You are on page 1of 6

© 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal (Vol.

48, July 2006).


For personal use only. Additional distribution in either paper or digital form is not permitted without ASHRAE’s permission.

By John Murphy, Member ASHRAE the sensible cooling performed by the


equipment to the sensible cooling load.

W
hile not a new concept,1 dedicated Therefore, as the sensible cooling load
in the space decreases, the total cooling
outdoor air systems are increasingly (both sensible and latent) provided by
the HVAC equipment also decreases. In
popular. However, many of the systems de- many applications, this results in elevated
space relative humidity levels at part-load
signed and installed today are suboptimal. This conditions.2
A dedicated outdoor air system uses
article discusses ways to optimize the design a separate unit to condition all of the
outdoor air brought into the building for
and control of dedicated outdoor air systems ventilation, and then delivers it either
directly to each occupied space or to
to lower both installed cost and energy use. the individual local units or air handlers

Basic, constant-volume HVAC equipment is traditionally About the Author


selected with sufficient cooling capacity to handle the peak John Murphy is a senior applications engineer with
cooling load and controlled by a thermostat that matches Trane in LaCrosse, Wis.
Consider delivering the conditioned outdoor air “cold”
whenever possible, and use recovered energy to reheat
only when needed. Providing cold (rather than neutral) air
from the dedicated outdoor air unit offsets a portion of the
space cooling loads, allowing the local HVAC units to be
downsized and use less energy.
serving those spaces ((Figure
Figure 1). Meanwhile, local HVAC units tion, and to deliver the air dry enough to also offset the space
in or near each space maintain space temperature by treating latent loads. Previous ASHRAE Journal articles3,4 included a
just recirculated indoor air. Treating the outdoor air separately step-by-step method for sizing the dedicated outdoor air unit
from recirculated return air makes it easy to verify sufficient using this approach.
ventilation airflow and enables enforcement of a maximum For most comfort-cooling applications, sizing the dedicated
humidity limit in the occupied spaces. outdoor air unit to limit space relative humidity to 60% or 65%,
To optimize both installed cost and energy use of dedicated at worst-case conditions, is generally considered acceptable and
outdoor air systems, consider the following. complies with requirements recently added to ANSI/ASHRAE
Standard 62.1-2004, Ventilation for Acceptable Indoor Air Qual-
1. Deliver Conditioned OA Drier Than the Space ity (Section 5.10).6 Designing for lower indoor humidity levels
Regardless of where the conditioned outdoor air is delivered, is certainly possible, but requires larger equipment, increasing
the dedicated outdoor air unit should dehumidify the outdoor air installed cost and energy consumption.
so that it is drier than the space. Delivering the air drier than the
space offsets the latent cooling loads associated with ventila- 2. Deliver Conditioned OA Cold Rather Than Neutral
tion. If the dew-point temperature of the conditioned outdoor Many dedicated outdoor air systems are designed to dehu-
air (CA) is lower than the dew point in the space ((Figure 2), it midify the outdoor air so it is drier than the space, and then
also can offset some, or all, of the space latent loads. reheat it to approximately space temperature (neutral). If the
This adequately limits indoor humidity at both full load conditioned outdoor air is delivered directly to the space,
and part load without needing additional dehumidification delivering it at a neutral dry-bulb temperature can simplify
enhancements in the local HVAC units. The local units only local comfort control because it has no impact on space
need to offset the space sensible cooling loads. Some refer sensible loads.
to this as “decoupling” the dehumidification load from the However, when a chilled-water or DX coil is used to dehu-
space sensible load. midify the outdoor air, a byproduct of that process is that the
A side benefit of this approach is that the local units oper- dry-bulb temperature of the air leaving the coil is colder than
ate with dry coils under most conditions. With the dedicated the space (Figure 2). If the dehumidified outdoor air (DH) is
outdoor air unit offsetting the space latent loads, the space reheated to neutral (CA), the sensible cooling performed by
dew point often will be below the dry-bulb temperature of the the dedicated outdoor air unit is wasted.
air supplied by the local units. Under such conditions, little In contrast, if the dedicated outdoor air unit dehumidifies
or no moisture condenses on local cooling coils, reducing the the outdoor air, but then delivers the conditioned air “cold”
potential to clog and overflow drain pans. (In draw-through (not reheated to neutral), the low dry-bulb temperature offsets
applications, special condensate traps may be necessary to part of the sensible cooling load in the space. At design load,
maintain an air seal.) this means less cooling capacity is required from the local
To provide the desired dehumidification, the dedicated out- HVAC equipment than in a neutral air system.
door air unit commonly is sized to offset the sensible and latent For an example elementary school, the dedicated outdoor
loads of the outdoor air brought into the building for ventila- air unit cools and dehumidifies the outdoor air to 52°F (11°C)

July 2006 ASHRAE Journal 31


85°F 180
Dedicated Sensible Cooling
OA OA Unit OA 80°F 160
re

Humidity Ratio, grains/lb of Dry Air


tu
e ra OA 140
CA CA p 75°F
m
Te

Dehumidification
b 120
l 70°F
-Bu Coil Curves
et 100
W 65°F
CA CA SA RA RA SA
60°F Space 80
SA SA 60
50°F ,%
DH CA idity
40°F 80
v e Hum 40
t i
RA RA 30°F 60
Rela 20
40
20
Conditioned Outdoor Conditioned Outdoor Air 0
Air Direct to Spaces To Local HVAC Units 30°F 40°F 50°F 60°F 70°F 80°F 90°F 100°F 110°F
Dry-Bulb Temp.

Figure 1: Common dedicated outdoor air system configurations. Figure 2: Sensible cooling is a by-product of ‘cold-coil’ dehumidification.

dew point, then reheats the air to 71°F (22°C) dry bulb before less cooling energy at each local HVAC unit. The neutral
delivering it directly into the classrooms. The dew point of air system throws away this sensible cooling benefit by
this conditioned outdoor air is low enough to offset the latent reheating the air to approximately space temperature.
load in the classrooms, but because it is delivered at a dry-bulb • May require less reheat energy. If “new” (not recovered)
temperature that is near the space temperature (74°F [23°C]), energy is used to reheat the dehumidified outdoor air, a
it offsets only a small portion of the sensible cooling load in cold air system avoids the energy costs of reheating for
the classrooms. much of the year.
Consider, however, if the dedicated outdoor air unit dehu- • Requires less overall fan airflow and, therefore, less over-
midifies the outdoor air to the same dew point, but delivers all fan energy. The supply airflow delivered by each local
it cold (not reheated). The conditioned outdoor air is still dry HVAC unit is less than in a neutral air system, and the
enough to offset the latent load in the classrooms, but because airflow delivered by the dedicated outdoor air unit is the
it is delivered at a dry-bulb temperature that is much lower same for both configurations.
than the space temperature (52°F [11°C] vs. 74°F [23°C]), it Less supply airflow and less cooling capacity mean smaller
offsets a significant portion of local HVAC equipment, which
the sensible cooling load in Dedicated OA Cooling Capacity Supply Airflow can lower the initial cost and
the classrooms. This reduces System Configuration Of Local HVAC Unit Of Local HVAC Unit increase usable floor space, or
the sensible load that must “Neutral” 2.8 tons 1,500 cfm provide an acoustical benefit
be offset by the local HVAC To Space (9.8 kW) (0.7 m3/s) by keeping the same sized
unit, allowing the local units “Cold” 1.8 tons 1,050 cfm cabinet and operating the fan
to be sized for less airflow To Space (6.3 kW) (0.5 m3/s) at a lower speed.
and less cooling capacity “Neutral” 2.8 tons 1,500 cfm In addition, if the fan in the
than in a neutral air system To Units (9.8 kW) (0.7 m3/s) local HVAC unit cycles on
(Table 1).7 “Cold” 1.8 tons 1,500 cfm and off with the compressor or
Since both systems dehu- To Units (6.3 kW) (0.7 m3/s) two-position water valve—as
midify the same quantity of Table 1: Delivering conditioned OA “neutral” vs. “cold.” may be the case in a water-
outdoor air to the same leav- source heat pump or a fan-
ing air dew point, the required cooling capacity and airflow of coil unit—the runtime of the local fan will be less at part-load
the dedicated outdoor air unit are the same whether the outdoor conditions than in a neutral air system.
air is delivered neutral or cold. What happens if conditioned outdoor air is delivered to
Compared with a neutral air system, a dedicated outdoor air the local HVAC units, rather than directly to the spaces?
system that delivers cold air directly to the occupied spaces: When the conditioned outdoor air is delivered cold to the lo-
• Requires less overall cooling capacity. The required cooling cal HVAC units, it mixes with recirculated return air from the
capacity of each local HVAC unit is less than in a neutral air space ((Figure 1, right-hand graphic). The resulting mixed air
system, and the required capacity of the dedicated outdoor enthalpy is lower, which reduces the cooling capacity required
air unit is the same for both configurations. by the coils in the local units. Because the conditioned outdoor
• Requires less overall cooling energy for much of the year. air is not delivered directly to the space, the sensible cooling
By taking advantage of the sensible cooling already done by load in the space is unchanged, so supply airflow is unaffected
the dedicated outdoor air unit, the cold air system requires (Table 1). Also, since the local fan is tasked with delivering the

32 ASHRAE Journal ashrae.org July 2006


outdoor air to the space, it cannot cycle off without interrupting charge directly into an occupied space—below 45°F (7°C) for
ventilation to the space. example. In this case, the dehumidified outdoor air could be
When should the conditioned OA be reheated? While the reheated to a more traditional supply air temperature—55°F
conditioned outdoor air should be delivered cold whenever (13°C) for example.
possible, there are times when the dedicated outdoor air unit The second consideration has to do with proper selection of
should reheat the dehumidified outdoor air. the local units. The pre-matched components of packaged DX
The first consideration is occupant comfort. As explained equipment (rooftop units, packaged terminal air conditioners,
earlier, delivering the conditioned outdoor air at a dry-bulb water-source heat pumps) typically limit selection to a finite
temperature colder than the space offsets part of the sensible cfm/ton (m3/s/kW) range of application.
cooling load in the space. As explained earlier, if cold, conditioned outdoor air is
As the space sensible cooling load decreases—due to delivered directly to the local HVAC units, it reduces the cool-
changes in outdoor conditions and internal loads—it is pos- ing capacity (tons [kW]) required by the local unit. However,
sible that the cold, conditioned outdoor air may provide more supply airflow (cfm [m3/s]) is unaffected. This raises the
sensible cooling than the space requires. The result is that the cfm/ton (m3/s/kW) required of the local unit, possibly above
space dry-bulb temperature drops. the maximum allowed for the equipment.
To avoid overcooling, the local HVAC unit could add heat In the case where conditioned outdoor air is delivered direct-
to the space if a source of heat is available (i.e., if the boiler ly to local HVAC units that have a limited cfm/ton (m3/s/kW)
is not shut off for the season). If this occurs in only a few range for selection, the dehumidified outdoor air should be
spaces, the sensible cooling reheated (but not necessarily
energy benefit to the remain- all the way to neutral) to allow
ing spaces may offset the BAS proper selection of the local
heating energy needed for units. This is not an issue
these few spaces. However, if the conditioned outdoor
if the source of reheat energy air is delivered directly to
in the dedicated outdoor air the space.
OA
unit is recovered from another The third consideration is
part of the system (hot gas to avoid condensation. Since
reheat or an air-to-air heat ex- CA water-source heat pumps in-
changer, for example), it may stalled in the ceiling plenum
be more economical to reheat traditionally do not have mix-
the conditioned outdoor air to ing boxes, dedicated outdoor
avoid overcooling any of the CA CA air systems used with that
spaces. This will be discussed type of equipment sometimes
further in the next section of deliver the conditioned out-
SA T T SA
this article. door air in close proximity
In hotel guestrooms or to the return air inlet of each
dormitories, where the sen- heat pump. The outdoor air
sible cooling loads are often RA RA mixes with the recirculated
drastically different in various return air in the ceiling ple-
spaces, there may be many num prior to entering each
hours when overcooling oc- Figure 3: Resetting CA dry bulb based on critical space. local unit.
curs in at least one space. For In this configuration, the
these applications, it may be simpler to deliver the conditioned dry-bulb temperature of the conditioned outdoor air deliv-
outdoor air at a neutral temperature because the benefit of de- ered to the ceiling plenum should be well above the expected
livering the air cold occurs less frequently. But in classrooms dew-point temperature of the air within the plenum. If cold
or offices, space sensible cooling loads are relatively high air is dumped into the ceiling plenum, it could cool surfaces
during daytime hours. In fact, for some climates, classrooms (beams, electrical conduit, ceiling framework). At night, when
may never reach the point when overcooling occurs during the dedicated outdoor air unit is off, wind or operating exhaust
occupied hours. These applications are well-suited for deliver- fans may cause humid outdoor air to leak into the plenum,
ing the conditioned outdoor air cold. which might lead to condensation on these cold surfaces.
Finally, for applications that require lower-than-normal
space dew points, the outdoor air may be dehumidified to 3. Use System-Level Controls
the point where the dry-bulb temperature of the air leaving Many dedicated outdoor air systems are designed to deliver
the cooling coil is colder than the designer is willing to dis- conditioned outdoor air at a constant dry-bulb temperature

July 2006 ASHRAE Journal 33


and dew point that does not exceed a setpoint. This control spaces as possible without overcooling any space, avoiding
approach is simple because it allows the dedicated outdoor the need for any local units to activate their heating coils. This
air unit to operate independently of the local HVAC units. provides the greatest benefit when the dedicated outdoor air
However, implementing a few system-level control strategies unit uses recovered energy for reheat, thereby avoiding the
can help minimize the additional energy cost of separately use of “new” energy for reheat, both at the dedicated outdoor
treating outdoor air. air unit and at the local units.
Dynamically resetting the dry-bulb temperature of the con-
Resetting Reheat Capacity ditioned outdoor air provides a unique benefit in a two-pipe
First, in a system delivering the conditioned outdoor air system, especially if the dedicated outdoor air unit is a packaged
cold, reset the dry-bulb temperature delivered by the dedicated piece of equipment that is not connected to the chiller or boiler
outdoor air unit, so it uses reheat only when needed to avoid plant. When the two-pipe system is in cooling mode (boiler off),
overcooling any of the spaces. Why reheat the dehumidified the dry-bulb temperature supplied by the dedicated outdoor air
air to neutral on the hottest day of the summer when all spaces unit is reset upward (by modulating the reheat) just enough to
need cooling? Instead, deliver the air cold to offset some of prevent overcooling the critical space. When the system is in
the space sensible cooling loads. As mentioned earlier, this heating mode (chiller off), the temperature is reset downward
can also allow the local HVAC units to be downsized, which just enough to prevent overheating the critical space. This im-
helps offset some of the added cost of the dedicated outdoor proves occupant comfort during changeover periods, and can
air system. save energy by minimizing the number of times the system
How do you control the changes over between cooling
reheat coil to avoid overcool- and heating modes.
Total-Energy Recovery Wheel
ing any spaces? A simple ap-
proach would be to activate Resetting Dehumidification
the reheat coil—reheating the Dedicated OA Capacity
dehumidified outdoor air to Unit With RA Path When the sensible cooling
neutral—whenever the ambient RA load in the space is high, the
CA
temperature drops to the point local HVAC unit may offset
where the sensible load in some part of the latent load. When
spaces is expected to be low the latent load in the space is
enough to result in overcool- low, the need for dehumidi-
CA CA
ing (say 80°F [27°C], but this fication is also lessened. In
limit could be changed after a either situation, the dew point
few months of experience in RH for the conditioned outdoor
operating the system). air could be reset upward
Local
An even more effective way Units to reduce dehumidification
to implement this strategy is to Off energy.
use a building automation sys- A humidity sensor could be
tem (BAS) to monitor all of the installed in each space (or in
local HVAC units and to iden- Figure 4: After-hours humidity control. several representative spaces)
tify the critical space—that is, with a BAS polling these sen-
the space with the lowest sensible cooling load, which is most at sors to determine the critical space—that is, the space with the
risk of overcooling ((Figure 3). If the local units use modulating highest humidity. Based on a signal from the BAS, the dedicated
chilled-water coils, the BAS could monitor the position of each outdoor air unit then reduces its dehumidification capacity, rais-
chilled-water control valve. The space with the lowest cool- ing the leaving air dew point just enough to still maintain the
ing load is served by the unit whose control valve is the most humidity level in the critical space at the desired upper limit. By
nearly closed. Alternatively, the BAS could monitor the space responding to actual humidity conditions, the system maintains
temperatures; the critical space is the one with a temperature the humidity at or below the desired upper limit in all spaces
closest to its heating setpoint. while minimizing dehumidification energy.
Based on a signal from the BAS, the dedicated outdoor air
unit then increases its reheat capacity, resetting the leaving air 4. Consider After-Hours Humidity Control
dry-bulb temperature upward just enough to prevent the criti- When the dedicated outdoor air unit delivers conditioned
cal space from overcooling. (The dew point of the conditioned outdoor air directly to the spaces, adding a return air path per-
air is controlled independently to meet the humidity control mits after-hours humidity control without operating the local
requirements of the spaces.) HVAC terminals ((Figure 4). And, if the dedicated outdoor air
This optimization strategy provides conditioned outdoor unit is a packaged piece of equipment, it eliminates after-hours
air that offsets as much of the sensible cooling loads in the operation of a central chilled-water plant.

34 ASHRAE Journal ashrae.org July 2006


When after-hours dehumidification is required, the dedi- design and control these systems to lower both installed cost
cated outdoor air unit closes the outdoor air damper and opens and energy use.
the return air damper to avoid conditioning unneeded outdoor Consider delivering the conditioned outdoor air “cold”
air. Due to the low sensible cooling loads during this time, a whenever possible, and use recovered energy to reheat only
source of reheat in the dedicated outdoor air unit typically is when needed. Providing cold (rather than neutral) air from the
necessary to avoid overcooling the building. dedicated outdoor air unit offsets a portion of the space cooling
loads, allowing the local HVAC units to be downsized and use
5. Use Exhaust Air Energy Recovery less energy. In addition, implementing system-level control
Finally, because all the outdoor air is brought in at a central strategies and exhaust air energy recovery can help minimize
location, consider including an air-to-air energy recovery de- the additional energy cost of separately treating outdoor air.
vice to precondition the outdoor air (Figure 4). This reduces
operating costs and may allow downsizing of the mechanical References
1. Trane. 1965. Air Conditioning Manual.
cooling, dehumidification, heating, and humidification equip-
2. Murphy, J. and B. Bradley. 2004. “Better part-load dehumidi-
ment. Also, it can help justify the added cost of routing the fication.” Trane Engineers Newsletter 33(2).
building exhaust back to the dedicated outdoor air handler 3. Morris, W. 2003. “The ABCs of DOAS: dedicated outdoor air
when a return air path is desired for after-hours humidity con- systems.” ASHRAE Journal 45(5).
trol. In non-arid climates, total-energy (or enthalpy) recovery 4. Trane. 2003. Designing Dedicated Outdoor-Air Systems. (Trane
devices typically result in a greater potential for equipment Applications Engineering Guide SYS-APG001-EN).
downsizing, and more energy savings, than sensible-energy 5. U.S. Environmental Protection Agency. 2001. Mold Remediation
in Schools and Commercial Buildings, EPA 402-K-01-001 (March).
recovery devices.6
www.epa.gov/iaq/molds.
6. Murphy, J. 2002. Air-to-Air Energy Recovery in HVAC Systems.
Summary (Trane Applications Engineering Manual SYS-APM003-EN).
Many of the dedicated outdoor air systems being designed 7. Murphy, J. 2002. Dehumidification in HVAC Systems. (Trane
and installed today are suboptimal, but there are ways to Applications Engineering Manual SYS-APM004-EN).

Advertisement formerly in this space.

July 2006 ASHRAE Journal 37

You might also like