External Retrofit

Remote Measuring Station – RMS


Retrofit Terminal Units

Product Overview

Model RMS
PRICE Remote Measuring Station pro-
vides accurate measurement of air flow via
its multi-point velocity pressure sensor.The
RMS can be mounted at the inlet of existing
mechanical or pressure dependent units
providing a means of flow measurement. Al-
ternately, the RMS can be installed anywhere
in a duct system where flow measurement
is desired. When combined with a pressure
transducer, the RMS can be interfaced with
a DDC system.
Basic Features
• Available in 8 sizes from 6" to 16"
diameter.
• Multiple pick-up points provide a more
representative indication of air volume
under varying flow conditions.
• Velocity pressure signal is amplified
for increased sensitivity and control

TERMINAL UNITS
response.
• Units fabricated from 22 GA zinc-
coated steel, mechanically sealed,
leak-resistant.
• Optional collar allows for ease of
connection to terminal unit.
• Rectangular or square sizes also
available.

Dimensional Data — Imperial (inches)/Metric (mm)


Unit CFM L/s
Size Range Range A
6 0 – 450 (0 – 212) 6 (152)
7 0 – 650 (0 – 307) 7 (178)
8 0 – 800 (0 – 378) 8 (203)
9 0 – 1050 (0 – 496) 9 (229)
10 0 – 1350 (0 – 637) 10 (254)
12 0 – 2100 (0 – 991) 12 (305)
14 0 – 3000 (0 – 1416) 14 (356)
16 0 – 4000 (0 – 1888) 16 (406)

✓ Product Selection Checklist


For custom sizes inquire 1] Select Unit Inlet Size based on air volume.
with customer service.

Product Information Index


Suggested Specification ................. F366

© Copyright E.H. Price Limited 2007. All Metric dimensions ( ) are soft conversion.
Imperial dimensions are converted to metric and rounded to the nearest millimetre.
F-325
Suggested Specification
Retrofit Terminal Units

External

General – RPV/REV/RDV General – RPX/REX/RDX


Furnish and install PRICE variable volume Furnish and install PRICE variable volume
retrofit units (RPV/REV/RDV 8000) of the sizes retrofit units (RPX/REX/RDX 8000) of the sizes
and capacities as shown on the plans. and capacities as shown on the plans. Unit
The assemblies shall be pressure indepen- shall be designed to operate the existing
dent and shall reset to any air flow between damper of terminal unit to be retrofitted.
zero and the maximum cataloged volume. The assemblies shall be pressure independent
The air flow sensor shall be of a cross and shall reset to any air flow between zero and
configuration located at the inlet of the as- the maximum cataloged volume.
sembly. The sensor shall have twelve total The air flow sensor shall be of a cross
pressure sensing ports and a center averag- configuration located at the inlet of the as-
ing chamber designed to accurately average sembly. The sensor shall have twelve total
the flow across the inlet of the assembly. pressure sensing ports and a center averag-
Sensor shall provide accuracy within 5% with ing chamber designed to accurately average
a 90° sheet metal elbow directly at the inlet the flow across the inlet of the assembly.
of the assembly. The air flow sensor shall Sensor shall provide accuracy within 5% with
amplify the sensed air flow signal. a 90° sheet metal elbow directly at the inlet
The unit shall be constructed of 22 gauge of the assembly. The air flow sensor shall
zinc-coated steel. The primary air valve amplify the sensed air flow signal.
TERMINAL UNITS

damper shall be heavy gauge metal, with The unit shall be constructed of 22 gauge
peripheral gasket, and solid steel shaft, zinc-coated steel.
pivoted in self-lubricating bearings. In the Controls
full closed position, air leakage past the Refer to Single Duct Controller Type, Page
closed damper shall not exceed 2% of the F349
nominal catalog rating at 3"w.g. inlet static
pressure, when tested in accordance with
ASHRAE 130.
Controls
Refer to Single Duct Controller Type, Page
F349

General – RPS/RES/RDS Model RMS


Furnish and install PRICE variable volume Furnish and install Model RMS remote mea-
retrofit units (RPS/RES/RDS 8000) of sizes suring stations of the sizes and capacities
and capacities as shown on the plans. shown on the plans.
The assemblies shall be pressure indepen- Units shall be constructed of 22 ga. zinc-
dent and shall reset to any air flow between coated steel, mechanically sealed.
zero and the maximum cataloged volume. The air flow sensor shall be of a cross
The air flow sensor shall be of a cross configuration located at the inlet of the as-
configuration located at the inlet of the as- sembly. The sensor shall have twelve total
sembly. The sensor shall have twelve total pressure sensing ports and a center averag-
pressure sensing ports and a center averag- ing chamber designed to accurately average
ing chamber designed to accurately average the flow across the inlet of the assembly.
the flow across the inlet of the assembly. Sensor shall provide accuracy within 5% with
Sensor shall provide accuracy within 5% with a 90° sheet metal elbow directly at the inlet
a 90° sheet metal elbow directly at the inlet of the assembly. The air flow sensor shall
of the assembly. The air flow sensor shall amplify the sensed air flow signal.
amplify the sensed air flow signal.
The unit shall be constructed of 22 gauge
zinc-coated steel. The primary air valve
damper shall be heavy gauge metal, with
peripheral gasket, and solid steel shaft,
pivoted in self-lubricating bearings. In the
full closed position, air leakage past the
closed damper shall not exceed 2% of the
nominal catalog rating at 3"w.g. inlet static
pressure, when tested in accordance with
ASHRAE 130.
Controls
Refer to Single Duct Controller Type, Page
F349

All Metric dimensions ( ) are soft conversion. © Copyright E.H. Price Limited 2007.

F-366 Imperial dimensions are converted to metric and rounded to the nearest millimetre.