Econo.
Inlet
Discharge
Economizer Port Location
The Economizer Port
• A port placed in the rotor housing can
locate any pressure between suction and
discharge.
• This port acts as a secondary suction
port.
• The additional flow does not reduce the
primary suction gas flow.
• The gas mixes in the screw threads and is
carried on to discharge.
• Compression efficiency is high as
additional frictional power is small.
• Like a “frictionless” compressor
Uses of the Econo. Port
• This secondary suction port is used
in two ways.
• Sideloads are generally gas flows
coming from a secondary, (higher
temp.) evaporator.
• Economizers are used to subcool
condenser liquid.
Sideload Evaporators
Condenser
Secondary Evaporator
Comp.
Evaporator
Econo.
? psia
96 F
200 psia
NH3 Sideload Example -
What pressure is the port ?
100 %
Volume
62% Volume
Econo.
? psia
96 F
200 psia
Port pressure ~=(Volume ratio)^k * (P suction)
NH3 k ~= 1.29
Port pressure = (1.6^1.29) * 20 psia = 37 psia
-17 F
20 psia
8F
37 psia
96 F
200 psia
Port pressure ~=(Volume ratio)^k * (P suction)
NH3 k ~= 1.29
Port pressure = (1.6^1.29) * 20 psia = 37 psia
-17 F Evaporator
96 F Condenser
Secondary Evaporator
8 F Secondary Evaporator
Comp.
-17 F Evaporator
1000
100
10
1
0 100 200 300 400 500 600 700 800 900
1000
100
Sideport
10 Evaporator
1
0 100 200 300 400 500 600 700 800 900
-20 F
18 psia
96 F
200 psia
Port pressure ~=(Volume ratio)^k * (P suction)
NH3 k ~= 1.29
Port pressure = (1.6^1.29) * 10 psia = 18 psia
-40 F Evaporator
96 F Condenser
Secondary Evaporator
-20 F Secondary Evaporator
Comp.
-40 F Evaporator
72 F
133 psia
96 F
200 psia
Port pressure ~=(Volume ratio)^k * (P suction)
NH3 k ~= 1.29
Port pressure = (1.6^1.29) * 73 psia = 133 psia
40 F Evaporator
96 F Condenser
Secondary Evaporator
72 F Secondary Evaporator
Comp.
40 F Evaporator
8F
37 psia
96 F
200 psia
Effect of Lower
Condensing Pressure
-17 F
20 psia
8F
37 psia
75 F
140 psia
Effect of Lower
Condensing Pressure
-17 F
20 psia
8F
37 psia
75 F
140 psia
Port pressure ~=(Volume ratio)^k * (P suction)
NH3 k ~= 1.29
Port pressure = (1.6^1.29) * 20 psia = 37 psia
-17 F
20 psia
8F
37 psia
75 F
140 psia
Econo. Pressure is a function of suction
pressure and port location only ! Not discharge
pressure !
-17 F
20 psia
8F
37 psia
96 F
200 psia
Zero flow
P=37 psia
Liquid from cond
16 lbm/min
P=37 psia
Liquid from cond
21 lbm/min
P=38 psia
Liquid from cond
28 lbm/min
P=40 psia
Thread packing brings up the pressure
in the screw thread
Sideload Capacity NH3 Refrig.
as a % of suction capacity
Sideload Temp.
% of Suct. Tons Refr.
400%
40F
300%
20F
200%
0F
100%
-10F
0%
-40 -20 0 20
Sat. Suct Temp. F
Sideload Evaporator Piping
Condenser
Secondary
SecondaryEvaporator
Evaporator
Evaporator
Economizer Piping
Condenser
Flash
Economizer
Evaporator
An Economizer is a special case of a sideload
evaporator, where part of the condensed liquid is
evaporated to cool the remainder of the condensed
liquid.
96F liq
Condenser
Flash 18 lbm/min
Economizer Comp.
17 F liq Evaporator -17F
(45psia) 100 lbm/min
(20 psia)
NH3
R-717
Single stage compression
10000
Absolute Pressure (PSIA)
1000
229 Tons
Refrigeration
100
in
/m
m
10
lb
(hg-hf)=458b/lbm
0
10
1
0 100 200 300 400 500 600 700 800 900
19% increase in
1000 evaporator tons
@273
sameTons
evaporator
Refrigeration
massflow
100
19 lbm/min
in
/m
m
10
lb
(hg-hf)=458b/lbm
0
10
(hg-hf)=545b/lbm
1
0 100 200 300 400 500 600 700 800 900
in
/m
m
100
lb
19 lbm/min
9
11
10 100 lbm/min
1
0 100 200 300 400 500 600 700 800 900
19 lbm/min
45 psia
119 lbm
96 F
The economizer vapor is at a lower 200 psia
compression ratio, and adds no
additional friction to the compression
NH3 Cycle efficiency
-17 F evaporator
96 F condensing
Capacity Power HP/TR
229 494 2.16 non-Econ
273 538 1.97 Econo.
19% 9% 9.6% improved
R-22 Cycle efficiency
-10 F evaporator
95 F condensing
Capacity Power HP/TR
106 212 2.0 non-Econ
136 230 1.7 Econo.
28% 8% 17% improved
Capacity and Power Non-E
800
700
600
Power NH3
TR & BHP
500 R507
R22
400
NH3 BHP
300 R507 BHP
Capacity R22 BHP
200
100
0
-60 -40 -20 0 20 40 60
700
Power
600
R507 Cap
400 R22 Cap
NH3 HP
R507 HP
300
R22 HP
Capacity
200
100
0
-60 -40 -20 0 20 40 60
4 NH3 E
R507 E
R22 E
3
NH3 non
R22 non
2 R507 non
0
-60 -40 -20 0 20 40 60
4.5
4
NH3 E
3.5
R507 E
3 R22 E
NH3 non
2.5 R22 non
R507 non
2
1.5
1
-55 -50 -45 -40 -35 -30 -25 -20
450
400
350
Lbm/min
300
NH3
250 R507
R22
200
150
100
50
0
-60 -40 -20 0 20 40 60
80.0%
70.0%
60.0%
30.0%
20.0%
10.0%
0.0%
-60 -40 -20 0 20 40 60