Al-MOATASEM ADMINISTRATION BUILDING- ABDEL-SALAM HEGAZY-TANTA - 25.10.

2010
-1 -
Item Descreption Unit Qty Unit Price Total Price

Supply ,install ,commisioning and guarantee of the


following :-

Installation only: Connection, testing and commissioning of air


cooled chiller, 380 voltage, 50Hz, complete with all fitting, control
valves, coil, filters, refrigerant , microprocessor interface, water
flow switches, balancing valve, flexible connection, butterfly valves,
strainer, pressure gauges, thermometer, safety devices, chillers
1 complete with base ,vibration isolators and all other accessories and No. 3
connections as shown per drawing and specifications.CH 100 T.R,
245 GPM at outdoor temperature 105 F and 54/44 F inlet/outlet
chilled water.

2 Chilled Water Pumps (CH.W.P)


Supply, install, testing and commissioning and guarantee:
Chilled Horizontal water pump, constant speed centrifugal
Horizontal split case pump complete with automatic air vent, gate
valves, flexible connections , strainer, check valve , drainage valve,
pressure gauge, all connection piping steel base, TEFC motor type,
coupling guard, opening drip proof motor, fitting and all other
accessories and according to the capacities and specification as
shown on drawing and specifications. CH.W.P- 245 GPM, 100 ft. No. 4
water Head 1450 rpm, 380/3/50,(one pump is standby).

3 Fan Coil Units (FCU)

3A F.C.U-1 18000 BTU/hr No. 5


3B F.C.U-2 24000 BTU/hr No. 58

3C F.C.U-3 30000 BTU/hr No. 15

3D F.C.U-4 48000 BTU/hr No. 5


3E F.C.U-5 60000 BTU/hr No. 2

4 Split units Air Conditioning


Supply, Installation, connection, testing and commissioning of
Split Air Conditioning units complete with all other
accessories and according to the capacities and specification as
shown on drawing and specifications. The duty and numbers are
given below:

SACU 24000 BtU/hr and electric heater No. 3


Supply, insstall, testing and guarantee of AHU for fresh air each of
cduty 3000CFM at 3.0" c/w cooling coil 20 TR and electrical
5 heaters, filter section (Pre- and Bag) all ancillaries, etc. No. 2

6 Supply Fans and Exhaust Fan (S.F.&Ex.F)


Supply, installation, connection, testing and commissioning of
Supply and exhaust fans complete with fan, motor, vibration
isolators, filters and all other accessories and according to the
capacities and specification as shown on drawing and
specifications. their duty and numbers are given below:

6A S. F.1 4450 CFM,1.5” WG E.S.P No. 1


Al-MOATASEM ADMINISTRATION BUILDING- ABDEL-SALAM HEGAZY-TANTA - 25.10.2010
-2 -
Item Descreption Unit Qty Unit Price Total Price

6B EX. F.1 8800 CFM,1.5” WG E.S.P No. 1

Supply, install and guarantee of exhaust fans for


7 toilets, wall or glass mounted with the capacities No.
shown on the drawings, 50 CFM and 75 CFM

8 Duct Works

Supply ducts and return and exhaust ducts (if required) made
of galvanized sheet metal of thickness according to SMACNA
c/w flanges, slip bars, hangers, supports control dampers, fire
9 dampers and all necessary ancilaries, etc. LS

Air duct insulatin 25 mm thickness from glass wool with


aluminum face to prevent condensation, density 24 kg/mm3
10 LS

Air duct as above but of double skin used in the roof of the
building and in the shafts , internal cladding of thicness o.6
mm and external of thickness accordindg to SMACNA,
complete with flanges. The insulation is hard board glass fibre
11 of rhickness 13 mm and to be glued on the sides of the LS
external ducts c/w flanges,hangers, supports control dampers,
fire dampers and all necessary ancilaries, etc.

12 Grilles

Air distributer supply grilles of face area 800x150 mm


complete with plenum insulate with closed cell insulation, neck
with circular damper, flexible insulatin duct of 10"/12" diameter
and collet to the ducts and plenum, all to fit in in false ceiling
12A boards and c/w hanging rods, necessary ancilaries,etc. LS

Air return grilles with dampers of face area 800x150 mm


complete with plenum insulate with closed cell insulation, neck
with circular damper, flexible insulatin duct of 10"/12" diameter
12B and collet to the ducts and plenum, all to fit in false ceiling LS
boards and c/w hanging rods, necessary ancilaries,etc.

Air return grilles with dampers of face corresponding to the


given data on the drawings for fresh air supply and
12C connection to the ducts , c/w necessary ancilaries,etc. LS

13 Piping

Chilled water from seamless black steel (schedule No. 40)


including all fittings, bends, elbows, expansion joints,
LS
supports, hangers, and all accessories according to
specification and drawings.

14 Piping insulation

Chilled water piping insulation with vapour barrier, density 70-


80 kg/ m3, inside diameter including elbows, reducers, valves, LS
pumps, etc

15 Valves andstrainers
Al-MOATASEM ADMINISTRATION BUILDING- ABDEL-SALAM HEGAZY-TANTA - 25.10.2010
-3 -
Item Descreption Unit Qty Unit Price Total Price

Balancing Valve, gate valves butterfly valves, Strainer, etc.


according to specification and drawings. LS

16 Expansion Tank

Supply, installation, connection, testing and


commissioning of chilled water expansion tank
complete with fitting, valves, controls valves and all
other accessories as shown per drawing and
specifications.

16A Chilled Water Expansion Tank, 1m3 No. 1

16B Make-up pump 5m3/hr at head 5 bar No. 1


17 Air separator

Supply, installation, connection, testing and


commissioning of chilled water air separator complete
No. 1
with fitting, valves and all other accessories as shown
per drawing and specifications

Control and operation panels (MCCs) for the chillers,


18 pumps and AHUs Class IP 44 complete with all LS
necessary cable glands, etc.

Wiring, cabling for power from the chilled water panel


in the room at roof to the chilled water system
19 LS
(chillers, pumps and AHUs) with all necessary
conduits, cable trays, cable ladders, etc.

Wiring, power cables and control cables of the whole


water system and coordination with the electrical
20 LS
contractor for Wiring, cabling for fine coil units and the
DX-split units in the floors.

Wiring, power cables and control cables of the whole


water system and coordination with the electrical
21 LS
contractor for Wiring, cabling for fine coil units and the
DX-split units in the floors.

22 Testing and commissioning of HVAC system LS

Any missing item that could be foreseen from the


contractor in order to consider this as turn key project.
23 LS
If no value given to this item, it means acceptance of
the above values to cover the whole project