AIR HEATER
HANS-PETTER HALVORSEN, 2010.02.09
Faculty of Technology, Postboks 203, Kjølnes ring 56, N-3901 Porsgrunn, Norway. Tel: +47 35 57 50 00 Fax: +47 35 57 54 01
TABLE OF CONTENTS
1 Introduction ................................................................................................................................................... 3
3 NI USB-6008 ................................................................................................................................................... 6
2
1 INTRODUCTION
This document gives a short description of the Air Heater Lab Equipment.
The focus will be to connect the system to a PC and create a simulation and control system in LabVIEW, C#.NET,
etc.
A proper development tool would be LabVIEW with “LabVIEW Control Design & Simulation Module” and
“LabVIEW PID and Fuzzy Logic Toolkit”.
A proper DAQ device would be the NI USB-6008 DAQ device from National Instruments, the inventor of
LabVIEW. The NI USB-6008 DAQ device is simple to configure and use.
The NI USB-6008 DAQ device is described in detail in the document “NI USB-6008 DAQ Device.pdf”.
3
2 SYSTEM DESCRIPTION
The Figure shows an air tube with heater and temperature sensor(s).
2.1 FEATURES
Fan: A fan makes air flow through the tube. The fan is operated manually with a knob. The fan position is
indicated or measured by a voltage signal which is in the range 2 - 5 V (min, max fan speed). This voltage signal
can be measured between two terminals. The normal fan speed is defined to be the maximum speed. (We do
not know the actual volumetric flow, but this information is not necessary here.)
Heater: The air is heated by an electrical heater. The supplied power is controlled by an external voltage signal
in the range 0 - 5 V (min power, max power). This heater control signal must be applied between two
terminals. This voltage is used to control a Pulse Width Modulator (PWM) which connects/disconnects the
mains voltage to the heater.) The PWM signal is indicated by a lamp. The PWM device requires 24 VDC power
supply, which is produced by an AC/DC converter.
Temperature sensors: Two Pt100 temperature elements are available. You can use any of these, but
Temperature sensor 1 may be regarded the default sensor. These two sensors have been calibrated equally.
The sensor signals are available as voltage signals at their respective terminals. The range is 1 - 5 V, and this
o
voltage range corresponds to the temperature range 20 - 50 C (with a linear relation). The normal sensor
position is defined to be the outermost position in the tube.
4
5 System Description
Analog I/O device: The Figure shows the NI USB-6008 device, but any I/O device supporting the above voltage
ranges can be used.
Controllers: A temperature control system can be implemented using one of the PID control functions in
LabVIEW. Alternatively, an industrial process controller can be used, for example the Fuji PYX5 PID-controller.
where,
In a simulator based on this model a proper initial value of Tout should be added. This initial value is applied to
the integrator in a block diagram representation of the model.
Note! You can adjust the parameters (θt, Kh, θd, Tenv) of the model by some simple experiments where you run
the simulator in parallel with the real process.
NI USB-6008 DAQ device is a simple and low-cost multifunction I/O device from National Instruments.
The NI USB-6008 is well suited for education purposes due to its small size and easy USB connection.
The NI USB-6008 DAQ device is described in detail (how the NI USB-6008 DAQ device works and how to use it
in LabVIEW) in the document “NI USB-6008 DAQ Device.pdf”.
6
4 LABVIEW CONTROL DESIGN & SIMULATION MODULE
LabVIEW (short for Laboratory Virtual Instrumentation Engineering Workbench) is a platform and development
environment for a visual programming language from National Instruments. The graphical language is named
"G". For more information about LabVIEW, go through the training kit “An Introduction to LabVIEW”. This
document and other information about LabVIEW are available from: http://home.hit.no/~hansha/.
In LabVIEW there is an additional module for design and simulation of control systems, called “LabVIEW
Control Design and Simulation Module” and a toolkit called “LabVIEW PID and Fuzzy Logic Toolkit”.
Control Design and Simulation VIs are available from the “Control Design and Simulation” palette:
In the “Simulation” Sub palette we have the “Control and Simulation Loop” which is very useful in simulations:
In the “Continuous Linear Systems” Sub palette we want to create a simulation model:
7
8 LabVIEW Control Design & Simulation Module
The most used blocks are Integrator, Transport Delay, State-Space and Transfer Function.
The “Signal Arithmetic” Sub palette is also useful when creating a simulation model:
Example: Simulation
Below we see an example of a simulation model using the Control and Simulation Loop.
Click on the border of the simulation loop and select “Configure Simulation Parameters…”
In this window you set some Parameters regarding the simulation, some important are:
Final Time (s) – set how long the simulation should last. For an infinite time set “Inf”.
Enable Synchronized Timing - Specifies that you want to synchronize the timing of the Control &
Simulation Loop to a timing source. To enable synchronization, place a checkmark in this checkbox and
then choose a timing source from the Source type list box.
You may also set some of these Parameters in the Block Diagram:
You may use the mouse to increase the numbers of Parameters and right-click and select “Select Input”.
In the “PID” Sub palette we have the functions/SubVIs for PID Control.
Below we see how we can use the PID Advanvanced.vi in order to control a simulated Model.