You are on page 1of 5

Bringing Grounding Down to Earth

Don't let the rules and requirements intimidate you. Grounding isn't as mysterious
as you might think.
By Tim Janof, P.E.

(published in EC&M, February 2005)

Do the myriad rules about impedance of the path through the


grounding sometimes seem a bit too much to grounding/grounded conductor.
handle? Do grounding implementation If you're unsure about this at your
problems sometimes leave you dazed and facility, measure the impedance of a copper
confused, with the correct solution wire from the electrode to the source and
seemingly a bit over your head? If so, don’t compare it with the impedance through the
feel alone. earth.
Despite the extensive literature on This difference in impedance means
grounding, some of its important concepts only a minute amount of fault current flows
seem to be missing from the electrical through the grounding electrode. The fault
industry's oral tradition and regular practice typically travels along the equipment ground
— and some grounding misconceptions (conductors and metal raceway systems),
seem to be solidly anchored in their place. through the neutral-ground bond, and back
Consequently, many designs and to the source through the grounded (neutral)
installations aren't as reliable or as safe as conductor. It's the high fault current through
they could be. the low-impedance path that causes an
But you can steer clear of the overcurrent device to trip—not the
confusion if you understand the concepts negligible amount of current that flows
behind the rules. With a better through the dirt via a ground rod (Figure 1).
understanding, you can have more
confidence that your grounding system will
function as you intended.

Back to basics
The first thing to understand is that
ground-fault current — like all electricity —
seeks to return to its power source. This
principle is what makes electrical circuits
work in the first place. What's the source of
ground-fault current? It doesn’t originate in
the earth, but at the utility transformer.
Kirchoff’s Law states that current
will flow in inverse proportion to the Figure 1 -- Each path's relative impedance
impedance of the paths presented to it. Thus, determines where most of the ground fault
the relative impedances of the various paths current flows.
determine how fault current gets back to its
source. If that's the case, what's the function of the
The impedance of the path between grounding electrode? Believe it or not, it has
the grounding electrode and the source is several, including the following:
almost always significantly higher than the
2

 Limiting voltages imposed by


lightning, surges, or accidental
contact with higher voltage lines.
 Stabilizing the voltage to earth
during normal operation, helping to
maintain the voltage within
predictable limits.
 Assisting the utility in clearing its
own faults by basically becoming Figure 2a -- Overlapping effective resistance
part of the utility's multi-point areas increase net resistance.
grounding system.
 Providing a path to earth for static
dissipation.

Ground rod spacing


Suppose you drive the first ground
rod for a system. If it has a ground resistance
of 25 ohms or more, 250.56 of the 2005
NEC requires you to drive a second rod. But
many contractors don’t bother measuring the
ground resistance. They simply plan on
driving two rods because doing so will meet
the requirements of 250.56, regardless of
actual ground resistance. Thus, two-rod
installations are common, but are they
necessarily correct? Figure 2b -- Non-overlapping effective
The Code requires you to space rods resistance areas reduce net resistance.
at least 6 feet apart [250.53(B)]. However,
this spacing is a minimum—and far from Main bonding jumper
ideal. When using the typical 8-foot or 10- The main bonding jumper is the link
foot ground rod, you get the best results by between the neutral and the equipment
spacing the rods at least 16 or 20 feet apart, ground bars within the service. This vital
respectively. This is much greater than the connection allows the ground-fault current
Code minimum 6-foot spacing. to return to the source. Without the main
Ground rods spaced less than two bonding jumper, the fault would have to
rod-lengths apart will interfere with each travel through high-impedance earth rather
other because their effective resistance areas than low-impedance copper. This high-
will overlap (Figure 2A). For reference, see impedance path would most likely limit the
IEEE-142 and Soares Book on Grounding. current and prevent circuit breakers from
The overlap increases the net resistance of tripping — or at least prevent them from
each rod, making the grounding electrode tripping soon enough to avoid equipment
system less effective than if the rods were damage.
spaced farther apart (Figure 2b). Size the main bonding jumper per
Table 250.66. Many people assume this
table indicates the maximum size main
bonding jumper is 3/0 AWG, but that’s
another common misconception. The
bonding jumper must be at least 12.5% of
the equivalent area of the phase conductors
[250.28(D)]. If you're running 11 sets of 500
3

kcmil conductors (a 4,000A service, for I2T = 78,883,920


example), the main bonding jumper would I = (78,883,920 ÷T)
need to be 700 kcmil minimum, not 3/0 I = (78,883,920 ÷0.5)
AWG. I = 12,560A
This issue is less of a concern with
bonding jumpers for secondary derived But if the available fault current is
systems, such as transformers and 65,000A or 100,000A at the load end of the
generators, since fault currents are typically grounding conductor, the grounding
much lower in those systems. conductor will be quickly destroyed in the
event of a fault, assuming the circuit breaker
Sizing equipment grounding conductors takes 30 cycles to open. You should be
Designers typically use Table mindful of the available fault current and
250.122 when sizing equipment grounding allow for the opening time of the circuit
conductors. In most cases, the size will be breakers, especially the main and feeder
adequate, especially for small branch breakers in the main switchboard. Perform
circuits. But when the available fault current I2T calculations as described above,
is high — say 100,000A — and when an particularly when the available fault current
upstream circuit breaker is set to delay its is high. You can see that correctly sizing
trip for several cycles, you must size equipment grounding conductors isn't as
grounding conductors more carefully. simple as applying NEC minimums.
Metallic raceways, which typically
carry more current than equipment Grounding system currents
grounding conductors, may not be installed Current is present in the grounding
properly or may come apart over time. system during normal operating conditions,
Consequently, the equipment grounding not just during a fault condition. This
conductor may be the only ground return probably explains why the Code permits
path available. Under-sized grounding ground-fault sensors to be set to as high as
conductors may melt during a fault before 1,200A to prevent nuisance tripping
they serve their purpose of providing a [230.95(A)].
continuous low-impedance current path back Other than ground faults, several
to the source during a fault condition. things can produce current in the grounding
It’s important to understand that system, including the following:
conductors have withstand ratings. The
Insulated Cable Engineers Association  Induced currents from adjacent
provides a standard called Short-Circuit current-carrying wires.
Characteristics of Insulated Cable, number  Induced currents from motors
P 32-382 (1994). This standard says that for (particularly single-phase).
a 5-second period, a conductor's withstand  Capacitive coupling between the
rating is 1A per 42.25 circular mils. phase and neutral wires to the
For example, a 3/0 AWG conductor grounding conductors. This
can safely carry 3,972A for 5 seconds. The phenomenon is known to cause
I2T, 5-second withstand rating is therefore nuisance GFCI tripping in long
78,883,920A. Now assume a circuit breaker circuits.
is set to open in 30 cycles—a delay you  Electrostatic discharge from
might see at the service. You can quickly equipment.
determine that the maximum current a 3/0
AWG can carry for 30 cycles (0.5 sec) is: Ground loops
You can form ground loops through
the interaction of power grounding and low-
4

voltage cabling. Low-voltage cabling often various grounding points. TIA/EIA J-STD-
contains a signal ground conductor that can 607-A recommends a maximum potential of
essentially bond the internal signal grounds 1V between grounding points. Interestingly,
between different pieces of electronic it also recommends one large ground loop
equipment together. If an internal bond also for grounding multi-story buildings (Figure
exists between the power ground and the 4). In computer networks, limiting the
signal ground within the electronic potential between grounding points clearly
equipment, current can flow through this takes precedence over concerns about
loop. Though shielded low-voltage cables circulating loops of ground currents.
are typically grounded only at one end to Audiovisual equipment is much more
prevent ground loops, a separate signal sensitive, however.
ground wire within the shield may still
create a bond.
For an example of where this
commonly occurs, think about a computer
network and the shields on devices like
printers, routers, and workstations. If you're
linking different pieces of equipment
together, you're interconnecting devices that
have a potential between their respective
ground pins (Figure 3). If you have a
complete circuit through the signal wires,
you have a ground loop. Ground currents
will flow because of this potential, and
they'll create electrical noise that can
interfere with system operation.
Electromagnetic fields that pass through this
loop could also cause current to flow.

Figure 4 -- Note the loop topology in this excerpt


from TIA/EIA J-STD-607-A.

Any given building has hundreds, if


not thousands of low-voltage cables, and
each may form its own ground loop in
combination with the power grounding
system. Unfortunately, there's no practical
way in a standard building to guarantee an
even ground plane throughout.
The best you can do is properly
Figure 3 --A ground loop can be formed between
power and signal grounds.
ground the key pieces of equipment. This
means providing ground bars in all
To minimize this phenomenon, you telecommunications and audio/video rooms,
must limit the potential between these and making sure every piece of equipment
within these rooms is tied to these ground
5

bars. This ensures a fairly even ground plane


within the room—at least in the lower
frequency range.
A commonly prescribed cure for
these kinds of grounding issues is to provide
equipotential ground planes over a wide
range of frequencies. Methods include using
ground meshes within slabs and signal
reference grids beneath raised floors. Given
the cost of such measures, these methods are
typically reserved for the most sensitive
communications facilities — not typical
commercial or institutional facilities. An
equipotential ground plane is only one step,
though. It’s not a cure-all for ground loops,
because currents can always be induced by
electromagnetic fields that pass through
conductors.
Don’t be overwhelmed by the vast
amount of minutia related to grounding.
Having a handle on a few basic grounding
concepts should help you sort things out.
Good grounding is key to the operational
success of any facility, so the more informed
your designs, the more reliable the
installation will be and the fewer power
quality issues will surface.

Tim Janof, P.E. is an associate and senior


project manager at Sparling, an electrical
engineering and technology consulting firm
with offices in Seattle and Portland.

You might also like