A Class 1 2.5 VA, ∅ 21 mm A 3NJ69 20-3BE11 1 1 unit 143 0.170
150 A / 1 A Class 0.5 1.5 VA, ∅ 21 mm A 3NJ69 20-3BE12 1 1 unit 143 0.170
150 A / 5 A Class 1 1.5 VA, ∅ 21 mm A 3NJ69 20-3BE21 1 1 unit 143 0.170
150 A / 5 A Class 0.5 1.5 VA, ∅ 21 mm A 3NJ69 20-3BE22 1 1 unit 143 0.170
200 A / 1 A Class 1 2.5 VA, ∅ 21 mm A 3NJ69 30-3BF11 1 1 unit 143 0.180
200 A / 1 A Class 0.5 5 VA, ∅ 21 mm A 3NJ69 30-3BF12 1 1 unit 143 0.180
200 A / 5 A Class 1 2.5 VA, ∅ 21 mm A 3NJ69 30-3BF21 1 1 unit 143 0.180
200 A / 5 A Class 0.5 2.5 VA, ∅ 21 mm A 3NJ69 30-3BF22 1 1 unit 143 0.180
250 A / 1 A Class 1 5 VA, ∅ 21 mm A 3NJ69 30-3BG11 1 1 unit 143 0.180
250 A / 1 A Class 0.5 5 VA, ∅ 21 mm A 3NJ69 30-3BG12 1 1 unit 143 0.180
250 A / 5 A Class 1 2.5 VA, ∅ 21 mm A 3NJ69 30-3BG21 1 1 unit 143 0.180
250 A / 5 A Class 0.5 2.5 VA, ∅ 21 mm A 3NJ69 30-3BG22 1 1 unit 143 0.180
Switch Disconnectors
SENTRON 3NJ62 in-line switch disconnectors with fuses up to 630 A
Accessories
3NJ69 30-3DC00
3NJ69 30-3DD00
7
Holders for ammeters A 3NJ69 00-4GA00 1 1 unit 143 0.040
For sizes 00, 1, 2, 3
3NJ69 00-4GA00
Ammeters
Moving-iron measuring instruments for measure-
ments on transformer x/1A with double overload
50 A / 1 A 0.6 VA A 3NJ69 00-4HB11 1 1 unit 143 0.100
100 A / 1 A 0.6 VA A 3NJ69 00-4HD11 1 1 unit 143 0.100
150 A / 1 A 0.6 VA A 3NJ69 00-4HE11 1 1 unit 143 0.100
200 A / 1 A 0.6 VA A 3NJ69 00-4HF11 1 1 unit 143 0.100
250 A / 1 A 0.6 VA A 3NJ69 00-4HG11 1 1 unit 143 0.100
3NJ69 00-4H...
Moving-iron measuring instruments for measure-
ments on transformer x/5A with double overload
50 A / 5 A 0.6 VA A 3NJ69 00-4HB21 1 1 unit 143 0.100
100 A / 5 A 0.6 VA A 3NJ69 00-4HD21 1 1 unit 143 0.100
150 A / 5 A 0.6 VA A 3NJ69 00-4HE21 1 1 unit 143 0.100
200 A / 5 A 0.6 VA A 3NJ69 00-4HF21 1 1 unit 143 0.100
250 A / 5 A 0.6 VA A 3NJ69 00-4HG21 1 1 unit 143 0.100
Bi-metal measuring instruments for measurements
on transformer x/1A with 1.2-times the overload
50 A / 1 A 1 VA A 3NJ69 00-4HB12 1 1 unit 143 0.100
100 A / 1 A 1 VA A 3NJ69 00-4HD12 1 1 unit 143 0.100
150 A / 1 A 1 VA A 3NJ69 00-4HE12 1 1 unit 143 0.100
200 A / 1 A 1 VA A 3NJ69 00-4HF12 1 1 unit 143 0.100
250 A / 1 A 1 VA A 3NJ69 00-4HG12 1 1 unit 143 0.100
Bi-metal measuring instruments for measurements
3NJ69 00-4H... on transformer x/5A with 1.2-times the overload
50 A / 5 A 1 VA A 3NJ69 00-4HB22 1 1 unit 143 0.100
100 A / 5 A 1 VA A 3NJ69 00-4HD22 1 1 unit 143 0.100
150 A / 5 A 1 VA A 3NJ69 00-4HE22 1 1 unit 143 0.100
200 A / 5 A 1 VA A 3NJ69 00-4HF22 1 1 unit 143 0.100
250 A / 5 A 1 VA A 3NJ69 00-4HG22 1 1 unit 143 0.100
Multi-function plugs
6 x 2.5 mm2, with fixing screws A 3NJ69 20-3EB00 1 1 unit 143 0.047
8 x 2.5 mm2, without fixing screws A 3NJ69 20-3ED00 1 1 unit 143 0.047
10 x 1.5 mm2 and 8 x 2.5 mm2, A 3NJ69 20-3EE00 1 1 unit 143 0.070
without fixing screws
3NJ69 20-3EB00
3NJ69 40-3EE00
Front panel
For NH: 3NJ62 13-1AA... and 3NJ62 13-3AA... A 3NJ69 33-4BB00 1 1 unit 143 0.500
3NJ69 33-4BB00 without/with EFM
For BS: 3NJ62 13-1AA... and 3NJ62 13-3AA... A 3NJ69 33-4BC00 1 1 unit 143 0.500
without/with EFM
1)
Not available in combination with multi-function plug.
Switch Disconnectors
SENTRON 3NJ62 in-line switch disconnectors with fuses up to 630 A
Accessories
7 3NJ69 43-1DA00
Contact extensions
3-pole A 3NJ69 43-1EB00 1 1 unit 143 8.400
4-pole A 3NJ69 44-1EB00 1 1 unit 143 9.200
3NJ69 44-1EB00
Electronic fuse monitor and line monitor N
EFM 10 – electronic fuse monitoring for AC networks A 3NJ69 40-3FB00 1 1 unit 143 0.400
EFM 20 – electronic fuse monitoring for AC networks A 3NJ69 40-3FC00 1 1 unit 143 0.450
EFM 25 – electronic fuse monitoring for DC networks A 3NJ69 40-3FE00 1 1 unit 143 0.450
3NJ69 23-3FB00
3NJ69 23-3FC00
Auxiliary switches
1 NO contact (1 NO) with cover A 3NJ69 40-2BB00 1 1 unit 143 0.024
1 NO contact (1 NO) A 3NJ69 00-2BC00 1 1 unit 143 0.020
1 NC contact (1 NC) with cover A 3NJ69 40-2CB00 1 1 unit 143 0.024
1 NC contact (1 NC) A 3NJ69 00-2CC00 1 1 unit 143 0.020
3NJ69 40-2BB00
3NJ69 00-2BC00
Current transformers
For main devices and contact extensions
300 A / 1 A Class 1 5 VA A 3NJ69 40-3BH11 1 1 unit 143 0.330
300 A / 1 A Class 0.5 5 VA A 3NJ69 40-3BH12 1 1 unit 143 0.330
300 A / 1 A Class 0.5 calibrated 5 VA D 3NJ69 40-3BH13 1 1 unit 143 0.330
300 A / 5 A Class 1 5 VA A 3NJ69 40-3BH21 1 1 unit 143 0.330
3NJ69 40-3B... 300 A / 5 A Class 0.5 5 VA A 3NJ69 40-3BH22 1 1 unit 143 0.330
300 A / 5 A Class 0.5 calibrated 5 VA D 3NJ69 40-3BH23 1 1 unit 143 0.330
400 A / 1 A Class 1 5 VA A 3NJ69 40-3BJ11 1 1 unit 143 0.430
400 A / 1 A Class 0.5 5 VA A 3NJ69 40-3BJ12 1 1 unit 143 0.430
400 A / 1A Class 0.5 calibrated 5 VA D 3NJ69 40-3BJ13 1 1 unit 143 0.430
400 A / 5 A Class 1 5 VA A 3NJ69 40-3BJ21 1 1 unit 143 0.430
400 A / 5 A Class 0.5 5 VA A 3NJ69 40-3BJ22 1 1 unit 143 0.430
400 A / 5 A Class 0.5 calibrated 5 VA D 3NJ69 40-3BJ23 1 1 unit 143 0.430
500 A / 1 A Class 1 5 VA A 3NJ69 40-3BK11 1 1 unit 143 0.460
500 A / 1 A Class 0.5 5 VA A 3NJ69 40-3BK12 1 1 unit 143 0.460
500 A / 1 A Class 0.5 calibrated 5 VA D 3NJ69 40-3BK13 1 1 unit 143 0.460
500 A / 5 A Class 1 5 VA A 3NJ69 40-3BK21 1 1 unit 143 0.460
500 A / 5 A Class 0.5 5 VA A 3NJ69 40-3BK22 1 1 unit 143 0.460
500 A / 5 A Class 0.5 calibrated 5 VA D 3NJ69 40-3BK23 1 1 unit 143 0.460
600 A / 1 A Class 1 5 VA A 3NJ69 40-3BL11 1 1 unit 143 0.460
600 A / 1 A Class 0.5 5 VA A 3NJ69 40-3BL12 1 1 unit 143 0.460
600 A / 1 A Class 0.5 calibrated 5 VA D 3NJ69 40-3BL13 1 1 unit 143 0.460
600 A / 5 A Class 1 5 VA A 3NJ69 40-3BL21 1 1 unit 143 0.460
600 A / 5 A Class 0.5 5 VA A 3NJ69 40-3BL22 1 1 unit 143 0.460
600 A / 5 A Class 0.5 calibrated 5 VA D 3NJ69 40-3BL23 1 1 unit 143 0.460
Switch Disconnectors
SENTRON 3NJ62 in-line switch disconnectors with fuses up to 630 A
Accessories
3NJ69 00-4GA00
Ammeters
Moving-iron measuring instruments for measuring
input on transformer x/1A with double overload
300 A / 1 A 0.6 VA A 3NJ69 00-4HH11 1 1 unit 143 0.100
400 A / 1 A 0.6 VA A 3NJ69 00-4HJ11 1 1 unit 143 0.100
500 A / 1 A 0.6 VA A 3NJ69 00-4HK11 1 1 unit 143 0.100
3NJ69 00-4H... 600 A / 1 A 0.6 VA
Moving-iron measuring instruments for measuring
A 3NJ69 00-4HL11 1 1 unit 143 0.100
7
input on transformer x/5A with double overload
300 A / 5 A 0.6 VA A 3NJ69 00-4HH21 1 1 unit 143 0.100
400 A / 5 A 0.6 VA A 3NJ69 00-4HJ21 1 1 unit 143 0.100
500 A / 5 A 0.6 VA A 3NJ69 00-4HK21 1 1 unit 143 0.100
600 A / 5 A 0.6 VA A 3NJ69 00-4HL21 1 1 unit 143 0.100
Bi-metal measuring instruments for measurements
on transformer x/1A with 1.2-times the overload
300 A / 1 A 1 VA A 3NJ69 00-4HH12 1 1 unit 143 0.100
400 A / 1 A 1 VA A 3NJ69 00-4HJ12 1 1 unit 143 0.100
500 A / 1 A 1 VA A 3NJ69 00-4HK12 1 1 unit 143 0.100
600 A / 1 A 1 VA A 3NJ69 00-4HL12 1 1 unit 143 0.100
Bi-metal measuring instruments for measurements
3NJ69 00-4H... on transformer x/5A with 1.2-times the overload
300 A / 5 A 1 VA A 3NJ69 00-4HH22 1 1 unit 143 0.100
400 A / 5 A 1 VA A 3NJ69 00-4HJ22 1 1 unit 143 0.100
500 A / 5 A 1 VA A 3NJ69 00-4HK22 1 1 unit 143 0.100
600 A / 5 A 1 VA A 3NJ69 00-4HL22 1 1 unit 143 0.100
Multi-function plugs
8 x 2.5 mm2, with fixing screws A 3NJ69 40-3EC00 1 1 unit 143 0.147
8 x 2.5 mm2, without fixing screws A 3NJ69 40-3ED00 1 1 unit 143 0.147
12 x 1.5 mm2 and 8 x 2.5 mm2, A 3NJ69 40-3EF00 1 1 unit 143 0.170
without fixing screws
3NJ69 40-3EC00
3NJ69 40-3ED00
3NJ69 40-3EF00
Front panel
For NH: 3NJ62 23-1AA... and 3NJ62 23-3AA... A 3NJ69 43-4BB00 1 1 unit 143 0.700
without/with EFM
For BS: 3NJ62 23-1AA... and 3NJ62 23-3AA... A 3NJ69 43-4BC00 1 1 unit 143 0.700
3NJ69 43-4BB00 without/with EFM
For NH: 3NJ62 33-1AA... and 3NJ62 33-3AA... A 3NJ69 53-4BB00 1 1 unit 143 0.700
without/with EFM
For BS: 3NJ62 33-1AA... and 3NJ62 33-3AA... A 3NJ69 53-4BC00 1 1 unit 143 0.700
without/with EFM
Switch Disconnectors
SENTRON 3NJ62 in-line switch disconnectors with fuses up to 630 A
Accessories
3NJ69 16-4EA00
Blanking covers
Mounting height 50 mm, IP41 A 3NJ69 00-4CB00 1 1 unit 143 0.800
3NJ69 00-4CB00
Connection modules
For power takeoff from field distribution bus up to 400 A A 3NJ69 15-3BA00 1 1 unit 113 1.524
7 3NJ69 15-3BA00
Guide rails
Depth 200 mm (1 x left and 1 x right) C 3NJ69 00-4FB00 1 1 unit 143 1.300
Depth 400 mm (1 x left and 1 x right) C 3NJ69 00-4FC00 1 1 unit 143 1.800
3NJ69 00-4FB00
3NJ69 00-4FC00
NH fuse puller tongs
For NH00 C XPT:8PT9624 1 1 unit 195 0.497
For NH1, 2, 3 C XPT:8PT9625 1 1 unit 195 0.505
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Introduction
■ Overview
All key product features at a glance
• Box terminals available for all sizes
• Connection of circular conductors and laminated conductors
• Fuse monitoring possible throughout
• Busbar supports can be built over
• Conversion of 5 /10 mm thick busbars without parts which can
be lost or broken off
• Convertibility of cable feeder at top/bottom without interven-
tion in the internal conducting paths
• Optimum integration in various system environments through
cover levels and on busbar systems with/without base
• Touch protection also with rear incoming unit
• Fuses are removed using a release shaft without the fuses
being touched
NSG0_00235
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Introduction
■ Benefits
Advantages during planning and configuration Advantages during installation
• Low level of equipment variance through easy convertibility of • Only one device variant is required for cable feeders at
cable feeder at top/bottom (delivered from factory with cable top/bottom and there is no need to intervene in the internal
feeder at bottom). conducting paths.
• Only one device variant for applications in industry and infra- • One device variant with very high short-circuit values dis-
structure thanks to touch and reach-around protection as a penses with having to order and install arc splitters to increase
standard feature. the electrical values.
• Uniform grid sizes for easy configuration. • On all sizes it is possible to install two CO contacts for indicat-
ing the switch position.
Advantages during operation and service
• All devices feature all-round touch protection.
• The optional rear covers for the cable connections guarantee
optimum touch protection even for distribution boards with ac- • Box terminals are available for all sizes and shorten the mount-
cess from the rear. ing time appreciably.
• Innovative design enables the highest safety for equipment • Snapping on the sizes NH000 and NH00 shortens the mount-
and personnel. ing time greatly compared to fixing with screws.
■ Application
Possible uses Mounting
3NP1 fuse switch disconnectors can be used for protecting and Floor mounting
switching the most diverse electrical loads:
• Motor starter combinations System
• In conjunction with SITOR fuses for the protection of frequency cover
NH 000, 00 (alternatively) NH 1, 2, 3
converters and soft starters
• Fusing of compensation modules
• Cable feeders
70
45
The devices are optimized for operation in all kinds of system Mounting plate
environments:
• Low-voltage switchboards for power distribution and MCCs 3NP1 fuse switch disconnector for floor mounting
(e.g. main and sub-distribution boards)
• Distribution systems with cover levels of 32 and 70 mm or Busbar mounting
45 and 70 mm
Mounting on Siemens 8US Mounting on Rittal Riline 60
• Mechanical engineering
busbar systems with 32/70 mm busbar systems with base
• Railway applications cover level
Fuse monitors are used to detect, indicate and report faults:
• MFM – electromechanical fuse monitoring for AC/DC networks
• EFM 10 – electronic fuse monitoring for AC networks
70
AC networks
NSG0_00237
• EFM 25 – electronic fuse monitoring with line monitoring for
DC networks Mounting plate Base
Busbar support Busbar support
Standards and specifications
3NP1 fuse switch disconnector for busbar mounting
The 3NP1 fuse switch disconnectors are compliant with:
• IEC 60947-1, EN 60947-1
• IEC 60947-3, EN 60947-3
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Introduction
■ Technical specifications
Standards IEC/EN 60439-1
Type 3NP1 123... 3NP1 133... 3NP1 143... 3NP1 153... 3NP1 163...
Rated uninterrupted current Iu A 160 160 250 400 630
For fuse links acc. to IEC 60269-1 Size 000 00 and 000 1 and 0 2 and 1 3 and 2
Conventional free-air thermal current A 160 160 250 400 630
Ith
Rated operational voltage Ue
50 Hz/60 Hz AC V 690 690 690 690 690
DC (3 conducting paths series-connected) V 440 440 440 440 440
DC (2 conducting paths series-connected) V 220/240 220/240 220/240 220/240 220/240
Rated insulation voltage Ui1) V 1000 1000 1000 1000 1000
Rated impulse withstand voltage Uimp kV 8 8 8 8 8
Rated conditional short-circuit current with Size/A 000 / 160 00 / 160 1 / 250 2 / 400 3 / 630
fuses
7
Rated current at 500 V / 690 V AC kA 80 80 80 80 50
Permissible let-through current of the fuses, kA 10 15 25 40 50
peak value
Short-circuit strength with fuses Size/A 000 / 160 00 / 160 1 / 250 2 / 400 3 / 630
Rated current at 500 V / 690 V, rms value kA 120 120 120 100 100
Let-through I2t value kA2s 56 158 780 2150 5400
Permissible let-through current of the fuses, kA 15 23 32 40 60
peak value
Rated switching capacity at 500 V AC kA 2 6 17 17 17
Rated making and breaking capacity
• At AC-21B, 22B, 23B 400 V AC A 160 160 250 400 630
• At AC-21B 500 V AC A 160 160 250 400 630
• At AC-22B 500 V AC A 125 160 250 400 630
• At AC-23B 500 V AC A 40 63 200 315 500
• At AC-21 B 690 V AC A 160 160 250 400 630
• At AC-22B 690 V AC A 50 125 250 400 500
• At AC-23B 690 V AC A 25 35 100 125 200
• At DC-21B 240 V DC A 160 160 250 400 630
• At DC-22B 240 V DC A 100 160 250 400 630
• At DC-23B 240 V DC A 80 100 200 250 400
• At DC-21B 440 V DC A 100 160 250 400 630
• At DC-22B 440 V DC A 50 125 200 315 500
• At DC-23B 440 V DC A 25 63 100 160 250
Capacitor switching capacity
At 400 V AC
• Capacitor rating kvar 50 50 50 50 50
• Rated current In A 72 72 72 72 72
At 525 V AC
• Capacitor rating kvar 50 50 50 50 50
• Rated current In A 55 55 55 55 55
Permissible ambient temperature2) °C -25 ... +55 for operation, -50 ... +80 during storage
Mechanical endurance, operating cycles 2000 2000 1600 1000 1000
Degree of protection (operator side)
Without molded-plastic masking frame/cable lug IP30 (switch closed) / IP20 (switch open)
cover
With molded-plastic masking frame/cable lug cover IP40 (switch closed) / IP20 (switch open)
Power loss of the switch at Ith (plus fuses) W 9 12 23 34 48
Max. conductor cross-section of main conductor
connection
Flat terminals mm2 -- Up to 95 (M8) Up to 150 (M10) Up to 240 (M10) Up to 300 (M10)
Box terminals mm2 1.5 ... 50 6 ... 70 70 ... 185 120 ... 240 150 ... 300
Prism terminal mm2 -- 16 ... 95 70 ... 150 120 ... 240 150 ... 300
Saddle terminals mm2 -- 1.5 ... 70 70 ... 150 120 ... 240 150 ... 300
Laminated conductors in box terminal mm 8x8 9x8 10 x 20 10 x 32 10 x 32
Rated operational current of auxiliary switch
3NP19...-1FA00 auxiliary switch A 0.25 (Ith = 5 A)
3NP19...-1FB00 auxiliary switch A 0.1 (Ith = 0.1 A)
Permissible mounting positions Vertical and horizontal (no derating)
1) 2)
Up to pollution degree 2, above this Ui = 690 V. Only with isolating links; otherwise, please observe specifications of fuse
manufacturer.
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Floor mounting
3NP133-1CA20
3NP1 133-1CA21
With electronic EFM 10 fuse monitoring
Flat terminals
160 00 / 000 A 3NP1 133-1CA12 1 1 unit 143 0.870
Box terminals
1001) 000 A 3NP1 123-1CA22 1 1 unit 143 0.590
160 00 / 000 A 3NP1 133-1CA22 1 1 unit 143 0.870
3NP1 133-1CA22
With electronic EFM 20 fuse monitoring and
line monitoring
Flat terminals
160 00 / 000 A 3NP1 133-1CA13 1 1 unit 143 0.870
Box terminals
1001) 000 A 3NP1 123-1CA23 1 1 unit 143 0.590
160 00 / 000 A 3NP1 133-1CA23 1 1 unit 143 0.870
3NP1 133-1CA23
1)
160 A available in combination with feeder terminal 3NP1 923-1BD00
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Floor mounting
Rated current Iu NH type LV HRC fuse links DT Order No. Price PU PS*/ PG Weight
acc. to IEC 60269-1 per PU (UNIT, P. unit per PU
SET, M) approx.
A Size kg
For 70 mm cover level
Basic units
Flat terminals
250 1 and 0 A 3NP1 143-1DA10 1 1 unit 143 2.190
400 2 and 1 A 3NP1 153-1DA10 1 1 unit 143 4.210
630 3 and 2 A 3NP1 163-1DA10 1 1 unit 143 6.310
Box terminals
250 1 and 0 A 3NP1 143-1DA20 1 1 unit 143 2.190
400 2 and 1 A 3NP1 153-1DA20 1 1 unit 143 4.660
3NP1 143-1DA20
630 3 and 2 A 3NP1 163-1DA20 1 1 unit 143 6.730
With electromechanical MFM fuse monitoring
Flat terminals
250
400
1 and 0
2 and 1
A
A
3NP1 143-1DA11
3NP1 153-1DA11
1
1
1 unit
1 unit
143
143
2.630
4.650
7
630 3 and 2 A 3NP1 163-1DA11 1 1 unit 143 6.750
Box terminals
250 1 and 0 A 3NP1 143-1DA21 1 1 unit 143 2.630
400 2 and 1 A 3NP1 153-1DA21 1 1 unit 143 5.100
3NP1 143-1DA21
630 3 and 2 A 3NP1 163-1DA21 1 1 unit 143 7.170
With electronic EFM 10 fuse monitoring
Flat terminals
250 1 and 0 A 3NP1 143-1DA12 1 1 unit 143 2.330
400 2 and 1 A 3NP1 153-1DA12 1 1 unit 143 4.350
630 3 and 2 A 3NP1 163-1DA12 1 1 unit 143 6.450
Box terminals
250 1 and 0 A 3NP1 143-1DA22 1 1 unit 143 2.330
400 2 and 1 A 3NP1 153-1DA22 1 1 unit 143 4.800
630 3 and 2 A 3NP1 163-1DA22 1 1 unit 143 6.870
3NP1 143-1DA22
With electronic EFM 20 fuse monitoring and
line monitoring
Flat terminals
250 1 and 0 A 3NP1 143-1DA13 1 1 unit 143 2.330
400 2 and 1 A 3NP1 153-1DA13 1 1 unit 143 4.350
630 3 and 2 A 3NP1 163-1DA13 1 1 unit 143 6.450
Box terminals
250 1 and 0 A 3NP1 143-1DA23 1 1 unit 143 2.330
400 2 and 1 A 3NP1 153-1DA23 1 1 unit 143 4.800
630 3 and 2 A 3NP1 163-1DA23 1 1 unit 143 6.870
3NP1 143-1DA23
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
For 40 mm busbar system
7 3NP1 133-1BB20
With electromechanical MFM fuse monitoring
Flat terminals
160 00 / 000 A 3NP1 133-1BB11 1 1 unit 143 1.420
Box terminals
160 00 / 000 A 3NP1 133-1BB21 1 1 unit 143 1.420
3NP1 133-1BB21
With electronic EFM 10 fuse monitoring
Flat terminals
160 00 / 000 A 3NP1 133-1BB12 1 1 unit 143 1.120
Box terminals
1001) 000 A 3NP1 123-1BB22 1 1 unit 143 0.940
160 00 / 000 A 3NP1 133-1BB22 1 1 unit 143 1.120
3NP1 133-1BB22
With electronic EFM 20 fuse monitoring and
line monitoring
Flat terminals
160 00 / 000 C 3NP1 133-1BB13 1 1 unit 143 1.120
Box terminals
1001) 000 C 3NP1 123-1BB23 1 1 unit 143 0.940
160 00 / 000 C 3NP1 133-1BB23 1 1 unit 143 1.120
3NP1 133-1BB23
1)
160 A available in combination with feeder terminal 3NP1 923-1BD00
Note:
Delivered from factory with cable feeder at bottom and convert-
ible by the customer.
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
For 40 mm busbar system
Rated current Iu NH type LV HRC fuse links DT Order No. Price PU PS*/ PG Weight
acc. to IEC 60269-1 per PU (UNIT, P. unit per PU
SET, M) approx.
A Size kg
For Rittal system with base
for busbar width 12 to 30 mm and thickness 5 mm or 10 mm
Basic units
Flat terminals
160 00 / 000 A 3NP1 133-1JB10 1 1 unit 143 0.980
Box terminals
1001) 000 A 3NP1 123-1JB20 1 1 unit 143 0.820
160 00 / 000 A 3NP1 133-1JB20 1 1 unit 143 0.980
3NP1 133-1JB20
With electromechanical MFM fuse monitoring
Flat terminals
160 00 / 000 C 3NP1 133-1JB11 1 1 unit 143 1.420
7
Box terminals
160 00 / 000 C 3NP1 133-1JB21 1 1 unit 143 1.420
3NP1 133-1JB21
With electronic EFM 10 fuse monitoring
Flat terminals
160 00 / 000 C 3NP1 133-1JB12 1 1 unit 143 1.120
Box terminals
1001) 000 C 3NP1 123-1JB22 1 1 unit 143 0.940
160 00 / 000 C 3NP1 133-1JB22 1 1 unit 143 1.120
3NP1 133-1JB22
With electronic EFM 20 fuse monitoring and
line monitoring
Flat terminals
160 00 / 000 C 3NP1 133-1JB13 1 1 unit 143 1.120
Box terminals
1001) 000 C 3NP1 123-1JB23 1 1 unit 143 0.940
160 00 / 000 C 3NP1 133-1JB23 1 1 unit 143 1.120
3NP1 133-1JB23
1)
160 A available in combination with feeder terminal 3NP1 923-1BD00
Note:
Delivered from factory with cable feeder at bottom and convert-
ible by the customer.
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
For 60 mm busbar system
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
For 60 mm busbar system
Rated current Iu NH type LV HRC fuse links DT Order No. Price PU PS*/ PG Weight
acc. to IEC 60269-1 per PU (UNIT, P. unit per PU
SET, M) approx.
A Size kg
For Rittal Riline60 system with base
for busbar width 12 to 30 mm and thickness 5 mm or 10 mm
Basic units
Flat terminals
160 00 / 000 A 3NP1 133-1JC10 1 1 unit 143 0.980
250 1 and 0 A 3NP1 143-1JC10 1 1 unit 143 2.850
400 2 and 1 A 3NP1 153-1JC10 1 1 unit 143 4.760
630 3 and 2 A 3NP1 163-1JC10 1 1 unit 143 6.840
Box terminals
1001) 000 A 3NP1 123-1JC20 1 1 unit 143 0.820
3NP1 133-1JC20 160 00 / 000 A 3NP1 133-1JC20 1 1 unit 143 0.980
250 1 and 0 A 3NP1 143-1JC20 1 1 unit 143 2.850
400
630
2 and 1
3 and 2
A
A
3NP1 153-1JC20
3NP1 163-1JC20
1
1
1 unit
1 unit
143
143
4.990
7.040
7
With electromechanical MFM fuse monitoring
Flat terminals
160 00 / 000 C 3NP1 133-1JC11 1 1 unit 143 1.420
250 1 and 0 C 3NP1 143-1JC11 1 1 unit 143 3.290
400 2 and 1 C 3NP1 153-1JC11 1 1 unit 143 5.200
630 3 and 2 C 3NP1 163-1JC11 1 1 unit 143 7.280
Box terminals
3NP1 133-1JC21 160 00 / 000 C 3NP1 133-1JC21 1 1 unit 143 1.420
250 1 and 0 C 3NP1 143-1JC21 1 1 unit 143 3.290
400 2 and 1 C 3NP1 153-1JC21 1 1 unit 143 5.430
630 3 and 2 C 3NP1 163-1JC21 1 1 unit 143 7.480
With electronic EFM 10 fuse monitoring
Flat terminals
160 00 / 000 C 3NP1 133-1JC12 1 1 unit 143 1.120
250 1 and 0 C 3NP1 143-1JC12 1 1 unit 143 2.990
400 2 and 1 C 3NP1 153-1JC12 1 1 unit 143 4.900
630 3 and 2 C 3NP1 163-1JC12 1 1 unit 143 6.980
Box terminals
1001) 000 C 3NP1 123-1JC22 1 1 unit 143 0.940
3NP1 133-1JC22 160 00 / 000 C 3NP1 133-1JC22 1 1 unit 143 1.120
250 1 and 0 C 3NP1 143-1JC22 1 1 unit 143 2.990
400 2 and 1 C 3NP1 153-1JC22 1 1 unit 143 5.130
630 3 and 2 C 3NP1 163-1JC22 1 1 unit 143 7.180
With electronic EFM 20 fuse monitoring and
line monitoring
Flat terminals
160 00 / 000 C 3NP1 133-1JC13 1 1 unit 143 1.120
250 1 and 0 C 3NP1 143-1JC13 1 1 unit 143 2.990
400 2 and 1 C 3NP1 153-1JC13 1 1 unit 143 4.900
630 3 and 2 C 3NP1 163-1JC13 1 1 unit 143 6.980
Box terminals
1001) 000 C 3NP1 123-1JC23 1 1 unit 143 0.940
3NP1 133-1JC23 160 00 / 000 C 3NP1 133-1JC23 1 1 unit 143 1.120
250 1 and 0 C 3NP1 143-1JC23 1 1 unit 143 2.990
400 2 and 1 C 3NP1 153-1JC23 1 1 unit 143 5.130
630 3 and 2 C 3NP1 163-1JC23 1 1 unit 143 7.180
1) 160 A available in combination with feeder terminal 3NP1 923-1BD00
Note:
Delivered from factory with cable feeder at bottom and convert-
ible by the customer.
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Accessories
3NP1 923-1BD00
3-way terminal, 3 x 2.5 ... 16 mm2, A 3NP1 923-1BE20 1 1 unit 143 0.134
for box terminal
(1 set= 3 units)
7
3NP1 923-1BE20
3-phase busbar
Iu = max. 225 A
(1 set = 5 units)
3NP1 933-1BF30 • For 2 x NH000 A 3NP1 923-1BF20 1 1 unit 143 0.268
• For 3x NH000 A 3NP1 923-1BF30 1 1 unit 143 0.436
• For 4x NH000 A 3NP1 923-1BF40 1 1 unit 143 0.650
Connection piece, Iu = max. 225 A A 3NP1 923-1BF50 1 1 unit 143 0.263
For 3-phase busbars
(1 set = 3 units)
3NP1 933-1BF50
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 923-1BG40 1 1 unit 143 0.004
For box terminal
(1 set= 3 units)
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Accessories
3NP1 923-1CB00
7
Masking frame supports A 3NP1 923-1CF00 1 1 unit 143 0.012
(1 set = 2 units)
3NP1 923-1CF00
3NP1 923-1DA00
Fixing kits
For 1 standard mounting rail A 3NP1 923-1EA00 1 1 unit 143 0.009
3NP1 923-1EA00
Auxiliary switches
1 CO A 3NP1 920-1FA00 1 1 unit 143 0.012
1 CO contact, solid-state compatible A 3NP1 920-1FB00 1 1 unit 143 0.012
3NP1 920-1FA00
Fuse carriers
Standard A 3NP1 923-1GA00 1 1 unit 143 0.124
With electronic EFM 10 fuse monitoring A 3NP1 923-1GB20 1 1 unit 143 0.551
With electronic EFM 20 fuse monitoring and A 3NP1 923-1GB30 1 1 unit 143 0.573
line monitoring
With electronic EFM 25 fuse monitoring and A 3NP1 923-1GB50 1 1 unit 143 0.573
line monitoring
3NP1 923-1GA00
Locking devices
(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006
3NP1 900-1HA00
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Accessories
3NP1 933-1BA00
Prism terminal single, 35... 95 mm2 A 3NP1 933-1BB10 1 1 unit 143 0.121
For flat connection
(1 set= 3 units)
3NP1 933-1BB10
3NP1 933-1BC00
3-way terminal, 3 x 2.5 ... 16 mm2 A 3NP1 933-1BE10 1 1 unit 143 0.087
For flat terminals
(1 set = 3 units)
3NP1 933-1BE10
3-way terminal, 3 x 2.5 ... 16 mm2 A 3NP1 923-1BE20 1 1 unit 143 0.134
For box terminal
(1 set= 3 units)
3NP1 923-1BE20
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 933-1BG10 1 1 unit 143 0.006
For flat connection
(1 set= 3 units)
3NP1 933-1BG10
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 933-1BG30 1 1 unit 143 0.004
For prism terminal
(1 set= 3 units)
3NP1 933-1BG30
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 933-1BG40 1 1 unit 143 0.006
For box terminal
(1 set= 3 units)
3NP1 933-1BG40
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Accessories
3NP1 933-1CB00
Cable connection covers with rear reach-around protec- A 3NP1 933-1CC00 1 1 unit 143 0.093
tion in case of busbar mounting (at top and bottom)
For flat terminal
7
3NP1 933-1CC00
Cable connection covers with rear reach-around A 3NP1 933-1CD00 1 1 unit 143 0.079
protection in case of busbar mounting (at top and bottom)
For flat terminal
3NP1 933-1CD00
Masking frame supports A 3NP1 933-1CF00 1 1 unit 143 0.012
(1 set = 2 units)
3NP1 933-1CF00
System masking frames
Dimensions (H x W) 215 x 130 mm A 3NP1 933-1DA00 1 1 unit 143 0.024
Fixing kits
For 2 standard mounting rails 125/150 mm A 3NP1 933-1EB00 1 1 unit 143 0.009
3NP1 933-1EB00
Auxiliary switches
1 CO A 3NP1 930-1FA00 1 1 unit 143 0.012
1 CO contact, solid-state compatible A 3NP1 930-1FB00 1 1 unit 143 0.012
3NP1 930-1FB00
Fuse carriers
Standard A 3NP1 933-1GA00 1 1 unit 143 0.165
With electromechanical MFM fuse monitoring A 3NP1 933-1GB10 1 1 unit 143 1.293
With electronic EFM 10 fuse monitoring A 3NP1 933-1GB20 1 1 unit 143 0.589
With electronic EFM 20 fuse monitoring A 3NP1 933-1GB30 1 1 unit 143 0.611
and line monitoring
3NP1 933-1GB10 With electronic EFM 25 fuse monitoring and A 3NP1 933-1GB50 1 1 unit 143 0.611
line monitoring
Locking devices
(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Accessories
3NP1 943-1BA00
Prism terminal single, 70... 150 mm2 A 3NP1 943-1BB10 1 1 unit 143 0.270
For flat terminal
(1 set = 3 units)
3NP1 943-1BB10
7
Prism terminals double, 2 x 35 ... 70 mm2 A 3NP1 943-1BB20 1 1 unit 143 0.311
For flat terminal
(1 set = 3 units)
3NP1 943-1BB20
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 943-1BG10 1 1 unit 143 0.009
For flat terminal
(1 set = 3 units)
3NP1 943-1BG10
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 943-1BG30 1 1 unit 143 0.004
For saddle-type or prism terminals
(1 set = 3 units)
3NP1 943-1BG30
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 943-1BG40 1 1 unit 143 0.014
For box terminal
(1 set= 3 units)
3NP1 943-1BG40
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Accessories
3NP1 943-1CB00
Cable connection covers with rear reach-around A 3NP1 943-1CD00 1 1 unit 143 0.277
protection (at top and bottom)
7
3NP1 943-1CD00
Masking frame supports (1 set = 2 units) A 3NP1 943-1CF00 1 1 unit 143 0.026
System masking frames
Dimensions (H x W) 375 x 220 mm A 3NP1 943-1DA00 1 1 unit 143 0.092
Fixing kits
For 2 standard mounting rails 125/150 mm A 3NP1 943-1EB00 1 1 unit 143 0.017
3NP1 943-1EB00
Auxiliary switches
1 CO A 3NP1 940-1FA00 1 1 unit 143 0.018
1 CO contact, solid-state compatible A 3NP1 940-1FB00 1 1 unit 143 0.018
3NP1 940-1FA00
Fuse carriers
Standard A 3NP1 943-1GA00 1 1 unit 143 0.602
With electromechanical MFM fuse monitoring A 3NP1 943-1GB10 1 1 unit 143 1.726
With electronic EFM 10 fuse monitoring A 3NP1 943-1GB20 1 1 unit 143 1.022
With electronic EFM 20 fuse monitoring A 3NP1 943-1GB30 1 1 unit 143 1.044
and line monitoring
With electronic EFM 25 fuse monitoring and A 3NP1 943-1GB50 1 1 unit 143 1.044
line monitoring
3NP1 943-1GB20
Locking devices
(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Accessories
3NP1 953-1BA00
Prism terminal single, 120... 240 mm2 A 3NP1 953-1BB10 1 1 unit 143 0.420
For flat terminal
(1 set = 3 units)
3NP1 953-1BB10
Prism terminals double, 2 x 70 ... 120 mm2 A 3NP1 953-1BB20 1 1 unit 143 0.473
For flat terminal
7 (1 set = 3 units)
3NP1 953-1BB20
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 943-1BG10 1 1 unit 143 0.009
For flat terminal
(1 set = 3 units)
3NP1 943-1BG10
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 953-1BG30 1 1 unit 143 0.006
For saddle-type or prism terminals
(1 set = 3 units)
3NP1 953-1BG30
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 953-1BG40 1 1 unit 143 0.029
For box terminals
(1 set = 3 units)
3NP1 953-1BG40
Device covers, auxiliary switches
Reach-around protection for busbar mounting
(1x at top, 1x at bottom)
3NP1 953-1CA10 • For System Siemens 8US A 3NP1 953-1CA10 1 1 unit 143 0.028
• For System Rittal A 3NP1 953-1CA20 1 1 unit 143 0.038
Cable connection covers (at top and bottom) A 3NP1 953-1CB00 1 1 unit 143 0.242
3NP1 953-1CB00
Cable connection covers A 3NP1 953-1CD00 1 1 unit 143 0.362
With rear reach-around protection (at top and bottom)
Masking frame supports (1 set = 2 units) A 3NP1 943-1CF00 1 1 unit 143 0.026
System masking frames
Dimensions (H x W) 375 x 245 mm A 3NP1 953-1DA00 1 1 unit 143 0.097
Auxiliary switches
1 CO A 3NP1 940-1FA00 1 1 unit 143 0.018
1 CO contact, solid-state compatible A 3NP1 940-1FB00 1 1 unit 143 0.018
3NP1 940-1FA00
Fuse carriers
Standard A 3NP1 953-1GA00 1 1 unit 143 0.754
With electromechanical MFM fuse monitoring A 3NP1 953-1GB10 1 1 unit 143 1.797
With electronic EFM 10 fuse monitoring A 3NP1 953-1GB20 1 1 unit 143 1.093
With electronic EFM 20 fuse monitoring and A 3NP1 953-1GB30 1 1 unit 143 1.115
line monitoring
With electronic EFM 25 fuse monitoring and A 3NP1 953-1GB50 1 1 unit 143 1.115
line monitoring
3NP1 953-1GB30
Locking devices
(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006
Switch Disconnectors
SENTRON 3NP1 Fuse Switch Disconnectors up to 630 A
Accessories
3NP1 963-1BA00
Prism terminal single, 150... 300 mm2 A 3NP1 963-1BB10 1 1 unit 143 0.643
For flat terminal
(1 set = 3 units)
3NP1 963-1BB10
Prism terminals double, 2 x 150 ... 185 mm2 A 3NP1 963-1BB20 1 1 unit 143 0.681
For flat terminal
(1 set = 3 units)
7
3NP1 963-1BB20
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 943-1BG10 1 1 unit 143 0.009
For flat terminal
(1 set = 3 units)
3NP1 943-1BG10
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 953-1BG30 1 1 unit 143 0.006
For saddle-type or prism terminals
(1 set = 3 units)
3NP1 953-1BG30
Auxiliary conductor connection, 0.25 ... 1 mm2 A 3NP1 953-1BG40 1 1 unit 143 0.029
For box terminals
(1 set = 3 units)
3NP1 953-1BG40
Device covers, auxiliary switches
Reach-around protection for busbar mounting
(1x at top, 1x at bottom)
3NP1 963-1CA10 • For System Siemens 8US A 3NP1 963-1CA10 1 1 unit 143 0.032
• For System Rittal A 3NP1 963-1CA20 1 1 unit 143 0.043
Cable connection covers (at top and bottom) A 3NP1 963-1CB00 1 1 unit 143 0.269
Cable connection cover A 3NP1 963-1CD00 1 1 unit 143 0.411
With rear reach-around protection (at top and bottom)
3NP1 963-1CB00
Masking frame supports (1 set = 2 units) A 3NP1 943-1CF00 1 1 unit 143 0.026
System masking frames
Dimensions (H x W) 375 x 290 mm A 3NP1 963-1DA00 1 1 unit 143 0.116
Auxiliary switches
1 CO A 3NP1 940-1FA00 1 1 unit 143 0.018
1 CO contact, solid-state compatible A 3NP1 940-1FB00 1 1 unit 143 0.018
3NP1 940-1FA00
Fuse carriers
Standard A 3NP1 963-1GA00 1 1 unit 143 0.825
With electromechanical MFM fuse monitoring A 3NP1 963-1GB10 1 1 unit 143 1.966
With electronic EFM 10 fuse monitoring A 3NP1 963-1GB20 1 1 unit 143 1.262
With electronic EFM 20 fuse monitoring and A 3NP1 963-1GB30 1 1 unit 143 1.284
line monitoring
With electronic EFM 25 fuse monitoring and A 3NP1 963-1GB50 1 1 unit 143 1.284
line monitoring
3NP1 963-1GB50
Locking devices
(1 set = 10 units) A 3NP1 900-1HA00 1 1 unit 143 0.006
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
Introduction
■ Overview ■ Application
The SENTRON 3NP5 fuse switch disconnectors are ideally
suited for surface mounting and installation in distribution
boards (e.g. ALPHA, SIKUS), meter cabinets
(e.g. ALPHA 400-ZS), and molded-plastic distribution systems
such as 8HP.
The possibility of mounting them onto a range of different busbar
systems allows their very diverse implementation in switchgear
cabinet and control engineering.
The SENTRON 3NP5 fuse switch disconnectors are ideal for
operation in combination with other switching devices, for exam-
ple in capacitor modules for reactive-power compensation.
3NP5 0 In conjunction with semiconductor protection fuses (e.g. SITOR),
3NP5 2 these are used for the effective protection of frequency convert-
ers and soft starters.
3NP5 4
7 The SENTRON 3NP5 fuse switch disconnectors are suitable for
use in any climate and comply with standards IEC 60947-1 and
IEC 60947-3.
3NP5 fuse switch disconnector range
In addition, the SENTRON 3NP5 series of fuse switch disconnec-
SENTRON 3NP5 fuse switch disconnectors are controls for the tors complies with the requirements of BS 5419 and is also ap-
occasional manual switching/isolating of loads and distribution proved for operation in marine applications.
boards. They are able to switch on, control and switch off the
specified rated current (including a specific overload). All SENTRON 3NP5 fuse switch disconnectors can be sealed as
standard (or can be sealed through accessories).
With the SENTRON 3NP5 fuse switch disconnectors, all poles of
downstream electric loads can be safely disconnected from the
system under load.
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
Introduction
■ Technical specifications
Standards IEC 60947-1, IEC 60947-3
Type 3NP50 3NP52 3NP53 3NP54
Rated uninterrupted current Iu A 160 250 400 630
For fuse links acc. to IEC 60269-1 Size 00 1 and 0 2 and 1 3 and 2
Conventional free-air thermal current Ith A 160 250 400 630
Rated operational voltage Ue
50/60 Hz AC V 690
DC V 440 (3 conducting paths series-connected),
220 (2 conducting paths series-connected and with fuse monitoring
through 3RV)
Rated insulation voltage Ui V 6901) 6901) 6901) 6901)
Rated impulse withstand voltage Uimp kV 6 6 6 6
Rated conditional short-circuit current
with fuses (by fast switch on)
With fuse links
Rated current Size/A 00/160 1/250 2/400 3/630
At 500 V AC (rms value)
Permissible let-through current of the fuses (peak value)
kA
kA
50
15
50
25
50
40
50
50 7
Short-circuit strength with fuses (with closed disconnector)
With fuse links
Rated current Size/A 00/160 1/250 2/400 3/630
At 500 V AC (rms value) kA 100 100 50 50
Maximum permissible let-through I2t value kA2s 223 780 2150 5400
Permissible let-through current of the fuses (peak value) kA 23 32 40 60
Rated short-circuit making capacity with isolating links2) Size 00 1 2 3
At 500 V AC (peak value) kA 6 17 17 17
Rated making and breaking capacity2) (infeed from top or bottom)3)
Size 00 1 0 2 1 3 2
Breaking current Ic (p.f. = 0.35) at 400 V AC, with fuse links, rms value, A 1600 2500 1600 4000 2500 5040 4000
Rated operational current Ie at AC-21B, AC-22B, AC-23B at 500 V AC, with fuse A 160 250 160 400 250 630 400
links
Breaking current Ic (p.f. = 0.35) (rms. value) A 1300 2500 1600 4000 2500 5040 4000
Rated operational current Ie at AC-21B, AC-22B, AC-23B at 690 V AC, with fuse A 160 250 160 400 250 630 400
links
Breaking current Ic (p.f. = 0.35) (rms. value) A 800 1280 1000 2520 1600 3200 2520
Rated operational current Ie at AC-21B, AC-22B A 160 250 160 400 250 630 400
Rated operational current Ie at AC-23B A 100 160 125 315 200 400 315
At 220 (440) V DC, with 2 (3) conducting paths series-connected and fuse links:
• Breaking current Ic (L/R = 15 ms) A 640 1000 640 1600 1600 2520 1600
• Rated operational current Ie at DC-23B A 160 250 160 250 250 630 400
Capacitor switching capacity
Capacitor rating at 400 V AC kvar 80 90 150 250
Rated current In at 525 V AC A 116 130 216 361
Capacitor rating kvar 100 125 200 300
Rated current In A 110 137 220 330
Permissible ambient temperature °C -25 ... +55 for operation4), -50 ... +80 when stored
Mechanical endurance, operating cycles 1600
Degree of protection
Without molded-plastic masking frame IP005)
With molded-plastic masking frame with closed fuse carrier on the operator side IP30
With molded-plastic masking frame with open fuse carrier IP10
Power loss of the switch at Ith (without power loss of fuse links)
Without busbar adapter W 7.8 (16.3)6) 7.5 15 39
Main conductor connections
Cable lug, max. conductor cross-section (stranded) mm2 2.5 ... 120 6 ... 150 6 ... 240 6 ... 2 × 240
Busbar mm 16 ... 22 22 ... 30 22 ... 30 22 ... 30
Clamp terminals mm2 2.5 ... 50 35 ... 120 -- --
Auxiliary switch 1 NO + 1 NC (accessories)
(the same voltage potential must be applied to both NO and NC contact)
At 50 Hz/60 Hz to 400 V AC, rated operational current Ie at AC-12/AC-15 A A 16/6
Flat terminal (DIN 46244) A 6.3 ... 0.8
Permissible mounting positions Vertical or horizontal
(partially reduced switching capacity with horizontal mounting)
Signaling contact for solid-state fuse monitoring 2 NO + 1 NC
Rated operational current Ie
At 250 V, DC-13 A 0.27
At 240 V, AC-15 A 1.5
Thermal free-air rated current Ith A 5
1) When observing degree of pollution 2 (instead of 3) operation is also possi- 4) When using isolating links. If using fuse links, please observe specifica-
ble up to Ui = 1000 V. tions of fuse manufacturer.
2) Rated making and breaking current according to IEC 60947-3 5) For 3NP52 with terminal clamp connection, degree of protection IP10.
Rated making current 6) With busbar adapter.
I = 10 × Ie (AC-23); 3 × Ie (AC-22); 1.5 × Ie (AC-21)
Rated breaking current
Ie = 8 × Ie (AC-23); 3 × Ie (AC-22); 1.5 × Ie (AC-21).
3) When using electronic fuse monitoring, infeed must be from the top.
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
Floor mounting
7 3NP50 60-0CA00
1 × 2.5 ... 50
1 × 2.5 ... 35
250 Flat 6 ... 1505) 1 and 0 1 Without } 3NP52 60-0CA00 1 1 unit 103 5.475
terminals 1 NO + A 3NP52 60-0CA10 1 1 unit 103 5.491
1 NC
Clamp 35 ... 120 1 and 0 1 Without C 3NP52 60-0CB00 1 1 unit 103 5.605
terminals 1 NO + B 3NP52 60-0CB10 1 1 unit 103 5.814
1 NC
3NP52 60-0CA00
400 Flat 6 ... 2405) 2 and 1 2 Without } 3NP53 60-0CA00 1 1 unit 103 6.532
terminals 1 NO + A 3NP53 60-0CA10 1 1 unit 103 6.551
1 NC
3NP53 60-0CA00
630 Flat 6 ... 2 × 2405) 3 and 2 3 Without } 3NP54 60-0CA00 1 1 unit 103 7.945
terminals 1 NO + B 3NP54 60-0CA10 1 1 unit 103 7.958
1 NC
3NP54 60-0CA00
1)
For LV HRC fuse links, see chapter 5 "Fuse Systems".
2)
For 3NP50 60 with flat connectors, appropriate 3NY1 106 cable lug covers
must be used to provide finger-safe cover, according to EN 50274
(see Accessories).
3)
According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235
(use M10 cable lug as necessary).
4)
If auxiliary switch is retrofitted, additional drill holes are required on the
switch.
5)
According to DIN 46234 or DIN 46235; with cable lug to DIN 46235:
Min. conductor cross-section 16 mm2 (use M12 cable lug if necessary).
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
For 40 mm busbar system
■ Overview
Note:
For switch versions "For installation in any distribution board" and
busbar adapters see page 7/117.
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
With fuse monitoring
7
160 Flat termi- 2.5 ... 1503) 00 and 000 1 NO + 1 NO + } 3NP50 60-0EA86 1 1 unit 103 2.484
nals 2) 1 NC 1 NC
1 NO + 2 NO B 3NP50 60-0EA26 1 1 unit 103 2.550
1 NC
Clamp 1 conductor 00 and 000 1 NO + 1 NO + B 3NP50 60-0EB86 1 1 unit 103 2.616
terminals 2.5... 50 1 NC 1 NC
2 conductor 1 NO + 2 NO B 3NP50 60-0EB26 1 1 unit 103 2.650
1 × 2.5 ... 50 1 NC
1 × 2.5 ... 35
250 Flat termi- 6 ... 1504) 1 and 0 1 NO + 1 NO + } 3NP52 60-0EA86 1 1 unit 103 6.014
nals 1 NC 1 NC
1 NO + 2 NO B 3NP52 60-0EA26 1 1 unit 103 6.867
1 NC
Clamp 35 ... 120 1 and 0 1 NO + 1 NO + B 3NP52 60-0EB86 1 1 unit 103 7.095
terminals 1 NC 1 NC
1 NO + 2 NO B 3NP52 60-0EB26 1 1 unit 103 6.659
3NP52 60-0EA86 1 NC
400 Flat termi- 6 ... 2404) 2 and 1 1 NO + 1 NO + } 3NP53 60-0EA86 1 1 unit 103 7.083
nals 1 NC 1 NC
1 NO + 2 NO B 3NP53 60-0EA26 1 1 unit 103 5.410
1 NC
3NP53 60-0EA86
630 Flat termi- 6 ... 2 × 3 and 2 1 NO + 1 NO + } 3NP54 60-0EA86 1 1 unit 103 8.462
nals 2404) 1 NC 1 NC
1 NO + 2 NO B 3NP54 60-0EA26 1 1 unit 103 9.233
1 NC
3NP54 60-0EA86
1)
For LV HRC fuse links, see chapter 5 "Fuse Systems".
2)
For 3NP50 60 with flat connectors, appropriate 3NY1 106 cable lug covers
must be used to provide finger-safe cover, according to EN 50274
(see Accessories).
3)
According to DIN 46234 or 16 ... 95 mm2 according to DIN 46235
(use M10 cable lug as necessary).
4)
According to DIN 46234 or DIN 46235, with cable lug to DIN 46235:
Min. conductor cross-section 16 mm2 (use M12 cable lug if necessary).
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
With fuse monitoring
For 40 mm busbar system
Rated Connection types For LV HRC Auxiliary switches DT Degree of protection IP00, PU PS*/ PG Weight
uninter- (on both sides) fuse links without fuse links, (UNIT, P. unit per PU
rupted acc. to without isolating links, SET, approx.
current DIN 436201) with terminal screws M)
Iu Connec- For conduc- On switch On MSP
tion tor cross- discon-
section nector
A mm2 NH size Version Version Order No. Price kg
per PU
Completely compartmentalized, with high speed closing features with fuse
monitoring by SIRIUS motor starter protectors 2)
Busbars with a width of 12 mm and thickness of 5 mm or 10 mm
160 Flat termi- 2.5 ... 1503) 00 and 000 1 NO + 1 NO + A 3NP50 65-1EF86 1 1 unit 103 2.908
nals 1 NC 1 NC
Connection 1 NO + 2 NO B 3NP50 65-1EF26 1 1 unit 103 2.950
at bottom 1 NC
Clamp 1 conductor 00 and 000 1 NO + 1 NO + B 3NP50 65-1EG86 1 1 unit 103 3.020
terminals 1 NC 1 NC
2.5 ... 50
2 conductors
1 NO +
1 NC
2 NO C 3NP50 65-1EG26 1 1 unit 103 2.973
7
1 × 2.5 ... 50
1× 2.5 ... 35
Connection
at bottom
1)
For LV HRC fuse links, see chapter 5 "Fuse Systems".
2)
For accessories and more devices on busbar systems, see chapter 10
"Busbar Systems".
3)
According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235
(use M10 cable lug as necessary).
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
With fuse monitoring
Fuse monitoring by electronic fuse monitoring device
Floor mounting
Rated Connection types For LV HRC Auxiliary switches DT Degree of protection IP00, PU PS*/ PG Weight
uninter- (on both sides) fuse links without fuse links, (UNIT, P. unit per PU
rupted acc. to without isolating links, SET, approx.
current DIN 436201) with terminal screws M)
Iu Connec- For con- On On the
tion ductor switch fuse
cross- discon- monitor
section nector
Version Version Order No. Price
A mm2 NH size per PU kg
Completely compartmentalized, with high speed closing feature,
with electronic fuse monitoring (self-powered), open-circuit principle
For rated operational voltages Ue from 400 V to 500 V AC,
infeed must come from above!
With plug-in connection for connecting cables from auxiliary switches
(approx. 1 m long) to the fuse monitoring device, status indicator:
7
green LED illuminated, fault indication: green LED flashing,
fuse failure: red LED (display per phase)
160 Flat ter- 2.5 ... 00 and 000 1 NO + 2 NO + B 3NP50 60-0HA13 1 1 unit 103 2.375
minals 2) 1203) 1 NC 1 NC
Clamp 1 con- 00 and 000 1 NO + 2 NO + B 3NP50 60-0HB13 1 1 unit 103 2.500
terminals ductors: 1 NC 1 NC
2.5 ... 50
2 con-
ductors:
1×
2.5 ... 50
1×
3NP50 60-0HA13 2.5 ... 35
250 Flat ter- 6 ... 1504) 1 and 0 1 NO + 2 NO + B 3NP52 60-0HA13 1 1 unit 103 5.865
minals 1 NC 1 NC
3NP52 60-0HA13
400 Flat ter- 6 ... 2404) 2 and 1 1 NO + 2 NO + B 3NP53 60-0HA13 1 1 unit 103 6.951
minals 1 NC 1 NC
3NP53 60-0HA13
630 Flat ter- 6 ...2404) 3 and 2 1 NO + 2 NO + B 3NP54 60-0HA13 1 1 unit 103 8.513
minals 1 NC 1 NC
3NP54 60-0HA13
1)
For LV HRC fuse links, see chapter 5 "Fuse Systems".
2)
For 3NP50 60 with flat connectors, appropriate 3NY1 106 cable lug covers
must be used to provide finger-safe cover, according to EN 50274
(see Accessories).
3)
According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235
(use M10 cable lug as necessary).
4)
According to DIN 46234 or DIN 46235; with cable lug to DIN 46235:
Min. conductor cross-section 16 mm2 (use M12 cable lug if necessary).
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
With fuse monitoring
For 40 mm busbar system
Rated Connection types For LV HRC Auxiliary switches DT Degree of protection IP00, PU PS*/ PG Weight
uninter- (on both sides) fuse links without fuse links, (UNIT, P. unit per PU
rupted acc. to without isolating links, SET, approx.
current DIN 436201) with terminal screws M)
Iu Connec- For con- On On the
tion ductor switch fuse
cross- discon- monitor
section nector
A mm2 NH size Version Version Order No. Price kg
per PU
Completely compartmentalized, with high speed closing feature,
with electronic fuse monitoring (self-powered), open-circuit principle
For rated operational voltages Ue from 400 V to 500 V AC, infeed
must come from above!
Busbars with a width of 12 mm and thickness of 5 mm or 10 mm
160 Flat ter- 2.5 ... 00 and 000 1 NO + 2 NO + B 3NP50 65-1HF13 1 1 unit 103 2.776
minals 1202) 1 NC 1 NC
Connec-
tion at
bottom 7
3NP50 65-1HF13
1) For LV HRC fuse links, see chapter 5 "Fuse Systems".
2) According to DIN 46234 or 16 mm2 ... 95 mm2 according to DIN 46235
(use M10 cable lug as necessary).
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
Accessories
7 3 m long
With electronic fuse monitoring for 3NP50 6.-.H.13
B
B
3NY1 911
3NY1 513-0
1
1
1 unit
1 unit
103
103
0.261
1.235
400 V ... 500 V 3NP52 60-.H.13 C 3NY1 513-2 1 1 unit 103 2.130
(with auxiliary switch 2 NO + 1 NC), 3NP53 60-.H.13 B 3NY1 513-3 1 1 unit 103 2.146
with plug-in connection, 3NP54 60-.H.13 C 3NY1 513-4 1 1 unit 103 0.325
without connector and connecting cable
3NY1 513-3
Plugs and connecting cables (6-pole) 3NP5 with EFM B 3NY1 915 1 1 unit 103 0.372
3 m long
3NY1 915
Auxiliary switches 1 NO + 1 NC
With actuating cams, 3NP501) B 3NY3 033 1 1 unit 103 0.015
screws and washers
(mounting kit)
3NY3 033
With fixing bracket and 3NP52 ... 3NP54 B 3NY3 034 1 1 unit 103 0.015
screws (mounting kit)
3NY3 034
Arc chute
(3 units each are required 3NP50 B 3NY4 031 1 1 unit 103 0.218
for 3NP52, 3NP53 and 3NP52 B 3NY4 011 1 1 unit 103 0.215
3NP54) 3NP53, 3NP54 B 3NY4 012 1 1 unit 103 0.240
3NY4 031
3NY4 011
Molded-plastic masking frames
As replacement for mask- 300 × 220 mm 3NY1 210 A 3NY1 102 1 1 unit 103 0.071
ing frames from assembly 300 × 245 mm 3NY1 211 A 3NY1 103 1 1 unit 103 0.075
kits for installation (without 300 × 290 mm 3NY1 212 A 3NY1 104 1 1 unit 103 0.084
fixing brackets and small
parts)
1)
If retrofitted, drill holes required.
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
Accessories
SITOR fuses for 3NP5 fuse switch disconnectors: Assignment table
For switch disconnectors SITOR fuses Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
Type Permissi- Required NH Opera- Rated Rated DT SET, M) approx.
ble conductor size tional current voltage2)
load cross- class
current1) section
Cu
A mm 2 A V kg
SITOR 3NE1 fuses for 3NP5
3NP50 16 1.5 000 gR/gS 16 690 } 3NE1 813-0 1 3 units 047 0.133
20 2.5 000 gR/gS 20 690 } 3NE1 814-0 1 3 units 047 0.124
25 4 000 gR/gS 25 690 } 3NE1 815-0 1 3 units 047 0.127
35 6 000 gR/gS 35 690 } 3NE1 803-0 1 3 units 047 0.128
40 10 000 gR/gS 40 690 } 3NE1 802-0 1 3 units 047 0.126
50 10 000 gR/gS 50 690 } 3NE1 817-0 1 3 units 047 0.129
63 16 000 gR/gS 63 690 } 3NE1 818-0 1 3 units 047 0.126
80 25 000 gR/gS 80 690 } 3NE1 820-0 1 3 units 047 0.124
100 35 00 gR/gS 100 690 } 3NE1 021-0 1 3 units 047 0.204
7
125 50 00 gRgS 125 690 } 3NE1 022-0 1 3 units 047 0.195
125 50 00 gR 125 690 A 3NE1 022-2 1 3 units 047 0.195
3NP52 160 70 1 gR/gS 160 690 } 3NE1 224-0 1 3 units 047 0.522
160 70 1 gR 160 690 A 3NE1 224-2 1 3 units 047 0.535
200 95 1 gR/gS 200 690 } 3NE1 225-0 1 3 units 047 0.518
200 95 1 gR 200 690 A 3NE1 225-2 1 3 units 047 0.508
250 120 1 gR/gS 250 690 } 3NE1 227-0 1 3 units 047 0.515
250 120 1 gR 250 690 A 3NE1 227-2 1 3 units 047 0.533
3NP53 315 2 × 70 2 gR/gS 315 690 A 3NE1 230-0 1 3 units 047 0.519
315 2 × 70 2 gR 315 690 A 3NE1 230-2 1 3 units 047 0.519
350 2 × 95 2 gR/gS 350 690 } 3NE1 331-0 1 3 units 047 0.687
350 2 × 95 2 gR 350 690 A 3NE1 331-2 1 3 units 047 0.684
400 2 × 95 2 gR/gS 400 690 } 3NE1 332-0 1 3 units 047 0.519
3NP54 450 2 × 120 2 gR/gS 450 690 A 3NE1 333-0 1 3 units 047 0.689
450 2 × 120 2 gR 450 690 A 3NE1 333-2 1 3 units 047 0.691
500 2 × 120 2 gR/gS 500 690 A 3NE1 334-0 1 3 units 047 0.765
560 2 × 150 3 gR/gS 560 690 A 3NE1 435-0 1 3 units 047 1.000
560 2 × 150 3 gR 560 690 A 3NE1 435-2 1 3 units 047 1.098
630 2 × 185 3 gR/gS 630 690 A 3NE1 436-0 1 3 units 047 1.113
625 2 × 185 3 gR 630 690 A 3NE1 436-2 1 3 units 047 1.038
710 2 × (40 x 5) 3 gR/gS 710 690 A 3NE1 437-0 1 3 units 047 1.045
690 2 × (40 x 5) 3 gR 690 600 D 3NE1 437-1 1 3 units 047 1.179
685 2 × (40 x 5) 3 gR 710 600 B 3NE1 437-2 1 3 units 047 1.031
800 2 × (50 x 5) 3 gR/gS 800 690 A 3NE1 438-0 1 3 units 047 1.560
750 2 × (50 x 5) 3 gR 750 600 B 3NE1 438-1 1 3 units 047 1.100
720 2 × (50 x 5) 3 gR 800 600 A 3NE1 438-2 1 3 units 047 1.067
655 2 × (40 x 5) 3 gR 670 690 A 3NE1 447-2 1 3 units 047 1.044
820 2 × (40 x 8) 3 gR 850 690 A 3NE1 438-2 1 3 units 047 1.067
SITOR fuses 3NE3 ... 3NE8, 3NC2 up to 3NC8 for 3NP5
3NP50 25 4 00 gR 25 690 } 3NE8 015-1 1 3 units 047 0.193
33 6 00 gR 35 690 } 3NE8 003-1 1 3 units 047 0.195
45 10 00 gR 50 690 } 3NE8 017-1 1 3 units 047 0.614
54 16 00 gR 63 690 } 3NE8 018-1 1 3 units 047 0.196
68 25 00 aR 80 690 } 3NE8 020-1 1 3 units 047 0.206
89 35 00 aR 100 690 } 3NE8 021-1 1 3 units 047 0.207
106 50 00 aR 125 690 } 3NE8 022-1 1 3 units 047 0.195
130 70 00 aR 160 690 } 3NE8 024-1 1 3 units 047 0.195
3NP523) 32 6 0 gR 32 1000 } 3NE4 101 1 3 units 047 0.824
40 10 0 gR 40 1000 } 3NE4 102 1 3 units 047 0.258
50 10 0 gR 50 1000 } 3NE4 117 1 3 units 047 0.274
63 16 0 gR 63 1000 } 3NE4 118 1 3 units 047 0.257
80 25 0 aR 80 1000 } 3NE4 120 1 3 units 047 0.261
95 35 0 aR 100 1000 } 3NE4 121 1 3 units 047 0.260
120 50 0 aR 125 1000 } 3NE4 122 1 3 units 047 0.265
150 70 0 aR 160 1000 } 3NE4 124 1 3 units 047 0.274
3NP53 100 35 1 aR 100 1000 A 3NE3 221 1 3 units 047 0.510
120 50 1 aR 125 1000 A 3NE3 222 1 3 units 047 0.506
150 70 1 aR 160 1000 } 3NE3 224 1 3 units 047 0.513
190 95 1 aR 200 1000 } 3NE3 225 1 3 units 047 0.586
230 120 1 aR 250 1000 } 3NE3 227 1 3 units 047 0.580
285 185 1 aR 315 1000 } 3NE3 230-0B 1 3 units 047 0.513
310 240 1 aR 350 1000 A 3NE3 231 1 3 units 047 0.515
330 240 1 aR 400 1000 A 3NE3 232-0B 1 3 units 047 0.520
360 2 × 150 1 aR 450 1000 } 3NE3 233 1 3 units 047 0.580
210 120 2 aR 250 800 } 3NE4 327-0B 1 3 units 047 0.780
270 240 2 aR 315 800 } 3NE4 330-0B 1 3 units 047 1.539
400 2 x (30 x 5) 2 aR 450 800 } 3NE4 333-0B 1 3 units 047 0.682
1) 3)
In the case of cyclic loads, the currents may have to be reduced again Due to the mechanical stress on the relatively long fuse blades, SITOR
(precise values on request). 3NE41 fuses should be switchable only occasionally and only at zero cur-
2)
When maintaining overvoltage category 2 (instead of 3) and degree of pol- rent.
lution 2 (instead of 3) to EN 60 947-1, the rated insulation voltage of the
3NP fuse switch disconnector is also Ui = 1000 V.
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
Accessories
For switch disconnectors SITOR fuses Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
Type Permissi- Required NH Opera- Rated Rated DT SET, M) approx.
ble conductor size tional current voltage2)
load cross- class
current1) section
Cu
A mm 2 A V kg
3NP54 360 240 2 aR 400 1000 A 3NE3 332-0B 1 3 units 047 0.683
400 2 x 150 2 aR 450 1000 A 3NE3 333 1 3 units 047 0.687
450 2 x 150 2 aR 500 1000 } 3NE3 334-0B 1 3 units 047 0.697
510 2 x 185 2 aR 560 1000 } 3NE3 335 1 3 units 047 0.692
580 2 x 185 2 aR 630 1000 } 3NE3 336 1 3 units 047 0.810
630 2 × 200 2 aR 710 900 } 3NE3 337-8 1 3 units 047 0.687
630 2 × 200 2 aR 800 800 } 3NE3 338-8 1 3 units 047 0.686
630 2 × 200 2 aR 900 690 } 3NE3 340-8 1 3 units 047 0.657
450 2 x (30 x 5) 2 aR 500 800 } 3NE4 334-0B 1 3 units 047 0.683
600 2 x (40 x 5) 2 aR 710 800 } 3NE4 337 1 3 units 047 0.689
145 70 3 gR 150 500 B 3NC2 423-3C 1 3 units 047 0.940
180 95 3 gR 200 500 B 3NC2 425-3C 1 3 units 047 0.940
7 225
255
120
185
3
3
gR
gR
250
300
500
500
B
B
3NC2 427-3C
3NC2 428-3C
1
1
3 units
3 units
047
047
0.940
0.940
330 240 3 gR 350 500 B 3NC2 431-3C 1 3 units 047 0.940
400 240 3 gR 400 500 B 3NC2 432-3C 1 3 units 047 0.940
135 70 3 gR 150 660 B 3NC8 423-3C 1 3 units 047 0.940
180 95 3 gR 200 660 B 3NC8 425-3C 1 3 units 047 0.940
225 120 3 gR 250 660 B 3NC8 427-3C 1 3 units 047 0.940
300 240 3 gR 350 660 B 3NC8 431-3C 1 3 units 047 0.940
425 2 x 150 3 gR 500 660 B 3NC8 434-3C 1 3 units 047 0.940
800 3 x (60 x 6) 3 aR 1000 600 C 3NC8 444-3C 1 3 units 047 0.940
1)
In the case of cyclic loads, the currents may have to be reduced again
(precise values on request).
2)
When maintaining overvoltage category 2 (instead of 3) and degree of pol-
lution 2 (instead of 3) to EN 60 947-1, the rated insulation voltage of the
3NP fuse switch disconnector is also Ui = 1000 V.
3)
Due to the mechanical stress on the relatively long fuse blades, SITOR
3NE41 fuses should be switchable only occasionally and only at zero cur-
rent.
For technical specifications and dimensional drawings of the
SITOR fuses, see chapter 5 "Fuse Systems"
Switch Disconnectors
SENTRON 3NP5 Fuse Switch Disconnectors up to 630 A
Assembly kits for distribution systems
3NY1 106
For separate covering of the With auxiliary 290 × 135 A 3NY1 116 1 1/225 units 103 0.071
upper and lower cable lug switch
connections 3NP50 with and 290 × 135 A 3NY1 108 1 1/200 units 103 0.048
without auxilia-
ry switch
Assembly kits for flush mounting
With molded-plastic masking 3NP50 60 250 × 149 B 3NY1 208 1 1 unit 103 0.531
frame, fixing brackets and 3NP52 60 300 × 220 B 3NY1 210 1 1 unit 103 0.287
small parts. For disconnec-
tors with and without auxiliary 3NP53 60 300 × 245 B 3NY1 211 1 1 unit 103 0.298
switches 3NP54 60 300 × 290 B 3NY1 212 1 1 unit 103 0.313
3NY1 212
Covers for cable lug connections Cover length
Can be screwed onto free 3NP52 99 A 3NY1 241 1 1 unit 103 0.205
screw end to protect against 3NP53/3NP54 95 B 3TX6 546-3B 1 1 unit 101 0.260
accidental touch
(1 set = 6 units) 120 B 3NY1 245 1 1 unit 103 0.336
3TX6 546-3B
Clamp terminals Conductor
(1 set = 3 units) cross-section
3NP50 2.5 ... 50 mm2 1) B 3NY1 903 1 1 unit 103 0.108
3NP52 35 ... 120 mm2 B 3NY1 907 1 1 unit 103 0.225
3NY1 907
Busbar adapters Busbar width
For 60 mm busbar system 3NP50 108 A 8US12 91-4SB00 1 1 unit 143 0.551
3NP52, 3NP53, 250 (length A 8US12 10-4AG00 1 1 unit 143 3.060
3NP542) 320mm, M10
terminal screws,
connecting ca-
bles must be
manufactured)
8US12 10-4AG00
Sealing lugs 3NP50 B 3NY1 940 1 1 unit 103 0.010
Retrofittable
(1 pack = 10 units)
1)
Also available in 2-wire version: 1 × 2.5 mm2 ... 50 mm2 and
1 × 2.5 ... 35 mm2.
2)
Disconnector is wider than adapter. The adapter can, however, be
expanded to 276 mm with two 8US19 98-2BM00 side modules.
* You can order this quantity or a multiple thereof.
Siemens LV 10.1 · 2011 7/117
© Siemens AG 2010
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
Introduction
■ Overview
All key product features at a glance
• Compliant with IEC/EN 60439-1, IEC/EN 60947-3
• Voltage levels up to 690 V AC
• Rated operational current from 160 A to 2000 A
• Fuse links according to IEC 60269 Part 1 can be used – nickel-
plated fuse blades are not permissible due to the high transfer
resistance
• In open position safe from touch by the back of the hand
(exception 3NJ56: IP00)
• Parking position for maintenance
• 1-pole or 3-pole switchable
• Vertical and horizontal mounting position
• Climate-proof
• Degree of protection IP30 with closed fuse carriers, IP10 with
7 open fuse carriers (exception 3NJ56: IP00)
1 4
2 6
13
12
7 Flat connector
8 Saddle terminal
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
Introduction
Overview of all components and accessory parts: 3NJ4/3NJ5 in sizes 1 to 3
2
7
7
16*BE
■ Benefits ■ Application
Parking position SENTRON 3NJ41 and 3NJ56 single-pole and 3-pole in-line fuse
switch disconnectors are designed for installation in low-voltage
For maintenance e.g., the fuse carriers of the 1-pole switchable distribution boards, substations and cable distribution cubicles.
in-line fuse switch disconnectors of sizes 1 to 3 and the 3-pole
switchable in-line fuse switch disconnectors of size 00 can be
mounted after being turned by 180° (fuse facing outwards).
This results in the following advantages:
• Visible disconnection point
• Depot for fuse links (parking position)
• No opportunity for mistakes on replacing the fuse links
• Additional touch protection in the vicinity of the lyre-shaped
contacts
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
Introduction
■ Technical specifications
Standards IEC 60947-1, IEC 60947-3
Type 3NJ41 0 3NJ41 2 3NJ41 3 3NJ41 4 3NJ56 3NJ41 5 3NJ41 8 3NJ41 6 3NJ41 7
3NJ50
Conventional thermal current
Free-air with gG fuses, Ith A 160 250 400 630 1250 630 800 1260 1600
Free-air with isolating link, Ith A -- -- -- 800 -- 1000 1250 1600 2000
Free-air with gTr fuses, Ith A -- -- -- -- 1154 722 910 1154 1444
Rated apparent power of the transformer, Sn kVA -- -- -- -- 800 500 630 800 1000
For fuse links and isolating links Size 00 1 2 3 4a 3 3 2x3 2x3
gG acc. to IEC 60269, In A 160 250 400 630 1250 630 800 2 x 630 2 x 800
Free-air with isolating link, In A -- -- -- -- -- 1000 1250 2 x 800 2 x 1000
gTr acc. to VDE 0636-2011, Irat A -- -- -- -- 1154 722 909 2 x 577 2 x 722
gTr acc. to VDE 0636-2011, Sn kVA -- -- -- -- 800 500 630 2 x 400 2 x 500
Rated operational voltage Ue V 690 690 690 690 690 690 400 690 400
7
At 40 Hz ...60 Hz AC
Rated insulation voltage Ui V 800 1000 1000 1000 1000 1000 690 1000 690
Rated impulse withstand voltage Uimp kV 8 12 12 12 12 12 8 12 8
Rated conditional short-circuit current with fuses
With gG fuse (rms value) kA 80/50 110 110 110 80 110 50 80 50
With gTr fuse (rms value) kA -- -- -- -- -- -- 50 -- --
Max. permissible power loss per W 12 32 45 48 110 51 61 48 51
fuse link
Rated short-time withstand current ICW kA -- 14.5 14.5 14.5 35 14.5 14.5 25 25
rms value
Rated making and breaking capacity
Rated operational current Ie for gG fuses
At AC-21B 400 V AC A 160 250 400 630 1250 630 800 2 x 630 2 x 800
AC-22B 400 V AC A 160 250 400 630 1250 630 800 2 x 630 2 x 800
AC-23B 400 V AC A -- 250 400 -- -- -- -- -- --
AC-21B 500 V AC A 160 250 400 630 1250 -- -- -- --
AC-22B 500 V AC A 160 250 400 630 1250 -- -- -- --
AC-23B 500 V AC A -- -- -- -- -- -- -- -- --
AC-21B 690 V AC A 100 250 400 630 1250 -- -- -- --
AC-22B 690 V AC A 100 250 -- -- -- -- -- -- --
AC-23B 690 V AC A -- -- -- -- -- -- -- -- --
Rated operational current Ie for gTr fuses
At AC-22B 400 V AC A -- -- -- -- -- 722 910 2 x 577 2 x 722
Rated operational current Ie for isolating links
At AC-22B 400 V AC A -- -- -- -- -- 1000 1250 2 x 800 2 x 1000
Capacitive switching capacity kvar -- 105 ... 155 ... 250 ...300 -- -- -- -- --
115 185
Permissible ambient temperature °C -25 ... +55, > 35 °C with derating factors
Mechanical endurance, operating cycles 1400 1400 800 800 500 800 500 500 500
Electrical endurance, operating cycles 200 200 200 200 100 100 100 100 100
Degree of protection
With closed fuse carrier, IP30 IP30 IP30 IP30 IP10 IP30 IP30 IP30 IP30
with terminal cover and peripheral cover
With open fuse carrier IP10 IP10 IP10 IP10 IP00 IP10 IP10 IP10 IP10
Power loss of the main current paths at Ith W 18 23 54 115 190 275 155 350 375
Main conductor connections
Terminal screws M8 M10 M12 M12 M16 2 × M12 2 × M12 3 × M12 4 × M12
Flat bars mm 20 30 30 30 80 80 x 10 80 x 10 -- --
Cable lug, max. conductor cross-section mm2 95 240 240 240 2 × 300 2 × 300 2 × 300 3 × 300 4 × 300
(stranded) 4 x 185 4 x 185
Tightening torque Nm 12 ... 15 30 ... 35 35 ... 40 35 ... 40 50 ... 60 35 ... 40 35 ... 40 35 ... 40 35 ... 40
Clamp/V terminals mm2 1.5 ... 70 25 ... 300 25 ... 300 25 ... 300 -- -- -- -- --
Fixing screws M8 M12 M12 M12 M16 M12 M12 M12 M12
Required tightening torque for mounting on bus- Nm 16 ... 18 35 ... 40 35 ... 40 35 ... 40 50 ... 60 35 ... 40 35 ... 40 35 ... 40 35 ... 40
bars
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
1-pole switchable
7
3NJ41 21-3BF01
3NJ41 21-3BF11
1)
Fixing screws for mounting on busbars must be ordered separately.
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
3-pole switchable
7 3NJ41 23-3BF01
M12 stud terminal
V terminal
A
A
3NJ41 33-3BJ01
3NJ41 33-3BT01
1
1
1 unit
1 unit
143
143
5.580
5.899
630 3 and 2 185 M12 flat connector } 3NJ41 43-3BF01 1 1 unit 143 6.426
M12 stud terminal A 3NJ41 43-3BJ01 1 1 unit 143 6.321
V terminal A 3NJ41 43-3BT01 1 1 unit 143 6.675
3NJ41 .3-3CF..
In-line fuse switch disconnectors, 3-pole switchable,
for integratable current transformers
160 00 and 000 100 M8 flat connector } 3NJ41 03-3BF12 1 1 unit 143 1.140
250 1 185 M10 flat connector } 3NJ41 23-3BF11 1 1 unit 143 5.890
400 2 and 1 185 M12 flat connector } 3NJ41 33-3BF11 1 1 unit 143 5.910
630 3 and 2 185 M12 flat connector } 3NJ41 43-3BF11 1 1 unit 143 6.870
Trans- Rated Center-to- Rated current Rated opera- DT Order No. Price PU PS*/ PG Weight
former apparent center of gTr fuses tional current Ie per PU (UNIT, P. unit per PU
apparent power of clearance with 3NJ4914- SET, approx.
power the gTr 8BA00 isolating M)
fuses link
kVA kVA mm A A kg
In-line fuse switch disconnectors, 3-pole switchable,
for secondary-side fusing of transformers and feeder lines
500 500 185 722 1000 A 3NJ41 53-3BF01 1 1 unit 143 11.030
630 630 185 909 1250 A 3NJ41 83-3BF01 1 1 unit 143 12.943
800 2 x 400 185 2 x 577 1600 C 3NJ41 63-3BF01 1 1 unit 143 12.943
1000 2 x 500 185 2 x 722 2000 C 3NJ41 73-3BF01 1 1 unit 143 12.943
3NJ41 63-3BF01
1) Fixing screws for mounting on busbars must be ordered separately.
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
Accessories
33NJ49 12-1AA01
Covers size 3 3NJ41 4 A 3NJ49 12-1EA00 1 1 unit 143 0.200
For double bars
7
3NJ49 12-1EA00
Cover size 00 3NJ41 03 A 3NJ49 12-1DA02 1 1 unit 143 0.005
(can also be used as spacer)
top and bottom
to cover long cable lugs and compen-
sate for combination of 3NJ41 03 with
terminals 3NJ41 2 to 3NJ41 4
(1 set = 2 units: short and long 2) )
3NJ49 12-1DA02
Blanking covers 50 mm wide A 3NJ49 12-2AA00 1 1 unit 143 0.189
For panel cut-out
3NJ49 12-2AA01
According to the size of the switch 100 mm wide A 3NJ49 12-2BA00 1 1 unit 143 0.215
disconnectors: sizes 1 to 3
(for fitting in the cutout of the control
panels)
3NJ49 12-2BA00
For 3NJ41 03 50 mm wide A 3NJ49 12-2CA00 1 1 unit 143 0.090
3NJ49 12-2CA01
Fixing clips 3NJ41 A 3NJ49 18-0AA00 1 1 unit 143 0.130
(1 set = 4 units, including
fixing accessories)
2 units per side, for fixing the cover of
the control panel front
3NJ49 18-0AAA00
1)
With cable lugs and connection from above, the terminal cover can be
extended by connecting two units together.
2)
Can be shortened (in exchange for short cover, included in the scope of
supply of the in-line disconnector).
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
Accessories
Adapters for screw fixing on busbar systems
7
• For fitting of two 3NJ41 03 fuse switch 3NJ41 03 A 3NJ49 18-0DA02 1 1 unit 143 0.751
disconnectors (= 1 holder) onto a busbar
system with 185 mm center-to-center
spacing (including adaptation of the
installation depth to that of the 3NJ41 2 to
3NJ41 4 fuse switch disconnectors)
• For fitting two 3NJ50 fuse switch discon- 3NJ50 13 and D 3NJ59 30-3BB 1 1 unit 143 0.675
nectors (= 1 holder) (to adapt the overall 3NJ50 33
depth of sizes 1 to 3)
• For fitting one 3NJ41 03 fuse switch dis- 3NJ41 03 A 3NJ49 18-0EA00 1 1 unit 143 0.232
connector (= 3 separate brackets) onto a
3NJ49 18-0DA02 busbar system with 60 mm center-to-cen-
ter spacing
Adapters with busbar terminals 3NJ41 03 D 3NJ49 18-0DB02 1 1 unit 143 0.751
For fitting two 3NJ41 03 fuse switch
disconnectors (= 1 holder) onto a busbar
system with 185 mm center-to-center
spacing (including adaptation of the overall
depth to the 3NJ41 2 to 3NJ41 4 fuse switch
disconnectors)
Fixing screws 3NJ41 03 B 3NJ49 18-0DC02 1 1 unit 143 0.200
for fitting 3NJ41 03 switch disconnectors
with integratable current transformers onto
adapters
3NJ49 18-0EA00 (1 set = 3 items)
Busbar supports 3NJ41 and 3NJ5 } 3NJ59 74-0AB 1 1 unit 143 0.463
For 100 mm and 185 mm center-to-center
spacing, for screwing on of busbars
3NJ59 74-0AB
Grounding kit with 3NJ41 4 to D 3NJ49 10-1AA00 1 1 unit 143 4.200
connecting cable 25 mm2 3NJ41 8
3NJ49 10-1AA00
Busbar terminals 3NJ41 03 } 3NJ49 11-3AA00 1 1 unit 143 0.176
3NJ49 11-3AA00
For rapid mounting of the in-line 3NJ41 2 to } 3NJ49 11-3BA01 1 1 unit 143 0.607
disconnectors onto the busbars 3NJ41 4
(1 set = 3 units)
3NJ49 11-3BA01
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
Accessories
3NJ49 11-4AA00
Prism terminal kit 3NJ41 03 A 3NJ49 11-1AA00 1 1 unit 143 0.098
Connector Al/Cu, 10 ... 70 mm2
(1 set = 3 units)
3NJ49 11-1AA00
Box terminal kit 3NJ41 2 to 3NJ41 4 A 3NJ49 11-2BQ00 1 1 unit 143 0.949
Connector Al/Cu, 95 ... 240 mm2
(for connection to flat connector)
(1 set= 3 units) 7
3NJ4911-2BQ00
Busbar connection assembly kit for NH 1, 2, 3
With flat connector
2 x 240 mm2 3NJ41 2 to 3NJ41 4 A 3NJ49 11-5AA00 1 1 unit 143 0.500
3NJ49 11-5AA00
2 x 300 mm2/3x 120 mm2 3NJ41 2 to 3NJ41 4 A 3NJ49 11-5BA00 1 1 unit 143 1.700
3NJ49 11-5BA00
1 x 400 mm2 3NJ41 2 to 3NJ41 4 A 3NJ49 11-5CA00 1 1 unit 143 1.800
3NJ49 11-5CA00
Busbar connection assembly kit for NH3
as double bars
3 x 300 mm2 / 4 x 185 mm2 3NJ41 4 A 3NJ49 11-6AA00 1 1 unit 143 2.800
3NJ49 11-6AA00
4 x 240 mm2 3NJ41 4 A 3NJ49 11-6BA00 1 1 unit 143 3.800
3NJ49 11-6BA00
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
Accessories
3NJ49 11-6BA00
Auxiliary switch mounting kit 3NJ41 to 3NJ50 A 3NJ49 13-1AA01 1 1 unit 143 0.029
For sizes 00 to 3 with connecting
cables, for 3-pole switchable switch
disconnectors only
3NJ49 13-6AA02
Fuse 630 kVA 909 A 3NJ41 8 C 3NJ49 14-8AA00 1 1 unit 143 1.341
Size NH 3
7
Specially for the protection of
transformers
(minimum order quantity 3 units)
Isolating links B 3NJ49 14-8BA00 1 1 unit 143 2.800
Size NH 3, 1250 A
3NJ49 14-8BA00
Mounting hooks A 3NJ49 18-1AA00 1 1 unit 143 0.120
(one per in-line disconnector required)
3NJ49 18-1AA00
Distance compensation 3NJ41 03 } 3NJ49 15-1BA00 1 1 unit 143 0.020
For fuse switch disconnectors, with 3NJ41 2 to 3NJ41 4 } 3NJ49 15-2BA00 1 1 unit 143 0.095
integratable current transformers if no
current transformer is built in.
3NJ49 15-1BA00
3NJ49 15-2BA00
Terminal strips 3NJ41 03 } 3NJ49 15-1CA00 1 1 unit 143 0.030
3NJ41 2 to 3NJ41 4 } 3NJ49 15-2CA00 1 1 unit 143 0.110
3NJ49 15-1CA00
3NJ49 15-2CA00
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
Accessories
Switch Disconnectors
SENTRON 3NJ4, 3NJ5 In-Line Fuse Switch Disconnectors up to 2000 A
Notes
Switching Devices
8/2 Introduction
8/8 Pushbuttons
8/20 DC Isolators
Insta Contactors
8/30 Insta contactors, DC technology
8/33 Insta contactors, AC technology
8
8/37 Soft-Starting Devices
Timers
8/38 Digital time switches
8/45 Mechanical time switches
8/49 Timers for buildings
8/51 Timers for industrial applications
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical specifications
under Entry List:
- Updates
- Downloads
- FAQ
- Manuals
- Characteristic curves
- Certificates
and at
www.siemens.com/lowvoltage/
configurators
- Configurators
Switching Devices
Introduction
■ Overview
Devices Page Field of application Standards Used in
Non-residential
Residential
buildings
buildings
Industry
Control switches 8/5 For the switching of lighting and other IEC/EN 60947-3; ✓ ✓ ✓
electrical devices up to 20 A. IEC/EN 60669-1;
For use in control cabinets for the logical GB14048.3-2002 CCC
linking of functions.
Light indicators 8/12 Light indicators for signaling switching DIN VDE 0710-1 ✓ -- ✓
states or faults in systems.
ON/OFF switches 8/15 For the switching of lighting, motors and 16 A ... 25 A and ✓ ✓ ✓
other electrical devices from 20 to 125 A. 40 A ... 100 A:
IEC/EN 60947-3;
IEC/EN 60669-1,
(VDE 0632-1)
32 A and 125 A:
IEC/EN 60947-3;
GB14048.3-2002 CCC
Busbar Systems 8/22 For fast and safe connection IEC/EN 60439-1 ✓ -- ✓
Switching Devices
Introduction
Residential
buildings
Non-resi-
Industry
dential
Remote control switches 8/24 For the switching of lighting up to IEC 60669-1 ✓ ✓ ✓
16 A in rooms using several push- IEC 60669-2
buttons and central ON/OFF IEC 60669-3
switches. EN 60669
EN 60669-2-2 and
EN 60669-2-2/A1
8
Insta contactors
Insta contactors, DC technology 8/30 Insta contactors 24, 40 and 63 A for IEC 60947-4-1 ✓ ✓ ✓
the switching of heating, lighting, IEC 60947-5-1
such as fluorescent lamps, incan- IEC 61095
descent lamps, ohmic or inductive EN 60947-4-1
loads. EN 60947-5-1
EN 61095
UL 508
Insta contactors, AC technology 8/33 Insta contactors 20, 25, 40 and 63 A IEC 60947-4-1 ✓ ✓ ✓
for the switching of heating, lighting, IEC 60947-5-1, IEC 61095,
such as fluorescent lamps, incan- EN 60947-4-1
descent lamps, ohmic or inductive EN 60947-5-1
loads. EN 61095
NF C 61-480
(NF EN 61095)
Switching Devices
Introduction
Non-residential
Residential
buildings
buildings
Industry
Timers
Digital time switches 8/38 Minute-precise switching of devices and sys- IEC 60730-1 and ✓ ✓ ✓
tem components in day, week and year pro- IEC 60730-2-7
grams. Unique due to the wide variety of EN 60730-1 and
functions offered by the Mini and Top versions; EN 60730-2-7
for PC programming Astro, Profi and Expert
Mechanical time switches 8/45 Accurate and 15-minute switching accuracy. IEC 60730-1 and ✓ ✓ ✓
With automatic time setting during commission- IEC 60730-2-7
ing and automatic switching to daylight EN 60730-1 and
savings. EN 60730-2-7
UL 60730
8
Timers for buildings 8/49 Lighting controls with stairwell lighting timers IEC 60699 ✓ ✓
ensure the safe use of stairwells and save EN 60669,
energy. Expanded applications for common DIN 18015
rooms and garages, as well as the time switch-
ing of ventilators and fluorescent lamps.
Timers for industrial 8/51 Multifunctional, delay, wiper, flashing and OFF- IEC 60255 ✓
applications delay timers in control circuits expand the use EN 60255
of distribution boards in both small and large
plants.
Switching Devices
Control switches
■ Overview
Two-way switches are used in control cabinets and distribution Control switches in a range of contact versions have an integral
boards for switching small loads on/off or over. control lamp for the ON setting.
Group switches with center position permit the positions The auxiliary switch (AS) signals the contact position of the
open/stop/closed, for example to control anti-clockwise rotation switch. It has the same design as the auxiliary switch used for
- Off - clockwise rotation. the miniature circuit breakers (see Chapter "Miniature Circuit
Breakers").
■ Benefits
• The control switches can be bus-mounted with each other or • The handle locking device prevents undesired manual on and
with 5TE4 8 pushbuttons, 5TE5 8 light indicators or 5TT4 1 re- off switching. This increases operational safety.
mote control switches and 5TT4 2 switching relays. This saves • The handle locking device is a universal accessory for all
time and space. switches and miniature circuit breakers. This simplifies
• For busbars, see page 8/22. logistics.
■ Technical specifications
5TE8 1
Standards IEC/EN 60947-3;
IEC/EN 60669-1
Approvals EN 60669
Rated operational current Ie Per conducting path A 20
Rated operational voltage Ue 1-pole V AC 230
Multipole V AC 400
Rated power dissipation Pv Contact per pole VA 0.7
Conventional thermal current Ithe (enclosed) A 20
Rated breaking capacity At p.f. = 0.65 A 60
Rated making capacity At p.f. = 0.65 A 60
Short-circuit strength
In conjunction with fuse of the same EN 60269 gL/gG kA 10
rated operational current
Rated impulse withstand voltage Uimp kV >5
Clearances Open contacts mm 2×>2
Between the poles mm >7
Creepage distances mm >7
Mechanical service life Switching cycles 25000
Electrical service life Switching cycles 10000
Minimum contact load V; mA 10; 300
Rated short-time currents
Per conducting path at p.f. = 0.7 Up to 0.2 s A 650
Up to 0.5 s A 400
(The respective rated surge current can Up to 1 s A 290
be calculated by multiplying by a factor of 1.5). Up to 3 s A 170
Terminals ±screw (Pozidriv) 1
Max. tightening torque Nm 1.2
Conductor cross-sections Rigid mm2 1.5 ... 6
Flexible, with end sleeve mm2 1 ... 6
Permissible ambient temperature °C -5 ... +40
Resistance to climate
At 95 % relative humidity Acc. to DIN 50015 °C 45
Switching Devices
Control switches
8
Group switches with center position (20 A)
With sealable switch position,
separate handle locking device can be retrofitted
Auxiliary switch cannot be retrofitted
1 CO 20 230 6 1 } 5TE8 141 1 1 unit 027 0.060
Switching Devices
Control switches
Spacers
8
Contour for modular devices with a mounting depth
of 70 mm;
can be snapped onto either side of the busbar, so
that two spacers allow for convenient cable routing
0.5 } 5TG8 240 1 2 units 027 0.010
Cap sets
For manual changing of the luminous plates for
5TE8 10 control switches
Cap set comprising 1 red, green, yellow, white and C 5TG8 068 1 1 set 027 0.006
blue plate each
Switching Devices
Pushbuttons
■ Overview
The pushbuttons are used in control systems, e.g. to switch on function for manual use, as control switches or for the switching
seal-in circuits or as pushbuttons with maintained-contact of loads up to 20 A.
■ Benefits
• Pushbuttons with setting function for momentary-contact or • Pushbuttons and light indicators with separate infeed in one
• In the case of devices with two pushbuttons and two lamps, • Pilot lights and caps can also be safely replaced during oper-
each pushbutton must be set separately. This increases the ation without the use of tools. Functionality is quickly restored.
application options of devices. • A range of different-colored, transparent caps enable the
signaling of plant states in compliance with IEC 60073. Three
indications are possible for each device - this saves space.
Switching Devices
Pushbuttons
■ Technical specifications
5TE4 8
Standards IEC/EN 60947-3;
IEC/EN 60669-1
Approvals EN 60669-1
Rated operational current Ie Per conducting path A 20
Rated operational voltage Ue 1-pole V AC 230
Multipole V AC 400
Rated power dissipation Pv Per pole VA 0.6
Conventional thermal current Ithe (enclosed) A 20
Rated breaking capacity At p.f. = 0.65 A 60
Rated making capacity At p.f. = 0.65 A 60
Rated impulse withstand voltage Uimp kV >5
Clearances Open contacts mm 2×>2
Between the poles mm >7
Creepage distances mm >7
Mechanical service life Switching cycles 25000
Minimum contact load V; mA 10; 300
Rated short-time currents
Per conducting path at p.f. = 0.7 Up to 0.2 s A 650
Switching Devices
Pushbuttons
1 NO, 1 NO
1 green pushbutton, 20 400 6 1 B 5TE4 804 1 1 unit 027 0.093
1 blue pushbutton
1 NO + 1 NC
1 red pushbutton 20 400 6 1 B 5TE4 805 1 1 unit 027 0.074
1 NO + 1 NC
1 green pushbutton 20 400 6 1 B 5TE4 806 1 1 unit 027 0.067
1 NO + 1 NC
1 yellow pushbutton 20 400 6 1 B 5TE4 807 1 1 unit 027 0.074
8 1 NO + 1 NC
1 blue pushbutton 20 400 6 1 B 5TE4 808 1 1 unit 027 0.071
2 NO
1 gray pushbutton 20 400 6 1 B 5TE4 811 1 1 unit 027 0.074
3 NO + N
1 gray pushbutton 20 400 6 1 B 5TE4 812 1 1 unit 027 0.093
4 NC
1 gray pushbutton 20 400 6 1 B 5TE4 813 1 1 unit 027 0.092
2 CO
1 gray pushbutton 20 400 6 1 B 5TE4 814 1 1 unit 027 0.089
1 NO
1 red pushbutton 20 230 6 1 } 5TE4 821 1 1 unit 027 0.073
2 NO
1 red pushbutton 20 400 6 1 B 5TE4 823 1 1 unit 027 0.084
2 NC
1 red pushbutton 20 400 6 1 B 5TE4 824 1 1 unit 027 0.083
Switching Devices
Pushbuttons
Red and green (1 set contains 10 lamps per color), D 5TG8 067 1 1 set 027 0.011
yellow, blue and white (1 set contains 5 lamps per color)
Red, green, yellow (1 set = 3 units) C 5TG8 070 1 1 set 027 0.007
Switching Devices
Light indicators
■ Overview
Light indicators are used to signal switching states or faults in They are available as single, double or triple light indicators.
systems.
The triple light indicators are used as phase or signal indicators.
■ Benefits
• Pilot lights and caps can also be safely replaced during oper- • The lamps are mounted in a slotted base, which protects
8 ation without the use of tools. Functionality is quickly restored.
• A range of different-colored, transparent caps enable the
against polarity reversal. This ensures the correct polarization
for all DC applications.
signaling of plant states in compliance with IEC 60073. Three • A range of different-colored, transparent caps enable the
indications are possible for each device - this saves space. signaling of plant states in compliance with IEC 60073. Three
indications are possible for each device - this saves space.
• The devices have preferred positions for the N terminals, so • A light indicator with three lamps enables three-phase signal-
that it is possible to bus-mount several devices. This ensures ing and "traffic-light signaling" in a single modular width. This
fast and simple installation saves valuable installation space and makes things more
• The options for bus mounting are described in the chapter manageable. This enables implementation of the signaling of
"Miniature circuit breakers". system states as defined in IEC 60073.
Switching Devices
Light indicators
■ Technical specifications
5TE5 8
Standards DIN VDE 0710-1
Rated operational voltage Ue Max. V AC 230 (for different voltages see 5TG8 lamps)
Rated power dissipation Pv VA See 5TG8 lamps
Clearances Between the terminals mm >7
Terminals ±screw (Pozidriv) 1
Max. tightening torque Nm 1.2
Conductor cross-sections Rigid mm2 1.5 ... 6
Flexible, with end sleeve mm2 1 ... 6
Permissible ambient temperature °C -5 ... +40
Resistance to climate
At 95 % relative humidity Acc. to DIN 50015 °C 45
5TG8 05.
Color coding according to IEC 60073
Rated power dissipation Pv Meaning
• LED VA 0.4
Safety of people Process state System state
Color and environment
8
Red Danger Emergency Faulty
Yellow Warning/Caution Abnormal
Green Safety Normal
Blue Stipulation
White No special significance assigned
Switching Devices
Light indicators
8 Red, transparent
(1 set = 5 units)
B 5TG8 061 1 1 set 027 0.004
Switching Devices
ON/OFF switches
■ Overview
The devices are used for the switching of lighting, motors and The ON/OFF switches in the rated currents 32 A to 125 A can be
other electrical devices. used as switch disconnectors according to IEC/EN 60947-3.
The rated currents of the range are 20 A to 125 A. There is a A special version of the ON/OFF switch with rated current 63 A
compact series of space-saving devices with up to 4 NO con- is available for use in meter cabinets. This version can be locked
tacts in a single MW available for rated currents 20 A and 32 A. in the "OFF" position using a special key. The clamping screws
are mechanically covered so that they are no longer accessible.
■ Benefits
• The switches can be retrofitted with auxiliary switches without • Clear and visible conductor connection in front of the busbar
the need for tools for safe and easy mounting.
• Uniform auxiliary switches for miniature circuit breakers and • The infeed can be either from the top or the bottom as the
switches. So no need to stock-keep additional components. terminals are identical. This simplifies connection.
• The 20 A and 32 A switches can be bus-mounted with each • Spacers can be used as a compensating element and have a
other or with 5TE4 8 pushbuttons, 5TE5 8 light indicators or width of 0.5 MW. They come with an integrated wiring duct for
5TT4 1 remote control switches and 5TT4 2 switching relays. the insertion of conductors.
This saves time and space • Two oppositely installed spacers thus offer space for large
• For busbars, see page 8/22. conductor cross-sections up to a 15 mm diameter. This simpli-
fies cable routing in the distribution board.
• The handle locking device is a universal accessory for all
switches and miniature circuit breakers. This simplifies
logistics.
Switching Devices
ON/OFF switches
■ Technical specifications
5TE8 1 5TE8 2
Standards IEC/EN 60947-3; IEC/EN 60947-3
IEC/EN 60669-1
Approvals EN 60669-1
Rated operational current Ie Per conducting path A 20 32
Rated operational voltage Ue 1-pole V AC 230
Multipole V AC 400
Rated power dissipation Pv Per pole, max. VA 0.7
Conventional free-air thermal current Ith A 20 32
Rated breaking capacity At p.f. = 0.65 A 60 96
Rated making capacity At p.f. = 0.65 A 60 96
Rated short-circuit making capacity Icm
In conjunction with fuse of the same rated EN 60269 gL/gG kA 10
operational current
Rated impulse withstand voltage Uimp kV >5
Clearances Open contacts mm 2×>2
Between the poles mm >7
Creepage distances mm >7
Mechanical service life Switching 25000
Switching Devices
ON/OFF switches
8
Electrical service life Switching 10000 5000 1000
cycles
Minimum contact load V; mA 24; 300
Rated power 1-pole kW 5 6.5 10 13 16 16
Switching of resistive loads 2-pole kW 9 11 18 22 28 28
including moderate overload AC-21 3-/4-pole kW 15 15 30 39 48 48
Rated short-time withstand current Icw
Per conducting path at p.f. = 0.7 Up to 0.2 s A 760 950 1500 2700 3400 3400
Up to 0.5 s A 500 630 1000 1650 2100 2100
(The corresponding rated surge current can be Up to 1 s A 400 500 800 1350 1700 1700
established by multiplying by factor 1.5.) Up to 3 s A 280 350 560 800 1000 1000
Terminals ±screw (Pozidriv) 2
Max. tightening torque Nm 3.5
Conductor cross-sections Rigid mm2 1 ... 35 2.5 ... 50
Flexible, with end sleeve mm2 1 ... 35 2.5 ... 50
Permissible ambient temperature °C -5 ... +40
Resistance to climate
At 95 % relative humidity Acc. to DIN 50015 °C 45
Switching Devices
ON/OFF switches
8 63
80 50
}
B
5TE8 512
5TE8 612
1
1
1 unit
1 unit
027
027
0.215
0.237
100 B 5TE8 712 1 1 unit 027 0.240
125 B 5TE8 812 1 1 unit 027 0.229
Switching Devices
ON/OFF switches
Terminal covers
For all 5TE8 5 to 5TE8 8 switches, B 5ST3 800 1 10 units 027 0.002
in 1 MW per pole version,
for covering screw openings,
sealable
Spacers
8
Contour for modular devices with a mounting
depth of 70 mm;
can be snapped onto either side of the busbar,
so that two spacers allow for convenient cable
routing
0.5 } 5TG8 240 1 2 units 027 0.010
Phase connectors
For easier wiring in various wiring versions
and bus mountings or as a fixpoint terminal for conduc-
tors from 2.5 mm2 to 50 mm2
1P 125 230 50 1 B 5TE9 112 1 1 unit 027 0.114
N-conductor connectors
For easier wiring in various wiring versions
and bus mountings or as a fixpoint terminal for N conduc-
tors from 2.5 mm2 to 50 mm2 with blue color marking
1P 125 230 50 1 B 5TE9 113 1 1 unit 027 0.114
Switching Devices
DC isolators
■ Overview ■ Benefits
DIN VDE 0100-712 specifies the use of special switch discon- • Compact DIN rail device for applications up to 1000 V DC
nectors for isolating solar modules in photovoltaic systems. With • Separate switching position display for unambiguous indica-
a high rated voltage of 1000 V DC, the 5TE2 515-1 switch dis- tion of the switching state
connectors from Siemens go well above and beyond meeting
these requirements. • Compatible with all miniature circuit breaker accessories –
reduced stock-keeping
The optimally coordinated BETA Low-Voltage Circuit Protection • The effective touch protection when grasping the device con-
product range – which includes DC overvoltage protection and siderably exceeds the requirements of BGV A3.
universal current-sensitive SIQUENCE TYPE B RCCBs – en-
ables the quick and easy implementation of standard-conform • Manual snap-on fixing and release systems that require no
protection for photovoltaic systems. tools enable fast assembly and disassembly of switch discon-
nectors
• Clear and visible conductor connection that can be easily
checked in front of the busbar
■ Technical specifications
5TE2 515-1
Standards IEC/EN 60947-3, IEC/EN 60669-1
Rated operational current Ie A 63
8
Rated operational voltage Ue For 4 poles in series V DC 1000
Rated power dissipation Pv Per pole, max. W 4.4
Rated short-circuit strength Icw 1000 V DC, 4-pole A 760
Rated short-circuit making capacity Icm 1000 V DC, 4-pole A 500
Rated impulse withstand voltage Uimp kV >5
Mechanical service life Switching 10000
cycles
Electrical service life Switching 5000
cycles
Utilization category DC-21B
Minimum contact load V; mA 24; 300
Terminals ±screw (Pozidriv) PZ 2
Max. tightening torque Nm 2.5 ... 3
Conductor cross-sections Rigid mm2 0.75 ... 35
Flexible, with end sleeve mm2 0.75 ... 25
Permissible ambient temperature °C -25 ... +45
Resistance to climate
At 95 % relative humidity Acc. to DIN 50015 °C 45
Switching Devices
DC isolators
■ Configuration
For DC voltages up to 1000 V, the four poles need to be con- For this reason it is essential to comply with the polarity specifi-
nected in series. In contrast to normal flush-mounting switches, cations of the switches when connecting the conductor. Suitable
these devices are also fitted with arcing chambers and perma- precautions should be taken during plant configuration to
nent solenoids to aid the positive quenching of the electric arc in ensure there can be no polarity reversal in DC operation
direct currents. (e.g. photovoltaic plants).
- 1 + 3 - 5 + 7
- 1 + 3 - 5 + 7
+ 2 - 4 + 6 - 8
+ 2 - 4 + 6 - 8
WR
I201_14005
I201_14006
+ -
-
+
- + + -
PV WR
PV
Legend:
PV: Photovoltaic
WR: Inverter
8
Switching Devices
Busbar systems
■ Overview
Siemens has developed a rail-mounting concept which makes The arrangement of the terminals on the devices is adapted to
the linking of switching devices just as easy as that of miniature the bus mounting. With only two busbars, this saves consider-
circuit breakers. able mounting time.
■ Benefits
8 • Uniform bus mounting on many devices • All 5TE8 switches (20 A and 32 A) in 1 MW can be fed via the
• All 5TE8 switches (20 A and 32 A), 5TE4 8 pushbuttons, single or two-phase busbars. Thus 2 two-phase busbars
5TE5 8 light indicators and 5TT4 1 remote control switches support a 4-pole infeed. This is unique.
and 5TT4 2 switching relays can be bus-mounted. This makes
installation tasks considerably easier.
Switching Devices
Busbar systems
Switching Devices
■ Overview ■ Benefits
Remote control switches are used in residential and non-resi- • All the devices have the VDE mark. This increases operational
dential buildings, as well as the switchgear engineering sector. safety.
They trip in the event of current inrushes, i.e. pulses, and then • Remote control switches with central/group switching support
electromechanically save the switching position (i.e. without convenient and high feature applications
auxiliary power), even in the event of a power failure. In residen-
tial and non-residential buildings, used in conjunction with push- • High functional reliability due to electromechanical design
buttons, they facilitate installation of systems where, for exam- without fault-prone electronics
ple, a corridor light needs to be switched from more than one • The devices have no standby losses
location. Because they save the switching position without • All devices have a switching position indicator and are oper-
standby losses, they enable the energy-efficient control of ated manually. This enables simple on-site operation and fast
lighting. recognition of the switching state.
With special functions, such as central and group control, or • The remote control switches can be bus-mounted on
series and shutter/blind control sequences, even high feature 5TE9 100 and 5TE9 101 busbars; e.g.: bus mounting of the
control tasks can be implemented easily and energy-efficiently. N conductor and/or infeed.
All the devices have the VDE mark and can also be equipped • All the remote control switches can be fitted with an additional
with an additional auxiliary switch. All devices have a switching auxiliary switch. This increases application flexibility.
position indicator and are operated manually. The switching
noise is particularly quiet and meets the requirements of residen-
tial buildings.
8
Note:
Busbars to match the 5TT4 1 remote control switch can be found
on page 8/22.
Switching Devices
■ Technical specifications
Remote control switches Auxiliary switches
5TT4 101 5TT4 103 5TT4 12 5TT4 13 5TT4 900 5TT4 901
5TT4 102 5TT4 104 5TT4 15 5TT4 14
5TT4 105
5TT4 115
Standards IEC 60669-1, IEC 60669-2, IEC 60669-3,
EN 60669, EN 60669-2-2, EN 60669-2-2/A1
Approvals VDE 0632
Contact type 1 NO 3 NO 1 NO Series 1 CO 1 CO
2 NO 4 NO 2 NO Shutter/
1 NO 1 NC 3 NO blind
1 NO 1 NC
Manual operation Yes --
Switching position indication Yes --
Rated control voltage Uc V AC 8 ... 230 --
V DC 12 ... 110 --
Primary operating range × Uc 0.8 ... 1.1 --
Rated frequency fc (AC types) Hz 50 --
Rated impulse withstand voltage Uimp kV 4 1
Rated power dissipation Pv
• Magnet coil, only pulse
• Per contact at 16 A
W/VA
W
4.5/7
1.2
9/13 4.5/7 --
-- 8
Minimum contact load V AC; mA 10; 100 10; 100 5 AC/DC; 1
Rated operational current Ie at p.f. = 0.6 ... 1 A 16 5 0.1
Rated operational voltage Ue
• 1 NO V AC 250 -- 250 -- 250 30 AC/DC
• 2 NO V AC 400 -- 400 250 --
• 3 NO V AC -- 400 400 -- --
• 4 NO V AC -- 400 -- -- --
• 1 NO + 1 NC V AC 250 -- 250 -- --
Glow lamp load at 230 V mA 5 --
• With one 5TT4 920 compensator mA 25 --
• With two 5TT4 920 compensators mA 45 --
Incandescent lamp load W 2400 --
Different phases between magnet coil/contact Permissible --
Contact gap mm > 1.2 < 1.2
Safe separation
Creepage distances and clearances between magnet coil/contact mm >6
Pushbutton malfunction
Protected against continuous voltage, safe due to design Yes PTC Yes1) Yes --
Minimum pulse duration ms 50
Electrical service life In switch-
At Ie/Ue or specified lamp load ing cycles 50000
Terminals ±screw (Pozidriv) 1
Conductor cross-sections
• Rigid mm2 1.5 ... 6 0.5 ... 4
• Flexible, with end sleeve mm2 1 ... 6 0.75 ... 4
Resistance to climate
At 95 % relative humidity Acc. to DIN 50015 °C 35
Permissible ambient temperature °C -10 ... +40
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Mounting position Any
1)
For 2.5 MW 5TT4 123-0 devices with PTC.
Switching Devices
Switching Devices
Compensators
For increasing the glow lamp load by 20 mA
250 -- 1 } 5TT4 920 1 1 unit 027 0.073
8
■ More information
Mechanical storage Busbar mounting
Remote control switches are used to switch lighting by means of
several pushbuttons. This makes complex cross/two-way
switching unnecessary. With each pushbutton impulse, the re-
mote control switch changes its contact position from "OFF" to
"ON", etc. In the event of a power failure, the last switching posi-
tion is mechanically stored. Electromechanical remote control
switches have no standby loss.
Pushbutton malfunction
Pushbuttons can jam, which may expose remote control
switches to a continuous voltage. All remote control switches are
protected against this type of malfunction through their design or
through PTC.
Central switching functions
Versions with central ON/OFF function allow the central switch-
ing of all connected remote control switches. This type of central • All 5TT4 1 remote control switches can be bus-mounted with
switching can also be actuated using a time switch. All remote each other. This saves time and space.
control switches can be switched to the ON or OFF switching Note:
state, regardless of their current switching state. Busbars to match the 5TT4 1 remote control switch can be found
Contact sequences on page 8/22.
1 – 2 – 1+2 – 0 or 1 - 0 - 2 - 0 means:
0: No contact closed
1: Only contact 1 closed
2: Only contact 2 closed
1+2: Contact 1 and Contact 2 are closed
The contact positions are constantly changing with each push-
button impulse.
Note:
Synchronous switching of the contacts cannot be guaranteed
with parallel switching. Products with central/group switching
must be used for the mutual control of several remote control
switches.
Switching Devices
Switching relays
■ Overview ■ Benefits
Switching relays are used in residential, non-residential and in- • Fast and simple installation thanks to bus-mounting
dustrial buildings for the purpose of contact multiplication. They • Switching position indicator when checking the plant for
can be used with safe isolation between coil voltage and con- enhanced safety
tact. Switching relays for direct voltages in particular are seeing
increasing use. • Manual intervention possible at any time – easy fault locating
due to manual operation.
With the 5TE9 100 and 5TE9 101 busbar, the switching relays
can be mounted quickly and safely, e.g. by bus-mounting the
N-conductor and/or infeed – and this applies to the whole range
of switching relays.
Note:
Busbars to match the 5TT4 2 switching relay can be found on
page 8/22.
■ Technical specifications
5TT4 201-. 5TT4 202-. 5TT4 204-. 5TT4 205-. 5TT4 206-. 5TT4 207-. 5TT4 217-.
Standards EN 60947-5-1, EN 60669-2-2
Contact type 1 NO 2 NO 4 NO 1 NO + 1 NC 1 CO 2 CO 2 CO
Manual operation Yes
8 Rated control voltage Uc V AC
V DC
8 ... 230
--
--
12 ... 110
Primary operating range × Uc 0.8 ... 1.1
Rated frequency fc Hz 50
Rated impulse withstand voltage Uimp kV 4
Rated power dissipation Pv
• Magnet coil W/VA 2.4/3.0 2.4/3.0 4.8/6.0 2.4/3.0 2.4/3.0 2.4/3.0 1.7
• Per contact at 16 A W 1.0
Minimum contact load V AC; mA 10; 100
Rated operational current Ie
At p.f. = 0.6 ... 1 A 16
Rated operational voltage Ue 250 400 400 400 250 400 400
Different phases
Between magnet coil/contact Permissible
Contact gap mm > 1.2 < 1.2
Safe separation
Between creepage distances and clearances
magnet coil/contact mm >6
Electrical service life
At Ie/Ue or specified lamp load Switch- 50000
ing cycles
Terminals ±screw (Pozidriv) 1
Conductor cross-sections
• Rigid mm2 1.5 ... 6
2
• Flexible, with end sleeve mm 1 ... 6
Resistance to climate
At 95 % relative humidity Acc. to DIN 50015 °C 35
Permissible ambient temperature °C -10 ... +40
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Mounting position Any
Switching Devices
Switching relays
Spacers
In the case of higher ambient temperatures, we 0.5 } 5TG8 240 1 2 units 027 0.010
recommend placing a spacer after every second
switching relay for better heat dissipation.
■ More information
Busbar mounting
• All 5TT4 2 switching relays can be bus-mounted with each
other. This saves time and space.
Note:
Busbars to match the 5TT4 2 switching relay can be found on
page 8/22.
Switching Devices
Insta Contactors
Insta contactors, DC technology
■ Overview
Insta contactors are standard devices in installation technology In addition to their basic function, they can also be used for the
and belong to the BETA switching device range. Insta contac- ON/OFF switching of single-phase and three-phase electrical
tors are particularly suitable for switching heating, lighting and motors.
motors. The 5TT5 7 Insta contactors meet the requirements of EN 60947
While Insta contactors have seen a considerable decline in use and are approved to UL 508.
in the electrical heating sector in residential buildings, they have
gained considerable significance for lighting circuits in build-
ings. Insta contactors are increasingly used in industry for
motors where distribution technology plays a major role, e.g. in
auxiliary installations for heat pumps and air conditioning tech-
nology.
■ Benefits
• Safe cable routing through the cable entry funnel - saves time • Switching position indicator for fast recognition of operating
during installation. state offers greater safety when checking the plant.
• The insulation goes right through into the cable entry funnel -
thus ensuring maximum touch protection.
Switching Devices
Insta Contactors
Insta contactors, DC technology
■ Technical specifications
5TT5 73 5TT5 74 5TT5 75
4-pole 4-pole 4-pole
Standards EN 60947-4-1; EN 60947-5-1; EN 61095; UL 508
Approvals UL 508; UL File No. E303328
Rated frequency at AC fn Hz 40 ... 450
Rated control voltage Uc V AC 24, 115, 230 24, 230
V DC 24, 110, 220 24, 220
Primary operating range × Uc 0.85 ... 1.1
Rated operational voltage Ue V 440
Rated operational current Ie At V AC Acc. to UL 480; acc. to IEC 440
• AC-1/AC-7a, NO contacts A 24 40 63
• AC-1/AC-7a, NC contacts A 24 30 30
• AC-3/AC-7b, NO contacts A 9 22 30
• AC-3/AC-7b, NC contacts A 6 -- --
Rated power dissipation Pv
• Pick-up power VA/W 4/4 5/5 6.5/6.5
• Holding power VA/W 4/4 5/5 4.2/4.2
• Per contact AC-1/AC-7a VA 1.5 3 6
Switching times
• Closing (NO contacts) ms ≤ 40
• Opening (NO contacts) ms ≤ 40
Rated impulse withstand voltage Uimp
Contact gap (S contacts) min.
kV
mm
≥4
2.4 2.8 2.6
8
Electrical service life
At Ie and load AC-1/AC-7a For switching 150000
cycles
AC-3/AC-7b For switching 500000 170000 240000
cycles
Mechanical service life For switching 1 million
cycles
Maximum switching frequency
At load AC-1/AC-7a Switching 300
cycles/h
AC-3/AC-7b Switching 600
cycles/h
Switching of resistive loads AC-1 V AC 230
For rated operational power Ps (NO contacts)
• Single-phase kW 5.3 8.8 13.8
• Three-phase kW 16 26 41
Switching of three-phase asynchronous motors AC-3 V AC 400
for rated operational power Ps (NO contacts)
• Single-phase kW --
• Three-phase kW 4 11 15
Minimum switching capacity V; mA ≥ 17; ≥ 200
Overload withstand capability
Per conducting path (NO contacts only) At 10 s A 72 176 240
Short-circuit protection, according to coordination type 1
Back-up fuse characteristic gL/gG A 35 63 80
Terminals ±screw (Pozidriv)
• Coil connection 1 1 1
• Main connection 1 2 2
Tightening torques
• Coil connection Nm 0.9 0.9 0.9
• Main connection Nm 1.0 2.5 2.5
Conductor cross-sections
• Coil connection
- Solid mm2 1.5 ... 4
- Stranded, with end sleeve mm2 1.5 ... 2.5
- AWG cables AWG 16 ... 10
Tightening torques lb. in 8
• Main connection
- Solid mm2 1.5 ... 10 2.5 ... 25
- Stranded, with end sleeve mm2 1.5 ... 2.5 2.5 ... 16
- AWG cables AWG 16 ... 8 16 ... 4
Tightening torques lb. in 9 20
Permissible ambient temperature
• For operation °C -25 ... +55
• For storage °C -50 ... +80
Degree of protection Acc. to EN 60529 IP20, with connected conductors
According to UL 508 In A 24 40 63
UL 508 General Use 240 V/480 V FLA A 24 40 63
UL 508 AC discharge lamps A 24 30 40
UL 508 motor load 240 V Power hp 3 7.5 10
UL 508 motor load 480 V Power hp 5 15 15
UL 508 Short-circuit at 480 V K5 fuses A 25 40 75
kA 5
Switching Devices
Insta Contactors
Insta contactors, DC technology
Spacers
For heat dissipation between the Insta contactors. 0.5 } 5TG8 240 1 2 units 027 0.010
We recommend placing a spacer after every
second Insta contactor.
Can be mounted reciprocally, so that two spacers
enable greater cable routing.
Switching Devices
Insta Contactors
Insta contactors, AC technology
■ Overview
Insta contactors without manual switch
The 5TT5 8 Insta contactors are equipped with an AC magnetic
system and are ideal for use under harsh conditions. The auxil- Insta contactors are playing an ever growing role in lighting cir-
iary switches can be mounted without tools. When equipped cuits in buildings Insta contactors are increasingly used in indus-
with terminal covers, the devices can also be sealed. try for motors where distribution technology plays a major role,
e.g. in installations for heat pumps and air conditioning technol-
ogy. In addition to their basic function, they can also be used for
the ON/OFF switching of single-phase and three-phase electri-
cal motors.
Insta contactors with manual switch
A key feature of Insta contactors with manual operation is the
fact that users can switch consumers/loads on and off by hand.
■ Benefits
• Extremely long service life of 3 million switching cycles is a • Insta contactors with O/I/Automatic function enable the testing
testimony to their reliability of a plant by manual switch without the need to apply a control
voltage
• Safe cable entry through cable entry funnel - saves time
during assembly • Switching position indicator for fast recognition of operating
state offers greater safety when checking the plant.
• Insulated right through to the cable entry funnel. This provides
enhanced touch protection
• Auxiliary switches can be retrofitted on all versions – even on
the 20 A type. More functionality when using the devices.
Switching Devices
Insta Contactors
Insta contactors, AC technology
■ Technical specifications
Insta contactors Auxiliary
switches
5TT5 80. 5TT5 82., 5TT5 84. 5TT5 85. 5TT5 910
5TT5 83.
Standards IEC 60947-4-1, IEC 60947-5-1, IEC 61095;
EN 60947-4-1, EN 60947-5-1, EN 61095
Approvals EN 61095
Number of poles 2 4 4 4 2
Rated frequency at AC Hz 50/60
Rated control voltage Uc V AC 24, 230 24, 115, 230 24, 230 24, 230 --
Primary operating range × Uc 0.85 ... 1.1 --
Rated operational voltage Ue V AC 230 400 230/400
Rated operational current Ie A 20 25 40 63 6/4 (230/400 V)
Rated power dissipation Pv
• Pick-up power (without manual switch VA/W 6/3.8 10/5 15.4/6 --
or manual switch in "I" position)
• Pick-up power (with manual switch in "AUTO" position) VA/W 12/10 33/25 62/50 --
• Holding power VA/W 2.8/1.2 5.5/1.6 7.7/3 --
• Per contact VA 1.7 2.2 4 8 --
Switching times
8
• Closing (NO contacts) ms 15 ... 25 10 ... 20 15 ... 20 --
• Opening (NO contacts) ms 20 20 10 --
• Closing (NC contacts) ms 20 ... 30 20 ... 30 5 ... 10 --
• Opening (NC contacts) ms 10 10 10 ... 15 --
Rated impulse withstand voltage Uimp kV 4
Rated insulation voltage Ui V 440 500
Contact gap, minimum mm 3.6 3.4 4
Electrical service life
At Ie and load
• AC-1/AC-7a For switching 200000 100000 --
• AC-3/AC-7b cycles 300000 500000 150000 --
Mechanical service life For switching 3 million
cycles
Maximum switching frequency
At load In switching 600
cycles/h
Switching of resistive loads AC-1/AC-7a
For rated operational power Ps
• Single-phase 230 V kW 4 5.4 8.7 13.3 --
• Three-phase 400 V kW -- 16 26 40 --
Switching of three-phase asynchronous motors AC-3/AC-7b
For rated operational power Ps
• Single-phase 230 V kW 1.31) 1.3 3.7 5 --
• Three-phase 400 V kW -- 4 11 15 --
Minimum switching capacity V; mA 17; 50 12; 5
Overload withstand capability
Per conducting path At 10 s A 72 68 176 240 --
(NO contacts only)
Short-circuit protection, according to coordination type 1
Back-up fuse characteristic gL/gG A 20 25 63 80 6
Terminals ±screw (Pozidriv)
• Coil connection 1 1.2 --
• Main connection 1 3.5 1
Tightening torques
• Coil connection Nm 0.6 --
• Main connection Nm 1.2 2 0.8
Conductor cross-sections
• Coil connection Rigid mm2 1.0 ... 2.5 --
Flexible, mm2 1.0 ... 2.5 --
with end sleeve
• Main connection Rigid mm2 1.0 ... 10 1 ... 25 1 ... 2.5
Flexible, mm2 1.0 ... 6 1 ... 16 1 ... 2.5
with end sleeve
Permissible ambient temperature
• For operation °C -5 ... +55
• For storage °C -30 ... +80
Degree of protection Acc. to EN 60529 IP20, with connected conductors
1)
For NO contacts only.
Switching Devices
Insta Contactors
Insta contactors, AC technology
5TT5 910-0
Sealable terminal covers
For Insta contactor 20 A 1 B 5TT5 910-5 1 2 units 027 0.002
For Insta contactor 25 A 2 B 5TT5 910-6 1 2 units 027 0.003
For Insta contactors 40 A and 63 A 3 B 5TT5 910-7 1 2 units 027 0.003
Switching Devices
Insta Contactors
Insta contactors, AC technology
8 5TT5 830-6
4 NO 400 40 230 3 } 5TT5 840-6 1 1 unit 027 0.399
24 B 5TT5 840-8 1 1 unit 027 0.402
3 NO + 1 NC 400 40 230 B 5TT5 841-6 1 1 unit 027 0.399
24 B 5TT5 841-8 1 1 unit 027 0.406
4 NO 400 63 230 } 5TT5 850-6 1 1 unit 027 0.394
5TT5 840-6
Auxiliary switches
For mounting on right-hand side
Max. one auxiliary switch per Insta contactor.
2 NO 230, AC-15 6 -- 0.5 } 5TT5 910-0 1 1 unit 027 0.045
1 NO + 1 NC 230, AC-15 6 -- } 5TT5 910-1 1 1 unit 027 0.046
Switching Devices
Soft-starting devices
■ Overview
The soft-starting device must not be operated with capacitive
The soft-starting device is an electronic control for the soft load. In order to ensure the safety of persons and systems, only
startup of one-phase asynchronous machines. A phase control suitably qualified personnel should work on these devices.
causes the current to rise steadily. This also increases the motor To prevent losses in the device, the power electronics are
torque and the drive starts up smoothly. Because drive elements bridged with relay contacts after startup. Can be retrofitted in
are handled more gently they can be designed more cost-effec- existing plants at any time.
tively. As well as a considerable reduction in startup noise, this
also helps prevent the tipping or sliding of materials to be trans-
ported. The starting current is minimized. There is no speed ■ Benefits
adjustment. There is no marked soft start behavior without a • On completion of startup, the power semiconductors are
mechanically connected load. bridged, which prevents overheating in the case of frequent
If the power semiconductor is to be protected against short cir- starting and inhibits premature wear and tear
cuits or ground faults during startup, a super-quick fuse must be
installed. Otherwise, the usual line and motor protective mea- • Separate setting of ramp up time and starting torque enables
sures must be used. In the case of high switching frequencies, optimum adaptation to the mechanics
we recommend installing a thermistor motor protection for • The LEDs for startup and continuous operation provide
monitoring the permissible motor temperature. constant information on the operating state.
■ Technical specifications
5TT3 440 5TT3 441
8
Standards EN 60947-4-2
Supply/motor voltage V AC 400 230
Primary operating range × Uc 0.8 ... 1.1
Rated power VA 3.5 1.4
Rated frequency Hz 50/60
Rated power dissipation Pv Coil/drive 3.5 1.7
Contact1) per pole 4.6 0.7
Rated output of motor
- Max. At 400 V VA 5500 1500
- Min. At 400 V VA 300 100
Startup voltage % 30 ... 70 20 ... 70
Starting ramp s 0.1 ... 10
Recovery time ms 100 200
Switching frequency
3 × IN, TAN = 10 s, νu = 20 % Switching 36 (up to 3kW) 10
cycles/h
3 × IN, TAN = 10 s, νu = 20 % Switching 20 (from 3...5.5 kW) 10
cycles/h
Semiconductor fuse Super quick A 35 20
Conductor cross-sections Rigid max. mm2 2 × 2.5
Flexible, with end sleeve min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60 -20 ... +55
Resistance to climate Acc. to EN 60068-1 20/60/4 20/55/4
1) For rated operational current.
Switching Devices
Timers
Digital time switches
■ Overview ■ Benefits
These days, time switching is taken for granted. • The menu-assisted operation with background lighting, con-
trast setting of the display and illuminated keys offer a clear
In fact, it is now hard to imagine many process sequences and overview for any application
energy saving processes without time switching. It could also be
argued that time switching satisfies a basic need in the electrical • The text-assisted programming of the time switches with their
installation sector. logical 4 pushbutton system and extremely intuitive menu-
driven handling saves time
The new generation of digital time switches have a much more
• Simple programming on the PC enables the fast creation of
diverse range of functions than earlier devices and, thanks to
complicated switching programs, thus saving time and
better solutions, are simpler to operate.
eliminating errors
They can be used for switching systems or system components, • Data keys enable the transfer of programs to the switch key,
or for functions, such as: irrigation systems, greenhouses, public thus saving huge amounts of time during commissioning and
gardens, swimming pools, filtering installations, canopy con- maintenance
trols, school bells, church bells, shop window lighting, advertis-
ing lighting, gym lighting, traffic signal controls, street lighting, • Intuitive operation of 5-way joystick
illuminated signs, office lighting, lighting of stairwells and • Energy saving option via astro function.
entrances, object illumination, preheating of industrial furnaces,
spraying machines, ovens, heating systems, air-conditioning
systems, fans and ventilation systems, heating and circulation
pumps and sauna systems.
All devices have the VDE mark and are UL approved
8 (not 7LF4 444).
Switching Devices
Timers
Digital time switches
■ Technical specifications
Mini Top Profi Astro Expert
7LF4 401-5 7LF4 411 7LF4 421 7LF4 431 7LF4 444
7LF4 412 7LF4 422 7LF4 432
Standards EN 60730-1, -2-7; UL 60730 EN 60730-1, -2-7
Approvals VDE, UL 60730-1,-2-7/UL 917 CSA C22.2 No. 14 and 177 VDE
Supply
• Rated control supply voltage Uc V AC 110 ... 240 120, 230 120, 230 230 120/230
V AC/DC -- -- 24 -- 24
- Primary operating range × Uc 0.85 ... 1.1 0.85 ... 1.1 0.85 ... 1.11) 0.85 ... 1.1 80 .. 253 V1)
- Frequency ranges Hz 50 ... 60 50 ... 60 50 ... 602) 50 ... 60 50 ... 602)
• Rated power dissipation Pv VA 0.035 2 2 2 2.5/43)
Channels/contacts
• Switching channels 1 1 or 2 4
- Rated operational voltage Ue V AC 250
- Rated operational current Ie At p.f. = 1 A 16
At p.f. = 0.6 A 10
• Contacts 1 CO 1 or 2 CO 4 CO
- Mechanical switching cycles (in millions) >5 10
- Electrical switching cycles At p.f. = 1 6000 (20 A) 100000
• Minimum contact load V; mA 12; 100
8
- Incandescent lamp load A 5 8
- Fluorescent lamp load At 7 μF VA 58 60
Uncorrected VA 1400
- Energy-saving lamp load W 100
Safety
• Different phases permissible between actuator/contact Yes
• Rated impulse withstand voltage Uimp kV 4
- EMC: burst Acc. to IEC 61000-4-4 kV > 4.4
- EMC: surge Acc. to IEC 61000-4-5 kV > 2.0
- Electrostatic discharge Acc. to IEC 61000-4-2 kV > 8.0
• Power reserve storage Mains/battery a 6/2 6 5
- Battery type Li primary cell
• Program memory Captive -- Yes
• Overvoltage category Acc. to EN 61010-1 III
Function
• Minimum switching sequences 1 min 1s
• Make and break cycles 1 min 1s
• Clock errors per day Typical s/day +0.3 ± 14) ± 0.86 ± 0.2
• Control input Terminal S -- Yes
• Memory spaces
- Programs5) 28 56 (2 × 28) 28 (2 × 14) 4 × 3 × 28
- Pulse (alternatively) -- 84 --
- Pulse cycle -- 1 s ... < 60 min --
Connections
• Terminals ±screw (Pozidriv) PZ 1
• Conductor cross-sections of main current paths
- Rigid, max. mm2 4
- Rigid, min. mm2 1.5
- Flexible with end sleeve Max. mm2 2.5
Environmental conditions
• Permissible ambient temperature °C -10 ... +55 -20 ... +55
• Storage temperature °C -20 ... +60
• Resistance to climate Acc. to EN 60068-1 10/055/21 20/055/21
• Degree of protection Acc. to EN 60529 IP20, with connected conductors
• Safety class Acc. to EN 60730-1 II
1)
For 24 V devices (7LF4 421-2, 7LF4 422-2 and 7LF4 444-2):
Tolerance -10/+10 %; operating range 0.9 ... 1.1 × Uc.
2)
For 24 V devices (7LF4 421-2, 7LF4 422-2 and 7LF4 444-2):
Frequency range 0 ... 60 Hz.
3)
For 24 V device (7LF4 444-2): Pv = 4 VA.
4)
At 25°C a clock error of +0.3s is assumed. Accuracy may deviate by a
further ±1s around this value.
5)
A program consists of an ON time, an OFF time and assigned ON and OFF
days or day blocks.
Switching Devices
Timers
Digital time switches
8 • 56 programs
1 CO 250 16 230 2 } 7LF4 411-0 1 1 unit 027 0.157
1 CO 250 16 120 2 B 7LF4 411-1 1 1 unit 027 0.159
• 2 channels
• 56 programs (28 per channel)
2 CO 250 16 230 2 A 7LF4 412-0 1 1 unit 027 0.182
2 CO 250 16 120 2 B 7LF4 412-1 1 1 unit 027 0.181
Profi digital time switches
• Weekly program
• With text-assisted programming concept languages:
German, English, French, Italian, Dutch, Spanish
• Simple program creation by means of PC using the
software included with the 7LF4 940-0 USB adapter
• Vacation program
• Random program
• Operating hours meter, counting range: 65535 h
• 1 channel
• 56 programs
• Pulse function, 84 start times
1 CO 250 16 230 2 A 7LF4 421-0 1 1 unit 027 0.195
1 CO 250 16 120 2 B 7LF4 421-1 1 1 unit 027 0.192
1 CO 250 16 24 AC/DC 2 A 7LF4 421-2 1 1 unit 027 0.189
• 2 channels
• 56 programs (28 per channel)
2 CO 250 16 230 2 A 7LF4 422-0 1 1 unit 027 0.210
2 CO 250 16 120 2 B 7LF4 422-1 1 1 unit 027 0.209
2 CO 250 16 24 AC/DC 2 B 7LF4 422-2 1 1 unit 027 0.207
Astro digital time switches
• Weekly program
• Astro function
• With text-assisted programming concept languages:
German, English, French, Italian, Dutch, Spanish
• Simple program creation by means of PC using the
software included with the 7LF4 940-0 USB adapter
• Vacation program
• 1 h test
• Input disable over PIN code
• Operating hours meter, counting range: 65535 h
• 1 channel
• 28 programs
• With control input,
delay time 0 min ... 23 h 59 min
1 CO 250 16 230 2 } 7LF4 431-0 1 1 unit 027 0.206
• 2 channels
• 28 programs (14 per channel)
2 CO 250 16 230 2 } 7LF4 432-0 1 1 unit 027 0.221
Switching Devices
Timers
Digital time switches
Switching Devices
Timers
Digital time switches
■ More information
Mini digital time switches
Easy commissioning:
You can get started with the programming straight away. Profi,
Astro and Expert are supplied with the time, date and automatic
daylight savings for Central Europe already set.
Clear contrast:
In order to maintain an overview even in bad light conditions and
extreme temperatures, the contrast of the display can be
adjusted - practical down to the very last detail.
Convenient programming:
It has never been so easy and uncomplicated to operate and
program a digital time switch.
1-channel time switches allow input of up to 56 switching pro-
grams, 2-channel time switches allow up to 28 programs per
channel and 4-channel time switches up to 84 programs per
channel. This means that the Profi, Astro and Expert time
switches are ideally equipped for even the most complex of
8 The Mini digital time switch with a width of only 1 MW and its tasks.
hourly, daily and weekly program is ideal for replacement and Each entry required is clearly indicated so no prolonged study-
use in distribution boards with limited space. ing of the operating instructions. And, particularly practical: you
The Mini digital time switch can be used flexibly as it can also be don't even need a power supply to program the digital time
operated in battery mode with all its functionalities. Furthermore, switches.
the actuator of the clock can be removed from its enclosure for The Profi, Astro and Expert digital time switches offer more than
easy programming over the 5-way joystick prior to mounting. reliable switching. Numerous integrated convenience functions
make them versatile and simple problem solvers.
Top, Profi, Astro and Expert digital time switches
A data key enables easy programming of the Profi, Astro and
Whether you are programming locally using the text-assisted
Expert digital time switches at a PC, simplifies the setting of time
programming, or sitting comfortably in front of your PC, the task
switch programs and saves enormous amounts of time. This pre-
is quicker and easier with the Top, Profi, Astro and Expert digital
vents human error and enables simple copying of complete time
time switches.
switch programs to different time switches.
Astro function:
The Astro and Expert time switches have one key strength: the
Astro function. The exact time of sunrise and sunset is available
for every location and every day in the year. This means, for
example, that the connected outer lighting is only switched on
when it is dark - whether it is winter when the days are shorter or
in summer when the days are much longer. The benefits are
obvious:
• Cost-savings, because electricity is only used when the light-
ing is really needed, and because this prolongs the service life
of the lighting itself. Particularly in the case of dusk-dependent
lighting controls.
• Safety and convenience, because the light is always switched
on when it's dark
• Ease-of-use, because the digital time switch doesn't have to
be reprogrammed throughout the year
• Installation couldn't be easier, because Astro digital time
Simple operation: switches work in the distribution board. No further need for
Four programming pushbuttons offer user-friendly assistance laborious cable laying to the light sensors. This means that it
with a text menu. is not necessary to lay cables across the lightning protection
zones. The compact 2-MW series is also ideally suited for ret-
Easy-to-read display: rofitting or replacement.
And if you need to change the settings of the digital time switch It goes without saying that the digital time switches Astro and
at the back of a dark control cabinet, the integral background Expert don't just switch at dawn and dusk, complex, combined
lighting of the display and the lighting of the control elements programs are also possible. You always have the choice be-
offer a clear overview. tween astronomically calculated and individually set switching
times, or a combination of both.
Switching Devices
Timers
Digital time switches
PC programming: Control input:
The delay time that can be adjusted in the control input enables
an additional switching of the relay, parallel to the switching pro-
gram. Settable overtravel 0 min to 23 h 59 min, the delay time
starts as soon as the voltage drops out at the control input.
1 h test:
The "1H TEST" function can be used for simulating switching. If
"1H TEST" is activated, the switching outputs are switched for
one hour. At the end of the specified time, the digital time switch
automatically resumes execution of the switching commands
according to the programmed switching times.
PIN code:
Input and programming can be disabled using a four-digit PIN
code.
Week programs:
Programs that are designed to be repeated regularly every
week, e.g. light control, heating control. A weekly program
The Profi, Astro and Expert digital time switches support plug-in comprises an ON/OFF time and assigned ON/OFF days.
data keys. This provides even greater safety and convenience.
Year programs:
For example, the data key lets you read out a program from a
digital time switch, copy it to a PC, where it can be saved and Programs that are only to be executed within a defined period of 8
edited - or simply transfer it to another time switch. You can also validity. They overlap with the week programs of the same chan-
work with several data keys and it takes only a matter of seconds nel according to an OR operation. The period of validity is spec-
to change programs. ified by entering the start/end date. Validity from start date
00:00:00 to end date 24:00:00. The start date must be prior to
A safety copy ensures fast service. So if a time switch has been the end date. Within their period of validity, these programs act
interfered with, you can simply use the data key to transfer the as weekly programs. Outside their period of validity, these
stored program back to the time switch. programs have no influence on the switching behavior.
Thanks to the standard operator interface, based on MS-Office, Exception programs:
there is no need for laborious program training.
have a higher priority than week and year programs. Week and
Pulse function for 1-channel devices: year programs of the same channel will not be executed within
With the pulse function, up to 84 start times and a pulse time can the period of validity of an exception program. However, within
be programmed onto the time switch. The pulse duration can be the period of validity other exception programs will be executed.
selected between 1 s and 59 min 59 s. The different exception programs overlap according to an OR
operation.
Random function:
Cycle function:
If the random function is activated, the set switching times are
shifted within a range of +/- 30 min. On the year time switch, channel 1 has an additional option for
"cyclic switching". The term "cyclic switching" means that within
Operating hours meter: a specific period, the time switch is switched on for a specific
For commercial fields of application in particular, it is often nec- duration (ON time). The cycle time can be set between 2 sec-
essary to establish the running time of the switched load, e.g. onds and 2 hours. The ON time can be set between one second
lighting. The operating hours meter shows the total ON time per and one hour.
channel and the date of the last reset.
Vacation period function:
In the vacation program, the vacation period is set with start and
end date. If the vacation program is activated, the digital time
switch does not carry out any programmed switching com-
mands during the relative period but, depending on the respec-
tive input, is set to "CONTINUOUSLY OFF" or "CONTINUOUSLY
ON" during the vacation period. At the end of the specified
vacation period, the digital time switch automatically resumes
execution of the switching commands according to the
programmed switching times.
Switching Devices
Timers
Digital time switches
USB adapters
The Profi, Astro and Expert time switches are easy to program at
the PC using the data key with the USB adapter and software.
This enables the simple and fast creation of complicated time
switch programs. Storing and copying time switch programs is
also very easy and convenient.
Switching Devices
Timers
Mechanical time switches
■ Overview ■ Benefits
These days, time switching is taken for granted. • The automatic setting system automatically sets the clock tim-
ers during commissioning. No need to manually adjust the
These days, energy savings through time switching have be- pointer for daylight savings.
come a matter of course. In fact, it is now hard to imagine many
process sequences without time switching. • The automatic make ready system also continues to operate
automatically after a voltage failure. No need for manual time
Mechanical time switches are used wherever the minimum reset.
switching interval is sufficient. The switching control pins can be
• The precision quartz clock mechanism adds all clock errors to
set without the use of tools at minimum intervals of 15 minutes.
approx. +/- 1 min clock accuracy per year. So there is also no
They can be used for switching systems or system components,
need to reset the clock timer during operation.
or for functions, such as: irrigation systems, greenhouses, public
gardens, swimming pools, filtering installations, canopy con-
trols, church bells, shop window lighting, advertising lighting,
gym lighting, traffic signal controls, street lighting, illuminated
signs, office lighting, lighting of stairwells and entrances, object
illumination, preheating of industrial furnaces, spraying ma-
chines, ovens, heating systems, air-conditioning systems, fans
and ventilation systems, heating and circulation pumps and
sauna systems.
All devices have the VDE mark and are approved to UL.
Switching Devices
Timers
Mechanical time switches
■ Technical specifications
Synchronous time switches without power Quartz-clock time switches with power reserve
reserve
7LF5 7LF5 7LF5 7LF5 7LF5 7LF5 7LF5 7LF5 7LF5 7LF5 7LF5
300-1 300-5 300-6 300-7 301-0 301-1 301-4 301-5 301-6 301-7 305-0
Standards EN 60730-1, -2-7, UL 917
Approvals UL 60730-1,-2-7/UL 917 CSA C22.2 No. 14 and 177
Operating mode Synchronous Quartz
• Time program Day Day Week Hour Day Day Day Week Day Week Day
Supply
• Rated control supply voltage Uc V AC 230 230
- Primary operating range × Uc 0.85 ... 1.1 0.85 ... 1.1
• Rated frequency Hz 50 50
- Frequency ranges Hz 50 50/60
• Rated power dissipation Pv VA 1 1 0.2 0.2 1 1 1
Channels/contacts
• Switching channels 1 1
- Rated operational voltage Ue V AC 250 250
- Rated operational current Ie
At p.f. = 1 A 16 16
At p.f. = 0.6 A 4 4
8 • Contacts
- Mechanical switching cycles in millions
1 NO
20
1 CO 1 CO 1 NO 1 CO 1 NO
20
1 CO 1 CO 1 CO 1 CO 1 CO
Switching Devices
Timers
Mechanical time switches
8
1 CO 250 16 230 3 A 7LF5 300-6 1 1 unit 027 0.153
Switching Devices
Timers
Mechanical time switches
■ More information
Mechanical time switches with day disk Mechanical time switches with week disk
Synchronous time switches without power reserve LED display
The control gear is driven by a synchronous motor so it is depen- The adjustment data for Central Europe are stored and an LED
dent on the power supply frequency. If this frequency is unsta- provides information on the current state.
ble, the devices cannot be used. In the event of a power failure,
the time switch will stop. So: simply unpack, snap into place, connect and set the desired
switching times - no tools required! This saves time and money.
Quartz-clock time switches with power reserve
Clear design
A quartz electronic circuit supplies the drive with a stabilized fre-
quency so that the time switch is not dependent on the power Extremely intuitive – thanks to clear design. The switching times
supply frequency. In the event of a power failure, the time switch are easy to read.
continues to operate on its power reserve. With the weekly time switch, the make and break cycles are only
120 minutes with a minimum switching interval of 240 minutes.
Automatic setting system
This supports fast and easy installation of the 7LF5 301-4 and
7LF5 301-5 time switches. These time switches self-adjust dur-
ing commissioning in fast mode to the correct time and correct
day within the Central European zone. They also automatically
set the correct time for daylight saving. A further advantage is
the quartz-precise adjustment of the correct time and the correct
day as soon as the supply voltage is reconnected after a power
failure.
Precision quartz mechanism
Clock accuracy: The internal precision clockwork has an accu-
racy of ± 1 min. per year. Until now, this level of accuracy and au-
tomatic operational safety was only possible using digital time
switches.
Optimization of power consumption due to minimum make and
break cycles of 15 minutes: it is possible to set the switching
times in 15-minute patterns, with a switching interval of at least
30 minutes.
Switching Devices
Timers
Timers for buildings
■ Overview ■ Benefits
In many installations there is great savings potential to be found • Energy savings through disconnection of unnecessary equip-
in the lighting of corridors, stairwells and ancillary rooms. Many ment
installations are in operation for hours without anyone being • Reliable durable switching of different illuminants using pat-
present. Lighting which is switched on unnecessarily in ancillary ented contact design
rooms often goes unnoticed for days.
• Suitable for energy-saving lamps
Due to the gradual phasing out of incandescent lamps starting • Ultra-quiet stairwell lighting timers - ideal for residential areas
in September 2009, it is crucial we switch to other types of light-
ing. In particular compact fluorescent lamps (energy-saving • Warning of impending switch-off according to DIN 18015-2 for
lamps such as the Osram Dulux EL) will be used more frequently stairwell lighting in apartment houses.
in stairwells as in other areas.
Our stairwell lighting timers offer different levels of convenience,
depending on the range of functions. On stairwell lighting timers
from Siemens, the required time can be precisely set without
tools using the push-to-lock knurling wheel. With modern four-
wire installations, stairwell lighting timers can always just be
pressed again. A maintained light switch prevents the need for
repeated pressing, for example when moving house. The vari-
ous types are available either with or without warning prior to
switch-off.
■ Technical specifications 8
7LF6 110 7LF6 111 7LF6 113 5TT1 303 7LF6 114 7LF6 115 7LF6 116 7LF6 112
Standards IEC 60669, EN 60669
Supply
• Rated control supply voltage Uc V AC 230
- Primary operating range At 50/60 Hz × Uc 0.9 ... 1.1
• Rated power dissipation Pv VA Approx. 5
Setting range min 0.5 ... 10 1 ... 10 0.5 ... 10 3 ... 60 0.5 ... 10
• Accuracy s ±30
Manual switches Automatic/permanent Yes
Minimum push duration ms 30
Voltage endurance At pushbutton input Yes
(pushbutton malfunc-
tion)
Short-circuit strength A 700 -- 700
Channels/contacts
• Switching channels
- Rated operational voltage Ue V AC 250
- Rated operational current Ie At p.f. = 1 A 16 -- 10 16
• Contact gap mm >3 0.3 >3
• Minimum contact load V; mA 10; 300
Max. incandescent lamp load W 2000 -- 2000 --
Max. energy-saving lamp load 14 W Unit(s) 20 -- 20 --
Fluorescent lamp load 58 W
- Uncorrected Unit(s) 20 -- 20
- DUO circuit Unit(s) 2 × 20 -- 2 × 20
- Siemens ECG 1 lamp Unit(s) 10 6 10
2 lamps Unit(s) 2×5 3 2×5
Glow lamp load mA 50 10 50 --
Max. fan load VA -- 200
Connections
• Terminals ±screw (Pozidriv) PZ 1
• Conductor cross-sections of main current paths
- Rigid mm2 1.5 ... 6
- Flexible, with end sleeve Min. mm2 1
Environmental conditions
• Resistance to climate Acc. to EN 60068-1 °C -20 ... +50
• Degree of protection Acc. to EN 60529 IP20, with connected conductors
Switching Devices
Timers
Timers for buildings
8 Lighting timers
With switch for continuous light and push-to-lock knurl-
ing wheel setting,
with warning by flashing prior to switch-off, setting range
0.5 ... 10 minutes,
4-fold extension of runtime by pressing the pushbutton
for 1 second,
for 4-wire circuit, L-momentary contact,
or 3-wire circuit, N-momentary contact
250 16 230 1 B 7LF6 114 1 1 unit 027 0.088
Energy-saving timers
With switches for continuous light and push-to-lock
knurling wheel setting,
setting range 3 ... 60 minutes,
switch off by pressing pushbutton a second time briefly
(< 1 s) as with remote control switch, reset by pressing
pushbutton a second time for longer (> 1 s),
for 4-wire circuit, L-momentary contact, resettable,
or 3-wire circuit, N-momentary contact, resettable
250 16 230 1 A 7LF6 116 1 1 unit 027 0.071
Switching Devices
Timers
Timers for industrial applications
■ Overview ■ Benefits
Time relays are primarily used in series applications where the • Suitable for universal use because the devices can be oper-
use of PLC controls is too labor and cost-intensive. Multifunction ated with 12 - 240 V AC/DC and work across a broad range
relays are now the market standard. Operation is clear, simple from seconds to hours
and offers a range of functions. • An off-delay without auxiliary power supports expanded
application.
■ Technical specifications
5TT3 185 5TT3 181 5TT3 184
5TT3 182
5TT3 183
Standards EN 60255; EN 61810
Supply
• Rated control supply voltage Uc V AC 12 ... 240 220 ... 240 110 ... 240
V DC 12 ... 240 -- 110 ... 240
- Primary operating range × Uc 0.8 ... 1.1
• Rated frequency fn Hz 45 ... 400 50/60
• Rated power dissipation Pv VA Approx. 1.5 Approx. 5 Approx. 1
Setting ranges See setting ranges, timing intervals
Recovery time ms 15 ... 80 Approx. 40 Approx. 100
Contacts
• Switching channels
8
- Rated operational voltage Ue V AC 250
- Rated operational current Ie A 4 8 5
• Contact gap mm μ contact
- Minimum contact load V; mA 10; 300
Rated impulse withstand voltage Uimp Input/output kV >4
Electrical service life In switching cycles 1A 1.5 × 105 -- 1.5 × 105
At AC-15 -- 1.5 × 105 --
Connections
• Terminals ±screw (Pozidriv) 2
• Conductor cross-sections of main current
paths
- Rigid, max. mm2 2 × 2.5
- Flexible, with end sleeve, min. mm2 2 × 1.5
Environmental conditions
• Permissible ambient temperature °C -40 ... +60
• Resistance to climate Acc. to EN 60068-1 40/60/4
Delay timers
1 CO 250 8 220 ... 240 AC 1 } 5TT3 181 1 1 unit 027 0.090
Wiper timers
1 CO 250 8 220 ... 240 AC 1 B 5TT3 182 1 1 unit 027 0.079
Flashing timers
Pulse time is equal to idle time
1 CO 250 8 220 ... 240 AC 1 B 5TT3 183 1 1 unit 027 0.084
Off-delay timers
1 CO 250 5 110 ... 240 AC 1 B 5TT3 184 1 1 unit 027 0.077
110 ... 240 DC
Switching Devices
Timers
Timers for industrial applications
■ More information
5TT3 185 multifunctional timers Time operation interruption/time addition
Setting aids For the functions AV, EW, IE, BI, the timing interval can be inter-
rupted at any time by activating B1 (+) and by removing the con-
The period of the flashing of the green LED 1 when set for a tim- trol voltage continued again (time addition).
ing interval is 1 s ± 4%, which can therefore be used as a setting
aid. This is particularly useful in the lower time setting range and Control input B1
for long delay times because the multiplication factors between
the individual time ranges are exact. The functions RV, IF, AW, AV/RV can be controlled using the con-
trol input B1 (+) with potential against terminal A2. The auxiliary
Example: voltage of terminal A1 can be used for this purpose, as well as
Delay time to be set: 40 min. any other voltage within the range 12 ... 240 V AC/DC. The oper-
Using the fine setting, this delay time can be set within the set- ation of parallel loads (e.g. contactors) from B1 (+) to A2 is also
ting range 3 ... 300min. However, in this case it takes a long time permissible.
to check the time and requires several operational sequences in If voltage is simultaneously applied to the control input B1 (+)
realtime. To speed up the setting process, the setting range will and A1 for the IF function, this triggers an output pulse with the
be switched to 0.03 ... 3 min. In this case, the required value cor- set time interval t1.
responds to a delay time 0.4 min (= 24 s). The timing interval is
triggered and the potentiometer is set to 24 flashing periods of
the yellow LED 2. The device is then set back to the setting
range 3 ... 300 min and the setting process is completed.
8
Control S1 Position Contact Possible time setting ranges t:
Function c 0.02 ... 1 s
switch 0.06 ... 6 s
A1-A2
0.3 ... 30 s
St 0.03 ... 3 min
B1-A2 0.3 ... 30 min
3 ... 300 min
15-18 0.3 ... 30 h
Response delay AV 1 t 3 ... 300 h
15-16
15-18
Passing make contact EW 2 t
15-16
function
15-18 t 0,5 s
Pulse generator, delayed IE 3
15-16
Flashing relay, 15-18
BI 4 t t
starting with impulse 15-16
A1 15
Control S2 A1-A2 16 18
LED 1 green
B1-A2
E1
LED 2 yellow Z
15-18
OFF-delay RV 5 t t t
15-16 E2
15-18 t
Pulse shape IF 6 t t t
15-16
15-18
Passing break contact AW 7 t t t
15-16
function
I201_11970
15-18 t t t t
Response delay 8
AV/RV 15-16 B1(+) A2
OFF-delay I2_10908b
9/2 Introduction
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical specifications
under Entry List:
- Updates
- Downloads
- FAQ
- Manuals
- Characteristic curves
9
- Certificates
and at
www.siemens.com/lowvoltage/
configurators
- Configurators
Introduction
■ Overview
Devices Page Field of application Standards Used in
Non-residential
Residential
buildings
buildings
Industry
Bell transformers 9/3 Power supply up to 40 VA as safety extra- EN 61558-2-8 ✓ ✓ --
low voltage (SELV) in residential buildings
for the supply of gongs, buzzers, bells, door
openers and remote control switches
9
Power supply units 9/7 Direct voltage power supply up to 24 V DC EN 61558-2-6 ✓ ✓ ✓
and 2 A as safety extra-low voltage (SELV)
for the supply of gongs, buzzers, bells, door
openers, switching relays and Insta contac-
tors
Bells and buzzers 9/9 Bells and buzzers serve to indicate alarm ✓ ✓ ✓
states or for general acoustic signaling.
They are used as modular installation
devices in distribution boards.
REG socket outlets 9/10 For power supply during maintenance in DIN VDE 0620-1, ✓ ✓ ✓
distribution boards in DIN VDE, CEE 7, CEE 7 standard sheet V,
CEI 23-50 and UL 489 versions CEI 23-50,
UL 498
Bell transformers
■ Overview ■ Benefits
A typical application for these bell transformers is short-time • Bell transformers with a footprint of only one modular width
use, as occurs with bells, gongs, door openers or remote control • Reliable device protection through PTC resistors; for protec-
switches in residential buildings. tion against overload and short-circuits
The standard EN 61558 distinguishes between transformers for • The bell transformers are IMQ (Italy) and VDE approved. This
short-time loading and those for permanent loading. This means ensures operational safety.
that clear requirements for bell transformers are defined. Bell
transformers must maintain 100 % of their rated power for
1 minute, or 20 % for 5 minutes, without tripping.
Siemens bell transformers are protected against short circuit or
moderate overload by a PTC resistor. If a disconnection occurs,
the bell transformer must be switched off for approx. 30 minutes
to cool down the PTC resistor.
■ Technical specifications
4AC3 006 4AC3 008 4AC3 016 4AC3 108 4AC3 116 4AC3 140
Standards EN 61558-2-8
Approvals EN 61558-2, IMQ
Rated operational power Ps VA 8 8 16 8 16 40
Rated operational voltage Ue V AC 230
Operating range at 50/60 Hz × Ue 0.9 ... 1.06
Rated frequency Hz 50
Operating frequency range Hz 45 ... 65 48 ... 62
Rated secondary voltage Usec
• In series connection
V AC 12
V AC --
2×4
8
2 × 12
24 9
Rated secondary current Isec
• At 4 V A AC -- 2 × 1.0 2 × 2.0 -- -- --
• At 8 V A AC -- 1 1 -- -- --
• At 12 V A AC 0.67 -- -- 2 × 0.33 2 × 0.67 2 × 1.67
• At 24 V -- -- -- 0.33 0.67 1.67
Rated power dissipation PV
• In no-load operation W 0.78 1.8 2.4 1.6 1.6 1.2
• At rated load W 1.65 5 7.5 3.6 8.2 17.2
Safe separation
• Creepage distances and clearances mm >3
Insulation class B
Test voltage, 50 Hz, 1 minute
• Primary against secondary winding kV 4 > 3.75
Terminals ±screw (Pozidriv) 1
Conductor cross-sections
• Rigid mm2 1 × 6 or 2 × 4
• Flexible, with end sleeve mm2 0.75
Permissible ambient temperature °C -10 .... +25
Permissible humidity % ≤ 80
Degree of protection Acc. to EN 60629 IP20
Safety class Acc. to EN 61140/ II
VDE 0140-1
Bell transformers
■ Overview ■ Benefits
These transformers up to 63 VA provide a safety extra-low volt- • The transformers with 24 VA, 40 VA and 63 VA cores are
age for supplying control current circuits, switching relays or molded, which means that they are hum-free and suitable for
Insta contactors in continuous operation as alternating voltage installation in sound-sensitive distribution boards
power supply for 8 V, 12 V or 24 V AC. • Reliable device protection through PTC; provide longstanding
Siemens transformers for permanent loading are protected protection against overload and short circuits
against short circuit or moderate overload by a PTC resistor. If a • The transformers are IMQ and VDE approved – this ensures
disconnection occurs, the transformer must be switched off for operational safety.
approx. 30 min to allow the PTC resistor to cool down.
EN 61558-2-2 specifies that with transformers for permanent
loading the difference between the non-loaded output voltage
and the output voltage loaded with the rated load must not ex-
ceed 10 %. This requirement places the highest demands on the
design of this type of transformer. It can only be met by using
high-quality core materials and a core design with an extraordi-
narily high efficiency, such as type EI to DIN 41302.
■ Technical specifications
4AC3 408 4AC3 516 4AC3 524 4AC3 540 4AC3 616 4AC3 624 4AC3 640 4AC3 663
Standards EN 61558-2-2
Approvals EN 61558-2, IMQ
Rated operational power Ps VA 8 16 24 40 16 24 40 63
Rated short-time power
p.f. = 0.5; t = 10 s VA 10 18 27 48 18 27 48 80 9
Rated operational voltage Ue V AC 230
Operating range at 50/60 Hz × Ue 0.9 ... 1.1
Rated frequency Hz 50
Operating frequency range Hz 48 ... 62
Rated secondary voltage Usec V AC 8 2×4 8 2 × 12
In series connection V AC No 8 No 24
Rated secondary current Isec
• At 4 V A AC No 2×2 No
• At 8 V A AC 1 2 3 5 No
• At 12 V A AC No 2 × 0.67 2×1 2 × 1.67 2 × 2.62
• At 24 V A AC No 0.67 1 1.67 2.62
Rated power dissipation PV
• In no-load operation VA 3.5 10.3 8.0 13.8 8.0 13.1 8.3 23.0
• At rated load W 2.6 4.6 2.7 6.9 3.6 6.3 5.7 10.0
Hum-free Core molded No Yes No Yes
Safe separation
Creepage distances and clearances mm ≥3
Insulation class B
Test voltage, 50 Hz, 1 minute
Primary against secondary winding kV ≥4
Terminals ±screw (Pozidriv) 1
Conductor cross-sections
• Rigid mm2 1 ... 6
• Flexible, with end sleeve, min. mm2 0.75
Permissible ambient temperature
In operation °C -10 ... +40
Permissible humidity % ≤ 80
Degree of protection Acc. to EN 60529 IP20
Safety class Acc. to II
EN 61140/VDE 0140-1
■ Overview ■ Benefits
The electronic power supply unit provides a 24 V DC supply to • Expanded applications due to safety extra-low voltage SELV.
systems with an operational voltage of 85 to 265 V AC or
85 to 300 V DC. The device operates in the lower class for Electronic power supply units
minimum power supply with a safety extra-low voltage (SELV). • Smallest electronic power supply unit in the lower power class
In the event of short circuits and high capacitive loads, the in 2 MW. This saves valuable space in distribution boards
power supply unit detects the overcurrent as soon as it is acti- • Universal applications in many systems, thanks to wide range
vated and shuts down immediately. It switches back on after voltage supply of 85 V to 265 V AC or 85 V to 300 V DC
2.5 seconds. The electronic power supply unit is suitable for
supplying the 5TT7 1 GSM alarm modules within a supply • Interference suppression to limit value Class B (lower limit)
voltage range of 150 to 230 V AC. even meets the requirements for residential buildings.
Power supply units for direct voltages with rectifiers are used to Power supply units with bridge rectifiers
supply gongs, bells, door openers, switching relays, remote
control switches, Insta contactors or for safety extra-low voltage • The power supply units are IMQ and VDE approved. This
systems (SELV) in continuous operation. They are protected ensures continuous operation.
against short circuit or moderate overload by a PTC resistor. If
tripped, the power supply unit must be switched off for approx.
30 mins. to allow the PTC resistor time to cool down.
■ Technical specifications
4AC2 400 4AC2 401 4AC2 402
Standards EN 61558-2-6 EN 60068-2,
EN 61558-1,
EN 61000-4
Approvals EN 61558-2; IMQ --
Rated operational power Ps
Rated operational voltage Ue
W
V AC
24
230
43 8.4
85 ... 265 9
V DC -- 85 ... 300
Permissible operational voltage
For the 5TT7 1 GSM alarm modules V AC/DC -- 150 ... 265
Primary operating range At 50/60 Hz × Ue 0.9 ... 1.1 --
Rated frequency Hz 50 50/60
Operating frequency range Hz 48 ... 52 --
Rated secondary voltage Usec V DC 12 24 24 ± 5 %
Rated secondary current Isec A DC 2.0 1.8 0.35
Current limitation PTC Electronic overload
protection
Residual ripple mV -- < 100
Rated power dissipation Pv In no-load operation W 5 6 --
At rated load W 10 15 --
Hum-free Core molded Yes --
Safe separation Creepage distances and mm 8 > 5.5
clearances
Insulation class B --
Test voltage
Primary against secondary winding 50 Hz, 1 min kV >4 --
Insulation resistance kV -- 4
Rated impulse withstand voltage/ Acc. to IEC 60664-1 -- 6 kV/2
degree of pollution
Static discharge Acc. to IEC/EN 61000-4-2 kV -- 8
RF irradiation Acc. to IEC/EN 61000-4-3 V/m -- 10
Transient overvoltage (burst) Acc. to IEC/EN 61000-4-4 kV -- 4
Transient overvoltage (surge) Acc. to IEC/EN 61000-4-5
• Supply lines A1, A2 kV -- 1
• A1/A2 and ground kV -- 2
RF, conducted disturbance Acc. to IEC/EN 61000-4-6 V -- 10
Interference suppression to lower limit class Acc. to EN 61000-6-3 -- Complied with
Terminals
• Screw (slotted-head) -- M2.5
• ±screw (Pozidriv) 1 --
Conductor cross-sections
• Rigid mm2 1.5 ... 6 0.5 ... 2.5
• Flexible, with end sleeve, min. mm2 0.75 0.5 ... 1.5
Permissible ambient temperature °C -10 ... +40 -20 ... +60
Permissible humidity % ≤ 80
Resistance to climate Acc. to IEC/EN 60068-1 -- 20/045/04
Resistance to vibrations Acc. to IEC/EN 60068-2-6 mm -- 0.35 amplitude
Frequency 10 ... 55 Hz
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Safety class Acc. to EN 61140 II
■ Overview ■ Benefits
Bells and buzzers are typically used in residential buildings and • Bell transformers and buzzers with a footprint of only one
non-residential buildings, such as shops, offices, banks, etc. modular width
They are used to indicate alarm states or for general acoustic • Reliable device protection through PTC; for protection against
signaling. overload and short circuits.
Bells and buzzers are used as modular installation devices in
distribution boards. These devices are designed for short-time
use in compliance with IEC 62080.
■ Technical specifications
7LQ2 204-0 7LQ2 204-1
7LQ2 205-0 7LQ2 205-1
7LQ2 206-0 7LQ2 206-1
Standards IEC 62080
Rated operational power Ps VA 5.5 4
Rated operational voltage Ue V AC 230 12
Primary operating range At 50/60 Hz × Ue 0.94 ... 1.06
Rated frequency Hz 50
Operating frequency range Hz 45 ... 65
Rated power dissipation PV In no-load operation W 0.83
Pollution degree Acc. to EN 61010-1 2
Working voltage Acc. to EN 61010-1 V AC 230 12
Insulating material group Acc. to EN 61010-1 II
Safe separation
• Clearance mm ≥3 ≥ 1.5 9
• Creepage distances in device mm ≥ 2.5 ≥ 1.5
Test voltage, 50 Hz, 1 min kV 1.25 1
Flammability Class V0
Conductor cross-sections
• Rigid mm2 1 × 6 or 2 × 4
• Flexible with end sleeve mm2 0.75
Volume dB ≥ 75
Permissible ambient temperature °C -10 ... +55
Permissible humidity % ≤ 80
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Safety class Acc. to EN 61140 II
Buzzers
230 5.5 1 B 7LQ2 205-0 1 1 unit 027 0.073
12 4 1 B 7LQ2 205-1 1 1 unit 027 0.070
Bell-buzzer combinations
230 5.5 1 B 7LQ2 206-0 1 1 unit 027 0.053
12 4 1 B 7LQ2 206-1 1 1 unit 027 0.103
■ Overview
The socket outlets for mounting in distribution boards to In distribution boards with 55 mm mounting depth the socket
DIN 43880 and on TH35 standard mounting rails to DIN 60715 outlet can only be used without the hinged lid. The lids can be
have since become standard in modern switchgear/distribution retrofitted on all devices. To make installation easier, the touch-
boards. They are used for tasks such as the connection of plug- protected terminals L, N and PE are located on the side of the
in communication devices in communication distribution boards, socket outlet.
in switchgear assemblies for maintenance purposes or in private
plants for the occasional use of devices with heavy starting and In plant sections where equipment is still live, even after the main
separate fusing. switch has been disconnected, this must be indicated accord-
The socket outlet range complies with a number of different stan- ing to EN 50110-1 and IEC/EN 60204-1. Yellow socket outlets are
dards and is available according to the standards of the follow- used for these applications.
ing countries: VDE for Germany, CEE7 for Belgium/France,
CEI for Italy and UL for USA.
■ Benefits
• Complete program according to VDE, UL, CEI and CEE for • By pulling on the hinges, the hinged lid stays open > 180°.
worldwide application. This facilitates manual insertion of connectors.
■ Technical specifications
5TE6 800 5TE6 801 5TE6 810 5TE6 802 5TE6 803 5TE6 804
Standards VDE 0620-1 VDE 0620-1 VDE 0620-1 CEI 23-50 CEE 7 stan- UL 498
dard sheet V
Approvals VDE 0620-1 -- UL File No.
E258598/
9 CSA C22.2
No. 182.3M
Rated operational voltage Ue V AC 230 125
Rated operational current Ie A AC 16 15
Terminals ±screw (Pozidriv) PZ1
Terminal tightening torque, max. N 1.2
Stripped length mm 10
Conductor cross-sections
• Rigid mm2 1.5 ... 6
• Flexible, with end sleeve mm2 0.5 ... 4
• Rigid AWG 10 ... 14
• Flexible AWG 14
Permissible ambient temperature °C -10 ... +55
Degree of protection
Acc. to EN 60529 IP20, with connected conductors
Mounting position Without cover: any, with cover: vertical or horizontal
Socket outlets
according to CEI 23-50
• With hinged lid
230 16 6 2.5 } 5TE6 802 1 1 unit 027 0.093
Socket outlets
according to CEE 7 Standard sheet V 9
• Without hinged lid, with grounding pin
230 16 6 2.5 } 5TE6 803 1 1 unit 027 0.089
Hinged lids for 5TE6 socket outlets 2.5 C 5TE9 120 1 1 unit 027 0.019
■ More information
Hinged lid for simple application
The hinged lid can be opened at an angle greater than 180 degrees. By pulling on the hinges, the covers stay open, which facilitates plugging in.
The hinged lids can be retrofitted on all versions.
Busbar Systems
10/2 Introduction
40 mm Busbar Systems
10/6 Introduction
10/7 Base assemblies up to 400 A
60 mm Busbar Systems
10/8 Introduction
10/9 Base assemblies up to 630 A
10/13 Base assemblies up to 1600 A
10/14 Infeed and connection components
10/16 Busbar adapters and device holders
10/23 Connector for 3NP1 fuse switch
disconnectors
10/24 Accessories
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical Specifications 10
under Entry List:
- Updates
- Downloads
- FAQ
- Manuals
- Characteristic curves
- Certificates
and at
www.siemens.com/lowvoltage/configurators
- Configurators
Busbar Systems
Introduction
■ Overview
Devices Page Application Standards Used in
Non-residential
Residential
buildings
buildings
Industry
40 mm Busbar Systems 10/6 Base assemblies up to 400 A, EN 13601 ✓ -- ✓
busbar supports, IEC 60439-1
busbars, IEC 61439-2
covers for the touch protection
NSE0_02112
10
Base assemblies up to 1600 A 10/13 Base assemblies up to 1600 A, EN 13601 ✓ -- ✓
busbar supports, IEC 60439-1
busbars, IEC 61439-2
covers for the touch protection UL 508 A
16(B
Infeed and connection components 10/14 Feeder for busbar systems, EN 13601 ✓ -- ✓
terminals... IEC 60439-1
IEC 61439-2
UL 508 A
Busbar adapters and device holders 10/16 Busbar adapters and device EN 13601 ✓ -- ✓
holders for the design of IEC 60439-1
3RV2/3RT2 load feeders IEC 61439-2
UL 508 A
Distribution board components 10/9 Longitudinal stays, assembly kits, IEC 60439-1 ✓ -- ✓
covers for the touch protection IEC 61439-3
DIN VDE 0603-1
Busbar Systems
General data
■ Overview
The use of busbar systems with their versatile rail-adaptable tion boards due to their small footprint, compact design and
connection, switching and installation devices is an ideal and quick assembly contacts. Mounting is implemented on longitu-
cost-effective electrotechnical enhancement of modern distribu- dinal stays. The busbar spacing is 60 mm.
6
5
7
8
4
3
2
1
I201_13633
3
$ Longitudinal stays
10
% Busbar supports, 3-phase
& Copper busbars
( Terminals
) Support for blanking cover
* Blanking covers
+ Supports
, Touch protection cover
9
- Busbar support, single-phase
■ Benefits ■ Design
Notable cost reduction compared to conventional installation in 8US busbar systems with 60 mm busbar center-to-center clear-
switchgear and control cabinets due to the following reasons: ance as well as flat copper profiles have become firmly estab-
• Mechanical fixing and electrical contacting in a single step lished on the world market.
• No access wiring and fewer busbar terminals used The permissible busbar temperature is decisive when dimen-
• Double use of the busbar space sioning the busbars. The busbar temperature is dependent on
the current and the current distribution, on the busbar cross-sec-
• Clear arrangement tion and the busbar surface, on the position of the busbars, con-
• Straightforward replacement of individual devices or whole vection and the ambient temperature. The values stated in the
combinations following table can only be considered as guide values because
• High operational safety through finger-safe covering of the the conditions vary with each location. The values are based on
adapters and device holders uninterrupted current over the whole busbar length.
All the above advantages are felt especially in cases where The busbar runs prove most advantageous when the incoming
many tap-off units of the same performance range are required. supply is centrally located and the load is distributed symmetri-
cally on both sides.
■ Application ■ Function
8US busbar systems are used for the direct busbar-mounting of
current-limiting devices (protection devices) such as fuse switch Short-circuit strength
disconnectors and motor starter protectors/circuit breakers as The short-circuit strength of the busbar system is dependent on
well as complete load feeders. the distance of the busbar supports and on the busbar cross-
8US busbar systems are designed for horizontal mounting of the section.
busbars. The short-circuit strength of the whole system is dependent on
the short-circuit strength of the busbars and of the adapters with
circuit breakers or switch disconnectors. If one of these values
is lower than the prospective short-circuit current at the place of
installation, a current-limiting protective device has to be
mounted upstream of the 8US busbar system. This may also be
mounted as a feeder circuit breaker on the busbar system itself.
Busbar Systems
General data
■ Technical specifications
Uninterrupted current for busbars, E-Cu bare, at 35 °C ambient temperature according to DIN 43671
Bar dimensions System Uninterrupted current at a busbar temperature of
65 °C 85 °C 105 °C
mm mm A A A
12 × 5 40 + 60 188 248 295
15 × 5 40 + 60 222 293 349
20 × 5 60 274 362 430
25 × 5 60 327 432 513
30 × 5 60 379 500 595
12 × 10 40 + 60 302 398 474
20 × 10 60 427 564 670
30 × 10 60 573 756 900
Special profile up to 1600 A 60 1020 1020 1600
10 Cover profiles
Bases, partitions, edge profiles and blanking covers
°C
°C
110
70
Machining of plastic profiles Take care when machining that no cracks are formed. A cross-cut circular saw with the
following characteristic values has proven successful in cutting cover profiles for busbars:
• D = 300 mm, B 0 2.2 mm,
• T = 120 R (5° negative replaceable tooth at a cutting rate of 50 ... 60 m/s)
• Tooth feed 0.05 ... 0.1 mm
The plastic parts are secured so that vibration is ruled out.
Approvals
Busbar supports, busbar device adapters, device hold- UR, CSA, cuUS- Listed
ers and terminals.
Infeed, connection modules, three-phase 5SH3 538 5SH3 535 8US19 21-1BA00 8US19 21-1AA00
Center-to-center clearance mm 60 60 60 60
Current carrying capacity of the terminal points A 80 560 300 440
The specified current carrying capacities reflect the ther-
mal load capability of the terminal points under favorable
conditions (with the largest conductors it is possible to
connect). This does not invalidate the assignment of con-
ductor cross-sections and current carrying capacities as
defined in national and international specifications.
Tightening torque Nm -- 30 8 ... 10 12 ... 15
Clamping space W × H mm -- -- 10 × 15 15 × 15
Conductors that can be used mm2 1.5 ... 16 150 ... 300 6 ... 50 (70) 35 ... 120
Cu, re, rm, f, f+AE Cu, Al Cu, rm, f, f+AE Cu, rm, f, f+AE
(reduction of the (connections with alu- (reduction of the (reduction of the
maximum conductor minum conductors maximum conductor maximum conductor
cross-sections may are not maintenance cross-sections may cross-sections may
be required) free), rm, sm, f be required), la. be required), la.
Cu 6 × 9 × 0.8 Cu 6/10 × 15.5 × 0.8
Busbar Systems
General data
■ Characteristic curves
Characteristic curves as a function of rated peak withstand current
40 mm Busbar Systems 60 mm Busbar Systems
pk kA
kA NSE0_00342b
pk NSE0_01546 kA 90
55 pk
NSE0_01547
50 55 1
80
45 50
2 x 12x5 45 75
T
40 2 x 15x5 30x10
70
35 40
1 x 12x5 35 65
30 1 x 15x5 30x5
30 60
25
25 55
20
200 250 300 350 400 mm 20 50
200 250 300 350 400 mm 45
40 20x5 20x10
Surge current 12x5 12x10
pk 35
Surge current pk
Spacing of busbar supports 30
Spacing of busbar supports 300 400 500 600 700 mm 800 900
5-pole busbar supports 2
1 Surge current pk
10
Busbar Systems
40 mm Busbar Systems
Introduction
■ Overview
The 40 mm busbar system for the lower performance range up to 400 A: Terminals and covers for infeed and connection components
The 40 mm busbar system is used in machine engineering and
distribution boards, in meter cabinets and in power distribution
systems of the low performance range up to 400 A.
The busbar cross-sections are adapted to the rated currents and
are available in the sizes 12 x 5 mm, 12 x 10 mm, 15 x 5 mm and
15 x 10 mm. The basic system is configured without covers. If
touch protection is required, this is possible with busbar covers.
10 Terminals round off the product range of the 40 mm busbar sys-
tem.
Busbar Systems
40 mm Busbar Systems
Base assemblies up to 400 A
■ Overview
2
1 3 4
NSE0_02112
10
M)
kg
%() Busbar supports
End and intermediate holders for
flat copper profiles
12 mm x 5 mm, 12 mm x 10 mm, A 8US19 03-3AB00 1 1 unit 143 0.184
15 mm x 5 mm, 15 mm x 10 mm
3-pole, with inside fixing
(PU = 2 busbar supports including
inlay parts for bar thickness 5 mm
and lateral finger-safe covers)
8US19 03-3AB00
8US19 03-5AA00
$ Flat copper profiles
(flat profile, approx. 2.4 m long,
bare, acc. to EN 12167)
12 mm × 5 mm B 8WC5 123 1 1 unit 143 1.100
8WC5 15 mm × 5 mm B 8WC5 121 1 1 unit 143 1.550
& Cover profiles for busbars
12 mm × 5 mm 1000 mm long A 8US19 22-2CA00 1 10 units 143 0.200
15 mm × 5 mm 1000 mm long A 8US19 22-2AA00 1 10 units 143 0.156
8US19 22-2CA00
Busbar Systems
60 mm Busbar Systems
Introduction
■ Overview
The 60 mm busbar system for the medium and top performance range up to 1600 A, here for example with the 3NP1 switch disconnector, size 3
The 60 mm busbar system is used preferably in control cabinet
installation, in motor control centers and in power distribution
systems of the medium power range (630 A) and top perfor-
10
mance range (1600 A, special profile).
The 60 mm busbar system can be configured as a basic system
without covers. The busbar cross-sections are available in the
sizes 12 x 5 mm to 30 x 10 mm and as a special profile.
Busbar adapters for SIRIUS, 3VL circuit breakers, 3KA and 3KL
switch disconnectors, and 3NP1 and 3NP5 fuse switch discon-
nectors offer numerous options for configuring this busbar sys-
tem. Feeder units, terminals and other accessories open up a
large range of application.
Busbars with a special profile are suitable for applications up to
1600 A. All components of the 60 mm busbar system can be fit-
ted.
Busbar Systems
60 mm Busbar Systems
Base assemblies up to 630 A
■ Overview
NSE0_02123
Busbar Systems
60 mm Busbar Systems
Base assemblies up to 630 A
Busbar support and end cap
Description Connections Standard DT Order No. Price PU PS*/ PG Weight
plus per PU (UNIT, P. unit per PU
UL, CSA SET, approx.
M)
kg
% Busbar supports
End and intermediate holders for flat copper profiles
12 mm x 5 mm, 12 mm x 10 mm,
15 mm x 5 mm, 15 mm x 10 mm,
20 mm x 5 mm, 20 mm x 10 mm,
25 mm x 5 mm, 25 mm x 10 mm,
30 mm x 5 mm, 30 mm x 10 mm
3-pole, with fixing screws A 8GK9 711-0KK03 1 1 unit 039 0.300
8GK9 711-0KK03
3-pole, with outside fixing L1–L3 A 8US19 23-2AA01 1 10 units 143 0.200
3-pole, with inside fixing L1–L3 A 8US19 23-3AA01 1 10 units 143 0.200
10
8US19 23-3AA01
4-pole, with inside fixing L1–L3 + PE/N A 8US19 23-4AA00 1 10 units 143 0.269
2-pole, with outside fixing A 8US19 23-5AA00 1 10 units 143 0.200
8US19 23-5AA00
N/PE busbar supports
• 1-pole, plus PE/N A 5SH3 540 1 1 unit 016 0.059
for flat copper profile
for 5/10 mm busbar
5SH3 540
• 1-pole, in addition for copper PE/N UL508 A 8US19 23-1AA01 1 1 unit 143 0.200
profiles 6 x 6 mm,
mounting on 8US1923-2AA01
3-pole busbar supports or free
standing
8US19 23-1AA01
Busbar Systems
60 mm Busbar Systems
Base assemblies up to 630 A
8US19 23-3UA01
& End covers
For covering unterminated
busbar ends
• For 8US19 23-2AA01, L1–L3 UL 508A A 8US19 22-1AC00 1 10 units 143 0.020
3AA01 and -3UA01
• 4-pole, L1–L3 + PE/N A 8US19 22-1AB00 1 1 unit 143 0.055
for 8US19 23-4AA00
1 pack = 2 units
(1x right, 1x left)
For 5SH3 532 holder
8US19 22-1AC00
• Height 230 mm (3-pole) B 5SH3 533 1 4 units 016 0.035
5SH3 534
• Height 290 mm C 5SH3 534 1 4/40 units 016 0.045
(4-pole or
3-pole + cable duct),
1 pack = 2 units
(1x right, 1x left)
Covers, supports for blanking covers, flat copper profiles and busbar connection parts 10
Description Length Width Standard DT Order No. Price PU PS*/ PG Weight
plus per PU (UNIT, P. unit per PU
UL, CSA SET, approx.
mm mm M) kg
( Cover profiles for busbars
12 mm x 5 mm 1000 A 8US19 22-2CA00 1 10 units 143 0.200
8US19 22-2CA00
15 mm x 5 mm, 1000 UL 508A A 8US19 22-2AA00 1 10 units 143 0.156
20 mm x 5 mm,
25 mm x 5 mm,
30 mm x 5 mm
8US19 22-2AA00
12 mm x 10 mm, 1000 UL 508A A 8US19 22-2BA00 1 10 units 143 0.105
15 mm x 10 mm,
20 mm x 10 mm,
25 mm x 10 mm,
30 mm x 10 mm
) Supports for blanking covers )
Mounting on busbar 1000 190 UL 508 B 5SH3 536 1 4/160 units 016 0.037
(2 units per section of
blanking cover)
5SH3 536
* Blanking covers
Mounting on 5SH3 536 1000 202 UL 508A A 5SH3 537 1 2 units 016 1.130
support for blanking covers
5SH3 537
1) Only with base plate 8US19 22-2UA01
Busbar Systems
60 mm Busbar Systems
Base assemblies up to 630 A
8US19 22-2UA01
$ Flat copper busbar (flat profile, bare)
Flat copper profile for universal applications
• 12 x 5 mm, current up to 200 A 2400 60 EN 12167 B 8WC5 123 1 1 unit 143 1.100
• 15 x 5 mm, current up to 250 A 2400 75 EN 12167 B 8WC5 121 1 1 unit 143 1.550
• 20 x 5 mm, current up to 320 A 2400 100 EN 12167 B 8WC5 126 1 1 unit 143 1.780
• 25 x 5 mm, current up to 400 A 2400 125 EN 12167 B 8WC5 131 1 1 unit 143 2.240
• 20 x 10 mm, current up to 520 A 2400 200 EN 12167 B 8WC5 128 1 1 unit 143 3.200
• 30 x 5 mm, current up to 447 A 2400 150 EN 12167 B 8WC5 133 1 1 unit 143 2.680
• 30 x 10 mm, current up to 630 A 2400 300 EN 12167 B 8WC5 134 1 1 unit 143 5.360
Flat copper profile for ALPHA distribution boards
• 12 x 5 mm, current up to 250 A 250 60 EN 12167 A 8GK9 731-0KK10 1 5 units 039 0.100
500 60 EN 12167 A 8GK9 731-0KK20 1 5 units 039 0.330
750 60 EN 12167 A 8GK9 731-0KK30 1 5 units 039 0.500
1000 60 EN 12167 A 8GK9 731-0KK40 1 5 units 039 0.660
1250 60 EN 12167 A 8GK9 731-0KK50 1 5 units 039 0.830
500 60 EN 12167 A 8GK9 733-0KK20 1 5 units 039 0.570
750 60 EN 12167 A 8GK9 733-0KK30 1 5 units 039 0.850
1000 60 EN 12167 A 8GK9 733-0KK40 1 5 units 039 1.120
8JK3 20
Busbar connection pieces
For flat profiles (max. 630 A)
20 mm × 5 mm, 40 -- -- A 8US19 21-2BE00 1 6 units 143 0.070
20 mm × 10 mm,
25 mm × 5 mm,
25 mm × 10 mm,
30 mm × 5 mm,
8US19 21-2BE00 30 mm × 10 mm
For flat profiles (max. 630 A)
12 mm × 5 mm, 55 -- -- A 8US19 21-2BF00 1 12 units 143 0.070
12 mm × 10 mm,
15 mm × 5 mm,
15 mm × 10 mm,
20 mm × 5 mm,
8US19 21-2BF00 20 mm × 10 mm
Busbar Systems
60 mm Busbar Systems
Base assemblies up to 1600 A
■ Overview
NSE0_02113
Flat copper profile
Busbar support
End cover
8US19 43-3AA00
Flat copper profiles
(approx. 2.4 m long, tinned)
Special profile up to 1600 A, cross section 720 mm2 A 8US19 48-2AA00 1 1 unit 143 15.360
8US19 48-2AA00
Cover profiles
For flat copper profiles, length 1000 mm A 8US19 22-2DA00 1 5 units 143 0.200
Busbar connection pieces
For special profiles/TT profiles up to 1600 A A 8US19 41-2BF00 1 3 units 143 1.134
8US19 41-2BF00
Barriers, closed
76 mm wide, 2400 mm long C 8US19 22-1JA00 1 1 unit 143 0.700
For additional touch protection at the top/bottom
76
48
NSB0_91362b
2400
8US19 22-1JA00
Supports for blanking covers
Mounting on busbar UL 508A B 5SH3 536 1 4/160 units 016 0.037
(2 units per section of blanking cover),
height 1000 mm
5SH3 536
Blanking covers
Mounting on 5SH3 536 support UL 508A A 5SH3 537 1 2 units 016 1.130
for blanking covers,
height 1000 mm
5SH3 537
Busbar Systems
60 mm Busbar Systems
Infeed and connection components
■ Overview
60 mm busbar system: Terminals and covers for infeed and connection components
10
M)
mm mm mm2 kg
Infeeds
Terminal plate with
cover
• 3-pole 200 20 1.5 ...16 A 5SH3 538 1 5 units 016 0.181
• 3-pole 200 54 6 ... 50 A 8US19 21-1BA00 1 1 unit 143 0.397
• 3-pole 200 81 35 ... 120 A 8US19 21-1AA00 1 1 unit 143 0.607
8US19 21-1AA00
5SH3 535
Terminal sets
3-pole 120 ... 300 A 8US19 41-2AA03 1 1 unit 143 0.160
without cover
for round cables
8US19 41-2AA03
Busbar Systems
60 mm Busbar Systems
Infeed and connection components
8US19 41-2AA04
Covers for 8US19 41-2AA03/04 A 8US19 22-1GC00 1 1 unit 143 0.150
terminal set
8US19 22-1GC00
Terminals for circular conductors
5 mm busbar thickness1)
12 mm × 5 mm, 1.5 ... 16 } 8US19 21-2AA00 100 100 units 143 0.100
15 mm × 5 mm, 4 ... 35 } 8US19 21-2AB00 100 50 units 143 4.600
20 mm × 5 mm, 16 ... 70 } 8US19 21-2AD00 1 50 units 143 0.072
25 mm × 5 mm, 16 ... 120 } 8US19 21-2AC00 1 50 units 143 0.107
30 mm × 5 mm 1.5 ... 16 } 8US19 21-2AA01 1 15 units 143 0.020
4 ... 35 } 8US19 21-2AB01 1 15 units 143 0.020
Terminals 16 ... 70 } 8US19 21-2AD01 1 15 units 143 0.020
16 ... 120 } 8US19 21-2AC01 1 15 units 143 0.020
20 mm × 5 mm, 25 mm × 5 mm, 95 ... 185 } 8US19 41-2AA01 1 6 units 143 0.315
30 mm × 5 mm
10 mm busbar thickness
150 ... 300 } 8US19 41-2AA02 1 3 units 143 0.425
10
12 mm × 10 mm,1) 1.5 ... 16 } 8US19 21-2BA00 1 100 units 143 0.020
15 mm × 10 mm,1) 4 ... 35 } 8US19 21-2BB00 1 50 units 143 0.040
20 mm × 10 mm, 16 ... 70 } 8US19 21-2BD00 1 50 units 143 0.070
25 mm × 10 mm, 16 ... 120 } 8US19 21-2BC00 1 50 units 143 0.100
30 mm × 10 mm 1.5 ... 16 } 8US19 21-2BA01 1 15 units 143 0.020
4 ... 35 } 8US19 21-2BB01 1 15 units 143 0.040
Terminals 16 ... 70 } 8US19 21-2BD01 1 15 units 143 0.070
16 ... 120 } 8US19 21-2BC01 1 15 units 143 0.100
20 mm × 10 mm, 95 ... 185 } 8US19 41-2AA01 1 6 units 143 0.315
25 mm × 10 mm, 150 ... 300 } 8US19 41-2AA02 1 3 units 143 0.425
30 mm × 10 mm
Covers for terminals for circular conductors
(attachment to busbar)
For terminals up to 120 mm2 } 8US19 22-1GA00 1 10 units 143 0.126
200 mm long, 84 mm wide
For terminals up to 300 mm2 2) } 8US19 22-1GA02 1 1 unit 143 0.696
200 mm long, 270 mm wide
8US19 22-1GA00
Terminals
For cable lugs up to 240 mm2, A 8US19 41-2AC00 1 6 units 143 0.368
10 mm bar thickness
(threaded bolts M10)
8US19 41-2AC00
For copper bars or laminated conductors A 8US19 41-2BB00 1 6 units 143 0.307
20 mm x 5 mm,
20 mm x 10 mm,
25 mm x 5 mm,
25 mm x 10 mm,
30 mm x 5 mm,
8US19 41-2BB00 30 mm x 10 mm
For 2 x 40 mm x 10 mm A 8US19 41-2BA00 1 3 units 143 0.824
8US1941-2BA00
1)
Cannot be used on a special profile up to 1600 A. 2)
Only for 20 mm × 5 mm, 20 mm × 10 mm, 25 mm × 5 mm, 25 mm × 10 mm,
30 mm × 5 mm and 30 mm × 10 mm.
Busbar Systems
60 mm Busbar Systems
Busbar adapters and device holders
■ Overview
Busbar Systems
60 mm Busbar Systems
Busbar adapters and device holders
Busbar Number Adapter Connecting cables Stan- DT Order No. Price PU PS*/ PG Weight
device of dard per PU (UNIT, P. unit per PU
adapters mount- Length Width Cross- Tem- Rated Rated Addi- SET, approx.
for ing rails sec- pera- current volt- tionally M)
(35 mm) tion ture age UL,
max. CSA
mm mm AWG °C A V kg
Size S0 devices with screw connection
MSPs/ 1 260 45 10 150 32 690 UL 508 } 8US12 51-5NT10 1 1 unit 143 0.183
circuit
breakers
Direct-on- 1 260 45 10 150 32 690 UL 508 } 8US12 51-5NT10 1 1 unit 143 0.183
line starters
Reversing 1 260 45 10 150 32 690 UL 508 } 8US12 51-5NT10 1 1 unit 143 0.183
starters
+ +
Device Device 1 260 45 -- -- -- -- UL 508 } 8US12 50-5AT10 1 1 unit 143 0.183
holder with holders
3RA22 20
Size S0 devices with spring-type terminals
MSPs/ 1 260 45 10 150 32 690 UL 508 } 8US12 51-5NT11 1 1 unit 143 0.183
circuit
breakers
Direct-on- 1 260 45 10 150 32 690 UL 508 } 8US12 51-5NT11 1 1 unit 143 0.183
line starters
Reversing 1 260 45 10 150 32 690 UL 508 } 8US12 51-5NT11 1 1 unit 143 0.183
starters
+ +
Device 1 260 45 -- -- -- -- UL 508 } 8US1250-5AT10 1 1 unit 143 0.183
Device holders
holder with
3RA22 20
10
Busbar Systems
60 mm Busbar Systems
Busbar adapters and device holders
For SIRIUS 3RV1/3RT1 load feeders
Busbar Number Adapter Connecting cables Stan- DT Order No. Price PU PS*/ PG Weight
device of dard per PU (UNIT, P. unit per PU
adapters for mount- Length Width Cross- Tem- Rated Rated Addi- SET, approx.
ing rails sec- pera- current volt- tionally M)
(35 mm) tion ture age UL,
max. CSA
mm mm AWG °C A V kg
Size S2 devices
MSPs/ 1 182 55 8 105 56 690 } 8US12 61-5FM08 1 1 unit 143 0.263
circuit
breakers
Contactors 1 182 55 8 105 56 690 } 8US12 61-5FM08 1 1 unit 143 0.263
+ overload
relay
Direct- 1 242 55 8 105 56 690 } 8US12 61-5FP08 1 1 unit 143 0.292
on-line
Reversing starters
feeder Reversing 1 242 55 8 105 56 690 } 8US12 61-5FP08 1 1 unit 143 0.292
starter
adapter
+ +
Connecting Device -- 242 54 -- -- -- -- -- } 8US12 60-5AP00 1 1 unit 143 0.243
wedge holders1)
+ +
Connecting -- -- -- -- -- -- -- -- } 8US19 98-1AA00 100 100 units 143 0.100
wedges
(2 units
needed for
attachment)
Size S3 devices with screw connection
MSPs/ -- 215 72 4 105 80 600 UR, A 8US12 11-4TR00 1 1 unit 143 0.470
circuit CSA
10
breakers
Device holder
1) Spacer and fixing screw for reversing contactor are included in the scope
of supply.
Busbar Systems
60 mm Busbar Systems
Busbar adapters and device holders
For motor starter protectors/circuit breakers and load disconnect switches which require busbar device adapters for
mounting on busbars
Busbar device Adapter Connecting cables Standard DT Order No. Price PU PS*/ PG Weight
adapters for Length Width Type Rated Rated Addi- per PU (UNIT, P. unit per PU
current voltage tionally SET, approx.
UL, CSA M)
mm mm A V kg
3VL circuit breakers1)
3VL12) 175 108 Busbars 160 690 A 8US12 11-4SL01 1 1 unit 143 0.597
3VL22) 175 108 Busbars 160 690 A 8US12 11-4SL01 1 1 unit 143 0.597
3VL32) 175 108 Busbars 250 690 A 8US12 11-4SL00 1 1 unit 143 0.662
3VL1 to 3VL4 320 184 M10 stud 400 690 A 8US12 10-4AF00 1 1 unit 143 2.769
and also with terminal +
RCD module2) A 8US19 27-4AF01 1 1 unit 143 0.575
3VL5 325 184 M8 stud 580 690 A 8US12 13-4AF00 1 1 unit 143 2.880
8US10 11-4SL01
terminal
3VL UL circuit breakers
VL150X UL 190 105 Tubular 150 600 UL 508A A 8US12 13-4AQ01 1 1 unit 143 1.020
CG-Frame contacts
VL150 UL 190 105 Tubular 150 600 UL 508A A 8US12 13-4AQ03 1 1 unit 143 1.020
DG-Frame contacts
VL250 UL 190 105 Tubular 250 600 UL 508A A 8US12 13-4AQ03 1 1 unit 143 1.020
FG-Frame contacts
8US12 13-4AQ01
VL400 UL 296 140 Tubular 400 600 UL 508A A 8US12 13-4AH00 1 1 unit 143 1.900
JG-Frame contacts
VL400X UL 296 140 Tubular 540 600 UL 508A A 8US12 13-4AH00 1 1 unit 143 1.900
LG-Frame contacts
10
8US12 13-4AH00
3KA und 3KL switch disconnectors
3KA523) 320 184 M10 stud 630 690 A 8US12 10-4AF00 1 1 unit 143 2.769
3KA533) terminal
3KL523)
3KL533)
3KA553) 320 250 M10 stud 630 690 A 8US12 10-4AG00 1 1 unit 143 3.060
3KA573) terminal
3KA583)
3KL553)
3KL573)
3NP5 fuse switch disconnectors
3NP50 60 175 108 Busbars 160 690 A 8US12 10-4AF00 1 1 unit 143 2.769
(NH00)
3NP524), 320 250 M10 stud 630 690 A 8US12 10-4AG00 1 1 unit 143 3.060
3NP534), terminals
3NP545)
1)
Observe the short-circuit strength of the busbar system.
Short-circuit strength > 50 kA on request.
2)
Usable only for 3VL circuit breakers with line-side box terminals.
3)
Without connecting cables. The connecting cable between adapter and
device should be manufactured in accordance with the rated current as a
round cable, e.g. H07V-R with cable lug, or as a flat conductor for a M10
stud terminal.
4)
Without connecting cables. The connecting cable between adapter and
device should be manufactured in accordance with the rated current as a
round cable, e.g. H07V-R with cable lug, or as a flat conductor for a M10
stud terminal.
5)
Without connecting cables. The connecting cable between adapter and
device should be manufactured in accordance with the rated current as a
round cable, e.g. H07V-R, bared at both ends for tunnel terminals.
Busbar Systems
60 mm Busbar Systems
Busbar adapters and device holders
SIRIUS 3RA6 compact feeder according to IEC and UL
Welded cable connection resistant up to 105 °C
Busbar Number Adapter Connecting cables Stan- DT Order No. Price PU PS*/ PG Weight
device of dard per PU (UNIT, P. unit per PU
adapter mount- Length Width Cross- Tem- Rated Rated Addi- SET, approx.
for ing rails section pera- current volt- tionally M)
(35 mm) ture age UL, CSA
max.
mm mm AWG °C A V kg
Size equivalent to 3RA61
Direct- 1 200 45 10 105 32 690 UR, CSA } 8US12 11-1NS10 1 1 unit 143 0.337
on-line
starters
Device
holder
Size equivalent to 3RA62
Reversing 1 200 45 10 105 32 690 UR, CSA } 8US12 11-1NS10 1 1 unit 143 0.337
starters
+ +
Device 1 200 45 -- -- -- -- UL 508 } 8US1 250-1AA10 1 1 unit 143 0.239
holders
Device
10 holder
Busbar Systems
60 mm Busbar Systems
Busbar adapters and device holders
For universal device design
Number of Adapter Connecting cables DT Order No. Price PU PS*/ PG Weight
mounting Length Width Cross- Tem- Length Rated Rated per PU (UNIT, P. unit per PU
rails section pera- current voltage SET, approx.
(35 mm) ture M)
max.
mm mm AWG °C mm A V kg
Devices 45 mm wide
Device holder for side mounting onto busbar device adapter,
no electrical contact
1 200 45 -- -- -- -- -- } 8US12 50-1AA10 1 1 unit 143 0.239
8US1250-1AA10
1 200 45 -- -- -- -- -- } 8US12 50-5AS10 1 1 unit 143 0.183
8US1250-5AS10
1 260 45 -- -- -- -- -- } 8US12 50-5AT10 1 1 unit 143 0.183 10
8US1250-5AT10
Devices 45 mm and 72 mm wide
Busbar device adapter with connection conductors for contact with
busbars, welded connection conductor resistant up to 150 °C
1 200 45 12 150 165 25 690 8US12 51-5DS11 1 1 unit 143 0.183
1 200 45 12 150 99 25 690 } 8US12 51-5DS10 1 1 unit 143 0.183
1 260 45 12 150 99 25 690 } 8US12 51-5DT10 1 1 unit 143 0.183
1 260 45 12 150 165 25 690 } 8US12 51-5DT11 1 1 unit 143 0.183
1 260 45 12 150 99 32 690 } 8US12 51-5NT10 1 1 unit 143 0.183
8US1251-5DS10 1 260 45 12 150 165 32 690 } 8US12 51-5NT11 1 1 unit 143 0.183
1 200 45 10 105 118 32 690 } 8US12 11-1NS10 1 1 unit 143 0.337
-- 215 72 4 105 210 100 690 A 8US12 11-4TR00 1 1 unit 143 0.470
8US1211-4TR00
Busbar Systems
60 mm Busbar Systems
Busbar adapters and device holders
For SIRIUS 3RV1/3RT1 load feeders
Busbar Number Adapter Connecting cables DT Order No. Price PU PS*/ PG Weight
device of mount- Length Width Cross- Rated Rated per PU (UNIT, P. unit per PU
adapters ing rails section current voltage SET, approx.
(35 mm) M)
mm mm mm2 A V kg
Busbar device adapters with terminals (at top) for any arrange-
ment of components
-- 1 182 45 1.5... 4 25 690 A 8US12 50-5RM07 1 1 unit 143 0.174
8US12 50-
5RM07
Device holders for lateral attachment to busbar device adapters
of the same length
Device 1 182 45 -- -- -- } 8US12 50-5AM00 1 1 unit 143 0.158
holders
Device 1 182 55 -- -- -- } 8US12 60-5AM00 1 1 unit 143 0.202
holders
Device -- 242 54 -- -- -- } 8US12 60-5AP00 1 1 unit 143 0.243
holders
Connecting -- -- -- -- -- -- } 8US19 98-1AA00 100 100 units 143 0.100
wedges
8US19 50-
(2 units
1AM00
needed for
10 attachment)
Connecting
wedge
Side modules for extending busbar device adapters and device
holders of the same length
Side -- 182 13.5 -- -- -- A 8US19 98-2BM00 1 4 units 143 0.036
modules
Side -- 200 9 -- -- -- A 8US19 98-2BJ10 1 1 unit 143 0.023
modules
8US19 98-
2BM00
Busbar Systems
60 mm Busbar Systems
Connector for 3NP1 fuse switch disconnectors
10
Box terminals
3NP1 133-1BC21 160 00 / 000 A 3NP1 133-1BC21 1 1 unit 143 1.420
250 1 and 0 A 3NP1 143-1BC21 1 1 unit 143 3.290
400 2 and 1 A 3NP1 153-1BC21 1 1 unit 143 5.430
630 3 and 2 A 3NP1 163-1BC21 1 1 unit 143 7.480
With electronic EFM 10 fuse monitoring
Flat terminals
160 00 / 000 A 3NP1 133-1BC12 1 1 unit 143 1.120
250 1 and 0 A 3NP1 143-1BC12 1 1 unit 143 2.990
400 2 and 1 A 3NP1 153-1BC12 1 1 unit 143 4.900
630 3 and 2 A 3NP1 163-1BC12 1 1 unit 143 6.980
Box terminals
160 000 A 3NP1 123-1BC22 1 1 unit 143 0.940
3NP1 133-1BC22 160 00 / 000 A 3NP1 133-1BC22 1 1 unit 143 1.120
250 1 and 0 A 3NP1 143-1BC22 1 1 unit 143 2.990
400 2 and 1 A 3NP1 153-1BC22 1 1 unit 143 5.130
630 3 and 2 A 3NP1 163-1BC22 1 1 unit 143 7.180
With electronic EFM 20 fuse monitoring and
line monitoring
Flat terminals
160 00 / 000 C 3NP1 133-1BC13 1 1 unit 143 1.120
250 1 and 0 C 3NP1 143-1BC13 1 1 unit 143 2.990
400 2 and 1 C 3NP1 153-1BC13 1 1 unit 143 4.900
630 3 and 2 C 3NP1 163-1BC13 1 1 unit 143 6.980
Box terminals
160 000 C 3NP1 123-1BC23 1 1 unit 143 0.940
3NP1 133-1BC23 160 00 / 000 C 3NP1 133-1BC23 1 1 unit 143 1.120
250 1 and 0 C 3NP1 143-1BC23 1 1 unit 143 2.990
400 2 and 1 C 3NP1 153-1BC23 1 1 unit 143 5.130
630 3 and 2 C 3NP1 163-1BC23 1 1 unit 143 7.180
Accessories
Connection modules
For 32-mm-cover level with A 3NP1 933-1BC00 1 1 unit 143 0.145
box terminal 6 mm ... 70 mm2
Busbar Systems
60 mm Busbar Systems
Accessories
10
8US19 98-7CB45
54 A 8US19 98-7CB54 1 10 units 143 0.100
8US19 98-7CB54
72 A 8US19 98-7CB72 1 10 units 143 0.100
8US19 98-7CB72
Connecting elements
For connecting busbar adapters } 8US19 98-1AA10 1 50 units 143 0.183
and device holders
8US19 98-1AA10
Spacers
Fixes the feeder to the busbar } 8US19 98-1BA10 1 10 units 143 0.183
adapter
8US19 98-1AA1
Vibration & shock kit
} 8US19 98-1CA10 1 1 unit 143 0.183
Busbar Systems
60 mm Busbar Systems
Accessories
For SIRIUS 3RV1/3RT1 load feeders
Description Length Width DT Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
SET, approx.
M)
mm mm kg
Busbar connection pieces
20 mm × 5 mm, 40 A 8US19 21-2BE00 1 6 units 143 0.070
20 mm × 10 mm,
25 mm × 5 mm,
25 mm × 10 mm,
30 mm × 5 mm,
30 mm × 10 mm
12 mm × 5 mm, 55 A 8US19 21-2BF00 1 12 units 143 0.070
12 mm × 10 mm,
15 mm × 5 mm,
15 mm × 10 mm,
8US19 21-2BE00 / 20 mm × 5 mm,
8US19 21-2BF00 20 mm × 10 mm
Mounting rails (35 mm) – plastic
with fixing screws
45 A 8US19 98-7CA15 1 10 units 143 0.009
55 A 8US19 98-7CA16 1 10 units 143 0.100
72 A 8US19 98-4AA00 1 10 units 143 0.143
90 A 8US19 98-7CA08 1 10 units 143 0.187
Mounting rail
110 A 8US19 98-7CA10 1 10 units 143 0.219
Connection holders
For fixing the motor starter protector to the mounting rail A 8US19 98-1DA00 100 20 units 143 0.100
(for SIRIUS size S00/S0)
NSE0_0347
8US19 98-1DA00
10
Screw holders
For supplementary screw mounting of the feeder B 8US19 98-1CA00 100 20 units 143 0.100
(for SIRIUS size S00/S0)
8US19 98-1CA00
Spacers
Fixes the feeder to the busbar adapter } 8US19 98-1BA00 100 100 units 143 0.100
(for SIRIUS size S00/S0)
8US19 98-1BA00
Connecting wedges
For mechanical linking of busbar device adapters and } 8US19 98-1AA00 100 100 units 143 0.100
device holder (2 units per combination)
Connecting wedge
Busbar Systems
■ Overview
Material properties Ambient temperatures
Busbar supports and busbar-mounting fuse bases (see "Built-in When dimensioning the busbars based on rated currents, the
components" from page 10/28) are manufactured from glass-fi- ambient temperature and the Cu busbar temperature must also
ber reinforced, thermoplastic polyester (color RAL 7035, light be taken into account.
gray). The material ensures excellent mechanical, chemical and
electrical properties. Furthermore, the material has an extremely The location of the busbar system and its ability to dissipate heat
low flammability and meets the requirements of UL 94 V0. This through convection also play a key role in this calculation. Be-
satisfies the load requirements of the busbar supports at rated cause conditions can vary for each distribution board, the values
operational voltage 500 V and rated currents at 200 A to 630 A, in the following table serve as a guideline only. However, they
as well as the rated short-circuit strength 50 kA. must be applied to the entire busbar length.
Dynamic rated short-circuit strength Diagram of the dynamic short-circuit strength of the busbars
10 The electrodynamic load of the busbars depends on the level of
I2_07483a
short-circuit current, the length of the busbar section through 80 Let-through current
which the current flows, the support spacing of the busbar sup- of the fuse links
Operating class
ports and, of course, on the distance between the busbars them- D
gL/gG
[kA]
selves. This is because, for example, if an LV HRC fuse is con-
nected upstream to the busbars in the protective device, the let- 70 n 630 A
through current iD is the maximum current to flow through this
protective device. The value iD depends on the maximum sys-
tem short-circuit current and the current-limiting action of the
protective device used. The permissible let-through values of 60
500 A
the protective equipment are specified by the manufacturers in 30x10 n
the form of a current limitation diagram as a function of the so- Busbar dimension
called prospective short-circuit current (r.m.s. value of the pos- mm
sible rated short-circuit current for the system). 50
30x5
The current-limiting characteristics for the fuse links can be
found in the Technical Information, see note on Technical Infor- n 400 A
mation at the beginning of the chapter. 20x10
40 n 315 A
12x10
For busbar supports with busbars of 12 mm x 5 mm to
20 mm x 5 mm, the distance between the holders of the support 20x5
12x5
spacing should be adapted to suit the bars in the distribution n 250 A
board and, if possible, should not exceed 250 mm. When using 30 n 200 A
busbars of 25 mm x 5 mm, 30 mm x 5 mm, 12 mm x 10 mm to 150 200 250 300 350 400 450 500 550
30 mm x 10 mm the distance can also be up to 500 mm. In the Distance between busbar support in mm
case of larger distances, subcarriers must be fitted, as in-
creased support spacing reduces the dynamic stability. iD: Let-through values (kA) of the LV HRC fuse links, operational class
gL/gG with rated current 200 A to 630 A for a prospective short-circuit
It is essential to ensure that the permissible current carrying ca- current Ip = 120 kA.
pacity of the individual busbars is not exceeded. A center infeed
is required in the limit range. However, the infeed can also be
carried out at both ends of the busbar.
Busbar Systems
■ Dimensional drawings 10
8GK9 busbar support N/PE busbar support Connection modules
5 SECTION: A-A
A
34
30,5
49,5
60
36,5
20
60
33
200
194
191
15
60
4 Nm
6,5
60
65
50
I2_13999a
I2_14000a
A NSE0_01568a
49,5
20 20 28 32
8GK9 711-0KK03 5SH3 540 5SH5 538
60
189
200
175
200
200
194
60
60
I2_07150a
80
I2_06439b
84 20 84 31
55 46 NSE0_01598
70 55 54 32
Busbar Systems
Built-in components
■ Overview
Rail-adaptable built-in components, such as NEOZED and have integrated reach-through guards, enable the implementa-
DIAZED bus-mounting bases, adapters for modular installation tion of cost-effective overall solutions.
devices, LV HRC fuse switch disconnectors and NEOZED bus-
mounting fuse switch disconnectors are made of glass-fiber re- Previously two optional solutions were provided, which can now
inforced, thermoplastic polyester. The material ensures the re- be replaced using new technology: touch protection over base
quired mechanical, chemical and electrical properties. and edges or touch protection over partitions.
Efficient power distribution up to 630 A. Higher overall efficiency and cost savings in the plant engineer-
Users have several options for mounting the SR60 busbar ing industry.
system: The fuse holders for cylindrical fuses, size 10 x 38 and for
1. Mounting in distribution boards American fuses, Class CC, can be used in the international plant
engineering industry. In addition, Siemens offers a broad range
The busbar supports are mounted on the longitudinal stays. of UL-approved components for the design of switchgear
Once the built-in components are mounted and connected, the assembly according to UL 508 A.
touch protection cover (section cover) protects against acciden- For further information, see Chapter "BETA Devices according to
tal contact with live parts. UL Standards" in Catalog LV 16 · 2009.
2. Installation in industrial control cabinets Fuse holders are available with a connection module 16 mm²
and screwless terminals; this offers users maximum safety and
The demand for comprehensive touch protection has generated comfort.
new solutions: built-in components, such as busbar fuse bases
5
4
10
3
2
I2_13634a
I201_13634
■ Benefits
• The direct contact of the rail-adaptable switching and installa- • New in-built components with touch protection ensure com-
tion devices on the Cu busbars reduces distribution panels prehensive touch protection without the previously required
and mounting times. partitions.
• Compared to conventional installation, the transfer resistance • International application due to UL-approved components.
of the connections is drastically reduced. This prevents un- • Enhanced effectiveness and increased safety due to screw-
necessary temperature rise. less terminals.
Busbar Systems
Built-in components
■ Technical specifications
NEOZED SR60 DIAZED SR60
bus-mounting bases bus-mounting bases
5SG6 202 5SF6 014 5SF6 214
5SG6 206 5SF6 015 5SF6 215
5SG6 207 5SF6 018 5SF6 218
5SF6 020 5SF6 220
D01 D02 DII DIII
Standards IEC 60269-3/ VDE 0636-3
Rated voltage V AC/DC 400/250 500 690/600
Rated frequency Hz 50
Rated current A 16 (with NEOZED 63 25 63
retaining springs)
Rated conditional short-circuit current kA AC 50 50
kA DC 8 8
For fuse links with power losses per phase W 2.5 5.5 4 7
Busbar center-to-center spacing mm 60 60
10
(When several devices are used next to each other, it is essential to comply with the
rated load factor acc. to EN 60 439-1, Table 1.)
• IEC/EN A 32 --
• UL/CSA A 30 30
Utilization categories
• IEC/EN AC-22B (500 V)
AC-21B (690 V, 30 A)
• UL/CSA Can only be used as fuse holder
Rated conditional short-circuit current
(type-tested with fuse links, operational class gL/gG)
• IEC/EN kA 100 (400 V, 500 V, 690 V) --
• UL/CSA kA 50 (600 V) 200
For fuse links with power losses per phase W 3 --
Screwless wire connections
• IEC/EN mm2 Cu 1.5 … 6 (f)
• UL/CSA AWG 16 … 10 (str)
Busbar Systems
Built-in components
36 mm wide
D02 63 400 2 B 5SG6 207 1 4 units 016 0.188
For NEOZED screw caps, adapter sleeves and fuse links, see chapter "Fuse Systems", NEOZED fuse systems.
Busbar Systems
Built-in components
Size Rated current Rated voltage Mount- DT Order No. Price PU PS*/ PG Weight
ing per PU (UNIT, P. unit per PU
width SET, approx.
M)
A V MW kg
DIAZED SR60 bus-mounting bases, 3P
Standard version
For 5/10 mm busbars
For use with DIAZED adapter rings
DII 25 500 2.3 B 5SF6 014 1 2/52 units 016 0.220
DIII 63 500 V AC/DC (acc. to 3.2 B 5SF6 214 1 2/52 units 016 0.301
DIN VDE 0636-3 also
690 V AC/600 V DC)
10
16 C 5SH3 075 1 10/5000 units 016 0.001
20 C 5SH3 076 1 10/3000 units 016 0.003
DIII 2 C 5SH3 078 1 10 units 016 0.009
4 C 5SH3 080 1 10 units 016 0.009
6 C 5SH3 081 1 10 units 016 0.008
10 C 5SH3 082 1 10 units 016 0.008
16 C 5SH3 083 1 10 units 016 0.007
20 C 5SH3 084 1 10 units 016 0.006
25 C 5SH3 085 1 10/1000 units 016 0.005
35 C 5SH3 086 1 10/3500 units 016 0.005
50 C 5SH3 087 1 10/600 units 016 0.004
For DIAZED screw caps, screw adapters and fuse links, see chapter "Fuse Systems", DIAZED fuse systems.
Busbar Systems
Built-in components
5SH5 525
Lateral modules
For greater heat dissipation for loads > 35 A with
NEOZED bus-mounting switch disconnectors
0.5 C 5SH5 526 1 5/50 units 016 0.051
5SH5 526
Reducers
For NEOZED fuse links D01
In SR60 bus-mounting switch disconnectors C 5SH5 527 1 10/100 units 016 0.001
5SH5 527
SR60 LV HRC bus-mounting fuse bases, 3P
Size 00
For 5/10 mm busbars
With cover, connections at top
Terminals up to 70 mm2
Rated voltage 690 V AC
With saddle-type terminal A 3NH4 052 1 4 units 014 0.663
10 3NH4 052
Busbar Systems
Built-in components
■ Dimensional drawings
NEOZED SR60 bus-mounting bases
D02/63 A D02/63 A D02/63 A
(a = 27 mm, t = busbar thickness) (a = 27 mm, b = 50 mm) (a = 36 mm, b = 50 mm)
60
60
200
194
189
169
177
60
60
I2_07478a
I2_13998
a t a 32
23 35
33,5 43
55 28 b
5SG6 202 (t = 5 mm) 5SG6 206 5SG6 207
10
60
60
60
200
194
189
169
169
169
60
60
60
I2_07497
I2_13998
I2_07496
a t a t a 32
36 36 35
43,5 43,5 43
66 66 28 b
5SF6 014, 5SF6 015 5SF6 214, 5SF6 215 5SF6 018, 5SF6 020 5SF6 218, 5SF6 220
(t = 5 mm) (t = 5 mm) (b = 70 mm) (b = 70 mm)
Busbar Systems
Built-in components
NEOZED SR60 covers SR60 LV HRC bus-mounting fuse bases, 3P
D02/63 A
89
99 64
33 33 29 4
60
60
60
60
5
200
200
200
200
60
60
60
60
10
60
60
60
200
200
200
60
60
60
I2_14009
I2_14008
42 57 26,8 100
5SH2 042 (1-fold: a = 42 mm) 5SH2 242 (1-fold: a = 57 mm) 5SG7 230
3NW7 430
200
194
60
I2_14001
3NW7 431,
3NW7 431-0HG,
3NW7 432-0HG
Introduction
11/2 Energy management systems
11/3 Measuring devices and E-counters
E-Counters
11/6 PAC1500 three-phase counters
11/9 PAC1500 single-phase counters
11/12 Expansion modules for E-counters N
11/35
Time and Pulse Counters
Time and pulse counters for mounting
11
onto standard rail
11/37 Time counters for front-panel
mounting
Accessories
11/39 7KT1 2 current transformers
11/40 7KT9 0 measuring selector switches
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical Specifications
under Entry List:
- Updates
- Download
- FAQ
- Manuals
- Characteristic curves
- Certificates
and at
www.siemens.com/lowvoltage/configurators
- Configurators
■ Overview
System configuration
Ethernet
Data processing
SENTRON powermanager server
Ethernet (Modbus)
Data detection PAC3200 PAC4200 PAC3200
Measuring/protection devices
Modbus RS485
PAC3100 SENTRON SENTRON
I202_01389
3WL 3VL
System overview
The SENTRON-based power management system is comprised SENTRON powermanager
of a PC with the related power management software and with
the related devices which are connected directly to the PC The SENTRON powermanager power management software
through Ethernet. • is an independent power management software
• can be operated with a PC and measuring instruments with
General goals of a power management system: Ethernet connection
• to identify savings potential • is expandable from the simple standard application to a fully
• to reduce power costs flexible customer solution
• is fully scalable with regard to the number of devices and to
• to ensure power availability the software's functions
through transparency of the momentary conditions and through • ensures the optimum integration of measuring instruments
from the SENTRON PAC range, SENTRON 3WL/3VL circuit
11
comprehensive power assignments and evaluations.
breakers and other devices
SENTRON powermanager is designed for:
• collecting
• monitoring
• evaluating
• presenting
• archiving
power data from SENTRON PAC3100, PAC3200 and PAC4200
power monitoring devices, SENTRON 3WL/3VL circuit breakers,
and any Modbus-capable detecting devices.
■ Benefits
• Transparency of power flows The components are optimally coordinated with each other. For
• Exact knowledge of the consumption profile example, special drivers for the SENTRON devices are inte-
grated in the SENTRON powermanager software so that on the
• Increase of power efficiency one hand the power data acquisition can take place without any
• Optimization of power supply contracts great configuration effort and on the other hand the most impor-
• Compliance with contractual terms tant measured values or states are indicated by predefined dis-
plays. This reduces the amount of engineering work.
• Assignment of power costs to cost centers
• Optimization of plant maintenance The SENTRON powermanager software comprises a server/cli-
ent software for the acquisition, processing, presentation and ar-
• Identification of critical plant conditions chiving of power data. These power data are supplied primarily
The SENTRON product family includes not only a power man- by power monitoring devices (PAC) or 3WL/3VL circuit breakers
agement software in the form of SENTRON powermanager but which are connected to the system through Ethernet.
also the matching hardware in the form of the SENTRON PAC
and the SENTRON 3WL/3VL for realizing a complete power
management system.
■ More information
Hardware components of the Power Management System are You can find more information on the Internet at:
dealt with in this chapter, its software components in chapter 13. www.siemens.com/powermanagementsystem
■ Overview
Devices Page Application Standards Used in
Non-residential
Residential
buildings
buildings
Industry
E-counters
PAC1500 three-phase counters 11/6 Measurement of consumption data and EN 50470-1, ✓ ✓ ✓
7KT1 5 E-counters plant capacity utilization in three-phase EN 50470-3
systems of system components, offices EN 62052-23,
or holiday apartments. EN 62053-31
PAC1500 single-phase counters 11/9 For the measurement of kWh in single- EN 50470-1, EN 50470-3, ✓ ✓ ✓
7KT1 53, 7KT1 14 E-counters phase systems, e.g. in industrial plants, EN 62053-31
offices and apartments in apartment
houses
11
• M-Bus
• Modbus RTU
• KNX/EIB
• RS 485
PAC3000 multicounters 11/17 Display of 35 electrical measured values IEC 60051-2, EN 60051-2 ✓ -- ✓
7KT1 31, 7KT1 34 and consumption values in switchgear IEC 61010-1, EN 61010-1
assemblies, infeed or outgoing units. (VDE 0411 T 1)
Easy commissioning due to fault detec- IEC 62053-21, EN 62053-
tion if connected incorrectly. 21 (VDE 0418 T 3-21)
7KT1 391 LAN couplers 11/21 Up-to-date consumption data of multi- IEEE 802 ✓ -- ✓
counters and E-counters available world-
wide using LAN data communication.
Non-residential
Residential
buildings
buildings
Industry
PAC3100 power monitoring 11/26 Display of 30 electrical measured values IEC 61557-12 ✓ -- ✓
devices and consumption values in switchgear
AC/DC power supply unit with assemblies, infeed or tap-off units.
screw connection International standards and multi-lingual
displays for worldwide use.
Control panel flush-mounting instrument
with graphics display, integrated digital
in- and outputs and a RS 485-interface
for the transfer of measured values and
configurations.
PAC3200 power monitoring 11/27 Display of over 50 electrical measured Energy-measurement ✓ -- ✓
devices values for switchgear assemblies, infeed accuracy according to
3 versions: or outgoing feeders. 10 dual-tarif energy IEC 62053
counters for precise energy monitoring
• AC/DC power supply unit with for power draw and feedback.
screw connection
International standards and multi-lingual
• DC power supply unit with extra- displays for worldwide use.
low voltage, screw connection
Control panel flush-mounting instrument
• AC/DC power supply unit with with graphics display, integrated digital
ring terminal lug connection in- and outputs and an integrated
Ethernet interface for the transfer of
measured values and configurations.
Plug-in options module for Modbus RTU
or PROFIBUS DP.
PAC4200 power monitoring 11/28 Display of over 200 electrical measured IEC 61557-12 ✓ -- ✓
devices values for switchgear assemblies, infeed
2 versions: or outgoing feeders. Extensive functions
for precise energy-monitoring for power
• AC/DC power supply unit with draw and feedback and for appraisal of
screw connection network quality.
PAC 4DI/2DO expansion modules 11/31 The SENTRON PAC 4DI/2DO expansion IEC 62053-31 ✓ -- ✓
module is used to expand the SENTRON
PAC4200 power monitoring device to up
to 10 digital inputs and 6 digital outputs.
Non-residential
Residential
buildings
buildings
Industry
Analog measuring devices
7KT1 0 measuring devices 11/32 Voltage and current measurement for IEC 60051-2, ✓ -- ✓
monitoring incoming and outgoing cur- EN 60051-2
rents as well as device currents in order
to prevent plant overload.
11
Time counters for front-panel 11/37 For monitoring operating hours and IEC 60255-6, ✓ ✓ ✓
mounting starting operations for planning preven- EN 60255-6
7KT5 5, 7KT5 6 tative maintenance tasks and prevent- (VDE 0435-301)
ing sudden shutdowns.
Accessories
7KT1 2 current transformers 11/39 Straight-through transformers for instal- IEC 60044-1, ✓ -- ✓
lation in distribution boards and non- EN 60044-1
contact measuring of primary currents. (VDE 0414 T 44-1)
Ideal for combining with switch discon-
nectors, multimeters, multicounters and
E-counters.
7KT9 0 measuring selector switches 11/40 For switching over the phases for volt- ✓ -- ✓
meters and ammeters
■ Overview
The E-counters (power meters) are used to record the amount of
electrical energy exported or imported. Siemens compact
E-counters are designed as modular devices for alternating
current and can be mounted on standard mounting rails. They
comply with the counter standard EN 50470 (Part 1 and 3) and
come with an LCD display.
Three-phases counters are available up to 80 A and in versions
with transformer connections (…/5 A to 10000/5 A).
E-counters store both active and reactive energy, and comply
with accuracy class 1 (for active energy).
All E-counters have a pulse output (S0) and are designed for
2-tariff measurements. The calibrated versions are in
accordance with the Directive 2004/22/EC on measuring instru-
ments.
At the same time the E-counters have an integrated optical inter-
face (IrDA) for connecting communication modules, which
enables their integration in a range of other systems, such as
3-phase counter PAC 1500 (7KT1 543) with direct connection up to 80 A energy management systems.
■ Benefits
• Complies with the new counter standard EN 50470
(Part 1 and 3)
• Easy-to-read LCD display
• Versions calibrated in accordance with the Directive
2004/22/EC on measuring instruments can be used for
invoicing purposes
• Exact recording thanks to accuracy class 1 (for active energy)
• Direct connection up to 80 A;
11 Transformer current connection .../5 A
• Sealable terminal covers
■ Technical specifications
PAC1500 three-phase E-counters 7KT1 543 7KT1 540
7KT1 545
Standards EN 50470-1, EN 50470-3,
EN 62053-23, EN 62053-31
Connection
• Direct connection 80 A --
• Transformer current connection -- .../5 A
General data
• Enclosure, mounting width Acc. to DIN 43880 MW 4
• Mounting Acc. to EN 60715 35 mm
• Mounting height mm 70
Function
• Operating mode Three-phase loads Conductors 2-3-4 3-4
• Storage of setting and counter reading Through (EEPROM) Yes
• Tariff for active and reactive energy T1/T2
Supply (through measuring terminals)
• Rated control supply voltage Un V AC 230
• Voltage range V 184 ... 276
• Rated frequency fn Hz 50
• Rated power dissipation Pv VA (W) ≤ 8 (0.6)
Overload capability
• Voltage Umax Continuous operation: V 480
Phase/phase
1 second: Phase/phase V 800
Continuous operation: Phase/N V 276
1 second: Phase/N V 300
• Current Imax Continuous operation A 80
Short-time operation (for 0.5 s) A -- 120
Short-time operation (for 10 ms) A 2400 --
Display (readout)
• Connection error and phase failure Display of rotating field error PHASE Err
■ Overview ■ Benefits
Digital 7KT1 53 E-counter.
11
2004/22/EC on measuring instruments.
At the same time the E-counters − except version 7KT1 140 −
have an integrated optical interface (IrDA) for connecting com-
munication modules. Integration of the E-counters, e.g. in en-
ergy management systems, is thus possible.
■ Technical specifications
PAC1500 single-phase counters, 7KT1 530 7KT1 531 7KT1 140
direct connection up to 80 A 7KT1 533
Standards EN 50470-1, EN 50470-3, EN 62053-23, EN 62053-31
General data
• Enclosures Acc. to DIN 43880 MW 2
• Mounting Acc. to EN 60715 35 mm
• Mounting height mm 70
Function
• Operating mode Single-phase loads Conductors 2
• Storage of setting and counter reading Through (EEPROM) Yes --
• Rate For active energy T1 T1 + T2 T1
For reactive energy T1 T1 + T2 --
Supply (through measuring terminals)
• Rated control supply voltage Un V AC 230
• Voltage range V 184 ... 276
• Rated frequency fn Hz 50
• Rated power dissipation Pv VA (W) ≤ 8 (0.6)
Overload capability
• Voltage Umax Continuous operation V 276
Short-time operation (for 1 s) V 300
• Current Imax Continuous operation A 80
Short-time operation (for 10 ms) A 2400
11 • Pulse count
• Pulse duration
Pulses/kWh
ms
1000
30 ± 5 30 ± 2
• Required voltage V AC 5 ... 230 ±5 %
V DC 5 ... 300
• Permissible current (pulse on) mA 90
• Permissible current (pulse off, maximum fault current) µA 1
Optical interfaces
• Calibration from the front (accuracy check) LED Pulses/kWh 1000
IR interface
• At the side for connecting communication modules -- Yes --
(M-Bus / Modbus RTU / RS 485 / KNX)
Safety Acc. to EN 50470-1
• For indoor areas Yes
• Overvoltage category 4
• Operational voltage V 300
• Test voltage 1.2/50 µs kV 6
• Flame resistance UL 94 Class V0
Terminal connections
• Lift terminals of main current paths Screw head Z ± Pozidriv PZ2
• Lift terminals for S0 pulse outputs Blade for slotted screw mm x mm 0.8 x 3.5
• Conductor cross-sections of operational current Rigid mm2 1.5 ... 35
and main current paths Flexible, with end sleeve mm2 1.5 ... 35
• Conductor cross-sections for S0 pulse outputs Rigid mm2 0.14 ... 2.5
Flexible, with end sleeve mm2 0.14 ... 2.5
Ambient conditions
• Mechanical environment M1
• Electromagnetic environment E2
• Operating temperature °C -10 ... +55
• Temperature limits for storage and transport °C -25 ... +70
• Relative humidity (without condensation) % ≤ 80
• Vibrations Sinus amplitude at 50 Hz mm ± 0.075
• Degree of protection Installed device IP511)/IP20
Front side/terminals
1)
For installation in a distribution board with at least IP51 degree of
protection.
11
11
7KT1 908
Expansion module Modbus RTU 1 B 7KT1 907 1 1 unit 027 0.050
For connecting PAC1500 E-counters to
RTU Modbus
7KT1 907
Expansion module RS 485 1 B 7KT1 903 1 1 unit 027 0.050
For connecting PAC1500 E-counters via
RS 485 to LAN coupler 7KT1 391
7KT1 903
Expansion module KNX 1 B 7KT1 900 1 1 unit 027 0.050
11
For connecting PAC1500 E-counters to
Instabus KNX
7KT1 900
■ Overview ■ Benefits
• Clear display of all necessary measured values
• All measured values can be read from a distance
• Customized setting of the measured quantities for the stan-
dard display
• Wide range of application thanks to flexible adaptation to
measuring current transformers
• Detection of connection errors during commissioning saves
considerable time when trying to locate faults
• Large, 11 mm high, green 7-segment displays for measured
values makes for easy reading
• Indication of units of measurement directly alongside the re-
lated measured values provide a clear overview.
PAC3000 multimeters
Multimeters are mainly used in power distribution boards for in-
feeds into buildings and plants. They replace the more common
analog voltmeters and ammeters with measuring point change-
over, as well as measuring devices for power outputs and power
factor p.f..
The standard measured quantity to be indicated in the 5 display
fields of the multimeter can be tailored to customer require-
ments. Versions for direct connection (63 A) or for transformers
(/5 A) with adjustable transformer primary current from 5 A to
5000 A, enable a wide range of application.
The green 7-segment displays for the measured values and the
orange indicators of the units of measurement directly alongside
■ Technical specifications
PAC3000 multimeters 7KT1 300 7KT1 301
Standards DIN 43751-1, DIN 43751-2 and EN 61010-1
Supply
• Rated control supply voltage Uc V AC 230
• Primary operating range × Uc 0.8 ... 1.2
• Rated frequency Hz 50
• Frequency ranges Hz 45 ... 65
• Rated power dissipation Pv VA ≤ 10
Overload capability
• Voltage Continuous: Phase/phase V 480
1 second: Phase/phase V 800
Continuous: Phase/N V 276
1 second: Phase/N V 460
• Current Continuous A 76 6
0.5 s A -- 110
10 ms A 1000 --
Measuring inputs
• Connection type Direct Transformer /5 A
• Voltage Ue Phase/phase V 400
Phase/N V 230
• Operating range voltage Phase/phase V 87 ... 400
Phase/N V 50 ... 230
• Current Ie A 63 5
• Operating range current A 0.1 ... 63 0.01 ... 5
• Transformer current Primary current of the transformer A -- 5 ... 5000
Smallest input step A -- 5
• Frequency Hz 50
• Frequency ranges Hz 45 ... 65
7KT1 300
■ More information
Readout data
You can continuously display 5 measured quantities from the fol-
lowing 23 options.
No. Measured value Display Unit Assign-
ment
1 Active power D1 W L1
2 Voltage D1 V L1
3 Current D1 A L1
4 Apparent power D1 VA L1
11 5
6
P.f.
Voltage
D1
D1
P.f.
V
L1
L1 – L2
7 Active power D2 W L2
8 Voltage D2 V L2
9 Current D2 A L2
10 Apparent power D2 VA L2
11 P.f. D2 P.f. L2
12 Voltage D2 V L2 – L3
13 Active power D3 W L3
14 Voltage D3 V L3
15 Current D3 A L3
16 Apparent power D3 VA L3
17 P.f. D3 P.f. L3
18 Voltage D3 V L3 – L1
19 Active power D1, D2, D3, D5 W ΣL
20 Apparent power D1, D2, D3, D5 VA ΣL
21 Reactive power D5 var ΣL
22 Frequency D4 Hz ΣL
23 P.f. D1, D2, D3, D4 P.f. ΣL
2 set values are also indicated:
24 Transformer setting D5 CT/A /5
25 Transformer setting CT/A 5 ... 5000
■ Overview ■ Benefits
• Clear display of all necessary measured values
• All measured values can be read from a distance
• Customized setting of the measured quantities for the stan-
dard display. Fast display of all measured quantities over op-
erator buttons
• Wide range of application thanks to flexible adaptation to
measuring current transformers
• Detection of incorrect connections during installation
• Communication with LAN or Modbus RTU enables integration
in an energy management system
Multicounter PAC3000
Multicounters are mainly used in power distribution boards for in-
feeds into buildings and plants. They replace the more common
analog voltmeters and ammeters with measuring point change-
over, as well as measuring devices for power outputs and power
factor p.f..
The standard measured quantity to be indicated in the 6 display
fields of the PAC3000 multicounter can be tailored to customer
requirements. The measured values of all measured quantities
can also be displayed quickly and easily over the operator but-
tons. Versions for direct connection (63 A) or for transformers
(/5 A) with adjustable transformer primary current from 5 to
5000 A, enable a wide range of application.
The green 7-segment displays for the measured values and the
orange indicators of the units of measurement directly alongside 11
the measured values make for easy reading.
■ Technical specifications
PAC3000 multicounters without communication interface 7KT1 310 7KT1 311
PAC3000 multicounters with RS 485 interface (Modbus RTU, for LAN couplers) 7KT1 340 7KT1 341
Standards EN 61010-1, EN 62053-21, -23, -31
Supply
• Rated control supply voltage Uc V AC 230
• Primary operating range × Uc 0.8 ... 1.2
• Rated frequency Hz 50
• Frequency ranges Hz 45 ... 65
• Rated power dissipation Pv VA ≤ 10
Overload capability
• Voltage Continuous: Phase/phase V 480
1 second: Phase/phase V 800
Continuous: Phase/N V 276
1 second: Phase/N V 460
• Current Continuous A 76 6
0.5 s A -- 110
10 ms A 2000 --
Measuring inputs
• Connection type Direct Transformer /5 A
• Voltage Ue Phase/phase V 400
Phase/N V 230
- Operating range voltage Phase/phase V 87 ... 480
Phase/N V 50 ... 276
• Current Ie A 63 5
- Operating range current A 0.3 ... 63 0.012 ... 5
• Transformer current Primary current of the transformer A -- 5 ... 5000
Smallest input step A -- 5
• Frequency Hz 50
- Operating frequency range Hz 45 ... 65
■ More information
Readout data
You can continuously display 6 measured quantities from the fol-
lowing 35 options.
No. Measured value Display Unit Assignment
1 Active power D1 W L1
2 Voltage D1 V L1
3 Current D1 A L1
4 Apparent power D1 VA L1
5 P.f. D1 P.f. L1
6 Voltage D1 V L1 – L2
7 Active power D2 W L2
8 Voltage D2 V L2
9 Current D2 A L2
10 Apparent power D2 VA L2
11 P.f. D2 P.f. L2
12 Voltage D2 V L2 – L3
13 Active power D3 W L3
14 Voltage D3 V L3
15 Current D3 A L3
16 Apparent power D3 VA L3
17 P.f. D3 P.f. L3
18 Voltage D3 V L3 – L1
19 Temperatures D6 °C –
20 Current, N conductor D6 A ∑L
21 Active power D4 W ∑L
22 Reactive power D5 var ∑L
23 Apparent power D5 var ∑L
24 Frequency D6 Hz ∑L
11 25
26
P.f.
Active energy rate 1
D1, D2, D3, D6
D4
P.f.
Wh
∑L
∑L →
27 Active energy rate 2 D4 Wh ∑L →
28 Active energy rate 1 D4 Wh ∑L ←
29 Active energy rate 2 D4 Wh ∑L ←
30 Reactive energy rate 1 D5 varh ∑L, ind.
31 Reactive energy rate 2 D5 varh ∑L, ind.
32 Reactive energy rate 1 D5 varh ∑L, chap.
33 Reactive energy rate 2 D5 varh ∑L, chap.
34 Apparent energy rate 1 D5 VAh ∑L
35 Apparent energy rate 2 D5 VAh ∑L
2 set values are also indicated:
36 Transformer setting D4 CT/A /5
37 Transformer setting D5 CT/A 5 ... 5000
All the measured values are transmitted via LAN.
■ Overview ■ Application
Usable E-counters and multicounters
Following E-counters and multicounters can be connected
to the LAN coupler:
Order No.
Energy counters
Digital 3-phase counters
• PAC1500, for direct connection 80 A, double rate 7KT1 543
• PAC1500, for direct connection 80 A, double rate, 7KT1 545
calibrated version
• PAC1500, for transformer connection .../5 A, double 7KT1 540
rate
• For transformer connection .../5 A, double rate, 7KT1 542
calibrated version
• For direct connection 125 A, double rate 7KT1 546
• For direct connection 125 A, double rate, 7KT1 548
calibrated version
• For direct connection 63 A, double rate 7KT1 520
7KT 391 LAN couplers
• For transformer connection .../5 A, double rate 7KT1 521
A LAN coupler supports worldwide data recall from multi- Digital 1-phase counters
counters and E-counters over a LAN link to the Internet.
• PAC1500, for direct connection 80 A, double rate 7KT1 531
Up to 30 devices can be linked with a LAN coupler. In turn, the • PAC1500, for direct connection 80 A, double rate, 7KT1 533
LAN coupler is connected to a LAN. calibrated version
Multicounters
Data communication between the LAN coupler and the PC takes
place using the TCP/IP protocol. • PAC3000, for direct connection 7KT1 340
• PAC3000, for transformer connection .../5 A 7KT1 341
■ Benefits • For transformer connection .../5 A 7KT1 342
■ Technical specifications
7KT1 391
Standards IEEE 802.3 AS, IEC 60950, EN 61000-6-2, EN 61000-6-3
General data
• Enclosures Acc. to DIN 43880 4 modules
• Mounting Acc. to EN 60715 Mounting onto standard mounting rail (35 mm)
• Mounting height mm 70
Supply
• Rated power dissipation Pv VA ≤ 10
• Rated control supply voltage Uc V AC 230
• Primary operating range × Uc 0.9 ... 1.10
• Rated frequency Hz 50
• Frequency ranges Hz 45 ... 65
Function
• System start Automatic upon switching on
• LAN server identification Over the IP address of the PC
• Transmission rate Limitation by LAN Mbit/s 100
• Operating system Windows XP/Vista/7
• Browser IE 7, 8; Mozilla Firefox 3.09 / 3.5.3 / 3.6; Opera 9.64 / 10 / 10.5;
Safari 3.2.2 /4.0.5; Google Chrome 3.0.195.27.
LAN interface
• HW interface Connection RJ 45
• SW interface TCP/IP
Interface to the measuring instruments
• HW interface RS 485 terminals Number 3 (+/-/shielded twisted pair)
• Line Version STP (shielded twisted pair)
Minimum cross-section mm2 2 × 0.2 or 2 x AWG 24
Maximum line capacity pF/m < 50
Impedance W 100
Maximum overall cable length m ≤ 1200
Type of installation Serial
Measuring instruments can be connected Number 30
directly
Safety according to IEC 60950
• Pollution degree 2
• Overvoltage category III
11
• Operational voltage V 300
• Enclosure material group II
• Clearances mm ≥ 4.0
• Creepage distances ≥ 4.5
• Test pulse voltage 1.2/50 μs kV 4
50 Hz, 1 min kV 4
• Flame resistance Acc. to UL 94 Class V0
• Fire load kJ 2977.8
Terminals
• Lift terminals ±screw (Pozidriv) PZ1
• Conductor cross-sections of main current Rigid mm2 0.75 ... 6
paths
2
Flexible with sleeve mm 0.75 ... 6
Environmental conditions
• Temperatures In operation °C -10 ... +55
Storage and transport °C -25 ... +70
• Relative humidity In operation % ≤ 80
• Vibrations Sinus amplitude at 50 Hz mm ± 0.25
• Safety class acc. to IEC 60950 III
• Degree of protection Installed device front side (terminals) IP20
■ Overview ■ Benefits
Measuring precisely with SENTRON PAC3100/3200/4200 SENTRON PAC General
The common features of all power monitoring devices in the
SENTRON PAC series:
• Simple mounting and commissioning
• High IP65 degree of protection (front side, when installed) per-
mits usage in extremely dusty and wet environments
• Intuitive operation using 4 function buttons and multilingual
plain text displays
• Easy adaptation to different systems using integrated and op-
tional
- Digital inputs and outputs
- Communication interfaces
• Worldwide use
- Min. 8 languages
- International approvals
- Developed and tested to European and international stan-
dards
• Low mounting depth
The SENTRON PAC power monitoring devices: SENTRON PAC3200 and SENTRON PAC4200
PAC3200 (left), PAC3100 (center) and PAC4200 (right)
Additional performance characteristics of the SENTRON
The power monitoring devices of the SENTRON PAC series are
PAC3200 and SENTRON PAC4200:
used to measure and indicate all relevant network parameters in
low-voltage power distribution. They can be used for single- • Precise energy recording
phase measurements as well as for multiphase measurements in • Versatile system integration
3 and 4-conductor networks (TN, TT, IT). - Integrated Ethernet interface
Power values for main distribution boards, electrical feeders or - Optional communication modules available
individual loads are recorded precisely and reliably, and impor- - Multifunctional digital inputs and outputs
tant measured values are supplied in addition for assessing the - Limit value monitoring
state of the plant and the quality of the network. • Can be connected directly to power supply networks up to
690 V AC (UL-L) , CATIII without voltage transformers.
More information
• Easy-to-use configuration software included as standard
11
SENTRON PAC4200
More information is available on the Internet at
www.siemens.com/powermanagementsystem Additional performance characteristics of the SENTRON
PAC4200:
• Monitoring the plant status and the system quality
- Basic information for evaluating network quality
- Logging of plant history in the form of operation, control and
system-related events
• Recording of the power range through power averaging (load
profile)
• Daily energy meters for apparent, active and reactive energy
across 365 days for cut-off date assessment
• Detection of gas, water, compressed air or other energy
sources via pulse counter to the digital inputs
• Can be expanded using modules to up to 10 digital inputs and
6 digital outputs
• Meters for apparent, active and reactive energy for the precise
detection of the power consumption of a partial process or
manufacturing process
• 10/100 Mbit/s Ethernet interface with gateway function for the
easy connection of devices with serial RS485 interface via ex-
pansion module PAC RS485 to an Ethernet network
• Comprehensive convenience indicators, such as user-defined
displays, bar and status indicators, phase diagram and list
and histogram graphics
• Satisfies the accuracy requirements of class 0.2S high-preci-
sion meters used by power supply companies according to
IEC 62053-22, which are normally reserved for exacting indus-
trial applications
NSG0_00238a
SIMATIC S7 environment.
System integration using block libraries
11 Optionally available block libraries make it easy to integrate the SENTRON VL Power monitoring devices
SENTRON WL
power monitoring devices in the SIMATIC PCS 7 process control
system and the SCADA-System SIMATIC WinCC. Together with Connecting Modbus-RTU devices to a power management system
the faceplates as user interface for SENTRON PAC3200, the through PAC4200
driver blocks and diagnostics blocks in the control system en-
able the operating and monitoring of technologically important
values and functions of the measuring devices in the respective
target system.
Faceplates
Industrial Ethernet
PROFIBUS
PROFIBUS
■ Technical specifications
■ Accessories
Version DT Order No. Price PU PS* PG Weight
per PU (UNIT, per PU
SET, M) approx.
kg
SENTRON PAC TMP
Adapter for mounting on standard A 7KM9 900-0YA00-0AA0 1 1 unit 133 0.105
mounting rail
7KM9 900-0YA00-0AA0
11
■ More information
Current transformers Software components
Suitable current transformers can be found For more information about the software components
• in chapter 2 "Molded Case Circuit Breakers" see chapter 13 and on the Internet at
• in the Industry Mall, section "Industry Automation and Drive www.siemens.com/powermanagementsystem
Technologies" --> "Low-Voltage Power Distribution and
Electrical Installation Technology" --> "Protection Devices"
--> "Molded Case Circuit Breakers"
--> "3VL Molded Case Circuit Breakers"
--> "3VL Molded Case Circuit Breakers up to 1600 A"
--> "Accessories and Spare Parts"
7KM2 111-1BA00-3AA0
SENTRON PAC3200 Ring terminal lug
connection
Control panel flush-mounting instrument A 7KM2 112-0BA00-2AA0 1 1 unit 133 0.325
96 mm x 96 mm
Cable lug terminals for connecting current
and voltage
AC/DC universal power supply unit: 11
UAUX:
95…240 V AC ±10 %, 50/60 Hz
110…340 V DC ±10 %
Measuring inputs
Ue: max. 3 AC 690/400 V, 50/60 Hz
7KM2 112-0BA00-2AA0 Ie: /1 A or /5 A
■ Accessories
Version DT Order No. Price PU PS* PG Weight
per PU (UNIT, per PU
SET, M) approx.
kg
SENTRON PAC TMP
Adapter for mounting on standard A 7KM9 900-0YA00-0AA0 1 1 unit 133 0.105
mounting rail
7KM9 900-0YA00-0AA0
■ More information
Current transformers Software components
Suitable current transformers can be found Software for PAC3200 see chapter 13, section "Configuring,
• in chapter 2 "Molded Case Circuit Breakers" visualizing and controlling with SIMATIC"
• in the Industry Mall, section "Industry Automation and Drive For more information about the software components
Technologies" --> "Low-Voltage Power Distribution and see chapter 13 and on the Internet at
Electrical Installation Technology" --> "Protection Devices" www.siemens.com/powermanagementsystem
--> "Molded Case Circuit Breakers"
--> "3VL Molded Case Circuit Breakers"
--> "3VL Molded Case Circuit Breakers up to 1600 A"
--> "Accessories and Spare Parts"
Measuring inputs
Ue: max. 3 AC 690/400 V, 50/60 Hz
7KM4 112-0BA00-3AA0 Ie: /1 A or /5 A
SENTRON PAC4200 Ring terminal lug
connection
Control panel flush-mounting instrument A 7KM4 212-0BA00-2AA0 1 1 unit 133 0.450
96 mm x 96 mm
Cable lug terminals for connecting current
and voltage
AC/DC universal power supply unit:
UAUX:
95…240 V AC ±10 %, 50/60 Hz
110…340 V DC ±10 %
Measuring inputs
Ue: max. 3 AC 690/400 V, 50/60 Hz
7KM4 112-0BA00-2AA0 Ie: /1 A or /5 A
■ Accessories
11 Version DT Order No. Price
per PU
PU
(UNIT,
PS* PG Weight
per PU
SET, M) approx.
kg
SENTRON PAC TMP
Adapter for mounting on standard A 7KM9 900-0YA00-0AA0 1 1 unit 133 0.105
mounting rail
7KM9 900-0YA00-0AA0
■ More information
Current transformers Software components
Suitable current transformers can be found For more information about the software components
• in chapter 2 "Molded case circuit breakers" see chapter 13 and on the Internet at
• in the Industry Mall, section "Industry Automation and Drive www.siemens.com/powermanagementsystem
Technologies" --> "Low-Voltage Power Distribution and
Electrical Installation Technology" --> "Protection Devices"
--> "Molded Case Circuit Breakers"
--> "3VL Molded Case Circuit Breakers"
--> "3VL Molded Case Circuit Breakers up to 1600 A"
--> "Accessories and Spare Parts"
■ Overview
The PAC PROFIBUS DP expansion module has the following
features:
• Pluggable PROFIBUS DP communication modules for
SENTRON PAC3200 and PAC4200 power monitoring devices
• Parameterizable from the front of the device or using parame-
terization software
• Using PROFIBUS DPV1, data can be transferred in both cyclic
and acyclic modes
• Easy engineering thanks to integration into SIMATIC STEP 7
and/or simple integration via GSD file for other programming
systems
• Optimum use of process image of a control for selection of in-
dividual measurment values for cyclical transfer
• All baudrates from 9.6 kbit/s up to 12 Mbit/s are supported
• Connection through 9-pole Sub-D connector according to
IEC 61158
• No external auxiliary power necessary
SENTRON PAC PROFIBUS DP expansion modules
• Additional display via the device display and via LEDs on the
module
■ Application
The SENTRON PAC PROFIBUS DP communication module is All individual measurement variables supplied by the SENTRON
plugged onto the rear of the power monitoring device. The de- PAC multifunction measuring instruments are selected and cycli-
vice identifies the module automatically and presents the param- cally transmitted by means of the GSD file. This permits the op-
eters of relevance for this module for selection in the parameter- timum use of the PROFIBUS Master process image.
ization menu.
11
Version DT Order No. Price PU PS* PG Weight
per PU (UNIT, per PU
SET, M) approx.
kg
PAC PROFIBUS DP
Expansion module for A 7KM9 300-0AB00-0AA0 1 1 unit 133 0.045
SENTRON PAC3200 and PAC4200
(PROFIBUS DP V1)
7KM9 300-0AB00-0AA0
■ Overview
The SENTRON PAC RS485 expansion module has the following
features:
• PAC RS485 plug-in communication module for SENTRON
PAC3200 and PAC4200 power monitoring devices
• Parameterizable from the front of the device or using parame-
terization software
• Support for the Modbus RTU protocol
• Plug and play
• Baud rates 4.8 / 9.6 / 19.2 and 38.4 kbit/s are supported
• Connection by means of 6-pole screw terminals
• No external auxiliary power necessary
• Status indication by LED on the module
■ Application
The SENTRON PAC RS485 communication module is plugged In connection with the SENTRON PAC3200 and 4200 multifunc-
into the back of the PAC power monitoring device. tion measuring instruments, the Modbus RTU protocols are sup-
The device identifies the module automatically and presents the ported with baud rates of 4.8/9.6/19.2 and 38.4 kBd.
parameters of relevance for this module for selection in the pa-
rameterization menu. The state of the module is indicated by the The SENTRON PAC RS485 expansion module is required for the
integrated LED. gateway function of the PAC4200 to achieve simple devices with
RS485 interface, such as the PAC3100, via Ethernet
(Modbus TCP).
7KM9 300-0AM00-0AA0
■ Overview
The SENTRON PAC 4DI/2DO expansion module is used to ex-
pand the SENTRON PAC4200 power monitoring device to up to
10 digital inputs and 6 digital outputs.
It offers the following features:
• Up to two 4DI/2DO modules can be plugged onto a PAC4200.
• The 4DI/2DO modules mean that the internal digital inputs and
outputs can be expanded by up to 8 inputs and 4 outputs.
• The 4DI/2DO expansion modules can be parameterized via
the front of the device or via the SENTRON powerconfig con-
figuration software.
• The digital inputs can be used without external voltage
sources. They are self-powered.
• All functions of the integrated multifunctional inputs/outputs on
the PAC4200 are also available in the 4DI/2DO expansion
module.
• Inputs and outputs can be used as an S0 interface conforming
to IEC 62053-31.
SENTRON PAC 4DI/2DO expansion modules • The connection is made via a 9-pole screw terminal.
• No external auxiliary power supply is required.
■ Application
There are many possible uses for the SENTRON PAC 4DI/2DO • Monitoring of multiple, single switches with auxiliary contacts
expansion module. Some of these include: via PAC4200
• Connection of up to 10 energy counters with pulsed output • Use of the digital outputs as pulse output for active and reac-
(S0) for detecting the consumption of other energy-carriers tive energy
e.g. gas, water or compressed-air consumption • Use of the digital outputs as outputs for switching operations
• Integration of other media into energy management system and/or for time synchronization.
■ Benefits
Digital inputs Digital outputs 11
Consumption recording and evaluation The digital outputs offer a high degree of flexibility as they can
• Cost-effective energy counters can be used as media coun- be used as follows:
ters. • For status display
• It is not necessary to replace meters as the basic power me- - for a limit value violation
ters with pulse output already installed can be used. - for a direction of rotation
- for an operating state on the PAC4200
• Other media can be easily integrated into a power manage-
ment system. • As remote-controlled switching outputs
• Increase the transparency of the power flows, because the • For synchronization of the periods load profile detection in
power consumption of a sub-process or the product-related other devices
power consumption can be detected and evaluated, for ex- • For signaling power measurement
ample. - related active energy
• Pulse counters can be easily assigned using user-definable - supplied active energy
displays. - related reactive energy
- supplied reactive energy
Status monitoring
The digital inputs reduce the wiring outlay thanks to the effective
integration of basic protection equipment and switchgear.
7KM9 200-0AB00-0AA0
■ Overview ■ Benefits
• The 7KT1 020 ammeters can be equipped with changeable
scales for primary currents of 60, 150 or 400 A AC, depending
on the transformer ratio of the installed current transformer.
The changeable scales are included in delivery. This ensures
universal application
• Permanent overload up to 20 % does not damage the device.
Protection for your plant.
■ Technical specifications
7KT1 000 7KT1 01. 7KT1 020
Standards EN 60051-2
Measuring ranges
• Direct measurement V AC 0 ... 500 -- --
A AC -- 0 ... 25 --
A AC -- 0 ... 40 --
11
A AC -- 0 ... 60 --
• Transformer measurement A AC -- -- 0 ... 150/5
Max. permissible measuring frequency Hz 45 ... 65
Display Pointer
Measuring accuracy at 23 ±1 °C % ±1.5 ±3 ±1.5
Rated operational power Ps VA <2 < 1.1
Temperature influence %/°C ±0.03
Overload capability Continuous 1.2 × Umeas 1.2 × Imeas
Short-time for 1 s 2 × Umeas 10 × Imeas
Test voltage 50 Hz, 1 min kV >2
Terminals ±screw (Pozidriv) 1 2 1
Conductor cross-sections Rigid, max. mm2 1 × 6/2 × 4 1 × 25/2 × 16 1 × 6/2 × 4
Flexible, with end sleeve, min. mm2 0.75 0.75
Permissible ambient temperature °C -10 ... +55
Degree of protection IP20, with connected conductors
■ Overview ■ Benefits
• The ammeters have 14 measuring ranges from 0 A to 20 A to
0 A to 999 A, which can be set using a coding switch. This
ensures universal application.
■ Technical specifications
7KT1 110 7KT1 120
Standards DIN 43751-1, -2
Rated control supply voltage Uc
Primary operating range
V AC
× Uc
230
0.9 ... 1.15
11
Rated frequency Hz 45 ... 65
Rated operational power Ps VA <2
Measuring range
• Voltage Direct measurement V AC 12 ... 600 --
• Current Direct measurement A AC -- 0.4 ... 20 direct
Transformer measurement A AC -- 0.1 ... 1000/5
Display 3 LEDs red; height 10 mm
• Voltage > 600 V HHH --
< 12 V -- -- -- --
• Current Direct > 20 A -- HHH
Transformer > 5 A -- HHH
Direct < 0.4 A -- -- -- --
Transformer < 0.1 A -- -- -- --
Measuring cycle /s 4 times
Measuring accuracy At 23 °C % ±0.5 ±1 digit
Temperature influence %/°C ±0.03
Overload capability
• Voltage Continuous V 720 --
Short-time for 1 s V 780 --
• Current Continuous, direct A -- 22
Continuous, transformer A -- 5.5
Short-time for 1 s, direct A -- 200
Short-time for 1 s, transformer A -- 50
Electrical isolation
• Clearances mm ≥3 ≥ 1.5
• Creepage distances in the device mm ≥ 4.3 ≥ 2.1
• Creepage distances on the printed board Printed boards not installed mm ≥ 3.0 ≥ 1.5
Test voltage 50 Hz, 1 min kV 2.2 1.35
Terminals ±screw (Pozidriv) 1
Conductor cross-sections Rigid, max. mm2 1 × 6/2 × 4
Flexible, with end sleeve, min. mm2 0.75
Permissible ambient temperature °C -10 ... +55
Degree of protection IP20, with connected conductors
■ More information
Range selector switch for 7KT1 120 digital ammeter
1234
Direct measurement
0000 20 A AC
0 Transformer measurement
11 1 2 3 4 1
1000
0100
25/5 A AC 0 0 0 1
40/5 A AC 1 0 0 1
200/5 A AC
250/5 A AC
1100 50/5 A AC 0 1 0 1 400/5 A AC
I2_00183c
0010 60/5 A AC 1 1 0 1 500/5 A AC
1010 80/5 A AC 0 0 1 1 600/5 A AC
0110 100/5 A AC 1 0 1 1 800/5 A AC
1110 150/5 A AC 0 1 1 1 999/5 A AC
■ Overview
and monitoring of production sequences, maintenance cycles
and warranty times.
As well as the proven electromechanical time and pulse coun-
ters for mounting in distribution boards, we also supply digital
time and pulse counters.
The fields of application for both counter types are very diverse,
such as the recording of operating hours of machines, systems
or building management systems, as well as pulse counting for
general volume flow counting, registration of starting frequen-
cies, starting cycles or production quantities in systems and ma-
chines.
■ Benefits
• Time and pulse counters help to plan maintenance intervals,
which safeguard and ensure high plant availability
• Versions without zero position and with electric or manual zero
position for all applications.
Time counters: Left: electromechanical, right: Electronic • Flexible application of the digital counters for power supplies
Time and pulse counters are used for the reliable monitoring of of 12 V to 150 V DC and 24 V to 240 V AC in a single device.
production and service times, which enables the exact planning
■ Technical specifications
7KT5 801 7KT5 802 7KT5 803 7KT5 804 7KT5 806 7KT5 807
Standards EN 60255-6; UL 863
Approvals UL 863, UL File No. E300537, CSA C22.2 No. 6 and 55
Rated control supply voltage Uc V AC -- 24 115 230 115 230
V DC 12 ... 24 --
Primary operating range At 50/60 Hz × Uc 0.9 ... 1.1
Rated frequency Hz -- 50 60
11
Rated power dissipation Pv VA <1 <2
Method of operation Counting of Hours
Display Drum-type register h 00000.00
Terminals ± screw (Phillips) 1
Conductor cross-sections Rigid mm2 1.5
Flexible, with end sleeve, min. mm2 0.75
Permissible ambient temperature °C -10 ... +70
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Safety class Acc. to EN 61140 II
Permissible humidity % < 80
7KT5 811 7KT5 812 7KT5 814 7KT5 821 7KT5 822 7KT5 823 7KT5 833
Standards EN 60255-6; UL 863
Approvals UL 863, UL File No. E300537, CSA C22.2 No. 6 and 55
Rated control supply voltage Uc V AC -- 24 230 24 ... 240
V DC 12 ... 24 -- -- 12 ... 150
Primary operating range At 50/60 Hz × Uc 0.9 ... 1.1
Rated frequency Hz -- 50/60
Rated power dissipation Pv VA <1 <2 <1
Method of operation Counting of Pulses Hours Pulses
Display Drum-type register 0000000 -- --
LCD h -- 000000.0 --
-- -- 0000000
Counting frequency Hz 10 -- 10
Pulse duration ms 50 -- 50
Resetting Electrical -- Yes
Mechanical -- Yes
Terminals ± screw (Phillips) 1
Conductor cross-sections Rigid mm2 1.5
Flexible, with end sleeve, min. mm2 0.75
Permissible ambient temperature °C -10 ... +70
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Safety class Acc. to EN 61140 II
Permissible humidity % < 80
■ More information
Time counters count the time in hours with an accuracy of two
decimal places (hundredths of hours). The pulse counter adds
the number of pulses, e.g. the making operations of devices.
A power supply is required at terminals 1 and 3 of the electronic
counters so that the device can constantly display the measured
values. Once terminal 3 is supplied with voltage (for DC "+"), the
counting procedure starts. If terminal 4 is supplied short-time
with voltage (for DC "+"), the counter is reset.
In the case of electronic counters, the counting result is saved
indefinitely in the event of a power failure (EEPROM). On recov-
ery of the power, the counting is continued from the saved value.
As well as a modern design, the electronic counter has a 7-digit
LCD, which can be reset electrically or manually.
■ Overview
Time and pulse counters for control cabinets, control and me-
chanical engineering are used, e.g. in boilers, machine tools or
compressors. The pulse counters count the starting frequencies.
This supports planning for preventative maintenance.
In-time and regular maintenance is the best protection against
unexpected shutdowns.
■ Benefits
• Time and pulse counters help to plan maintenance intervals,
which safeguard and ensure high plant availability.
■ Technical specifications
7KT5 500 7KT5 501 7KT5 502 7KT5 503 7KT5 504 7KT5 505
Standards EN 60255-6
Rated control supply voltage Uc V AC -- 115 230 115 230 24
V DC 10 ... 80 --
Primary operating range × Uc 0.9 ... 1.1
Rated frequency Hz -- 50 60 50
Rated power dissipation Pv VA <1 0.2 1.8 0.9 1.8 0.2
Method of operation Counting of Hours
Display Drum-type register h 00000.00
Pulse duration Pulse length, pulse interval ms 50
Front-panel mounting
• Without masking frame
Switchboard cutout
mm × mm 45.2 × 45.2+0.3
11
55 mm × 55 mm
• With masking frame Ø mm 50.2+0.3
55 mm × 55 mm
Terminals ± screw (Phillips) 1
Conductor cross-sections Rigid mm2 1.5
Flexible, with end sleeve, min. mm2 0.75
Permissible ambient temperature °C -10 ... +70
Degree of protection Acc. to EN 60529
• Front panel IP65
• Installation with seal IP43
• Terminals IP20, with connected conductors
Safety class Acc. to EN 61140 II
Permissible humidity % < 93
7KT5 600 7KT5 601 7KT5 602 7KT5 603 7KT5 604
Standards EN 60255-6
Rated control supply voltage Uc V AC -- 115 230 115 230
V DC 10 ... 50 --
Primary operating range × Uc 0.9 ... 1.1
Rated frequency Hz -- 50 60
Rated power dissipation Pv VA <1
Method of operation Counting of Hours
Display Drum-type register h 00000.00
Pulse duration Pulse length, pulse interval ms 50
Front-panel mounting Switchboard cutout mm × mm 68+0.5 × 68+0.5
Terminals ± screw (Phillips) 1
Conductor cross-sections Rigid mm2 1.5
Flexible, with end sleeve, min. mm2 0.75
Permissible ambient temperature °C -10 ... +70
Degree of protection Acc. to EN 60529
• Front panel IP52
• Terminals IP00
Safety class Acc. to EN 61140 II
Permissible humidity % < 93
11 ductors
■ Overview ■ Benefits
This 3-phase current transformer can be used in distribution • The current transformer has accuracy class 1 in accordance
boards according to DIN 43880. The measuring leads are routed with EN 60044-1. This value is better than most measuring de-
vertically through the standard mounting rail. vices in this area of application.
This type of current transformer is suitable for supply systems or • The versions designed for a transformer ratio of 60/5 A,
outgoing conductors in connection with the installation of a 5TE8 100/5 A and 150/5 A enable an even broader range of appli-
switch or a 5TE1 disconnector, as the primary connecting leads cations.
do not have to be interrupted.
The current transformer is designed for cables of up to 13 mm in
diameter, e.g. H07V-R with 50 mm2 conductor cross-section.
■ Technical specifications
7KT1 200 7KT1 201 7KT1 202
Standards EN 60044-1
Secondary rated current strength A 5
Accuracy class Cl. 1
Rated power VA 1.25 2.5 3.75
Rated frequency fn Hz 50/60
Thermal current limit Ith Short-time A 60 × Ie
Thermal continuous current A 1 × Ie
Overcurrent limit factor FS 5
Rated impulse withstand voltage Uimp kV >3
Creepage distances and clearances mm >3
Rated operational voltage Ue V AC 720
Rated operational current Ie A AC 3 × 60 3 × 100 3 × 150
Terminals ±screw (Pozidriv) PZ 1
Conductor cross-sections
- Rigid mm2 0.5 ... 4
- Flexible, with end sleeve mm2 0.5 ... 2.5
Permissible ambient temperature °C -5 ... +60
11
Resistance to climate Acc. to EN 60068-1 20/60/4
■ Overview ■ Benefits
Measuring selector switches are used as CO contacts of the • The devices have a rated insulation voltage of 660 V. This per-
phases for voltages and currents in three-phase systems for volt- mits use in many systems.
meters and ammeters.
The design of these switches is adapted to match the modular
installation devices. They support use in compliance with
EN 60947-3.
11
Monitoring Devices
12/2 Introduction
Transfer Switches
12/5 SENTRON Transfer Control Devices
for ATSE
12
Monitoring Devices
Introduction
■ Overview
Devices Page Field of application Standards Used in
Non-residential
Residential
buildings
buildings
Industry
Transfer switches
SENTRON transfer control devices 12/5 The SENTRON ATC5300, equipped with IEC 60947-6-1 ✓ ✓ ✓
for ATSE two motor-driven circuit breakers,
serves as a transfer system that auto-
matically or manually switches between
two power supply systems in low-volt-
age power distribution applications.
Priority switches 12/17 For a reduction of the connection fee in IEC 60669; -- ✓ --
accordance with German Federal Reg- BTO § 6 Section 4
ulations on Tariffs when used in systems
with electric storage heaters where the
continuous-flow heaters are switched
with priority.
Monitoring Devices
Introduction
Non-residential
Residential
buildings
buildings
Industry
Phase and phase sequence monitors 12/19 For the visual signaling of phase failures IEC 60255 -- -- ✓
or phase sequences in three-phase
systems.
The phase sequence is arbitrary. The
device is also suitable for 1, 2 or
3-phase operation.
Insulation monitors for industrial 12/20 To increase system availability and IEC 60255; -- -- ✓
applications operating safety through continuous IEC 61557
monitoring of the isolation resistance in
ungrounded direct voltage or alternat-
ing voltage networks.
Fault signaling units 12/31 Evaluation and display of fault alarms IEC 60255 ✓ -- ✓
and alarm signals for monitoring indus-
trial plants and control systems.
With 4 inputs and connections for
39 expansion fault signaling units.
Level relays 12/33 Control of liquid levels in containers with IEC 60255 ✓ -- ✓
3 electrode connections for 1-step and
2-step level control. High immunity to
interference of the measuring circuit
isolated from the system.
Monitoring Devices
Introduction
Non-residential
Residential
buildings
buildings
Industry
Line circuit relays 12/35 For disconnecting the voltage or field IEC 60255 -- ✓ --
circuit of unused lines when loads are
disabled.
12
monitoring in the event of valve closure
or dry runs.
Thermistor motor protection relays 12/41 For the prevention of thermal motor IEC 60255 -- -- ✓
overloads, e.g. due to high switching
frequency, single-phasing, disabled
cooling or excessive ambient tempera-
tures.
With detection of wire breaks in the sen-
sor circuit.
Monitoring Devices
Transfer Switches
SENTRON transfer control devices for ATSE
■ Overview
Mode of operation
The SENTRON ATC5300 controls the transfer between the main
and standby power supplies fully automatically, while talking into
consideration the set limit values and delay times. It detects
fluctuations occurring in the main power supply quickly and
switches to the standby power supply. The control device only
switches to the standby power supply after it has ensured that
the standby supply is delivering the required power supply qual-
ity. The devices switches back to the main power supply taking
into consideration the set parameters once the required power
supply quality is available again. If the standby power supply
and/or the main power supply is fed by a generator, the control
device also offers a wide range of settings, such as a generator
lead time, generator delay time, and generator start test at spec-
ified times.
The SENTRON ATC5300 can control air circuit breakers, com-
pact molded case circuit breakers, switch disconnectors or con-
tactors. The circuit breakers are controlled via the related motor-
ized operating mechanisms.
Setting parameters and monitoring using
SENTRON ATC SOFTWARE
SENTRON ATC5300 network switchover controls
In addition to operation and parameterization on-site, you can
Automatic system transfer with the SENTRON ATC5300 also monitor and set the parameters of the controller using the
The SENTRON ATC5300, equipped with two motor-driven circuit SENTRON ATC software. The software offers a high level of con-
breakers, serves as a transfer system that automatically or man- venience and quick access to all device settings, e.g. complex
ually switches between two power supply systems in low-voltage settings which occur when connecting generators.
power distribution applications. Measurement variables
In particular, the SENTRON ATC5300 is deployed everywhere The SENTRON ATC5300 records and monitors the following
where a power failure is especially critical, e.g. in hospitals, in measurement variables:
conjunction with UPS systems, and for industrial processes.
Measured variables Default setting Limit value setting Delay time Can be deactivated
Rated system voltage Un V AC 100 ... 690 70 % ... 98 % (75 % ... 100 %) 1) 0.1 s ... 900 s --
102 % ... 120 % (100 % ... 115 %) 1) 0.1 s ... 900 s ✓
✓
12
Voltage asymmetry % 1 % ... 20 % 0.1 s ... 900 s
Phase failure % 60 % ... 85 % 0.1 s ... 30 s ✓
Direction of rotation Left, right -- -- ✓
Frequency Hz 50/60 80 % ... 100 % 0.1 s ... 900 s ✓
101 % ... 120 % 0.1 s ... 900 s ✓
Battery voltage Ub V DC 12/24/48 70 % ... 100 %2) 0 ... 60 s ✓
110 % ... 140 %2) ✓
1)
Hysteresis value for enabling back-transfer
2)
Warning only, no switching
✓ yes
-- no
Monitoring Devices
Transfer Switches
SENTRON transfer control devices for ATSE
■ Benefits
• 8 digital inputs, 6 of which are programmable and 7 relay out-
The advantages of the SENTRON ATC5300 at a glance: puts, 5 of which are programmable
• Controls compact molded case circuit breakers MCCB, air cir- • 4 selectable operating modes: off, manual, automatic, test
cuit breakers ACB, switch disconnectors LBS, or contactors
• Data, parameter and logged events (e.g. power failure, faults)
• Two measuring inputs for single-phase and multi-phase power remain accessible and unaltered even after a power failure or
supply systems restarting a device
• Option for switching between system to system, generator to • Status display of the connected switches or contactors
system, system to generator, and generator to generator
configurations • Logging and statistical processing of occurring events
possible
• Direct measurement of three-phase industrial systems rang-
ing up to 400 V ACL-N or 690 V ACL-L (converter costs, no • Easy system integration through integrated MODBUS inter-
assembly and installation costs for converters) face (RTU and ASCII) for integrating e.g. into a power
management system
• Has two voltage supply units to cover all standard AC/DC volt-
age supplies, alternative supply via main and standby system • The illuminated LED display makes reading measured values
possible and parameters easy, even under unfavorable lighting condi-
tions
• Low space requirements due to door installation and compact
design • The SENTRON SOFTWARE ATC programming software saves
considerable time when setting parameters and setting up the
• Two displays for monitoring the normal/standby system and SENTRON ATC5300
displaying the phase and interlinked cable voltages
• Generator test run function for mandatory testing intervals
• Setting control parameters for generator activation require-
ments • Command option for switching to the second set of protection
parameters in the ETU76B (air circuit breaker 3WL).
• Calendar clock
■ Integration
Implementation of an automatic transfer system Q1 and Q2, configured with SENTRON circuit breakers
The SENTRON ATC5300 is used to automatically and manually All SENTRON circuit breakers connected to the SENTRON
switch from a main power supply to a standby power supply and ATC5300 must be equipped with the following accessories:
vice versa. In case system faults occur, the SENTRON ATC5300 • 3VL circuit breakers MCCB
controls the switching operations fully automatically. This en- The following is also required for each MCCB:
sures a very high level of operational continuity. - A motor drive
SENTRON ATC5300 allows the implementation of an automatic - An alarm switch
transfer control unit in conjunction with compact molded case - Two auxiliary switches 1 NO/1 NC
circuit breakers MCCB, air circuit breakers ACB, switch discon- • 3WL air circuit breakers ACB
nectors LBS, or contactors. The following is also required for each 3WL ACB:
12 The following devices are ideally matched to the SENTRON
ATC5300:
- A motor drive
- A closing solenoid
- An auxiliary release (shunt release)
• SENTRON 3VL Molded Case Circuit Breakers - Tripped signal switch
• SENTRON 3WL Air circuit breakers - One auxiliary switch block 2 NO/2 NC (standard fittings)
Component interaction
• Feed-in system line 1 (main system) and line 2 (standby
system) are connected to SENTRON ATC5300.
• In case of system anomalies, the SENTRON ATC5300 acti-
vates components Q1 and Q2 accordingly.
• Q1 and Q2 can be implemented with compact molded case
circuit breakers MCCB, air circuit breakers ACB, switch dis-
connectors LBS, or contactors.
Monitoring Devices
Transfer Switches
SENTRON transfer control devices for ATSE
LINE 1 LINE 2
L1 L2 L3 N L1 L2 L3 N
QF1
QF2
x x x x x x x x
Q1 Q2
I202_01380
LOAD L1 L2 L3 N
■ Technical specifications
ATC5300 ATC5300
Auxiliary supply Reversing time of control device s 1
Rated voltage Un Communication cables
• AC V AC 220 ... 240 RS232 serial interface bit/s 1200 ... 38400
• DC V DC 12 / 24 / 48 • With programmable baud rate
Operating range • Connection through RJ6/6 connector
• AC V AC 187 ... 264 RS485 serial interface bit/s 1200 … 38400
• DC V DC 9 ... 70 • Optically insulated
Frequency Hz 45 ... 65 • With programmable baud rate
• Connection through plug-in terminals
Max. power consumption VA 9
at Un = 240 V AC Real-time clock
Max. power loss Energy storage Stored-energy capacitors
• At 240 V AC W 6.3 Operating time without feeding voltage Days Approx. 12 ... 15
• At 48 V DC W 4.1
Insulation voltage
Max. current consumption
Rated insulation voltage Ui V 690
12
• At 12 V DC mA 300
• At 24 V DC mA 180 Ambient conditions
• At 48 V DC mA 90 Operating temperature °C -20 … +60
Safety in the event of short interruptions ms 50 Storage temperature °C -30 … +80
Measuring inputs Relative humidity % <90
Max. rated voltage Un Max. pollution degree 3
• Phase-phase V AC 690
• Phase-neutral V AC 400 Overvoltage category 3
Phase-phase measuring range V AC 80 ... 800 Measuring category CAT III
Frequency ranges Hz 45 ... 65 Connections
Measuring method RMS value (true RMS) Terminal type Removable/pluggable
Measuring input impedance Cable cross-section mm2 0.2 ... 2.5 (24 ... 12 AWG)
• Phase-phase MΩ >1.1 Max. tightening torque Nm 0.5 (4.5 lbf·in)
• Phase-neutral MΩ >0.5 Enclosure
Connection method Single-phase, two-phase, or Enclosure material Thermoplast LEXAN 3412R
three-phase system
Version Door installation
Measuring errors ±0.25 %,
Value range ±1 digit Degree of protection IP41 front, IP20 rear
Digital inputs Weight g 950
Number of inputs 8, 6 of which are program- Certificates and conformity
mable ATS/ATSE standard Complies with the ATS/ATSE
Type of input Negative standard IEC 60947-6-1, in
combination with 3VL or
Input current mA ≤10 3WL1)
Input signal Environment classification 3K6 acc. to IEC 60721-3-3
• Logic state "0" V ≤1.5 (typical 2.9)
• Logic state "1" V ≥ 5.3 (typical 4.3) 3B2 acc. to IEC 60721-3-3
Input signal delay ms ≥ 50 3C3 acc. to IEC 60721-3-3
Relay outputs 3S2 acc. to IEC 60721-3-3
Number of outputs 7, 5 of which are program- 3M6 acc. to IEC 60721-3-3
mable EMC Acc. to IEC 60947-6-1
Contact configuration 1) For more information see device manual at:
• 2 relays with 1 NO contact 12 A, at 250 V AC (AC-1) www.siemens.com/lowvoltage/manuals
• 3 relays with 1 NO contact 8 A, at 250 V AC (AC-1)
• 2 relays with 1 CO contact 8 A, at 250 V AC (AC-1)
Monitoring Devices
Transfer Switches
SENTRON transfer control devices for ATSE
3KC9 000-8TL30
SENTRON SOFTWARE ATC A 3KC9 000-8TL70 1 1 unit 143 0.300
Software for setting parameters and remote control
operations, incl. connection cable from control
device to PC,
cable length 1.8 m
• CD incl. software and manuals.
• Minimum hard- and software requirements:
- Pentium, 64 MB RAM
3KC9 000-8TL70 - COM interface (serial RS232)
- CD drive
- Windows 95/98/2000/XP/Vista/Windows 7
12
Monitoring Devices
Monitoring Devices for Electrical Values
Residual current monitors
■ Overview 100 % I n
Disconnection
Plant safety and operating safety are becoming increasingly im-
n
portant alongside the protection of personnel. Shutdowns due to
Residual current I
the unexpected tripping of protective devices cause high costs.
It is possible to detect residual currents in the electrical installa-
tion before the protective device responds.
Residual current monitors (RCM) monitor residual current in 50 % I n
electrical installations and issue a signal when the residual cur- Alarm
rent exceeds a set value.
RCMs are used primarily in plants where a fault should result in
a signal but not in disconnection. This enables plant operators to
I2_16044
detect faults and eliminate their causes before the protective
devices disconnect the installation, which increases plant and
operating safety and cuts costs. Time t
The summation current transformer detects all conductors re- Time characteristic of the rated residual current ΙDn
quired to conduct the current, i.e. including the neutral conduc-
tor where applicable. In a fault-free system, the magnetizing ef-
fects of the conductors through which current is flowing cancel ■ Benefits
each other out for the summation current transformer, i.e. the • Higher plant availability and operating safety through perma-
sum of all currents is zero. If a residual current is flowing due to nent monitoring of residual currents
an insulation fault, a residual magnetic field is left in the core of • Adjustable limit values for residual current and response time
the transformer and produces a voltage. This voltage is evalu- enable timely detection and signaling – plant shutdowns are
ated using the electronics of the RCM. The switched contact can often avoidable
be used e.g. to operate an acoustic/optical signaling device, a
higher-level control system or a circuit breaker. • Devices for every application:
The summation current transformers are available in various
sizes, the RCMs can be used optionally for signaling and/or
switching
• Additional fire protection can be implemented using the
monitoring system.
■ Technical specifications
RCM analog RCM digital RCM digital, 4 channels
Standards EN 62020, IEC 62020
Rated operational voltage Ue V AC 230
• Frequency Hz 50/60
Rated residual current ΙDn
• Type A A 0.03 ... 3 0.03 ... 3 0.03 ... 3
12
• Type AC A 3 ... 5 3 ... 30 3 ... 30
Response time tv s 0.02 ... 5 0.02 ... 10, INS, SEL1) 0.02 ... 10, INS, SEL1)
Relay contacts 1 × alarm 1 × alarm, 1 × alarm,
1 × tripping operation 4 × tripping operation
• Rated voltage V AC 230 230 230
• Rated current A 6 6 6
Summation current transformer mm ∅ 20 ... 210
Test/Reset Yes/Yes
External tripping operation/external reset --/Yes Yes/Yes Yes/Yes
Mounting width MW 2 3 3
Degree of protection
• Contacts IP20
• Front IP41
Operating temperature °C -10 ... +50
1) INS: instantaneous, SEL: selective.
Monitoring Devices
Monitoring Devices for Electrical Values
Residual current monitors
RCM digital
230, 50/60 Hz 0.03 ... 3 (Type A) 0.02 ... 10, 3 B 5SV8 001-6KK 1 1 unit 027 0.236
3 ... 30 (Type AC) INS, SEL1)
1)
INS: instantaneous, SEL: selective.
12
M)
mm kg
Summation current transformer
Including holder for standard 20 B 5SV8 700-0KK 1 1 unit 027 0.076
mounting rail
30 B 5SV8 701-0KK 1 1 unit 027 0.095
Including holder for wall mounting1) 35 B 5SV8 702-0KK 1 1 unit 027 0.161
70 B 5SV8 703-0KK 1 1 unit 027 0.274
105 B 5SV8 704-0KK 1 1 unit 027 0.545
Including holder for wall mounting 140 B 5SV8 705-0KK 1 1 unit 027 1.222
210 B 5SV8 706-0KK 1 1 unit 027 2.040
Holders for standard mounting rails B 5SV8 900-1KK 1 2 units 027 0.004
Suitable for summation current transformer with internal
diameter of 20 mm, 30 mm, 35 mm, 70 mm and 105 mm
1)
Mounting on standard mounting rail with optional holder for standard
mounting rail also possible.
Monitoring Devices
Monitoring Devices for Electrical Values
Voltage relays
■ Overview ■ Benefits
Voltage relays are used for device and plant protection, supply- • Complete voltage protection in a compact design for overvolt-
ing safety light devices and the detection of N-conductor breaks age and undervoltage monitoring in a single device
and short-time voltage interruptions. • Plants and devices are reliably and easily protected by phase-
They are available as undervoltage, overvoltage and under/ failure relays
overvoltage relays. The devices are equipped with different • Overvoltages and consequential damage due to high volt-
functions, depending on their intended use, and comply with the ages are prevented through N-conductor monitoring
pertinent regulations. • Asymmetry monitoring in the voltage relay also protects three-
phase AC motors against operation with voltage skew.
■ Technical specifications
5TT3 400 5TT3 404 5TT3 406 5TT3 194 5TT3 195
5TT3 401 5TT3 405
5TT3 402
5TT3 403
Standards IEC 60255; IEC 61810
Rated control voltage Uc V AC 230/400 400
Operating range (overload capability) × Uc 1.1 1.35
Rated frequency Hz 50/60
Response values ON-switching × Uc 0.9/0.95 4 % hysteresis
OFF-switching 0.7/0.85 0.7 ... 0.95 0.9 ... 1.3
Minimum contact load V; mA 10; 100
Phase asymmetry Setting accuracy % -- Approx. 5 ... 10 -- Approx. 5 ... 10
Repeat accuracy % -- 1 -- 1
Phase failure detection At L1 or L2 or L3 ms 100 --
N-conductor monitoring -- Yes --
Rated insulation voltage Ui Between coil/contact kV 4
Contacts μ contact (AC-11) A 4
Electrical isolation Creepage distances and
clearances
Actuator/contact mm 3 5.5
Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5 >4
Terminals ±screw (Pozidriv) 1
Conductor cross-sections
• Rigid, max. mm2 2 × 2.5
• Flexible, with end sleeve, min. mm2 0.5
Permissible ambient temperature
Resistance to climate Acc. to EN 60068-1
°C -20 ... +60
20/60/4
12
5TT3 196
Standards IEC 60255; IEC 61810
Rated control voltage Uc V AC 24
Rated power dissipation Pv
• Coil/drive VA 0.6
• Contact1) per pole VA 0.8
Hysteresis % 4
Response values × Uc
• Undervoltage Undervoltage 0.82
• Overvoltage Overvoltage 1.18
Residual ripple tripping ΔUc Infinitely variable % 0 ... 15
Overload capability 33 V DC Continuous
35 V DC ms 500
45 V DC ms 10
Creepage distances and clearances mm 4
Rated impulse withstand voltage Uimp Input/output kV > 2.5
Minimum contact load V/mA 24/300
Rated operational current Ie AC-11 A 1
AC-1 A 4
Contacts μ contact
Electrical service life In switching cycles at Ie 5 × 105
Terminals +/-screw (Pozidriv) 1
Conductor cross-sections
• Rigid, max. mm2 2 × 2.5
• Flexible, with end sleeve, min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Resistance to climate Acc. to EN 60068-1 20/60/4
1)
For rated operational current.
Monitoring Devices
Monitoring Devices for Electrical Values
Voltage relays
Voltage relays
5TT3 411 5TT3 412
Rated control voltage Uc V AC 230 230/400
Overload capability × Uc 1.15 1.1
Rated frequency Hz 50/60
Response values ON-switching 2 % hysteresis 4 % hysteresis
OFF-switching × Uc 0.9 0.9
Minimum contact load V/mA 10/100
Phase failure detection At L1, L2 or L3 ms -- 100
N-conductor monitoring -- Yes
Rated insulation voltage Ui Between coil/contact kV 4
Contacts AC-15 NO contacts 3 3
AC-15 NC contacts 2 1
Electrical service life in switching cycles AC-15, 1 A, 230 V AC 5 × 105
Rated impulse withstand voltage Acc. to IEC 60664-1 kV 4
Pollution degree 2
Terminals ±screw (Pozidriv) 2
Conductor cross-sections
• Rigid mm2 2 × 2.5
• Flexible, with end sleeve mm2 2 × 1.5
Permissible ambient temperature °C -20 … +60
Resistance to climate Acc. to EN 60068-1 20/060/04
Monitoring Devices
Monitoring Devices for Electrical Values
Voltage relays
Monitoring Devices
Monitoring Devices for Electrical Values
Voltage relays
12
2 NO + 2 NC 230 4 230 4 C 5TT3 411 1 1 unit 027 0.220
Single, two or three-phase against N,
with asymmetry, reverse voltage and phase failure
detection, with N-conductor monitoring, and one
test button each for the phases, switching thresh-
olds: 0.9 × Un, 4 % hysteresis
1 CO, 1 NO, 1 NC 230 4 230/400 4 C 5TT3 412 1 1 unit 027 0.230
Monitoring Devices
Monitoring Devices for Electrical Values
Current relays
■ Overview ■ Benefits
Current relays monitor single and three-phase systems for the • Devices with an extremely broad range of applications of min-
flow of current, e.g. in emergency lighting installations, and the imum 0.1 A to maximum 15 A without transformer
loading of motors. They are available as undercurrent, overcur- • Permanent overload capability up to 20 A or 30 A max. for up
rent and under/overcurrent relays. to 3 seconds, protect the function against uncontrolled plant
states and increase plant availability
• Range changing enables the precise setting of current values
through a high resolution
• Ultra compact current relays require only the smallest of
spaces and save costs
■ Technical specifications
5TT6 111 5TT6 112
Standards IEC 60255; DIN VDE 0435-303
Rated control current Ic A 1 ... 10
Rated control voltage Uc V AC 230
Primary operating range × Uc 0.9 ... 1.1
Overload capability, continuous A 15
Overload capability, short-time At 50 °C ambient tempera- A 20
ture max. 3 s
Rated frequency Hz 50/60
Response values ON-switching Infinitely variable
OFF-switching permanent, 4 % hysteresis
Switching delay tv Infinitely adjustable s 0.1 ... 20
Response time Non-adjustable ms Current corresponds to the rated operational power of the continu-
ous-flow heater
Minimum contact load V; mA 10; 100
Rated insulation voltage Ui Between coil/contact kV 2.5
Contacts
μ contact (AC-15) NO contacts A 3
NC contacts A 1
Electrical isolation Creepage distances and mm 3
clearances
actuator/contact
Rated impulse withstand voltage Uimp Actuator/contact kV >4
Terminals ±screw (Pozidriv) 1
Conductor cross-sections Rigid max. mm2 2 × 2.5
12
Flexible, with end sleeve 2
min. mm 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Resistance to climate Acc. to EN 60068-1 20/60/4
Monitoring Devices
Monitoring Devices for Electrical Values
Current relays
12
2 CO each for 230 5 0.5 ... 5 4 B 5TT6 120 1 1 unit 027 0.245
overcurrent/
undercurrent
respectively
Monitoring Devices
Monitoring Devices for Electrical Values
Priority switches
■ Overview ■ Benefits
In the mixed operation of electric hot water and electric storage Reduction of the connection fee, which depends on the maxi-
heaters, the priority switch interrupts the charging procedure of mum load to be supplied (BTO, German Federal Regulation on
the storage heater if hot water is required during the low-tariff Tariffs § 6 Section 4), when used in systems with continuous-flow
time, thus limiting the connected load in compliance with heaters and electric storage heaters where the continuous-flow
BTO § 6. The control circuit terminals must be sealable. heaters are switched with priority.
■ Technical specifications
5TT6 101 5TT6 102 5TT6 103
Standards EN 60669, BTO § 6 Section 4
Rated control current Ic A 40 54 6 ... 40
(Current corresponds to the rated operational power of the
continuous-flow heater).
Rated frequency Hz 50
Response currents A 13 23 6
(Continuous rise not permissible)
Rated operational power
For continuous-flow heaters Up to 230 V AC kW 9 12 1.5 ... 9
Up to 3 × 230 V AC kW 27 36 4.5 ... 27
Rated impulse withstand voltage Uimp kV > 2.5
Rated operational voltage Ue V AC 250
Rated operational current Ie At Ue = 230 V AC A 1
Terminals ±screw (Pozidriv) 1
Conductor cross-sections
• Coil For conductor cross-sections up to mm2 10
• Contacts For conductor cross-sections up to mm2 2 × 2.5
Permissible ambient temperature °C -20 ... +40
Resistance to climate Acc. to DIN 50016 FW 24
Monitoring Devices
Monitoring Devices for Electrical Values
Fuse monitors
■ Overview ■ Benefits
Fuse monitors serve to monitor all types and versions of melting • Increase in plant availability, because fuse failures – which
fuses that cannot be equipped with a fault signal contact. This could cause considerable damage to the plant – are detected
enables integration in fault signaling circuits or a central alarm in in plenty of time.
order to improve plant availability. • A fuse failure is detected even if the load is switched off. This
ensures the highest level of plant availability.
■ Technical specifications
5TT3 170
Standards IEC 60255; IEC 61810
Rated control voltage Uc V 3 AC 380 ... 415
Primary operating range × Uc 0.8 ... 1.1
Rated frequency Hz 50 ... 400
Internal resistance of measuring paths Ω/V > 1000
Max. permissible rear feed % 90
Response/release time ms < 50
Rated impulse withstand voltage Uimp kV >4
Input/output
Rated operational voltage Ue V AC 250
Rated operational current Ie AC-1 A 4
Electrical service life AC-11 in switching cycles at 1 A 1.5 × 105
Terminals ±screw (Pozidriv) 1
Conductor cross-sections Rigid, max. mm2 2 × 2.5
Flexible, with end sleeve, min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +45
Resistance to climate Acc. to EN 60068-1 20/45/4
12
Fuse monitors
For all low-voltage fuse systems. Can be used in
asymmetric systems afflicted with harmonics and
regenerative feedback motors. Signal also for dis-
connected loads.
230 4 380 ... 415 2 } 5TT3 170 1 1 unit 027 0.153
Monitoring Devices
Monitoring Devices for Electrical Values
Phase and phase sequence monitors
■ Overview ■ Benefits
Phase monitors monitor the voltages in three-phase system and • The three-phase LED display in the phase monitor and the
signal the power failure of one or more phases over a floating LED display in the phase sequence monitors provide constant
contact. Phase sequence monitors monitor the phase sequence information on the switching state of the plant
in three-phase systems and signal any changes in the phase se- • The compact design in 1 MW saves space.
quence – change of rotating field – over a floating changeover
contact.
■ Technical specifications
5TT3 421 5TT3 423
Standards IEC 60255; IEC 61810
Rated control voltage Uc V AC 230/400 400
Primary operating range × Uc 0.8 ... 1.1
Rated frequency Hz 50/60
Rated power dissipation Pv Electronics VA 9
Contacts VA 0.2
Rated operational voltage Ue V AC 250
Rated operational current Ie A 4
Minimum contact load V; mA 10; 100
Rated insulation voltage Ui Between coil/contact kV 4
Contacts μ contact (AC-11) A 3
Electrical isolation Creepage distances and
clearances
Actuator/contact mm 4
Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5
Terminals ±screw (Pozidriv) 1
Conductor cross-sections Rigid, max. mm2 2 × 2.5
Flexible, with end sleeve, min. mm2 –
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Safety class Acc. to EN 61140 II
Permissible ambient temperature °C -20 ... +60
Resistance to climate Acc. to EN 60068-1 20/60/4
Monitoring Devices
Monitoring Devices for Electrical Values
Insulation monitors for industrial applications
■ Overview
Insulation monitors are used for protection of persons and These types of measurements are specified according to
against fire in non-grounded systems (IT systems). The insula- DIN VDE 0100-410 – Low-voltage electrical installations –
tion resistance of the system being monitored is measured Protection against electric shock (similar to IEC 60364-4-41).
against ground.
■ Technical specifications
5TT3 470 5TT3 471
Power supply Uc V AC 220 ... 240 --
V DC -- --
Primary operating range With AC supply × Uc 0.8 ... 1.1 --
For DC supply V DC -- --
Frequency range for Uc Hz 45 ... 400 --
Rated power dissipation Pv VA Approx. 2 --
For DC supply W -- Approx. 1
Rated impulse withstand voltage Uimp Terminals A1 to A2 kV <4 <4
Terminals L to PU kV <4 <4
Terminals A1, A2 to L, PU kV <4 <3
Terminals against contacts kV <6 <6
Measuring circuit For direct voltage and alternat- For direct voltage systems
ing voltage networks
Measurement voltage range Umeas V AC 0 ... 500 --
V DC -- 12 ... 280
Primary operating range × Umeas 0 ... 1.1 0.9 ... 1.1
Frequency range for Umeas Hz 10 ... 1000 --
Alarm values Measuring shunt RAL kΩ 5 ... 100 5 ... 200
Setting of alarm value On absolute scale Infinitely variable Infinitely variable
Alternating current internal resistance Internal testing resistor kΩ > 250 --
Direct current internal resistance Internal testing resistor kΩ > 250 --
L+ and L- to PU kΩ -- 75 each
Measurement voltage Umeas Internal V DC Approx. 15 --
Max. measurement current Imeas Short circuit mA < 0.1 0.2 ... 4 depending on the
voltage
Direct interference voltage Max. permissible V DC 500 --
Response delay At RAL 50 kΩ and 1 μF
and ∞ up to 0.9 x Rmeas s < 1.3 0.8
and Rmeas from ∞ to 0 Ω s < 0.7 0.4
12 Switching hysteresis
Contacts
At Rmeas 50 kΩ
μ contact
% 15
2 CO
10 ... 15
2 CO
Rated operational voltage Ue V AC 230 230
Rated operational current Is Thermal current limit Ith A 4 4
DC-13 at 24 V DC A -- 2
DC-13 at 250 V DC A -- 0.2
AC-15 A -- 3
AC-15 NO contacts A 5 --
AC-15 NC contacts A 2 --
Terminals ±screw (Pozidriv) 2 2
Conductor cross-sections Rigid, max. mm2 2 × 2.5
Flexible, with end sleeve, min. mm2 1 × 0.50
Permissible ambient temperature °C -20 ... +60
Degree of protection Terminals (acc. to EN 60529) IP20
Enclosure (acc. to EN 60529) IP40
Resistance to climate Acc. to EN 60068-1 20/060/04
Monitoring Devices
Monitoring Devices for Electrical Values
Monitoring of medical premises
■ Overview ■ Benefits
In areas that conform to Group 2 of DIN VDE 0100-710, any in- • TÜV-certified switchover device with increased functionality
terruption to the examination and/or treatment of patients would • Plant state signal over contacts – No specific manufacturer's
place those patients at risk. bus system
Limit monitoring • Easy operation over potentiometers as the set limit value is
always visible
This is prevented through the use of changeover and monitoring
units. These monitor the insulation resistance of the non- • Easy to integrate in existing plants, including plants from other
grounded IT system, the load current and the temperature of the manufacturers.
transformer. If the limit value is exceeded, the insulation monitor
gives out a warning signal.
Voltage monitoring
In addition, a special voltage relay monitors the voltage of the
power supply and switches to a second power supply if it falls
below the specified limit values.
■ Technical specifications
Switchover device
7LQ3 361 7LQ3 362
Standards IEC 60364-7-710; DIN VDE 0100-710
Power supply Uv V AC 230 230/400
Primary operating range × Uv 0.9 … 1.1
Supply frequency fv Hz 50 … 60
Insulation coordination IEC 60664-1
Rated impulse withstand voltage kV 4
Pollution degree 3
Power loss max. Pv W 10.7
Power section
Contactors Mechanically latched; mechanically and electrically locked
Rated operational current acc. to DIN VDE 0100-710 A 51 32
Rated operational current AC-3 A 113 71
Short-circuit protection acc. to DIN VDE 0100-710
• Max. backup protection gG A 63
Switchover time s 0.1 ... 10
Measuring circuit insulation monitoring
Response value Rresp kΩ 50 12
Response deviation DIN VDE 61557-8
Response time ton at Ron = 50 kΩ, Ce = 1 μF RF from ∞ to 0.5 × Rto s < 1.3
RF from ∞ to 0 kΩ s < 0.7
Hysteresis % 15
Measurement voltage Um V DC Approx. 15
Measurement current Im max (at RF = 0 Ω) µA < 50
Internal resistance DC Ri kΩ > 250
Impedance Zi at 50 Hz kΩ > 250
Permissible direct interference voltage Ufg V DC < 300
Test button External/internal
Measuring circuit load current monitoring
Response value, A 5 … 50
adjustable with external transformer 50/5 A, Class 1
Hysteresis % 4
Temperature influence %/°C ≤ 0.05
Time delay tv, adjustable s 0.1 … 20
Measuring circuit temperature monitoring
Response value kΩ 3.2 … 3.8
Release value kΩ 1.5 … 1.8
PTC thermistor Acc. to DIN 44081/44082 Unit(s) 1 … 6 in series
Measuring circuit, voltage monitoring
Response values ON-switching 2 % hysteresis 4 % hysteresis
OFF-switching × Uc 0.9 0.9
Phase failure detection At L1, L2 or L3 ms -- 100
N-conductor monitoring -- Yes
Monitoring Devices
Monitoring Devices for Electrical Values
Monitoring of medical premises
Switchover device
7LQ3 361 7LQ3 362
Connection
Terminals
• Load circuit Feeder terminals mm² 4 ... 16
Output terminals
• Communication Status signals mm² 2.5
Fault indications
Environmental conditions
Permissible ambient temperature °C -20 ... 45
Mounting position Vertical
Insulation monitors
7LQ3 354 7LQ3 355
Standards EN 61557-8
Power supply Uv V AC 230
Primary operating range × Uv 0.9 … 1.1
Supply frequency fv Hz 50 … 60
Power loss max. Pv VA Approx. 7
Rated system voltage Un (measuring circuit) V AC 0 … 300
Rated frequency fn Hz 10 … 1000
EMC immunity to interference IEC 61000-6-2
EMC emitted interference IEC 61000-6-3
Insulation coordination IEC 60664-1
Rated impulse withstand voltage kV 4
Pollution degree 3
Flammability class UL 94V-0
Measuring circuit insulation monitoring
Response value Rresp kΩ 50 50 ... 500
Response deviation EN 61557-8
Response time ton at Ron = 50 kΩ, Ce = 1 μF RF from ∞ to 0.5 × Ron s < 1.3
RF from ∞ to 0 kΩ s < 0.7
Hysteresis % 15
Measurement voltage Um V DC Approx. 15
Measurement current Im max (at RF = 0 Ω) µA < 50
12 Internal resistance DC Ri
Impedance Zi at 50 Hz
kΩ
kΩ
> 250
> 250
Permissible direct interference voltage Ufg V DC < 300
Measuring circuit load current monitoring
Response value, A 5 … 50
adjustable with external transformer 50/5 A, Class 1
Hysteresis % 4
Temperature influence %/°C ≤ 0.05
Time delay tv, adjustable s 0.1 … 20
Measuring circuit temperature monitoring
Response value kΩ 3.2 … 3.8
Release value kΩ 1.5 … 1.8
PTC thermistor Acc. to DIN 44081/44082 Unit(s) 1 … 6 in series
Display and control elements
Operating error Acc. to IEC 61557-8
LED display
• Current and temperature monitoring One red and one green LED
• Ready-to-run Green
• Insulation fault Red
• Line breakage monitoring of the isolation measuring circuit Red
• Display of current insulation resistance -- 11-step LED chain
Pushbuttons Test and Reset
Monitoring Devices
Monitoring Devices for Electrical Values
Monitoring of medical premises
Insulation monitors
7LQ3 354 7LQ3 355
Output relay
Contacts for Overtemperature 2 CO
Overload 2 CO
Insulation fault 2 CO
Mode of operation Working current
Contacts AC-15 NO contacts A AC/V AC 3/230
AC-15 NC contacts A AC/V AC 1/230
Electrical service life AC-15, 1 A, 230 V AC Switching 30000
cycles
Thermal current A AC 5
Connection
Terminals ±screw (Pozidriv) 2
• Conductor cross-sections Rigid mm2 2 × 2.5
• Insulation fault Flexible, with end sleeve mm2 1 × 2.5
Environmental conditions
Permissible ambient temperature °C -20 … +60
Resistance to climate Acc. to EN 60068-1 20/060/04
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Mounting position any
Vibration strain Acc. to IEC 60068-2-6
• Amplitude mm 0.35
• Frequency Hz 10 … 55
Monitoring Devices
Monitoring Devices for Electrical Values
Monitoring of medical premises
12
Resistance to climate Acc. to IEC/EN 60068-1 05/055/04
Terminal marking EN 50005
Conductor connections
• Solid mm2 1×4
• Strand with sleeve and plastic collar mm2 1 × 2.5
• Strand with sleeve and plastic collar DIN 46228-1/-2/-3/-4 mm2 2 × 1.5
• Strand with sleeve DIN 46228-1/-2/-3 mm2 2 × 2.5
Conductor mounting Box terminals with wire protection
Device dimensions mm 80 × 80 × 35
Monitoring Devices
Monitoring Devices for Electrical Values
Monitoring of medical premises
Voltage relays
5TT3 411 5TT3 412
Rated control voltage Uc V AC 230 230/400
Overload capability × Uc 1.15 1.1
Rated frequency Hz 50/60
Response values ON-switching 2 % hysteresis 4 % hysteresis
OFF-switching × Uc 0.9 0.9
Minimum contact load V/mA 10/100
Phase failure detection At L1, L2 or L3 ms -- 100
N-conductor monitoring -- Yes
Rated insulation voltage Ui Between coil/contact kV 4
Contacts AC-15 NO contacts 3 3
AC-15 NC contacts 2 1
Electrical service life in switching cycles AC-15, 1 A, 230 V AC 5 × 105
Rated impulse withstand voltage Acc. to IEC 60664-1 kV 4
Pollution degree 2
Terminals ±screw (Pozidriv) 2
Conductor cross-sections
• Rigid mm2 2 × 2.5
• Flexible, with end sleeve mm2 2 × 1.5
Permissible ambient temperature °C -20 … +60
Resistance to climate Acc. to EN 60068-1 20/060/04
IT line transformer
4AT3/4AT4
In the case of isolating transformers used to set up medical IT systems,
overcurrent protective devices are only permissible as protection against
short circuits. To protect the isolating transformers against overload they
are fitted with monitoring devices that signal an excessive rise in tempera-
ture (e.g. 7LQ3 354 insulation monitors).
Standards EN 61558-2-15
Safety class I
Static shield between primary and secondary winding with insulated connection
Thermistor transformer protection Warning in the event of thermal overload1)
Insulation monitoring With center tap
Short-circuit voltage uz % ≤3
No-load supply current i0
• Starting current (rush), max.
%
x I1N
≤3
8
12
Rated ambient temperature ta /Thermal Class 55 °C/H
1)
Tripping units must be ordered separately.
Monitoring Devices
Monitoring Devices for Electrical Values
Monitoring of medical premises
Insulation monitors
With load current and temperature monitoring for medical
premises
230 6 B 7LQ3 354 1 1 unit 027 0.396
12
Test and signaling panels
For switchover devices,
24 V AC/DC, 50/60 Hz
Surface mounting B 7LQ3 356 1 1 unit 027 0.325
Monitoring Devices
Monitoring Devices for Electrical Values
Monitoring of medical premises
■ Accessories
SIRIUS 4AT isolating transformers
Further information about the SIRIUS 4AT isolating transformers
can be found in the catalog IC 10 · 2011.
12
Rated Voltage rise Rated voltages Short-circuit protection for the DT1) Order No. PU PS*/ PG Cu Weight
power Pn during transformer (UNIT, P. unit weight per PU
no-load SET, per PU approx.
operation uA M) approx.
Input Output With fuse, With circuit breaker
U1N U2N gG opera- Type Set
tional value
class
kVA % V V A A kg kg
Isolating transformer
• Degree of protection IP00
2.5 3.6 230 230-115 35 3RV20 21-4CA10 21 C 4AT30 12-1TA71-3MA0 1 1 unit 104 7.400 25.500
3.15 3.6 230 230-115 35 3RV10 31-4EA10 26 C 4AT36 02-1TA71-3MA0 1 1 unit 104 6.800 33.000
4 3.6 230 230-115 50 3RV10 31-4EA10 29 C 4AT36 12-1TA71-3MA0 1 1 unit 104 9.400 36.000
5 3.6 230 230-115 50 3RV10 31-4FA10 36 C 4AT39 02-1TA71-3MA0 1 1 unit 104 9.700 45.000
6.3 3.6 230 230-115 63 3RV10 31-4GA10 40 C 4AT39 12-1TA71-3MA0 1 1 unit 104 13.800 49.000
8 3.7 230 230-115 63 3RV10 41-4JA10 49 C 4AT43 02-1TA71-3MA0 1 1 unit 104 12.600 63.000
• Degree of protection IP23
2.5 3.6 230 230-115 35 3RV20 21-4CA10 21 C 4AT30 12-1TA71-3MC0 1 1 unit 104 7.400 33.200
3.15 3.6 230 230-115 35 3RV10 31-4EA10 26 C 4AT36 02-1TA71-3MC0 1 1 unit 104 6.800 50.000
4 3.7 230 230-115 50 3RV10 31-4EA10 29 D 4AT36 12-1TA71-3MC0 1 1 unit 104 9.400 44.000
5 3.6 230 230-115 50 3RV10 31-4FA10 36 C 4AT39 02-1TA71-3MC0 1 1 unit 104 9.700 59.000
6.3 3.9 230 230-115 63 3RV10 31-4GA10 40 C 4AT39 12-1TA71-3MC0 1 1 unit 104 13.800 63.000
8 3.7 230 230-115 63 3RV10 41-4JA10 49 C 4AT43 02-1TA71-3MC0 1 1 unit 104 12.400 77.000
1)
Delivery time depends on the number of units ordered, the specified
delivery time applies to an order quantity of up to 5 units.
Monitoring Devices
Monitoring Devices for Electrical Values
Monitoring of medical premises
■ More information
TÜV-certified switchover device
The 7LQ3 361 and 7LQ3 362 switchover devices have been
tested and certified by TÜV Rhineland. Switchover devices
comply with DIN VDE 0100-710:2002-11 and
IEC 60364-7-710:2002-11.
Rhineland TÜV certificate for 7LQ3 361 and 7LQ3 362 switchover
devices
12
Monitoring Devices
Monitoring Devices for Plants and Devices
GSM alarm modules
■ Overview ■ Benefits
The GSM alarm module (GSM = Global System for Mobile Com- • Mobile monitoring and control of electrical plants and system
munications) enables cost-effective remote control of industrial components
and private building management, e.g. of heating, air-condition- • Fast and reliable alarm signaling over SMS
ing and cooling systems. But it is also possible to safely control
elevators and escalators and all kinds of production equipment, • Simple operation and parameterization over SMS
such as machines, automatic devices and conveyor belts. The • Saves space and can be retrofitted in any plant
GSM alarm module is particularly suitable for distant plants, • 1 administrator telephone number from any mobile network for
such as monitoring the heating of summer houses or the pumps configuration
of a water treatment plant.
• Transmission of alarm messages to up to 5 cell phones
Using voltage relays, current relays, fuse monitors, miniature cir- • Customized tests for 2 alarm inputs and switchable output.
cuit breakers, residual current operated circuit breakers or surge
arresters fitted with auxiliary switches or signal contacts, there
are virtually no limits to the type of monitoring tasks that can be
carried out. The use of remote controlled mechanisms with min-
iature circuit breakers and residual current operated circuit
breakers also allows realization of a range of cost-effective and
interesting solutions.
Note:
Since the availability of mobile networks cannot be guaranteed,
GSM alarm modules should not be used for safety-relevant con-
trol functions.
■ Technical specifications
5TT7 120-0
Rated power Ps W 4.5
Digital inputs V DC 24; 2-wire connection, isolated
Signal voltage "0" at the input V DC -2 ... 2
Signal voltage "1" at the input V DC 8 ... 30
Maximum contact load At p.f. = 1 V; A 250; 5
Maximum contact load V; A 30; 5
Rated operational voltage Ue V DC 10 ... 30
• Permissible residual ripple
- At 10 V % <1
- At 30 V % < 10
12
Vibration resistance Acc. to EN 60068-2-34 g 1 at 10 ... 500 Hz
Shock resistance Acc. to EN 60068-2-27 g 30 for 18 ms
Shock resistance Acc. to EN 60068-2-29 g 25 for 6 ms
EMC Acc. to EN 6100-6-2, Complied with
EN 61000-6-3
Frequency band E-GSM 900 / GSM 1800
Power class GSM 900:4 (2 CO) / GSM 1800:1 (1 CO)
GPRS class Multislot Class 8, operation mode Class B, HSCSD, SAT
Connections
• Terminals ±screw (Pozidriv) 1
• Conductor cross-sections of main current paths
- Rigid, max. mm2 1.5 ... 4
- Flexible, with end sleeve, min. mm2 1 ... 2.5
Ambient temperature °C -20 ... +50
Storage temperature °C -20 ... +50
Humidity at 40 °C % 0 ... 95
Monitoring Devices
Monitoring Devices for Plants and Devices
GSM alarm modules
Aerials1)
Rod aerial with magnet base, with MMC con- B 5TT7 908-1 1 1 unit 027 0.075
nection and connecting cable
Flat form for adhesion, with MMC connection B 5TT7 908-2 1 1 unit 027 0.048
and connecting cable
1)
Essential accessories.
12
Monitoring Devices
Monitoring Devices for Plants and Devices
Fault signaling units
■ Overview ■ Benefits
Fault signaling units are used in small plants where the installa- • Ultra compact device designs that only require the smallest of
tion of complex fault signaling systems would be too labor-inten- spaces in distribution boards
sive and too expensive. In the event of a fault, they enable fast • The modular design means that it is easy to add devices as
fault localization of all monitoring devices and limit monitors from your system expands.
a central location. This increases plant availability. With the cor-
rect sensor configuration, they also provide the option of preven-
tative maintenance.
• 4 fault signal inputs with LED
• 1 LED as centralized fault indicator
• One unit each for centralized fault indication and acoustic
signaling
• With acknowledgment for acoustic indicators
• Open-/closed-circuit principle to the 4 inputs can be adjusted
via jumpers X1 - X2
• A maximum of 39 5TT3 461 expansion fault signaling units can
be connected to the 5TT3 460 centralized fault signaling unit
• The maximum possible cable length between 5TT3 460 cen-
tralized fault signaling units and 5TT3 461 expansion fault sig-
naling units is approx. 100 m with a conductor cross-section
of 1.5 mm2.
■ Technical specifications
5TT3 460 5TT3 461
Standards IEC 60255; IEC 61810
Rated control voltage Uc V AC 230
Primary operating range × Uc 0.8 ... 1.1
Rated frequency fn Hz 50/60
Fault signaling inputs S1 ... S4 V AC 230
Signal voltage V 7 ... 10
To terminals S and H
Noise pulse duration ms ≥ 100
Acknowledgment pulse duration ms ≥ 200
Contacts
• Rated operational voltage Ue V AC 230 --
• Rated operational current Ie A 5 --
• Minimum contact load
Connections
V; mA 10; 100 --
12
• Terminals ±screw (Pozidriv) PZ 1
• Conductor cross-sections
- Rigid, max. mm2 2 × 2.5
- Flexible, with end sleeve, min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Humidity class Acc. to IEC 60068-2-30 F
Monitoring Devices
Monitoring Devices for Plants and Devices
EMERGENCY STOP modules
■ Overview ■ Benefits
EMERGENCY STOP circuits are common safety measures in all • The electrical isolation between electric circuit and control
laboratory equipment and industrial plants. The EMERGENCY meets the requirements of the standard
STOP modules used here must meet the most rigorous demands • An LED for the operating and switching state provides con-
with regard to functional reliability. Benchmark is the degree of stant information on the operating state
self-monitoring. The Directive 98/37/EC on Safety of Machines,
valid from 31.02.1994, only specifies global safety standards. • The safety category 4 to EN 954-1 expands the application
Details on how to implement individual safety demands are de- options in many fields
fined in standards, e.g. by the European Committee for Electro- • Compliance with the regulations according to EC Machine
technical Standardization (CENELEC), which are based on inter- Directive 98/37/EC supports a high safety standard for those
national standards. working in the plants.
■ Technical specifications
5TT5 200
Standards IEC 60204-1; EN 60204-1 (VDE 0113-1)
Supply
• Rated control voltage Uc V AC 230
- Primary operating range × Uc 0.8 ... 1.1
• Rated frequency fn Hz 50
• Rated power dissipation Pv Coil/drive 3.5
Contact per pole VA 0.8
Control voltage Terminal Y1 V AC/DC 24
Control current Terminal Y1 mA DC 45
Recovery time ms 500
Safety
• Electrical isolation, creepage distances and clearances, actuator/contact mm 3
• Rated impulse withstand voltage Uimp actuator/contact kV >4
Contacts
• Contacts NO contacts AC-15 A 3
NC contacts AC-15 A 2
NO contact/NC contact AC-1 A 5
• Contact gap mm >1
• Electrical service life AC-15, 2 A, 230 V AC Switching 105
cycles
• Reliable switching frequency Switching 600
12
cycles/h
Vibration resistance
Amplitude Acc. to EN 60068-2-610 Up to 55 Hz mm 0.35
Connections
• Terminals ±screw (Pozidriv) PZ 1
• Conductor cross-sections of main current paths
- Rigid Max. mm2 2 × 2.5
- Flexible, with end sleeve Min. mm2 1 × 0.5
Permissible ambient temperature °C 0 ... +50
Resistance to climate Acc. to EN 60068-1 0/55/04
Monitoring Devices
Monitoring Devices for Plants and Devices
Level relays
■ Overview ■ Benefits
Level relays are used for the monitoring and control of conduc- The measuring range up to 450 kΩ enables a differentiation be-
tive, non-combustible liquids and powders. They ensure over- tween foam and liquid. It also increases the universal application
flow and dry run protection. Due to their sensor performance, the for resistance measurements.
devices can also be used for general resistance monitoring.
Due to its low-frequency, electrically isolated measuring circuit,
LED displays: the device has a high immunity to interference against system
• Green LED: lights up when operational voltage is applied coupling, which enables cable lengths of up to 1500 m and sup-
presses the effects of electrolysis in the liquid
• Yellow LED: lights up if MIN output relay is activated
• The two outputs for minimum and maximum control can also
• Red LED: lights up if MAX output relay is activated.
be used for the advance warning and tripping of limit values
• 3 electrode connections for 1-step and 2-step level control
• All standard products can be used as electrodes
• High immunity to interference of the measuring circuit isolated
from the system
• Programmable for open-circuit principle (with bridge X2 COM)
or closed-circuit principle (without jumper)
• Separately adjustable delay times for tv min and tv max,
0.2 s to 2 s.
■ Technical specifications
5TT3 435
Standards IEC 60255; IEC 61810
Supply
• Rated control voltage Uc V AC 230
- Primary operating range × Uc 0.8 ... 1.1
• Rated frequency fn Hz 50/60
Setting range of the liquid level kΩ 2 ... 450
Switching point hysteresis of set value
• At 450 kΩ % 3
• At 2 kΩ % 6
Voltage temperature influence From set value % <2
Max. cable length to the Set value kΩ
Electrodes at 100 μF/km 450 m 50
100 m 200
35 m 500
10
5
m
m
1500
3000 12
Electrode voltage Max. V AC Approx. 10
Electrode current Max. mA AC Approx. 1.5
Response delay Adjustable s 0.2 ... 20
OFF-delay Adjustable s 0.2 ... 20
Rated operational voltage Ue V 250
Rated operational current Ie A 5
Test voltage
Input/auxiliary circuit kV 4
Input/output circuit kV 4
Auxiliary/output circuit kV 4
Connections
• Terminals ±screw (Pozidriv) PZ 2
• Conductor cross-sections
- Rigid Max. mm2 2 × 2.5
- Flexible, with end sleeve Min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Resistance to climate Acc. to EN 60068-1 20/60/4
Monitoring Devices
Monitoring Devices for Plants and Devices
Level relays
Immersion electrodes
• Made of stainless steel, with PG13 sealing cap
• Temperature range 0 ... 60 °C
• Suitable for pure water in open containers
With terminal connection B 5TG8 223 1 1/24 units 027 0.087
12
Monitoring Devices
Monitoring Devices for Plants and Devices
Line circuit relays
■ Overview ■ Benefits
Line circuit relays are used to interrupt circuits and prevent elec- • High availability to a wide range of loads, as all resistive,
tromagnetic fields in circuits where there are currently no active capacitive and inductive loads are detected
loads. • Adjustable from 2 VA to 20 VA
If the loads are disconnected, and the line circuit relay measures
a usage of only 2 to 20 VA - adjustable - it disconnects the cable • With status display for contact adjustment
to the supply voltage and switches over to extra-low voltage. As • With switch continuously ON
soon as loads are reconnected, the line circuit relay detects the • With safety information on stickers for socket outlets and
increase in usage and switches back to the supply voltage. distribution boards.
While the line circuit relay switches off any unnecessary system
components, it is not a device for ensuring isolation in the sense
of safe disconnection.
The line circuit relay is unable to detect consumers with elec-
tronic power supply units, e.g. electronically controlled vacuum
cleaners. It is expedient to connect such equipment to a base
load resistor (PTC resistor) so that the line circuit relay is reset to
supply voltage.
■ Technical specifications
5TT3 171
Standards IEC 60255; IEC 61810
Rated control voltage Uc V AC 230
Primary operating range × Uc 0.85 ... 1.15
Rated frequency Hz 50/60
Rated power dissipation Pv Electronics VA 5
Contacts VA 2.6
Monitoring voltage V 3
Response value adjustable VA 2 ... 20
Release value % of the response value 70
Rated impulse withstand voltage Uimp Input/output kV >4
Rated operational voltage Ue V AC 250
Rated operational current Ie AC-1 A 16
AC-11 A 3
Contacts μ contact
Electrical service life In switching cycles at 3 A AC-11 5 × 105
12
Terminals +/-screw (Pozidriv) PZ 1
Conductor cross-sections
• Rigid Max. mm2 2 × 2.5
• Flexible, with end sleeve Min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +45
Degree of protection Acc. to IEC/EN 60529 IP20, with connected conductors
Safety class Acc. to EN 61140/VDE 0140-1 II
Humidity class Acc. to IEC 60068-2-30 F
Monitoring Devices
Monitoring Devices for Plants and Devices
Dusk switches
■ Overview ■ Benefits
Dusk switches are used for the demand-oriented switching of • The devices 7LQ2 101 and 7LQ2 103 have 2 switching chan-
lighting installations for shop windows or paths in order to cut nels that can be set independently of each other. This requires
operating costs. a light sensor
A light sensor measures the level of daylight. Switching depends • 12 dusk switches can be switched parallel to a light sensor.
on the desired brightness. A time delay and the switching This saves the multiple installation of light sensors in a single
hysteresis prevent clock-pulse behavior. system and all dusk switches operate independently of each
The sensor must be mounted so that it is not influenced by the other and can be adjusted individually.
lighting feedback.
■ Technical specifications
7LQ2 100 7LQ2 101 7LQ2 102 7LQ2 103 5TT3 303
Standards EN 60730
Rated control voltage Uc V AC 230
Primary operating range At 50/60 Hz × Uc 0.8 ... 1.2
Rated frequency fn Hz 45 ... 65
Measuring ranges, setting ranges Lux 2 ... 500 2 × 2 ... 500 2 ... 500 2 × 2 ... 500 2 ... 500
Time delay Non-adjustable s 75 ± 25 No 75 ± 25 No 50
Adjustable No 2 × 50 ... 100 No 2 × 50 ... 100 No
± 25 ± 25
Status indication, LED Switching status indication Instantaneous No
Switching state OFF Green No
Switching state ON Red No
Incandescent lamp load W 2000 2 × 2000 2000 2 × 2000 1200
Different phases Actuator/contact permissible Yes No
Contact/contact No Yes No Yes No
Electrical isolation Creepage distances and
clearances
Actuator/contact mm 4 No
Contact/contact mm No 4 No 4 No
Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5 No
1.2/50 μs Contact/contact kV No > 2.5 No > 2.5 No
Contacts μ contact 1 NO 2 NO 1 NO 2 NO 1 NO
• Rated operational voltage Ue V AC 250
• Rated operational current Is
- At p.f. = 1 A 16 10
- At p.f. = 0.4 A 4 2
12 • Minimum contact load
• Contact switching Closes with approaching
V; mA 10; 100
Terminals 3/4 5/6 and 9/10 3/4 5/6 and 9/10 No
darkness
Connections
• Terminals ±screw (Pozidriv) PZ 1
• Conductor cross-sections
- Rigid mm2 1.5 ... 6 1.5
- Flexible, with end sleeve Min. mm2 0.75 0.5
Environmental conditions
• Permissible ambient temperature
- Device °C -10 ... +55
- Light sensor °C -30 ... +70 --
• Permissible humidity
- Device % < 80
- Light sensor % < 98 --
• Degree of protection Acc. to EN 60529
- Device IP20, with connected conductors IP54
- Light sensor IP55 IP65 No
• Safety class Acc. to EN 61010 II
Monitoring Devices
Monitoring Devices for Plants and Devices
Dusk switches
2-channel version,
Setting range 2 ... 500 lux
with 7LQ2 910 light sensor,
for surface mounting, IP55,
expandable to 24 channels through parallel
switching of 12 devices, which can be mutually
controlled through a light sensor.
250 16 230 3 B 7LQ2 101 1 1 unit 027 0.253
with 7LQ2 911 light sensor,
for flush wall mounting, IP65
expandable to 24 channels through parallel
switching of 12 devices, which can be mutually
controlled through a light sensor.
250 16 230 3 B 7LQ2 103 1 1 unit 027 0.279
1-channel version,
Setting range 2 ... 500 lux
for surface mounting, IP54,
with integrated light sensor
250 10 230 – C 5TT3 303 1 1 unit 027 0.226
Degree of protection IP65, for 7LQ2 102 and 7LQ2 103, B 7LQ2 911 1 1 unit 027 0.080
for flush wall mounting, 2 ... 500 lux
Monitoring Devices
Monitoring Devices for Plants and Devices
Temperature controllers
■ Overview ■ Benefits
The temperature controllers are used for controlling or limiting • Electronic temperature controllers with red/green LED for sup-
temperatures in residential and non-residential buildings, as well ply voltage indication, switching status indication and temper-
as in industrial areas. They're used for heating registers, panel ature sensor monitoring. This supports the monitoring of safe
and hot air heating and direct floor heating, as a limiting thermo- operation at all times
stat for air-conditioning systems and cooling systems, switch- • The temperature sensor with the measuring element KTY or a
gear cabinet cooling, etc. as well as for temperature control in PT100 is monitored for short-circuits and interruptions. This
humid and dusty rooms. Can also be used for inaccessible room protects against unpleasant surprises during operation.
temperature setting for rooms in public buildings, such as
schools, dayrooms and comparable applications.
■ Technical specifications
7LQ2 001 7LQ2 002 7LQ2 003 7LQ2 005
Standards EN 60730
Rated control voltage Uc V AC 230
Primary operating range At 50/60 Hz × Uc 0.8 ... 1.2
Rated frequency fn Hz 45 ... 65
Measuring ranges, setting ranges °C -30 ... +30 0 ... +60 +40 ... +100 2 ... +400
Switching hysteresis Adjustable °C 1 ... 5 4 ... 20
Status indication, LED
Switching status indication
• Actuating voltage Green
• Switching state ON Red
• Break or short circuit of the sensor conductor Red flashing
Different phases Actuator/contact permissible Yes
Electrical isolation Creepage distances and
clearances, actuator/contact mm 4
Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5
(1.2/50 μs)
Contacts μ contact 1 CO
• Rated operational voltage Ue V AC 250
• Rated operational current Is
- At p.f. = 1 A 16
- At p.f. = 0.4 A 4
• Minimum contact load V; mA 10; 100
12 • Contact switching Closes with increasing
temperature
Terminals 3/4
Connections
• Terminals ±screw (Pozidriv) PZ 1
• Conductor cross-sections
- Rigid mm2 1.5 ... 6
- Flexible, with end sleeve Min. mm2 0.75
Environmental conditions
• Permissible ambient temperature
- Device °C -10 ... +55
- Temperature sensor °C -30 ... +105 --
• Permissible humidity
- Device % ≤ 80
- Temperature sensor % ≤ 98 --
• Degree of protection Acc. to EN 60529
- Device IP20, with connected conductors
- Temperature sensor IP65 --
• Safety class Acc. to EN 61010 II
Monitoring Devices
Monitoring Devices for Plants and Devices
Temperature controllers
12
Monitoring Devices
Monitoring Devices for Plants and Devices
P.f. controllers
■ Overview
The p.f. controllers monitor the phase displacement between in the event of valve closure or dry runs. A current transformer is
current and voltage. Because the phase displacement angle used for higher rated currents.
changes with the load of the motor, this measurement method is
ideal for the monitoring of asynchronous motors for underload If the p.f. value set at the p.f. monitor is fallen below for the dura-
and no-load operation, independent of size. However, in some tion of the set response delay, the output relay switches to the
cases, the p.f. barely changes if the load of the motor changes, alarm state and the red LED lights up. If it exceeds the p.f. value,
e.g. in the case of relatively minor load changes on large-scale the output relay switches back without any significant delay.
motors or single-phase split-pole motors or collector motors. • Adjustable p.f. response value, from 0 to 0.97
The p.f. controller monitors single and three-phase asynchro- • Current range up to 8 A
nous motors up to approx. 5 A (without current transformer) for • LED display for operation and alarm
underload and no-load operation. This is phase-sequence-inde- • Automatic resetting of alarm.
pendent and increases plant availability. Typical applications are
fan monitoring in the case of V-belt breakage, pump monitoring
■ Benefits
• The ultra compact p.f. controller requires only the smallest of
spaces and saves costs.
■ Technical specifications
5TT3 472
Standards IEC/EN 60255, VDE 0435
Rated control voltage Uc 3 V AC 400
Primary operating range With AC supply × Uc 0.8 ... 1.1
Frequency range fn Hz 45 ... 65
Rated power dissipation Pv VA Approx. 11
Rated impulse withstand voltage Uimp Against contacts kV <4
Current measuring circuits For AC systems
Current measuring range Imeas A AC 0.4 ... 8
Short-time load carrying capacity For 2 s A 20
For 0.5 s A 40
Current transformer, Class 3 or better Secondary current A 1 or 5
Setting range Adjustable p.f. 0 ... 0.97
Response delay Adjustable s 1 ... 100
12
Short-circuit strength Fuse 4 A gL A 4
Contacts μ contact 1 CO
• Rated operational voltage Ue V AC 250
• Rated operational current Ie Thermal current A 4
AC-15 NO contacts A 3
AC-15 NC contacts A 1
AC-13 at 24 V DC A 1
• Minimum contact load V; mA 10; 100
Connections
• Terminals ±screw (Pozidriv) PZ 2
• Conductor cross-sections
- Rigid Max. mm2 2 × 2.5
- Flexible, with end sleeve Min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Resistance to climate Acc. to EN 60068-1 20/60/4
Degree of protection Acc. to EN 60529 IP20, with connected conductors
Monitoring Devices
Monitoring Devices for Plants and Devices
Thermistor motor protection relays
■ Overview
Thermistor motor protection relays monitor the thermistors • Response value: 3.2 to 3.8 kΩ
wound in motors. This helps prevent thermal motor overloads, • Release value: 1.5 to 1.8 kΩ
e.g. due to high switching frequency, single-phasing, disabled
cooling or excessive ambient temperatures. Up to 6 thermistors • Max. cable length of sensor supply cable NYM 2 × 1.5
in series can be monitored. A conductor break in the sensor con- is 100 m
ductor will immediately trip the device. The device can also be • Remote Reset: over A1/A2 (NC contact) or over X1/X2
used for monitoring wound quick-break switches - e.g. bimetal (NO contact)
thermostats. This offers all-round motor protection.
LED displays:
• For the detection of
- Temperature limits being exceeded • Green LED: lights up when operational voltage is applied
- Wire breaks in sensor circuits • Red LED: lights up in the event of overtemperatures or an
• 1 input for 1 to 6 thermistors interruption in the sensor circuit.
• With 2 LEDs green/red for ready-to-run and fault
■ Benefits
• The test button for the diagnosis of the devices ensures high • A remote reset enables the device to be switched back on
functional reliability for users again centrally at any time. This increases plant availability.
• The ultra compact thermistor motor protection relay requires
only the smallest of spaces. This saves costs
■ Technical specifications
5TT3 431
5TT3 432
Standards IEC 60255; IEC 61810
Rated control voltage Uc V AC 230
Primary operating range × Uc 0.9 ... 1.1
Rated frequency Hz 50/60
Response value kΩ 3.2 ... 3.8
Release value kΩ 1.5 ... 1.8
Minimum contact load V; mA 10; 100
Rated insulation voltage Ui Between coil/contact kV 4
Rated impulse withstand voltage Uimp Actuator/contact kV > 2.5
Contacts μ contact (AC-11) A 3
• Rated operational voltage Ue
• Rated operational current Ie
V AC
A
230
5 12
Actuator/contact mm 4
Connections
• Terminals ±screw (Pozidriv) PZ 1
• Conductor cross-sections
- Rigid Max. mm2 2 × 2.5
- Flexible, with end sleeve Min. mm2 1 × 0.5
Permissible ambient temperature °C -20 ... +60
Resistance to climate Acc. to EN 60068-1 20/60/4
Monitoring Devices
Monitoring Devices for Plants and Devices
Notes
12
Software
13/2 Introduction
Technical Information
can be found at
www.siemens.com/lowvoltage/support
under Product List:
- Technical Specifications
under Entry List: 13
- Updates
- Download
- FAQ
- Manuals
- Characteristics
- Certificates
and at
www.siemens.com/lowvoltage/configurators
- Configurators
Software
Introduction
■ Overview
SIMARIS design
Software tool for the quick and effective dimensioning of power
distribution for non-residential and industrial buildings:
• Dimensioning on the basis of real products according to
acknowledged technical rules and standards (VDE, IEC)
• Automatic access to an integrated product database
• Easy implementation and modification in the planning and
realization concept
• Reduction of routine work
SIMARIS project
Software tool to provide a quick overview of the space require-
ment for electrical power distribution and simple costing for pur-
pose-built and industrial buildings:
• Automatic selection and placement of matching distribution
systems
• Fast overview of space requirements and budget
• Thorough planning from the medium voltage supply to the
distribution board
• Easy adaptation of the project plans in case of changes in
use or expansions
• New from Version 2.0 upwards: Automatic generation of
specifications
SIMARIS curves
Software tool for quickly and easily comparing tripping charac-
teristics in Siemens low-voltage-protection equipment:
• Characteristic curve display and overview
• Device selection via order number or selection aid
• Saving of selected devices as favorites
• Saving of several characteristic curves including selected
settings as a complete project
13
More information about SIMARIS
You can find more information and order options on the Internet
at:
www.siemens.com/simaris
Software
Introduction
13
Switch ES Power
Shared software platform for communication-capable
SENTRON 3WL and SENTRON 3VL circuit breakers:
• Parameterization, documentation, operation and monitoring
in one software
• Clear representation of all available parameters
• All the available status information and measured values are
displayed in dialog boxes
• Software for SENTRON 3WL and SENTRON 3VL
Software
Planning the Power Distribution System with SIMARIS
SIMARIS design
■ Overview ■ Benefits
SIMARIS design • Reduction of routine work
• Dimensioning on the basis of real products according to
acknowledged technical rules and standards
• Integrated product database
• Detailed knowledge of products and systems not required
• Easy implementation and modification in the planning and
realization concept
• Clear-cut presentation of changes with specification of the
revision date
• Detailed parts lists with exact product descriptions
• Easy adaptation in case of changes in use or expansions
• Comprehensive documentation with simple data transfer
(Office, CAD etc.)
■ Application
SIMARIS design is suitable for dimensioning electric power dis-
tribution systems in all industrial and non-residential buildings.
From shopping centers to hospitals and production buildings –
with SIMARIS design it is possible to reduce the amount of work
required for the overall planning of power distribution systems
SIMARIS design is a software tool for the quick and effective di-
and hence the time spent on selecting and dimensioning the
mensioning of power distribution for non-residential and indus-
necessary equipment.
trial buildings.
In the planning phase already, the complete circuit can be di-
mensioned on the basis of real products. This avoids additional
costs due to uncoordinated systems in the implementation
phase. The right components and distribution systems for the
case in question are selected automatically in the light of the
product data stored in SIMARIS design.
Every configuration of the electric power distribution is subject
to frequent change and adaptation in the implementation phase
as well as in the planning phase. SIMARIS design incorporates
each change into the supply concept and automatically checks
its reliability in terms of the regulations and standards currently
in force.
Even an analysis of selectivity, for example for safety power sup-
ply elements, can be simply performed with SIMARIS design. All
these steps are precisely documented in SIMARIS design.
Software
Planning the Power Distribution System with SIMARIS
SIMARIS project
■ Overview
Detailed information about Siemens units or their order numbers
are not needed because SIMARIS project makes the selection
automatically on the basis of the parameters entered. For each
item of switchgear or each distribution, SIMARIS project takes
the wiring, control and measurement etc. into account.
A system plan drawn up professionally in SIMARIS design can
also be imported into SIMARIS project, which means that select-
ing devices becomes redundant and the project structure is
formed automatically. Convenient output variants are available
to document the results, and Version 2.0 and higher also in-
cludes the automatic generation of specifications for the
planned systems.
Typical versions of a system planned in SIMARIS project can be
saved and imported continually into new projects from the favor-
ites library. Automatically created systems can also be subse-
quently optimized or changed. This is particularly relevant if
planning becomes more detailed and the budget needs to be re-
inforced as a result.
For detailed calculation of costs – on an up-to-date and regional
basis – and for more project support please contact your
SIMARIS project is a software tool for providing a quick overview Siemens representative.
of the space requirement for electrical power distribution in non-
residential and residential buildings, for simple costing of the re- More information and order options
quired systems and for the automatic generation of specifica- can be found on the Internet at:
tions. www.siemens.com/simarisproject
The following is determined in SIMARIS project based on the
pre-defined project structure and the basic technical specifica-
tions selected:
• For medium-voltage switchgear: selection of the required sys-
tem and the required fields, then presentation of a front view
with dimensions.
• For transformers: selection of the required system and then
the required quantity. Selected transformers are presented as
a parts list.
• For low-voltage switchgear and distribution boards: selection
of the required protection devices and switching devices per
system. The best suited distribution system is automatically
selected from the created list of distribution devices, is
equipped with the devices and presented graphically in an
automatically generated front view including dimensions.
• For busway systems: selection of the required system, then
specification of the length and selection of the additionally re-
13
quired components, e.g. infeeds, junction units and tap-off
units. All the resulting components are listed in a parts list.
■ Benefits ■ Application
• Automatic selection and placement of matching distribution SIMARIS project is suitable for establishing space requirements
systems and determining the costs of electrical power distribution in all
• Fast overview of space requirements and budget industrial and non-residential buildings. From shopping centers
• Thorough planning from the medium voltage supply to the dis- to hospitals and production buildings – with SIMARIS project it is
tribution board possible to reduce the amount of work required for the overall
planning of power distribution systems and hence the time spent
• Intuitive and easy to operate on selecting and dimensioning the necessary equipment.
• Saving planned systems for similar projects individually in the
favorites library and importing them from there into new proj-
ects
• e.g. graphic views, lists and specifications
• Easy adaptability to changes in use or expansions
• Importing of a project drawn up in SIMARIS design 5.0 profes-
sional
Software
Planning the Power Distribution System with SIMARIS
SIMARIS curves
■ Overview ■ Benefits
• Characteristic curve display and overview
• Clearly structured catalog selection
• Device selection via order number or selection aid
• Saving of selected devices as favorites
• Saving of several characteristic curves including settings as
complete project
• User-friendly system documentation
■ Application
SIMARIS curves is a software tool for displaying tripping charac-
teristics, let-through power curves and let-through current
curves of Siemens low-voltage controls and fuses. Ranging from
shopping malls through hospitals to production shops –
SIMARIS curves lets you call up the required curves quickly and
documents in the required output language.
SIMARIS curves is a software tool for the quick and simply com-
parison of tripping characteristics for Siemens low-voltage-pro-
tection equipment and fuses.
With SIMARIS curves it is possible to simulate parameter set-
tings on protective devices. The respective characteristic curve
is selected by direct entry of the Siemens order number or with
a user-friendly selection tool. Individual products with default at-
tributes can be stored as favorites and called up again. Tripping
characteristics with tolerance ranges are available for presenta-
tion along with let-through current and let-through power charac-
teristic curves. A printout summary documents the characteristic
curves selected and each of their settings.
More information and order options
can be found on the Internet at:
www.siemens.com/simariscurves
13
Software
ALPHA SELECT Planning and
Configuration Software
■ Overview
Whether you are an installation engineer or a control cabinet en-
gineer, an electrical wholesaler or a planner – the software
ALPHA SELECT makes it quicker and easier than ever before to
plan and configure distribution boards and meter cabinets.
Easy-to-use, intuitive functions accompany you step-by-step
through the entire project, from planning to installation. Configu-
ration errors are virtually impossible thanks to the collision tests
and configuration rules saved in the program.
ALPHA SELECT comprises:
• ALPHA SIMBOX small distribution boards
• ALPHA 400-ZS meter cabinets
• ALPHA Distribution Boards
• ALPHA 8HP molded-plastic distribution systems
• ALPHA BOX IEC wall-mounted distribution boards
In addition you can use the electronic catalogs (EGH selection
catalog and CA 01) to select BETA low-voltage circuit protection
products, GAMMA instabus products (for building manage-
ment) and many other items from the Siemens Industry product
selection.
Calculation of power loss
13
Selection of the ALPHA distribution system Parts list with calculation
Distribution board equipment, front view Illustration of the device structure as single-pole circuit diagram
Software
ALPHA SELECT Planning and
Configuration Software
Start with the selection of a suitable distribution system and dis-
tribution board by selecting the required degree of protection, ■ Benefits
safety class and dimensions. You can then just drag & drop the • Cabinet selection: simple selection of cabinet system, degree
required assembly kits, devices and accessories of your choice. of protection, safety class and dimensions
Essential accessories are determined automatically. When se- • Selection of equipment using technical specifications
lecting the devices, customer specifications can be prepared
using either item numbers or in accordance with the electrical • Alternative structuring of the devices according to
structure. In case 2 a graphical representation in the form of a - Electrical structure and graphic output as 1-pole circuit dia-
1-pole circuit diagram has been available since the launch of gram
Version 6.0. - Item numbers in the customer specifications
• Positioning of assembly kits and devices using drag & drop
The graphic representation of the structure enables individual
levels, such as doors, covers, equipment racks or devices, to be • Automatic determination of key accessories
visualized, rendered transparent and hidden in order to provide • Numbering of assembly kits in the assembly drawing
users with a constant overview of already configured compo-
• Automatic issue of item codes for devices
nents.
• Calculation of power loss
There is also an integrated option for power loss calculation
which enables comparison of the calculated power loss values • Differentiated calculation options, including allowance made
of the devices installed in the distribution board with the thermal for assembly work
rating of the distribution board, giving due consideration to the • Listing in the assembly structure of devices placed in the as-
point of installation and the permissible overtemperature sembly kits, including numbering of the assembly kits and the
(related to 35 °C ambient temperature). item codes of the devices
Frequently required components can be saved as favorites for • Easy drawing up of quotations for projects: Clearly arranged
integration in other projects at any time. output selection for parts lists, assembly drawing and assem-
bly structure
Used in conjunction with existing calculation aids, users are able
• Clearly arranged calculation aids. Calculations for individual
to tailor parts lists, assembly drawings and assembly structures
items and assembly, for material surcharges, shipment costs,
to individual requirements and output as both a hard copy and
discounts and miscellaneous extras are easy to perform in the
in electronic form.
parts list. Standard discounts for each price group can also be
In addition to planning and calculation in the program, users are saved in the memory.
also able to produce parts lists and graphic documentation to • Option for quotations with individual company logo
accompany customer quotations or for ordering the required
components. • Update over the web with quick download times
• Manual available as a download
The workshop version, which comprises a structured list of the
distribution boards and the respectively installed parts and
graphical representation of the different user-defined layers, di- ■ Technical specifications
rectly supports the building of distribution boards configured us-
ALPHA SELECT system requirements:
ing ALPHA SELECT.
• Processor: from 1 GHz
www.siemens.com/alpha-select
• Main memory: minimum 512 MB
• operating system: Windows 7/VISTA/XP/2000
• Free hard disk space: 100 ... 500 MB
(depending on the number of modules installed)
13 • Display resolution: minimum 1024×768 with 16-bit color inten-
sity
■ More information
Support for planning and configuration is available from:
• www.siemens.com/lowvoltage/technical-support
• Tel.:+49 (0)9 11 8 95 72 22
Software
Configuring, Visualizing and Controlling with SIMATIC
SIMATIC PCS 7 powerrate
■ Overview ■ Benefits
• Identification of power-intensive consumer devices and pro-
cesses in order to introduce measures for improving power ef-
ficiency
• Comparison of consumption profiles for greater efficiency of
process design
• Optimizing the company according to energy parameters
based on an assessment of consumption and costs
• Complying with the contractually agreed power limit, thus pre-
venting higher power supply costs or penalty payments
• Integration of the SENTRON PAC3200 and
SENTRON PAC4200 measuring devices, with a quick over-
view of selected measured values and signals
• Integration of switches, with an overview of switch status and
switching possibilities
• Exact assignment and comparison of the consumption data of
certain work processes through batch-related consumption
recording
Software
Configuring, Visualizing and Controlling with SIMATIC
SIMATIC PCS 7 powerrate
■ More information
Information about using SIMATIC PCS 7 Powerrate
is available from
Siemens AG, Technical Support
Tel.: +49 (0) 911 895 7 222
Fax.: +49 (0) 911 895 7 223
www.siemens.com/automation/support-request
You can find further general information on the Internet at:
www.siemens.com/powermanagementsystem
13
Software
Configuring, Visualizing and Controlling with SIMATIC
SIMATIC WinCC powerrate
■ Overview ■ Benefits
• Identification of power-intensive consumer devices and pro-
cesses in order to introduce measures for improving power ef-
ficiency
• Comparison of consumption profiles for greater efficiency of
process design
• Optimizing the company according to energy parameters
based on an assessment of consumption and costs
• Complying with the contractually agreed power limit, thus pre-
venting higher power supply costs or penalty payments
• Integration of the SENTRON PAC3200 and SENTRON 4200
measuring devices, with a quick overview of selected mea-
sured values and signals
• Integration of switches, with an overview of switch status and
switching possibilities
• Exact assignment and comparison of the consumption data of
certain work processes through batch-related consumption
recording
Software
Configuring, Visualizing and Controlling with SIMATIC
SIMATIC WinCC powerrate
■ More information
Information about using SIMATIC WinCC Powerrate
is available from
Siemens AG, Technical Support
Tel.: +49 (0) 911 895 7 222
Fax.: +49 (0) 911 895 7 223
www.siemens.com/automation/support-request
You can find further general information on the Internet at:
www.siemens.com/powermanagementsystem
13
Software
Configuring, Visualizing and Controlling with SIMATIC
SIMATIC PCS 7 Library PAC3200
■ Overview ■ Benefits
• Full integration of SENTRON PAC3200 in the PCS 7 process
control system through PROFIBUS DPV1 using a certified
PCS 7 add-on module
• Reading out and displaying device data
• Inputting limit values for monitoring through the driver block
• Resetting values on the device (min/max values)
■ Application
SIMATIC PCS 7 Library PAC3200 is used in all areas in which
PCS 7 is used. Full integration in PCS 7 means that there is no
need for a special system environment. Predefined modules and
symbols give you the assurance of building on tested and certi-
fied product components. In future the PAC4200 can also be
used as a measuring instrument.
1)
For currently-supported SIMATIC PCS 7 versions see
http:/support.automation.siemens.com
Software
Configuring, Visualizing and Controlling with SIMATIC
3WL/3VL block library for SIMATIC PCS 7
■ Overview ■ Benefits
• Full integration of SENTRON circuit breaker in the PCS 7 pro-
cess control system through PROFIBUS DPV1 using a certi-
fied PCS 7 add-on module
• Remote switching and monitoring
• Reading out of maintenance information
• Automatic information in case of overload, short-circuit and
faults
• Reading out and displaying device data
• Limit monitoring through the driver block
• Resetting values on the device (min/max values)
■ Application
The 3WL/3VL block library for SIMATIC PCS 7 is used in all areas
in which PCS 7 is used. Full integration in PCS 7 means that there
is no need for a special system environment. Predefined mod-
ules and symbols give you the assurance of building on tested
and certified product components.
The 3WL/3VL PCS 7 block library for SENTRON circuit breaker
allows for the simple and quick integration of the SENTRON
circuit breaker into the PCS 7 process world.
It comprises one driver block, one diagnostics block and the
faceplates. The blocks in the SIMATIC S7 supply current, power
and energy data to the faceplates in the user interface of the pro-
cess control system, generate signals and guarantee connec-
tion to the maintenance system of PCS 7.
Faceplates
Faceplates serve as a user interface for operating and monitor-
ing and enable the SENTRON circuit breaker to be displayed
and performed simply as a PCS 7 object.
The 3WL/3VL block library for SIMATIC PCS 7 provides for con-
tinual plant transparency. Critical plant states are recognized
quickly and costs owing to outages avoided. System availability
is permanently increased
This transforms the SENTRON circuit breaker into an integral
component of PCS 7.
The operating systems supported are the same as those for the
SIMATIC PCS 7.
13
■ Selection and ordering data
SIMATIC PCS 7 V 6.1 SP1 and PCS 7 V 7.0 SP1
Version DT Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
SET, M) approx.
kg
3WL/3VL block library for SIMATIC PCS 7
Engineering license B 3ZS2 782-1CC10-0YG0 1 1 unit 133 0.250
• For operation on one PCS 7 OS (single workstation system or server) and
an automation system (AS).
• When using additional PCS 7 OS devices, you need an engineering license
for each PCS 7 OS.
Software
Configuring, Visualizing and Controlling with SIMATIC
PAC3200 block library for SIMATIC WinCC
System requirements
■ Overview
The SENTRON PAC3200 block library for SIMATIC WinCC is
SENTRON PAC3200 block library for SIMATIC WinCC released for
• WinCC V 6.2 SP2
• WinCC V 7.0
• WinCC V 7.0 SP1
WinCC options AS-OS Engineering and Basic Process Control
must be installed. The block library is available for both S7-300
and S7-400. At least one S7 CPU317-2DP is required for use in
the S7-300 area. At least one S7 CPU414-2 is required for use in
the S7-400 area.
Supported operating systems are the same as for
SIMATIC WinCC.
■ Benefits
• Full integration of the SENTRON PAC3200 in SIMATIC WinCC
through PROFIBUS DPV1 The block library is a certified
WinCC add-on module
• Reading out and displaying device data
• Inputting limit values for monitoring through the driver block
The SENTRON PAC3200 block library for SIMATIC WinCC • Resetting values on the device (min/max values)
enables the seamless integration of the SENTRON PAC3200
multifunction measuring instrument in WinCC.
■ Application
It comprises one driver block, one diagnostics block and the
faceplates. The blocks in the SIMATIC S7 supply energy data to The SENTRON PAC3200 block library for SIMATIC WinCC is
the faceplates in the user interface of WinCC, generate signals used in all areas in which WinCC is used. Predefined blocks and
and guarantee connection to the maintenance system of WinCC. symbols give you the assurance of building on tested and certi-
fied product components. In future the PAC4200 can also be
Faceplates used as a measuring instrument.
Faceplates serve as a user interface for operating and monitor- The blocks work in a cyclic mode with fast updating of the impor-
ing and enable technologically important values and functions of tant measured quantities and, in future, in an acyclic mode with
the SENTRON PAC3200 to be displayed and performed in little space requirement in the process image.
WinCC.
Between the faceplates and the blocks as well as between the
blocks and the SENTRON PAC3200 there exist on the system
side bidirectional communication connections not only for dis-
playing values in the faceplates but also for forwarding input
data to the device.
This makes the SENTRON PAC3200 power monitoring device an
integral component of WinCC.
13
■ Selection and ordering data
SIMATIC WinCC V 7.0 and WinCC V 7.0 SP 1
Version DT Order No. Price PU PS*/ PG Weight
per PU (UNIT, P. unit per PU
SET, M) approx.
kg
SENTRON PAC3200 block library for SIMATIC WinCC1)
Engineering license 3ZS2 791-1CC10-0YG0 1 1 unit 133 0.250
• For operation on one PCS 7 OS (single workstation system or server) and
an automation system (AS).
• When using additional WinCC OS devices, you need an engineering license
for each WinCC OS.
Software
Configuring, Visualizing and Controlling with SENTRON
SENTRON powermanager
■ Overview
The SENTRON-based power management system is comprised SENTRON powermanager is designed for:
of a PC with the related power management software and with • collecting
the related devices which are connected directly to the PC
through Ethernet. • monitoring
• evaluating
General goals of a power management system:
• presenting
• to identify savings potential
• archiving
• to reduce power costs
• to ensure power availability power data from SENTRON PAC3100, PAC3200 and PAC4200
multifunction measuring instruments, SENTRON 3WL/3VL circuit
through transparency of the momentary conditions and through breakers, and any modbus-capable detecting devices.
comprehensive power assignments and evaluations.
"Expert" and "Web" option packs
The SENTRON powermanager PC-based power management
software The SENTRON powermanager standard package already cov-
ers the usual requirements. With this package the user receives
• is an independent power management software an easy-to-engineer power management software which en-
• can be operated with a PC and measuring instruments with ables the data detected by the measuring instruments to be
Ethernet connection read out, presented, archived and processed in basic evalua-
• is expandable from the simple standard application to tions. With the "Expert" option pack the user receives full flexibil-
a fully flexible customer solution ity for the presentation of graphic interfaces (e.g. single line pre-
sentations) in order to integrate his own images and devices.
• is fully scalable with regard to the number of devices and to The data/images are displayed as standard using a Windows cli-
the software's functions ent which must be installed on the PC. The "Web" pack is offered
13 • Ensures the optimum integration of measuring instruments
from the SENTRON PAC range, SENTRON 3WL/3VL circuit
to meet the market's demands for web presentation.
■ Benefits
• Transparency of power flows This reduces the engineering work for the customer and gives
• Exact knowledge of the consumption profile the user the assurance of knowing that the device functions are
optimally supported in the software.
• Increase of power efficiency
• Optimization of power supply contracts The SENTRON powermanager software comprises a server/cli-
ent software for the acquisition, processing, presentation and ar-
• Compliance with contractual terms chiving of power data. These power data are supplied primarily
• Assignment of power costs to cost centers by multifunction measuring instruments (PAC) or 3WL/3VL circuit
• Optimization of plant maintenance breakers which are connected to the system through Ethernet.
• Identification of critical plant conditions
In the SENTRON product family the user will find not only a
power management software in the form of SENTRON power-
manager but also the matching hardware in the form of
SENTRON PAC measuring instruments and SENTRON 3WL/3VL
circuit breakers for realizing a complete power management
system. The components are optimally coordinated with each
other, e.g. special drivers for the SENTRON devices are inte-
grated in the SENTRON powermanager software so that on the
one hand the power data acquisition can take place without any
great configuration effort and on the other hand the most impor-
tant measured values or states are indicated by predefined dis-
plays.
Software
Configuring, Visualizing and Controlling with SENTRON
SENTRON powermanager
■ Application
Applications • Archiving of measured quantities
The product offers a standard power management solution • Monitoring of status and limits, with generation of correspond-
which provides the user with the following basic functionality: ing signals
• Collection of measured quantities from the devices • Reserve curve display for visualizing the achieved data and
online data
• Presentation of the measured quantities from the devices in ta-
ble form in a predefined standard view for • Cost center reports based on predefined rates and the ar-
SENTRON PAC3100, PAC3200 and PAC4200 measuring in- chived consumption data
struments and 3WL/3VL circuit breakers • OPC server
• Free presentation of measured quantities possible, including • Configuration of the system including user management
from non-Siemens devices using generic Modbus drivers
System configuration
Ethernet
Data processing
SENTRON powermanager server
Ethernet (Modbus)
Data detection PAC3200 PAC4200 PAC3200
Measuring/protection devices
Modbus RS485
PAC3100 SENTRON SENTRON
I202_01389
3WL 3VL
Software
Configuring, Visualizing and Controlling with SENTRON
SENTRON powermanager
■ More information
13 You can find more information on the Internet at:
www.siemens.com/powermanagementsystem
Software
Configuring, Visualizing and Controlling with SENTRON
Switch ES Power
■ Overview ■ Benefits
• Parameterization, documentation, operation and monitoring in
one software
• Documentation of measured values and settings
• Clear representation of all available parameters
• All the available status information and measured values are
clearly displayed in dialog boxes
• Software for SENTRON 3WL and SENTRON 3VL
• Easy connection build-up through acyclic PROFIBUS DPV1
data traffic
• Identical storage format for parameters with the Breaker Data
Adapter (BDA)
• Easy-to-operate Windows interface
• No programming knowledge required for operation
Object manager of Switch ES Power
• Uniform data management for circuit breaker parameters
• Automatic parameterization if components are replaced
Software
Notes
13
Appendix
20/5 UL Notes
Appendix
Catalog notes
■ Overview
Trademarks Symbols
All product designations may be registered trademarks or prod- The symbols used in this catalog are listed below. These sym-
uct names of Siemens AG or supplier companies whose use by bols are use in conjunction with an orange background to mark
third parties for their own purposes may violate the rights of the special selection criteria (e.g. connections, types of coordina-
owner. tion, etc.).
Amendments
Connections
All technical data, dimensions and weights are subject to
change without notice unless otherwise specified on the pages Screw terminals
of this catalog. Ring terminal lug connection
Dimensions Switching capacity of 3WL circuit breakers
All dimensions are in mm. N ECO switching capacity
(Icu up to 55/66 kA at 500 V)
Images
S Standard switching capacity
The illustrations are not binding. (Icu up to 66/80 kA at 500 V)
Appendix
Ordering notes
■ Logistics
General Packaging, packing units
With regard to delivery service, communications and environ- The packaging in which our equipment is dispatched provides
mental protection, our logistics service ensures "quality from the protection against dust and mechanical damage during trans-
moment of ordering right through to delivery". By designing our port, thus ensuring that all our products arrive in perfect condi-
infrastructure according to customer requirements and imple- tion.
menting electronic order processing, we have successfully opti-
mized our logistics processes. We select our packaging for maximum environmental compati-
bility and reusability (e.g. crumpled paper instead of polystyrene
We are proud of our personal consulting service, on-time deliv- chips for protection during transport in packages up to 32 kg)
eries and 1-day transport within Germany. and, in particular, with a view to reducing waste.
To this end, we supply the preferred types marked with } With our multi-unit packaging and reusable packaging, we offer
ex works. you specific types of packaging that are both kind to the environ-
ment and tailored to your requirements:
We regard the DIN ISO 9001 certification and consistent quality
checks as an integral part of our services. Your advantages at a glance:
Electronic order processing is fast, cost-efficient and error-free. • Lower order costs.
Please contact us if you want to benefit from these advantages. • Cost savings through uniform-type packaging: low/no dis-
posal costs.
• Reduced time and cost thanks to short unpacking times.
• "Just-in-time" delivery directly to the production line helps re-
duce stock: cost savings through reduction of storage area.
• Fast assembly thanks to supply in sets.
• Standard Euro boxes - corresponding to the Euro pallet mod-
ular system - suitable for most conveyor systems.
• Active contribution to environmental protection.
Appendix
Ordering notes
■ Overview
Ordering special versions Ordering very small quantities
When ordering products that differ from the standard versions When small orders are placed, the costs associated with order
listed in the catalog, "–Z" must be added to the Order No. indi- processing are greater than the order value. We therefore rec-
cated and the required features must be specified using alpha- ommend that you combine several small orders. Where this is
numeric order codes or plain text. not possible, we regret that we are obliged to make a small pro-
cessing charge: for orders with a net goods value of less than
€ 250 we charge an € 20 supplement to cover our order pro-
cessing and invoicing costs.
Explanations on the Selection and Ordering Data
Delivery time class (DT)
Preferred types are device types that can be delivered immediately ex works, i.e. they are dispatched
DT Meaning within 24 hours.
} Preferred type Normal quantities of the products are usually delivered within the specified time following receipt of your
order at our branch.
A Two workdays
In exceptional cases, the actual delivery time may differ from that specified.
B One week
The delivery times apply up to the ramp at Siemens AG (products ready for dispatch).
C Three weeks
The transport times depend on the destination and type of shipping. The standard shipping time for Ger-
D Six weeks
many is one day.
X On request
The delivery time classes specified here represent the state at 10/2010. They are permanently optimized.
Up-to-date information can be found at www.siemens.com/industrymall.
Price units (PU)
The price unit defines the number of units, sets or meters to which the specified price and weight apply.
PS/P. unit (packaging size/packaging unit)
The packaging size / packaging unit defines the number, e.g. of units, sets or meters, for outer packaging.
• The first digit in the PS/P. unit column (packaging size/packaging unit) indicates the minimum order quantity. You can only order this
specified quantity or a multiple thereof.
• The second digit in the PS/P. unit column (packaging size/packaging unit) specifies the number of units contained in larger packaging
(e.g. in a carton). You must order this quantity or a multiple thereof if you want the item to be delivered in a larger packaging quantity.
Examples:
Appendix
UL notes
With our UL-certified products for low-voltage power distribution Here you will find information on for example UL standards, UL
and electrical installation you are on the safe side and can build classification and a number of technical particularities of UL.
control cabinets according to UL standard easily and quickly. Under "UL Overview/Standards and Approvals" we provide a
UL-certified products to be found in this catalog include for ex- summary of the available products and product groups. A table
ample: lists the UL standards to which the products conform and con-
tains links to the corresponding UL reports.
• SENTRON circuit breakers, motor starter protectors and switch
disconnectors Under "Portfolio" we round off with a list of our most relevant
• ALPHA FIX terminal blocks products for low-voltage power distribution and electrical instal-
lation as well as for low-voltage controls (including links to the re-
• SENTRON busbar systems spective Internet product pages).
• Miniature circuit breakers and fuses from the BETA low-voltage Simply click on the navigation bar and go on a UL discovery
circuit protection range tour!
Appendix
■ Overview
In many industries the production, processing, transport and In this catalog, special attention is drawn to devices which com-
storage of combustible substances are accompanied by escap- ply with the ATEX Directive. However, it does not replace inten-
ing gases, vapor or spray which find their way into the environ- sive study of the relevant fundamentals and directives when
ment. Other processes result in combustible dust. Together with planning and installing electrical systems.
the oxygen in the air, the result can be an explosive atmosphere
which will explode if ignited.
Serious injury to persons and damage to property can result par-
ticularly in the chemical and petrochemical industry, mineral oil
and natural gas production, mining, mills (e.g. grain, solid mate-
rials) and many other sectors.
To guarantee the maximum possible safety in these areas, the
legislators of most countries have drawn up requirements in the
form of laws, regulations and standards. In the course of global-
ization, great progress has been made with regard to uniform di-
rectives for explosion protection.
With Directive 94/9/EC, the European Union laid the foundations
for complete harmonization by requiring that all new devices as
from 1st July 2003 have to be approved in accordance with this
directive.
Appendix
Further documentation
■ Overview
We regard product support as just as important as the products
and systems themselves.
Visit our site on the Internet for a comprehensive offering of sup-
port for low-voltage power distribution and electrical installation
products, such as
• Operating instructions and manuals for direct download
• Online registration for seminars and events
• Up-to-date answers to your queries and problems
• Software upgrades and updates for fast download
• Telephone assistance in more than 190 countries
• Photos and graphics for external use
and much, much more - all conveniently and easily accessible.
Address:
www.siemens.com/lowvoltage
Appendix
■ Overview
Approvals, test certificates, characteristic curves
An overview of the certificates available for low-voltage power
distribution and electrical installation products along with more
technical documentation can be consulted daily on the Internet
at:
www.siemens.com/lowvoltage/support
Appendix
Appendix
Appendix
■ CE mark of conformity
Manufacturers of products which fall within the subject area to All the products in this catalog are in conformance with the EC
which EC directives apply must identify their products, operating directives and bear the CE mark.
instructions or packaging with a CE mark. • Low-voltage directive
The CE mark confirms that a product fulfills the appropriate ba- • EMC directive
sic requirements of all pertinent directives. The mark is a manda- • Machinery directive
tory requirement for putting products into circulation throughout
the EC. • Ex protection directive
The CE mark of conformity: >.
■ Accident prevention
Test certificates and approvals from the BIA (German statutory
industrial accident insurance institution in Bonn) and from SUVA
(Swiss institute for accident prevention) are available for some
devices in safety control systems. For details, see the respective
product descriptions.
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
Appendix
■ More information
You can find more information about standards and approvals at
www.siemens.com/lowvoltage/support
Appendix
Siemens contacts
Appendix
Solution partners
Appendix
Online Services
Information and ordering options available
on the Internet and DVD
Appendix
Service & Support
The unmatched complete service
for the entire life cycle
For machine constructors, solution providers and plant opera- Our Service & Support accompanies you worldwide in all mat-
tors: The service offering from Siemens Industry, Automation and ters concerning automation and drives from Siemens. We pro-
Drive Technologies includes comprehensive services for a wide vide direct on-site support in more than 100 countries through all
range of different users in all sectors of the manufacturing and phases of the life cycle of your machines and plants.
process industry
You have an experienced team of specialists at your side to pro-
To accompany our products and systems, we offer integrated vide active support and bundled know-how. Regular training
and structured services that provide valuable support in every courses and intensive contact among our employees - even
phase of the life cycle of your machine or plant - from planning across continents - ensure reliable service in the most diverse
and implementation through commissioning as far as mainte- areas.
nance and modernization.
Appendix
Service & Support
The unmatched complete service
for the entire life cycle
■ Optimization
During the service life of ma-
chines and plants, there is often
a great potential for increasing
productivity or reducing costs.
To help you achieve this poten-
tial, we are offering a complete
range of optimization services.
Appendix
■ Overview
In all issues for more efficiency - comprehensive support and ac-
Product information cess at any time to tried and tested tools, quickly and easily via
Website Fast and targeted information about low-voltage the Internet.
power distribution:
www.siemens.com/lowvoltage
Product documentation
Service & support Comprehensive technical information - from planning
portal to configuration and operation:
www.siemens.com/lowvoltage/support
Product training
SITRAIN Portal Comprehensive training program about our prod-
ucts, systems and engineering tools:
www.siemens.com/lowvoltage/training
Product hotline
Technical support Support in all technical queries about our products:
E-mail: support.automation@siemens.com
www.siemens.com/lowvoltage/technical-support
Appendix
Software licenses
■ Overview
Software types Factory license
Software requiring a license is categorized into types. With the Factory License the user has the right to install and use
The following software types have been defined: the software at one permanent establishment only. The perma-
• Engineering software nent establishment is defined by one address only.The number
of hardware devices on which the software may be installed re-
• Runtime software sults from the order data or the Certificate of License (CoL).
Engineering software Certificate of license
This includes all software products for creating (engineering) The Certificate of License (CoL) is the licensee's proof that the
user software, e.g. for configuring, programming, parameteriz- use of the software has been licensed by Siemens. A CoL is
ing, testing, commissioning or servicing. required for every type of use and must be kept in a safe place.
Data generated with engineering software and executable
programs can be duplicated for your own use or for use by third- Downgrading
parties free-of-charge. The licensee is permitted to use the software or an earlier ver-
sion/release of the software, provided that the licensee owns
Runtime software such a version/release and its use is technically feasible.
This includes all software products required for plant/machine
operation, e.g. operating system, basic system, system expan- Delivery versions
sions, drivers, etc. Software is constantly being updated.
The duplication of the runtime software and executable pro- The following delivery versions
grams created with the runtime software for your own use or for • PowerPack
use by third-parties is subject to a charge. • Upgrade
You can find information about license fees according to use in can be used to access updates.
the ordering data (e.g. in the catalog). Examples of categories of
use include per CPU, per installation, per channel, per instance, Existing bug fixes are supplied with the ServicePack version.
per axis, per control loop, per variable, etc. PowerPack
Information about extended rights of use for parameteriza-
tion/configuration tools supplied as integral components of the PowerPacks can be used to upgrade to more powerful software.
scope of delivery can be found in the readme file supplied with The licensee receives a new license agreement and CoL
the relevant product(s). (Certificate of License) with the PowerPack. This CoL, together
with the CoL for the original product, proves that the new soft-
License types ware is licensed.
A separate PowerPack must be purchased for each original
Siemens Industry Automation & Drive Technologies offers vari- license of the software to be replaced.
ous types of software license:
• Floating license Upgrade
• Single license An upgrade permits the use of a new version of the software on
the condition that a license for a previous version of the product
• Rental license is already held.
• Trial license The licensee receives a new license agreement and CoL with
the upgrade. This CoL, together with the CoL for the previous
Floating license product, proves that the new version is licensed.
The software may be installed for internal use on any number of A separate upgrade must be purchased for each original license
devices by the licensee. Only the concurrent user is licensed. of the software to be upgraded.
The concurrent user is the person using the program. Use be- ServicePack
gins when the software is started.
A license is required for each concurrent user. ServicePacks are used to debug existing products.
ServicePacks may be duplicated for use as prescribed accord-
Single license ing to the number of existing original licenses.
Unlike the floating license, a single license permits only one License key
installation of the software.
The type of use licensed is specified in the ordering data and Siemens Industry Automation & Drive Technologies supplies
in the Certificate of License (CoL). Types of use include for software products with and without license keys.
example per device, per axis, per channel, etc. The license key serves as an electronic license stamp and
One single license is required for each type of use defined. is also the "switch" for activating the software (floating license,
rental license, etc.).
Rental license The complete installation of software products requiring license
A rental license supports the "sporadic use" of engineering keys includes the program to be licensed (the software) and the
software. Once the license key has been installed, the software license key (which represents the license).
can be used for a specific number of hours (the operating hours
do not have to be consecutive).
One license is required for each installation of the software. Detailed explanations concerning license conditions can be found in the
“Terms and Conditions of Siemens AG” or under
Trial license www.siemens.com/industrymall
(Industry Mall Online-Help System)
A trial license supports "short-term use" of the software in a non-
productive context, e.g. for testing and evaluation purposes.
It can be transferred to another license.
Appendix
Subject index
■ Overview
Numerics B
4. contact (N conductor) Base load resistors
For 3LD 7/22, 7/24, 7/25 For electronic devices 12/35
Bases
For 8US 10/12
A Basic element
Accessories For surge arresters 6/17
For PAC3200 power monitoring devices 11/26, 11/27, 11/28 Basic switch version
Adapter for screw fixing For 3KA/3KE 7/34
For 3NJ4/3NJ5 7/124 Bell transformers 9/4
Adapter sleeve fitters Bells 9/9
For DIAZED fuse bases 5/16 Bi-metal ammeters
For NEOZED 5/11 For 3NJ62 7/83
Adapter sleeves Bi-metal measuring instruments
For DIAZED fuse bases 5/16 For 3NJ62 7/83
For NEOZED fuse bases 5/11 Blanking covers
Adapters with busbar terminal For 3NJ4/3NJ5 7/123
For 3NJ4/3NJ5 7/124 For 3NJ62 7/88
Aerials For 8US 10/13
For GSM alarm modules 12/30 Block library 3WL/3VL for SIMATIC PCS 7 13/14
Air circuit breakers/non-automatic air circuit breakers 1/1 ... 1/54 Box terminal assembly kit
ALPHA SELECT 13/7 For 3NJ4/3NJ5 7/125
Ammeter selector switches 11/40 Box terminals
Ammeters 3NP1 version 7/92, 7/93, 7/97
Analog 11/32 For 3NJ4/3NJ5 7/125
Digital 11/34 Breaker blocking covers
For 3NJ62 7/73, 7/83, 7/85, 7/87 For miniature circuit breakers 3/57
Analog ammeter 11/32 Busbar adapter systems 2/89
Analog voltmeters 11/32 Busbar adapters
Arc chute 3NP5 7/117
For 3KA/3KE 7/41, 7/42 For main miniature circuit breakers (SHU) 3/57
For 3NP5 7/114 For MINIZED switch disconnectors 5/11
Arcing contacts Busbar connection pieces
For 3KA/3KE 7/41, 7/42 For 8US 10/12, 10/13, 10/24, 10/25
Assembly kits Busbar covers
For SR60 distribution board components 10/9 For 3NJ62 7/88
Assembly kits for flush mounting Busbar device adapters
For 3NP 7/117 For 8US 10/16
Assembly tools Busbar supports 10/10
For 3LD 7/21, 7/22, 7/24 For 3NJ4/3NJ5 7/124
For 8US 10/13
Auxiliary conductor connections
For 3NP1 7/98, 7/100, 7/102, 7/104, 7/105 Busbar terminals
For 3NJ4/3NJ5 7/124
Auxiliary releases
For circuit breakers 1/23, 1/40, 2/57, 2/59 ... 2/60 Busbars 5/29 ... 5/32
Acc. to UL 489 3/53
Auxiliary switch mounting kit 7/126
Acc. to UL 508 3/45, 5/32
For 3NJ4/3NJ5 7/126
For residual current protective devices 4/24, 4/25
Auxiliary switches Standard 3/28, 3/39 ... 3/42
For 3KA/3KE 7/40, 7/42
Bus-mounting bases
For 3KL 7/49, 7/50, 7/56
DIAZED 5/15
For 3LD 7/21, 7/22, 7/24, 7/25
For 3NJ62 7/73, 7/82, 7/84, 7/86 Buzzers 9/9
For 3NP1 7/99, 7/101, 7/103, 7/104, 7/105
For 3NP5 7/114
For circuit breakers 1/23, 1/40, 2/57, 2/59 ... 2/61 C
Auxiliary switches (AS) Cable connection cover
For Control Switches 8/7 For 3NP1 7/99, 7/101, 7/103, 7/104, 7/105
For cylindrical fuse holders 5/21 Cap sets
For DC isolators 8/20 For Control Switches 8/7
For Insta contactors 8/32, 8/35, 8/36 For light indicators 8/14
For miniature circuit breakers 3/31, 3/52 For pushbuttons 8/11
For MINIZED switch disconnectors 5/8 Caps
For ON/OFF switches 8/18 For DIAZED fuse bases 5/16
For remote control switches 8/27
Centralized fault signaling unit 12/31
For residual current protective devices 4/14
For switch disconnectors 7/28 Changeover switches
For 3KA/3KE 7/41, 7/42
Changeover switches with interruption
For 3KA/3KE 7/41
Changeover switches without interruption
For 3KA/3KE 7/42
Circuit breaker terminals 3/59
Appendix
Subject index
Circuit breakers Current relays 12/16
Air 1/1 ... 1/54 Current transformer busbars 7/83
Auxiliary releases for 1/23, 1/40, 2/57, 2/59 ... 2/60 For 3NJ62 7/83, 7/85
Auxiliary switches 1/23, 1/40 Current transformers 2/91 ... 2/93, 7/82, 11/39, 12/27
Auxiliary switches for 2/57, 2/59 ... 2/61 For 3NJ4/3NJ5 7/127
Communication-capable 1/26, 1/43, 2/12 ... 2/29, 2/40 ... 2/51, 2/98 For 3NJ62 7/73, 7/82, 7/84, 7/86
Connection methods for 1/27 ... 1/28, 1/45 ... 1/46 Cylindrical fuse bases
Conversion sets 1/47 SITOR 5/60
Fixed mounting 1/7 ... 1/10, 1/15 ... 1/18, 1/50, 2/10 ... 2/54
Generator protection 2/46 ... 2/51 Cylindrical fuse holders 5/20, 5/21
Guide frames for 1/30 ... 1/33, 1/53 ... 1/54 SITOR 5/60
Interlocks for 2/83 ... 2/88 Cylindrical fuse links 5/19, 5/20
Molded-case 2/1 ... 2/98 SITOR 5/59, 5/60
Non-automatic molded case circuit breakers 2/30 ... 2/31, 2/52 ... 2/53
Operating mechanisms for 1/23, 1/25, 1/40, 2/55, 2/56, 2/62 ... 2/69
Plug-in version 2/70 ... 2/75 D
RCD modules 2/76 Data keys
Shunt releases 1/23, 1/40 For digital time switches 8/41
Shunt releases for 2/57, 2/59 ... 2/60
DC isolators 8/20
System protection 2/10 ... 2/25, 2/34 ... 2/51
Undervoltage releases 1/23, 1/40 Delay timers 8/51
Undervoltage releases for 2/57, 2/59 ... 2/60 Device adapters for 8US 10/16
With electronic release 1/7 ... 1/22, 1/34, 2/10 ... 2/29, 2/34 ... 2/51 Device holders
Withdrawable bridging units 1/48 For 8US 10/16
Withdrawable grounding units 1/48 DIAZED
Withdrawable short-circuits 1/48 Bus-mounting bases 5/15, 10/30, 10/31
Withdrawable version 1/11 ... 1/14, 1/19 ... 1/22, 1/51 ... 1/52, 2/70 ... 2/75 Fuse bases 5/14
Clamp terminals Fuse links 5/13, 5/14
For 3NP5 7/117 Digital ammeters 11/34
Combination surge arresters 6/6 Digital time switches 8/40, 8/41
Communication modules for E-counters 11/12 Astro 8/40
Communication-capable circuit breakers 1/26, 1/43, 2/12 ... 2/29, Data keys 8/41
2/40 ... 2/51, 2/98 Expert 8/41
Compensator 8/27 Mini 8/40
Profi 8/40
Complete version
Software 8/41
For 3KA/3KE 7/34
Top 8/40
Completely compartmentalized USB adapters 8/41
3NP5 version 7/108, 7/109, 7/110, 7/111, 7/112, 7/113 Digital voltmeters 11/34
Configuration 13/7 Direct current
Configuring, Visualizing and Controlling with SIMATIC 13/9 ... 13/15 Non-automatic air circuit breakers 1/50 ... 1/54
Connecting terminal plates Direct operating mechanisms
For 8US 10/14 For 3KA/3KE 7/41, 7/42
Connecting wedges Direct voltage monitors 12/13
For 8US 10/25 Distance compensation
Connection assembly kits For 3NJ4/3NJ5 7/126
For 3NJ4/3NJ5 7/125
Door-coupling rotary operating mechanisms
Connection holders For 3K switch disconnectors 7/57 ... 7/63
For 8US 10/25 Door-coupling rotary operating mechanisms IP65
Connection methods For 3KA/3KE 7/40, 7/41, 7/42
For circuit breakers 1/27 ... 1/28, 1/45 ... 1/46 For 3KL 7/48, 7/49
For fixed-mounted circuit breakers 2/77 ... 2/82 For 3KM 7/55, 7/56
Connection modules 10/23 Double pushbuttons 8/10, 8/11
For 3NJ62 7/88
Dusk switches 12/37
For 3NP1 7/100
Light sensor 12/37
Contact extensions
For 3NJ62 7/82, 7/84, 7/86
Control pushbuttons 8/10
Control switches 8/6
E
Control switches 8/6 ECG control switches 8/50
Group switches 8/6 E-counters 11/8
Two-way switches 8/6 Three-phase 11/8
Conversion sets EFM 10
Fixed-mounted circuit breakers to withdrawable circuit breakers 1/47 For 3NP1 7/90
Coupling drivers EFM 20
For door-coupling rotary operating mechanisms 7/62 For 3NP1 7/90
Cover IP20 EFM 25
For 3KL 7/48, 7/49 For 3NP1 7/90
Cover profiles Electromechanical fuse monitoring
For 8US 10/11, 10/13 For 3NP1 7/90
Cover rings 5/17 Electronic fuse monitoring
Cover support For 3NP1 7/90
For 3NP1 7/99, 7/101, 7/103, 7/104, 7/105 For 3NP5 7/112, 7/113
Covers 1/26, 1/35, 1/41, 3/35, 4/25 Electronic fuse monitoring with DC monitoring
For DIAZED fuse bases 5/16 For 3NP1 7/90
For DIAZED SR60 bus-mounting bases 10/31 Electronic fuse monitors
For LV HRC fuse bases 5/48 For 3NP5 7/112, 7/113
For miniature circuit breakers 3/35 Electronic releases 1/7 ... 1/22, 1/34, 1/35, 2/10 ... 2/29, 2/34 ... 2/51
For NEOZED fuse bases 5/10 EMERGENCY STOP modules 12/32
For NEOZED SR60 bus-mounting bases 10/30 End and intermediate holders
For 3NJ4/3NJ5 7/123 For 8US 10/7, 10/10, 10/11
For residual current protective devices 4/14 End caps
For time counters 11/38 For busbars 4/25, 8/23
Covers for cable lug connections Acc. to UL 508 3/45, 5/32
For 3NP5 7/117 Standard 3/28, 3/41, 3/42
Covers for terminals for circular conductors End covers
For 8US 10/15 For 8US 10/11
CubicleBUS modules 1/43
Appendix
Subject index
Energy counters 11/8 Fuse tongs 5/60
Three-phase 11/8 Fuse-base covers
Energy management 11/2 For LV HRC fuse bases 5/49
Energy-saving timers 8/50 Fuses
ETU electronic releases 1/7 ... 1/22, 1/34, 2/12 ... 2/29, 2/40 ... 2/51 For 3KL 7/50
Expansion fault signaling units 12/31 For 3KM 7/50
Expansion modules for E-counters 11/12 For 3NJ4/3NJ5 7/126
For 3NP5 7/115
Expansion modules for power monitoring devices
PAC 4DI/2DO 11/31
PAC PROFIBUS DP 11/29
PAC RS 485 11/30 G
Extension terminals 10/12 Generator protection 2/16 ... 2/29, 2/46 ... 2/51
Grounding brackets
For 3KA/3KE 7/41, 7/42
F Grounding set
Fault signal contacts (FC) For 3NJ4/3NJ5 7/124
For miniature circuit breakers 3/31, 3/52 Group switches 8/6
Fault signaling units 12/31 GSM alarm modules 12/30
Centralized fault signaling unit 12/31 Guide frames
Expansion fault signaling units 12/31 For circuit breakers 1/30 ... 1/33, 1/53 ... 1/54
Feeder terminals 3/59 Guide rails
For 3NP1 7/98 For 3NJ62 7/88
Fixed mounting
Circuit breakers 1/7 ... 1/10, 1/15 ... 1/18, 1/50
Fixed-mounted circuit breakers 2/10 ... 2/54 H
Connection methods for 2/77 ... 2/82 Handle coupler
Fixing clips For residual current protective devices 4/22
For 3NJ4/3NJ5 7/123 Handle locking devices
Fixing kits For control switches 8/7
For 3NP1 7/99, 7/101, 7/103 For miniature circuit breakers 3/34, 3/53
Fixing parts For ON/OFF switches 8/19
For miniature circuit breakers 3/34 Handle with masking plate
For residual current protective devices 4/27 For door-coupling rotary operating mechanisms 7/62
Fixing screws High speed closing
For 3NJ4/3NJ5 7/124 3NP5 version 7/108, 7/109, 7/110, 7/111, 7/112, 7/113
Flashing timers 8/51 Holder
Flat copper profile For front panel installation 3/35, 8/41, 8/48
For 8US 10/13 Holders for ammeters
Flat copper profiles For 3NJ62 7/83, 7/85, 7/87
For 8US 10/7
Flat terminals
3NP1 version 7/92, 7/93, 7/97 I
For 3N4/3NJ5 7/121
Immersion electrodes
Front panel For level relays 12/34
For 3NJ62 7/83, 7/85, 7/87
Infeeds
Fuse bases For 8US 10/14
DIAZED 5/14
Inscription labels 3/34, 4/27
NEOZED 5/9, 5/10
For 3LD 7/21, 7/22, 7/23, 7/24, 7/25
Fuse carriers
Insta contactors
For 3NP1 7/99, 7/101, 7/104, 7/105
AC technology 8/35, 8/36
For 3NP5 7/114
DC technology 8/32
Fuse covers
Instabus KNX 11/13
For 3KL 7/48, 7/49
For 3KM 7/55, 7/56 Insulation monitors 12/20, 12/26
Fuse links Interlocks 1/26, 1/36
Class CC fuse system 5/26 For circuit breakers 2/83 ... 2/88
Cylindrical fuses 5/20 Intermediate frames 3/35
DIAZED 5/13, 5/14 Isolating links
NEOZED 5/7 For 3NJ4/3NJ5 7/126
Fuse monitor connections For LV HRC fuse bases 5/49
For 3KL 7/48, 7/49
For 3KM 7/55, 7/56
Fuse monitoring
For 3NP5 7/110
Fuse monitors 5/43, 12/18
Fuse partitions
For 3KL 7/48, 7/49
For 3KM 7/55, 7/56
Fuse pullers
For LV HRC fuse links 5/49
Fuse switch disconnectors
MINIZED 5/8
Fuse systems 5/2 ... 5/64
Busbars 5/29 ... 5/32
Class CC 5/26
Class CC fuse system 5/26
Cylindrical fuse systems 5/19 ... 5/21
DIAZED 5/13 ... 5/17
DIAZED fuse systems 5/13 ... 5/17
LV HRC fuse bases 5/46 ... 5/49
LV HRC fuse links 5/35 ... 5/41
LV HRC signal detectors 5/43
NEOZED 5/7 ... 5/11
NEOZED fuse systems 5/7 ... 5/11
Photovoltaic fuses 5/64
Appendix
Subject index
K Monitoring devices 12/2 ... 12/41
Knob-operated mechanism Current relays 12/16
For 3LD 7/23 Dusk switches 12/37
EMERGENCY STOP modules 12/32
Fault signaling units 12/31
Fuse monitors 12/18
L GSM alarm modules 12/30
Labeling systems 3/34, 4/27 Insulation monitors 12/20
LAN couplers 11/22 Level relays 12/34
Lateral modules Line circuit relays 12/35
For 8US 10/22 Monitoring of medical premises 12/26, 12/27
Leakage current measurement devices 4/14 Network switchover control 12/8
p.f. controller 12/40
LEDs Phase monitors 12/19
For light indicators 8/14 Phase sequence monitors 12/19
For pushbuttons 8/11 Priority switches 12/17
Level relays 12/34 Residual current monitors 12/10
Light indicators 8/13 Temperature controllers 12/39
Light sensor Thermistor motor protection relays 12/41
For dimmer switch 12/37 Voltage relays 12/13
Lighting timers 8/50 Monitoring of medical premises 12/26, 12/27
Lightning arresters 6/4 Motor protection 2/26 ... 2/29
Line circuit relays 12/35 Motor starter protectors/Circuit breakers
Link rails 3/59 Generator protection 2/16 ... 2/29
For 3NP1 7/98 Motor protection 2/26 ... 2/29
For overvoltage protection devices 6/13 Starter protection 2/30 ... 2/31
Lock System protection 2/10 ... 2/25
For miniature circuit breakers 3/34 Mounting hook
Locking caps 5/8 For 3NJ4/3NJ5 7/126
Locking devices 1/27, 1/35 Mounting plates 3/57
For 3NP1 7/99, 7/101, 7/104, 7/105 Moving-iron ammeters
For miniature circuit breakers 3/34 For 3NJ62 7/83, 7/85, 7/87
For residual current protective devices 4/14 Moving-iron measuring instruments 7/83
Locking mechanisms 1/27, 1/36 For 3NJ62 7/83, 7/85, 7/87
LV HRC bus-mounting bases 5/47 Multicounters 11/19
LV HRC contact covers Multi-function plugs
LV HRC bus-mounting bases 5/48 For 3NJ62 7/73, 7/83, 7/85, 7/87
LV HRC fuse bases 5/46 ... 5/49 Multifunction timers 8/51
LV HRC fuse links 5/35 ... 5/41 Multimeters 11/16
LV HRC signal detectors 5/43
Lyre-shaped fuse covers
For 3KL 7/48 N
N conductor monitors 12/14
N or PE terminals
M For 3LD 7/21, 7/22, 7/25
Magnetic releases 2/30 ... 2/31, 2/52 ... 2/53 N-conductor connectors 8/19
Main connections 1/28, 1/45 ... 1/46, 2/7 NEOZED
Main miniature circuit breakers (SHU) 3/56, 3/57 Adapter sleeve fitters 5/11
Male connectors Adapter sleeves 5/11
For lightning arresters 6/12 Busbar adapters 5/11
For surge arresters 6/12, 6/17 Caps 5/10
Covers 5/10
M-Bus 11/13
Fuse bases 5/9, 5/10
Measuring devices Retaining springs 5/11
Analog 11/32 Screw caps 5/11
Three-phase 11/3 ... 11/40
NEOZED bus-mounting bases 10/30
Measuring selector switches 11/40
NEOZED fuse links 5/7
Mechanical coupling of operating handles
Network switchover control 12/8
For 3NJ4/3NJ5 7/126
Non-automatic air circuit breakers
Mechanical time switches 8/47, 8/48
Air 1/1 ... 1/54
MFM Direct current 1/50 ... 1/54
For 3NP1 7/90
Non-automatic molded case circuit breakers 2/30 ... 2/31, 2/52 ... 2/53
Miniature circuit breakers 3/2 ... 3/59
10 000 A, high current 3/15
10 000 A, universal current 3/16, 3/17
10,000 A 3/11 ... 3/14 O
15,000 A 3/18 ... 3/20 OFF switches 8/17 ... 8/19
25 kA 3/21, 3/22 Off-delay timers 8/51
6000 A 3/6, 3/7 ON-OFF switch 8/17 ... 8/19
Acc. to UL 489 and IEC 3/48 ... 3/53 Operating mechanisms
Additional components 3/31 ... 3/35 For circuit breakers 1/23, 1/25, 1/40, 2/55, 2/56, 2/62 ... 2/69
Busbars 3/28, 3/39 ... 3/42, 3/45, 3/53
Operating mechanisms for fixed mounting
Circuit breaker terminals 3/59
For 3KA/3KE 7/40
Compact range 1+N in 1 MW 3/28
High current, 10 000 A 3/15 Operating protective covers
Main miniature circuit breakers (SHU) 3/56, 3/57 For miniature circuit breakers 3/57
RC units 3/32, 3/33 Outgoing modules for PE/N
Universal current, 10 000 A 3/16, 3/17 For 8US 10/14
With plug-in terminal 3/25 Overvoltage protection devices 6/2 ... 6/18
MINIZED Accessories for surge arresters 6/12
Fuse switch disconnectors 5/8 Combination surge arresters 6/6
Switch disconnectors 5/8 Configuration 6/14
Molded case circuit breakers 2/1 ... 2/98 Lightning arresters 6/4
Link rails 6/13
Molded-plastic enclosures 3/35, 4/27
Surge arresters 6/9, 6/10, 6/11, 6/17
Molded-plastic masking frames
Overvoltage relays 12/13
For 3NP5 7/114, 7/117
Appendix
Subject index
P Residual current protective devices 4/2 ... 4/28
p.f. controller 12/40 Accessories 4/27
Additional components 4/14
PAC PROFIBUS DP 11/29
Busbars 4/24, 4/25
PAC RS 485 11/30 Leakage current measurement devices 4/14
PAC1500 11/6 RC units 4/16, 4/17
PAC1500 single-phase counters 11/9 RCBO 4/19 ... 4/22
PAC1500 three-phase counters 11/6 RCCB 4/5 ... 4/8
PAC3100 11/23, 11/26 RCCB socket outlets (SRCDs) 4/26
PAC3100 power monitoring devices 11/23, 11/26 Residual-current operated circuit breakers 4/28
SIGRES 4/7, 4/8
PAC3200 11/23, 11/27, 13/15
SIQUENCE RCCBs 4/10 ... 4/12
PAC3200 block library for SIMATIC WinCC 13/15
Residual-current operated circuit breakers 4/28
PAC3200 power monitoring devices 11/23, 11/27
Retaining springs
PAC4200 11/23, 11/28 For NEOZED 5/11
PAC4200 power monitoring devices 11/23, 11/28 Rotary operating mechanisms
Padlocks 3/34, 3/53, 4/14 For 3LD 7/21, 7/22, 7/25
Parallel switches For switch disconnectors 7/28
For 3KA/3KE 7/41, 7/42 RS 485 11/13
Parking position
For 3NJ4/3NJ5 7/119
Partition S
For 8US 10/13
Saddle terminals
Partitions
For 3NJ4/3NJ5 7/125
For LV HRC bus-mounting bases 5/48
For 3NP1 7/100, 7/102, 7/105
For LV HRC fuse bases 5/48, 5/49
Phase connectors 8/19 Screw adapters
For DIAZED fuse bases 5/16
Phase monitors 12/19
Screw caps
Phase sequence monitors 12/19 For DIAZED fuse bases 5/15
Photovoltaic For NEOZED fuse bases 5/11
Cylindrical fuse holders 5/64 Screw holders
Cylindrical fuse links 5/64 For 8US 10/25
DC isolators 8/20
Sealable covers
Photovoltaic fuses 5/64 For 3NP1 7/98
Planning 13/7 Sealing lugs
Planning the Power Distribution System with SIMARIS 13/4 ... 13/6 For 3NP5 7/117
Plug-in version Selection and ordering data (paper) 7/82
Circuit breakers 2/70 ... 2/75 Selector switches
Power Management System 11/2 For ammeters 11/40
Power supply units 9/8, 12/30 For voltmeters 11/40
Priority switches 12/17 Series remote control switches 8/26
Prism terminal Shaft couplings
For 3NJ4/3NJ5 7/125 For door-coupling rotary operating mechanisms 7/62
For 3NP1 7/100, 7/102 Short-time relays 12/14
PROFIBUS 1/44 Shunt releases
PROFIBUS DP 11/29 For circuit breakers 1/23, 1/40, 2/57, 2/59 ... 2/60
Protective devices with device holder 1/34 Shunt trips (ST)
Pulse counters For miniature circuit breakers 3/31, 3/52
Electronic 11/36 Shutter/blind remote control switches 8/26
Mechanical 11/36 Signaling combination
Pushbuttons 8/10, 8/11 For insulation monitors 12/27
Control pushbuttons 8/10 Signaling panels 12/26
Double pushbuttons 8/10, 8/11 SIMARIS curves 13/6
SIMARIS design 13/4
SIMARIS project 13/5
Q SIMATIC PCS 7 Library PAC3200 13/13
Quartz-clock time switches 8/47 SIMATIC PCS 7 powerrate 13/9, 13/10
SIMATIC WinCC powerrate 13/11, 13/12
Single-phase measuring devices
R Analog measuring devices 11/32
Rated current modules 1/24, 1/34 Digital measuring devices 11/34
Rating Plug 1/24, 1/34 Time and pulse counters 11/36
RC units Time counters for front-panel mounting 11/38
For miniature circuit breakers 3/32, 3/33 SIQUENCE RCCBs 4/10 ... 4/12
For residual current protective devices 4/16, 4/17 SITOR fuses
RCBO 4/19 ... 4/22 For 3KL 7/50
RCCB protective socket outlets 4/26 For 3KM 7/50
For 3NP5 7/115
RCCB socket outlets (SRCDs) 4/26
SITOR semiconductor fuses 5/50 ... 5/64
RCCBs 4/5 ... 4/8
Cylindrical fuse design 5/59, 5/60
RCD modules LV HRC design 5/51 ... 5/57
For circuit breakers 2/76 NEOZED and DIAZED, SILIZED design 5/62
Reach-around protection Socket outlets
For 3NP1 7/99, 7/101, 7/103, 7/104, 7/105 For modular installation devices 9/10, 9/11
Reducers 5/8 SCHUKO 4/26
For door-coupling rotary operating mechanisms 7/62 Soft-starting devices 8/37
REG socket outlets 9/10, 9/11 Software
Remote control switches 8/26 For digital time switches 8/41
Remote controlled mechanisms (RC) Spacers
For miniature circuit breakers 3/31 For 8US 10/24, 10/25
For residual current protective devices 4/14 For Control Switches 8/7
Residual current monitors 12/10 For Insta contactors 8/32
For miniature circuit breakers 3/34
For ON/OFF switches 8/19
For switching relays 8/29
Appendix
Subject index
Stairwell lighting timers 8/50 Time counters
Starter protection 2/30 ... 2/31 Electronic 11/36
Stud terminal For front-panel mounting 11/38
For 3NJ4/3N5 7/121 Mechanical 11/36
Summation current transformer Time switches
For residual current monitors 12/10 Digital 8/40, 8/41
Support rails Mechanical 8/47, 8/48
For 8US 10/25 Quartz 8/47
Synchronous 8/47
Supports for blanking covers
For 8US 10/11 Timers 8/38 ... 8/52
For buildings 8/50
Surge arresters
For fans 8/50
For measuring and control technology 6/17
For industry 8/51
Type 2 6/9, 6/10
Time switches
Type 3 6/11
Digital 8/40, 8/41
Switch disconnectors 7/27 Mechanical 8/47, 8/48
MINIZED 5/8
Touch protection
Switch ES Power 1/43, 13/19 For RCCBs 4/27
Switching devices 8/2 ... 8/52 Touch protection covers
Busbars 8/23 For busbars 4/25
Control switches 8/6 Acc. to UL 489 3/53
DC isolators 8/20 Acc. to UL 508 3/45, 5/32
Insta contactors Standard 3/40
AC technology 8/35, 8/36
Transformers
DC technology 8/32
Bell transformers 9/4
Light indicators 8/13
For permanent load 9/6
OFF switches 8/17 ... 8/19
ON-OFF switch 8/17 ... 8/19 Transformers, bells and socket outlets 9/2 ... 9/12
Pushbuttons 8/10, 8/11 Triple terminals
Remote control switches 8/26 For 3NP1 7/98, 7/100
Soft-starting devices 8/37 Two-way switches 8/6
Switching relays 8/29
Timers
Digital time switches 8/40, 8/41 U
Mechanical time switches 8/47, 8/48
Under and overvoltage relays 12/14
Timers for buildings 8/50
Timers for industrial applications 8/51 Undervoltage relays 12/13
Switching relays 8/29 Undervoltage releases
For circuit breakers 1/23, 1/40, 2/57, 2/59 ... 2/60
Switching shafts
For 3LD 7/22, 7/23, 7/24 Undervoltage releases (UR)
For miniature circuit breakers 3/31
Switchover device
For medical premises 12/26 Unequipped section covers
For 3NJ4/3NJ5 7/124
Synchronous time switches 8/47
USB adapters
System covers
For digital time switches 8/41
For 3NP1 7/99, 7/101, 7/103, 7/104, 7/105
System protection 2/10 ... 2/25, 2/34 ... 2/51
V
T Voltage relays 12/13, 12/14, 12/27
Voltmeter selector switches 11/40
Temperature controllers 12/39
Voltmeters
Temperature sensor 12/39
Analog 11/32
Terminal covers 3/34, 3/35, 3/57, 4/27, 7/82, 8/19, 11/38 Digital 11/34
For 3KA/3KE 7/40, 7/42
For 3KL 7/48, 7/49, 7/50
For 3KM 7/55, 7/56
For 3LD 7/21, 7/22, 7/23, 7/25 W
For 3NJ62 7/84, 7/86 Wall enclosures 3/35, 4/27
Sealable 8/32, 8/35, 8/36 Wiper timers 8/51
Terminal sets Wiring 1/35
For 8US 10/14, 10/15 Withdrawable bridging units 1/48
Terminal strips Withdrawable grounding units 1/48
For 3NJ4/3NJ5 7/126 Withdrawable short-circuits 1/48
Terminals 7/84
Withdrawable version
Covers 7/28
Circuit breakers 1/11 ... 1/14, 1/19 ... 1/22, 1/51 ... 1/52, 2/70 ... 2/75
For 3NJ62 7/82, 7/86
For 8US 10/15
For busbars 4/25
Acc. to UL 489 3/53
Acc. to UL 508 3/45, 5/32
Standard 3/28, 3/42
Terminals for circular conductors
For 8US 10/15
Test combination
For insulation monitors 12/27
Test panels 12/26
Thermal-magnetic releases 2/10 ... 2/13, 2/34 ... 2/39
Thermistor motor protection relays 12/41
Three-phase busbar
For 3NP1 7/98
Three-phase measuring devices 11/3 ... 11/40
Current transformers 11/39
E-counters 11/8
LAN couplers 11/22
Measuring selector switches 11/40
Multicounters 11/19
Multimeters 11/16
Appendix
Order number index
incl. export markings
■ Overview
Order No. Export markings Page Order No. Export markings Page
ECCN AL ECCN AL
3K 3LD22 17 N N 7/15
3KA N N 7/34 3LD22 2 N N 7/8, 7/10
3KC90 00-8TL3 EAR99 N 12/8 3LD22 3 N N 7/16 ... 17, 7/20
3KC90 00-8TL7 5D992 N 12/8 3LD22 4 N N 7/13
3KE N N 7/36 ... 38 3LD22 5 N N 7/7, 7/9
3KL N N 7/45 ... 46 3LD22 6 N N 7/18 ... 20
3KM N N 7/54 3LD23 0 EAR99 N 7/6, 7/10
3KX22 1 N N 7/36, 7/41 ... 42 3LD23 1 EAR99 N 7/11 ... 12, 7/14
3KX22 3 N N 7/41 ... 42 3LD23 3 N N 7/16 ... 17
3KX22 50 N N 7/41 ... 42 3LD24 05-0 N N 7/6
3KX22 52-0 N N 7/42 3LD24 05-1 EAR99 N 7/6
3KX22 52-1 N N 7/41 ... 42 3LD24 05-3 EAR99 N 7/10
3KX31 N N 7/40, 7/49, 7/56 3LD24 05-7 EAR99 N 7/10
3KX35 0 N N 7/48 ... 49, 7/55 ... 56 3LD24 1 EAR99 N 7/11 ... 12, 7/14
3KX35 1 N N 7/35, 7/40, 7/47 ... 48, 7/55 3LD24 3 N N 7/16 ... 17
3KX35 2 N N 7/47 ... 48, 7/55 3LD25 04-0 N N 7/6
3KX35 3 N N 7/35, 7/40, 7/47 ... 49, 7/55 3LD25 04-1 N N 7/6
3KX35 52-3D N N 7/40, 7/48, 7/55 3LD25 04-3 N N 7/10
3KX35 52-3E N N 7/40, 7/49, 7/56 3LD25 14-0 N N 7/11 ... 12
3KX35 53 N N 7/40, 7/48, 7/55 3LD25 14-1 N N 7/11 ... 12
3KX35 56 N N 7/35, 7/47 3LD25 17 N N 7/15
3KX35 57 N N 7/40 ... 41, 7/49, 7/56 3LD25 2 N N 7/10
3KX35 6 N N 7/50 3LD25 3 N N 7/16 ... 17
3KX36 N N 7/50 3LD25 4 N N 7/13
3KY22 0 N N 7/41 3LD25 5 N N 7/7
3KY22 32 N N 7/42 3LD25 6 N N 7/18 ... 19
3KY22 34 N N 7/42 3LD27 04-0 N N 7/6
3LD 3LD27 04-1 N N 7/6
3LD20 03-0 N N 7/6 3LD27 1 N N 7/11 ... 12
3LD20 03-1TL N N 7/6 3LD27 2 N N 7/10
3LD20 03-1TP N N 7/6 3LD27 3 N N 7/16 ... 17
3LD20 03-2 N N 7/6 3LD27 6 N N 7/18 ... 19
3LD20 13 N N 7/11 ... 12 3LD28 N N 7/6, 7/11 ... 12, 7/16 ... 18
3LD20 17 N N 7/15 3LD92 00-2 N N 7/21
3LD20 2 N N 7/8 3LD92 00-5B N N 7/6 ... 9, 7/21 ... 25
3LD20 3 N N 7/16 ... 17 3LD92 00-5BF N N 7/21 ... 25
3LD20 4 N N 7/13 3LD92 00-5C N N 7/12 ... 13, 7/17 ... 18,
3LD20 5 N N 7/7, 7/9 7/21 ... 25
3LD20 6 N N 7/18 3LD92 00-5CF N N 7/21 ... 25
3LD21 03-0 N N 7/6 3LD92 00-6 N N 7/21 ... 25
3LD21 03-1 N N 7/6 3LD92 01 N N 7/21
3LD21 03-2 N N 7/6 3LD92 05 N N 7/21 ... 22, 7/24 ... 25
3LD21 03-3 N N 7/10 3LD92 20 N N 7/8 ... 9, 7/16 ... 17, 7/22
3LD21 03-4 N N 7/10 3LD92 21 N N 7/22
3LD21 13-0 N N 7/11 ... 12 3LD92 24 N N 7/21 ... 22
3LD21 13-1 N N 7/11 ... 12 3LD92 40-0 N N 7/16 ... 17, 7/23
3LD21 13-3 N N 7/14 3LD92 40-2 EAR99 N 7/23
3LD21 13-4 N N 7/14 3LD92 41 EAR99 N 7/23
3LD21 2 N N 7/8, 7/10 3LD92 42 N N 7/23
3LD21 3 N N 7/16 ... 17 3LD92 43 EAR99 N 7/23
3LD21 4 N N 7/13 3LD92 45 EAR99 N 7/23
3LD21 5 N N 7/7, 7/9 3LD92 50 N N 7/6 ... 7, 7/13, 7/16 ... 17,
7/24
3LD21 6 N N 7/18 ... 19
3LD92 51 N N 7/24
3LD22 03-0 N N 7/6
3LD92 56 N N 7/21 ... 22, 7/24
3LD22 03-1 N N 7/6
3LD92 80 N N 7/6, 7/11 ... 12, 7/16 ... 18,
3LD22 03-3 N N 7/10 7/25
3LD22 13-0 N N 7/11 ... 12 3LD92 81 N N 7/25
3LD22 13-1 N N 7/11 ... 12
Appendix
Order number index
incl. export markings
Order No. Export markings Page Order No. Export markings Page
ECCN AL ECCN AL
3LD92 84 N N 7/24 ... 25 3NJ49 11-3 N N 7/124
3LD92 86 N N 7/21 ... 25 3NJ49 11-4 N N 7/125
3NA, 3NC 3NJ49 11-5 N N 7/125
3NA N N 5/35 ... 40 3NJ49 11-6A N N 7/125
3NC10 00 EAR99H N 5/60 3NJ49 11-6B N N 7/125
3NC10 03 N N 5/59 3NJ49 11-6C N N 7/126
3NC10 06 N N 5/59 3NJ49 12-1A N N 7/123
3NC10 08 N N 5/59 3NJ49 12-1D N N 7/123
3NC10 1 N N 5/59 3NJ49 12-1E N N 7/123
3NC10 2 N N 5/59 3NJ49 12-1F N N 7/123
3NC10 32 N N 5/59 3NJ49 12-2 N N 7/123
3NC10 38 EAR99H N 5/60 3NJ49 12-3 N N 7/124
3NC10 38-1 N N 5/60 3NJ49 13 N N 7/126
3NC10 38-2 N N 5/60 3NJ49 14-8A N N 7/126
3NC10 38-3 N N 5/60 3NJ49 14-8B EAR99 N 7/126
3NC10 9 N N 5/60 3NJ49 15-1B N N 7/126
3NC14 0 N N 5/59 3NJ49 15-1C N N 7/126
3NC14 1 N N 5/59 3NJ49 15-1E N N 7/127
3NC14 2 N N 5/59 3NJ49 15-1F N N 7/127
3NC14 3 N N 5/59 3NJ49 15-2B N N 7/126
3NC14 4 N N 5/59 3NJ49 15-2C N N 7/126
3NC14 50 N N 5/59 3NJ49 15-2D N N 7/127
3NC14 51 EAR99H N 5/60 3NJ49 15-2E N N 7/127
3NC14 51-1 N N 5/60 3NJ49 15-2F N N 7/127
3NC14 9 N N 5/60 3NJ49 15-2G N N 7/127
3NC2 N N 5/51, 5/59 ... 60, 7/51, 3NJ49 15-2H N N 7/127
7/116
3NJ49 15-2J N N 7/127
3NC3 N N 5/54 ... 56
3NJ49 15-2K N N 7/127
3NC5 N N 5/57
3NJ49 18-0A N N 7/123
3NC73 2 N N 5/57
3NJ49 18-0DA N N 7/124
3NC73 3 N N 5/57
3NJ49 18-0DB N N 7/124
3NC8 N N 5/51 ... 52, 7/51, 7/116
3NJ49 18-0DC N N 7/124
3ND, 3NE, 3NG, 3NH
3NJ49 18-0E N N 7/124
3ND N N 5/41
3NJ49 18-1 N N 7/126
3NE1 N N 5/51 ... 53, 7/50 ... 51,
7/115 3NJ50 N N 7/121 ... 122
3NE32 N N 5/55, 7/51, 7/115 3NJ56 N N 7/121
3NE33 N N 5/55, 7/51, 7/116 3NJ59 N N 7/124
3NE34 N N 5/55 3NJ62 02 N N 7/69
3NE35 N N 5/57 3NJ62 03-1AA N N 7/69
3NE36 2 N N 5/55 3NJ62 03-1AB N N 7/69
3NE36 35-0 N N 5/55 3NJ62 03-1AC N N 7/69
3NE36 35-6 N N 5/55 3NJ62 03-3AA N N 7/69
3NE36 36 N N 5/55 3NJ62 03-3AB N N 7/69
3NE36 37 N N 5/55 3NJ62 03-3AC N N 7/69
3NE4 N N 5/54, 5/57, 7/51, 3NJ62 03-4 N N 7/69
7/115 ... 116 3NJ62 04 N N 7/70
3NE5 N N 5/56 3NJ62 12 N N 7/69
3NE6 N N 5/57 3NJ62 13-1AA N N 7/69
3NE7 N N 5/56 3NJ62 13-1AB N N 7/69
3NE8 N N 5/52, 5/54, 7/51, 7/115 3NJ62 13-1AC N N 7/69
3NE94 N N 5/57 3NJ62 13-3AA N N 7/69
3NE96 2 N N 5/57 3NJ62 13-3AB N N 7/69
3NE96 3 N N 5/57 3NJ62 13-3AC N N 7/69
3NG N N 5/49 3NJ62 13-4 N N 7/69
3NH N N 5/46 ... 48, 10/32 3NJ62 14 N N 7/70
3NJ 3NJ62 22 N N 7/69
3NJ41 N N 7/121 ... 122 3NJ62 23-1AA N N 7/69
3NJ49 10 N N 7/124 3NJ62 23-1AB N N 7/69
3NJ49 11-1 N N 7/125 3NJ62 23-1AC N N 7/69
3NJ49 11-2 N N 7/125 3NJ62 23-3AA N N 7/69
Appendix
Order number index
incl. export markings
Order No. Export markings Page Order No. Export markings Page
ECCN AL ECCN AL
3NJ62 23-3AB N N 7/69 3NP19 0 N N 7/99, 7/101, 7/103 ... 105
3NJ62 23-3AC N N 7/69 3NP19 20 N N 7/99
3NJ62 23-4 N N 7/69 3NP19 23-1BD N N 7/98
3NJ62 24 N N 7/70 3NP19 23-1BE EAR99 N 7/98, 7/100
3NJ62 32 N N 7/69 3NP19 23-1BF1 EAR99 N 7/98
3NJ62 33-1AA N N 7/69 3NP19 23-1BF2 EAR99 N 7/98
3NJ62 33-1AB N N 7/69 3NP19 23-1BF3 EAR99 N 7/98
3NJ62 33-1AC N N 7/69 3NP19 23-1BF4 EAR99 N 7/98
3NJ62 33-3AA N N 7/69 3NP19 23-1BF5 N N 7/98
3NJ62 33-3AB N N 7/69 3NP19 23-1BG N N 7/98
3NJ62 33-3AC N N 7/69 3NP19 23-1C N N 7/99
3NJ62 33-4 N N 7/69 3NP19 23-1D N N 7/99
3NJ62 34 N N 7/70 3NP19 23-1E N N 7/99
3NJ62 4 N N 7/71 3NP19 23-1G N N 7/99
3NJ62 5 N N 7/71 3NP19 30 N N 7/101
3NJ62 6 N N 7/71 ... 72 3NP19 33-1BA N N 7/100
3NJ62 7 N N 7/71 ... 72 3NP19 33-1BB N N 7/100
3NJ62 8 N N 7/71 ... 72 3NP19 33-1BC N N 7/100, 10/23
3NJ62 9 N N 7/71 ... 72 3NP19 33-1BE EAR99 N 7/100
3NJ69 0 N N 7/82 ... 88 3NP19 33-1BG N N 7/100
3NJ69 1 N N 7/88 3NP19 33-1C N N 7/101
3NJ69 20-2 N N 7/82 3NP19 33-1D N N 7/101
3NJ69 20-3B N N 7/82, 7/84 3NP19 33-1E N N 7/101
3NJ69 20-3D N N 7/83 3NP19 33-1G N N 7/101
3NJ69 20-3E N N 7/83, 7/85 3NP19 40 N N 7/103 ... 105
3NJ69 20-3F EAR99 N 7/82 3NP19 43-1BA N N 7/102
3NJ69 23-1B N N 7/82 3NP19 43-1BB EAR99 N 7/102
3NJ69 23-1D N N 7/82 3NP19 43-1BG N N 7/102, 7/104 ... 105
3NJ69 23-1E N N 7/82 3NP19 43-1C N N 7/103 ... 105
3NJ69 23-4 N N 7/83 3NP19 43-1D N N 7/103
3NJ69 24 N N 7/82 3NP19 43-1E N N 7/103
3NJ69 30-2 N N 7/84 3NP19 43-1G N N 7/103
3NJ69 30-3B N N 7/84 3NP19 53-1BA N N 7/104
3NJ69 30-3D N N 7/85 3NP19 53-1BB EAR99 N 7/104
3NJ69 30-3FB EAR99 N 7/84 3NP19 53-1BG N N 7/104 ... 105
3NJ69 30-3FC EAR99 N 7/84 3NP19 53-1C N N 7/104
3NJ69 30-3FE N N 7/84 3NP19 53-1D N N 7/104
3NJ69 33-1B N N 7/84 3NP19 53-1G N N 7/104
3NJ69 33-1D N N 7/84 3NP19 63-1BA N N 7/105
3NJ69 33-1E N N 7/84 3NP19 63-1BB EAR99 N 7/105
3NJ69 33-4 N N 7/85 3NP19 63-1C N N 7/105
3NJ69 34 N N 7/84 3NP19 63-1D N N 7/105
3NJ69 40-2 N N 7/86 3NP19 63-1G N N 7/105
3NJ69 40-3B N N 7/86 3NP5 N N 7/108 ... 113
3NJ69 40-3E N N 7/87 3NW
3NJ69 40-3FB EAR99 N 7/86 3NW1 N N 5/26
3NJ69 40-3FC N N 7/86 3NW20 1 N N 5/26
3NJ69 40-3FE N N 7/86 3NW20 2 N N 5/26
3NJ69 43-1C N N 7/86 3NW20 3 N N 5/26
3NJ69 43-1D N N 7/86 3NW20 4 N N 5/26
3NJ69 43-1E N N 7/86 3NW20 5 N N 5/26
3NJ69 43-4 N N 7/87 3NW20 6 N N 5/26
3NJ69 44 N N 7/86 3NW20 8 EAR99H N 5/26
3NJ69 5 N N 7/87 3NW21 N N 5/26
3NP 3NW22 N N 5/26
3NP11 2 N N 7/92, 7/94 ... 97, 10/23 3NW3 N N 5/26
3NP11 3 N N 7/92, 7/94 ... 97, 10/23 3NW60 01-1 N N 5/19
3NP11 4 N N 7/93, 7/96 ... 97, 10/23 3NW60 01-4 N N 5/64
3NP11 5 N N 7/93, 7/96 ... 97, 10/23 3NW60 02 N N 5/19
3NP11 6 N N 7/93, 7/96 ... 97, 10/23 3NW60 03-1 N N 5/19
Appendix
Order number index
incl. export markings
Order No. Export markings Page Order No. Export markings Page
ECCN AL ECCN AL
3NW60 03-4 N N 5/64 3NY19 03 N N 7/117
3NW60 04-1 N N 5/19 3NY19 07 N N 7/117
3NW60 04-4 N N 5/64 3NY19 10 N N 7/114
3NW60 05-1 N N 5/19 3NY19 11 N N 7/114
3NW60 05-4 N N 5/64 3NY19 15 N N 7/114
3NW60 06-1 N N 5/19 3NY19 4 N N 7/117
3NW60 06-4 N N 5/64 3NY3 N N 7/114
3NW60 07 N N 5/19 3NY4 N N 7/114
3NW60 08-1 N N 5/19 3SB, 3TX, 3UF
3NW60 08-4 N N 5/64 3SB N N 2/61, 7/40, 7/48 ... 49,
7/55 ... 56
3NW60 1 N N 5/19
3TX N N 2/59 ... 60, 7/117
3NW61 N N 5/19
3UF N N 2/98
3NW62 N N 5/19
3VL
3NW63 N N 5/19
3VL17 0 EAR99 N 2/10 ... 11, 2/34 ... 37
3NW70 13 N N 5/20
3VL17 1 EAR99 N 2/10 ... 11, 2/30 ... 31,
3NW70 13-4 N N 5/64 2/34 ... 37, 2/52 ... 53
3NW70 14 N N 5/20, 5/64 3VL17 2 EAR99 N 2/10 ... 11, 2/34 ... 37
3NW70 23 N N 5/20 3VL17 9 EAR99 N 2/10 ... 11, 2/34 ... 37
3NW70 23-4 N N 5/64 3VL27 05 EAR99 N 2/12 ... 13, 2/34 ... 35,
3NW70 24 N N 5/20, 5/64 2/38 ... 39
3NW70 33 N N 5/21 3VL27 06 EAR99 N 2/12 ... 13, 2/20 ... 21,
3NW70 33-1 N N 5/24 2/24 ... 25, 2/28 ... 31,
2/34 ... 35, 2/38 ... 39,
3NW70 34 N N 5/20, 5/24 2/44 ... 47
3NW70 53 N N 5/20 3VL27 08 EAR99 N 2/12 ... 13, 2/34 ... 35,
3NW70 54 N N 5/20 2/38 ... 39
3NW70 63 N N 5/21 3VL27 10-1C EAR99 N 2/20, 2/24, 2/28, 2/44, 2/46
3NW70 64 N N 5/20 3VL27 10-1D EAR99 N 2/12, 2/30
3NW71 N N 5/20 ... 21 3VL27 10-1E EAR99 N 2/34, 2/38, 2/52
3NW72 N N 5/20 ... 21 3VL27 10-2C EAR99 N 2/21, 2/25, 2/29, 2/45, 2/47
3NW73 13 N N 5/20 3VL27 10-2D EAR99 N 2/13, 2/31
3NW73 14 N N 5/20 3VL27 10-2E EAR99 N 2/35, 2/39, 2/53
3NW73 23 N N 5/20 3VL27 10-3C EAR99 N 2/21, 2/25, 2/29, 2/45, 2/47
3NW73 24 N N 5/20 3VL27 10-3D EAR99 N 2/13, 2/31
3NW73 33 N N 5/21 3VL27 10-3E EAR99 N 2/35, 2/39, 2/53
3NW73 34 N N 5/20 3VL27 12 EAR99 N 2/12 ... 13, 2/34 ... 35,
2/38 ... 39
3NW73 53 N N 5/20
3VL27 16 EAR99 N 2/12 ... 13, 2/20 ... 21,
3NW73 54 N N 5/20 2/24 ... 25, 2/28 ... 31,
3NW73 63 N N 5/21 2/34 ... 35, 2/38 ... 39,
2/44 ... 47, 2/52 ... 53
3NW73 64 N N 5/20
3VL37 20-1C EAR99 N 2/20, 2/24, 2/28, 2/44, 2/46
3NW74 30 N N 10/31
3VL37 20-1D EAR99 N 2/12
3NW74 31 N N 10/31
3VL37 20-1E EAR99 N 2/34, 2/38
3NW74 32 N N 10/31
3VL37 20-2C EAR99 N 2/21, 2/25, 2/29, 2/45, 2/47
3NW75 1 N N 5/26
3VL37 20-2D EAR99 N 2/13
3NW75 2 N N 5/26
3VL37 20-2E EAR99 N 2/35, 2/39
3NW75 33-0 N N 5/26
3VL37 20-3C EAR99 N 2/21, 2/25, 2/29, 2/45, 2/47
3NW75 33-1 N N 5/24
3VL37 20-3D EAR99 N 2/13
3NW75 34 N N 5/24
3VL37 20-3E EAR99 N 2/35, 2/39
3NW79 01 N N 5/21
3VL37 25-1C EAR99 N 2/20, 2/24, 2/28, 2/44, 2/46
3NW79 02 N N 5/21
3VL37 25-1D EAR99 N 2/12, 2/30
3NW79 03 N N 5/21
3VL37 25-1E EAR99 N 2/34, 2/38, 2/52
3NW79 03-1 N N 5/24
3VL37 25-2C EAR99 N 2/21, 2/25, 2/29, 2/45, 2/47
3NW8 N N 5/19 ... 20
3VL37 25-2D EAR99 N 2/13, 2/31
3NX, 3NY
3VL37 25-2E EAR99 N 2/35, 2/39, 2/53
3NX N N 5/43, 5/48 ... 49
3VL37 25-3C EAR99 N 2/21, 2/25, 2/29, 2/45, 2/47
3NY10 N N 7/114
3VL37 25-3D EAR99 N 2/13, 2/31
3NY11 N N 7/114, 7/117
3VL37 25-3E EAR99 N 2/35, 2/39, 2/53
3NY12 N N 7/117
3VL47 2 EAR99 N 2/12 ... 13, 2/30 ... 31,
3NY13 N N 7/114
2/34 ... 35, 2/38 ... 39
3NY14 N N 7/114
3NY15 N N 7/114
Appendix
Order number index
incl. export markings
Order No. Export markings Page Order No. Export markings Page
ECCN AL ECCN AL
3VL47 3 EAR99 N 2/12 ... 13, 2/20 ... 21, 3VL92 00-3 EAR99 N 2/77 ... 78
2/24 ... 25, 2/28 ... 31, 3VL92 00-4 EAR99 N 2/71, 2/78
2/34 ... 35, 2/38 ... 39,
2/44 ... 47 3VL92 10 N N 2/90
3VL47 4 EAR99 N 2/12 ... 13, 2/20 ... 21, 3VL92 15 EAR99 N 2/78
2/24 ... 25, 2/30 ... 31, 3VL92 16-4 EAR99 N 2/77 ... 78
2/34 ... 35, 2/38 ... 39,
2/44 ... 47, 2/52 ... 53 3VL92 16-5GC3 N N 2/76
3VL57 3 EAR99 N 2/12 ... 13, 2/30 ... 31, 3VL92 16-5GC4 EAR99H N 2/76
2/34 ... 35, 2/38 ... 39 3VL92 16-5GD EAR99H N 2/76
3VL57 4 EAR99 N 2/12 ... 13, 2/34 ... 35, 3VL92 16-8 N N 2/90
2/38 ... 39
3VL92 8 N N 2/90
3VL57 50-1C EAR99 N 2/28
3VL93 00-3A EAR99 N 2/62
3VL57 50-1DC EAR99 N 2/12
3VL93 00-3H EAR99 N 2/62, 2/83 ... 85
3VL57 50-1DK N N 2/30
3VL93 00-3MA N N 2/66
3VL57 50-1E EAR99 N 2/34, 2/38
3VL93 00-3MC N N 2/66
3VL57 50-2C EAR99 N 2/29
3VL93 00-3MD N N 2/66
3VL57 50-2DC EAR99 N 2/13
3VL93 00-3ME N N 2/66
3VL57 50-2DK N N 2/31
3VL93 00-3MJ EAR99 N 2/66
3VL57 50-2E EAR99 N 2/35, 2/39
3VL93 00-3ML EAR99 N 2/66
3VL57 50-3C EAR99 N 2/29
3VL93 00-3MN EAR99 N 2/66
3VL57 50-3DC EAR99 N 2/13
3VL93 00-3MQ EAR99 N 2/66
3VL57 50-3DK N N 2/31
3VL93 00-3MS EAR99 N 2/66
3VL57 50-3E EAR99 N 2/35, 2/39
3VL93 00-3T EAR99 N 2/79
3VL57 63-1C EAR99 N 2/20, 2/24, 2/44, 2/46
3VL93 00-4E EAR99 N 2/79
3VL57 63-1D EAR99 N 2/12, 2/30
3VL93 00-4P EAR99 N 2/70 ... 71
3VL57 63-1E EAR99 N 2/34, 2/38, 2/52
3VL93 00-4R EAR99 N 2/79
3VL57 63-2C EAR99 N 2/21, 2/25, 2/45, 2/47
3VL93 00-4TA N N 2/79
3VL57 63-2D EAR99 N 2/13, 2/31
3VL93 00-4TC EAR99 N 2/79
3VL57 63-2E EAR99 N 2/35, 2/39, 2/53
3VL93 00-4TD EAR99 N 2/79
3VL57 63-3C EAR99 N 2/21, 2/25, 2/45, 2/47
3VL93 00-4W EAR99 N 2/71
3VL57 63-3D EAR99 N 2/13, 2/31
3VL93 00-8B EAR99 N 2/83 ... 85, 2/94 ... 95
3VL57 63-3E EAR99 N 2/35, 2/39, 2/53
3VL93 00-8CA3 N N 2/77 ... 79
3VL67 80-1 EAR99 N 2/20, 2/24, 2/30, 2/44, 2/46,
2/52 3VL93 00-8CA4 EAR99 N 2/77 ... 79
3VL67 80-2 EAR99 N 2/21, 2/25, 2/31, 2/45, 2/47, 3VL93 00-8CB EAR99 N 2/77 ... 79
2/53 3VL93 00-8CE N N 2/77 ... 79
3VL67 80-3 EAR99 N 2/21, 2/25, 2/31, 2/45, 2/47, 3VL93 00-8L EAR99 N 2/83 ... 85
2/53 3VL93 00-8S EAR99 N 2/83 ... 85
3VL77 10 EAR99 N 2/20 ... 21, 2/24 ... 25, 3VL93 20 N N 2/90
2/44 ... 47
3VL93 21 EAR99 N 2/83 ... 85
3VL77 12 EAR99 N 2/20 ... 21, 2/24 ... 25,
2/30 ... 31, 2/44 ... 47, 3VL93 24 EAR99 N 2/79
2/52 ... 53 3VL93 25-5GE3 N N 2/76
3VL87 16-1 EAR99 N 2/20, 2/24, 2/30, 2/44, 2/46, 3VL93 25-5GE4 EAR99H N 2/76
2/52
3VL93 25-5GF EAR99H N 2/76
3VL87 16-2 EAR99 N 2/21, 2/25, 2/31, 2/45, 2/47,
2/53 3VL93 25-8 N N 2/90
3VL87 16-3 EAR99 N 2/21, 2/25, 2/31, 2/45, 2/47, 3VL94 00-1 N N 2/59
2/53 3VL94 00-2AB EAR99 N 2/59
3VL90 00-4 EAR99 N 2/70 ... 75 3VL94 00-2AD EAR99 N 2/59
3VL90 00-8AP EAR99 N 2/84 ... 88 3VL94 00-2AH EAR99 N 2/61
3VL90 00-8AQ EAR99 N 2/98 3VL94 00-2AJ EAR99 N 2/61
3VL90 00-8AU N N 2/98 3VL94 00-3A EAR99 N 2/63
3VL90 00-8AV EAR99 N 2/98 3VL94 00-3H EAR99 N 2/63, 2/66, 2/85
3VL90 00-8L EAR99 N 2/83 ... 88 3VL94 00-3MA N N 2/66
3VL91 00-3MA N N 2/66 3VL94 00-3MC N N 2/66
3VL91 00-3MC EAR99 N 2/66 3VL94 00-3MD N N 2/66
3VL91 00-3MD EAR99 N 2/66 3VL94 00-3ME N N 2/66
3VL91 00-3ME N N 2/66 3VL94 00-3MJ N N 2/66
3VL91 00-4 EAR99 N 2/70, 2/77 3VL94 00-3ML EAR99 N 2/66
3VL91 12-5GA EAR99H N 2/76 3VL94 00-3MN EAR99 N 2/66
3VL91 12-5GB EAR99 N 2/76 3VL94 00-3MQ EAR99 N 2/66
3VL91 15 EAR99 N 2/77 3VL94 00-3MS EAR99 N 2/66
3VL91 16 EAR99 N 2/77 3VL94 00-3T EAR99 N 2/79 ... 81
Appendix
Order number index
incl. export markings
Order No. Export markings Page Order No. Export markings Page
ECCN AL ECCN AL
3VL94 00-4 EAR99 N 2/72, 2/79 3WL
3VL94 00-8B EAR99 N 2/85, 2/94 3WL11 N N 1/7 ... 8, 1/11 ... 12,
1/15 ... 16, 1/19 ... 20
3VL94 00-8CA EAR99 N 2/79
3WL12 N N 1/7 ... 9, 1/11 ... 13,
3VL94 00-8CB3 N N 2/79
1/15 ... 17, 1/19 ... 21,
3VL94 00-8CB4 EAR99 N 2/79 1/50 ... 52
3VL94 00-8L EAR99 N 2/85 3WL13 N N 1/9 ... 10, 1/13 ... 14,
3VL94 40-5GG N N 2/76 1/17 ... 18, 1/21 ... 22
3VL94 40-5GH EAR99 N 2/76 3WL91 11-0AA1 N N 1/34
3VL94 40-8 EAR99 N 2/90 3WL91 11-0AA2 N N 1/34
3VL94 6 EAR99 N 2/79 3WL91 11-0AA3 N N 1/34
3VL95 0 EAR99 N 2/63, 2/73, 2/80, 2/85 ... 86 3WL91 11-0AA5 N N 1/34
3VL95 6 N N 2/90 3WL91 11-0AA6 N N 1/34
3VL96 00-3A EAR99 N 2/63 ... 64 3WL91 11-0AB01 N N 1/39
3VL96 00-3H EAR99 N 2/63 ... 64, 2/66, 2/86 ... 87 3WL91 11-0AB02 N N 1/39
3VL96 00-3MA N N 2/66 3WL91 11-0AB03 N N 1/39
3VL96 00-3MC N N 2/66 3WL91 11-0AB04 N N 1/39
3VL96 00-3MD N N 2/66 3WL91 11-0AB07 N N 1/39
3VL96 00-3ME N N 2/66 3WL91 11-0AB08 N N 1/39
3VL96 00-3MJ EAR99 N 2/66 3WL91 11-0AB10 N N 1/39
3VL96 00-3ML EAR99 N 2/66 3WL91 11-0AB12 N N 1/39
3VL96 00-3MN EAR99 N 2/66 3WL91 11-0AB18 N N 1/39
3VL96 00-3MQ EAR99 N 2/66 3WL91 11-0AD N N 1/40
3VL96 00-3MS EAR99 N 2/66 3WL91 11-0AE N N 1/40
3VL96 00-4 EAR99 N 2/73, 2/81 3WL91 11-0AF N N 1/40
3VL96 00-8B EAR99 N 2/86, 2/95 3WL91 11-0AG N N 1/40
3VL96 00-8CA EAR99 N 2/80 ... 81 3WL91 11-0AH N N 1/38
3VL96 00-8CB EAR99 N 2/80 ... 81 3WL91 11-0AJ N N 1/38
3VL96 00-8CE N N 2/79 ... 81 3WL91 11-0AK N N 1/34 ... 35
3VL96 00-8L EAR99 N 2/86 ... 87 3WL91 11-0AL N N 1/45
3VL96 00-8S EAR99 N 2/87 3WL91 11-0AM0 N N 1/45
3VL96 8 N N 2/90 3WL91 11-0AM9 N N 1/47
3VL97 0 EAR99 N 2/81, 2/84 ... 88 3WL91 11-0AN0 N N 1/46
3VL97 1 EAR99 N 2/83 ... 88, 2/90 3WL91 11-0AN1 N N 1/46
3VL98 00-1S N N 2/60 3WL91 11-0AN2 N N 1/46
3VL98 00-1UD N N 2/60 3WL91 11-0AN3 N N 1/46
3VL98 00-1UG N N 2/60 3WL91 11-0AN4 N N 1/46
3VL98 00-1UH N N 2/60 3WL91 11-0AP N N 1/41
3VL98 00-1UJ N N 2/60 3WL91 11-0AR N N 1/41
3VL98 00-1UK EAR99 N 2/60 3WL91 11-0AS N N 1/41
3VL98 00-1UL N N 2/60 3WL91 11-0AT N N 1/34 ... 35, 1/37, 1/43 ... 44,
2/98
3VL98 00-1UM N N 2/60
3WL91 11-0BA0 N N 1/42
3VL98 00-1UN N N 2/60
3WL91 11-0BA10 N N 1/42
3VL98 00-1UP N N 2/60
3WL91 11-0BA14 N N 1/37, 2/59 ... 60
3VL98 00-1UQ N N 2/60
3WL91 11-0BA2 N N 1/35
3VL98 00-1UR N N 2/60
3WL91 11-0BA3 N N 1/35
3VL98 00-1US N N 2/60
3WL91 11-0BA4 N N 1/35
3VL98 00-1UU N N 2/60
3WL91 11-0BA5 N N 1/35
3VL98 00-1UV N N 2/60
3WL91 11-0BA7 N N 1/35, 1/38
3VL98 00-2 EAR99 N 2/60
3WL91 11-0BA8 N N 1/35 ... 36
3VL98 00-3AS N N 2/65
3WL91 11-0BB1 N N 1/36
3VL98 00-3AT N N 2/65
3WL91 11-0BB2 N N 1/36
3VL98 00-3AU EAR99 N 2/65
3WL91 11-0BB3 N N 1/36
3VL98 00-3AW EAR99 N 2/65
3WL91 11-0BB4 N N 1/36
3VL98 00-3H EAR99 N 2/65, 2/87 ... 88
3WL91 11-0BB5 N N 1/42
3VL98 00-3M N N 2/66
3WL91 11-0BB6 N N 1/43
3VL98 00-4 EAR99 N 2/74 ... 75, 2/81 ... 82
3WL91 11-0BC N N 1/43, 1/47, 2/98
3VL98 00-8 EAR99 N 2/81 ... 82, 2/87 ... 88,
2/96 ... 97 3WL91 11-0BD N N 1/48
3VL98 16-2 EAR99 N 2/61 3WL91 12 N N 1/36
3VL98 16-8 N N 2/90 3WL92 N N 1/30 ... 33, 1/53 ... 54
Appendix
Order number index
incl. export markings
Order No. Export markings Page Order No. Export markings Page
ECCN AL ECCN AL
3WL93 N N 1/34 5SH2 N N 5/16, 10/31
3ZS 5SH30 N N 5/16, 10/31
3ZS23 N N 1/43, 2/98, 13/19 5SH31 N N 5/16
3ZS27 10 EAR99S N 13/18 5SH32 0 N N 5/16
3ZS27 11 EAR99S N 13/18 5SH32 1 N N 5/16
3ZS27 12-0CC20-0YA 5D992 N 13/18 5SH32 2 N N 5/16
3ZS27 12-0CC20-0YD EAR99S N 13/18 5SH32 8 N N 5/16
3ZS27 13 EAR99S N 13/18 5SH33 N N 5/16 ... 17
3ZS27 14 EAR99S N 13/18 5SH34 N N 5/17
3ZS27 81 On req. 13/13 5SH35 N N 5/31, 10/10 ... 11,
3ZS27 82 5D992 N 13/14 10/13 ... 14
3ZS27 85 EAR99S N 13/10 5SH37 N N 5/16
3ZS27 91 On req. 13/15 5SH4 N N 5/11
3ZS27 95 EAR99S N 13/12 5SH50 N N 5/11
3ZS28 5D992 N 13/18 5SH51 N N 5/11
4AC, 4AT, 4NC 5SH52 N N 5/10, 10/30
4AC N N 9/4, 9/6, 9/8, 12/30 5SH53 N N 5/30 ... 31
4AT N N 12/27 5SH54 N N 5/11
4NC N N 2/92 ... 93 5SH55 0 N N 5/11
5SA, 5SB, 5SC, 5SD 5SH55 1 N N 5/30
5SA N N 5/13 5SH55 25 N N 10/32
5SB N N 5/13 5SH55 26 N N 10/32
5SC N N 5/13 5SH55 27 N N 5/8, 10/32
5SD4 N N 5/62 5SH55 3 N N 5/8
5SD5 N N 5/62 5SJ, 5SK, 5SL, 5SM
5SD6 N N 5/14 5SJ N N 3/25, 3/48 ... 52
5SD74 1 N N 6/4, 6/12 5SK N N 3/59
5SD74 2 N N 6/10, 6/12 5SL N N 3/6 ... 7
5SD74 3 N N 6/11 ... 12 5SM1 N N 4/14, 4/26
5SD74 41 N N 6/6 5SM2 N N 3/32 ... 33, 4/16 ... 17
5SD74 42 N N 6/6 5SM31 N N 4/6
5SD74 43 N N 6/6 5SM33 1 N N 4/5 ... 8
5SD74 44 N N 6/6 5SM33 2 EAR99H N 4/10
5SD74 48 N N 6/12 5SM33 42-0 N N 4/5
5SD74 6 N N 6/9, 6/12 5SM33 42-4 EAR99H N 4/10 ... 11
5SD74 7 N N 6/10 5SM33 42-6 N N 4/6 ... 8
5SD74 8 N N 6/9 ... 10, 6/12 5SM33 44-0 N N 4/5
5SD74 9 N N 6/12 ... 13 5SM33 44-4 EAR99H N 4/10 ... 11
5SD75 N N 6/17 5SM33 44-6 N N 4/6 ... 8
5SD8 N N 5/13 5SM33 45 N N 4/5 ... 6
5SE, 5SF, 5SG, 5SH 5SM33 46-0 N N 4/5
5SE N N 5/7, 5/62 5SM33 46-4 EAR99H N 4/10 ... 11
5SF N N 5/14 ... 15, 10/30 ... 31 5SM33 46-6 N N 4/6 ... 8
5SG1 N N 5/9 5SM33 47-4 EAR99H N 4/10 ... 11
5SG5 N N 5/9 ... 10 5SM33 47-6 N N 4/6 ... 7
5SG6 N N 10/30 5SM33 48 N N 4/6
5SG71 1 N N 5/8 5SM33 5 N N 4/7
5SG71 2 N N 5/8 5SM34 N N 4/5 ... 6, 4/8
5SG71 3 N N 5/8 5SM36 1 N N 4/6, 4/8
5SG71 5 N N 5/8 5SM36 2 EAR99H N 4/10
5SG71 6 N N 5/8 5SM36 42-0 N N 4/5
5SG72 N N 10/31 5SM36 42-4 EAR99H N 4/10 ... 11
5SG76 N N 5/8 5SM36 42-6 N N 4/6 ... 7
5SH11 1 N N 5/15 5SM36 44-0 N N 4/5
5SH11 2 N N 5/15 5SM36 44-4 EAR99H N 4/10 ... 11
5SH11 3 N N 5/15 5SM36 44-6 N N 4/6 ... 8
5SH11 4 N N 5/15 5SM36 44-8 N N 4/8
5SH11 6 N N 5/15 5SM36 45 N N 4/5 ... 6, 4/8
5SH11 7 N N 5/15 5SM36 46-0 N N 4/5
5SH12 N N 5/15 5SM36 46-4 EAR99H N 4/10 ... 11
Appendix
Order number index
incl. export markings
Order No. Export markings Page Order No. Export markings Page
ECCN AL ECCN AL
5SM36 46-5 EAR99H N 4/10 5ST37 50 N N 3/41, 4/25, 5/30
5SM36 46-5K N N 4/11 5ST37 50-0 N N 3/45, 5/32
5SM36 46-6 N N 4/6 ... 8 5ST37 6 N N 3/28, 3/42
5SM36 46-8 N N 4/8 5ST37 7 N N 3/41, 3/45, 4/25, 5/32
5SM36 47-4 EAR99H N 4/10 ... 11 5ST38 00 N N 3/34, 8/19
5SM36 47-5 EAR99H N 4/10 5ST38 01 N N 3/34, 3/53, 8/7, 8/19
5SM36 47-5K N N 4/11 5ST38 02 N N 3/34, 3/53, 4/14
5SM36 47-6 N N 4/6 ... 8 5ST38 03 N N 3/34
5SM36 48 N N 4/6, 4/8 5ST38 05 N N 4/22
5SM36 5 N N 4/7 5ST38 06 N N 3/34
5SM37 42 N N 4/6 5ST38 07 N N 3/34
5SM37 44 N N 4/6 5SU, 5SV, 5SW, 5SY, 5SZ
5SM37 45 N N 4/5 ...6, 4/8 5SU N N 4/11 ... 12, 4/19 ... 22
5SM37 46-4 EAR99H N 4/10 5SV N N 12/10
5SM37 46-5 EAR99H N 4/10 5SW1 N N 3/35, 4/27
5SM37 46-6 N N 4/6 ... 7 5SW30 N N 3/35, 4/14, 4/27
5SM37 47-4 EAR99H N 4/10 5SW33 00 N N 4/14
5SM37 47-5 EAR99H N 4/10 5SW33 01 N N 4/14
5SM37 48 N N 4/6 5SW33 02 N N 4/14
5SM38 N N 4/8 5SW33 03 N N 4/14
5SP, 5ST 5SW33 1 N N 4/14, 4/27
5SP N N 3/15 ... 16, 3/56 ... 57 5SW33 3 N N 4/14
5ST13 N N 3/57 5SY4 N N 3/11 ... 14
5ST18 N N 3/59 5SY5 N N 3/16 ... 17
5ST21 34 N N 3/35, 4/27 5SY6 N N 3/28
5ST21 35 N N 3/35, 4/27 5SY7 N N 3/18 ... 20
5ST21 36 N N 3/35, 4/27 5SY8 N N 3/21 ... 22
5ST21 4 N N 4/25 5SZ N N 4/26
5ST21 56 N N 4/25 5TE, 5TG, 5TT
5ST21 57 N N 4/25, 5/31 5TE1 N N 7/27
5ST21 7 N N 3/34, 4/27 5TE2 N N 8/20
5ST21 8 N N 5/30 5TE4 N N 8/10 ... 11
5ST21 90 N N 5/30 5TE5 N N 8/13
5ST21 91 N N 5/30 5TE6 N N 9/10 ... 11
5ST21 92 N N 5/30 5TE8 N N 8/6, 8/17 ... 18
5ST21 96 N N 5/30 5TE9 N N 7/28, 8/19, 8/23, 9/11
5ST21 97 N N 5/30 5TG N N 3/34, 8/7, 8/11, 8/14, 8/19,
8/29, 8/32, 12/34 ... 35
5ST22 N N 3/34, 4/27
5TT1 N N 8/50
5ST26 N N 5/24
5TT3 N N 5/43, 8/37, 8/51,
5ST30 1 N N 3/31, 3/52, 5/8, 8/7, 8/18,
12/13 ... 14, 12/18 ... 20,
8/20
12/27, 12/31, 12/34 ... 35,
5ST30 2 N N 3/31, 3/52 12/37, 12/40 ... 41
5ST30 3 N N 3/31, 3/52 5TT41 N N 8/26
5ST30 4 N N 3/31 5TT42 0 N N 8/29
5ST30 5 N N 3/31, 4/14 5TT42 1 N N 8/29
5ST36 N N 3/28, 3/39 ... 40, 3/45, 3/53, 5TT49 N N 8/27
4/24 ... 25, 5/31 ... 32
5TT5 N N 8/32, 8/35 ... 36, 12/32
5ST37 0 N N 3/41, 3/45, 4/24,
5TT6 N N 12/16 ... 17
5/29 ... 30, 5/32
5TT7 N N 12/30
5ST37 1 N N 3/41, 3/45, 4/24 ... 25,
5/29 ... 30, 5/32 7KM
5ST37 3 N N 3/40, 4/24 7KM2 5D992 N 11/27
5ST37 40 N N 3/40 7KM3 EAR99APP N 11/26
5ST37 41 N N 3/40 7KM4 5D992 N 11/28
5ST37 42 N N 3/40 7KM92 EAR99H N 11/31
5ST37 43 N N 3/40 7KM93 N N 11/29 ... 30
5ST37 44 N N 3/40 7KM99 N N 11/26 ... 28
5ST37 45 N N 3/40 7KT
5ST37 46 N N 3/40 7KT10 0 N N 11/32
5ST37 48 N N 3/41, 5/30 7KT10 10 N N 11/32
5ST37 48-0 N N 3/45, 5/32 7KT10 11 N N 11/32
Appendix
Order number index
incl. export markings
Order No. Export markings Page Order No. Export markings Page
ECCN AL ECCN AL
7KT10 12 N N 11/32 8UC6 N N 2/67, 7/40 ... 42, 7/48 ... 50,
7KT10 2 N N 11/32 7/55 ... 56, 7/62
7KT11 1 N N 11/34 8UC7 N N 2/67, 2/69, 7/34, 7/36, 7/38,
7/40 ... 42, 7/46,
7KT11 2 N N 11/34 7/48 ... 50, 7/54 ... 56,
7KT11 4 N N 11/11 7/61 ... 62
7KT12 N N 11/39 8UC9 N N 7/36 ... 38, 7/41 ... 42, 7/46,
7/50, 7/62 ... 63
7KT13 0 N N 11/16
8US, 8WC
7KT13 1 N N 11/19
8US10 N N 2/89
7KT13 4 N N 11/19
8US12 0 N N 10/14
7KT13 9 N N 11/22
8US12 1 N N 2/90, 7/117, 10/18 ... 21
7KT15 N N 11/8, 11/11
8US12 50 N N 10/16 ... 17, 10/20 ... 22
7KT19 N N 11/13
8US12 51-5DS10 N N 5/24, 10/16, 10/21
7KT55 N N 11/38
8US12 51-5DS11 On req. 10/16, 10/21
7KT56 N N 11/38
8US12 51-5DT N N 5/24, 10/16, 10/21
7KT58 0 N N 11/36
8US12 51-5N N N 10/17, 10/21
7KT58 1 N N 11/36
8US12 6 N N 10/18, 10/22
7KT58 2 N N 11/36
8US12 9 N N 7/117
7KT58 3 N N 11/36
8US19 0 N N 10/7
7KT90 0 N 9I999 11/38
8US19 21-1 N N 10/14
7KT90 10 N N 11/40
8US19 21-2AA N N 10/15
7KT90 11 N N 11/40
8US19 21-2AB N N 10/15
7KT90 2 N N 11/38
8US19 21-2AC N N 10/15
7LF, 7LQ
8US19 21-2AD00 N N 10/15
7LF4 N N 8/40 ... 41
8US19 21-2AD01 N N 10/15
7LF5 N N 8/47
8US19 21-2BA N N 10/15
7LF61 10 N N 8/50
8US19 21-2BB N N 10/15
7LF61 11 N N 8/50
8US19 21-2BC N N 10/15
7LF61 12 N N 8/50
8US19 21-2BD00 N N 10/15
7LF61 13 N N 8/50
8US19 21-2BD01 N N 10/15
7LF61 14 N N 8/50
8US19 21-2BE N N 10/12, 10/24 ... 25
7LF61 15 N N 8/50
8US19 21-2BF N N 10/12, 10/24 ... 25
7LF61 16 N N 8/50
8US19 22 N N 10/7, 10/11 ... 13, 10/15
7LF9 N N 3/35, 8/41, 8/48
8US19 23 N N 10/10 ... 11
7LQ20 N N 12/39
8US19 27 N N 2/90, 10/19
7LQ21 00 N N 12/37
8US19 41-2AA01 N N 10/15
7LQ21 01 N N 12/37
8US19 41-2AA02 N N 10/15
7LQ21 02 N N 12/37
8US19 41-2AA03 N N 10/14
7LQ21 03 N N 12/37
8US19 41-2AA04 N N 10/15
7LQ22 N N 9/9
8US19 41-2AC N N 10/15
7LQ29 N N 12/37, 12/39
8US19 41-2B N N 10/13, 10/15
7LQ33 5 N N 12/26 ... 27
8US19 43 N N 10/13
7LQ33 60 N N 12/27
8US19 48 N N 10/13
7LQ33 61 N N 12/26
8US19 98-1AA0 N N 10/18, 10/22, 10/25
7LQ33 62 N N 12/26
8US19 98-1AA1 N N 10/24
8GB, 8GK
8US19 98-1BA0 N N 10/25
8GB N N 3/35
8US19 98-1BA1 N N 10/24
8GK4 N N 10/9
8US19 98-1CA0 N N 10/25
8GK97 1 N N 10/10
8US19 98-1CA1 N N 10/24
8GK97 3 N N 10/12
8US19 98-1D N N 10/25
8HP, 8JH, 8JK
8US19 98-2 N N 10/22
8HP27 0 N N 7/39
8US19 98-4 N N 10/25
8HP27 1 N N 7/39
8US19 98-7 N N 5/24, 10/24 ... 25
8HP27 3 N N 7/39
8WC N N 10/7, 10/12
8HP27 4 N N 7/39
XP
8HP27 5 N N 7/39
XPT --N N 7/88
8HP27 6 N N 7/39
8JH N N 5/31
8JK N N 10/12
8UB, 8UC
8UB N N 7/37 ... 38
Appendix
Notes
Appendix
Notes
Appendix
■ Overview
By using this catalog you can acquire hardware and software Export regulations
products described therein from Siemens AG subject to the fol-
lowing terms. Please note! The scope, the quality and the condi- Our obligation to fulfill this agreement is subject to the proviso
tions for supplies and services, including software products, by that the fulfillment is not prevented by any impediments arising
any Siemens entity/regional having a registered office outside of out of national and international foreign trade and customs re-
Germany, shall be subject exclusively to the General Terms and quirements or any embargos and/or other sanctions.
Conditions of the respective Siemens entity. The following terms If you transfer goods (hardware and/ or software and/ or technol-
apply exclusively for orders placed with Siemens AG. ogy as well as corresponding documentation, regardless of the
mode of provision) delivered by us or works and services (in-
For customers with a seat or registered office in Germany cluding all kinds of technical support) performed by us to a third
The General Terms of Payment as well as the General Conditions party worldwide, you shall comply with all applicable national
for the Supply of Products and Services of the Electrical and and international (re-) export control regulations.
Electronics Industry shall apply. If required to conduct export control checks, you, upon request
For software products, the General License Conditions for Soft- by us, shall promptly provide us with all information pertaining to
ware Products for Automation and Drives for Customers with a particular end customer, destination and intended use of goods,
Seat or Registered Office in Germany shall apply. works and services provided by us, as well as any export control
restrictions existing.
For customers with a seat or registered office outside of
Germany The products listed in this catalog / price list may be subject to
European / German and/or US export regulations.
The General Terms of Payment as well as the General Conditions
for Supplies of Siemens Automation and Drives for Customers Therefore, any export requiring a license is subject to approval
with a Seat or registered Office outside of Germany shall apply. by the competent authorities.
For software products, the General License Conditions for According to current provisions, the following export regulations
Software Products for Automation and Drives for Customers must be observed with respect to the products featured in this
with a Seat or registered Office outside of Germany shall apply. catalog / price list:
General
AL Number of the German Export List
All dimensions are in mm. In Germany, according to the German Products marked other than "N" require an export license.
law on units in measuring technology, data in inches only apply
In the case of software products, the export designations of the
to devices for export. relevant data medium must also be generally adhered to.
Illustrations are not binding. Goods labeled with an "AL" not equal to "N" are subject to a
European or German export authorization when being
Insofar as there are no remarks on the corresponding pages, exported out of the EU.
- especially with regard to data, dimensions and weights given - ECCN Export Control Classification Number
these are subject to change without prior notice. Products marked other than "N" are subject to a re-export
The prices are in € (Euro) ex works, excluding packaging. license to specific countries.
In the case of software products, the export designations of the
The sales tax (value added tax) is not included in the prices. relevant data medium must also be generally adhered to.
It shall be debited separately at the respective rate according to Goods labeled with "ECCN" not equal to "N" are subject to a US
the applicable legal regulations. re-export authorization.
Prices are subject to change without prior notice. We will debit Even without a label or with an "AL: N" or "ECCN: N", authoriza-
the prices valid at the time of delivery. tion may be required due to the final destination and purpose for
Surcharges are added to the price of products that contain which the goods are to be used.
silver, copper, aluminum, lead and/or gold if the respective basic The deciding factors are the AL or ECCN export authorization
official prices for these metals are exceeded. These surcharges indicated on order confirmations, delivery notes and invoices.
will be determined based on the official price and the metal fac-
tor of the respective product. Errors excepted and subject to change without prior notice.
The surcharge will be calculated on the basis of the official price
on the day prior to receipt of the order or prior to the release
order.
The metal factor determines the official price as of which the
metal surcharges are charged and the calculation method used.
The metal factor, provided it is relevant, is included with the price
information of the respective products.
An exact explanation of the metal factor and the text of the
Comprehensive Terms and Conditions of Sale and Delivery are
available free of charge from your local Siemens business office
under the following Order Nos.:
• 6ZB5310-0KR30-0BA1
(for customers based in Germany)
• 6ZB5310-0KS53-0BA1
(for customers based outside Germany)
or download them from the Internet:
www.siemens.com/industrymall
(Germany: Industry Mall Online Help System)
Catalogs
Industry Automation, Drive Technologies and Low Voltage Distribution
Further information can be obtained from our branch offices listed
in the appendix or at www.siemens.com/automation/partner
Interactive Catalog on DVD Catalog Motion Control Catalog
for Industry Automation, Drive Technologies and CA 01 SINUMERIK & SIMODRIVE NC 60
Low Voltage Distribution Automation Systems for Machine Tools
SINUMERIK & SINAMICS NC 61
Drive Systems Equipment for Machine Tools
Variable-Speed Drives SIMOTION, SINAMICS S120 and PM 21
SINAMICS G110, SINAMICS G120 D 11.1 Motors for Production Machines
Standard Inverters SINAMICS S110 PM 22
SINAMICS G110D, SINAMICS G120D The Basic Positioning Drive
Distributed Inverters
SINAMICS G130 Drive Converter Chassis Units D 11 Low-Voltage
SINAMICS G150 Drive Converter Cabinet Units Controls and Distribution – LV 1
SINAMICS GM150, SINAMICS SM150 D 12 SIRIUS, SENTRON, SIVACON
Medium-Voltage Converters SICUBE System Cubicles and Cubicle Air-Conditioning LV 50
SINAMICS S120 Chassis Format Units and D 21.3 PDF: SIDAC Reactors and Filters LV 60
Cabinet Modules
SINAMICS S150 Converter Cabinet Units PDF: SIVACON 8PS Busbar Trunking Systems LV 70
SINAMICS DCM Converter Units D 23.1 Low-Voltage Controls and Distribution – LV 90
SIRIUS, SENTRON, SIVACON
Three-phase Induction Motors D 84.1
• H-compact Power Supply and System Cabling
• H-compact PLUS
Power supply SITOP KT 10.1
Asynchronous Motors Standardline D 86.1 System cabling SIMATIC TOP connect KT 10.2
Synchronous Motors with Permanent-Magnet D 86.2
Technology, HT-direct Process Instrumentation and Analytics
DC Motors DA 12 Field Instruments for Process Automation FI 01
SIMOREG DC MASTER 6RA70 Digital Chassis DA 21.1 SIREC Recorders and Accessories MP 20
Converters
SIPART, Controllers and Software MP 31
SIMOREG K 6RA22 Analog Chassis Converters DA 21.2
Products for Weighing Technology WT 10
PDF: SIMOREG DC MASTER 6RM70 Digital Converter DA 22
Cabinet Units PDF: Process Analytical Instruments PA 01
SIMOVERT PM Modular Converter Systems DA 45 PDF: Process Analytics, PA 11
Components for the System Integration
SIEMOSYN Motors DA 48
MICROMASTER 420/430/440 Inverters DA 51.2 Safety Integrated
MICROMASTER 411/COMBIMASTER 411 DA 51.3 Safety Technology for Factory Automation SI 10
SIMOVERT MASTERDRIVES Vector Control DA 65.10
SIMOVERT MASTERDRIVES Motion Control DA 65.11 SIMATIC HMI/PC-based Automation
Synchronous and asynchronous servomotors for DA 65.3 Human Machine Interface Systems/ ST 80/
SIMOVERT MASTERDRIVES PC-based Automation ST PC
SIMODRIVE 611 universal and POSMO DA 65.4
SIMOTION, SINAMICS S120 and PM 21 SIMATIC Industrial Automation Systems
Motors for Production Machines Products for Totally Integrated Automation and ST 70
SINAMICS S110 PM 22 Micro Automation
The Basic Positioning Drive SIMATIC PCS 7 Process Control System ST PCS 7
Low-Voltage Three-Phase-Motors Add-ons for the SIMATIC PCS 7 ST PCS 7.1
Process Control System
IEC Squirrel-Cage Motors D 81.1
PDF: Migration solutions with the SIMATIC PCS 7 ST PCS 7.2
MOTOX Geared Motors D 87.1 Process Control System
Automation Systems for Machine Tools SIMODRIVE NC 60
• Motors SIMATIC NET
• Converter Systems SIMODRIVE 611/POSMO Industrial Communication IK PI
Automation Systems for Machine Tools SINAMICS NC 61
• Motors SIMATIC Sensors
• Drive System SINAMICS S120 Sensor Technology for Factory Automation FS 10
Drive and Control Components for Hoisting Equipment HE 1 Industrial Identification Systems ID 10
Mechanical Driving Machines
Flender Standard Couplings MD 10.1 System Solutions
Applications and Products for Industry are part of the
Electrical Installation Technology interactive catalog CA 01
PDF: ALPHA Distribution Boards and Terminal Blocks ET A1
PDF: ALPHA 8HP Molded-Plastic Distribution System ET A3
PDF: BETA Low-Voltage Circuit Protection ET B1
PDF: DELTA Switches and Socket Outlets ET D1
PDF: GAMMA Building Management Systems ET G1 Download-Center
PDF versions of the catalogs are available on the Internet at:
PDF: These catalogs are only available as pdf files. www.siemens.com/buildingtechnologies/infocenter
Siemens AG
Industry Sector
Building Technologies Division
Low Voltage Distribution
Postfach 10 09 53
93009 REGENSBURG
GERMANY
www.siemens.com/lowvoltage