You are on page 1of 4

ST7009A,B,C,D

Electronic Programmable Timer


24-HOUR OR 7-DAY TIME SWITCHES
SPECIFICATION DATA
FEATURES
• Universal 24-hour or 7-day programming accurate to the
second.

• UL and CUL recognized components.

• Multiple on-off daily programs with unlimited flexibility.

• Program simplicity with a minimal number of keys and


program steps.

• Holiday programming.

• Built-in program backup.

• Daylight Savings Time changeover in the spring and fall.

ST7009A,C • Screw wiring terminals.

ST7009B,D

APPLICATION
The ST7009 family of one and two-switch Programmable Timers are All models feature large keys and a large LCD display for easy circular
compact time controls providing 24-hour or 7-day microprocessor- programming of schedules. The ST7009 allows for selection of any
based switching. Heavy duty 16A spdt relay contacts can switch low- combination of days and additional programming events per day.
or line-voltage loads. Up to 21 on and 21 off functions are available
per day. Built-in program backup provides retention of memory and time of
day during a power outage. The ST7009 features an automatic
These timers are applicable for time-of-day control of pumps, fans, internal recharging battery backup program for up to a two-week
heaters, HVAC control circuits, lighting and many other types of period. The ST7009 also offers a holiday programming schedule of
commercial and industrial equipment. one or more days that can be programmed up to a week in advance.

® U.S. Registered Trademark


Copyright © 1997 Honeywell Inc. • All Rights Reserved 68-3003
ST7009A,B,C,D ELECTRONIC PROGRAMMABLE TIMER

SPECIFICATIONS Channels:
ST7009A,C: 1.
ST7009B,D: 2.
IMPORTANT
The specifications given in this publication do not include Programs:
normal manufacturing tolerances; therefore, an individual 42 per day.
unit may not exactly match the listed specifications. Also, this Holiday Program:
product is tested and calibrated under closely controlled Yes.
conditions, and some minor differences in performance can
be expected if those conditions are changed. Reserve Carryover (Minimum):
2 weeks.
Models:
OS Number Type Input Voltage Channels Relay Output Battery Reserve
ST7009A1003 24-hour, 7-day 24V, 50/60 Hz 1 1 spdt 7-day
ST7009B1002 24-hour, 7-day 24V, 50/60 Hz 2 2 spdt 7-day
ST7009C1001 24-hour, 7-day 120V, 50/60 Hz 1 1 spdt 7-day
ST7009D1000 24-hour, 7-day 120V, 50/60 Hz 2 2 spdt 7-day

Daylight Savings Time Key: Shortest Switching Time:


Yes. 1 minute.
Power Input: Accuracy:
ST7009A,B: 24V, 50/60 Hz. + 4 minutes per yr.
ST7009C,D: 120V, 50/60 Hz. Ambient Temperature:
Power Consumption: -20°F (-28°C) to 140°F (60°C).
4 VA. Ambient Humidity:
Output: 0 to 95% RH, non-condensing.
ST7009A,C: 1 spdt relay. LCD Time Display:
ST7009B,D: 2 spdt relays. Selectable AM/PM or 24-hour.
Mounting: Manual 3-way Override:
ST7009A,C: Surface or DIN Rail. Temporary or permanent on or off.
ST7009B,D: Panel or Surface. LCD status indication display.
Switching Capacity: Contact Material:
16A resistive at 277 Vac. Silver cadmium oxide.
1000W tungsten at 240 Vac.
1/2 hp at 120 Vac; 1 hp at 240 Vac. Dimensions:
See Fig. 1.

3-1/4
(83)

DIN RAIL
MOUNTING

2 (51) 2-1/8 (54)


2-1/16 (52) 3 (76)

M12192

ST7009A,C

Fig. 1. ST7009A,C, ST7009B,D dimensions in in. (mm) (1 of 2).

68-3003 2
ST7009A,B,C,D ELECTRONIC PROGRAMMABLE TIMER

2-1/4 (57)
2-1/8 (54)
1-5/8 (41) 2-7/8 (73)

2-1/4
3 (57)
(76)
2-1/2
(64)

1 2 3 4 5 6 7 8 2-1/2 (64) M12191

ST7009B,D

Fig. 1. ST7009A,C, ST7009B,D dimensions in in. (mm) (2 of 2).

PROGRAMMING current year by entering the date with the m key and the
month with the h key. (If in military time, set the date with the h
key and the month with the m key). Example: April 7 is
Daylight Savings Time Changeover displayed as 04:07 if in AM/PM time, or 07:04 in military time.
For areas where Daylight Savings Time is not observed, please skip G Press the +1h key once. A 5 is displayed under Fr. Enter the
to Set Time and Day Clock section. date for Winter Daylight Savings Time changeover for the
current year by entering the date with the m key and the
The ST7009 offers manual or automatic Daylight Savings Time month with the h key. (If in military time, set the date with the h
changeover in the spring and fall. key and the month with the m key.)
H Press the key to save the data and exit the Daylight
Savings Time programming mode.
For manual changeover:
Press the + 1h key to set the clock time either ahead one hour or
back one hour. Set Time and Day Clock
A Select military (24:00 hr) or AM/PM time mode by pressing and
For automatic changeover: holding the h key while pressing the +1h key to toggle between
NOTE: The following programming steps need to be performed only military and AM/PM. (AM is displayed when in AM/PM mode.)
at initial installation, or if the Reset key is pressed at any B Press and hold the key while completing steps C
time. After programming is complete, the automatic time through F.
switch changes the time at 2:00 AM on the first Sunday of C If automatic changeover to Daylight Savings Time has not
April and the last Sunday of October until the year 2079. been programmed, press the +1h key once to set the timer
when Daylight Savings Time is in effect (+1h is displayed).
Entering programming mode: D Set the hour with the h key. If AM or PM is not displayed, the
A Select military (24:00 hr) or AM/PM time by simultaneously unit is in military time. See step A to change to AM/PM time.
pressing the +1h and h keys. (AM or PM is displayed when in E Set the minutes with the m key.
AM/PM time.) F Press the Day key repeatedly to select the day of the week
B Enter the Daylight Savings time by simultaneously pressing (1 is Monday, 7 is Sunday).
the +1h and Day keys once. A 1 is displayed under Mo. Then G Release the key; a colon flashes. If the days are also
enter today’s date with the m key and the month with the h flashing, the day of the week was not entered (see step F).
key. (For military time, set the date with the h key and the
month with the m key). Example: February 15 is displayed as Set Program Schedule
02:15 for AM/PM time, or as 15:02 in military time. A Press the Prog. key. is displayed.
C Press the +1h key once. A 2 is displayed under Tu. Then enter
the current year with the m key. If you go past the current year,
hold down the m key until the years scroll up to 2079 and then
back to 1995.
D Press the +1h key once. A 3 is displayed under We and AU Press the Prog. key again to display the number of free programs.
(for preset European dates). If European dates are desired, Fr 42 is displayed. Press the Prog. key again to advance to
press the key to enter the data and exit the Daylight the first program.
Savings Time programming mode.
B Press the key. The on symbol [ ] is displayed beneath
E Press the m key once. cHA is displayed (for entering North
CH1. Press the key again to toggle to off [ ] . Press
American dates).
the key again to toggle to on. Select either on or off.
C Press the h key to select the hour for switching time.
NOTE: If the m key is inadvertently pressed two times, HA is
D Press the m key to select the minute for switching time.
displayed. Press the m key two more times, or until
E If the program is used every day of the week (24-hour time
the display shows cHA. (HA is for specific dates and
control), press the Prog. key to advance to the next program.
is not currently used.)
F If 7-day time control is desired, press the Day key; a flashing
underline is displayed beneath Day 1. Press the Day key a
F Press the +1h key once. A 4 is displayed under Th. Enter the
second time to advance the underline to Day 2. To delete a
date for Summer Daylight Savings Time changeover for the

3 68-3003
ST7009A,B,C,D ELECTRONIC PROGRAMMABLE TIMER

day from the program, use the Day key to advance to that day with the key. Example: Programming was completed at
and press the Sel. (select) key. The chosen day flashes. 2:00 PM and CH1 was programmed to be on at 8:00 AM
Continue pressing the Day and Sel. keys to delete additional and off at 5:00 PM. After pressing the key, CH1 turns
days until only the desired days remain and the remaining off. Press to turn it on. Automatic operation begins at
days are not flashing on the display. the 5:00 PM off time.
G Press the Prog. key and repeat steps B through F to enter
additional programs for on and off times. Review and Change of Programs
A To review a program at any time, press the Prog. key. Each
NOTE: More than one off time program can be entered to
press of the Prog. key displays a program in the sequence it
gain automatic control of manual overrides.
was entered.
B To change a program, select the program to be changed with
H Press the key to enter the Run Mode.
the Prog. key, and enter the new time of day and/or days of
the week as done in the Set Holiday Program section. The old
Set Eighth Day Holiday/Vacation Program program is overwritten with the new selections. Press the
Multiple programs (more than one on and off time) can be entered for Prog. key to store the new program.
holidays or vacation periods. Example: Enter off, and 12:01 AM to C To delete an individual program, select the program as
shut off the load(s) on vacations and holidays. explained in step A and press the m key and then the h key
A Press the Prog. key, select on or off, and use h and m to enter until -:- is displayed. Press either the Prog. or the key
the hour and minutes, but do not select or delete any days. until -:- flashes. The program is deleted after a few seconds.
B Press the key. is displayed indicating the Eighth Day
Holiday/Vacation Program. Manual Override
C Press the key to enter the Run mode. The time switch is When in the Run Mode, ( symbol is displayed), press the
now permanently preset with the on/off schedule to be key to reverse the load status (switch the load off if on, or on if off).
implemented for holidays and extended vacation periods. See The hand symbol is displayed to indicate that the override is active.
Set Holiday Program section. At the next scheduled switching time, the automatic time control
resumes, eliminating the override.
Set Holiday Program Press the key a second time. [ ] is displayed indicating
The Holiday Program can be implemented at any time up to six days the load is switched permanently on.
in advance of the holiday(s) or vacation period. It can also be Press the key a third time. [ ] is displayed indicating the
activated on the holiday or first day of the vacation period. load is switched permanently off.
Press the key a fourth time to return to automatic
A When in the Run Mode, press the key. -:-HO is displayed.
programming. is displayed.
B Press the Day key to select the day of the week that the
Holiday Program should begin.
C Press the Sel. key to select the number of days that the
Holiday Program should run. (Enter up to 99 days. If the Sel. TERMINAL DESIGNATIONS
key is held down, the numbers scroll up rapidly to 99 and then
start over with 01).
ST7009A,C
D Press the key to store the program. The holiday symbol
NO NC
is displayed.
M
E To review or change the Holiday Program, press the key.
To cancel the Holiday Program, press the key a second time.
1 2 3 4 5
On the day the Holiday Program begins, the Eighth Day Program is
implemented at 12:00 AM Midnight taking priority over the regular INPUT ISOLATED CONTACTS
daily programs. The holiday symbol and the number of days of the
program run are displayed. Each day is counted down until all days of ST7009B,D
the holiday/vacation period are shown. When complete, the display NO NC NO NC
reverts to normal. To cancel the Holiday Program, press the key. M

IMPORTANT
The output relays switch on or off only at the programmed
1 2 3 4 5 6 7 8
times. After programming is complete, if the switch is
desired in the on position, it must be turned on manually CIRCUIT 1 CIRCUIT 2
INPUT ISOLATED CONTACTS M11346

Home and Building Control Home and Building Control Honeywell Asia Pacific Inc.
Honeywell Inc. Honeywell Limited-Honeywell Limitée Room 3213-3225
Honeywell Plaza 155 Gordon Baker Road Sun Hung Kai Centre
P.O. Box 524 North York, Ontario No. 30 Harbour Road
Minneapolis MN 55408-0524 M2H 2C9 Wanchai
Hong Kong
Honeywell Latin American Division Honeywell Europe S.A.
Miami Lakes Headquarters 3 Avenue du Bourget
14505 Commerce Way Suite 500 B-1140 Brussels Belgium
Miami Lakes FL 33016

Helping You Control Your World®


Printed in U.S.A. on recycled paper
68-3003 J.S. 2-97 containing at least 10%4post-consumer paper fibers