International standards ask for PO-levels below 5 pC. Many cable manufacturers want to measure down to 1 pC. The measuring sensitivity of a POmeasuring system is also limited by interference from the mains and airborne electromagnetic interference. The attenuation of a power cable increases with the measuring frequency which limits the sensitivity for PO-pulses originating far away from the cable end.
Original Description:
Original Title
e1-60 Partial Discharge Measurements on Power Cables
International standards ask for PO-levels below 5 pC. Many cable manufacturers want to measure down to 1 pC. The measuring sensitivity of a POmeasuring system is also limited by interference from the mains and airborne electromagnetic interference. The attenuation of a power cable increases with the measuring frequency which limits the sensitivity for PO-pulses originating far away from the cable end.
International standards ask for PO-levels below 5 pC. Many cable manufacturers want to measure down to 1 pC. The measuring sensitivity of a POmeasuring system is also limited by interference from the mains and airborne electromagnetic interference. The attenuation of a power cable increases with the measuring frequency which limits the sensitivity for PO-pulses originating far away from the cable end.
TEST SYSTEMS Hit
E1-60
Partial Discharge Measurements
on Power Cables
A. Jenni
September 802 HAEFELY il
HIGH VOLTAGE TECHNOLOGYYU
Partial Discharge Measurements
on Power Cables
A.Jenni
{In regard to PD-messurements a long cable does not
have like a lumped
capacitance. The high frequency characteristics must be considered in order to
choose a suitable measuring system.
International standards
turers want to meas
k for PD-levels below 5 pC. Many cable manufac:
ra down to 1 pC. The characteristic impedanc
HV cable
is between 10 and 60 ohms. This means that the measuring sensitivity must be
better than 1 pC on a load of 10 ohms.
The measuring sensitivity of a PD-
measuring system is algo limited by in-
terference from the mains and airborne
electromagnetic interference in the
ambient of manufacturing areas where
routine test fields are mostly located. As it
js costly to suppress interference in the
low frequency range, the cut-off fre-
‘quency should not be too low.
The attenuation of a power cable in-
creases with the measuring frequency
which limits the sensitivity for PD-pulses
originating far away from the cable end,
Therefore, the measuring frequency
should be as low as possible. It is
therefore most desirable that excessive
partial discharges in a long cable can be
located.
‘A PD-measuring system in a routine
test field must be easy to operate by
relatively low trained staff, The measuring
results should not leave too much room
for interpretation and they should be
reproducible. Investment and operating
cost for a PD-measuring system should be
as low as possible.
It fs obvious that the many conflicting
targets must lead to compromises in
many respects. There are a number of PD-
measuring systems commercially
available all with their advantages and
disadvantages. As far as the author
knows, none of the available systems
have been designed especially for cables.
Partial discharges in cable:
PD-pulses which can occur in a cable are
composed of a spectrum of frequencies
between OHz and several MHz. The
amplitude is the same over the whole fre-
quency range, Figure 1.1
t
‘Fig 1 Fraqooneyspecrum of 3 PO pula
APO pulse which is propagating along
a cable is subjected to distortions. Even
though the charge of the pulses does not
decrease significantly on its way, the
shape of the pulse changes. The upper
part of the frequency spectrum is
attenuated considerably more than the
lower part. The width of a PD-pulse which
is not distorted varies from a few 10 ns to
a few 100 ns, Figure 2.1)
Fig 2 OF Popul shape of PD-tte, 02 PO pulse
A PO-source in a cable always
Produces two PD-pulses, each with a
‘charge of 0/2. One is propagated towards
the near end A of the cable to which the
PD-detector is connected. The other is
propagated towards the far end B where it
is reflected. The reflection arrives at the
PD-detector with a time delay of At,
Figures 3 and 4.
t
4
Fig 4 PDspulse and refecton: Br tine delay of
If the PD-source is very close to the far
‘end, so that the time lag between the two
pulses is within the PD-pulse width, the
two pulses with the charge Q/2 appear at
the measuring system superimposed. The
resulting pulse has a charge of Q, Figure
5
Fig 5 Superposition of PD-pulse and is relection
No reflection occurs if the cable is ter-
inated by its characteristic impedance,
Figure 6. Only Q/2 appears at the near end
Of the cable even if the PD-site is very
close to the far end. 50 per cent of the
charge Is absorbed by the terminating
impedance. The characteristic impedance
‘of power cables varies between 10 and
60 ohms.
ae 7
Fig 21 Gable erat, Distance of POs fom far
nd8:POS PO measuting system
The travelling velocity v of a PD-pulse
in an XLPE cable is approximately
470 mlus. The distance of the PO-site
from the far end of the cable is calculated
28 follows:
O8-v-At
Fig 6 Cable terminated with ie charactoriie
Response of partial discharge
measuring systems
Up to now only the influence of the cable
‘on the PO-pulses were considered. Thepulses appearing at point A must_be
measured with @ measuring system. The
two pulses which appear at the entrance
of a PO-measuring system when PD on a
cable is measured can be superimposed.
Superposition occurs when a pulse is
followed by @ second pulse with a short
delay, before the first pulse is processed in
the measuring system
Depending on whether the resulting
output is increased or decreased only 2
positive or negative superposition is being
discussed, which means a positive or
negative measuring error. Negative super-
position is not allowed, The superposition
characteristics of a PD measuring system
depend on the measuring frequency, the
bandwidth and the types of filters used,
‘Two-pulse diagram
‘The two-pulse diagram of a PD-measuring
system is a useful tool for finding out
whether the system is adequate for
measurements on long power cables or
ot. It determines the superposition
characteristics and the pulse resolution
time of the system,
-'|
ig? Diagram with two puoe ganarator G:F Lond
‘resistor 80-120 brn, Cx Coupling copacion Td
Inet Unt Detector
Instead of a cable a two-pulse
‘generator is connected to the PD-detector
via @ coupling capacitor and input unit. An
auxiliary oscilloscope is connected in
parallel with the output of the two-pulse
‘generator, Figure 7. The pulses from the
generator are similar to those originating
from a cable with PD.
The pulse spacing can be varied
between O and 100ys. Assuming a
travelling velocity of 170 m/s the two-
pulse calibrator is good for cables in
which the PD site varies between O and
8500 m from the far end. The two-pulse
.gram, Figures 3 and 4, is received by
iting ‘the output signal versus pulse
separation time.
Fig 8 Two-plee dvaram typical for brond bard
In 18|the kind of response according to
Figure 8 is defined as alpha response. No
negative superposition occurs. For pulse
separation times below t, (about 5 us)
there is positive superposition, t, is also
referred to as pulse resolution’ time
Pulse pairs with a separation time longer
than t are measured as two separate
pulses.
the PD-site in the cable is varied by in-
jecting defined PD-pulses along the cable
PD of the very far end would still result in
positive superposition, notin the detector,
but in the cable, for a pulse separation
time below the pulse width, dotted line in
Figure 11
Fig 9 Twospulse Segram with negative supe/pae:
‘A PD-measuring system with a two-
pulse diagram according to Figure 9 has
according t0 51a beta response. PD from a
source with a distance between |; and |p
from the far end is measured with @
negative measuring error. This kind of
two-pulse diagram is typical for PD-
detectors with a relatively narrow band
width
According to I), is defined as the
critical cable tength. Cables shorter than |,
can be considered as lumped capacitance,
The positive superposition is always
above 1.4.
PD-measurement with
reflection suppressor
‘As already mentioned, negative super-
position errors can be avoided by ter
‘inating the cable with its characteristic
impedance when measuring with narrow-
bband detectors. Another solution with @
Fig 11 Two-gulee dagram tor PO-measurrvent
Influence of the cabl
attenuation
Two:pulse diagrams received from two-
pulse generators do not take into account
the attenuation of the cable.
The attenuation of a power cable
depends on the measuring frequency and
the type of cable. According to) the
‘attenuation at 100 kHz varies for different
types of power cables between 0.7 and
1.1 dB/km. At 500 kHz the attenuation is
between 1.7 and 3.1 dB/km,
if a two-pulse diagram is produced by
injecting defined PO-pulses along the
cable according to Figute 12, the resulting
diagram looks like Figure 13,
Fig 10 Diagram with retain suppressor AS
between input uit and detector
similar result is the electronic reflection
suppressor, Figure 10. This device locks
the input of the amplifier during some
50 ns after the first PD-pulse from the PD-
site has arcived. The reflected pulse can
therefore not enter the detector")
If the two-pulse diagram of such an
arrangement is plotted with a two-pulse
‘generator, the diagram shows no super-
position, neither positive nor negative.
‘The diagram looks slightly different when,
instead of using the two-pulse generator,
Fig 72 injection of pues along the cable with puke
generator PG
Description of new
PD-measuring system
Based on the above considerations a
PO-measuring system has been
developed, illustration No 1 and Figure 14.-Muzesion 1 PO-dectactr tye 560
To allow matching the impedance of
the input circuit to the measuring cable an
active input unit has been chosen. The
input unit provides, besides the PD-signal
also the power frequency signal for the
time base of the CRT, for fixing the zero
passage of the sine wave and for meast
19 the _ac-peak voltage of the test
voltage. Three different frequency ranges
were chosen for measuring partial dis-
charges,
Broad band measurement
The lower cut-off frequency is 40 kHz.
This is not ideal ifthe ultimate sensitiyity
is determined by the attenuation in a long
cable. A lower cut-off frequency leg
5 kH2) would result in a lower attenuation
of the measuring signal in along cable. In
reality, however, the sensitivity of the
‘measuring eystem is in most cases deter-
mined by the low frequency interference
level from the mains, appearing at the
input of the detector via the test voltage.
40 kHz is high enough to avoid most of
this interference,
Fig 18 Two pulse diagram of type 660. Mescuing
‘ange 40-400 tte
‘The upper cut-off frequency of 400 kHz
results in a sufficient relative bandwidth
10 assure that no negative superposition
can occur. Figure 15 shows the measured
two-pulse diagram for this frequency
range. The pulse resolution time is ~1 us.
ig 14 Block dngram of he PO-measuring system
u #3 Rim ao-soo ute, Wr Windom pocesor
row band measurement
PD-measurement with a narrow band
range has the advantage that interference
from the high voltage source can be
suppressed relatively easily with selective
filters The discussed PD-detector has two
nartow band measuring ranges, 108
£8 kHz and 250 + 16 kHz. The disadvan-
tage of narrow band measurement is the
possibility of negative superposition for
measurements on long cables. Having
two measuring ranges allows the
‘selecting of the one with the lower exter
nal interference level.
Fig 16 Two pee aagram of type 660 with norow
‘band measuring rnge 108 8 ite
Figure 16 shows the two-pulse
diagram of the narrow band ranges.
Cables up to 250m respectively 120m
can be tested without worrying about
negative superposition. This measuring
range is ideal for type tests on samples in
HV laboratories with a relatively high in-
terference level
The area between |, and |p
{corresponding to 260 m end 600 m with
8 propagation velocity of 170 mus) can
‘be measured correctly when the cable is
more than twice I long by measuring
from both ends of the cable,
Reflection suppressor
Both narrow band ranges can be operated
with a reflection suppressor in series,
Figure 17. This results in two-pulse
diagrams according to Figures 18 and 19,
ig 1? Two pulse diagram of type 560 with narrow
‘and measuring range and reflection suporestor 108
eKOnly the PD-pulse coming directly from
the PD-site is measured. The reflected
pulse is suppressed. The negative land
Positive) superposition disappears for
both frequency ranges allowing PD-
measurements on any length of cable
J] EHE)
Fig 18 POsocation with broad-band measuring
Fig 19 Pleture on CRT screen to locate PO tos
Read-out
The highest PD-pulse is indicated on a
igital display directly in pC. An XY
recorder which plots the PD-level as a
function of the test voltage can be con-
nected
An oscilloscope measures distinct PD-
pulses and surveys the PD-pattern. The
selected measuring range and the PD-
level is also indicated digitally on the
screen. This information is thus fixed on
photographs which may be taken, Instead
of the usual ellipse a double sine wave
hhas been chosen {ill 2). It can be con:
verted into a double straight line picture
(il 3). window gate with a variable
width. which can be shifted from
0-360°C, allows discrimination between
interference and PD outside the window.
‘A phase shift of 30° allows better
surveillance of PD located exactly in the
zero line crossing, il 4).
The measuring circuit is calibrated by
means of the external or internal
calibrator. Pulses corresponding to
defined partial discharges are injected via
2 low voltage or high voltage injection
‘capacitor into the measuring circuit.
A two-pulse generator used for check-
ing PD-detectors with the two-pulse
diagram is integrated into the calibrator
cE
Imystation & Double sine wave wit 30° phase shite
PD oncero costing
Imustaion 5 Pol discharge eabator with two:
puleegonoatortye 460
Partial discharge location
‘The new PD-detactor is also provided
with a broad band measuring range
limited to SOkHe and 10MHz, This
measuring range permits a very accurate
image of the PD-pulses coming out of the
cable to be depicted.
Tho time base of the oscilloscope can
be set so that the width of the screen cor-
responds to the length of the cable. This is
achieved by injecting a calibration pulse
Into the near end of the cable. The time
delay between the injected pulse and its
reflection determines the sweep time of
the oscilloscope,
The PO site in the cable can then be
determined by measuring the location of
its reflection on the scceen. |, corresponds
to the distance of the PD-site from the far
lend of the cable in percentage of the com:
plete length. Tests have shown that
‘method locates partial discharges above
10 pC with an accuracy of approximately
2 por cont. Partial discharge sites which
are very close together (cavity nests)
behave like a single PD-site
Conclusion
PD-measurements on solid insulated
power cables have become so important
that the development of @ PD-detector
tailored to PDsmeasurements on cables
appeared 10 be justified. The first ox:
perience gained with the new measuring
system is encouraging. It is well suited for
use in routine and type test fields of cable
makers. The optimised measuring fre-
{quencies and the reflection suppressor
reduces costs for interference control. The
measuring sensitivity of better than 1 pC
is reached even under extreme conditions
regarding cable length and impedance,
The PO-sites producing pulses above
10pC can be located with a sufficient
accuracy of 2 per cent of the cable length
The new PD-measuring system will
help to improve the quality of power
cables and to reduce costs for quality
References
(1) H Bors, Verlaan aur Messung von Tent
Bevscksicngung dee Einfvsses de Rabat,
(2) G'S Eager G Bader. O X Hoinich, R Suares
ne rel corona detection of power cabes,
(eee Tans. Vol PAS-€8 No’ 12 Dat 1969 po
Wrz,
A Lukaschewitech van Hove Ritter Schupoe,
Stockel” Bors, "Prufungen an. Kebain- und
(0872 Pan 813, 1960)
(4) PCE, Pubihation 124-980 1974
18) OrF #4 Kreuger, ‘Disenarge detection, methods
CGIGRE 1906 Paper No 209,
(6) PU Reyna, Parealecharge_ measuring
17) E Lemke, ‘A new method for P-maasuremant
fon polyethylene insltod power cables” 1H
Beind Katie. ‘Usber den Einfluss von imouls-
verrerengen eines Kabels aut da, Merewer
{anveig Diplomat am Schering nat 10
Hannover, 1978.
H Bors, Moglehkstn und Grenzen der Ortong
von "Tallertiadungen an kunsttoftraioten
itaton Unveretat
‘
oi
Hennover 1398
i]
Y~[MILE HABFELY & CO [TD
LEHENMATTSTRASSE
CH-4026 BASEL/SWITZERLAND
PHONE +4161, 315511
FAK +4161, 3112187
TELEX 962469
HAEFELY iil
HIGH VOLTAGE TECHNOLOGY