Scope:-
General:-
Number of phases : 3;
(maximum) : 50 °C;
Construction:-
Provisions shall be included for electrical close, and electrical and manual
trip.
Mechanism:-
The mechanism shall utilize low energy requirement, three direct drive
magnetic actuators capable of fast opening and closing operations with
0.2 second delay. Actuator should not require any operating power to
hold the unit in either open or closed condition. The use of one magnetic
actuator to drive the vacuum bottles through multiple linkages is not
acceptable. A rechargeable battery in combination with a tripping
capacitor, allowing fast multiple open-closed-open operations, must
power the magnetic actuator.
Design shall permit multiple operations after loss of primary control voltage
to allow dead line operation. Inbuilt Battery bank should provide back-up
up to 48 hours in case of failure of 240V AC control supply.
Current Sensing:-
(PTs) are not acceptable for protection purpose. Embedded sensors are
must for this purpose.
Battery Backup/UPS:-
The control unit AC power input must have integrated high-energy surge
protection (per IEEE C62.41) and line fuse to protect the control from
incoming line surges. The integrated power supply must have a staged
shutdown feature to protect the electronics during extreme temperatures.
Control equipment
Control cabinet:-
The control for the Autorecloser shall be through a high end numerical
relay having inbuilt UPS and power control electronics Cabinets that
houses equipment for protection and control and shall be mounted
independently of the AR. Cabinets shall be adequately sealed and dust
protected and shall be internally treated to prevent moisture
condensation. The degree of protection shall be suitable for Outdoor
installation.
Protection characteristics:-
• Under and over voltage protection and alarm (Single and three-
phase)
Over-current function:-
A cold load pick-up (CLP) feature shall be provided that allows user
selectable modification of protection element characteristics under
conditions of system energisation. The CLP function may be provided in
one of the following two ways:
The instantaneous O/C element and the Low Set Definite Time O/C
element could be blocked for the CLP time duration; and
The pick-up current setting of the IDMTL O/C element and the Low Set
Definite Time O/C element may be modified with a settable factor to
increase the pick-up current of these elements for the CLP duration. The
instantaneous O/C element should be blocked for this time.
Directional Protection:-
Sag and Swell Detection for Transient Stability and other Quality
Parameters:-
Metering:-
• Power factor
• Frequency
As far as the metering with the help of inbuilt sensors is concerned, in case
of failure of external metering CT/PTs, all current and voltage values must
be accurate to within ± 1%, and power values accurate within ± 2%.
The controller shall have load profile feature that stores historical load
data. User-selectable load profile data sampling of 5, 15, 30, 60 minute
time interval which will store the data at least for 40 days.
Reset times shall ideally be separately selectable for SEF and the
combination of over-current and earth fault functions. The reset time shall
be selectable from 3s to 200s with increment 1 sec.
Dead times shall ideally be separately selectable for SEF and the
combination of over-current and earth fault functions. The dead time
between each successive recloser shall be independently selectable from
instantaneous and from a minimum of 0.1s up to a maximum of 200s for all
reclosings.
‘HOT LINE TAG’ function shall allow the AR controller to be set in the
following modes:
Remote:- In this mode a local operator can trip the AR and change the
mode. A remote operator can trip or close the AR and change
configuration parameters. All reporting functions are active.
Local:- In this mode a local operator can trip and close the AR and
change configuration parameters. Only monitoring functions are
available to remote operators.
Control Features:-
The control must have the following pushbuttons with indicating LEDs:-
• Open
• Close
• Remote Blocked
• Reclose Blocked
• Alternate Settings
• Ground Blocked
• Lockout
• Unit Status
• After a trip or lockout, the display must read the phase currents,
tripping element and distance to fault
The AR controller shall contain a real time clock (with leap year support)
that can be set both locally and remotely.
Tele-control requirements
Communications
Applicable Standards:-
The recloser and its control must be designed and tested to meet the
following standards:
• ANSI C37.61/ IEEE 321-1973: IEEE Standard Guide for the Application,
Operation and Maintenance of Automatic Circuit Reclosers