AT7030

FLAME DETECTION TRANSFORMER

INSTRUCTION SHEET
Dimensions
See fig. 1.
Ambient temperature
--20 ... +60 _C
Relative humidity
90% max. at 40 _C (non condensing)
Supply voltage
220 ... 240 V (--15%, +10%), 50 ... 60 Hz
Power consumption
2 VA
Electrical connection
Mains Ph1/Ph2 : 6.3 x 0.8 mm faston on 5 mm pitch, suitable
for all codes of RAST5 connectors.
APPLICATION GND: mounting terminal (hole) combined with
6.3 x 0.8 mm faston.
Flame detection: 2.8 x 0.8 mm faston
The AT7030 flame detection transformer provides in
combination with Honeywell series S456., S457. and S4585 Enclosure
automatic ignition controls, reliable flame detection at mains IP 40
situations where the line voltage has a floating value to
Operation duration
ground (for instance phase -- phase mains)
Duty cycle 100 %
Basically there are two applications:
1. The AT7030A flame detection transformer for automatic Weight
ignition controls with special application connection. Ca. 95 g
This application is necessary if flame detection and high Flame detection cable
voltage are combined. See fig. 2. Length 2 x 500 mm maximum
2. The AT7030B flame detection transformer for automatic
ignition controls with separate flame detection and high Ø 4.2
4.8
voltage. See fig. 3.

DESCRIPTION 24.5
37
Subject to change without notice. Printed in the Netherlands.

The AT7030 flame detection transformer is mounted into a


temperature and shock resistant plastic housing. R2.1
To avoid influences of dirt and moisture the complete 45
assembly is encapsulated.
All connections are pluggable as there are the mains, flame Ø 4.2
60
detection pins and the ground terminal. 1.1 2.5
One of the mounting holes has to be used as ground terminal,
so fast and easy mounting is supplied 5 Ø 4.2
1

8.9
Ph1
Ph2

45
SPECIFICATIONS 5
2

Model
AT7030 flame detection transformer. 76.5 ¦ 0.5
Suffix A: 1 pin output, for combined flame detection/high Fig. 1. AT7030 outline drawing
voltage
Suffix B: 2 pin output, for separate flame detection/high
voltage

EN1R--9136 0010R4--NE
INSTALLATION AND CHECKOUT
IMPORTANT Automatic ignition
Installer must be a trained experienced service control Special applications input
person.
Disconnect power supply to prevent electrical shock
and/or equipment damage. 1 2
The appliance manufacturer’s instructions should
always be followed when provided.
Conduct a thorough check out when installation is
completed. Ph1
Ph1
Mounting (see fig. 1.) Ph2
Ph2
The AT7030 flame detection transformer enables a wide
variety of mounting possibilities. Fig. 2. AT7030A wiring with combined flame detection
Mounting position and high voltage (single rod)
The AT7030 flame detection transformer can be mounted in
two directions (60 x 35 and 45 x 19.7 mm), both with mounting
hole and GND connection combined.
Wiring

CAUTION
Wiring must be in accordance with local regulations.

Lead wire should have good quality insulation, suitable for the
temperatures encountered.
Use lead wire which is proven against moisture.
Automatic ignition
control
GENERAL CONSIDERATIONS Flame detection

The AT7030 flame detection transformer should be externally


fused. 1 2

High temperatures will affect product life.


To ensure reliable long term operation, mount the AT7030
flame detection transformer at a position in the appliance with
a low ambient temperature and a low radiation. Ph1
Ph1
Ph2

WARNING Ph2
Fig. 3. AT7030B wiring with separate flame detection
Do not use AT7030 in line -- neutral applications. and high voltage (dual rod)
Output pin 1 and output pin 2 of the AT7030B are not
protected against electrical shock.
Accessibility of terminals and basic insulated wires
shall be prevented.

Home and Building Control


Combustion Controls Center Europe
Honeywell BV
Phileas Foggstraat 7
7821 AJ Emmen
The Netherlands
Tel: +31 (-- )591 695911
Fax: +31 (-- )591 695200
http://europe.hbc.honeywell.com

EN1R--9136 0010R4--NE 2