HAVA KANALLARINDAKİ SES SEVİYESİNİN TESBİTİ

KANALLARDA

Lw=10+50logV+10logA (dB)
V=Kanaldaki Hava Hızı (m/s)
A=Kanal Kesiti (m2)

a (cm) b (cm) A (m2) V (m/s) Lw (dB)


20 30 0.06 5 32.73

DİRSEK+T+ÇAPRAZ PARCALAR

Ld,t,çp=Lwx1,35 Ld,t,çp (dB)


44.19

Lameli Izgaralar,Köprülü Izgaralar,Hava Dağıtıcıları ve Menfezlerde SES

Lw=10+10logS+30logƒ+60logV (dB) S ƒ V Lw
S=Kesit (m2) 0.48 0.08 2.5 22.16
ƒ=Direnç Degeri=2∆P/(ρV2) a (mm) b (mm) Dh (mm) έ V (m/s), Re ƒ" ƒ
V=Çıkış Hızı m/s 800 600 685.71 0.15 2.5 113828.57 0.08 0.08
Veya έ
Lw=17+30log∆P+10logS PVC Borular 0.01
έ=Kanal Pürüzlülük Katsayısı (Galvaniz=0,15) Sac Kanallar 0.15
Beton Kanallar Pürüzsüz 0.5
Beton Kanallar Pürüzlü 1,0-3,0
Flxıbl Borular 0,2-0,3

VANTİLATÖRLERDE SES DÜŞÜMÜ

Lw=5+10logQ+20log∆P
Q=Debi m3/h Q (m3/h) ∆P (Pa) Lw (dB)
∆P=Basınç Düşümü (Pa) 100 100 65

Kesit Genişlemesinde Ses Düşümü

m=S1/S2
S1=Küçük Kesit m 2

S2=Büyük Kesit m2 Lw=(m+1)2/(4m) dB


S1 S2
S1 (m2) S2 (m2) m Lw (dB)
10 20 0.5 1.13

ODALARDAKİ SES BASINÇ SEVİYESİ VE REZONANS SÜRESİ


Oda Tipi Ses Basınç Sev.dB Rezonans Süresi(s)
Oturma/yatak odası 35/30 0.5
Hastahane: Yataklı Odalar Gündüz/gece 35/30 1
Muayene Odaları,Holler,Koridorlar 40 2
Operasyon Odaları 40 3
Konferans Salonları:Radyo/TV Sütüdyoları 15/25 1/1,5
Tiyatro/Opera 30/25 1/1,5
Konser Salonu 25 2
Sinema,Dünlenme/Okuma Salonu 35 1
Kilise,camii 35 3
Bürolar: Toplantı Salonu 35 1
Küçük Büro Odası 40 0.5
Büyük Büro Odası 45 0.5
Lokantalar 40-55 1
Müzeler 40 1.5
Okuma Salonu/Sınıf 35/40 1
Jimnastik Salonları/Yüzme Havuzları 45/50 1,5/2
YAPI VE İZALAOSYON MADDELERİNİN
ÖZGÜL ISI KAPASİTELERİ (C kj/kgK)
MADDE C (kj/kgK)
Anorganik Yapı ve İzalasyon Maddeleri 1
Tahta ve Tahtalı Maddeler 2.1
Bitkisel Lif ve Tekstil Lifleri 1.3
Köpüklü Plastikler ve Plastikler 1.5
Aliminyum 0.8
Diger Metaller 0.4
Hava (ρ:1,25) 1
Su 4.2

Doyma Sıcaklığı=ts=100*(p0,25) p (Bar) ts (oC)


5 149.53

Doyma Basıncı=p=(ts/100)4 ts p
100 1

Doymuş Buharın Yoğunluğu=ρ''=(p/2)+0,1 p ρ''


0.1

Yoğunlukların Sıcaklıkla Değişimi

Hava ρ=1,275*(273/(273+t)) t (oC) ρh (kg/m3)


80 0.99

Su ρsu=1,002045x103-1,029905x10(-1)*t-3,698162x10(-3)xt2+3,991053x10(-6)xt3
t (oC) ρsu (kg/m )
3

80 972.18

Özgül Isıların Sıcaklıkla Değişimi

Suyun Özgül Isısı=ρ=4,177375-(2,144614x10(-6)xt)-(3,165823x10(-7)xt2)+(4,134309x10(-8)xt3

V (m/s) ρ'su (kj/kgK)


100 4.22

Isı İletkenliklerinin Sıcaklıklan Değişimi

Su α=2040x(1+0,015t)x(V0,87/(dh0,3)) w/m2K dh=(15-100)mm dh=Hidrolik Çap (mm),V=hız (m/s)


t (oC) V (m/s) dh (mm) αsu (w/m2K)
10 2 30 1545.57
Hava ve Duman αh=4,4x(V0,75/dh0,25)
V (m/s) dh (mm) αHava (w/m2K)
2 30 3.16
Kızgın Buhar αkb=(4,4+0,3t/100)xV0,75/dh0,25
t=sıcaklık t (oC) V (m/s) dh (mm) αkb (w/m2K)
V=Hız 10 2 30 3.18
dh=Hidrolik Çap
Basınç İle Hız Arasındaki Bağlantı

P=(ρ/2)*V2 ρ (kg/m3) V (m/s) P (Pa)


1000 5 12500
V=(P/(ρ/2))0,5 ρ (kg/m3) P (Pa) V (m/s)
1000 12500 5
10/14/2003
KONSOL HESABI

EŞİT KENAR KÖŞEBENTLER


Maximum Egilme Momenti L F (cm2) G( kg/m) J (cm4)
40x4 3.07 2.41 2.58
Mb=(F*a*b)/l 50X5 4.8 3.77 4.59
60X6 6.91 5.42 9.43
Sehim 70X7 9.4 7.38 17.6
f=(F*a2*b2)/(3*E*J*l) 80X8 12.3 9.66 29.6
90X9 15.5 12.2 47.8
Mb=Makximum Egilme Gerilmesi (kg-cm)100X10 19.2 15.1 73.3
F=Kuvet (kg) 120X12 27.5 21.6 152
a,b=Kuvvet in mesnetlere olan mesafesi (cm)
E=Elastisite modulu (kg/cm2) (30*106)
J=Atalet momenti (cm4)
l=Konsol boyu cm
f=Sehim (cm)
Γç=Cekme gerilmesi=F/A
A=Alan
Pt=Emniyet Gerilmesi (Celikler icin 1400 kg/cm2)= 1400

Fyangin=24 kgsu+26,28 kgboru=50,28 kg


Fpik boru=54 kgsu+42,3 kgboru=96,3 kg
Fkonsol=5,4mtx2,41=13,1 kg
Ftoplam= 159.68

DUBEL HESABI
Metrik Adubel
dubel= 8 0.5
Kullanilan Dubel sayısı 4
1 Dubele gelen yuk= 39.92 Γçdubel= F/Adubel= 79.46 kg/cm2 TRUE
Γçdubel<Pt oldugundan dubeller uygundur
KONSOL HESABI

Pik Boru Icin


Kullanilan Konsol=40x4 L Profil Fpik a b l Mb
Mb=(Fpikxaxb)/l 96.3 25 45 70 1547.68

Sehim

F a b E J I f
96.3 25 45 30000000 2.35 70 0.01

Bu hesaplar tüm yükün köşebentlere yansımış olduğu hale gore yapilmistir; halbuki köşe askının
yanısıra M10 rotlarlanda sabitlendirilmiş olduğu bilgilerinize bunulur.
I F
Mb=F*L F kg
f 45
f=F*I3/(3*E*J) F kg E kg/cm2 J
96.3 30000000 2.35
F
a a Mb=F*I/4 F kg l cm Mb kg-cm
45 70 787.5
f=F*I /(48*E*J)
3
F kg a cm a cm E kg/cm2 J cm4
I 96.3 25 45 30000000 2.35

F Mb=(F*a*b)/l F kg a cm b cm l Mb kg-cm
a b 96.3 25 45 70 1547.68
f=(F*a2*b2)/(3*E*J*l) F a b E kg/cm2 J cm4
96.3 25 45 30000000 2.35

I
l cm Mb kg-cm
70 3150
l cm f cm
70 0.16

l cm f cm
70 0.01

l cm f cm
70 0.01
OMEGA HESABI
FORMÜLLER
W Min H =0.02*(Dd*(T1-T2)*L*1,8)^0.5
H
Max L =2500*(H^2)/(Dd*(T1-T2))

L Min W =0.5*H 40.06

Terçih edilen W=1.5*H 120.18


W OMEGA GENİŞLİĞİ
H OMEGA YÜKSEKLİĞİ OMEGA HESABI
L SABİT MESNETLER ARASI MESAFE L(m) Dd(mm) ∆T Min H(cm)
Dd BORU DIŞ ÇAPI 60 165.1 90 80.12
∆T SICAKLIK FARKI
T1 BORUDAN GEÇEN SUYUN SICAKLIĞI
T2 ÇEVRE SICAKLIĞI

ÇELİK BORULAR NOT:1 inç=25,4 mm


Min H 'ın Kontrolu
İNÇ Di Dd A Do Test H(m)
1/2'' 15 21.3 A=tablo 1 de alınacak 0.43 165.1 0.85
3/4'' 20 26.9
1'' 25 33.7 Tablo 1
11/4'' 32 42.4 Tasarım Sıcaklığı (F) A Tasrım Sıcaklığı (F) A
11/2'' 40 48.3 150=65,56 C o
0.4 600=315,56 oC 2.2
2'' 50 60.3 200-93,3 oC 0.5 700=371 oC 2.5
21/2'' 65 76.1 300=148,9 oC 1 800=426,67 oC 2.8
3'' 80 88.9 400=204,4 oC 1.4 900=482,2 oC 2.95
4'' 100 114.3 500=260 oC 1.5 1000=537,78 oC 3.15
5'' 125 139.7
6'' 150 165.1 NOT:1F=1,8*oC+32 C
o o
F
8'' 204 250 80 176
10'' 254 300
o
F o
C
UZAMA MİKTARI 176 80

L(m) UZ.KAT.SAY. T UZAMA MİK (mm) RECKNAGEL-SPRENGER' GÖRE


20 0 70 17.5
13 mm üstünde ise H (m) W
17.5 1.1 H

10R 10R
KOLLEKTÖR ÇAPI R=5Dd
W=0,5H-1,5H
D=(d12+d22+d32+d42+d52)0,5 W=0,5H W=1,5H
0.55 1.65
d1 d2 d3 d4 d5 d6 d7 D (mm)
15 20 32 40 50 63 90 133.48

D=Kollektör Çapı mm
d=Kollektör Üstündeki Branşman Çapı mm

GENLEŞMEDE L MESAFESİNİN HESAPLANMASI


L

Min H2=0,0025*Do*L*∆T Do L ∆T Min H


Maximum L=(400*(H2))/Do*∆T 76.1 13 70 2.17
Test H=A*Do
Do=mm Pipe Dimeter Do H ∆T Max L
L=mt Pıpe Lenght 76.1 2.17 70 13
∆T=oC
H=mt A Do Test H
2.35 76.1 2.15

Tablo 1
Tasarım Sıcaklığı (oF) A Tasrım Sıcaklığı (oF) A
150=65,56 C o
0.4 600=315,56 oC 2.2
200-93,3 C
o
0.5 700=371 C o
2.5
300=148,9 oC 1 800=426,67 oC 2.8
400=204,4 oC 1.4 900=482,2 oC 2.95
500=260 oC 1.5 1000=537,78 oC 3.15

NOT:1F=1,8*oC+32 C
o o
F
80 176

o
F o
C
1000 537.78
a (cm) b (cm) A (m2) V (m/s) Lw (dB)
33 17 0.056 5 32

KISIM NO Qkıs(m /h) Qtop (m3/h) V (m/s) b (cm) dh (mm) έ (mm)


3
A (m2) a (cm) ƒ
1 1000 1000 5 0.056 33 17 222 0.15 0.018
2 200 1200 5 0.067 37 18 243 0.15 0.017
3 350 1550 3 0.144 54 27 357 0.15 0.016
4 100 1650 2 0.229 68 34 451 0.15 0.015
5 250 1900 6 0.088 42 21 280 0.15 0.017
6 1900 8 0.066 36 18 242 0.15 0.018
7 1900 2 0.264 73 36 484 0.15 0.015
8 1900 5 0.106 46 23 306 0.15 0.017
9 1900 3 0.176 59 30 395 0.15 0.016
10 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
11 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
12 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
13 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
14 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
15 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
16 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
17 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
18 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
19 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
20 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
21 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
22 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
23 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
24 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
25 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
26 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
27 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
28 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
29 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
30 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
31 1900 ### #DIV/0! #DIV/0! #DIV/0! 0.15 ###
32 1900 ### #DIV/0! #DIV/0! 0.15 ###
L (m) ΔP (pa/m)ΔP (Pa)
2.000 0.27 0.54
1 0.26 0.26
1 0.09 0.09
1 0.04 0.04
1 0.37 0.37
1 0.67 0.67
1 0.04 0.04
1 0.25 0.25
1 0.08 0.08
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
1 #DIV/0! #DIV/0!
KANAL KESİTİ HESABI
YUVARLAK DİKDÖRTGEN Eşdeğer ÇAP Eşdeğer ÇAP
DEBİ(m3/h) HIZ (m/s) KESİT(m2) ÇAP(cm) a(m) b(m) De cm De=4A/Çevre-cm
10000 4 0.69 94.06 0.59 1.18 89.77 78.57

DEBİ HESABI

ÇAP (cm) HIZ(m/s) KESİT(m2) DEBİ (m3/h)


94.06 4 0.69 10000
HAVA KANALLARINDA KABUL EDILEBILIR KACAK MIKTARLARI

TABLO 1. KANAL SINIFLANDIRILMASI/DW 142

KANAL BASIÇ
STATIK BASINÇ HAVA HAVA
SINIFI POZİTİF NEGATİF HIZI KAÇAĞI
1 2 3 4 5
pa pa m/sec
Düşük 500 500 10 SINIF A
Orta 1000 750 20 SINIF B
2000 750 40 SINIF C
Yüksek 2500 750 40 SINIF D

TABLO 2. HAVA KACAK LİMİTLERİ/DW 142

HAVA KAÇAĞI HAVA KAÇAĞI LİMİTLERİ


1 2 DEĞERLER
1m2 havalandırma kanalında 1 sn de Qk(l/s) p Qk
kaçabilecek hava miktarı:l/s kacak pascal m3/h
Düşük basınç-Sınıf A 0,027xp^0,65 0.85 200 3.04
Orta basınç-Sınıf B 0,009xp^0,65 0.67 750 2.4
Yüksek basınç-Sınıf C 0,003xp^0,65 0.19 600 0.69
Yüksek basınç-Sınıf D 0,001xp^0,65 0.1 1250 0.37

Kanalda olabilecek Maximum Hava Kacağı


Statik Basınç Düşük Basınç Orta Basınç Yüksek Basınç
Farkı Pa Sınıf A Sınıf B Sınıf C Sınıf D
1 2 3 4 5
100 0.54 0.18
200 0.84 0.28
300 1.1 0.37
400 1.32 0.44
500 1.53 0.51
600 0.58 0.19
700 0.64 0.21
800 0.69 0.23
900 0.75 0.25
1000 0.8 0.27
1100 0.29 0.1
1200 0.3 0.1
1300 0.32 0.11
1400 0.33 0.11
1500 0.35 0.12
1600 0.36 0.12
1700 0.38 0.13
1800 0.39 0.13
1900 0.4 0.14
2000 Not:1m2 kanal yüzeyinde 0.42 0.14
2100 litre cinsinden değerlerdir. 0.14
2200 0.15
2300 0.15
2400 0.16
2500 0.16

Tablo 3. Kanalda olusacak max. hava kacak limitleri

Maximum Test Kaçağı=Yüzey alanı x Maksimum sistem kacağı x %10-%15

Qtest kacagi= Y.Alani Tablo 3'den Izin verilen


lt/s m2 lt/s/m2 % miktari
15.54 185 0.84 10
Eşdeğer ÇAP
De=4A/Çevre-cm
78.57
KLIMA SANTRALLERININ FAN GUCLERININ HESABI

Q (m3/h) ∆P (Pa) µ P (kw) μ=Verim


20160 100 0.65 0.86 ∆P=Basınç Farkı
Q=Debi
P=elektrik Gücü

AHU NO Q (m3/h) ∆P (Pa) µ P (kw)


AHU 1 2 1066 0.72 0
AHU 2
AHU 3
AHU 4
AHU 5
AHU 6
AHU 7
AHU 8
AHU 9
AHU 10
GAZ BORUSUNUN HESABI

Q=0,001*d2,623*(∆P/CL)0,541 C=0,00223*(t+273)*s0,848*μ0,152

d (mm) ∆P (Pa) t (oC) s μ C L (m) Q (lt/s)


20 0.75 20 1.56 8 1.31 30 0.03

Q ∆P (Pa) t oC s μ C L (m) d (mm)


0.03 0.75 20 1.56 8 1.31 30 21.03
s
Q=Debi (lt/s) Doğal Gaz L 0.61
d=Borunun iç çapı (mm) Doğal Gaz H 0.55
t=Sıcaklık (oC) Metan 0.74
C=Vizkozite Propan 1.56
s=Gaz yoğunluğunun havanın yoğunluğuna oranı n-Bütan 2.09
μ=Gazın Vizkozitesi (Doğal gaz=12 , Propan=8)
L=Boru uzunluğu (m)
SULLU SÖNDÜRME SİSTEMLERİ

Su Depoları

Not:1 Hidrant 3 Yangın Dolabı 2 saat kullanılacak şekilde hesap yapılacak.


Yukarıdaki not yanlız Rus standartlarında mevcuttur Ulaslar arası standartlar aşağıdaki tablolardaki gibidir.
Siprinkler Söndürme Sistemleri İçin Su İhtiyacı

NFBI ve DIN NORMLARI Debi (l/dak) Süre (dak)


Düşük Tehlikeli Sınıfı 1000 45
Orta Tehlikeli Sınıfı 2000 60
Yüksek Tehlikeli Sınıfı Hüdrolik Hesaplar ile Belirlenir
Yüksek Binalar Hüdrolik Hesaplar ile Belirlenir

Yangın Dolapları Ve Hidrantların Su İhtiyacı


NFBI ve DIN NORMLARI Yangın Dolabı Debisi (l/dak) Hidrant Debisi (l/dak) Süre (dak)
Düşük Tehlikeli Sınıfı 100 400 30
Orta Tehlikeli Sınıfı 100 1000 60
Yüksek Tehlikeli Sınıfı 200 1500 90
Not:Yapıda sullu söndürme sistemi olarak sadece yangın dolapları sistemleri mevcut ise
su kapasitesi en az 200 litre debiyi 60 dakika süre ile karşılayacak şekilde en az 12 m3
olacaktır.Yanlız çevre hidrantı bulunması durumunda su ihtiyacı en az 1900 litre debiyi
90 dakika süre ile karşılayacak kapasitede hidrolik hesap ile bulunacaktır.
Hidrant çıkışında 700 kPa basınç olmalıdır.Hidrantlar arası uzaklık çok riskli bölgelerde
50 m, riskli bölgelerde 100 m, orta riskli bölgelerde 125 m, az riskli bölgelerde 150 m alınmalıdır.

YANGIN DOLAPLARI:Boru 50 mm den az olmamalı.Dolap dizayn debisi 400 l/dak ve lans


girişindeki basıncı 700 kPa olmalıdır.Basınç 900 kPa lı geçerse basınç düşürücü kullanılmalı.
Yangın Deposu Hacmi

Hidrant Yangın Dolabı Siprink Süre (dak) Yangın Suyu Deposu(lt)


1 3 0 120 84000

ÖNEMLİ NOTLAR
SİPRİNKLER:Büro ve konutlar haricindeki bütün yüksek binalarda,Yapı yüksekliği 30,5 mt den fazla
olan büro binaları,Yapı yüksekliği 51,5 mt geçen apartmanlarda,Araç kapasitesi 20 den fazla veya birden
fazla bodrum katı bulunan kapalı otoparklarda, Yatak sayısı 200 ü geçen otel,pansiyon ve misafirhanelerde
Toplam kullanım alanı 200 m2 nin üzerinde olan katlı mağazalar,alışveriş ,ticaret,eğlence ve toplanma
yerleri otomatik sprinkler sistemi ile korunacaktır.
POMPALAR:Pompalar kapalı vana (sıfır debi) basma yüksekliği anma basma yüksekliğinin en fazla
%140 ı kadar olmalı ve %150 debideki basma yüksekliği anma basma yüksekliğinin %65 inden daha
küçük olmamalı.NOT:Pompa odası veya pompa istasyonunda +4oC üzerinde sıcaklık sürekli
sağlanabilmesi için uygun gereçler sağlanacaktır.

Basınç İle Hız Arasındaki Bağlantı

P=(ρ/2)*V2 ρ (kg/m3) V (m/s) P (Pa)


1000 5 12500
V=(P/(ρ/2))0,5 ρ (kg/m3) P (Pa) V (m/s)
1000 12500 5
BACA HESABI

Qk (kcal/h) h (m) F=Qk*0,012/(h)0,5 D


2500000 80 3354.1 65.27

ALT HAVALANDIRMA

Qk(kcal/h F=4,5*(Qk+60)/860 cm2 D


1425000 7456.71 86.35

ÜST HAVALANDIRMA

Qk(kcal/h) F=2,5*(Qk+60)/860 cm2 D


1425000 4142.62 64.36

DAVLUMBAZ DEBİ VE BOYUTLARI

Debi=V=2.X.Ux.Vx (m3/s)
Ux=Davlumbazın Alın Çevresi (m)
Vx=Toplama Hızı
30 -40
O O
X=Davlumbazın Masaya olan uzaklık

Vx

X 0,3-0,4X

X (mt) Ux (mt) Vx (m/s) V (m3/s)


MASA 1 7.2 0.6 8.64

Vx (m/s)
Sakin Havada 0,1-0,15
Zayıf Çapraz Akımlarda 0,15-0,30
Şiddetli Çapraz Akımlarda 0,20-0,40

Tecrübe Değerleri Vx (m/s)


Dört Tarafı Açık Olan Davlumbazlar 0,9-1,2
Üç Tarafı Açık Olan Davlumbazlar 0,8-1,1
İki Tarafı Açık Olan Davlumbazlar 0,7-0,9
Tek Tarafı Açık Olan Davlumbazlar 0,5-0,8

Banyolarda Havalandırma

Debi=L.h.V.=2.vs.L.w m3/s vs L w Q (m3/s)


vs=Emiş Hızı=0,1-0,8 m/s 0.6 6 4 28.8
L=Banyo Uzunluğu=m
w=Banyo Genişliği=m
Her m2 Alan Başına Havalandırma=2.vs.(w/L)0,2 (m3/s)
vs (m/s) w (m) L (m) Q m3/s
0.6 4 6 1.11
FORMÜLLER

BORULARDA BASINÇ KAYBI L V C D hmSS


1 2.6 140 0.2 0.03
h=BASINÇ KAYBI(mss) DEBİ(m3)
V=ORTALAMA HIZ(m/s) V D Q=3,14*D2*V/4
D=BORU İÇ ÇAPI (m). 2.6 0.2 293.9
L=BORU BOYU(m) BORU ÇAPI
C=PÜRÜZLÜLÜK KAT SAYISI V Q D
Cbakır=150 , Cçelik=140 , Ckorozyonlu=100 1.5 169.56 0.2
Cplastik=150
Q=DEBİ(m3/h) DEBİ DEĞİŞİMİ(m3) FARK(m3)
M=KÜTLESEL DEBİ m3/h A V µ M Q-M
A=KESİT(ALAN) m2 0.03 2.6 1 293.89 0.02
µ=YOGUNLUK kg/dm3
SERVİS TİPLERİNE GÖRE SU HIZLARI B0RU İÇİNDEKİ SU MİKTARI
Servis Tipi Hız (m/s)
Genel servis 1,2 ila 3,0 0.03 m3 31.4 lt
Şehir suyu 0,9 ila 2,1
Kazan besleme 1,8 ila 4,6
Pompa emmesi ve drenaj hattı 1,2 ila 2,1
VÜCUT YÜZEYİ ALANI
M L Ad
0.25 0.3 0.05

POMPALAR-HİDROFORLAR

Sistem Basma Yüksekliği(Ha) 1 2 3 4 5 6 Ha


Hgeo=Statik yükseklik 1 6 0 0 20.3 9.81 1 26.3
(Pa-Pe)/(µ*g)=Basınç Farkı 2
(Va2-Ve2)/(2*g)=Hız Basıncı 3 NOT:Uygulamada Hız Basıncı İhmal Edilebilir
Hv=Toplam Boru ve Vana Kaybı 4
g=Yerçekim ivmesi (9,81) 5
µ=Yoğunluk 6
n=Verim

POMPA GÜCÜ (kw) µ Q Ha n P (kw)


1.2 4.2 1 0.85 0.02
NOT:7,5 kw ya kadar%20, 7,5-40kw ya kadar %15, 40kw nin üzeri %10 emniyet payı koyulacak.