Clearly, today’s dynamic signal sensors are not The ICP® transducer power supply is
directly usable, or infrastructure friendly without implemented as a software programmable power
some sort of dynamic signal analyzer, or PC supply in order to accommodate IEEE P1451.4(1)
analyzer involved. Direct connection to a reverse bias transducer interface requirements.
Programmable Loop Controller (PLC) or other ICP® transducer bias monitoring is preformed in
commonly available plant floor controller is not the analog domain so as to permit long term
an option due to the typical dynamic signal monitoring of sensor health.
bandwidths and processing involved. Some
implementations of 4-20 milliamps proportional
to overall level are just now becoming available 24 bit Sigma-Delta converters perform the analog
however. to digital conversion. All converters operate in a
synchronous fashion. While most simple
applications do not demand it, the sample rate is
software programmable between 1 and 96 KHz.
REQUIREMENTS This wide dynamic range eliminates the need for
any sort of programmable gain in most
What is required in order to effectively deploy manufacturing applications, requiring only that
dynamic signal solutions to the production floor the sensitivity of the sensor be carefully selected.
on a more cost-effective basis is either smarter
sensors, or smarter signal conditioning. The
general requirements of this signal conditioning The core of digital signal processing capability of
are as follows: the signal conditioner is a floating point
programmable Digital Signal Processor (DSP).
a.) NEMA 4, no fans or special cooling The DSP is low-power floating-point unit and is
b.) 24 VDC power w/noise rejection programmable in C, C++, and utilizing 3rd party
c.) 1-4 ICP® dynamic sensor support packages in MATLAB® Simulink®. Program
d.) IEEE 1451 smart sensor support memory is an 8-megabyte FLASH memory, to
e.) Flexible communications options allow signal-conditioning algorithms to be
f.) Integral computational capability developed, stored, and executed upon power up
g.) Dynamic range matching sensor of the unit. A significant portion of the FLASH
h.) Onboard “results” memory memory may be utilized for long-term results
i.) Some digital input / outputs storage. Data storage memory consists of 16-32
j.) Some quasi-static signal ability megabytes of dynamic ram. Putting this in
k.) Flexible signal output expansion perspective, this is enough memory to buffer
approximately 5 minutes worth of time history at
a 5000 Hz bandwidth.
ARCHITECTURE
The architecture chosen to meet the above- Serial communications, slow speed analog input /
mentioned requirements is shown in block output and optically isolated digital input / output
diagram form in Figure 1. The package chosen to are handled by a separate communications
meet the requirements is shown in Figure 2. processor. This processor also can act as a
watchdog processor and affect a total reset if
necessary. This processor also contains
The fundamental design is single board in nature. sufficient resources to communicate with through
The sealed NEMA 4 rated unit is designed to an IEEE 1451.2 interface to a Network Capable
operate without fans or special cooling up to and Applications Processor (NCAP(2,3) ) with onboard
beyond 50 degrees C. Total power consumption IP address and HTTP server.
is less than 4 Watts, greatly simplifying
packaging. DC power at 24 volts was chosen as Additional high and low speed input / output
the nominal supply since it is quite readily design flexibility has been provided in the core
available in a plant-manufacturing environment. design to allow multi-board synchronization, high
band-width network communications daughter- detection methodologies and fault detection
boards and wireless networking communications strategies.
support. External battery back up, a battery
backed real-time clock and power fail support
was also integrated into the signal conditioner to It was quickly realized that no absolute time or
facilitate deployment under harsh and relatively frequency domain limit checking routine would
unpredictable conditions. suffice, but rather combinatorial time and
frequency domain distributions must be learned,
adapted and trended over time in order to
determine what was “normal” and what was
CASE HISTORY “abnormal” or fault criteria. This normal
distribution must be learned as a function of part
The Modal Shop was approached by a group of strikes, or “hits” and stored for up to 10,000
manufacturing engineers associated with Ford cycles. It was also quickly determined that a key
Motor manufacturing operations. Their goal was to reliable fault detection was to strictly
to create a simple, stand-alone, robust, reliable differentiate between cutting operations and non-
and readily deployable transfer line spindle- cutting operations. Generally speaking, you can
monitoring device. The device was to be used on expect cutting operations to display smoothly
critical machining operations in a production cyclical vibration increases as a function of tool
environment. The device was intended to be able wear, dropping at tool change time. One can also
to detect nothing more than the fact that expect non-cutting operation signatures to remain
something significant is different, and light a relatively flat over the life of a spindle. The
light to say “hey, come look at me ”. The goal attached figures and data plots, all of which are a
was not to diagnose the fault, but to provide an function of part strikes clearly indicate when fault
operator or process engineer with an indication of conditions are present.
whether the fault was machining related or not.
The types of problems to be detected were
bearing failures, and a host of machining related Sixteen critical machines were selected from a
problems such as loose, broken, or missing tool Ford Engine Plant, and data was collected for
inserts. over 6 million machining “hits” and analyzed
against the original fault criterion for robustness
and reliability. The resulting algorithms were
Analysis of other monitoring devices and systems coded and proven first on a PC utilizing stored
revealed that there were either too many sensors, disk time histories, and then ported to the DSP
or they were too hard to setup and required inside the signal conditioner, and verified by
extensive tweaking. Therefore one of the goals playing the digitized time histories into the signal
was to use a single spindle mounted vibration conditioner.
sensor. Setup and configuration of the device
was to be as automatic as possible, and
installation require no more than a skilled trades It was originally envisioned that the device would
worker. Connections were to require no more merely light a light when a fault was detected,
than sensor and power. Configuration of the and the fault light would be manually reset. It
device should require no more than an was quickly recognized that there was advantage
approximation of cycle time, teaching it what to connecting the box directly to the local PLC
signatures of non-rotating, and idling spindles for process feedback. It was also recognized that
were. there was also advantage to providing operations
personnel with the ability to “look back” at
operational vibration data as a function of “hit” or
In a 2 year case by case study the approach to part processed.
generation of the signal-conditioning algorithm
was to use actual plant data as much as possible
rather than manufactured laboratory data. Actual Figures 3 through 6 are derived from actual
operating time histories of accelerometer sensed operating plant vibration data, and are
vibration data was collected on more than 250 representative of the type of information
machines throughout the organization. These generated and stored in the signal conditioner.
time histories were used to formulate cycle
TEDS,
ICP® BNC
Monitor
Out
3.3V
Digital
IEEE Micro Converter
1451.2 4 Latched Input Filter
Outputs Tacho / Short
Measurement +5 V
2 Inputs Term Analog
Backup
5v Analog RS232
4 x 12 Bit In & Radio 20 V
2 x 12 Bit Out Optical Isolation ICP®
24v
ACKNOWLEGMENT REFERENCES
The authors would like to thank the Ford Engine [1] IEEE P1451.4 Proposed Standard for Mixed-
Manufacturing plant staff and the Manufacturing mode Communication Protocols and Transducer
Noise and Vibration staff for their support in the Electronic Data Sheet (TEDS) Formats
initial deployment of this Smart Signal
Conditioner application. The authors would also [2] IEEE 1451.1-1999 Standard for a Smart
like to thank R.A. Simpson and associates for Transducer Interface for Sensors and Actuators -
their support in the human interface graphics and Network Capable Application Processor (NCAP)
display presentation formatting. Information Model