APPLICATION CHARTS

What Type and Gauge of Wire Should I Use?

Type NM-B (Indoor Applications)

Application Gauge/Conductor

Grounded Receptacles 12/2 w/Ground

Wall Light Switches 12/2 w/Ground

3-Way Light Switches 12/3 w/Ground

Lighting Fixtures 14/2 w/Ground

Lighting Fixtures w/ Outlets 12/2 w/Ground

Combination Switch and Receptacle 12/2 w/Ground

Lighted Medicine Cabinet 14/2 w/Ground

Exhaust Fan 12/2 w/Ground

Electric Wall Heater (Up to 1650 Watts at 120V) 12/2 w/Ground

Electric Wall Heater (Over to 1650 Watts at 120V) 10/2 w/Ground

Workshop Power Tools 12/2 w/Ground

Large A/C Over 20 amps 10/3 w/Ground

Room A/C 12/2 w/Ground

Built-In Single Ovens (Up to 30 amps ) 10/3 w/Ground

Built-In Double Ovens (Up to 50 amps ) 6/3 w/Ground

Apartment Size Range (Up to 30 amps) 10/3 w/Ground

Double Oven Range (Up to 45 amps) 8/3 w/Ground

Double Oven Range (Up to 60 amps) 6/3 w/Ground

Dishwashers 12/2 w/Ground

Disposals (Must have toggle switch at the unit) 12/2 w/Ground

Food Freezer (On separate circuit) 12/2 w/Ground

Electric Dryer (Up to 30 amps) 10/3 w/Ground

Other Major Appliances 10/3 w/Ground

Cerro Wire L L C • www.cerrowire.com


1099 Thompson Road, SE • Hartselle, AL 35640 • Phone 256.773.2522 • Fax 256.773.5849
APPLICATION CHARTS

What Type and Gauge of Wire Should I Use?

Type UF-B (Outdoor Applications)

Application Gauge/Conductor

Swimming Pool Filters and Pumps 12/2 w/Ground

Outdoor Post Lights 14/2 w/Ground

Patio Spot Lights 12/2 w/Ground

Dusk to Dawn Lights 12/2 w/Ground

Patio-Pool Water Proof Receptacles 12/2 w/Ground

Switches and Grid Receptacles 12/2 w/Ground

Size and Amp Ratings

NM, TW and UF Wire SER Cable

14 AWG - 15 AMPS 8 AWG - 50 AMPS

12 AWG - 20 AMPS 6 AWG - 65 AMPS

10 AWG - 30 AMPS 4 AWG - 100 AMPS

8 AWG - 40 AMPS 2 AWG - 125 AMPS

6 AWG - 55 AMPS 1 AWG - 150 AMPS

All wire must be fused according to amp. Rating ampacities are based on
NEC® Table 310-16.

WARNING! Installation of electrical wire can be hazardous, if done


improperly, can result in personal injury or property damage. For safe
wiring practices, consult the National Electrical Code® and your local
building inspector.

Cerro Wire L L C • www.cerrowire.com


1099 Thompson Road, SE • Hartselle, AL 35640 • Phone 256.773.2522 • Fax 256.773.5849
APPLICATION CHARTS

What Type of Wire Do I Need?

Type Construction Applications

Non-Metallic • Smooth plastic jacket For general wiring of homes, farm


Sheathed Cable • THHN insulated buildings, stores and shops. It is flame
conductors and moisture resistant, but should not
• 2 or 3 conductors with be used in wet locations.
or without ground

Underground Feeder • Plastic jacket and plastic Direct burial in the earth as feeder or
Cable insulation branch circuit cable. Indoor or outdoor
• 2 or 3 conductors with wiring, where subject to damp or corrosive
or without ground conditions. Inside hollow brick, tile or
masonry walls. Barns when acids, fungus,
alkalis or moisture are present.

Service Entrance Cable • For neutral (third wire) May be used without conduit from pole
twist bare strands that are to building and down the side of building
wrapped around insulated where not subject to mechanical injury.
conductors Use as service entrance cable.
• Available with either
copper or aluminum
conductors

XLP-USE Underground • Flame and moisture Suitable for direct burial in the earth as
Service Cable resistant a service entrance cable, feeder or
• Available with either branch circuit cable at 75°C service. Can
copper or aluminum also be used in conduit or duct, in wet
conductors or dry locations.

Triplexed Secondary • Polyethylene covered Used for secondary distribution and


UD Cable aluminum phase underground service at 600 Volts or less.
conductors

90°C Small Diameter • Nylon jacket over PVC 600 Volts building wire, suitable for new
Building Wire insulation work and in re-wiring of existing raceways.
• Type-2 8 AWG and larger Use in conduit, duct or EMT. THHN rated
75°C in wet location, 90°C. THWN-2
rated 90°C wet/dry locations. See code
ampacity for size.

Bare Copper Wire • Soft drawn annealed For grounding services.


copper
• Solid and stranded
• Large range of sizes

Submersible • Pump-Cable Twisted Used within well casing for wiring


Pump-Cable Twisted • Fully annealed solid copper submersible pump units. Temperature
• Moisture resistant range -20°C to 75°C. Voltage rating 600
conductors Volts.
• Twisted assembly
• UL listed, type THW