You are on page 1of 2

®

DSEULTRA
®

STARTING
WITH SPECIFICATION

QUALITY. DC SUPPLY
8V to 35V continuous

CRANKING DROPOUTS
Able to survive 0V for 50mS, providing supply
DSE710 & DSE720 was at least 10V before dropout and supply
recovers to 5V. This is achieved without the
AUTO START & AUTO MAINS FAILURE CONTROL MODULES need for internal batteries.

MAXIMUM OPERATING CURRENT


180mA at 12V. 190mA at 24V

MAXIMUM STANDBY CURRENT


145mA at 12V. 150mA at 24V

GENERATOR INPUT RANGE


35V(L-N) to 333V AC (L-N) absolute maximum
50Hz - 60Hz (min 15V AC)

AUXILIARY OUTPUTS
Solid state
DSE710 DSE720 2.4A DC at supply voltage

FUEL/START OUTPUTS
Solid state
3.4A DC at supply voltage

GENERATOR C.T.
5A secondary 0.5VA

MAINS (UTILITY) SENSING INPUT


RANGE (DSE720 only)
35V(L-N) to 333V AC (L-N)
50Hz - 60Hz (min 15V AC)

DSE710 & DSE720 DIMENSIONS


209mm x 146mm x 30.3mm
8.2” x 5.7” x 1.2”

DSE710 & DSE720 PANEL CUTOUT:


182mm x 137mm
7.2” x 5.4”

The DSE710 is an Automatic FEATURES OPERATION MAXIMUM PANEL THICKNESS


8mm
Start Control Module that offers • PC configurable The module is operated using 0.3”
an advanced range of engine • Digital and analogue inputs the front STOP/RESET, MANUAL,
monitoring and protection • Digital outputs AUTO, TEST and START push
features. The module has been • Automatic mains (utility) supply buttons. ENVIRONMENTAL TESTING
designed to monitor generator monitoring (DSE720 only) STANDARDS
frequency, generator volts, • Automatic shutdown or warning An additional push button next to
generator current, engine oil when fault conditions are detected the LCD display is used to scroll
ELECTRO MAGNETIC CAPABILITY
• Manual start through the modules’ metering
pressure, engine coolant BS EN 61000-6-2
• Engine pre-heat displays. EMC Generic Emission Standard for the
temperature, engine running
• Engine monitoring and protection Industrial Environment
hours and battery volts. features CONFIGURATION BS EN 61000-6-4
EMC Generic Emission Standard for the
• Protected Solid State (PSS) The modules can be configured using Industrial Environment
The module also displays the outputs the front panel or remotely using the
engine speed. When the module • Front panel mounting DSE810 interface and a PC. ELECTRICAL SAFETY
detects a fault condition it • Front panel programming BS EN 60950
Safety of Information Technology Equipment,
automatically shuts down the • Tamper proof engine hours As well as configuration the DSE810 including Electrical Business Equipment
engine and indicates the exact counter interface has the ability to provide
fault on the modules LCD display • Remote start real time diagnostic facilities. TEMPERATURE
• LED indicators BS EN 60068-2-2
or relevant LED indicator. Test Ab to +70oC 60067-2-2 Hot
• Configurable timers Test Ab to -30oC 60068-2-1 Cold
The module can be configured • Configurable outputs
using the front panel or via the • Configurable inputs VIBRATION
• Back-lit character/icon LCD BS EN 60068-2-6
DSE810 interface and a PC. The Ten sweeps in each of three major axes
display
module can also be controlled 5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
from a PC that is located up to
BENEFITS HUMIDITY
100 meters away. • Transfer between mains (utility) BS 2011 part 2.1 60068-2-30
Test Cb Ob Cyclic
and generator power (DSE720 93% RH @ 40oC for 48 hours
The DSE720 is an Automatic only)
Mains Failure Control Module • On-site module configuration and SHOCK
and incorporates all the features remote configuration (Max 100 BS EN 60068-2-27
Three shocks in each of three major axes
of the DSE710 plus the ability to Meters) using PC software 15gn in 11mS
automatically monitor the mains • User-friendly set-up and button
supply and switch over to the layout
generator when the mains • Multiple engine parameters are
power fails. monitored simultaneously
• License free PC software
DEEP SEA ELECTRONICS PLC TELEPHONE EMAIL ®
Highfield House +44 (0)1723 890099 sales@deepseaplc.com
Hunmanby Industrial Estate
Hunmanby, North Yorkshire FACSIMILE WEBSITE
YO14 0PH England +44 (0)1723 893303 www.deepseaplc.com

Registered in England & Wales No.01319649 VAT No.316923457

DEEP SEA ELECTRONICS INC TELEPHONE EMAIL


3230 Williams Avenue +1 (815) 316 8706 sales@deepseausa.com
Rockford
IL 61101-2668 USA FACSIMILE WEBSITE
+1 (815) 316 8708 www.deepseausa.com

DSE710 & DSE720


MECHANICAL LOAD

LOAD
DSE720 ONLY INSTRUMENTATION AND
ALARMS
CTs MUST BE 5 AMP
SECONDARY
The DSE710 and DSE720 both
L1
P1 P2
provide comprehensive metering
L1
S1 S2
and alarm facilities.
L2 L2

The table below outlines the


FROM L3 L3 module’s capabilities.
GENERATOR FROM
MAINS
N N

DSE710/DSE720
2 AMP 2 AMP
FUSES ELECTRICAL INTERLOCK FUSES

G M Generator Frequency
NORMALLY OPEN NORMALLY CLOSED
Engine Speed
Generator Volts (L1-N, L2-N, L3-N)
Generator Volts (L1-L2, L2-L3, L3-L1)
+ +
Generator Current (L1, L2, L3)
Engine Oil Pressure
Engine Coolant Temperature
18 19 20 21 26 27 9 8 22 23 24 25
Hours Run Counter
L1 N L1 L2 L3 N
CLOSE GEN

CLOSE MAINS

L1 L2 L3 COM

GEN VOLTS
Battery Volts
MAINS

Mains Volts (DSE720 only)


COOLANT TEMP

MODULE 710/720
REMOTE START
OIL PRESSURE

(L1-N, L2-N, L3-N)


CHRG ALT
OUTPUT 1

OUTPUT 2
EM STOP

BATTERY
INPUT 1

INPUT 2
CRANK
FUEL
+VE
-VE

1 2 3 4 5 6 7 10 11 12 13 15 16 14 17

2 AMP 2 AMP
FUSE FUSE
TO ENGINE EARTH

WL
FUEL CRANK CHARGE
BATTERY RELAY RELAY
SOLENOID SOLENOID ALT

BATTERY NEGATIVE MUST BE GROUNDED


SCREW TERMINALS TIGHTENING TORQUE = 0.8Nm (7lb-in)

* NOTE. ALL THE OUTPUTS ARE SOLID STATE AND ARE POSITIVE SWITCHING

RELATED MATERIALS
TITLE PART NO’S
DSE710 Manual 053-013
DSE720 Manual 053-005
DSE7xx Software Manual 057-002

DEEP SEA ELECTRONICS PLC maintains a policy of continuous development and reserves the right to
change the details shown on this data sheet without prior notice. The contents are intended for guidance only.

This data sheet is printed on 9lives 55 Silk, which is produced with 55% recycled fibre
from both pre and post-consumer sources, together with 45% virgin ECF fibre.
055-035/02/08 (2)