Classic Series
Standard Materials
Body & Cover: Coating: Ductile Iron ASTM A536 NSF Listed Fusion Bonded Epoxy Lined and Coated 316 Stainless Steel (1-1/4 8) ASTM B62 Bronze (10 24) (Stainless Steel Optional) Buna-N (standard) EPDM (optional) Viton (optional) Stainless Steel
B C
D

F500 (Globe) F1500 (Angle)


1/05

Globe
L M

Angle

Trim:

Elastomers:

Stem, Nut & Spring:

Dimensions
A
VALVE SIZE 2 2-1/2 3 4 6 8 10 12 14 16 GLOBE THRD. 9-3/8 11 10-1/2

B
GLOBE 150# 9-3/8 11 12 15 20 25-3/8 29-3/4 34 39 41-3/8

C
300# 10 11-5/8 13-1/4 15-5/8 21 26-3/8 31-1/8 35-1/2 40-1/2 43-1/2

D
CENTER 6-3/8 8-1/2 8-3/4 10-1/4 14 19-1/2 22-1/2 24-3/4 26 30-1/2

E
THRD. 4 5-1/2 5-1/4

F
ANGLE 150# 4 5-1/2 5-3/4 6-3/4 8-1/2 11 14-7/8 17

G
ANGLE 300# 4-1/4 5-13/16 6-1/8 7-1/8 8-7/8 11-1/2 15-5/8 17-3/4

H
ANGLE THRD. 4 4 5-1/4

I
ANGLE 150# 4 4 5-3/4 6-3/4 8-1/2 11 14-7/8 17

J
ANGLE 300# 4-1/4 4-5/16 6-1/8 7-1/8 8-7/8 11-1/2 15-5/8 17-3/4

K
PORT SIZE 1/2 1/2 1/2 1/2 1/2 1/2 1 1 1 1

L
PORT SIZE 1/2 1/2 1/2 1/2 1/2 1 1 1 1 1

M
PORT SIZE 1/4 3/8 3/8 3/8 1/2 1/2 1 1 1 1

N
PORT SHIPPING SIZE WEIGHTS* 1/4 1/4 1/4 1/4 1/2 3/4 3/4 1 1 1 40 70 105 230 375 800 1100 1720 2600 3300

GLOBE COVER TO ANGLE

*Estimated in lbs.

Description Description
The WATTS ACV Models F500 and F1500 are full port, dual chamber basic valves that incorporate a one-piece disc and diaphragm assembly. This assembly is the only moving part within the valve, allowing it to open or close as commanded by the pilot control system. When pressure is applied to the upper diaphragm chamber and released from the lower diaphragm chamber, the valve travels to a closed position. When pressure is applied to the lower diaphragm chamber and released from the upper diaphragm chamber the valve travels to a full open position. When pressure is balanced between the upper and lower diaphragm chambers, the valve will hold an intermediate position until commanded to modulate open or closed by the pilot control system. Model F500: Globe Pattern Dual Chamber Basic Valve Model F1500: Angle Pattern Dual Chamber Basic Valve

Operating Operating Pressure Pressure


Threaded = 400 psi / 150 Flanged=250 psi / 300 Flanged = 400 psi

Operating Operating Temperature Temperature


Buna-N: 160F Maximum EPDM: 300F Maximum Viton: 250F Maximum 8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com

Flow Data - ACV F500 (Globe) / F1500 (Angle)


Valve Size - Inches Maximum Continuous Flow Rate Gpm (Water) Maximum Intermittent Flow Rate Gpm (Water) CV Factor GPM (Globe) CV Factor GPM (Angle) 2 208 260 55 66 2-1/2 300 370 75 99 3 460 570 125 170 4 800 1000 220 280 6 1800 2300 460 650 8 3100 3900 775 1100 10 4900 6000 1200 1600 12 7000 8600 1730 2500 14 8500 10500 2100 3060 16 11000 14000 2800 4210
Estimated

Maximum continuous flow based on velocity of 20 ft. per second. Maximum intermittent flow based on velocity of 25 ft. per second. The CV factor of a valve is the flow rate in US GPM at 60 F that will cause a 1 psi drop in pressure. The factors stated are based upon a fully open valve. CV factor can be used in the following equations to determine Flow (Q) and Pressure Drop (r P): Q (Flow) = CV r P rP (Pressure Drop) = (Q/CV)2

2-1/ 2 2

10

100 80 60 40

Pressure Drop (p.s.i.)

30 20

10 8 6 4 3 2

2 100,000

6 8 10

20

40 60 80 100

200

500

1000

2000

5000 10000 20000

Flow Rate - Gallons per minute (Water)

Valve Cover Chamber Capacity


Valve Size (in) fl.oz. U.S. Gal 2 4 2-1/2 10 3 10 4 22 6 70 1-1/4 2-1/2 4 6-1/2 9-1/2 8 10 12 14 16

Valve Travel
Valve Size (in) Travel (in) 2 1/2 2-1/2 5/8 3 3/4 4 1 6 1-1/2 8 2 10 2-1/2 12 3 14 3-1/2 16 4

8550 Hansen Road Houston, Texas 77075 (Ph) 713.943.0688 (Fx) 713.944.9445 www.wattsacv.com

12 14 16

Angle Globe
2

2-1/

Headloss

10

12 14 16