IS-Limiter
IS-Limiter
IS-limiter
The world’s fastest
switching device
„ Reduces substation cost
„ Solves short-circuit problems
in new substations and substation extensions
„ Optimum solution for interconnection of
switchboards and substations
„ In most cases the only technical solution
„ Tried and tested in thousands of installations
„ Worldwide in service
„ The peak short-circuit current will never be
reached
„ The short-circuit current is limited
at the very first current rise
© ABB AG -2-

- 6549 E 24-02-05 -
IS-Limiter
IS-limiter
Link between
in-plant generation The world’s fastest
and switching device
public systems
© ABB AG -3-

- 6550 E 24-02-05 -
IS-Limiter
Technical Data
Rated voltage Rated current Interrupting
current (RMS)

„ 0.75 kV, ...5000 A, ...140 kA


„ 12 kV, ...4000 A, ...210 kA
„ 17.5 kV, ...4000 A, ...210 kA
„ 24 kV, ...3000 A, ...140 kA
„ 36 kV, ...2500 A, ...140 kA
„ 40.5 kV, ...2500 A, ...140 kA

For higher rated currents


IS-limiters can be connected in parallel.
© ABB AG -4-

- 6554 E 24-02-05 -
IS-Limiter
Insert holder and insert

Current path uninfluenced Current commutated to fuse


© ABB AG -5-

- 6553 E 24-02-05 -
IS-Limiter
Breaking of a short-circuit current by IS-limiter

i=i1+ i2 without
IS-limiter

CB
i=i1+ i2
with IS-limiter
IS-limiter

Single line diagram of a busbar system Current curve i=i1+ i2


with IS-limiter at the short-circuit location
© ABB AG -6-

- 6552 E 24-02-05 -
IS-Limiter
IS-limiter
installed in bus-tie
Advantages:
„ Improving power quality,
„ Increasing the reliability of the system,
IS-limiter „ Reduction of the network-impedance,
„ Optimal load flow,
„ Existing busbar system has not to be changed.
© ABB AG -7-

- 6555 E 24-02-05 -
IS-Limiter
IS-limiter in generator feeder
Advantages:
„ Generator can be connected independent on
the short-circuit capability of the system,
„ Existing busbar system has not to be changed,
„ No need of expensive generator breaker.
© ABB AG -8-

- 6556 E 24-02-05 -
IS-Limiter
IS-limiter for connection of a
IS-limiter in the bus-tie generator
with current-direction
comparison to a fully loaded system
Advantages:
„ Private / industrial generator feeder can be
Tripping of IS-limiter
connected to the (fully loaded) grid,
No Tripping of IS-limiter
„ Selective tripping of the IS-limiter (IS-limiter will
operate only for short-circuit faults in the grid)
© ABB AG -9-

- 6557 E 24-02-05 -
IS-Limiter
IS-limiter in parallel with
reactor
Advantages:
„ Avoid coppers losses of the reactor,
„ Avoid voltage drop of the reactor,
„ No electro-magnetical field on the reactor

Outgoing feeders
© ABB AG -10-

- 6558 E 24-02-05 -