You are on page 1of 114

Power Distribution Systems 1.

0-1
January 2008
Sheet 01 001

Power Distribution
Systems
Contents i
Power Distribution Systems Grounding/Ground Fault Protection
System Design Grounding — Equipment, ii
Basic Principles. . . . . . . . . . . 1.1-1 System, MV System,
Modern Electric Power LV System . . . . . . . . . . . . . . 1.4-6
Technologies . . . . . . . . . . . 1.1-1 Ground Fault Protection . . . . 1.4-11 1
Goals of System Design . . . 1.1-2 Lightning and Surge
Voltage Classifications; BILs — Protection . . . . . . . . . . . . . . 1.4-14
Basic Impulse Levels . . . . . 1.1-4 Grounding Electrodes. . . . . . 1.4-14 2
3-Phase Transformer Power Quality
Winding Connections . . . . 1.1-5 Terms, Technical Overview . . 1.4-15
Types of Systems — Radial, TVSS . . . . . . . . . . . . . . . . . . . 1.4-16
3
Loop, Selective, Two-Source, Harmonics and
Sparing Transformer, Spot
Network, Distribution . . . . 1.1-6
Nonlinear Loads . . . . . . . . . 1.4-18 4
UPS . . . . . . . . . . . . . . . . . . . . 1.4-22
Health Care Facility Other Application Considerations
Design Considerations . . . 1.1-14 5
Secondary Voltage . . . . . . . . 1.4-28
Generator Systems . . . . . . 1.1-17
Energy Conservation . . . . . . 1.4-29
Generator System Design
Building Control Systems . . 1.4-30
Types of Generators . . . . . . . 1.2-1
Cogeneration. . . . . . . . . . . . . 1.4-30
6
Generator Systems . . . . . . . 1.2-2
Emergency Power. . . . . . . . . 1.4-30
Generator Grounding. . . . . . 1.2-3
Generator Controls. . . . . . . . 1.2-4
Peak Shaving. . . . . . . . . . . . . 1.4-31 7
Sound Levels. . . . . . . . . . . . . 1.4-32
Generator Short Circuit
Characteristics . . . . . . . . . . 1.2-4 Reference Data
Generator Protection . . . . . . 1.2-5 IEEE Protective Relay 8
Numbers . . . . . . . . . . . . . . . 1.5-1
System Analysis
Codes and Standards . . . . . . 1.5-6
Systems Analysis . . . . . . . . . 1.3-1
Motor Protective
9
Short Circuit Currents . . . . . 1.3-2
Device Data . . . . . . . . . . . . . 1.5-7
Fault Current Waveform
Chart of Short Circuit 10
Relationships . . . . . . . . . . . 1.3-3
Currents for Transformers . . 1.5-9
Fault Current Calculations
Transformer Full
and Methods Index . . . . . . 1.3-4
Determine X and R from
Load Amperes 11
and Impedances . . . . . . . . . 1.5-10
Transformer Loss Data . . . 1.3-19
Transformer Losses,
Voltage Drop
Considerations . . . . . . . . . . 1.3-23
TP-1 Losses . . . . . . . . . . . . . 1.5-12 12
Power Equipment Losses . . . 1.5-13
System Application Considerations
NEMA Enclosure Definitions . . 1.5-13
Capacitors/Power Factor. . . 1.4-1
Cable R, X, Z Data . . . . . . . . . 1.5-15 13
Overcurrent Protection
Conductor Ampacities . . . . . 1.5-16
and Coordination . . . . . . . . 1.4-3
Conductor Temperature 14
Protection of Conductors . . . 1.4-5
Ratings . . . . . . . . . . . . . . . . 1.5-16
Circuit Breaker Cable
Formulas and Terms . . . . . . . 1.5-18
Temperature Ratings . . . . . 1.4-5
Zone Selective Interlocking . 1.4-5
Seismic Requirements . . . . . 1.5-19 15
Ground Fault Protection . . . 1.4-6
Suggested Ground 16
Fault Settings . . . . . . . . . . . . . 1.4-6

17

18

19

20
Designing a Distribution System 21

CA08104001E For more information visit: www.eaton.com


1.0-2 Power Distribution Systems
January 2008
Sheet 01 002

This page intentionally left blank.


i

ii

10

11

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-1
January 2008 System Design
Sheet 01 003

Basic Principles The basic principles or factors requir- Modern Electric Power i
ing consideration during design of
The best distribution system is one the power distribution system include: Technologies
that will, cost effectively and safely,
■ Functions of structure, present Several new factors to consider in ii
supply adequate electric service to
and future. modern power distribution systems
both present and future probable
■ Life and flexibility of structure. result from two relatively recent
loads — this section is included to aid
in selecting, designing and installing ■ Locations of service entrance and
changes. The first recent change is 1
utility deregulation. The traditional
such a system. distribution equipment, locations
dependence on the utility for problem
and characteristics of loads,
The function of the electric power locations of unit substations.
analysis; energy conservation mea- 2
distribution system in a building or surements and techniques; and a
■ Demand and diversity factors simplified cost structure for electricity
installation site is to receive power at
of loads.
one or more supply points and deliver
■ Sources of power; including
has changed. The second change is less 3
it to the individual lamps, motors, and obvious to the designer yet will have
all other electrically operated devices. normal, standby and emergency an impact on the types of equipment
The importance of the distribution (see Section 42). and systems being designed. It is the 4
system to the function of a building ■ Continuity and quality of diminishing quantity of qualified build-
makes it almost imperative that the power available and required ing electrical operators; maintenance
best system be designed and installed. (see Section 41). departments; and facility engineers. 5
■ Energy efficiency and management. Modern electric power technologies
In order to design the best distribution
system, the system design engineer ■ Distribution and utilization voltages. may be of use to the designer and
must have information concerning the ■ Bus and/or cable feeders. building owner in addressing these
6
loads and a knowledge of the various ■ Distribution equipment and new challenges. The advent of micro-
types of distribution systems that are processor devices (smart devices)
applicable. The various categories of
motor control.
into power distribution equipment has
7
■ Power and lighting panelboards
buildings have many specific design expanded facility owners’ options and
and motor control centers.
challenges, but certain basic principles capabilities, allowing for automated
are common to all. Such principles, ■ Types of lighting systems. communication of vital power system
8
if followed, will provide a soundly ■ Installation methods. information (both energy data and
system operation information) and
executed design. ■ Power monitoring systems.
electrical equipment control.
9
■ Electric utility requirements.
These technologies may be grouped as:
10
■ Power monitoring and control.
■ Building management systems
interfaces. 11
■ Lighting control.
■ Automated energy management.
12
■ Predictive diagnostics.
Various sections of this guide cover
the application and selection of such 13
systems and components that may be
incorporated into the power equip-
ment being designed. See Sections 2, 14
3, 4, 23 and 43.
15

16

17

18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.1-2 Power Distribution Systems
System Design January 2008
Sheet 01 004

i Goals of System Design 2. Minimum Initial Investment: 4. Maximum Flexibility and


The owner’s overall budget for Expendability: In many industrial
When considering the design of an first cost purchase and installa- manufacturing plants, electrical
electrical distribution system for a tion of the electrical distribution utilization loads are periodically
ii given customer and facility, the electri- system and electrical utilization relocated or changed requiring
cal engineer must consider alternate equipment will be a key factor changes in the electrical distribu-
design approaches which best fit the in determining which of various tion system. Consideration of the
1 following overall goals. alternate system designs are to be layout and design of the electrical
selected. When trying to minimize distribution system to accommo-
1. Safety: The No. 1 goal is to design initial investment for electrical date these changes must be con-
2 a power system which will not equipment, consideration should sidered. For example, providing
present any electrical hazard to be given to the cost of installation, many smaller transformers or
the people who utilize the facility, floor space requirements and pos- loadcenters associated with a
3 and/or the utilization equipment sible extra cooling requirements as given area or specific groups of
fed from the electrical system. well as the initial purchase price. machinery may lend more flexibility
It is also important to design a for future changes than one large
4 system which is inherently safe 3. Maximum Service Continuity: transformer; the use of plug-in
for the people who are responsi- The degree of service continuity busways to feed selected equip-
ble for electrical equipment and reliability needed will vary ment in lieu of conduit and wire
5 maintenance and upkeep. depending on the type and use may facilitate future revised
of the facility as well as the loads equipment layouts.
The National Electrical Code or processes being supplied by
6 (NEC), NFPA 70 and NFPA 70E, the electrical distribution system. In addition, consideration must be
as well as local electrical codes For example, for a smaller com- given to future building expansion,
provide minimum standards and mercial office building a power and/or increased load require-
7 requirements in the area of wiring outage of considerable time, say ments due to added utilization
design and protection, wiring several hours, may be acceptable, equipment when designing the
methods and materials as well as whereas in a larger commercial electrical distribution system.
8 equipment for general use with
the overall goal of providing safe
building or industrial plant only In many cases considering trans-
a few minutes may be acceptable. formers with increased capacity
electrical distribution systems and In other facilities such as hospitals, or fan cooling to serve unexpected
9 equipment. many critical loads permit a maxi- loads as well as including spare
The NEC also covers minimum mum of 10 seconds outage and additional protective devices and/
requirements for special occupan- certain loads, such as real-time or provision for future addition of
10 cies including hazardous locations computers, cannot tolerate a loss these devices may be desirable.
and special use type facilities such of power for even a few cycles. Also to be considered is increasing
as health care facilities, places of appropriate circuit capacities or
11 Typically, service continuity and quantities for future growth.
assembly, theaters, etc. and the reliability can be increased by:
equipment and systems located in Power monitoring communication
these facilities. Special equipment A. Supplying multiple utility power
12 and special conditions such as sources or services.
systems connected to electronic
metering can provide the trending
emergency systems, standby and historical data necessary for
B. Supplying multiple connection
systems and communication sys-
13 tems are also covered in the code.
paths to the loads served. future capacity growth.

C. Using short-time rated power


It is the responsibility of the design
14 circuit breakers.
engineer to be familiar with the
NFPA and NEC code requirements D. Providing alternate customer-
as well as the customer’s facility, owned power sources such as
15 process, and operating procedures; generators or batteries supplying
to design a system which protects uninterruptable power supplies.
personnel from electrical live
16 conductors and utilizes adequate E. Selecting the highest quality elec-
circuit protective devices which will trical equipment and conductors.
selectively isolate overloaded or F. Using the best installation methods.
17 faulted circuits or equipment as
quickly as possible. G. Designing appropriate system
alarms, monitoring and diagnostics.
18
H. Selecting preventative mainte-
nance systems or equipment to
19 alarm before an outage occurs.

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-3
January 2008 System Design
Sheet 01 005

5. Maximum Electrical Efficiency 7. Maximum Power Quality: Summary


(Minimum Operating Costs): The power input requirements of
It is to be expected that the engineer
i
Electrical efficiency can generally all utilization equipment has to be
be maximized by designing sys- considered including the accept- will never have complete load infor-
tems that minimize the losses in able operating range of the equip- mation available when the system is ii
conductors, transformers and utili- ment and the electrical distribution designed. The engineer will have to
zation equipment. Proper voltage system has to be designed to meet expand the information made avail-
level selection plays a key factor these needs. For example, what able to him on the basis of experience 1
in this area and will be discussed is the required input voltage, cur- with similar problems. Of course, it
later. Selecting equipment, rent, power factor requirement? is desirable that the engineer has as
such as transformers, with lower Consideration to whether the much definite information as possible 2
operating losses, generally means loads are affected by harmonics concerning the function, requirements,
higher first cost and increased (multiples of the basic 60 cycle and characteristics of the utilization
floor space requirements; thus, per second sine wave) or generate devices. The engineer should know 3
there is a balance to be considered harmonics must be taken into whether certain loads function
between the owner’s utility energy account as well as transient separately or together as a unit, the
change for the losses in the trans- voltage phenomena. magnitude of the demand of the loads 4
former or other equipment versus viewed separately and as units, the rated
the owner’s first cost budget and The above goals are interrelated voltage and frequency of the devices,
cost of money. and in some ways contradictory. their physical location with respect 5
As more redundancy is added to to each other and with respect to the
6. Minimum Maintenance Cost: the electrical system design along source and the probability and possi-
Usually the simpler the electrical with the best quality equipment bility of the relocation of load devices 6
system design and the simpler to maximize service continuity, and addition of loads in the future.
the electrical equipment, the less flexibility and expandability, and
Coupled with this information, a
the associated maintenance costs power quality, the more initial
knowledge of the major types of electric
7
and operator errors. As electrical investment and maintenance
systems and equipment become are increased. Thus, the designer power distribution systems equips the
engineers to arrive at the best system
more complicated to provide must weigh each factor based
design for the particular building.
8
greater service continuity or on the type of facility, the loads
flexibility, the maintenance costs to be served, the owner’s past It is beyond the scope of this guide to
and chance for operator error experience and criteria. present a detailed discussion of loads 9
increases. The systems should be that might be found in each of several
designed with an alternate power types of buildings. Assuming that the
circuit to take electrical equipment design engineer has assembled the 10
(requiring periodic maintenance) necessary load data, the following
out of service without dropping pages discuss some of the various
essential loads. Use of drawout types of electrical distribution systems 11
type protective devices such as that can be utilized. The description of
breakers and combination starters types of systems, and the diagrams
can also minimize maintenance used to explain the types of systems 12
cost and out-of-service time. on the following pages omits the
location of utility revenue metering
equipment for clarity. A discussion of 13
short circuit calculations, coordination,
voltage selection, voltage drop, ground
fault protection, motor protection, and 14
other specific equipment protection
is also presented.
15

16

17

18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.1-4 Power Distribution Systems
System Design January 2008
Sheet 01 006

i Voltage Classifications Table 1.1-2. Metal-Clad Switchgear Voltage


and Insulation Levels (From ANSI/IEEE
Voltage Recommendations by
ANSI and IEEE standards define C37.20.2-1999) Motor Horsepower
various voltage classifications for Rated Maximum Impulse Some factors affecting the selection
ii single-phase and 3-phase systems. Voltage (kV rms) Withstand (kV) of motor operating voltage include:
The terminology used divides voltage
4.76 60 ■ Motor, motor starter and cable
classes into: 8.25 95
1 15.0 95
first cost.
■ Low voltage. ■ Motor, motor starter and cable
27.0 125 installation cost.
■ Medium voltage. 38.0 150
2 ■ High voltage. ■ Motor and cable losses.
■ Extra-high voltage. Table 1.1-3. Metal-Enclosed Switchgear ■ Motor availability.
Voltage and Insulation Levels ■ Voltage drop.
3 ■ Ultra-high voltage.
(From ANSI C37.20.3-1987)
■ Qualifications of the building
Table 1.1-1 presents the nominal sys- Rated Maximum Impulse operating staff; and many more.
tem voltages for these classifications. Voltage (kV rms) Withstand (kV)
4 The following table is based in part
Table 1.1-1. Standard Nominal System 4.76 60
on the above factors and experience.
Voltages and Voltage Ranges 8.25 75
Since all the factors affecting the selec-
5 (From IEEE Standard 141-1993) 15.0 95
tion are rarely known, it is only an
Voltage Nominal System Voltage 15.5 110
25.8 125 approximate guideline.
Class 3-Wire 4-Wire
6 38.0 150
Table 1.1-5. Selection of Motor Horsepower
Low Voltage 240/120 208Y/120
Table 1.1-4. Liquid-Immersed Transformers Ratings as a Function of System Voltage
240 240/120
Voltage and Basic Lightning Impulse Motor Voltage Motor System
7 480
600 —
480Y/277
Insulation Levels (BIL) (Volts) hp Range Voltage

Medium Voltage 2,400 4160Y/2400 (From ANSI/IEEE C57.12.00-2000) 460 up to 500 480
8 4,160
4,800
8320Y/4800
12000Y/6930
Applica-
tion
Nominal BIL
System (kV Crest) 
2,300
4,000
250 to 2000
250 to 3000
2,400
4,160
6,900 12470Y/7200 Voltage 4,600 250 to 3000 4,800
13,200 13200Y/7620 (kV rms) 13,200 above 2000 13,800
9 13,800 13800Y/7970
23,000 20780Y/12000 Distribu- 1.2 30 — — —
34,500 22860Y/13200 tion 2.5 45 — — — Table 1.1-6. Dry-Type Transformers Voltage
46,000 24940Y/14400 5.0 60 — — — and Basic Lightning Impulse Insulation
10 69,000 34500Y/19920 8.7 75 — — — Levels (BIL) — From ANSI/IEEE C57.12.01-1989)
High Voltage 115,000 — 15.0 95 — — — Nominal BIL (kV Crest) 
138,000 — 25.0 150 125 — — System
11 161,000 — 34.5 200 150 125 — Voltage
230,000 — 46.0 250 200 — — (kV rms)
Extra-High Voltage 345,000 — 69.0 350 250 — —
12 500,000 — Power 1.2 45 30 — —
1.2
2.5


10
20
20
30
30
45
765,000 — 2.5 60 45 — — 5.0 — 30 45 60
Ultra-High Voltage 1,100,000 — 5.0 75 60 — — 8.7 — 45 60 95
13 8.7 95 75 — — 15.0 — 60 95 110
BIL — Basic Impulse Levels 15.0 110 95 — — 25.0 95  110 125 150
25.0 150 — — — 34.5 — 125  150 200
14 ANSI standards define recommended
and required BIL levels for:
34.5 200 — — —  BIL values in bold typeface are listed as
46.0 250 200 — — standard. Others listed are in common use.
69.0 350 250 — — Optional higher levels used where exposure
■ Metal-Clad Switchgear
15 (typically vacuum breakers). 115.0 550 450 350 — to overvoltage occurs and higher protection
138.0 650 550 450 — margins are required.
■ Metal-Enclosed Switchgear (typi- 161.0 750 650 550 —  Lower levels where surge arrester
cally load interrupters, switches).
16 230.0 900 825 750 650 protective devices can be applied with
lower spark-over levels.
■ Liquid Immersed Transformers. 345.0 1,175 1,050 900 —
500.0 1,675 1,550 1,425 1,300
■ Dry-Type Transformers.
765.0 2,050 1,925 1,800 —
17 Tables 1.1-2 through 1.1-6 contain  BIL values in bold typeface are listed as
those values. standard. Others listed are in common use.

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-5
January 2008 System Design
Sheet 01 007

Table 1.1-7. 3-Phase Transformer Winding Connections


Phasor Notes i
Diagram

DELTA-DELTA Connection 1. Suitable for both ungrounded and effectively grounded sources. ii
2. Suitable for a 3-wire service or a 4-wire service with a mid-tap ground.
Phasor H2 X2
Diagram:
1

H1 H3 X1 X3 2
Angular Displacement (Degrees): 0

DELTA-WYE Connection 1. Suitable for both ungrounded and effectively grounded sources. 3
2. Suitable for a 3-wire service or a 4-wire grounded service with XO grounded.
Phasor H2 X2 3. With XO grounded, the transformer acts as a ground source for the
Diagram:
secondary system. 4
4. Fundamental and harmonic frequency zero-sequence currents in the secondary
X1 X0
lines supplied by the transformer do not flow in the primary lines. Instead the
zero sequence currents circulate in the closed delta primary windings. 5
H1 H3 X3 5. When supplied from an effectively grounded primary system does not see load
unbalances and ground faults in the secondary system.
Angular Displacement (Degrees): 30
6
WYE-DELTA Connection 1. Suitable for both ungrounded and effectively grounded sources.
2. Suitable for a 3-wire service or a 4-wire delta service with a mid-tap ground.
Phasor
Diagram:
H2 X2 3. Grounding the primary neutral of this connection would create a ground source 7
for the primary system. This could subject the transformer to severe overloading
during a primary system disturbance or load unbalance.
X1
4. Frequently installed with mid-tap ground on one leg when supplying
combination 3-phase and single-phase load where the 3-phase load is much
8
H1 H3 larger than single-phase load.
X3
5. When used in 25 kV and 35 kV 3-phase 4-wire primary systems,
Angular Displacement (Degrees): 30 ferroresonance can occur when energizing or de-energizing the transformer 9
using single-pole switches located at the primary terminals. With smaller kVA
transformers the probability of ferroresonance is higher.
WYE-WYE Connection 1. Suitable for both ungrounded and effectively grounded sources. 10
2. Suitable for a 3-wire service only, even if XO is grounded.
Phasor H2 X2 3. This connection is incapable of furnishing a stabilized neutral and its use may
Diagram:
result in phase-to-neutral overvoltage (neutral shift) as a result of unbalanced 11
phase-to-neutral load.
X0 4. If a 3-phase unit is built on a three-legged core, the neutral point of the primary

H1 H3 X1 X3
windings is practically locked at ground potential. 12
Angular Displacement (Degrees): 0
13
GROUNDED WYE-WYE Connection 1. Suitable for 4-wire effectively grounded source only.
2. Suitable for a 3-wire service or for 4-wire grounded service with XO grounded.
Phasor
Diagram:
H2 X2 3. 3-phase transformers with this connection may experience stray flux tank 14
heating during certain external system unbalances unless the core configuration
(four or five legged) utilized provides a return path for the flux.
H0 X0 4. Fundamental and harmonic frequency zero-sequence currents in the secondary
lines supplied by the transformer also flow in the primary lines (and primary
15
H1 H3 X1 X3 neutral conductor).
5. Ground relay for the primary system may see load unbalances and ground
Angular Displacement (Degrees): 0 faults in the secondary system. This must be considered when coordinating 16
overcurrent protective devices.
6. 3-phase transformers with the neutral points of the high voltage and low
voltage windings connected together internally and brought out through an 17
HOXO bushing should not be operated with the HOXO bushing ungrounded
(floating). To do so can result in very high voltages in the secondary systems.
DELTA-DELTA Connection with Tap 1. Suitable for both ungrounded and effectively grounded sources. 18
2. Suitable for a 3-wire service or a 4-wire service with a mid-tap ground.
Phasor H2 X2 3. When using the tap for single-phase circuits the single-phase load kVA should
Diagram:
X4 not exceed 5% of the 3-phase kVA rating of the transformer. The 3-phase rating
of the transformer is also substantially reduced.
19

H1 H3 X1 X3 20
Angular Displacement (Degrees): 0
21

CA08104001E For more information visit: www.eaton.com


1.1-6 Power Distribution Systems
System Design January 2008
Sheet 01 008

i Types of Systems Low voltage feeder circuits run from A fault on the secondary low voltage
the switchgear or switchboard assem- bus or in the source transformer will
In many cases, power is supplied by blies to panelboards that are located interrupt service to all loads. Service
the utility to a building at the utilization closer to their respective loads as cannot be restored until the necessary
ii voltage. In these cases, the distribution shown in Figure 1.1-1. repairs have been made. A low voltage
of power within the building is achieved feeder circuit fault will interrupt service
Each feeder is connected to the switch- to all loads supplied over that feeder.
through the use of a simple radial
1 distribution system.
gear or switchboard bus through a
circuit breaker or other overcurrent A modern and improved form of the
In cases where the utility service voltage protective device. A relatively small conventional simple radial system
2 is at some voltage higher than the utili- number of circuits are used to distribute distributes power at a primary voltage.
zation voltage within the building, the power to the loads from the switch- The voltage is stepped down to
system design engineer has a choice gear or switchboard assemblies and utilization level in the several load
3 of a number of types of systems which panelboards. areas within the building typically
may be used. This discussion covers through secondary unit substation
Since the entire load is served from a transformers. The transformers are
several major types of distribution
single source, full advantage can be
4 systems and practical modifications
taken of the diversity among the loads.
usually connected to their associated
of them. load bus through a circuit breaker, as
This makes it possible to minimize the shown in Figure 1.1-2. Each secondary
1. Simple Radial. installed transformer capacity. However,
5 the voltage regulation and efficiency
unit substation is an assembled unit
2. Loop-Primary System — consisting of a 3-phase, liquid-filled
of this system may be poor because or air-cooled transformer, an integrally
Radial Secondary System. of the low voltage feeders and single
6 3. Primary Selective System — source. The cost of the low voltage-
connected primary fused switch, and
low voltage switchgear or switchboard
Secondary Radial System. feeder circuits and their associated circuit with circuit breakers or fused switches.
breakers are high when the feeders are
7 4. Two-Source Primary — long and the peak demand is above
Circuits are run to the loads from these
Secondary Selective System. low voltage protective devices.
1000 kVA.
8 5. Sparing Transformer System.
6. Simple Spot Network.
Primary Fused Switch
9 7. Medium Voltage Distribution
Transformer
System Design.

10 1. Simple Radial System 600 V Class


Switchboard
The conventional simple radial system
receives power at the utility supply
11 voltage at a single substation and steps
Distribution
the voltage down to the utilization level. Dry-Type
In those cases where the customer
12 receives his supply from the primary
Transformer

system and owns the primary switch Distribution MCC Distribution Lighting
and transformer along with the second- Panel Panel Panelboard
13 ary low voltage switchboard or switch-
gear, the equipment may take the form
of a separate primary switch, separate Figure 1.1-1. Simple Radial System
14 transformer, and separate low voltage
switchgear or switchboard. This equip-
ment may be combined in the form of
15 an outdoor pad-mounted transformer 52 Primary Main Breaker
with internal primary fused switch
and secondary main breaker feeding
16 an indoor switchboard. 52 52 52 52 52 52 Primary Feeder Breakers
Another alternative would be a
17 secondary unit substation where
the primary fused switch, transformer
and secondary switchgear or switch-
18 board are designed and installed as
a close coupled single assembly.

19 In those cases where the utility owns the


primary equipment and transformer, the Secondary Unit
supply to the customer is at the utiliza- Substation
Primary
20 tion voltage, and the service equipment Cables
then becomes low voltage main distri-
bution switchgear or a switchboard.
21 Figure 1.1-2. Primary and Secondary Simple Radial System

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-7
January 2008 System Design
Sheet 01 009

Since each transformer is located In addition, if only one primary fuse on break switches with load side bus
within a specific load area, it must a circuit opens, the secondary loads are connection) sectionalizing switches i
have sufficient capacity to carry the then single phased, causing damage to and primary load break fused switch
peak load of that area. Consequently, low voltage motors. as shown in Figure 1.1-4.
if any diversity exists among the load ii
area, this modified primary radial Another approach to reducing costs When pad-mounted compartmental-
system requires more transformer is to eliminate the primary feeder ized transformers are utilized, they are
capacity than the basic form of the breakers completely, and utilize a furnished with loop feed oil immersed 1
simple radial system. However, single primary main breaker or fused gang operated load break sectionaliz-
because power is distributed to the switch for protection of a single pri- ing switches and drawout current
load areas at a primary voltage, losses mary feeder circuit with all secondary limiting fuses in dry wells as shown 2
are reduced, voltage regulation is unit sub-stations supplied from this in Figure 1.1-5. By operating the
improved, feeder circuit costs are circuit. Although this system results appropriate sectionalizing switches,
reduced substantially, and large low in less initial equipment cost, system it is possible to disconnect any section 3
voltage feeder circuit breakers are reliability is reduced drastically since of the loop conductors from the rest of
eliminated. In many cases the inter- a single fault in any part of the primary the system. In addition, by opening the
rupting duty imposed on the load conductor would cause an outage to transformer primary switch (or remov- 4
circuit breakers is reduced. all loads within the facility. ing the load break drawout fuses in the
pad-mounted transformer) it is possible
This modern form of the simple radial 2. Loop Primary System — to disconnect any transformer from 5
system will usually be lower in initial Radial Secondary System the loop.
investment than most other types of
This system consists of one or more A key interlocking scheme is normally
primary distribution systems for build-
“PRIMARY LOOPS” with two or more recommended to prevent closing all
6
ings in which the peak load is above
1000 kVA. A fault on a primary feeder transformers connected on the loop. sectionalizing devices in the loop. Each
primary loop sectionalizing switch and
circuit or in one transformer will cause This system is typically most effective
when two services are available from the feeder breakers to the loop are
7
an outage to only those secondary
loads served by that feeder or trans- the utility as shown in Figure 1.1-3. Each interlocked such that to be closed they
former. In the case of a primary main primary loop is operated such that one require a key (which is held captive 8
bus fault or a utility service outage, of the loop sectionalizing switches is until the switch or breaker is opened)
service is interrupted to all loads until kept open to prevent parallel operation and one less key than the number of
the trouble is eliminated. of the sources. When secondary unit key interlock cylinders is furnished. 9
substations are utilized, each trans- An extra key is provided to defeat the
Reducing the number of transformers former has its own duplex (2-load interlock under qualified supervision.
per primary feeder by adding more 10
primary feeder circuits will improve
the flexibility and service continuity
of this system; the ultimate being one Primary Main Breaker 1 52 52 Primary Main Breaker 2 11
secondary unit substation per primary
feeder circuit. This of course increases 52
the investment in the system but Tie 12
minimizes the extent of an outage 52 52 Breaker 52 52 Loop Feeder Breaker
resulting from a transformer or
Loop A
primary feeder fault.
Loop B
13
Primary connections from one second-
ary unit substation to the next second- NC NO NC NC
ary unit substation can be made with Fault Sensors 14
“double” lugs on the unit substation
primary switch as shown, or with sep-
arable connectors made in manholes 15
or other locations.
Depending on the load kVA connected 16
to each primary circuit and if no ground
fault protection is desired for either the
primary feeder conductors and trans- NC NC NO NC NC NC 17
formers connected to that feeder or
the main bus, the primary main and/or
feeder breakers may be changed to 18
primary fused switches. This will sig-
nificantly reduce the first cost, but also
decrease the level of conductor and 19
equipment protection. Thus, should
a fault or overload condition occur,
downtime increases significantly and Secondary Unit Substations Consisting of: 20
higher costs associated with increased Duplex Primary Switches/Fused Primary Switches/
Transformer and Secondary Main Feeder Breakers
damage levels and the need for fuse
replacement is typically encountered. Figure 1.1-3. Loop Primary — Radial Secondary System 21

CA08104001E For more information visit: www.eaton.com


1.1-8 Power Distribution Systems
System Design January 2008
Sheet 01 010

When a primary feeder conductor fault


i Loop
Feeder
Loop
Feeder
occurs, the associated loop feeder
breaker opens and interrupts service
Load Break to all loads up to the normally open 52
ii Loop Switches
primary loop load break switch
(typically half of the loads). Once it is Loop A Loop A
determined which section of primary
1 cable has been faulted, the loop sec-
tionalizing switches on each side of In cases where only one primary line
Fused is available, the use of a single primary
Disconnect the faulted conductor can be opened,
2 Switch the loop sectionalizing switch which
breaker provides the loop connections
to the loads as shown here.
had been previously left open then
closed and service restored to all Figure 1.1-6. Single Primary Feeder —
3 secondary unit substations while Loop System
the faulted conductor is replaced.
If the fault should occur in a conductor A basic primary loop system which
4 directly on the load side of one of the utilizes a single primary feeder breaker
loop feeder breakers, the loop feeder connected directly to two loop feeder
breaker is kept open after tripping and switches which in turn then feed the
Figure 1.1-4. Secondary Unit Substation
5 Loop Switching the next load side loop sectionalizing loop is shown in Figure 1.1-6. In this
switch manually opened so that the basic system the loop may be normally
faulted conductor can be sectionalized operated with one of the loop section-
6 Loop
Feeder
Loop
Feeder
and replaced. alizing switches open as described
above or with all loop sectionalizing
Note: Under this condition, all secondary switches closed. If a fault occurs in the
Load Break
7 Loop Switches unit substations are supplied through the
other loop feeder circuit breaker, and thus
basic primary loop system, the single
loop feeder breaker trips, and second-
all conductors around the loop should be
ary loads are lost until the faulted con-
sized to carry the entire load connected to
8 the loop. Increasing the number of primary ductor is found and eliminated from
loops (two loops shown in Figure 1.1-6) will the loop by opening the appropriate
Load Break reduce the extent of the outage from a con- loop sectionalizing switches and then
9 Drawout Fuses
ductor fault, but will also increase the sys- reclosing the breaker.
tem investment.
3. Primary Selective System —
10 When a transformer fault or overload
Secondary Radial System
occurs, the transformer primary fuses
open, and the transformer primary The primary selective — secondary
11 switch manually opened, disconnect- radial system, as shown in Figure 1.1-7,
ing the transformer from the loop, differs from those previously described
and leaving all other secondary unit in that it employs at least two primary
12 Figure 1.1-5. Pad-Mounted Transformer substation loads unaffected. feeder circuits in each load area. It is
Loop Switching
In addition, the two primary main
13 breakers which are normally closed
Primary Metal-Clad
Switchgear Lineup
and primary tie breaker which is nor- 52 52 Primary Main Breaker
mally open are either mechanically
14 or electrically interlocked to prevent Bus A 52 Bus B
paralleling the incoming source lines.
For slightly added cost, an automatic 52 52 52 52 Primary Feeder Breaker
15 throw-over scheme can be added
between the two main breakers and Feeder A1 Feeder B1 Feeder B2
tie breaker. During the more common To Other
16 event of a utility outage, the automatic
Feeder A2 Substations

transfer scheme provides significantly NO

17 reduced power outage time.


The system in Figure 1.1-3 has higher NC
costs than in Figure 1.1-2, but offers
18 increased reliability and quick restora- NO Typical Secondary Unit
tion of service when 1) a utility outage Substation Duplex Primary
Switch/Fuses
occurs, 2) a primary feeder conductor Transformer/600 V Class
19 fault occurs, or 3) a transformer fault
NC
Secondary Switchgear
or overload occurs.
NO
20 Should a utility outage occur on one of
the incoming lines, the associated pri- NC
mary main breaker is opened and the
21 tie breaker closed either manually or
through an automatic transfer scheme. Figure 1.1-7. Basic Primary Selective — Radial Secondary System

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-9
January 2008 System Design
Sheet 01 011

designed so that when one primary or most of the loads, may more than
circuit is out of service, the remaining Primary
Feeders
offset the greater cost. Having two- i
feeder or feeders have sufficient sources allows for either manual or
capacity to carry the total load. Half automatic transfer of the two primary
of the transformers are normally Non-Load Break main breakers and tie breaker should ii
connected to each of the two feeders. Selector Switches one of the sources become unavailable.
Inter-
When a fault occurs on one of the lock
primary feeders, only half of the Load Break
Disconnect
The primary selective-secondary radial 1
load in the building is dropped. system, however, may be less costly or
Fuses more costly than a primary loop —
Duplex fused switches as shown in secondary radial system of Figure 1.1-3 2
Figure 1.1-7 and detailed in Figure 1.1-8 depending on the physical location
are the normal choice for this type of the transformers while offering
of system. Each duplex fused switch comparable downtime and reliability. 3
consists of two (2) load break 3-pole The cost of conductors for the two
switches each in their own separate types of systems may vary greatly
structure, connected together by bus depending on the location of the 4
bars on the load side. Typically, the transformers and loads within the
load break switch closest to the Figure 1.1-9. Fused Selector Switch in facility and greatly override primary
transformer includes a fuse assembly One Structure switching equipment cost differences 5
with fuses. Mechanical and/or key between the two systems.
interlocking is furnished such that This means limited cable space espe-
cially if double lugs are furnished for
both switches cannot be closed at
each line as shown in Figure 1.1-7 and
4. Two-Source Primary — 6
the same time (to prevent parallel Secondary Selective System
operation) and interlocking such that should a faulted primary conductor
have to be changed, both lines would
access to either switch or fuse assem-
have to be deenergized for safe
This system uses the same principle
of duplicate sources from the power
7
bly cannot be obtained unless both
switches are opened. changing of the faulted conductors. supply point utilizing two primary
In Figure 1.1-7 when a primary feeder main breakers and a primary tie breaker. 8
fault occurs the associated feeder The two primary main breakers and
Primary primary tie breaker being either
Feeders breaker opens, and the transformers
normally supplied from the faulted manually or electrically interlocked 9
feeder are out of service. Then manu- to prevent closing all three at the same
Load Break
ally, each primary switch connected to time and paralleling the sources. Upon
Switches
the faulted line must be opened and loss of voltage on one source, a manual 10
then the alternate line primary switch or automatic transfer to the alternate
can be closed connecting the trans- source line may be utilized to restore
Fuses
former to the live feeder, thus restoring power to all primary loads. 11
service to all loads. Note that each of the Each transformer secondary is
primary circuit conductors for Feeder arranged in a typical double-ended
A1 and B1 must be sized to handle the unit substation arrangement as shown
12
sum of the loads normally connected in Figure 1.1-10. The two secondary
to both A1 and B1. Similar sizing of main breakers and secondary tie
Feeders A2 and B2, etc., is required. breaker of each unit substation are
13
If a fault occurs in one transformer, again either mechanically or electrically
interlocked to prevent parallel opera-
Figure 1.1-8. Duplex Fused Switch in
the associated primary fuses blow
tion. Upon loss of secondary source
14
and interrupts the service to just
Two Structures the load served by that transformer. voltage on one side, manual or auto-
matic transfer may be utilized to transfer
As an alternate to the duplex switch Service cannot be restored to the
the loads to the other side, thus restor-
15
arrangement, a non-load break selector loads normally served by the faulted
transformer until the transformer ing power to all secondary loads.
switch mechanically interlocked with a
load break fused switch can be utilized is repaired or replaced. This arrangement permits quick resto- 16
as shown in Figure 1.1-9. The non-load ration of service to all loads when a
Cost of the primary selective —
break selector switch is physically primary feeder or transformer fault
secondary radial system is greater 17
located in the rear of the load break occurs by opening the associated sec-
than that of the simple primary radial
fused switch, thus only requiring one ondary main and closing the second-
system of Figure 1.1-1 because of the
structure and a lower cost and floor ary tie breaker. If the loss of secondary
space savings over the duplex
additional primary main breakers, tie
breaker, two-sources, increased num- voltage has occurred because of a pri- 18
arrangement. The non-load break mary feeder fault with the associated
ber of feeder breakers, the use of pri-
switch is mechanically interlocked to primary feeder breaker opening, then
prevent its operation unless the load
mary-duplex or selector switches, and
all secondary loads normally served 19
the greater amount of primary feeder
break switch is opened. The main by the faulted feeder would have to
cable required. The benefits from the
disadvantage of the selector switch is be transferred to the opposite primary
that conductors from both circuits are
reduction in the amount of load lost
feeder. This means each primary 20
when a primary feeder is faulted, plus
terminated in the same structure. feeder conductor must be sized to
the quick restoration of service to all
carry the load on both sides of all the
secondary buses it is serving under 21

CA08104001E For more information visit: www.eaton.com


1.1-10 Power Distribution Systems
System Design January 2008
Sheet 01 012

secondary emergency transfer. If the In either of the above emergency con- nameplate kVA rating. Typically these
i loss of voltage was due to a failure of ditions, the in-service transformer of transformers are furnished with fan-
one of the transformers in the double- a double-ended unit substation would cooling and/or lower than normal tem-
ended unit substation, then the associ- have to have the capability of serving perature rise such that under emer-
ii ated primary fuses would open taking the loads on both sides of the tie gency conditions they can carry on a
only the failed transformer out of breaker. For this reason, transformers continuous basis the maximum load
service, and then only the secondary utilized in this application have equal on both sides of the secondary tie
1 loads normally served by the faulted kVA rating on each side of the double- breaker. Because of this spare trans-
transformer would have to be trans- ended unit substation and the normal former capacity, the voltage regulation
ferred to the opposite transformer. operating maximum load on each provided by the double-ended unit
2 transformer is typically about 2/3 base substation system under normal
conditions is better than that of the
systems previously discussed.
3
The double-ended unit substation
52 52 Primary Main Breakers arrangement can be utilized in con-
4 52
junction with any of the previous
systems discussed which involve two
primary sources. Although not recom-
52 52 52 52 Primary Feeder Breakers
5 mended, if allowed by the utility,
momentary re-transfer of loads to the
To Other Substations To Other Substations restored source may be made closed
6 transition (anti-parallel interlock
Typical schemes would have to be defeated)
Double-Ended for either the primary or secondary
Unit
7 Substation
systems. Under this condition, all
equipment interrupting and momentary
ratings should be suitable for the fault
8 current available from both sources.
For double-ended unit substations
equipped with ground fault systems
9 special consideration to transformer
neutral grounding and equipment
10 operation should be made — see
Primary Fused Transformer Tie Breaker Secondary Main Breaker “Grounding” and “Ground Fault
Switch Protection” in Section 1.4. Where
11 two single-ended unit substations are
Figure 1.1-10. Two-Source Primary — Secondary Selective System connected together by external tie con-
ductors, it is recommended that a tie
12 breaker be furnished at each end of
the tie conductors.

13 5. Sparing Transformer System


K K K The sparing transformer system concept
came into use as an alternative to the
14 capital cost intensive double-ended
secondary unit substation distribution
system (see Two-Source Primary —
15 Sparing Transformer
Secondary Selective System). It essen-
tially replaces double-ended substations
with single-ended substations and one
16 or more “sparing” transformer substa-
K K tions all interconnected on a common
secondary bus (see Figure 1.1-11).
17
Generally no more than 3 to 5 single-
Typical Secondary Busway Loop
ended substations are on a sparing loop.
18 The essence of this design philosophy
is that conservatively designed and
loaded transformers are highly reliable
19 electrical devices and rarely fail. There-
K K
fore, this design provides a single com-
Typical Single-Ended Substation
mon backup transformer for a group of
20 transformers in lieu of a backup trans-
former for each and every transformer.
This system design still maintains a
21 Figure 1.1-11. Sparing Transformer System
high degree of continuity of service.

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-11
January 2008 System Design
Sheet 01 013

Referring to Figure 1.1-11, it is appar- In facilities with no qualified electrical The major advantage of the secondary
ent that the sparing concept backs up power operators, an open transition network system is continuity of ser- i
primary switch and primary cable fail- with key interlocking is often a prudent vice. No single fault anywhere on the
ure as well. Restoration of lost or failed design. primary system will interrupt service
utility power is accomplished similarly
Note: Each pair of “main breaker/tie breaker”
to any of the system’s loads. Most ii
to primary selective scheme previously faults will be cleared without inter-
key cylinders should be uniquely keyed to
discussed. It is therefore important to prevent any paralleled source operations. rupting service to any load. Another
use an automatic throwover system in outstanding advantage that the net- 1
a two source lineup of primary switch- Careful sizing of these transformers work system offers is its flexibility
gear to restore utility power as dis- as well as careful specification of the to meet changing and growing load
cussed in the “Two-Source Primary” transformers is required for reliability. conditions at minimum cost and 2
scheme — see Figure 1.1-10. Low temperature rise specified with minimum interruption in service to
continuous overload capacity or other loads on the network. In addition
A major advantage of the sparing
transformer system is the typically upgraded types of transformers to flexibility and service reliability, the 3
should be considered. secondary network system provides
lower total base kVA of transformation.
exceptionally uniform and good volt-
In a double-ended substation design, One disadvantage to this system is 4
age regulation, and its high efficiency
each transformer must be rated to the external secondary tie system, materially reduces the costs of
carry the sum of the loads of two busses see Figure 1.1-11. As shown, all single-
and usually requires the addition of system losses.
cooling fans to accomplish this rating.
ended substations are tied together on 5
the secondary with a tie busway or Three major differences between the
In the “sparing” concept, each trans- cable system. Location of substations network system and the simple radial
former carries only its own load, which is therefore limited because of voltage system account for the outstanding 6
is typically not a fan-cooled rating. Major advantages of the network. First,
drop and cost considerations.
space savings is also a benefit of this a network protector is connected in
system in addition to first cost savings. Routing of busway, if used, must be the secondary leads of each network 7
carefully layed out. It should also be transformer in place of, or in addition
The sparing transformer system
noted, that a tie busway or cable fault to, the secondary main breaker, as
operates as follows:
will essentially prevent the use of the shown in Figure 1.1-12. Also, the 8
■ All main breakers, including the sparing transformer until it is repaired. secondaries of each transformer in
sparing main breaker are normally Commonly, the single-ended substa- a given location (spot) are connected
closed; the tie breakers are normally tions and the sparing transformer together by a switchgear or ring bus 9
open. must be clustered. This can also be from which the loads are served over
■ Once a transformer (or primary an advantage, as more kVA can be short radial feeder circuits. Finally, the
cable or primary switch/fuse) fails, supported from a more compact primary supply has sufficient capacity 10
the associated secondary main space layout. to carry the entire building load with-
breaker is opened. The associated out overloading when any one primary
tie breaker is then closed, which 6. Simple Spot Network Systems feeder is out of service. 11
restores power to the single-ended The ac secondary network system A network protector is a specially
substation bus. is the system that has been used for designed heavy duty air power breaker, 12
■ Schemes which require the main many years to distribute electric power spring close with electrical motor-charged
to be opened before the tie is closed in the high-density, downtown areas mechanism, with a network relay to
(“open transition”), and which allow of cities, usually in the form of utility
any tie to be closed before the grids. Modifications of this type of
control the status of the protector
(tripped or closed). The network relay
13
substation main is opened, system make it applicable to serve is usually a solid-state microprocessor-
(“closed transition”) are possible. loads within buildings. based component integrated 14
With a closed transition scheme it is
common to add a timer function that
opens the tie breaker unless either Typical Feeder 15
main breaker is opened within a time Primary Circuit
interval. This closed transition allows To Other
power to be transferred to the sparing Network Transformer
Networks
16
transformer without interruption, such
as for routine maintenance, and then Network Protector
back to the substation. This closed Fuses 17
transition transfer has an advantage in Optional Main, 50/51
some facilities, however, appropriate Relaying and/or
Network Disconnect
interrupting capacities and bus bracing Tie Tie
Drawout
18
must be specified suitable for the Low Voltage
momentary parallel operation. LV Feeder NC NC Switchgear
19
Customer Customer Customer
Loads Loads Loads
20
Figure 1.1-12. Three-Source Spot Network
21

CA08104001E For more information visit: www.eaton.com


1.1-12 Power Distribution Systems
System Design January 2008
Sheet 01 014

into the protector enclosure which with that feeder circuit. This operation They are also economical when
i functions to automatically close the does not interrupt service to any loads. compared to two transformer double-
protector only when the voltage After the necessary repairs have been ended substations with normally
conditions are such that its associated made, the system can be restored to opened tie breakers.
ii transformer will supply power to the normal operating conditions by closing
secondary network loads, and to auto- the primary feeder breaker. All network Emergency power should be connected
matically open the protector when protectors associated with that feeder to network loads downstream from
1 power flows from the secondary to the will close automatically. the network, or upstream at primary
network transformer. The purpose of voltage, not at the network bus itself.
the network protector is to protect the The chief purpose of the network bus
2 integrity of the network bus voltage normally closed ties is to provide for 7. Medium Voltage Distribution
and the loads served from it against the sharing of loads and a balancing System Design
transformer and primary feeder faults of load currents for each primary ser-
3 by quickly disconnecting the defective vice and transformer regardless of A. Single Bus, Figure 1.1-13
feeder-transformer pair from the the condition of the primary services.
The sources (utility and/or generator(s))
network when backfeed occurs. Also, the ties provide a means for are connected to a single bus. All feeders
4 isolating and sectionalizing ground are connected to the same bus.
The simple spot network system
resembles the secondary-selective fault events within the switchgear
network bus, thereby saving a portion
5 radial system in that each load area
of the loads from service interruptions, Utility
is supplied over two or more primary
feeders through two or more trans- yet isolating the faulted portion for
G
corrective action.
6 formers. In network systems, the
transformers are connected through The use of spot network systems
network protectors to a common bus, provides users with several important
7 as shown in Figure 1.1-12, from which advantages. First, they save trans-
loads are served. Since the transform- former capacity. Spot networks permit
ers are connected in parallel, a primary equal loading of transformers under 52 52
8 feeder or transformer fault does not all conditions. Also, networks yield
cause any service interruption to the lower system losses and greatly Main Bus
loads. The paralleled transformers improve voltage conditions. The volt-
9 supplying each load bus will normally age regulation on a network system
carry equal load currents, whereas is such that both lights and power can
equal loading of the two separate be fed from the same load bus. Much
10 transformers supplying a substation in larger motors can be started across-
52
the secondary-selective radial system the-line than on a simple radial
is difficult to obtain. The interrupting system. This can result in simplified One of Several Feeders
11 duty imposed on the outgoing feeder motor control and permits the use
breakers in the network will be greater of relatively large low voltage motors
with the spot network system. Figure 1.1-13. Single Bus
with their less expensive control.
12 The optimum size and number of pri- Finally, network systems provide a This configuration is the simplest
mary feeders can be used in the spot greater degree of flexibility in adding system, however, outage of the utility
future loads; they can be connected results in total outage.
13 network system because the loss of
to the closest spot network bus.
any primary feeder and its associated Normally the generator does not have
transformers does not result in the Spot network systems are economical adequate capacity for the entire load.
14 loss of any load even for an instant. for buildings which have heavy con- A properly relayed system equipped
In spite of the spare capacity usually centrations of loads covering small with load shedding, automatic voltage/
supplied in network systems, savings areas, with considerable distance frequency control may be able to
15 in primary switchgear and secondary between areas, and light loads within maintain partial system operation.
switchgear costs often result when the distances separating the concen-
compared to a radial system design trated loads. They are commonly used Any future addition of breaker sections
16 with similar spare capacity. This in hospitals, high rise office buildings, to the bus will require a shutdown of
occurs in many radial systems and institutional buildings where a the bus, since there is no tie breaker.
because more and smaller feeders high degree of service reliability is B. Single Bus with Two-Sources from the
17 are often used in order to minimize required from the utility sources. Spot Utility, Figure 1.1-14
the extent of any outage when a network systems are especially eco-
primary fault event occurs. nomical where three or more primary Same as the single bus, except that
18 In spot networks, when a fault occurs feeders are available. Principally, this two utility sources are available.
is due to supplying each load bus This system is operated normally with
on a primary feeder or in a transformer, the main breaker to one source open.
the fault is isolated from the system through three or more transformers
19 through the automatic tripping of the and the reduction in spare cable and Upon loss of the normal service the
transformer capacity required. transfer to the standby Normally
primary feeder circuit breaker and all Open (NO) breaker can be automatic
of the network protectors associated
20 or manual. Automatic transfer is pre-
ferred for rapid service restoration
especially in unattended stations.
21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-13
January 2008 System Design
Sheet 01 015

Again, the closing of the tie breaker can The third tie breaker allows any bus
Utility #1 Utility #2 be manual or automatic. The statements to be fed from any utility source. i
made for the retransfer of scheme B
apply to this scheme also. Caution for Figures 1.1-14, 1.1-15 and
Normal Standby
1.1-16: If continuous paralleling of ii
Utility #1 Utility #2 sources is planned, reverse current,
reverse power and other appropriate
relaying protection should be added. 1
When both sources are paralleled for
any amount of time, the fault current
52 NC 52 NO available on the load side of the main 2
device is the sum of the available
52 NC 52 NC fault current from each source plus
the motor fault contribution. It is 3
Loads required that bus bracing, feeder
NO
Bus #1 Bus #2 breakers and all load side equipment
Figure 1.1-14. Single Bus with Two-Sources
52
is rated for the increased available 4
fault current.
Retransfer to the “Normal” can be
closed transition subject to the approval 52 52
Summary
5
of the utility. Closed transition momen-
tarily (5 – 10 cycles) parallels both The medium voltage system configura-
utility sources. Caution: when both Load Load
tions shown are based on using metal- 6
sources are paralleled, the fault current clad drawout switchgear. The service
available on the load side of the main Figure 1.1-15. Two-Source Utility with continuity required from electrical sys-
device is the sum of the available fault Tie Breaker tems makes the use of single source 7
current from each source plus the motor systems impractical.
fault contribution. It is recommended If looped or primary selective distribu-
tion system for the loads is used, the In the design of a modern medium 8
that the short circuit ratings of the bus, voltage system the engineer should:
feeder breakers and all load side buses can be extended without a shut-
equipment are rated for the increased down by closing the tie breaker and 1. Design a system as simple as
available fault current. If the utility transferring the loads to the other bus. possible. 9
requires open transfer, the disconnec- This configuration is more expensive
tion of motors from the bus must be 2. Limit an outage to as small a
than B. The system is not limited to two portion of the system as possible. 10
ensured by means of suitable time delay buses only. Another advantage is that
on reclosing as well as supervision of the design may incorporate momentary 3. Provide means for expanding the
the bus voltage and its phase with paralleling of buses on retransfer after system without major shutdowns.
respect to the incoming source voltage. the failed line has been restored to pre-
11
vent another outage. See the Caution 4. Relay the system so that only the
This busing scheme does not preclude faulted part is removed from
the use of cogeneration, but requires for Figures 1.1-14, 1.1-15 and 1.1-16. 12
service, and damage to it is mini-
the use of sophisticated automatic syn- In Figure 1.1-16, closing of the tie mized consistent with selectivity.
chronizing and synchronism checking breaker following the opening of a
controls, in addition to the previously main breaker can be manual or auto- 5. Specify and apply all equipment 13
mentioned load shedding, automatic matic. However since a bus can be fed within its published ratings and
frequency and voltage controls. through two tie breakers the control national standards pertaining to
This configuration is more expensive scheme should be designed to make the equipment and its installation. 14
than the scheme shown in Figure 1.1-13, the selection.
but service restoration is quicker. Again,
a utility outage results in total outage to
15
Utility #1 Utility #2 Utility #3
the load until transfer occurs. Extension
of the bus or adding breakers requires 16
a shutdown of the bus.
If paralleling sources, reverse current,
reverse power, and other appropriate 17
relaying protection should be added
as requested by the utility. 52 NC 52 NC 52 NC
18
C. Multiple Sources with Tie Breaker, NO NO
Bus #1 Bus #2 Bus #3
Figure 1.1-15 and Figure 1.1-16 52 52
This configuration is similar to configu- 19
ration B. It differs significantly in that
both utility sources normally carry the 52 NO 52 Typical Feeder 52 52 52 NO
loads and also by the incorporation 20
of a normally open tie breaker. The Tie Busway
outage to the system load for a utility
outage is limited to half of the system. 21
Figure 1.1-16. Triple-Ended Arrangement

CA08104001E For more information visit: www.eaton.com


1.1-14 Power Distribution Systems
System Design January 2008
Sheet 01 016

i Health Care Facilities ■ NFPA 101 — Life Safety Code. The electrical system requirements for
■ NFPA 110 — Standard for Emergency the Essential Electrical System (EES)
Health Care Facilities are defined by and Standby Power Systems. vary according to the type of health
NFPA (National Fire Protection Agency) ■ NFPA 111 — Standard on Stored
care facility. Health care facilities are
ii as “Buildings or portions of buildings Electrical Energy Emergency and categorized by NFPA 99 as Type 1,
in which medical, dental, psychiatric, Standby Power Systems. Type 2 or, Type 3 facilities. Some
nursing, obstetrical, or surgical care example health care facilities, classi-
1 are provided.” Due to the critical These NFPA guidelines represent the fied by Type, are summarized in the
nature of the care being provided at most industry recognized standard following Table 1.1-8.
these facilities and their increasing requirements for health care electrical
2 dependence on electrical equipment design. However, the electrical design Table 1.1-8. Health Care Facilities
for preservation of life, health care engineer should consult with the Description Definition EES Type
facilities have special requirements for authorities having jurisdiction over
3 the design of their electrical distribu- the local region for specific electrical
Hospitals NFPA 99 Chap. 13 Type 1
Nursing Homes NFPA 99 Chap. 17 Type 2
tion systems. These requirements are distribution requirements. Limited Care
typically much more stringent than Facilities NFPA 99 Chap. 18 Type 2
4 commercial or industrial facilities. Health Care Electrical System Ambulatory
The following section summarizes Requirements Surgical
some of the unique requirements Facilities NFPA 99 Chap. 14 Type 3 
5 of health care facility design. Health care electrical systems usually Other Health
consist of two parts: Care Facilities NFPA 99 Chap. 14 Type 3 
There are several agencies and organi-  If electrical life support or critical care areas
6 zations that develop requirements for 1. Non-essential or Normal Electrical are present then facility is classified as Type 1.
health care electrical distribution sys- System.
tem design. The following is a listing 2. Essential Electrical System.
Type 1 Essential Electrical
7 of some of the specific NFPA (National Systems (EES)
Fire Protection Agency) standards that All electrical power in a health care
affect health care facility design and facility is important, though some Type 1 Essential Electrical Systems
8 implementation: loads are not critical to the safe opera- (EES) have the most stringent require-
tion of the facility. These “non-essential” ments for providing continuity of
■ NFPA 37 — Standard for Stationary or “normal” loads include things such electrical service and will, therefore,
9 Combustion Engines and Gas as general lighting, general lab equip- be the focus of this section. Type 1
Turbines. ment, non-critical service equipment, EES requirements meet or exceed
■ NFPA 70 — National Electrical Code. patient care areas, etc. These loads are the requirements for Type 2 and
10 ■ NFPA 99 — Health Care Facilities. not required to be fed from an alter- Type 3 facilities.
nate source of power.

11
Normal Source Normal Source Normal Source Emergency Power Supply

12 G

13

14

15

16
Non-Essential Loads Non-Essential Loads

17

18 Manual Transfer Switch

Equipment Life Safety Critical


Delayed Automatic Transfer Switch System Branch Branch
19 Emergency System
Automatic (Non-Delaying)
Transfer Switch Essential Electrical System
20
Figure 1.1-17. Typical Large Hospital Electrical System — Type 1 Facility
21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-15
January 2008 System Design
Sheet 01 017

Sources: Type 1 systems are required Table 1.1-9. Type 1 EES Applicable Codes B. Critical Branch — supplies power
to have a minimum of two independent Description Standard Section for task illumination, fixed equip- i
sources of electrical power. A normal ment, selected receptacles and
source that generally supplies the Design NFPA 99 4.4.1.1.1 selected power circuits for areas
entire facility and one or more alter- Sources NFPA 99 4.4.1.1.4 thru
4.4.4.1.1.7.2
related to patient care. The ii
nate sources that supply power when Uses NFPA 99 4.4.1.1.8 (1-3) purpose of the critical branch
the normal source is interrupted. The Emergency is to provide power to a limited
alternate source(s) must be an on-site Power Supply number of receptacles and loca- 1
generator driven by a prime mover Classification NFPA 110 4 tions to reduce load and minimize
unless a generator(s) exists as the Distribution NFPA 99 4.4.2 the chances of fault conditions.
normal power source. In the case NEC 517-30 The transfer switch(es) feeding the 2
where a generator(s) is utilized as the critical branch must be automatic
normal source, it is permissible for the Systems and Branches of Service: The type. They are permitted to have
alternate source to be a utility feed. Type 1 EES consists of two separate appropriate time delays that will 3
Alternate source generators must be power systems capable of supplying follow the restoration of the life
classified as Type 10, Class X, Level 1 power considered essential for life safety branch but should have
gensets per NFPA 110 2-2 capable safety and effective facility operation power restored within 10 seconds 4
of providing power to the load in a during an interruption of the normal of normal source power loss.
maximum of 10 seconds. Typically, power source. They are the Emergency The critical branch provides power
the alternate sources of power are System and the Equipment System. to circuits serving the following 5
supplied to the loads through a series areas and functions:
1. Emergency System — consists of
of automatic and/or manual transfer
switches. (See Section 25.) The
circuits essential to life safety and 1. Critical care areas. 6
critical patient care.
transfer switches can be non-delayed 2. Isolated Power Systems in
automatic, delayed automatic, or The Emergency System is an electrical special environments.
manual transfer depending on the sub-system that must be fed from an 3. Task illumination and selected
7
requirements of the specific branch automatic transfer switch or series of receptacles in the following
of the EES that they are feeding. It is automatic transfer switches. This patient care areas: infant
permissible to feed multiple branches Emergency System consists of two nurseries, medication prep
8
or systems of the EES from a single mandatory branches that provide power areas, pharmacy, selected
automatic transfer switch provided to systems and functions essential to acute nursing areas, psychiatric
that the maximum demand on the life safety and critical patient care. bed areas, ward treatment
9
EES does not exceed 150 kVA. This rooms, nurses’ stations.
configuration is typically seen in A. Life Safety Branch — supplies
smaller health care facilities that power for lighting, receptacles, 4. Specialized patient care task 10
must meet Type 1 EES requirements. and equipment to perform the illumination, where needed.
(See Figure 1.1-18.) following functions: 5. Nurse call systems.
6. Blood, bone and tissue banks.
11
1. Illumination of means of egress.
Normal Source 2. Exit signs and exit direction signs. 7. Telephone equipment rooms
3. Alarms and alerting systems.
and closets. 12
Alternate 8. Task illumination, selected
Source 4. Emergency communications
receptacles, and selected
systems.
power circuits for the following: 13
G 5. Task illumination, battery general care beds (at least
chargers for battery powered one duplex receptacle), angio-
lighting, and select receptacles graphic labs, cardiac catheter- 14
at the generator. ization labs, coronary care
6. Elevator lighting control, com- units, hemodialysis rooms,
munication and signal systems. selected emergency room 15
7. Automatic doors used for egress. treatment areas, human
physiology labs, intensive care
Non-Essential
Loads These are the only functions units, selected postoperative 16
permitted to be on the life safety recovery rooms.
Entire Essential branch. Life Safety Branch equip-
Electric System ment and wiring must be entirely
9. Additional circuits and single- 17
(150 kVA or Less) phase fraction motors as needed
independent of all other loads and for effective facility operation.
branches of service. This includes
Figure 1.1-18. Small Hospital Electrical
separation of raceways, boxes or 18
System — Single EES Transfer Switch
cabinets. Power must be supplied
to the Life Safety Branch from a
non-delayed automatic transfer
19
switch.
20

21

CA08104001E For more information visit: www.eaton.com


1.1-16 Power Distribution Systems
System Design January 2008
Sheet 01 018

Table 1.1-10. Type 1 — Emergency System The following equipment must be must be configured such that the loads
i Applicable Codes arranged for delayed automatic or will not cause the generator to over-
Description Standard Section manual transfer to the emergency load and must be shed in the event the
power supply: generator enters an overload condition.
ii General NFPA 99 4.4.2.2.2
NEC 517-31 1. Select heating equipment. Ground Fault Protection — per NFPA
Life Safety NFPA 99 4.4.2.2.2.2 2. Select elevators. 70 NEC article 230-95, ground fault
1 Branch NEC 517-32
3. Supply, return and exhaust
protection is required on any feeder or
Critical Branch NFPA 99 4.4.2.2.2.3 service disconnect 1000 A or larger on
NEC 517-33 ventilating systems for surgical, systems with line to ground voltages of
obstetrical, intensive care,
2 Wiring NFPA 99 4.4.2.2.4
coronary care, nurseries, and
150 volts or greater and phase-to-phase
NEC 517-30(c) voltages of 600 volts or less. For health
emergency treatment areas. care facilities (of any type), a second
3 2. Equipment System — consists of 4. Supply, return and exhaust level of ground fault protection is
major electrical equipment necessary ventilating systems for airborne required to be on the next level of
for patient care and Type 1 operation. infectious/isolation rooms, labs feeder downstream. This second level
4 The Equipment System is a subsystem
and medical areas where hazard- of ground fault is only required for
ous materials are used. feeders that serve patient care areas
of the EES that consists of large electri- and equipment intended to support life.
cal equipment loads needed for patient 5. Hyperbaric facilities.
5 care and basic hospital operation. 6. Hypobaric facilities.
100% selective coordination of the two
levels of ground fault protection must
Loads on the Equipment System that 7. Autoclaving equipment. be achieved with a minimum six-cycle
are essential to generator operation are
6 required to be fed by a non-delayed 8. Controls for equipment listed above. separation between the upstream and
downstream device.
automatic transfer switch. 9. Other selected equipment in
kitchens, laundries, radiology NEC 517-17 prohibits the installation
7 The following equipment must be rooms, and central refrigeration of ground fault protection between the
arranged for delayed automatic transfer as selected. on-site generator(s) and any EES transfer
to the emergency power supply: switch or on the load side of a transfer
8 Table 1.1-11. Type 1 — Equipment System
switch feeding EES circuits. (See Figure
1. Central suction systems for medical Applicable Codes
and surgical functions. 1.1-19 — Additional Level of Ground
Description Standard Section Fault). The intent of this code section is
9 2. Sump pumps and other equipment
to prevent a ground fault that causes a
required for the safe operation of General NFPA 99 4.4.2.2.3
NEC 517-34 trip on the normal system to also cause
a major apparatus.
10 Equipment NFPA 99 4.4.2.2.3 (3-5) a trip on the emergency system. Such
3. Compressed air systems for NEC 517-34(a)-(b) an event could result in complete power
medical and surgical functions. loss of both normal and emergency
11 4. Smoke control and stair Any loads served by the generator that power sources and could not be recov-
pressurization systems. are not approved as outlined above as ered until the source of the ground
part of the Essential Electrical System fault was located and isolated from
5. Kitchen hood supply and exhaust
12 systems, if required to operate must be connected through a separate the system. To prevent this condition,
NEC 700-26 removes the
during a fire. transfer switch. These transfer switches

13 Normal Source Normal Source(s)


G
Generator Breakers are
14 Typically Supplied with
480/277 V ➀ 480/277 V ➀ 480/277 V ➀ Ground Fault Alarm
Only. (NEC 700-26)
15 1000 A
or Larger
GF
Service
Entrance
1000 A
or Larger
GF
Service
Entrance
1000 A
or Larger
GF
Service
Entrance
Additional Level
of Ground Fault
16 is not Permitted
Between Generator
Additional Level and EES Transfer
GF GF GF GF GF of Ground Fault GF GF GF GF GF GF Switches.
17 Protection (NEC 517-17a(1))

Non-Essential Loads
18 Non-Essential Loads

19 GF = Ground Fault Protection Required Additional Level of Ground Fault is


not Permitted on Load Side of EES
Transfer Switches. (NEC 517-17a(2))
20 Essential Electrical System

Figure 1.1-19. Additional Level of Ground Fault Protection



21 Ground fault protection is required for service disconnects 1000 amperes and larger or systems with less than 600 volts phase-to-phase and greater
than 150 volts to ground per NEC 230-95.

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-17
January 2008 System Design
Sheet 01 019

ground fault protection requirement Maintenance and Testing trained in development and execution
for the emergency system source. Regular maintenance and testing of of annual preventative maintenance i
Typically, the emergency system the electrical distribution system in procedures of health care facility
generator(s) are equipped with ground a health care facility is necessary to electrical distribution systems.
fault alarms that do not automatically ensure proper operation in an emer- ii
disconnect during a ground fault. gency and, in some cases, to maintain Paralleling Emergency Generators
government accreditation. Any health
Table 1.1-12. Ground Fault Protection
care facility receiving Medicare or Without Utility Paralleling 1
Applicable Codes
Medicaid reimbursement from the In many health care facilities (and
Description Standard Section other large facilities with critical
government must be accredited by the
Services NEC 230-95 Joint Commission on Accreditation of loads), the demand for standby 2
Feeders NEC 215-10 Health Care Organizations (JCAHO). emergency power is large enough to
JCAHO has established a group of require multiple generator sets to
Additional Level NEC
NFPA 99
517-17
4.3.2.5 standards called the Environment of power all of the required Essential 3
Alternate Source NEC 700-26 Care, which must be met for health Electrical System (EES) loads. In many
NEC 700-7 (d) care facility accreditation. Included in cases, it becomes more flexible and
these standards is the regular testing easier to operate the required multiple 4
Wet Locations — A wet location in a of the emergency (alternate) power generators from a single location
health care facility is any patient care system(s). The emergency power sys- utilizing Generator Paralleling Switch-
area that is normally subject to wet tem must be tested in accordance with gear. Figure 1.1-20 on Page 1.1-18 5
conditions while patients are present. NFPA 110 Standard for Emergency and shows an example of a typical one-line
Typical wet locations can include oper- Standby Power Systems guidelines at for a paralleling switchgear lineup
ating rooms, anesthetizing locations, intervals not less than 20 days and not feeding the EES. 6
dialysis locations, etc. (Patient beds, exceeding 40 days. Generators must
A typical abbreviated sequence of
toilets, sinks, are not considered wet be tested for a minimum of 30 minutes
locations.) These wet locations require under the criteria defined in NFPA 110.
operation for a multiple emergency 7
generator and ATS system follows.
special protection to guard against
One method to automate the task of Note that other modes of operation
electric shock. The ground fault current
in these areas must be limited not to monthly generator tests is through the such as generator demand priority and 8
use of PowerNet communications. automated testing modes are available
exceed 6 mA.
With the PowerNet integrated metering, but are not included below. (Reference
In areas where the interruption of power monitoring and control system, a facility Section 43 for complete detailed 9
is permissible, ground fault circuit maintenance director can initiate a sequences of operation.)
interrupters (GFCI) can be employed. generator test, control/monitor loads,
GFCIs will interrupt a circuit when meter/monitor generator test points
1. Entering Emergency Mode 10
ground fault current exceeds the and create a JCAHO compliant report a. Upon loss of normal source,
present level (typically 2-5 mA). automatically from a central PC. The automatic transfer switches
report contains all metered values, send generator control system 11
In areas where the interruption of test results, date/time information, etc. a run request.
power cannot be tolerated, protection necessary to satisfy JCAHO require-
from ground fault currents is accom- ments. This automated generator testing
b. All available generators are 12
plished through the use of an Isolated started. The first generator up
procedure reduces the labor, training to voltage and frequency is
Power System. Isolated Power Sys- and inaccuracies that occur during
tems provide power to an area that is manual emergency power system tests.
closed to the bus. 13
isolated from ground (or ungrounded). (See Power Monitoring Section 2.) c. Unsheddable loads and Load
This type of system limits the amount Shed Priority 1 loads are pow-
of current that flows to ground in Table 1.1-14. Maintenance and Testing ered in less than 10 seconds. 14
the event of a single line-to-ground Applicable Codes
d. The remaining generators are
fault and maintains circuit continuity. Description Standard Section synchronized and paralleled
Electronic Line Isolation Monitors (LIM)
to the bus as they come up to 15
are used to monitor and display leakage Grounding NFPA 99 4.3.3.1
voltage and frequency.
currents to ground. When leakage Emergency Power NFPA 99 4.4.4.1.1
current thresholds are exceeded, visible System JCAHO EC.2.14(d) e. As additional generators are 16
and/or audible alarms are initiated to Generator NFPA 110 8.4.2 paralleled to the emergency
alert occupants of a possible hazardous Transfer Switches NFPA 110 8.4.5 bus, Load Shed Priority levels
condition. This alarm occurs without Breakers NFPA 99 4.4.4.1.2
are added, powering their 17
interrupting power to allow for the NFPA 110 8.4.6 associated loads.
safe conclusion of critical procedures. f. The system is now in
Table 1.1-13. Wet Location Applicable Codes
Routine maintenance should be per- Emergency Mode. 18
formed on circuit breakers, transfer 2. Exit from Emergency Mode
Description Standard Section switches, switchgear, generator equip-
General NFPA 99 4.3.2.2.9 ment, etc. by trained professionals a. Automatic transfer switches 19
NEC 517-20 to ensure the most reliable electrical sense the utility source is within
system possible. See Section 43 for acceptable operational toler-
Isolated Power
Systems
NFPA 99
NEC
4.3.2.6
517-160 Eaton - Electrical Services & Systems ances for a time duration set at 20
E-ESS), which provides engineers, the automatic transfer switch.

21

CA08104001E For more information visit: www.eaton.com


1.1-18 Power Distribution Systems
System Design January 2008
Sheet 01 020

b. As each automatic transfer With Utility Paralleling Many health care facilities are taking
i switch transfers back to utility Today, many utilities are offering their advantage of these utility incentives by
power, it removes it’s run customers excellent financial incen- adding generator capacity over and
request from the generator tives to utilize their onsite generation above the NFPA requirements. Figure
ii plant. capacity to remove load from the utility 1.1-21 on Page 1.1-19 shows an exam-
c. When the last automatic trans- grid. These incentives are sometimes ple one-line of a health care facility with
fer switch has retransferred to referred to as Limited Interruptible complete generator backup and utility
1 the utility and all run requests Rates (LIP). Under these incentives, interconnect.
have been removed from the utilities will greatly reduce or eliminate NFPA 110 requirements state that the
generator plant, all generator kWhr or kW Demand charges to their
2 circuit breakers are opened. customers with onsite generation
normal and emergency sources must
be separated by a fire rated wall.
d. The generators are allowed capabilities. In exchange, during times
of peak loading of the utility grid, the The intent of this requirement is so that
3 to run for their programmed
utility can ask their LIP rate customers a fire in one location cannot takeout
cool- down period.
to drop load from the grid by utilizing both sources of power. To meet this
e. The system is now back in their onsite generation capabilities. requirement, the Paralleling Switchgear
4 Automatic/Standby Mode. must be split into separate sections
Health care facilities are ideally suited with a tie bus through a fire rated wall.
to take advantage of these programs For more information on Generator
5 because they already have significant Paralleling Switchgear, see Section 43.
onsite generation capabilities due to
the Code requirements described.
6
Utility
7
Transformer Generators X = Number of Units
8
Utility G1 G2 Gx
Metering
9
Typical
Generator
Breaker
10 Service Main

11 Normal Bus Emergency Bus

Optional Optional Electrically


12 Electrically Operated Stored
Energy Breakers
Operated
Stored EF1 EF2 EFx
F1 F2 Fx
Energy
13 Breakers

14
Equipment Life Safety Critical Load Shed/Load
ATS # 1 ATS # 2 ATS # X Add ATS Units
15 Non-Essential
Loads

Optional Closed
16 EP1 EP2 Typical
Panelboards
EPX Transition
Paralleling of
Generators and
Utility
17
Figure 1.1-20. Typical One-Line for a Paralleling Switchgear Line-up Feeding the Essential Electrical System (EES)
18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.1-19
January 2008 System Design
Sheet 01 021

Utility Fire Rated Wall i


or Separation Barrier

Transformer
Generators X = Number of Units ii
Utility G1 G2 Gx
Metering 1
Utility
Closed
Protective Typical
Relay Transition
Paralleling of Generator
2
Generators and Breaker
Service Main Utility, Plus
Soft Loading/ 3
Unloading
Normal Bus Emergency Bus
TIE Optional TIE 4
Optional Electrically Operated
Electrically Stored Energy
Operated
Field Installed
Cable or Busway
Breakers 5
Stored F1 F2 Fx EF1 EF2 EFx
Energy
Breakers 6

Equipment Life Safety Critical Load Shed/


7
ATS # 1 ATS # 2 ATS # X Load Add
Non-Essential ATS Units
Loads 8
EP1 EP2 EPX Typical
Panelboards 9
Figure 1.1-21. Typical One-Line Health Care Facility with Complete Generator Backup and Utility Interconnect
10

11

12

13

14

15

16

17

18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.1-20 Power Distribution Systems
January 2008
Sheet 01022

This page intentionally left blank.


i

ii

10

11

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.2-1
January 2008 Generator System Design
Sheet 01 023

Generators and Types of Engines Types of Generators


i
Generator Systems Many generator sets are relatively Generators can be either synchronous
small in size, typically ranging from or asynchronous. Asynchronous
several kilowatts to several mega- generators are also referred to as ii
watts. These units are often required induction generators. The construction
to come on line and operate quickly. is essentially the same as an induction
They need to have the capacity to motor. It has a squirrel-cage rotor and 1
run for an extended period of time. wound stator. An induction generator
The internal combustion engine is is a motor driven above its designed
an excellent choice as the prime synchronous speed thus generating 2
mover for the majority of these power. It will operate as a motor if it
applications. Turbines may also be is running below synchronous speed.
Typical Diesel Genset Caterpillar utilized. Diesel fueled engines are the The induction generator does not have 3
most common, but other fuels used an exciter and must operate in parallel
Introduction include natural gas, digester gas, with the utility or another source. The
The selection and application of gener- landfill gas, propane, biodiesel, induction generator requires vars from 4
ators into the electrical distribution crude oil, steam and others. an external source for it to generate
system will depend on the particular power. The induction generator
Some campuses and industrial
application. There are many factors facilities use and produce steam
operates at a slip frequency so its 5
to consider including code require- output frequency is automatically
for heating and other processes. locked in with the utility's frequency.
ments, environmental constraints, These facilities may find it economi-
fuel sources, control complexity, utility cally feasible to produce electricity as An induction generator is a popular
6
requirements and load requirements. a by-product of the steam production. choice for use when designing cogen-
The Health Care Requirements for These installations would typically be eration systems, where it will operate
legally required emergency standby classified as a cogeneration facility in parallel with the utility. This type of
7
generation systems are described producing a fairly constant power generator offers certain advantages
starting on Page 1.1-14. Systems output and operating in parallel with over a synchronous generator. For
described in this section are applicable the electric utility system. example, voltage and frequency are
8
to Health Care requirements, as well controlled by the utility; thus voltage
as other facilities that may require a and frequency regulators are not
high degree of reliability. The electrical required. In addition, the generator
9
supply for data centers, financial construction offers high reliability and
institutions, telecommunications, little maintenance. Also, a minimum
government and public utilities of protective relays and controls are
10
also require high reliability. Threats required. Its major disadvantages are
of disaster or terror attacks have that it requires vars from the system
prompted many facilities to require and it normally cannot operate as a
11
complete self-sufficiency for standby/emergency generator.
continuous operation.
Synchronous generators, however, 12
are the most common. Their output is
determined by their field and governor
controls. Varying the current in the 13
dc field windings controls the voltage
output. The frequency is controlled
by the speed of rotation. The torque 14
applied to the generator shaft by
the driving engine controls the power
output. In this manner, the synchro- 15
nous generator offers precise control
over the power it can generate. In
cogeneration applications, it can be 16
used to improve the power factor of
the system.
17

18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.2-2 Power Distribution Systems
Generator System Design January 2008
Sheet 01 024

Generator Systems Multiple Isolated Standby Generators Multiple generator systems have a
i The second type of generator system more complex control and protection
Emergency Standby Generator System is a multiple isolated set of standby requirement as the units have to be
There are primarily three types of gen- generators. Figure 1.2-2 shows multi- synchronized and paralleled together.
ii erator systems. The first and simplest ple generators connected to a parallel- The generators are required to share
type is a single generator that operates ing bus feeding multiple transfer the load proportionally without swings
independently from the electric utility switches. The utility is the normal or prolonged hunting in voltage or
1 power grid. This is typically referred to source for the transfer switches. The frequency for load sharing. They may
as an Emergency Standby Generator generators and the utility are never also require multiple levels of load
System. Figure 1.2-1 shows a single continuously connected together in shedding and/or load restoration
2 standby generator, utility source this scheme. Multiple generators may schemes to match generation capacity.
and a transfer switch. In this case, the be required to meet the load require- Multiple Generators Operating in
load is either supplied from the utility ments (N system). Generators may be
3 or the generator. The generator and applied in an N+1 or a 2N system for
Parallel with Utility System
the utility are never continuously improved system reliability. The third type of system is either one
connected together. This simple radial with a single or multiple generators
4 system has few requirements for pro- that operate in parallel with the utility
tection and control. It also has the least Utility system. Figure 1.2-3 shows two gener-
impact on the complete electric power G1 G2 ators and a utility source feeding a
5 distribution system. It should be noted switchgear lineup feeding multiple
that this type of generator system loads. This system typically requires
Switchgear
improves overall electrical reliability generator capacity sufficient to carry
6 but does not provide the redundancy the entire load or sophisticated load
that some facilities require if the shedding schemes. This system will
ATS-1 ATS-2
generator fails to start or is out for require a complete and complex
7 maintenance. protection and control scheme. The
electric utility may have very stringent
and costly protection requirements
8 Load 1 Load 2
for the system. IEEE standard 1547
Utility describes the interconnection require-
Figure 1.2-2. Multiple Isolated Set of ments for paralleling to the utility.
9 G1
Standby Generators
In an N system, where N is the number Utility
10 of generators required to carry the G1 G2
load; if a generator fails or is out for
maintenance, then the load may be Switchgear
11 dropped. This is unacceptable for most
ATS critical 24/7 operations. In an N + 1
system, N is the number of generators
12 needed to carry the load and 1 is
an extra generator for redundancy.
If one generator fails to start or is out
13 Load for maintenance, it will not affect the Load 1 Load 2 Load 3
load. In a 2N system, there is complete
100% redundancy in the standby
14 generation system such that the failure Figure 1.2-3. Multiple Generators Operating
Figure 1.2-1. Emergency Standby in Parallel with Utility System
of one complete set of generators
Generator System will not affect the load.
15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.2-3
January 2008 Generator System Design
Sheet 01 025

Generator Fundamentals The application of generators requires need to be switched for 4-wire loads or
A generator consists of two primary
special protection requirements. ground fault relays could misoperate i
The size, voltage class, importance and unbalanced neutral current may
components, a prime mover and an and dollar investment will influence be carried on ground conductors.
alternator. The prime mover is the the protection scheme associated with ii
energy source used to turn the rotor An IEEE working group has studied the
the generator(s). Mode of operation practice of low resistance grounding of
of the alternator. It is typically a diesel will influence the utility company's
combustion engine for most emer- medium voltage generators within the
gency or standby systems. In cogener-
interface protection requirements. general industry. This “working 1
Paralleling with the electric utility is group” found that, for internal genera-
ation applications, the prime mover the most complicated of the utility
may come from a steam driven turbine tor ground faults, the vast majority of
or other source. On diesel units, a gov-
inter-tie requirements. IEEE ANSI 1547 the damage is done after the generator 2
provides recommended practices. breaker is tripped off-line and the field
ernor and voltage regulator are used
to control the speed and power output. and the turbine is tripped. This is due
Generator Grounding to the stored energy in the generator 3
The alternator is typically a synchro- Generator grounding methods need flux that takes several seconds to dissi-
nous machine driven by the prime to be considered and may affect the pate after the generator is tripped off-
mover. A voltage regulator controls its distribution equipment and ratings. line. It is during this time that the Low 4
voltage output by adjusting the field. Generators may be connected in delta Resistance Ground contributes huge
The output of a single generator or or wye but wye is the most typical energy over time into the generator
multiple paralleled generator sets is connection. A wye-connected genera- ground fault. One of the solutions set 5
controlled by these two inputs. The tor can be solidly grounded, low forth by this “working group” is a
alternator is designed to operate at a impedance grounded, high impedance Hybrid High Resistance Grounding
specified speed for the required output grounded or ungrounded. Section 1.4 (HHRG) scheme as shown in Figure 6
frequency, typically 60 or 50 hertz. The discusses general grounding schemes, 1.2-4. In the HHRG scheme, the Low
voltage regulator and engine governor benefits of each and protection Resistance Ground (LRG) is quickly
along with other systems define the considerations. tripped off-line when the generator 7
generator’s response to dynamic protection senses the ground fault.
load changes and motor starting A solidly grounded generator may have
The LRG is cleared at the same time
characteristics. a lower zero sequence impedance than
that the generator breaker clears leav- 8
its positive sequence impedance. In this
ing the High Resistance Ground por-
Generators are rated in power and case, the equipment will need to be
tion connected to control the transient
voltage output. Most generators are rated for the larger available ground
overvoltages during the coast-down 9
designed to operate at a 0.8 power fac- fault current. The generator ground can
phase of the generator thereby all but
tor. For example, a 2000 kW generator be the same as the system ground or it
eliminating generator damage.
at 277/480 V would have a kVA rating
of 2500 kVA (2000 kW/ 08 pf) and a
could be a separate ground. If they are
separate grounds, then the neutral will
10
continuous current rating of 3007 A
( 2500 kVA ⁄ 480V 3 ). 11
HRG
Typical synchronous generators
for industrial and commercial power
Gen
51G
R 59G
12
systems range in size from 100 to 86
3,000 kVA and from 208 V to 13,800 V. R LRG
Phase
There are other ratings available and Relays
87GN 13
these discussions are applicable to
those ratings as well.
Generators must be considered in the 14
short circuit and coordination study as
they may greatly impact the rating of
the electrical distribution system. This 15
is especially common on large installa-
tions with multiple generators and Figure 1.2-4. Hybrid High Resistance Grounding Scheme
systems that parallel with the utility 16
source. Short circuit current contribu-
tion from a generator typically ranges
from 8 to 12 times full load amperes. 17

18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.2-4 Power Distribution Systems
Generator System Design January 2008
Sheet 01 026

i
Generator Controls Generator Short Circuit
The engine generator set has controls Characteristics
to maintain the output frequency
ii (speed) and voltage. These controls If a short circuit is applied directly to
consist of a governor and voltage reg- the output terminals of a synchronous
ulator. As loads change on the system generator it will produce an extremely
1 the frequency and voltage will change. high current initially; gradually
The speed control will then adjust the decaying to a steady state value.
governor to correct for the load (kW) This change is represented by a
2 change. The voltage regulator will
change the field current to adjust
varying reactive impedance. There
are three specific reactance's used for
the voltage to the desired voltage short circuit fault currents. They are:
3 value. These are the basic controls
■ Subtransient reactance Xd” which is
found on all synchronous generators.
used to determine the fault current
Multiple generator systems require during the first 1 to 5 cycles.
4 more sophisticated controls. Genera- ■ Transient reactance Xd’ which is
tors are paralleled in a multi-generator used to determine the fault current
system and they must share the load. during the next 5 to 200 cycles.
5 These systems often have a load shed ■ Synchronous reactance Xd” which
scheme, which adds to the complexity. is used to determine the steady
6 Multiple generator schemes need a state fault current.
master controller to prevent units from The subtransient reactance Xd”
being connected out of phase. The will range from a minimum of
7 sequence of operation is to send a approximately 9% for a two pole
start signal to all generators simulta- round rotor machine to approximately
neously. The first unit up to frequency 32% for a low speed salient pole
8 and voltage will be permitted to close hydro-generator. The initial symmetri-
its respective breaker and energize the cal fault current can be as much
paralleling bus. Breakers for the other as 12 times full load current.
9 generators are held open, not permit-
ted to close, until certain conditions Depending on the generator type,
are met. Once the paralleling bus is the zero sequence impedance may be
10 energized the remaining generators less than the subtransient reactance
must be synchronized to it before and the ground fault current substan-
the generators can be paralleled. tially higher than the three phase short
11 Synchronization compares the volt- circuit current. For example, a 2500
age phasors angle and magnitude. kVA, 480/277 V, 4 pole, 2/3rds pitch
Both generators must be operating stand-by generator has a 0.1411
12 at the same frequency and lined up per unit subtransient reactance Xd”
within typically 5 to 10 degrees with and a 0.033 per unit zero sequence
each other. The voltage magnitude Xo reactance. The ground current is
13 typically must be within 20 to 24%. approximately a third larger than the
three-phase fault current. The ground
A synch-scope is typically supplied on fault current can be reduced to the
14 paralleling gear. The synch-scope dis- three-phase level by simply adding a
plays the relative relationship between small reactance between the generator
voltage phasors on the generator to be neutral and ground while still being
15 paralleled and the bus. If the generator considered solidly grounded.
is running slower than the bus (less
than 60 Hz) then the needle on the The electric power system analysis
16 scope will spin in the counterclockwise must be performed based on the worst
direction. If it is running faster then it case operating conditions. Typically
will rotate in the clockwise direction. this is when all sources are paralleled.
17 The greater the frequency difference, If the system can operate with both
the faster is the rotation. It is important the utility supply and generators in
that the generators are in phase before parallel then the equipment must be
18 they are paralleled. Severe damage rated for the combined fault current
will occur if generators are paralleled plus motor contribution. If the genera-
out-of-phase. tor and utility will not be paralleled,
19 then both cases will need to be looked
at independently and the worst case
used for selecting the equipment
20 ratings.

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.2-5
January 2008 Generator System Design
Sheet 01 027

Generator Protection
Generator protection will vary and Generator Protection ANSI/IEEE
i
depend on the size of the generator, Std 242-1986

type of system and importance of the ii


generator. Generator sizes are defined
as: small — 1000 kVA maximum up 1 1 1 1
to 600 V (500 kVA maximum when 51 Alternate
Location
51V 32 40 1
above 600 V); medium over 1000 kVA
to 12,500 kVA maximum regardless of
voltage; large — from 12,500 – 50,000 2
kVA. The simplest is a single generator
system used to feed emergency
1
and/or standby loads. In this case, 3
3
the generator is the only source Gen 51G 87
available when it is operating and
it must keep operating until the 1
4
normal source returns. 51 Preferred
Location Gen
Figure 1.2-5 Part (A) shows minimum
recommended protection for a single 1 5
generator used as an emergency or 51G
standby system. Phase and ground
time overcurrent protection (Device (A) (A) Single Isolated Generator on Low Voltage System
6
(B)
51 and 51G) will provide protection for (B) Multiple Isolated Generator on Medium Voltage System
external faults. For medium voltage
generators, a voltage controlled time
7
overcurrent relay (Device 51V) is Figure 1.2-5. Typical Protective Relaying Scheme for Small Generators
recommended for the phase protec-
tion as it can be set more sensitive
8
than standard overcurrent relays and
is less likely to false operate on normal R
overloads. This scheme may not pro-
9
vide adequate protection for internal
generator faults when no other power 10
source exists. Local generator control- 50/5A 87-1
lers may offer additional protection
for voltage and frequency conditions 11
50/5A 87-2
outside the generator’s capabilities.
Figure 1.2-5 Part (B) shows the
recommended protection for multiple 50/5A 87-3
12
isolated medium voltage small gener-
ators. Additional protection may be
desired and could include generator 13
differential, reverse power and loss of
field protection. Differential protection
(Device 87) can be accomplished with 14
either a self-balancing set of CTs as Gen
in Figure 1.2-6 or with a percentage
differential scheme as in Figure 1.2-7 15
on Page 1.2-6. The percentage differ-
ential scheme offers the advantage
of reducing the possibility for false 16
tripping due to CT saturation. The
self-balancing scheme offers the
advantages increased sensitivity; Figure 1.2-6. Self-Balancing Generator 17
needing three current transformers Differential Relay Scheme
in lieu of six and the elimination of
current transformer external wiring 18
from the generator location to the
generator switchgear location.
19

20

21

CA08104001E For more information visit: www.eaton.com


1.2-6 Power Distribution Systems
Generator System Design January 2008
Sheet 01 028

Reverse power protection (Device 32)


i is used to prevent the generator
from being motored. Motoring could
Grounding
damage (with other hazards) the prime Resistor
ii mover. A steam turbine could overheat
51G
and fail. A diesel or gas engine could
either catch fire or explode. A steam
1 turbine can typically withstand
approximately 3% reverse power
where a diesel engine can withstand
2 up to 25% reverse power.
Loss of field protection (Device 40) is
3 needed when generators are operating 87

in parallel with one another or the 01 R1


power grid. When a synchronous PC
4 generator loses its field, it will con- R1

tinue to generate power as an induc- 02 R2


tion generator obtaining its excitation Gen
R2
5 from the other machines on the OC
03
system. During this condition, the R3

rotor will quickly overheat due to the 87G R3


6 slip frequency currents induced in it.
Loss of excitation in one machine
could jeopardize the operation of
7 the other machines beyond their 52
capability and the entire system.

9
OC = Operating Coil
To Main Bus PC = Permissive Coil
10
Figure 1.2-7. Generator Percentage Differential Relay (Phase Scheme)
11 and Ground Differential Scheme Using a Directional Relay

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.2-7
January 2008 Generator System Design
Sheet 01 029

Typical protection for larger genera-


tors is shown in Figure 1.2-8. It adds i
phase unbalance and field ground
fault protection. Phase unbalance 3
(Device 46) or negative sequence
87B
ii
overcurrent protection prevents the 81U/O
generators from rotor overheating
damage. Unbalanced loads, fault 1
conditions or open phasing will
27/59
produce a negative sequence current
to flow. The unbalanced currents 2
induce double system frequency
currents in the rotor, which quickly
causes rotor overheating. Serious 3 1 1 1 3
damage will occur to the generator 51V 40 32 46
if the unbalance is allowed to persist.
3 1 4
Other protection functions such as 87G
87
under/over voltage (Device 27/59) 60
could be applied to any size generator. Voltage Regulator and 5
The voltage regulator typically main- Metering Circuits
tains the output voltage within its 1
desired output range. This protection 1 64 6
can provide backup protection in case 49
the voltage regulator fails. Under/over
frequency protection (Device 81U/81O) 7
could be used for backup protection Gen
for the speed control. Synch check E

relays (Device 25) are typically applied 8


as a breaker permissive close function
where generators are paralleled.
Many modern protective relays are 51G
9
microprocessor-based and provide a
full complement of generator protec- 10
tion functions in a single package.
The cost per protection function has
been drastically reduced such that it 11
is feasible to provide more complete
protection even to smaller generators. Figure 1.2-8. Typical Protective Relaying Scheme for Large Generator

IEEE ANSI 1547 provides recom- 12


mended practices for utility inter-tie
protection. If the system has closed
transition or parallel capability, addi- 13
tional protection may be required by
the utility. Typically, no additional pro-
tection is required if the generator is 14
paralleled to the utility for a maximum
of 100 msec or less. Systems that
offer soft transfer, peak shaving or 15
co-generation will require additional
utility inter-tie protection. The
protection could include directional 16
overcurrent and power relays
and even transfer trip schemes.
Please consult your local utility 17
for specific requirements.
18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.2-8 Power Distribution Systems
Generator System Design January 2008
Sheet 01 030

i Generator Set Sizing Typical rating definitions for diesel Electrical rating definitions for natural
gensets are: standby, prime plus 10, gas powered gensets are typically
and Ratings continuous and load management defined as standby or continuous with
(paralleled with or isolated from definitions similar to those mentioned
ii Many factors must be considered utility). Any diesel genset can have above for diesels. Natural gas gensets
when determining the proper size or several electrical ratings depending recover more slowly than diesel
electrical rating of an electrical power on the number of hours of operation gensets when subjected to block
1 generator set. The engine or prime per year and the ratio of electrical loads. Diesel engines have a much
mover is sized to provide the actual load/genset rating when in operation. more direct path from the engine gov-
or real power in kW, as well as speed The same diesel genset can have a ernor and fuel delivery system to the
2 (frequency) control through the use
of an engine governor. The generator
standby rating of 2000 kW at 0.8 power combustion chamber and this results
factor (pf) and a continuous rating of in a very responsive engine-generator.
is sized to supply the kVA needed at 1825 kW at 0.8 pf. The lower continu- A natural gas engine is challenged
3 startup and during normal running ous rating is due to the additional with air-fuel flow dynamics and a
operation and it also provides voltage hours of operation and higher load much more indirect path from the
control using a brushless exciter and that the continuous genset must engine governor (throttle actuator)
4 voltage regulator. Together the engine carry. These additional requirements and fuel delivery system (natural
and generator provide the energy put more stress on the engine and gas pressure regulator, fuel valve and
necessary to supply electrical loads generator and therefore the rating actuator, carburetor mixer, aftercooler,
5 in many different applications is decreased to maintain longevity intake manifold) to the combustion
encountered in today’s society. of the equipment. chamber and this results in a
The generator set must be able to less responsive engine-generator.
6 supply the starting and running
Different generator set manufacturers Diesel gensets recover about twice
use basically the same diesel genset as fast as natural gas gensets.
electrical load. It must be able to pick electrical rating definitions and these
up and start all motor loads and low
7 power factor loads, and recover with-
are based on international diesel For the actual calculations involved
fuel stop power standards from for sizing a genset, there are readily
out excessive voltage dip or extended organizations like ISO, DIN and accessible computer software pro-
recovery time. Non-linear loads like
8 variable frequency drives, uninterrupt-
others. A standby diesel genset rating grams which are available on the
is typically defined as supplying vary- genset manufacturer's Internet sites
ible power supply (UPS) systems and ing electrical loads for the duration of a or from the manufacturer's dealers
switching power supplies also require
9 attention because the SCR switching
power outage with the load normally or distributors. These programs are
connected to utility, genset operating used to quickly and accurately size
causes voltage and current waveform < 100 hours per year and no overload generator sets for their application.
distortion and harmonics. The har-
10 monics generate additional heat in the
capability. A prime plus 10 rating is The programs take into consideration
typically defined as supplying varying the many different parameters dis-
generator windings and the generator electrical loads for the duration of a cussed above including the size and
may need to be upsized to accommo-
11 date this. The type of fuel (diesel,
power outage with the load normally type of the electrical loads (resistive,
connected to utility, genset operating inductive, SCR etc.), reduced voltage
natural gas, propane etc.) used is ≤ 500 hours per year and overload soft starting devices (RVSS), motor
12 important as it is a factor in determin- capability of 10% above its rating types, voltage, fuel type, site condi-
ing generator set transient response. for one hour out of twelve. A continu- tions, ambient conditions and other
It is also necessary to determine ous rating is typically defined as variables. The software will optimize
13 the load factor or average power supplying unvarying electrical loads the starting sequences of the motors
consumption of the generator set. (i.e., base loaded) for an unlimited time. for the least amount of voltage dip
This is typically defined as the load The load management ratings apply to and determine the starting kVA needed
14 (kW) x time (hrs. while under that gensets in parallel operation with the from the genset. It also provides
particular load) / total running time. utility or isolated/islanded from utility transient response data including
When this load factor or average and these ratings vary in usability voltage dip magnitude and recovery
15 power is taken into consideration from < 200 hours per year to unlimited duration. If the transient response is
with peak demand requirements usage. Refer to generator set manufac- unacceptable, then design changes
and the other operating parameters turers for further definitions on load can be considered including oversizing
16 mentioned above, the overall electrical
rating of the genset can be deter-
management ratings, load factor or the generator to handle the additional
average power consumption, peak kvar load, adding RVSS devices to
mined. Other items to consider include demand and how these ratings are reduce the inrush current, improving
17 the unique installation, ambient and typically applied. Even though there is system power factor and other
site requirements of the project. These some standardization of these ratings methods. The computer software
will help to determine the physical across the manufacturers, there also programs are quite flexible in that they
18 configuration of the overall system. exists some uniqueness with regards allow changes to the many different
to how each manufacturer applies variables and parameters to achieve
their generator sets. an optimum design. The software
19 allows, for example, minimizing
voltage dips or using paralleled
gensets vs. a single genset.
20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.2-9
January 2008 Generator System Design
Sheet 01 031

Genset Sizing Guidelines Generator Set Installation ■ Hazardous waste considerations


i
for fuel, antifreeze, engine oil.
Some conservative rules of thumb and Site Considerations ■ Meeting local building and
for genset sizing include:
There are many different installation electrical codes.
1. Oversize genset 20 – 25% for parameters and site conditions ■ Genset exposure (coastal
ii
reserve capacity and for motor that must be considered to have a conditions, dust, chemicals etc.).
starting. successful generator set installation. ■ Properly sized starting systems 1
2. Oversize gensets for unbalanced The following is a partial list of areas (compressed air, batteries and
loading or low power factor to consider when conducting this charger).
running loads. design. Some of these installation ■ Allowing adequate space for 2
parameters include: installation of the genset and for
3. Use 1/2 hp per kW for motor loads. maintenance (i.e., air filter removal,
■ Foundation type (crushed rock,
4. For variable frequency drives, concrete, dirt, wood, separate oil changing, general genset 3
oversize the genset by at concrete inertia pad etc.). inspection etc…).
least 40%. ■ Foundation to genset vibration ■ Flex connections on all systems that
dampening (spring type, cork are attached to the genset and a 4
5. For UPS systems, oversize the rigid structure (fuel piping, founda-
genset by 40% for 6 pulse and and rubber etc.).
tion vibration isolators, exhaust, air
15% for 6 pulse with input filters ■ Noise attenuation (radiator fan intake, control wiring, power cables, 5
or 12 pulse. mechanical noise, exhaust noise, radiator flanges/duct work etc.).
air intake noise).
6. Always start the largest motor ■ Diesel fuel day tank systems
first when stepping loads.
■ Combustion and cooling air (pumps, return piping).
6
requirements.
■ Fuel storage tank (double walled,
For basic sizing of a generator system, ■ Exhaust backpressure requirements.
the following example could be used: ■ Emissions permitting.
fire codes) and other parameters. 7
■ Delivery and rigging requirements. Please see the generator set manufac-
Step 1: Calculate Running Amperes turer’s Application and Installation
■ Motor loads: ■ Genset derating due to high Guidelines for proper application 8
❑ 200 hp motor . . . . . . . . . . . . 156 A
altitudes or excessive ambient and operation of their equipment.
temperatures.
❑ 100 hp motor . . . . . . . . . . . . . 78 A 9
❑ 60 hp motor . . . . . . . . . . . . . . 48 A
■ Lighting Load . . . . . . . . . . . . . . 68 A
■ Miscellaneous Loads . . . . . . . . 95 A
10
■ Running Amperes . . . . . . . . . . 445 A

Step 2: Calculating Starting Amperes


11
Using 1.25 Multiplier
■ Motor loads: 12
❑ . . . . . . . . . . . . . . . . . . . . . . . 195 A
❑ . . . . . . . . . . . . . . . . . . . . . . . . 98 A
❑ . . . . . . . . . . . . . . . . . . . . . . . . 60 A
13
■ Lighting Load . . . . . . . . . . . . . . 68 A
■ Miscellaneous Loads . . . . . . . . 95 A 14
■ Starting Amperes . . . . . . . . . . 516 A

Step 3: Selecting kVA of Generator 15


■ Running kVA =
(445 A x 480 V x 1.732)/
1000 = 370 kVA 16
■ Starting kVA =
(516 A x 480 V x 1.732)/ 17
1000 = 428 kVA
Solution
Generator must have a minimum
18
starting capability of 428 kVA and min-
imum running capability of 370 kVA. Figure 1.2-9. Typical Genset Installation 19
Note: Courtesy of Caterpillar, Inc.
Also, please see Section “Factors Gov-
erning Voltage Drop” on Page 1.3-21
for further discussion on generator 20
loading and reduced voltage starting
techniques for motors.
21

CA08104001E For more information visit: www.eaton.com


1.2-10 Power Distribution Systems
January 2008
Sheet 01032

This page intentionally left blank.


i

ii

10

11

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-1
January 2008 System Analysis
Sheet 01 033

Systems Analysis The principal types of computer Short circuit calculations define
i
programs utilized to provide system momentary and steady-state fault
A major consideration in the studies include: currents for LV and MV breaker and
design of a distribution system is to fuse duty and bus bracings at any
ensure that it provides the required
■ Short circuit — identify 3-phase and selected location in the system and also ii
line-to-ground fault currents and determine the effect on the system
quality of service to the various
system impedances. after removal of utility power due to
loads. This includes serving each
load under normal conditions and, ■ Arc flash — calculates arc flash breaker operation or scheduled power 1
under abnormal conditions, providing energy levels which lead to the outages. Computer software programs
the desired protection to service selection of personal protective can identify the fault current at any
and system apparatus so that equipment (PPE). bus, in every line or source connected 2
interruptions of service are minimized ■ Circuit breaker duty — identify to the faulted bus, or to it and every
consistent with good economic and asymmetrical fault current based adjacent bus, or to it and every bus
mechanical design. on X/R ratio. which is one and two buses away, or 3
■ Protective device coordination — currents in every line or source in the
Under normal conditions, the impor- system. The results of these calculations
determine characteristics and set-
tant technical factors include voltage
tings of medium voltage protective permit optimizing service to the loads 4
profile, losses, load flow, effects of while properly applying distribution
relays and fuses, and entire low
motor starting, service continuity and apparatus within their intended limits.
voltage circuit breaker and fuse
reliability. The prime considerations
coordination.
5
under faulted conditions are apparatus The following additional studies
protection, fault isolation and service ■ Load flow — simulate normal should be considered depending
continuity. During the system prelimi- load conditions of system voltages, upon the type and complexity of the 6
nary planning stage, before selection power factor, line and transformer distribution system, the type of facility
of the distribution apparatus, several loadings. and the type of loads to be connected
distribution systems should be analyzed ■ Motor starting — identify system to the system: 7
and evaluated including both economic voltages, motor terminal voltage,
motor accelerating torque, and ■ Harmonic Analysis
and technical factors. During this stage
if system size or complexity warrant, motor accelerating time when ■ Transient Stability 8
it may be appropriate to provide a starting large motors. ■ Insulation Coordination
thorough review of each system under ■ Grounding Study
both normal and abnormal conditions. ■ Switching Transient 9

10

11

12

13

14

15

16

17

18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.3-2 Power Distribution Systems
System Analysis January 2008
Sheet 01 034

i Short Circuit Currents — The ac component is not constant rated secondary current. Limiting the
if rotating machines are connected power source fault capacity will thereby
General to the system because the impedance reduce the maximum fault current from
of this apparatus is not constant. The the transformer.
ii The amount of current available in a
short circuit fault is determined by the
rapid variation of motor and generator
impedance is due to these factors: The electric network which determines
capacity of the system voltage sources the short circuit current consists of an
1 and the impedances of the system, Subtransient Reactance (x d" ), deter- ac driving voltage equal to the pre-
including the fault. Voltage sources mines fault current during the first fault system voltage and an imped-
include the power supply (utility or cycle, and after about 6 cycles this ance corresponding to that observed
2 on-site generation) plus all rotating value increases to the transient reac- when looking back into the system
machines connected to the system at tance. It is used for the calculation from the fault location. In medium
the time of the fault. A fault may be of the momentary interrupting and/or and high voltage work, it is generally
3 either an arcing or bolted fault. In an momentary withstand duties of satisfactory to regard reactance as the
arcing fault, part of the circuit voltage is equipment and/or system. entire impedance; resistance may be
consumed across the fault and the total neglected. However, this is normally
Transient Reactance (x d ' ), which deter-
4 fault current is somewhat smaller than
mines fault current after about 6 cycles
permissible only if the X/R ratio of the
for a bolted fault, so the latter is the medium voltage system is equal to or
worst condition, and therefore is the and this value in 1/2 to 2 seconds more than 25. In low voltage (1000 volts
increases to the value of the synchro-
5 value sought in the fault calculations.
nous reactance. It is used in the setting
and below) calculations, it is usually
worthwhile to attempt greater accuracy
Basically, the short circuit current is of the phase OC relays of generators by including resistance with reactance
determined by applying Ohm’s Law and medium voltage circuit breakers.
6 to an equivalent circuit consisting of
in dealing with impedance. It is for this
Synchronous Reactance (xd ), which reason, plus ease of manipulating the
a constant voltage source and a time various impedances of cables and
varying impedance. A time varying determines fault current after steady
7 impedance is used in order to account state condition is reached. It has no buses and transformers of the low
effect as far as short circuit calcula- voltage circuits, that computer studies
for the changes in the effective voltages are recommended before final selection
of the rotating machines during the tions are concerned but is useful in
8 fault. In an ac system, the resulting the determination of relay settings. of apparatus and system arrangements.
short circuit current starts out higher Transformer Impedance, in percent, is When evaluating the adequacy
in magnitude than the final steady of short circuit ratings of medium
9 state value and asymmetrical (due
defined as that percent of rated primary
voltage circuit breakers and fuses,
voltage that must be applied to the
to the dc offset) about the X-axis. transformer to produce rated current both the rms symmetrical value and
10 The current then decays toward a flowing in the secondary, with second- asymmetrical value of the short circuit
lower symmetrical steady-state value. ary shorted through zero resistance. current should be determined.
The time varying characteristic of the Therefore, assuming the primary
impedance accounts for the symmetri- For low voltage circuit breakers and
11 cal decay in current. The ratio of the
voltage can be sustained (generally fuses, the rms symmetrical value
referred to as an infinite or unlimited should be determined along with
reactive and resistive components (X/R supply), the maximum current a trans-
ratio) accounts for the dc decay, see either: the X/R ratio of the fault at
12 Figure 1.3-1. The fault current consists
former can deliver to a fault condition is the device or the asymmetrical short
the quantity of (100 divided by percent circuit current.
of an exponentially decreasing direct- impedance) times the transformer
13 current component superimposed
upon a decaying alternating-current.
The rate of decay of both the dc and ac Total Current - A Wholly Offset
Asymmetrical Alternating Wave
14 components depends upon the ratio of
reactance to resistance (X/R) 3.0
rms Value of Total Current
of the circuit. The greater this ratio, Alternating Component -
2.5
15 the longer the current remains higher Symmetrical Wave
than the steady-state value which it rms Value of
2.0
would eventually reach. Alternating Component
16 The total fault current is not symmetrical 1.5
Scale of Curent Values

with respect to the time-axis because


of the direct-current component, 1.0
17 hence it is called asymmetrical current.
0.5
The dc component depends on the
point on the voltage wave at which 1 2 3 4
18 the fault is initiated.
0

See Table 1.3-2 for multiplying factors 0.5


19 that relate the rms asymmetrical value
of Total Current to the rms symmetri- -1.0
cal value, and the peak asymmetrical Direct Component - The Axis
20 value of Total Current to the rms
-1.5 of Symmetrical Wave Time in Cycles of
a 60 Hz Wave
symmetrical value. -2.0
21
Figure 1.3-1. Structure of an Asymmetrical Current Wave

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-3
January 2008 System Analysis
Sheet 01 035

Fault Current Waveform Relationships i


The following Figure 1.3-2 describes Based on a 60 Hz system and t = 1/2 cycle
the relationship between fault (ANSI/IEEEC37.13.1990/10.1.4)
current peak values, rms symmetrical – 2 π 60
----------------
ii
values and rms asymmetrical values 120 –π
Ip  ---------------- ----------
depending on the calculated X/R ratio. Peak multiplication factor = ----- = 2 1 + e X ⁄ R  = 2  1 + e
X⁄R
I    1
The table is based on the following  
general formulas:


– ωt
------------
( – 2 ) ( 2 π 60 )
-------------------------------
120 –2 π
2
1. Ip = I 2  1 + e X ⁄ R I rms asym -------------------------------
X⁄R
------------
X⁄R
  rms multiplication factor = ------------------------------ = 1 + 2e = 1 + 2e
  I 3
– 2ωt Example for X/R =15
---------------
X⁄R
2. I rms asym = I 1 + 2e –π 4
 ------- 
15 
Peak mf = 2  1 + e 
= 2.5612
Where:   5
I = Symmetrical rms current
–2 π
Ip = Peak current ----------
rms mf = 1 + 2e
15
= 1.5217 6
e = 2.718
ω=2πf 7
f = Frequency in Hz
t = Time in seconds 8

2.8
9
2.7 10
PEAK MAXIMUM ASYMMETRICAL

RMS MAXIMUM ASYMMETRICAL


Based Upon: rms Asym = dc 2 + rms Sym2
2.6 with dc V e
RMS SYMMETRICAL

Taken at Current Peak


T 11

RMS SYMMETRICAL
2.5

2.4 12
2.3
13
2.2 1.8
R
O
CT

14
FA

2.1 1.7
N
ATION FACTOR =

O
TI

ATION FACTOR =
CA

2.0 1.6
15
LI
IP
LT

1.9 1.5
U
M

R
AK

CTO 16
PE

1.8 FA 1.4
PEAK MULTIPLICA

ON
RMS MULTIPLICA

TI
1.7 ICA 1.3
IPL 17
LT
L

M U
L

1.6 RMS 1.2

1.5 1.1
18
1.4
1 1.5 2 2.5 3 4 5 6 7 8 9 10 15 20 25 30 40 50 60 70 80 90 100 19
CIRCUIT X/R RATIO
A (T
TAN PHASE)
20
Figure 1.3-2. Relation of X/R Ratio to Multiplication Factor
21

CA08104001E For more information visit: www.eaton.com


1.3-4 Power Distribution Systems
System Analysis January 2008
Sheet 01 036

i Fault Current Calculations Synchronous Motors — Use 5.0 times Medium Voltage Motors
motor full load current (impedance
value of 20%). If known, use actual values otherwise
The calculation of asymmetrical cur-
use the values indicated for the same
rents is a laborious procedure since
ii the degree of asymmetry is not the
When the motor load is not known, type of motor.
the following assumptions generally
same on all three phases. It is common
practice for medium voltage systems,
are made: Calculation Methods
1 to calculate the rms symmetrical fault 208Y/120 V Systems The following pages describe various
current, with the assumption being methods of calculating short circuit
■ Assume 50% lighting and 50%
made that the dc component has currents for both medium and low
2 decayed to zero, and then apply
motor load.
voltage systems. A summary of the
a multiplying factor to obtain the first or types of methods and types of calcula-
half-cycle rms asymmetrical current, tions is as follows:
3 which is called the “momentary cur- ■ Assume motor feedback contribu-
tion of twice full load current of ■ Medium Voltage Switchgear —
rent.” For medium voltage systems
transformer. exact method . . . . . . . . . Page 1.3-5
(defined by IEEE as greater than 1000
4 volts up to 69,000 volts) the multiply- or
■ Medium Voltage Switchgear —
ing factor is established by NEMA quick check table . . . . . . Page 1.3-7
and ANSI standards depending upon 240/480/600 V 3-Phase, 3-Wire or ■ Medium Voltage Switchgear
5 the operating speed of the breaker. 4-Wire Systems Example 1 — Verify ratings of
For low voltage systems, short circuit ■ Assume 100% motor load. breakers . . . . . . . . . . . . . Page 1.3-8
study software usually calculates the ■ Medium Voltage Switchgear
6 symmetrical fault current and the or Example 2 — Verify ratings
faulted system X/R ratio using ANSI of breakers with rotating
■ Assume motors 25% synchronous
guidelines. If the X/R ratio is within the loads . . . . . . . . . . . . . . . . Page 1.3-9
7 standard, and the breaker interrupting
and 75% induction.
■ Medium Voltage Switchgear
current is under the symmetrical fault or Example 3 — Verify ratings
value, the breaker is properly rated. If
8 the X/R ratio is higher than ANSI stan- ■ Assume motor feedback contribu- of breakers with
tion of four times full load current generators . . . . . . . . . . . Page 1.3-10
dards, the study applies a multiplying
factor to the symmetrical calculated of transformer. ■ Medium Voltage Fuses —
9 value (based on the X/R value of the exact method . . . . . . . . . Page 1.3-11
480Y/277 V Systems in Commercial Buildings ■ Power Breakers — Asymmetry
system fault) and compares that value
to the breaker symmetrical value to ■ Assume 50% induction motor load. derating factors . . . . . . . Page 1.3-11
10 assess if it is properly rated. In the past, ■ Molded Case Breakers — asymmetry
or
especially using manual calculations, a derating factors . . . . . . . Page 1.3-12
multiplying factor of 1.17 (based on ■ Assume motor feedback contribu-
11 the use of an X/R ratio of 6.6 represent- tion of two times full load current
■ Short Circuit Calculations —
Short cut method for
ing a source short circuit power factor of transformer or source. a system . . . . . . . . . . . . . Page 1.3-13
of 15%) was used to calculate the
12 asymmetrical current. These values
■ Short Circuit Calculations —
Short cut method for
take into account that medium voltage end of cable . . . . . . . . . . Page 1.3-15
breakers are rated on maximum asym-
13 metry and low voltage breakers are ■ Short Circuit Calculations —
rated average asymmetry. Short cut method for end of
cable chart method . . . . Page 1.3-16
14 To determine the motor contribution ■ Short Circuit Currents —
during the first half-cycle fault current, Chart of transformers 300 to
when individual motor horsepower 3750 kVA . . . . . . . . . . . . . Page 1.5-9
15 load is known, the subtransient reac-
tances found in the IEEE Red should
be used in the calculations. When the
16 system motor load is unknown, the
following assumptions generally
are made:
17
Induction Motors — Use 4.0 times
motor full load current (impedance
18 value of 25%).
Note: For motors fed through adjustable
frequency drives or solid-state soft starters,
19 there is no contribution to fault current, unless
1) they have an internal run contactor or
2) they have a bypass contactor.
20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-5
January 2008 System Analysis
Sheet 01 037

Fault Current Calculations a voltage = maximum rated voltage


divided by K (for example, 4.76/1.24 =
greater than the available system fault
current of 20,000 amperes, the breaker i
for Specific Equipment — 3.85). If this breaker is applied in a is acceptable (assumes the breaker’s
Exact Method system rated at 2.4 kV the calculated momentary and fault close rating is
fault current must be less than 36 kA. also acceptable). ii
The purpose of the fault current calcu- For example, consider the following case: Note: If the system available fault current
lations is to determine the fault current were 22,000 amperes symmetrical, this
at the location of a circuit breaker, fuse Assume a 12.47 kV system with breaker could not be utilized even though 1
or other fault interrupting device in 20,000 amperes symmetrical available. the “Maximum Symmetrical Interrupting
order to select a device adequate for the In order to determine if an Eaton’s Capability” is greater than 22,000 since
calculated fault current or to check the Cutler-Hammer Type 150 VCP-W 500 Test 1 calculation is not satisfied. 2
thermal and momentary ratings of non- vacuum breaker is suitable for this
interrupting devices. When the devices application, check the following: For approximate calculations, Table 1.3-1
to be used are ANSI-rated devices, the provides typical values of % reactance 3
fault current must be calculated and the From Table 5.4-1 in Section 5 under (X) and X/R values for various rotating
device selected as per ANSI standards. column “Rated Maximum Voltage” equipment and transformers. For sim-
The calculation of available fault current
V = 15 kV, under column “Rated short plification purposes, the transformer 4
circuit Current” I = 18 kA, “Rated impedance (Z) has been assumed to be
and system X/R rating is also utilized Voltage Range Factor” K = 1.3. primarily reactance (X). In addition, the
to verify adequate bus bar bracing and
momentary withstand ratings of Test 1 for V/Vo x I or 15 kV/12.47 kV x resistance (R) for these simplified cal- 5
18 kA = 21.65; also check K x I (which culations has been ignored. For detailed
devices such as contactors. calculations, the values from the IEEE
is shown in the column headed
Medium Voltage VCP-W “Maximum Symmetrical Interrupting Red Book Standard 141, for rotating 6
Capability”) or 1.3 x 18 kA = 23.4 kA. machines, and ANSI C57 and/or C37
Metal-Clad Switchgear Since both of these numbers are for transformers should be utilized.
The applicable ANSI Standards C37 7
is the latest applicable edition. The Table 1.3-1. Reactance X
following is a review of the meaning System Reactance X Used for Typical Values and Range
of the ratings. (See Section 5.) Component Short Circuit Close and Latch on Component Base 8
Duty (Momentary) % Reactance X/R Ratio
The Rated Maximum Voltage
This designates the upper limit of 2-Pole Turbo Generator
4-Pole Turbo Generator
X
X
X
X
9 (7 – 14)
15 (12 – 17)
80 (40 – 120)
80 (40 – 120)
9
design and operation of a circuit
breaker. For example, a circuit breaker Hydro Generator with Damper Wedges X X 20 (13 – 32) 30 (10 – 60)
with a 4.76 kV rated maximum voltage and Synchronous Condensers
10
cannot be used in a 4.8 kV system. Hydro Generator without Damper Windings .75X .75X 16 (16 – 50) 30 (10 – 60)
All Synchronous Motors 1.5X 1.0X 20 (13 – 35) 30 (10 – 60)
K-Rated Voltage Factor Ind. Motors Above 1000 hp, 1800 Rpm 1.5X 1.0X 17 (15 – 25) 30 (15 – 40) 11
The rated voltage divided by this factor and Above 250 hp, 3600 Rpm
determines the system kV a breaker can All Other Induction Motors 50 hp and Above 3.0X 1.2X 17 (15 – 25) 15 (2 – 40)
be applied up to the short circuit kVA Ind. Motors Below 50 hp and Neglect Neglect — — 12
rating calculated by the formula All Single-Phase Motors
Distribution System from Remote X X As Specified 15 (5 – 15)
3 × Rated SC Current × Rated Max. Voltage Transformers or Calculated 13
Note: Interrupting capabilities of some of Current Limiting Reactors X X As Specified 80 (40 – 120)
or Calculated
today’s vacuum breakers may have K = 1,
whereby the interrupting current is constant Transformers 14
across its entire operating range. OA to 10 MVA, 69 kV X X 8.0 18 (7 – 24)
OA to 10 MVA, above 69 kV X X 8.0 to 10.5 18 (7 – 24)
Rated Short Circuit Current
FOA 12 to 30 MVA X X Depends on 20 (7 – 30) 15
This is the symmetrical rms value of Primary
FOA 40 to 100 MVA X X Windings BIL 38 (32 – 44)
current that the breaker can interrupt
at rated maximum voltage. It should
Rating 16
be noted that the product 3 x 4.76 x Table 1.3-2. Typical System X/R Ratio Range (for Estimating Purposes)
29,000 = 239,092 kVA is less than the
nominal 250,000 kVA listed. This Type of Circuit X/R Range 17
rating (29,000 amperes) is also the Remote generation through other types of circuits such as transformers rated 10 MVA 15 or less
base quantity that all the “related” or smaller for each 3-phase bank, transmission lines, distribution feeders, etc.
capabilities are referred to. Remote generation connected through transformer rated 10 MVA to 100 MVA 15 – 40
18
for each 3-phase bank, where the transformers provide 90 percent or more
Maximum Symmetrical Interrupting of the total equivalent impedance to the fault point.
Capability Remote generation connected through transformers rated 100 MVA or larger 30 – 50 19
This is expressed in rms symmetrical for each 3-phase bank where the transformers provide 90 percent or more
amperes or kiloamperes and is K x I of the total equivalent impedance to the fault point.
rated; 29,000 x 1.24 = 35,960 rounded Synchronous machines connected through transformers rated 25 to 100 MVA 30 – 50 20
to 36 kA. for each 3-phase bank.
Synchronous machines connected through transformers rated 100 MVA and larger. 40 – 60
This is the rms symmetrical current
that the breaker can interrupt down to
Synchronous machines connected directly to the bus or through reactors. 40 – 120 21

CA08104001E For more information visit: www.eaton.com


1.3-6 Power Distribution Systems
System Analysis January 2008
Sheet 01 038

The Close and Latch Capability impedances and their X/R ratios are Step 3: Reduce the reactance network
i This is also a related quantity expressed given in Table 1.3-1. to an equivalent reactance. Call this
in rms asymmetrical amperes by 1.6 x reactance XI.
The ANSI Standard C37.010 allows the
maximum symmetrical interrupting
ii capability. For example 1.6 x 36 = 57.6
use of the X values only in determin- Step 4: Setup the same network for
ing the E/X value of a fault current. The resistance values.
or 58 kA, or 1.6 K x rated short circuit R values are used to determine the X/R
current. Step 5: Reduce the resistance network
1 ratio, in order to apply the proper mul-
to an equivalent resistance. Call this
Another way of expressing the close tiplying factor, to account for the total
fault clearing time, asymmetry, and resistance RI. The above calculations
and latch rating is in terms of the peak of XI and RI may be calculated by
2 current, which is the instantaneous decrement of the fault current.
several computer programs.
value of the current at the crest. ANSI The steps in the calculation of fault
Standard C37.09 indicates that the currents and breaker selection are Step 6: Calculate the E/XI value, where
3 ratio of the peak to rms asymmetrical described hereinafter: E is the prefault value of the voltage at
value for any asymmetry of 100% to the point of fault nominally assumed
20% (percent asymmetry is defined as Step 1: Collect the X and R data of the 1.0 pu.
4 the ratio of dc component of the fault circuit elements. Convert to a common X
in per unit to 2 ) varies not more than kVA and voltage base. If the reactances Step 7: Determine X/R = ------I as
previously calculated. RI
±2% from a ratio of 1.69. Therefore the and resistances are given either in
5 close and latch current expressed in ohms or per unit on a different voltage Step 8: Go to the proper curve for
terms of the peak amperes is = 1.6 x or kVA base, all should be changed the type of fault under consideration
1.69 x K x rated short circuit current. to the same kVA and voltage base. (3-phase, phase-to-phase, phase-to-
6 This caution does not apply where ground), type of breaker at the location
In the calculation of faults for the pur- the base voltages are the same as
poses of breaker selection, the rotating (2, 3, 5 or 8 cycles), and contact parting
the transformation ratio. time to determine the multiplier to the
7 machine impedances specified in
calculated E/XI.
ANSI Standard C37.010 Article 5.4.1 Step 2: Construct the sequence
should be used. The value of the networks and connect properly for the See Figures 1.3-3, 1.3-4 and 1.3-5 for
8 impedances and their X/R ratios should type of fault under consideration. Use 5-cycle breaker multiplying factors.
be obtained from the equipment man- the X values required by ANSI Stan- Use Figure 1.3-5 if the short circuit is
ufacturer. At initial short circuit studies, dard C37.010 for the “interrupting” fed predominantly from generators
9 data from manufacturers is not available. duty value of the short circuit current. removed from the fault by two or more
Typical values of

10
130 130 130

11 120 120 120


8

7
5

110 110 110


12
4
6

12
10
5

100
6
100 100
4

4
13
3

90 90 90 3

14 80 80 80
IME
Ratio X/R
Ratio X/R

Ratio X/R
TIME

70 70
GT

70
15
IN
ING

RT

60 60 60
PA
T
PAR

16 50 50
AC

50
NT
T
AC

CO
NT

40 40 40
17
CO

30 30 30
5-CYCLE 5-CYCLE 5-CYCLE
BREAKER BREAKER BREAKER
18 20 20 20

10 10 10
19
1.0 1.1 1.2 1.3 1.4 1.0 1.1 1.2 1.3 1.4 1.0 1.1 1.2 1.3 1.4

20 Multiplying Factors for E / X Amperes Multiplying Factors for E / X Amperes Multiplying Factors for E / X Amperes

Figure 1.3-3. 3-phase Fault Multiplying Figure 1.3-4. Line-to-Ground Fault Multiplying Figure 1.3-5. 3-phase and Line-to-Ground
21 Factors Which Include Effects of ac and Factors Which Include Effects of ac and Fault Multiplying Factors Which Include
dc Decrement dc Decrement Effects of dc Decrement Only

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-7
January 2008 System Analysis
Sheet 01 039

transformations or the per unit reac- Section 5 of ANSI C37 provides further Application Above 3,300 Feet (1,000 m)
tance external to the generation is 1.5 guidance for medium voltage breaker The rated one-minute power frequency i
times or more than the subtransient application. withstand voltage, the impulse with-
reactance of the generation on a com- stand voltage, the continuous current
mon base. Also use Figure 1.3-5 where Reclosing Duty
rating, and the maximum voltage rating ii
the fault is supplied by a utility only. ANSI Standard C37.010 indicates the must be multiplied by the appropriate
reduction factors to use when circuit correction factors below to obtain
Step 9: Interrupting duty short circuit breakers are used as reclosers. Cutler- modified ratings which must equal or 1
current = E/XI x MFx = E/X2. Hammer VCP-W breakers are listed at exceed the application requirements.
Step 10: Construct the sequence 100% rating factor for reclosing.
(positive, negative and zero) networks Note: Intermediate values may be obtained 2
by interpolation.
properly connected for the type of Application Quick Check Table
fault under consideration. Use the
X values required by ANSI Standard For application of circuit breakers in a
Table 1.3-3. Altitude Derating 3
Altitude in Correction Factor
C37.010 for the “Close and Latch” radial system supplied from a single
Feet (Meters) Current Voltage
duty value of the short circuit current. source transformer. Short circuit duty
was determined using E/X amperes
4
Step 11: Reduce the network to an 3,300 (1,006) (and Below) 1.00 1.00
and 1.0 multiplying factor for X/R ratio 5,000 (1,524) 0.99 0.95
equivalent reactance. Call the reac- of 15 or less and 1.25 multiplying 10,000 (3,048) 0.96 0.80
tance X. Calculate E/X x 1.6 if the factor for X/R ratios in the range of
5
breaker close and latch capability is 15 to 40.
given in rms amperes or E/X x 2.7 if
the breaker close and latch capability Table 1.3-4. Application Quick Check Table 6
is given in peak or crest amperes. Source Operating Voltage
Transformer kV
Step 12: Select a breaker whose: MVA Rating 7
a. Maximum voltage rating exceeds Motor Load 2.4 4.16 6.6 12 13.8
the operating voltage of the system: 100% 0%
8
V max 1 1.5
E
b. ------- ≤ I × -------------- ≤ KI 1.5 2 50 VCP-W 250
X2 Vo
2 2.5 12 kA 50 VCP-W 250
10.1 kA
150 VCP-W 500
23 kA
150 VCP-W 500
22.5 kA
150 VCP-W 500
19.6 kA
9
2.5 3
See Table 6.0-1, Section 6. 3 3.75

Where:
3.75 5 50 VCP-W 250 10
5 7.5 36 kA 50 VCP-W 250
I = Rated short circuit current 7.5 10 50 VCP-W 350 33.2 kA

Vmax = Rated maximum voltage 10  10 49 kA 11


of the breaker 10 12 
12 15 50 VCP-W 350 75 VCP-W 500
VD = Actual system voltage 46.9 kA 41.3 kA 12
15 20
KI = Maximum symmetrical
interrupting capacity 20  20 Breaker Type and 150 VCP-W 750 150 VCP-W 750
25 Symmetrical Interrupting Capacity 35 kA 30.4 kA 13
c. E/X x 1.6 ≤ rms closing and 30 at the Operating Voltage
latching capability of the breaker 50  150 VCP-W 1000 150 VCP-W 1000
46.3 kA 40.2 kA 14
and/or
 Transformer impedance 6.5% or more, all other transformer impedances are 5.5% or more.
E/X x 2.7 ≤ Crest closing and
latching capability of the breaker.
15
The ANSI standards do not require the
inclusion of resistances in the calcula- 16
tion of the required interrupting and
close and latch capabilities. Thus the
calculated values are conservative. 17
However, when the capabilities of
existing switchgears are investigated,
the resistances should be included. 18
For single line-to-ground faults the
symmetrical interrupting capability 19
is 1.15 x the symmetrical interrupting
capability at any operating voltage
but not to exceed the maximum 20
symmetrical capability of the breaker.

21

CA08104001E For more information visit: www.eaton.com


1.3-8 Power Distribution Systems
System Analysis January 2008
Sheet 01 040

Application on Symmetrical Current Rating Basis For 3-Phase Fault


i E-
I 3-Phase = ----
Example 1 — Fault Calculations X
Given a circuit breaker interrupting and momentary rating in the table below,
ii verify the adequacy of the ratings for a system without motor loads, as shown.
where X is ohms per phase and E is
the highest typical line-to-neutral
Table 1.3-5. Short Circuit Duty operating voltage or
1 Type V Max. 3-Phase Symmetrical Interrupting Capability Close and Latch or
I
Breaker at V Max. Max. KI at 4.16 kV Oper. Voltage Momentary I 3-Phase = ----B-
X
2 50VCP – W250 4.76 kV 29 kA 36 kA 4.76
----------- (29) = 33.2 kA I1
58 kA I3
where X is per unit reactance
4.16
LG Symmetrical Interrupting Capability IB is base current
3 — 36 kA 1.15 (33.2) = 38.2 kA I2
Base current I B = −−3.75 MVA
−−−−−−−−−−−−−−−−− = .52 kA
Note: Interrupting capabilities I1 and I2 at operating voltage must not exceed maximum 3 ( 4.16 kV )
4 symmetrical interrupting capability Kl.

Check capabilities I1, I2 and I3 on the following utility system where there is no I .52 - = 8.6 kA Sym.
I 3-Phase = ----1- = -----------------
5 motor contribution to short circuit. X .0604
24,200 Watts Load Losses
System X
−− = 9 (is less than 15)
6 13.8 kV
On 13.8 kV System, 3.75 MVA Base
R
would use 1.0 multiplying factor for
X short circuit duty, therefore, short
7 R
= 15 3.75 MVA- = .01 pu or 1%
Z = -------------------------------- circuit duty is 8.6 kA sym. for 3-phase
375 MVA
fault I1 and momentary duty is 8.6 x
375 MVA 1.6 = 13.7 kA I3.
8 Available 2 2 2 2X
2 
Z = X + R = R  -------2- + 1
R  For Line-to-Ground Fault
9 3I B
3E - = --------------------------
Z - = ---------------
1 - = -----------------
1 - = .066% I LG = -------------------------- -
R = ---------------------- ˙ 2X 1 + X 0 2X 1 + X 0
13.8 kV 2 266 15.03
X
10 -------- + 1
2 For this system, X0 is the zero sequence
3750 kVA R reactance of the transformer which
is equal to the transformer positive
11 X = X
sequence reactance and X1 is the posi-
----- ( R ) = 15 (.066) = .99% tive sequence reactance of the system.
R
12 4.16 kV Transformer Standard 5.5% Impedance Therefore,
has a ±7.5% Manufacturing Tolerance
3(.52)
I LG = −−−−−−−−−−−−−−−−−−−−−−−−−− = 9.1 kA Sym.
13 50VPC-W250 5.50 Standard Impedance 2(.0604) + .0505
-.41 (-7.5% Tolerance)
Transformer Z = Using 1.0 multiplying factor (see
5.09%
Table 1.3-6), short-circuit duty = 9.1 kA
14 Sym. LG (I2)
Answer
15 Figure 1.3-6. Example 1 — One-Line Diagram
The 50VCP-W250 breaker capabilities
From transformer losses per unit or percent exceed the duty requirements and
16 R is calculated may be applied.

31,000 Watts Full Load 24.2 kW - = .0065 pu or .65%


R = ------------------------------- With this application, short cuts could
17 – 6,800 Watts No Load 3750 kVA have been taken for a quicker check of
the application. If we assume unlim-
2 2 2 2 ited short circuit available at 13.8 kV
18 Transformer X = Z –R (5.09) – (.65) = 25.91 – .42 = 25.48 and that Trans. Z = X
X = 5.05%
I .52- = 9.5 kA Sym.
Then I 3-Phase = ----B- = -------------
19 X .055
X R X/R
13.8 kV System .99% .066% 15 X/R ratio 15 or less multiplying factor
20 Transformer 5.05% .65% 8 is 1.0 for short circuit duty.
System Total 6.04% .716 % 9
The short circuit duty is then 9.5 kA
or .0604 pu .00716 pu
Sym. (I1, I2) and momentary duty is
21 9.5 x 1.6 kA = 15.2 kA (I3).

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-9
January 2008 System Analysis
Sheet 01 041

Example 2 — Fault Calculations


Given the system shown with motor 13.8 kV System i
loads, calculate the fault currents X = 15
and determine proper circuit breaker 21 kA Sym. Available
selection.
13.8 kV R ii
X = 5.5% X
All calculations on per unit basis. 7500 kVA Z = 5.53% = 10
R = 0.55% R
7.5 MVA Base 1
7.5 MVA- = .628 kA 6.9 kV
Base Current I B = ------------------------------
3 6.9 kV
1 2

X R X/R 3
13.8 kV System
X X
= 25 = 35
X = .628 (6.9)
----------- --------------- = .015 .015 .001 15 R R 4
21 (13.8) 2 3
197A FL 173A FL
Transformer .055 .0055 10 X''d = 20% X''d = 25%
Total Source Transformer .070 pu .0065 pu 11
5
3000 hp Synchronous Motor 3000 hp
1.0 PF 2500 hp
Ind.
6
X = .20 (.628)
------------------- = .638 pu at 7.5 MVA base Syn.
.197
2500 hp Ind. Motor 7
Figure 1.3-7. Example 2 — One-Line Diagram
(.628)- = .908 pu at 7.5 MVA base
X = .25 ------------------
(.173) Source of Interrupting Momentary X X (1) 1 8
Short Circuit Current E/X Amperes E/X Amperes R R (X) R
E- = I----B- where X on per unit base I3 Source Transformer .628 .628 11 11 = 157
I 3-Ph = ---- .070
= 8.971
.070
= 8.971
.070 9
X X
I1 3000 hp Syn. Motor .628 .628 25 = 39
= .656 = .984 25
Table 1.3-6. Multiplying Factor for E/X (1.5) .638 .638 .638
Amperes (ANSI C37.010, 1979, Figures 1.1-8, I1 2500 hp Syn. Motor .628
= .461
.628
= .691 35 35 = 39
10
1.1-9 and 1.1-10) (1.5) .908 .908 .908
System Type VCP-W Vacuum I3F = 10.088 10.647 Total 1/R = 235
X/R Circuit Breaker or 10.1 kA x 1.6 11
Rated Interrupting Time, 5 Cycle 17.0 kA Momentary Duty
Type of Fault
Ratio 3-Phase LG 3-Phase & LG I B = .628 = .062
Total X = -------
12
- --------------
Source of Short Circuit I 3F 10.1
Local Remote 13
System X
----- = .062 (235) = 14.5 is a Multiplying Factor of 1.0 from Table 1.3-6
1 1.00 1.00 1.00 R
15  1.00 1.00 1.00
20 1.00 1.02 1.05 Table 1.3-7. Short Circuit Duty = 10.1 kA 14
25 1.00 1.06 1.10
30 1.04 1.10 1.13 Breaker V 3-Phase Symmetrical Interrupting Capability Close and Latch
Type Max. or Momentary
36 1.06 1.14 1.17 at V Max. Max. KI at 6.9 kV Oper. Voltage 15
40 1.08 1.16 1.22
45 1.12 1.19 1.25 75VCP-W500 8.25 kV 33 kA 41 kA 8.25 (33) = 39.5 kA 66 kA
50 1.13 1.22 1.27 6.9
55 1.14 1.25 1.30 150VCP-W500 15 kV 18 kA 23 kA 15 (18) (39.1) = 23 kA 37 kA
16
60 1.16 1.26 1.32 6.9
65 1.17 1.28 1.33 (But not to exceed KI)
70 1.19 1.29 1.35 17
75 1.20 1.30 1.36 Answer
80 1.21 1.31 1.37
85 — — 1.38
Either breaker could be properly 18
90 1.22 1.32 1.39 applied, but price will make the type
95 — — 1.40 150VCP-W500 the more economical
100 1.23 1.33 1.41 selection. 19
100 1.24 1.34 1.42
120 1.24 1.35 1.43
130 1.24 1.35 1.43
 Where system X/R ratio is 15 or less, the
20
Multiplying Factor is 1.0.

21

CA08104001E For more information visit: www.eaton.com


1.3-10 Power Distribution Systems
System Analysis January 2008
Sheet 01 042

Example 3 — Fault Calculations Answer


i Check breaker application or generator bus for the system of generators shown. The 50VCP-W250 breaker could be
Each generator is 7.5 MVA, 4.16 kV 1040 amperes full load, I B = 1.04 kA applied.
ii Sub transient reactance Xd” = 11% or, X = 0.11 pu

1 X- ratio is 30
Gen ----
R

2 1 1 1 1 3 1 1 1 1 3
−−−− = −− + −− + −− = −− and −−− = −− + −− + −− = −−
XS X X X X RS R R R R

3 XS = X
G1 G2 G3
or X S = X R
----- and R S = ---- Therefore, System --------
X- = 30
----- = Gen ----
3 3 RS R R
4
Since generator neutral grounding reactors are used to limit the I LG to I3-phase or
below, we need only check the I3 short circuit duty.
5
I I I 31
I B Phase = ----B- + ----B- + ----B- + ----------B- = 3(1.04)
4.16 kV
----------------------- = 28.4 kA Symmetrical E/X Amperes
X X X X .11
6
System X
----- of 30 is a Multiplying Factor of 1.04 from Table 1.3-6.
7 R
Short-circuit duty is 28.4 (1.04) = 29.5 kA Symmetrical
8 3-Phase Symmetrical Interrupting Capability Figure 1.3-8. Example 3 — One-Line Diagram
Breaker Type V Max. at V Max. Max. KI at 4.16 kV Oper. Voltage
50VCP-W250 4.76 kV 29 kA 36 kA 4.76
9 4.16
(29) = 33.2 kA

10

11

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-11
January 2008 System Analysis
Sheet 01 043

Medium Voltage Fuses — Step 4 — Construct the sequence includes induction and synchronous
motor loads. The assumption is made i
networks using resistances and
Fault Calculations connect properly for the type of that in 208Y/120-volt systems the
fault under consideration and reduce contribution from motors is 2 times the
There are two basic types of medium to a single equivalent resistance. full load current of step-down trans- ii
voltage fuses. The following definitions former. This corresponds to an assumed
are taken from ANSI Standard C37.40. Step 5 — Calculate the E/XI value, 50% motor aggregate impedance on a
Expulsion Fuse (Unit)
where E is the prefault value of the kVA base equal to the transformer kVA 1
voltage at the point of fault normally rating or 50% motor load. For 480-,
A vented fuse (unit) in which the assumed 1.0 in pu. For 3-phase faults 480Y/277- and 600-volt systems the
expulsion effect of the gases produced E/XI is the fault current to be used in assumption is made that the contribu- 2
by internal arcing, either alone or aided determining the required interrupting tion from the motors is four times
by other mechanisms, results in current capability of the fuse. the full load current of the step-down
interruption. transformer which corresponds to an 3
Note: It is not necessary to calculate a
Current-Limiting Fuse (Unit) single phase-to-phase fault current. This assumed 25% aggregate motor imped-
current is very nearly 3 /2 x 3-phase fault. ance on a kVA base equal to the trans-
A fuse unit that, when its current-
responsive element is melted by a
The line-to-ground fault may exceed the former kVA rating or 100% motor load. 4
3-phase fault for fuses located in generating
current within the fuse’s specified stations with solidly grounded neutral In low voltage systems which contain
current- limiting range, abruptly generators, or in delta-wye transformers generators the subtransient reactance 5
introduces a high resistance to with the wye solidly grounded, where the should be used.
reduce current magnitude and sum of the positive and negative sequence
duration, resulting in subsequent impedances on the high voltage side (delta) If the X/R to the point of fault is greater
current interruption. is smaller than the impedance of the than 6.6, a derating multiplying factor 6
transformer. (MF) must be applied. The X/R ratio is
There are two classes of fuses; calculated in the same manner as that
power and distribution. They are For single line-to-ground fault; for medium voltage circuit breakers. 7
distinguished from each other by X I = X I (+) + X I (–) + X I (0) Calculated symmetrical amperes x
the current ratings and minimum
MF ≤ breaker interrupting rating. 8
melting type characteristics.
E ×3
I f = ------ The multiplying factor MF can be
The current limiting ability of a XI calculated by the formula:
current limiting fuse is specified by 9
its threshold ratio, peak let-through – ( π ) ⁄ ( X/R )
current and I2t characteristics.
Step 6 — Select a fuse whose 2 [ 1 + 2.718 ]
published interrupting rating MF = −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
Interrupting Ratings of Fuses exceeds the calculated fault current.
2.29 10
If the X/R of system feeding the
Modern fuses are rated in amperes Figure 1.3-2 should be used where breaker is not known, use X/R = 15.
rms symmetrical. They also have a older fuses asymmetrically rated are 11
listed asymmetrical rms rating which involved. For fused breakers by the formula:
is 1.6 x the symmetrical rating.
The voltage rating of power fuses used
1 + 2 × ( 2.718 )
– ( 2π ) ⁄ ( X/R ) 12
Refer to ANSI/IEEE C37.48 for fuse on 3-phase systems should equal MF = −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
interrupting duty guidelines. or exceed the maximum line-to-line 1.25

Calculation of the Fuse Required


voltage rating of the system. Current If the X/R of the system feeding the 13
limiting fuses for 3-phase systems breaker is not known, use X/R = 20.
Interrupting Rating: should be so applied that the fuse
Step 1 — Convert the fault from Refer to Table 1.3-8 for the standard
the utility to percent or per unit on
voltage rating is equal to or less than
ranges of X/R and Power Factors used
14
1.41 x nominal system voltage.
a convenient voltage and kVA base. in testing and rating low voltage break-
ers. Refer to Table 1.3-9 for the circuit 15
Step 2 — Collect the X and R data of all Low Voltage Power Circuit breaker interrupting rating multiplying
the other circuit elements and convert
to a percent or per unit on a conve- Breakers — Fault Calculations factors to be used when the calculated
X/R ratio or power factor at the point 16
nient kVA and voltage base same as The steps for calculating the fault cur- the breaker is to be applied in the
that used in Step 1. Use the substran- rent for the selection of a low voltage power distribution system falls outside
sient X and R for all generators and of the Table 1.3-8 X/R or power factors
motors.
power circuit breaker are the same as
those used for medium voltage circuit used in testing and rating the circuit
17
Step 3 — Construct the sequence breakers except that where the con- breakers. MF is always greater than 1.0.
networks using reactances and connect nected loads to the low voltage bus 18
properly for the type of fault under
consideration and reduce to a single
equivalent reactance. 19

20

21

CA08104001E For more information visit: www.eaton.com


1.3-12 Power Distribution Systems
System Analysis January 2008
Sheet 01 044

i Molded Case Breakers and Low Voltage Circuit Breaker


Insulated Case Circuit Interrupting Derating Factors
ii Breakers — Fault Calculations Refer to Table 1.3-8 for the standard Established standard values include
ranges of X/R and power factors used the following:
The method of fault calculation is the
in testing and rating low voltage
same as that for low voltage power Table 1.3-8. Standard Test Power Factors
1 circuit breakers. Again the calculated
breakers. Refer to Table 1.3-9 for
the circuit breaker interrupting rating Interrupting Power Factor X/R Test
fault current x MF ≤ breaker interrupt- Rating in kA Test Range Range
de-rating factors to be used when the
ing capacity. Because molded case
2 breakers are tested at lower X/R ratios
calculated X/R ratio or power factor Molded Case Circuit Breaker
at the point the breaker is to be applied 10 or Less .45 – .50 1.98 – 1.73
the MFs are different than those for
in the power distribution system falls Over 10 to 20 .25 – .30 3.87 – 3.18
low voltage power circuit breakers. Over 20 .15 – .20 6.6 – 4.9
3 outside of the Table 1.3-8 X/R or power
factors used in testing and rating the Low Voltage Power Circuit Breaker
– π ⁄ −
X 2

1 + 2.718  R 2 circuit breakers. All .15 Maximum 6.6 Minimum
4 MF = ----------------------------------------------------
Normally the short circuit power factor
– π ⁄ −
X 1
− For distribution systems where the
1 + 2.718  R 1 or X/R ratio of a distribution system
calculated short circuit current X/R
need not be considered in applying
5 low voltage circuit breakers. This is
ratio differs from the standard values
X 1 ⁄ R 1 = test X/R value. given in the above table, circuit breaker
because the ratings established in
interrupting rating derating factors from
the applicable standard are based
6 X 2 ⁄ R 2 = X/R at point where breaker on power factor values which amply
Table 1.3-9 table should be applied.
is applied. cover most applications.
7
Table 1.3-9. Circuit Breaker Interrupting Rating Derating Factors
% P.F. X/R Interrupting Rating
8 Molded Case or Insulated Case Power Circuit Breaker
>10 kA
< / = 10 kA < / = 20 kA >20 kA Unfused Fused
9
50 1.73 1.000 1.000 1.000 1.000 1.000
30 3.18 .847 1.000 1.000 1.000 1.000
10 25 3.87 .805 .950 1.000 1.000 1.000
20 4.90 .762 .899 1.000 1.000 1.000
15 6.59 .718 .847 .942 1.000 .939
12 8.27 .691 .815 .907 .962 .898
11 10 9.95 .673 .794 .883 .937 .870
8.5 11.72 .659 .778 .865 .918 .849
7 14.25 .645 .761 .847 .899 .827
12 5 19.97 .627 .740 .823 .874 .797

Note: These are derating factors applied to the breaker and are the inverse of MF.
13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-13
January 2008 System Analysis
Sheet 01 045

Short Circuit Calculations — Short Cut Method i


Determination of Short Circuit Current
Note 1: Transformer impedance generally relates to self-ventilated rating (e.g., with OA/FA/FOA transformer use OA base). ii
Note 2: kV refers to line-to-line voltage in kilovolts.
Note 3: Z refers to line-to-neutral impedance of system to fault where R + jX = Z.
Note 4: When totaling the components of system Z, arithmetic combining of impedances as “ohms Z”. “per unit Z”. etc., is considered a 1
short cut or approximate method; proper combining of impedances (e.g., source, cables transformers, conductors, etc). should use
individual R and X components. This Total Z = Total R + j Total X (See IEEE “Red Book” Standard No. 141).

1. Select convenient kVA base for system to


2
be studied.
kVA base 2
(a) Per unit = pu impedance kVA base 2 = −−−−−−−−−−−−−−− × (pu impedance on kVA base 1)
2. Change per unit, or percent, impedance from
one kVA base to another:
kVA base 1 3
kVA base 2
(b) Percent = % impedance kVA base 2 = −−−−−−−−−−−−−−− × (% impedance on kVA base 1)
kVA base 1
(ohms impedance) (kVA base)
4
3. Change ohms, or percent or per-unit, etc.: (a) Per unit impedance = pu Z = percent −−−−−−−−−−−−−− = −−−−−−−−−−(−kV
−−−−−−−−−−−−impedance −−−−−2−−−−−−−−−− −−−−−−−−−−−−−−
) ( 1000 )
100

(b) % impedance = % Z =
(ohms impedance) (kVA base)
−−−−−−−−−−−−−−−−2−−−−−−−−−− −−−−−−−−−−−−−−
( kV ) ( 10 )
5
(% impedance) ( kV )2
(c) Ohms impedance = −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−(10)
−−−−
kVA base 6
4. Change power-source impedance to per-unit (a) — if utility fault capacity given in kVA
or percent impedance on kVA base as selected
for this study: kVA base in study
7
Per-unit impedance = pu Z = ------------------------------------------------------------------------------------------
-
power-source kVA fault capacity

(b) — if utility fault capacity given in rms symmetrical short circuit amperes 8
kVA base in study
Per-unit impedance = pu Z = ---------------------------------------------------------------------------------------------------------------
-
(short-circuit current) ( 3 )(kV of source) 9
5. Change motor rating to kVA: (a) — motor kVA — ( 3 ) (kV) (I) where I = motor nameplate full-load amperes
(b) — if 1.0 power factor synchronous motor kVA = (0.8) (hp)
10
(c) — if 0.8 power factor synchronous motor kVA = (1.0) (hp)
(d) — if induction motor kVA = (1.0) (hp)

3-phase kVA
11
6. Determine symmetrical short circuit current: (a) Base current = I Base = −−−−−−−−−−−−−−−−− or −−−−1-phase
−−−−−−−−−−−−kVA
−−−−−−−
( 3 ) ( kV ) kV line-to-neutral

(b) Per unit I SC = −1.0


−−−−
12
puZ

(c) rms Symmetrical current = ISC = (pu ISC) (IBase Amperes)


13
3-phase kVA base 1-phase kVA base
(d) rms Symmetrical current = Amperes = -------------------------------------------------- or --------------------------------------------------
( puZ ) ( 3 ) ( kV ) ( puZ ) ( kV )
(3-phase kVA base) (100) 1-phase kVA base (100)
14
(e) = ---------------------------------------------------------------------- or ------------------------------------------------------------------
(%Z) ( 3 ) ( kV ) (%Z) ( kV )

(g)
(kV) (1000)
= ----------------------------------- 15
3 (ohms Z)

(a) Symmetrical short circuit kVA = kVA base (kVA base) (100) ( kV )2 ( 1000 )
-------------------------- = ---------------------------------------------- = ----------------------------------
7. Determine symmetrical short circuit kVA: ( puZ ) %Z ohms Z 16
3(line-to-neutral kV) 2 ( 1000 )
(b) = -----------------------------------------------------------------------------
(ohms Z)
17
8. Determine line-to-line short circuit current: (a) — from 3-phase transformer — approx. 86% of 3-phase current
(b) — three single-phase transformers (e.g., 75 kVA, Z = 2%) calculate same as one 3-phase unit
(i.e., 3 x 75 kVA = 225 kVA, Z = 2%). 18
(c) — from single-phase transformer — see Page 1.3-15.

19
9. Determine motor contribution (or feedback) as
source of fault current:
(a) — synchronous motor — 5 times motor full load current (impedance 20%) See IEEE
(b) — induction motor — 4 times motor full-load current (impedance 25%) Standard No. 141 
(c) — motor loads not individually identified, use contribution from group of motors as follows:
— on 208Y/120 volt systems — 2.0 times transformer full-load current 20
— on 240-480-600 volt 3-phase, 3-wire systems — 4.0 times transformer full-load current
— on 480Y/277 volt 3-phase, 4-wire systems
— In commercial buildings, 2.0 times transformers full-load current (50% motor load)
— In industrial plants, 4.0 times transformer full-load current (100% motor load) 21

CA08104001E For more information visit: www.eaton.com


1.3-14 Power Distribution Systems
System Analysis January 2008
Sheet 01 046

Example Number 1
i
How to Calculate Short Circuit Currents at Ends of Conductors
ii A. System Diagram B. Impedance Diagram (Using “Short Cut” Method for Combining Impedances
and Sources).
1 A B C
Utility Source 500 MVA
V
Major Contribution
Utility
2
Cables
Transformer
3 1,000 kVA
V
Switchboard Fault
5.75%
480 Volts Cables
4
Cable Fault
Switchboard Fault

5 .002 pu 1.00 pu 1.00 pu 1.00 pu


100 Feet (30 m)
3 – 350 kcmil Cable
6 A B C
in Steel Conduit
.0575 pu .027 pu .027 pu .027 pu
Switchboard Fault
Mixed Load — Motors and Lighting
7 Each Feeder — 100 Feet (30 m) of 3 – 350 kcmil
.027 pu
Cable in Steel Conduit Feeding Lighting and
250 kVA of Motors Cable Fault
8 Cable Fault
Combining Series Impedances: ZTO L = 1 + Z2 + ... +Zn

9 C. Conductor impedance from Table 1.5-19, Combining Parallel Impedances:


1
ZTOTAL
= 1 + 1 + ... 1
Z1 Z2 Zn
Page 1.5-14. Conductors: 3 – 350 kcmil cop-
per, single conductors Circuit length: 100 feet
10 (30 m), in steel (magnetic) conduit Impedance
.0595 pu .342 pu .0507 pu
Z = 0.00619 ohms/100 feet (30 m).
ZTOT = 0.00619 ohms (100 circuit feet) E .0777 pu
11 .027 pu .027 pu
D. Fault current calculations (combining imped-
ances arithmetically, using approximate
12 “Short Cut” method — see Note 4,
Page 1.3-13)

13 Equation
Step (See) Calculation
1 – Select 1000 kVA as most convenient base, since all data except utility source is on
secondary of 1000 kVA transformer.
14
2 4(a) kVA base
Utility per unit impedance = Z pu = ------------------------------------------ 1000
- = --------------------- = 0.002 pu
utility fault kVA 500.000
15 %Z = 5.75 = 0.0575 pu
3 3(a) Transformer per unit impedance = Z pu = ---------
- -----------
100 100

16 4 4(a) and kVA base


Motor contribution per unit impedance = Z pu = --------------------------------------- 1000
- = -------------------- = 1.00 pu
9(c) 4 x motor kVA 4 x 250

17 5 3(a) Cable impedance in ohms (see above) = 0.00619 ohms


(ohms)(kVA base) = (0.00619)(1000) = 0.027pu
Cable impedance per unit = Z pu = -------------------------------------------------
- -------------------------------------------
2 2
(kV) (1000) (0.480) (1000)
18
6 6(d) Total impedance to switchboard fault = 0.0507 pu (see diagram above)
3-phase kVA base =
19 Symmetrical short circuit current at switchboard fault = −−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−1000
−−−−−−−−−−−−−−−− = 23,720 amperes rms
( Z pu ) ( 3 ) ( kV ) ( 0.0507 ) ( 3 ) ( 0.480 )

7 6(d) Total impedance to cable fault = 0.0777 pu (see diagram above)


20
Symmetrical short circuit current at cable fault = 3-phase kVA base =
−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−1000
−−−−−−−−−−−−−−−− = 15, 480 amperes rms
( Z pu ) ( 3 ) ( kV ) ( 0.0777 ) ( 3 ) ( 0.480 )
21
Figure 1.3-9. Example Number 1

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-15
January 2008 System Analysis
Sheet 01 047

Example Number 2
i
Fault Calculation — Secondary Side of Single-Phase Transformer

A. System Diagram Deriving Transformer R and X:


ii
R = 0.1498 Z
{
480-Volt 3-Phase Switchboard Bus at 50,000 Amp Symmetrical, X/R = 6.6 X = 0.9887 Z X
− = 6.6 X = 6.6 R
R 1
2 2 2 2 2 2 2
Z= X +R = ( 6.6R ) + R = 43.56R + R = 44.56R = 6.6753R
100 Ft. Two #2/0 Copper Conductors, Magnetic Conduit R = 0.0104 Ohms
{
X = 0.0051 Ohms 2
R= −−−−Z−−−− R = 0.1498Z
6.6753
75 kVA
V Single-Phase 480-120/240 Volts; Z = 2.8%, R = 1.64%, X = 2.27%
X = 6.6R X = 0.9887Z 3
120 Volts
F2
Half-winding of Transformer
{ Multiply % R by 1.5
Multiply % X by 1.2 } Reference: IEEE Standard No. 141 4
240 V Full-winding of Transformer
F1

B. Impedance Diagram — Fault F1 C. Impedance Diagram — Fault F2 5

RSyst = 0.00054 RSyst = 0.00356 RSyst = 0.00054 XSyst = 0.00356 6


RCond = 0.00677 RCond = 0.00332 RCond = 0.00677 XCond = 0.00332

RTfmr = 0.0164 RTfmr = 0.0227 RTfmr = 0.0246 XTfmr = 0.0272 7


RTotal
T = 0.02371 RTotal
T = 0.02958 RTotal
T = 0.03191 XTotal
T = 0.03408
F1 F1 F2 F2
8
D. Impedance and Fault Current Calculations — 75 kVA Base
Note: To account for the outgoing and return paths of single-phase circuits (conductors,
systems, etc.) use twice the 3-phase values of R and X. 9
75
ZSyst = −−−−−−−−−−−−−−−−−−−−−−−−−−− = 0.0018 pu (From Page 1.3-13 RSyst = 2 (0.1498 x Z) = 0.00054 pu
3 × 0.480 × 50,000 Formula 4(b) )
XSyst = 2 (0.9887 x Z) = 0.00356 pu 10
×−−kVA 0.0104 × 75
RCond = 2  −−−−−−2−−−−−−−−−−−
ohms Base
ZCond = −−−−−−−−−−− −−−−−−−−−−−− (From Page 1.3-13 = 0.00677 pu
( kV ) × 1000
2  0.48 × 1000
Formula 3(a) )
0.0051 × 75 
11
XCond = 2  −−−−−−−−− −−−−−−−−−− = 0.00332 pu
 ( 0.48 ) 2 × 1000
Full-winding of Transformer (75 kVA Base)
1.64
RTfmr = −−−−− = 0.0164 pu 12
100
2.27
XTfmr = −−−−− = 0.0277 pu
100 13
1.64
Half-winding of Transformer (75 kVA Base) RTfmr = 1.5 ( −−−−− ) = 0.0246 pu
100
14
XTfmr = 1.2 ( 2.27
−−−−− ) = 0.0272 pu
100

Impedance to Fault F1 — Full Winding Z= 2


( 0.02371 ) + ( 0.02958 )
2 = 0.03791 pu 15
Impedance to Fault F2 — Half Winding
Z= 2 2 = 0.04669 pu
Short circuit current F1 = 75 ÷ (0.03791 x 0.240 kV) = 8,243 Ampere Symmetrical ( 0.03191 ) + ( 0.03408 )
Short circuit current F2 = 75 ÷ (0.04669 x 0.120 kV) = 13,386 Ampere Symmetrical 16
Figure 1.3-10. Example Number 2
17
Method 1: Short Cut Methods — of the conductors can be calculated Add source and conductor impedance or
as follows. 0.00923 + 0.00273 = 0.01196 total ohms
End of Cable
This method uses the approximation 277 volts/30,000 amperes = 0.00923 Next, 277 volts/0.01196 ohms = 23,160 18
of adding Zs instead of the accurate ohms (source impedance) amperes rms at load side of conductors
method of Rs and Xs. Conductor ohms for 500 kcmil conduc- 19
tor from reference data in this section X 30,000 amperes available
For Example: For a 480/277-volt sys-
tem with 30,000 amperes symmetrical in magnetic conduit is 0.00551 ohms 100 feet (30 m)
available at the line side of a conductor per 100 feet (30 m). For 100 feet (30 m) 2 – 500 kcmil per phase 20
run of 100 feet (30 m) of 2 – 500 kcmil and 2 conductors per phase we have:
per phase and neutral, the approxi- X If = 23,160 amperes
0.00551/2 = 0.00273 ohms (conductor 21
mate fault current at the load side end impedance) Figure 1.3-11. Short Circuit Diagram

CA08104001E For more information visit: www.eaton.com


1.3-16 Power Distribution Systems
System Analysis January 2008
Sheet 01 048

Method 2: Chart Approximate Method Step Five


i The chart method is based on the following: Enter the chart along the bottom horizontal scale with the
distance (in feet) from the transformer to the fault point.
Motor Contribution Draw a vertical line up the chart to the point where it inter-
ii For system voltages of 120/208 volts, it is reasonable to sects the selected curve. Then draw a horizontal line to the
assume that the connected load consists of 50% motor load, left from this point to the scale along the left side of the chart.
and that the motors will contribute four times their full load
1 current into a fault. For system voltages of 240 and 480 volts, Step Six
it is reasonable to assume that the connected load consists The value obtained from the left-hand vertical scale is the fault
of 100% motor load, and that the motors will contribute current (in thousands of amperes) available at the fault point.
2 four times their full load current into a fault. These motor
contributions have been factored into each curve as if all For a more exact determination, see the formula method.
motors were connected to the transformer terminals. It should be noted that even the most exact methods for
3 calculating fault energy use some approximations and some
Feeder Conductors assumptions. Therefore, it is appropriate to select a method
The conductor sizes most commonly used for feeders which is sufficiently accurate for the purpose, but not more
4 from molded case circuit breakers are shown. For conductor burdensome than is justified. The charts which follow make
sizes not shown, the following table has been included for use of simplifications which are reasonable under most cir-
conversion to equivalent arrangements. In some cases it cumstances and will almost certainly yield answers which
5 may be necessary to interpolate for unusual feeder ratings. are on the safe side. This may, in some cases, lead to appli-
Table 1.3-10 is based on using copper conductor. cation of circuit breakers having interrupting ratings higher
than necessary, but should eliminate the possibility of apply-
Table 1.3-10. Conductor Conversion (Based on Using Copper Conductor)
6 ing units which will not be safe for the possible fault duty.
If Your Conductor is: Use Equivalent Arrangement

3 – No. 4/0 Cables 2 – 500 kcmil


7 4 – No. 2/0 Cables 2 – 500 kcmil
UTILITY KVA
V
3 – 2000 kcmil Cables 4 – 750 kcmil
5 – 400 kcmil Cables 4 – 750 kcmil
8 6 – 300 kcmil Cables 4 – 750 kcmil
800 Ampere Busway 2 – 500 kcmil 12.5
1000 Ampere Busway 2 – 500 kcmil
9 1600 Ampere Busway 4 – 750 kcmil
10.0

Short Circuit Current Readout 250 kcmil


W
WG
10 The readout obtained from the charts is the rms symmetrical
7.5 W
WG

amperes available at the given distance from the trans-


5.0
former. The circuit breaker should have an interrupting
11 capacity at least as large as this value.
2.5
How to Use the Short Circuit Charts
12
Step One 0
0 2 5 10 20 50 100 200 500 1000 2000 5000
Obtain the following data: Distance in Feet from T
13
1. System voltage Figure 1.3-12. 225 kVA Transformer/4.5% Impedance/208 Volts
2. Transformer kVA rating (from transformer nameplate)
14 3. Transformer impedance (from transformer nameplate)
4. Primary source fault energy available in kVA KV
15 (from electric utility or distribution system engineers)
Fault Current in Thousands of Amperes (Sym.)

30
kcmil
Step Two
25
Select the applicable chart from the following pages. The
16 charts are grouped by secondary system voltage which is #4 A F 50,000

listed with each transformer. Within each group, the chart 20 B


for the lowest kVA transformer is shown first, followed in
17 ascending order to the highest rated transformer.
F

15

Step Three
18 Select the family of curves that is closest to the “available 10
source kVA.” The black line family of curves is for a source of
500,000 kVA. The lower value line (in red) family of curves is
19 for a source of 50,000 kVA. You may interpolate between
5

curves if necessary, but for values above 100,000 kVA it is


appropriate to use the 500,000 kVA curves. 0
20 Step Four
0 2 5 10 20
Distance in Feet from T
50 100 200 500 1000 2000 5000

Select the specific curve for the conductor size being used. If Figure 1.3-13. 300 kVA Transformer/4.5% Impedance/208 Volts
21 your conductor size is something other than the sizes shown
on the chart, refer to the conductor conversion Table 1.3-10.

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-17
January 2008 System Analysis
Sheet 01 049

B i
KV A
Fault Current in Thousands of Amperes (Sym.)

30 120
F
ii
25 100
F 50,000
W
WG

20 80 B
1

15 60 F 2
4
2
10 40
3
5 20 #4 AWG
A

4
0 0
0 2 5 10 20 50 100 200 500 1000 2000 5000 0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T Distance in Feet from T
5
Figure 1.3-14. 500 kVA Transformer/4.5% Impedance/208 Volts Figure 1.3-17. 1500 kVA Transformer/5.5% Impedance/208 Volts
6
A A
7
Fault Current in Thousands of Amperes (Sym.)

60 120 –

– B
50 100 W
WG

W
WG
F 50,000 F 50,000 8
40 B 80

F
F 9
30 60

20 40
10
4– kcmil

10 20 11
0 0
0 2 5 10 20
Distance in Feet from T
50 100 200 500 1000 2000 5000 0 2 5 10 20
Distance in Feet from T
50 100 200 500 1000 2000 5000
12
Figure 1.3-15. 750 kVA Transformer/5.5% Impedance/208 Volts Figure 1.3-18. 2000 kVA Transformer/5.5% Impedance/208 Volts
13

kcmil A A
14
kcmil
Fault Current in Thousands of Amperes (Sym.)

Fault Current in Thousands of Amperes (Sym.)

60 12

50
B
10
15
F 50,000 B F 50,000
F
40 8 16
30 6 4
2 17
20 W
WG 4

18
10 2

0 0
19
0 2 5 10 20 50 100 200 500 1000 2000 5000 0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T Distance in Feet from T

Figure 1.3-16. 1000 kVA Transformer/5.5% Impedance/208 Volts Figure 1.3-19. 300 kVA Transformer/4.5% Impedance/480 Volts
20

21

CA08104001E For more information visit: www.eaton.com


1.3-18 Power Distribution Systems
System Analysis January 2008
Sheet 01 050

i
A A
Fault Current in Thousands of Amperes (Sym.)

Fault Current in Thousands of Amperes (Sym.)


30 60
ii
25 50 kcmil
F 50,000 F 50,000
1 20 40
#4 AWG
A
– B

2 15 B #1/0 AWG
#4 A
A
AWG
30
F

10 20
3 4 750 kcmil

5 10

4
0 0
0 2 5 10 20 50 100 200 500 1000 2000 5000 0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T Distance in Feet from T
5
Figure 1.3-20. 500 kVA Transformer/4.5% Impedance/480 Volts Figure 1.3-23. 1500 kVA Transformer/5.5% Impedance/480 Volts
6
A A
7
Fault Current in Thousands of Amperes (Sym.)

Fault Current in Thousands of Amperes (Sym.)

30 60 4– kcmil

750
25 50 B W
WG
8 500
F 50,000 F 50,000

20 B 40

9 F
F
15 30

10 10
4– kcmil
20

#4 A
11 5 10

0 0
12 0 2 5 10 20
Distance in Feet from T
50 100 200 500 1000 2000 5000 0 2 5 10 20
Distance in Feet from T
50 100 200 500 1000 2000 5000

Figure 1.3-21. 750 kVA Transformer/5.5% Impedance/480 Volts Figure 1.3-24. 2000 kVA Transformer/5.5% Impedance/480 Volts
13

14 A
Fault Current in Thousands of Amperes (Sym.)

30
W
WG
15 25
B

F 50,000

F
16 20

15
17 4 – 750 kcmil
2

10

18
5

19 0
0 2 5 10 20 50 100 200 500 1000 2000 5000
Distance in Feet from T

20 Figure 1.3-22. 1000 kVA Transformer/5.5% Impedance/480 Volts

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-19
January 2008 System Analysis
Sheet 01 051

Determining X and R Values How to Estimate Short Method 2:


i
Circuit Currents at Transformer Refer to Page 1.5-9 in the Reference
from Transformer Loss Data section, and use appropriate row of
Secondaries: data based on transformer kVA and
Method 1: ii
primary short circuit current available.
Given a 500 kVA, 5.5% Z transformer Method 1:
This will yield more accurate results
with 9000 W total loss; 1700 W no-load To obtain 3-phase rms symmetrical and allow for including motor short
loss; 7300 W load loss and primary short circuit current available at circuit contribution. 1
voltage of 480 V. transformer secondary terminals,
2
use the formula:
3 ×  −−−−−−500
−−−−−−−−−−− × R = 7300 Watts
2
 3 × 0.480 I SC 100
= I FLC × ------------
%Z
%R = .0067 ohms 3
where %Z is the transformer impedance
in percent, from Tables 1.5-6 through
0.0067 × 500
%R = −−−−−−−−−−−−−−−−−−2−− = 1.46% 1.5-11, Page 1.5-11. 4
10 × 0.48
This is the maximum 3-phase symmet-
2 2
%X = 5.5 – 1.46 = 5.30% rical bolted-fault current, assuming
sustained primary voltage during fault, 5
Method 2: i.e., an infinite or unlimited primary
Using same values above. power source (zero source impedance).
Since the power source must always 6
2
I R Losses have some impedance this a conserva-
%R = −−−−−−−−−−−−−−−−− tive value; actual fault current will be
10 × kVA 7
somewhat less.
7300
−−−−−−−−−−−−− = 1.46 Note: This will not include motor short
10 × 500 circuit contribution. 8
2 2
%X = 5.5 – 1.46 = 5.30%

See Tables 1.5-12 through 1.5-15


9
on Page 1.5-13 for loss data on
transformers. 10

11

12

13

14

15

16

17

18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.3-20 Power Distribution Systems
System Analysis January 2008
Sheet 01 052

Voltage Drop Considerations Computer Equipment: With the Motor Starting


i The first consideration for voltage
proliferation of data-processing and
Motor inrush on starting must be limited
computer- or microprocessor-controlled
drop is that under the steady-state manufacturing, the sensitivity of com- to minimize voltage dips. Table 1.3-11
ii conditions of normal load, the voltage
at the utilization equipment must be
puters to voltage has become an on the next page will help select the
proper type of motor starter for various
important consideration. Severe dips of
adequate. Fine-print notes in the NEC short duration can cause a computer motors, and to select generators of
1 recommend sizing feeders and branch to “crash” — shut down completely, adequate size to limit voltage dip.
circuits so that the maximum voltage and other voltage transients caused See Section 30 for additional data
drop-in either does not exceed 3%, by starting and stopping motors can on reduced voltage motor starting.
2 with the total voltage drop for feeders cause data-processing errors. While Utility Systems
and branch circuits not to exceed 5%, voltage drops must be held to a mini-
for efficiency of operation. (Fine print Where the power is supplied by a
mum, in many cases computers will
3 notes in the NEC are not mandatory.) utility network, the motor inrush can
require special power-conditioning
be assumed to be small compared
In addition to steady-state conditions, equipment to operate properly.
to the system capacity, and voltage
voltage drop under transient condi-
4 tions, with sudden high-current, short-
Industrial Plants: Where large motors at the source can be assumed to
be constant during motor starting.
exist, and unit substation transformers
time loads, must be considered. The are relatively limited in size, voltage Voltage dip resulting from motor
most common loads of this type are
5 motor inrush currents during starting.
dips of as much as 20% may be per- starting can be calculated on the basis
of the voltage drop in the conductors
missible in some cases, if they do not
These loads cause a voltage dip on occur too frequently. Lighting is often between the power source and
the system as a result of the voltage
6 drop in conductors, transformers and
supplied from separate transformers, the motor resulting from the inrush
and is minimally affected by voltage current. Where the utility system is
generators under the high current. dips in the power systems. However, it limited, the utility will often specify the
This voltage dip can have numerous
7 adverse effects on equipment in the
is usually best to limit dips to between maximum permissible inrush current
5 and 10% at most. One critical consid- or the maximum hp motor they will
system, and equipment and conduc- eration is that a large voltage dip can permit to be started across-the-line.
tors must be designed and sized to
8 minimize these problems. In many
cause a dropout (opening) of magnetic
Transformer Considerations
motor contactors and control relays.
cases, reduced-voltage starting of The actual dropout voltage varies con- If the power source is a transformer,
motors to reduce inrush current
9 will be necessary.
siderably among starters of different and the inrush kVA or current of the
motor being started is small compared
manufacturers. The only standard that
exists is that of NEMA, which states to the full-rated kVA or current of the
10 Recommended Limits of that a starter must not drop out at 85% transformer, the transformer voltage
Voltage Variation of its nominal coil voltage, allowing dip will be small and may be ignored.
only a 15% dip. While most starters As the motor inrush becomes a signifi-
General Illumination: Flicker in
11 incandescent lighting from voltage will tolerate considerably more volt- cant percentage of the transformer
age dip before dropping out, limiting full-load rating, an estimate of the
dip can be severe; lumen output drops transformer voltage drop must be
about three times as much as the dip to 15% is the only way to ensure
12 voltage dips. That is, a 10% drop in continuity of operation in all cases. added to the conductor voltage drop
to obtain the total voltage drop to the
voltage will result in a 30% drop in X-Ray Equipment: Medical x-ray and motor. Accurate voltage drop calcula-
light output. While the lumen output
13 drop in fluorescent lamps is roughly
similar diagnostic equipment, such as tion would be complex and depend
CAT-scanners, are extremely sensitive upon transformer and conductor
proportional to voltage drop, if the to low voltage. They present a small, resistance, reactance, and impedance,
voltage dips about 25%, the lamp will
14 go out momentarily and then restrike.
steady load to the system until the as well as motor inrush current and
instant the x-ray tube is “fired.” This power factor. However, an approxima-
For high-intensity discharge (HID) presents a brief but extremely high tion can be made on the basis of the
lamps such as mercury vapor, high-
15 pressure sodium or metal halide, if the
instantaneous momentary load. In low power-factor motor inrush current
some modern x-ray equipment, the (30 – 40%) and impedance of the trans-
lamp goes out because of an excessive firing is repeated rapidly to create former.
voltage dip, it will not restrike until it
16 has cooled. This will require several
multiple images. The voltage regula-
tion must be maintained within the
minutes. These lighting flicker effects For example, if a 480 V transformer
manufacturer’s limits, usually 2 to 3%,
can be annoying, and in the case of has an impedance of 5%, and the
17 HID lamps, sometimes serious. In
under these momentary loads, to
motor inrush current is 25% of the
ensure proper x-ray exposure.
areas where close work is being done, transformer full-load current (FLC),
such as drafting rooms, precision then the worst case voltage drop will
18 assembly plants, and the like, even be 0.25 x 5%, or 1.25%.
a slight variation, if repeated, can be
19 very annoying, and reduce efficiency. The allowable motor inrush current is
Voltage variation in such areas should determined by the total permissible
be held to 2 or 3% under motor-starting voltage drop in transformer and con-
20 or other transient conditions. ductors.

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-21
January 2008 System Analysis
Sheet 01 053

Table 1.3-11. Factors Governing Voltage Drop


Type of Starting Starting How Starting Starting Torque per Unit of Full-Load Amperes i
Motor  Torque Current  Started Current Full Load Torque per kVA Generator
% Full-Load  Motor Rpm Capacity for Each

1750 1150  850


1% Voltage Drop ii
Design A Normal Normal Across-the-Line 600 – 700 1.5 1.35 1.25 .0109 – .00936
Resistance 480 – 560 ➁ .96 .87 .80 .0136 – .0117 1
Autotransformer 375 – 450 ➁ .96 .87 .80 .0170 – .0146
Design B Normal Low Across-the-Line 500 – 600 1.5 1.35 1.25 .0131 – .0109
Resistance
Autotransformer
400 – 480 ➁
320 – 400 ➁
.96
.96
.87
.87
.80
.80
.0164 – .01365
.0205 – .0170
2
Design C High Low Across-the-Line 500 – 600 — .2 to 2.5 — .0131 – .0109
Resistance
Autotransformer
400 – 480 ➁
320 – 400 ➁


1.28 to 1.6
1.28 to 1.6


.0164 – .01365
.0205 – .0170
3
Wound Rotor High Low Secondary Controller 100% current — — — —
for 100%
Torque







.0655
4
Synchronous (for compressors) Low — Across-the-Line 300 40% Starting, 40% Pull-In .0218
Synchronous (for centrifugal pumps) Low — Across-the-Line 450 – 550 60% Starting, 110% Pull-In .0145 – .0118
Autotransformer 288 – 350  38% Starting, 110% Pull-In .0228 – .0197 5
 Consult NEMA MG-1 sections 1 and 12 for the exact definition of the design letter.
 In each case, a solid-state reduced voltage starter can be adjusted and controlled to provide the required inrush current and torque characteristics.
 Where accuracy is important, request the code letter of the the motor and starting and breakdown torques from the motor vendor.
6
 Using 80% taps.

Engine Generator Systems From the nameplate data on the motor Example: 7
With an engine generator as the the full-load amperes of a 7-1/2 hp. Assuming a project having a
source of power, the type of starter 220-volt, 1750 rpm, 3-phase, squirrel- 1000 kVA generator, where the
that will limit the inrush depends on cage motor is 19.0 amperes. Therefore: voltage variation must not exceed
8
the characteristics of the generator. Starting current (%F.L.) = 10%. Can a 75 hp, 1750 rpm, 220-volt,
Although automatic voltage regulators 3-phase, squirrel-cage motor be 9
are usually used with all ac engine- 10 × 100 × 1000 started without objectionable lamp
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− = 3.45 or 345%.
generators, the initial dip in voltage is 19.0 × 220 × 3 × 0.40 flicker (or 10% voltage drop)?
caused by the inherent regulation of 10
the generator and occurs too rapidly From tables in the circuit protective
From Table 1.3-11, a NEMA design C or
for the voltage regulator to respond. devices reference section the full-load
NEMA design D motor with an autotrans-
It will occur whether or not a regulator amperes of this size and type of motor
is installed. Consequently, the percent
former starter gives approximately this
is 158.0 amperes. To convert to same 11
starting ratio. It could also be obtained
of initial voltage drop depends on the basis as column 7, 158 amperes must
from a properly set solid-state adjust-
ratio of the starting kVA taken by the be divided by the generator capacity
motor to the generator capacity, the
able reduced voltage starter.
and % voltage drop, or: 12
inherent regulation of the generator, The choice will depend upon the
158
the power-factor of the load thrown torque requirements of the load since −−−−−−−−−−−−−−− = 0.0158 amperes per kVA 13
on the generator, and the percentage the use of an autotransformer starter 1000 × 10 per 1% voltage drop
load carried by the generator. reduces the starting torque in direct
proportion to the reduction in starting Checking against the table, 0.0158 falls
A standard 80% power-factor engine- current. In other words, a NEMA within the .0170 – .0146 range. This 14
type generator (which would be design C motor with an autotrans- indicates that a general-purpose motor
used where power is to be supplied former would have a starting torque with autotransformer starting can
to motor loads) has an inherent of approximately full-load (see Table be used. 15
regulation of approximately 40% 1.3-11) whereas the NEMA design D Note: Designers may obtain calculated
from no-load to full-load. This means motor under the same conditions
that a 50% variation in load would would have a starting torque of
information from engine generator
manufacturers.
16
cause approximately 20% variation approximately 1-1/2 times full-load.
in voltage (50% x 40% = 20%). The calculation results in conservative
Note: If a resistance starter were used for results. The engineer should provide
17
Assume that a 100 kVA, 80% PF the same motor terminal voltage, the start-
to the engine-generator vendor the
engine-type generator is supplying ing torque would be the same as that
starting kVA of all motors connected to
the power and that the voltage drop obtained with autotransformer type, but the
the generator and their starting sequence.
18
should not exceed 10%. Can a 7-1/2 hp, starting current would be higher, as shown.
The engineer should also specify the
220-volt, 1750 rpm, 3-phase, squirrel- maximum allowable drop. The engineer
cage motor be started without Short-Cut Method 19
should request that the engine-generator
exceeding this voltage drop? Column 7 in Table 1.3-11 has been vendor consider the proper generator
worked out to simplify checking. size when closed-transition autotrans-
Starting ratio =
The figures were obtained by using former reduced voltage starters, and
20
Percent voltage drop × gen. kVA × 1000 the formula above and assuming soft-start solid-state starter are used;
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− 1 kVA generator capacity and 1%
F.L. amperes × volts × 3 × reg. of gen. so the most economical method of 21
voltage drop. installation is obtained.

CA08104001E For more information visit: www.eaton.com


1.3-22 Power Distribution Systems
System Analysis January 2008
Sheet 01 054

Voltage Drop Formulas If the receiving end voltage, load current and power factor
i (PF) are known.
Approximate Method
2 2
Voltage Drop E VD = ( E R cosθ + I R ) + ( E R sinθ + I X ) – E R
ii
E VD = IR cosθ + IX sinθ
ER is the receiving end voltage.
1 where Abbreviations are same as below “Exact Method.” Exact Method 2 — If receiving or sending mVA and its
power factor are known at a known sending or receiving
Exact Methods voltage.
2 Voltage Drop
2
Exact Method 1 — If sending end voltage and load PF 2 2 ( ZMVA R )
- + 2ZMVA R cos ( γ – θ R )
E S = E R + ---------------------------------
3 are known. 2
ER
2 2
E VD = E S + IR cosθ + IX sinθ – E S – ( IX cosθ – IR sinθ ) or
4 2
where: 2 2 ( ZMVA R )
- – 2ZMVA S cos ( γ – θ S )
E R = E S + ---------------------------------
2
5 EVD = Voltage drop, line-to-neutral, volts ES
ES = Source voltage, line-to-neutral, volts where:
6 I = Line (Load) current, amperes ER = Receiving Line-Line voltage
in kV
R = Circuit (branch, feeder) resistance, ohms
7 X = Circuit (branch, feeder) reactance, ohms
ES = Sending Line-Line voltage
in kV
cosθ = Power factor of load, decimal
8 MVAR = Receiving 3-phase mVA
sinθ = Reactive factor of load, decimal
MVAS = Sending 3-phase mVA
9 Z = Impedance between and
receiving ends

10 γ = The angle of impedance Z


θR = Receiving end PF
11 θS = Sending end PF, positive
when lagging

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.3-23
January 2008 System Analysis
Sheet 01 055

Voltage Drop Table 1.3-12. Temperature Correction Factors


for Voltage Drop
To select minimum conductor size:
i
1. Determine maximum desired
Voltage Drop Tables Conductor Percent Correction voltage drop, in volts.
Size Power Factors %
Note: Busway voltage drop tables are
100 90 80 70 60
2. Divide voltage drop by (amperes x ii
shown in Section 23 of this catalog. circuit feet).
No. 14 to No. 4 5.0 4.7 4.7 4.6 4.6
Tables for calculating voltage drop for No. 2 to 3/0 5.0 4.2 3.7 3.5 3.2
3. Multiply by 100. 1
copper and aluminum conductors, in 4/0 to 500 kcmil 5.0 3.1 2.6 2.3 1.9 4. Find nearest lower voltage drop
either magnetic (steel) or nonmagnetic 600 to 1000 kcmil 5.0 2.6 2.1 1.5 1.3
value in tables, in correct column
(aluminum or non-metallic) conduit,
for type of conductor, conduit and 2
appear on Page 1.3-24. These tables Calculations power factor. Read conductor size
give voltage drop per ampere per
for that value.
100 feet (30 m) of circuit length. The To calculate voltage drop: 3
circuit length is from the beginning 1. Multiply current in amperes by 5. Where this results in an oversized
point to the end point of the circuit the length of the circuit in feet to cable, verify cable lug sizes for
regardless of the number of conductors. get ampere-feet. Circuit length is molded case breakers and fusible 4
the distance from the point of switches. Where lug size available
Tables are based on the following
origin to the load end of the circuit. is exceeded, go to next higher
conditions: rating. 5
1. Three or four single conductors in 2. Divide by 100.
a conduit, random lay. For three- Example:
3. Multiply by proper voltage drop
conductor cable, actual voltage
value in tables. Result is voltage A 3-phase, 4-wire lighting feeder on 6
drop will be approximately the a 208-volt circuit is 250 feet (76.2 m)
drop.
same for small conductor sizes long. The load is 175 amperes at 90%
and high power factors. Actual Example: PF. It is desired to use aluminum con- 7
voltage drop will be from 10 to A 460-volt, 100-hp motor, running at ductors in aluminum conduit. What
15% lower for larger conductor 80% PF, draws 124 amperes full-load size conductor is required to limit the
sizes and lower power factors. current. It is fed by three 2/0 copper voltage drop to 2% phase-to-phase? 8
2. Voltage drops are phase-to-phase, conductors in steel conduit. The feeder 1. VD = −−− 2−− × 208 = 4.16 volts
for 3-phase, 3-wire or 3-phase, length is 150 feet (46 m). What is the 100
4-wire 60 Hz circuits. For other voltage drop in the feeder? What is 9
circuits, multiply voltage drop the percentage voltage drop? 2. −−−−−4.16
−−−−−−−−−− = 0.0000951
175 × 250
given in the tables by the follow-
ing correction factors:
1. 124 amperes x 150 feet (46 m) = 10
18,600 ampere-feet 3. 0.0000951 × 100 = 0.00951
3-phase, 4-wire, 2. Divided by 100 = 186 4. In table, under Aluminum Conduc-
phase-to-neutral x 0.577 tors, nonmagnetic conduit, 90%
11
1-phase, 2-wire x 1.155 3. Table: 2/0 copper, magnetic conduit, PF, the nearest lower value is
1-phase, 3-wire, 80% PF = 0.0187 0.0091. Conductor required is
phase-to-phase x 1.155 186 x 0.0187 = 3.48 volts drop 500 kcmil. (Size 4/0 THW would
12
1-phase, 3-wire, 3.48 x 100 = 0.76% drop have adequate ampacity, but the
phase-to-neutral x 0.577 460 voltage drop would be excessive). 13
3. Voltage drops are for a conductor 4. Conclusion: .76% voltage drop is
temperature of 75°C. They may be very acceptable (See NEC 2005
used for conductor temperatures Article 215, which suggests that a 14
between 60°C and 90°C with voltage drop of 3% or less on a
reasonable accuracy (within ±5%). feeder is acceptable.)
However, correction factors in 15
the table below can be applied if
desired. The values in the table are
in percent of total voltage drop. 16
For conductor temperature of 60°C –
SUBTRACT the percentage from 17
Table 1.3-12.
For conductor temperature of 90°C –
ADD the percentage from Table 1.3-12. 18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.3-24 Power Distribution Systems
System Analysis January 2008
Sheet 01 056

Table 1.3-13. Voltage Drop — Volts per Ampere per 100 Feet (30 m); 3-Phase, Phase-to-Phase
i Conductor Size Magnetic Conduit (Steel) Nonmagnetic Conduit (Aluminum or Nonmetallic)
AWG Load Power Factor, % Load Power Factor, %
or kcmil
ii 60 70 80 90 100 60 70 80 90 100
Copper Conductors
14 .3390 .3910 .4430 .4940 .5410 .3370 .3900 .4410 .4930 .5410
1 12 .2170 .2490 .2810 .3130 .3410 .2150 .2480 .2800 .3120 .3410
10 .1390 .1590 .1790 .1980 .2150 .1370 .1580 .1780 .1970 .2150
8 .0905 .1030 .1150 .1260 .1350 .0888 .1010 .1140 .1250 .1350
2 6
4
.0595
.0399
.0670
.0443
.0742
.0485
.0809
.0522
.0850
.0534
.0579
.0384
.0656
.0430
.0730
.0473
.0800
.0513
.0849
.0533
2 .0275 .0300 .0323 .0342 .0336 .0260 .0287 .0312 .0333 .0335
1 .0233 .0251 .0267 .0279 .0267 .0218 .0238 .0256 .0270 .0266
3 1/0 .0198 .0211 .0222 .0229 .0213 .0183 .0198 .0211 .0220 .0211
2/0 .0171 .0180 .0187 .0190 .0170 .0156 .0167 .0176 .0181 .0169
3/0 .0148 .0154 .0158 .0158 .0136 .0134 .0141 .0147 .0149 .0134
4 4/0 .0130 .0134 .0136 .0133 .0109 .0116 .0121 .0124 .0124 .0107
250 .0122 .0124 .0124 .0120 .0094 .0107 .0111 .0112 .0110 .0091
300 .0111 .0112 .0111 .0106 .0080 .0097 .0099 .0099 .0096 .0077
5 350 .0104 .0104 .0102 .0096 .0069 .0090 .0091 .0091 .0087 .0066
500 .0100 .0091 .0087 .0080 .0053 .0078 .0077 .0075 .0070 .0049
600 .0088 .0086 .0082 .0074 .0046 .0074 .0072 .0070 .0064 .0042
6 750
1000
.0084
.0080
.0081
.0077
.0077
.0072
.0069
.0063
.0040
.0035
.0069
.0064
.0067
.0062
.0064
.0058
.0058
.0052
.0035
.0029
Aluminum Conductors
7 12 .3296 .3811 .4349 .4848 .5330 .3312 .3802 .4328 .4848 .5331
10 .2133 .2429 .2741 .3180 .3363 .2090 .2410 .2740 .3052 .3363
8 .1305 .1552 .1758 .1951 .2106 .1286 .1534 .1745 .1933 .2115
8 6 .0898 .1018 .1142 .1254 .1349 .0887 .1011 .1127 .1249 .1361
4 .0595 .0660 .0747 .0809 .0862 .0583 .0654 .0719 .0800 .0849
2 .0403 .0443 .0483 .0523 .0535 .0389 .0435 .0473 .0514 .0544
1 .0332 .0357 .0396 .0423 .0428 .0318 .0349 .0391 .0411 .0428
9 1/0 .0286 .0305 .0334 .0350 .0341 .0263 .0287 .0322 .0337 .0339
2/0 .0234 .0246 .0275 .0284 .0274 .0227 .0244 .0264 .0274 .0273
3/0 .0209 .0220 .0231 .0241 .0217 .0160 .0171 .0218 .0233 .0222
10 4/0 .0172 .0174 .0179 .0177 .0170 .0152 .0159 .0171 .0179 .0172
250 .0158 .0163 .0162 .0159 .0145 .0138 .0144 .0147 .0155 .0138
300 .0137 .0139 .0143 .0144 .0122 .0126 .0128 .0133 .0132 .0125
11 350 .0130 .0133 .0128 .0131 .0100 .0122 .0123 .0119 .0120 .0101
500 .0112 .0111 .0114 .0099 .0076 .0093 .0094 .0094 .0091 .0072
600 .0101 .0106 .0097 .0090 .0063 .0084 .0085 .0085 .0081 .0060
12 750 .0095 .0094 .0090 .0084 .0056 .0081 .0080 .0078 .0072 .0051
1000 .0085 .0082 .0078 .0071 .0043 .0069 .0068 .0065 .0058 .0038

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-1
January 2008 System Application Considerations
Sheet 01 057
Capacitors

Capacitors and Power Factor ANSI Standard C37.06 (indoor oilless Low Voltage Capacitor Switching
i
circuit breakers) indicates the preferred
ratings of Eaton’s Cutler-Hammer Type Circuit breakers and switches for use
Capacitor General Application VCP-W vacuum breaker. For capacitor with a capacitor must have a current
Considerations switching careful attention should be rating in excess of rated capacitor ii
paid to the notes accompanying the current to provide for overcurrent from
Additional application information overvoltages at fundamental frequency
is available in Section 37 regarding table. The definition of the terms are
capacitors and harmonic filters in ANSI Standard C37.04 Article 5.13 and harmonic currents. The following 1
(for the latest edition). The application percent of the capacitor-rated current
as follows: should be used as a general guideline:
guide ANSI/IEEE Standard C37.012
■ Capacitor selection. covers the method of calculation Fused and unfused switches. . . . 165% 2
■ Where to install capacitors in a plant of the quantities covered by C37.06
distribution system. Standard. Molded case breaker or
■ Locating capacitors on reduced
equivalent . . . . . . . . . . . . . . . . . 150% 3
Note that the definitions in C37.04
voltage and multi-speed starters. make the switching of two capacitors DSII power circuit breakers. . . . . 135%
■ Harmonic considerations. banks in close proximity to the switch-
Magnum DS power 4
■ Eliminating harmonic problems. gear bus a back-to-back mode of
circuit breaker . . . . . . . . . . . . . . 135%
■ National Electrical Code switching. This classification requires
requirements. a definite purpose circuit breaker Contactors: 5
(breakers specifically designed for Open type . . . . . . . . . . . . . . . . . . . 135%
Medium Voltage capacitance switching).
Capacitor Switching We recommend that such application
Enclosed type . . . . . . . . . . . . . . . . 150% 6
be referred to Eaton. The NEC, Section 460-8(c), requires the
Capacitance switching constitutes
severe operating duty for a circuit disconnecting means to be rated not 7
A breaker specified for capacitor less than 135% of the rated capacitor
breaker. At the time the breaker opens switching should include as applicable:
at near current zero the capacitor is current (for 600 V and below).
fully charged. After interruption, when 1. Rated maximum voltage. See Section 37 for switching device 8
the alternating voltage on the source 2. Rated frequency. ampere ratings. They are based on
side of the breaker reaches its opposite percentage of capacitor-rated current
maximum, the voltage that appears 3. Rated open wire line charging as indicated (above). The interrupting 9
across the contacts of the open breaker switching current. rating of the switch must be selected
is at least twice the normal peak line- to match the system fault current
to-neutral voltage of the circuit. If a 4. Rated isolated cable charging and
available at the point of capacitor appli- 10
breakdown occurs across the open shunt capacitor switching current.
cation. Whenever a capacitor bank is
contact the arc is reestablished. Due to 5. Rated back-to-back cable charging purchased with less than the ultimate
the circuit constants on the supply side and back-to-back capacitor switch- kvar capacity of the rack or enclosure, 11
of the breaker, the voltage across the ing current. the switch rating should be selected
open contact can reach three times the based on the ultimate kvar capacity —
normal line-to-neutral voltage. After 6. Rated transient overvoltage factor. not the initial installed capacity. 12
it is interrupted and with subsequent
alternation of the supply side voltage, 7. Rated transient inrush current and Refer to Section 37 for recommended
the voltage across the open contact is its frequency. selection of capacitor switching 13
even higher. 8. Rated interrupting time. devices; recommended maximum
capacitor ratings for various motor
9. Rated capacitive current types and voltages; and for required 14
switching life. multipliers to determine capacitor
kvars required for Power Factor
10. Grounding of system and Correction. 15
capacitor bank.
Loadbreak interrupter switches are
permitted by ANSI/IEEE Standard 16
C37.30 to switch capacitance but
they must have tested ratings for the
purpose. Refer to Cutler-Hammer 17
Type MVS ratings.
18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.4-2 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 058
Capacitors

i Motor Power Factor % AR — percent reduction in line To derate a capacitor used on a system
current due to the capacitor. A voltage lower than the capacitor volt-
Correction capacitor located on the motor side age rating, such as a 240-volt capacitor
of the overload relay reduces line used on a 208-volt system, use the
ii See Section 37 containing suggested
maximum capacitor ratings for
current through the relay. Therefore, following formula:
a different overload relay and/or
induction motors switched with the setting may be necessary. The reduc- Actual kvar =
1 capacitor. The data is general in nature tion in line current may be determined
( Applied Voltage )
2
and representative of general purpose by measuring line current with and Nameplate kvar × ---------------------------------------------------------------------
-
induction motors of standard design. without the capacitor or by calculation ( Nameplate Voltage )
2

2 The preferable means to select capaci- as follows:


tor ratings is based on the “maximum For the kVAC required to correct the
recommended kvar” information (Original PF) power factor from a given value of
% AR = 100 – 100 × −−−−−−−−−−−−−−−−−−−−−−−
3 available from the motor manufacturer. (Improved PF) COS φ1 to COS φ2, the
If this is not possible or feasible, formula is:
the tables can be used. If a capacitor is used with a lower kvar
kVAC = KW (tan phase1 – tan phase2)
4 An important point to remember
rating than listed in tables, the % AR
can be calculated as follows: Capacitors cause a voltage rise.
is that if the capacitor used with the
motor is too large, self-excitation may Actual kvar At light load periods the capacitive
5 cause a motor-damaging overvoltage % AR = Listed % AR × −−−−−−−−−−−−−−−−−−−−−− voltage rise can raise the voltage at
kvar in Table
when the motor and capacitor combi- the location of the capacitors to an
nation is disconnected from the line. The tables can also be used for other unacceptable level. This voltage rise
6 In addition, high transient torques motor ratings as follows: can be calculated approximately by
capable of damaging the motor shaft the formula
A. For standard 60 Hz motors
or coupling can occur if the motor
7 is reconnected to the line while
operating at 50 Hz: MVA r
% VR = −−−−−−−−−−−

kvar = 1.7 – 1.4 of kvar listed MVA SC
rotating and still generating a voltage
% AR = 1.8 – 1.35 of % AR listed
of self-excitation.
8 B. For standard 50 Hz motors MVAR is the capacitor rating and
Definitions MVASC is the system short circuit
operating at 50 Hz:
kvar — rating of the capacitor in capacity.
9 reactive kilovolt-amperes. This value
kvar = 1.4 – 1.1 of kvar listed
% AR = 1.4 – 1.05 of % AR listed With the introduction of variable speed
is approximately equal to the motor
no-load magnetizing kilovars. C. For standard 60 Hz wound-rotor drives and other harmonic current
10 motors: generating loads, the capacitor imped-
kvar = 1.1 of kvar listed ance value determined must not be
% AR= 1.05 of % AR listed resonant with the inductive reactances
11 of the system.
Note: For A, B, C, the larger multipliers apply
for motors of higher speeds; i.e., 3600 rpm =
12 1.7 mult., 1800 rpm = 1.65 mult., etc.

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-3
January 2008 System Application Considerations
Sheet 01 059
Protection and Coordination

Overcurrent Protection damage or withstand characteristics, tion transformer can be coordinated


i
(e) calculation of maximum short with the low voltage breakers. Trans-
and Coordination circuit currents (and ground fault former damage points, based on ANSI
currents if ground fault protection is standards, and low voltage cable
Overcurrents in a power distribution included) available at each protective heating limits can be plotted on this ii
system can occur as a result of both device location, (f) understanding of set of curves to assure that apparatus
normal (motor starting, transformer operating characteristics and available limitations are not exceeded.
inrush, etc.) and abnormal (overloads, adjustments of each protective device, 1
ground fault, line-to-line fault, etc.) (g) any special overcurrent protection Ground-fault curves may also be
conditions. In either case, the funda- requirements including utility limita- included in the coordination study
mental purposes of current-sensing tions. Refer to (Figure 1.4-1). if ground-fault protection is provided, 2
protective devices are to detect the but care must be used in interpreting
abnormal overcurrent and with proper To ensure complete coordination, the their meaning.
coordination, to operate selectively time-trip characteristics of all devices
Standard definitions have been 3
to protect equipment, property and in series should be plotted on a single
personnel while minimizing the out- sheet of standard log-log paper. established for overcurrent protective
devices covering ratings, operation
age of the remainder of the system. Devices of different-voltage systems
and application systems.
4
With the increase in electric power can be plotted on the same sheet by
consumption over the past few converting their current scales, using M — Motor (100 hp). Dashed line
decades, dependence on the contin- the voltage ratios, to the same voltage- shows initial inrush current, starting 5
ued supply of this power has also basis. Such a coordination plot is current during 9-sec. acceleration, and
increased so that the direct costs shown in Figure 1.4-1. In this manner, drop to 124 A normal running current,
of power outages have risen signifi- primary fuses and circuit breaker all well below CB A trip curve. 6
cantly. Power outages can create dan- relays on the primary side of a substa-
gerous and unsafe conditions as a
result of failure of lighting, elevators, 7
ventilation, fire pumps, security sys- SCALE X 100 = CURRENT IN AMPERES AT 480 VOLTS

10,000
tems, communications systems, and

1000

2000

3000

4000
5000
6000
7000
8000
9000
100

200

300

400

500
600
700
800
900
70
80
90
.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
1000 1000
the like. In addition, economic loss 900
800
700
4.16 kV 250 MVA
900
800
700
8
from outages can be extremely high 600
500
600
500
as a result of computer downtime, 400 400

or, especially in industrial process 300 B 300 9


plants, interruption of production. 200
A D
200
C
Protective equipment must be adjusted D 10
and maintained in order to function 100
90
80
250 Amperes 100
90
1000 80
properly when an overcurrent occurs, 70
60
kVA 4,160 V ∆
70
60
5.75%
but coordination begins during power 50 480/277 V 50
11
40 19,600 Amperes 40
system design with the knowledgeable ANSI 3-Phase
30 Thru Fault 30
analysis and selection and application Protection Curve
20 (More Than 10 in C 1,600 Amperes 20
of each overcurrent protective device Lifetime) 12
in the series circuit from the power 24,400 Amperes
B
source(s) to each load apparatus. The 10
9
8 600 Amperes
10
9
8
objective of coordination is to localize 7
M 7
13

TIME IN SECONDS
TIME IN SECONDS

6 6
the overcurrent disturbance so that the 5
20,000 Amperes
5
4 4
protective device closest to the fault
3 3
on the power-source side has the first A 175 Amperes
14
chance to operate; but each preceding 2 B C 2

protective device upstream toward the


power source should be capable, within 1
.9
.8 100 hp –
1
.9
.8 15
its designed settings of current and .7
.6
M 124 Amperes FLC .7
.6
time, to provide backup and de-energize .5 .5
X = Available fault current
16
.4 .4
the circuit if the fault persists. Sensitivity including motor
.3 contribution. .3
of coordination is the degree to which Ground
the protective devices can minimize .2 Fault Trip .2

C
the damage to the faulted equipment.
.1 .1
17
.09 .09
To study and accomplish coordination .08
.07
.08
.07
Transformer
requires (a) a one-line diagram, the .06 .06

roadmap of the power distribution


.05
.04
B Inrush .05
.04
18
system, showing all protective devices
Max. 3-Phase
4.16 kV Fault

.03 .03

A
480V Fault

and the major or important distribution


and utilization apparatus, (b) identifi-
.02 .02
19
Max.

cation of desired degrees of power .01 .01


70
80
90
100

200

300

400

500
600
700
800
900
1000

2000

3000

4000
5000
6000
7000
8000
9000
10,000

.5 .6 .7 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60
continuity or criticality of loads
throughout system, (c) definition SCALE X 100 = CURRENT IN AMPERES AT 480 VOLTS 20
of operating-current characteristics
(normal, peak, starting) of each Figure 1.4-1. Time-Current Characteristic Curves for Typical Power Distribution System
utilization circuit, (d) equipment Protective Devices Coordination Analysis 21

CA08104001E For more information visit: www.eaton.com


1.4-4 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 060
Protection and Coordination

A — CB (175 A) coordinates selectively Maximum 480 V 3-phase fault indicated In a fully rated system, all circuit break-
i with motor M on starting and running on the horizontal current axis. ers must have an interrupting capacity
and with all upstream devices, except adequate for the maximum available
that CB B will trip first on low level Maximum 4160 V 3-phase fault indicated, fault current at their point of applica-
ii ground faults. converted to 480 V basis. tion. All breakers are equipped with
4160 long-time-delay (and possibly short
B — CB (600 A) coordinates selectively I 480 V = I 4160 V × −−−−−−− delay) and instantaneous overcurrent
1 with all upstream and downstream 480
trip devices. A main breaker may have
devices, except will trip before A on short time-delay tripping to allow
The ANSI protection curves are speci-
limited ground faults, since A has no a feeder breaker to isolate the fault
fied in ANSI C57.109 for liquid-filled
2 ground fault trips.
transformers and C57.12.59 for dry-type while power is maintained to all the
C — Main CB (1600 A) coordinates transformers. remaining feeders.
selectively with all downstream
3 devices and with primary fuse D,
Illustrative examples such as shown A selective or fully coordinated system
here start the coordination study from permits maximum service continuity.
for all faults on load side of CB. The tripping characteristics of each
the lowest rated device proceeding
4 D — Primary fuse (250 A, 4,160 V) upstream. In practice the setting or overcurrent device in the system must
coordinates selectively with all rating of the utility’s protective device be selected and set so that the breaker
secondary protective devices. Curve sets the upper limit. Even in cases nearest the fault opens to isolate the
5 converted to 480 V basis. Clears trans- where the customer owns the medium faulted circuit, while all other breakers
former inrush point (12 x FLC for 0.1 sec.), voltage or higher distribution system, remain closed, continuing power to
indicating that fuse will not blow on the setting or rating of the lowest set the entire unfaulted part of the system.
6 inrush. Fuse is underneath right-half of protective device at the source deter-
The 2005 National Electrical Code 
ANSI 3-phase withstand curve, indicat- mines the settings of the downstream
(NEC) has added specific requirements
ing fuse will protect transformer for devices and the coordination.
for designing certain circuits with
7 high-magnitude faults up to ANSI rating.
Therefore the coordination study selective coordination. Article 100
Delta-Wye secondary side short circuit should start at the present setting or has added, under Coordination
(Selective), the following definition:
8 is not reflected to the primary by the rating of the upstream device and
work towards the lowest rated device. “Localization of an overcurrent condi-
relation
If this procedure results in unaccept- tion to restrict outages to the circuit or
9 V able settings, the setting or rating of equipment affected, accomplished by
I P = −−−S × I S the upstream device should be the choice of overcurrent protective
VP
reviewed. Where the utility is the sole devices and their ratings or settings.”
10 for L-L and L-G faults. For line-to-line fault source they should be consulted.  NEC 2005 NFPA 70: National Electrical Code
the secondary (low voltage) side fault Where the owner has its own medium International Electrical Code Series.
current is 0.866 x I 3-phase fault current. or higher voltage distribution the set-
11 tings or ratings of all upstream devices Article 620.62 (Elevators, Dumbwait-
However the primary (high voltage) side should be checked. ers, Escalators, Moving Walks,
fault is the same as if the secondary Wheelchair Lifts, and Stairway Chair
If perfect coordination is not feasible, Lifts) requires “Where more than one
12 fault was a 3-phase fault. Therefore in
then lack of coordination should be driving machine disconnecting means
coordination studies, the knee of the
short-time pickup setting on the sec- limited to the smallest part of the system. is supplied by a single feeder, the over-
13 ondary breaker should be multiplied by Application data is available for all pro- current protective devices in each dis-
tective equipment to permit systems to connecting means shall be selectively
−−−−1−−−− or 1.1547 be designed for adequate overcurrent coordinated with any other supply
0.866
14 protection and coordination. For circuit side overcurrent protective device.”
A similar requirement under Article
before it is compared to the minimum breakers of all types, time-current curves
permit selection of instantaneous and 700.27 is as follows; “Emergency
melting time of the upstream primary
15 fuse curve. In the example shown, the inverse-time trips. For more complex cir- system(s) overcurrent devices shall
be selectively coordinated with all
knee is at 4000 amperes 30 sec., and cuit breakers, with solid state trip units,
trip curves include long- and short-time supply side overcurrent protective
the 30-sec. trip time should be com-
16 pared to the MMT (minimum melt delays, as well as ground-fault tripping, devices.” Also Article 701.18, added
with a wide range of settings and fea- “Legally required standby system(s)
time) of the fuse curve at 4000 x 1.1547
tures to provide selectivity and coordina- overcurrent devices shall be selec-
= 4619 amperes. In this case there is
17 adequate clearance to the fuse curve. tion. For current-limiting circuit breakers, tively coordinated with all supply
fuses, and circuit breakers with integral side overcurrent devices.”
In the example shown, the ANSI 3-phase fuses, not only are time-current charac- In addition, for health care facilities,
18 through fault protection curve must teristic curves available, but also data Article 517.26, Application of Other
be multiplied by 0.577 and replotted on current-limiting per-formance and Articles requires that “The essential
in order to determine the protection protection for downstream devices. electrical system shall meet the
19 given by the primary for a single line
requirements of Article 700, except
to ground fault in the secondary.
as amended by Article 517.”
20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-5
January 2008 System Application Considerations
Sheet 01 061
Protection and Coordination

All breakers must have an interrupting Protection of Conductors E. Tap Conductors. Tap conductors
capacity not less than the maximum
(Excerpts from NEC 240.4) shall be permitted to be protected i
available short circuit current at their against overcurrent in accordance
point of application. A selective Conductors, other than flexible cords with the following:
system is a fully rated system with and fixture wires, shall be protected ii
tripping devices chosen and adjusted against overcurrent in accordance with 1. 210-19(A)(3) and (A)(4) Household
to provide the desired selectivity. their ampacities as specified in Section Ranges and Cooking Appliances
The tripping characteristics of each 310-15, unless otherwise permitted or and Other Loads. 1
overcurrent device should not overlap, required in (A) through (G). 2. 240.5(B)(2) Fixture Wire.
but should maintain a minimum time
interval for devices in series (to allow A. Power Loss Hazard. Conductor 3. 240.21 Location in Circuit. 2
for normal operating tolerances) at all overload protection shall not be
required where the interruption of 4. 368.17(B) Reduction in Ampacity
current values. Generally, a maximum
of four low voltage circuit breakers can the circuit would create a hazard, Size of Busway. 3
be operated selectively in series, with such as in a material handling
magnet circuit or fire pump circuit. 5. 368.17(C) Feeder or Branch Circuits
the feeder or branch breaker down- (busway taps).
stream furthest from the source. Short circuit protection shall be 4
provided. 6. 430.53(D) Single Motor Taps.
Specify true rms sensing devices in
Note: FPN See NFPA 20-2003, standard for
order to avoid false trips due to rapid the Installation of Stationary Pumps for Fire Circuit Breaker Cable 5
currents or spikes. Specify tripping
elements with I2t or I4t feature for
Protection. Temperature Ratings
improved coordination with other B. Devices Rated 800 Amperes UL listed circuit breakers rated 125 A 6
devices having I2t or I4t (such as or Less. The next higher standard or less shall be marked as being suit-
OPTIM trip units) characteristics, overcurrent device rating (above able for 60ºC (140ºF), 75ºC (167ºF) only
and fuses. the ampacity of the conductors or 60/75ºC (140/167ºF) wire. All Cutler- 7
being protected) shall be permit- Hammer breakers rated 125 A or less
In general for systems such as shown are marked 60/75ºC. All UL listed circuit
in the example: ted to be used, provided all of the
following conditions are met. breakers rated over 125 A are suitable
8
1. The settings or ratings of the pri- for 75ºC conductors. Conductors rated
mary side fuse and main breaker 1. The conductors being protected
for higher temperatures may be used,
must not exceed the settings are not part of a multi-outlet
but must not be loaded to carry more
9
allowed by NEC Article 450. branch circuit supplying recepta-
cles for cord- and plug-connected current than the 75ºC ampacity of that
size conductor for equipment marked
2. At 12 x IFL the minimum melting portable loads.
or rated 75ºC or the 65ºC ampacity of
10
time characteristic of the fuse
should be higher than 0.1 second. 2. The ampacity of the conductors that size conductor for equipment
does not correspond with the marked or rated 65ºC. However, when
3. standard ampere rating of a fuse or applying derated factors, so long as
11
a circuit breaker without overload the actual load does not exceed the
4. The primary fuse should be to the trip adjustments above its rating lower of the derated ampacity or the
left of the transformer damage (but that shall be permitted to have 75ºC or 60ºC ampacity that applies.
12
curve as much as possible. The other trip or rating adjustments).
correction factor for a single line- Zone Selective Interlocking
to-ground factor must be applied 3. The next higher standard rating 13
to the damage curve. selected does not exceed 800 Trip elements equipped with zone
amperes. selective interlocking, trip without
5. The setting of the short-time delay intentional time delay unless a 14
element must be checked against C. Devices Rated Over 800 Amperes. restraint signal is received from
the fuse MMT after it is corrected Where the overcurrent device a protective device downstream.
for line-to-line faults. is rated over 800 amperes, the Breakers equipped with this feature 15
ampacity of the conductors it pro- reduce the damage at the point of
6. The maximum fault current must tects shall be equal to or greater
be indicated at the load side of fault if the fault occurs at a location
each protective device.
than the rating of the overcurrent between the zone of protection. 16
device as defined in Section 240.6.
7. The setting of a feeder protective The upstream breaker upon receipt
D. Small Conductors. Unless specifi-
device must comply with Article cally permitted in 240.4(E) or
of the restraint signal will not trip until 17
240 and Article 430 of the NEC. its time-delay setting times out. If the
240.4(G), the overcurrent protec- breaker immediately downstream of the
It also must allow the starting tion shall not exceed 15 amperes
and acceleration of the largest for 14 AWG, 20 amperes for 12
fault does not open, then after timing 18
motor on the feeder while carrying out, the upstream breaker will trip.
AWG, and 30 amperes for 10 AWG
all the other loads on the feeder. copper; or 15 amperes for 12 AWG Breakers equipped with ground fault
and 25 amperes for 10 AWG alu- trip elements should also be specified
19
minum and copper-clad aluminum to include zone interlocking for the
after any correction factors for ground fault trip element.
ambient temperature and number
20
of conductors have been applied.
21

CA08104001E For more information visit: www.eaton.com


1.4-6 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 062
Protection and Coordination

Ground Fault Protection Suggested Ground Fault Settings Any of these current-limiting devices
i Article 230-95 of NEC requires ground-
— fuses, fused breakers, or current-
For the main devices: limiting breakers — cannot only clear
fault protection of equipment shall be A ground fault pickup setting equal these large faults safely, but also will
ii provided for solidly grounded wye
electrical services of more than 150
to 20 – 30% of the main breaker rating limit the Ip and I2t let-through signifi-
but not to exceed 1200 amperes, and cantly to prevent damage to apparatus
volts to ground, but not exceeding a time delay equal to the delay of the downstream, extending their zone of
1 600 volts phase-to-phase for each short time element, but not to exceed protection. Without the current limita-
service disconnect rated 1000 amperes 1 second. tion of the upstream device, the fault
or more. current could exceed the withstand
2 The rating of the service disconnect
For the feeder ground fault setting:
A setting equal to 20 – 30% of the
capability of the downstream equip-
shall be considered to be the rating ment. Underwriters Laboratories tests
feeder ampacity and a time delay to
of the largest fuse that can be installed and lists these series combinations.
3 or the highest continuous current trip
coordinate with the setting of the main
Application information is available
(at least 6 cycles below the main).
setting for which the actual overcurrent for combinations which have been
device installed in a circuit breaker is If the desire to selectively coordinate tested and UL-listed for safe operation
4 rated or can be adjusted. ground fault devices results in settings downstream from MDSL, TRI-PAC, and
which do not offer adequate damage Current Limit-R, or Series C breakers of
The maximum allowable settings are: protection against arcing single line- various ratings, under high available
5 1200 amperes pickup, 1 second or less ground faults, the design engineer fault currents.
trip delay at currents of 3000 amperes should decide between coordination
or greater. Protective devices in electrical distri-
and damage limitation.
6 bution systems may be properly coor-
The characteristics of the ground-fault For low voltage systems with high- dinated when the systems are designed
trip elements create coordination magnitude available short circuit and built, but that is no guarantee that
7 problems with downstream devices currents, common in urban areas and they will remain coordinated. System
not equipped with ground fault large industrial installations, several changes and additions, plus power
protection. The National Electrical solutions are available. High interrupt- source changes, frequently modify the
8 Code exempts fire pumps and contin- ing Series C molded case breakers, protection requirements, sometimes
uous industrial processes from this current-limiting circuit breakers, or causing loss of coordination and even
requirement. current-limiting fuses, limiters integral increasing fault currents beyond the
9 It is recommended that in solidly with molded-case circuit breakers ratings of some devices. Consequently,
(TRI-PAC) or mounted on power cir- periodic study of protective-device
grounded 480/277-volt systems where
cuit breakers (MDSL) can be used to settings and ratings is as important for
main breakers are specified to be
10 equipped with ground fault trip elements handle these large fault currents. To safety and preventing power outages
provide current limiting, these devices as is periodic maintenance of the
that the feeder breakers be specified
must clear the fault completely within distribution system.
to be equipped with ground fault trip
11 elements as well. the first half-cycle, limiting the peak
current (Ip) and heat energy (I2t) let-
through to considerably less than
12 what would have occurred without
the device. For a fully fusible system,
rule-of-thumb fuse ratios or more accu-
13 rate I2t curves can be used to provide
selectivity and coordination. For fuse-
breaker combinations, the fuse should
14 be selected (coordinated) so as to per-
mit the breaker to handle those over-
loads and faults within its capacity;
15 the fuse should operate before or
with the breaker only on large faults,
approaching the interrupting capacity
16 of the breaker, to minimize fuse
blowing. Recently, unfused, truly
current-limiting circuit breakers with
17 interrupting ratings adequate for
the largest systems (Type Series C,
FDC, JDC, KDC, LDC and NDC
18 frames or Type Current Limit-R)
have become available.
19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-7
January 2008 System Application Considerations
Sheet 01 063
Grounding/Ground Fault Protection

Grounding with such an object while grounded The equipment grounding system
i
could be seriously injured or killed. must be bonded to the grounding
Grounding encompasses several dif- In addition, current flow from the acci- electrode at the source or service;
ferent but interrelated aspects of elec- dental grounding of an energized part however, it may be also connected
trical distribution system design and of the system could generate sufficient to ground at many other points. ii
construction, all of which are essential heat (often with arcing) to start a fire. This will not cause problems with
to the safety and proper operation of To prevent the establishment of such the safe operation of the electrical
the system and equipment supplied by unsafe potential difference requires distribution system. Where computers, 1
it. Among these are equipment ground- that (1) the equipment grounding data processing, or microprocessor-
ing, system grounding, static and conductor provide a return path for based industrial process control
lightning protection, and connection ground fault currents of sufficiently systems are installed, the equipment 2
to earth as a reference (zero) potential. low impedance to prevent unsafe grounding system must be designed
voltage drop, and (2) the equipment to minimize interference with their
1. Equipment Grounding grounding conductor be large enough proper operation. Often, isolated 3
to carry the maximum ground fault grounding of this equipment, or
Equipment grounding is essential
current, without burning off, for suffi- isolated electrical supply systems are
to safety of personnel. Its function is
cient time to permit protective devices required to protect microprocessors 4
to ensure that all exposed noncurrent-
(ground fault relays, circuit breakers, from power system “noise” that does
carrying metallic parts of all structures
fuses) to clear the fault. The grounded not in any way affect motors or other
and equipment in or near the electrical
conductor of the system (usually the electrical equipment. Such systems 5
distribution system are at the same
neutral conductor), although grounded must use single-point ground concept
potential, and that this is the zero
at the source, must not be used for to minimize “noise” and still meet
reference potential of the earth. Equip-
equipment grounding. the NEC requirements. Any separate 6
ment grounding is required by both the
isolated ground mat must be tied to
National Electrical Code (Article 250) The equipment grounding conductor the rest of the facility ground mat
and the National Electrical Safety Code may be the metallic conduit or race- system for NEC compliance. 7
regardless of how the power system is way of the wiring system, or a sepa-
grounded. Equipment grounding also rate equipment grounding conductor, 2. System Grounding
provides a return path for ground fault run with the circuit conductors, as 8
currents, permitting protective devices permitted by NEC. If a separate equip- System grounding connects the
to operate. Accidental contact of an ment grounding conductor is used, it electrical supply, from the utility, from
energized conductor of the system may be bare or insulated; if insulated, transformer secondary windings, or 9
with an improperly grounded noncur- the insulation must be green, green from a generator, to ground. A system
rent-carry metallic part of the system with yellow stripe or green tape. can be solidly grounded (no inten-
(such as a motor frame or panelboard Conductors with green insulation tional impedance to ground), imped- 10
enclosure) would raise the potential of may not be used for any purpose ance grounded (through a resistance
the metal object above ground poten- other than for equipment grounding. or reactance), or ungrounded (with
tial. Any person coming in contact no intentional connection to ground. 11
3. Medium Voltage System: Grounding
Table 1.4-1. Features of Ungrounded and Grounded Systems (from ANSI C62.92) 12
Description A B C D E
Ungrounded Solidly Grounded Reactance Grounded Resistance Grounded Resonant Grounded
13
(1) Apparatus Fully insulated Lowest Partially graded Partially graded Partially graded
Insulation
(2) Fault to Usually low Maximum value rarely Cannot satisfactorily be Low Negligible except when 14
Ground Current higher than 3-phase short reduced below one-half Petersen coil is short
circuit current or one-third of values for circuited for relay
solid grounding purposes when it may
compare with solidly-
15
grounded systems
(3) Stability Usually unimportant Lower than with other Improved over solid Improved over solid Is eliminated from
methods but can be grounding particularly grounding particularly consideration during 16
made satisfactory by use if used at receiving end if used at receiving end single line-to-ground
of high-speed breakers of system of system faults unless neutralizer
is short circuited to
isolate fault by relays
17
(4) Relaying Difficult Satisfactory Satisfactory Satisfactory Requires special
provisions but can be
made satisfactory
18
(5) Arcing Likely Unlikely Possible if reactance is Unlikely Unlikely
Grounds excessive
(6) Localizing Effect of fault transmitted Effect of faults localized Effect of faults localized to Effect of faults Effect of faults
19
Faults as excess voltage on to system or part of system or part of system transmitted as excess transmitted as excess
sound phases to all system where they occur where they occur unless voltage on sound phases voltage on sound phases
parts of conductively reactance is quite high to all parts of conduc- to all parts of conduc- 20
connected network tively connected network tively connected network
(7) Double Likely Likely Unlikely unless Unlikely unless Seem to be more likely
Faults reactance is quite high resistance is quite high but conclusive informa- 21
and insulation weak and insulation weak tion not available

CA08104001E For more information visit: www.eaton.com


1.4-8 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 064
Grounding/Ground Fault Protection

Table 1.4-1. Features of Ungrounded and Grounded Systems (Continued)


i Description A B C D E
Ungrounded Solidly Grounded Reactance Grounded Resistance Grounded Resonant Grounded

ii (8) Lightning
Protection
Ungrounded neutral Highest efficiency and
service arresters must be lowest cost
If reactance is very high
arresters for ungrounded
Arresters for ungrounded,
neutral service usually
Ungrounded neutral
service arresters must
applied at sacrifice in cost neutral service must be must be applied at be applied at sacrifice
and efficiency applied at sacrifice in cost sacrifice in cost and in cost and efficiency
1 and efficiency efficiency
(9) Telephone Will usually be low Will be greatest in Will be reduced from Will be reduced from Will be low in magnitude
Interference except in cases of double magnitude due to higher solidly grounded values solidly grounded values except in cases of double
2 faults or electrostatic fault currents but can faults or series resonance
induction with neutral be quickly cleared at harmonic frequencies,
displaced but duration particularly with high but duration may be great
3 may be great speed breakers
(10) Radio May be quite high during Minimum Greater than for Greater than for May be high during faults
Interference faults or when neutral solidly grounded, solidly grounded,
is displayed when faults occur when faults occur
4 (11) Line Will inherently clear Must be isolated for Must be isolated for Must be isolated for Need not be isolated but
Availability themselves if total length each fault each fault each fault will inherently clear itself
of interconnected line is in about 60 to 80 percent
5 low and require isolation of faults
from system in increas-
ing percentages as length
6 becomes greater
(12) Adaptability Cannot be interconnected Satisfactory indefinitely Satisfactory indefinitely Satisfactory with solidly- Cannot be interconnected
to Interconnec- unless interconnecting with reactance-grounded with solidly-grounded or reactance-grounded unless interconnected
7 tion system is ungrounded
or isolating transformers
systems systems systems with proper
attention to relaying
system is resonant
grounded or isolating
are used transformers are used.
Requires coordination
8 between interconnected
systems in neutralizer
settings
9 (13) Circuit Interrupting capacity Same interrupting Interrupting capacity Interrupting capacity Interrupting capacity
Breakers determined by capacity as required for determined by 3-phase determined by 3-phase determined by 3-phase
3-phase conditions 3-phase short circuit will fault conditions fault conditions fault conditions
practically always be
10 satisfactory
(14) Operating Ordinarily simple but Simple Simple Simple Taps on neutralizers must
Procedure possibility of double be changed when major
11 faults introduces compli- system switching is per-
cation in times of trouble formed and difficulty may
arise in interconnected
12 systems. Difficult to tell
where faults are located
(15) Total Cost High, unless conditions Lowest Intermediate Intermediate Highest unless the arc
are such that arc tends suppressing characteris-
13 to extinguish itself, when tic is relied on to eliminate
transmission circuits may transmission circuits
be eliminated, reducing when it may be lowest
14 total cost for the particular types
of service

15 Because the method of grounding


affects the voltage rise of the unfaulted
The aforementioned definition is of
significance in medium voltage distri-
of the 3-phase current at the point
of fault. Damage to cable shields must
phases above ground, ANSI C62.92 bution systems with long lines and be checked. Although this fact is not
16 classifies systems from the point of with grounded sources removed dur- a problem except in small cables, it is
view of grounding in terms of a ing light load periods so that in some a good idea to supplement the cable
coefficient of grounding locations in the system the X0 /X1, shields returns of ground fault current
17 Highest Power Frequency
R0 /X1 may exceed the defining limits. to prevent damage, by installing an
Other standards (cable and lightning equipment grounding conductor.
rms Line – Ground Voltage
COG = --------------------------------------------------------------------------------------------- arrester) allow the use of 100% rated
The burdens on the current transform-
18 rms Line – Line Voltage at Fault
Location with the Fault Removed
cables and arresters selected on the
ers must be checked also (for satura-
basis of an effectively grounded
system only where the criteria in the tion considerations), where residually
This same standard also defines connected ground relays are used
19 systems as effectively grounded when above are met. In effectively grounded
and the current transformers supply
COG ≤ .8 such a system would have system the line-to-ground fault current
is high and there is no significant current to phase relays and meters.
X0 /X1 ≤ 3.0 and R0 /X1 ≤ 1.0. Any other
20 grounding means that does not satisfy voltage rise in the unfaulted phases. If ground sensor current transformers
these conditions at any point in a With selective ground fault isolation (zero sequence type) are used they
system is not effectively grounded. the fault current should be at least 60% must be of high burden capacity.
21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-9
January 2008 System Application Considerations
Sheet 01 065
Grounding/Ground Fault Protection

Table 1.4-2 taken from ANSI-C62.92 current transformers rating of the Grounding Point
indicates the characteristics of the source. This rule will provide sensitive The most commonly used grounding i
various methods of grounding. differential protection for wye-con- point is the neutral of the system or the
nected generators and transformers neutral point created by means of a
Reactance Grounding against line-to-ground faults near the zigzag or a wye-broken delta grounding ii
It is generally used in the grounding neutral. Of course, if the installation transformer in a system which was oper-
of the neutrals of generators directly of ground fault differential protection ating as an ungrounded delta system.
connected to the distribution system is feasible, or ground sensor current 1
bus, in order to limit the line-to-ground transformers are used, sensitive differ- In general, it is a good practice that all
fault to somewhat less than the 3-phase ential relaying in resistance grounded source neutrals be grounded with the
fault at the generator terminals. If the system with greater fault limitation same grounding impedance magnitude. 2
reactor is so sized, in all probability is feasible. In general, ground sensor However, neutrals should not be tied
the system will remain effectively current transformers (zero sequence) together to a single resistor. Where
grounded. do not have high burden capacity. one of the medium voltage sources is 3
Resistance grounded systems limit the the utility, their consent for impedance
Resistance Grounded circulating currents of triple harmonics grounding must be obtained.
Medium voltage systems in general and limit the damage at the point 4
should be low resistance grounded. The neutral impedance must have a
of fault. This method of grounding
The ground fault is typically limited to voltage rating at least equal to the rated
is not suitable for line-to-neutral
about 200 – 400 A but less than 1000 connection of loads.
line-to-neutral voltage class of the sys- 5
amperes (a cable shield consideration). tem. It must have at least a 10-second
With a properly sized resistor and On medium voltage systems, 100% rating equal to the maximum future
relaying application, selective fault cable insulation is rated for phase-to- line-to-ground fault current and a con- 6
isolation is feasible. The fault limit neutral voltage. If continued operation tinuous rating to accommodate the
provided has a bearing on whether with one phase faulted to ground is triple harmonics that may be present.
residually connected relays are used desired, increased insulation thick- 7
or ground sensor current transformers ness is required. For 100% insulation, 4. Low Voltage System: Grounding
are used for ground fault relaying. fault clearance is recommended within Solidly grounded 3-phase systems
one minute; for 133% insulation, one (Figure 1.4-2) are usually wye- 8
In general, where residually connected hour is acceptable; for indefinite connected, with the neutral point
ground relays are used (51N), the fault operation, as long as necessary, grounded. Less common is the “red-
current at each grounded source 173% insulation is required. leg” or high-leg delta, a 240 V system 9
should not be limited to less than the
supplied by some utilities with one
Table 1.4-2. Characteristics of Grounding winding center-tapped to provide 120 V
Grounding Classes Ratios of Symmetrical Percent Fault Per Unit Transient to ground for lighting. This 240 V, 10
and Means Component Parameters ➀ Current LG Voltage 3-phase, 4-wire system is used where
120 V lighting load is small compared
X0/X1 R0/X1 R0/X0  
to 240 V power load, because the 11
A. Effectively ➃
installation is low in cost to the utility.
1. Effective 0-3 0-1 — >60 ≤2
A corner-grounded 3-phase delta
2. Very effective 0-1 0-0.1 — >95 <1.5
system is sometimes found, with 12
B. Noneffectively
1. Inductance one phase grounded to stabilize all
a. Low Inductance 3-10 0-1 — >25 <2.3 voltages to ground. Better solutions
b. High Inductance >10 — <2 <25 ≤2.73  are available for new installations. 13
2. Resistance
a. Low Resistance 0-10 — ≥2 <25 <2.5
b. High Resistance — >100 ≤(-1) <1 ≤2.73 Phase A 14
3. Inductance and Resistance >10 — >2 <10 ≤2.73 • • • Phase B
4. Resonant  — — <1 ≤2.73 N
5. Ungrounded/Capacitance • Phase C
15
a. Range A -∞ to -40  — — <8 ≤3 • Neutral
b. Range B -40 to 0 — — >8 >3 
 Values of the coefficient of grounding (expressed as a percentage of maximum phase-to-phase Grounded Wye
voltage) corresponding to various combinations of these ratios are shown in the ANSI C62.92 16

Appendix figures. Coefficient of grounding affects the selection of arrester ratings. • Phase B
Ground-fault current in percentage of the 3-phase short circuit value.
 Transient line-to-ground voltage, following the sudden initiation of a fault in per unit of the crest • • • Phase C
Phase A
17
of the prefault line-to-ground operating voltage for a simple, linear circuit.
 In linear circuits, Class A1 limits the fundamental line-to-ground voltage on an unfaulted phase to • Neutral


138% of the prefault voltage; Class A2 to less than 110%.
See ANSI 62.92 para. 7.3 and precautions given in application sections.
18
Center-Tapped (High-Leg) Delta
 Usual isolated neutral (ungrounded) system for which the zero-sequence reactance is capacitive
(negative).
 Same as NOTE (6) and refer to ANSI 62.92 para. 7.4. Each case should be treated on its own merit.
• Phase A 19
 Under restriking arcing ground fault conditions (e.g., vacuum breaker interrupter operation), this • • Phase B

value can approach 500%. • Phase C
20
Under arcing ground fault conditions, this value can easily reach 700% but is essentially unlimited.
Corner-Grounded Delta

Figure 1.4-2. Solidly Grounded Systems


21

CA08104001E For more information visit: www.eaton.com


1.4-10 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 066
Grounding/Ground Fault Protection

Ungrounded systems (Figure 1.4-3) Selecting the Low Voltage System With one phase grounded, the voltage
i can be either wye or delta, although Grounding Method to ground of the other two phases
the ungrounded delta system is far There is no one “best” distribution rises 73%, to full phase-to-phase
more common. system for all applications. In choosing voltage. In low voltage systems this
ii among solidly grounded, resistance is not important, since conductors
grounded, or ungrounded power are insulated for 600 V.
• Phase A
distribution, the characteristics of the
1 system must be weighed against the
A low voltage resistance grounded
• • Phase B
Phase C requirements of power loads, lighting
system is normally grounded so that
the single line-to-ground fault current
loads, continuity of service, safety,
2 Ungrounded Delta
and cost.
exceeds the capacitive charging
current of the system. If data for the
Phase A charging current is not available use
• • • Phase B Under ground fault conditions, each
3 N system behaves very differently. A 40 – 50 ohm resistor in the neutral
• Phase C solidly grounded system produces of the transformer.
Ungrounded Wye high fault currents, usually with arcing, In commercial and institutional
4 and the faulted circuit must be cleared installations, such as office buildings,
Figure 1.4-3. Ungrounded Systems on the first fault within a fraction of a shopping centers, schools, and hospi-
second to minimize damage. An tals, lighting loads are often 50% or
5 Resistance-grounded systems ungrounded system will pass limited more of the total load. In addition, a
(Figure 1.4-4) are simplest with a wye current into the first ground fault —
connection, grounding the neutral feeder outage on first ground fault is
only the charging current of the sys- seldom crucial — even in hospitals,
6 point directly through the resistor. tem, caused by the distributed capaci- which have emergency power in criti-
Delta systems can be grounded by tance to ground of the system wiring
means of a zig-zag or other grounding cal areas. For these reasons, a solidly
and equipment. In low voltage sys- grounded wye distribution, with the
7 transformer. Wye broken delta trans- tems, this is rarely more than 1 or 2 neutral used for lighting circuits, is
former banks may also be used. amperes. Therefore, on first ground usually the most economical, effective,
fault an ungrounded system can con- and convenient design. In some
8 Phase A tinue in service, making it desirable instances it is an NEC requirement.
• • • Phase B where power outages cannot be toler-
N ated. However, if the ground fault is In industrial installations, the effect
9 R • Phase C intermittent, sputtering or arcing, a of a shutdown caused by a single
high voltage — as much as 6 to 8 times ground fault could be disastrous.
phase voltage — can be built up across An interrupted process could cause
10 Resistance-Grounded Wye the system capacitance, from the the loss of all the materials involved,
phase conductors to ground. Similar often ruin the process equipment
• • Phase A high voltages can occur as a result of itself, and sometimes create extremely
11 resonance between system capaci- dangerous situations for operating
• • • Phase B
tance and the inductances of trans- personnel. On the other hand, lighting
• Phase C
12 • formers and motors in the system. The is usually only a small fraction of the
N • phase-to-phase voltage is not affected. total industrial electrical load. A solidly
R • This high transient phase-to-ground grounded neutral circuit conductor
voltage can puncture insulation at is not imperative and, when required,
13 weak points, such as motor windings, can be obtained from inexpensive
Delta With Derived Neutral Resistance- and is a frequent cause of multiple lighting transformers.
Grounded Using Zig-Zag Transformer motor failures on ungrounded sys-
14 tems. Locating a first fault on an Because of the ability to continue in
ungrounded system can be difficult. operation with one ground fault on
Figure 1.4-4. Resistance-Grounded Systems the system, many existing industrial
If, before the first fault is cleared, a
15 This derives a neutral point, which second ground fault occurs on a differ- plants use ungrounded delta distribu-
can be either solidly or impedance- ent phase, even on a different, remote tion. Today, new installations can have
grounded. If the grounding transformer feeder, it is a high-current phase-to- all the advantages of service continuity
16 has sufficient capacity, the neutral cre- ground-to-phase fault, usually arcing, of the ungrounded delta, yet minimize
ated can be solidly grounded and used that can cause severe damage if at the problems of the system, such as
as part of a 3-phase, 4-wire system. least one of the grounds is not cleared the difficulty of locating the first
17 Most transformer-supplied systems immediately. If the second circuit is ground fault, risk of damage from a
are either solidly grounded or resis- remote, enough current may not flow second ground fault, and damage tran-
tance grounded. Generator neutrals to cause protection to operate. This sient overvoltages. A high-resistance
18 are often grounded through a reactor, can leave high voltages and stray grounded wye distribution can con-
to limit ground fault (zero sequence) currents on structures and jeopardize tinue in operation with a ground fault
currents to values the generator can personnel. on the system, will not develop tran-
19 withstand. sient overvoltages, and, because the
In general, where loads will be con- ground point is established, locating
nected line-to-neutral, solidly grounded a ground fault is less difficult than
20 systems are used. High resistance on an ungrounded system especially
grounded systems are used as substi- when a “pulsing contactor” design is
tutes for ungrounded systems where applied. When combined with sensi-
21 high system availability is required. tive ground-fault protection, damage

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-11
January 2008 System Application Considerations
Sheet 01 067
Grounding/Ground Fault Protection

from a second ground fault can be this makes ground fault protection
nearly eliminated. Ungrounded delta mandatory on 480Y/277-volt services, Main i
systems can be converted to high- but not on 208Y/120-volt services. On a
resistance grounded systems, using 208-volt system, the voltage to ground Neutral

a zig-zag or other grounding trans- is 120 volts. If a ground fault occurs,


Service
Transformer
GFR
ii
former to derive a neutral, with similar the arc goes out at current zero, and Sensor
Typical
Feeder
benefits, see Section 38. While the the voltage to ground is often too low Ground Bus

majority of manufacturing plants use to cause it to restrike. Therefore, arc-


Main Bonding
1
solidly grounded systems, in many ing ground faults on 208-volt systems Jumper
Typical
instances, the high-resistance tend to be self-extinguishing. On a Grounding Equipment
grounded distribution will be the most 480-volt system, with 277 volts to Electrode
Conductor
Grounding
Conductor
4W Load
2
advantageous. ground, restrike usually takes place
after current zero, and the arc tends to
Ground Fault Protection be self-sustaining, causing severe and Figure 1.4-5. Ground Return Sensing Method 3
A ground fault normally occurs in one increasing damage, until the fault is When an energized conductor faults
of two ways: By accidental contact of cleared by a protective device. to grounded metal, the fault current
an energized conductor with normally returns along the ground return path to
4
The NEC requires ground fault
grounded metal, or as a result of protection on the service disconnecting the neutral of the source transformer.
an insulation failure of an energized means. This protection works so fast This path includes the main bonding 5
conductor. When an insulation failure that for ground faults on feeders, or jumper — as shown in Figure 1.4-5.
occurs, the energized conductor con- even branch circuits, it will often open A current sensor on this conductor
tacts normally noncurrent-carrying the service disconnect before the (which can be a conventional bar-type 6
grounded metal, which is bonded to feeder or branch circuit overcurrent or window type CT) will respond to
or part of the equipment grounding device can operate. This is highly ground fault currents only. Normal
conductor. In a solidly grounded sys- undesirable, and in the NEC (230-95) neutral currents resulting from 7
tem, the fault current returns to the a Fine Print Note (FPN) states that unbalanced loads will return along
source primarily along the equipment additional ground fault protective the neutral conductor and will not be
grounding conductors, with a small equipment will be needed on feeders detected by the ground return sensor. 8
part using parallel paths such as build- and branch circuits where maximum
ing steel or piping. If the ground return This is an inexpensive method of sensing
continuity of electric service is neces- ground faults where protection per
impedance were as low as that of the sary. Unless it is acceptable to discon- NEC (230-95) is desired. For it to 9
circuit conductors, ground fault cur- nect the entire service on a ground
rents would be high, and the normal operate properly, the neutral must be
fault almost anywhere in the system, grounded in only one place as indicated
phase overcurrent protection would such additional stages of ground in Figure 1.4-5. In many installations, 10
clear them with little damage. Unfortu- fault protection must be provided.
nately, the impedance of the ground the servicing utility grounds the neutral
At least two stages of protection are at the transformer and additional
return path is usually higher, the fault mandatory in health care facilities grounding is required in the service 11
itself is usually arcing and the imped- (NEC Sec. 517-17).
ance of the arc further reduces the equipment per NEC (250-24(a)(2)).
In such cases, and others including
fault current. In a 480Y/277-volt sys- Overcurrent protection is designed to
protect conductors and equipment multiple source with multiple, inter- 12
tem, the voltage drop across the arc
can be from 70 to 140 V. The resulting against currents that exceed their connected neutral ground points,
residual or zero sequence ground
ground fault current is rarely enough ampacity or rating under prescribed
sensing methods should be employed. 13
to cause the phase overcurrent protec- time values. An overcurrent can result
tion device to open instantaneously from an overload, short circuit or (high A second method of detecting ground
and prevent damage. Sometimes, the level) ground fault condition. When faults involves the use of a zero 14
ground fault is below the trip setting of currents flow outside the normal sequence sensing method, as illus-
the protective device and it does not current path to ground, supplementary trated in Figure 1.4-6. This sensing
trip at all until the fault escalates and ground fault protection equipment will method requires a single, specially- 15
extensive damage is done. For these be required to sense low-level ground designed sensor either of a toroidal
reasons, low level ground protection fault currents and initiate the protec- or rectangular shaped configuration.
devices with minimum time delay set- tion required. Normal phase over- This core balance current transformer 16
tings are required to rapidly clear current protection devices provide surrounds all the phase and neutral
ground faults. This is emphasized by no protection against low-level conductors in a typical 3-phase, 4-wire
the NEC requirement that a ground ground faults. distribution system. The sensing 17
fault relay on a service shall have a method is based on the fact that the
There are three basic means of sensing
maximum delay of one second for vectorial sum of the phase and neutral
ground faults. The most simple and
faults of 3000 amperes or more.
direct method is the ground return currents in any distribution circuit will 18
The NEC (Sec. 230-95) requires that method as illustrated in Figure 1.4-5. equal zero unless a ground fault condi-
ground fault protection, set at no more This sensing method is based on the fact tion exists downstream from the sensor.
than 1200 amperes, be provided for that all currents supplied by a trans- All currents that flow only in the circuit 19
each service disconnecting means former must return to that transformer. conductors, including balanced or
rated 1000 amperes or more on solidly unbalanced phase-to-phase and phase-
grounded wye services of more than to-neutral normal or fault currents, and 20
150 volts to ground, but not exceeding harmonic currents, will result in zero
600 volts phase-to-phase. Practically, 21

CA08104001E For more information visit: www.eaton.com


1.4-12 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 068
Grounding/Ground Fault Protection

sensor output. However, should any neutral. In a residual sensing scheme, or in multi-tier schemes where addi-
i conductor become grounded, the fault the relationship of the polarity mark- tional levels of ground fault protection
current will return along the ground ings — as noted by the “X” on each are desired for added service continuity.
path — not the normal circuit conduc- sensor — is critical. Since the vectorial Additional grounding points may be
ii tors — and the sensor will have an sum of the currents in all the conduc- employed upstream of the residual
unbalanced magnetic flux condition tors will total zero under normal, non- sensors but, not on the load side.
and a sensor output will be generated ground faulted conditions, it is impera-
1 to actuate the ground fault relay. tive that proper polarity connections Both the zero sequence and residual
are employed to reflect this condition. sensing methods have been com-
monly referred to as “vectorial
2 Zero
Sequence
Alternate
Sensor
summation” methods.
Sensor Location Sensor
Residual
Main Polarity
Sensors Most distribution systems can utilize
Marks
either of the three sensing methods
3 Main
exclusively or a combination of the
Neutral
sensing methods depending upon
the complexity of the system and
4 Neutral
the degree of service continuity
GFR Typical
Feeder
and selective coordination desired.
Typical
Different methods will be required
5 GFR Feeder
depending upon the number of
Typical supply sources and the number and
4W Load Typical
location of system grounding points.
6 4W Load

Figure 1.4-6. Zero Sequence Sensing Method As an example, one of the more
Figure 1.4-7. Residual Sensing Method frequently used systems where
7 Zero sequence sensors are available
As with the zero sequence sensing
continuity of service to critical loads
with various window openings for is a factor is the dual source system
circuits with small or large conductors, method, the resultant residual sensor
illustrated in Figure 1.4-8. This system
8 and even with large rectangular win- output to the ground fault relay or inte-
gral ground fault tripping circuit will
utilizes tie-point grounding as permit-
dows to fit over bus bars or multiple ted under NEC Sec. 250-24(a)(3).
large size conductors in parallel. Some be zero if all currents flow only in the
The use of this grounding method is
9 sensors have split cores for installation circuit conductors. Should a ground
limited to services that are dual fed
over existing conductors without fault occur, the current from the
disturbing the connections. (double-ended) in a common enclosure
faulted conductor will return along the
or grouped together in separate enclo-
10 This method of sensing ground faults
ground path, rather than on the other
sures and employing a secondary tie.
circuit conductors, and the residual
can be employed on the main discon-
nect where protection per NEC (230-95) sum of the sensor outputs will not be This scheme utilizes individual sensors
11 is desired. It can also be easily employed zero. When the level of ground fault connected in ground return fashion.
in multi-tier systems where additional current exceeds the pre-set current Under tie breaker closed operating
levels of ground fault protection are and time delay settings, a ground conditions either the M1 sensor or M2
12 desired for added service continuity. fault tripping action will be initiated. sensor could see neutral unbalance
Additional grounding points may be currents and possibly initiate an
This method of sensing ground faults
employed upstream of the sensor but, improper tripping operation. However,
can be economically applied on main
13 not on the load side.
service disconnects where circuit
with the polarity arrangements of these
two sensors along with the tie breaker
Ground fault protection employing breakers with integral ground fault
ground return or zero sequence sensing auxiliary switch (T/a) and interconnec-
protection are provided. It can be used
14 methods can be accomplished by the in protection schemes per NEC (230-95)
tions as shown, this possibility is
use of separate ground fault relays
(GFRs) and disconnects equipped with
15 standard shunt trip devices or by circuit Power Power
breakers with integral ground fault Transformer Transformer
protection with external connections
16 arranged for these modes of sensing. In
some cases, a reliable source of control Main Neutral Sensor Neutral Sensor Main
power is needed. Bkr. Main Bkr. 52-1 Tie Bkr. Main Bkr. 52-2 Bkr.
17 The third basic method of detecting
52-1
ØA, ØB, ØC
52-T
ØA, ØB, ØC
52-2

ground faults involves the use of multi- Neutral Neutral


ple current sensors connected in a resid- Neutral Sensor
18 ual sensing method as illustrated in Typical ( )B5
Tie Bkr. 52-T
Typical
( )B5
Figure 1.4-7. This is a very common 4-Wire ( )B4
( )B4 52-T 52-T 4-Wire
M2N
M1G

M2G
M1N

Feeder
TN
TG

sensing method used with circuit break- a Feeder


19 ers equipped with electronic trip units, 33-
a

current sensors and integral ground 4-Wire 52-T 4-Wire


fault protection. The 3-phase sensors B5 B4 B4 B5 B4 B5 Load
Load
20 are required for normal phase overcur- B4 B5
Digitrip
Main Bkr.
Digitrip
Main Bkr.
Digitrip
Main Bkr. B4 B5
rent protection. Ground fault sensing is Digitrip 52-1 52-2 52-2 Digitrip
obtained with the addition of an identi-
21 cally rated sensor mounted on the
Figure 1.4-8. Dual Source System — Single Point Grounding

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-13
January 2008 System Application Considerations
Sheet 01 069
Grounding/Ground Fault Protection

eliminated. Selective ground fault types may be employed to accomplish GFR next upstream from the fault and
tripping coordination between the the desired end results. that device will operate instantaneously i
tie breaker and the two main circuit to clear the fault with minimum dam-
breakers is achieved by pre-set current Since the NEC (230-95) limits the age and maximum service continuity.
pickup and time delay settings between maximum setting of the ground fault This operating mode permits all GFRs ii
devices GFR/1, GFR/2 and GFR/T. protection used on service equipment to operate instantaneously for a fault
to 1200 A (and timed tripping at 3000 A within their zone and still provide
The advantages of increased service for one second), to prevent tripping complete selectivity between zones. 1
continuity offered by this system can of the main service disconnect on a The National Electrical Manufacturers
only be effectively utilized if additional feeder ground fault, ground fault Association (NEMA) states, in their
levels of ground fault protection are protection must be provided on all the application guide for ground fault 2
added on each downstream feeder. feeders. To maintain maximum service protection, that zone interlocking is
Some users prefer individual ground- continuity, more than two levels (zones) necessary to minimize damage from
ing of the transformer neutrals. In such of ground fault protection will be ground faults. A 2-wire connection 3
cases a partial differential ground fault required, so that ground fault outages is required to carry the restraining
scheme should be used for the mains can be localized and service interrup- signal from the GFRs in one zone to
and tie breaker. tion minimized. To obtain selectivity the GFRs in the next zone. 4
between different levels of ground
An example of a residual partial differ- fault relays, time delay settings should Circuit breakers with integral ground
ential scheme is shown in Figure 1.4-9.
The scheme typically relies upon the
be employed with the GFR furthest fault protection and standard circuit 5
downstream having the minimum breakers with shunt trips activated
vector sum of at least two neutral time delay. This will allow the GFR by the ground fault relay are ideal for
sensors in combination with each
breakers’ 3-phase sensors. To reduce
nearest the fault to operate first. ground fault protection. Many fused 6
With several levels of protection, this switches over 1200 A, and Cutler-
the complexity of the drawing, each will reduce the level of protection for Hammer Type FDP fusible switches
of the breakers’ 3-phase sensors have
not been shown. It is absolutely critical
faults within the upstream GFR zones. in ratings from 400 A to 1200 A, are 7
Zone interlocking was developed for listed by UL as suitable for ground
that the sensors’ polarities are sup- GFRs to overcome this problem. fault protection. Fusible switches so
plied as shown, the neutral sensor listed must be equipped with a shunt 8
ratings of the mains and tie are the GFRs (or circuit breakers with integral trip, and be able to open safely on
same, and that there are no other ground fault protection) with zone faults up to 12 times their rating.
grounds on the neutral bus made interlocking are coordinated in a 9
downstream of points shown. system to operate in a time delayed Power distribution systems differ
mode for ground faults occurring most widely from each other, depending
An infinite number of ground fault remote from the source. However, this upon the requirements of each user,
protection schemes can be developed time delayed mode is only actuated and total system overcurrent protec-
10
depending upon the number of alternate when the GFR next upstream from the tion, including ground fault currents,
sources, the number of grounding fault sends a restraining signal to the must be individually designed to meet
points and system interconnections upstream GFRs. The absence of a these needs. Experienced and knowl-
11
involved. Depending upon the individ- restraining signal from a downstream edgeable engineers must consider the
ual system configuration, either mode GFR is an indication that any occurring power sources (utility or on-site), the
of sensing or a combination of all ground fault is within the zone of the effects of outages and costs of down-
12
time, safety for people and equipment,

Power Power
initial and lifecycle costs, and many 13
other factors. They must apply protec-
Transformer Transformer tive devices, analyzing the time-current
characteristics, fault interrupting 14
capacity, and selectivity and coordina-
X
X
X
X tion methods to provide the most safe
Neutral Neutral
Sensor Main Sensor Main
and cost-effective distribution system. 15
Main Breaker 52-1 Breaker 52-2 Main
Breaker Breaker Further Information
52-1 PRSC-4E — System Neutral Ground-
52-2 ■
ing and Ground Fault Protection
16
Phase A, Tie Breaker Phase A,
Phase B, (ABB Publication).
Phase B, 52-T
Phase C Phase C ■ PB 2.2 — NEMA Application Guide 17
Neutral X
Neutral for Ground Fault Protective Devices
Neutral Sensor X for Equipment.
Tie Breaker 52-T ■ IEEE Standard 142 — Grounding of 18
Trip Unit
Trip Unit

Typical X
Typical X

4-Wire
X
4-Wire
X
Industrial and Commercial Power
Feeder 52-1 52-T 52-2 Feeder Systems (Green Book).
a a a ■ IEEE Emerald Book (Standard 1100). 19
■ UL 96A, Installation Requirements
4-Wire Load 4-Wire Load for Lightning Protection Systems.
Trip Unit Trip Unit Trip Unit 20
Main Breaker Tie Breaker Main Breaker
52-1 52-T 52-2
21
Figure 1.4-9. Dual Source System — Multiple Point Grounding

CA08104001E For more information visit: www.eaton.com


1.4-14 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 070
Grounding/Ground Fault Protection

Lightning and Surge Protection One of the most effective grounding Medium Voltage Equipment Surge
i Physical protection of buildings
electrodes is the concrete-encased
Protection Considerations
electrode, sometimes called the Ufer
from direct damage from lightning ground, named after the man who Transformers
ii is beyond the scope of this section.
Requirements will vary with geo-
developed it. It consists of at least 20
feet (6 m) of steel reinforcing bars or If the voltage withstand/BIL rating of
graphic location, building type and rods not less than 1/2 inches (12.7 mm) the transformer is less than that of the
1 environment, and many other factors in diameter, or at least 20 feet (6 m) switchgear feeding the transformer,
(see IEEE/ANSI Standard 142, Ground- of bare copper conductor, size No. 4 surge protection is recommended at
ing of Industrial and Commercial AWG or larger, encased in at least 2 the transformer terminals, in line with
2 Power Systems). Any lightning protec- inches (50.8 mm) of concrete. It must established practices. In addition, con-
tion system must be grounded, and be located within and near the bottom sideration should be given to utilizing
the lightning protection ground must of a concrete foundation or footing surge arresters and/or surge capaci-
3 be bonded to the electrical equipment that is in direct contact with the earth. tors for transformers having equal or
grounding system. Tests have shown this electrode to greater withstand/BIL ratings than that
provide a low-resistance earth ground of the switchgear feeding the trans-
4 Grounding Electrodes even in poor soil conditions. former for distribution systems where
At some point, the equipment and reflected voltage waves and/or reso-
system grounds must be connected The electrical distribution system and nant conditions may occur. Typically
5 to the earth by means of a grounding equipment ground must be connected incoming voltage surges are reflected
electrode system. to this grounding electrode system by at the transformer primary terminals
a grounding electrode conductor. All (because of the change in impedance)
6 Outdoor substations usually use a other grounding electrodes, such as resulting in voltages at the ends of the
ground grid, consisting of a number of those for the lightning protection sys- transformer primary terminals/wind-
ground rods driven into the earth and tem, the telephone system, television ings of up to two (2) times the incom-
7 bonded together by buried copper antenna and cable TV system grounds, ing voltage wave. System capacitance
conductors. The required grounding and computer systems, must be bonded and inductance values combined with
electrode system for a building is to this grounding electrode system. the transformer impedance values can
8 spelled out in the NEC Article 250. cause resonant conditions resulting
in amplified reflected waves. Surge
The preferred grounding electrode arresters/capacitors when required,
9 is a metal underground water pipe in should be located as close to the trans-
direct contact with the earth for at least former primary terminals as practical.
10 feet (3 m). However, because under-
10 ground water piping is often plastic Motors
outside the building, or may later be Surge capacitors and, where appropri-
replaced by plastic piping, the NEC ate, surge arresters should be applied
11 requires this electrode to be supple- at the motor terminals.
mented by and bonded to at least one
other grounding electrode, such as Generators
12 the effectively grounded metal frame
of the building, a concrete-encased
Surge capacitors and station
class surge arresters at the machine
electrode, a copper conductor ground terminals.
13 ring encircling the building, or a made
Further Information
electrode such as one or more driven
ground rods or a buried plate. Where ■ IEEE/ANSI Standard 142 — Ground-
14 any of these electrodes are present, ing Industrial and Commercial
they must be bonded together into Power Systems (Green Book).
one grounding electrode system. ■ IEEE Standard 241 — Electric Power
15 Systems in Commercial Buildings
(Gray Book).
■ IEEE Standard 141 — Electric Power
16 Distribution for Industrial Plants
(Red Book).
17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-15
January 2008 System Application Considerations
Sheet 01 071
Power Quality

Power Quality Terms Defining the Problem Another option is to buy power condi-
i
Power quality problems can be resolved tioning equipment to correct any and
Technical Overview in three ways: by reducing the variations all perceived power quality problems
in the power supply (power distur- without any on-site investigation.
Introduction bances), by improving the load equip- ii
Power Quality Terms
Sensitive electronic loads deployed ment’s tolerance to those variations, or
by inserting some interface equipment Power Disturbance: Any deviation
today by users require strict require-
ments for the quality of power delivered (known as power conditioning equip- from the nominal value (or from some 1
ment) between the electrical supply selected thresholds based on load
to loads.
and the sensitive load(s) to improve the tolerance) of the input ac power
For electronic equipment, power compatibility of the two. Practicality characteristics. 2
disturbances are defined in terms of and cost usually determine the extent Total Harmonic Distortion or Distortion
amplitude and duration by the elec- to which each option is used.
tronic equipment operating envelope.
Factor: The ratio of the root-mean-
square of the harmonic content to the
3
Electronic loads may be damaged and Many methods are used to define
power quality problems. For example, root-mean-square of the fundamental
disrupted, with shortened life
expectancy, by disturbances. one option is a thorough on-site quantity, expressed as a percentage 4
investigation which includes inspecting of the fundamental.
The proliferation of computers, variable wiring and grounding for errors, Crest Factor: Ratio between the peak
frequency motor drives, UPS systems monitoring the power supply for value (crest) and rms value of a periodic 5
and other electronically controlled power disturbances, investigating waveform.
equipment is placing a greater demand equipment sensitivity to power distur-
on power producers for a disturbance- bances, and determining the load Apparent (Total) Power Factor: The 6
free source of power. Not only do these disruption and consequential effects ratio of the total power input in watts
types of equipment require quality (costs), if any. In this way, the power to the total volt-ampere input.
power for proper operation; many quality problem can be defined, 7
times, these types of equipment are Sag: An rms reduction in the ac
alternative solutions developed,
also the sources of power disturbances voltage, at the power frequency, for
and optimal solution chosen.
that corrupt the quality of power in a the duration from a half-cycle to a few 8
given facility. Before applying power-conditioning seconds. An undervoltage would have
equipment to solve power quality a duration greater than several seconds.
Power Quality is defined according problems, the site should be checked 9
to IEEE Standard 1100 as the concept Interruption: The complete loss of
for wiring and grounding problems.
of powering and grounding electronic voltage for a time period.
Sometimes, correcting a relatively
equipment in a manner that is suitable inexpensive wiring error, such as a Transient: A sub-cycle disturbance 10
to the operation of that equipment. loose connection or a reversed neutral in the ac waveform that is evidenced
IEEE Standard 1159 notes that “within and ground wire, can avoid a more by a sharp brief discontinuity of the
the industry, alternate definitions or expensive power conditioning solution. waveform. May be of either polarity 11
interpretations of power quality have and may be additive to or subtractive
been used, reflecting different points Sometimes this approach is not practical
from the nominal waveform.
of view.” because of limitations in time; expense
is not justified for smaller installations;
12
Surge or Impulse: See transient.
In addressing power quality problems monitoring for power disturbances
at an existing site, or in the design may be needed over an extended Noise: Unwanted electrical signals
stages of a new building, engineers period of time to capture infrequent that produce undesirable effects 13
need to specify different services or disturbances; the exact sensitivities of in the circuits of control systems
mitigating technologies. The lowest the load equipment may be unknown in which they occur.
cost and highest value solution is to and difficult to determine; and finally,
14
selectively apply a combination of dif- Common-Mode Noise: The noise volt-
the investigative approach tends to age that appears equally and in phase
ferent products and services as follows: solve only observed problems. Thus
unobserved or potential problems
from each current-carrying conductor 15
Key Services/Technologies in the to ground.
“Power Quality” Industry: may not be considered in the solution.
For instance, when planning a new Normal-Mode Noise: Noise signals 16
■ Power quality surveys, analysis facility, there is no site to investigate. measurable between or among active
and studies. Therefore, power quality solutions are circuit conductors feeding the subject
■ Power monitoring. often implemented to solve potential
or perceived problems on a preventive
load, but not between the equipment 17
■ Grounding products and services. grounding conductor or associated
basis instead of a thorough on-site signal reference structure and the active
■ Surge protection.
■ Voltage regulation.
investigation. circuit conductors. 18
■ Harmonic solutions.
■ Lightning protection (ground rods, 19
hardware, etc.).
■ Uninterruptible Power Supply (UPS)
or Motor-Generator (M-G) set. 20

21

CA08104001E For more information visit: www.eaton.com


1.4-16 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 072
Power Quality

Methodology for Ensuring Effective Power The proliferation of communication The benefit of implementing cascaded
i Quality to Electronic Loads and computer network systems network protection is shown in
The Power Quality Pyramid is an effec- has increased the need for proper Figure 1.4-11. Combined, the two
tive guide for addressing power quality grounding and wiring of ac and data/ stages of protection at the service
ii problems at an existing facility. The communication lines. In addition to entrance and branch panel locations
framework is also effective for specify- reviewing ac grounding and bonding reduce the IEEE 62.41 recommended
ing engineers who are designing a practices, it is necessary to prevent test wave (C3 – 20 kV, 10 kA) to less than
1 new facility. Power quality starts with ground loops from affecting the signal 200 V voltage, a harmless disturbance
grounding (the base of the pyramid) reference point. level for 120 V rated sensitive loads.
and then moves upward to address
2 the potential issues. This simple, 2. Surge Protection If only building entrance feeder protec-
tion were provided, the let-through
yet proven methodology, will provide Surge Protection Devices (SPDs) are voltage will be approximately 950 V in
the most cost-effective approach. recommended as the next stage power
3 As we move higher up the pyramid, quality solutions. NFPA, UL 96A, IEEE
a 277/480 V system exposed to induced
lightning surges. This level of let-through
the cost per kVA of mitigating potential Emerald Book and equipment manu- voltage can cause degradation or physi-
problems increase and the quality facturers recommend the use of surge
4 of the power increases (Refer to protectors. The transient voltage surge
cal damage of most electronic loads.
Figure 1.4-10). suppressors (also called TVSS) shunt Wherever possible, consultants, speci-
short duration voltage disturbances to fiers and application engineers should
5 ground, thereby preventing the surge ensure similar loads are fed from the
from affecting electronic loads. When same source. In this way, disturbance-
generating loads are separated from
6 installed as part of the facility-wide
Cost Per kVA

design, SPDs are cost-effective electronic circuits affected by power


compared to all other solutions disturbances. For example; motor loads,
HVAC systems and other linear loads
7 (on a $/kVA basis).
should be separated from the sensitive
The IEEE Emerald book recommends process control and computer systems.
the use of a two-stage protection
8 concept. For large surge currents, The most effective and economic
diversion is best accomplished in solution for protecting a large number
two stages: the first diversion should of loads is to install parallel SPDs at
9 5. Uninterruptible Power Supply
(UPS, Gen. Sets, etc.) be performed at the service entrance the building service entrance feeder
to the building. Then, any residual and panelboard locations. This reduces
4. Harmonic Distortion the cost of protection for multiple
voltage resulting from the action can
10 3. Voltage Regulation be dealt with by a second protective sensitive loads.
2. Surge Protection device at the power panel of the com-
puter room (or other critical loads).
11 1. Grounding

Figure 1.4-10. Power Quality Pyramid Input - high energy


12 TVSS
transient disturbance; IEEE Category
1. Grounding CP
TVSS 20,000 V
C3 Impulse 20,000 V; 10,000 A
480 V 120/208 V
PEAK VOLTAGE

Grounding represents the foundation


13 of a reliable power distribution sys- Computer or Best achievable
Sensitive
tem. Grounding and wiring problems Stage 1 Protection Loads
performance with single TVSS
at main panel (950 V, at Stage 1)
can be the cause of up to 80% of all (Service Entrance) Stage 2 Protection
14 power quality problems. All other (Branch Location)
800 V
forms of power quality solutions are System Test Parameters:
IEEE C62.41[10] and C62.45 [10] 400 V
dependent upon good grounding
15 procedures. test procedures using category; 0
25 uS 50 uS
480 V main entrance panels;
TIME (MICROSECONDS)
100 feet (30 m) of 3-phase wire;
16 480/208 V distribution transformer;
and 208 V branch panel.
Two stage (cascade
approach) achieves best
possible protection (less
= SPD or TVSS than 200 V at Stage 2)
17
Figure 1.4-11. Cascaded Network Protection

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-17
January 2008 System Application Considerations
Sheet 01 073
Power Quality

The recommended system approach ■ Building entrance SPDs protect tion wires, the area between wires is
for installing SPDs is summarized in the facility against large external reduced and the mutual inductance i
Figure 1.4-12. transients, including lightning. affect minimized.
■ SPDs are bi-directional and prevent
transient and noise disturbances
Increasing the diameter of the installation ii
1. wires is of negligible benefit. Induc-
Identify Critical Loads from feeding back within a system tance is a “skin effect” phenomenon and
when installed at distribution or
branch panels.
a function of wire circumference. Since 1
2. only a marginal reduction in inductance
Identify Non-Critical Loads ■ Two levels of protection safeguard is achieved when the diameter of the
sensitive loads from physical
damage or operational upset.
installation conductors is increased, 2
3.
the use of large diameter wire results
Identify Noise and in only minimal improvement (see
Side Mounted SPD vs. Integral SPD
Disturbance Generating Loads
Directly connecting the surge sup-
Figure 1.4-14). 3
presser to the bus bar of electrical Further benefits provided by integrated
4. distribution equipment results in surge suppression designs are the
Review Internal Power Distribution Layout
the best possible level of protection. elimination of field installation costs and
4
Compared to side mounted devices, the amount of expensive “outboard”
5. connecting the SPD unit to the bus wall space taken up by side mounted
Identify Facility Exposure to bar eliminates the need for lead wires SPD devices.
5
Expected Levels of Disturbance
and reduces the let-through voltage
up to 50% (see Figure 1.4-13). Building Entrance Feeder Installation
6. Considerations 6
Apply Mitigating Equipment to: Given that surges are high frequency Installing a SPD device immediately
a) Service Entrance Main Panels disturbances, the inductance of the after the switchgear or switchboard
b) Key Sub-Panels installation wiring increases the main breaker is the optimal location
7
c) Critical Loads
let-through voltage of the protective for protecting against external distur-
d) Data and Communication Lines
device. Figure 1.4-14 shows that bances such as lightning. When placed
for every inch of lead length, the in this location, the disturbance is
8
Figure 1.4-12. System Approach for Installing SPDs let-through voltage is increased by “intercepted” by the SPD and reduced
There may be specific critical loads an additional 15 to 25 V above the to a minimum before reaching the
within a facility that require a higher manufacturers stated suppression distribution and/or branch panel(s).
9
level of protection. A series SPD is best performance.
suited for protecting such loads. The use of a disconnect breaker
Lead length has the greatest effect on eliminates the need to de-energize 10
Advantages of the System Approach are: the actual level of protection realized. the building entrance feeder equip-
Twisting of the installation wires is ment should the SPD fail or require
■ The lowest possible investment the second most important installation 11
in mitigating equipment to protect isolation for Megger testing.
consideration. By twisting the installa-
a facility.
12
208Y/120 Panelboard
(integrated versus side mounted SPD)
13
1000 Side Mounted SPD Device
Side Mounted SPD SPD Integrated
Let-Through Voltage at Bus Bar

(assuming 14-inch (355.6 mm) lead length to bus)


used for Retrofit
Applications
into Panelboards,
Switchboards, MCCs 800 14
600
15
N 400
SPD
SPD
Integrated SPD
(direct bus bar connection)
16
200

GRO UND G RO UND


0 17
Surge
Event
-200
G
G -2.00 0.00 2.00 4.00 6.00 8.00 10.00 18
N
\
Microseconds
19
Figure 1.4-13. Performance Comparison of Side Mounted vs. Integrated SPD

20

21

CA08104001E For more information visit: www.eaton.com


1.4-18 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 074
Power Quality

Reference Section 36 for detailed


i Additional Let-Through Voltage Using IEEE C1(6000V, 3000A)[3] information on SPDs.
Additional Let-Through Voltage ➀

Waveform (UL 1449 Test Wave)[12]


900 14 AWG 3. Voltage Regulation
ii 800
700
209V (23%) 10 AWG
Voltage Regulation (i.e., sags or over-
4 AWG
600
673V (75%) voltage) disturbances are generally
500
site- or load-dependent. A variety of
1 400
mitigating solutions are available
300
200 depending upon the load sensitivity,
100 fault duration/magnitude and the
2 0
specific problems encountered. It is
3 Feet (914.4 mm) 1 Foot (304.8 mm)
Lead Length Lead Length, recommended to install monitoring
equipment on the ac power lines to
3 Loose Wiring Twisted Wires Twisted Wires
assess the degree and frequency of
Figure 1.4-14. The Effect of Installation Lead Length on Let-Through Voltage occurrences of voltage regulation
4  Additional to UL 1449 ratings. problems. The captured data will allow
for the proper solution selection.
The size or capacity of a suppressor is switch is about 50 to 60 V. This increase
5 measured in surge current per phase. in disturbance voltage can result in 4. Harmonics Distortion
Larger suppressors rated at approxi- process disruption and downtime.
mately 250 kA per phase should be Harmonics and Nonlinear Loads
installed at the service entrance to Installing Dataline Surge Protection
6 survive high-energy surges associated Most facilities also have communica-
Until recently, most electrical loads were
linear. Linear loads draw the full sine
with lightning. tion lines that are potential sources wave of electric current at its 60 cycle
for external surges. As identified by
7 A 250 kA per phase surge rating allows the Power Quality Pyramid, proper
(Hz) fundamental frequency — Figure
for over a 25 year life expectancy 1.4-15 shows balance single-phase,
grounding of communication lines is linear loads. As the figure shows,
assuming an IEEE defined high essential for dependable operation.
8 exposure environment. Lower surge NEC Article 800 states that all data,
little or no current flows in the neutral
rating devices may be utilized; how- conductor when the loads are non-
power and cable lines be grounded linear and balanced.
ever, device reliability and long-term and bonded.
9 performance may be compromised. With the arrival of non-linear
Power disturbances such as lightning electronic loads, where the ac voltage
For aerial structures, the 99.8 percen- can elevate the ground potential is converted to a dc voltage, harmon-
10 tile recorded lightning stroke current between two communicating pieces ics are created because of the use
is less than 220 kA. The magnitude of of electronic equipment with different
surges conducted or induced into a of only part of the ac sine wave.
ground references. The result is current In this conversion from ac to dc,
11 facility electrical distribution system is flowing through the data cable causing the electronics are turned on in the
considerably lower given the presence component failure, terminal lock-up,
of multiple paths for the surge to travel 60 cycle wave at a given point in
data corruption and interference. time to obtain the required dc level.
12 along. It is for this reason that IEEE
The utilization of only part of the
C62.41 recommends the C3 (20 kV, NFPA 780 D — 4.8 warns that “surge
10 kA) test wave for testing SPDs suppression devices should be installed sign wave causes harmonics.
13 installed at building entrance feeders. on all wiring entering or leaving elec- It is important to note that the current
tronic equipment, usually power, data distortion caused by loads such as rec-
SPDs with surge ratings greater than or communication wiring.”
250 kA are not required, however, higher tifiers or switch mode power supplies
14 ratings are available and may provide Surge suppressers should be installed causes the voltage distortion. That
longer life. at both ends of a data or communica- voltage distortion is caused by distorted
tion cable. In those situations where currents flowing through an impedance.
15 Installing Panelboard Surge one end of the cable is not connected The amount of voltage distortion
Protection Devices into an electronic circuit (e.g., contactor depends on:
16 Smaller surge capacity SPDs (120 kA coil), protection on the electronic end ■ System impedance.
per phase) are installed at branch pan- only is required.
■ Amount of distorted current.
elboards where power disturbances
To prevent the coupling or inducing of
17 are of lower energy but occur much
more frequently. This level of surge power disturbances into communication
Devices that can cause harmonic dis-
turbances include rectifiers, thrusters
current rating should result in a lines, the following should be avoided:
and switching power supplies, all of
18 greater than 25 year life expectancy. ■ Data cables should not be run over which are non-linear. Further, the pro-
fluorescent lighting fixtures. liferation of electronic equipment such
When isolated ground systems are
■ Data cables should not be in the as computers, UPS systems, variable
used, the SPD should be installed such
19 that any common mode surges are vicinity of electric motors. speed drives, programmable logic
controllers, and the like: non-linear
shunted to the safety ground. ■ The right category cable should
loads have become a significant part
be used to ensure transmission
20 The use of a disconnect breaker is performance.
of many installations. Other types of
optional. The additional let-through harmonic-producing loads include arcing
■ Data cables must be grounded at devices (arc furnaces, fluorescent lights)
voltage resulting from the increased
21 inductance caused by the disconnect both ends when communicating and iron core storable devices (trans-
between buildings. formers, especially during energization).

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-19
January 2008 System Application Considerations
Sheet 01 075
Power Quality

Non-linear load currents vary widely present on the three phases add Harmonic Issues
from a sinusoidal wave shape; often together in the neutral, as shown in
Harmonic currents perform no work
i
they are discontinuous pulses. This Figure 1.4-16, rather than cancel each
means that non-linear loads are other out, as shown in Figure 1.4-15. and result in wasted electrical energy
that may over burden the distribution ii
extremely high in harmonic content. Odd non-triplen harmonics are
system. This electrical overloading
classified as “positive sequence”
Triplen harmonics are the 3rd, 9th, may contribute to preventing an
or “negative sequence” and are the
15th,...harmonics. Further, triplen existing electrical distribution system 1
1st, 5th, 7th, 11th, 13th, etc.
harmonics are the most damaging from serving additional future loads.
to an electrical system because these In general, as the order of a harmonic In general, harmonics present on a dis-
harmonics on the A-phase, B-phase gets higher, its amplitude becomes tribution system can have the following 2
and C-phase are in sequence with each smaller as a percentage of the funda- detrimental effects:
other. Meaning, the triplen harmonics mental frequency.
1. Overheating of transformers and 3
rotating equipment.
60 Hz Fundamental
2. Increased hysteresis losses.
3. Decreased kVA capacity.
4
A Phase
4. Overloading of neutral.
5. Unacceptable neutral-to-ground 5
voltages.

120º
6. Distorted voltage and current 6
waveforms.
Lagging
B Phase
7. Failed capacitor banks.
8. Breakers and fuses tripping.
7
9. Double or ever triple sized neutrals
to defy the negative effects of 8
120º triplen harmonics.
Lagging C Phase
In transformers, generators and uninter- 9
ruptible power supplies (UPS) systems,
harmonics cause overheating and failure
Balance
at loads below their ratings because the 10
harmonic currents cause greater heating
Neutral
Current than standard 60 Hz current. This results
from increased eddy current losses,
hysteresis losses in the iron cores, and
11
Figure 1.4-15. Balanced Neutral Current Equals Zero conductor skin effects of the windings.
In addition, the harmonic currents acting 12
on the impedance of the source cause
60 Hz Fundamental harmonics in the source voltage, which
is then applied to other loads such as 13
3rd Harmonic motors, causing them to overheat.
A Phase
The harmonics also complicate the
application of capacitors for power fac- 14
tor correction. If, at a given harmonic
frequency, the capacitive impedance
120º equals the system reactive impedance, 15
B Phase
Lagging the harmonic voltage and current can
reach dangerous magnitudes. At the
same time the harmonics create prob- 16
lems in the application of power factor
correction capacitors, they lower the
120º C Phase actual power factor. The rotating meters 17
Lagging used by the utilities for watthour and
various measurements do not detect
the distortion component caused by 18
the harmonics. Rectifiers with diode
front ends and large dc side capacitor
Neutral
Triplen
banks have displacement power factor 19
Current
of 90% to 95%. More recent electronic
meters are capable of metering the

Phase Triplen Harmonics true kVA hours taken by the circuit. 20


Added in the Neutral
Single-phase power supplies for com-
puter and fixture ballasts are rich in 21
Figure 1.4-16. Unbalanced Single-Phase Loads with Triplen Harmonics third harmonics and their odd multiples.

CA08104001E For more information visit: www.eaton.com


1.4-20 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 076
Power Quality

Even with the phase currents perfectly Total Harmonic Distortion Table 1.4-6. Current Distortion Limits for
i balanced, the harmonic currents in
Revised standard IEEE 519-1992 indi-
General Distribution Systems (120 V Through
the neutral can total 173% of the 69000 V)
phase current. This has resulted in cates the limits of current distortion
Maximum Harmonic Current Distortion in
ii overheated neutrals. The Information allowed at the PCC (Point of Common
Coupling) point on the system where the
Percent of IL
Technology Industry Council (ITIC) for- Individual Harmonic Order (Odd Harmonics)
merly known as CBEMA, recommends current distortion is calculated, usually
ISC /IL <11 11 17 23 35 TDD
1 that neutrals in the supply to electronic the point of connection to the utility or
<h <h <h <h
equipment be oversized to at least 173% the main supply bus of the system. <17 <23 <35
of the ampacity of the phase conductors The standard also covers the harmonic
2 <20  4.0 2.0 1.5 .6 .3 5.0
to prevent problems. CBEMA also limits of the supply voltage from the 20<50 7.0 3.5 2.5 1.0 .5 8.0
recommends derating transformers, utility or cogenerators. 50<100 10.0 4.5 4.0 1.5 .7 12.0
loading them to no more than 50% to 100<1000 12.0 5.5 5.0 2.0 1.0 15.0
3 70% of their nameplate kVA, based on Table 1.4-4. Low Voltage System Classification >1000 15.0 7.0 6.0 2.5 1.4 20.0
a rule-of-thumb calculation, to com- and Distortion Limits for 480 Volt Systems  All power generation equipment is limited to
pensate for harmonic heating effects. Class C AN DF these values of current distortion,
4 regardless of actual ISC/IL where:
In spite of all the concerns they cause, Special Application  10 16,400 3% ISC = Maximum short circuit current at PCC.
non-linear loads will continue to General System 5 22,800 5% IL = Maximum demand load current (funda-
5 increase. Therefore, the design of Dedicated System

2 36,500 10% mental frequency component) at PCC.
TDD = Total Demand Distortion. Even
non-linear loads and the systems that Special systems are those where the rate
of change of voltage of the notch might harmonics are limited to 25% of the odd
supply them will have to be designed harmonic limits above. Current distortions
6 so that their adverse effects are greatly mistrigger an event. AN is a measurement
of notch characteristics measured in volt-
that result in a dc offset, e.g., half-wave
reduced. Table 1.4-3 shows the typical converters, are not allowed.
microseconds, C is the impedance ratio of
harmonic orders from a variety of total impedance to impedance at common
7 harmonic generating sources. point in system. DF is distortion factor. Harmonic Solutions
In spite of all the concerns non-linear
Table 1.4-3. Source and Typical Harmonics Table 1.4-5. Utility or Cogenerator Supply loads cause, these loads will continue
8 Source Typical
Harmonics 
Voltage Harmonic Limits to increase. Therefore, the design
Voltage 2.3-69 kV 69-138 kV >138 kV of non-linear loads and the systems
6 Pulse Rectifier 5, 7, 11, 13, 17, 19… Range that supply them will need design so
9 12 Pulse Rectifier 11, 13, 23, 25…
Maximum 3.0% 1.5% 1.0%
adverse harmonic effects are greatly
18 Pulse Rectifier 17, 19, 35, 37… reduced. Table 1.4-7 and depicts many
Individual
Switch-Mode Power Harmonic harmonic solutions along with their
10 Supply 3, 5, 7, 9, 11, 13…
Total 5.0% 2.5% 1.5% advantages and disadvantages.
Fluorescent Lights 3, 5, 7, 9, 11, 13…
Harmonic
Arcing Devices 2, 3, 4, 5, 7…
Distortion
Transformer Energization 2, 3, 4
11  Generally, magnitude decreases as harmonic
order increases. V
Percentages are −−−h x 100 for each
12 harmonic V1

and
13
h = hmax 1/2

14 Vthd = ∑ 2
Vh
h=2
It is important for the system designer
15 to know the harmonic content of the
utility’s supply voltage because it will
affect the harmonic distortion of
16 the system.

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-21
January 2008 System Application Considerations
Sheet 01 077
Power Quality

Table 1.4-7. Harmonic Solutions for Given Loads


Load Solutions Advantages Disadvantages i
Type

Drives and Rectifiers —


Includes 3-Phase
Line Reactors ■ Inexpensive. ■ May require additional compensation. ii
■ For 6-pulse standard drive/rectifier, can
UPS Loads reduce harmonic current distortion from
80% down to about 35 – 40%.
K-Rated/Drive Isolation ■ Offers series reactance (similar to line ■ No advantage over reactors for
1
Transformer reactors) and provides isolation for reducing harmonics unless in pairs
some transients. for shifting phases.
dc Choke ■ Slightly better than ac line reactors ■ Not always an option for drives.
2
for 5th and 7th harmonics. ■ Less protection for input semiconductors.
12-Pulse Convertor ■ 85% reduction versus standard
6-pulse drives.
■ Cost difference approaches 18-pulse drive
and blocking filters, which guarantee
3
IEEE 519 compliance.
Harmonic Mitigating ■ Substantial (50% – 80%) reduction in ■ Harmonic cancellation highly dependent
Transformers/Phase Shifting harmonics when used in tandem. on load balance. 4
■ Must have even multiples of
matched loads.
Tuned Filters ■ Bus connected — accommodates ■ Requires allocation analysis. 5
load diversity. ■ Sized only to the requirements of that system.
■ Provides PF correction. Must be resized if system changes.
Broadband Filters ■ Makes 6-pulse into the equivalent ■ Higher cost. 6
of 18-pulse. ■ Requires one filter per drive.
18-Pulse Converter ■ Excellent harmonic control for drives ■ High cost.
above 100 hp. 7
■ IEEE 519 compliant.
Active Filters ■ Handles load/harmonic diversity. ■ High cost.
■ Complete solution up to 50th harmonic. 8
Computers/ Neutral Blocking Filter ■ Eliminates the 3rd harmonic from load. ■ High cost.
Switch-Mode ■ Relieves system capacity. ■ May increase voltage distortion.
Power Supplies ■ Possible energy savings.
9
Harmonic Mitigating ■ 3rd harmonic recalculated back to the load. ■ Requires fully rated circuits and
Transformers ■ When used as phase-shifted transformers, oversized neutrals to the loads.
reduces other harmonics. 10
■ Reduces voltage “flat-topping”.
Oversized Neutral/Derated ■ Tolerate harmonics rather than correct. ■ Upstream and downstream equipment
Transformer ■ Typically least expensive. fully rated for harmonics. 11
K-Rated Transformer ■ Tolerate harmonics rather than correct. ■ Does not reduce system harmonics.
Fluorescent
Lighting
Harmonic Mitigating
Transformers
■ 3rd harmonic recalculated back to the load. ■ Requires fully rated circuits and
oversized neutrals to the loads.
12
■ When used as phase-shifted transformers,
reduces other harmonics.
■ Reduces voltage “flat-topping”.
K-Rated Transformer ■ Tolerate harmonics rather than correct them. ■ Does not reduce system harmonics.
13
Low Distortion Ballasts ■ Reduce harmonics at the source. ■ Additional cost and typically more
expensive than “system” solutions. 14
Welding/Arcing Active Filters ■ Fast response and broadband ■ High cost.
Loads harmonic correction.
■ Reduces voltage flicker. 15
Tuned Filters ■ SCR controlled tuned filters simulates ■ SCR controlled units are high cost
an active filter response. but fixed filters are reasonable.
System Tuned Filters ■ Provides PF correction. ■ System analysis required to verify application. 16
Solutions ■ Lower cost compared to other systems. Must be resized if system changes.
Harmonic Mitigating ■ Excellent choice for new design ■ No PF correction benefit.
Transformers or upgrade. 17
Active Filters ■ Ideal solution and ■ Highest cost.
handles system diversity.
18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.4-22 Power Distribution Systems
Uninterruptible Power Systems (UPS) January 2008
Sheet 01 078

5. Uninterruptible Power The normal power source supplied by Uninterruptible Power Supply (UPS)
i Systems (UPS) the local utility or provider is not stable systems have evolved to serve the
enough over time to continuously needs of sensitive equipment and
The advent of solid-state semiconduc- serve these loads without interruption. can supply a stable source of electrical
ii tors over 40 years ago, and their It is possible that a facility outside a power, or switch to backup to allow
subsequent evolution to transistors, major metropolitan area served by the for an orderly shutdown of the loads
and the miniaturization of electronics utility grid will experience outages of without appreciable loss of data or
1 into microprocessor over 25 years ago, some nature 15 – 20 times in one year. process. In the early days of main-
has created numerous computation Certain outages are caused by the frame computers, motor-generator
machines that assist us in every con- weather, and others by the failure sets provide isolation and clean power
2 ceivable manner. These machines, of the utility supply system due to to the computers. They did not have
and their clever configurations, equipment failures or construction deep reserves, but provided extensive
whether they take the form of comput- interruptions. Some outages are ride-through capability while other
3 ers, appliance controls, fax machines, only several cycles in duration, while sources of power (usually standby
phone systems, computers of all others may be for hours at a time. emergency engine generator sets)
sizes, server systems and server were brought to bear to serve the
4 farms, emergency call centers, data In a broader sense, other problems motor-generator sets while the
processing at banks, credit companies, exist in the area of power quality, and normal source of power was
private company communication net- many of those issues also contribute unstable or unavailable.
5 works, government institutions, and to the failure of the supply to provide
defense agencies all rely on a narrow that narrow range of power to the UPS systems have evolved along the
range of nominal ac power in order for sensitive loads mentioned above. lines of rotary types and static types of
6 these devices to work properly. Power Quality problems take the systems, and they come in many con-
Indeed, many other types of equip- form of any of the following: power figurations, and even hybrid designs
ment also require that the ac electrical failure, power sag, power surge, having characteristics of both types.
7 power source be at or close to nominal undervoltage, overvoltage, line noise, The discussion that follows attempts
voltage and frequency. Disturbances frequency variations, switching to compare and contrast the two
of the power translate into failed transients, and harmonic distortion. types of UPS systems, and give basic
8 processes, lost data, decreased Regardless of the reason for outages guidance on selection criteria. This
efficiency and lost revenue. and power quality problems, the sensi- discussion will focus on the medium,
tive loads can not function normally large and very large UPS systems
9 without a backup power source and in required by users who need more
many cases the loads must be isolated than 10 kVA of clean reliable power.
from the instabilities of the utility sup-
10 ply and power quality problems and
given clean reliable power on a contin-
uous basis, or be able to switch over to
11 reliable clean electrical power quickly.

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-23
January 2008 Uninterruptible Power Systems (UPS)
Sheet 01 079

Power Ratings of UPS Systems low rotational speeds. These legacy system checks are performed then
■ Small UPS: Typically 300 VA to 10 kVA,
types of hybrid UPS systems are not the input Contactor is closed. The i
the focus of this discussion, since only Static Disconnect Switch is turned on
and sometimes as high as 18 kVA one or two vendors offer these hybrid and the conduction angle is rapidly
■ Medium UPS: 10 kVA to 60 kVA types of rotary UPS systems, although increased from zero to an angle that ii
■ Large UPS: 100 kVA to 200 kVA admittedly they continue to be used in causes the dc bus voltage between
units, and higher when units are very large-scale data center applica- the Utility Converter and the Flywheel
paralleled tions. See Figure 1.4-17 for the modern Converter to reach approximately 650 1
■ Very Large UPS: 200 kVA to 750 kVA high speed Rotary UPS systems volts through the rectifying action of
units, and higher when units are discussed in this section of the guide. the freewheeling diodes in the Utility
paralleled These types of modern Rotary UPS Converter. As soon as this level of dc 2
systems are advanced, integrated voltage is reached the Static Discon-
Each of these categories is arbitrary designs utilizing scalable configura- nect turns on fully. The next steps
because manufacturers have many tions of high-speed flywheel, motor involved the Utility Converter IGBTs to 3
different UPS offerings for the same and generator in one compact UPS start firing which allows the converter
application. The choice of UPS type package. The new rotary technologies to act as a Rectifier, a regulating volt-
and the configuration of UPS modules have the potential to replace battery age source and an active harmonic 4
for a given application depends upon backup systems, or at least reduce filter. As the IGBTs begin to operate,
many factors, including how many the battery content for certain applica- the dc bus is increased to a normal
Power Quality problems the UPS is tions. The appeal of rotary systems is operating voltage of approximately 5
expected to solve, how much future the avoidance of the purchase, mainte- 800 volts, and the output bus is trans-
capacity is to be purchased now for nance, and facility space required by ferred from Bypass to the output of
future loads, the nature of the sensi- dc battery based backup systems. the power electronics module. The 6
tive loads and load wiring, which transfer from Bypass is completed
type of UPS system is favored, rotary High Speed Rotary when the Output Contactor is closed
or static, choices of battery or dc
Concept of Operation and the Bypass Contactor opened in 7
storage technology considered, and a make-before-break manner.
a host of other application issues. The modern Rotary type of UPS
operation is understood by reviewing The firing of the SCRs in the Static 8
Rotary UPS Systems the four topics below: Startup Mode, Disconnect Switch is now changed so
Normal Operation Mode, Discharge that each SCR in each phase is only
Typical Ratings Mode, and Recharge Mode. turned on during the half-cycle, which 9
300 kVA – 900 kVA/720 kW maximum permits real power to flow from the
Startup Mode utility supply to the UPS. This firing
Typical Rotary Configurations The UPS output is energized on pattern at the Static Disconnect Switch 10
Rotary UPS systems are among the Bypass as soon as power is applied prevents power from the Flywheel
oldest working systems developed from the Source to the system input. from feeding backwards into the
to protect sensitive loads. Many of The UPS continues the startup proce- utility supply and assures that all of 11
these systems are complicated engine- dure automatically when the front the Flywheel energy is available to
generator sets coupled with high iner- panel controls are placed into the support the Load.
tial flywheels operated at relatively “Online” position. Internal UPS 12

Static Bypass Option


13
It = Input Current
Ir = Real Load Current
Ic = Charging Current
14
Ig = Voltage Regulation Current
Bypass Contactor
15
It = Ir + Ic + Ig Id = Ih + Ix + Ir
Input Static Disconnect
Output
Contactor Switch Line Inductor
Contactor 16
Source Load

Flywheel Converter Utility Converter Ic Inverter


Output Transformer
17
Fuse

Ix
Field Coil ac dc Filter Inductor Ig Id = Output Current 18
Ih = Harmonic Current
Driver dc ac Ix = Reactive Load Current
Ir = Real Load Current 19
Ih
Integrated Motor/Flywheel/
and Generator 20
Figure 1.4-17. Typical High Speed Modern Rotary UPS 21

CA08104001E For more information visit: www.eaton.com


1.4-24 Power Distribution Systems
Uninterruptible Power Systems (UPS) January 2008
Sheet 01 080

Immediately after the output is trans- output voltage. full charge in the Normal Operation
i ferred from Bypass to the power elec- Mode, however the IGBT gating points
tronic module, the Flywheel Field is The Load current consists of three are changed to increase current into
excited which also provides magnetic components: the harmonic current the Flywheel.
ii lift to unload the Flywheel bearings.
The Flywheel Inverter is turned on
required by the load, the reactive load
current, and the real current, which High Speed Rotary Advantages
and gradually increases frequency does the work. The Utility Converter
at a constant rate to accelerate the ■ Addresses all power quality
1 Flywheel to approximately 60 RPM.
supplies both the harmonic and reac- problems.
Once the Flywheel reached 60 RPM, tive currents. Since these currents sup-
■ Battery systems are not required
the Flywheel Inverter controls the ply no net power to the load, the
or used.
2 acceleration to keep currents below Flywheel supplies no energy for
■ No battery maintenance required.
the maximum charging and the these currents. They circulate between
maximum input settings. Once the the Utility Converter and the Load. ■ Unlimited discharge cycles.
3 Flywheel reaches 4000 RPM, the
UPS is fully functional and capable of
The power stage controls analyze ■ 150 second recharge time available.
the harmonic current requirements ■ Wide range of operating
supporting the Load during a power of the load and set the firing angle of
quality event. Flywheel acceleration temperatures can be accommo-
4 continues until the Flywheel reaches
the inverter IGBTs to make the Utility dated (-20 to 40 degrees C).
“full charge” at 7,700 RPM. The Converter a very low impedance
■ Small compact size and less floor
total time to complete startup is less source to any harmonic currents.
space required (500 kW systems
5 than 5 minutes. Thus, non-linear load currents are
takes 20 sq.ft.).
supplied almost entirely from the
Normal Operation Mode Utility Converter with little effect on ■ N+1 reliability available up to 900
6 Once the UPS is started and the Fly- the quality of the UPS output voltage kVA maximum.
wheel is operating at greater than waveform and with almost no trans- ■ No disposal issues.
4,000 RPM, the UPS is in the Normal mission of load harmonics currents
High Speed Rotary Disadvantages
7 Operating Mode where it is regulating to the input of the UPS.
output voltage and supplying reactive ■ Flywheel does not have deep
and harmonic currents required by the Discharge Mode reserve capacity — rides through
8 Load. At the same time it cancels the The UPS senses the deviation of for up to 13 seconds at 100% load.
effect of load current harmonics on the the voltage or frequency beyond pro- ■ Some enhanced flywheel systems
UPS output voltage. grammed tolerances and quickly dis- may extend the ride through to 30
9 Input current consists of three compo-
connects the supply source by turning seconds at 100% load.
off the Static Disconnect Switch and ■ Mechanical flywheel maintenance
nents: real load current, charging cur- opening the Input Contactor. The dis-
rent, and voltage regulation current. required every 2 – 3 years, and oil
10 Real current is current that is in phase
connect occurs in less than one-half changes required every year.
cycle. Then the Utility Converter starts
with the supply voltage and supplies delivering power from the dc bus to ■ Recharge fast rates require the
real power to the Load. Real current input to be sized for 125% of
11 flowing through the line inductor
the Load, and the Flywheel Converter
nominal current.
changes the firing point of its IGBTs
causes a slight phase shift of the cur- to deliver power to the dc bus. The ■ Flywheels failures in field not
12 rent lagging the voltage by 10 degrees UPS maintains a clean output voltage understood.
and ensures that the UPS can quickly within 3% or nominal voltage to the ■ Requires vacuum pumps for
transfer to Bypass without causing Load when input power is lost. high speed flywheels.
13 unacceptable switching transients. The
■ Limited number of vendors and
second component is charging current Recharge Mode
experience.
required by the Flywheel to keep the When input power is restored to
14 rotating mass fully charged at rated
RPM, or to recharge the rotating mass
acceptable limits, the UPS synchro-
nizes the output and input voltages,
after a discharge. The power to main- closes the Input Contactor and turns
15 tain full charge is low at 2 kW and on the Static Disconnect Switch. The
is accomplished by the IGBTs of the Utility Converter then transfers power
Flywheel Converter gating to provide from the Flywheel to the input source
16 small pulses of motoring current to the by linearly increasing the real input
Flywheel. This current can be much current. The transfer time is program-
higher if fast recharge times are mable from 1 to 15 seconds. As soon
17 selected. The final component of as the load power is completely trans-
input current is the voltage regulation ferred to the input source, the Utility
current, which is usually a reactive cur- Converter and Flywheel Converter
18 rent that circulates between the input start to recharge the Flywheel and
and the Utility Converter to regulate return to Normal Operation Mode. The
the output voltage. Leading reactive Flywheel recharge power is program-
19 current causes a voltage boost across mable between a slow and fast rate,
the line inductor, and a lagging current and using the fast rate results in an
causes a bucking voltage. By control- increase of UPS input current over
20 ling the Utility Converter to maintain nominal levels. Recharging the Fly-
nominal output voltage, just enough wheel is accomplished by controlling
reactive current flows through the line the Utility and Flywheel Converter in a
21 inductor to make up the difference similar manner as is used to maintain
between the input voltage and the

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-25
January 2008 Uninterruptible Power Systems (UPS)
Sheet 01 081

Static UPS Systems 2. The Rectifier/Charger function When the UPS recognizes a
converts the normal ac power to requirement to transfer to the i
Typical Ratings dc power to charge the Battery Bypass mode it simultaneously
40 kVA – 750 kVA/600 kW, and higher and power the Inverter. The Load turns the Static Switch ON, the
when multiple units are paralleled is isolated from the normal input Output Breaker to OPEN, and the ii
Source. Bypass Breaker to CLOSE. The
Typical Static UPS Configurations Output Breaker opens and the
Static UPS systems modules are avail-
3. The Battery stores dc energy Bypass Breaker closes in about 50 1
for use when input power to the milliseconds. The restoration of
able in three basic types configurations
UPS fails. The amount of power normal conditions at the UPS
known as Standby, Line Interactive, and
Double Conversion. See the Section 41
available from the dc Battery results in the automatic restora- 2
system and time to discharge tion of the UPS module powering
in this guide for details on all the UPS
voltage is a function of the type of the Load through the Rectifier/
configurations available from Eaton.
The lighter power ratings are likely to
Battery selected and the ampere- Charger and Inverter with Load 3
hour sized used. Battery systems isolation from power quality
be one of the first two types configura-
should be sized for no less than problems, and the opening of the
tions,e.g. Standby or Line Interactive.
Most medium or large static UPS instal-
5 minutes of clean power usage Bypass circuit. 4
from a fully charged state, and in
lations use the Double Conversion
many cases are sized to provide Static Double Conversion Advantages
technology in one or multiple module
configurations configuration, i.e. or
more time on Battery power. ■ Addresses all power quality 5
multiple UPS units in parallel, and 4. The dc link connects the output of problems.
that will be the primary focus of our the Rectifier/Charger to the input ■ Suitable for applications from 5 kVA
discussion. Figure 1.4-18 illustrates the of the Inverter and to the Battery. to over 2500 kVA. 6
one-line diagram of a simple single Typically the Rectifier/Charger is ■ Simple battery systems are
Double Conversion UPS module. Brief sized slightly higher than 100% of sized for application.
explanations appear for the Standby UPS output since it must power
7
■ Long battery backup times and long
and Line Interactive UPS systems the Inverter and supply charger life batteries are available.
after the text explaining the Double power to the Battery.
Conversion static UPS type of system. ■ Higher reliability is available 8
5. The Bypass circuit provides a path using redundant UPS modules.
A. Double Conversion Concept of for unregulated normal power to
Operation — The basic operation be routed around the major elec- 9
of the Double Conversion UPS is: tronic sub-assemblies of the UPS
to the Load so that the Load can
1. Normal power is connected to
continue to operate during main- 10
the UPS input through the facility
tenance, or when the UPS elec-
electrical distribution system.
tronics fails. The Bypass Static
This usually involves two input
Switch can switch to conducting 11
circuits that must come from the
mode in 150 – 120 milliseconds.
same Source.
12

Bypass Breaker (Optional) UPS Module 13

Bypass Static Switch 14


Source Load
Normal Rectifier/Charger
Inverter
Output 15
Breaker Breaker
ac dc
dc ac 16
Battery Breaker
17
Battery

18
Figure 1.4-18. Typical Static UPS, Double Conversion Type with Battery Backup
19

20

21

CA08104001E For more information visit: www.eaton.com


1.4-26 Power Distribution Systems
Uninterruptible Power Systems (UPS) January 2008
Sheet 01 082

Static Double Conversion Disadvantages 3. The Battery stores dc energy for C. Static Line Interactive UPS
i ■ Battery systems, battery maintenance, use by the Inverter when input Concept of Operation — The basic
and battery replacement are required. power to the UPS fails. The operation of the Line Interactive
amount of power available from UPS is:
■ Large space requirement for
ii battery systems (higher life takes
the dc Battery system and time to
discharge voltage is a function of 1. The Line Interactive type of UPS
more space, e.g., 500 kW takes 80 has a different topology than the
the type of Battery selected and
1 to 200 sq.ft. depending upon the Static Double Conversion and
the ampere-hour sized used.
type of battery used, VRLA 10 year, Standby systems. The normal
Battery systems should be sized
VRLA 20 year or flooded). input power is connected to the
for the anticipated outage.
2 ■ Limited discharge cycles of battery Load in Parallel with a Battery
system. 4. The dc link connects the output of and bi-directional Inverter/Charger
■ Narrow temperature range for the Rectifier/Charger to the input assembly. The input source usu-
3 application. of the Inverter and to the Battery. ally terminates at a line inductor
Typically the Rectifier/Charger and the output of the inductor is
■ Efficiencies are in the 90 – 94%
is sized only to supply charger connected to the Load in parallel
range, which is lower than some
4 line interactive configurations.
power to the Battery, and is with the Battery and Inverter/
rated far lower than in the Charger circuit. See Figure 1.4-20
■ Bypass mode places load at risk Double Conversion UPS. for further details.
unless bypass has UPS backup.
5 5. The Bypass circuit provides a 2. The traditional Rectifier circuit
■ Redundancy of UPS modules
results in higher costs. direct connection of input source is eliminated and this results in
to the Load. The Load operates a smaller footprint and weight
6 ■ Output faults are cleared by the
from unregulated power. The reduction. However, line condi-
bypass circuit.
Bypass Static Switch can switch tioning is compromised.
■ Output rating of the UPS is 150% to non-conducting mode in 150 –
7 for 30 seconds. 120 milliseconds. When the UPS 3. When the input power fails, the
■ Battery disposal and safety recognizes the loss of normal Battery/Inverter Charger circuit
issues exist. input power it transfers to Battery / reverses power and supplies the
8 Inverter mode by simultaneously Load with regulated power.
B. Standby UPS Concept of
turning the Inverter ON and the Static Line Interactive UPS Advantages
Operation — The basic operation
9 Static Switch OFF.
of the Standby UPS is: ■ Slight improvement of power condi-
Static Standby UPS Advantages tioning over Standby UPS systems.
1. The Standby UPS topology is
■ Lower costs than double conversion. ■ Small footprints and weights.
10 similar to the Double Conversion
■ Efficient design.
type, but the operation of the UPS ■ Rectifier and charger are
is different in significant ways. economically sized. ■ Batteries are sized for the
11 Normal power is connected to ■ Efficient design. application.
the UPS input through the facility ■ Batteries are sized for the
electrical distribution system. This Static Line Interactive UPS Disadvantages
application.
12 usually involves two input circuits ■ Impractical over 5 kVA.
that must come from the same Static Standby UPS Disadvantages ■ Not as good conditioning as
Source. See Figure 1.4-19 for ■ Impractical over 2 kVA. double conversion.
13 details.
■ Little to no isolation of load from ■ Standby power is from battery alone.
2. The Rectifier/Charger function power quality disturbances. ■ Battery systems, battery mainte-
converts the normal ac power to ■ Standby power is from battery nance, and battery replacement are
14 dc power to charge the Battery alone. required.
only and does not simultaneously ■ Battery systems, battery mainte- ■ Limited discharge cycles for the
power the Inverter. The Load is battery system.
15 connected to the input source
nance, and battery replacement
are required. ■ Narrow temperature range for
through the Bypass static switch. application.
■ Limited discharge cycles of
The Inverter is in the standby
16 mode ready to serve the load
battery system. ■ Battery disposal and safety
■ Narrow temperature range for issues exist.
from Battery power if the input
power source fails. application.
17 ■ Output faults are cleared by the
bypass circuit.
18 ■ Battery disposal and safety
issues exist.

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-27
January 2008 Uninterruptible Power Systems (UPS)
Sheet 01 083

UPS Module
i

Bypass Static Switch


ii

2
Source Load
Rectifier/
Normal
Breaker
Charger Inverter Output
Breaker
3
ac dc
4
dc ac
Battery
Breaker 5
Battery 6

7
Figure 1.4-19. Typical Static UPS, Standby Type with Battery Backup

8
UPS Module
9

Source Load
10
Inductor
11

Bidirectional 12
Inverter/Charger

dc
13
ac
14

15
Battery

16
Figure 1.4-20. Typical Static UPS, Line Interactive Type with Battery Backup
17

18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.4-28 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 084
Other Application Considerations

Secondary Voltage Technical Factors loads are supplied from a 480-volt sys-
i The choice between 208Y/120 V and The principal advantage of the use of tem through step-down transformers,
higher secondary voltages in buildings voltage drop in the 480-volt supply
480Y/277 V secondary distribution for conductors can be compensated for by
is that for a given load, less current
ii commercial and institutional buildings
depends on several factors. The most means smaller conductors and lower the tap adjustments on the transformer,
voltage drop. Also, a given conductor resulting in full 120-volt output. Since
important of these are size and types these transformers are usually located
size can supply a large load at the
1 of loads (motors, fluorescent lighting,
same voltage drop in volts, but a lower close to the 120-volt loads, secondary
incandescent lighting, receptacles) voltage drop should not be a problem.
and length of feeders. In general, large percentage voltage drop because of
the higher supply voltage. Fewer or If it is, taps may be used to compensate
2 motor and fluorescent lighting loads,
smaller circuits can be used to transmit by raising the voltage at the transformer.
and long feeders, will tend to make the
higher voltages, such as 480Y/277 V, the power from the service entrance The interrupting ratings of circuit
point to the final distribution points.
3 more economical. Very large loads and
Smaller conductors can be used in many
breakers and fuses at 480 volts have
long runs would indicate the use of increased considerably in recent years,
medium voltage distribution and load- branch circuits supplying power loads, and protective devices are now available
and a reduction in the number of light-
4 center unit substations close to the
ing branch circuits is usually possible.
for any required fault duty at 480 volts.
loads. Conversely, small loads, short In addition, many of these protective
runs, and a high percentage of incan- It is easier to keep voltage drops within devices are current limiting, and can
5 descent lighting would favor lower acceptable limits on 480-volt circuits be used to protect downstream equip-
utilization voltages such as 208Y/120 V. than on 208-volt circuits. When 120-volt ment against these high fault currents.
Industrial installations, with large
6 motor loads, are almost always 480 V,
often ungrounded delta or resistance
grounded delta or wye systems (see
7 section on ground fault protection). Elevator
Panel
Practical Factors
8 Since most low voltage distribution
T
Typical

equipment available is rated for up to


Emergency
600 volts, and conductors are insulated Typical
9 for 600 volts, the installation of 480-volt
HVAC
V
Panel
Lighting Panel
(Typical
T Every
systems uses the same techniques and Third Floor)
is essentially no more difficult, costly,
10 or hazardous than for 208-volt systems. 480Y/277 208Y/120 V T
Typical
The major difference is that an arc of Panel Panel
120 volts to ground tends to be self- Dry Ty
11 extinguishing, while an arc of 277 volts
480∆-208Y/120 V
(Typical
T Every Floor)
to ground tends to be self-sustaining HVAC
V Busway Emergency Elevator
and likely to cause severe damage. Feeder Riser Lighting
12 For this reason, the National Electrical Riser
Riser

Code requires ground fault protection of


equipment on grounded wye services
13 of more than 150 volts to ground but not
Building and
Miscellaneous
T
Typical Typical

Loads
exceeding 600 volts phase-to-phase T
Typica l
(for practical purpose, 480Y/277 V ser-
14 vices), for any service disconnecting T
Typical Typical
means rated 1000 amperes or more. Spare

15 The National Electrical Code permits


voltage up to 300 volts to ground on ➀ ➀ ➀ ➀ ➀ ➀ ➀
circuits supplying permanently installed
16 electric discharge lamp fixtures, provided Automatic
the luminaires do not have an integral ➀
4000 A
T
Transfer Switch
Main CB
manual switch and are mounted at Gen. CB
Emergency
17 least 8 feet (2.4 m) above the floor. CTs
T
Utility
or Standby
g
This permits a 3-phase, 4-wire, solidly s Generator
grounded 480Y/277-volt system to Utility V
Service 100,000 A Available
A Fault Current
18 supply directly all of the fluorescent
and high-intensity discharge (HID)
lighting in a building at 277 volts, as Figure 1.4-21. Typical Power Distribution and Riser Diagram for a Commercial Office Building
19 well as motors at 480 volts.  Include ground fault trip.

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-29
January 2008 System Application Considerations
Sheet 01 085
Other Application Considerations

Economic Factors Motors and controls are another cause rise, with no more than 80°C (or some-
Utilization equipment suitable for of wasted energy that can be reduced. times 115°C) average winding temper- i
principal loads in most buildings is New, energy efficient motor designs ature rise at full load. A better method
available for either 480-volt or 208-volt are available using more and better would be to evaluate transformer
systems. 3-phase motors and their core steel, and larger windings. losses, based on actual loading cycles ii
controls can be obtained for either throughout the day, and consider the
For any motor operating 10 or more cost of losses as well as the initial cost
voltage, and for a given horsepower
are less costly at 480 volts. Fluorescent
hours per day, it is recommended to of the transformers in purchasing. 1
use the energy-efficient types. These
and HID lamps can be used with either motors have a premium cost of about NEMA standard TP-1 is being adopted
277- or 120-volt ballasts. However, in
almost all cases, the installed equip-
20% more than standard motors. by many states and is another method 2
Depending on loading, hours of use, of energy efficient design. NEMA TP-1
ment will have a lower total cost at the and the cost of energy, the additional establishes minimum operating effi-
higher voltage. initial cost could be repaid in energy ciencies for each distribution trans- 3
saved within a few months, and it former size at a loading equal to 35% of
Energy Conservation rarely takes more than two years. the transformer full load kVA. The 35%
Because of the greatly increased cost Since, over the life of a motor, the cost loading value in the NEMA standard 4
of electrical power, designers must of energy to operate it is many times reflects field studies conducted by the
consider the efficiency of electrical the cost of the motor itself, any motor U.S. Department of Energy which showed
distribution systems, and design for with many hours of use should be of that dry-type transformers installed in 5
energy conservation. In the past, espe- the energy-efficient type. commercial facilities are typically
cially in commercial buildings, design loaded at an average of 35% of their
Where a motor drives a load with
was for lowest first cost, because
variable output requirements such
full load capacity over a 24 hour time 6
energy was inexpensive. Today, even period. Table 1.4-8 compares losses for
in the speculative office building, as a centrifugal pump or a large fan, both low temperature rise and TP-1
customary practice has been to run the
operating costs are so high that
motor at constant speed, and to throttle
transformers using a 75 kVA design. 7
energy-conserving designs can justify
their higher initial cost with a rapid the pump output or use inlet vanes or Table 1.4-8. Load Losses
payback and continuing savings. outlet dampers on the fan. This is highly Temp. Load Losses in Watts 8
Buildings that must meet LEED certifi- inefficient and wasteful of energy. In Rise ºC No 25% 35% 50% 75% Full
cations may require energy saving recent years, solid-state variable- Loss Load Load Load Load Load
designs. There are four major sources frequency, variable-speed drives for 9
ordinary induction motors have been 150 360 490 620 885 1,535 2,450
of energy conservation in a commercial
building — the lighting system, the available, reliable, and relatively inex- 115 420 480 610 805 1,170 1,950
motors and controls, the transformers, pensive. Using a variable-speed drive, 80 500 535 615 730 945 1,410 10
and the HVAC system. the throttling valves or inlet vanes or TP-1 230 310 480 745 1,235 2,280
output dampers can be eliminated, 150
The lighting system must take advan- saving their initial cost, and energy will 11
tage of the newest equipment and be saved over the life of the system. HVAC systems have traditionally been
techniques. New light sources, familiar An additional benefit of both energy- very wasteful of energy, often being
light sources with higher efficiencies, efficient motors and variable-speed designed for lowest first cost. This, 12
solid-state ballasts with dimming con- drives (when operated at less than full too, is changing. For example, reheat
trols, use of daylight, environmental speed) is that the motors operate at systems are being replaced by variable
design, efficient luminaires, computer- reduced temperatures, resulting in air volume systems, resulting in equal 13
ized or programmed control, and the increased motor life. comfort with substantial increases in
like, are some of the methods that efficiency. While the electrical engineer
Transformers have inherent losses.
can increase the efficiency of lighting
Transformers, like motors, are designed
has little influence on the design of the 14
systems. They add up to providing the HVAC system, he/she can specify that
necessary amount of light, with the for lower losses by using more and
all motors with continuous or long duty
better core materials, larger conductors,
desired color rendition, from the most
etc., and this results in increased initial
cycles are specified as energy efficient 15
efficient sources, where and when it is types, and that the variable-air-volume
needed, and not providing light where cost. Since the 480-volt to 208Y/120-volt
fans do not use inlet vanes or outlet
stepdown transformers in an office
or when it is not necessary. Using the
building are usually energized 24 hours
dampers, but are driven by variable- 16
best of techniques, office spaces that speed drives. Variable-speed drives
originally required as much as 3.5 a day, savings from lower losses can
can often be desirable on centrifugal
be substantial, and should be consid-
watts per square foot have been given
ered in all transformer specifications.
compressor units as well. Since some 17
improved lighting, with less glare and of these requirements will be in HVAC
higher visual comfort, using as little as One method of obtaining reduced
specifications, it is important for the
losses is to specify transformers with
1.0 to 2.0 watts per square foot. In an
220°C insulation systems designed for
energy-conscious electrical engineer 18
office building of 200,000 square feet to work closely with the HVAC engineer
(60,960 m), this could mean a saving of 150°C average winding temperature
at the design stage.
400 kW, which, at $.05 per kWh, 250 days 19
per year, 10 hours per day, could save
$50,000 per year in energy costs. Obvi-
ously, efficient lighting is a necessity. 20

21

CA08104001E For more information visit: www.eaton.com


1.4-30 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 086
Other Application Considerations

Building Control Systems Because building design and control One reason is that most cogenerators
i In order to obtain the maximum benefit
for maximum energy saving is impor- are connected to feeders serving other
tant and complex, and frequently customers. Utilities desire to reclose
from these energy-saving lighting, involves many functions and several the feeder after a transient fault is
ii power, and HVAC systems, they must
be controlled to perform their functions
systems, it is necessary for the design cleared. Reclosing in most cases will
engineer to make a thorough building damage the cogenerator if it had
most efficiently. Constant monitoring and environmental study, and to remained connected to their system.
1 would be required for manual operation,
so some form of automatic control is
weigh the costs and advantages of
many systems. The result of good Islanding is another reason why the
required. The simplest of these design can be economical, efficient utility insists on the disconnection of
2 energy-saving controls, often very operation. Poor design can be wasteful, the cogenerator. Islanding is the event
effective, is a time clock to turn various and extremely costly. that after a fault in the utility’s system
systems on and off. Where flexible is cleared by the operation of the
3 control is required, programmable Cogeneration protective devices, a part of the
controllers may be used. These range system may continue to be supplied
from simple devices, similar to multi- Cogeneration is another outgrowth of by cogeneration. Such a condition is
4 function time clocks, up to full micro- the high cost of energy. Cogeneration dangerous to the utility’s operation
processor-based, fully programmable is the production of electric power during restoration work.
devices, really small computers. For concurrently with the production of
steam, hot water, and similar energy Major cogenerators are connected to
5 complete control of all building systems,
uses. The electric power can be the the subtransmission or the transmission
computers with specialized software
can be used. Computers can not only main product, and steam or hot water system of a utility. Major cogenerators
have buy-sell agreements. In such
6 control lighting and HVAC systems, the by-product, as in most commercial
installations, or the steam or hot water cases utilities use a trip transfer scheme
and provide peak demand control, to
minimize the cost of energy, but they can be the most required product, to trip the cogenerator breaker.
7 can perform many other functions. and electric power a by-product, as in
many industrial installations. In some
Guidelines that are given in ANSI
Fire detection and alarm systems can Guide Standard 1001 are a good
operate through the computer, which industries, cogeneration has been
starting point, but the entire design
8 can also perform auxiliary functions common practice for many years, but
should be coordinated with the utility.
such as elevator control and building until recently it has not been economi-
communication in case of fire. Build- cally feasible for most commercial
Emergency Power
9 ing security systems, such as closed- installations. This has been changed
Most areas have requirements for
circuit television monitoring, door by the high cost of purchased energy,
alarms, intruder sensing, can be plus a federal law (Public Utility Regu- emergency and standby power systems.
10 performed by the same building latory Policies Act, known as PURPA) The National Electrical Code does not
specifically call for any emergency or
computer system. that requires public utilities to purchase
any excess power generated by the standby power, but does have require-
11 The time clocks, programmable cogeneration plant. In many cases, ments for those systems when they
controllers, and computers can practical commercial cogeneration are legally mandated and classed as
obtain data from external sensors systems have been built that provide emergency (Article 700), legally required
12 and control the lighting, motors, and some or all of the electric power standby (Article 701) by municipal,
other equipment by means of hard required, plus hot water, steam, and state, federal, or other codes, or by any
wiring-separate wires to and from sometimes steam absorption-type governmental agency having jurisdic-
13 each piece of equipment. In the more air conditioning. Such cogeneration tion. Optional standby systems, not
complex systems, this would result in systems are now operating success- legally required, are also covered in
a tremendous number of control fully in hospitals, shopping centers, the NEC (Article 702).
14 wires, so other methods are frequently
used. A single pair of wires, with elec-
high-rise apartment buildings and
Emergency systems are intended to
even commercial office buildings.
tronic digital multiplexing, can control supply power and illumination essen-
Where a cogeneration system is being tial for safety to human life, when the
15 or obtain data from many different
considered, the electrical distribution normal supply fails. NEC requirements
points. Sometimes, coaxial cable is
used with advanced signaling equip- system becomes more complex. The are stringent, requiring periodic testing
interface with the utility company is criti- under load and automatic transfer to
16 ment. Some systems dispense with
cal, requiring careful relaying to protect emergency power supply on loss of
control wiring completely, sending
and receiving digital signals over the both the utility and the cogeneration normal supply. See Figure 1.4-22 on
system. Many utilities have stringent Page 1.4-31. All wiring from emergency
17 power wiring. The newest systems
requirements that must be incorporated source to emergency loads must be
may use fiber-optic cables to carry
tremendous quantities of data, free into the system. Proper generator con- kept separate from all other wiring and
trol and protection is necessary, as well. equipment, in its own distribution and
18 from electromagnetic interference.
An on-site electrical generating plant raceway system, except in transfer
The method used will depend on
the type, number, and complexity tied to an electrical utility, is a sophisti- equipment enclosures and similar
cated engineering design. locations. The most common power
19 of functions to be performed.
source for large emergency loads is an
Utilities require that when the engine-generator set, but the NEC also
protective device at their substation permits the emergency supply (subject
20 opens that the device connecting a to local code requirements) to be storage
cogenerator to the utility open also.
21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-31
January 2008 System Application Considerations
Sheet 01 087
Other Application Considerations

Utility
Source
i
Typical Application: Three engine generator sets serve the load, plus one additional engine
generator set for redundancy to achieve N+1 level of performance. Open or Closed transition is available.
ii
G1 G2 G3 G4
Paralleling Switchgear
with Distribution
Revenue 1
Metering
HMI
Touchscreen 2
52G1 52G2 52G3 52G4

Main D1 D2 D3 D4
Service 3

ATS1 ATS2 ATS3 ATS4


6
N E N E N E N E
To Normal To Emergency
Distribution Circuits
Circuits 7
EDP1 EDP2 EDP3 EDP4
8
Optional Remote PC
with Software
LP1 BP1 LP2 BP2 LP3 BP3 LP4 BP4
9

Figure 1.4-22. Typical Emergency Power System 10


batteries, uninterruptible power sup- or fire-fighting operations. NEC full load, as is usually the case, such a
plies, a separate emergency service, requirements are similar to those for scheme would require automatic dis- 11
or a connection to the service ahead emergency systems, except that wir- connection of the nonessential loads
of the normal service disconnecting ing may occupy the same distribution before transfer. Simpler and more eco-
means. Unit equipment for emergency and raceway system as the normal nomical in such a case is a separate 12
illumination, with a rechargeable bat- wiring if desired. Optional standby emergency bus, supplied through an
tery, a charger to keep it at full capacity systems are those not legally required, automatic transfer switch, to feed all
when normal power is on, one or more and are intended to protect private critical loads. The transfer switch con- 13
lamps, and a relay to connect the bat- business or property where life safety nects this bus to the normal supply,
tery to the lamps on loss of normal does not depend on performance of in normal operation. On failure of the
power, is also permitted. Because of the system. Optional systems can be normal supply, the engine-generator 14
the critical nature of emergency treated as part of the normal building is started, and when it is up to speed
power, ground fault protection is not wiring system. Both legally required the automatic switch transfers the
required. It is considered preferable and optional standby systems should emergency loads to this source. On 15
to risk arcing damage, rather than be installed in such a manner that they return of the normal source, manual
to disconnect the emergency supply will be fully available on loss of normal or automatic retransfer of the emer-
completely. For emergency power, power. It is preferable to isolate these gency loads can take place. 16
ground fault alarm is required by NEC systems as much as possible, even
700.7(D) to indicate a ground fault though not required by code. Peak Shaving
in solidly grounded wye emergency Many installations now have emer-
17
systems of more than 150 volts Where the emergency or standby
source, such as an engine generator gency or standby generators. In the
to ground and circuit-protective past, they were required for hospitals
devices rated 1000 amperes or more. or separate service, has capacity to
and similar locations, but not common
18
supply the entire system, the transfer
Legally required standby systems, as scheme can be either a full-capacity in office buildings or shopping centers.
required by the governmental agency automatic transfer switch, or, less However, many costly and unfortunate 19
having jurisdiction, are intended to costly but equally effective, normal experiences during utility blackouts in
supply power to selected loads, other and emergency main circuit breakers, recent years have led to the more fre-
than those classed as emergency electrically interlocked such that on quent installation of engine generators 20
systems, on loss of normal power. failure of the normal supply the emer- in commercial and institutional systems
These are usually loads not essential gency supply is connected to the load. for safety and for supplying important
to human safety, but loss of which However, if the emergency or standby loads. Industrial plants, especially in 21
could create hazards or hamper rescue source does not have capacity for the

CA08104001E For more information visit: www.eaton.com


1.4-32 Power Distribution Systems
System Application Considerations January 2008
Sheet 01 088
Other Application Considerations

process industries, usually have some It is important that the electrical sys- Some reduction or attenuation takes
i form of alternate power source to tem designer providing a substantial place through building walls, the
prevent extremely costly shutdowns. source of emergency and standby remainder may be reflected in various
These standby generating systems power investigate the possibility of directions, resulting in a build-up or
ii are critical when needed, but they are using it for peak shaving, and even apparent higher levels, especially if
needed only infrequently. They repre- of partial utility company financing. resonance occurs because of room
sent a large capital investment. To be Frequently, substantial savings in dimensions or material characteristics.
1 sure that their power will be available power costs can be realized for a
when required, they should be tested small additional outlay in distribution Area Consideration
periodically under load. and control equipment. In determining permissible sound lev-
2 els within a building, it is necessary to
The cost of electric energy has risen Peak shaving equipment operating in consider how the rooms are to be used
to new high levels in recent years, and parallel with the utility are subject to the and what levels may be objectionable
3 utilities bill on the basis not only of comments made under cogeneration to occupants of the building. The
power consumed, but also on the as to separation from the utility under ambient sound level values given in
basis of peak demand over a small fault conditions. Table 1.4-9 are representative average
4 interval. As a result, a new use for values and may be used as a guide in
in-house generating capacity has determining suitable building levels.
developed. Utilities measure demand
Sound Levels
5 charges on the basis of the maximum Sound Levels of Electrical Equipment
Decrease in sound level varies at an
demand for electricity in any given approximate rate of 6 decibels for each
for Offices, Hospitals, Schools and doubling of the distance from the
specific period (typically 15 or 30
Similar Buildings
6 minutes) during the month. Some
Insurance underwriters and building
source of sound to the listener. For
utilities have a demand “ratchet clause” example, if the level 6 feet (1.8 m)
that will continue demand charges on owners desire and require that the from a transformer is 50 dB, the level
7 a given peak demand for a full year, electrical apparatus be installed at a distance of 12 feet (3.7 m) would
unless a higher peak results in even for maximum safety and the least be 44 dB and at 24 feet (7.3 m) the
higher charges. One large load, coming interference with the normal use of level decreases to 38 dB, etc. However,
8 on at a peak time, can create higher the property. Architects should take
particular care with the designs for
this rule applies only to equipment
electric demand charges for a year. in large areas equivalent to an out-
hospitals, schools and similar build- of-door installation, with no nearby
9 Obviously, reducing the peak demand ings to keep the sound perception of reflecting surfaces.
can result in considerable savings in such equipment as motors, blowers
the cost of electrical energy. For those and transformers to a minimum. Table 1.4-9. Typical Sound Levels
10 installations with engine generators Description Average
for emergency use, modern control Even though transformers are Decibel
systems (computers or programmable relatively quiet, resonant conditions Level (dB)
controllers) can monitor the peak may exist near the equipment which
11 demand, and start the engine-generator will amplify their normal 120 Hz Radio, Recording and TV Studios 25 – 30
Theatres and Music Rooms 30 – 35
to supply part of the demand as it hum. Therefore, it is important that Hospitals, Auditoriums and Churches 35 – 40
consideration be given to the reduc-
12 approaches a preset peak value. The
engine-generator must be selected tion of amplitude and to the absorp-
Classrooms and Lecture Rooms 35 – 40
Apartments and Hotels 35 – 45
to withstand the required duty cycle. tion of energy at this frequency. Private Offices and Conference Rooms 40 – 45
This problem begins in the designing
13 The simplest of these schemes trans-
stages of the equipment and the build-
Stores 45 – 55
fer specific loads to the generator. Residence (Radio, TV Off)
More complex schemes operate the ing. There are two points worthy of and Small Offices 53
consideration: 1) What sound levels Medium Office (3 to 10 Desks) 58
14 generator in parallel with the normal
are desired in the normally occupied Residence (Radio, TV On) 60
utility supply. The savings in demand
charges can reduce the cost of owning rooms of this building? 2) To effect Large Store (5 or More Clerks) 61
this, what sound level in the equip- Factory Office 61
15 the emergency generator equipment.
ment room and what type of associ- Large Office 64
In some instances, utilities with little ated acoustical treatment will give the Average Factory 70
reserve capacity have helped finance Average Street 80
most economical installation overall?
16 the cost of some larger customer-
owned generating equipment. In A relatively high sound level in the Transformer Sound Levels
return, the customer agrees to take equipment room does not indicate Transformers emit a continuous 120 Hz
17 some or all of his load off the utility an abnormal condition within the hum with harmonics when connected
system and on to his own generator at apparatus. However, absorption may to 60 Hz circuits. The fundamental
the request of the utility (with varying be necessary if sound originating in frequency is the “hum” which annoys
18 limitations) when the utility load an unoccupied equipment room is people primarily because of its contin-
approaches capacity. In some cases, objectionable outside the room. uous nature. For purposes of reference,
the customer’s generator is paralleled Furthermore, added absorption sound measuring instruments convert
19 with the utility to help supply the peak material usually is desirable if there is a the different frequencies to 1000 Hz
utility loads, with the utility buying the “build-up” of sound due to reflections. and a 40 dB level. Transformer sound
supplied power. Some utilities have levels based on NEMA publication TR-1
20 been able to delay large capital expen- are listed in Table 1.4-10.
ditures for additional generating
capacity by such arrangements.
21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.4-33
January 2008 System Application Considerations
Sheet 01 089
Other Application Considerations

Table 1.4-10. Maximum Average Sound Levels — Decibels on vibration dampeners is about 10%
kVA Liquid-Filled Transformers Dry-Type Transformers of the fundamental frequency. The i
Self-Cooled Forced-Air Self-Cooled Forced-Air
reduction in the transmitted vibration
Rating (OA) Cooled Rating (FA) Rating (AA) Cooled Rating (FA) is approximately 98%. If the floor or
beams beneath the transformer are ii
300 55 — 58 67 light and flexible, the isolator must be
500 56 67 60 67 softer or have improved characteristics
750 58 67 64 67
in order to keep the transmitted vibra- 1
1000 58 67 64 67 tions to a minimum. (Enclosure covers
1500 60 67 65 68
2000 61 67 66 69
and ventilating louvers are often
2500 62 67 68 71
improperly tightened or gasketed 2
3000 63 67 68 71
and produce unnecessary noise). The
3750 64 67 70 73 building structure will assist the damp-
5000 65 67 71 73
eners if the transformer is mounted 3
6000 66 68 72 74 above heavy floor members or if
7500 67 69 73 75 mounted on a heavy floor slab. Posi-
10,000 68 70 — 76 tioning of the transformer in relation 4
to walls and other reflecting surfaces
Since values given in Table 1.4-10 Sounds due to structure-transmitted has a great effect on reflected noise
are in general higher than those given vibrations originating from the trans- and resonances. Often, placing the 5
in Table 1.4-9, the difference must be former are lowered by mounting the transformer at an angle to the wall,
attenuated by distance and by proper transformers on vibration dampeners rather than parallel to it, will reduce
use of materials in the design of the or isolators. There are a number of noise. Electrical connections to a 6
building. An observer may believe that different sound vibration isolating substation transformer should be
a transformer is noisy because the level materials which may be used with good made with flexible braid or conduc-
in the room where it is located is high. results. Dry-type power transformers tors; connections to an individually 7
Two transformers of the same sound are often built with an isolator mounted mounted transformer should be in
output in the same room increase the between the transformer support and flexible conduit.
sound level in the room approximately case members. The natural period of 8
3 dB, and three transformers by about the core and coil structure when mounted
5 dB, etc.
9

10

11

12

13

14

15

16

17

18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.4-34 Power Distribution Systems
January 2008
Sheet 01090

This page intentionally left blank.


i

ii

10

11

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-1
January 2008 Reference Data
Sheet 01 091
IEEE Protective Relay Numbers

Table 1.5-1. Selected IEEE Device Numbers for Switchgear Apparatus


Device Function Definition Typical i
Number Uses

2 Time-delay starting or closing relay A device which functions to give a desired amount Used for providing a time-delay for
of time delay before or after any point of operation re-transfer back to the normal source
ii
in a switching sequence or protective relay system, in an automatic transfer scheme.
except as specifically provided by device functions
48, 62 and 79 described later. 1
6 Starting circuit breaker A device whose principal function is to connect —
a machine to its source of starting voltage.
19 Starting to running transition timer A device which operates to initiate or cause the Used to transfer a reduced voltage
2
automatic transfer of a machine from the starting starter from starting to running.
to the running power connection.
21 Distance relay A device which functions when the circuit — 3
admittance, impedance or reactance increases or
decreases beyond predetermined limits.
23 Temperature control device A device which functions to raise or to lower the Used as a thermostat to control 4
temperature of a machine or other apparatus, or space heaters in outdoor equipment.
of any medium, when its temperature falls below
or rises above, a predetermined level. 5
24 Volts per hertz relay A device that operates when the ratio of voltage —
to frequency is above a preset value or is below
a different preset value. The relay may have any
combination of instantaneous or time delayed
6
characteristics.
25 Synchronizing or synchronism check device A device which operates when two ac circuits are In a closed transition breaker
within the desired limits of frequency, phase angle transfer, a 25 relay is used to ensure 7
or voltage, to permit or cause the paralleling of two-sources are synchronized
these two circuits. before paralleling. Cutler-Hammer
FP-5000 feeder protective relay. 8
27 Undervoltage relay A device which functions on a given value of Used to initiate an automatic transfer
undervoltage. when a primary source of power
is lost. Cutler-Hammer FP-5000/
FP-4000/MP-4000 protective relays.
9
30 Annunciator relay A non-automatically reset device that gives a Used to remotely indicate that a
number of separate visual indications upon the
functioning of protective devices, and which may
protective relay has functioned, or
that a circuit breaker has tripped.
10
also be arranged to perform a lockout function. Typically, a mechanical “drop” type
annunciator panel is used.
32 Directional power relay A relay which functions on a desired value of power Used to prevent reverse power from 11
flow in a given direction, or upon reverse power feeding an upstream fault. Often
resulting from arc back in the anode or cathode used when primary backup genera-
circuits of a power rectifier. tion is utilized in a facility. Cutler-
Hammer FP-5000 protective relay.
12
33 Position switch A device which makes or breaks contact when the Used to indicate the position of a
main device or piece of apparatus, which has no
device function number, reaches a given point.
drawout circuit breaker (TOC switch). 13
34 Master sequence device A device such as a motor-operated multi-contact —
switch, or the equivalent, or a programmable
device, that establishes or determines the operating
14
sequence of the major devices in equipment
during starting and stopping or during sequential
switching operations. 15
37 Undercurrent or underpower relay A relay which functions when the current or power Cutler-Hammer MP-3000/MP-4000
flow decreases below a predetermined value. motor protective relays.
38 Bearing protective device A device which functions on excessive bearing Cutler-Hammer MP-3000/MP-4000 16
temperature, or on other abnormal mechanical motor protective relays.
conditions, such as undue wear, which may
eventually result in excessive bearing temperature. 17
40 Field relay A device that functions on a given or abnormally —
high or low value or failure of machine field current,
or on an excessive value of the reactive component
of armature current in an ac machine indicating
18
abnormally high or low field excitation.
41 Field circuit breaker A device which functions to apply, or to remove, —
the field excitation of a machine. 19
42 Running circuit breaker A device whose function is to connect a machine —
to its source of running or operating voltage.
This function may also be used for a device, such 20
as a contactor, that is used in series with a circuit
breaker or other fault-protecting means, primarily
for frequent opening and closing of the circuit. 21

CA08104001E For more information visit: www.eaton.com


1.5-2 Power Distribution Systems
Reference Data January 2008
Sheet 01 092
IEEE Protective Relay Numbers

Table 1.5-1. Selected IEEE Device Numbers for Switchgear Apparatus (Continued)
i Device Function Definition Typical
Number Uses

ii 43 Manual transfer or selector device A manually operated device that transfers control
or potential circuits in order to modify the plan of

operation of the associated equipment or of some


of the associated devices.
1 44 Unit sequence starting relay A device that functions to start the next available —
unit in multiple-unit equipment upon the failure or
non-availability of the normally preceding unit.
2 46 Reverse-phase, or phase balance, current relay A relay which functions when the polyphase Cutler-Hammer FP-5000/FP-4000
currents are of reverse-phase sequence, or when feeder protective relays and MP-3000/
the polyphase currents are unbalanced or contain MP-4000 motor protective relays.
3 the negative phase-sequence components above
a given amount.
47 Phase-sequence voltage relay A relay which functions upon a predetermined Cutler-Hammer FP-5000/FP-4000
4 value of polyphase voltage in the desired phase
sequence.
feeder protective relays and MP-3000/
MP-4000 motor protective relays.
48 Incomplete sequence relay A relay that generally returns the equipment to the —
5 normal, or off, position and locks it out of the
normal starting, or operating or stopping sequence
is not properly completed within a predetermined
amount of time. If the device is used for alarm
6 purposes only, it should preferably be designated
as 48A (alarm).
49 Machine, or transformer, thermal relay A relay that functions when the temperature of a Cutler-Hammer MP-3000/MP-4000
7 machine armature, or other load carrying winding motor protective relays.
or element of a machine, or the temperature
of a power rectifier or power transformer
(including a power rectifier transformer) exceeds
8 a predetermined value.
50 Instantaneous overcurrent, or rate-of-rise relay A relay that functions instantaneously on an Used for tripping a circuit breaker
excessive value of current, or an excessive rate of instantaneously during a high level
9 current rise, thus indicating a fault in the apparatus short circuit. Can trip on phase-
of the circuit being protected. phase (50), phase-neutral (50N),
phase-ground (50G) faults.
10 Cutler-Hammer Digitrip 3000,
FP-5000/FP-4000 protective relays,
MP-3000/MP-4000 motor
protective relays.
11 51 ac time overcurrent relay A relay with either a definite or inverse time Used for tripping a circuit breaker
characteristic that functions when the current in an after a time delay during a sustained
ac circuit exceeds a predetermined value. overcurrent. Used for tripping a
12 circuit breaker instantaneously
during a high level short circuit .
Can trip on phase (51), neutral (51N) or
ground (51G) overcurrents.
13 Cutler-Hammer Digitrip 3000,
FP-5000/FP-4000 protective relays,
MP-3000/MP-4000 motor
14 protective relays.
52 ac circuit breaker A device that is used to close and interrupt an A term applied typically to medium
ac power circuit under normal conditions or to voltage circuit breakers, or low
15 interrupt this circuit under fault or emergency
conditions.
voltage power circuit breakers.
Cutler-Hammer VCP-W Vacuum
Circuit Breaker, Magnum DS
Low Voltage Power Circuit Breaker
16 53 Exciter or dc generator relay A device that forces the dc machine field excitation —
to build up during starting or that functions when
the machine voltage has built up to a given value.
17 55 Power factor relay A relay that operates when the power factor Cutler-Hammer FP-5000/FP-4000
in an ac circuit rises above or below a feeder protective relays and MP-4000
predetermined value. motor protective relay.
18 56 Field application relay A device that automatically controls the application —
of the field excitation to an ac motor at some
predetermined point in the slip cycle.
19 59 Overvoltage relay A relay that functions on a given value of Used to trip a circuit breaker,
overvoltage. protecting downstream equipment
from sustained overvoltages.
20 Cutler-Hammer FP-5000/FP-4000
feeder protective relays and MP-4000
motor protective relay.
60 Voltage or current balance relay A relay that operates on a given difference in —
21 voltage, or current input or output of two circuits.

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-3
January 2008 Reference Data
Sheet 01 093
IEEE Protective Relay Numbers

Table 1.5-1. Selected IEEE Device Numbers for Switchgear Apparatus (Continued)
Device Function Definition Typical i
Number Uses

62 Time-delay stopping or opening relay A time-delay relay that serves in conjunction with
the device that initiates the shutdown, stopping,
Used in conjunction with a 27 device
to delay tripping of a circuit breaker
ii
or opening operation in an automatic sequence. during a brief loss of primary voltage,
to prevent nuisance tripping.
63 Pressure switch A switch which operates on given values or on a Used to protect a transformer during
1
given rate of change of pressure. a rapid pressure rise during a short
circuit. This device will typically act
to open the protective devices above 2
and below the transformer. Typically
used with a 63-X auxiliary relay to
trip the circuit breaker.
3
64 Ground protective relay A relay that functions on a failure of the insulation Used to detect and act on a ground-
of a machine, transformer, or of other apparatus to fault condition. In a pulsing high
ground, or on flashover of a dc machine to ground. resistance grounding system, a 64
device will initiate the alarm. 4
65 Governor A device consisting of an assembly of fluid, —
electrical or mechanical control equipment used for
regulating the flow of water, steam, or other media 5
to the prime mover for such purposes as starting,
holding speed or load, or stopping.
66 Notching or jogging device A device that functions to allow only a specified Cutler-Hammer MP-3000/MP-4000 6
number of operations of a given device, or motor protective relays.
equipment, or a specified number of successive
operations within a given time of each other. It also
functions to energize a circuit periodically or for
7
fractions of specified time intervals, or that is used
to permit intermittent acceleration or jogging of a
machine at low speeds for mechanical positioning. 8
67 ac directional overcurrent relay A relay that functions on a desired value of ac Cutler-Hammer FP-5000 feeder
overcurrent flowing in a predetermined direction. protective relay.
69 Permissive control device A device that is generally a two-position manually Used as a remote-local switch for 9
operated switch that in one position permits the circuit breaker control.
closing of a circuit breaker, or the placing of
equipment into operation, and in the other position
prevents the circuit breaker to the equipment from
10
being operated.
71 Level Switch A switch that operates on given values, or on a
given rate of change of level.
Used to indicate a low liquid level
within a transformer tank in order
11
to save transformers from loss-of-
insulation failure. An alarm contact is
available as a standard option on a 12
liquid level gauge. It is set to close
before an unsafe condition actually
occurs.
13
72 dc circuit breaker A device that is used to close and interrupt a —
dc power circuit under normal conditions or to
interrupt this circuit under fault or emergency
conditions. 14
73 Load-resistor contactor A device that is used to shunt or insert a step of —
load limiting, shifting or indicating resistance in
a power circuit; to switch a space heater in circuit; 15
or to switch a light or regenerative load resistor
of a power rectifier or other machine in and out
of circuit. 16
74 Alarm relay A device other than an annunciator, as covered —
under device number 30, which is used to operate,
or to operate in connection with, a visible or
audible alarm.
17
78 Phase-angle measuring relay A device that functions at a predetermined phase —
angle between two voltages, between two currents,
or between voltage and current. 18
79 ac reclosing relay A relay that controls the automatic closing and Used to automatically reclose a
locking out of an ac circuit interrupter. circuit breaker after a trip, assuming
the fault has been cleared after the 19
power was removed from the circuit.
The recloser will lock-out after a
predetermined amount of failed
attempts to reclose.
20

21

CA08104001E For more information visit: www.eaton.com


1.5-4 Power Distribution Systems
Reference Data January 2008
Sheet 01 094
IEEE Protective Relay Numbers

Table 1.5-1. Selected IEEE Device Numbers for Switchgear Apparatus (Continued)
i Device Function Definition Typical
Number Uses

ii 81 Frequency relay A relay that functions on a predetermined value of


frequency — either under or over or on normal
Used to trip a generator circuit
breaker in the event the frequency
system frequency — or rate of change frequency. drifts above or below a given value.
Cutler-Hammer FP-5000/FP-4000
1 feeder protective relays and
MP-4000 motor protective relay.
83 Automatic selective control or transfer relay A relay that operates to select automatically Used to transfer control power
2 between certain sources or conditions in sources in a double-ended
equipment, or performs a transfer operation switchgear lineup.
automatically.
3 85 Carrier or pilot-wire relay A device that is operated or restrained by a signal —
transmitted or received via any communications
media used for relaying.
4 86 Locking-out relay An electrically operated hand, or electrically, reset
relay that functions to shut down and hold an
Used in conjunction with protective
relays to lock-out a circuit breaker
equipment out of service on the occurrence of (or multiple circuit breakers) after
abnormal conditions. a trip. Typically required to be
5 manually reset by an operator before
the breaker can be reclosed.
87 Differential protective relay A protective relay that functions on a percentage or Used to protect static equipment,
6 phase angle or other quantitative difference of two such as cable, bus or transformers,
currents or of some other electrical quantities. by measuring the current differential
between two points. Typically the
7 upstream and/or downstream circuit
breaker will be incorporated into the
“zone of protection.” Cutler-Hammer
FP-5000 feeder protective relay (87B)
8 and MD-3000 protective relay.
90 Regulating device A device that functions to regulate a quantity or —
quantities, such as voltage, current, power, speed,
9 frequency, temperature and load, at a certain value
or between certain (generally close) limits for
machines, tie lines or other apparatus.
10 91 Voltage directional relay A device that operates when the voltage across an
open circuit breaker or contactor exceeds a given

value in a given direction.

11 94 Tripping or trip-free relay A relay that functions to trip a circuit breaker,


contactor, or equipment, or to permit immediate

tripping by other devices, or to prevent immediate


reclosure of a circuit interrupter, in case it should
12 open automatically even though its closing circuit
is maintained closed.

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-5
January 2008 Reference Data
Sheet 01 095
Suggested IEEE Designations for Suffix Letters

Suggested IEEE Designations Main Device Other Suffix Letters


i
for Suffix Letters The following letters denote the main The following letters cover all other
device to which the numbered device distinguishing features, characteris-
Auxiliary Devices is applied or is related: tics or conditions not specifically ii
described in Auxiliary Devices through
These letters denote separate auxiliary A Alarm/auxiliary power Main Device Parts, which serve to
devices, such as the following:
AC Alternating current describe the use of the device in the 1
C Closing relay/contactor equipment, such as:
BP Bypass
A Automatic
CL Auxiliary relay, closed
BT Bus tie 2
(energized when main device BF Breaker failure
is in closed position) C Capacitor
C Close 3
CS Control switch DC Direct current
D Decelerating/down
D “Down” position switch relay E Exciter
E Emergency 4
L Lowering relay F Feeder/field
F Failure/forward
O Opening relay/contactor G Generator/ground
HS High speed 5
OP Auxiliary relay, open M Motor/metering
(energized when main device L Local/lower
is in open position) MOC Mechanism operated contact
M Manual
6
PB Push button S Synchronizing/secondary
O Open
R Raising relay T Transformer 7
OFF Off
U “UP” position switch relay TOC Truck-operated contacts
ON On
8
X Auxiliary relay Main Device Parts R Raise/reclosing/remote/reverse
Y Auxiliary relay These letters denote parts of the
main device, except auxiliary contacts, T Test/trip 9
Z Auxiliary relay position switches, limit switches, TDC Time-delay closing contact
and torque limit switches:
Actuating Quantities TDDO Time delayed relay coil 10
C Coil/condenser/capacitor drop-out
These letters indicate the condition or
electrical quantity to which the device CC Closing coil/closing contactor
responds, or the medium in which it is
TDO Time-delay opening contact 11
located, such as the following: HC Holding coil TDPU Time delayed relay coil pickup
A Amperes/alternating M Operating motor THD Total harmonic distortion 12
C Current OC Opening contactor

F Frequency/fault S Solenoid 13
I0 Zero sequence current SI Seal-in

I-, I2 Negative sequence current T Target 14


I+, I1 Positive sequence current TC Trip coil
15
P Power/pressure
PF Power factor
16
S Speed
T Temperature 17
V Voltage/volts/vacuum
VAR Reactive power 18
VB Vibration
W Watts 19

20

21

CA08104001E For more information visit: www.eaton.com


1.5-6 Power Distribution Systems
Reference Data January 2008
Sheet 01 096
Codes and Standards

Codes and Standards testing laboratories have been recog- A design engineer should conform
i The National Electrical Code (NEC),
nized and accepted. The Institute of to all applicable codes, and require
Electrical and Electronic Engineers (IEEE) equipment to be listed by UL or
NFPA Standard No. 70, is the most publishes a number of books (the another recognized testing laboratory
ii prevalent electrical code in the United
States. The NEC, which is revised
“color book” series) on recommended wherever possible, and to meet ANSI
practices for the design of industrial or NEMA standards. ANSI/IEEE recom-
every three years, has no legal stand- buildings, commercial buildings, mended practices should be followed
1 ing of its own, until it is adopted as law emergency power systems, grounding, to a great extent. In many cases, stan-
by a jurisdiction, which may be a city, and the like. Most of these IEEE standards dards should be exceeded to get a
county, or state. Most jurisdictions have been adopted as ANSI standards. system of the quality required. The
2 adopt the NEC in its entirety; some They are excellent guides, although design goal should be a safe, efficient,
adopt it with variations, usually more they are not in any way mandatory. long-lasting, flexible, and economical
rigid, to suit local conditions and electrical distribution system.
3 requirements. A few large cities, such
as New York and Chicago, have their
own electrical codes, basically similar Professional Organizations
4 to the NEC. The designer must deter-
American National Standards Institute National Electrical Manufacturers
mine which code applies in the area
of a specific project. (ANSI) Association (NEMA)
5 The Occupational Safety and Health Headquarters: 1300 North 17th Street
Suite 1847
Act (OSHA) of 1970 sets uniform 1819 L Street, NW Rosslyn, VA 22209
national requirements for safety in the 6th Floor
6 workplace — anywhere that people are Washington, DC 20036
703-841-3200
employed. Originally OSHA adopted 202-293-8020 www.nema.org
the 1971 NEC as rules for electrical
7 safety. As the NEC was amended every Operations: National Fire Protection Association
three years, the involved process for 25 West 43rd Street (NFPA)
modifying a federal law such as OSHA 4th Floor 1 Battery March Park
8 made it impossible for the act to adopt New York, NY 10036 Quincy, MA 02169-7471
each new code revision. To avoid this 212-642-4900 617-770-3000
problem, the OSHA administration
9 in 1981 adopted its own code, a con- www.ansi.org www.nfpa.org
densed version of the NEC containing Institute of Electrical and Electronics Underwriters Laboratories (UL)
10 only those provisions considered Engineers (IEEE) 333 Pfingsten Road
related to occupational safety. OSHA
Northbrook, IL 60062-2096
was amended to adopt this code, Headquarters:
847-272-8800
11 based on NFPA Standard 70E, Part 1, 3 Park Avenue
which is now federal law. 17th Floor www.ul.com
The NEC is a minimum safety New York, NY 10016-5997
International Code Council (ICC)
12 standard. Efficient and adequate 212-419-7900
5203 Leesburg Pike
design usually requires not just Operations: Suite 600
meeting, but often exceeding NEC
13 requirements to provide an effective,
445 Hoes Lane Falls Church, VA 22041
1-888-422-7233
Piscataway, NJ 08854-1331
reliable, economical electrical system.
732-981-0060
www.iccsafe.org
14 Many equipment standards have been
www.ieee.org
established by the National Electrical The American Institute of Architects (AIA)
Manufacturers’ Association (NEMA) International Association of Electrical 1735 New York Avenue, NW
15 and the American National Standards Inspectors (IAEI) Washington, DC 20006-5292
Institute (ANSI). Underwriters Laboratory 202-626-7300
901 Waterfall Way
(UL) has standards that equipment
Suite 602
16 must meet before UL will list or label it.
Richardson, TX 75080-7702
www.aia.org
Most jurisdictions and OSHA require
972-235-1455
that where equipment listed as safe by
17 a recognized laboratory is available, www.iaei.org
unlisted equipment may not be used.
UL is by far the most widely accepted
18 national laboratory, although Factory
Mutual Insurance Company lists some
equipment, and a number of other
19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-7
January 2008 Reference Data
Sheet 01 097
Motor Protective Device Data

Motor Protection Table 1.5-2. Motor Circuit Protector (MCP), Circuit Breaker and Fusible Switch Selection Guide
In line with 2005 NEC 430.6(A) Horsepower Full Load Fuse Size NEC 430.52 Recommended Cutler-Hammer i
Amperes Maximum Circuit Motor Circuit
circuit breaker, HMCP and fuse rating (NEC) FLA Amperes
selections are based on full load Breaker Protector Type HMCP
currents for induction motors running Time Delay Non-Time Delay Amperes Type Amperes Adj. Range
ii
at speeds normal for belted motors 230 Volts, 3-Phase
and motors with normal torque 1 3.6 10 15 15 HFD 7 21 – 70 1
characteristics using data taken from 1-1/2 5.2 10 20 15 HFD 15 45 – 150
NEC Table 130.250 (3-phase). Actual 2 6.8 15 25 15 HFD 15 45 – 150
3 9.6 20 30 20 HFD 30 90 – 300
motor nameplate ratings shall be used 2
for selecting motor running overload 5 15.2 30 50 30 HFD 30 90 – 300
protection. Motors built special for low 7-1/2 22 40 70 50 HFD 50 150 – 500
10 28 50 90 60 HFD 50 150 – 500
speeds, high torque characteristics, 15 42 80 150 90 HFD 100 300 – 1000 3
special starting conditions and
20 54 100 175 100 HFD 100 300 – 1000
applications will require other 25 68 125 225 125 HFD 150 450 – 1500
considerations as defined in the 30 80 150 250 150 HFD 150 450 – 1500 4
application section of the NEC. 40 104 200 350 150 HFD 150 750 – 2500
50 130 250 400 200 HFD 150 750 – 2500
These additional considerations may
require the use of a higher rated HMCP,
60 154 300 500 225 HFD 250 1250 – 2500 5
75 192 350 600 300 HKD 400 2000 – 4000
or at least one with higher magnetic 100 248 450 800 400 HKD 400 2000 – 4000
pickup settings. 125
150
312
360
600
700
1000
1200
500
600
HLD
HLD
600
600
1800 – 6000
1800 – 6000
6
Circuit breaker, HMCP and fuse 200 480 1000 1600 700 HND 600 1800 – 6000
ampere rating selections are in
line with maximum rules given in 460 Volts, 3-Phase 7
NEC 430.52 and Table 430.250. Based 1 1.8 6 6 15 HFD 7 21 – 70
1-1/2 2.6 6 10 15 HFD 7 21 – 70
on known characteristics of Eaton’s
Cutler-Hammer type breakers, specific
2
3
3.4
4.8
6
10
15
15
15
15
HFD
HFD
7
15
21 – 70
45 – 150
8
units are recommended. The current 5 7.6 15 25 15 HFD 15 45 – 150
ratings are no more than the maxi- 7-1/2 11 20 35 25 HFD 30 90 – 300
mum limits set by the NEC rules for 10 14 25 45 35 HFD 30 90 – 300 9
motors with code letters F to V or 15 21 40 70 45 HFD 50 150 – 500
without code letters. Motors with 20 27 50 90 50 HFD 50 150 – 500
lower code letters will require further 25 34 60 110 70 HFD 70 210 – 700 10
considerations. 30 40 70 125 70 HFD 100 300 – 1000
40 52 100 175 100 HFD 100 300 – 1000
In general, these selections were 50 65 125 200 110 HFD 150 450 – 1500 11
based on: 60 77 150 150 125 HFD 150 750 – 2500
75 96 175 300 150 HJD 150 750 – 2500
1. Ambient — Outside enclosure not
more than 40°C (104°F).
100 124 225 400 175 HJD 150 750 – 2500
12
125 156 300 500 225 HKD 400 2000 – 4000
150 180 350 600 250 HJD 400 2000 – 4000
2. Motor starting — Infrequent 200 240 450 800 350 L600 600 1800 – 6000
starting, stopping or reversing.
575 Volts, 3-Phase
13
3. Motor accelerating time — 1 1.4 3 6 15 HFD 3 9 – 30
10 seconds or less. 1-1/2
2
2.1
2.7
6
6
10
10
15
15
HFD
HFD
7
7
21 – 70
21 – 70
14
4. Locked rotor — Maximum 6 times 3 3.9 10 15 15 HFD 7 21 – 70
motor FLA. 5 6.1 15 20 15 HFD 15 45 – 150
7-1/2 9 20 30 20 HFD 30 90 – 300 15
Type HMCP motor circuit protector 10 11 20 35 25 HFD 30 90 – 300
may not set at more than 1300% of 15 17 30 60 40 HFD 30 90 – 300
the motor full-load current to comply 20 22 40 70 50 HFD 50 150 – 500 16
with NEC 430.52. (Except for NEMA 25 27 50 90 60 HFD 50 150 – 500
Design B energy high-efficiency 30 32 60 100 60 HFD 70 210 – 500
motors which can be set up to 1700%.) 40 41 80 125 80 HFD 100 300 – 1000 17
50 52 100 175 100 HFD 100 300 – 1000
Circuit breaker selections are based 60 62 110 200 125 HFD 150 750 – 2500
on types with standard interrupting 75
100
77
99
150
175
250
300
150
175
HFD
HJD
150
150
750 – 2500
750 – 2500
18
ratings. Higher interrupting rating
types may be required to satisfy 125 125 225 400 200 HJD 250 1250 – 2500
150 144 300 450 225 HJD 250 1250 – 2500
specific system application
200 192 350 600 300 HKD 400 2000 – 4000 19
requirements.
For motor full load currents of 208 and
200 volts, increase the corresponding
20
230-volt motor values by 10 and 15%
respectively.
21

CA08104001E For more information visit: www.eaton.com


1.5-8 Power Distribution Systems
Reference Data January 2008
Sheet 01 098
Motor Protective Device Data

Table 1.5-3. 60 Hz, Recommended Protective Setting for Induction Motors


i hp Full Load Minimum Wire Size Minimum Conduit Size, Fuse Size NEC 430-152 Recommended Cutler-Hammer:
Amperes 75°C Copper Ampacity Inches (mm) Maximum Amperes  Circuit Motor Circuit Protector
(NEC) FLA at 125% FLA THW THWN Time Non-Time Breaker  Type GMCP/HMCP
ii Size Amperes XHHN Delay Delay Amperes Type Amperes Adjustable Range
115 Volts, Single-Phase
1 3/4 13.8 12 20 .50 (12.7) .50 (12.7) 25 45 30 ED 2-Pole Device
1 16 12 20 .50 (12.7) .50 (12.7) 30 50 35 ED Not Available
1-1/2 20 10 30 .50 (12.7) .50 (12.7) 35 60 40 ED
2 2
3
24
34
10
8
30
50
.50 (12.7)
.75 (19.1)
.50 (12.7) 45
.50 (12.7) 60
80
110
50
70
ED
ED
5 56 4 85 1.00 (25.4) .75 (19.1) 100 175 100 ED
7-1/2 80 3 100 1.00 (25.4) 1.00 (25.4) 150 250 150 ED
3 230 Volts, Single-Phase
3/4 6.9 12 20 .50 (12.7) .50 (12.7) 15 25 15 ED 2-Pole Device
4 1
1-1/2
8
10
12
12
20
20
.50 (12.7)
.50 (12.7)
.50 (12.7)
.50 (12.7)
15
20
25
30
20
25
ED
ED
Not Available

2 12 12 20 .50 (12.7) .50 (12.7) 25 40 30 ED


3 17 10 30 .50 (12.7) .50 (12.7) 30 60 40 ED
5 5 28 8 50 .50 (12.7) .50 (12.7) 50 90 60 ED
7-1/2 40 8 50 .75 (19.1) .50 (12.7) 70 125 80 ED
 Consult fuse manufacturer’s catalog for smaller fuse ratings.
6  Types are for minimum interrupting capacity breakers. Ensure that the fault duty does not exceed breaker’s I.C.

10

11

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-9
January 2008 Reference Data
Sheet 01 099
Chart of Short Circuit Currents for Transformers

Table 1.5-4. Secondary Short Circuit Current of Typical Power Transformers


Trans- Maximum 208 Volts, 3-Phase 240 Volts, 3-Phase 480 Volts, 3-Phase 600 Volts, 3-Phase i
former Short Rated Short Circuit Current Rated Short Circuit Current Rated Short Circuit Current Rated Short Circuit Current
Rating Circuit Load rms Symmetrical Amps Load rms Symmetrical Amps Load rms Symmetrical Amps Load rms Symmetrical Amps
3-Phase
kVA and
kVA
Available
Contin- Trans- 50% Com- Contin- Trans- 100% Com- Contin- Trans- 100% Com- Contin- Trans- 100% Com-
ii
uous former Motor bined uous former Motor bined uous former Motor bined uous former Motor bined
Impedance from Current, Current, Current, Current,
Percent Primary Alone Load Alone Load  Alone  Load  Alone  Load 
Amps Amps Amps Amps
System
  
1
300 50,000 834 14,900 1700 16,600 722 12,900 2900 15,800 361 6400 1400 7800 289 5200 1200 6400
5% 100,000 834 15,700 1700 17,400 722 13,600 2900 16,500 361 6800 1400 8200 289 5500 1200 6700
150,000 834 16,000 1700 17,700 722 13,900 2900 16,800 361 6900 1400 8300 289 5600 1200 6800 2
250,000 834 16,300 1700 18,000 722 14,100 2900 17,000 361 7000 1400 8400 289 5600 1200 6800
500,000 834 16,500 1700 18,200 722 14,300 2900 17,200 361 7100 1400 8500 289 5700 1200 6900
Unlimited 834 16,700 1700 18,400 722 14,400 2900 17,300 361 7200 1400 8600 289 5800 1200 7000 3
500 50,000 1388 21,300 2800 25,900 1203 20,000 4800 24,800 601 10,000 2400 12,400 481 8000 1900 9900
5% 100,000 1388 25,200 2800 28,000 1203 21,900 4800 26,700 601 10,900 2400 13,300 481 8700 1900 10,600
150,000 1388 26,000 2800 28,800 1203 22,500 4800 27,300 601 11,300 2400 13,700 481 9000 1900 10,900
250,000 1388 26,700 2800 29,500 1203 23,100 4800 27,900 601 11,600 2400 14,000 481 9300 1900 11,200
4
500,000 1388 27,200 2800 30,000 1203 23,600 4800 28,400 601 11,800 2400 14,200 481 9400 1900 11,300
Unlimited 1388 27,800 2800 30,600 1203 24,100 4800 28,900 601 12,000 2400 14,400 481 9600 1900 11,500
750 50,000 2080 28,700 4200 32,900 1804 24,900 7200 32,100 902 12,400 3600 16,000 722 10,000 2900 12,900 5
5.75% 100,000 2080 32,000 4200 36,200 1804 27,800 7200 35,000 902 13,900 3600 17,500 722 11,100 2900 14,000
150,000 2080 33,300 4200 37,500 1804 28,900 7200 36,100 902 14,400 3600 18,000 722 11,600 2900 14,500
250,000 2080 34,400 4200 38,600 1804 29,800 7200 37,000 902 14,900 3600 18,500 722 11,900 2900 14,800 6
500,000 2080 35,200 4200 39,400 1804 30,600 7200 37,800 902 15,300 3600 18,900 722 12,200 2900 15,100
Unlimited 2080 36,200 4200 40,400 1804 31,400 7200 38,600 902 15,700 3600 19,300 722 12,600 2900 15,500
1000
5.75%
50,000
100,000
2776
2776
35,900
41,200
5600
5600
41,500 2406
46,800 2406
31,000
35,600
9800
9800
40,600 1203
45,200 1203
15,500
17,800
4800
4800
20,300
22,600
962
962
12,400
14,300
3900
3900
16,300
18,200
7
150,000 2776 43,300 5600 48,900 2406 37,500 9800 47,100 1203 18,700 4800 23,500 962 15,000 3900 18,900
250,000 2776 45,200 5600 50,800 2406 39,100 9800 48,700 1203 19,600 4800 24,400 962 15,600 3900 19,500
500,000 2776 46,700 5600 52,300 2406 40,400 9800 50,000 1203 20,200 4800 25,000 962 16,200 3900 20,100 8
Unlimited 2776 48,300 5600 53,900 2406 41,800 9800 51,400 1203 20,900 4800 25,700 962 16,700 3900 20,600
1500 50,000 4164 47,600 8300 55,900 3609 41,200 14,400 55,600 1804 20,600 7200 27,800 1444 16,500 5800 22,300
5.75% 100,000 4164 57,500 8300 65,800 3609 49,800 14,400 64,200 1804 24,900 7200 32,100 1444 20,000 5800 25,800 9
150,000 4164 61,800 8300 70,100 3609 53,500 14,400 57,900 1804 26,700 7200 33,900 1444 21,400 5800 27,200
250,000 4164 65,600 8300 73,900 3609 56,800 14,400 71,200 1804 28,400 7200 35,600 1444 22,700 5800 28,500
500,000 4164
Unlimited 4164
68,800
72,500
8300
8300
77,100 3609
80,800 3609
59,600
62,800
14,400
14,400
74,000 1804
77,200 1804
29,800
31,400
7200
7200
37,000 1444
38,600 1444
23,900
25,100
5800
5800
29,700
30,900
10
2000 50,000 — — — — — — — — 2406 24,700 9600 34,300 1924 19,700 7800 27,500
5.75% 100,000 — — — — — — — — 2406 31,000 9600 40,600 1924 24,800 7800 32,600
150,000 — — — — — — — — 2406 34,000 9600 43,600 1924 27,200 7800 35,000 11
250,000 — — — — — — — — 2406 36,700 9600 46,300 1924 29,400 7800 37,200
500,000 — — — — — — — — 2406 39,100 9600 48,700 1924 31,300 7800 39,100
Unlimited — — — — — — — — 2406 41,800 9600 51,400 1924 33,500 7800 41,300 12
2500 50,000 — — — — — — — — 3008 28,000 12,000 40,000 2405 22,400 9600 32,000
5.75% 100,000 — — — — — — — — 3008 36,500 12,000 48,500 2405 29,200 9600 38,800
150,000
250,000 —
— —













3008
3008
40,500
44,600
12,000
12,000
52,500 2405
56,600 2405
32,400
35,600
9600
9600
42,000
45,200
13
500,000 — — — — — — — — 3008 48,100 12,000 60,100 2405 38,500 9600 48,100
Unlimited — — — — — — — — 3008 52,300 12,000 64,300 2405 41,800 9600 51,400
3000 50,000 — — — — — — — — 3609 30,700 14,000 44,700 2886 24,600 11,500 36,100
14
5.75% 100,000 — — — — — — — — 3609 41,200 14,000 55,200 2886 33,000 11,500 44,500
150,000 — — — — — — — — 3609 46,600 14,000 60,600 2886 37,300 11,500 48,800
250,000 — — — — — — — — 3609 51,900 14,000 65,900 2886 41,500 11,500 53,000 15
500,000 — — — — — — — — 3609 56,800 14,000 70,800 2886 45,500 11,500 57,000
Unlimited — — — — — — — — 3609 62,800 14,000 76,800 2886 50,200 11,500 61,700
3750
5.75%
50,000
100,000
















4511
4511
34,000
47,500
18,000
18,000
52,000 3608
65,500 3608
27,200
38,000
14,400
14,400
41,600
52,400
16
150,000 — — — — — — — — 4511 54,700 18,000 72,700 3608 43,700 14,400 58,100
250,000 — — — — — — — — 4511 62,200 18,000 80,200 3608 49,800 14,400 64,200
500,000 — — — — — — — — 4511 69,400 18,000 87,400 3608 55,500 14,400 69,900 17
Unlimited — — — — — — — — 4511 78,500 18,000 96,500 3608 62,800 14,400 77,200
 Short circuit capacity values shown correspond to kVA and impedances shown in this table. For impedances other than these, short circuit currents
are inversely proportional to impedance. 18
 The motor’s short circuit current contributions are computed on the basis of motor characteristics that will give four times normal current.
For 208 volts, 50% motor load is assumed while for other voltages 100% motor load is assumed. For other percentages, the motor short circuit
current will be in direct proportion. 19

20

21

CA08104001E For more information visit: www.eaton.com


1.5-10 Power Distribution Systems
Reference Data January 2008
Sheet 01 100
Transformer Full Load Amperes and Impedances

Table 1.5-5. Transformer Full-Load Current, 3-Phase, Self-Cooled Ratings


i Voltage, Line-to-Line
kVA 208 240 480 600 2,400 4,160 7,200 12,000 12,470 13,200 13,800 22,900 34,400
ii 30 83.3 72.2 36.1 28.9 7.22 4.16 2.41 1.44 1.39 1.31 1.26 0.75 0.50
45 125 108 54.1 43.3 10.8 6.25 3.61 2.17 2.08 1.97 1.88 1.13 0.76
75 208 180 90.2 72.2 18.0 10.4 6.01 3.61 3.47 3.28 3.14 1.89 1.26
1 112-1/2
150
312
416
271
361
135
180
108
144
27.1
36.1
15.6
20.8
9.02
12.0
5.41
7.22
5.21
6.94
4.92
6.56
4.71
6.28
2.84
3.78
1.89
2.52
225 625 541 271 217 54.1 31.2 18.0 10.8 10.4 9.84 9.41 5.67 3.78
300 833 722 361 289 72.2 41.6 24.1 14.4 13.9 13.1 12.6 7.56 5.04
2 500 1388 1203 601 481 120 69.4 40.1 24.1 23.1 21.9 20.9 12.6 8.39
750 2082 1804 902 722 180 104 60.1 36.1 34.7 32.8 31.4 18.9 12.6
1000 2776 2406 1203 962 241 139 80.2 48.1 46.3 43.7 41.8 25.2 16.8
3 1500 4164 3608 1804 1443 361 208 120 72.2 69.4 65.6 62.8 37.8 25.2
2000 — 4811 2406 1925 481 278 160 96.2 92.6 87.5 83.7 50.4 33.6
2500 — — 3007 2406 601 347 200 120 116 109 105 63.0 42.0
4 3000
3750




3609
4511
2887
3608
722
902
416
520
241
301
144
180
139
174
131
164
126
157
75.6
94.5
50.4
62.9
5000 — — — 4811 1203 694 401 241 231 219 209 126 83.9
7500 — — — — 1804 1041 601 361 347 328 314 189 126
5 10,000 — — — — 2406 1388 802 481 463 437 418 252 168

10

11

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-11
January 2008 Reference Data
Sheet 01 101
Impedances Data

Approximate Impedance Data Table 1.5-9. 600 Volt Primary Class 3-Phase Table 1.5-11. 600 Volt Primary Class 3-Phase
Table 1.5-6. Typical Impedances —
NEMA TP-1 Energy Efficient Dry-Type NEMA TP-1 Energy Efficient Dry-Type i
Distribution Transformers, Aluminum Wound Distribution Transformers, Copper Wound
3-Phase Transformers Liquid-Filled 
kVA %Z %R %X X/R kVA %Z %R %X X/R
kVA Liquid-Filled
150°C Rise Aluminum 150°C Rise Copper
ii
Network Padmount
15 4.7 4.5 1.5 0.32 15 4.7 4.0 2.4 0.62
30 4.6 3.4 3.1 0.92 30 3.8 3.0 2.3 0.78
37.5
45



— 45 5.2 3.7 3.7 0.99 45 4.7 3.4 3.2 0.96
1
50 — — 75 5.0 3.0 4.0 1.34 75 4.4 2.7 3.4 1.25
75 — 3.4 112.5 5.7 2.9 4.9 1.67 112.5 5.0 2.3 4.4 1.94
112.5 — 3.2 150 4.9 2.5 4.2 1.65 150 4.3 2.5 3.5 1.40 2
150 — 2.4
225 5.3 2.4 4.7 2.00 225 6.4 2.1 6.1 2.94
225 — 3.3 300 5.1 2.2 4.6 2.11 300 5.7 2.0 5.3 2.65
300 5.00 3.4 500 7.7 1.7 7.5 4.39 500 7.1 1.1 7.0 6.36 3
500 5.00 4.6
750 8.0 1.4 7.8 5.43 750 8.2 0.8 8.1 10.13
750 5.00 5.75
115°C Rise Aluminum 115°C Rise Copper
1000
1500
5.00
7.00
5.75
5.75 15 4.3 4.1 1.1 0.27 15 4.7 3.9 2.7 0.71
4
2000 7.00 5.75 30 4.0 3.6 1.8 1.50 30 4.1 2.6 3.2 1.25
2500 7.00 5.75 45 4.6 2.7 3.8 1.39 45 4.3 2.2 3.7 1.71
3000 — 6.50 75 5.5 2.7 4.8 1.79 75 5.0 2.8 4.1 1.45
5
3750 — 6.50 112.5 5.6 2.7 5.0 1.86 112.5 5.3 2.1 4.9 2.36
5000 — 6.50 150 5.1 2.2 4.6 2.11 150 4.1 1.6 3.7 2.26
 Values are typical. For guaranteed values, 225 6.6 2.1 6.3 3.01 225 6.4 1.8 6.2 3.45
6
refer to transformer manufacturer. 300 5.3 2.1 4.9 2.38 300 5.1 1.8 4.8 2.63
500 6.5 1.1 6.4 5.80 500 6.9 1.0 6.7 6.70
Table 1.5-7. 15 kV Class Primary — 80°C Rise Aluminum 80°C Rise Copper 7
Oil Liquid-Filled Substation Transformers 15 3.0 2.4 1.8 0.76 15 2.1 1.7 1.3 0.80
30 3.4 2.4 2.5 1.06 30 3.0 2.1 2.2 1.04
kVA %Z %R %X X/R
45 3.3 1.6 2.9 1.77 45 4.2 1.9 3.8 1.97 8
65°C Rise
75 4.3 1.9 3.9 1.99 75 3.9 1.5 3.6 2.31
112.5 5.00 1.71 4.70 2.75 112.5 4.2 1.9 3.8 2.03 112.5 4.0 1.5 3.7 2.58
150
225
5.00
5.00
1.88
1.84
4.63
4.65
2.47
2.52
150 4.8 1.4 4.6 3.2 150 4.2 1.6 3.9 2.38 9
225 5.5 1.4 5.3 3.76 225 3.8 1.1 3.6 3.21
300 5.00 1.35 4.81 3.57
300 6.1 1.4 5.9 4.13 300 6.2 1.0 6.1 6.41
500 5.00 1.50 4.77 3.18
750 5.75 1.41 5.57 3.96 500 5.3 0.8 5.3 6.45 500 5.2 0.6 5.2 8.09 10
1000 5.75 1.33 5.59 4.21 Note: Values are typical. Measurements at Note: Values are typical. Measurements at
1500 5.75 1.12 5.64 5.04
2000 5.75 0.93 5.67 6.10 temperature rise +20ºC. temperature rise +20ºC. 11
2500 5.75 0.86 5.69 6.61
Table 1.5-10. 600 Volt Primary Class
NEMA Type TP-1 Dry-Type Transformers 12
Table 1.5-8. 15 kV Class Primary —
Dry-Type Substation Transformers kVA Temperature Rise Impedance

kVA %Z %R %X X/R 300 80 3.16 at 100ºC


150°C Rise 300 115 3.03 at 135ºC 13
300 150 7.06 at 170ºC
300 4.50 2.87 3.47 1.21
500 115 5.97 at 135ºC
500
750
5.75
5.75
2.66
2.47
5.10
5.19
1.92
2.11 500 150 6.04 at 170ºC 14
1000 5.75 2.16 5.33 2.47 750 115 7.21 at 135ºC
1500 5.75 1.87 5.44 2.90 750 150 No Test
2000 5.75 1.93 5.42 2.81 15
2500 5.75 1.74 5.48 3.15
80°C Rise
16
300 4.50 1.93 4.06 2.10
500 5.75 1.44 5.57 3.87
750 5.75 1.28 5.61 4.38
1000 5.75 0.93 5.67 6.10
17
1500 5.75 0.87 5.68 6.51
2000 5.75 0.66 5.71 8.72
2500 5.75 0.56 5.72 10.22 18

19

20

21

CA08104001E For more information visit: www.eaton.com


1.5-12 Power Distribution Systems
Reference Data January 2008
Sheet 01 102
Transformer Losses

Approximate Transformer Loss Data Table 1.5-14. 600 Volt Primary Class Dry-Type Transformer Losses at Reduced Loads
i Table 1.5-12. 15 kV Class Primary —
Distribution Class NEMA TP-1 Information on losses based on actual
Oil Liquid-Filled Substation Transformers kVA No Load Full Load transformer test data can be obtained
Watts Loss Watts Loss from the manufacturer. Transformer
ii kVA No Load Full Load
150°C Rise manufacturers provide no load watt
Watts Loss Watts Loss
15 95 673 losses and total watt losses in accor-
65°C Rise dance with ANSI standards. The
30 165 1020
1 112.5 550 2470 45 200 1656 calculated difference between the
150 545 3360
75 300 2239 no load losses and the total losses
225 650 4800
112.5 400 3291 are typically described as the load
2 300 950 5000 150 530 3824 losses. Although transformer coils
500 1200 8700
750 1600 12,160
225 650 5300 are manufactured with either aluminum
300 830 6600 or copper conductors, the industry
3 1000 1800 15,100 500 1400 8523
has sometimes referred to these load
1500 3000 19,800
750 1800 10,822 losses as the “copper losses.”
2000 4000 22,600
115°C Rise
4 2500 4500 26,000
15 100 619
Transformer losses for various loading
30 165 1071 can be estimated in the following
Table 1.5-13. 15 kV Class Primary — manner. The no load watt losses of the
45 210 1216
5 Dry-Type Substation Transformers
75 290 2020 transformer are due to magnetization
kVA No Load Full Load 112.5 440 2994 and are present whenever the trans-
Watts Loss Watts Loss 150 530 3287 former is energized. The load watt
6 150°C Rise 225 690 4698 losses are the difference between the
300 1600 10,200 300 830 6200 no load watt losses and the full load
500 1900 15,200 500 1650 5593 watt losses. The load watt losses are
7 750 2700 21,200 80°C Rise proportional to I2R and can be esti-
1000 3400 25,000 15 165 362 mated to vary with the transformer
1500 4500 32,600 30 180 709 load by the square of the load current.
8 2000 5700 44,200 45 290 732
2500 7300 50,800 75 360 1458
For example, the approximate watts
80°C Rise 112.5 470 2095 loss data for a 1000 kVA oil-filled
9 300 1800 7600
150 650 2131 substation transformer is shown in
500 2300 9500 225 830 3154 the table as having 1,800 watts no
750 3400 13,000 300 1100 4281 load losses and 15,100 watts full load
10 1000 4200 13,500
500 1800 4086 losses, so the load losses are approxi-
1500 5900 19,000 mately 13,300 watts (15,100 – 1,800).
2000 6900 20,000 Note: Loss and efficiency data shown are The transformer losses can be calcu-
11 2500 7200 21,200
for transformers that meet NEMA TP-1 and
federally mandated energy efficiency levels.
lated for various loads as follows.
NEMA TP-1 establishes minimum operating At 0% load:
efficiencies for each transformer kVA rating
12 at reduced loading equal to 35% of the
1,800 watts
transformer base kVA. The 35% loading At 50% load:
level reflects the results of field studies
13 which show the actual overage load on 1,800 watts + (13,300)(.5)2 =
installed distribution transformers is far 1,800 watts + 3,325 watts = 5,125 watts
below their full load rating.
At 100% load:
14 1,800 watts + 13,300 watts = 15,100 watts
At 110% load:
15 1,800 watts + (13,300)(1.1)2 =
1,800 watts + 16,093 watts = 17,893 watts
16 Since transformer losses vary between
designs and manufacturers, additional
losses such as from cooling fans can
17 be ignored for these approximations.
Note: 1 watthour = 3.413 Btu.
18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-13
January 2008 Reference Data
Sheet 01 103
Power Equipment Losses and Enclosures/Knockout Dimensions

Power Equipment Losses Enclosures


Table 1.5-15. Power Equipment Losses The following are reproduced from NEMA 250.
i
Equipment Watts Table 1.5-16. Comparison of Specific Applications of Enclosures for Indoor Nonhazardous Locations
Loss
Provides a Degree of Protection Against the Type of Enclosures
ii
Medium Voltage Switchgear (Indoor, 5 and 15 kV) Following Environmental Conditions 1 2 4 4X 5 6 6P 12 12K 13
1200 Ampere Breaker 600
2000 Ampere Breaker 1400 Incidental Contact with the Enclosed Equipment X X X X X X X X X X 1
3000 Ampere Breaker 2100 Falling Dirt X X X X X X X X X X
4000 Ampere Breaker 3700 Falling Liquids and Light Splashing — X X X X X X X X X
Medium Voltage Switchgear (Indoor, 5 and 15 kV) Circulating Dust, Lint, Fibers, and Flyings  — — X X — X X X X X 2
Settling Airborne Dust, Lint, Fibers, and Flyings  — — X X X X X X X X
600 Ampere Unfused Switch 500 Hosedown and Splashing Water — — X X — X X — — —
1200 Ampere Unfused Switch 750
100 Ampere CL Fuses 840 Oil and Coolant Seepage
Oil or Coolant Spraying and Splashing














X

X

X
X
3
Medium Voltage Starters (Indoor, 5 kV) Corrosive Agents — — — X — — X — — —
400 Ampere Starter FVNR 600 Occasional Temporary Submersion — — — — — X X — — —
800 Ampere Starter FVNR 1000 Occasional Prolonged Submersion — — — — — — X — — — 4
600 Ampere Fused Switch 500  These enclosures may be ventilated.
1200 Ampere Fused Switch 800  These fibers and flying are nonhazardous materials and are not considered the Class III type
Low Voltage Switchgear (Indoor, 480 Volts) ignitable fibers or combustible flyings. For Class III type ignitable fibers or combustible flyings 5
800 Ampere Breaker 400 see the National Electrical Code, Article 500.
1600 Ampere Breaker 1000
2000 Ampere Breaker 1500 Table 1.5-17. Comparison of Specific Applications of Enclosures for Outdoor Nonhazardous Locations 6
3200 Ampere Breaker 2400 Provides a Degree of Protection Against the Type of Enclosures
4000 Ampere Breaker 3000 Following Environmental Conditions 3 3R  3S 4 4X 6 6P
5000 Ampere Breaker 4700 7
Fuse Limiters – 800 Ampere CB 200 Incidental Contact with the Enclosed Equipment X X X X X X X
Fuse Limiters – 1600 Ampere CB 500 Rain, Snow and Sleet  X X X X X X X
Sleet  — — X — — — —
Fuse Limiters – 2000 Ampere CB 750
Windblown Dust X — X X X X X
8
Fuse Truck – 3200 Ampere CB 3600
Hosedown — — — X X X X
Fuse Truck – 4000 Ampere CB 4500
Corrosive Agents — — — — X — X
Structures – 3200 Ampere
Structures – 4000 Ampere
4000
5000
Occasional Temporary Submersion — — — — — X X 9
Occasional Prolonged Submersion — — — — — — X
Structures – 5000 Ampere 7000
 These enclosures may be ventilated.
High Resistance Grounding 1200  External operating mechanisms are not required to be operable when the enclosure is ice covered. 10
Panelboards (Indoor, 480 Volts)  External operating mechanisms are operable when the enclosure is ice covered.
225 Ampere, 42 Circuit 300
Low Voltage Busway (Indoor, Copper, 480 Volts) Table 1.5-18. Comparison of Specific Applications of Enclosures for Indoor Hazardous Locations 11
800 Ampere 44 per foot Provides a Degree of Protection Against Class Enclosure Types Enclosure Type
1200 Ampere 60 per foot Atmospheres Typically Containing 7 and 8, Class I Groups  9, Class II Groups 
1350 Ampere 66 per foot
(For Complete Listing, See NFPA 497M) A B C D E F G 10 12
1600 Ampere 72 per foot Acetylene I X — — — — — — —
2000 Ampere 91 per foot Hydrogen, Manufactured Gas I — X — — — — — —
2500 Ampere 103 per foot Diethyl Ether, Ethylene, Cyclopropane I — — X — — — — — 13
3200 Ampere 144 per foot Gasoline, Hexane, Butane, Naphtha, Propane,
4000 Ampere 182 per foot Acetone, Toluene, Isoprene I — — — X — — — —
5000 Ampere 203 per foot Metal Dust II — — — — X — — — 14
Motor Control Centers (Indoor, 480 Volts) Carbon Black, Coal Dust, Coke Dust II — — — — — X — —
Flour, Starch, Grain Dust II — — — — — — X —
NEMA Size 1 Starter 39 Fibers, Flyings 
NEMA Size 2 Starter 56 Methane with or without Coal Dust
III —
MSHA —










X


X
15
NEMA Size 3 Starter 92
 For Class III type ignitable fibers or combustible flyings see the National Electrical Code, Article 500.
NEMA Size 4 Starter 124 
NEMA Size 5 Starter 244
Due to the characteristics of the gas, vapor, or dust, a product suitable for one Class or Group may
not be suitable for another Class or Group unless so marked on the product.
16
Structures 200
Note: If the installation is outdoors and/or additional protection is required by Tables 1.5-16 and
Adjustable Frequency Drives (Indoor, 480 Volts) 1.5-17, a combination-type enclosure is required.
Adjustable Frequency Drives > 96% 17
efficiency

Note: The information provided on power 18


equipment losses is generic data intended
to be used for sizing of HVAC equipment.
19

20

21

CA08104001E For more information visit: www.eaton.com


1.5-14 Power Distribution Systems
Reference Data January 2008
Sheet 01 104
Conductor Resistance, Reactance, Impedance

Average Characteristics of diameters, and the like. Therefore, ■ For interlocked armored cable, use
i 600-Volt Conductors — data for medium voltage cables should magnetic conduit data for steel
be obtained from the manufacturer of armor and non-magnetic conduit
Ohms per 1000 Feet (305 m) the cable to be used. data for aluminum armor.
ii The tables below are average charac- 2 2
Application Notes ■ Z = X +R
teristics based on data from IEEE Stan-
dard 141-1993. Values from different ■ Resistance and reactance are phase- ■ For busway impedance data, see
1 sources vary because of operating to-neutral values, based on 60 Hz ac, Section 21 of this catalog.
temperatures, wire stranding, insula- 3-phase, 4-wire distribution, in ■ For PF (power factor) values less
tion materials and thicknesses, overall ohms per 100 feet (30 m) of circuit than 1.0, the effective impedance Z e
2 diameters, random lay of multiple con- length (not total conductor lengths). is calculated from
ductors in conduit, conductor spacing, ■ Based upon conductivity of 100% Z e = R × PF + X sin (arc cos PF)
and other divergences in materials,
3 test conditions and calculation meth-
for copper, 61% for aluminum.
■ For copper cable data, resistance
■ Based on conductor temperatures based on tinned copper at 60 Hz;
ods. These tables are for 600-volt 5 kV
of 75°C. Reactance values will have 600V and 5 kV nonshielded cable
and 15 kV conductors, at an average
4 temperature of 75°C. Other parameters
negligible variation with tempera- based on varnished cambric insula-
ture. Resistance of both copper tion; 5 kV shielded and 15 kV cable
are listed in the notes. For medium
and aluminum conductors will be based on neoprene insulation.
voltage cables, differences among
5 manufacturers are considerably
approximately 5% lower at 60°C or
■ For aluminum cable data, cable is
5% higher at 90°C. Data shown in
greater because of the wider variations cross-linked polyethylene insulated.
tables may be used without signifi-
in insulation materials and thick-
6 nesses, shielding, jacketing, overall
cant error between 60°C and 90°C.

7 Table 1.5-19. 60 Hz Impedance Data for 3-Phase Copper Cable Circuits, in Approximate Ohms per 1000 Feet (305 m) at 75ºC (a) Three Single Conductors
Wire Size, In Magnetic Duct In Nonmagnetic Duct
AWG or 600 V and 5 kV Nonshielded 5 kV Shielded and 15 kV 600 V and 5 kV Nonshielded 5 kV Shielded and 15 kV
8 kcmil
R X Z R X Z R X Z R X Z

8 .811 .0754 .814 .811 .0860 .816 .811 .0603 .813 .811 .0688 .814
8 (Solid) .786 .0754 .790 .786 .0860 .791 .786 .0603 .788 .786 .0688 .789
9 6 .510 .0685 .515 .510 .0796 .516 .510 .0548 .513 .510 .0636 .514
6 (Solid) .496 .0685 .501 .496 .0796 .502 .496 .0548 .499 .496 .0636 .500
4 .321 .0632 .327 .321 .0742 .329 .321 .0506 .325 .321 .0594 .326
10 4 (Solid) .312 .0632 .318 .312 .0742 .321 .312 .0506 .316 .312 .0594 .318
2 .202 .0585 .210 .202 .0685 .214 .202 .0467 .207 .202 .0547 .209
1 .160 .0570 .170 .160 .0675 .174 .160 .0456 .166 .160 .0540 .169
11 1/0 .128 .0540 .139 .128 .0635 .143 .127 .0432 .134 .128 .0507 .138
2/0 .102 .0533 .115 .103 .0630 .121 .101 .0426 .110 .102 .0504 .114
3/0 .0805 .0519 .0958 .0814 .0605 .101 .0766 .0415 .0871 .0805 .0484 .0939
12 250
4/0 .0640
.0552
.0497
.0495
.0810
.0742
.0650
.0557
.0583
.0570
.0929
.0797
.0633
.0541
.0398
.0396
.0748
.0670
.0640
.0547
.0466
.0456
.0792
.0712
300 .0464 .0493 .0677 .0473 .0564 .0736 .0451 .0394 .0599 .0460 .0451 .0644
350 .0378 .0491 .0617 .0386 .0562 .0681 .0368 .0393 .0536 .0375 .0450 .0586
13 400 .0356 .0490 .0606 .0362 .0548 .0657 .0342 .0392 .0520 .0348 .0438 .0559
450 .0322 .0480 .0578 .0328 .0538 .0630 .0304 .0384 .0490 .0312 .0430 .0531
500 .0294 .0466 .0551 .0300 .0526 .0505 .0276 .0373 .0464 .0284 .0421 .0508
14 600 .0257 .0463 .0530 .0264 .0516 .0580 .0237 .0371 .0440 .0246 .0412 .0479
750 .0216 .0495 .0495 .0223 .0497 .0545 .0194 .0356 .0405 .0203 .0396 .0445

15 Note: More tables on Page 1.5-15.

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-15
January 2008 Reference Data
Sheet 01 105
Conductor Resistance, Reactance, Impedance

Table 1.5-20. 60 Hz Impedance Data for 3-Phase Copper Cable Circuits, in Approximate Ohms per 1000 Feet (305 m) at 75ºC (b) Three Conductor Cable
Wire Size, In Magnetic Duct and Steel Interlocked Armor In Nonmagnetic Duct and Aluminum Interlocked Armor i
AWG or 600 V and 5 kV Nonshielded 5 kV Shielded and 15 kV 600 V and 5 kV Nonshielded 5 kV Shielded and 15 kV
kcmil
R X Z R X Z R X Z R X Z
ii
8 .811 .0577 .813 .811 .0658 .814 .811 .0503 .812 .811 .0574 .813
8 (Solid) .786 .0577 .788 .786 .0658 .789 .786 .0503 .787 .786 .0574 .788
6
6 (Solid)
.510
.496
.0525
.0525
.513
.499
.510
.496
.0610
.0610
.514
.500
.510
.496
.0457
.0457
.512
.498
.510
.496
.0531
.0531
.513
.499
1
4 .321 .0483 .325 .321 .0568 .326 .321 .0422 .324 .321 .0495 .325
4 (Solid)
2
.312
.202
.0483
.0448
.316
.207
.312
.202
.0508
.0524
.317
.209
.312
.202
.0422
.0390
.315
.206
.312
.202
.0495
.0457
.316
.207
2
1 .160 .0436 .166 .160 .0516 .168 .160 .0380 .164 .160 .0450 .166
1/0 .128 .0414 .135 .128 .0486 .137 .127 .0360 .132 .128 .0423 .135
2/0 .102 .0407 .110 .103 .0482 .114 .101 .0355 .107 .102 .0420 .110 3
3/0 .0805 .0397 .0898 .0814 .0463 .0936 .0766 .0346 .0841 .0805 .0403 .090
4/0 .0640 .0381 .0745 .0650 .0446 .0788 .0633 .0332 .0715 .0640 .0389 .0749
250 .0552 .0379 .0670 .0557 .0436 .0707 .0541 .0330 .0634 .0547 .0380 .0666 4
300 .0464 .0377 .0598 .0473 .0431 .0640 .0451 .0329 .0559 .0460 .0376 .0596
350 .0378 .0373 .0539 .0386 .0427 .0576 .0368 .0328 .0492 .0375 .0375 .0530
400 .0356 .0371 .0514 .0362 .0415 .0551 .0342 .0327 .0475 .0348 .0366 .0505 5
450 .0322 .0361 .0484 .0328 .0404 .0520 .0304 .0320 .0441 .0312 .0359 .0476
500 .0294 .0349 .0456 .0300 .0394 .0495 .0276 .0311 .0416 .0284 .0351 .0453
600 .0257 .0343 .0429 .0264 .0382 .0464 .0237 .0309 .0389 .0246 .0344 .0422
750 .0216 .0326 .0391 .0223 .0364 .0427 .0197 .0297 .0355 .0203 .0332 .0389 6
Table 1.5-21. 60 Hz Impedance Data for 3-Phase Aluminum Cable Circuits, in Approximate Ohms per 1000 Feet (305 m) at 90ºC (a) Three Single Conductors
Wire Size, In Magnetic Duct In Nonmagnetic Duct
7
AWG or 600 V and 5 kV Nonshielded 5 kV Shielded and 15 kV 600 V and 5 kV Nonshielded 5 kV Shielded and 15 kV
kcmil
R X Z R X Z R X Z R X Z 8
6 .847 .053 .849 — — — .847 .042 .848 — — —
4 .532 .050 .534 .532 .068 .536 .532 .040 .534 .532 .054 .535
2 .335 .046 .338 .335 .063 .341 .335 .037 .337 .335 .050 .339 9
1 .265 .048 .269 .265 .059 .271 .265 .035 .267 .265 .047 .269
1/0 .210 .043 .214 .210 .056 .217 .210 .034 .213 .210 .045 .215
2/0
3/0
.167
.133
.041
.040
.172
.139
.167
.132
.055
.053
.176
.142
.167
.133
.033
.037
.170
.137
.167
.132
.044
.042
.173
.139
10
4/0 .106 .039 .113 .105 .051 .117 .105 .031 .109 .105 .041 .113
250
300
.0896
.0750
.0384
.0375
.0975
.0839
.0892
.0746
.0495
.0479
.102
.0887
.0894
.0746
.0307
.0300
.0945
.0804
.0891
.0744
.0396
.0383
.0975
.0837
11
350 .0644 .0369 .0742 .0640 .0468 .0793 .0640 .0245 .0705 .0638 .0374 .0740
400 .0568 .0364 .0675 .0563 .0459 .0726 .0563 .0291 .0634 .0560 .0367 .0700
500 .0459 .0355 .0580 .0453 .0444 .0634 .0453 .0284 .0535 .0450 .0355 .0573 12
600 .0388 .0359 .0529 .0381 .0431 .0575 .0381 .0287 .0477 .0377 .0345 .0511
700 .0338 .0350 .0487 .0332 .0423 .0538 .0330 .0280 .0433 .0326 .0338 .0470
750 .0318 .0341 .0466 .0310 .0419 .0521 .0309 .0273 .0412 .0304 .0335 .0452 13
1000 .0252 .0341 .0424 .0243 .0414 .0480 .0239 .0273 .0363 .0234 .0331 .0405

Table 1.5-22. 60 Hz Impedance Data for 3-Phase Aluminum Cable Circuits, in Approximate Ohms per 1000 Feet (305 m) at 90ºC (b) Three Conductor Cable 14
Wire Size, In Magnetic Duct and Steel Interlocked Armor In Nonmagnetic Duct and Aluminum Interlocked Armor
AWG or 600 V and 5 kV Nonshielded 5 kV Shielded and 15 kV 600 V and 5 kV Nonshielded 5 kV Shielded and 15 kV
kcmil
R X Z R X Z R X Z R X Z 15
6 .847 .053 .849 — — — .847 .042 .848 — — —
4
2
.532
.335
.050
.046
.534
.338

.335

.056

.340
.532
.335
.040
.037
.534
.337

.335

.045

.338
16
1 .265 .048 .269 .265 .053 .270 .265 .035 .267 .265 .042 .268
1/0 .210 .043 .214 .210 .050 .216 .210 .034 .213 .210 .040 .214
2/0 .167 .041 .172 .167 .049 .174 .167 .033 .170 .167 .039 .171 17
3/0 .133 .040 .139 .133 .048 .141 .133 .037 .137 .132 .038 .138
4/0 .106 .039 .113 .105 .045 .114 .105 .031 .109 .105 .036 .111
250 .0896 .0384 .0975 .0895 .0436 .100 .0894 .0307 .0945 .0893 .0349 .0959 18
300 .0750 .0375 .0839 .0748 .0424 .0860 .0746 .0300 .0804 .0745 .0340 .0819
350 .0644 .0369 .0742 .0643 .0418 .0767 .0640 .0245 .0705 .0640 .0334 .0722
400 .0568 .0364 .0675 .0564 .0411 .0700 .0563 .0291 .0634 .0561 .0329 .0650
19
500 .0459 .0355 .0580 .0457 .0399 .0607 .0453 .0284 .0535 .0452 .0319 .0553
600 .0388 .0359 .0529 .0386 .0390 .0549 .0381 .0287 .0477 .0380 .0312 .0492
700 .0338 .0350 .0487 .0335 .0381 .0507 .0330 .0280 .0433 .0328 .0305 .0448
750 .0318 .0341 .0466 .0315 .0379 .0493 .0309 .0273 .0412 .0307 .0303 .0431 20
1000 .0252 .0341 .0424 .0248 .0368 .0444 .0239 .0273 .0363 .0237 .0294 .0378

21

CA08104001E For more information visit: www.eaton.com


1.5-16 Power Distribution Systems
Reference Data January 2008
Sheet 01 106
Conductor Ampacities

Current Carrying Capacities of Copper and Aluminum and Copper-Clad Aluminum Conductors
i From National Electrical Code (NEC), 2005 Edition (NFPA70-2005)
Table 1.5-23. Allowable Ampacities of Insulated Conductors Rated 0 – 2000 Volts, 60°C to 90°C (140°F to 194°F). Not more than three current-carrying
ii conductors in raceway, cable or earth (directly buried), based on ambient temperature of 30°C (86°F)
Size Temperature Rating of Conductor (See Table 310.16) Size
AWG or 60°C (140°F) 75°C (167°F) 90°C (194°F) 60°C (140°F) 75°C (167°F) 90°C (194°F) AWG or
1 kcmil Types Types kcmil

TW, UF RHW, THHW, TBS, SA, SIS, TW, UF RHW, THHW, TBS, SA, SIS,
2 THW, THWN,
XHHW, USE, ZW
FEP, FEPB, MI,
RHH, RHW-2,
THW, THWN,
XHHW, USE
THHN, THHW,
THW-2, THWN-2,
THHN, THHW, RHH, RHW-2,
THW-2, THWN-2, USE-2, XHH,
3 USE-2, XHH, XHHW, XHHW-2,
XHHW, XHHW-2, ZW-2
ZW-2
4 Copper Aluminum or Copper-Clad Aluminum

18 — — 14 — — — —
16 — — 18 — — — —
5 14  20 20 25 — — — —
12  25 25 30 20 20 25 12 
10  30 35 40 25 30 35 10 
6 8 40 50 55 30 40 45 8
6 55 65 75 40 50 60 6
4 70 85 95 55 65 75 4
7 3 85 100 110 65 75 85 3
2 95 115 130 75 90 100 2
1 110 130 150 85 100 115 1
8 1/0 125 150 170 100 120 135 1/0
2/0 145 175 195 115 135 150 2/0
3/0 165 200 225 130 155 175 3/0
9 4/0 195 230 260 150 180 205 4/0
250 215 255 290 170 205 230 250
300 240 285 320 190 230 255 300
10 350 260 310 350 210 250 280 350
400 280 335 380 225 270 305 400
500 320 380 430 260 310 350 500
600 355 420 475 285 340 385 600
11 700 385 460 520 310 375 420 700
750 400 475 535 320 385 435 750
800 410 490 555 330 395 450 800
12 900 435 520 585 355 425 480 900
1000 455 545 615 375 445 500 1000
1250 495 590 665 405 485 545 1250
13 1500 520 625 705 435 520 585 1500
1750 545 650 735 455 545 615 1750
2000 560 665 750 470 560 630 2000
14 Correction Factors
Ambient For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown Ambient
Temperature °C above by the appropriate factor shown below. Temperature °F
15
21 – 25 1.08 1.05 1.04 1.08 1.05 1.04 70 – 77
26 – 30 1.00 1.00 1.00 1.00 1.00 1.00 78 – 86
16 31 – 35 .91 .94 .96 .91 .94 .96 87 – 95
36 – 40 .82 .88 .91 .82 .88 .91 96 – 104
41 – 45 .71 .82 .87 .71 .82 .87 105 – 113
46 – 50 .58 .75 .82 .58 .75 .82 114 – 122
17 51 – 55 .41 .67 .76 .41 .67 .76 123 – 131
56 – 60 — .58 .71 — .58 .71 132 – 140
61 – 70 — .33 .58 — .33 .58 141 – 158
18 71 – 80 — — .41 — — .41 159 – 176
 See NEC Section 240.4 (D).
19 Note: For complete details of using Table 1.5-23, see NEC Article 310 in its entirety.

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-17
January 2008 Reference Data
Sheet 01 107
Conductor Ampacities

Ampacities for Conductors (1) General. For explanation of type (1) Each cable has not more than three
Rated 0 – 2000 Volts letters used in tables and for recog- current-carrying conductors. i
nized sizes of conductors for the
(Excerpts from NEC 310-15) various conductor insulations, see (2) The conductors are 12 AWG copper.
310.13. For installation requirements, (3) Not more than 20 current-carrying ii
(A) General. see 310.1 through 310.10 and the conductors are bundled, stacked,
(1) Tables or Engineering Supervision. various articles of this Code. For or supported on “bridle rings.”
Ampacities for conductors shall be flexible cords, see Table 400.4, 1
permitted to be determined by Table 400.5(A), and Table 400.5(B). A 60 percent adjustment factor shall
tables as provided in 310.15(B) or be applied where the current-carrying
under engineering supervision, as (2) Adjustment Factors. conductors in these cables that are 2
provided in 310.15(C). (a) More Than Three Current-Carrying stacked or bundled longer than 24
Conductors in a Raceway or Cable. inches (600 mm) without maintaining
Note: FPN No. 1: Ampacities provided by
this section do not take voltage drop into Where the number of current- spacing exceeds 20. 3
consideration. See 210.19(A), FPN No. 4, carrying conductors in a raceway (b) More Than One Conduit, Tube, or
for branch circuits and 215.2(A), FPN No. 2, or cable exceeds three, or where
for feeders. single conductors or multiconductor
Raceway. Spacing between con- 4
duits, tubing, or raceways shall be
cables are stacked or bundled longer maintained.
Note: FPN No. 2: For the allowable ampaci- than 600 mm (24 in.) without main-
ties of Type MTW wire, see Table 13.5.1 taining spacing and are not installed Table 1.5-24. NEC (2005) Table 310.15(B)(2)(a) 5
in NFPA 79-2002, Electrical Standard for Adjustment Factors for More than Three Current-
Industrial Machinery.
in raceways, the allowable ampacity
of each conductor shall be reduced Carrying Conductors in a Raceway or Cable
as shown in Table 1.5-24. Each Number of Percent of Values in Tables
6
(2) Selection of Ampacity. Where more
than one calculated or tabulated current-carrying conductor of a Current-Carrying as Adjusted for Ambient
paralleled set of conductors shall Conductors Temperature if Necessary
ampacity could apply for a given
be counted as a current-carrying
7
circuit length, the lowest value shall 4–6 80
be used. conductor. 7–9 70

Exception: Where two different Note: FPN No. 1: See Annex B, Table
10 – 20 50
8
B.310.11, for adjustment factors for more 21 – 30 45
ampacities apply to adjacent portions than three current-carrying conductors in 31 – 40 40
of a circuit, the higher ampacity shall 41 and Above 35
be permitted to be used beyond the
a raceway or cable with load diversity. 9
point of transition, a distance equal to Note: FPN No. 2: See 366.23(A) for correc- (3) Bare or Covered Conductors.
10 feet (3.0 m) or 10 percent of the Where bare or covered conductors
circuit length figured at the higher
tion factors for conductors in sheet metal
auxiliary gutters and 376.22 for correction are used with insulated conductors, 10
ampacity, whichever is less. factors for conductors in metal wireways. their allowable ampacities shall be
limited to those permitted for the
Note: FPN: See 110.14(C) for conductor Exception No. 1: Where conductors of adjacent insulated conductors.
11
temperature limitations due to termination different systems, as provided in 300.3,
provisions. are installed in a common raceway or (4) Neutral Conductor.
cable, the derating factors shown in 12
(B) Tables. Ampacities for conductors (a) A neutral conductor that carries
Table 1.5-24 shall apply only to the only the unbalanced current from
rated 0 to 2000 volts shall be as
number of power and lighting conduc-
specified in the Allowable Ampacity
tors (Articles 210, 215, 220 and 230).
other conductors of the same 13
Table 310.16 through Table 310.19, circuit shall not be required to
and Ampacity Table 310.20 and Exception No. 2: For conductors be counted when applying the
Table 310.21 as modified by (B)(1) installed in cable trays, the provisions provisions of 310.15(B)(2)(a). 14
through (B)(6). of 392.11 shall apply. (b) In a 3-wire circuit consisting of
Note: FPN: Table 310.16 through Table 2-phase wires and the neutral of
310.19 are application tables for use in
Exception No. 3: Derating factors
shall not apply to conductors in a 4-wire, 3-phase, wye-connected
15
determining conductor sizes on loads nipples having a length not exceeding system, a common conductor carries
calculated in accordance with Article 220. approximately the same current as
Allowable ampacities result from consider-
24 inches (600 mm).
the line-to-neutral load currents of
16
ation of one or more of the following: Exception No. 4: Derating factors shall the other conductors and shall be
not apply to underground conductors counted when applying the provi-
(1) Temperature compatibility with entering or leaving an outdoor trench sions of 310.15(B)(2)(a).
17
connected equipment, especially if those conductors have physical pro-
the connection points. tection in the form of rigid metal con- (c) On a 4-wire, 3-phase wye circuit
(2) Coordination with circuit and duit, intermediate metal conduit, or rigid where the major portion of the load 18
system overcurrent protection. nonmetallic conduit having a length consists of nonlinear loads, harmonic
not exceeding 3.05 m (10 ft) and if currents are present in the neutral
(3) Compliance with the requirements the number of conductors does not conductor; the neutral shall there- 19
of product listings or certifications. exceed four. fore be considered a current-
See 110.3(B). carrying conductor.
Exception No. 5: Adjustment factors 20
(4) Preservation of the safety benefits shall not apply to Type AC cable or to (5) Grounding or Bonding Conductor.
of established industry practices Type MC cable without an overall outer A grounding or bonding conductor
and standardized procedures. jacket under the following conditions: shall not be counted when applying 21
the provisions of 310.15(B)(2)(a).

CA08104001E For more information visit: www.eaton.com


1.5-18 Power Distribution Systems
Reference Data January 2008
Sheet 01 108
Formulas and Terms

Table 1.5-25. Formulas for Determining Amperes, hp, kW and kVA


i To Direct Alternating Current
Find Current Single-Phase 2-Phase — 4-Wire  3-Phase
ii Amperes (l) When −−−−−×−−746
−hp −−−− hp × 746
−−−−−−−−−−−−−−−−−−−−−−−
hp × 746
−−−−−−−−−−−−−−−−−−−−−−−−−−−−
hp × 746
−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
Horsepower is Known E × % eff E × % eff × pf 2 × E × % eff × pf 3 × E × % eff × pf
Amperes (l) When kW × 1000 kW × 1000 kW × 1000 kW × 1000
−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−
1 Kilowatts is Known E E × pf 2 × E × pf 3 × E × % pf
Amperes (l) When — kVA × 1000
−−−−−−−−−−−−−−−−−−− kVA × 1000 −−−−−−−−
kVA ×−−1000
−−−−−−
−−−−−−−−−−−−−−−−−−−
kVA is Known E 2×E 3×E
2 Kilowatts I×E
−−−−−−−
l × E × pf
−−−−−−−−−−−−−−
l × E × 2 × pf
−−−−−−−−−−−−−−−−−−−−
l × E × 3 × pf
−−−−−−−−−−−−−−−−−−−−−−
1000 1000 1000 1000
kVA — I×E I×E×2 I×E× 3
−−−−−−− −−−−−−−−−−−− −−−−−−−−−−−−−−−
3 1000 1000 1000
Horsepower (Output) I × E × % eff I × E × % eff × pf I × E × 2 × % eff × pf I × E × 3 × % eff × pf
−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−− −−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−−
746 746 746 746
4  For 2-phase, 3-wire circuits the current in the common conductor is 2 times that in either of the two other conductors.
Note: Units of measurement and definitions for E (volts), I (amperes), and other abbreviations are given below under Common Electrical Terms.

5 Common Electrical Terms How to Compute Power Factor


Ampere (l) = unit of current or rate of flow of electricity
Watts
Determining Watts pf = ----------------------------------------------
6 Volt (E) = unit of electromotive force Volts × Amperes

Ohm (R) = unit of resistance 1. 1. From watthour meter.


Watts = rpm of disc x 60 x Kh
7 E
Ohms law: I = −− (dc or 100% pf)
R
Where Kh is meter constant
Megohm = 1,000,000 ohms
printed on face or nameplate
8 Volt Amperes (VA) = unit of apparent power of meter.
= E × l (single-phase)
If metering transformers are used,
9 = E×l× 3 above must be multiplied by the
Kilovolt Amperes (kVA) = 1000 volt-amperes transformer ratios.
10 Watt (W) = unit of true power 2. Directly from wattmeter reading.
Where:
= VA × pf
11 = .00134 hp Volts = line-to-line voltage as
measured by voltmeter.
Kilowatt (kW) = 1000 watts
12 Power Factor (pf) = ratio of true to apparent power Amperes = current measured in
W kW line wire (not neutral) by ammeter.
= -------- ------------
13 Watthour (Wh)
VA kVA
= unit of electrical work
Table 1.5-26. Temperature Conversion
(F° to C°) C° = 5/9 (F°-32°)
= one watt for one hour (C° to F°) F° = 9/5(C°)+32°
14 = 3.413 Btu C° -15 -10 -5 0 5 10 15 20
= 2,655 foot. lbs. F° 5 14 23 32 41 50 59 68

15 Kilowatt-hour (kWh) = 1000 watthours


Cº 25
F° 77
30
86
35 40 45
95 104 113
50 55
122 131
60
140
C° 65 70 75 80 85 90 95 100
Horsepower (hp) = measure of time rate of doing work
F° 149 158 167 176 185 194 203 212
16 = equivalent of raising 33,000 lbs. one foot. in one minute
= 746 watts 1 Inch = 2.54 centimeters
17 Demand Factor = ratio of maximum demand to the total connected load
1 Kilogram = 2.20 lbs.
1 Square Inch = 1,273,200 circular mills
Diversity Factor = ratio of the sum of individual maximum demands of 1 Circular Mill = .785 square mil
18 the various subdivisions of a system to the maximum
1 Btu = 778 foot. lbs.
demand of the whole system
= 252 calories
19 Load Factor = ratio of the average load over a designated period 1 Year = 8,760 hours
of time to the peak load occurring in that period

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-19
January 2008 Reference Data
Sheet 01 109
Seismic Requirements

Seismic Requirements i
General
Starting more than 15 years ago, ii
Eaton embarked on a comprehensive
program centered around designing
and building electrical distribution 1
and control equipment capable of
meeting and exceeding the seismic
load requirements of the Uniform 2
Building Code (UBC) and California
Building Code (CBC). The entire
program has been updated to also 3
meet the Year 2003 International
Building Code (IBC) unified seismic
requirements. 4
These codes emphasize building
design requirements. Electrical 5
equipment and distribution system
components are considered attach-
ments to the building. The equipment
Uniform Building Code Seismic Zones
6
is acceptable if it can withstand
the seismic event and perform its 0 1 2A 2B 3 4
function immediately afterwards. 7
A cooperative effort with the equip- Those areas within
ment user, the building designer No Minor Moderate Moderate Major Zone 3 determined
damage damage damage damage damage by the proximity to
and the equipment installer ensures
certain major faults 8
that the equipment is correctly
mounted to a foundation that can
withstand the effects of an earthquake. Figure 1.5-1. UBC Seismic Zone Map of the United States 9
Cutler-Hammer electrical distribution Uniform Building Code (UBC) States is shown in Figure 1.5-1
and power control equipment has
been tested and seismically proven The 1997 Uniform Building Code,
(Figure 16-3 of the UBC, Chapter 16).
Ca is taken equal to the maximum
10
for requirements exceeding the UBC, Chapter 16 of Division IV-Earthquake of 0.44 x 1.5 = 0.66.
CBC and the IBC. Over one hundred Design, requires that structures and
different assemblies representing all portions of structures shall be designed Ip: Is the Seismic Importance Factor 11
product lines have been successfully to withstand the seismic ground motion (Table 16-K, page 2-30). It is taken
tested and verified to seismic levels specified in the codes. Section 1632 of as maximum and equal to 1.5.
higher than the maximum seismic the codes — Lateral Force on Elements 12
of Structures, Nonstructural Compo- Wp: Is the Equipment Operating Weight.
requirements specified in the UBC,
CBC and the IBC. The equipment nents and Equipment Supported by Therefore, the maximum theoretical
maintained structural integrity and Structures, and under subsection static seismic loads (including all the
13
demonstrated the ability to function Section 1632.1: General, states that: conservatism possible) are:
before and immediately after the “Elements of structures and their
seismic tests. attachments, permanent nonstructural F p = 4.0 × ( .44 × 1.5 ) × 1.5 × W p 14
components and their attachments,
A technical paper, Earthquake Require- and the attachments for permanent The codes state that the design lateral
ments and Cutler-Hammer Distribution equipment supported by a structure accelerations and resultant loads, deter- 15
and Control Equipment Seismic shall be designed to resist the total mined above, are static loads to be dis-
Capabilities (SA.125.01.S.E), provides design seismic forces prescribed in tributed in proportion to the mass dist-
a detailed explanation of the applicable Section 1632.2.” ribution of the element or component. 16
seismic codes and the Cutler-Hammer Therefore, assuming a uniformly distrib-
program to qualify equipment. Section 1632.2, Design for Total Lateral uted mass, the static loads computed in
The paper may be found at Force, specifies that the total design lat- the above formula are imposed at the 17
www.EatonElectrical.com. Type in eral static seismic force, Fp, is defined C.G. or at conservatively one half the
SA12501SE in document search. as (see equation 32-1 in code, Page 2-18): height of the equipment from its base.
18
F p = 4.0 C a I p W p The complete Response Spectrum
Curve starts at 0.33g at 1.0 Hz, linearly
Where: increases to 2.15g at 2.15 Hz (Ts ). 19
Ca: Is the Seismic Coefficient for Zone 4, The peak spectral accelerations then
Table 16-Q. It is equal to a maximum covers a wide band of frequencies
of 0.44 Na where Na is Near Source up to 11 Hz (To) then gradually 20
Factor and is equal to a maximum decreases to 0.86 g (ZPA) at 33 Hz.
of 1.5 (see Table 16-S, page 2-35). This curve represents the complete
The Seismic Zone Map of the United 1997 UBC Design Response Spectrum. 21

CA08104001E For more information visit: www.eaton.com


1.5-20 Power Distribution Systems
Reference Data January 2008
Sheet 01 110
Seismic Requirements

California Building Code Year 2003 A. Ground Motion


i California Building Code adopted the International Building Code (IBC) According to the code, the first and
1997 UBC as the CBC-Title 24. The seis- most important step in the process is to
On December 9, 1994, the International determine the Maximum Considered
ii mic requirements are basically the same
as described in the UBC. When consider-
Code Council (ICC) was established as Earthquake Spectral Response Accel-
a nonprofit organization dedicated to eration at short periods of 0.2 seconds
ing the maximum seismic requirements, developing a single set of comprehen- (SS) and at a period of 1.0 second (S 1).
1 the UBC and CBC are basically identical. sive and coordinated national codes. These values are determined from a
Again, as in the UBC, the Response The ICC founders — the Building Offi- set of 24 Spectral Acceleration Maps
Spectrum Curve starts at 0.33g at 1.0 Hz, cials and Code Administrators (BOCA), which include numerous contour lines
2 linearly increases to 2.15g at 2.15 Hz (Ts). the International Conference of Build- indicating the severity of the earthquake
The peak spectral accelerations then ing Officials (ICBO), and the Southern requirements at a particular location
cover a wide band of frequencies up Building Code Congress International in the country.
3 to 11 Hz (To) then gradually decreases (SBCCI) — created the ICC in response
to 0.86g (ZPA) at 33 Hz. to technical disparities among the
4 three nationally recognized model
ANSI C37.81 codes now in use in the U.S. The ICC
The seismic requirements for Class 1E offers a single, complete set of con-
5 switchgear in nuclear power plants struction codes without regional limi-
are defined in ANSI C37.81. Eaton tations — the International IBC Codes.
elected to test the equipment to 2/3 According to Chapter 16, Structure
6 of the nuclear requirements. Design, the seismic requirements of
electrical equipment in buildings may
be computed in two steps. The first
7 step is to determine the maximum
ground motion to be considered at the
site. The second step is to evaluate the
8 equipment mounting and attachments
inside the building or structure. The two
sets are then evaluated to determine
9 appropriate seismic test requirements.
The ground motion, the in-structure
seismic requirements of the equipment,
10 and the seismic response spectrum
requirements are discussed below.
11

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-21
January 2008 Reference Data
Sheet 01 111
Seismic Requirements

The maps indicate low to moderate


seismic requirements for the entire i
country, with the exception of two
particular areas; the West Coast (the
State of California) and the Midwest ii
(the New Madrid areas). Areas with
the seismic requirements at the New
Madrid are approximately 40% higher 1
than the maximum requirements of
the West Coast.
2
The Design Response Spectrum/
Spectral accelerations are equal to
0.68g at zero period (ZPA), increase 3
linearly to a peak acceleration of 1.7g
at 0.146 seconds (or 6.9 Hz) and stay
constant to 0.73 seconds (or 1.37 Hz) 4
then gradually decrease to 1.24g at 1
second (or 1 Hz).
B. ASCE7 Section 9.6.1.3 Seismic Forces
5
The code provides a formula for
computing the seismic requirements
Seismic Zones
6
of electrical and mechanical equip-
ment inside a building or a structure. 0 1 2A 2B 3 4
The formula is designed for evaluating 7
the equipment attachment to the Those areas within
equipment foundations. No Minor Moderate Moderate Major Zone 3 determined
damage damage damage damage damage by the proximity to
The seismic loads are defined as: certain major faults 8
F p = .4a p S DS W p ( 1 + 2 Z ⁄ h ) ⁄ ( R p ⁄ I p )
Figure 1.5-2. Bellcore Earthquake Zone Map 9
Where:
The following parameters produce the Bellcore Requirements
Fp : Seismic design force imposed at maximum required force:
the component’s C.G. and distrib- The Bellcore Generic Requirements 10
uted relative to component mass ■ Z is taken equal to H (GR-63-CORE, Issue 1, dated 1995)
distribution. (equipment on roof). for the Network Equipment-Building
■ Ip is taken equal to 1.5. System (NEBS) (Reference 10), and 11
ap : Component amplification factor the Physical Protection Section 5.4 of
■ Ap is taken equal to 2.5.
that varies from 1.00 to 2.50. the code includes a map of the seismic
■ Rp is taken equal to 2.5. zones (Figure 1.5-2), as well as a pro- 12
SDS: Spectral acceleration, short ■ SDS is equal to 1.7g as computed in posed Response Spectrum Curve for
period, as determined in the previous section. testing communication equipment.
previous section.
The acceleration at C.G. of equipment
Descriptions of the test requirements 13
Wp: Component operating weight. and test levels of equipment are
is then computed equal to:
also included.
Rp: Component response modification Acceleration = 0.4 x 2.5 x 1.7g (1 + 2) / 14
factor that varies from 1.0 to 5.0. (2.5/1.5) = 3.06g
Ip : Component importance factor that For equipment on grade, the accelera- 15
is either 1.0 or 1.5. tion at C.G. is then computed equal to:
Z: Highest point of equipment in Acceleration = 0.4 x 2.5 x 1.7g (1 + 0) /
a structure relative to grade (2.5 /1.5) = 1.02g
16
elevation.
The base forces associated with the
h: Average roof height of structure static loads at the C.G. of the equipment 17
relative to grade elevation. could be computed as 3.06/1.5 = 2.04g.
Finally ASCE7 Section 9.6.1.3 provides 18
for FP is not required to be taken as
greater than FP = 1.6 SDS IP WP
When IP = 1.5
19

20

21

CA08104001E For more information visit: www.eaton.com


1.5-22 Power Distribution Systems
Reference Data January 2008
Sheet 01 112
Seismic Requirements

Final Combined Requirements


i To better compare all seismic levels 10
9
and determine the final envelope 8 IBC, New Madrid
7
CH Seismic Envelope

Acceleration (g peak)
ii seismic requirements, the UBC, CBC,
Y2K IBC for California, Y2K IBC for
6
5

4
IBC, California
New Madrid area, and Bellcore final
1 seismic requirements are plotted in 3

Equiv. Bellcore
Figure 1.5-3. All curves are plotted at
2
5% damping.
2 An envelopment of the seismic levels in
the frequency range of 3.2 Hz to 100 Hz 1.0
.9
is also shown. This level is taken as .8
3 Cutler-Hammer generic seismic test
.7
.6
requirements for all certifications. .5
UBC and CBC
.4
4 Eaton performed additional seismic test
.3
runs on the equipment at approximately
120% of the generic enveloping seismic
5 requirements (see Figure 1.5-4). The
.2

testing is designed to establish addi-


tional margin and prepare for future .1
6 changes in the codes. 1 2 3 4 5 6 7 8 9 10
10
2 3 4
Frequency Hz
5 6 7 8 9 10
100
2 3 4 5 6 7 8 9 10
1000

7 Figure 1.5-3. Required Response Spectrum Curve

8 10
9
8
7 120% of CH Seismic Envelope
Acceleration (g peak)

9 5

4
CH Seismic Envelope

10 2

11 1.0
.9
.8
.7
12 .6
.5

.4

13 .3

.2

14
.1
1 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10 2 3 4 5 6 7 8 9 10
15 10 Frequency Hz 100 1000

Figure 1.5-4. Eaton Test Required Response Spectrum Curve


16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E


Power Distribution Systems 1.5-23
January 2008 Reference Data
Sheet 01 113
Seismic Requirements

Product Specific Test Summaries


Table 1.5-27. Distribution Equipment Qualified
i
for Applications through Seismic Zone 4
Cutler-Hammer Equipment ii
Low Voltage Panelboards
Pow-R-Line C 1a, 2a, 3a, 4, 5p, F16,
Column Type 1
Low Voltage Switchboards
Pow-R-Line C
Pow-R-Line i 2
Multimeter
Instant
IFS
Low Voltage Deadfront Switchboards
3
Motor Control Centers
Advantage
Series 2100 4
Freedom 2100
Low Voltage Busway
Pow-R-Way and Associated Fittings 5
Pow-R-Way III and Associated Fittings
Transfer Switch Equipment
Low Voltage Metal-Enclosed Switchgear 6
Type DS II
Magnum
DS-VSR Size 5 Vacuum Starter
Network Protectors
7
Submersible Type CMD and Type CM-22
Wall Mounted
Dry-Type Distribution Transformers 8
Types EP, EPT, DS, DT3
Substation Transformers
Dry-Type 9
Liquid
Unitized Dry-Type Power Centers
750 kVA Maximum 10
Excitation Control Assemblies
MGR, PRX-400B, WDR1000, WDR2000,
WTA-300B
ECS 2100
11
Metal-Enclosed Load Interrupter Switchgear
Type WLI 5, 15 and 38 kV
Type WVB 5 and 15 kV 12
Type MVS 5 and 15 kV
Medium Voltage Metal-Clad Switchgear
Type VacClad-W 13
Metal-Enclosed Non-Segregated Phase Bus
600 V, 5 and 15 kV
Medium Voltage Control 14
AMPGARD Figure 1.5-5. Sample Seismic Certificate
Vacuum Replacement Circuit Breakers Cutler-Hammer is a federally registered trademark of
Eaton Corporation. National Electrical Code and NEC
DHP-VR for DHP Switchgear
are registered trademarks of the National Fire Protec- 15
Loadcenters tion Association, Quincy, Mass. NEMA is the registered
Heavy Duty Safety Switches trademark and service mark of the National Electrical
Manufacturers Association. UL and CUL are federally
Enclosed Control registered trademarks of Underwriters Laboratories 16
Inc. Uniform Building Code (UBC) is a trademark of the
International Conference or Building Officials (ICBO).
BOCA is a registered trademark of Building Officials
and Code Administrators International, Inc. SBCCI is 17
a registered trademark of Southern Building Code
Congress International.

18

19

Equipment Seismic Label


20

21

CA08104001E For more information visit: www.eaton.com


1.5-24 Power Distribution Systems
January 2008
Sheet 01114

This page intentionally left blank.


i

ii

10

11

12

13

14

15

16

17

18

19

20

21

For more information visit: www.eaton.com CA08104001E

You might also like