Earthing transformers are usually oil immersed and may be installed outdoor. In
cases where a separate reactor is connected between the transformer neutral
and earth, the reactor and the transformer can be incorporated in the same
Most of the time in service the loading of earthing transformers is very low. It is
the randomly occurring short – duration currents that cause any heating of
significance. Ageing of the cellulose materials is then not a matter of concern.
Regarding acceptable temperatures there are two aspects to consider. The
temperature during currents of say 10 seconds duration must not cause
softening of the winding conductor material, say 250o C for copper and 200 o C
for aluminium.
For currents with duration in the order of hours or more, temperatures that
cause excessive gas development in the oil should be avoided. Temperatures for
items in direct contact with the oil should then not exceed 140 o C
The system earth fault protection relay may not be effective at low currents. To
prevent damage to earthing transformer by such current, oil thermometer with
alarm/trip contacts is recommended. Alternatively, the value of maximum
continuous earth fault current may be declared and sensitive protection
provided.