DESIGN REFERENCE FOR

ELEVATOR INSTALLATIONS
三菱エレベータNexWay技術資料 07.10.24 2:11 PM ページ 1

BASIC SPECIFICATIONS
BASIC SPECIFICATIONS OF THE NexWay OF THE NexWay

● Capacity and Speed ●: Applicable ● Control, Door and Operation Systems ●: Applicable −: Not applicable

Rated Number Rated speed (m/sec) Operation system


capacity of
(kg) persons Number of
2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0 8.0 9.0 elevators Contlol system Door system 1-car selective 2-car selective Σ AI-22 group Σ AI-2200C group
in a bank collective collective control system control system
750 10 ● ● ● ● ● ● ● ● ● ● (Standard) (option) (option) (option)

900 12 ● ● ● ● ● ● ● ● ● ● 1 car ●(1C-2BC) ― ― ―

1050 14 ● ● ● ● ● ● ● ● ● ● 2 cars ― ●(2C-2BC)* 1   ― * 2 ―

1200 16 ● ● ● ● ● ● ● ● ● ●
VVVF control with
3 cars ― ― ●(3C-ΣAI-22) ●(3C-ΣAI-2200C)
microprocessor,
1350 18 ● ● ● ● ● ● ● ● ● ● VVVF control and 2-panel center
Data Network opening〈CO〉
4 cars ― ― ●(4C-ΣAI-22) ●(4C-ΣAI-2200C)
1600 21 ● ● ● ● ● ● ● ● ● ● System (Standard),
with multiple 2-panel side
microprocessor opening〈2S〉
1800 24 ● ● ● ● ● ● ● 5 cars ― ― ― ●(5C-ΣAI-2200C)
modules (option),
(VFGH) 4-panel center
2000 26 ● ● ● ● ● opening〈2CO〉
6 cars (option) ― ― ― ●(6C-ΣAI-2200C)
2250 30 ● ● ● ● ●
7 cars ― ― ― ●(7C-ΣAI-2200C)
2500 33 ● ● ● ● ●

3000 40 ● ● ● ● ● 8 cars ― ― ― ●(8C-ΣAI-2200C)

Notes: 1. Capacity and number of persons are based on EN81-1 (1998). Notes: * 1. When the capacity and speed exceed the range shown in the left page, the operation system 2C-2BC should be 2C-ΣAI-22.
2. Please consult our local subcontractor for specifications outside the table above. * 2. Please consult our local subcontractor, when 2C-ΣAI-22 system is required instead of 2C-2BC system.
3. The specifications in green frame ( ) are for the space saving models.
4. Refer to page 5 to 12 for the hoistway and machine room layout plans for the models with specifications marked in gray ( ).
For the layouts for models with other specifications, please consult our local subcontractor.

Selective collective (2BC) ΣAI-22&ΣAI-2200C Group Control Systems


The system consists of call buttons in the car, and a The systems, which employ an intelligent expert
● Specifications riser of up and down destination floor buttons installed system and fuzzy logic, are specially designed for
at each elevator hall (single button at terminal floors), group control of 3 to 8 elevators (as described above).
Rated speed 2.0 2.5 3.0 3.5 4.0 5.0 6.0 7.0 8.0 9.0
which connect electrically with microprocessors Practical information required for group control is
Maximum number of stops 128: One gate (1D1G), 64: Two gates (1D2G & 2D2G) supervising floor selection and direction of travel. A car stored in the system's memory as a "Knowledge
Maximum travel (m) 150 *1 200 *1 250 *1 will respond to those car and hall calls that comply with Database". Drawing from this database, various traffic
its direction of service. conditions are monitored and analyzed applying IF-
Minimum floor height (mm) 2,500 *2
When there are no more calls registered for the car's THEN decision rules to maximize the effectiveness of
Notes: *1 Please consult our local subcontractor if the maximum travel exceeds the values specified in the table above. direction of travel, the car's service direction is each elevator operation.
*2 For some elevator specifications, the floor height (distance between floors) must be a minimum of 2,500mm.
Please consult us if the floor height is less than “Entrance height HH + 700mm”. reversed. The systems perform assignments to the most-used
locations, and thereby provide superb efficiency and
service.
In addition to the above, ΣAI-2200C system performs
optimal car allocation using Dynamic Rule-set
Optimizer.

1 2
三菱エレベータNexWay技術資料 07.10.5 11:54 AM ページ 3

STANDARD
REFERENCE DATA FOR ELEVATOR PLANNING STANDARD INSTALLATION INSTALLATION

Elevator traffic reaches a peak when people employed Selecting the Elevator Speed ● Notes on Installation Planning
in the building arrive for work in the morning, when The maximum number of floors served in a building
they break for lunch at midday, and when they leave serves as the criterion for selecting the speed at which Points Relating to the Points Relating to the
for home in the evening. Obviously, the elevators must Elevator Arrangement
the elevators should travel. To select elevators using Hoistway Machine Room
be capable of handling the increased traffic during the chart below, if the building has 23 floors, select
these peaks. And during actual business hours, the ● Elevator installations should be properly ● In steel-reinforced concrete ● Provide the recommended width
elevators with a speed of 3.5m/sec or 4.0m/sec.
elevators must be able to respond promptly to serve planned according to such factors as the buildings, design the hoistways so and height to assure that there will
the people who are on the move inside the building as size and nature or kind of the building, that concrete walls are at least be sufficient room for inspection and
the traffic flow and peak traffic demand 120mm thick. maintenance.
well as those who arrive at or leave the building. So
or conditions, the location of public ● Hoistways must be no more than ● Since the elevator drive equipment
that the elevators best suited to the conditions and transportation facilities and stores. 30mm out of plumb. generates considerable heat,
environment at hand can be selected, Mitsubishi ● Dispersing elevators in different areas of
● No wiring or distribution panels sufficient ventilation and or air-
Electric applies computer simulation, traffic a building adversely affects their should be built into or mounted on conditioning capacity must be
computation, and other techniques based on its wealth passenger-carrying efficiency. Therefore, hoistway walls. provided to assure that the
of experience in this field to offer a wide range of elevators should, as far as possible, be ● It is forbidden under most building machine-room temperature does
elevator consulting services. Given below are reference concentrated in the center of the
codes to install any conduit work or not exceed 40℃.
building.
data useful for general planning. ● When two groups of elevators face each
piping in hoistways except as ● When occupied areas of the building

required for the elevator itself. are in close proximity to the


other, ample space should be left
● Pit-depth and overhead-height machine room, such as in the case
Max. no. of floors served Recommended elevator speed between the groups.
● The number of elevators in each group dimensions must always be at least of elevators for the low and middle
should be decided on the basis of the the minimum shown in the drawings. floors of a high-rise building, it may
60 floors ● If it proves necessary to make use of
physical arrangement of the elevators be desirable to provide additional

9.0 m/sec
55 floors and the floors served. space below the pit, contact our soundproofing or intervening walls.
● As much as possible, all the floors local subcontractor.

8.0 m/sec
50 floors ● When the building is to be of steel
served by one group of elevators should

7.0 m/sec
45 floors be functionally and structurally similar. construction, our local
6.0 m/sec Dissimilarity among the floors served will subcontractor should be brought
40 floors result in a drop in service level. into the discussion at the earliest
● In residential buildings, hotels, and the possible moment.
5.0 m/sec

35 floors
like, it is not desirable for the elevator
4.0 m/sec

30 floors hall to be located farther than 50 meters


from any apartment or room.
3.5 m/sec

25 floors

● Some Examples of Bank Arrangements


3.0 m/sec

20 floors
2.5 m/sec

15 floors
Desirable Plans
m/sec
m/sec

2.0
1.75
m/sec

10 floors
1.5
1.0 m/sec

5 floors

● Selecting the Operation System


Scale of building Large-scale office building
Numb
er of Medium-scale office building
eleva
tors
Operation system 1 2 3 4 5 6 7 8

1-car selective collective (2BC) ◎

2-car selective collective (2BC) ◎


Undesirable Plans
ΣAI-22 group control system ◎

ΣAI-2200C group control system ◎ ◎ ◎ ◎ ◎

Applicable system ◎ Recommended system

3 4
三菱エレベータNexWay技術資料 07.10.5 11:55 AM ページ 5

RATED SPEED OF
RATED SPEED OF 2.0∼3.0 m/sec 2.0∼3.0 m/sec

AM (min)
● Car frame height (HB) according to car design and car depth
100-125
R1 Car frame Car designs
height (HB)
(mm) S10 S20 S30 N10 N20 N30 N40 N50 N60 N70 N80

(by owner)
Vent. fan

3450 ○ ○ ○ ○ BB≧1400 ○ ○ ○ ○

BH
3650 ○ ○

BB
BB<1400

BM (min)
Note: The dimensions HB are calculated when the ceiling height (HL) is 2300mm and without the emergency exit on ceiling.

Access door : (by owner)


Please consult our local subcontractor if required the emergency exit.

Vent. window
(by owner)
JJ
Top clearance (TC) Machine-room height (HM)

Height: 2000
● ●

Width: 1000
AA
R2 (Unit: mm) (Unit: mm)
AH

Control Control Attachment Rated speed Travel (TR) (m) Rated speed Regulation
panel panel panel
(m/sec) TR≦100 100<TR≦150 (m/sec)
EN81-1
Hoistway Wall socket
(by owner)
Power receiving box Lighting outlet Intercom (option) 2.0 1760 1910
(by owner) (by owner)
2.0
2.5 1840 1990 2.5 2500
Machine room 3.0 2190 2340
3.0

● Reaction loads in machine room and pit (Unit: kN) ● Pit-depth (PD) *2 (Unit: mm) ● Overhead-height (OH) *2 (Unit: mm)
Hoisting hook or trolley beam (by owner)
Rated Rated capacity (kg) Rated Travel Rated capacity (kg) Rated Travel Rated capacity (kg)
speed speed TR speed TR
(m/sec) 750 900 1050 1200 1350 1600 (m/sec) (m) 750 900 1050 1200 1350 1600 (m/sec) (m) 750 900 1050 1200 1350 1600
Cinder-concrete finish
TR≦100 2080

HM (min.)
R1 91 104 108 112 118 123 TR≦100 5210 (by owner)
2.0 100<TR≦120 2800
R2 59 67 68 73 74 82 2.0 100<TR≦120 5360
2.0
120<TR≦150 − 3000 3020
2.5 P1 106 116 122 130 140 154 120<TR≦150 − 5360
TR≦100 2080
P2 96 103 107 113 119 128 TR≦100 5290
2.5 100<TR≦120 2840

TC
R1 104 108 112 118 123 2.5 100<TR≦120 5440
120<TR≦150 − 3040 3060
R2 67 68 73 74 82 TR≦100 2650
120<TR≦150 − 5440
3.0 −
P1 120 125 134 144 159 TR≦100 5640

OH (min.)
3.0 100<TR≦120 − 3130
3.0 −

Entrance height:
P2 107 111 117 123 132 120<TR≦150 3330 3350 100<TR≦150 5790

HB
HH=2100
Note: The dimensions OH are calculated when the car frame height (HB) is 3450mm.

HL
● Dimension table of car, hoistway and machine room Highest
floor

Car Internal dimensions of hoistway (mm) *2 Internal dimensions of machine room (mm)
internal

Total height
In-line arrangement In-line arrangement Facing arrangement *3
Rated Rated Number Entrance dimensions

Travel(TR)
Code (mm) 1-unit 2-unit 3-unit 4-unit 1-unit 2-unit 3-unit 4-unit
speed capacity of width
installation installation installation installation 4 units 6 units 8 units
number installation installation installation installation
(m/sec) (kg) persons JJ (mm)
Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width Width Width
AA x BB AH x BH AH x BH AH x BH AH x BH AM x BM AM x BM AM x BM AM x BM AM AM AM
2.0
2.5 P 10 750 10 800 1400 x 1300 2000 x 2050 3900 x 2050 5900 x 2050 7900 x 2050 2350 x 3455 4200 x 3455 6200 x 3455 8200 x 3455 4200 6200 8200

P 12 900 12 900 1600 x 1300 2300 x 2050 4300 x 2050 6500 x 2050 8700 x 2050 2350 x 3455 4400 x 3455 6600 x 3455 8800 x 3455 4400 6600 8800 Lowest
floor
P 14 1050 14 900 1600 x 1500 2300 x 2250 4300 x 2250 6500 x 2250 8700 x 2250 2350 x 3655 4400 x 3655 6600 x 3655 8800 x 3655 4400 6600 8800
2.0

PD (min.)
2.5 P 16 1200 16 1000 1800 x 1500 2500 x 2250 4700 x 2250 7100 x 2250 9500 x 2250 2500 x 3655 4750 x 3655 7150 x 3655 9550 x 3655 4750 7150 9550
3.0
P 18 1350 18 1100 2000 x 1500 2700 x 2250 5100 x 2250 7700 x 2250 10300 x 2250 2700 x 3655 5150 x 3655 7750 x 3655 10350 x 3655 5150 7750 10350

P 21 1600 21 1100 2000 x 1700 2700 x 2450 5100 x 2450 7700 x 2450 10300 x 2450 2700 x 3855 5150 x 3855 7750 x 3855 10350 x 3855 5150 7750 10350
Notes: * 1. All the above dimensions are calculated based on EN81-1 (1998).
* 2. The dimensions PD, OH and BH are calculated when the counterweight without safety gear is located in back of the car. P1 P2
* 3. These machine room depth BM with a facing arrangement should be (2BH+3500) mm when lobby width is 3.5m.
* 4. The dimensions shown are minimum requirements, particularly in the figures of TC, OH and PD. Hoistway section
     Necessary tolerance should be separately considered for the building construction errors.
* 5. The dimensions TC, OH, PD and reaction load are calculated according to car and hoistway dimensions on the above table and conditions.

5 6
三菱エレベータNexWay技術資料 07.10.5 11:55 AM ページ 7

RATED SPEED OF
RATED SPEED OF 3.5, 4.0 m/sec 3.5, 4.0 m/sec

Vent. fan
AM (min) ● Car frame height (HB) according to car design and car depth
100-125 R1 (by owner)
Car frame Car designs
height (HB)
(mm) S10 S20 S30 N10 N20 N30 N40 N50 N60 N70 N80

Vent. window
BH

(by owner)

BB
3450 ○ ○ ○ ○ BB≧1400 ○ ○ ○ ○

3650 ○ ○

BM (min) = lobby width + 2BH


JJ BB<1400
R2
AH AA
Note: The dimensions HB are calculated when the ceiling height (HL) is 2300mm and without the emergency exit on ceiling.

(by owner)
Please consult our local subcontractor if required the emergency exit.

Lobby width:
3500-4500
Attach-
ment Attachment Control Control Control

Access door :
panel panel panel panel panel

Elevator lobby Attach-


ment
panel
Attachment
panel
Control
panel
Control
panel
Control
panel
Group
control
panel
Intercom

Height: 2000
Width: 1000
(option)

● Top clearance (TC) (Unit: mm) ● Machine-room height (HM) (Unit: mm)
Wall socket
(by owner) Rated speed Travel (TR) (m) Rated speed Regulation
Power receiving box (m/sec) TR≦100 100<TR≦120 120<TR≦150 (m/sec)
EN81-1
BH

(by owner)
Lighting outlet
(by owner) 3.5 2520 2670 3.5 2500
4.0 4.0
3070
Hoistway Machine room

● Reaction loads in machine room and pit (Unit: kN) ● Pit-depth (PD) *2 (Unit: mm) ● Overhead-height (OH) *2 (Unit: mm)
Rated Rated capacity (kg) Rated Travel Rated capacity (kg) Rated Travel Rated capacity (kg) Hoisting hook or trolly beam (by owner)
speed speed TR speed TR
(m/sec) 750 900 1050 1200 1350 1600 (m/sec) (m) 750 900 1050 1200 1350 1600 (m/sec) (m) 750 900 1050 1200 1350 1600

HM (min.)
R1 123 127 132 133 141 TR≦100 3020 TR≦100 5970 Cinder-concrete finish
3.5 − (by owner)
R2 80 79 82 90 94 3.5 100<TR≦120 − 3370 100<TR≦150 6120
3.5 −
P1 125 131 140 151 165 120<TR≦150 3570 3590 4.0 TR≦150 − 6520

P2 115 119 125 131 140 4.0 TR≦150 − 3920 Note: The dimensions OH are calculated when the car frame   
   height (HB) is 3450mm.

TC
OH (min.)
R1 127 132 133 141

R2 79 82 90 94
4.0 −
P1 128 140 151 165

HB
Entrance height:
P2 119 125 131 140

HH=2100

HL
● Dimension table of car, hoistway and machine room Highest
floor
Car Internal dimensions of hoistway (mm) *2 Internal dimensions of machine room (mm)
internal
In-line arrangement In-line arrangement Facing arrangement *3
dimensions

Total height
Rated Rated Number Entrance
Code (mm) 2-unit 3-unit 4-unit 2-unit 3-unit 4-unit
speed capacity of width 4 units 6 units 8 units

Travel (TR)
number installation installation installation installation installation installation
(m/sec) (kg) persons JJ (mm)
Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width Width Width
AA x BB AH x BH AH x BH AH x BH AM x BM AM x BM AM x BM AM AM AM

3.5 P 12 900 12 900 1600 x 1300 4400 x 2100 6650 x 2100 8900 x 2100 4500 x 3455 6750 x 3455 9000 x 3455 4500 6750 9000 Lowest
floor
P 14 1050 14 900 1600 x 1500 4400 x 2300 6650 x 2300 8900 x 2300 4500 x 3655 6750 x 3655 9000 x 3655 4500 6750 9000

PD (min.)
3.5 P 16 1200 16 1000 1800 x 1500 4800 x 2300 7250 x 2300 9700 x 2300 4800 x 3655 7250 x 3655 9700 x 3655 4800 7250 9700
4.0
P 18 1350 18 1100 2000 x 1500 5200 x 2300 7850 x 2300 10500 x 2300 5200 x 3655 7850 x 3655 10500 x 3655 5200 7850 10500

P 21 1600 21 1100 2000 x 1700 5200 x 2500 7850 x 2500 10500 x 2500 5200 x 3855 7850 x 3855 10500 x 3855 5200 7850 10500
P2 P1 P1 P2
Notes: * 1. All the above dimensions are calculated based on EN81-1 (1998).
* 2. The dimensions PD, OH and BH are calculated when the counterweight without safety gear is located in back of the car.
* 3. These machine room depth BM with a facing arrangement should be (2BH+3500) mm when lobby width is 3.5m.
* 4. The dimensions shown are minimum requirements, particularly in the figures of TC, OH and PD. Hoistway section
     Necessary tolerance should be separately considered for the building construction errors.
* 5. The dimensions TC, OH, PD and reaction load are calculated according to car and hoistway dimensions on the above table and conditions.

7 8
三菱エレベータNexWay技術資料 07.10.24 2:13 PM ページ 9

RATED SPEED OF
RATED SPEED OF 5.0 m/sec 5.0 m/sec

AM (min)
● Car frame height (HB) dimensions according to car design and car depth
100-125
R1
Car frame Car designs
height (HB)
(mm) S10 S20 S30 N10 N20 N30 N40 N50 N60 N70 N80

Vent. window
BH
BB

(by owner)
3600 ○ ○ ○ ○ ○ ○ ○ ○ ○

BM (min) = lobby width + 2BH


4000 ○ ○
JJ
R2
AH AA Group control panel Note: The dimensions HB are calculated when the ceiling height (HC) is 2300mm and without the emergency exit on ceiling.

Width: 1600 or 1900


Please consult our local subcontractor if required the emergency exit.

Lobby width:
Intercom (option)

3500-4500
Reactor Control Reactor Control Reactor Control
panel panel panel panel panel panel
Distribution

Access door
Elevator lobby

(by owner):
panel

Height: 2000
Reactor Control Reactor Control Reactor Control Distribution
panel panel panel panel panel panel panel

Wall socket
(by owner) ● Top clearance (TC) dimensions (Unit: mm) ● Machine-room height (HM) (Unit: mm)

Power receiving box


Rated speed Travel (TR) (m) Rated speed Regulation
(by owner)
(m/sec) TR≦150 150<TR≦200 (m/sec)
EN81-1
BH

Lighting outlet
(by owner)
5.0 3200 3600 5.0 2500

Hoistway Machine room

● Reaction loads in machine room and pit (Unit: kN) ● Pit-depth (PD) dimensions (Unit: mm) ● Overhead-height (OH) dimensions (Unit: mm)

Rated capacity (kg) Rated capacity (kg) Rated capacity (kg) Hoisting hook or trolly beam (by owner)
Rated Rated Travel Rated Travel
speed 1800 speed TR speed TR
(m/sec) 1200 1350 1600 (m/sec) (m) 1200 1350 1600 1800 (m/sec) (m) 1200 1350 1600 1800

HM (min.)
TR≦150 150<TR≦120 Cinder-concrete finish
(by owner)
R1 175 180 185 190 225 TR≦150 3950 TR≦150 6800
5.0 5.0
R2 125 130 135 145 155 150<TR≦120 4250 150<TR≦200 7200
5.0
P1 210 220 230 255 260 Note: The dimensions OH are calculated when the car frame
height (HB) is 3600mm.

TC
OH (min.)
P2 195 200 210 230 235

● Dimension table of car, hoistway and machine room

HB
Entrance height:
Car Internal dimensions of hoistway (mm) *2 Internal dimensions of machine room (mm)
dimensions

HH=2100
In-line arrangement In-line arrangement Facing arrangement *3

HL
(mm)
Rated Number Entrance
Code 2-unit 3-unit 4-unit 2-unit 3-unit 4-unit Highest
capacity of width Interior 4 units 6 units 8 units floor
number installation installation installation installation installation installation
(kg) persons JJ (mm)
Rated Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width Width Width
speed AA x BB AH x BH AH x BH AH x BH AM x BM AM x BM AM x BM AM AM AM

Total height
(m/sec)

Travel (TR)
P 16 1200 16 1000 1800 x 1500 5100 x 2350 7700 x 2350 10300 x 2350 5500 x 3850 8100 x 3850 10700 x 3850 5500 8100 10700

P 18 1350 18 1100 2000 x 1500 5500 x 2350 8300 x 2350 11100 x 2350 5700 x 3850 8500 x 3850 11300 x 3850 5700 8500 11300

P 21 1600 21 1100 2000 x 1700 5500 x 2550 8300 x 2550 11100 x 2550 5700 x 4050 8500 x 4050 11300 x 3850 5700 8500 11300
Lowest
P 24 1800 24 1100 2100 x 1800 5700 x 2700 8600 x 2700 11500 x 2700 5800 x 4200 8700 x 4200 11600 x 4200 5800 8700 11600 floor
Notes: * 1 All the above dimensions are calculated based on EN81-1 code (1998).

PD (min.)
* 2 The dimensions BH are calculated when the counterweight is equipped without safety gear.
* 3 These are the machine room width dimensions with a facing arrangement and a lobby width of 3.5m.
* 4 The dimensions shown are minimum requirements, particularly in the figures of TC, OH and PD.
Necessary tolerance should be separately considered for the building construction errors.
* 5 TC, OH, PD and reaction load are calculated according to car and hoistway dimensions on the above table.
(When the counterweight is back drop.) P2 P1 P1 P2
* 6 The shaft independently housing a single car is not recommended because noise increases.
Please consult our local subcontractor if the shaft of that kind is required.
Hoistway section

9 10
三菱エレベータNexWay技術資料 07.10.24 2:13 PM ページ 11

RATED SPEED OF
RATED SPEED OF 6.0 m/sec 6.0 m/sec

AM (min)
● Car frame height (HB) dimensions according to car design and car depth
100-125
R1
Car frame Car designs
height (HB)
(mm) S10 S20 S30 N10 N20 N30 N40 N50 N60 N70 N80

BH

Vent. window
BB

(by owner)
3600 ○ ○ ○ ○ ○ ○ ○ ○ ○

BM (min) = lobby width + 2BH


4000 ○ ○
JJ
R2
AH AA Group control panel Note: The dimensions HB are calculated when the ceiling height (HC) is 2300mm and without the emergency exit on ceiling.

Width: 1600 or 1900


Please consult our local subcontractor if required the emergency exit.

Lobby width:
Intercom (option)

3500-4500
Reactor Control Reactor Control Reactor Control
panel panel panel panel panel panel
Distribution

Access door
Elevator lobby

(by owner):

Height: 2000
panel
Reactor Control Reactor Control Reactor Control Distribution
panel panel panel panel panel panel panel

Wall socket
(by owner) ● Top clearance (TC) dimensions (Unit: mm) ● Machine-room height (HM) (Unit: mm)

Power receiving box


Rated speed Travel (TR) (m) Rated speed Regulation
(by owner)
(m/sec) (m/sec)
BH

Lighting outlet TR≦150 150<TR≦200 EN81-1


(by owner)
6.0 3200 3600 6.0 2500

Hoistway Machine room

● Reaction loads in machine room and pit (Unit: kN) ● Pit-depth (PD) dimensions (Unit: mm) ● Overhead-height (OH) dimensions (Unit: mm)

Rated capacity (kg) Rated capacity (kg) Rated capacity (kg) Hoisting hook or trolly beam (by owner)
Rated Rated Travel Rated Travel
speed 1800 speed TR speed TR
(m/sec) 1200 1350 1600 (m/sec) (m) 1200 1350 1600 1800 (m/sec) (m) 1200 1350 1600 1800

HM (min.)
TR≦150 150<TR≦120 Cinder-concrete finish
(by owner)
R1 175 180 185 190 225 TR≦150 3950 TR≦150 6800
6.0 6.0
R2 125 130 135 145 155 150<TR≦120 4250 150<TR≦200 7200
6.0
P1 210 220 230 255 260 Note: The dimensions OH are calculated when the car frame
height (HB) is 3600mm.

TC
OH (min.)
P2 195 200 210 230 235

● Dimension table of car, hoistway and machine room

HB
Entrance height:
Car Internal dimensions of hoistway (mm) *2 Internal dimensions of machine room (mm)
dimensions

HH=2100
In-line arrangement In-line arrangement Facing arrangement *3

HL
(mm)
Rated Number Entrance
Code 2-unit 3-unit 4-unit 2-unit 3-unit 4-unit Highest
capacity of width Interior 4 units 6 units 8 units floor
number installation installation installation installation installation installation
(kg) persons JJ (mm)
Rated Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width x Depth Width Width Width
speed AA x BB AH x BH AH x BH AH x BH AM x BM AM x BM AM x BM AM AM AM

Total height
(m/sec)

Travel (TR)
P 16 1200 16 1000 1800 x 1500 5100 x 2350 7700 x 2350 10300 x 2350 5500 x 3850 8100 x 3850 10700 x 3850 5500 8100 10700

P 18 1350 18 1100 2000 x 1500 5500 x 2350 8300 x 2350 11100 x 2350 5700 x 3850 8500 x 3850 11300 x 3850 5700 8500 11300

P 21 1600 21 1100 2000 x 1700 5500 x 2550 8300 x 2550 11100 x 2550 5700 x 4050 8500 x 4050 11300 x 3850 5700 8500 11300
Lowest
P 24 1800 24 1100 2100 x 1800 5700 x 2700 8600 x 2700 11500 x 2700 5800 x 4200 8700 x 4200 11600 x 4200 5800 8700 11600 floor
Notes: * 1 All the above dimensions are calculated based on EN81-1 code (1998).

PD (min.)
* 2 The dimensions BH are calculated when the counterweight is equipped without safety gear.
* 3 These are the machine room width dimensions with a facing arrangement and a lobby width of 3.5m.
* 4 The dimensions shown are minimum requirements, particularly in the figures of TC, OH and PD.
Necessary tolerance should be separately considered for the building construction errors.
* 5 TC, OH, PD and reaction load are calculated according to car and hoistway dimensions on the above table.
(When the counterweight is back drop.) P2 P1 P1 P2
* 6 The shaft independently housing a single car is not recommended because noise increases.
Please consult our local subcontractor if the shaft of that kind is required.
Hoistway section

11 12
三菱エレベータNexWay技術資料 07.10.5 11:55 AM ページ 13

ENTRANCE LAYOUT
ENTRANCE LAYOUT DRAWINGS DRAWINGS

Type E-102 (standard) Type E-302, E-312 (option)

Door plan (section B-B)

Hoistway entrance

Door elevation
(section A-A)
Building structure Building structure
(by owner) (by owner)

Note: 1. Triangular key-hole is required under EN81-1. Note: 1. Triangular key-hole is required under EN81-1.
Wall and floor finishing 2. Details in sections A-A and B-B are not for Wall and floor finishing 2. Details in sections A-A and B-B are not for
(by owner) BS-476 fire rated doors. (by owner) BS-476 fire rated doors.

13 14
三菱エレベータNexWay技術資料 07.10.5 3:40 PM ページ 15

ELECTRICAL
ELECTRICAL INSTALLATION INSTALLATION

● Power Feeder Data *1 Table 1


Feeder Size Calculation
Speed Rated load Traction motor Current at 400V *2 Capacity of NF in M/R Heat ● The feeder size must be selected to withstand Feeder size Coefficient Feeder size Coefficient
(m/sec) (kg) (kW) power supply at 400V system emission (mm2) K (mm2) K
FLU (A) FLAcc (A) (kVA) (A) (W)
continuous flow of the following current at an
3.5 5.1 60 87.3
750 15 27 52 16 75 2330 ambient temperature of 40°C. 5.5 8.0 80 115
31 56 18 75 2800
900 15
19 75 3260
1.25 x FLU(A)……………In case of FLU ≦ 50 (A) 8 11.6 100 148
1050 15 33 61
14 20.6 125 184
1150 15 37 64 21 75 3570 1.10 x FLU(A)……………In case of FLU > 50 (A)
1200 20 37 67 21 75 3730 22 32.1 150 225
1350 20 41 72 23 75 4190 The wire length per feeder size must be calculated 30 42.5 200 287
2.0 82 26 75 4970 38 54.3 250 371
1600 20 47 with the following formula.
1800 23 57 98 31 100 5600 50 70.7 325 473
2000 28 59 107 33 100 6210 L ≦ K x E/FLAcc
2250 28 66 115 36 100 7000
Where, FLU: Full load up current (A) at E volts
2500
3000
37
37
73
86
129
146
39
46
100
125
7800
9400 FLAcc: Full load accelerating current (A) at E volts
Table 2
750 18 31 64 18 75 2910 No. of Diversity factor
900 18 36 69 20 75 3490 L: Wire length (m) elevators
1050 18 39 75 21 75 4070 on common For FLU For FLAcc
18 43 79 23 75 4460
K: Coefficient (Please see Table 1.)
1150 feeder Without express zone With express zone
1200 25 44 82 23 75 4660 E: Power supply voltage (V) 2 2.0 1.7 1.85
1350 25 48 88 25 75 5240
2.5 56 100 29 100 6210 ● In case of feeding power to a group of elevators 3 2.7 2.4 2.7
1600 25
1800 28 67 121 34 100 7000 4 3.1 2.95 3.4
35 70 134 37 100 7800
through a common feeder, the capacity of the power 5 3.25 3.6 4.2
2000
2250 35 79 141 40 125 8800 supply transformer, the feeder size, and the ampere 6 3.3 4.1 4.9
2500 47 87 159 43 125 9700 7 3.71 4.6 5.6
3000 47 103 179 51 150 11700 rating of the no-fuse (NF) breaker are determined 8 4.08 5.1 6.3
750 22 34 74 19 75 3490 through multiplying by the following diversity factor. 9 4.45 5.6 6.9
900 22 39 81 21 75 4190
10 4.8 6.0 7.6
1050 22 45 90 23 75 4890 (Refer to Table 2.)
1150 22 48 94 25 75 5350
1200 30 50 98 25 100 5590
1350 30 56 105 28 100 6280
3.0 1600 30 65 119 32 100 7450
1800 34 76 143 40 125 8400
2000 42 81 163 42 125 9400
2250 42 91 170 46 150 10500
2500 56 101 186 50 150 11700
3000 56 120 209 59 175 14000
750 25 40 97 21 75 4070
900 25 44 99 23 75 4890
1050 25 51 113 27 100 5700
1150 25 55 117 29 100 6240
1200 35 57 124 30 100 6520
1350 35 63 131 33 100 7330
3.5 1600 35 74 144 37 125 8690
1800 39 92 174 46 125 9800
2000 49 94 197 47 150 10860
2250 49 102 212 52 150 12210
2500 65 112 228 57 175 13570
3000 65 134 262 67 200 16280
750 29 44 110 23 75 4660
900 29 49 112 26 100 5590
1050 29 57 123 30 100 6520
1150 29 61 128 31 100 7140
1200 40 64 135 33 125 7450
1350 40 71 143 36 125 8380
4.0 1600 40 83 165 41 150 9930
1800 45 102 196 49 150 11200
2000 56 104 231 51 150 12410
2250 56 113 249 56 175 13960
2500 74 125 267 61 175 15510
3000 74 148 305 72 225 18610
1200 42 80 196 41 125 9400
1350 42 88 211 44 125 10500
5.0 1600 50 103 238 50 150 12500
1800 53 114 253 57 175 14000
1200 56 92 237 46 150 11200
1350 56 102 252 50 150 12600
6.0 1600 56 120 284 59 175 14900
1800 63 133 304 65 200 16800
1200 65 103 290 55 150 13100
7.0 1350 65 114 321 58 175 14700
1600 65 137 382 68 200 17400
1200 74 118 351 66 175 14900
8.0 1350 74 130 369 70 200 16800
1600 74 154 440 80 225 19900
1200 83 127 399 76 200 16800
9.0 1350 83 142 418 79 200 18900
1600 83 171 499 90 250 22400

Notes: * 1. The values in the table above are for the case where power supply voltage is 400V. If the power supply voltage is within
the range of 380 to 440V (except for 400V), calculate values by referring to page 16. If the power supply voltage is not within
the range of 380 to 440V, please consult our local subcontractor.
* 2. If the power supply voltage is other than 400V, the FLU and FLAcc current vary inversely with power supply voltage as follows.
(Current at E volts) = (Current at 400 volts) x (400 / E) where, E: power supply voltage

15 16
三菱エレベータNexWay技術資料 07.10.5 11:55 AM ページ 17

ELECTRICAL
ELECTRICAL INSTALLATION INSTALLATION NOTES ON INSTALLATION PLANNING

● Electrical Equipment Required for Elevator Operation Elevator Site Requirements ● All other work related to building construction.
● The temperature of the machine room shall be below
● The machine-room power-receiving panel and the
40°C. electrical wiring for illumination, plus the power from
● The following conditions are required for maintaining
it to the electrical room.
● The laying of conduit and wiring between the elevator
NF breaker *2 elevators performance:
a. The relative humidity shall be below 90% on a pit and the terminating point for the emergency bell,
monthly average and below 95% on a daily intercom, etc.
● The power consumed in installation work and test
Ground wire *1 average.
b. The machine room and the elevator hoistway operation.
● All the necessary building materials for grouting in of
shall be free of dust or harmful gas.
● The walls, floors and ceiling of the machine room
brackets, bolts, etc.
● The provision and subsequent alteration as required,
shall be finished with mortar or other materials so as
to prevent concrete dust. and eventual removal of the scaffolding as required
by the elevator contractor, and any protection of the
work as may be required during progress.
Work Not Included in Elevator Contract ● The provision of a suitable locked space for the

The following items are not a part of elevator storage of elevator equipment and tools during
installation work, and are the responsibility of the elevator installation.
building owner or general contractor.

Notes: *1. The minimum size of ground wire is determined according to the ampere
● Construction of the elevator machine room with
Ordering Information
proper beams and slabs, equipped with a lock,
rating of the NF breaker installed at the power source side. Please include the following information when ordering
*2. The ampere rating of the power-source NF breaker should be of one step complete with illumination, ventilation and
or requesting estimates.
larger than of the receiving-box NF breaker installed in the elevator waterproofing.
● The desired number of units, speed, and loading
machine room. ● Access to the elevator machine room sufficient to
capacity.
allow passage of the control panel and traction
● The number of stops or number of floors to be
machine.
served.
Traction-Machinery Power Supply Intercom (where necessary) Suspension hook facilities and ladders in the
● The total elevator travel and floor-to-floor height.

It is necessary to install power-supply equipment of This is essential to establish the communication machine room.
● Operation system.
● Finishing of the machine-room floor and the walls
sufficient capacity to ensure the elevators accelerating between elevator passengers and outside in case of ● Selected car design and size.

smoothly and landing accurately. emergency. and floors in the vicinity of the entrance hall after
● Entrance design.

The power supply should be kept within a voltage- The master station transceiver is usually in a location completion of the installation.
● Signal equipment.
● Construction of an illuminated, ventilated and water-
fluctuation range of +5 ~ -10%, and a voltage- readily accessible to the supervisor, in the central ● A sketch of part of the building where the elevators

imbalance factor of 5%. supervisor's room or elevator lobby. The wiring work proofed elevator hoistway.
are to be installed.
● A ladder to the elevator pit.
When selecting protective breakers on the power- between the master station and the elevator machine ● The voltage, phase and frequency of power source
● Provision for the cutting of the necessary holes and
supply side, be guided by voltage ratings of the no- room is not included in the elevator contract. for the motor and lighting.
fuse breakers supplied with the elevators. To facilitate piping and wiring, it is desirable to decide joists and for making good thereafter as required.
● Separate beams, when the hoistway dimensions
on the position of the master station at the earliest
Power Supply for Lighting stage of building design. markedly exceed the specifications, and intermediate
beams when two or more elevators are installed.
Lighting for the elevator cars and indicators, where
possible, should be supplied via a separate circuit that Lighting Equipment
will not be affected by power failures elsewhere. The machine room should be fitted with good lighting
for maintenance work. The light switch should be ● Saving energy and space

Ventilation Equipment positioned close to the machine-room entrance.



High-efficiency transport mechanism
Environment-conscious industrial
waste treatment ● Comfortable, quiet ride
Smooth door operation
A machine-room ventilation device having a sufficient

● Welfare-awareness / Universal design

capacity to keep the room temperature below 40°C is Inspection Power Outlets ● Riding and boarding safety
Safety in emergencies
required. These should be installed in the machine room and pit

● High reliability
● Safe service spots

A ventilation window should also be installed at the for use during inspection and maintenance.
opposite side of ventilation fan.

17 18