Professional Documents
Culture Documents
Synchronous Generator
Course Work
Load Test (With purely Inductive Star Connected Load, where cos ∅=1)
Load Voltage(V) Load Current(A)
0 6.2
20 5.23
40 4.25
60 3.7
80 3.06
100 2.26
115 1.7
OBJECTIVES
Part A. To determine the regulation of an alternator using following tests
Open circuit test
Short circuit test
Load test
Part B. Understanding the operation of synchronization
Synchronization using dark lamp method
APPARATUS
DC Ammeter (1.0A)
AC Ammeter (0-5-10A)
AC Voltmeter (0-150-300V)
Rheostat (1040Ω)
Inductive Load (Star connected)
THEORY
Part A.
Open circuit and Short circuit test
Open circuit and Short circuit characteristic are as following
V, I
Open circuit characteristic
VT
C’
Ia’ B’
Ia
A’
If Ia’ Field Current
raxa
Is/c
Eg=Vo/c
If
Vo/c
Eg=Vo/c
If
R’ Y’ B’
Lr Ly Lb
R Y B
Generator side
At the instance of switch connecting the system and generator, each phases of the generator should
PROCEDURE
Open circuit test
Connect the circuit as follows and run the generator in synchronous speed, by varying the output
voltage observe the field current.
A
220V V
DC
220V
DC
Load test
Connect the circuit as follows and run the generator in synchronous speed, by varying the connected
load observe the load current and load voltage.
A
A
220V V
DC
Sync
hronization using Dark lamp method
Connect the circuit as follows and run the generator in synchronous speed.
If the System side two sets of pharos have the very small relative
rotational speed (ωs) voltage across lamps will rise
and fall slowly. We can observe it by the brightness
change R’ Y’ B’ in the bulbs.
At Lr Ly Lb the correct phase position lamps are equally dark
during the middle of this period Switch (Circuit Breaker)
must be closed to cause no interruptions.
R Y B
Generator side
CALCULATIONS
1. Characteristic of open circuit voltage and short
circuit current with respect to field current
300
290
280
270
f(x) = 912.1 x³ − 1713.59 x² + 1130.34 x + 10.45
260
250
240
230
220
210
200
190
180
170
160
150
140
130
120
110
100
90
80
70
60
50
40
30
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Field Current(A)
Vo /c AC
2. when ra is negligible x s= =
Is/c AB
From the graph (short circuit current and open circuit voltages calculated using the equations of
the graphs)
Field Current(A) Short circuit Open circuit Synchronous
current(A) voltage(V) Reactance( x s)
0.1 3.935 107.2321 27.25085
0.2 7.574 175.2268 23.1353
0.3 11.213 219.9067 19.61176
0.4 14.852 246.7444 16.61355
0.5 18.491 261.2125 14.12647
0.6 22.13 268.7836 12.14567
0.7 25.769 274.9303 10.66903
30
25
20
Synchronous Reactance xs (Ω)
15
10
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
Field current(A)
120
100
80
Load Voltage(V
60
40
20
0
1 2 3 4 5 6 7
Load Current(A)
Load Voltage Vs Load Current
DISCUSSION
About synchronous generator
A synchronous machine is an ac rotating machine whose speed under steady state condition is
proportional to the frequency of the current in its armature. The magnetic field created by the
armature currents rotates at the same speed as that created by the field current on the rotor, which is
rotating at the synchronous speed, and a steady torque results. Synchronous machines are commonly
used as generators especially for large power systems, such as turbine generators and hydroelectric
generators in the grid power supply. Because the rotor speed is proportional to the frequency of
excitation, synchronous motors can be used in situations where constant speed drive is required.
Since the reactive power generated by a synchronous machine can be adjusted by controlling the
magnitude of the rotor field current,
According to the construction of the rotor of the synchronous generator there are two types. For high
speed synchronous machines cylindrical rotor constructions are used. Salient or projecting poles
construction is used in comparatively small machines and machines driven at a relatively low speed.
To study and analysis about this synchronous generator we have to consider about the flux linkage,
induced voltage, Armature resistance, synchronous reactance and the short circuit ratio, which is
known as SCR.
Importance of SCR for synchronous reactance
SCR is given by inverse of per unit saturated synchronous reactance. Therefore, if we know SCR value
we can have an idea about the Xs. Therefore for a particular generator when use in power system this
will be useful to design parameter. This results in a significant phase angle (lagging) between the
induced Voltage and the armature current and also as the value of SCR gets higher and higher, the
Synchronous reactance reduces considerably causing a good voltage regulation at the output
terminals. In the cases of parallel operation of generators, Synchronous reactance is essential in
determining the circulating current within the two generators. As Xs is a function of SCR we can have
an idea about the circulating current by knowing the SCR.
300 30
250 25
Synchronous Reactance xs (Ω)
200 20
150 15
100 10
50 5
0 0
0 00.1 0.10.2 0.2 0.30.3 0.4
0.4 0.5 0.6 0.70.7 0.8
0.6
Field Field
Current(A)
current(A)
Load Voltage(V)
80
60
40
20
0
1 2 3 4 5 6 7
Load Current(A)
At high field currents, the rotor flux increment is much slower with an increase in mmf and it is the
saturated state. Therefore the constant values of Xs can be expected up to unsaturated region. At the
saturated region the slow increment of flux affects to the armature reaction and the self inductance
of the armature (stator) coils. Effects of load changes on a synchronous generator are a very useful
thing to study. When we consider this variation we can say that field currents remain unchanged and
therefore the internal generated voltage is constant if mover has constant speed.