Damper types
1
UL555 is the test standard for fire dampers. UL555S is the standard for smoke dampers.
Combination fire and smoke dampers must meet both.
2
Under the present UL555 dampers designed to close while fans operate must maintain their fire
resistance under dynamic airflow pressure. Static rated dampers are used when fans shut down
in event of a fire.
1
Several million fire dampers are installed each year in barriers that are
designed to slow the spread of fire. See Figure 1.3
2. Smoke dampers are actuated. They must open and close when
required to provide fresh air or to stop smoke passage. They do not have to
have high limit sensors or fusible links to close automatically. Smoke dampers
often provide signaling for indicator lights as discussed below.
Practices vary by geographical region and by type of smoke control
mandated by codes. Most commonly, a smoke detector (or two) inside the ducts
will shut down the fan(s) and close the damper(s) if smoke is detected. Area
smoke detectors are sometimes wired to a central fire alarm panel and a panel
contact or a remote relay initiates closing.
Smoke dampers need not be within the wall providing the smoke barrier,
merely within 24 inches. As a result, the actuators may be axle shaft mounted.
However most are jackshaft mounted with linkage to the damper blades. See
Figure 2.
3. Combination fire and smoke dampers are more common than simple
smoke dampers. Since these are fire rated, the damper blades must be in the
barrier wall. The actuator cannot be in the wall so a jackshaft and linkage are
3
Photographs courtesy of Pottorff.
2
employed with the actuator connected to the jackshaft extension outside the
damper sleeve. 4 Almost all actuators today are direct coupled.
Courtesy Pottorff-PCI
Basic Control
There are several accepted methods for temperature sensing and actuator
control.
A fusible link that restrains a shaft spring can perform the fire damper
function while an actuator provides the smoke control function. The fusible link
disconnects the damper blades from the actuator and ensures its closure. The
actuator can open and close for smoke management only until the fusible link
melts.
Alternately, an electric bimetal sensor with a reset button can be used for
the single primary sensor. See Figure 3.
Combination fire and smoke dampers in more sophisticated smoke control
systems will have two sensors – primary and secondary. The primary can be
overridden by firefighters’ control; the secondary is manual reset only.
When a dual sensor is used, the first sensor is always electric. It opens,
removes power, and lets the actuator spring the damper closed. The second
4
There are other methods; however this is standard in the US today.
3
sensor may be a fusible link or a higher temperature electric sensor. Typically,
the temperatures are 165ºF (74ºC) for the primary and 250ºF (121ºC) for the
secondary. In about 20% of cases, 350ºF (171ºC) is used for the secondary
sensor.
The system in Figure 3 is found in about 80% of the combination fire and
smoke dampers. A smoke detector with a local thermal sensor is used as
shown. This is a containment damper application.
4
Reopenable Dampers
SMOKE DETECTOR OR
OTHER ALARM SYSTEM
CONTACTS LOCATED HERE
165F 250F
N
A
O ACTUATOR
HOT
H
HOA
Sequence of operation
FIRE FIGHTERS Auto: If duct temperature reaches 165°F or external alarm
CONTROL PANEL
contact opens, power is cut to actuator and damper springs
closed.
If the Hand-Off-Auto switch at the Fire Fighters’ Control
Station is moved to hand, then the contact and thermal
switch are bypassed and the actuator again receives
power and the damper opens.
If the duct temperature reaches 250°F, then the actuator springs
the damper closed. Manual reset is required.
If the HOA switch is moved to off at any time, the
actuator springs closed.
5
Original damper designs were released by external springs only and the
actuator did not have an internal spring. Later, a fusible link and dual springs
were standard. They used one fire spring that closed the damper until manually
reset and a spring to close the damper if the actuator lost power. The actuator
could reopen against this spring. Now most manufacturers use electronic
methods of sensing and control. This means the actuator spring is the only
spring in the most recent designs.
Indicator lights
The Fire Fighters’ Smoke Control System5 (FSCS) has status indication
lights in addition to the manual HOA switches. The lights allow the position of the
dampers to be determined and allow verification of damper positions and
override status.
The indicator lights can be initiated from auxiliary switches on the actuator
or damper blade switches. Proximity switches are sometimes used, but the cost
is usually prohibitive. With the spring in the actuator to operate the damper,
actuator switches are often preferred as they are as reliable as blade switch
indication. The linkage between the actuator-jackshaft and the damper is more
robust than the typical coat hanger connection from damper blade to switch
package.
Full engineered smoke control systems exist only in about 10% of
applications. With these the fire fighters have control of dampers and indicator
lights show status.
Figure 5 shows a simple method of wiring to indicator lights. This system
would be typical for a containment damper and the lights could be in a panel or a
local junction box, possibly in the ceiling. A FSCS panel would often have an
amber light indicating fault. If the damper is closed, the red light is on. If the
damper is open, the green light is on. A variety of wiring methods is possible.
5
Also referred to as Fire Fighters' Control Panel and Fire Fighters' Control Station in different
sources. NPPA 92 uses Fire Fighters Smoke Control System.
6
In some jurisdictions the red light means “FIRE” or “Problem” and the
green means OK. In others, green means on and red means off, particularly for
fans. Although rare, some dampers are normally open when not powered and
the red and green could be confused. This can confuse the fire fighter in the
confusion of a fire. Indication lights should be discussed with the fire department
to ensure correct operation.
Green On Red On
= =
Open Closed
NO Contact
NC Contact
Contacts can be
actuator auxiliary
contacts or damper
blade switches.
Hot Com
24 V 24 V
or L1 or N
7
constraints, one damper and actuator are technically and economically superior
to two (or three if the wall is also a fire barrier).
Actuator Proportional
Shaft
Stairwell
Pressurization
6
In January of 2008, California will go over to the IBC (International Building Code) which uses
the UL555S 75 second operation time. This is the standard in almost all of the US.
8
maximum for operation. The Belimo FSAF24-SR meets the 75 second
requirement.
Conclusion