You are on page 1of 6

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

Series LFII Residential


Concealed Pendent Sprinklers, Flat Plate
4.2 K-factor
General (60,5) K-factor that provides the re-
quired residential flow rates at reduced
Description pressures, enabling smaller pipe sizes
and water supply requirements.
The Tyco® Rapid Response™ Series The Series LFII (TY2596) has been de-
LFII (TY2596) Residential Concealed signed with heat sensitivity and water
Pendent Sprinklers are decorative, fast distribution characteristics proven to
response, fusible solder sprinklers de- help in the control of residential fires
signed for use in residential occupan- and to improve the chance for occu-
cies such as homes, apartments, dor- pants to escape or be evacuated.
mitories, and hotels.
The Series LFII (TY2596) Residen-
The cover plate assembly conceals the tial Concealed Pendent Sprinklers are
sprinkler operating components above shipped with a Disposable Protective
the ceiling. The flat profile of the cover Cap. The Protective Cap is temporar-
plate provides the optimum aestheti- ily removed for installation, and then
cally appealing sprinkler design. In it can be replaced to help protect the
addition, the concealed design of the sprinkler while the ceiling is being in-
Series LFII (TY2596) provides 1/2 inch
(12,7 mm) vertical adjustment. This ad-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
Sprinkler/Model
justment provides a measure of flexi-
bility with regard to which the length of
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
Identification
fixed pipe drops to the sprinklers must
be cut.
pushing the ceiling product against
the Protective Cap. When the ceiling
Number
The Series LFII are to be used in wet installation is complete the Protective SIN TY2596
pipe residential sprinkler systems for Cap is removed and the Cover Plate
one-and two-family dwellings and mo- Assembly installed.
bile homes per NFPA 13D; wet pipe
notice
residential sprinkler systems for resi-
dential occupancies up to and includ- The Series LFII (TY2596) Residential
ing four stories in height per NFPA Concealed Pendent Sprinklers de-
13R; or, wet pipe sprinkler systems for scribed herein must be installed and
the residential portions of any occu- maintained in compliance with this
pancy per NFPA 13. document and with the applicable
The Series LFII (TY2596) has a 4.2 standards of the National Fire Pro-
tection Association, in addition to the
standards of any authorities having ju-
risdiction. Failure to do so may impair
the performance of these devices.
IMPORTANT The owner is responsible for maintain-
Always refer to Technical Data ing their fire protection system and de-
Sheet TFP700 for the “INSTALLER vices in proper operating condition.
WARNING” that provides cautions The installing contractor or sprinkler
with respect to handling and instal- manufacturer should be contacted
lation of sprinkler systems and com- with any questions.
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.

Page  of 6 MAY, 2008 TFP440


Page  of 6 TFP440

Minimum Flow (b) and Minimum Flow (b) and


Minimum Flow (b) and Residual Pressure Residual Pressure
Maximum Residual Pressure For Sloped Ceiling For Sloped Ceiling
Coverage Maximum For Horizontal Ceiling (Greater Than 2 Inch (Greater Than 4 Inch
Area (a) Spacing (Max. 2 Inch Rise Rise Up To Rise Up To
Ft. x Ft. Ft. (m) for 12 Inch Run) Max. 4 Inch Rise Max. 8 Inch Rise
(m x m) for 12 Inch Run) for 12 Inch Run)

160°F/71°C 160°F/71°C 160°F/71°C


Sprinkler Sprinkler Sprinkler
12 x 12 12 13 GPM (49,2 LPM) 18 GPM (68,1 LPM) 18 GPM (68,1 LPM)
(3,7 x 3,7) (3,7) 9.6 psi (0,66 bar) 18.4 psi (1,27 bar) 18.4 psi (1,27 bar)
14 x 14 14 14 GPM (53,0 LPM) 18 GPM (68,1 LPM) 18 GPM (68,1 LPM)
(4,3 x 4,3) (4,3) 11.1 psi (0,77 bar) 18.4 psi (1,27 bar) 18.4 psi (1,27 bar)
16 x 16 16 16 GPM (60,6 LPM) 18 GPM (68,1 LPM) 18 GPM (68,1 LPM)
(4,9 x 4,9) (4,9) 14.5 psi (1,00 bar) 18.4 psi (1,27 bar) 18.4 psi (1,27 bar)
18 x 18 18 20 GPM (75,7 LPM) 20 GPM (75,7 LPM) N/A
(5,5 x 5,5) (5,5) 22.7 psi (1,57 bar) 22.7 psi (1,57 bar)
20 x 20 20 24 GPM (90,8 LPM) 26 GPM (98,4 LPM) N/A
(6,1 x 6,1) (6,1) 32.7 psi (2,25 bar) 38.3 psi (2,64 bar)

(a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next
highest coverage area for which hydraulic design criteria are stated.
(b) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using
the nominal K-factor. Refer to Hydraulic Design Criteria Section for details.

TABLE A
NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA
FOR THE SERIES LFII (TY2596) RESIDENTIAL CONCEALED PENDENT SPRINKLER

Technical Retainer . . . . . . . . . . . . . . . . . . Brass


Cover Plate Ejection Spring ���������������
System Type. Only wet pipe systems
may be utilized.
Data . . . . . . . . . . . . . . . . . . Stainless Steel

DuPont Registered Trademark
Hydraulic Design. The minimum re-
quired sprinkler flow rate for systems
Approvals: designed to NFPA 13D or NFPA 13R
UL and C-UL Listed. NYC Approved
under MEA 44-03-E. Operation are given in Table A as a function of
temperature rating and the maximum
The Series LFII Concealed Pendent When exposed to heat from a fire, the allowable coverage areas. The sprin-
Sprinklers are only listed and approved Cover Plate, which is normally sol- kler flow rate is the minimum required
with the Series LFII Concealed Cover dered to the Support Cup at three discharge from each of the total num-
Plates having a factory applied finish. points, falls away to expose the Sprin- ber of “design sprinklers” as specified
kler Assembly. At this point the De- in NFPA 13D or NFPA 13R.
Maximum Working Pressure:
175 psi (12,1 bar) flector supported by the Arms drops For systems designed to NFPA 13, the
down to its operated position. The fus- number of design sprinklers is to be
Discharge Coefficient: ible link of the Sprinkler Assembly is
K=4.2 GPM/psi1/2 (60,5 LPM/bar1/2) the four most hydraulically demanding
comprised of two link halves that are sprinklers. The minimum required dis-
Temperature Rating: soldered together with a thin layer of charge from each of the four sprinklers
160°F/71°C Sprinkler with solder. When the rated temperature is is to be the greater of the following:
139°F/59°C Cover Plate reached, the solder melts and the two
• The flow rates given in Table A for
Vertical Adjustment: link halves separate allowing the sprin-
NFPA 13D and 13R as a function of
1/2 inch (12,7 mm) kler to activate and flow water.
temperature rating and the maximum
Finishes: allowable coverage area.
Refer to Ordering Procedure section. Design Criteria • A minimum discharge of 0.1 gpm/
Physical Characteristics: sq. ft. over the “design area” com-
Body . . . . . . . . . . . . . . . . . . . . . Brass The Tyco
����® Rapid Response™ Series
LFII (TY2596) Residential Concealed prised of the four most hydraulically
Cap . . . . . . . . . . . . . . . . . . . . . Bronze demanding sprinklers for the actual
Saddle . . . . . . . . . . . . . . . . . . . . Brass Pendent Sprinklers are UL and C-UL
Listed for installation in accordance coverage areas being protected by
Sealing Assembly . . . . . . . . . . . . . . . . the four sprinklers.
. . . . . . . . .Beryllium Nickel w/ Teflon† with the following criteria.
Soldered Link Halves . . . . . . . . Nickel Note: When conditions exist that are Obstruction To Water Distribution.
Lever . . . . . . . . . . . . . . . . . . . . Bronze outside the scope of the provided cri- Locations of sprinklers are to be in ac-
Compression Screw . . . . . . . . . Brass teria, refer to the Residential Sprinkler cordance with the obstruction rules of
Deflector . . . . . . . . . . . . . . . . . Copper Design Guide TFP490 for the manu- NFPA 13 for residential sprinklers.
Guide Pin Housing . . . . . . . . . Bronze
Guide Pins . . . . . . . . . Stainless Steel facturer's recommendations that may
Support Cup . . . . . . . . . . . . . . . . Steel be acceptable to the Authority Having
Cover Plate . . . . . . . . . . . . . . . Copper Jurisdiction.
TFP440 Page  of 6

Operational Sensitivity. The sprin-


BODY SEALING klers are to be installed relative to the
(1/2" NPT) ASSEMBLY ceiling mounting surface as shown in
Figure 3.
CAP Sprinkler Spacing. The minimum
SPRINKLER spacing between sprinklers is 8 feet
WRENCHING (2,4 m). The maximum spacing be-
AREA tween sprinklers cannot exceed the
SADDLE
length of the coverage area (Ref. Table
A) being hydraulically calculated (e.g.,
COMPRESSION maximum 12 feet for a 12 ft. x 12 ft.
SUPPORT
SCREW coverage area, or 20 feet for a 20 ft. x
CUP WITH
20 ft. coverage area).
ROLL FORMED
THREADS The Series LFII must not be used in
LEVER applications where the air pressure
above the ceiling is greater than
GUIDE that below. Down drafts through
PIN the Support Cup could delay sprin-
SOLDER LINK kler operation in a fire situation.
ELEMENT
GUIDE PIN
HOUSING
DEFLECTOR
(OPERATED
DEFLECTOR POSITION)
SPRINKLER/SUPPORT CUP
ASSEMBLY
WRENCH
RECESS
THREAD INTO RETAINER
SUPPORT CUP WITH THREAD
UNTIL MOUNTING DIMPLES
SURFACE IS
FLUSH WITH EJECTION
CEILING SPRING

PUSH WRENCH
IN TO ENSURE
ENGAGEMENT
SOLDER COVER PLATE/RETAINER COVER WITH SPRINKLER
TAB ASSEMBLY PLATE WRENCHING AREA

FIGURE 1 FIGURE 2
SERIES LFII (TY2596) RESIDENTIAL W-TYPE 18
CONCEALED PENDENT SPRINKLER SPRINKLER WRENCH

2-1/2" DIA. SPRINKLER-


(63,5 mm) 1/2" (12,7 mm) SUPPORT CUP
FACE OF
THREADED SPRINKLER ASSEMBLY
1/2"
NPT ADJUSTMENT FITTING
OPERATED
SPRINKLER

COVER
1-15/16"±1/4" PLATE
(49,2 mm
RETAINER
1/8" GAP ±6,4 mm)
(3,2 mm)

1/2" (12,7 mm)


COVER- SPRINKLER- MOUNTING 1" (25,4 mm)
RETAINER SUPPORT CUP 3/16" SURFACE
ASSEMBLY ASSEMBLY (4,8 mm)
3-3/16" DIA. DISPOSABLE DEFLECTOR IN
(81,0 mm) TIP PROTECTIVE CAP OPERATED POSITION

FIGURE 3
SERIES LFII (TY2596) RESIDENTIAL CONCEALED PENDENT SPRINKLER
INSTALLATION DIMENSIONS / PROTECTIVE CAP / ACTIVATED DEFLECTOR
Page  of 6 TFP440

Installation If the Sprinkler has been damaged and


the Deflector does not move up and
Automatic sprinklers must never be
painted, plated, coated, or otherwise
The Series LFII (TY2596) must be down freely, replace the entire Sprin- altered after leaving the factory. Modi-
installed in accordance with the kler assembly. Do not attempt to mod- fied or over heated sprinklers must be
following instructions: ify or repair a damaged sprinkler. replaced.
Step 6. Screw on the Cover Plate As- Care must be exercised to avoid dam-
notice sembly until its flange comes in con- age -before, during, and after installa-
Damage to the fusible Link Assembly tact with the ceiling. tion. Sprinklers damaged by dropping,
during installation can be avoided by striking, wrench twist/slippage, or the
Do not continue to screw on the Cover
handling the sprinkler by the support like, must be replaced.
Plate Assembly such that it lifts a ceil-
cup only (i.e., do not apply pressure to ing panel out of its normal position. The owner is responsible for the in-
the fusible link Assembly). spection, testing, and maintenance of
If the Cover Plate Assembly cannot
A 1/2 inch NPT sprinkler joint should their fire protection system and devic-
be engaged with the Mounting Cup
be obtained with a minimum to max- es in compliance with this document,
or the Cover Plate Assembly cannot
imum torque of 7 to 14 ft.lbs. (9,5 to as well as with the applicable stan-
be engaged sufficiently to contact the
19,0 Nm). Higher levels of torque may dards of the National Fire Protection
ceiling, the Sprinkler Fitting must be
distort the sprinkler inlet with conse- Association (e.g., NFPA 25), in addition
repositioned.
quent leakage or impairment of the to the standards of any other authori-
sprinkler. ties having jurisdiction. The installing
Do not attempt to compensate for in- Care and contractor or sprinkler manufacturer
should be contacted relative to any
sufficient adjustment in the Cover
Plate/Retainer Assembly by under-or Maintenance questions.
over-tightening the Sprinkler. Read- The Tyco
����® Rapid Response™ Series notice
just the position of the sprinkler fitting LFII (TY2596) must be maintained
to suit. and serviced in accordance with the The owner must assure that the sprin-
following instructions: klers are not used for hanging of any
Step 1. The sprinkler must only be objects and that the sprinklers are only
installed in the pendent position and cleaned by means of gently dusting
with the centerline of the sprinkler notice
with a feather duster; otherwise, non-
perpendicular to the mounting Absence of a Cover Plate may delay the operation in the event of a fire or inad-
surface. sprinkler operation in a fire situation. vertent operation may result.
Step 2. Remove the Protective Cap. When properly installed, there is a Automatic sprinkler systems should be
Step 3. With pipe thread sealant nominal 1/8 inch (3,2 mm) air gap be- inspected, tested, and maintained by a
applied to the pipe threads, and using tween the lip of the Cover Plate and qualified Inspection Service in accor-
the W-Type 18 Wrench shown in Figure the ceiling, as shown in Figure 3. This dance with local requirements and/or
2, install and tighten the Sprinkler/ air gap is necessary for proper oper- national codes.
Support Cup Assembly into the fitting. ation of the sprinkler by allowing heat
The W-Type 18 Wrench will accept a flow from a fire to pass below and
1/2 inch ratchet drive. above the Cover Plate to help assure
appropriate release of the Cover Plate
Step 4. Replace the Protective Cap in a fire situation. If the ceiling is to be
by pushing it upwards until it bottoms repainted after the installation of the
out against the Support Cup. The Sprinkler, care must be exercised to
Protective Cap helps prevent damage ensure that the new paint does NOT
to the Deflector and Guide Pins during seal off any of the air gap.
ceiling installation and/or during
application of the finish coating of the Factory painted Cover Plates MUST
ceiling. It may also be used to locate NOT be repainted. They should be re­
the center of the clearance hole by placed, if necessary, by factory paint-
gently pushing the ceiling material ed units. Non-factory applied paint
against the center point of the Cap. may adversely delay or prevent sprin-
kler operation in the event of a fire.
notice Do not pull the Cover Plate relative to
As long as the protective Cap remains the Enclosure. Separation may result.
in place, the system is considered to Before closing a fire protection system
be “Out Of Service”. main control valve for maintenance
Step 5. After the ceiling has been work on the fire protection system
completed with the 2-1/2 inch (63 mm) which it controls, permission to shut
diameter clearance hole and in prep- down the affected fire protection sys-
aration for installing the Cover Plate tem must be obtained from the prop-
Assembly, remove and discard the er authorities and all personnel who
Protective Cap, and verify that the De- may be affected by this action must be
flector moves up and down freely. notified.
Sprinklers which are found to be leak-
ing or exhibiting visible signs of corro-
sion must be replaced.
TFP440 Page  of 6

Limited Ordering
Warranty Procedure
Products manufactured by Tyco Fire When placing an order, indicate the
& Building Products (TFBP) are war­ full product name. Contact your local
ranted solely to the original Buyer for distributor for availability.
ten (10) years against defects in mate­ Sprinkler Assembly:
rial and workmanship when paid for Series LFII (TY2596), K=4.2, Resi-
and properly installed and maintained dential Concealed Pendent Sprin-
under normal use and service. This kler without Cover Plate Assembly,
warranty will expire ten (10) years from P/N 51-122-1-160.
date of shipment by TFBP. No warran-
ty is given for products or com­ponents Cover Plate Assembly:
manufactured by companies not af- Cover Plate Assembly having a (spec-
filiated by ownership with TFBP or for ify) finish for the Series LFII (TY2596),
products and components which have K=4.2, Residential Concealed Pendent
been subject to misuse, improper in- Sprinkler, P/N (specify).
stallation, corrosion, or which have not Chrome. . . . . . . . . . . . . . . . . . . . P/N 56-122-9-135
been installed, maintained, modi­fied or Signal White (a)
repaired in accordance with ap­plicable (RAL 9003). . . . . . . . . . . . . . . . P/N 56-122-4-135
Standards of the National Fire Protec- Pure White (b)
tion Association, and/or the standards (RAL 9010). . . . . . . . . . . . . . . . P/N 56-122-3-135
of any other Authorities Having Juris- Custom . . . . . . . . . . . . . . . . . . . P/N 56-122-X-135
diction. Materials found by TFBP to be (a) Previously known as Bright White.
defective shall be either repaired or re- (b) Eastern Hemisphere sales only.
placed, at TFBP’s sole option. TFBP
neither assumes, nor authorizes any Sprinkler Wrench:
person to assume for it, any other ob- Specify: W-Type 18 Sprinkler Wrench,
ligation in connection with the sale of P/N 56-000-1-265.
products or parts of prod­ucts. TFBP
shall not be responsible for sprinkler
system design errors or inac­curate or
incomplete information sup­plied by
Buyer or Buyer’s repre­sentatives.
In no event shall TFBP be liable, in
contract, tort, strict liability or under
any other legal theory, for incidental,
indirect, special or consequential dam­
ages, including but not limited to labor
charges, regardless of whether TFBP
was informed about the possibility of
such damages, and in no event shall
TFBP’s liability exceed an amount
equal to the sales price.
The foregoing warranty is made in lieu
of any and all other warranties, ex-
press or implied, including warranties
of merchantability and fitness for a
particular purpose.
This limited warranty sets forth the ex­
clusive remedy for claims based on
failure of or defect in products, materi­
als or components, whether the claim
is made in contract, tort, strict liability
or any other legal theory.
This warranty will apply to the full ex­
tent permitted by law. The invalidity,
in whole or part, of any portion of this
warranty will not affect the remainder.
Page  of 6 TFP440

© 2008 TYCO FIRE & BUILDING PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446

You might also like