Background
Many buildings are still constructed or remodelled without consideration of energy conserving
strategies or other sustainability aspects. To provide substantial improvements in energy
consumption and comfort levels, there is a need to treat buildings as complete optimised entities
(as indicated in Figure 1) not as the sum of a number of separately optimised components.
Integrated building performance simulation is ideal for this because it is not restricted to the
building structure itself but can include the indoor environment, while simultaneously taking into
account the outdoor environment, mechanical, electrical or structural systems, and traditional and
renewable energy supply systems. By assessing equipment and system integration ideas, it can
aid building analysis and design in order to achieve a good indoor environment in a sustainable
manner, and in that sense to care for people now and in the future. For an overview of current
building performance simulation software, see http://www.eren.doe.gov/buildings/tools_directory
ESP-r comprises a central Project Manager (PM) around which is arranged support databases, a
simulator (consisting of specialised concurrent solvers for domains such as heat flow, fluid flow,
power flow, control, etc.), performance assessment tools and a variety of third party applications
for CAD, visualisation, report generation, etc. (Figure 2). The PM's function is to co-ordinate
problem definition and give/receive the data model to/from the support applications. Most
importantly, the PM supports an incremental evolution of designs as required by the nature of the
design process.
Lighthouse Viewing Gallery Maximum Capacity Thermal Comfort Glare Sources (cd/m 2)
160 80
Version: reference 3 opt 2 + RE
140 70
Contact: ESRU W Winter
120 60
or
Date: Sep-97 Spring
W/ 100 ki
50
ng Summer
m2 80
58.40 40
ho
60 48.13 41.60 38.60 ur
30
40 s/
12.00 20
we
20 0.00
k
0 He Co Lig PV PV D 10
atin olin hti e h WT
g g ng 0
o
16.0-18.018.0-20.020.0-22.0Temperature
Resultant 22.0-24.024.0-26.0(C)
26.0-28.028.0-30.0
Figure 3: Integrated Performance Appraisal with Passive and Active RE Systems Applied
The design support was based on performance assessment method whereby computer simulation
is used to determine the multivariate performance of an initial design of the building (e.g.
corresponding to current best practice). The multivariate performance data are presented in the
form of an integrated performance view as in Figure 3. The model is then modified by incorporating
one of the renewable technologies and re-assessed. In this way, the contribution of the individual
renewable technologies may be assessed and the different possible permutations compared.
In comparison with the initial design hypothesis, the cumulative effect of advanced glazing, a fast
response, critically controlled, convective heating system, high efficacy lamps and luminairs,
lighting control and transparent insulation facade resulted in a 58% reduction in annual heating
energy demand, a 67% reduction in heating plant capacity, an 80% reduction in lighting energy
demand and a 68% reduction in overall energy demand.
Figure 3 summarises the overall performance results. The combination of ducted wind turbines and
PV components proved to be a successful matching of renewable energy systems to meet the
seasonal energy demands. The wind turbines produce electricity predominately during the winter
period when the PV components can contribute little. Conversely, the PV components supply
power predominately during the summer period when the winds are light. The combination of the
two systems gives rise to an embedded renewable energy approach that is well suited to the
climate of Glasgow.
Case study: building reconstruction using a double-skin facade
This project (Dunovska and Hensen 2001) was about reconstructing and converting an old factory
hall in Prague into a modern office development (Figure 4). It includes a new two-floor
superstructure on top of the original building. The superstructure is completely enclosed by a glass
shell, thus forming a double skin facade (Figure 5).
Figure 4 View of the refurbished building Figure 5 Double skin façade concept in summer
An extensive simulation study was carried out to predict the thermal behavior. It was proposed to
control the double facade space so it would be closed in winter and serve as thermal buffer zone.
In summer the controllable flaps would open to allow natural ventilation through the façade, and
active shading would reduce the solar radiation gains (Figure 5).
55
E_SF=0
E_SF=0.5
50 3500
E_SF=0.85
W_SF=0
45 3000
W_SF=0.5 East
W_SF=0.85 W est
air temperature (°C)
2500
40 Te
Qmax (W)
2000
35
1500
30
1000
25
500
20 0 zona2
0 0.5
15 0.85 1 zona1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 0 0.5
shading faktor 0.85 1
time (h)
Figure 6 shows the double facade outlet temperatures for different shading levels (SF). On a warm
summer day, when the shading is closed (SF = 0.85), the façade air temperature can rise by 11°C
on the eastern side and by 17°C on the western side of the building. Figure 7 shows the maximum
cooling load for several levels of shading in two offices with different orientation. The cooling load
reduces significantly with increased shading, even though the temperature in the double facade
increases.
Challenges
Although most practitioners will be aware of the emerging building simulation technologies, few as
yet are able to claim expertise in its application. This situation is poised to change with the advent
of: performance based standards; societies dedicated to the effective deployment of simulation -
such as IBPSA1 ; appropriate training and continuing education; and the growth in small-to-medium
sized practices offering simulation-based services. One thing is clear: as the technology becomes
more widely applied (see e.g. Drkal et al. 2001, Bartak et al. 2001), the demands on simulation
programs will grow. While this is welcome, in that demand fuels development, it is also
problematic because the underlying issues are highly complex. Although contemporary programs
are able to deliver an impressive array of performance assessments (see e.g. Hensen and
As indicated in Figure 8 there are many opportunities (and challenges) for expanding the scope
(and thus the impact and usefulness) of building performance simulation.
Conclusions
This paper has elaborated and demonstrated the state-of-the-art in integrated building simulation
and it’s value when used in (sustainable) building design. This paper has also argued the
importance of this technology and how it will benefit in an economical and environmental context.
Since many people in the field are not yet aware of this, there is a need for an organisation such as
IBPSA. Its mission is to address the challenges above, and to promote and support moving the
technology into the everyday practice of engineers and architects.
REFERENCES
Bartak M, F Drkal, J Hensen, M Lain, T Matuska, J Schwarzer and B Sourek 2001. “Simulation to
support sustainable HVAC design for two historical buildings in Prague”, in Proc. PLEA 2001,
Florianopolis, Brazil (in print).
Clarke J A (1985) ‘Energy simulation in building design’ Adam Hilger, Bristol and Boston.
Clarke J A, J Hensen, C M Johnstone and I Macdonald (1999). "On the use of simulation in the
design of embedded energy systems," in Proc. Building Simulation '99 in Kyoto, pp. 113-119,
International Building Performance Simulation Association.
Drkal F, M Bartak, J Hensen, M Lain and J Schwarzer 2001. “Prispevek k vyvoji ve vetrani a
klimatizaci”, in Proc. 50 year Environmental Engineering, Czech Technical University in
Prague. (Contribution to the development of ventilation and air-conditioning)
Dunovska T and J Hensen 2001. “Some experiences with building simulation in Czech
construction industry”, in Proc. Building Simulation 2001 in Rio de Janeiro, pp. 837-840,
International Building Performance Simulation Association.
Hensen J and N Nakahara 2001. (Guest editors) Special issue on building performance simulation,
Energy and Buildings, vol. 33, nr. 4.