Professional Documents
Culture Documents
310BC - 330BC
CONTENTS
Introduction Section 1
Stop - Start Section 2
Programming parameters Section 3
Reading out measurements Section 4
Alarms - what to do Section 5
The events logger Section 6
Preventive maintenance Section 7
Economy mode Section 8
2.2 Stop
Open the front door and activate the red “OFF” push-button display shows * Stand-by *
Alarm LED lights. Acoustic alarm sounds for 10 seconds.
WARNING: Please read maintenance section, if UPS has to be stopped for more than one week.
2.3 Start
Open the front door and activate the green “ON” push-button display shows Normal operation
Load power xx%
3.2 Parameters
Key Function
Activates “ON”
Activates “OFF”
1. Press
Programming of the other parameters can be performed in exactly the same way.
7JA0001GB rev 02 Page 3 of 6
4.0 READING OUT MEASUREMENTS
Press as indicated below one key or two keys simultaneously (Used values are only random for
illustration):
Press Display shows Comments
2. Press or to move inside the alarm stack. (Last message is “No alarms”).
1. If the messages "Battery monitor warning" of "Battery monitor alarm" pop up go to point 5.3.6.
2. Check the local mains power supply. One or more fuses may be blown or somebody could by an
accident have switched off the supply.
3. Check if the cooling air intake down on the front door or exhaust on the top cover on your UPS
has been blocked.
4. Check if somebody has switched more load on the UPS - the max. output capacity may be
exceeded.
5. If there is no output voltage from the UPS - the mains supply is present and atempt to restart
gives no result - by-pass the UPS by means of the external service by-pass switch if present -
else open the front door and turn the by-pass handle from "OFF" to "ON". Then call for assi-
stance.
6. "Battery monitor alarm" means no back-up capacity any longer. Call for assistance.
"Battery monitor warning" means reduced back-up capacity. Reset the "Battery monitor
warning" alarm signal according to point 3.2 and start-up a battery capacity test according to
point 7.3. When finished - record the obtained back-up time and reset an eventual new alarm
from the battery monitor. Let the UPS recharge the battery for at least 8 hours, and with the
same load as before start-up again a second battery capacity test. If this results in improved
back-up time continue with further capacity tests until none or insignificant improvements take
place. Above might "wake-up" the battery - else call for assistance.
MODE COMMENTS
2. Press or to move inside the events stack. (Last message is “No events”).
3. Press to display the time where the event happend (Time is UTC = Universal Time
Coordination = GMT)
4. Press to leave the events stack, or wait 20 seconds for automatic reset.
7.2 Fan
The fan is recommended to be replaced every 3rd year.
7.3 Battery
Every three months it is recommended to check, whether the battery has still a capacity /
condition to ensure sufficient back-up time by performing a battery capacity /condition test.
1. Press
To interrupt a running test - perform point 1-3 but press key instead of in point 3.
Please notice that after a battery capacity test it last about 8 hours before the battery is recharged
and full back-up time again is available.
Battery tests should preferably be made during uncritical periods of computer operation for reasons
of safety!
If the UPS has to be taken out of operation for some time it has to be switched off from the mains
supply to prevent a total discharge and damage of the battery. But the UPS must at least be in
operation for min. 12 hours in a 3 month period to ensure that the battery is sufficient charged.
Otherwise the battery also might be damaged.
In economy mode the load is supplied directly from the mains, however the UPS is monitoring the
mains and the output voltages and will in case of mains failure switch into battery operation without
interruptions.
The system will in order to keep the batteries fully charged at all times switch to normal operation in
a pre-programmed sequence.
The operation of the system is described in this guide with the exceptations of the following points:
- When starting up, the system will first go into normal operation to ensure a fully charged
battery but will then switch into by-pass after the pre-programmed time (typically 8 - 10 hours).