You are on page 1of 40

 

 
 
 
Solar PV Electricity Solutions for Academic 
Campuses in India
A white paper 
 
 
 
 
Chetan S. Solanki  
Department of Energy Science and Engineering 
Indian Institute of Technology Bombay (IIT Bombay) 

October 2010 
Solar PV Electricity Solutions for Academic Campuses in India  
 

Contents 
1.  Introduction .................................................................................................................................... 4 
2.  Solar Radiation Map of India ........................................................................................................... 5 
2.1   Peak hours of solar radiation ................................................................................................. 6 
2.2   Horizontal surface and tilted surface .................................................................................... 7 
3.  Solar PV technologies: Converting light to electricity ....................................................................... 7 
3.1   Efficiency of PV modules of different technologies ............................................................ 10 
3.2   Rated power of PV modules ................................................................................................ 10 
3.3   Cost of PV modules of different technologies ..................................................................... 11 
4.  Per unit area PV Electricity Generation Potential .......................................................................... 11 
4.1  Efficiency of PV module ........................................................................................................ 12 
4.2   Per unit area electricity generation from PV modules ........................................................ 13 
4.3   Daily solar radiation data ..................................................................................................... 13 
4.4   Optimum tilt of PV modules – permanently fixed............................................................... 14 
4.5   Optimum tilt of PV modules – seasonally fixed ................................................................... 15 
4.6   Example calculations: PV electricity for three story academic building .............................. 16 
5.  PV system configurations .............................................................................................................. 17 
5.1   Possible PV system configuration for academic campuses ................................................. 18 
5.2   Commonly used PV system configurations ......................................................................... 19 
5.3   Designing a PV system ......................................................................................................... 20 
5.4 Example calculations for standalone PV system design ........................................................ 21 
5.5   Typical Cost of PV system components ............................................................................... 23 
6.  Spaces for PV installations in academic campus ............................................................................ 23 
6.1   Installation on building roof tops & sun shades .................................................................. 24 
6.2   Solar PV Installation on parking lots/path ways .................................................................. 25 
6.3   Solar PV installations on ground .......................................................................................... 25 
7.  Cost of solar PV electricity ............................................................................................................. 26 
7.1   Calculating Life Cycle Cost ................................................................................................... 26 
© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     2 

 
Solar PV Electricity Solutions for Academic Campuses in India  
7.2   Comparison of LCC of Solar, Diesel and Grid electricity ...................................................... 28 
8.  Energy efficiency is recommended ................................................................................................ 29 
8.1  Energy efficiency of buildings ............................................................................................... 29 
8.2  Energy efficiency of electrical loads ..................................................................................... 30 
8.3  Energy efficiency of users ..................................................................................................... 30 
9.  Subsidies for installing solar PV systems ....................................................................................... 30 
9.1   Subsidy for rooftop PV systems ........................................................................................... 31 
9.2   Interest rate subsidies ......................................................................................................... 32 
10. Recommendations for use of Solar PV electricity .......................................................................... 33 
 

Appendix:  Monthly  average  daily  solar  radiation  data  of  various  cities  of  India;  Global  (on  horizontal 
surface),  diffused  (on  horizontal  surface)  and  Global  (on  surface  tilted  to  latitude  of  location) 
represented in kWh/m2‐day………………………………………………………………………………………………………………35 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     3 

 
Solar PV Electricity Solutions for Academic Campuses in India  
 

Solar PV Energy for Academic Campuses in India 
A White Paper 
 
Chetan S. Solanki 
Department of Energy Science and Engineering 
IIT Bombay 

1. Introduction 
Electricity from renewable energy (RE) sources is increasingly been seen as the viable solution for energy 
deficiency, energy security and for social development. Among the many RE technologies and sources, 
electricity  produced  directly  from  the  sun using solar photovoltaic (SPV) technology is gaining interest 
from government and investments from private enterprises.  
 
Historically,  it  has  been  about  50  years  since  the  first  operational  silicon  solar  cell  was  demonstrated. 
However,  the  last  15  years  have  seen large  improvements  in  the  technology,  with  the  best  confirmed 
cell efficiency being over 24%. The main drivers have improved electrical and optical design of the cells. 
Improvements in the first area include improved passivation of contact and surface regions of the cells 
and  a  reduction  in  the  volume  of  heavily  doped  material  within  the  cell.  Optically,  reduced  reflection 
and  improved  trapping  of  the  light  within  the  cell  have  had  a  large  impact.  These  features  have 
increased silicon cell efficiency to a confirmed value of 24.7%. Together with technical progress there is 
support  from  the  government  for  solar  PV  technologies  around  the  world.  Overall  effect  is  significant 
growth of the PV technology. Currently the world annual production is over 10,000 MW. The solar PV 
technologies  are  now  increasingly  seen  as  major  electricity  source  for  Indian  scenario.  The 
announcement  of  Jawaharlal  Nehru  National  Solar Mission  confirms  this,  which  target  to  install  about 
10,000 MW of solar PV modules in India by 2022. 
 
On  a  practical  level,  the  peak  of  solar  electricity  generation  correlates  with  the  consumption  almost 
perfectly. The main reason for not having to look at SPV technology so seriously earlier was because of 
its high initial cost of installation. The cost is still formidable, but the alternative is to use diesel based 
electricity to cover for the peak shortages. With rising diesel costs, worrisome suppliers and dwindling 
global  supplies,  solar  electricity  from  SPV  has  just  turned  competitive  to  diesel.  The  next  target  in 
making solar PV widely acceptable is making electricity from it as cheap as that from coal. Though there 
is still a long way to go, the trend is unmistakable. SPV is here to stay and the faster we accept its utility, 
the easier it will be to solve much of our current concerns. 
 
Overall considering the concerns about rising electricity cost, increased concern for climate change and 
need  to  find  alternative  energy  solutions,  and  with  considerable  government  support,  solar  PV 
technology is increasingly seen as viable option for our current and future energy supply. 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     4 

 
Solar PV Electricity Solutions for Academic Campuses in India  
 
 
Academic campuses are ideal places for use of solar PV modules for the following reasons: 
1. Most  of  the  operation  of  academic  campuses  takes  place  in  the  day  time,  which  is  in 
synchronous with the availability of sun light. With this condition the expensive battery storage 
is minimized.  
2. Academic  campuses  do  not  have  significant  heavy  loads  like  ACs,  meaning  that  the  required 
power density is low. It is easier to generate smaller power density with solar PV solutions.   
3. Use  of  solar  PV  modules  in  campus  will  sensitize  young  minds  on  importance  of  renewable 
energy technologies who would become future scientist, academicians or policy makers. 
 
This  document  describes  the  solar  PV  potential,  particularly  for  academic  institutions  in  India.  The 
Section 2 describes the available solar radiation at various parts of the country, followed by Section  3 
giving the commercially available solar PV technologies for electricity generation. Available surface area 
in  academic  campuses  may  be  a  limitation.  Therefore  Section  4  describes  the  per  unit  area  electricity 
generation potential of PV technologies. Configuration of PV systems and system design is explained in 
Section  5.  Several  spaces  can  be  used  to  install  solar  PV  modules  in  academic  environment;  the 
possibilities  are  described  in  Section  6.  The  cost  of  electricity  generated  using  solar  PV  modules  is 
described in section 7 while Section 8 looks at possibility of minimizing energy consumption in order to 
reduce the overall cost of PV systems. At the end various subsidy scheme of government for promoting 
use of solar PV technology is described and recommendations were made for using solar PV electricity in 
academic campuses in India. 

2. Solar Radiation Map of India 
 
Electricity from the SPV is dependent on the amount of sunlight falling on the solar panels. The longer 
the hours of sunlight falling on them and the greater the amount of sunlight falling on them the better it 
is for electricity generation. Solar insolation in a given location is given by the unit kWh/m2‐day. In India, 
the  average  solar  insolation  varies  between  4  –  7  kWh/m2‐day.  This  solar  radiation  referred  as  global 
solar radiation and it consist of direct and diffuse solar radiation (due to cloud cover, dust, etc) reaching 
at a point on earth. What it means is that every day the amount of solar energy falling on 1 m2 area in 
India is about 4 – 7 units. Given India’s location in the equatorial belt, it is abundant sunshine. Also the 
fact that we have between 250 and 300 days of clear sunny days, gives the location year round reliable 
source of energy. Given the above figures the annual solar radiation falling on 1 m2 area in a given year 
is  between  1600  and  2200  kWh.  (To  give  a  perspective,  the  solar  industry  leader,  Germany’s  annual 
global  solar  radiation  is  between  950  and  1350  kWh/m2‐day.)  For  India  that  translates  to  about  6000 
million GWh. That’s a huge potential to tap.  
 
 
 
© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     5 

 
Solar PV Electricity Solutions for Academic Campuses in India  
 
 
 
 

Fig: Solar radiation map of India 
 
It  can  be  observed  from  the  solar  radiation  map  of  India  that  although  the  highest  annual  global 
radiation is received in Rajasthan and northern Gujarat, other regions also receive fairly large amounts 
of  radiation  as  compared  to  many  parts  of  the  world  including  Japan,  Europe  and  the  US  where 
development and deployment of solar technologies is maximum. 
 

2.1   Peak hours of solar radiation 
The solar cell efficiency and module output power is specified for W/m2 of radiation intensity and at 25 
degree  centigrade  of  cell  temperature.  This  condition  is  known  as  standard  test  condition  (STC). 
Normally the solar radiation intensity varies from morning to afternoon to sunset. A typical variation of 
solar radiation intensity as a function of time in hours is given  in Fig. below.  One  can  notice from the 
figure that the intensity of global radiation varies from 0 W/m2 at the sunrise and sunset to about 0.9 
kW/m2 at the noon time. The integration of the solar intensity curve, gives solar insolation falling at a 
unit area over a day and therefore the unit of solar insolation (loosely also referred as solar radiation) is 
Watt‐hour/m2‐time, for instance Wh/m2‐day or kWh/m2‐day.  It is mentioned in the previous paragraph 
that the annual solar insolation in India varies between 4 – 7 kWh/m2‐day or 1460 to 2555 kWh/m2‐year. 
 
Since  the  solar  cells  and  modules  are  characterized  for  1000  W/m2  or  1kW/m2  of  solar  radiation 
intensity, it is useful to represent the daily or annual solar radiation data in terms of ‘number of hours’ 
of 1000 W/m2. For instance, a 5 kWh/m2‐day of global solar insolation is equivalent of 5 hours of 1000 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     6 

 
Solar PV Electricity Solutions for Academic Campuses in India  
W/m2 of solar intensity.  This concept is demonstrated in Fig. below and very useful in estimating the 
amount of energy generated from a given PV module. In the Fig. below the area of the global radiation 
curve and the dotted rectangle should be equal. 
 

1
5 hours 
0.8
Radiation (kW/m2)

0.6
Global 
0.4 radiation 

0.2
Diffuse radiation
0
6 8 10 12 14 16 18
Hours
 
Fig: Daily variation in global and diffuse radiation intensity at a given location and equivalent ‘number of 
hours’ of 1000 W/m2 (for which solar cells and modules are characterized). Typically diffuse radiation is 
about  10  to  20%  of  global  radiation  in  India  for  a  clear  sky.  During  monsoon  or  cloudy  sky  conditions 
diffuse radiation is about 50 to 80% of the global radiation. 
 

2.2   Horizontal surface and tilted surface 
The  global  solar  radiation  data  are  typically  represented  as  amount  of  solar  radiation  received  on  a 
horizontal surface at a given location. In order to intercept more solar radiation, the solar PV modules 
are mounted at an angle to horizontal plane. Therefore, sometimes, it is useful to know the global solar 
radiation data on a tilted surface. This is discussed in detail in later sections.  

3. Solar PV technologies: Converting light to electricity 
Solar PV is a semiconductor device which converts sunlight directly into electricity. The operation of light 
to electricity conversion requires a built‐in electric field, normally obtained by making P‐N junction or P‐
i‐N  junction  structures.  A  solar  PV  panel  or  a  solar  PV  module  when  exposed  to  sunlight  generates 
voltage  and  current  at  its  output  terminal.  This  voltage  and  current  can  be  used  for  our  electricity 
requirements.  The  amount  of  electricity  a  solar  PV  module  can  generate  depends  on  the  amount  of 
sunlight falling on it. The higher is the intensity of the sunlight the more will be the electricity generated 
from it. When no sunlight falls on a solar PV module, no electricity is generated.  

The development of solar PV technologies has been taking place since 1950s. The solar cell development 
was  being  done  mainly  for  space  applications  till  1970s.  After  the  first  oil  shock  of  1973  the  solar  cell 
technology has been seriously considered for terrestrial power generation applications. Since then lot of 
development has occurred in cell design and cell material with an objective to increase in efficiency and 
decrease in cost per Watt. There are many technologies which are still under research and some of them 
© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     7 

 
Solar PV Electricity Solutions for Academic Campuses in India  
have  come  to  a  commercial  stage.  Among  the  commercial  SPV  technologies,  wafer  crystalline  Si 
technologies are most commonly fabricated and used.  

The commercial SPV technologies can be divided in two categories:  

1. Crystalline Silicon (c‐Si) wafer‐based cell technologies 

2. Thin film substrate‐based cell technologies 

The c‐Si wafer based technologies are divided in to mono‐crystalline, multi‐crystalline, electronic grade 
Si, solar grade Si and ribbon Si. The overall scenario c‐Si wafer based technologies is shown in Figure 
below. 

Raw Si in the form of SiO2 

Metallurgical grade Si 

High purity chlorosilanes gases  Purification 

High purity electronic grade Si  Thin film  Solar grade Si 


deposition 

Ingot pulling  Block casting  Sheet pulling Block casting 


or sheet 
pulling
Wire sawing  Wire sawing  Laser cutting

Multi‐crystalline 
Wafer dicing 
Mono‐crystalline 
wafer  wafer 
Si sheets Wafer or 

Solar cell  Solar cell  Solar cell Solar cell Solar cell 


Route‐I  Route‐II  Route‐III Route‐IV Route‐V 
 

Fig: Overview of Si based technologies. It also shows the route of thin film Si cell technologies1. 

Overall  thin  film  technologies  can  be  divided  in  two  categories:  Si  based  and  non‐Si  based,  which  can 
further be divided in flexible and rigid substrates. Categorizations of thin film technologies and leading 
companies in various categories are given in the figure below. 

                                                            
1
 C.S. Solanki, Solar Photovoltaics: Fundamentals, Technologies and Applications, Prentice Hall of India, 2009. 
© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     8 

 
Solar PV Electricity Solutions for Academic Campuses in India  

, Nex Power 

Fig: Tree of thin film technologies and leading companies. 

Both Crystalline Si wafer (c‐Si) based technology and amorphous Si (a‐Si) thin film solar cell technology 
makes  use  of  Si  but  they  are  fundamentally  quite  different  technologies.  C‐Si  wafers  have  ordered 
arrangement of Si atoms while in a‐Si it is completely disordered (amorphous), which is the main reason 
for  different  (a)  solar  cell  structure,  (b)  different  way  of  making  contacts  and  finally  (c)  different 
performance of the devices. C‐Si is based on p‐n junction while a‐Si is based on p‐i‐n junction. Other thin 
film technologies like CdTe and CIGS have poly‐crystalline material and cells are based on p‐n junction. 

Today solar PV modules of following technologies are commercially available: 

 Mono‐crystalline wafer‐based modules 
 Multi‐crystalline wafer‐based modules 
 Cadmium Teluride (CdTe) thin film modules 
 Copper Indian Gallium Selenide (CIGS) thin film modules 
 Amorphous Si (a‐Si) thin film modules 
 
 
 
 
 
 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     9 

 
Solar PV Electricity Solutions for Academic Campuses in India  
3.1   Efficiency of PV modules of different technologies 
PV modules from different technologies vary in terms of efficiency and cost per Watt. The efficiency of 
cells and modules of different technologies are listed in Table below. 

Technology  Highest Cell Lab  Highest module  Typical commercial 


Efficiency*(%)  Efficiency*(%)  module efficiency(%) 

Mono c‐Si  25  22.9  14  to 16 

Multi c‐Si  20.4  15.5  14  to 16 

a‐Si (single junction)  9.5  8.2  5.5 to 6.5 

a‐Si (double‐junction)  10.6  ‐  ‐ 

a‐Si/micro c‐Si  ~14.2(unstabilized)  ‐  8 to 10 


(double junction) 

a‐Si (triple‐junction)  13.0  10.4  ‐ 

CdTe  16.7  10.9  8 to 9 

CIGS  19.9  13.5  10 to 12.5 

*Ref: Martin A. Green, Keith Emery, Yoshihiro Hishikawa and Wilhelm Warta, Solar cell efficiency table 
(version 34), Prog. In Photovoltaic: Res. Appl. 2009; 17:320–326. Efficiency measured under the global 
AM1_5 spectrum (1000W/m2) at 258C (IEC 60904‐3: 2008, ASTM G‐173‐03 global) stable efficiencies.  

   3.2   Rated power of PV modules 
The efficiency and power output of a solar cell and modules are given for light condition corresponding 
to 1000 W/m2 and at 25oC temperature, known as standard test condition (STC). The rated power of a 
cell and module is referred as peak power or Wp. The peak power of PV module changes with change in 
falling solar radiation and temperature of the cell under real life conditions. Typically one does not get 
the  condition  corresponding  to  STC.  Solar  radiation  is  normally  lower  than  the  STC  condition  and  cell 
temperature is normally higher than the STC condition, both of these have effect of decreasing power 
output from the PV module.  

The  conditions  specified  in  the  STC  does  not  occur  for  most  of  the  time  and  locations.  This  happens 
because  of  two  reasons;  the  real  solar  irradiation  is  normally  less  than  1000  W/m2  and  the  module 
temperature  under  real  operation  is  more  than  the  STC  specified  temperature  of  25oC.  Both  of  these 
reasons result in lower module power output than the expected under the STC condition. Thus, in order 
to have more realistic figure for the possible power output from a PV module, the performance of the 
modules  is  described  in  two  other  test  conditions;  standard  operating  conditions  (SOC)  and  nominal 
operating  conditions  (NOC).  Both  of  these  use  a  different  concept  of  temperature,  called  as  nominal 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     10 

 
Solar PV Electricity Solutions for Academic Campuses in India  
operating cell temperature (NOCT). The NOCT is defined as the temperature reached by a cell in open 
circuited module under following conditions: 

‐ Irradiation: 800 W/m2, 
‐ Ambient temperature: 20oC 
‐ Wind speed: 1 m/s  
‐ Mounting: open back side 
 
The NOCT can be used to give more realistic cell temperature of the module under operating conditions. 
The NOCT lies usually between 42 to 50oC.  Under different ambient temperature and solar radiation the 
NOCT  will  change.  In  India,  since  ambient  temperature  is  always  quite  higher  than  20oC  considered  in 
NOC, therefore actual cell temperature lies between 55 to 70oC. 

Table: Comparison of test condition under which PV module characteristics are described. 
Conditions  STC  SOC  NOC 
(Standard test  (Standard operating  (Nominal operating 
condition)  condition)  condition) 
2
Irradiation (W/m )  1000  1000  800 
o o
Temperature ( C)  25  NOCT (42 to 50 C)  NOCT (42 to 50oC) 
Rated power (Wp)  100 (reference)  91 to 94  72 to 75 
 
Since the NOC conditions are more common in real life situations, therefore for PV module power rating 
under NOC conditions (or prevailing conditions) should be considered. And the rated power under NOC 
conditions  is  smaller  than  rated  power  under  STC  conditions.  But  note  that  in  most  designs  the  STC 
rated  power  of  PV  modules  is  considered,  which  is  then  discounted  in  terms  of  efficiency  to  consider 
losses for higher operating cell temperature. 
 

   3.3   Cost of PV modules of different technologies  
The cost of solar PV technologies is stated in terms of Rs per Wp. The cost of PV modules varies between 
75 Rs/Wp to 125 Rs/Wp. This variation is due to the technology and also due to the volume of purchase. 
Normally  for  higher  volume  purchase,  like  several  100  kWp  or  few  MWp,  the  cost  of  c‐Si  based  PV 
modules was between 90 to 110 Rs/Wp in Sep. 2010. 

4. Per unit area PV Electricity Generation Potential  
 
In the last section it is mentioned that the average solar radiation in India is quite high. But the question 
how much of that radiation can be extracted into electricity from SPV module covering certain area. The 
calculation is very simply dependent on the efficiency of the SPV used and available solar insolation at a 
given  location.  If  high  efficiency  modules  are  used,  more  of  the  solar  energy  can  be  converted  to 
electricity. Lesser efficiency would mean less electricity conversion.  
© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     11 

 
Solar PV Electricity Solutions for Academic Campuses in India  
 
Depending on the kind of technology, efficiencies vary between 8% for thin film SPV and 16% for mono‐
crystalline  SPV.  It  should  be,  however,  noted  that  higher  efficiencies  mean  greater  generation  of 
electricity for a given unit area. A 100 watt solar module will generate the same amount of electricity in 
a given locality no matter how efficient or inefficient it is. The only thing that may differ is the size of the 
100 Wp module. A less efficient module will be bigger than a high efficiency module. A PV module of 1 
meter square area with efficiency of 14% and 8 % would generate 140 Watt and 80 Watt respectively 
under standard test condition (1000 W/m2 and at 25oC). 
 

4.1  Efficiency of PV module  
Efficiency of PV modules is calculated as follows: 
A commercially available module has the following given parameters: 
 The peak power rating of the module (Wp) 
 The area of the module (m2) 
Dividing the peak power rating by t he area of the module, we get Wp/m2. Since the modules are rated 
at STC of 1000 W/m2, the efficiency of the module can be written as: 
 Wp / m2 
Efficiency    *100%  
 1000 W / m 2 
 
For instance a 200 Wp and a 230 Wp Moser Baer crystalline silicon solar module has the L x W of 1661 
mm x 991 mm. Similarly a 340 Wp and 380 Wp thin film solar module has the dimension of 2600 mm x 
2200 mm. The estimated solar PV module efficiencies are given in Table below. 
 
Table:  Estimated efficiencies of PV module 

Parameters  200 Wp c‐Si  230 Wp c‐Si  340 Wp thin film  380 Wp thin film 


Type of Module  Crystalline Silicon  Thin Film 
Power Rating  200  230  340  380 
2
Area (m )  1.64  5.72 
2
Wp/m   121.2  139.4  59.4  66.4 
Efficiency  12.1%  13.9%  5.9%  6.6% 
 
As  can  be  seen  from  the  above  example,  the  crystalline  modules  have  higher  efficiency  than  thin  film 
ones.  The  information  about  efficiency  of  PV  modules  is  useful  in  determining  the  total  area  of  PV 
modules required to generate given amount of energy.   
 
Alternatively a 13.9% efficient SPV of 200 Wp will have the area of 1.43 m2. This is calculated by dividing 
200 Wp by the efficiency. In this instance the area of the module can be calculated as follows: 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     12 

 
Solar PV Electricity Solutions for Academic Campuses in India  
 Wp 
Area(m 2 )    
 Wp / m2 
 

4.2   Per unit area electricity generation from PV modules 
From the efficiency of the modules one can then calculate how much electricity can be generated in a 
given area. Suppose the location has an average daily solar radiation of 5.5 kWh/m2‐day, then using the 
various efficiencies one can determine the electricity generated from the modules. 
 
Electricity generated from individual panel of a given power rating is the product of the efficiency of PV  
module and average daily solar radiation.  
 
Electricity Generated (kWh / m 2 / day )  Eff . of mod . * Ave. daily radiation(kWh / m 2 / day )  
 
Table: Estimated electricity generation on per unit area basis from PV modules of different efficiencies. 

Parameters  c‐Si Low  c‐Si High  Thin Low  Thin High 


Efficiency  12.1%  13.9%  5.9%  6.6% 
Average  Daily  Solar  Radiation 
(kWh/m2‐day)  5.5 ( or 5.5 hours of 1000 W/m2) 
Electricity generated 
(kWh/m2‐day)  0.66  0.76  0.32  0.36 
 
Thus from a PV module data sheet its efficiency can be estimated and from a given global solar radiation 
data, per unit area electricity (on daily, monthly or yearly basis) can be estimated.  
 

4.3   Daily solar radiation data 
Global  solar  radiation  data  are  normally  available  for  main  locations  in  the  form  of  daily  average. 
Multiplying  the  number  of  days  in  a  month  to  daily  average  global  solar  radiation  data  one  will  get 
monthly  global  solar  radiation  data.  As  an  example  monthly  averaged  daily  global  solar  radiation  for 
Hyderabad  is  given  in  Table  below.  For  many  other  locations  across  India  the  monthly  averaged  daily 
global radiation data are given in Appendix. 
 

Table: Monthly averaged daily global solar radiation on horizontal surface and at surface tilted at latitude angle for 
Hyderabad. 

Month  Average Daily Global Solar  Average Daily Global Solar 


Radiation (Horizontal)  Radiation (Latitude) 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     13 

 
Solar PV Electricity Solutions for Academic Campuses in India  
January  5.5  6.7 
February  6.2  7.1 
March  6.5  6.8 
April  6.9  6.7 
May  6.9  6.4 
June  5.8  5.3 
July  4.9  4.6 
August  5.2  5.0 
September  5.2  5.2 
October  5.8  6.3 
November  5.4  6.4 
December  5.1  6.3 
AVERAGE  5.78  6.06 
 
The figures here represent the energy falling on the surface during the day or the number of hours when 
the  radiation  is  1000  W/m2.    Note  in  the  above  Table  that  that  during  the  summer  the  radiation  on 
horizontal surface is greater than that of the radiation on the latitudinal tilted surface. 
 

4.4   Optimum tilt of PV modules – permanently fixed 
In  order  to  maximize  the  interception  of  solar  radiation,  and  hence  maximize  the  generation  of  solar 
radiation, the solar PV modules should be kept perpendicular to the sun rays. Since the position of the 
sun is changing throughout the day, the position of the PV modules should also be changing throughout 
the day, i.e. sun tracking is required. The precise tracking of the sun, in most cases, is not possible due to 
the additional cost of infrastructure required for tracking. Also, it requires maintenance. Therefore fixed 
mounting  of  solar  PV  modules,  over  certain  period,  months  or  even  year,  is  advised  and  preferred 
option.  
The  question  is  how  the  collector  should  be  optimally  oriented  for  capturing  maximum  possible 
sunlight? For a clear day, the intensity of solar radiation at a given location is symmetrical around the 
solar noon time of the location.   Also the radiation intensity is  maximum at  noon time. Therefore the 
solar PV modules are oriented to maximize solar radiation interception at noon time. It can be shown 
that if the PV modules are to be fixed throughout the year, at a fixed angle, the optimum tilt of solar PV 
modules  should  be  equivalent  to  the  latitude  angle  of  the  location.  Also,  if  the  modules  installation  is 
done  in  the  Northern  hemisphere  the  orientation  should  be  South  facing  and  if  the  PV  modules  are 
being installed in Southern hemisphere then the PV modules should be installed North facing. 

Thus,  if  PV  modules  are  integrated  as  part  of  roof  of  a  building  in  academic  campus,  the  roof  should 
have a tilt angle, equivalent to latitude angle of the location and in India the roof should be south facing. 
The latitude angle of Hyderabad is 17.37o North and hence the buildings on which solar PV modules are 
to be mounted should have 17.37o tilt, and the roof should be facing South. 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     14 

 
Solar PV Electricity Solutions for Academic Campuses in India  
4.5   Optimum tilt of PV modules – seasonally fixed 
It can be noted from the Table of daily global solar radiation for Hyderabad that during the summer the 
radiation on horizontal surface is greater than that of the radiation on the latitudinal tilted surface. Thus, 
tilt of PV modules in a given season can affect the energy generated from it. This knowledge can be used 
to optimize the electricity generation for a given season. 

In  the  previous  section  it  has  been  discussed  that  a  fixed  solar  collector  installed  in  the  Northern 
hemisphere  should  be  facing  South  and  should  be  inclined  to  an  angle  equal  to  the  latitude  of  the 
location.  But  adjustment  of  solar  PV  modules  inclination  few  times  a  year  can  enhance  the  energy 
collection over the year, by enhancing the intercepted radiation. The PV module inclination adjustment 
can  also  improve  the  system  performance  for  a  given  season.  For  instance,  an  academic  building  will 
require larger energy for running fan in summer. Or if solar PV modules are installed for a ski resort, it 
would be desirable that the collector perform better in winter.  

The optimized tilt angle of solar PV modules in winter season should be equal to latitude angle+15o and 
for  the  summer  it  should  be  latitude  angle‐15o.  The  relative  gain  in  the  electricity  production  of  a  PV 
module when it is mounted to latitude15o as compared to its performance when it is mounted at the 
latitude angle is shown in Fig. below.  Note that the graph is only an indicative relative gain. Different 
locations will have different relative gain as it will depend on the local weather, percentage of diffuse 
radiation and seasonal change of the weather.  

1.4
Relative energy production

1.2 Latitude ‐ 15o

1
Latitude
0.8
Latitude + 15o
0.6

0.4
Jan Feb Mar Apr May Jun July Aug Sep Oct Nov Dec
 
Fig.: Relative collector performance as a function of collector tilt angle 

Periodically changing the tilt of the PV modules requires additional structural arrangement that allows 
change  in  tilt,  manually  or  automatic.  This  can  add  to  the  cost  but  results  in  additional  energy 
generation.  In  general,  15  to  25%  additional  energy  (as  compared  to  permanently  fixed  mounted  PV 
panels) can be generated with 5 to 10% higher life cycle cost. 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     15 

 
Solar PV Electricity Solutions for Academic Campuses in India  
4.6   Example calculations: PV electricity for three story academic building  
Based on the information discussed so far in this section, it is now possible to estimate whether there is 
enough space or not in a building to supply all its electricity requirement using solar PV modules. Other 
than the cost of PV system, there is limitation of availability of open area, like terrace, to install solar PV 
modules.  The  calculations  given  in  Table  below  are  based  on  certain  assumption  for  the  electricity 
requirement  of a building  and terrace area availability. First order calculations  suggests that academic 
buildings,  tall  up  to  three  floors,  have  sufficient  space  at  the  terrace  to  fulfill  most  if  not  all  of  its 
electricity requirement, provided there is no AC load. 

Table: Examples calculations for satisfying electricity needs of a academic building using PV modules 

Total floor area of building 
Description  Quantity  Units 
No of floors in building  3 
Area per floor  
(this is taken as example, calculations for any other 
area would be valid as well)  1000  Sq ft 
Total floor area  3000  Sq ft 

Estimation of load 
Estimated Load per unit area of the building  100  Sq ft 
Hour  of 
Item  No.  Wattage  usage per day
Lights 
(assuming 
efficient lights)  2  50  9  900  Wh 
Fans 
(assuming 
efficient fan)  1  50  9  450  Wh 
Computers 
(assuming  one 
computer  in 
every 200 sq ft)  1  50  4  200  Wh 
Total daily electricity required  1550  Wh 

Total  daily  energy  required  for  whole  building   


(all three floors)  46500  Wh 
46.5  kWh 

Available space of PV installation on roof  70%  of total floor area 


Total available space for PV module installations  700  Sq ft 
63.6  Sq meter 
Total possible installation of PV modules (in terms of Watts) 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     16 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Solar  radiation  intensity  (Standard  Test 
Condition)  1000  W/m2 
PV module efficiency  15% 
Wattage of PV modules per sq meter  150 
Total  wattage  of  PV  modules  that  can  be  installed  on 
roof  9545  Watt 
Daily generation of electricity from PV modules 
daily available solar radiation  5  kWh 
5  Hours of 1000 W/m2 
Energy that can be generated per day using PV modules  47727.3  Wh 
47.7  kWh 
Comments:  One  can  see  from  the  above  calculations  that  even  for  three  story  building  there  is 
sufficient generation of electricity from PV modules to full fill all the electricity requirements of the 
building. Please note that no PV system losses are taken in calculations, which invariably are there 
up to 15 to 20%. In summary, one to three story buildings always have sufficient roof area to full fill 
most of its electricity requirements.  
 
This is only example calculations, proper calculations should be done for each building. The steps for 
designing solar PV systems for a given electricity requirement is given in section 5.  
 
However  one  should  note  that  several  assumptions,  which  are  very  reasonable,  are  made  in  this 
calculation. The actual electricity requirement can be higher or lower, the actual roof area available 
for PV module installations could be higher or lower, the actual amount of solar radiation available 
at a given location could be higher or lower.   
 

5. PV system configurations  
 
The PV systems are designed to supply power to electrical loads. The load may be of DC or AC type and 
depending  upon  the  application,  the  load  may  require  power  during  the  day  time  only  or  during  the 
night  time  only  or  even  for  24  hours  a  day.  Since  a  PV  panel  generates  power  only  during  sunshine 
hours, some energy storage arrangement is required to power the load during the non‐sunshine hours. 
The  load  can  be  a  DC  or  an  AC  load.  This  energy  storage  is  usually  accomplished  through  batteries. 
During the non‐sunshine hours, the load may also be powered by auxiliary power sources such as diesel 
generator,  wind  generator  or  by  connecting  the  PV  system  to  the  grid  or  some  combination  of  these 
auxiliary sources.  

PV systems can be broadly divided into the following three categories: 

1. Standalone PV systems 
2. Grid connected PV systems and  

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     17 

 
Solar PV Electricity Solutions for Academic Campuses in India  
3. Hybrid PV systems 
 
A standalone system is the one which is not connected to the power grid. In contrast, the PV systems 
connected to the grid are called grid connected PV systems. Hybrid PV systems could be standalone or 
grid connected type, but have at least one more source other than the PV. 

The  primary  difference  between  the  standalone  and  grid  connected  systems  comes  from  the  energy 
storage feature, which is a direct consequence of their connection (or absence of connection) with the 
grid. While the standalone PV systems usually have a provision for energy storage, the grid connected 
PV systems have none or rather they don’t need one. The excess or deficit energy produced by the PV 
source  in  grid  connected  systems  (difference  of  energy  produced  by  the  PV  source  and  the  energy 
required by the load) is supplied to the grid or drawn from the grid. As a standalone PV system is not 
connected  to  the  grid,  it  must  have  battery  support  or  an  auxiliary  source  to  supplement  the  load 
requirements during the night hours or otherwise. 

Be it the standalone system or the grid connected system, other sources of power (other than the PV as 
the  main  source)  may  also  be  connected  to  them  for  auxiliary  support  and  better  reliability.  For 
instance,  a  standalone  PV  system  can  also  have  a  wind  generator  connected  to  it  or  it  can  have  two 
power sources, a wind generator and/or a diesel generator, connected to it. The same is true for the grid 
connected systems. Whenever there is more than one type of power sources connected in a system, the 
configuration is known as hybrid system. A hybrid system with PV as the main source, is called a hybrid 
PV system. Factors such as resource (solar, wind, grid) availability, initial cost of the system, criticality of 
the  load,  etc.  influence  the  decision  as  to  whether  or  not  to  have  a  hybrid  system  and  if  yes,  what 
configuration? For instance, a PV‐wind hybrid configuration can be installed when both solar and wind 
resources,  at  a  given  location,  are  abundantly  available.  Similarly,  when  the  amount  of  PV  power 
installed is not adequate to meet the load demand (say due to cost factor), a diesel generator or another 
renewable energy (RE) generator can be installed along with the PV source. 

5.1   Possible PV system configuration for academic campuses 
A  possible  PV  system  configuration,  incorporating  various  sources  of  electricity  like  PV  modules,  grid, 
and diesel/Wind generator is shown in the Fig. below. It should be noted that it is optional to connect 
one or more sources of electricity in the system. The system can only run on Solar PV electricity or it can 
also be coupled with grid electricity. Many times, when grid electricity connected is not available or not 
reliable,  then  it  is  advisable  to  have  solar  PV  with  diesel  generator,  wherein  diesel  generator  may  be 
used for emergency conditions when there is not enough sun light, like in rainy season. 
 
 
 
 
 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     18 

 
Solar PV Electricity Solutions for Academic Campuses in India  

Grid  DC‐AC   AC 


Converter  Load 

 
Electronic  DC 
PV  
Controller  Load 
Panel 

Diesel /wind Generator 

 
Fig: Possible configuration of solar PV system with option of connecting the system with grid or diesel or 
wind generator. 
 

5.2   Commonly used PV system configurations 
The  current  trend  in  usage  of  PV  systems  is  in  providing  day  time  electricity  needs  and  supplying 
electricity to the grid. This usually reduces the cost of storage for night time application and manages to 
solve the peak time energy shortage. These are grid connected systems without any battery storage. As 
per the prevailing policies, the gird connection in India is possible for power plants of 1MW and larger 
capacities.  For  connecting  PV  systems  of  smaller  sizes,  less  than  MW,  institution  are  required  to  have 
arrangement with state electricity board, regulatory boards.  
 
In  a  number  of  industrial  and  commercial  locations  SPV  is  replacing  diesel  as  the  preferred  source  of 
electricity  generation.  While  in  industrial  locations  the  quantum  of  power  and  therefore  energy 
requirement is very high, the size of PV systems tends to be large as well. So most of the time the PV 
plant is setup in roof‐top as well as over land dedicated for SPV power plant. These systems are almost 
always  grid  connected  to  switch  seamlessly  between  SPV  electricity  when  it  is  available  and  grid 
electricity when the sun is unavailable, such as during monsoons. 
 
In academic locations the need for electricity is usually to power office equipments and basic needs such 
as lighting and ventilation. This is an example of captive power plants where PV plants are installed to 
satisfy  the  electricity  needs  of  campus  only.  In  most  instances  the  SPV  is  installed  over  building  roof‐
tops. In absence power source, other than PV, battery storage is required. 
 
 
 
 
 
© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     19 

 
Solar PV Electricity Solutions for Academic Campuses in India  
5.3   Designing a PV system 
 
Design of grid connected system:  
A  grid  connected  system  will  not  have  any  battery  back  up  as  the  grid  itself  acts  as  medium  to  store 
energy. Therefore one need to put enough solar PV modules to fulfill daily energy requirements. Since 
the PV systems are connected to grid, one can install less than the required PV modules or more than 
the required PV modules. The amount of PV modules to install may then be govern by the availability of 
money, availability of roof top area, upper limit set by policies, etc. 
 
For  instance,  if  you  install  2  kWp  of  PV  modules  (normally  would  take  about  15  square  meter  of  roof 
area) on your roof and you daily solar insolation in your area is 5 kWh/m2‐day, then PV modules would 
be generating 10 kWh or 10 units of electricity every day. In order to connect a PV system to the grid, 
one  requires  electronic  components  like  Maximum  Power  Point  Tracker,  DC  to  DC  converter  and  an 
Inverter. All these components may come as single unit, as an inverter for grid connection. Efficiency of 
such  electronics  is  over  80%  at  small  power  level  (few  kW)  inverter,  but  the  large  power  (several 
hundred kW) grid connected inverter would have efficiency above 92%. One must consider the electrical 
losses in electronics required for grid connection to estimate what is the actual energy fed in to the grid.  
 
Design standalone PV system 
A  standalone  PV  systems  are  designed  to  full  fill  all  the  electrical  energy  requirement  of  a  premises, 
wherein the load can run during day time or night time. In such systems, a battery bank is used to store 
the electricity. A PV system design requires the estimation of load (in terms of daily energy), estimation 
of battery in a PV system and estimation of size of PV modules, etc.  
 
The design of PV system is normally done in three steps: 
Step 1: estimation of daily electrical energy required 
Step 2:  Estimation of battery requirement 
Step 3‐ Estimation of PV module requirements 
 
In order to estimate the electrical load, one must know the power ratings of various appliances used in 
institute  and  the  number  of  hours  of  daily  usage  of  each  appliances.  Table  below  provides  the 
appliances along with their power rating and the approximate hours they are used.  
 
Table: Power ratings of various appliances used in academic institutions 

Appliance  Power Rating (Watt) 
Tubelights  40 
CFLs  8 – 28 
Ceiling Fans  55 – 85 
Wall Fans  65 – 100 
Air‐Condition Systems  1000 – 5000 
© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     20 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Appliance  Power Rating (Watt) 
Laptops  80 – 100 
PCs  250 – 300 
TV  150 – 250 
Printers  300 – 500 
Projectors  1000 – 3000 
Water Pumps  350 – 3500 
 

5.4 Example calculations for standalone PV system design 
 Let us design a PV system to power a typical academic establishment with the following loads. They are 
to operate between 9:00 AM to 6:00 PM.  
 
Table: Estimation of daily electrical energy requirements 

Load  Power  Rating  Usage in hours per  No. of Units  Electricity  


(Watt)  day  (Wh) 
Tubelights  40  9  6  2160 
Fans  80  9  6  4320 
CRT PCs  300  8  6  14400 
Printer  500  2  1  1000 
  920 Watt       
Total daily electricity demanded (Wh)  21880 
Total daily electricity demanded (kWh)  21.88 
 
Solution: Daily energy required is 21.88 units or 21.88 kWh. The location is in Hyderabad. The average 
annual global solar radiation is 5.78 kWh/m2‐day. 
 
Simplistically, the panels required can be found by: 
 
Electricity Needed (kWh)
SPV (kW )   
Global Solar Radiation(equivalent hours )
 In this case, 21.88 kWh divided by 5.78 hours = 3.78 kW 
 
However,  there  are  other  additional  components  that  are  needed.  Batteries  to  provide  for  non‐peak 
solar hours or when there is no sunlight. Usage of inverters, batteries and other electronics bring their 
own inefficiencies. An SPV system has to be designed keeping these factors in the picture. Table below  
indicates the steps to design an SPV system. 
 
 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     21 

 
Solar PV Electricity Solutions for Academic Campuses in India  
 
 
Table: Design steps for estimating the required size of batteries and PV modules for given daily electrical 
energy needs 

Steps  Description  Values   


Calculating  the    21.88 kWh   
electricity needed 
Inverter Rating  Slightly  greater  than  the  1 kW   
total load rating 
  Inverter Efficiency  85%   
  Energy  to  the  load  and  25.74 
inverter   
       
Sizing of batteries 
  Estimating  the  energy  33%  This  is  an  assumption,  if 
that needs to be stored  loads  run  in  the  night 
hours  then  battery 
storage  capacity  may  be 
much  higher  (in  worst 
case 100%).  
  Battery Efficiency  85%   
  Energy  that  needs  to  be  10 kWh 
stored   
  Battery Voltage  12V   
  Battery  Ampere‐Hr  840 Ah 
capacity   
  Battery  Depth  of  60%   
Discharge 
  Actual Battery capacity  1400 Ah 
 
Sizing of PV modules 
  Energy  needed  during  25.74 kWh   
the day 
  Total system efficiency  80%   
  PV  Panel  operating  85%   
performance 
  Average  global  solar  5.78 hours   
radiation 
  Actual PV size  6.54 kW 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     22 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Thus  PV  modules  of  6.54  kWp  are  required  to  provide  the  daily  electricity  of  about  21.88  kWh  in  an 
standalone PV system. 
 
The battery acts as a storage when the office functions during the non‐peak sunshine hours such as early 
morning  and  late  in  the  evening.  The  excess  electricity  generated  during  noon  time  is  stored  in  the 
battery which is used when the intensity is less. The figure of 33% is arbitrary figure taken here. Ideally it 
should be arrived after having analyzed the load pattern during the day. Battery size would double if 2 
days of autonomy is needed. Autonomy means when the system can provide reliable electricity when 
the sun is down, such as during monsoon.  

5.5   Typical Cost of PV system components 
The Table below gives the typical cost of various PV components that are used in PV system, both for 
grid and off‐grid systems. 
 
Table: Typical cost of PV systems 
Component  Specified  in  terms  of  Available  in  range  of  Typical cost 
“unit”  “units” 
Solar PV modules   Peak wattage, Wp  40 Wp to 300 Wp  90 to110 Rs per Wp 

Battery   Ah capacity and terminal  20  Ah  to  several  60 to 80 Rs / Ah @ 12 V 


Voltage  hundred Ah, 12 V 
Inverter (off‐grid)  kW  1 to 25 kW  16000  to  2000  Rs  per  5 
kW 
MPPT (off‐grid)  Input DC voltage, current  12  to  72  Volt,  10  A  to  16000 to 20000 Rs for 24 
handling capacity  50 A  V, 30 A 
Inverter  (grid‐ kW  1 to 10 kW  30,000 Rs Per kW 
connected),   100 kW  15000 Rs per kW 
250 kW  10000 Rs per kW 
Charge  controller  (off‐ Input DC voltage, current  12  to  72  Volt,  10  A  to  10000 to 12000 Rs for 24 
grid)  handling capacity  50 A  V, 30 A 
Fabrication  cost  of  PV  Rs  per  Watt  of  system    10 Rs per Watt 
system  (supporting  capacity 
frames, wires, etc.) 

6. Spaces for PV installations in academic campus 
 
There  are  several  locations  in  the  academic  campus  that  can  be  utilized  for  installation  of  solar  PV 
modules.  Since  most  of  the  buildings  in  a  given  campus  are  of  same  height,  building  terraces  offer 
excellent  locations  for  SPV  installations.  Parking  roof‐tops,  PV  shelters  for  open  restaurants  with 
campus, unused land parcels can all be possible locations for PV installation.  

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     23 

 
Solar PV Electricity Solutions for Academic Campuses in India  
 
Thus the possible spaces for installation of PV modules could include: 
‐ Roof tops of buildings, both academic and residential 
‐ Roof tops of canteen  
‐ Roofs of parking area and path ways 
‐ Any other open area 
 
If the planning for use of solar PV modules is done in advance the solar PV modules themselves can be 
used as roof material. Use of solar PV modules as roof material has potential of saving the cost by saving 
the construction materials for roof tops. This is particularly suitable for spaces like roof tops of parking 
areas, roof top of sports complex, canteen etc.  
 
Some of the examples of use of Solar PV modules for various applications are discussed here. 

6.1   Installation on building roof tops & sun shades 
Roof  tops  of  buildings  are  good  places  to  install  PV  modules.  Normally  the  roof  tops  are  not  used  for 
useful  purposes  and  available  for  use.  Installing  PV  modules  at  the  rooftop  will  have  additional 
advantage  of  reducing  the  heat  gain  of  the  building  from  the  top,  which  would  reduce  the  cooling 
requirement or increase the comfort level. 

For one to three story buildings (e.g. department buildings, households etc.) there is always enough roof 
top space to generate electricity for supplying the complete load of the building, if air conditioning load 
is not there (refer to section 4). 

 
Fig: Solar PV modules on roof tops 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     24 

 
Solar PV Electricity Solutions for Academic Campuses in India  

Fig: Solar PV modules as Sun shades 

6.2   Solar PV Installation on parking lots/path ways 
Parking  lots  are  one  of  the  ideal  spaces  for  installation  of  PV  modules,  specially  when  PV  modules 
themselves  are  used  as  roofing  material.  Image  below  depicts  the  use  of  solar  PV  modules  on  a  very 
large size parking lot. 

 
 

6.3   Solar PV installations on ground 
If there is not sufficient space available on the roof tops and parking lots, then solar PV modules can be 
installed on ground. It requires dedicated space for installation of PV modules. Image below depicts the 
installation of PV modules on ground. 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     25 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Since India is in the northern hemisphere, only south facing panels can have maximum solar radiation. 
The  most  important  factor  for  SPV  location  selection  is  shadow‐free  eastern,  southern  and  western 
sides. Trees shades and building shadows should be accounted for ideal SPV placement. 

7. Cost of solar PV electricity  
The cost of installation of SPV is formidable because of the fact that all the future expenses are incurred 
at  the  beginning  of  the  project.  Since  all  future  expenses  mainly  involve  only  nominal  operation  and 
maintenance  and  fractional  replacement  expenses.  In  most  cases  the  investor  is  discouraged  by  the 
possibility of spending so much before the solar PV project is implemented.  

In this section basic calculations are given in order to find out the cost of electricity generated from PV 
modules and other resources like diesel generator so that the comparison between solar PV electricity 
and other sources can be made.  

7.1   Calculating Life Cycle Cost 
While calculating the cost of generating per unit of solar electricity, we use the concept of Lifecycle Cost 
of  Electricity  (LCOE).  LCOE  is  the  ratio  of  Total  Lifecycle  Cost  (TLCC)  and  the  Total  Lifetime  Energy 
Production (TLEP). TLCC calculates the present worth of all the expenses incurred by the system during 
its lifetime. It includes costs such as initial cost of installment, recurring expenses such as operation and 
maintenance  and  replacement  expenses  for  battery,  inverter  and  balance  of  systems.  TLEP  sums  the 
total electricity generated during the life of the plant. The present worth of all the electricity generated 
in 25 years of the life of the system is calculated discounted at some prevailing rate. It should be noted 
that the amount of electricity generated falls steadily during the life of the system. And as the value of 
investment changes as time changes, so does the value of electricity generated. 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     26 

 
Solar PV Electricity Solutions for Academic Campuses in India  
TLCC
LCC of elecricity  N
 
 [ Initial kWh * (1  System deg radation) ]
n 1
n

Where is N is life of system in years. 

TLCC can be calculated as follows: 

TLCC = LCC (Initial investments + Recurring Cost + Replacement cost) 

Thus in order to find out the TLCC one needs to know (i) initial investments, (ii) recurring cost (the cost 
of maintenance) and (iii) replacement cost incurred for the operation of system during its lifetime. 

(i) Initial investments mean the cost of system is estimated at the time of installation. This is nothing but 
the sum of all costs of the PV system components. 

(ii) The recurring costs are given as: 

 1  Inflation   1  Inflation  
N

LCC Re curring Cost  OM *   *     


 Discount rate  Inlation   1  Discount Rate  

Here the OM is nothing but Operation and Maintenance cost of the system at today’s rate.  

(iii) LCC Replacement Costs are given as: 

   1  Inflation  R y 
LCC Re placement Cost    Item Cost * 1      
   1  Discont Rate  
  

Where Ry = Replacement year 

Generally discount rate is greater than the inflation rate. Complex formula can be formed around tax, 
depreciation and debt components.  

For  calculating  the  LCC  of  Diesel  based  system,  one  must  calculate  the  LCC  of  diesel  annual  expense, 
diesel generator replacement, its respective O&M and initial expenses if any. 

 1  Fuel Escalation    1  Fuel Esc.  


N

LCC of Diesel  Ann. Diesel Cost *   * 1    


 Discount Rate  Fuel Escal.    1  DiscountRate  
Here N is life of system during which the operation is considered. 

Diesel based systems will face replacement expenses in generator and parts replacements and recurring 
expenses  in  operation  and  maintenance.  Environmental  costs  are  difficult  to  calculate  but  a  very 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     27 

 
Solar PV Electricity Solutions for Academic Campuses in India  
conspicuous component of costs; they are not included. Adding them will give the LCC of diesel based 
system. 

Similarly, the LCC of grid electricity can be calculated, only the annual diesel expense would be replaced 
by  annual  electricity  expenses.  Since  there  are  no  other  additional  expenses  in  terms  of  recurring  or 
replacement costs, the LCC of grid electricity will be the lowest. 

7.2   Comparison of LCC of Solar, Diesel and Grid electricity 
We shall now compare the cost of generating one unit of electricity from these various options. Table 
below  describes the assumptions and the LCC. 

Table: Comparison of Life Cycle Cost of Solar, diesel and grid electricity for the load of about 3 kW. 

Parameter  Solar  Diesel  Grid Electricity 

Interest Rate  14.29%  14.29%  ‐ 

Discount Rate  16.6%  16.6%  ‐ 

General Inflation  5%  ‐  ‐ 

Fuel Inflation  ‐  10%  ‐ 

Electricity Inflation  ‐  ‐  10% 

Unit Price  Rs. 100/W  Rs. 38/litre  Rs. 5/kWh 

No. of Years  25  25  25 

Units  generated  in  a  1,80,161  1,99,655  1,99,655 


year 

Cost  of  Electricity  Rs. 13.94/kWh  Rs. 18.77/kWh  Rs. 3 to 5 / kWh (domestic) 


(Rs/kWh)  Rs. 6 to 8 / kWh (commercial) 
Rs. 8 to 15 / kWh (industrial) 
    Rs. 14 to 15 / kWh for grid+diesel combined option 

From the Table it is obvious that the grid electricity when available will have to be utilized. But between 
solar  and  diesel,  solar  has  already  proved  competitive.  Going  forward,  assuming  a  10%  drop  in  SPV 
prices and 10% increase in diesel, the difference between the two would increase to Rs. 6.29 per kWh 
from the current Rs. 4.83 per kWh. 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     28 

 
Solar PV Electricity Solutions for Academic Campuses in India  
One can note from the above table that solar PV electricity is competitive with diesel+grid option, even 
in  today  cost  terms.  For  the  diesel  based  system  other  than  cost,  the  factors  like  availability,  cost 
uncertainty, maintenance, and storage of diesel also does not favor the use of diesel generator.  

The above table gives an estimation of cost of electricity for solar, diesel and grid electricity. However, 
the  final  cost  of  electricity  depends  on  many  parameters  related  to  site  where  the  electricity  is 
generated  and  used.  Therefore  there  will  always  be  some  variation  in  the  cost  of  electricity  from  one 
location  to  other  location.  The  Table  below  gives  an  indication  of  range  of  prices  of  electricity  on  per 
kWh basis for various electricity sources. These prices are indicative prices of prevailing condition as in 
year  2009‐10  and  can  change  with  the  time.  As  noted  earlier,  the  cost  of  diesel  based  electricity  is 
expected to rise further while the cost of PV based electricity is expected to decrease further with time. 

Table: Typical values of cost of electricity for various sources 

Source  LCOE (Rs per kWh) 

Grid electricity  Rs. 3 to 5 (domestic) 
Rs. 6 to 8 (commercial) 
Rs. 8 to 15 (industrial) 
Diesel based electricity  17 to 21 

Solar PV electricity (grid connected)  10 to 15 

Solar PV electricity (off‐grid)  12 to 17 

Wind based electricity  4 to 6 

8. Energy efficiency is recommended 
As can be seen from the calculations shown in the previous section that the cost of electricity generated 
from PV modules is much more expensive as compared to grid electricity. Therefore all efforts should be 
made  to  decrease  the  electricity  requirement  of  a  given  building,  before  planning  to  use  solar  PV  for 
electricity generation. Reduced energy consumption without affecting the operations can greatly reduce 
the amount of PV modules and battery required and, therefore, it can reduce the cost of PV system. 

 Decrease  in  electricity  requirement,  without  decreasing  the  usage  of  loads  or  functionality,  invariably 
requires  increase  in  energy  efficiency.  The  increase  in  energy  efficiency  for  an  academic  building  and 
appliances  can  be  obtained  in  several  ways.  It  includes  the  way  building  is  constructed  and  used,  the 
way electrical loads are selected and the way the users of electricity treat it. These are listed here: 

8.1  Energy efficiency of buildings 
If  PV  electricity  generation  is  planned  before  construction  of  building,  then  design  the  building  using 
what is known as “solar passive architecture”. In such design the heat intercepted by building wall and 
© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     29 

 
Solar PV Electricity Solutions for Academic Campuses in India  
roof  is  minimized,  use  of  day  light  for  illumination  is  increased,  arrangements  are  made  for  proper 
ventilation of spaces. Thus by incorporating the principles of solar passive architecture, one can reduce 
the energy consumption for cooling, light and ventilation. 

If building is already in place for which PV modules are to be installed, make efforts to decrease the heat 
gain of the building. This can be done in several ways; make the outer surfaces (walls and roofs) white 
(or light in color) so that some of the energy is reflected, make arrangements for sunshades particularly 
for south facing walls. A roof can be covered with white shiny tiles (may be broken tiles available at low 
cost) or in best case mirrors can be installed on the roof top to reflect most of incoming radiations. 

8.2  Energy efficiency of electrical loads 
 Electrical  loads  as  efficient  as  possible  should  be  used.  Investment  in  more  efficient  load  pays  back 
within few months to few years time. Light source can be replaced with more efficient florescent lamps, 
or LED based lighting. Also an electronic choke should be used with tube lights. More efficient fans are 
available  now  a  days.  Star  rating  system  is  being  used  to  mark  the  efficiency  of  air  conditioner  and 
refrigerator. These systems with higher star rating should be used. Laptops consume much less power as 
compared to desktops PCs (about 70 Watt as against 250 Watt), therefore as long as possible lap tops 
should be promoted for computing.  

Following are some of options that are available and can be used for electrical loads: 

 People detector based on IR signal 
 Timer based load switching 
 Light dimmers 
 Solid state lighting (LED) 
 Solid state fan regulators 

8.3  Energy efficiency of users 
 Users  of  electrical  energy  play  very  important  role  in  determining  the  effectiveness  of  energy  used. 
Efforts should be made to make all users aware about the negative environmental effects of use of fossil 
fuel based energy. In case of PV system usage, users should be made be aware to saving of electricity 
whenever  possible,  they  should  be  made  aware  of  high  cost  of  solar  PV  electricity.  Well  designed 
posters,  awareness  generation  workshops  and  e‐mail  reminders  can  play  important  role  in  promoting 
efficient use of electricity. 

9. Subsidies for installing solar PV systems 
 
Various kinds of subsidies are provided by both central and state government for installation of solar PV 
systems. These subsidies can be divided in following categories: 

 Subsidy for SPV rooftop systems for replacing diesel generators 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     30 

 
Solar PV Electricity Solutions for Academic Campuses in India  
 Subsidy for off‐grid PV systems 

 Subsidy for rural electrification 

 Interest rate subsidy 

Details  of  available  subsidies  are  given  in  following  sections.  The  details  of  subsidies  can  also  be 
obtained from Ministry of New and Renewable Energy Webpage, http://www.mnre.gov.in/ 

It must be noted that these subsidies are policy matters of the MNRE and may change time to time. 

9.1   Subsidy for rooftop PV systems 
Rooftop solar photovoltaic systems (with or without grid interaction) will be supported for installation in 
industrial and commercial establishments/ complexes (excluding manufacturers of SPV cells/modules), 
housing  complexes,  institutions  and  others  which  face  electricity  shortages  and  are  using  diesel 
generators for backup power. 
 
Central  Financial  Assistance  (CFA)  for  SPV  rooftop  Systems  (with  or  without  grid  interaction)  will  be 
limited to 100 kWp capacity. Minimum capacity of installation will be 25 kWp. In special cases, smaller 
capacity  systems,  not  less  than  10  kWp,  could  be  considered  for  financial  support  from  the  Ministry. 
Beneficiaries will exclude manufacturers of SPV cells/modules. Maximum system capacity for sanction of 
CFA will be linked to the capacity of the existing diesel sets installed by the beneficiary entity. An entity 
seeking CFA for a particular kWp SPV system must have a DG set of at least that capacity installed in its 
premises. 
 
The Central Financial Assistance is mentioned in Table below. The Government’s intent is to phase out 
the CFA scheme and emphasis on the Interest rate subsidy scheme mentioned in Table below. 
 
 
Table  – Central Financial Assistance for decentralized Solar PV Applications  
 
System Capacity  Central Finance Assistance 

Stand‐alone SPV Power Plants      

          >1 kWp  Rs. 225/Wp  Rs. 125/Wp 

          >10 kWp with distribution line  Rs. 270/Wp  Rs. 150/Wp 

SPV Traffic Lights  Rs.150/Wp  for  systems  with  battery  bank  of  6 


hrs/Rs.115/Wp  without  battery  bank  for  organizations 
SPV Blinkers  not availing accelerated depreciation. 
SPV Power Packs < 1kWp  Rs.100/Wp  for  systems  with  battery  bank  of  6  hrs  / 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     31 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Solar Billboards <= 1 kWp  Rs.75/Wp without battery bank for organizations availing 
accelerated depreciation. 
Other systems for Commercial and Urban 
areas 

SPV  Rooftop  Systems  in  Urban  Areas  –  Rs. 75/ Wp, limited to 30% of the cost of systems to profit 


from 10 kW to 100 kW  making bodies availing depreciation benefits Rs. 100/ Wp, 
limited  to  40%  of  the  cost  of  systems  to  non‐  profit 
making bodies 

9.2   Interest rate subsidies 
There  is  also  scheme  for  providing  subsidy  in  the  form  of  soft  loan  or  low  interest  loans.  Almost  all 
interested people can avail this type of subsidies. The details of interest rate subsidy program is given 
below in Table. 

Table– Interest Rate subsidies available through IREDA and Banks 

Features  Implementation through 

  IREDA (Indian Renewable Energy Development  Banks 
Agency) 

Eligible Categories  All categories of users including intermediaries  Individuals  and  organizations 


and  commercial  organizations.  Manufacturers  which  do  not  claim  any 
of PV systems are not available.  depreciation  benefits  on  the 
investment 

Rate of Interest  7%  (commercial  borrowers,  who  can  claim  5% 


depreciation benefits) 

5%  (individuals  and  other  organizations  which 


undertake  not  to  claim  depreciation  benefits). 
Financial  intermediaries  who  borrow  funds 
from IREDA for on‐lending at 5% or 7% rate of 
interest,  will  be  charged  an  interest  rate  of 
2.5%  or  4.5%  respectively  by  IREDA.  Such 
intermediaries  will  not  be  able  to  claim 
depreciation  benefit  and  the  on‐lending 
arrangement  will  not  be  treated  as  a  lease 
arrangement. 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     32 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Loan Period  5 years  5 years 

Moratorium  1 year  No moratorium 

Amount of Loan  Upto 80% of the cost of the  Upto 85% of the cost of the 

Project  systems 

Upper  limits  for  a  No limit  Rs. 5 lakhs 


loan 

Service Charge  1% of the loan disbursed  Rs.300 per loan disbursed 

Systems covered  All types of SPV systems are covered under this  All  types  of  SPV  systems  are 


scheme.  Loans  will  not  be  provided  at  covered  under  this  scheme. 
subsidized  rates  for  systems  that  are  available  Loans  will  not  be  provided  at 
with capital subsidy, with the exception of solar  subsidized rates for systems that 
generators  and  solar  pumps  for  which  both  are  available  with  capital 
subsidies and soft loans will be available during  subsidy,  with  the  exception  of 
2005‐06.  solar  generators  and  solar 
pumps  for  which  both  subsidies 
and  soft  loans  will  be  available 
during  2005‐06.  For  solar  home 
systems  installed  as  part  of  the 
MNRE  programme  for 
electrification of remote villages, 
banks may provide soft loans for 
the  unsubsidized  portion  of  the 
cost of the systems. 

Note those users can either available subsidy in capitol cost or interest rate subsidy (soft loan) but not 
both. 

10. Recommendations for use of Solar PV electricity 
The report has described how PV modules can be used to generate electricity for academic campuses in 
India. The emphasis is given to academic campuses for the report can be used to design and implement 
solar PV system for other applications as well.  

The report has brought out the points, particularly from technology perspective to demonstrate how it 
is  possible  to  use  solar  PV  power  for  electricity  generation.  It  is  feasible  to  install  solar  PV  power  for 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     33 

 
Solar PV Electricity Solutions for Academic Campuses in India  
fulfilling electricity needs of academic campuses in India. It is feasible both from technology as well as 
economic perspective. Therefore it is recommended to install PV modules.  

There are some other points, which are important considering the long term perspective on the growth 
of  the  country,  mentioned  here  which  support  the  recommendations  for  installing  PV  modules  for 
electricity generation in academic campuses. These points are: 

 There are power shortages in many areas of the country where there is grid. But there are large 
number  of  areas  where  grid  has  not  yet  reached.  Supplying  power  to  all  requires  use  of 
alternative sources. 

 India is blessed with good amount of sun shine. The sunshine is available bright enough is most 
of the areas of the country for generation of electrical energy.  

 There  are  favorable  government  policies  exist  in  the  country  for  promotion  of  solar  PV 
technologies for power generation. 

 Use of PV power is useful in reducing the pollution.  

 Installation and use of PV modules would result in public awareness. Increased public awareness 
can be useful in setting appropriate policies for long term sustainable development. 

 Installation  of  PV  modules  for  power  generation  would  results  in  creation  of  employment  for 
hundreds of thousands of people across the country over coming decade. 

 Use of solar PV power in the campus would sensitize young people about the climate change, 
availability and use of alternative energy sources. These young students in future would become 
researchers and policy makers of future.  Skilled researchers and knowledgeable policy makers 
are desirable for the country’s growth. 

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     34 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Appendix‐A 
Monthly  averaged  daily  global  (G),  monthly  averaged  daily  diffused  (D)  and  monthly  averaged  daily 
global radiation on the horizontal surface and on the surface tilted at latitude of the location (GL). G, D 
and GL are in kWh/m2‐day (kilo‐Watt‐hour/ m2‐day). 

January to April 

Jan Feb Mar Apr

G D GL G D GL G D GL G D GL

City

Ahmedabad 5 1.2 6.8 5.9 1.3 7.3 6.6 1.6 7.2 7.3 1.8 7.2

Bangalore 5.6 1.6 6.4 6.4 1.6 7.0 6.8 1.9 7.0 6.8 2.2 6.6

Bhubaneshwar 5.2 1.4 6.7 5.9 1.4 7.0 6.3 2 6.8 6.5 2.4 6.4

Bhopal 4.8 1 6.6 5.9 1 7.4 6.3 1.6 6.9 7 1.8 6.9

Chandigarh 3.6 1.6 5.4 4.7 2 6.2 5.6 2.4 6.4 6.6 2.6 6.6

Chennai 5.4 1.8 7.5 6.3 1.7 6.9 6.6 2 6.8 6.8 2.2 6.6

Delhi 4.3 1.3 6.3 5 1.4 6.6 6 2 6.8 6.8 2.4 6.8

Gwalior 4.5 1 6.5 5.5 1 7.1 6.2 1.6 7.0 7.5 1.8 7.4

Goa 5.6 1.4 6.7 6.3 1.4 7.1 6.6 1.8 6.9 6.8 2.4 6.6

Guwahati 3.8 1.6 5.2 4.8 2 6.0 5.4 2.4 5.9 5.8 2.8 5.7

Hyderabad 5.5 1.4 6.7 6.2 1.5 7.1 6.5 2 6.8 6.9 2.4 6.7

Indore 5.1 1.1 6.9 5.9 1.3 7.3 6.4 1.6 6.9 7.4 2 7.3

Jabalpur 4.9 1.1 6.6 5.7 1 7.1 6.2 1.6 6.8 6.9 1.8 6.8

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     35 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Jamnagar 4.9 1 6.5 5.8 1.2 7.1 6.2 1.8 6.8 7 2.2 6.9

Jodhpur 4.6 1 6.7 5.6 1.1 7.3 6.6 1.7 7.4 7.3 1.8 7.2

Kolkatta 4.7 1.4 6.1 5.6 1 6.7 6.2 1.6 6.7 6.6 1.7 6.5

Lucknow 4.3 1.4 6.2 5.2 1.2 6.7 5.9 2 6.6 6.8 2.4 6.7

Mumbai 5.2 1.4 6.6 5.9 1.4 6.9 6.5 1.8 6.9 6.9 2.2 6.7

Nagpur 5 1.2 6.6 5.9 1.2 7.1 6.3 1.8 6.8 6.8 2.2 6.7

Patna 4.4 1.6 6.0 5.3 1.7 6.6 6.1 2.2 6.7 6.7 2.5 6.6

Pune 5.3 1.4 6.6 6 1.4 7.0 6.6 1.8 7.0 6.8 2.2 6.6

Ranchi 4.7 1.2 6.4 5.6 1.0 7.0 6.4 1.8 7.0 7 2.2 6.9

Solapur 5.6 1.4 6.9 6.3 1.4 7.3 6.6 2.0 7.0 6.8 2.4 6.6

Trivendrum 6 1.8 6.5 6.6 1.8 7.0 6.8 2.0 6.9 6.5 2.4 6.4

Visakhapatnam 5.3 1.5 6.5 6 1.6 6.9 6.5 2.0 6.9 6.5 2.5 6.3

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     36 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Appendix‐A (continued) 
Monthly  averaged  daily  global  (G),  monthly  averaged  daily  diffused  (D)  and  monthly  averaged  daily 
global radiation on the horizontal surface and on the surface tilted at latitude of the location (GL). G, D 
and GL are in kWh/m2‐day (kilo‐Watt‐hour/ m2‐day). 

May to August 

May Jun Jul Aug

G D GL G D GL G D GL G D GL

City

Ahmedabad 7.6 2 6.9 6.6 3 5.9 5 3.4 4.6 4.6 3.3 4.4

Bangalore 6.4 2.6 6.0 6 3 5.6 4.6 2.9 4.4 4.8 3 4.7

Bhubaneshwar 6.4 2.6 5.8 5.3 3 4.8 4.6 3 4.3 4.8 3 4.6

Bhopal 7.2 2 6.5 6.2 2.9 5.5 4.7 3.2 4.4 4.4 3.1 4.2

Chandigarh 7.3 2.8 6.7 7 3.2 6.2 6.2 3.2 5.6 5.8 3 5.5

Chennai 6.3 2.4 5.9 5.5 2.8 5.1 5.2 2.9 4.9 5.6 2.8 5.4

Delhi 7.2 2.8 6.6 6 3.1 5.3 5.7 3 5.1 5.6 2.9 5.3

Gwalior 7.1 2 6.4 6.5 2.8 5.7 5.2 3 4.7 5 3 4.8

Goa 6.6 2.6 6.1 4.9 3 4.6 3.8 3.1 3.6 4.4 3 4.2

Guwahati 5.6 3 5.1 4.6 3.2 4.2 4.8 3.2 4.4 5 3 4.8

Hyderabad 6.9 2.5 6.4 5.8 3.2 5.3 4.9 3.3 4.6 5.2 3.2 5.0

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     37 

 
Solar PV Electricity Solutions for Academic Campuses in India  

Indore 7.4 2.1 6.7 6.4 3 5.8 4.9 3.4 4.6 4.4 3.2 4.2

Jabalpur 6.6 2.2 6.0 5.8 2.8 5.2 4.8 3 4.5 4.4 3 4.2

Jamnagar 7.4 2.1 6.7 6.2 3.1 5.6 5 3.4 4.7 4.8 3.2 4.6

Jodhpur 7.8 2.2 7.1 7.4 3 6.5 6.2 3 5.6 6 3 5.7

Kolkatta 6.4 2 5.9 5.2 2.8 4.7 4.8 3.1 4.4 4.8 3.1 4.6

Lucknow 7.2 2.6 6.5 6.4 3.2 5.7 5.6 3.1 5.1 5.6 3 5.3

Mumbai 7.2 2.4 6.6 5.4 3 4.9 4.4 3.3 4.1 4 3.2 3.8

Nagpur 6.8 2.5 6.2 5.6 3.1 5.1 4.4 3.2 4.1 4.4 3.2 4.2

Patna 6.8 2.7 6.2 6.2 3.2 5.5 5.2 3.2 4.7 5.6 3 5.3

Pune 7.2 2.4 6.6 5.6 3.4 5.1 4.4 3.4 4.2 4.4 3.4 4.2

Ranchi 6.9 2.3 6.3 6 2.9 5.4 4.8 3 4.4 5 3 4.8

Solapur 6.6 2.6 6.1 5.7 3.3 5.2 4.6 3.4 4.4 4.8 3.3 4.6

Trivendrum 6.8 2.6 6.5 5.2 2.6 5.0 5.4 2.8 5.2 5.8 2.8 5.6

Visakhapatnam 6.4 2.6 5.9 5 3 4.6 4.8 3 4.5 5 3 4.8

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     38 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Appendix‐A (continued) 
Monthly  averaged  daily  global  (G),  monthly  averaged  daily  diffused  (D)  and  monthly  averaged  daily 
global radiation on the horizontal surface and on the surface tilted at latitude of the location (GL). G, D 
and GL are in kWh/m2‐day (kilo‐Watt‐hour/ m2‐day). 

September to December 

Sep Oct Nov Dec

G D GL G D GL G D GL G D GL

City

Ahmedabad 5.6 2.7 5.8 6 1.7 7.0 5.3 1.1 7.0 4.8 1 6.7

Bangalore 5.2 2.9 5.2 5.4 2.6 5.7 5 2 5.1 4.9 2 5.6

Bhubaneshwar 5.2 2.8 5.3 5.2 2.2 5.8 5.3 1.5 6.6 5.1 1.4 6.7

Bhopal 5.1 2.6 5.2 5.8 1.6 6.8 5.3 1 7.1 4.7 1 6.6

Chandigarh 5.8 2.5 6.2 5.2 1.9 6.6 4.3 1.4 6.3 3.5 2 5.4

Chennai 5.8 2.8 5.8 5 2.4 5.3 4.9 2.2 5.4 4.7 2 5.3

Delhi 5.7 2.2 6.0 5.4 1.5 6.7 4.7 1.1 6.8 4 1.2 6.1

Gwalior 5.6 2.3 5.9 5.8 1.5 7.1 5 1 7.0 4.3 1 6.4

Goa 5 2.8 5.0 5.4 2.4 5.8 5.7 1.6 6.7 5.4 1.4 6.5

Guwahati 4.6 2.8 4.7 4.6 2.2 5.4 4.5 1.6 6.1 4 1.4 5.7

Hyderabad 5.2 3 5.2 5.8 2.3 6.3 5.4 1.8 6.4 5.1 1.4 6.3

Indore 5.2 2.8 5.3 5.8 1.8 6.7 5.4 1.2 7.1 4.8 1.6 6.6

Jabalpur 5 2.5 5.1 5.6 1.6 6.5 4.9 1 6.4 4.5 1 6.3

Jamnagar 5.6 2.6 5.8 6 1.6 7.0 5.3 1.1 6.9 4.8 1.1 6.6

Jodhpur 6.2 2 6.5 6 1.2 7.4 5.1 1.1 7.2 4.5 1.1 6.8

Kolkatta 5 2.4 5.1 5.2 1.4 5.9 4.5 1 5.7 4.2 1.5 5.6

Lucknow 5.5 2.4 5.8 5.2 1.6 6.3 4.8 1.3 6.7 4.2 1.2 6.2

Mumbai 5.2 3 5.3 5.6 2 6.3 5.3 1.4 6.5 4.9 1.1 6.3

Nagpur 5 2.8 5.1 5.6 1.8 6.4 5.3 1.2 6.5 4.8 1 6.5

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     39 

 
Solar PV Electricity Solutions for Academic Campuses in India  
Patna 5.4 2.8 5.6 5.2 2 6.1 4.9 1.6 6.6 4.3 1.5 6.1

Pune 5.4 3 5.4 5.6 2.3 6.2 5.4 1.5 6.6 5 1.3 6.4

Ranchi 5.2 2.6 5.3 5.2 1.8 6.0 5.4 1 7.2 4.8 0.9 7.0

Solapur 5.3 3 5.3 5.6 2.2 6.1 5.4 1.7 6.4 5.2 1.4 6.5

Trivendrum 6 2.6 6.0 5.4 2.4 5.6 5.3 2.4 5.6 5 2.1 5.4

Visakhapatnam 5.2 2.8 5.3 5.2 2.4 5.7 5.2 1.8 6.2 5 1.4 6.3

© C.S. Solanki, Dept. of Energy Science and Engineering, IIT Bombay     40 

You might also like